luxCONTROL lighting control system SMART sensors

luxCONTROL lighting control system SMART sensors
luxCONTROL lighting control system
SMART sensors
SMART Sensor 5DPI 19fe
Ambient light sensor and presence detector for lighting control
Product description
• Optional ambient light sensor and presence detector for
PCA EXCEL one4all devices from the y II generation
• Can be remote controlled
• Compact dimensions for luminaire installation
• Simple cable connection to the ballast via SMART interface
• Power supply via ballast
• Lighting control and presence detection can be deactivated
• Individual adjustment of the parameters with configuration
software
• Optional with corridorFUNCTION profile
39
• Optional connection with second ballast possible via accessory
5
3,5
cable
19
• Max. installation height 5 m
• 5-year guarantee
12,5
Power supply via
SMART interface
Current draw
1 mA from SMART interface
Operating temperature
0 ... +60 °C
Storage temperature
-20 ... +65 °C
Type of protection
IP20
Max. casing temperature tc
63 °C
16
16,7
23,2
25,6
Technical data
Ordering data
È
Standards, page 5
Wiring diagrams and installation examples, page 6, 7
Type
Article number
Packaging, carton
SMART Sensor 5DPI 19fe
28000922
20 pc(s).
SMART Sensor 5DPI 19fe cF n.o.
28000929
20 pc(s).
SMART Sensor 5DPI 19fe cF 01
28000927
20 pc(s).
SMART Sensor 5DPI 19fe cF 30
28000928
20 pc(s).
Specific technical data
Type
Detection
Light detection angle Light measurement at
asymmetric
the sensor head1
Illuminance
(factory default)2
Motion detection angle
symmetric
Max. cable length
Control output (devices)
corridorFUNCTION
profile
SMART Sensor 5DPI 19fe
31°
40 – 1,000 lx
500 lx
92°
0.8 m
2
–
SMART Sensor 5DPI 19fe cF
n.o.
31°
40 – 1,000 lx
500 lx
92°
0.8 m
2
never off
SMART Sensor 5DPI 19fe cF 01
31°
40 – 1,000 lx
500 lx
92°
0.8 m
2
switch-off 1 minute
SMART Sensor 5DPI 19fe cF 30
31°
40 – 1,000 lx
500 lx
92°
0.8 m
2
switch-off 30 minutes
1
The measured value at the sensor head corresponds to approx. 60 to 3000 lux on the surface measured.
2
The illuminance is set for a room defined by Tridonic. Depending on the actual room (reflectance) the measured illuminance may deviate from this value.
The illuminance should therefore be checked in the installation and adjusted if necessary.
Data sheet 11/16-CO012-14
Subject to change without notice.
www.tridonic.com
1
ACCESSORIES
luxCONTROL lighting control system
SMART sensors
SMART Sensor T5 Clip + Cap
Product description
• Clip for mounting the sensor directly to the lamp and cover to
protect against indirect light
ACCESSORIES
Ordering data
Type
Article number
Packaging, bag
Packaging, carton
SMART Sensor T5 Clip + Cap
86459499
10 pc(s).
200 pc(s).
Type
Article number
Packaging, bag
Packaging, carton
SMART Sensor T8 Clip + Cap
86459500
10 pc(s).
200 pc(s).
SMART Sensor T8 Clip + Cap
Product description
• Clip for mounting the sensor directly to the lamp and cover to
protect against indirect light
Ordering data
Data sheet 11/16-CO012-14
Subject to change without notice.
www.tridonic.com
2
ACCESSORIES
luxCONTROL lighting control system
SMART sensors
SMART Sensor Cap
Product description
• Cover to protect against indirect light
ACCESSORIES
Ordering data
Type
Article number
Packaging, bag
Packaging, carton
SMART Sensor Cap
86459501
50 pc(s).
500 pc(s).
