Engineering Data Submittal Manual Project Name: ___________________________ Engineer: ___________________________ ___________________________ Contractor: ___________________________ Architect: ___________________________ Date Received: MODELS BS/BT SPLIT SYSTEMS Revision A 20D21401NN 20D218-17NN Date Submitted: ___________________________ Unit Tag Model Number ____________ ___________________________ ____________ ___________________________ ____________ ___________________________ ____________ ___________________________ ____________ ___________________________ ____________ ___________________________ ____________ ___________________________ ____________ ___________________________ ____________ ___________________________ ____________ ___________________________ ____________ ___________________________ ____________ ___________________________ ____________ ___________________________ ____________ ___________________________ ____________ ___________________________ ____________ ___________________________ Notes: ____________________________________________________________________ ___________________________________________________________________________ ___________________________________________________________________________ ___________________________________________________________________________ ___________________________________________________________________________ TABLE OF CONTENTS Section 1: Introduction and General Information Introduction..................................................................................................................................................................4 Unpacking....................................................................................................................................................................4 Pre-Installation............................................................................................................................................................5 Components................................................................................................................................................................5 Consumer Instructions...............................................................................................................................................6 Equipment Installation................................................................................................................................................6 Section 2: Installation Considerations Electrical......................................................................................................................................................................6 Thermostat...................................................................................................................................................................6 Looping Pumping Modules.........................................................................................................................................6 Desuperheater Package.............................................................................................................................................6 Desuperheater Piping.................................................................................................................................................6 Unit Placement ...........................................................................................................................................................7 Service Access and Installation Space ....................................................................................................................7 Unit Air Pad..................................................................................................................................................................7 Review..........................................................................................................................................................................7 Unit Orientation...........................................................................................................................................................7 Duct Work.....................................................................................................................................................................7 Industry Standard........................................................................................................................................................7 Unit Model Nomenclature Decoder...........................................................................................................................8 Air Handler Model Nomenclature Decoder...............................................................................................................8 Section 3: Model Nomenclature and AHRI Performance Data Cased”A” Coil Model Nomenclature Decoder..........................................................................................................9 Uncased ”A” Coil Model Nomenclature Decoder....................................................................................................9 Air Duct Supply and Unit Physical Data..................................................................................................................11 Unit Physical Data.....................................................................................................................................................11 Section 4: Equipment Data Unit Connections and Clearance.............................................................................................................................12 Air Handler Dimensions............................................................................................................................................13 A Coil Dimensional and Physical Data....................................................................................................................14 Water Flow Calculations and Selection Unit Electrical Data...................................................................................................................................................15 Section 4: Equipment Data MPD Air Handler Fan Speeds...................................................................................................................................16 Air Handler Electrical Data.......................................................................................................................................17 Glossary of Terms......................................................................................................................................................18 Section 5: Glossary of Terms and Correction Factors Sensible Cooling Correction Factors:.....................................................................................................................18 Heating & Cooling Calculations:..............................................................................................................................18 Cooling Correction Factors:.....................................................................................................................................18 Heating Correction Factors:.....................................................................................................................................18 Section 6: Water Flow Calculations and Selection Water Flow Calculations and Selection...................................................................................................................19 Section 7: Extended Data Extended Data - 036, 040, 060, 072.................................................................................................................... 