- Computers & electronics
- Computer components
- Chassis components
- Computer cooling components
- Hardware cooling accessories
- Trane
- Dual-Duct
- Installation and Maintenance Manual
Trane Dual-Duct Installation and Maintenance Manual 68 Pages
Trane Dual-Duct Installation and Maintenance Manual
advertisement
Installation, Operation, and Maintenance
VAV-UCM 4.2
SAFETY WARNING
Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and airconditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that are attached to the equipment.
March 2014
VAV-SVX01D-EN
Introduction
Read this manual thoroughly before operating or servicing this unit.
Warnings, Cautions, and Notices
Safety advisories appear throughout this manual as required.Your personal safety and the proper operation of this machine depend upon the strict observance of these precautions.
The three types of advisories are defined as follows:
WARNING
CAUTION s
Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
Indicates a potentially hazardous situation which, if not avoided, could result in minor or moderate injury. It could also be used to alert against unsafe practices.
NOTICE: Indicates a situation that could result in equipment or property-damage only accidents.
Important Environmental Concerns
Scientific research has shown that certain man-made chemicals can affect the earth’s naturally occurring stratospheric ozone layer when released to the atmosphere. In particular, several of the identified chemicals that may affect the ozone layer are refrigerants that contain Chlorine, Fluorine and Carbon (CFCs) and those containing Hydrogen, Chlorine, Fluorine and
Carbon (HCFCs). Not all refrigerants containing these compounds have the same potential impact to the environment.Trane advocates the responsible handling of all refrigerants-including industry replacements for CFCs such as HCFCs and HFCs.
Important Responsible Refrigerant Practices
Trane believes that responsible refrigerant practices are important to the environment, our customers, and the air conditioning industry. All technicians who handle refrigerants must be certified. The Federal Clean Air Act
(Section 608) sets forth the requirements for handling, reclaiming, recovering and recycling of certain refrigerants and the equipment that is used in these service procedures. In addition, some states or municipalities may have additional requirements that must also be adhered to for responsible management of refrigerants. Know the applicable laws and follow them.
WARNING
Proper Field Wiring and Grounding
Required!
Failure to follow code could result in death or serious injury. All field wiring MUST be performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in
NEC and your local/state electrical codes.
WARNING
Personal Protective Equipment (PPE)
Required!
Installing/servicing this unit could result in exposure to electrical, mechanical and chemical hazards.
• Before installing/servicing this unit, technicians
MUST put on all PPE required for the work being undertaken (Examples; cut resistant gloves/sleeves, butyl gloves, safety glasses, hard hat/bump cap, fall protection, electrical PPE and arc flash clothing).
ALWAYS refer to appropriate Material Safety Data
Sheets (MSDS)/Safety Data Sheets (SDS) and OSHA guidelines for proper PPE.
• When working with or around hazardous chemicals,
ALWAYS refer to the appropriate MSDS/SDS and
OSHA/GHS (Global Harmonized System of
Classification and Labelling of Chemicals) guidelines for information on allowable personal exposure levels, proper respiratory protection and handling instructions.
• If there is a risk of energized electrical contact, arc, or flash, technicians MUST put on all PPE in accordance with OSHA, NFPA 70E, or other country-specific requirements for arc flash protection, PRIOR to servicing the unit. NEVER PERFORM ANY
SWITCHING, DISCONNECTING, OR VOLTAGE
TESTING WITHOUT PROPER ELECTRICAL PPE AND
ARC FLASH CLOTHING. ENSURE ELECTRICAL
METERS AND EQUIPMENT ARE PROPERLY RATED
FOR INTENDED VOLTAGE.
Failure to follow instructions could result in death or serious injury.
© 2014 Trane All rights reserved VAV-SVX01D-EN
Copyright
This document and the information in it are the property of
Trane, and may not be used or reproduced in whole or in part without written permission. Trane reserves the right to revise this publication at any time, and to make changes to its content without obligation to notify any person of such revision or change.
Trademarks
VariTrac, VariTrane, Trane and the Trane logo are trademarks or registered trademarks ofTrane in the United
States and other countries.Trane is a business of Ingersoll
Rand. All trademarks referenced in this document are the trademarks of their respective owners.
Revision History
VAV-SVX01D-EN
Updated board photo and part number (BRD04939 replaced BRD02806).
Introduction
VAV-SVX01D-EN 3
Table of Contents
Introduction
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Warnings, Cautions, and Notices . . . . . . . . 2
Important Environmental Concerns . . . . . 2
Important Responsible Refrigerant
Practices . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
General Information
. . . . . . . . . . . . . . . . . . . . . 6
Overview of Manual . . . . . . . . . . . . . . . . . . . 6
Chapter Overview . . . . . . . . . . . . . . . . . . . . . 6
Unit Control Module 4.2 (UCM 4.2) . . . . . . . 6
Specifications . . . . . . . . . . . . . . . . . . . . . . . 6
UCM 4.2 Enhancements . . . . . . . . . . . . . . . 6
UCM 4.2 Features . . . . . . . . . . . . . . . . . . . . 7
Shipping . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
VAV Start Up/Check Out Procedure
Chapter Overview . . . . . . . . . . . . . . . . . . . . . 9
UCM 4.2 Pre-Power Check-Out . . . . . . . . . . 9
Light Emitting Diode (LED) Operations . . . 9
Zone Sensor Check-out . . . . . . . . . . . . . . . . 10
UCM 4.2 Installation and Wiring
Chapter Overview . . . . . . . . . . . . . . . . . . . . 11
UCM 4.2 Power Wiring . . . . . . . . . . . . . . . . 11
Power Requirements . . . . . . . . . . . . . . . . 11
Zone Sensor Wiring . . . . . . . . . . . . . . . . . . . 11
Location and Mounting . . . . . . . . . . . . . . 11
Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Multiple UCM’s Per Zone Sensor . . . . . . 12
Multiple UCM’s per Auxiliary Duct
Temperature Sensor . . . . . . . . . . . . . . . . 12
Zone Sensor Hardwired Option . . . . . . . 12
Zone Sensor Wireless Option . . . . . . . . . 12
Communication Wiring . . . . . . . . . . . . . . . . 12
Communication Link Wiring . . . . . . . . . . 12
DIP Switch Settings . . . . . . . . . . . . . . . . . . . 13
Wireless Zone Sensor
. . . . . . . . . . . . . . . . . . . 17
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Dimensional Diagrams . . . . . . . . . . . . . . . . 17
Setting the Address, Mounting, Wiring, and Associating the Receiver and Sensor 18
4
Choosing a Location for Mounting the Sensor . . . . . . . . . . . . . . . . . . . . . . . . . .18
Setting the Rotary Address Switches on the Receiver and the Sensor . . . . . . . .19
Factory Wiring of the Receiver to the VAV UCM . . . . . . . . . . . . . . . . . . . . . . .20
Receiver Cover . . . . . . . . . . . . . . . . . . . . . .22
Applying Power to the Receiver . . . . . . . .22
Powering the Sensor and Associating the Sensor to the Receiver . . . . . . . . . . . .23
Testing Signal and Battery Strength . . . .23
Disassociation . . . . . . . . . . . . . . . . . . . . . .23
UCM Programming and Operation
Chapter Overview . . . . . . . . . . . . . . . . . . . . .24
Accessing Rover/Comm4 . . . . . . . . . . . . . . .24
Rover Overview . . . . . . . . . . . . . . . . . . . . .24
Laptop Requirements and Complete
Connection Instructions . . . . . . . . . . . . . . .24
UCM Home Tabs: At a Glance . . . . . . . . . . .26
Status Tab . . . . . . . . . . . . . . . . . . . . . . . . . .27
Setpoints Tab . . . . . . . . . . . . . . . . . . . . . . .27
Wireless Tab . . . . . . . . . . . . . . . . . . . . . . . .28
Advanced Configuration Tab . . . . . . . . . .28
UCM Home Tabs: Instructions . . . . . . . . . . .28
Configuration . . . . . . . . . . . . . . . . . . . . . . .28
Setpoints Tab . . . . . . . . . . . . . . . . . . . . . . .28
Setup Tab . . . . . . . . . . . . . . . . . . . . . . . . . .30
Wireless Tab . . . . . . . . . . . . . . . . . . . . . . . .33
Advanced Configuration Tab . . . . . . . . . .34
Entering and Exiting the Service Mode . . .35
Overriding VAVs . . . . . . . . . . . . . . . . . . . . . .35
Resetting Diagnostics . . . . . . . . . . . . . . . . . .35
Saving VAV Program . . . . . . . . . . . . . . . . . .35
Downloading Program Files from
PC to DDC UCM 4.2 . . . . . . . . . . . . . . . . . .36
Sequence of Operations
. . . . . . . . . . . . . . . . . .38
Chapter Overview . . . . . . . . . . . . . . . . . . . . .38
Single Duct Units . . . . . . . . . . . . . . . . . . . . . .38
Override Conditions (Single Duct) . . . . . . .38
Fan-Powered Units . . . . . . . . . . . . . . . . . . . .39
VAV-SVX01D-EN
Parallel Fan-Powered Units . . . . . . . . . . . . 39
Occupied Units . . . . . . . . . . . . . . . . . . . . . 39
Override Conditions (Parallel Fans) . . . . . 39
Series Fan-Powered Units . . . . . . . . . . . . . 40
Occupied Units . . . . . . . . . . . . . . . . . . . . . 40
Override Conditions (Series Fan) . . . . . . . 40
Zone Sensor Functions . . . . . . . . . . . . . . . . 40
Flow Sensor . . . . . . . . . . . . . . . . . . . . . . . . . 41
Failure Modes . . . . . . . . . . . . . . . . . . . . . . . . 41
Air and Water Balancing
. . . . . . . . . . . . . . . . 42
Chapter Overview . . . . . . . . . . . . . . . . . . . . 42
Air Balancing . . . . . . . . . . . . . . . . . . . . . . . . 42
System Checkout . . . . . . . . . . . . . . . . . . . 42
System Setup . . . . . . . . . . . . . . . . . . . . . . 42
VAV Single Duct Unit Air Balancing . . . . 42
Water Balancing . . . . . . . . . . . . . . . . . . . . . . 44
Troubleshooting
. . . . . . . . . . . . . . . . . . . . . . . . 45
Chapter Overview . . . . . . . . . . . . . . . . . . . . 45
Diagnostic Log . . . . . . . . . . . . . . . . . . . . . 45
Diagnostic Table . . . . . . . . . . . . . . . . . . . . 46
UCM Failure Procedures . . . . . . . . . . . . . 46
UCM Communication Loss Procedures . 47
Wired Zone Sensor Failure Procedures . 47
Wired Zone Setpoint Failure Procedures 48
Wireless Zone Sensor Failure Procedures 49
Airflow Failure Procedures . . . . . . . . . . . 51
Auxiliary Temperature Sensor Failure
Procedures . . . . . . . . . . . . . . . . . . . . . . . . 53
Auxiliary C02 Sensor Failure Procedures 53
VAV Damper Failure Procedures . . . . . . . 53
VAV Series Fan Failure Procedures . . . . 54
VAV Parallel Fan Failure Procedures . . . 54
VAV Electric Heat Stage(s) Failure
Procedures . . . . . . . . . . . . . . . . . . . . . . . . 56
VAV Proportional Hot water failure . . . . 56
Trane/Honeywell Proportional valve check out procedures . . . . . . . . . . . . . . . . . 57
Cartridge Failure . . . . . . . . . . . . . . . . . . . . 57
Actuator Failure . . . . . . . . . . . . . . . . . . . . 57
VAV Two Position Hot water failure . . . . 57
Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . .58
Appendix
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .66
VAV-SVX01D-EN 5
General Information
Overview of Manual
Note: One copy of the document is shipped with VAV units that have UCM 4.2 DDC controllers and is customer property. It must be retained by the unit's maintenance personnel.
This booklet describes proper installation, operation, and maintenance procedures for delivered air systems. By carefully reviewing the information within this manual and following the instructions, the risk of improper operation and/or component damage will be minimized.
Should equipment failure occur, contact a qualified service organization with qualified, experienced HVAC technicians to properly diagnose and repair this equipment.
Chapter Overview
This chapter contains information about the following:
• Unit Control Module 4.2 (UCM 4.2)
• Specifications
• UCM 4.2 Enhancements
• UCM 4.2 Features
• Shipping
• Storage
Unit Control Module 4.2 (UCM
4.2)
The UCM 4.2 is a microprocessor-based, Direct Digital
Controller (DDC) for the (Variable Air Volume) VAV terminal unit. It contains the control logic to modulate the flow of supply air through the VAV terminal in response to the load requirements within the VAV zone.
The function of the UCM is to control theVAV terminal unit to vary the volumetric airflow rate to the zone. Units have been made with either pneumatic, analog electronic, or microprocessor controls (DDC VAV). This manual discusses only terminal units with Comm4 DDC/VAV controls. Factory installed DDC/VAV controls are available with all single duct terminal units, dual duct units, as well as parallel fan-powered and series fan-powered units.Two
UCMs are required for dual duct units (one for the heating duct and one for the cooling duct).
The UCM modulates a VAV's damper blade based on a zone temperature, measured airflow, and airflow set points to continuously control conditioned air delivery to the space. The volume of incoming air is monitored and the damper adjusts to provide accurate control independent of the duct pressure.The damper modulates between operator airflow set points depending on space conditions. Additionally, fan and heat outputs may be energized depending on the application. Available inputs
6 include a twisted/shielded communication link, zone sensor, auxiliary temperature sensor (optional), CO
2
Sensor (optional), and Occupy/Unoccupy Sensor
(optional), and 24 VAC power.
Specifications
Power Requirements
The UCM 4.2 requires 24VAC, 50/60 Hz NEC Class 2 power.
The UCM itself consumes 8 VA. Our factory installed devices draw from 3 to 12 VA. Typical values are 4 VA for a damper actuator, 10 to 12 VA for an electric heat contractor, and 6 VA for a fan relay. The NEC Class 2 transformer should be sized to handle the total VA of all devices.The binary outputs are rated at steady-state 12 VA max.
Operating Environments - UCM 4.2
32° to 140°F (0° to 60°C), 10% to 90% relative humidity, noncondensing
Storage Environments - UCM 4.2
-40° to 150°F (-40° to 65.6°C), 10% to 90% relative humidity, non-condensing
Mounting
Typically, the UCM 4.2 is factory installed. However, UCM
4.2 is available with retrofit kits, in which case it must be field installed.
Tracer Summit and UCM 4.2 Communications
Link Wiring
Communications Link wiring must be 18 AWG twisted shielded pair wire. Each conductor must be stranded tinned copper.The maximum total wire length is 5,000 feet
(1,524 m). See
“UCM 4.2 Installation and Wiring,” p. 11
for further information about wire selection.
UCM 4.2 Enhancements
• The enhanced VAV UCM is backward compatible with
VariTrane® D VAV boxes (VXXD and VXXE) VariTrac® dampers, and VariTrac II dampers.
• UCM 4.2 adds support for operation with VariTrane
Series F valves (¼-turn blade dampers) via 90-second drive time.
• UCM 4.2 adds a second, C0
2 interfacing, mode of operation to the auxiliary analog input (TB3-5).This is a 1 to 10 volt DC input with a mapping of input voltage to C0
2 output data value of 200 parts per million (PPM) of C0
2 per volt. The use of this new auxiliary analog input as an interface to a C0
2 detector is mutually exclusive with the use of the input as auxiliary temperature input. Therefore, the use of the C0
2 interfacing mode of operation is not recommended for stand-alone applications requiring auto-changeover.
VAV-SVX01D-EN
• UCM 4.2 adds a binary 24 VAC, dry contact input. It can be configured either as a generic input or as an occupancy detector input.
• UCM 4.2 adds a VariTrac Bypass Damper mode of operation. In this mode, supply air temperature and supply air pressure is made available on the Comm4 link. The damper position is a Comm4-control parameter. A Comm4 configurable failsafe position was added.The supply air temperature uses a new "S" input (TB3-7). The use of this new input is mutually exclusive with the zone temp input (TB3-1).
• UCM 4.2 now assumes the hot water valve is closed after reset. This prevents a reset during hot water override from causing the valve to stop moving. This also changes the behavior after reset, when there is a reheat demand, the hot water valve now opens (from assumed closed position) to the desired reheat position.
• In a wireless system, the hard-wired sensor can now be configured as not present. The hard-wired sensor failures will not be reported as long as at least one wireless zone sensor is reporting valid temperature values.
Note: This is an older wireless system that has been obsoleted and not the one discussed in the wireless zone sensor section.
Figure 1.
UCM 4.2 board layout
General Information
• For standalone units, series or parallel fan operation will use the unoccupied fan control when the local unoccupied request (** function) is received. In UCM
3.3 and prior, the fan would operate as if occupied during local unoccupied request.
• UCM 4.2 adds a local minimum heating flow set point.
The use of and value of this set point is configurable.
UCM 4.2 Backward Compatibility
UCM 4.2 can be used to replace UCM I, UCM II, and UCM
III with no compatibility issues. However, if the communicating device (i.e. Command Unit I or Comfort
Manager™ I) is a COM 3 device (1992 or earlier), then you will need an upgrade chip. The Comfort Manager chip upgrade is Kit 1511 and the Command Unit chip upgrade is Kit 1512.
UCM 4.2 Features
UCM Outputs
UCMTriac outputs for controlling a fan or reheat are rated at 12 VA each.