REMOTECONTROL IR6
Product description
• Optional infra-red remote control
• Switching on and off (On/Off button)
• Dimming (Up/Down button)
• Activation of automatic lighting control
• Setting the threshold control point (Set button)
Ordering data
Type
Article number Dimensions L x W x HPackaging carton
REMOTECONTROL IR6
28000647
Data sheet 11/16-CO012-14
Subject to change without notice.
www.tridonic.com
86.5 x 40.5 x 7.2 mm 500 pc(s).
3
ACCESSORIES
luxCONTROL lighting control system
SMART sensors
SMART Sensor Extension Cable
Product description
• Cable for optional connection of the sensor with a second ballast
• Only use with SMART Sensor 19fe
Type
Article number
Length
Packaging, carton
SMART Sensor Extension Cable
86459176
0.8 m
1,500 pc(s).
SMART Sensor Cover Frame
6,4
Product description
7,8
ACCESSORIES
Ordering Data
• Cover frame for attaching the sensor
Ø34
directly to the luminaire casing
5
21,4
23,4
16,25
Ordering data
Type
Article number
Packaging, bag
Packaging, carton
SMART Mounting Ring 5DPI
86459428
50 pc(s).
200 pc(s).
Data sheet 11/16-CO012-14
Subject to change without notice.
www.tridonic.com
4
luxCONTROL lighting control system
SMART sensors
SMART Sensor 5DPI 19fe
In combination with the PCA EXCEL one4all based on the y-II platform,
SMART Sensor 5DPI 19fe provides the basis for an easy-to-use and costeffective lighting system.
When the sensor detects movement it triggers a predefined motion
detection profile in the ballast.
Constant lighting control acts exclusively on the “presence value”.
As the amount of natural ambient light changes the illuminance from the
artificial lighting system is adjusted.
With a SMART Sensor 5DPI 19fe installed, PCA EXCEL one4all based on the
y II platform, can be switched on and off via DSI or DALI signals,
switchDIM or the mains.
With the sensor installed the setpoint value (dimming) can be temporarily
changed by means of DALI or switchDIM.
Set point can be changed and set via REMOTECONTROL IR6 on the sensor.
The configuration of the sensors is done via masterCONFIGURATOR
software tool (version 2.02 or higher).
For further information please refer to the y II documentation.
Standards
EN 61547
EN 61347-1
EN 61347-2-11
EN 55015
Installation
• Before connecting / disconnecting the sensor to / from the SMART
interface the power supply has to be switched off
• Only for the use of ballasts with y II label
• The SMART Sensors have to be connected only to the SMART
interface of PCA EXCEL one4all based on the y II range
• The SMART interface is not SELV
The installation instructions for mains voltage therefore apply
• Please ensure that the detection range of the sensor lies in the
lighting area of the controlled luminaires.
• Please ensure that the detection ranges of the sensors do not
overlap. This may have influence to the lighting control.
• Heaters, fans, printers and copiers located in the detection zone
may cause incorrect presence detection.
• To avoid false readings, the sensor should be installed so there is
no direct light from the lamp in the detection zone.
•
•
•
•
Mounting with cams at the sensor housing:
The back side of the sensor should not be exposed to the light
output of the lamp as this can negatively influence the operation of
the sensor.
To avoid any malfunction we strongly recommend:
– Use the SMART Sensor cap (which can be ordered as accessories)
or
– Alternatively: Mount the sensor away from light exposure from
behind
To avoid false measurements caused by the light from other
luminaires we recommend that the sensor should be located centrally
in the luminaire.
Sensor wires must be routed separately from the lamp wires and
mains cables otherwise the lighting control system may malfunction.
If separate routing is not possible (for reasons of space) shielded
lamp wires and mains cables must be used
Application wiring and functionality see separate user manual
smartSENSOR.
Ø 19.0 +0.10
-0.00
Ø 5.2 +0.10
-0.00
13.25 ±0.10
variant 1
drilling hole for
IR-Receiver
Ø 19.0 +0.10
-0.00
Size of the sheet: 0.8 – 1.2 mm
12.5 ±0.10
1.5 ±0.10
3.8 +0.20
-0.00
On the housing of the sensor are fixing cams integrated. With this cams the
sensor can be mounted directly in the luminaire housing.
variant 2
drilling hole for
IR-Receiver
Mounting with cover frame in luminair housing:
Note:
By the installation is to be paid attention to the fact that the IR sensor and
the light sensor is visible.