20-25 ENGINEERING SPECIFICATIONS: This Page Intentionally Left Blank 20D218-17NN BS/BT Rev A 3 Enertech Global, LLC ENGINEERING SPECIFICATIONS: Section 1: Introduction and General Information Introduction This geothermal heat pump provides heating and cooling as well as optional domestic water heating capability. Engineering and quality control is built into every geothermal unit. Good performance depends on proper application and correct installation. Notices, Cautions, Warnings & Dangers “NOTICE” Notification of installation, operation or maintenance information which is important, but which is NOT hazard-related. “CAUTION” Indicates a potentially hazardous situation or an unsafe practice which, if not avoided, COULD result in minor or moderate injury or product or property damage. ⚠ CAUTION ⚠ DO NOT OPERATE THE GEOTHERMAL HEAT PUMP UNIT DURING BUILDING CONSTRUCTION PHASE. “WARNING” Indicates potentially hazardous situation which, if not avoided, COULD result in death or serious injury. Unit Protection Protect units from damage and contamination due to plastering (spraying), painting and all other foreign materials that may be used at the job site. Keep all units covered on the job site with either the original packaging or equivalent protective covering. Cap or recap unit connections and all piping until unit is installed. Precautions must be taken to avoid physical damage and contamination which may prevent proper start-up and may result in costly equipment repair. “DANGER” Indicates an immediate hazardous situation which, if not avoided, WILL result in death or serious injury. Inspection Upon receipt of any geothermal equipment, carefully check the shipment against the packing slip and the freight company bill of lading. Verify that all units and packages have been received. Inspect the packaging of each package and each unit for damages. Insure that the carrier makes proper notation of all damages or shortage on all bill of lading papers. Concealed damage should be reported to the freight company within 15 days. If not filed within 15 days the freight company can deny all claims. Storage All geothermal units should be stored inside in the original packaging in a clean, dry location. Units should be stored in an upright position at all times. Units should not be stacked unless specially noted on the packaging. Note: Notify Enertech Global’s shipping department of all damages within 15 days. It is the responsibility of the purchaser to file all necessary claims with the freight company. Enertech Global, LLC Unpacking Enertech units are mounted to wooden Pallets for easy handling during shipment and installation. Units are protected during shipment with durable cardboard corner posts, top and air coil panels. Shrink wrap is applied covering the entire unit and attachment to the pallet. Upon receipt of the unit carefully remove the shrink wrap. Using a box cutter slit the shrink wrap on the cardboard top and corner posts. Use caution to not damage the finished surface of the unit. (Keep all cardboard or other packaging material for safe storage and transport to the job site prior to installation) Remove appropriate unit service panels to locate technical documents and accessory items prior to installation. Removal and Disposal Geothermal units removed from service should have all components, oils, antifreeze and refrigerants properly disposed of according to local and national environmental recycling codes, regulations, standards and rules. 4 20D218-17NN BS/BT Rev A ENGINEERING SPECIFICATIONS: Section 1: Introduction and General Information Pre-Installation Components Special care should be taken in locating the geothermal unit. Installation location chosen should include adequate service clearance around the unit. All compressor bearing units should be placed on a formed plastic air pad, or a high density, closed cell polystyrene pad slightly larger than the base of the unit. Flex connectors should also be installed in between the ductwork and the air handling unit. All units should be located in an indoor area where the ambient temperature will remain above 55°F and should be located in a way that piping and ductwork or other permanently installed fixtures do not have to be removed for servicing and filter replacement. Master Contactor energizes compressor and optional hydronic pump and/or desuperheater pump package. Pre-Installation Steps Low Voltage Circuit Breaker attached directly to the transformer, protects the transformer and low voltage circuit. Logic Board operates the compressor and protects unit by locking out when safety switches are engaged. It also provides fault indicator(s). Terminal Strip provides connection to the thermostat or other accessories to the low voltage circuit. Transformer converts incoming (source) voltage to 24V AC. 1. Compare the electrical data on the unit nameplate with packing slip and ordering information to verify that the correct unit has been shipped. Reversing Valve controls the cycle of the refrigerant system (heating or cooling), Energized in cooling mode. 2. Open both, compressor and blower sections and remove any packaging material or documentation included in the units. At this time you can remove any packaging used to support or hold the blower during shipping. Remove and discard the blower motor shaft shipping bracket from the rear of the blower. High Pressure Switch protects the refrigerant system from high refrigerant pressure, by locking unit out if pressure exceeds setting. Low Pressure Switch protects the refrigerant system from low suction pressure, if suction pressure falls below setting. 3. Inspect all electrical connections and wires. Connections must be clean and tight at the terminals, and wires should not touch any sharp edges or copper pipes. Flow Switch (Freeze Protection Device) protects the water heat exchanger from freezing by shutting down the compressor if water flow decreases. (Not installed in all units) 4. Verify that all refrigerant tubing is free of dents and kinks. Refrigerant tubing should not be touching other unit components. Compressor pumps refrigerant through the heat exchangers and pressurizes the refrigerant, which increases the temperature of the refrigerant. 5. Before unit start-up, read all manuals and become familiar with unit components and operation. Thoroughly check the unit before operating. ⚠ CAUTION ⚠ ALL GEOTHERMAL EQUIPMENT IS DESIGNED FOR INDOOR INSTALLATION ONLY. DO NOT INSTALL OR STORE UNIT IN A CORROSIVE ENVIRONMENT OR IN A LOCATION WHERE TEMPERATURE AND HUMIDITY ARE SUBJECT TO EXTREMES. EQUIPMENT IS NOT CERTIFIED FOR OUTDOOR APPLICATIONS. SUCH INSTALLATION WILL VOID ALL WARRANTIES. 20D218-17NN BS/BT Rev A 5 Enertech Global, LLC ENGINEERING SPECIFICATIONS: Section 2: Installation Considerations Consumer Instructions Electrical Dealer should instruct the consumer in proper operation, maintenance, filter replacements, thermostat and indicator lights. Also provide the consumer with the manufacturer’s Owner’s Manual for the equipment being installed. All wiring, line and low voltage, should comply with the manufacturer's recommendations, The National Electrical Code, and all local codes and ordinances. Thermostat Thermostats should be installed approximately 54 inches off the floor on an inside wall in the return air pattern and where they are not in direct sunlight at anytime. Enertech Global D-I-Y Policy Enertech Global’s geothermal heat pumps and systems installations may include electrical, refrigerant and/or water connections. Federal, state and local codes and regulations apply to various aspects of the installation. Improperly installed equipment can lead to equipment failure and health/ safety concerns. For these reasons, only qualified technicians should install an Enertech Global built geothermal system. Looping Pumping Modules Must be wired to the heat pump’s electric control box. A special entrance knockout is provided below the thermostat entrance knockout. A pump module connection block, connected to the master contactor, and circuit breaker is provided to connect the Pump Module wiring. Because of the importance of proper installation, Enertech Global does not sell equipment directly to homeowners. Internet websites and HVAC outlets may allow for purchases directly by homeowners and do-it-yourselfers, but Enertech Global offers no warranty on equipment that is purchased via the internet or installed by persons without proper training. Desuperheater Package Water heating is standard on all residential units (units may be ordered without). It uses excess heat, during both heating and cooling cycles, to provide hot water for domestic needs. A