Wiring Diagram
shows a typical wiring diagram for the redesigned UCM hardware.The new service part number is BRD04939.
Zone Sensor, Auxiliary Sensor, and
Thumbwheel Set Point Calibration
If there is a discrepancy between a measured temperature and what the UCM reports, a calibration offset value can be edited in the UCM setup screen to correct the displayed value.
Flow Sensor Calibration
If there is a discrepancy between a measured flow and what the UCM reports, the measured value can be entered, which automatically calculates a calibration multiplier to correct the displayed value.
Water Valve Override
Each UCM that has proportional or staged hot water heat outputs can be edited to override the water valve to its maximum position.
Ventilation Set Points and Ratio Calculation
Set point values needed for a space to satisfy indoor air quality requirements are provided. A resultant ventilation ratio can be used to calculate an air handler's outside air damper minimum position or other control strategies.
VAV-SVX01D-EN 7
General Information
Water Heat Output Configuration
UCMs that have hot water heat outputs can be configured for normally open or normally closed.
Zone Sensor Functions
Zone sensor functions now include: air valve drive to maximum, use unoccupied set points, timed override, and cancel timed override.
Slaving of Zone Sensors
Up to three (3) UCM 4.2 may be connected to a single zone sensor.
Generic UCM Capability
UCM 4.2 can be configured to control non-Trane VAV boxes.
Shipping
Each VAV product and its service literature are shipped in the same package. When unpacking, make sure that the literature is not lost or discarded with the packing material.
Visually inspect the individual components for obvious defects or damage. All components are thoroughly inspected before leaving the factory. Any claims for damage incurred during shipment must be filed with the carrier.
Storage
When any component of the VAV system and/or field installed accessories must be stored for a period of time prior to being installed, they must be protected from the elements. The storage location temperature should be between -40° to 150°F (-40° to 65.6°C) and the relative humidity should be 10% to 90%, non-condensing.
The warranty will not cover damage to the VAV system or controls due to negligence during storage. A controlled indoor environment must be used for storage.
8 VAV-SVX01D-EN
VAV Start Up/Check Out Procedure
Chapter Overview
This chapter contains information about the following:
• Unit 4.2 Pre-Power Check-Out
• Light Emitting Diode (LED) Operations
• Zone Sensor Check-Out
UCM 4.2 Pre-Power Check-Out
WARNING
Live Electrical Components!
During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury.
• Check the supply voltage atTB1. Proper polarity must be maintained.TB1-1 is the hot side (+) andTB1-2 is the ground side (-) of the 24VAC input.The UCM cannot be powered from a common 24 VAC transformer that is supplying power to a device containing a full-wave rectifier bridge in its power supply. The acceptable voltage is 20 to 28 VAC (24 VAC cataloged). However, voltages at either extreme may result in increased system instability.
• Verify that communications wiring has properly been terminated at TB2-1 (+) and TB2-2 (-). Polarity is very important on the communications link.
• Verify that the zone sensor connections are correct as detailed in the UCM wiring chapter.
• Verify that the proper unit DIP switch settings have been set on each UCM.
• Verify that the tubing is properly connected to the transducer.
Light Emitting Diode (LED)
Operations
The UCM has one green LED located near TB3 and one yellow LED located near TB2 on the UCM circuit board.
These LED’s are used to help diagnose communication
(yellow) or circuit board problems (green).
The green LED (red on older boards) is a power indicator.
It is steady on when the power is on and the software is functioning correctly. If it blinks with a 1 second on 1 second off cycle when power is applied, then the board is not functioning and must be replaced.
Table 1.
Green LED power function indication
LED State
"On”
Blinking
"Off”
Indication
Board functioning correctly
Board malfunction (Replace Board)
Board does not have power
The yellow LED functions as the communication indicator.
The indication from the yellow LED is as follows:
:
Table 2.
Yellow LED communication indicator function
LED State Indication
"On”
Incorrect (reversed) communication polarity, no connection, or shorted lines.
Blinking slowly approx. 1 blink/ sec.
Communication is occurring on the link but not for that particular UCM.
Blinking quickly (multiple blinks/ sec.)
Communication is occurring on the link, specifically with that UCM.
"Off”
Polarity is correct and no communication is occurring on the link
VAV-SVX01D-EN 9
VAV Start Up/Check Out Procedure
Zone Sensor Check-out
If an erroneous temperature is being reported to the UCM, use the
“Zone sensor temperature-resistance table,” p. 10
to verify the integrity of the adjustable set point potentiometer or sensor. The resistance should be measured across the terminals to which the device is connected.
Note: Disconnect the zone sensor from the UCM when making the checks listed in the table below.
Table 3.
Zone sensor temperature-resistance table
Temp ( °F)
55
Thermostat
Thumbwheel
Resistance (Ohms)
792
Sensor Resistance (k
Ohms)
17.0
68
69
70
71
64
65
66
67
60
61
62
63
56
57
58
59
539
519
500
481
617
597
578
558
694
675
656
636
772
753
733
714
76
77
78
79
72
73
74
75
383
364
344
325
461
442
422
403
11.2
11.0
10.7
10.4
10.2
10.0
9.7
9.5
80
81
82
83
306
286
267
247
9.3
9.0
8.8
8.6
84
85
228
208
8.4
8.2
Note:
Thumbwheel resistance checks are made at TB3-2 and TB3-3 on the zone sensor. Temperature sensor resistance is measured at TB3-1 and TB3-2 of the zone sensor.
13.6
13.3
13.0
12.6
12.3
12.1
11.8
11.5
16.5
16.1
15.7
15.4
15.0
14.6
14.3
14.0
10 VAV-SVX01D-EN
UCM 4.2 Installation and Wiring
WARNING
Hazardous Voltage!
Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/ tagout procedures to ensure the power can not be inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury.
WARNING
Proper Field Wiring and Grounding
Required!
All field wiring MUST be performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in
NEC and your local/state electrical codes. Failure to follow code could result in death or serious injury.
Chapter Overview
This chapter contains information about the following:
• UCM 4.2 Power Wiring
• Zone Sensor Wiring
• Communication Wiring
• DIP Switch Settings Selection
UCM 4.2 Power Wiring
Power Requirements
NOTICE:
Use Copper Conductors Only!
Unit terminals are not designed to accept other types of conductors. Failure to use copper conductors could result in equipment damage.
Use at least 16 AWG for power wiring and connect to terminal TB1-1 (+) and TB1-2 (-). 24 VAC is required to power the UCM control and has an acceptable voltage tolerance of 20 to 28 VAC. Replace the UCM control box cover after field wiring to prevent any electromagnetic interference.
Note: A dedicated 24 VAC, 50VA NEC class 2 transformer is recommended to power the UCM. When powering multiple UCM’s from one transformer, polarity must be maintained. Terminal TB1-1 is designated positive (+) and terminal TB1-2 is negative (-) to the unit casing ground.
The power consumption for cooling only Series F Models
(VariTrac and VariTrane) is 12 VA (4 VA for the air valve/ actuator and 8 VA for the board). To determine the total
VAV-SVX01D-EN
UCM power requirement, add the power consumption per stage to the circuit board power requirement. For example, a Series F unit containing magnetic contactors with three stages of reheat would consume 42 VA.
Table 4.
VA rating for components
Style
F - Style Actuator
Air Valve Actuator C through E Style
Varitrac Actuator
Fan Power Fan Output
Hot Water Proportional
Hot Water 2 Position
Electric Heater Magnetic Contactor
Electric Heater Mercury Contactor
Volt Amps
4 VA
12 VA
3 VA
6 VA
4 VA
6.5 VA
10 VA
12 VA
Note: VariTrane™ and VariTrac™ cooling only Series D and E models consume 20 VA (12 VA for the actuator and 8 VA for the UCM).The heating output ratings remain the same.
See
for UCM terminal locations and
through
for wiring of output devices.
Zone Sensor Wiring
Location and Mounting
A zone sensor in each control zone should be located in the most critical area of the zone. Sensors should not be mounted in direct sunlight or in the area’s supply air stream. Subdivision of the zone may be necessary for adequate control and comfort.
Avoid mounting zone sensors in areas subject to the following:
• Drafts or “dead spots” behind doors or corners
• Hot or cold air ducts
• Radiant heat from the sun or appliances
• Concealed pipes or chimneys
• Unheated or uncooled surfaces behind the sensor such as outside walls
• Air flows from adjacent zones or other units
Wiring
Each unit must be controlled by a zone sensor that is designated specifically for use with the UCM control. Field wiring for the zone sensors must meet the following requirements:
• Must be 14 to 18 AWG
• Refer to the sensor instructions for terminal connections.
• If local codes require enclosed conductors, the zone sensor wires should be installed in conduit. Do not
11
UCM 4.2 Installation and Wiring
route zone sensor wires in conduit with 24VAC or other high power conducting wires.
Multiple UCM’s Per Zone Sensor
Up to three (3) UCM’s may be connected to a single zone sensor and thumbwheel set point.
• Connect terminal connections TB3-1, TB3-2, and TB3-
3 in parallel (i.e. daisy chain) from the master UCM to the slaved UCM(s).
Note: Proper polarity must be maintained.
• Cut jumper wires W1 and W2 on the slaved UCM’s
(never cut jumper wires W1 and W2 on master UCM).
Multiple UCM’s per Auxiliary Duct
Temperature Sensor
Up to three (3) UCMs may be connected to a single auxiliary duct temperature sensor.
• Connect terminal connections TB3-5 and TB3-6 in parallel (i.e. daisy chain) from the master UCM to the slaved UCM(s).
Note: Proper polarity must be maintained.
• Cut jumper wire W4 on the slaved UCMs (never cut jumper wire W4 on the master UCM).
Zone Sensor Hardwired Option
Depending on the zone sensor options used, a maximum of five wires may be required to run from the UCM to the zone sensor. The zone sensor options are:
• Zone sensor only (2 wires) - Part Number
X13511528010
• Sensor with night set back - Part Number
X13511530010
• Zone sensor with external adjustable - Part Number
X13511529010
• Zone sensor with external adjustable night set back, timed override (TOV) on/cancel button - Part Number
X13511527010
• Digital zone sensor - Part Number X13790866010
• Communications jack - Part Number X13651467020
(for one box of 12)
Note: All wiring from the zone sensor to the
Communication link must be twisted shielded pair wiring.
Zone Sensor Wireless Option
Wireless Zone Sensor
Receiver is used to receive a signal from the wireless zone sensor and can be factory installed- Part Number
X13790855010.
The wiring harness connects the receiver to the UCM 4.2
- Part Number X19051692010.
Zone Sensor
The wireless zone sensor with night setback timed override (TOV) on/cancel button. Also can be ordered for
Celsius and Fahrenheit setpoint adjustment - Part Number
X13790492010 (F), X13790494010 (C). Digital Wireless Part
Number: X13790822010.
Communication Wiring
Communication Link Wiring
The “Communication Link” is the communication wiring between Tracer Summit® and all VAV box Unit Control
Modules (UCM). Tracer Summit can be connected to the
UCM communication link in a “daisy chain” configuration.
Note: It is not necessary for each UCM to be connected to the line in sequential order by address. Also, multiple communication links may be run and terminated at Tracer Summit. However, a consistent, documented wiring path will help troubleshoot communication problems after installation.
Field wiring for the communication link must meet the following requirements:
1.
Communication link wiring must be at least 18 AWG twisted shielded pair wire. Shields must be grounded at Tracer Summit or Central Control Panel (CCP) only.
More than one ground reference will cause communications failures. Shields must be daisy chained.Tape the shield at the lastVAV UCM to prevent any connection between the shield and ground. Wire specifications are as follows:
Plenum Cable
Stranded, tinned copper insulated with extruded FEP.
Conductors cabled and shielded with overall aluminum/Mylar tape and stranded, tinned copper drawn wire. Extruded jacket, 300 volt, 150°C NEC 725-
2 (b) class 2, type CL2P, 25 pF/ft.
Non-Plenum Cable
Stranded tinned copper insulated with polyethylene.
Conductors cabled and shielded with overall aluminum/polyester tape and stranded, tinned copper drain wire. Chrome gray PVC jacket, 300V, 60°C NEC type CM, 24 pF/ft.
Table 5.
Wire capacitance
Max. Communication
Link Wiring Length Max. Wire Capacitance
1,000 feet (304.8m)
2,000 feet (609.6 m)
3,000 feet (914.4m)
4,000 feet (1,219.2 m)
Up to 60 pF/ft. (196.9 pF/m)
Up to 50 pF/ft. (164.0 pF/m)
Up to 40 pF/ft. (131.2 pF/m)
Up to 30 pF/ft. (98.4 pF/m)
5,000 feet (1,524 m) Up to 25 pF/ft. (82.0 pF/m)
Note:
Wire capacitance must comply with this table.
12 VAV-SVX01D-EN
2. The maximum wire length should not exceed 5,000 feet (1,524 m).
3. Communication link wiring cannot pass between buildings.
4. A maximum of 63 UCMs can be connected to each
COM Link. Daisy chaining is a typical configuration.
“STAR” chaining is also acceptable.
Note: Polarity is extremely important and must be observed on communication link connections.
5. At the VAV box, communication link wires must be connected toTB2-1, 3 (+) andTB2-2, 4 (-) terminals on the UCM.
6. Verify that the UCM address is properly set (DIP switch
SW1). See
for proper DIP switch settings.
DIP Switch Settings
DIP Switch SW1 contains six switches for addressing the
UCM. These switches allow a user to set a unique communication address for each UCM. Each UCM on a given communication link must have a unique address in order forTracer Summit or the CCP to communicate to it.
Refer to
for UCM 4.2 DIP switch settings.
Note: When using Rover™ service tool to communicate to the UCM, you must add 64 to the DIP switch address. For example, a UCM with the DIP switch address set to 1 would be UCM Number 65 in
Rover.
Figure 2.
Rover screen/application
Table 6.
DIP switch settings for UCM 4.2
UCM
Unit #
7
8
5
6
3
4
1
2
Address
69
70
71
72
65
66
67
68
1
OFF
ON
OFF
ON
OFF
ON
OFF
ON
2
ON
OFF
OFF
ON
ON
OFF
OFF
ON
3
OFF
OFF
OFF
ON
ON
ON
ON
OFF
Dip
4
ON
ON
ON
OFF
ON
ON
ON
ON
VAV-SVX01D-EN
5
ON
ON
ON
ON
ON
ON
ON
ON
6
ON
ON
ON
ON
ON
ON
ON
ON
UCM 4.2 Installation and Wiring
Address
101
102
103
104
97
98
99
100
93
94
95
96
89
90
91
92
85
86
87
88
81
82
83
84
77
78
79
80
73
74
75
76
117
118
119
120
113
114
115
116
109
110
111
112
105
106
107
108
121
122
123
UCM
Unit #
37
38
39
40
33
34
35
36
29
30
31
32
25
26
27
28
21
22
23
24
17
18
19
20
13
14
15
16
9
10
11
12
53
54
55
56
49
50
51
52
57
58
59
45
46
47
48
41
42
43
44
Table 6.
DIP switch settings for UCM 4.2 (continued)
Dip
4
ON
ON
ON
OFF
ON
ON
ON
ON
OFF
OFF
OFF
ON
OFF
OFF
OFF
OFF
ON
ON
ON
OFF
ON
ON
ON
ON
OFF
OFF
OFF
ON
OFF
OFF
OFF
OFF
ON
ON
ON
OFF
ON
ON
ON
ON
OFF
OFF
OFF
ON
OFF
OFF
OFF
OFF
OFF
OFF
OFF
3
OFF
OFF
OFF
ON
ON
ON
ON
OFF
OFF
OFF
OFF
ON
ON
ON
ON
OFF
OFF
OFF
OFF
ON
ON
ON
ON
OFF
OFF
OFF
OFF
ON
ON
ON
ON
OFF
OFF
OFF
OFF
ON
ON
ON
ON
OFF
OFF
OFF
OFF
ON
ON
ON
ON
OFF
ON
ON
ON
1
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
2
ON
OFF
OFF
ON
ON
OFF
OFF
ON
ON
OFF
OFF
ON
ON
OFF
OFF
ON
ON
OFF
OFF
ON
ON
OFF
OFF
ON
ON
OFF
OFF
ON
ON
OFF
OFF
ON
ON
OFF
OFF
ON
ON
OFF
OFF
ON
ON
OFF
OFF
ON
ON
OFF
OFF
ON
ON
OFF
OFF
5
ON
ON
ON
ON
ON
ON
ON
ON
OFF
OFF
OFF
ON
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
ON
OFF
ON
ON
ON
ON
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
ON
OFF
ON
ON
ON
ON
OFF
OFF
OFF
6
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
ON
OFF
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
13
UCM 4.2 Installation and Wiring
Table 6.
DIP switch settings for UCM 4.2 (continued)
UCM
Unit #
60
61
62
63
Address
124
125
126
127
1
ON
OFF
ON
OFF
2
ON
ON
OFF
OFF
3
OFF
OFF
OFF
OFF
Dip
4
OFF
OFF
OFF
OFF
5
OFF
OFF
OFF
OFF
6
OFF
OFF
OFF
OFF
.
The following figures show wiring diagrams for typical applications of UCM 4.2
Figure 3.
Wiring diagram for single duct units with factory installed electric reheat
HEATER STAGE
CONTACTOR(S)
9.
OPTIONAL
TRANSFORMER
10.