SMART Mounting Ring 5DPI (art.no. 28000910)
Size of the sheet: 0.8 – 1.2 mm
Ø 5.3 +0.20
-0.00
Ø 21.8 +0.20
-0.00
13.75 +0.10
-0.10
Data sheet 11/16-CO012-14
Subject to change without notice.
www.tridonic.com
5
luxCONTROL lighting control system
SMART sensors
A)
corridorFUNCTION with integrated motion sensor
Soft start of PCA EXCEL one4all is followed by activation of motion detection
and constant light control.
2
3
4
6
7
PCA EXCEL one4all
SMART Interface
DA
DA
PCA EXCEL one4all
6
7
SMART Interface
DA
optional
SMART Sensor Extension
Cable (art.no. 86459176)
B)
corridorFUNCTION with external motion sensor
The corridorFUNCTION is activated when a standard motion sensor is
connected to the central interface (D1, D2). If movement is detected by the
motion sensor the PCA EXCEL one4all ballasts switch on; if no movement
is detected they switch to the “absence value” after the delay time on the
motion sensor.
Only the “presence value” is constant light controlled.
For the corridorFUNCTION profile there will be used the profile of the sensor.
The motion detector integrated in the SMART Sensor is inactive in this
mode.
2
3
4
6
7
SMART Interface
DA
DA
PCA EXCEL one4all
6
7
DA
SMART Interface
DA
optional
SMART Sensor Extension
Cable (art.no. 86459176)
C)
Compatibility with the controllers must be checked before a PCA EXCEL
one4all with connected SMART Sensor 5DPI is integrated in a DSI or
DALI light management system.
2
3
4
DALI
DSI
Switch ON/OFF via DSI command. DSI command = 0 zero-power switch OFF,
DSI commands > 0 switch ON.
ON means activation of the motion detector by sensor.
PCA EXCEL one4all
DSI
6
7
PCA EXCEL one4all
SMART Interface
DA
DA
PCA EXCEL one4all
6
7
DA
SMART Interface
DA
optional
SMART Sensor Extension
Cable (art.no. 86459176)
DALI
Switch ON/OFF via DALI commands.
Control possible via DALI commands.
For more information see the y II documentation.
Extension via SMART Sensor Extension Cable
If DALI is used both ballasts must be in the same group and controlled via
group commands.
D)
switchDIM
PCA EXCEL one4all with switchDIM function can be switched ON/OFF by a
short key press. By dimming up and down with a long press the set-point of
the light control can be changed temporarily. After switching OFF and ON
again the
previous setted value will be activated again.
If presence control and switchDIM are used in combination there may be
loss of synchronism if several ballasts are connected to the same
momentary-action switch and the ballasts or the sensors connected to
them are large distances apart.
Data sheet 11/16-CO012-14
Subject to change without notice.
www.tridonic.com
2
3
4
N
L
6
7
PCA EXCEL one4all
SMART Interface
DA
DA
PCA EXCEL one4all
6
7
DA
SMART Interface
DA
optional
SMART Sensor Extension
Cable (art.no. 86459176)
6
luxCONTROL lighting control system
SMART sensors
Light regulation
Presence detection
Precise light measurement via photo diodes.
31°
h
h
a
x
1.50 m
0.90 m
0.22 m
2.00 m
1.20 m
0.30 m
2.50 m
1.50 m
0.37 m
3.00 m
1.80 m
0.45 m
3.50 m
2.10 m
0.52 m
4.00 m
2.40 m
0.60 m
4.50 m
2.70 m
0.67 m
5.00 m
3.00 m
0.75 m
Detection area:
46°
Scope:
2.5 m presence detection
5 m motion detection
92°
h
1 m = 1.094 yd
d
h*
d
1.50 m
3.10 m
2.00 m
4.10 m
2.50 m
5.20 m
3.00 m
6.20 m
3.50 m
7.20 m
4.00 m
8.30 m
4.50 m
9.30 m
5.00 m
10.40 m
* The recommended
maximum room height for
office applications is 3 m and
for corridor applications for
example 4 m.
x
x
Calculation of the diameter:
d = 2 × tan(0,5 × a) × h
a
The sensor detection zone is dimensioned so that the entire work area is
covered and evaluated, not just a single point.