double wall desuperheater exchanger (coil) located between the compressor and the reversing valve, extracts superheated vapor to heat domestic water; while satisfying its heating and cooling needs. The water circulation pump comes pre-mounted in all residential units, but must be electrically connected to the master contactor. Leaving it disconnected ensures that the pump will not run without a water supply. Enertech Global has set forth this policy to ensure installations of Enertech Global geothermal systems are done safely and properly. The use of welltrained, qualified technicians helps ensure that your system provides many years of comfort and savings. The Desuperheater package can make up to 60% (depending on heat pump usage) of most domestic water needs, but a water heater is still recommended. Equipment Installation Special care should be taken in locating the unit. All vertical units should be placed on a vibration absorbing pad (air pad) slightly larger than the base of the unit. Down flow units should be placed on a non-combustible base. Flex connectors should also be installed in between the ductwork and the unit. All units should be located in an indoor area were the ambient temperature will remain above 55°F and should be located in a way that piping and duct work or other permanently installed fixtures do not have to be removed for servicing and filter replacement. Enertech Global, LLC Desuperheater Piping All copper tubes & fittings should be 5/8” O.D (1/2” nom) minimum with a maximum of 50ft separation. Piping should be insulated with 3/8” wall closed cell insulation. Note: Copper is the only approved material for piping the desuperheater. 6 20D218-17NN BS/BT Rev A ENGINEERING SPECIFICATIONS: Section 2: Installation Considerations Duct Work Unit Placement All new ductwork shall be designed as outlined in the Sheet Metal and Air Conditioning Contractors National Association (SMACNA) or Air Conditioning Contractors of America (ACCA) or American Society of Heating, Refrigerating and Air Conditioning Engineers (ASHRAE) handbooks. When installing a geothermal heating and cooling unit, there are several items the installer should consider before placing the equipment. Service Access and Installation Space Is there enough space for service access? A general rule of thumb is at least 2 to 2-1/2 feet in the front and air coil sides depending on return ductwork size. All supply/return plenums should be isolated from the unit by a flexible connector (canvas) or equivalent to prevent transfer of vibration noise to the ductwork. The flex connector should be designed so as not to restrict airflow. Turning vanes should be used on any transition with airflow over 500 CFM. All metal ductwork should be insulated on the inside to prevent heat loss/ gain, condensation and to absorb air noise. If the unit is being installed with existing ductwork, the ductwork must be designed to handle the air volume required by the unit being installed. When running a cooling or heating load on a building; size ductwork accordingly to the building design load and heat pump CFM. Unit Air Pad All geothermal heating and cooling equipment should be placed on either, a formed plastic air pad, or a high density, closed cell polyethylene pad. Down flow units should be placed on a noncombustible base. This helps eliminate vibration noise that could be transmitted through the floor. The use of corner pads alone is not recommended. Review The installer has verified that all applicable wiring, ductwork, piping, and accessories are correct and on the job site. Industry Standard When sizing ductwork use 400 CFM per Ton. As a general rule, maximum recommended face velocity for a supply outlet used in a residential application is 750 FPM. Maximum recommended return grille velocity is 600 FPM. Systems with higher velocities are likely to have noise problems. Unit Orientation Configure left or right side return and discharge air pattern prior to air handler unit installation. In buildings where ceilings are 8 feet or more, at least 50 percent of the return air should be taken back to the heat pump from the ceiling or high sidewall location and not more than 50 percent from the floor or low sidewall location. Table 1: Maximum Air Velocities ⚠ NOTICE ⚠ Location Main Ducts WHEN MATCHING AN ST048 OR ST060 WITH AN MPD060B, REFER TO THE CFM CHART IN THE ENGINEERING SECTION FOR THE PROPER AIRFLOW JUMPER SETTINGS. 20D218-17NN BS/BT Rev A Branch Ducts Grills, Registers, Diffusers 7 Supply Return 900 FPM 600 FPM 750 FPM 600 FPM 700 FPM 600 FPM Enertech Global, LLC ENGINEERING SPECIFICATIONS: Section 3: Model Nomenclature and AHRI Performance Data Unit Model Nomenclature Decoder Air Handler Model Nomenclature Decoder Enertech Global, LLC 8 20D218-17NN BS/BT Rev A ENGINEERING SPECIFICATIONS: Section 3: Model Nomenclature and AHRI Performance Data Cased”A” Coil Model Nomenclature Decoder Uncased ”A” Coil Model Nomenclature Decoder 20D218-17NN BS/BT Rev A 9 Enertech Global, LLC ENGINEERING SPECIFICATIONS: Section 3: Model Nomenclature and AHRI Performance Data AHRI Performance Data, BS/BT Cased/Uncased Coil UNIT BS018 Rating TYPE F/L COOL F/L EER F/L HEAT F/L COP P/L COOL P/L EER P/L HEAT P/L COP WL 19,200 15.7 22,300 5.4 0.0 0.0 0.0 0.0 GW 21,700 25.5 18,500 4.5 0.0 0.0 0.0 0.0 WL 23,500 15.1 27,500 4.7 18,400 16.7 3.6 20,000 23.8 GL BT024 BT036 BT048 BT060 BT072 GW GL WL GW GL 20,100 18.6 26,000 22.9 24,500 33300 35000 33900 WL 48600 GL 50800 GW WL 54100 58700 GW 65100 WL 65,100 GL GW GL 61000 72,300 67,800 17.6 15.4 21.7 Rating TYPE BS018 GW BT024 BT036 BT048 BT060 BT072 20,400 WL GW GL WL 23,600 26,800 24,900 24.6 42600 39400 26.9 30800 4.5 28.7 42300 4.5 59,100 4.8 42,600 3.8 47900 24.2 4.3 49700 32.2 14.7 75,400 4.3 51,200 15.8 16.9 50,300 3.4 55,800 22.5 21.7 62,800 3.9 57,700 0.0 0.0 0.0 14.6 28,000 4.6 18,400 15.6 18,200 3.4 20,300 22.2 22.7 17.3 23,000 3.6 0.0 4.2 0.0 18.0 32000 5.8 27600 26.0 26.2 45700 4.6 42100 15.4 67600 4.6 45300 17.7 17.6 45900 3.7 49200 25.5 59900 GW 66200 WL 65,500 62300 73,900 69,900 22.7 36200 4.5 27700 54000 5.1 57000 14.3 77,200 16.4 52,000 20.8 3.9 4.2 64,800 10 15,400 3.9 30.4 25900 4.8 36900 19.0 41600 5.9 40500 28.8 30900 4.4 30.1 42300 4.5 59,700 4.8 43,800 3.8 50900 35.6 4.3 52,200 16.2 3.4 56,700 23.2 4.0 5.5 25700 28700 37300 21,900 0.0 4.4 17.1 19.9 0.0 0.0 17,900 35200 3.8 0.0 4.2 25.8 14.8 55700 5.0 0.0 34100 21.0 44600 21,000 4.1 0.0 4.5 14,600 5.4 P/L COP 18,500 18.9 37600 5.0 P/L HEAT 25.3 0.0 51900 6.0 P/L EER P/L COOL 5.4 34600 4.7 4.2 49,400 F/L COP 22,600 22700 26.4 F/L HEAT 15.7 5.7 18.6 3.7 56600 4.2 36700 45500 22.5 4.0 5.7 4.7 24500 17.6 37200 15,100 0.0 28.5 17.1 51500 Enertech Global, LLC 27000 27500 44200 GL GL 5.2 31900 4.8 17.0 GW 55000 3.7 17.6 67400 49200 GL 4.2 25200 15.5 WL WL 35100 21,500 17,400 40900 35400 GW 4.7 0.0 27.8 4.6 GW GL 43400 17,800 20,700 46500 19.2 20,000 GL 4.3 0.0 24.9 16.5 F/L EER 19,500 22,700 0.0 27900 F/L COOL WL 3.6 17.4 AHRI Performance Data, BS/BT Air Handler UNIT 14,700 58,800 27.5 22900 34200 51900 37800 49,300 4.3 5.0 5.3 4.1 4.2 20D218-17NN BS/BT Rev A ENGINEERING SPECIFICATIONS: Section 4: Equipment Data Air Duct Supply and Unit Physical Data Return and Supply Air Duct System Supply Air Flex Connector Flex Connector Return Air The air handling unit comes with an ECM blower motor. For maximum performance, the blower speed should be set to maintain between 350 and 450 CFM/ton. Changing the wires (for PSC) at the blower will change the blower speed. AHRI Air Handler and “A” Coil Matches Compressor Section 018 024 036 048 060 072 Air Handler Air Handler Match MPD024A MPD024A MPD036A MPD060B MPD060B MPD072A A-Coil Match ACD024B ACD024B ACD036B ACD060C ACD060C ACD060C Return Air Plenum PHYSICAL UnitUNIT Physical DataDATA - BS / BT Split - BS/BT Compressor Section Model Number BS018 Compressor Type Single Stage Scroll Compressor Connection Size (I.D.) Liquid - Vapor Source Water Conn. (Resid.) Source Water Conn. (Comm.) HWG Water (if applicable) Refrigerant Charge (oz.) * BT024 BT036 BT048 BT060 BT072 Dual Stage Unloading Scroll Compressor 3/8" - 5/8" 3/8" - 5/8" 3/8" - 5/8" 3/8" - 3/4" 3/8" - 7/8" 3/8" - 7/8" 1" Dbl. O-Ring 1" FPT 3/4" FPT 39 1" Dbl. O-Ring 1" FPT 3/4" FPT 42 1" Dbl. O-Ring 