3RD 2ND 1ST
DAMPER
ACTUATOR
WIRING
24VAC 60HZ
NEC CLASS-2
CONTROL CIRCUIT
LOAD= 12VA
(WITHOUT HEAT)
8.
OPTIONAL
FACTORY
INSTALLED
WIRELESS
24VAC
BL
Y
Y
BL
GND 24V
UCM or EI Board
TB1-1 TB2-6
TB1-2
TB3-3
TB2-5 TB3-2
TB3-1
ADDRESS
SWITCH
J1 1
ACT
BIP GND 24V
D.D.C.\U.C.M.
CONTROL BOARD
J3
+ + + -
YEL GRN
ZONE GND SET A/CO2 GND
1
7.
R
BK
G
PRESSURE
TRANSDUCER
+
VOUT
-
D.D.C.\U.C.M.
CONTROL BOX
SHIELDED TWISTED PAIR
COMMUNICATIONS WIRING
OPTIONAL FACTORY INSTALLED
WIRELESS
TB3-5
5.
R (HOT)
O (COMMON)
GR (NC CONTACT)
BK (RETURN)
Y
(TB1-1) 24VAC
(TB4-1) BIP
(TB1-1) 24VAC
(TB1-2) GND
NOT CONNECTED
OPTIONAL FIELD INSTALLED
OCCUPANCY SENSOR
6.
TB3-6
OPTIONAL
AUX TEMP SENSOR
NOTE:
1.
2. 1/4" QUICK CONNECT REQUIRED FOR ALL FIELD CONNECTIONS.
3.
ZONE SENSOR TERMINALS 1 (-) AND 2 (+) REQUIRE SHIELDED TWISTED PAIR
WIRING FOR COMMUNICATIONS JACK EQUIPPED ZONE SENSOR OPTION.
4.
NO ADDITIONAL WIRING REQUIRED FOR NIGHT SETBACK OVERRIDE (ON/CANCEL).
5.
6.
7.
FACTORY WIRING
FIELD WIRING
OPTIONAL OR ALTERNATE WIRING
THE OPTIONAL BINARY INPUT CONNECTS BETWEEN TB4-1 (BIP) AND 24VAC (HOT) FROM
TRANSFORMER. THE BINARY INPUT CAN BE RECONFIGURED AS AN OCCUPANCY INPUT VIA THE
COMMUNICATIONS INTERFACE.
AS SHIPPED, THE AUX INPUT IS CONFIGURED AS AN AUX TEMP INPUT. THE AUX INPUT CAN BE
RECONFIGURED AS A CO2 SENSOR INPUT VIA THE COMMUNICATIONS INTERFACE.
S TERMINAL NOT TO BE USED WITH VARITRANE.
8.
9.
10.
IF UNIT MOUNTED TRANFORMER IS NOT PROVIDED, POLARITY FROM UNIT TO UNIT MUST BE
MAINTAINED TO PREVENT PERMANENT DAMAGE TO CONTROL BOARD. IF ONE LEG OF 24VAC
SUPPLY IS GROUNDED, THEN GROUND LEG MUST BE CONNECTED TO TB1-2.
CONTACTORS ARE 24 VAC: 12VA MAX/COIL (MERCURY CONTACTORS). 10VA MAX/COIL
(MAGNETIC CONTACTORS)
OPTIONAL FUSE, DISCONNECT SWITCH & TRANSFORMER LOCATED IN HEATER.
11.
ZONE SENSOR TERMINALS 6 AND 7 REQUIRE SHIELDED TWISTED PAIR
WIRING FOR OPTIONAL USE OF COMMUNICATIONS JACK.
11 10 7 6 3 2 1
DIGITAL DISPLAY ZONE SENSOR
W/ COMM. JACK
REMOTE MTD.
4.
11.
OPTIONAL FIELD INSTALLED
DIGITAL DISPLAY ZONE SENSOR
TB2-6
TB2-5
TB3-3
TB3-2
TB3-1
2(+) 1(-)
ZONE SENSOR
W/ COMM. JACK
REMOTE MTD.
3.
3
4.
2 1
OPTIONAL FIELD
INSTALLED ZONE SENSOR
6.
CO2
SENSOR
24V
GND
OUT
+
0
V
(TB1-1) 24V
(TB3-6) GND
(TB3-5) A/CO2
OPTIONAL FIELD INSTALLED
CO2 SENSOR
WARNING
HAZARDOUS VOLTAGE!
DISCONNECT ALL ELECTRIC POWER
INCLUDING REMOTE DISCONNECTS AND
FOLLOW LOCK OUT AND TAG PROCEDURES
BEFORE SERVICING. INSURE THAT ALL
MOTOR CAPACITORS HAVE DISCHARGED
STORED VOLTAGE. UNITS WITH VARIABLE
SPEED DRIVE, REFER TO DRIVE
INSTRUCTIONS FOR CAPACITOR DISCHARGE.
FAILURE TO DO THE ABOVE COULD RESULT
IN DEATH OR SERIOUS INJURY.
AVERTISSEMENT
TENSION DANGEREUSE!
COUPER TOUTES LES TENSIONS ET
OUVRIR LES SECTIONNEURS À DISTANCE,
PUIS SUIVRE LES PROCÉDURES DE
VERROUILLAGE ET DES ÉTIQUETTES AVANT
TOUTE INTERVENTION. VÉRIFIER QUE TOUS
LES CONDENSATEURS DES MOTEURS SONT
DÉCHARGÉS. DANS LE CAS D'UNITÉS
COMPORTANT DES ENTRAÎNEMENTS À
VITESSE VARIABLE, SE REPORTER AUX
INSTRUCTIONS DE L'ENTRAÃŽNEMENT POUR
DÉCHARGER LES CONDENSATEURS.
NE PAS RESPECTER CES MESURES DE
PRÉCAUTION PEUT ENTRAÎNER DES
BLESSURES GRAVES POUVANT ÊTRE
MORTELLES.
ADVERTENCIA iVOLTAJE PELIGROSO!
DESCONECTE TODA LA ENERGà A ELÉCTRICA,
INCLUSO LAS DESCONEXIONES REMOTAS Y
SIGA LOS PROCEDIMIENTOS DE CIERRE Y
ETIQUETADO ANTES DE PROCEDER AL
SERVICIO. ASEGÚRESE DE QUE TODOS
LOS CAPACITORES DEL MOTOR HAYAN
DESCARGADO EL VOLTAJE ALMACENADO.
PARA LAS UNIDADES CON TRANSMISIÓN
DE VELOCIDAD VARIABLE, CONSULTE LAS
INSTRUCCIONES PARA LA DESCARGA
DEL CONDENSADOR.
EL NO REALIZAR LO ANTERIORMENTE
INDICADO, PODRÃ A OCASIONAR LA MUERTE
O SERIAS LESIONES PERSONALES.
14 VAV-SVX01D-EN
Figure 4.
Wiring diagram for fan-powered units with field installed reheat
UCM 4.2 Installation and Wiring
VAV-SVX01D-EN 15
UCM 4.2 Installation and Wiring
Figure 5.
Wiring diagram for fan-powered units with factory installed electric reheat
HEATER
TERMINAL
BOX WIRING
DAMPER
ACTUATOR
WIRING
FAN CONTROL
BOX WIRING
OPTIONAL
FACTORY
INSTALLED
WIRELESS
24VAC
BL
Y
Y
BL
2ND STG HEAT
1ST STG HEAT
GND
UCM or EI Board
24V
TB1-1
TB1-2
TB2-6
TB2-5
TB3-3
TB3-2
TB3-1
R-FAN
24 VAC
BR
Y
BL
ADDRESS
SWITCH
+ + -
J1 1
ACT
D.D.C.\U.C.M.
BIP GND 24V
CONTROL BOARD
+ -
YEL
J3
GRN
ZONE GND SET A/CO2 GND
1
S
7.
R
BK
G
PRESSURE
TRANSDUCER
+
VOUT
-
11 10 7 6 3 2 1
DIGITAL DISPLAY ZONE SENSOR
W/ COMM. JACK
REMOTE MTD.
4.
6.
OPTIONAL FIELD INSTALLED
DIGITAL DISPLAY ZONE SENSOR
TB2-6
TB2-5 TB3-2
TB3-3
TB3-1
2(+) 1(-) 3 2
ZONE SENSOR
W/ COMM. JACK
REMOTE MTD.
3.
4.
1
OPTIONAL FIELD
INSTALLED ZONE SENSOR
D.D.C.\U.C.M.
CONTROL BOX
SHIELDED
TWISTED PAIR
COMMUNICATIONS
WIRING
OPTIONAL FACTORY INSTALLED
WIRELESS
5.
R (HOT)
O (COMMON)
GR (NC CONTACT)
BK (RETURN)
Y
(TB1-1) 24VAC
(TB4-1) BIP
(TB1-1) 24VAC
(TB1-2) GND
NOT CONNECTED
OPTIONAL FIELD INSTALLED
OCCUPANCY SENSOR
TB3-5 TB3-6
6.
OPTIONAL
AUX TEMP SENSOR
6.
+
0
(TB1-1) 24V
24V
CO2
SENSOR GND
OUT
(TB3-6) GND
(TB3-5) A/CO2
V
OPTIONAL FIELD INSTALLED
CO2 SENSOR
NOTE:
1.
FACTORY WIRING
FIELD WIRING
OPTIONAL OR ALTERNATE WIRING
2. 1/4" QUICK CONNECT REQUIRED FOR ALL FIELD CONNECTIONS.
3.
4.
ZONE SENSOR TERMINALS 1 (-) AND 2 (+) REQUIRE SHIELDED TWISTED PAIR WIRING FOR COMMUNICATIONS
JACK EQUIPPED ZONE SENSOR OPTION.
NO ADDITIONAL WIRING REQUIRED FOR NIGHT SETBACK OVERRIDE (ON/CANCEL).
5.
6.
7.
THE OPTIONAL BINARY INPUT CONNECTS BETWEEN TB4-1 (BIP) AND 24VAC (HOT) FROM TRANSFORMER.
THE BINARY INPUT CAN BE RECONFIGURED AS AN OCCUPANCY INPUT VIA THE COMMUNICATIONS
INTERFACE.
AS SHIPPED, THE AUX INPUT IS CONFIGURED AS AN AUX TEMP INPUT. THE AUX INPUT CAN BE
RECONFIGURED AS A CO2 SENSOR INPUT VIA THE COMMUNICATIONS INTERFACE.
S TERMINAL NOT TO BE USED WITH VARITRANE.
8.
ZONE SENSOR TERMINALS 6 AND 7 REQUIRE SHIELDED TWISTED PAIR WIRING FOR COMMUNICATIONS
JACK EQUIPPED ZONE SENSOR OPTION.
WARNING
HAZARDOUS VOLTAGE!
DISCONNECT ALL ELECTRIC POWER
INCLUDING REMOTE DISCONNECTS AND
FOLLOW LOCK OUT AND TAG PROCEDURES
BEFORE SERVICING. INSURE THAT ALL
MOTOR CAPACITORS HAVE DISCHARGED
STORED VOLTAGE. UNITS WITH VARIABLE
SPEED DRIVE, REFER TO DRIVE
INSTRUCTIONS FOR CAPACITOR DISCHARGE.
FAILURE TO DO THE ABOVE COULD RESULT
IN DEATH OR SERIOUS INJURY.
AVERTISSEMENT
TENSION DANGEREUSE!
COUPER TOUTES LES TENSIONS ET
OUVRIR LES SECTIONNEURS À DISTANCE,
PUIS SUIVRE LES PROCÉDURES DE
VERROUILLAGE ET DES ÉTIQUETTES AVANT
TOUTE INTERVENTION. VÉRIFIER QUE TOUS
LES CONDENSATEURS DES MOTEURS SONT
DÉCHARGÉS. DANS LE CAS D'UNITÉS
COMPORTANT DES ENTRAÎNEMENTS À
VITESSE VARIABLE, SE REPORTER AUX
INSTRUCTIONS DE L'ENTRAÃŽNEMENT POUR
DÉCHARGER LES CONDENSATEURS.
NE PAS RESPECTER CES MESURES DE
PRÉCAUTION PEUT ENTRAÎNER DES
BLESSURES GRAVES POUVANT ÊTRE
MORTELLES.
ADVERTENCIA iVOLTAJE PELIGROSO!
DESCONECTE TODA LA ENERGà A ELÉCTRICA,
INCLUSO LAS DESCONEXIONES REMOTAS Y
SIGA LOS PROCEDIMIENTOS DE CIERRE Y
ETIQUETADO ANTES DE PROCEDER AL
SERVICIO. ASEGÚRESE DE QUE TODOS
LOS CAPACITORES DEL MOTOR HAYAN
DESCARGADO EL VOLTAJE ALMACENADO.
PARA LAS UNIDADES CON TRANSMISIÓN
DE VELOCIDAD VARIABLE, CONSULTE LAS
INSTRUCCIONES PARA LA DESCARGA
DEL CONDENSADOR.
EL NO REALIZAR LO ANTERIORMENTE
INDICADO, PODRÃ A OCASIONAR LA MUERTE
O SERIAS LESIONES PERSONALES.
16 VAV-SVX01D-EN
Wireless Zone Sensor
Overview
TheTrane Wireless Zone Sensor set includes a sensor and a receiver that work together to provide the same functions as the equivalent Trane wired sensor (#4190-
1090), such as the standard 10 k temperature input (with the exception of the communication jack). No further software or hardware is necessary for site evaluation, installation, or maintenance.
The sensor transmits the zone temperature, all zone temperature setpoint functions, timed override Occupied
Figure 6.
Outside dimensions for sensor
(On) and timed override Unoccupied (Cancel) information to the receiver. The receiver electrically reproduces the zone temperature resistance, all zone temperature setpoint function resistances, and timed override On and timed override Cancel information as sent by the sensor.
Dimensional Diagrams
See
and
for dimensions of the
Wireless Zone Sensor set. The dimensions are the same for both the sensor and the receiver.
1.08 in (2.75 cm)
2.90 in (7.35 cm)
4.78 in (12.14 cm)
2.62 in (6.65 cm)
Note: The dimensions are the same for both the sensor and the receiver.
VAV-SVX01D-EN 17
Wireless Zone Sensor
Figure 7.
Mounting hole dimensions for sensor
3.27 in (8.30 cm)
2.36 in (6.00 cm)
1.34 in (3.41 cm)
Setting the Address, Mounting,
Wiring, and Associating the
Receiver and Sensor
The following procedure list shows the recommended order for installation:
• Choosing a location for mounting the sensor
• Setting the rotary address switches on the receiver and on the sensor
• Replacing and securing the receiver cover
• Powering the sensor and associating the sensor to the receiver
• Applying power to the receiver
• Testing signal and battery strength
• Disassociation
Note: The dimensions are the same for both the sensor and the receiver.
Choosing a Location for Mounting the
Sensor
Placement of the receiver and the sensor set is critical to proper operation. In most installations, distance is not the limiting factor for proper radio signal quality. It is more greatly affected by walls, barriers, and general clutter. For best radio transmission range and reliability, wherever possible, mount the receiver and sensor in line of sight.Try
to minimize the number of barriers between the pair of devices. In general, sheetrock walls and ceiling tiles offer little restriction to the propagation of the radio signal throughout the building; concrete or metal barriers offer the most restriction.The transmission range for the sensor is as follows:
• Open range: 2,500 ft (762 m) (packet error rate = 2%)
• Usable range: 200 ft (61 m)
• Typical range: 75 ft (23 m)
18 VAV-SVX01D-EN
Wireless Zone Sensor
Ambient considerations
Avoid locations that are outside the operating temperature and humidity range (see
).
• Avoid placing the sensor inside metal enclosures
• Avoid radio transmissions through thick, solid concrete walls
Location Considerations for the Sensor
When selecting a location for the sensor, consider both thermal and radio transmission characteristics of the location.
Setting the Rotary Address Switches on the Receiver and the Sensor
Note: To expedite the installation and association process, set the addresses before applying power to the receiver.
Thermal considerations
• Avoid areas of direct sunlight
• Avoid areas in the direct air stream of air diffusers
• Avoid exterior walls and other walls that have a temperature differential between their two sides
• Avoid areas close to sources of heat such as sunlight, appliances, or other equipment
• Avoid drafty areas
• Avoid dead spots behind doors, projection screens, or corners
The process of establishing communication between the receiver and sensor is referred to as association. The receiver and the sensor must have their rotary switches set to the same address in order to enable communication between the two devices (see
). Important limitations are as follows:
• Only one associated receiver/sensor set can communicate within the reception range of the wireless system.
• It is not possible to associate more than one sensor to a receiver, nor is it possible to associate more than one receiver to a sensor.
Radio transmission considerations
• Avoid metal barriers between the sensor and receiver, such as plastered walls with metal lathe as they will decrease radio signal quality.
Figure 8.
Setting the rotary address switches on the receiver and the sensor
Do not remove the insulation strip yet.
!
LE
A
L
S4
LED1
LED2
LED3
SIGNAL
LED5
S1 S2 S3
POWER
S5
C33 C34
J1
S5
HEATING SET
FAN/SYSTEM
SETPOINT
ZONE
GND
24VAC/DC
GND
COMM +
COMM -
C35
R77
Setting the Receiver Address
1.
Using a small screwdriver, set the three rotary address switches (locations S1, S2, S3) on the receiver
(
) to an address between 001 and 999.
