Relay for complete monitoring 3-phase mains HRN-43, HRN-43N

Relay for complete monitoring 3-phase mains HRN-43, HRN-43N
MONITORING RELAYS
Relay for complete monitoring 3-phase mains HRN-43, HRN-43N
Technical parameters
Supply
Supply terminals:
Supply voltage:
Consumption:
Supply voltage tolerance:
Measuring circuit
Nominal voltage:
Terminals:
Upper level Umax:
Bottom level Umin:
Max. permanent overload:
Hysteresis:
Asymmetry:
Peak overload <1ms:
Time delay t1:
Time delay t2:
Accuracy
Set. accuracy (mechanical):
Repeat accuracy:
Temperature dependance:
Limit values tolerance:
Output
Number of contacts:
Rated current:
Breaking capacity:
Inrush current:
Switching voltage:
Min. breaking capacity DC:
Mechanical life:
Electrical life (AC1):
Other information
Operating temperature:
Storage temperature:
Electrical strength:
Operating position:
Mounting:
Protection degree:
Overvoltage cathegory:
Pollution degree:
Max. cable size (mm2):
Dimensions:
Weight:
Standards:
HRN-43
!
monitoring 3-phase mains:
- voltage in 2 levels 160-276 V (3x400/230 V) or 280-480 V (3x400 V)
- phase asymmetry
- phase sequence
- phase failure
!
function “MEMORY” - manual reset, “RESET” button on front pannel
!
HRN-43 - for circuits 3x400 V (without neutral)
!
HRN-43N - for circuits 3x400/230 V (with neutral)
!
2 output relays, selectable function of 2nd relay (independent / parallel)
!
fixed (t1) and adjustable (t2) delay to eliminate short voltage drops and peaks
!
galvanically separated supply voltage AC 400 V, AC 230 V, AC/DC 24 V
!
output contact: 2x changeover 16 A / 250 V AC1
!
3-MODULE, DIN rail mounting
HRN-43N
A1 - A2
AC 230 V, AC 400 V, AC/DC 24 V
max. 4.5 VA
-15 %; +10 %
3x400 V
L1, L2, L3
240 - 480 V
3x400/230 V
L1, L2, L3, N
138 - 276 V
35 - 99 % Umax
3x480V
adjustable 5 % or 10 % of set value
5 - 20 %
600 V<1ms
350 V<1ms
fixed, max. 200 ms
adjustable 0-10 s
5%
<1 %
< 0.1 % / 0C
5%
Description
Hysteresis from faulty to normal state
Function of 2. relay (1.-paralel, 2.-independent)
Selection of function MEMORY
Supply voltage
Indication overvoltage/
undervoltage, failure
Sequence indication
Asymmetry indication
Umin adjusting
Umax adjusting
Asymmetry 5-20 % setting
Time pause t2
Symbol
HRN-43N
16 A / AC1
4000 VA / AC1, 384 W / DC
30 A / < 3 s
250 V AC1 / 24 V DC
500 mW
3x107
0.7x105
-20 .. +55 0C
-30 .. +70 0C
4 kV (supply - output)
any
DIN rail EN 60715
IP 40 from front panel
HRN-43
A1
2x changeover (AgNi)
L1
L2
L3
N
3~
16
18 26
A1
L1
L2
L3
U
A2
15
3~
16
A2
25
15
L1
L2
L3
N
Un
Un
A1 A2 N
L1 L2 L3
A1 A2
L1 L2 L3
III.
2
solid wire max.1x 2.5 or 2x1.5/ with sleeve max. 1x1.5
90 x 52 x 65 mm, see page 157-159
239 g
EN 60255-6, EN 61010-1
HRN-43N
18 26
28
U
Connection
16 15 18 28 25 26
102
28
16 15 18 28 25 26
HRN-43
25
Function
Overvoltage - undervoltage
Hysteresis
L1
Legend:
L1, L2, L3 - 3-phase voltage
RESET - press of the button on frontal pannel
t1 - time delay, fixed
t2 - time delay, adjustable 0-10 sec
15-18 output relay 1
25-28 output relay 2
LED U indication overvoltage / undervoltage
x
L2 Uma
Umin
x
L3 Uma
Umin
RESET
t1 t2
t1
t1
t2
Selection of 2nd relay function:
In order to monitore 2 levels of voltage, it is possible to select
if output relay will respond to each level individually (see
the diagram) or both relays will switch in parallel way (see
diagram “phase sequence”). Selection via DIP switch.
15-18
t1
t2
t1
25-28
LED
MEMORY - ON (DIP-2)
Phase sequence
Legend:
L1, L2, L3 - 3-phase voltage
RESET - press of the button on frontal pannel
t1 - time delay, fixed
t2 - time delay, adjustable 0-10 sec
15-18 output relay 1
25-28 output relay 2
LED indication of range of phases
L1
L2
L3
L3
L2
L3
L2
L2
L3
L2
L3
RESET
t1
t1
t1
Selection of 2nd relay function:
The function is not implied when monitoring phase
sequence, the relays are switched in parallel way..
15-18
(25-28)
t1
t1
LED
MEMORY - ON (DIP-2)
Asymmetry - phase failure
L1
L2
L3
Legend:
LL1, L2, L3 - 3-phase voltage
RESET - press of the button on frontal pannel
t1 - time pause, fixed
t2 - time pause, adjustable 0-10 sec
- adjustable asymmetry 5-20%
15-18 output contact of relay 1
25-28 output contact of relay 2
LED - asymmetry indicator
100%
0%
100%
0%
100%
0%
100%
0%
Hysteresis
RESET
t1
t2
t1
t2
t1
t2
t1
t2
t1
t2
15-18
(25-28)
LED
t1
Selection of 2nd relay function:
The function is not implied when monitoring phase
sequence, the relays are switched in parallel way.
DIP switch is ignored.
MEMORY ON (DIP-2)
Function description
Relay is designated to monitor 3-phase circuits. Type HRN-43N controls voltage against neutral wire, type HRN-43 controls interphase voltage. Relay can monitor voltage in two levels (overvoltage/
undervoltage), phase assymetry , sequence and failure. Each faulty state is indicated by individual LED. By DIP switch (No.3) it is possible to define function of the other relay – independayt function
(1x for overvoltage, 1x for undervoltage) or in parallel. Time delays t1(fixed) – when changing from faulty to normal state or when de-energized and t2 (adjustable) when changing from normal to
faulty state. These delays prevent incorrect conduct and oscillation of output device during short voltage peaks in the main or during gradual voltage decline into normal.
Voltage control
Set upper level Umax in range 138-276 V (or 240 - 480 V for HRN-43) and lower level Umin in range 35-99% Umax. In case any phase passes this range, after a delay which eliminated short voltage
peaks, contact breaks. output contact again switches after returning back into monitored voltage range and exceeding fixed hysteresis (which is adjustable in two values by DIP switch).
Phase sequence
monitors correctness of phase sequence. In case of unwanted change output contact breaks. In case of energization of a device with incorrect phase sequence, contact stays open.
Asymmetry
Rate of assymetry between individual phases is set in a range of 5-20%. In case set asymmetry is exceeded, output relay breaks and LED indicating asymmetry shines. Delays t1, t2 and hysteretic are
applicable when returning to normal state.
103
MONITORING RELAYS
Hysteresis
Umax
Umin
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project