1" FPT 3/4" FPT 61 1" Dbl. O-Ring 1" FPT 3/4" FPT 93 1" Dbl. O-Ring 1" FPT 3/4" FPT 92 1" Dbl. O-Ring 1" FPT 3/4" FPT 93 190 26 216 53 53 42 42 190 26 216 53 53 42 42 201 26 227 61 52 48 41 226 26 252 68 58 54 46 229 26 255 69 59 54 46 244 26 270 74 63 58 49 Unit Weight Tare Weight Shipped Weight Corner A Corner B Corner C Corner D UNIT WEIGHT DATA (lbs) * Always check the unit data plate for specific charge volume. B C D Unit Front A B:\ENGINEERING\RECORDS\Component Drawings\PDF\20D808-02NN REVB Revision History Description of Change REV A CREATED TABLE AND ADDED WEIGHTS FOR 060-072 B Changed Lineset size needed (O.D.) to Connection size (I.D.) Liquid - Vapor C ADDED WEIGHTS FOR 018,024,036,048 & UPDATED CHARGE AMOUNTS 20D218-17NN BS/BT Rev A 11 ECN Date Name 16-072-N16 12/30/2016 M. TRIPP 1/23/2017 M. TRIPP 8/8/2017 M. TRIPP 17-273-N01 Enertech Global, LLC ENGINEERING SPECIFICATIONS: Section 4: Equipment Data Unit Connections and Clearance A C J H G F B E D Enertech Recommends A Minimum of 2 to 2 1/2 Feet of Service Area Clearance For Installation And Maintenance. MODEL SIZE CABINET OVERALL WATER CONNECTIONS LINE-SET CONNECTIONS ELECTRICAL KNOCKOUTS Notes: A B C D E F G H J K L M N O P Q 018-072 26.000 26.000 21.000 3.000 8.000 11.125 13.875 16.375 18.875 13.875 15.625 17.625 4.625 6.625 10.625 15.875 POWER SUPPLY EXTERNAL PUMP SUPPLY T-STAT CONNECTION M L T'STAT CONNECTION Q DESUPERHEATER PUMP ON/OFF SWITCH K P EXTERNAL PUMP SUPPLY POWER SUPPLY O N All desuperheater connections are 3/4” FPT. All electrical knockouts are sized 1/2” or 3/4” conduit. All measurements are in inches. All drawings are typical, individual models may vary. Enertech Global, LLC 12 20D218-17NN BS/BT Rev A ENGINEERING SPECIFICATIONS: Section 4: Equipment Data Air Handler Dimensions Model Size (tons) All Dimensions in Inches A B C D E F G H J K L M N P R MPD024A 2 17 5/8 43 21 15 5/8 12 1/2 13 1/2 11 6 3/4 16 3/4 14 10 3/4 10 3/4 2 1 1/2 5 MPD036A 3 21 1/8 48 21 19 12 1/2 15 3/8 13 6 3/4 20 17 12 3/4 10 1/4 2 1/4 4 3/8 5 MPD060B 4-5 24 5/8 58 7/8 21 3/4 22 1/4 14 1/4 19 3/4 17 1/4 6 3/4 26 23 16 3/4 14 3/8 4 1/4 4 3/8 4 1/2 MPD072A 6 24 5/8 58 7/8 21 3/4 22 1/4 14 1/4 19 3/4 17 1/4 6 3/4 26 23 16 3/4 14 3/8 4 1/4 4 3/8 4 1/2 Return Air Opening 20D218-17NN BS/BT Rev A 13 Model Width Depth MPD024A 15 1/2 19 3/4 MPD036A 19 3/4 19 3/4 MPD060B 23 1/2 20 3/4 MPD072A 23 1/2 20 3/4 Enertech Global, LLC ENGINEERING SPECIFICATIONS: Section 4: Equipment Data A Coil Dimensional and Physical Data C B A Size (tons) Model ACD024B ACD036B ACD060C A 16 5/8 19 5/8 23 3/4 2 3 4-6 All Dimensions in Inches C Liquid 14 1/2 3/8 18 1/2 3/8 27 7/8 3/8 B 19 19 20 1/2 Suction 3/4 3/4 7/8 Water Flow Calculations and Selection All Dimensions In Inches (nominal) Model Size (Tons) A B C D E F 024 2 17.5 21.0 20.0 15.2 19.2 2.1 036 3 21.0 21.0 24.0 18.7 19.2 060 5 24.5 22.0 34.0 22.0 19.9 G H P Q Weight (lbs...) 11.0 3.3 .88 .38 45 10.6 15.7 11.9 14.2 3.3 .88 .38 50 12.8 19.8 24.8 26.8 3.3 .88 .38 72 I J 4.1 1.8 2.3 11.1 8.5 2.2 4.3 1.8 2.3 12.9 2.2 4.2 1.9 2.3 17.3 NOTES: 1.The AC series coils are designed as high efficiency “A” coils to be K installed on new and existing indoor furnaces. These coils may be used in up flow and down flow applications. 2.Coils are ETL and CSA approved. 3.Primary and secondary drain connections are available on the LH or RH side of the drain pan, and are 3/4” FPT. Center line of drains located from pan corner, 1 1/2” for primary and 3 1/2” for secondary. 4.Drain pan is injection molded high temperature UL approved plastic. 5.All coils are equipped with factory-installed TXV, 15% bleed type. Enertech Global, LLC 14 L M N 13.8 9.2 O ⚠ WARNING ⚠ IF USING A DUAL FUEL APPLICATION, “A” COIL MUST BE INSTALLED ON THE OUTLET OF THE FURNACE. INSTALLATION ON THE RETURN COULD CAUSE FURNACE HEAT EXCHANGER FAILURE, AND MAY VOID FURNACE WARRANTY. 20D218-17NN BS/BT Rev A ENGINEERING SPECIFICATIONS: Section 4: Equipment Data 20D237‐16NN: BS/BT‐Electrical Data Unit Electrical Data Model BS018 BT024 BT036 BT048 BT060 BT072 60 Hz Power RLA Fan Motor FLA HWG Pump FLA Ext. Loop Pump FLA 9.0 9.0 9.0 9.0 11.7 11.7 11.7 11.7 6.5 6.5 15.3 15.3 15.3 15.3 11.6 11.6 21.2 21.2 21.2 21.2 14.0 14.0 27.1 27.1 27.1 27.1 16.5 16.5 29.7 29.7 29.7 29.7 17.6 17.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.5 0.0 0.5 0.0 0.5 0.0 0.5 0.0 0.5 0.0 0.5 0.0 0.5 0.0 0.5 0.0 0.5 0.0 0.5 0.0 0.5 0.0 0.5 0.0 0.5 0.0 0.5 0.0 0.5 0.0 0.5 0.0 0.5 0.0 0.0 4.0 4.0 0.0 0.0 4.0 4.0 0.0 0.0 0.0 0.0 4.0 4.0 0.0 0.0 0.0 0.0 5.5 5.5 0.0 0.0 0.0 0.0 5.5 5.5 0.0 0.0 0.0 0.0 5.5 5.5 0.0 0.0 Compressor Voltage Code/ HWG Option Volts Phase LRA 00 01 10 11 00 01 10 11 20 21 00 01 10 11 20 21 00 01 10 11 20 21 00 01 10 11 20 21 00 01 10 11 20 21 208/230 208/230 208/230 208/230 208/230 208/230 208/230 208/230 208/230 208/230 208/230 208/230 208/230 208/230 208/230 208/230 208/230 208/230 208/230 208/230 208/230 208/230 208/230 208/230 208/230 208/230 208/230 208/230 208/230 208/230 208/230 208/230 208/230 208/230 1 1 1 1 1 1 1 1 3 3 1 1 1 1 3 3 1 1 1 1 3 3 1 1 1 1 3 3 1 1 1 1 3 3 48.0 48.0 48.0 48.0 58.3 58.3 58.3 58.3 55.4 55.4 83.0 83.0 83.0 83.0 73.0 73.0 104.0 104.0 104.0 104.0 83.1 83.1 152.9 152.9 152.9 152.9 110.0 110.0 179.2 179.2 179.2 179.2 136.0 136.0 Min Total Circuit Unit FLA AMPS 9.0 9.5 13.0 13.5 11.7 12.2 15.7 16.2 6.5 7.0 15.3 15.8 19.3 19.8 11.6 12.1 21.2 21.7 26.7 27.2 14.0 14.5 27.1 27.6 32.6 33.1 16.5 17.0 29.7 30.2 35.2 35.7 17.6 18.1 11.3 11.8 15.3 15.8 14.6 15.1 18.6 19.1 8.1 8.6 19.1 19.6 23.1 23.6 14.5 15.0 26.5 27.0 32.0 32.5 17.5 18.0 33.9 34.4 39.4 39.9 20.6 21.1 37.1 37.6 42.6 43.1 22.0 22.5 Max Fuse HACR 20 20 20 25 25 25 30 30 15 15 30 35 35 35 25 25 45 45 50 50 30 30 60 60 60 60 35 35 60 60 70 70 40 40 Notes: 1. All line and low voltage wiring must adhere to the National Electrical Code and local codes, whichever is the most stringent. 2. In determining the correct supply wire size and maximum length, reference NFPA 70, Section 310. If the calculation is close to the maximum allowable ampacity of a particular wire size, use the next size up. This will ensure that no adverse effects occur, such as light dimming and/or shortened compressor life. 3. All fuses class RK-5. 4. Min/Max Voltage: 208/230/60 = 187-252 *The external loop pump FLA is based on a maximum of three UP26-116F-230V pumps (1/2hp) for 048-072 and two pumps for 018-036. 20D218-17NN BS/BT Rev A 15 Enertech Global, LLC ENGINEERING SPECIFICATIONS: Section 4: Equipment Data MPD Air Handler Fan Speeds Model Number BST024 with MPD024A Change to: COOL Jumper C HEAT Jumper C ADJUST Jumper ‐ BST036 with MPD036A Change to: COOL Jumper C HEAT Jumper C ADJUST Jumper Norm BST048 with MPD060B Change to: COOL Jumper C HEAT Jumper C ADJUST Jumper Norm BST060 with MPD060B Ship Set On: COOL Jumper B HEAT Jumper B ADJUST Jumper Norm BST072 with MPD072A Change to: COOL Jumper C HEAT Jumper C ADJUST Jumper + COOL Jumper A B C D A B C D A B C D A B C D A B C D A B C D A B C D A B C D A B C D A B C D A B C D A B C D HEAT Jumper A B C D A B C D A B C D A B C D A B C D A B C D A B C D A B C D A B C D A B C D A B C D A B C D ADJUST Jumper ‐ ‐ ‐ ‐ Norm Norm Norm Norm + + + + ‐ ‐ ‐ ‐ Norm Norm Norm Norm + + + + ‐ ‐ ‐ ‐ Norm Norm Norm Norm + + + + ‐ ‐ ‐ ‐ Norm Norm Norm Norm + + + + .40" 920 910 910 820 930 930 870 870 930 930 930 930 1510 1450 1200 1060 1560 1550 1300 1150 1560 1550 1530 1320 1710 1610 1350 1260 2180 2020 1710 1570 2240 2230 1940 1810 2400 2400 1640 1450 2510 2500 2080 1850 2570 2380 2160 High SPD CFM Y2 .60" .80" 920 910 900 900 900 900 800 800 930 920 920 890 860 820 840 810 930 920 930 900 930 890 930 890 1500 1490 1430 1420 1150 1150 1040 1030 1560 1510 1550 1520 1310 1310 1150 1140 1560 1510 1550 1520 1520 1500 1320 1320 1700 1690 1600 1580 1340 1330 1250 1230 2170 2120 2020 2000 1700 1690 1570 1550 2170 2120 2170 2110 1920 1910 1800 1750 2400 2390 2400 2390 1630 1610 1450 1440 2510 2500 2460 2420 2070 2050 1850 1830 2510 2370 2130 2450 2360 2120 Low SPD CFM Y1 .60" .80" 810 800 740 720 700 670 660 640 820 810 750 730 700 670 680 650 930 920 860 830 800 760 780 750 1270 1260 1100 1090 890 890 800 800 1450 1430 1240 1230 1010 1010 870 870 1570 1520 1430 1430 1160 1160 1020 1010 1410 1400 1320 1300 1110 1100 1040 1030 1810 