Note: Do not use 000 as an address for installation. If you set the receiver address to 000, it will:
– Return the receiver outputs to their factory defaults indefinitely (zone temperature and setpoint outputs: 72.5°F [22.5°C])
– Remove all association knowledge
VAV-SVX01D-EN
B1 +
Pb
Pb-FREE
LED1
LED2
LED3
SIGNAL
LED5
BATTERY
STATUS
S1 S2
ADDRESS
S3
STATUS
S4
– Make the receiver unable to associate with a sensor
• Read the switches from left to right in the order in which they are numbered (S1, S2, S3).
• Zero is at the 9 o'clock position.
2. Make a notation of the address and location of the receiver.
19
Wireless Zone Sensor
Setting the Sensor Address
1.
Using a small screwdriver, set the three rotary address
be associated with.
2. Make a notation of the address and location where this sensor is to be mounted.
Note: Do not use 000 as an address for installation. If you set the address to 000, it will:
– Remove all association knowledge
– Revert to a low-power hibernation mode.
– Send a disassociation request to the receiver. If the sensor and receiver are associated and communicating at the time the sensor is set to
000 and the Test button is pressed, the receiver will also become unassociated and will be available for re-association.
• Read the switches from left to right in the order in which they are numbered (S1, S2, S3).
• Zero is at the 9 o'clock position.
3. Make a notation of the address and location of the sensor.
Factory Wiring of the Receiver to the VAV
UCM
The required power for the receiver is 24 VAC or 24 Vdc and is less than 1 VA. The receiver is designed to be powered by the VAV UCM controller.
Note: A dedicated transformer is not necessary or advised.
20 VAV-SVX01D-EN
Wireless Zone Sensor
Figure 9.
Factory wiring of the receiver to the VAV UCM
TO J8
TO J9
TO J10
W (HOT)
BK (CLOSE)
R (OPEN)
PROP.
WATER
VALVE
24VAC
12VA MAX
OPTIONAL FIELD INSTALLED
PROPORTIONAL WATER VALVE
DAMPER
ACTUATOR
WIRING
24VAC 60HZ
NEC CLASS-2
CONTROL CIRCUIT
LOAD= 12VA
(WITHOUT HEAT)
8.
OPTIONAL
FACTORY
INSTALLED
WIRELESS
24VAC
BL
Y
Y
BL
OPTIONAL
FUSE, DISCONNECT
& TRANSFORMER
GND
UCM or EI Board
24V
GREEN
GROUND
SCREW
OPTIONAL POWER
TRANSFORMER
(50VA)
OPTIONAL
DISCONNECT
SWITCH
BK
BK
BL
OPTIONAL
FUSE
Y
+ + -
J1 1
ACT
BIP GND 24V
D.D.C.\U.C.M.
CONTROL BOARD
+ -
GRN
ZONE GND SET A/CO2 GND
1
R
BK
G
PRESSURE
TRANSDUCER
ADDRESS
SWITCH
YEL
J3
7.
+
VOUT
-
GND
UCM or EI Board
24V
5.
R (HOT)
O (COMMON)
GR (NC CONTACT)
BK (RETURN)
Y
(TB1-1) 24VAC
(TB4-1) BIP
(TB1-1) 24VAC
(TB1-2) GND
NOT CONNECTED
OPTIONAL FIELD INSTALLED
OCCUPANCY SENSOR
TB1-1 TB2-6
TB1-2 TB2-5
TB3-3
TB3-2
TB3-1
Table 7.
D.D.C.\U.C.M.
CONTROL BOX
SHIELDED TWISTED PAIR
COMMUNICATIONS WIRING
TB3-5 TB3-6
OPTIONAL FACTORY INSTALLED
WIRELESS
TB2-6
TB2-5 TB3-2
TB3-3
TB3-1
6.
(TB1-1) 24V
CO2
SENSOR
24V
GND
OUT
+
0
V
(TB3-6) GND
(TB3-5) A/CO2
OPTIONAL FIELD INSTALLED
CO2 SENSOR
NOTE:
1.
6.
OPTIONAL
AUX TEMP SENSOR
2(+) 1(-) 3 2
ZONE SENSOR
W/ COMM. JACK
REMOTE MTD.
3.
4.
1
FACTORY WIRING
FIELD WIRING
OPTIONAL OR ALTERNATE WIRING
OPTIONAL FIELD
INSTALLED ZONE SENSOR
2. 1/4" QUICK CONNECT REQUIRED FOR ALL FIELD CONNECTIONS.
3.
ZONE SENSOR TERMINALS 1 (-) AND 2 (+) REQUIRE SHIELDED TWISTED PAIR
WIRING FOR COMMUNICATIONS JACK EQUIPPED ZONE SENSOR OPTION.
4.
NO ADDITIONAL WIRING REQUIRED FOR NIGHT SETBACK OVERRIDE (ON/CANCEL).
5.
6.
7.
THE OPTIONAL BINARY INPUT CONNECTS BETWEEN TB4-1 (BIP) AND 24VAC (HOT) FROM
TRANSFORMER. THE BINARY INPUT CAN BE RECONFIGURED AS AN OCCUPANCY INPUT VIA THE
COMMUNICATIONS INTERFACE.
AS SHIPPED, THE AUX INPUT IS CONFIGURED AS AN AUX TEMP INPUT. THE AUX INPUT CAN BE
RECONFIGURED AS A CO2 SENSOR INPUT VIA THE COMMUNICATIONS INTERFACE.
S TERMINAL NOT TO BE USED WITH VARITRANE.
TO J10
TO J9
TO J8
2ND STG.
1ST STG.
HOT
HEATER STAGE
CONTACTOR(S)
24VAC, 12VA
MAX/COIL
OPTIONAL FIELD INSTALLED
ELECTRIC HEATER
TO J9
TO J8
ON - OFF
WATER VALVE
24 VAC
12VA MAX
OPTIONAL FIELD INSTALLED
0N-OFF WATER VALVE
8.
9.
IF UNIT MOUNTED TRANFORMER IS NOT PROVIDED, POLARITY FROM UNIT TO UNIT MUST BE
MAINTAINED TO PREVENT PERMANENT DAMAGE TO CONTROL BOARD. IF ONE LEG OF 24VAC
SUPPLY IS GROUNDED, THEN GROUND LEG MUST BE CONNECTED TO TB1-2.
OPTIONAL FUSE, DISCONNECT SWITCH & TRANSFORMER WIRING. WIRINGS GOES THRU TO
NEXT COMPONENT WHEN OPTIONS ARE NOT CHOSEN/
10.
TRANSFORMER WIRE COLORS: 120V - W, 208V - R, 240V - O, 277V - BR, 480V - R/BK
575V -R, 190V - R, 220V - R, 347V - R.
11.
ZONE SENSOR TERMINALS 6 AND 7 REQUIRE SHIELDED TWISTED PAIR
WIRING FOR OPTIONAL USE OF COMMUNICATIONS JACK.
Wiring harness: wire identification
Wire Label
HEATING SET
FAN/SYSTEM
SETPOINT
ZONE
GND-SIGNAL
Color
N/A
N/A
Red
White
Black
Function
Not used. For future use.
Not used. For future use.
Space temperature setpoint
Zone temperature
Ground for setpoint and zone signal
11 10 7 6 3 2 1
DIGITAL DISPLAY ZONE SENSOR
W/ COMM. JACK
REMOTE MTD.
4.
11.
OPTIONAL FIELD INSTALLED
DIGITAL DISPLAY ZONE SENSOR
WARNING
HAZARDOUS VOLTAGE!
DISCONNECT ALL ELECTRIC POWER
INCLUDING REMOTE DISCONNECTS AND
FOLLOW LOCK OUT AND TAG PROCEDURES
BEFORE SERVICING. INSURE THAT ALL
MOTOR CAPACITORS HAVE DISCHARGED
STORED VOLTAGE. UNITS WITH VARIABLE
SPEED DRIVE, REFER TO DRIVE
INSTRUCTIONS FOR CAPACITOR DISCHARGE.
FAILURE TO DO THE ABOVE COULD RESULT
IN DEATH OR SERIOUS INJURY.
AVERTISSEMENT
TENSION DANGEREUSE!
COUPER TOUTES LES TENSIONS ET
OUVRIR LES SECTIONNEURS À DISTANCE,
PUIS SUIVRE LES PROCÉDURES DE
VERROUILLAGE ET DES ÉTIQUETTES AVANT
TOUTE INTERVENTION. VÉRIFIER QUE TOUS
LES CONDENSATEURS DES MOTEURS SONT
DÉCHARGÉS. DANS LE CAS D'UNITÉS
COMPORTANT DES ENTRAÎNEMENTS À
VITESSE VARIABLE, SE REPORTER AUX
INSTRUCTIONS DE L'ENTRAÃŽNEMENT POUR
DÉCHARGER LES CONDENSATEURS.
NE PAS RESPECTER CES MESURES DE
PRÉCAUTION PEUT ENTRAÎNER DES
BLESSURES GRAVES POUVANT ÊTRE
MORTELLES.
ADVERTENCIA iVOLTAJE PELIGROSO!
DESCONECTE TODA LA ENERGà A ELÉCTRICA,
INCLUSO LAS DESCONEXIONES REMOTAS Y
SIGA LOS PROCEDIMIENTOS DE CIERRE Y
ETIQUETADO ANTES DE PROCEDER AL
SERVICIO. ASEGÚRESE DE QUE TODOS
LOS CAPACITORES DEL MOTOR HAYAN
DESCARGADO EL VOLTAJE ALMACENADO.
PARA LAS UNIDADES CON TRANSMISIÓN
DE VELOCIDAD VARIABLE, CONSULTE LAS
INSTRUCCIONES PARA LA DESCARGA
DEL CONDENSADOR.
EL NO REALIZAR LO ANTERIORMENTE
INDICADO, PODRÃ A OCASIONAR LA MUERTE
O SERIAS LESIONES PERSONALES.
Table 7.
Wiring harness: wire identification (continued)
Wire Label Color Function
24 VAC/DC
GND-POWER
COMM +
COMM -
Blue
Yellow
N/A
N/A
24 VAC/Vdc power
Ground for 24 VAC/dc
Not used. For future use.
Not used. For future use.
Note:
Both GND-SGNAL and GND-POWER must be wired for the receiver to operate (See
VAV-SVX01D-EN 21
Wireless Zone Sensor
Replacing and Securing the Receiver
Cover
1. To replace the receiver cover on the base plate, hook the cover over the top of the base plate. Apply light pressure to the bottom of the cover until it snaps in place.
2. If necessary to keep the cover securely attached, install the security screw into the bottom of the receiver
(
Figure 10.
Snap receiver cover on base plate and attach security screw
Figure 11.
LED5 stays on after applying power to the receiver
LED5 stays constantly On
Security screw
Applying Power to the Receiver
Restore power to the UCM. Observe LED5 on the receiver
(
). It will light and stay constantly On when
24V power is normal.
Receiver Indicates Readiness to Associate
After initial power up, the receiver conducts a channel scan for 10 seconds. During this time, the receiver selects from
16 available channels the clearest channel on which to operate. LED1, LED2, and LED3 flash rapidly in succession
(round-robin style) while the channel scan is in progress.
Note: Do not attempt association until the channel scan is finished. After the channel scan is finished, LED3 will begin blinking (one-blink pattern) to show that the receiver is ready to be associated with a sensor.
LED3 will stop blinking when association has been established (
Figure 12.
LED3 blinks when the receiver is ready to be associated with a sensor
22
LED3
LED3 will begin to blink after
10 seconds
VAV-SVX01D-EN
Powering the Sensor and Associating the
Sensor to the Receiver
1. Verify the sensor is set to the same address as the associated receiver.
2. Remove the insulation barrier, which is a plastic strip
located between the two batteries ( Figure 13, p. 23 ).
3. Association will automatically occur between the sensor and the receiver. If the first association attempt is unsuccessful, the sensor will automatically reattempt association with the receiver every 10 minutes.
Note: A disassociated sensor will transmit an association request every 10 minutes. An associated sensor that has lost communication with the receiver will transmit an association request every 50 minutes.
Note: LED3 on the receiver stops blinking to indicate that association has been established.
Figure 13.
Removing the insulation barrier on the sensor
SENSOR
Wireless Zone Sensor
2. View LED1, LED2, and LED3 to determine the strength of the signal. View LED5 to determine the strength of the battery.
Note: The LEDs will turn Off after 5 seconds to conserve battery strength.
3. Record the results in your commissioning statement.
Figure 14.
Testing signal and battery strength
SENSOR
LED1
LED2
LED3
LED5
Signal strength
B1 +
+
LED1
LED2
LED3
LED5
–
SIGNAL
LED5
BATTERY
STATUS
S1 S2
ADDRESS
S3
STATUS
S4
WIRELESS
IINSTALL
+
J1
Pb
Pb-FREE
–
B2 -
S5
Testing Signal and Battery Strength
The following recommended test indicates signal and battery strength. It verifies that the association process was successful and that the batteries have adequate charge. (For more information on LEDs, see
1.
Firmly press and release the Test button (S5) on the bottom of the sensor (
VAV-SVX01D-EN
S5
(Test button)
Push S5 firmly, then release
Disassociation
The receiver removes all stored association information, conducts a channel scan, and restarts itself, if any of the following are true:
• The receiver address is changed from its current setting (001-999)
• The receiver receives a disassociation notification from its associated sensor
• The receiver does not receive a communication from its associated sensor within 35 minutes
23
UCM Programming and Operation
Chapter Overview
Note: For Instructions on how to use Rover Comm4, refer to the Rover Comm4 online Help by clicking
Contents and Index on the Help menu.
This chapter contains information about the following:
• Accessing Rover/Comm4
• UCM Home Tabs: At a Glance
Laptop Requirements and Complete
Connection Instructions
• UCM Home Tabs: Instructions
• Entering and Exiting the Service Mode
For instructions on connecting a PC laptop to a Comm4 link, refer to the Installing Rover Service Tool Version 5.0,
3270 3275.
• Overriding VAVs
• Resetting Diagnostics
Note: A hard copy of this document is in the Rover package and an electronic copy (Installation.pdf) can be found on the Rover installation CD-ROM.
Accessing Rover/Comm4
To connect to a Comm4 Link
Rover Overview
1.
Insert the Comm4 card in the PC laptop.
Rover is a service tool that allows parameters to be viewed or adjusted in UCM v 2.0 and higher. Prior to UCM v 2.0, you would need to use EveryWare to access units that were stand alone.The operating and programming guide for Rover is EMTX-SVX01*-EN. Rover Comm4 is a software application for monitoring, configuring, and testing VAV II/
III/IV controllers on Comm4 links. Rover Comm4 replaces
Every Ware service software.
2. Connect the cables as shown in the appropriate figure.
See
for connecting to a Comm4 controller through a zone sensor and
for Connecting to a Comm4 controller using alligator clips.
Note: Make sure to maintain polarity.
Figure 15.
Connecting to a Comm4 controller through a zone sensor.
RJ11 plug
Adapter cable
Comm4
PCMCIA card
24 VAV-SVX01D-EN
Figure 16.
Connecting to a Comm4 controller using alligator clips
UCM Programming and Operation
4. Double-click on the Comm4 Service Tool icon to access a Comm4VAV UCM.This tool allows the user to monitor, configure, and test Comm4.
Figure 17.
Rover service tool
Comm4
PCMCIA card
Adapter cable
RJ11 plug
3. Double-click the Rover icon on the laptop PC desktop.
The Rover Service Tool screen will appear.
5. Rover/Comm4 will launch. Click to launch the Scan for
Devices dialog box.
Figure 18.
Rover/Comm4 application with the Scan for Devices dialog box.
VAV-SVX01D-EN 25
UCM Programming and Operation
6. The user may search by the address of a single UCM or scan the range of UCM addresses specified
Note: Address for VAV UCM's range from 65-127.
7.
Select the desired device or range of devices and click the Scan button. You’ll be able to watch as the applications scan for the selected data.
Note: The numbers selected for each device (65-127) can be referenced back to address selection for the UCM(s). See
settings.
Figure 19.
Scanning for Devices screen
8. Once the scan is complete, the results will populate the device tree on the left-hand side of the Rover/Comm4 screen.
Figure 20.
Rover/Comm4 screen
9. Access the desired UCM from the device tree.
UCM Home Tabs: At a Glance
Figure 21.
UCM home tabs
26 VAV-SVX01D-EN
Status Tab
Unit Info
UnitType:The different types of units for the selected
UCM.
Software Revision: The version of the UCM software.
Setpoints
Active Heating: The active (or actual) heating setpoint currently used by the UCM.
Active Cooling: The active (or actual) cooling setpoint currently used by the UCM.
Zone Sensor: Shows the setpoint set at the zone sensor for the controlled space.
Control
Mode: Shows whether the UCM is in occupied or unoccupied mode. The control mode determines which heating or cooling setpoints to use.
Action: Shows the UCM’s heating or cooling action.
The cool control action modulates the air valve as if the supply duct air is colder than the space temperature.
The heat control action modulates the air valve as if the supply duct air is warmer than the space temperature.
Binary Input
Type: For version 4.0 or higher UCMs, shows whether the BIP is configured for occupancy or as a Generic BIP.
Status: Shows the position of the binary input Open/
Closed as a generic input or Occupied Unoccupied from an occupancy input.
Fan
Type: The type of fan for the unit may be Series,
Parallel, or -- (none).
Status: Shows whether the fan is enabled or disabled.