This ensures that false readings are not made as a result of moving objects
across the work surface such as white paper, which would otherwise lead to
a sudden change in the brightness level.
The absolute value depends on the luminaire used and the reflectance in the
room. The rate at which the dimming value is changed is dynamically linked
to the overall lighting level.
The following operating modes can be set for lighting control via the
masterCONFIGURATOR configuration software (version 2.02 or higher):
Active
Constant light control is active.
Inactive
Constant light control is deactivated. The lighting switches
to a defineable value.
Permanent change of light control set point
The Up/Down button on the remote control enables the setpoint value to be
changed temporarily. Pressing the Set button on the remote control stores
the setpoint value permanently. The light source indicates that the value has
been stored successfully by flashing twice.
In DALI operation the setpoint can be adjusted also with the
masterCONFIGURATOR (version 2.02 or higher).
The DALI “RESET” command restores the default value set at the factory.
Bright-out
If the nominal illuminance (e.g. 500 lux) is exceeded by more than 150 %
(e.g. 750 lux), the lighting is switched off even if motion is detected. The
lighting is switched on again when the measured light value falls below the
setpoint.
This function can be adjusted via the masterCONFIGURATOR (version 2.02
or higher).
The following operating modes can be set for the motion detector via the
masterCONFIGURATOR configuration software (version 2.02 or higher):
Active
The light is switched on or off automatically depending
on whether or not there is a person in the room.
Only Off
The motion detector only switches the connected lighting off. The luminaires are switched on manually via the
connected external switch or infra-red control.
Never Off
If it has not detected any movement the sensor dims to
the “Absence value” parameter and remains at this value
Inactive
The motion sensor is deactivated. The light must be
switched on or off manually.
Run-on time
The time that starts as soon as the presence of a person is no longer
detected. If the presence of a person is detected again during the run-on
time the run-on time is restarted from zero. If no presence is detected during
the run-on time the fade time is started as soon as the run-on time expires.
Fade time
The time during which the luminous intensity is faded from the presence
value to the absence value.
Switch off delay
The time during which the absence value is held before the lighting is
switched off. Depending on the profile selected the switch-off delay may
have different values or may not be defined.
Absence value
The luminous intensity when there is no person present.
Presence value
The luminous intensity when persons are present.
Dead time “Manual-off”
If the system is switched off manually via the switch or REMOTECONTROL
IR6 the motion sensor is deactivated. At the end of a delay time if motion has
not been detected the motion sensor is activated again. If the sensor detects
motion during the “Manual-off” delay, the time will be reset to the start.
Data sheet 11/16-CO012-14
Subject to change without notice.
www.tridonic.com
7
luxCONTROL lighting control system
SMART sensors
General settings
Parameter
Motion Detector
Light Regulation
Setpoint Light Regulation
Bright-out timeout
Bright-out threshold
Switch On Value
Default Values
enabled, on/off
enabled
500 lx
0 min
150 %
auto (calculated)
Default Parameter Motion Detector
Parameter
1 Fade-in time
A Presence value
2 Run-on time
3 Fade time
B Absence value
4 Switch-off delay
5 Fade-off time
Manual-off
Default Values
Adjustable range
< 0.7 s
–
controlled
Absence value to 100 %
20 min
10 s to 42.4 min
32 s
0 – 90.5 s
10 %
0 % to presence value
never off / 1 min / 30 min
0 s to 42.3 min /never off
< 0.7 s–
20 min
3 s to 42.5 min
Data sheet 11/16-CO012-14
Subject to change without notice.
www.tridonic.com