1780 1680 1660 1410 1400 1300 1270 1860 1820 1870 1850 1610 1600 1500 1470 2040 2030 1860 1850 1180 1170 1060 1040 2510 2500 2340 2330 1520 1500 1330 1310 Not Available 2570 2510 2550 1780 1750 1730 1540 1520 1500 .40" 820 750 710 680 830 770 710 700 930 880 810 800 1290 1120 900 820 1450 1240 1010 880 1570 1430 1160 1020 1420 1330 1130 1060 1810 1680 1410 1320 1890 1900 1610 1500 2040 1860 1190 1060 2510 2340 1530 1330 .40" 420 370 350 330 420 380 360 350 470 440 410 400 540 410 350 N/A 570 480 400 320 670 560 450 400 860 810 680 640 1160 1090 950 910 1290 1220 1030 1000 1020 930 610 550 1300 1160 700 570 FAN G .60" 410 360 340 320 410 370 350 340 460 430 400 390 530 400 340 N/A 540 430 350 290 630 530 400 350 850 800 670 630 1140 1090 930 990 1270 1200 1020 980 1020 930 590 530 1300 1160 620 460 .80" 400 350 330 310 410 360 330 330 460 420 380 370 520 400 330 N/A 500 410 300 N/A 620 490 380 300 850 790 660 620 1140 1050 910 960 1250 1190 980 950 1010 910 570 510 1270 1140 530 420 1390 820 720 1390 760 640 1370 690 540 Notes: 1. Dehumidification mode can be enabled by cutting the jumper on the ECM board. When cut, cooling CFM is reduced by 15%, and heating/ auxiliary heat CFM remains unchanged. Example: Model 036 with HEAT and COOL jumpers on C setting and ADJUST jumper on Norm setting would run at 1115 CFM with jumper cut, instead of 1310 CFM with jumper intact. 2. Gray shaded areas are recommended settings. Other settings may be used, depending upon application. DO NOT cut dehumidification jumper if CFM setting will cause airflow to be below 250 CFM per ton on first stage, and below 325 CFM per ton on second stage. Example: Model 036 should not run below 750 CFM in frist stage, or below 975 CFM in second stage. 3. The COOL and HEAT jumpers should both be set at the same position. COOL controls heating and cooling airflow; HEAT controls electric heat airflow. 4. Above CFM will be maintained up to 0.50" ESP for models MPD024 and 036, and up to 0.75" ESP for models MPD048 and 060. Enertech Global, LLC 16 20D218-17NN BS/BT Rev A ENGINEERING SPECIFICATIONS: Section 4: Equipment Data Air Handler Electrical Data 60 HZ Power Model MPD024A MPD036A MPD060B MPD072A Volts Phase 208/230 1 208/230 208/230 208/230 1 1 1 Field-Installed Elect Heat Motor Amps / HP Minimum Circuit Ampacity2 Maximum Fuse Size2 3.5 10 54.9 60 5.4 10 # Circuits kW1 None 0 1 10 None 0 1 10 56.4 60 2 15 30.3 / 56.4 40 / 70 None 0 8.5 15 1 10 58.9 70 2 15 32.8 / 58.9 40 / 70 2.8 / 0.33 4.3 / 0.50 6.8 / 1.0 2 20 58.9 / 58.9 70 / 70 None 0 8.5 15 1 10 58.9 70 2 2 15 32.8 / 58.9 40 / 70 58.9 / 58.9 70 / 70 20 6.8 / 1.0 Notes: 1.Nominal kW at 240V. Derate 25% for 208V. 2.Units with field-installed electric heat 15kW and larger have two circuits. Data shown as “XX/ XX” refers to circuit 1 before the “/” and circuit 2 after the “/” 3.Always refer to unit nameplate data prior to installation 20D218-17NN BS/BT Rev A 17 Enertech Global, LLC ENGINEERING SPECIFICATIONS: Section 5: Glossary of Terms and Correction Factors Glossary of Terms CFM = Airflow, Cubic Feet/Minute HR = Total Heat Of Rejection, Btu/hr COP = Coefficient of Performance = BTU Output / BTU Input KW = Total Power Unit Input, Kilowatts DH = Desuperheater Capacity, Btu/hr LAT = Leaving Air Temperature, Fahrenheit EAT = Entering Air Temperature, Fahrenheit (Dry Bulb/Wet Bulb) LC = Latent Cooling Capacity, Btu/hr EER = Energy Efficiency Ratio = BTU output/Watts input SC = Sensible Cooling Capacity, Btu/hr EWT = Entering Source Water Temperature, Fahrenheit LWT = Leaving Source Water Temperature, Fahrenheit ELT = Entering Load Water Temperature, Fahrenheit LLT = Leaving Load Water Temperature, Fahrenheit GPM = Water Flow, Gallons Per Minute TC = Total Cooling Capacity, Btu/hr HC = Total Heating Capacity, Btu/hr WPD = Water Pressure Drop, PSI & Feet of Water HE = Total Heat Of Extraction, Btu/hr Sensible Cooling Correction Factors: Cooling Correction Factors: EAT (DB) °F EAT (WB) °F 70 75 55 1.201 1.289 60 0.943 1.067 1.192 65 0.797 0.952 1.106 1.261 67 0.624 0.812 1.000 1.188 1.343 0.697 0.820 0.944 1.067 0.637 0.817 0.983 70 75 80 85 90 EAT (WB) °F TC HR kW 55 0.8215 0.8293 0.8635 60 0.8955 0.9001 0.9205 65 0.9701 0.9715 0.9774 67 1.0000 1.0000 1.0000 70 1.0446 1.0425 1.0335 75 1.1179 1.1124 1.0878 Heating & Cooling Calculations: LAT = EAT + Heating Correction Factors: Heating Cooling EAT °F HC HE kW HC CFM x 1.08 LAT (DB) = EAT (DB) SC CFM x 1.08 50 1.0465 1.1188 0.8024 55 1.0351 1.0918 0.8436 60 1.0253 1.0645 0.8928 65 1.0108 1.0300 0.9454 70 1.0000 1.0000 1.0000 75 0.9895 0.9701 1.0553 80 0.9742 0.9489 1.0518 LWT = EWT HE GPM x 500 LWT = EWT + HR GPM x 500 LC = TC - SC Enertech Global, LLC 18 20D218-17NN BS/BT Rev A ENGINEERING SPECIFICATIONS: Section 6: Water Flow Calculations and Selection Water Flow Calculations and Selection Proper flow rate is crucial for reliable operation of geothermal heat pumps. The performance data shows three flow rates for each entering water temperature (EWT column). The general “rule of thumb” when selecting flow rates is the following: Top flow rate: Open loop systems (1.5 to 2.0 gpm per ton) Middle flow rate: Minimum closed loop system flow rate (2.25 to 2.50 gpm/ton) Bottom flow rate: Nominal (optimum) closed loop system flow rate (3.0 gpm/ton) Although the “rule of thumb” is adequate in most areas of North America, it is important to consider the application type before applying this “rule of thumb.” Antifreeze is generally required for all closed loop (geothermal) applications. Extreme Southern U.S. locations are the only exception. Open loop (well water) systems cannot use antifreeze, and must have enough flow rate in order to avoid freezing conditions at the Leaving Source Water Temperature (LWT) connection. Calculations must be made for all systems without antifreeze to determine if the top flow rate is adequate to prevent LWT at or near freezing conditions. The following steps should taken in making this calculation: Determine minimum EWT based upon your geographical area. Go to the performance data table for the heat pump model selected and look up the the Heat of Extraction (HE) at the “rule of thumb” water flow rate (GPM) and at the design Entering Air Temperature (EAT). Example 1: EWT = 50°F. Model GXT048, high capacity. Flow rate = 6 GPM. Air Flow = 1500 CFM. HE = 36,700 Btuh. TD = 36,700 / (6 x 500) = 12.2°F LWT = 50 - 12.2 = 37.8°F Since the water flow is leaving at approximately 38°F, the flow rate is acceptable. Example 2: EWT = 40°F. Model GXT048, high capacity. Flow rate = 6 GPM. Air Flow = 1500 CFM. HE = 36,700 Btuh. TD = 36,700 / (6 x 500) = 12.2°F LWT = 40 - 12.2 = 27.8°F Water flow rate must be increased to avoid freezing. Performance Data Notes: 1. Capacity data is based upon 15% (by volume) methanol antifreeze solution. 2. Desuperheater capacity is based upon 0.2 GPM Flow per nominal ton at 70°F entering hot water temperature. 3. Interpolation between above categories is permissible; extrapolation is not. 4. See Flow Rate Selection above for proper application. Calculate the temperature difference (TD) based upon the HE and GPM of the model. TD = HE / (GPM x 500). Calculate the LWT. LWT = EWT - TD. If the LWT is below 35-38°F, there is potential for freezing conditions if the flow rate or water temperature is less than ideal conditions, and the flow rate must be increased. 