Present Value: Shows whether the fan is on or off.
Auxiliary Input
Type: Shows the two types of auxillary inputs, temperature and C0
2
. They are mutually exclusive to one another.
Value: The displayed value will reflect either the temperature (if it has a temperature sensor input) or the PPM (if it is configured with a C0
2 input).
Other
Position: The air valve or damper position.
Flow: This line displays the unit's airflow rate expressed in the flow units selected in the setup menu.
This line will not be shown if the UCM is using position control instead of flow control. The UCM will use position control if the flow sensor is failed or not installed.The UCM will also use position control if the
UCM Programming and Operation
unit's airflow rate is less than 5% or greater than 110% of the unit's cataloged CFM. For example, the UCM will use position control for a size 600 CFM unit if the flow is less than 30 CFM (5%) or greater than 660 CFM
(110%).
Note: Although the UCM will read flow down to
5% of cataloged and up to 110% of cataloged, the range of MIN FLOW settings is 0%, or 10% to 100% of cataloged. The range of MAX FLOW settings is 100% of cataloged. In the example above, the lowest allowable MIN FLOW set point is 60
CFM (zero is also permissible) and 600 CFM is the highest allowable MAX FLOW set point.
ZoneTemp:The temperature, as reported by the zone sensor. If the UCM is at version 4 or greater and the unit type is Bypass Damper Round or Rectangular, this field is replaced by the supply air temperature. Dashes appear if the zone sensor is not functioning when allowed to be displayed.
Flow Control: The flow control override of the UCM.
Valid values: Auto, Open, Closed, Min, or Max.
Present Minimum: If the UCM is in pressure independent mode (using flow control), the present minimum, expressed in the appropriate flow units, appears in the Present Minimum field. If the UCM is in pressure dependant mode (using position control), the minimum is expressed as percentage open.
Ventilation Ratio: The ventilation ratio equals the outside air requirement divided by the air valve flow.
Type the occupied outside air requirement and the unoccupied outside air requirement on the Setpoints tab.
Max Hot water Override: Used to give status if Hot water Valve is being overridden.
Heat
Type: This field shows the different types of reheat.
Choices are 1) None; 2) 3 Stage Electric; 3) Electric Slow
Pulse Width Modulation; 4) Proportional Hot Water with -Auxillary Heat; and 5) 3 Stage Hot Water.
Status: Shows whether the heat is enabled or disabled.
Present Value: Shows whether the heat is on or off.
Setpoints Tab
The UCM Home screens that are shown are non adjustable and are used to show values only.
Note: The Setpoints tab will be defined in programming the configuration menus.
VAV-SVX01D-EN 27
UCM Programming and Operation
Wireless Tab
Note: This tab displays the older style wireless not to be confused with the new wireless that is being currently offered.
When the UCM version is 3.0 or higher, this tab displays the wireless sensor serial number assignments. Up to five wireless sensors may be assigned to a UCM. Four sensors may be chosen as averaging, one sensor can be chosen as backup.The backup sensors are optional. Backup sensors for temperature and setpoint inputs only affect the UCM if all averaging sensors fail. Backup button functions are always used. Any combination of backup strategies is valid.
For version 4.0 UCMs or higher, if the hardwired sensor is configured as not present then the hardwired zone temperature failure flag will not be set as long as at least one wireless sensor is transmitting a valid zone temperature. Likewise, if the hardwired sensor is
Figure 22.
Select the configure button configured as not present then the hardwired setpoint sensor failure flag will not be set as long as at least one wireless sensor is transmitting a valid setpoint.
Advanced Configuration Tab
The UCM Home Tabs (and their screens) that are shown are non adjustable and are used to show values only. The advanced configuration tab will be defined in programming the configuration menus
UCM Home Tabs: Instructions
Configuration
To access the data fields for each tab and to make adjustments, select the Configure button as shown in
Figure 22, p. 28 . To make adjustments, find the correct
parameter, change it, and download to UCM.
Setpoints Tab
Figure 23.
Setpoints tab
28 VAV-SVX01D-EN
In Rover, the setpoints can be viewed at the UCM
Setpoints tab and then also changed by selecting the
Configure button. Following are descriptions of each line on the UCM Setpoints tab.
Heating Setpoints
Active:The set point cannot be edited and reflects the set point currently being used for Heating temperature control.
Occupied: Set points have a range of 30.0°F- 100.0°F
(-1.1°C - 37.8°C). If a zone sensor thumbwheel set point is not being used, this set point will be used as the
UCM's active heating set point during occupied times.
The cooling set point must be greater than or equal to the heating set point plus 2.0°F (1.1°C).
Note: Occupied cooling and heating set points must be set within the cooling set point high limit and the heating set point low limit in order to control to the proper set points.
Unoccupied: Set points have a range of 30.0°F -
100.0°F (-1.1°C - 37.8°C). This heating set point is used when the UCM is unoccupied.The unoccupied heating set point must be less than or equal to the unoccupied colling set point minus 2°F (1.1°C). The unoccupied cooling set point must be greater than or equal to the unoccupied heating set point plus 2.0°F (1.1°C).
Low Limit: This limit applies to the occupied mode only starting in UCM version 4.1. Prior to version 4.1, the limits would affect both the unoccupied and occupied setpoints. The occupied heating set point is subject to high and low limits. The cooling set point high limit and the heating set point low limit "cap" your unoccupied set points, which directly impacts energy savings. The upper level device is responsible for preventing the resulting set points from being crossed.
This may happen if the heating set point low limit is above the cooling set point high limit. Having the cooling set point high limit and the heating set point low limit set to the factory defaults (cooling high limit
= 102°F (38.8°C), heating low limit = 43°F (6.1°C)) should prevent them from impacting field operation.
High Limit: This limit applies to the occupied mode only starting in UCM version 4.1. Prior to version 4.1, the limits would affect both the unoccupied and occupied setpoints. Both limits have a range of 30.0°F
- 100.0°F (-1.1°C - 37.8°C). The set point limits will be applied to the active heating set point by the UCM but will not restrict operator entry of set points.
Cooling Setpoints
Active:The set point cannot be edited and reflects the set point currently being used for cooling temperature control.
Occupied: Set points have a range of 30.0°F - 100.0°F
(-1.1°C - 37.8°C). If a zone sensor thumbwheel set point is not being used, this set point will be used as the
VAV-SVX01D-EN
UCM Programming and Operation
UCM's active cooling set point during occupied times.
The cooling set point must be greater than or equal to the heating set point plus 2.0°F (1.1°C).
Note: Occupied cooling and heating set points must be set within the cooling set point high limit and the heating set point low limit in order to control to the proper set points.
Unoccupied: Set points have a range of 30.0°F -
100.0°F (-1.1°C - 37.8°C). This cooling set point is used when the UCM is unoccupied.The unoccupied cooling set point must be greater than or equal to the unoccupied heating set point plus 2.0°F (1.1°C).
Low Limit: This limit applies to the occupied mode only starting in UCM version 4.1. Prior to version 4.1, the limits would affect both the unoccupied and occupied setpoints. Occupied Cooling set point is subject to high and low limits. The cooling set point high limit and the heating set point low limit "cap" your unoccupied set points, which directly impacts energy savings. The upper level device is responsible for preventing the resulting set points from being crossed.
This may happen if the heating set point low limit is above the cooling set point high limit. Having the cooling set point high limit and the heating set point low limit set to the factory defaults (cooling high limit
= 102°F (38.8°C), heating low limit = 43°F (6.1°C)) should prevent them from impacting field operation.
High Limit: This limit applies to the occupied mode only starting in UCM version 4.1. Prior to version 4.1, the limits would affect both the unoccupied and occupied setpoints. Both limits have a range of 30.0°F
- 100.0°F (-1.1°C - 37.8°C). The set point limits will be applied to the active heating set point by the UCM but will not restrict operator entry of set points.
Flow
Table 8.
Valid flow ranges (by model)
VariTrane C
VariTrane D
VariTrane F
0, 10-150%
0, 10-110%
0, 10-100%
Minimum: Although the UCM will read flow down to
5% of cataloged, the range of MIN FLOW settings is 0%, or 10% to 100% of cataloged.The UCM will not drive its flow below this minimum flow value under normal operating conditions while in the cool mode. Cool mode occurs when cool air is in the supply duct. The entry in the Cooling Minimum field must be less than or equal to the entry in the Maximum field.
Maximum: This range is 10% to 100% of the unit's cataloged CFM size. Cooling and heating flow can be edited to zero.The UCM will not drive its flow above this maximum flow value under normal operating conditions while in the Cool mode. Cool mode occurs when cool air is in the supply duct. The entry for
29
UCM Programming and Operation
Maximum Flow must be greater than or equal to the entry in any of the Minimum fields.
Min Heating:The UCM will not drive its position/flow below this value under normal operating conditions while in the HEAT mode (warm air in the supply duct) or while it is using local heat. The Min Heating Flow value must be less than or equal to the Maximum Flow value.
Min Local Heat: If the Min Local Heat flow is enabled, then the Min Local Heat flow is used to determine the minimum position/flow instead of the Min Heating
Flow when local heat is on.The entry for Min Heating
Flow must be less than or equal to the entry for the
Maximum Flow.
Outdoor Air Required
Occupied:The UCMs use these values to calculate the ventilation ratio. Valid range: 0 to 100%.
Unoccupied:The UCMs use these values to calculate the ventilation ratio. Valid range: 0 to 100%.
Offsets
Heat Offset: This is the value subtracted from the cooling thumbwheel setpoint to derive the heating
Figure 24.
Setup tab setpoint. This defines the minimum difference between the cooling and heating setpoints. Valid
Range: 2°F to 10°F.
Control Offset: When control offset is active, the
UCM adds the value to the edited occupied cooling setpoint and subtracts the control offset value from the edited occupied heating setpoint to determine the active setpoints. The control offset value does not affect a zone sensor thumbwheel setpoint.
Fan Control Setpoint
The entry on this line determines when a parallel fan will be turned ON and OFF. If "Parallel fan control" has been edited to "DEG" the fan control offset will be entered as a temperature offset (2° - 10°F) (1.1°C - 5.5°C) which will be added to the heating set point. If "Parallel fan control" has been edited to "FLOW" this line will be entered as a percent
(0 to 100%) if the unit is a VariTrane unit.The entry field on this line will appear as "-" if the unit does not have a parallel fan.
Important: This field is visible ONLY with Parallel Fan
Powered units.
Setup Tab
The following are descriptions of each line on the Setup tab. To make changes: Select the Configure button in
Rover and select the Setup tab. Make adjustments if
30 necessary by opening a drop down arrow or changing a value and press the download button.
VAV-SVX01D-EN
Other Fields
Unit Type: Select the proper unit type. The unit type information is maintained in the controller's EEPROM.
Important: Edit the unit type BEFORE editing any items on the above list!
Unit types available for all versions:
• VariTrane C
• VariTrac - Round
• VariTrane D
• Generic
Unit types available for VAV version 4.0 and above:
• Bypass Damper - Round
• Bypass Damper - Rectangular
• VariTrane F - Round
• VariTrane F - Rectangular
• VariTrac - Rectangular
Editing the unit type also affects the following entries:
• Heat type (The default is none)
• Fan type (The default is none)
• Unit size (The default is the smallest unit size)
• Air valve drive time
• Control Algorithm gains (KP, reset times, valve flow constant) for air valve and water valve.
Heat Type: The entry in the Heat Type field identifies what type of heat control algorithm the UCM should use. If you edit the unit type, Rover automatically changes the heat type to 0 (None). If you edit the heat type or if it changes automatically, Rover automatically assigns the heat outputs per factory specifications.
Possible selections include the following:
• NONE - No heat available
• 1-3 stages electric
• Slow pulse width modulation - Electric (3 min.
time base).
• Prop hot water and aux. output
• 1-3 stages hot water/perimeter
Max Hot Water Override:When the Max Hot Water
Override check box is selected, the UCM turns on all hot water outputs.This may be useful for water system balancing. The Maximum Hot Water Override affects only the following heat types:
• 3-Stage Hot Water - Rover energizes all three heat outputs. If the unit has a fan, output 3 is not affected.
• Hot Water with Auxiliary Output - Rover drives open the hot water valve connected to outputs 1 and 2. If not controlling a fan, output 3 energizes.
Note: For the Max Hot Water Override to be effective, the user MUST enable unit heat.
VAV-SVX01D-EN
UCM Programming and Operation
The UCM will maintain the "Max hot water override" condition over power failures.The only way to cancel a Max HotWater Override is to clear the Max HotWater
Override check box. If the unit does not have "1-3 stages hot water" or "proportional hot water and aux.
output will be grayed out and non selectable
Local Heat Setpoint: When the UCM version is 4.0
and the unit type is not "Bypass Damper - Rectangular" or "Bypass Damper - Round", this value is used to determine whether the Present Cooling Flow is compared to the Min Local Heat Flow setpoint or to the
Min Heat Flow setpoint to determine when terminal local heat is allowed.
Unit Size:The unit size is dependent on the unit type.
Select the unit size from a predetermined list.The unit size for VariTrane C, VariTrane D, VariTrac, and VariTrac-
Round type units are designated by their flow size using the appropriate units (CFM, CMS, or L/S). The unit size for VariTrane F-Round, VariTrane F-
Rectangular, VariTrac-Rectangular, Bypass Damper-
Round, and Bypass Damper-Rectangular type units are designated by the dimensions (in inches) of their blade dampers.
Flow Override: The entry in this field has the highest priority of all flow overrides (group, binary inputs, or upper level system functions). Override status can be
Auto, Open, Closed, Minimum, or Maximum. When a non-auto flow override is edited from the UCM level, the flow override will be maintained over power failures. See Sequence of Operations for more information.
Note: This is an excellent service point for checking damper operation and CFM flow.
Fan Type: Select the type of fan used by the UCM. If you edit the unit type field, Rover automatically changes the entry to 0 (None). When the value of this field is not None, the configuration of Output 3 is set to
Normally Open. Valid Selections: None, Parallel,
Series.
Note: The UCM may lockout the fan on its own if any of the following apply: control action
HEAT; flow override to drive OPEN, CLOSE, or MAX; or if the zone temperature sensor does not have valid input.
Parallel Fan Control: This entry will determine if a parallel fan will be controlled based on zone temperature or on flow conditions. If "Parallel fan control" has been edited to "DEG" the fan control offset will be entered as a temperature offset (2° - 10°F) (1.1°
- 5.5°C) which will be added to the heating set point. If
"Parallel fan control" has been edited to "FLOW" this line will be entered as a percent (0 to 100%) if the unit is a VariTrane unit. The entry field on this line will disappear if the unit does not have a parallel fan.
Note: See
“Sequence of Operations,” p. 38
of this manual for details on parallel fan operation.
31
UCM Programming and Operation
BIP Configuration: Version 4.0 or higher UCMs are provided with a binary input that can be used to monitor either an occupancy sensor or provide the status of a generic binary input. Valid Selections:
Occupancy, Generic.
BIP Configuration default is Generic. The BIP
Configuration interface is for dry relay contacts connected to TB4-1. In generic mode, the state of the input is only passed on from the UCM to Summit. CPL code must be written in order for Summit to utilize any signal received from this generic input. When configured as a generic input and communications are active, an occupancy input state will be reflected by the
UCM to the upper level system controller. The upper level system controller shall be responsible for causing any system changes necessary to provide occupied control. When configured for generic mode, loss of communications will result in the UCM defaulting back into occupied mode. In occupancy detector mode, the absence of a 24 VAC signal at TB4-1 indicates occupancy and the presence of 24 VAC indicates nonoccupancy. When configured for an occupancy sensor and communications are active, an occupancy input state will be reflected by the UCM to an upper level system controller. The upper level system controller shall be responsible for causing any system changes necessary to provide occupied control. When configured for an occupancy sensor and communications are not active and occupancy is detected, the UCM shall transition to the occupied mode of operation. Upon loss of the occupancy indication from the occupancy detector, the VAV UCM will revert back to unoccupied mode. However, when configured for an occupancy sensor and communications are active, loss of communications does not result in the VAV UCM defaulting to occupied mode.
Cooling Flow
Present Value: This present value shows the current flow being reported by the UCM.
Measured Value: If the present value of flow is incorrect the operator can enter the Measured value and Cooling Flow Correction factor will automatically be recalculated.
Note: This can be used to have the correct present value at the UCM as compared to the actual CFM at the inlet of the unit
Correction Factor: Value displayed to show how much the flow input needed to be corrected.
Auxiliary Input
Type: When the UCM version is 4.0 or higher the analog input labelled A/C0
2 can be used to monitor either an auxiliary temperature sensor or a C0
2 sensor.
Aux Input Select defaults to AuxTmp SensorThis entry determines the configuration of the A/C0
2 input on terminal TB3-5 of the UCM. Selecting AUX TMP
32
SENSOR configures the input to use an auxiliary temperature sensor. Selecting C0
2
Sensor configures the input to use a C0
2 sensor. They are mutually exclusive.
Value: When the UCM version is less than 4.0 or when the UCM version is 4.0 higher and the Auxiliary Input
Type is set to Temp Sensor, the current auxiliary temperature is displayed in this field. The value is reported after applying the calibration offset by the
UCM. If the temperature sensor fails, dashes (---) display instead of the temperature.
Calibration: The auxiliary temperature calibration offset adds the offset to the value read by the auxiliary temperature sensor.