20D218-17NN BS/BT Rev A 19 Enertech Global, LLC ENGINEERING SPECIFICATIONS: Section 7: Extended Data BS018 EWT Flow °F GPM 25 30 40 50 60 70 80 90 100 110 120 WPD PSI FT 4.5 3.6 8.3 2.3 1.2 2.8 3.4 2.2 5.0 4.5 3.3 7.5 2.3 1.1 2.6 3.4 2.0 4.7 4.5 3.0 7.0 2.3 1.0 2.4 3.4 1.9 4.3 4.5 2.8 6.4 2.3 1.0 2.2 3.4 1.7 4.0 4.5 2.6 6.0 2.3 0.9 2.1 3.4 1.6 3.7 4.5 2.4 5.6 2.3 0.8 2.0 3.4 1.5 3.5 4.5 2.3 5.2 2.3 0.8 1.8 3.4 1.4 3.3 4.5 2.1 4.9 2.3 0.7 1.7 3.4 1.3 3.1 4.5 2.0 4.6 2.3 0.7 1.6 3.4 1.3 2.9 4.5 1.9 4.4 2.3 0.7 1.6 3.4 1.2 2.8 4.5 1.8 4.2 Enertech Global, LLC Aiflow LAT (DB) Full Load Heating HC HE Power COP DH CFM °F MBtuh MBtuh kW W/W MBtuh 700 850 700 850 700 850 700 850 700 850 700 850 700 850 700 850 700 850 700 850 700 850 700 850 700 850 700 850 700 850 700 850 700 850 700 850 700 850 700 850 700 850 700 850 87.9 85.3 87.7 85.1 88.6 85.9 89.0 86.2 90.1 87.1 91.1 88.0 91.5 88.4 92.7 89.4 93.9 90.4 94.4 90.8 95.5 91.8 96.8 92.9 97.3 93.4 98.2 94.1 99.6 95.3 100.2 95.8 100.6 96.2 102.2 97.5 102.8 98.1 102.6 97.9 104.3 99.3 105.0 99.9 13.5 14.1 13.4 13.9 14.1 14.6 14.4 14.9 15.2 15.7 15.9 16.6 16.3 16.9 17.2 17.8 18.1 18.7 18.4 19.1 19.3 20.0 20.3 21.0 20.7 21.4 21.3 22.1 22.4 23.2 22.8 23.7 23.1 24.0 24.3 25.2 24.8 25.8 24.6 25.6 25.9 26.9 26.4 27.4 9.5 9.9 9.4 9.8 10.0 10.4 10.3 10.7 11.1 11.5 11.8 12.2 12.1 12.5 13.0 13.5 13.8 14.3 14.1 14.7 15.0 15.6 15.9 16.5 16.2 16.9 16.9 17.6 17.9 18.6 18.3 19.0 18.6 19.4 19.7 20.5 20.2 21.0 20.0 20.8 21.2 22.0 21.7 22.5 1.19 1.23 1.2 1.2 1.19 1.23 1.21 1.24 1.20 1.23 1.22 1.26 1.24 1.28 1.23 1.27 1.26 1.30 1.27 1.31 1.26 1.30 1.29 1.33 1.30 1.34 1.29 1.33 1.32 1.36 1.33 1.37 1.32 1.36 1.35 1.39 1.36 1.41 1.35 1.39 1.38 1.42 1.39 1.44 3.34 3.36 3.4 3.4 3.46 3.48 3.49 3.52 3.72 3.74 3.82 3.84 3.86 3.88 4.10 4.13 4.21 4.24 4.26 4.28 4.49 4.51 4.61 4.64 4.66 4.69 4.84 4.87 4.97 5.00 5.03 5.06 5.14 5.17 5.28 5.31 5.33 5.37 5.36 5.39 5.50 5.54 5.56 5.59 3.4 3.1 3.3 3.0 3.5 3.2 3.6 3.3 3.7 3.4 3.9 3.6 4.0 3.7 4.2 3.9 4.5 4.1 4.6 4.2 4.8 4.4 5.1 4.7 5.3 4.8 5.5 5.0 5.8 5.3 6.0 5.5 6.1 5.6 6.5 6.0 6.7 6.1 6.7 6.2 7.2 6.6 7.4 6.8 Operation Not Recommended 20 Aiflow LAT (DB) CFM °F TC MBtuh Full Load Cooling SC HR Power MBtuh MBtuh kW EER DH Btuh/W MBtuh 30.8 28.9 24.3 22.8 26.4 24.8 27.6 25.9 21.5 20.2 23.4 21.9 24.4 22.9 18.7 17.5 20.3 19.1 21.2 19.9 15.9 14.9 17.3 16.2 18.0 16.9 13.2 12.4 14.3 13.4 15.0 14.0 10.7 10.0 11.6 10.9 12.1 11.4 8.5 8.0 9.3 8.7 9.7 9.1 6.7 6.2 7.2 6.8 7.6 7.1 1.0 1.0 2.6 2.7 2.1 2.2 1.9 1.9 3.6 3.6 3.0 3.1 2.7 2.8 4.6 4.7 4.0 4.0 3.7 3.7 5.7 5.8 5.0 5.1 4.6 4.7 6.8 7.0 6.1 6.2 5.7 5.8 8.2 8.3 7.3 7.5 6.9 7.0 9.6 9.8 8.7 8.9 8.2 8.4 11.2 11.4 10.2 10.4 9.7 9.9 Operation Not Recommended 700 850 700 850 700 850 700 850 700 850 700 850 700 850 700 850 700 850 700 850 700 850 700 850 700 850 700 850 700 850 700 850 700 850 700 850 700 850 700 850 700 850 700 850 700 850 700 850 700 850 60.7 62.8 59.9 62.0 59.8 62.0 59.7 61.9 59.6 61.7 59.5 61.6 59.4 61.6 59.7 61.9 59.6 61.8 59.5 61.7 60.3 62.3 60.2 62.3 60.1 62.2 61.0 63.0 61.0 63.0 60.9 62.9 61.9 63.8 61.9 63.8 61.8 63.7 62.8 64.6 62.7 64.6 62.7 64.5 63.6 65.3 63.5 65.2 63.4 65.2 21.6 21.8 21.5 21.8 21.7 21.9 21.8 22.0 21.3 21.5 21.4 21.7 21.5 21.8 20.7 20.9 20.8 21.1 20.9 21.2 19.8 20.0 19.9 20.2 20.0 20.3 18.6 18.9 18.8 19.0 18.9 19.1 17.4 17.6 17.5 17.7 17.6 17.8 16.0 16.2 16.1 16.3 16.2 16.4 14.7 14.8 14.8 15.0 14.9 15.0 14.6 15.8 15.2 16.5 15.2 16.6 15.3 16.6 15.4 16.8 15.5 16.8 15.6 16.9 15.3 16.7 15.4 16.7 15.5 16.8 14.9 16.2 15.0 16.3 15.1 16.4 14.3 15.6 14.4 15.6 14.5 15.7 13.7 14.8 13.7 14.9 13.8 15.0 13.0 14.1 13.0 14.2 13.1 14.2 12.4 13.5 12.5 13.6 12.6 13.6 24.0 24.4 24.5 25.0 24.5 25.0 24.5 25.0 24.7 25.2 24.6 25.1 24.5 25.0 24.4 25.0 24.3 24.8 24.3 24.8 24.0 24.6 23.9 24.4 23.8 24.3 23.5 24.1 23.3 23.8 23.2 23.7 22.9 23.6 22.6 23.3 22.5 23.1 22.5 23.2 22.1 22.8 22.0 22.6 22.2 23.0 21.7 22.5 21.5 22.2 0.70 0.76 0.89 0.96 0.82 0.89 0.79 0.85 0.99 1.07 0.92 0.99 0.88 0.95 1.11 1.19 1.03 1.11 0.99 1.06 1.25 1.34 1.15 1.24 1.11 1.20 1.42 1.53 1.31 1.41 1.26 1.36 1.63 1.75 1.51 1.62 1.45 1.56 1.89 2.03 1.75 1.88 1.68 1.81 2.20 2.38 2.04 2.20 1.96 2.12 20D218-17NN BS/BT Rev A ENGINEERING SPECIFICATIONS: Section 7: Extended Data BT024 EWT Flow °F GPM 25 30 40 50 60 70 80 90 100 110 120 WPD PSI FT 6.0 5.6 12.9 3.0 2.1 4.9 4.5 3.5 8.1 6.0 5.0 11.6 3.0 2.0 4.6 4.5 3.3 7.5 6.0 4.7 10.8 3.0 1.8 4.2 4.5 3.0 6.9 6.0 4.3 9.9 3.0 1.7 3.9 4.5 2.8 6.4 6.0 4.0 9.2 3.0 1.6 3.6 4.5 2.6 6.0 6.0 3.7 8.5 3.0 1.5 3.4 4.5 2.4 5.6 6.0 3.5 8.0 3.0 1.4 3.2 4.5 2.3 5.3 6.0 3.3 7.6 3.0 1.4 3.2 4.5 2.2 5.1 6.0 3.1 7.1 3.0 1.3 3.1 4.5 2.1 4.9 6.0 2.9 6.8 3.0 1.3 3.0 4.5 2.0 4.7 6.0 2.8 6.5 Aiflow LAT (DB) Full Load Heating HC HE Power COP DH CFM °F MBtuh MBtuh kW W/W MBtuh 900 1000 900 1000 900 1000 900 1000 900 1000 900 1000 900 1000 900 1000 900 1000 900 1000 900 1000 900 1000 900 1000 900 1000 900 1000 900 1000 900 1000 900 1000 900 1000 900 1000 900 1000 900 1000 87.2 85.7 87.7 86.2 88.3 86.8 88.4 86.9 90.3 88.5 91.0 89.2 91.1 89.3 92.9 91.0 93.7 91.7 93.9 91.8 95.6 93.4 96.4 94.2 96.6 94.3 98.0 95.6 99.0 96.5 99.1 96.7 100.2 97.6 101.2 98.5 101.4 98.7 101.9 99.2 103.0 100.1 103.2 100.3 16.7 17.0 17.2 17.5 17.8 18.1 17.9 18.2 19.7 20.0 20.4 20.7 20.5 20.8 22.3 22.6 23.0 23.4 23.2 23.6 24.8 25.2 25.7 26.1 25.8 26.3 27.2 27.7 28.1 28.6 28.3 28.8 29.3 29.8 30.3 30.8 30.5 31.0 31.0 31.5 32.0 32.6 32.2 32.8 11.5 11.4 12.0 12.0 12.5 12.5 12.6 12.6 14.3 14.3 14.9 14.9 15.0 15.0 16.7 16.8 17.4 17.4 17.5 17.6 19.1 19.1 19.8 19.9 20.0 20.0 21.2 21.3 22.1 22.2 22.2 22.3 23.1 23.2 24.0 24.1 24.2 24.3 24.6 24.7 25.5 25.6 25.7 25.8 1.54 1.63 1.5 1.6 1.56 1.64 1.56 1.65 1.58 1.67 1.60 1.69 1.61 1.70 1.63 1.73 1.66 1.75 1.66 1.76 1.69 1.79 1.72 1.82 1.73 1.82 1.76 1.86 1.79 1.89 1.79 1.89 1.82 1.93 1.85 1.96 1.86 1.96 1.89 1.99 1.92 2.02 1.92 2.03 3.18 3.06 3.3 3.2 3.36 3.23 3.37 3.24 3.66 3.52 3.73 3.58 3.74 3.60 4.00 3.85 4.07 3.92 4.09 3.93 4.30 4.13 4.37 4.21 4.39 4.22 4.54 4.36 4.62 4.44 4.64 4.46 4.71 4.53 4.80 4.61 4.81 4.63 4.82 4.63 4.90 4.71 4.92 4.73 4.2 4.1 4.2 4.2 4.4 4.3 4.4 4.4 4.8 4.7 5.0 4.9 5.0 5.0 5.4 5.3 5.7 5.6 5.7 5.6 6.1 6.0 6.4 6.3 6.4 6.4 6.7 6.7 7.1 7.0 7.1 7.1 7.3 7.3 7.7 7.6 7.8 7.7 7.9 7.8 8.3 8.2 8.3 8.3 20D218-17NN BS/BT Rev A Operation Not Recommended 21 Aiflow LAT (DB) CFM °F TC MBtuh Full Load Cooling SC HR Power MBtuh MBtuh kW EER DH Btuh/W MBtuh 22.8 21.8 20.2 19.4 21.2 20.2 21.5 20.6 18.4 17.6 19.2 18.4 19.6 18.7 16.4 15.7 17.2 16.4 17.5 16.7 14.4 13.8 15.1 14.4 15.4 14.7 12.4 11.9 13.0 12.4 13.2 12.6 10.3 9.9 10.8 10.3 11.0 10.5 8.3 8.0 8.7 8.3 8.9 8.5 6.8 6.5 7.1 6.8 7.2 6.9 1.8 1.8 3.2 3.3 2.8 2.8 2.8 2.8 4.2 4.3 3.8 3.8 3.7 3.8 5.3 5.3 4.8 4.8 4.7 4.7 6.4 6.5 5.8 5.9 5.8 5.8 7.7 7.8 7.1 7.1 7.0 7.1 9.2 9.3 8.4 8.5 8.4 8.4 10.9 11.0 10.0 10.1 9.9 10.0 12.6 12.8 11.7 11.8 11.6 11.7 Operation Not Recommended 900 1000 900 1000 900 1000 900 1000 900 1000 900 1000 900 1000 900 1000 900 1000 900 1000 900 1000 900 1000 900 1000 900 1000 900 1000 900 1000 900 1000 900 1000 900 1000 900 1000 900 1000 900 1000 900 1000 900 1000 900 1000 62.0 63.1 60.9 62.1 60.8 62.1 60.8 62.0 60.5 61.8 60.5 61.7 60.5 61.7 60.6 61.8 60.5 61.8 60.5 61.8 60.8 62.0 60.8 62.0 60.8 62.0 61.2 62.4 61.2 62.4 61.2 62.4 61.9 63.0 61.9 63.0 61.8 63.0 62.8 63.9 62.8 63.9 62.8 63.8 64.0 65.0 63.9 65.0 63.9 64.9 26.3 26.7 26.6 27.0 26.8 27.1 26.9 27.2 26.1 26.5 26.3 26.6 26.4 26.7 25.3 25.7 25.5 25.8 25.6 25.9 24.4 24.7 24.5 24.9 24.6 25.0 23.2 23.5 23.3 23.6 23.4 23.7 21.6 21.9 21.7 22.0 21.8 22.1 19.8 20.0 19.9 20.2 20.0 20.2 18.4 18.6 18.5 18.7 18.6 18.8 17.5 18.2 18.6 19.4 18.6 19.4 18.6 19.4 18.9 19.7 19.0 19.7 19.0 19.8 18.9 19.7 18.9 19.7 18.9 19.7 18.6 19.4 18.7 19.4 18.7 19.5 18.2 19.0 18.3 19.0 18.3 19.0 17.6 18.3 17.6 18.4 17.7 18.4 16.7 17.4 16.7 17.4 16.8 17.4 15.6 16.2 15.6 16.2 15.6 16.3 30.3 30.9 31.1 31.7 31.1 31.7 31.1 31.8 31.0 31.6 30.9 31.6 31.0 31.6 30.6 31.2 30.5 31.2 30.6 31.2 30.1 30.8 30.1 30.7 30.1 30.8 29.5 30.2 29.5 30.1 29.5 30.1 28.7 29.4 28.6 29.3 28.6 29.3 27.8 28.6 27.7 28.4 27.6 28.4 27.6 28.4 27.4 28.2 27.3 28.1 1.16 1.23 1.31 1.39 1.27 1.34 1.25 1.32 1.42 1.50 1.37 1.45 1.35 1.43 1.54 1.63 1.48 1.57 1.46 1.55 1.69 1.79 1.62 1.72 1.60 1.70 1.87 1.98 1.80 1.91 1.77 1.88 2.09 2.22 2.02 2.14 1.99 2.11 2.37 2.51 2.28 2.42 2.25 2.39 2.71 2.87 2.61 2.76 2.57 2.73 Enertech Global, LLC ENGINEERING SPECIFICATIONS: Section 7: Extended Data BT036 EWT Flow °F GPM 25 30 40 50 60 70 80 90 100 110 120 WPD PSI FT 9.0 3.5 8.0 4.5 1.2 2.8 6.8 2.1 4.8 9.0 3.2 7.4 4.5 1.2 2.7 6.8 2.0 4.5 9.0 3.1 7.1 4.5 1.1 2.5 6.8 1.8 4.2 9.0 2.8 6.5 4.5 1.0 2.3 6.8 1.7 3.9 9.0 2.6 6.0 4.5 0.9 2.1 6.8 1.6 3.6 9.0 2.4 5.6 4.5 0.9 2.0 6.8 1.5 3.4 9.0 2.3 5.2 4.5 0.8 1.9 6.8 1.4 3.2 9.0 2.2 5.0 4.5 0.8 1.9 6.8 1.4 3.1 9.0 2.1 4.9 4.5 0.8 1.8 6.8 1.3 3.0 9.0 2.0 4.7 4.5 0.8 1.8 6.8 1.2 2.9 9.0 2.0 4.5 Aiflow LAT (DB) Full Load Heating HC HE Power COP DH CFM °F MBtuh MBtuh kW W/W MBtuh 1100 1300 1100 1300 1100 1300 1100 1300 1100 1300 1100 1300 1100 1300 1100 1300 1100 1300 1100 1300 1100 1300 1100 1300 1100 1300 1100 1300 1100 1300 1100 1300 1100 1300 1100 1300 1100 1300 1100 1300 1100 1300 1100 1300 91.8 88.7 91.7 88.6 92.8 89.5 93.5 90.1 94.9 91.3 96.2 92.4 97.0 93.1 98.2 94.2 99.7 95.4 100.6 96.2 101.6 97.1 103.2 98.5 104.3 99.4 105.0 100.0 106.9 101.6 108.0 102.6 108.6 103.1 110.6 104.8 111.9 105.9 112.2 106.2 114.4 108.0 115.8 109.2 25.9 26.2 25.7 26.1 27.1 27.4 27.9 28.3 29.6 29.9 31.1 31.5 32.1 32.5 33.5 33.9 35.2 35.7 36.4 36.8 37.5 38.0 39.5 40.0 40.7 41.2 41.6 42.2 43.8 44.3 45.2 45.7 45.8 46.4 48.2 48.8 49.8 50.4 50.1 50.8 52.7 53.4 54.4 55.1 18.0 18.4 17.9 18.3 19.1 19.5 19.9 20.3 21.4 21.9 22.8 23.3 23.7 24.2 25.0 25.5 26.6 27.1 27.6 28.2 28.7 29.2 30.4 31.0 31.6 32.2 32.3 32.9 34.3 34.9 35.6 36.2 36.0 36.6 38.2 38.9 39.6 40.3 39.6 40.3 42.0 42.8 43.6 44.3 2.30 2.28 2.3 2.3 2.33 2.30 2.35 2.33 2.38 2.36 2.42 2.40 2.45 2.43 2.48 2.46 2.53 2.51 2.56 2.54 2.60 2.57 2.64 2.62 2.68 2.65 2.73 2.71 2.78 2.76 2.81 2.79 2.89 2.87 2.95 2.92 2.98 2.95 3.09 3.06 3.15 3.12 3.18 3.16 3.30 3.37 3.3 3.4 3.41 3.49 3.48 3.56 3.64 3.72 3.76 3.84 3.83 3.92 3.95 4.04 4.08 4.17 4.16 4.25 4.23 4.33 4.37 4.47 4.46 4.56 4.47 4.56 4.62 4.72 4.71 4.81 4.64 4.74 4.80 4.90 4.89 5.00 4.75 4.86 4.91 5.02 5.01 5.12 6.7 6.2 6.7 6.1 7.0 6.4 7.2 6.6 7.5 6.9 7.9 7.3 8.1 7.5 8.4 7.8 8.9 8.2 9.2 8.4 9.5 8.7 10.0 9.2 10.3 9.5 10.7 9.8 11.3 10.4 11.6 10.7 12.0 11.1 12.7 11.7 13.1 12.1 13.5 12.5 14.3 13.2 14.7 13.6 Enertech Global, LLC Operation Not Recommended 22 Aiflow LAT (DB) CFM °F TC MBtuh Full Load Cooling SC HR Power MBtuh MBtuh kW EER DH Btuh/W MBtuh 20.9 20.6 18.9 18.6 20.0 19.7 20.5 20.2 17.8 17.5 18.8 18.6 19.2 19.0 16.5 16.2 17.5 17.2 17.8 17.6 14.3 14.1 15.2 15.0 15.5 15.3 12.5 12.3 13.2 13.0 13.5 13.3 10.6 10.5 11.3 11.1 11.5 11.3 8.9 8.8 9.5 9.3 9.7 9.5 7.4 7.3 7.9 7.7 8.0 7.9 3.4 3.5 5.1 5.3 4.6 4.8 4.4 4.5 6.4 6.6 5.8 5.9 5.5 5.7 7.9 8.0 7.1 7.3 6.8 7.0 9.4 9.6 8.6 8.7 8.2 8.4 11.1 11.3 10.1 10.3 9.7 9.9 12.9 13.2 11.8 12.0 11.3 11.5 14.7 15.0 13.5 13.8 13.0 13.3 16.6 17.0 15.4 15.7 14.8 15.0 Operation Not Recommended 1100 1300 1100 1300 1100 1300 1100 1300 1100 1300 1100 1300 1100 1300 1100 1300 1100 1300 1100 1300 1100 1300 1100 1300 1100 1300 1100 1300 1100 1300 1100 1300 1100 1300 1100 1300 1100 1300 1100 1300 1100 1300 1100 1300 1100 1300 1100 1300 1100 1300 63.8 65.2 62.4 63.9 62.4 63.9 62.4 63.9 61.4 63.1 61.4 63.1 61.4 63.1 60.7 62.4 60.7 62.4 60.7 62.4 60.5 62.2 60.5 62.2 60.5 62.2 60.5 62.2 60.5 62.2 60.5 62.2 60.8 62.5 60.8 62.5 60.8 62.5 61.2 62.9 61.2 62.9 61.2 62.9 61.9 63.5 61.9 63.5 61.9 63.5 30.0 31.4 32.0 33.4 32.0 33.4 32.0 33.4 33.0 34.5 33.0 34.5 33.0 34.5 33.9 35.4 33.9 35.4 33.9 35.4 32.8 34.3 32.8 34.3 32.8 34.3 31.8 33.2 31.8 33.2 31.8 33.2 30.2 31.7 30.2 31.7 30.2 31.7 28.4 29.7 28.4 29.7 28.4 29.7 26.2 27.5 26.2 27.5 26.2 27.5 19.3 20.8 20.9 22.5 20.9 22.5 20.9 22.5 22.1 23.8 22.1 23.8 22.1 23.8 23.0 24.8 23.0 24.8 23.0 24.8 23.2 25.0 23.2 25.0 23.2 25.0 23.2 25.0 23.2 25.0 23.2 25.0 22.9 24.6 22.9 24.6 22.9 24.6 22.3 24.0 22.3 24.0 22.3 24.0 21.5 23.2 21.5 23.2 21.5 23.2 34.9 36.6 37.7 39.6 37.4 39.2 37.3 39.1 39.3 41.3 39.0 40.9 38.8 40.7 40.9 42.9 40.5 42.5 40.3 42.3 40.6 42.6 40.1 42.1 40.0 42.0 40.5 42.5 40.0 42.0 39.8 41.8 40.0 42.0 39.4 41.4 39.2 41.2 39.2 41.2 38.6 40.6 38.4 40.3 38.3 40.3 37.6 39.6 37.4 39.3 1.44 1.53 1.69 1.80 1.59 1.69 1.56 1.66 1.86 1.97 1.75 1.86 1.71 1.82 2.06 2.18 1.94 2.06 1.90 2.02 2.29 2.43 2.16 2.29 2.11 2.24 2.55 2.71 2.41 2.56 2.36 2.50 2.85 3.02 2.69 2.85 2.63 2.79 3.18 3.37 3.00 3.18 2.93 3.12 3.54 3.76 3.34 3.55 3.27 3.47 20D218-17NN BS/BT Rev A ENGINEERING SPECIFICATIONS: Section 7: Extended Data BT048 EWT Flow °F GPM 25 30 40 50 60 70 80 90 100 110 120 WPD PSI FT 12.0 5.0 11.5 6.0 1.6 3.6 9.0 2.9 6.7 12.0 4.5 10.4 6.0 1.5 3.4 9.0 2.7 6.3 12.0 4.3 9.8 6.0 1.4 3.2 9.0 2.5 5.9 12.0 4.0 9.1 6.0 1.3 2.9 9.0 2.4 5.5 12.0 3.7 8.5 6.0 1.2 2.8 9.0 2.2 5.1 12.0 3.5 8.0 6.0 1.1 2.6 9.0 2.1 4.8 12.0 3.3 7.5 6.0 1.1 2.5 9.0 2.0 4.6 12.0 3.1 7.1 6.0 1.0 2.4 9.0 1.9 4.3 12.0 2.9 6.7 6.0 1.0 2.3 9.0 1.8 4.1 12.0 2.8 6.4 6.0 0.9 2.2 9.0 1.7 4.0 12.0 2.7 6.1 Aiflow LAT (DB) Full Load Heating HC HE Power COP DH CFM °F MBtuh MBtuh kW W/W MBtuh 1400 1600 1400 1600 1400 1600 1400 1600 1400 1600 1400 1600 1400 1600 1400 1600 1400 1600 1400 1600 1400 1600 1400 1600 1400 1600 1400 1600 1400 1600 1400 1600 1400 1600 1400 1600 1400 1600 1400 1600 1400 1600 1400 1600 93.2 90.5 93.4 90.7 94.3 91.5 94.9 92.0 96.5 93.4 97.5 94.3 98.2 94.9 99.4 95.9 100.5 97.0 101.3 97.6 102.0 98.2 103.2 99.3 104.0 100.0 104.1 100.1 105.5 101.3 106.4 102.1 105.9 101.6 107.3 102.9 108.2 103.7 107.0 102.7 108.5 104.0 109.4 104.8 35.1 35.4 35.4 35.7 36.8 37.1 37.7 38.0 40.1 40.4 41.7 42.0 42.7 43.1 44.4 44.8 46.2 46.6 47.3 47.7 48.3 48.7 50.2 50.7 51.5 51.9 51.6 52.1 53.6 54.1 55.0 55.5 54.2 54.7 56.3 56.8 57.7 58.2 56.0 56.5 58.2 58.7 59.6 60.1 25.3 25.7 25.7 26.0 26.9 27.3 27.7 28.1 29.9 30.3 31.3 31.7 32.2 32.7 33.8 34.3 35.4 35.9 36.4 36.9 37.4 37.8 39.1 39.6 40.2 40.7 40.3 40.8 42.2 42.7 43.4 43.9 42.7 43.2 44.6 45.2 45.9 46.5 44.3 44.8 46.3 46.9 47.6 48.2 2.86 2.84 2.8 2.8 2.90 2.88 2.93 2.91 2.98 2.97 3.03 3.02 3.06 3.05 3.10 3.09 3.16 3.14 3.19 3.17 3.21 3.20 3.27 3.25 3.30 3.28 3.31 3.29 3.36 3.35 3.40 3.38 3.38 3.36 3.44 3.42 3.47 3.46 3.43 3.41 3.49 3.47 3.52 3.51 3.60 3.65 3.6 3.7 3.72 3.77 3.77 3.83 3.94 4.00 4.03 4.08 4.09 4.14 4.20 4.26 4.29 4.35 4.35 4.41 4.41 4.47 4.50 4.57 4.57 4.63 4.57 4.64 4.67 4.74 4.74 4.81 4.70 4.76 4.80 4.87 4.87 4.94 4.78 4.85 4.89 4.96 4.96 5.03 8.0 7.5 8.0 7.5 8.3 7.8 8.5 8.0 8.9 8.4 9.2 8.7 9.4 8.9 9.8 9.3 10.2 9.6 10.4 9.8 10.7 10.1 11.1 10.5 11.3 10.7 11.4 10.8 11.9 11.2 12.2 11.5 12.0 11.4 12.5 11.8 12.8 12.1 12.4 11.7 12.9 12.2 13.2 12.5 Operation Not Recommended 20D218-17NN BS/BT Rev A 23 Aiflow LAT (DB) CFM °F TC MBtuh Full Load Cooling SC HR Power MBtuh MBtuh kW EER DH Btuh/W MBtuh 30.7 30.2 25.4 24.9 27.3 26.9 28.2 27.8 22.2 21.8 23.9 23.5 24.7 24.3 19.1 18.8 20.6 20.2 21.3 20.9 16.4 16.1 17.6 17.3 18.2 17.9 13.9 13.7 15.0 14.8 15.5 15.3 11.7 11.5 12.6 12.3 13.0 12.8 9.6 9.4 10.3 10.1 10.6 10.5 7.8 7.6 8.4 8.2 8.7 8.5 3.5 3.5 6.1 6.1 5.3 5.3 4.9 4.9 7.8 7.8 6.8 6.8 6.4 6.4 9.6 9.6 8.5 8.5 8.0 8.0 11.5 11.6 10.3 10.4 9.7 9.8 13.7 13.7 12.3 12.3 11.6 11.7 16.0 16.0 14.4 14.5 13.7 13.8 18.5 18.6 16.7 16.8 15.9 16.0 21.3 21.4 19.3 19.4 18.4 18.5 Operation Not Recommended 1400 1600 1400 1600 1400 1600 1400 1600 1400 1600 1400 1600 1400 1600 1400 1600 1400 1600 1400 1600 1400 1600 1400 1600 1400 1600 1400 1600 1400 1600 1400 1600 1400 1600 1400 1600 1400 1600 1400 1600 1400 1600 1400 1600 1400 1600 1400 1600 1400 1600 55.4 57.1 54.3 56.1 54.3 56.0 54.2 56.0 54.8 56.5 54.7 56.4 54.7 56.4 55.6 57.2 55.5 57.2 55.5 57.1 56.3 57.9 56.2 57.8 56.2 57.8 56.9 58.4 56.8 58.4 56.8 58.3 57.7 59.2 57.6 59.1 57.6 59.1 58.7 60.1 58.6 60.1 58.6 60.0 59.5 60.9 59.4 60.8 59.4 60.8 57.2 58.1 57.9 58.7 58.2 59.1 58.3 59.1 56.0 56.8 56.3 57.2 56.4 57.2 53.5 54.3 53.8 54.6 53.9 54.7 51.2 51.9 51.4 52.2 51.5 52.3 48.9 49.6 49.1 49.9 49.2 49.9 46.2 46.9 46.5 47.2 46.5 47.2 43.1 43.7 43.3 44.0 43.4 44.0 40.1 40.7 40.3 40.9 40.4 41.0 37.2 39.6 38.8 41.3 38.9 41.5 39.0 41.5 38.1 40.6 38.2 40.7 38.3 40.8 36.9 39.3 37.0 39.4 37.1 39.5 35.9 38.2 36.0 38.3 36.1 38.4 35.0 37.2 35.1 37.4 35.1 37.4 33.8 36.0 33.9 36.1 33.9 36.1 32.2 34.3 32.3 34.4 32.4 34.5 31.0 33.1 31.1 33.2 31.2 33.2 63.6 64.7 65.7 66.8 65.4 66.6 65.3 66.4 64.6 65.7 64.3 65.5 64.2 65.3 63.1 64.2 62.7 63.8 62.5 63.6 61.8 62.9 61.4 62.5 61.1 62.2 60.8 62.0 60.3 61.4 60.0 61.1 59.8 60.9 59.1 60.2 58.8 59.9 58.5 59.6 57.7 58.8 57.3 58.4 57.7 58.9 56.7 57.9 56.3 57.4 1.86 1.92 2.28 2.36 2.13 2.20 2.06 2.13 2.52 2.61 2.36 2.43 2.28 2.36 2.80 2.89 2.61 2.70 2.53 2.61 3.12 3.22 2.92 3.01 2.82 2.92 3.51 3.62 3.27 3.38 3.17 3.27 3.96 4.09 3.70 3.82 3.58 3.70 4.51 4.66 4.21 4.35 4.08 4.21 5.16 5.33 4.81 4.97 4.66 4.81 Enertech Global, LLC ENGINEERING SPECIFICATIONS: Section 7: Extended Data BT060 EWT Flow °F GPM 25 30 40 50 60 70 80 90 100 110 120 WPD PSI FT 15.0 7.4 17.1 7.5 2.3 5.4 11.3 4.4 10.1 15.0 6.8 15.6 7.5 2.2 5.1 11.3 4.1 9.5 15.0 6.4 14.7 7.5 2.0 4.7 11.3 3.8 8.8 15.0 5.9 13.7 7.5 1.9 4.4 11.3 3.6 8.2 15.0 5.5 12.8 7.5 1.8 4.2 11.3 3.4 7.8 15.0 5.2 12.1 7.5 1.7 3.9 11.3 3.2 7.4 15.0 5.0 11.4 7.5 1.6 3.8 11.3 3.0 7.0 15.0 4.7 10.9 7.5 1.5 3.5 11.3 2.8 6.6 15.0 4.4 10.2 7.5 1.5 3.4 11.3 2.7 6.3 15.0 4.3 9.9 7.5 1.4 3.3 11.3 2.7 6.1 15.0 4.1 9.6 Aiflow LAT (DB) Full Load Heating HC HE Power