EXAMPLE: If the auxiliary temperature sensor indicates a temperature of 74.0°F (23.3°C) and the auxiliary temperature calibration offset is -1.5°F, the actual temperature used by Rover is 72.5°F (22.5°C).
Valid range: -10.0°F - 10.0°F (-5.5°C - 5.5°C).
Note: It may take 30 seconds (after a new offset is entered) before the calibration is factored into the auxiliary temperature.
Outputs
1-3: The outputs can be either Normally Open or
Normally Closed. Outputs 1 and 2 can be edited only when the heat type is 3-Stage Hot Water. In all other cases they are set to Normally Open. If there is a fan, output 3 is set to Normally Open and cannot be edited.
If there is no fan, output 3 can be edited if the heat type is either 3-Stage Hot Water or Hot Water with Auxiliary
Output.
Wired Zone Temperature
Value: This field displays the value of the wired zone temperature sensor after the UCM has added the wired zone temperature calibration offset. If the zone sensor has failed or is not present, dashes (---) appear.
Calibration:The zone temperature sensor calibration offset.The UCM adds the offset to the value read by the zone sensor. After you add a new offset, Rover may take up to 30 seconds to update the displayed temperature. Valid Range: -10°F - 10°F (-5.5°C - 5.5°C).
Wired Sensor
Use: This input determines the function of the wired zone temperature sensor. Select Averaged to use the sensor as part of a wired system OR to use the sensor as an averaging sensor in an older style wireless system.
Type: This line is used to edit the type of temperature sensor being used.The sensor type can be selected as either Thermistor or RTD.
Note: Factory supplied sensors are thermistors.
VAV-SVX01D-EN
Note: Set point vote determines the weighting of the set point vote. The range is 0-9. This number represents the number of votes the sensor gets when the set points are averaged. If "0" is selected the sensor gets no vote.
Wired Thumbwheel
Select the check box to enable the local thumbwheel setpoint input. If the Thumbwheel Setpoint check box is not selected, the UCM does not respond to the following thumbwheel functions:
• Setpoint
• Ability to generate a "drive to max" command
• Ability to generate a "go unoccupied" command
Note: Disabling thumbwheel functions does not disable the On/Cancel push button feature.
Figure 25. Wireless tab
UCM Programming and Operation
Setpoint: This line displays the value of the thumbwheel setpoint after the calibration offset is applied. If theThumbwheel is placed in the ** position and the ON button is pressed, the UCM will request to go unoccupied. If the Thumbwheel is placed in the * position and the ON button is pressed, the UCM will request a maximum override. Valid Range: 50°F - 85°F
(10°C - 29.4°C) Fail, Max, Unocc.)
Calibration: The value of the zone temperature sensor calibration offset. The UCM adds the offset to the value read by the zone sensor. After you add a new offset, Rover may take up to 30 seconds to update the displayed temperature.Valid Range: -10°F - 10°F (-5.5°C
- 5.5°C).
Wireless Tab
This tab was used for the old style wireless system that used spread spectrum technology. For details on how this can be set up for existing applications using the older style wireless sensor see VAV-SVX01B-EN (VAV UCM 4.0).
VAV-SVX01D-EN 33
UCM Programming and Operation
Advanced Configuration Tab
Figure 26. Advanced configuration tab
Air Valve/Damper
Drive time:This adjustment can be used to match the
DDC UCM 4.2 to the actuator drive time.The air valve damper actuator drive time will be automatically adjusted to the type of Trane Unit type selected.
Min DriveTime: Displays the minimum time that the output can be driven.This value restricts the change in the mechanical output. Until the desired change in position will take at least the minimum drive time, the output will not be changed.
Air Flow
KP: This is an internal factor used by the PID control loop that modulates the air valve or damper.The value is predetermined by unit type and unit size.
Reset Time: This is an internal factor used by the PID control loop that modulates the air valve or damper.
The value is predetermined by unit type and unit size.
PWM Heat
KP: This is an internal factor used by the PID control loop that modulates the terminal heating.The value is predetermined by unit type and unit size.
Reset Time: This is an internal factor used by the PID control loop that modulates the terminal heating.The
value is predetermined by unit type and unit size.
Other
UCM 2/3 Trane Box: Shows whether the UCM is configured as a Trane box. By default only a box configured as generic is not a Trane box.
34
Cmd Unit I / Comfort Manager: Select the check box to use the VariTrane D best fit configuration. Clear the check box to use the Generic best fit configuration.This
check box applies to UCM versions 4.0 and higher.
When aVariTrane F style UCM orVariTrac - Rectangular
UCM is programmed, it is also configured to its best fit to a generic style or VariTrane D style box. Using this method, newer boxes can be used as replacements or to expand legacy systems.
Note: The Command Unit I and Comfort
Managers do not recognize a generic unit type.
Valve Gain: This is an internal factor used by the PID control loop that modulates the air valve or damper.
The value is predetermined by unit type and unit size.
Water Valve DriveTime: The drive time, in seconds, to stroke the water valve from 0 to 100%.
Valve Flow Constant:This is an internal factor used by the PID control loop that modulates the air valve or damper. The value is predetermined by unit type and unit size.
IAQ Multiplier: This value is usually sent by the ICS system to adjust the minimum flow setpoint.When the value is greater than 1.0, the VariTrac energy saver feature to ignore minimum flow is ignored and the minimum flow is enforced at the unit controller.
VariTrane F PD Min Position:The minimum damper position for aVariTrane F style box when it is operating in the pressure dependant mode. Valid range: 0 to
100%.
VAV-SVX01D-EN
Entering and Exiting the Service
Mode
Controllers must be online and in the service mode to receive an override. The service mode disables control fromTracer and places Rover/Comm4 in command of the controller. Controllers that are in the service mode appear in bold in the device tree on the left side of your screen.
More than one controller can be in the service mode at one time.
You can place a controller in the service mode manually or let Rover/Comm4 do so automatically when you start an override. Controllers exit the service mode automatically
15 minutes after the last override or when you manually release them.
To enter the service mode:
1.
Connect to the Comm4 link and scan for devices. See
‘Accessing Rover/Comm4’
2. In the device list on the left side of your screen, doubleclick the controller that you want to place in the service mode.
3. Click the Enter Service Mode button. While the controller is in the service mode, it appears in bold in the device list.
To exit the service mode, do one of the following:
• Wait for 15 minutes (Rover Comm4 does not need to be online with the controller).
• For each controller in the service mode, click the Exit
Service Mode button.
Overriding VAVs
When you override a controller, Rover Comm4 automatically places the controller in the service mode.
The controller is automatically released from the service mode after 15 minutes or when you click the Exit Service
Mode button for the device. You can manually release overrides by selecting the appropriate release command in the Override dialog box.
1.
On theTools menu, click Overrides.
2. Select whether to override TUCs or VAVs.
3. Click the units you want to override.
4. In the list of overrides, click the type of override you want to perform.
5. Click the Override button. The controller automatically enters the service mode and exits the service mode 15 minutes after receiving an override.
Resetting Diagnostics
You can reset diagnostics only for TUCs (not VAV units).
UCM Programming and Operation
1.
In the device list on the left side of your screen, doubleclick the controller for which you want to reset diagnostics.
2. Click the Diagnostics button.
3. Click the Reset button. Rover Comm4 attempts to clear all diagnostics on the controller and a message appears.
4. Click OK to close the message and the Diagnostics dialog box. You can click the Diagnostics button again to verify which diagnostics have been cleared.
Saving VAV Program
Each VAV unit with a UCM 4.2 has been factory commissioned with a program that can be saved to your hard drive.
This can be used to save the original program for a backup in case unit needs to be put back to original specifications or to download into a UCM 4.2 DDC controller that has like parameters that has been corrupted.
1.
Select the Configure button, and the Configuration screen will appear.
VAV-SVX01D-EN 35
UCM Programming and Operation
Figure 27.
Configuration screen (save as)
2. Click the File menu and click Save As.
Figure 28.
Save As prompt
3. The Save As dialog box will appear. Name unit and click Save.
Downloading Program Files from PC to
DDC UCM 4.2
1.
Select the Configure button, and the Configuration screen will appear
36 VAV-SVX01D-EN
Figure 29.
Configuration screen (open)
UCM Programming and Operation
2. Click the File menu and click Open.
3. The Open dialog box will appear. Select the file you wish to open and click the Open button.
Figure 30.
Open dialogue box
4. Download to DDC VAV controller.
5. Program is now in controller.
VAV-SVX01D-EN 37
Sequence of Operations
Chapter Overview
This chapter contains information about the following:
• Single Duct Units
• Override Conditions (Single Duct)
• Fan-Powered Units
• Parallel Fan-Powered Units
• Override Conditions (Parallel Fans)
• Series Fan-Powered Units
• Override Conditions (Series Fan)
• Zone Sensor Functions
• Flow Sensor
• Failure Modes
Single Duct Units
When the UCM control action is COOL, the UCM controls the modulation of the air valve as a cooling source to maintain the “active cooling set point”. Airflow is varied between the minimum and maximum flow set points to maintain temperature set points. A PI control algorithm is utilized to minimize the measured difference between the active zone set point and the actual zone temperature.
It is possible for units to utilize electric or hot water heating coils to maintain temperature set points. After the temperature loop calls for minimum cooling flow and the zone temperature is at or below the heating set point, these units shall control to their respective “Minimum
Heating Flow”. Once this “Minimum Heating Flow” is established, heat is allowed to operate according to the
“Heat Control Type” specified for the controller. For electric heat units, this heating minimum flow set point must be at or above 20% of the unit cataloged airflow.
Electric heat may be pulse width modulation or staged electric heat. Staging has the following ON and OFF switch points. UCM 3.3 and later allow hot water to turn on regardless of flow/position
Table 9.
Set points
Stage
1
2
3
ON Switch point
At the heating set point
1°F below the heating set point
2°F below the heating set point
Off Switch point
0.5°F above the heating set point
0.5°F below the heating set point
1.5°F below the heating set point
Hot water heat control may be either ON/OFF or proportional. ON/OFF hot water is activated on the same schedule as staged of electric heat.
Utilization of the “Heating Minimum Flow” set point allows separate minimum flows to be active depending on whether or not the unit heat is active.
38
Override Conditions (Single Duct)
The UCM occupied controls can be overridden by the following override commands:
Unoccupied
If the control mode is unoccupied (either as edited by software or as determined by the binary input), the unoccupied cooling and heating temperature set points are used for temperature control. Heat outputs remain active.
Heating
If the control action is edited to HEAT, the UCM controls the air valve as a heating source rather than cooling. Electric reheat is available the supply air temperature (or auxiliary temperature) is below 70ºF. Local hot water reheat is always available to keep the zone above the heating set point.The “Heating Minimum Flow Set Point” will set the minimum flow.
Flow Control Override
Flow control may be overridden by any of the following commands:
• Drive Air Valve Fully Open. The air valve will be fully open and heat outputs disabled.
• Drive AirValve Fully Closed.The air valve is driven fully closed and heat outputs disabled.
• Drive Air Valve to Minimum Flow. The air valve is driven to the minimum airflow set point. The heat outputs remain operational.
• Drive Air Valve to Maximum Flow. The air valve is driven to the maximum airflow set point. The heat outputs remain operational.
Heat Control Override
Heat control can be disabled, locking out heat outputs.
Control Offset
Control offset may be enabled, which adjusts the edited cooling and heating set points.
Recalibrate (Reset)
The recalibrate function can be enabled. If enabled, the unit will perform a recalibration.
VAV-SVX01D-EN
Sequence of Operations
Fan-Powered Units
Table 10.
Fan actuation schedule
FAN TYPE
Series
OCCUPIED
ON
UNOCCUPIED
OFF if valve closed
AND reheat off
Parallel based on
Temperature
Cool mode: ON if zone temp
<heating set point + fan offset fan offset +
0.5°F
Heat mode: fan off unless reheat is on
Cool mode: OFF if zone temp > heating set point + Heat mode: fan off unless reheat is on
Parallel based on Flow
Cool mode: ON if flow < fan set point OR if flow < active minimum flow set point
Heat mode: fan off unless reheat is on
Cool mode: OFF if flow > fan set point +
5% AND flow > active minimum flow set point
Heat mode: fan off unless reheat is on
OFF unless local reheat is on
OFF unless local reheat is on
Parallel Fan-Powered Units
Occupied Units
Air valve control for parallel fan-powered units is the same as for single duct units.
The first heat output is utilized to control the fan. The remaining outputs are utilized to control heat. Fan energization is a function of the “Parallel Fan Control
Offset”. The parallel fan control can be specified as an offset temperature in degrees above the heating set point or as a flow offset in CFM.The fan will be energized above the fan control offset if reheat is required.
Parallel Fan Flow Type Control
If the fan control is based on flow, the unit fan will be energized whenever primary airflow is below this set point. For this parallel fan configuration, the fan control point, if specified in a percentage of unit airflow, must be set between 15% and 30% of the units cataloged airflow to assure proper operation. A differential of 5% exists to avoid excessive fan cycling.
Note: The fan control offset is entered in CFM when used on a VariTrane unit.
Parallel Fan Temperature Type Control
When the fan control offset is in terms of a temperature above the heating set point, the fan shall be energized whenever the zone temperature is below the heating set point plus the fan control offset. A differential of 0.5°F
(0.3°C) shall apply to this switch over to avoid fan cycling.
Heat stages are energized on the following schedule:
Table 11.
Heat stages
Stage point
1
2
ON Switch point
At the heating set point
1°F below the heat set point
OFF Switch
0.5°F above the heat set point
0.5°F below the heat set point
Whenever the fan is energized, the primary airflow is controlled at the “Heating Minimum Flow” set point.
Override Conditions (Parallel
Fans)
The UCM occupied controls can be overridden by the following override commands:
Unoccupied
If the control mode is unoccupied, the unoccupied cooling and heating temperature set points are used for temperature control. Fan and heat outputs are activated at the unoccupied heating set point.
Heating
If the control action is HEAT, the UCM controls the air valve as a heating source rather than cooling. Fan and heat outputs are disabled for parallel units with electric heat. If the heat type is hot water heat, then the fan will remain on if the heat is on during the heating control action.
Flow Control Override
Flow control may be overridden by any of the following commands:
• Drive Air Valve Fully Open.The air valve will be driven fully open. Fan and heat outputs are disabled.
• Drive AirValve Fully Closed.The air valve is driven fully closed. Fan and heat outputs are disabled.
• Drive Air Valve to Minimum Flow. The air valve is driven to the minimum airflow set point. The fan and heat outputs remain operational.
• Drive Air Valve to Maximum Flow. The air valve is driven to the maximum airflow set point.The fan and electric heat outputs are disabled (hot water heat remains enabled).
Heat Control Override
Heat control can be disabled, locking out heat outputs.
Fan Control Override
Fan control can be disabled, locking out both fan and heat outputs. This affects only parallel fan-powered units.
Control Offset
Control Offset may be enabled, which adjusts the edited cooling and heating set points.
VAV-SVX01D-EN 39
Sequence of Operations
Recalibrate (Reset)
The recalibrate function can be enabled.
Series Fan-Powered Units
Occupied Units
Air valve control for series fan-powered units is the same as both single duct and parallel fan-powered units. During the occupied mode of operation, the series fan is continuously energized. Heat stages are energized on the following schedule:
Table 12.
Heat stages
Stage
1
2
ON Switch point
At the heating set point
1°F below the heat set point
OFF Switch point
0.5°F above the heating set point
0.5°F below the heat set point
Override Conditions (Series Fan)
The UCM occupied controls can be overridden by the following override commands:
Unoccupied
If the control mode is edited to unoccupied, the unoccupied cooling and heating temperature set points are used for temperature control.The series fan and heat outputs will be activated as necessary to maintain the current unoccupied set points.The fan control point is not utilized on series units. On electric heating and hot water heating units, the fan and heat are energized at the unoccupied heating set point.The minimum cooling flow set point is reset to zero unless minimums are being enforced by a group override. A series fan will be energized anytime the air valve’s position is greater than
0%.
Heating
If the control action is edited to HEAT, the UCM controls the air valve as a heating source rather than cooling.The unit fan remains operational. Unit heat on an electric heat unit is locked out, but remains active on hot water units.
Flow Control Override
Flow control may be overridden by any of the following commands:
• Drive Air Valve Fully Open.The air valve will be driven fully open. Fan operation is unaffected, but heat outputs are locked out.
• Drive AirValve Fully Closed.The air valve is driven fully closed. The fan and heat outputs are locked out.
• Drive Air Valve to Minimum Flow. The air valve is driven to the minimum airflow set point. The fan and heat outputs remain operational.
40
• Drive Air Valve to Maximum Flow. The air valve is driven to maximum airflow set point.The fan and heat outputs remain operational.
Heat Control Override
Heat control can be disabled locking out heat outputs.
Fan Control Override
Fan control override does not affect fan operation on series fan-powered units.
Control Offset
Control offset may be enabled which adjusts the edited cooling and heating set points.
Recalibrate (Reset)
The recalibrate function can be enabled.
Zone Sensor Functions
The zone sensor utilizes a thermistor element to measure zone temperature. The zone sensor has the following options:
Zone Temperature
Each zone sensor module includes a zone temperature sensor.
Set Point
A UCM will only use the zone sensor thumbwheel set point
(during occupied time) if “Zone sensor thumbwheel functions” is edited to ENABLE on the UCM setup screen.
ON Timed Override (TOV) and CANCEL Timed
Override (TOV)
The ON (TOV) and CANCEL (TOV) commands can be issued by pressing the ON or CANCEL buttons on any of the UCM zone sensor modules.
• When an ON button on a zone sensor is pressed
(shorting the zone temperature sensor circuit), the
UCM will set aTOV signal, clear theTOV cancel signal if it is set, and start the two hour timed override timer.
The TOV signal will be maintained for two minutes.
• When a CANCEL button on a zone sensor module is pressed for at least two seconds, the UCM must set a
TOV cancel signal, clear the TOV signal if it is set, and set the timed override timer to zero.
• Pressing any zone sensor module’s ON or CANCEL button will not affect the zone temperature reported from the UCM.
Note: TOV push buttons should be pressed for at least 2 seconds and not more than 15 seconds.
Drive to Max and Go Unoccupied
When a zone sensor thumbwheel is turned to its high-end limit, indicated by a “*” on the thumbwheel, and the ON button is pressed, the UCM will initiate a “Drive to Max”
VAV-SVX01D-EN
command. When a zone sensor thumbwheel is turned to its low limit, indicated by a “**” on the thumbwheel, and the ON button is pressed, the UCM will initiate a “Go
UNOCCUPIED” command. The UCM will maintain the command until the zone sensor set point is adjusted to within the range of 50° to 85°. Any zone sensor module that has a thumbwheel and ON (TOV) button can initiate these commands.
Notes:
• The UCM will not send these commands if “Zone sensor thumbwheel functions” is edited to DISABLE on the UCM setup screen.
• When an ICS is connected to the UCM, the UCM will pass the commands to the ICS without taking any control action of its own. Since this is true, it may take a minute or so after the command is initiated before the
UCM actually goes unoccupied or is driven to maximum.
• The UCM will not generate aTOV signal when a Drive
Max or Unoccupied command is initiated.
• Pressing the ON button will not affect the zone temperature reported from the UCM.
• The UCM will remain in the Drive Max or Unoccupied status over power failures IF “*” or “**” (respectively) have been initiated prior to the power failure.
Note: TOV push buttons should be pressed for at least 2 seconds and not more than 15 seconds.
Flow Sensor
The flow control is pressure independent utilizing the
VariTrane flow-sensing ring.The flow ring provides one of the most accurate differential pressure flow measurements in the industry by averaging pressure differentials across 16 sensing points. These sensing points, arranged in a ring configuration to compensate for various inlet duct configurations, provide a signal accurate to within +/-5% of cataloged CFM provided there is 1½inlet diameters of straight ductwork upstream of the VAV box. The pressure differential signal from the flow ring is then converted to an electrical signal, which is utilized in the control algorithm of the unit controller. It is recommended that the recalibrate sequence be initiated on a weekly basis. Assuming 1½ inlet diameters of straight duct work and proper system recalibration, total system flow measurement accuracy (flow ring, transducer, and
UCM controller) during the occupied mode should be +/-
5% of cataloged airflow over the typical operating range of
20% to 100% of unit cataloged airflow.
Failure Modes
Each UCM has diagnostic capabilities, which allow it to sense various failure conditions.This diagnostic capability aids in maintenance and trouble shooting of the system.
Along with reporting these failure conditions, the UCM will follow a pre-programmed operating sequence designed
VAV-SVX01D-EN
Sequence of Operations
to maintain zone comfort during a failure. The failure conditions and backup operating sequences are explained below.
Temperature Sensor Failure
Failure of a zone temperature sensor (open or below low limit of 0°F (-17.8°C) will cause fan and heat outputs to be disabled and airflow to be controlled to the minimum cooling flow set point. If the measured temperature fails above the high limit (short or above 100°F (37.8°C), the airflow shall be controlled to the maximum flow set point.
Flow Sensor Failure.
If a flow sensor failure is reported
(open, short, fails calibration, or is out of the normal range of 5% to 110% of box cataloged), the UCM will immediately revert to a position-based, pressure dependent control algorithm. This allows full operation of the unit and maintains the ability to control the zone temperature. If a flow sensor has failed, it is periodically checked for proper operation. If found to be operating properly, the UCM will be switched to the standard pressure independent control.
Otherwise, position control is used as long as the flow signal remains out of range.
Local Thermostat Set Point Failure
Failure of a local thermostat set point adjustment potentiometer will cause the UCM to revert to the edited occupied cooling and heating set point.
Communications Failure
A fifteen-minute failure in communications between the
UCM and Tracer Summit will cause the UCM to:
• Operate in the occupied mode (provided that no occupancy sensor is present on input TB4-1).
• Set the IAQ multiplier to 1.0.
• Disable the control offset.
• Use the control action as determined by the auxiliary sensor.The auxiliary temperature is compared to the zone temperature. If the supply air temperature is 10ºF (5.5°C) greater than the zone temperature, then the control action will be heat. If the supply air temperature is less than or equal to the zone temperature, the control action will be cool. If the supply air temperature is between the zone temperature and the zone temperature +10ºF (5.5°C)(zone temperature < supply air temperature < zone temperature
+ 10ºF) (5.5°C), the control action remains the same and the UCM controls to the minimum flow set point. If an auxiliary sensor is not installed and the VAV unit is not underTracer Summit control, the UCM will retain the last control action in effect.
41
Air and Water Balancing
Chapter Overview
This chapter contains information about the following:
• Air Balancing
• Water Balancing
Air Balancing
After the unit has been mounted and all electrical and duct connections have been made, the air distribution system should be balanced. The proper variable air volume balancing procedures depend on the type of VAV system used and the options specified on theVariTrane® unit.This
section will cover the basic balancing procedures and calibrations needed to balance an air distribution system using VariTrane units. This section suggests only one balancing procedure. Since there are many possible air balancing procedures, keep in mind that these procedures are only suggestions.
Note: Before performing these balancing procedures, the calibration command should be initiated at least 15 minutes prior to the balancing procedure.
System Checkout
• Check the VAV system installation for conformity to design.
• Walk the entire system from air handling equipment to the terminal unit to determine variations of installation from the plans.
• Check for inadvertent obstructions in the ductwork
(such as closed fire dampers).
• Insure that any turning vanes, filters, and dampers
(both volume and fire) are installed in the correct position.
• There should be a 1.5 duct diameter long run of straight ducting into the VAV units inlet.
System Setup
• Set the outside air dampers to their minimum position.
• Start the supply and return air fan(s).
• Before balancing the system, ensure that there is enough CFM for all zones.
6. Drive all VAV boxes MAX.
• Starting with each individual branch duct, open all the VAV units in that branch duct to the maximum cooling position.
Note: This can be done using Rover or EveryWare by giving each UCM a "Drive Max " command or by rotating the Zone sensor set point knob to the " * " position, and hold the TOV ON button for two seconds. The damper will remain at its maximum set point until the zone sensor knob is moved back into the normal operating range.
7.
Read airflow at the most remote unit. In most systems, this will be the VAV unit located furthest from the fan.
This will be the unit in the system that will be critical from an air delivery set point. If airflow is not adequate, increase the supply fan CFM to achieve adequate airflow.
• If the CFM is at or above design, the system can now be balanced. If the measured CFM is below design, insure the VariTrane unit is in full cooling position.
• If the air delivery through this VariTrane unit is still below the design requirements, increase the supply fan CFM to achieve adequate airflow.
Note: To increase supply fan CFM check to make sure
VFD/IGV are giving max output. If not at max output; adjust discharge static setpoint until at max output. If already at max output then make the required adjustments to pulley sizes, motor sizes and electrical connections to accommodate fan speed changes. If any adjustment have been made, repeat step 2.
• If after adjusting the fan to its maximum capacity there is still a shortage of airflow, shut off part of the system to provide enough airflow to balance the other part of the system. This can be done using Rover or the
"Override to Unoccupied" command ("**") at the zone sensor.
8. After determining that there is enough CFM for all zones, drive all the VAV boxes to MIN.
Note: If the VAV boxes have already been assigned to groups and these groups are separate thermal zones, then the balancing can be done on a group basis.
VAV Single Duct Unit Air Balancing
Select a group to balance and give the VAV units a recalibrate command and then the group a flow override
Drive MAX command.
Note: If the VAV boxes have not been placed in a group, each individual UCM can be overridden to Drive
MAX in the Override menu in Rover. However, this will be more time consuming.
42 VAV-SVX01D-EN
Figure 31. Measured value field
Air and Water Balancing
If reported flow in Rover is different from the measured
CFM (flow hood measurement) a cooling flow correction
Figure 32. UCM set point menu can be calculated by Rover by entering the measured flow in the measured value field. See above,
VAV-SVX01D-EN 43
Air and Water Balancing
1. Adjust eachVAV box maximum flow set point required for its zone using the UCM set points menu. See
.
Note: This could already be done in the factory in its commissioning process.
2. After balancing a group/box, return that group/box flow override to AUTO.
3. Continue to the next group/box repeating VAV unit air balancing procedures until each unit is delivering the correct CFM.
4. Upon completion of the VAV air balancing, remove all overrides.
5. Initiate a recalibrate command.
Water Balancing
Figure 33. Rover configuration UCM setup menu
Each VAV UCM can have its hot water valve overridden to drive fully OPEN (2-position and proportional).This can be done in the Rover Configuration UCM setup menu and can be used to assist in water balancing.
1. Access VAV UCM with Rover service software.
2. Select a VAV box to balance, and drive its hot water valve open (max hot water override).
3. Using hydraulic pressure gauges, measure the flow across the high and low ports. Convert this data from a pressure differential to gallons per minute (GPM).
4. Adjust the circuit setter until it is within design specifications.
5. Once achieved, lock the circuit setter in place. Mark the position with a permanent indicator.
6. Remove all gauges and software overrides.
44 VAV-SVX01D-EN
Troubleshooting
WARNING
Live Electrical Components!
During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury.
Chapter Overview
This chapter contains information about the following:
• SP: Diagnosing the Problem
• Diagnostic Log
• Diagnostic Table
• Troubleshooting Procedures
• UCM Failure Procedures
• UCM Communication Loss Procedures
• Wired Zone Sensor Failure Procedures
• Wired Zone Setpoint Failure Procedures
• Wireless Zone Sensor Failure Procedures
• Airflow Failure Procedures
• Auxiliary Temperature Sensor Failure Procedures
• Auxiliary C0
2
Sensor Failure Procedures
• VAV Damper Failure Procedures
• VAV Series Fan Failure Procedures
• VAV Parallel Fan Failure Procedures
• Trane/Honeywell Proportional Valve Check Out
Procedures
Diagnostic Log
The Diagnostic Log reports diagnostic and informational modes/items that are not in the unit’s normal operation.
Figure 34.
Diagnostic log
Some of the items reported (see
to aid in understanding current operation. Reported items are: 1)Timed Override Exists, 2) CancelTimed Override, 3)
AuxiliaryTemperature Sensor Not Present, 4) Unoccupied
Request from Zone Sensor ** Function, 5) Max Flow
Request from Zone Sensor * Function, 6) Calibration in
Progress, and 7) Pressure Dependent Operation.
VAV-SVX01D-EN 45
Troubleshooting
Figure 35.
Items reported
Diagnostic Table
Use the Diagnostic Table (
parameters and Comm. 4 UCM actions to help understand issue.
Table 13.
Failure parameters and Comm. 4 UCM actions
Sensed
Parameter Failure Criteria Action Taken
Zone Temperature
Thumbwheel
Setpoint
Open OR Short (> 25 seconds) AND no active wireless sensors.
If failed open, control valve as if very cold temperature. If failed shorted, control as if very hot temperature.
Open OR short AND no active wireless sensors.
Setpoints from EEPROM used.
Air Flow
For UCM 3.3 and prior,
Flow < 10% when flow control point > 10% OR flow > 110% or 150% for series C.
For UCM 4, Flow < 5% when flow control point
> 10% OR flow > 115% or 155% for series C.
If unsuccessful at recovering flow signal, operate in pressure dependent mode until flow signal regained.
For UCM 4, if flow input is open or shorted the flow failure flag will be set and pressure dependent mode will be used.
UCM 4 will also indicate open/short for the air flow sensor.
UCM 3.3 is the only version that sets the failure flag if the valve is flowing too much air
(>110% or 150% for series C)
Table 13.
Failure parameters and Comm. 4 UCM actions
Sensed
Parameter
Auxiliary
Temperature
CO (a)
Supply Air
Temperature (b)
(VariTrac Bypass
Damper mode)
Supply Air
Pressure
(VariTrac Bypass
Damper mode)
Failure Criteria
Open or short
Short or C0
2
value
< 200 ppm
Open or short
Open or short
Action Taken
Tracer supplied data used for auto changeover logic.
For UCM 4 with the aux input configured for C0
2 mode: if the C0
2
input is shorted or reading below 200 ppm, the
Failed C0
2
sensor failure flag will be set.
For UCM 4 in bypass damper mode: if the
SAT input is shorted or open, the Failed SAT sensor failure flag will be set.
For UCM 4 in bypass damper mode: if the
SAP input is shorted or open, the Failed SAP sensor failure flag will be set.
(a) UCM 4.0 and above will not detect an open. Instead, it will report 258 ppm.
(b) New to UCM 4.2
UCM Failure Procedures
In the event that the UCM is not operating, properly inspect the following:
• Incorrect supply voltage/No voltage
46 VAV-SVX01D-EN
• The green LED indicates power and should be "steady"
ON.
• Measure the power input to TB1-1 (power) and TB1-2
(ground) of the UCM board.The supply voltage should be between 20 and 28 VAC (24 VAC cataloged).
However, voltages at either extreme may result in system instability.
• If no voltage, check up stream of controller to see were voltage has been interrupted. See complete wiring diagrams,
to
Important: For final step check program by downloading good program using Rover, see page 48.
UCM Communication Loss Procedures
In the event that the UCM is not communicating properly inspect the following:
1.
Incorrect supply voltage/No voltage
• The green LED indicates power and should be
"steady" ON.
• Measure the power input toTB1-1 (power) andTB1-
2 (Common/ground) of the UCM board.The supply voltage should be between 20 and 28 VAC (24 VAC cataloged). However, voltages at either extreme may result in system instability.
• If no voltage, check up stream of controller to see were voltage has been interrupted. See complete wiring diagrams,
to
2. Communication link polarity is reversed.
• The yellow LED will be ON indicating a reversed polarity. Switch the communication link connection.
3. UCM is not addressed correctly
• Verify the DIP switch settings on the UCM.
4. Communication link signal has interference
• Communication link should not be routed near or with any voltage source.
5. Incorrect wire used
• Recommended wire is twisted shielded pair. See
Chapter 2 for the wiring specifications for the UCM.
• Be sure all other recommended actions listed above have been taken. Disconnect the communication link from the board and check the board's ability to communicate with the Trane Rover/ EveryWare
Software. If communications do not exist, the board is assumed defective.
6. UCM not correctly addressed or two UCM's addressed the same
• Check the DIP switches on the first VAV box and remove the communication link from the second
VAV box.
VAV-SVX01D-EN
Troubleshooting
7.
Communication wiring error (shorts, open, or reversed polarity)
• Remove the communication link past the first VAV box and verify the polarity. Check resistance across the communication wires for possible shorts or open circuitry.
8. Communication link failure/down
• One UCM failure can bring down all UCM communications.The link is set up as a daisy chain see chapter 2 for details. If whole link is down remove sections of the comm. link from UCMs to isolate portions of the link to find bad UCM(s). Start at the BCU/CCP and remove comm. link from all units except first UCM and see if you can communicate with the one UCM. If the UCM cannot communicate with BCU/CCP, check UCM with
Rover. If you can communicate with the UCM with
Rover then the issue is in the BCU/CCP. If you can communicate with UCM the problem is further down. Go half way down the link from the BCU/CCP and remove the downstream half of the link and see if the communication comes up with the still attached UCM's. If it does not, you know the bad
UCM(s) are in the existing attached link. If communication does come up then the issue is further down the link. Repeat until UCM(s) bringing down comm. link are found.
9. Defective UCM board
Wired Zone Sensor Failure Procedures
In the event that the UCM reports an incorrect zone temperature, properly inspect the following:
1. Actual room temperature is higher or lower than what the UCM reads
• Check the location and installation of the zone sensor. Change the calibration factor in the UCM setup screens.
Note: If Zone sensor is off more than ± 2 degrees continue to number 2.
2. Zone sensor wired incorrectly
• Check wiring for the correct connections. See
Chapter 2 for further details on zone sensor wiring.
3. Defective zone sensor
• Disconnect the zone sensor terminal plug from the
UCM and using an Ohmmeter, measure the resistance across the terminals 1 and 2. Compare the resistance to temperature using Table 3. The resistance should shown value should be within ± 2 degrees near those measured with an accurate temperature measuring device. If not, the zone sensor needs to be replaced.
4. Defective wiring or UCM
• With wires still connected to VAV UCM, disconnect zone sensor wires and check voltage (DC) from
47
Troubleshooting
wires that were connected to terminals 1 and 2 of zone sensor. You should measure 5VDC. If you do not have 5VDC then see if the VAV UCM is outputting 5VDC. This can be done by disconnecting the wires on the VAV UCM on terminalsTB3-1 andTB3-2 and measure the VDC. It should be 5VDC. If you have 5VDC at the UCM the wires going to the zone have an open. If 5VDC is not present check incoming power to the UCM board on
TB1-1 andTB1-2. Should measure 24 VAC ± 10%. If you measure the proper voltage at TB1-1 and TB1-
2 and no voltage at TB3-1and TB3-2 replace UCM.