COP DH CFM °F MBtuh MBtuh kW W/W MBtuh 1600 1850 1600 1850 1600 1850 1600 1850 1600 1850 1600 1850 1600 1850 1600 1850 1600 1850 1600 1850 1600 1850 1600 1850 1600 1850 1600 1850 1600 1850 1600 1850 1600 1850 1600 1850 1600 1850 1600 1850 1600 1850 1600 1850 94.6 91.7 94.6 91.6 95.6 92.5 96.0 92.9 97.8 94.5 98.9 95.5 99.4 95.9 101.4 97.7 102.7 98.8 103.3 99.3 105.0 100.8 106.4 102.0 107.0 102.6 107.9 103.4 109.5 104.7 110.2 105.3 109.9 105.1 111.5 106.5 112.2 107.1 110.4 105.5 112.0 106.9 112.7 107.6 42.5 43.3 42.5 43.2 44.2 45.0 45.0 45.7 48.1 48.9 50.0 50.9 50.9 51.8 54.3 55.2 56.5 57.5 57.5 58.5 60.4 61.4 62.9 63.9 64.0 65.0 65.6 66.7 68.2 69.4 69.4 70.6 68.9 70.1 71.7 72.9 73.0 74.2 69.8 71.0 72.6 73.8 73.8 75.1 30.1 30.7 30.1 30.8 31.6 32.3 32.3 33.0 35.1 35.9 36.8 37.6 37.6 38.4 40.7 41.6 42.7 43.6 43.6 44.5 46.2 47.2 48.4 49.4 49.4 50.4 50.9 51.9 53.3 54.4 54.3 55.4 53.9 55.0 56.4 57.6 57.6 58.7 54.6 55.7 57.1 58.3 58.3 59.5 3.65 3.67 3.6 3.7 3.70 3.71 3.73 3.74 3.80 3.82 3.87 3.88 3.90 3.92 3.98 4.00 4.05 4.07 4.08 4.10 4.16 4.18 4.23 4.25 4.26 4.28 4.30 4.32 4.38 4.40 4.41 4.43 4.41 4.43 4.48 4.50 4.52 4.54 4.45 4.47 4.53 4.55 4.56 4.58 3.41 3.46 3.4 3.5 3.51 3.55 3.54 3.58 3.71 3.75 3.79 3.84 3.83 3.87 4.00 4.05 4.09 4.14 4.13 4.18 4.26 4.31 4.36 4.41 4.40 4.45 4.46 4.52 4.57 4.62 4.61 4.67 4.58 4.64 4.69 4.75 4.73 4.79 4.59 4.65 4.70 4.76 4.74 4.80 9.9 9.3 9.8 9.2 10.1 9.5 10.3 9.7 10.8 10.2 11.3 10.6 11.5 10.8 12.1 11.4 12.5 11.8 12.8 12.0 13.3 12.5 13.8 13.0 14.1 13.3 14.4 13.6 15.0 14.1 15.2 14.4 15.2 14.3 15.8 14.9 16.1 15.2 15.4 14.6 16.0 15.1 16.3 15.4 Enertech Global, LLC Operation Not Recommended 24 Aiflow LAT (DB) CFM °F TC MBtuh Full Load Cooling SC HR Power MBtuh MBtuh kW EER DH Btuh/W MBtuh 25.7 24.9 22.1 21.4 23.5 22.8 24.2 23.5 20.3 19.7 21.6 20.9 22.2 21.6 18.2 17.6 19.4 18.8 19.9 19.3 15.9 15.4 17.0 16.4 17.5 16.9 13.7 13.2 14.5 14.1 15.0 14.5 11.5 11.1 12.3 11.9 12.6 12.2 9.6 9.3 10.2 9.9 10.5 10.2 7.9 7.7 8.5 8.2 8.7 8.4 4.8 4.9 7.5 7.6 6.7 6.7 6.3 6.4 9.4 9.4 8.4 8.4 7.9 8.0 11.4 11.4 10.2 10.2 9.7 9.8 13.5 13.6 12.2 12.3 11.6 11.7 15.9 16.0 14.4 14.4 13.7 13.8 18.4 18.5 16.8 16.9 16.1 16.1 21.2 21.3 19.4 19.5 18.6 18.7 24.3 24.4 22.3 22.4 21.4 21.5 Operation Not Recommended 1600 1850 1600 1850 1600 1850 1600 1850 1600 1850 1600 1850 1600 1850 1600 1850 1600 1850 1600 1850 1600 1850 1600 1850 1600 1850 1600 1850 1600 1850 1600 1850 1600 1850 1600 1850 1600 1850 1600 1850 1600 1850 1600 1850 1600 1850 1600 1850 1600 1850 56.7 58.8 55.1 57.4 55.2 57.5 55.3 57.6 54.6 56.9 54.7 57.0 54.8 57.1 54.7 57.1 54.8 57.2 54.9 57.3 55.3 57.6 55.4 57.6 55.5 57.7 55.9 58.2 56.0 58.2 56.1 58.3 56.6 58.8 56.7 58.9 56.8 58.9 57.3 59.4 57.4 59.5 57.5 59.6 58.3 60.3 58.4 60.4 58.5 60.5 62.6 63.5 64.5 65.5 64.7 65.7 64.9 65.9 64.9 65.9 65.1 66.1 65.3 66.3 63.8 64.8 64.0 65.0 64.2 65.2 61.6 62.5 61.8 62.7 62.0 62.9 58.7 59.5 58.8 59.7 59.0 59.9 55.3 56.1 55.5 56.3 55.7 56.5 52.0 52.8 52.1 52.9 52.3 53.1 49.0 49.8 49.2 49.9 49.3 50.1 40.3 42.3 43.1 45.2 42.9 45.0 42.7 44.8 43.9 46.1 43.8 45.9 43.6 45.7 43.6 45.8 43.5 45.6 43.3 45.4 42.7 44.8 42.6 44.7 42.4 44.5 41.6 43.6 41.4 43.5 41.3 43.3 40.4 42.4 40.3 42.3 40.1 42.1 39.2 41.1 39.1 41.0 38.9 40.8 37.5 39.3 37.3 39.2 37.2 39.0 70.9 72.2 74.5 75.9 74.1 75.5 74.1 75.4 75.9 77.3 75.4 76.9 75.4 76.8 75.8 77.3 75.3 76.8 75.2 76.7 74.8 76.4 74.2 75.7 74.1 75.6 73.3 74.9 72.6 74.2 72.5 74.0 71.7 73.3 70.9 72.5 70.7 72.3 70.5 72.2 69.6 71.2 69.3 70.9 70.1 71.8 69.0 70.7 68.7 70.3 2.43 2.55 2.92 3.06 2.75 2.88 2.68 2.81 3.20 3.35 3.01 3.16 2.94 3.08 3.51 3.68 3.31 3.46 3.22 3.38 3.87 4.06 3.64 3.82 3.55 3.72 4.30 4.50 4.05 4.24 3.94 4.13 4.81 5.04 4.53 4.74 4.41 4.62 5.43 5.69 5.11 5.35 4.98 5.22 6.17 6.46 5.81 6.09 5.66 5.93 20D218-17NN BS/BT Rev A ENGINEERING SPECIFICATIONS: Section 7: Extended Data BT072 EWT Flow °F GPM 25 30 40 50 60 70 80 90 100 110 120 WPD PSI FT 18.0 9.3 21.5 9.0 2.9 6.7 13.5 5.4 12.4 18.0 8.4 19.5 9.0 2.7 6.3 13.5 5.0 11.6 18.0 7.9 18.3 9.0 2.5 5.8 13.5 4.7 10.8 18.0 7.4 17.0 9.0 2.3 5.4 13.5 4.4 10.1 18.0 6.9 15.8 9.0 2.2 5.1 13.5 4.1 9.4 18.0 6.4 14.8 9.0 2.1 4.8 13.5 3.9 8.9 18.0 6.1 14.0 9.0 2.0 4.5 13.5 3.7 8.4 18.0 5.7 13.3 9.0 1.8 4.1 13.5 3.4 7.8 18.0 5.4 12.4 9.0 1.7 4.0 13.5 3.2 7.5 18.0 5.2 11.9 9.0 1.7 3.9 13.5 3.1 7.2 18.0 5.0 11.5 Aiflow LAT (DB) Full Load Heating HC HE Power COP DH CFM °F MBtuh MBtuh kW W/W MBtuh 1950 2200 1950 2200 1950 2200 1950 2200 1950 2200 1950 2200 1950 2200 1950 2200 1950 2200 1950 2200 1950 2200 1950 2200 1950 2200 1950 2200 1950 2200 1950 2200 1950 2200 1950 2200 1950 2200 1950 2200 1950 2200 1950 2200 92.1 89.9 92.3 90.1 93.1 90.8 93.3 91.0 95.3 92.8 96.1 93.5 96.4 93.7 98.8 95.9 99.7 96.8 100.0 97.0 102.2 99.0 103.3 100.0 103.6 100.3 105.1 101.6 106.3 102.7 106.6 103.0 107.0 103.3 108.2 104.4 108.5 104.7 107.2 103.5 108.4 104.6 108.7 104.9 46.5 47.3 47.0 47.8 48.6 49.4 49.0 49.8 53.2 54.1 55.1 55.9 55.5 56.4 60.6 61.5 62.6 63.6 63.1 64.2 67.9 68.9 70.2 71.3 70.7 71.9 74.0 75.2 76.5 77.7 77.1 78.4 77.8 79.1 80.5 81.8 81.1 82.4 78.3 79.5 80.9 82.2 81.6 82.9 31.6 32.1 32.2 32.6 33.6 34.1 33.8 34.3 37.8 38.3 39.4 39.9 39.7 40.2 44.4 45.0 46.2 46.9 46.6 47.2 51.0 51.7 53.1 53.8 53.5 54.2 56.5 57.4 58.8 59.7 59.3 60.1 60.0 60.9 62.4 63.4 62.9 63.8 60.4 61.3 62.8 63.7 63.3 64.2 4.37 4.46 4.3 4.4 4.40 4.49 4.45 4.54 4.54 4.63 4.60 4.69 4.65 4.74 4.75 4.84 4.81 4.91 4.86 4.96 4.95 5.05 5.02 5.12 5.07 5.17 5.11 5.22 5.18 5.29 5.24 5.35 5.22 5.33 5.29 5.40 5.35 5.46 5.24 5.35 5.31 5.42 5.37 5.48 3.12 3.11 3.2 3.2 3.24 3.22 3.23 3.21 3.44 3.43 3.51 3.49 3.50 3.49 3.74 3.72 3.82 3.80 3.81 3.79 4.02 4.00 4.10 4.08 4.09 4.07 4.24 4.22 4.33 4.31 4.32 4.30 4.37 4.35 4.46 4.44 4.45 4.43 4.38 4.36 4.47 4.45 4.45 4.44 10.5 10.3 10.5 10.2 10.8 10.5 11.0 10.7 11.5 11.3 11.9 11.6 12.1 11.8 12.7 12.5 13.1 12.9 13.4 13.1 13.9 13.6 14.4 14.1 14.6 14.3 14.9 14.6 15.4 15.1 15.7 15.4 15.7 15.3 16.2 15.8 16.4 16.1 15.9 15.6 16.4 16.1 16.7 16.4 Operation Not Recommended 20D218-17NN BS/BT Rev A 25 Aiflow LAT (DB) CFM °F TC MBtuh Full Load Cooling SC HR Power MBtuh MBtuh kW EER DH Btuh/W MBtuh 24.8 23.9 21.3 20.5 22.6 21.8 23.4 22.6 19.6 18.8 20.8 20.0 21.5 20.7 17.5 16.9 18.7 18.0 19.3 18.6 15.3 14.8 16.3 15.7 16.9 16.3 13.1 12.7 14.0 13.5 14.5 13.9 11.0 10.6 11.7 11.3 12.1 11.7 9.1 8.8 9.7 9.3 10.0 9.7 7.4 7.1 7.9 7.6 8.2 7.9 4.5 4.6 7.7 7.7 6.7 6.8 6.2 6.3 9.7 9.7 8.6 8.7 8.1 8.1 11.9 11.9 10.7 10.7 10.0 10.1 14.3 14.4 12.9 13.0 12.2 12.3 16.9 17.0 15.4 15.4 14.6 14.6 19.7 19.8 18.0 18.1 17.1 17.2 22.8 22.9 20.9 21.0 19.9 20.0 26.1 26.3 24.0 24.1 22.9 23.1 Operation Not Recommended 1950 2200 1950 2200 1950 2200 1950 2200 1950 2200 1950 2200 1950 2200 1950 2200 1950 2200 1950 2200 1950 2200 1950 2200 1950 2200 1950 2200 1950 2200 1950 2200 1950 2200 1950 2200 1950 2200 1950 2200 1950 2200 1950 2200 1950 2200 1950 2200 1950 2200 58.3 59.7 57.0 58.5 56.9 58.4 56.9 58.4 56.3 57.9 56.2 57.8 56.2 57.8 56.2 57.8 56.1 57.7 56.1 57.6 56.5 58.1 56.5 58.0 56.4 58.0 57.2 58.7 57.1 58.6 57.1 58.6 58.0 59.5 58.0 59.4 57.9 59.4 58.9 60.3 58.9 60.2 58.8 60.2 59.7 61.1 59.7 61.0 59.6 61.0 72.6 73.4 74.4 75.2 74.7 75.5 74.9 75.7 74.9 75.6 75.2 76.0 75.4 76.2 73.8 74.6 74.1 74.9 74.3 75.1 71.5 72.2 71.8 72.6 72.0 72.7 68.2 68.9 68.5 69.2 68.6 69.4 64.1 64.8 64.4 65.1 64.6 65.2 59.6 60.2 59.9 60.5 60.0 60.6 54.9 55.4 55.1 55.7 55.3 55.8 45.6 48.1 48.4 51.0 48.6 51.2 48.6 51.3 49.9 52.6 50.0 52.8 50.1 52.9 50.1 52.9 50.3 53.0 50.4 53.1 49.4 52.1 49.6 52.3 49.6 52.4 48.0 50.7 48.2 50.8 48.3 50.9 46.2 48.8 46.4 48.9 46.5 49.0 44.4 46.8 44.5 47.0 44.6 47.0 42.7 45.0 42.8 45.2 42.9 45.2 82.6 83.8 86.3 87.7 86.0 87.3 85.8 87.1 87.9 89.4 87.5 88.9 87.3 88.7 88.2 89.7 87.7 89.2 87.5 88.9 87.4 88.9 86.8 88.3 86.5 88.0 85.9 87.4 85.2 86.7 84.8 86.3 83.9 85.6 83.1 84.7 82.7 84.3 81.9 83.6 80.9 82.6 80.4 82.1 80.1 82.0 79.0 80.7 78.4 80.1 2.93 3.07 3.50 3.67 3.30 3.46 3.20 3.36 3.83 4.02 3.61 3.79 3.50 3.67 4.21 4.42 3.98 4.17 3.85 4.04 4.66 4.89 4.40 4.62 4.26 4.47 5.19 5.44 4.90 5.14 4.74 4.98 5.81 6.10 5.49 5.76 5.31 5.58 6.55 6.87 6.18 6.49 5.99 6.28 7.41 7.77 6.99 7.34 6.77 7.11 Enertech Global, LLC Greenville, IL - Mitchell, SD www.enertechgeo.com [email protected] MEMBER Rev Tab 20D218-17NN 170814B
* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project
advertisement