Note: If no voltage atTB1-1 andTB1-2 see UCM failure procedures
5. Zone sensors shorted out
• Check the resistance across the wires. Disconnect wires from UCM and zone sensor making sure the ends are not touching each other and measure resistance. It should be infinity or no conductivity. If lower resistance is shown wires are shorted together and needs to be replaced.
6. More than one UCM connected to a single zone sensor
• Cut jumper wires (W1 and W2) on all slave units. If jumper is not cut it will give erroneous temperature value.
65
66
67
68
69
60
61
62
63
64
70
71
72
73
74
55
56
57
58
59
75
76
77
78
79
Table 14.
Zone sensor temperature resistance
Temp ( o F)
Thermostat
Thumbwheel
Resistance
(Ohms)
792
772
753
733
714
597
578
558
539
519
694
675
656
636
617
500
481
461
442
422
403
383
364
344
325
Sensor Resistance
(k Ohms)
17.0
16.5
16.1
15.7
15.4
15.0
14.6
14.3
14.0
13.6
13.3
13.0
12.6
12.3
12.1
11.8
11.5
11.2
11.0
10.7
10.4
10.2
10.0
9.7
9.5
48
Table 14.
Zone sensor temperature resistance
Temp (
80
81
82
83
84
85 o F)
Thermostat
Thumbwheel
Resistance
(Ohms)
306
286
267
247
228
208
Sensor Resistance
(k Ohms)
9.3
9.0
8.8
8.6
8.4
8.2
Note:
Thumbwheel resistance checks are made at terminal 2 and 3 on the zone sensor. Temperature sensor resistance is measured at terminal
1 and 2 of the zone sensor.
Wired Zone Setpoint Failure Procedures
In the event that the UCM reports an incorrect zone setpoint, properly inspect the following:
1.
Zone sensor setpoint wired incorrectly
• Check wiring for the correct connections. See Chapter
2 for further details on zone sensor wiring.
2. Defective zone sensor setpoint dial
• Disconnect the zone sensor terminal connections from the UCM and using an Ohmmeter, measure the resistance across the terminals 2 (common) and 3
(setpoint) of the zone sensor. Compare the resistance to specified set point on sensor using
.
The resistance shown should correlate within ± 2 degrees of setpoint shown on
If not, the zone sensor needs to be replaced.
3. Defective wiring or UCM
• With wires still connected to VAV UCM, disconnect zone sensor setpoint wires and check voltage (DC) from wires that were connected to terminals 2 and
3 of zone sensor. These should measure 5VDC. If meter does not read 5VDC then see if the VAV UCM is outputting 5VDC. This can be done by disconnecting the wires on the VAV UCM on terminalsTB3-2 andTB3-3 and measure the VDC. It should be 5VDC. If 5VDC is shown on terminalsTB3-
2 andTB3-3 at the UCM the wires going to the zone have an open. If 5VDC is not present check incoming power to the UCM board on TB1-1 and TB1-2. This should measure 24 VAC ± 10%. If you measure the proper voltage atTB1-1 andTB1-2 and no voltage at
TB3-2 and TB3-3 replace UCM.
Note: If no voltage at TB1-1 and TB1-2 see UCM see
UCM failure procedures.
4. Zone sensor setpoint is shorted out
• Check the resistance across the wires. Disconnect wires from UCM and zone sensor making sure the ends are not touching each other and measure resistance. It should be infinity or no conductivity. If lower resistance is shown wires are shorted together and needs to be replaced.
5. More than one UCM connected to a single zone sensor
VAV-SVX01D-EN
Troubleshooting
• Cut jumper wires (W1 and W2) on all slave units. If jumper is not cut it will give erroneous temperature setpoint value.
Wireless Zone Sensor Failure Procedures
In the event that the UCM reports an incorrect zone
Temperature/sepoint, properly inspect the following:
Note: No special tools or software are necessary to service and test the wireless zone sensor system.
The system can be testing by using the following:
1) LEDs 1, 2, 3, and 5 on the sensor and on the receiver; 2) The Test button (S5) on the sensor; 3)
The address test mode on the receiver; and 4) A common volt-ohm meter.
Figure 36. Wireless sensor set components with base plates removed
LED 1
LED 2
LED 3
LED 5
LED 1
LED 2
LED 3
LED 5
Diagnostics
Note: Reading diagnostics can show if the sensor has an issue or it has not been setup properly. Use this information as a starting point
• LED1, LED2, and LED3 will respond to diagnostics by exhibiting specific blinking patterns.They will occur on the sensor as a result of pressing the Test button (S5)
(
). They will occur on the receiver independently of any user action (
).
Table 15.
Diagnostics: LED1, LED2, LED3 on the sensor
User Action LED Display (a) Indicates…
Press Test
Button (SS)
Press Test
Button (SS)
Press Test
Button (SS)
Press Test
Button (SS)
LED1:Off
LED2:Off
LED3: 1-blink pattern repeated 3 times
Disassociated:
* Sensor is not associated with a receiver
LED1:Off
LED2:Off
LED3: 2-blink pattern repeated 3 times
Address set to 000:
* Address not set to between
001-999
LED1:Off
LED2:Off
LED3: 3-blink pattern repeated 3 times
Not Configured:
* Sensor configuration properties not properly set
(defective sensor)
LED1:Off
LED2:Off
LED3: 4-blink pattern repeated 3 times
Input Voltage Too High:
* No RF transmission is permitted with an input battery voltage greater than
3/9 V
(a) Blink pattern is On for ¼ s, Off for ¼ s, with 2 s Off between repetitions.
Table 16.
Diagnostics: LED1, LED2, LED3 on the receiver
User
Action
None
None
LED Display (a)
LED1:Off
LED2:Off
LED3:1-blink pattern repeated continuously
LED1:Off
LED2:Off
LED3:2-blink pattern repeated continuously
Indicates…
Disassociated
* Receiver is not associated, waiting for a sensor.
* Receiver lost communication with sensor.
* Receiver has no devices on its wireless personal area network.
* Association with a device has been manually removed.
Address set to 000
* Address not set to between
001-999
None
(a)
LED1:Off
LED2:Off
LED3:3-blink pattern repeated continuously
Not Configured
* Receiver configuration properties not properly set
(defective receiver)
1 Blink pattern is On for ¼ s, Off for ¼ s, with 2 s Off between repetitions.
1.
If the wireless zone sensor system failure
• Observe LED5 on the receiver. LED5 will be On solid green whenever the receiver is powered.
• Make sure the receiver is properly grounded. Both the black wire (GND SIGNAL) and the yellow wire
(GND-POWER) must be grounded.
VAV-SVX01D-EN 49
Troubleshooting
• Press the Test button (S5) on the sensor. LED5 should turn On solid green, indicating proper battery strength. LED1, LED2, and LED3 will indicate signal strength (See table 2).
Table 18.
Signal quality: LED1, LED2, LED3 on the sensor
User Action
None
Press Test
Button (SS)
Press Test
Button (SS)
Press Test
Button (SS)
Press Test
Button (SS)
LED Display Indicates…
LED1:Off
LED2:Off
LED3:Off
Normal state
* No Test button press
LED1:Off
LED2:Off
LED3:Off
Associated; no communication with receiver
* Associated, but no signal from the receiver after pressing Test button
LED1:On
LED2:On
LED3:On
Displays for 5 seconds, then constantly off
Excellence signal quality
* Adequate signal margin for reliable communication.
LED1:Off
LED2:On
LED3:On
Displays for 5 seconds, then constantly off
Marginal signal quality
* Reduced battery life likely.
* Consider moving the sensor or receiver to a better location.
LED1:Off
LED2:Off
LED3:On
Displays for 5 seconds, then constantly off
Poor signal quality
* Unreliable communication.
* Strongly recommend moving the sensor or receiver to a better location.
Table 17.
Battery status: LED5 on the sensor
User Action LED Display
Solid green for 5 seconds
Indicates…
Battery condition is adequate for proper operation.
Press Test
Button (SS)
Solid red for 5 seconds
No light
Battery condition is low.
Batteries should be replaced.
Batteries are totally dead or not installed properly, or sensor is defective.
None
Blinking red: 1-blink pattern 1 repeated 5 times. Cycle repeats every 15 minutes.
Battery condition is low.
Approximately 14 days of operation remain before the battery is too weak to power the sensor.
Note:
1 Blink pattern is On for ¼ s, Off for 3/4 s, with 2 s Off between repetitions.
Figure 37.
50
Note: When checking signal strength, both LED1 and
LED3 on the receiver and sensor should illuminate in unison if the sensor and receiver are associated.
Use this feature to confirm association. If not associated, see setup procedures in Wireless chapter. If unit still does not work proceed in checking Receiver and sensor with testing procedures below.
2. Procedure for Testing the Receiver
• Make sure the receiver is powered.
• Set the receiver address to 000 to force the zone temperature output and zone temperature setpoint output to their test mode values (see
).
Table 19.
Output failure modes of operation
Situation
Receiver address = 000
Zone
Temperature
Output
11.17 kΩ, 72.5 o F
(22.5
o C), indefinitely
Zone Setpoint
Output
451 Ω, 72.5 o F
(22.5 o C), indefinitely
Receiver address = 001 to 999
Receiver has powered up, but has not received a communication from sensor.
Receiver address = 001 to 999
Receiver does not receive a communication within 35 minutes from the sensor it is associated with
Receiver has no power
Thermistor in sensor has failed to either open or close
Setpoint potentiometer has failed to either open or close
11.17 kΩ, 72.5 o
(22.5 o C)
F 451 Ω, 72.5 o
(22.5 o C)
F
Open
Open
Open
Normal value
Open
Open
Normal value
Open
3. Measure the receiver output resistance by following the procedures
• Make sure the black wire (GNS-SIGNAL) and the yellow wire (GND-POWER) are grounded (see above for wiring diagrams).
• Make sure the receiver is powered up.
• Disconnect the SETPOINT wire (red) and the ZONE wire (white) from the host unit controller.
• Measure resistance between the grounded GND-
SIGNAL wire and either the SETPOINT or ZONE wire. Compare resistance measurements to those presented in
Table 20.
Receiver resistance table
Zone or Setpoint
Temperature
55 o F (12.8 o C)
60 o F (15.6 o C)
65 o F (18.3 o C)
70 o F (21.1 o C)
Nominal Zone
Temperature
Output Resistance
17.47 k Ω
15.3 k Ω
13.49 k Ω
11.9 k Ω
Nominal Space
Temperature
Setpoint Output
Resistance
812 Ω
695 Ω
597 Ω
500 Ω
VAV-SVX01D-EN
Troubleshooting
Table 20.
Receiver resistance table (continued)
Zone or Setpoint
Temperature
75 o F (23.9 o C)
80 o F (26.7 o C)
85 o F (29.4 o C)
Nominal Zone
Temperature
Output Resistance
10.5 k Ω
9.3 k Ω
8.25 k Ω
Nominal Space
Temperature
Setpoint Output
Resistance
403 Ω
305 Ω
208 Ω
• When the test is complete, reset the receiver address to its previous setting.
• Press theTest button (S5) on the sensor to force reassociation.
Confirm association and communication by noting LED1,
LED2, and LED3 as described in "Signal Quality Test"
• Pressing theTest button (S5) on the sensor initiates a signal quality test. LED1, LED2, and LED3 respond by indicating excellent, marginal, or poor signal quality. The LEDs can be observed on both the sensor (
) and the receiver ( Table 20, p. 50 ).
Table 21.
Signal quality: LED1, LED2, LED3 on the sensor
User
Action
None
LED Display
LED1:Off
LED2:Off
LED3:Off
LED1:Off
LED2:Off
LED3:Off
LED1:On
LED2:On
LED3:On
Displays for 5 seconds, then constantly off
Press Test
Button
(SS)
LED1:Off
LED2:On
LED3:On
Displays for 5 seconds, then constantly off
LED1:Off
LED2:Off
LED3:On
Displays for 5 seconds, then constantly off
Indicates…
Normal state
* No Test button press
Associated; no communication with receiver
* Associated, but no signal from the receiver after pressing Test button
Excellence signal quality
* Adequate signal margin for reliable communication.
Marginal signal quality
* Reduced battery life is likely.
* Consider moving the sensor or receiver to a better location.
Poor signal quality
* Unreliable communication.
* Strongly recommend moving the sensor or receiver to a better location.
measure the proper voltage atTB1-1 andTB1-2 and no voltage at TB3-1and TB3-2 replace UCM.
Note: If no voltage at TB1-1 and TB1-2 see UCM see UCM failure procedures
• Disconnect the receiver sepoint wires on the VAV
UCM on terminals TB3-2 and TB3-3 and measure the VDC. It should be 5VDC. If 5VDC is not present check incoming power to the UCM board onTB1-1 and TB1-2. Should measure 24 VAC ± 10%. If you measure the proper voltage atTB1-1 andTB1-2 and no voltage at TB3-2and TB3-3 replace UCM.
Note: If no voltage at TB1-1 and TB1-2 see UCM see UCM failure procedures
Airflow Failure Procedures
In the event that the air valve is reading position instead of flow or in the event that the measured flow reads incorrectly, i.e. different from the balance report, properly inspect the following:
• Recalibrate VAV unit by cycling power to unit.This can also be accomplished with Rover, Summit or CCP software.
Note: Cycling power to the VAV board will automatically cause the unit to calibrate, however, following the procedure outlined below will provide a more accurate calibration.
It is only necessary to perform this procedure in instances where you are experiencing incorrect flow readings or if the unit reverts to pressure dependent mode despite being above 5% and below 110% of cataloged flow and performing a
"normal calibration") does not correct the problem.
1.
Steps for Calibration
• Log on to the UCM with Rover software.
• Turn the central air handler "off." If this is not possible,Trane recommends pulling the transducer tubes off during the calibration process to simulate this.
• Select the "calibrate unit" option button
Figure 38.
Rover software
• If sensor and receiver still do not operate properly, replace bad components. If unit passes tests, check
UCM operation.
4. Defective VAV UCM
• Disconnect the receiver sensor wires on the VAV
UCM on terminals TB3-1 and TB3-2 and measure the VDC. It should be 5VDC. If 5VDC is not present check incoming power to the UCM board onTB1-1 and TB1-2. Should measure 24 VAC ± 10%. If you
VAV-SVX01D-EN 51
Troubleshooting
• Rover software will indicate that calibration is taking place in diagnostic log
• When calibration is complete, the box will release to auto. Drive the box open to make sure that the box is not below 5% of its cataloged CFM. The controller is accurate in reading flow from 5% to
110% of cataloged CFM.
• Release the box to auto and perform any necessary balancing work. See
“Air and Water Balancing,” p. 42
for details.
Figure 39.
Sensor signal vs. airflow delivery
5
• Check to see if flow has been established, If flow not established or inaccurate proceed to Step
2.
2. The tubing or flow ring is off, reversed, plugged, or has a leak.
• Check with a magnehelic gauge and compare with the delta pressure (DP) chart located on the VAV box.
1
4 " 5 " 6 " 8 " 1 0 " 1 2 " 1 4 "1 6 "
0.1
0.01
10 100
C fm
• Check the tubing for reversal and/or leaks.
• Check the flow ring for plugged holes. Blow out with compressed air if necessary.
3. Wrong unit size downloaded into the UCM setup menu
• Verify that the actual unit size matches the unit's nameplate.
4. Poor inlet configuration
• Trane recommends 1½-duct diameters of straight duct before the inlet of the box (a 12-inch box should have 18” of straight run duct before the inlet).
5. To determine whether or not the transducer has failed, perform the following steps:
• Check the 24 volts AC supply atTB1-1 andTB1-2 on the UCM board.Voltage should be between 20 volts
AC and 28 volts AC. If voltage not available see UCM failure procedures.
• Read the input voltage to the transducer from the
UCM controller between the green and red wires on
J3 of the UCM board. The voltage should be
52
1,000 10,000 between 4.50 volts DC and 5.50 volts DC (5 volts DC cataloged). If voltage not available replace UCM.
• Remove the high and low tubes from the transducer
(to simulate no flow). Read the transducer output voltage on J3 of the UCM board between the green and the black wires with a voltmeter. The voltage should be between 0.20 volts DC and 0.30 volts DC
(0.25 volts DC is the null voltage output of the transducer indicating zero flow). If voltage not available replace transducer
Note: The formula for the Transducer output voltage is 0.25 + 0.75 * <delta P>, where delta P is the pressure in inches of water column. Delta P can range from 0 to 5 inches of W.C.
• With flow across the flow ring measure the differential pressure with a magnahelic and use
Transducer output voltage formula to check accuracy of reported value. Read the transducer output voltage between the green and the black wires. The measured value should correspond to the value given in the transducer output formula. If transducer is off by ± 5%, replace transducer.
VAV-SVX01D-EN
Auxiliary Temperature Sensor Failure
Procedures
In the event that the UCM reports an incorrect or failed
Auxiliary temperature, properly inspect the following:
1.
Make sure VAV UCM has been configured for auxiliary input
Figure 40.
UCM setup screen
Troubleshooting
Should measure 24 VAC ± 10%. If proper voltage measured on TB1-1 and TB1-2 and no voltage at
TB3-1 and TB3-2 replace UCM.
Note: If no voltage at TB3-5 and TB3-6 see UCM see
UCM failure procedures.
6. More than one UCM connected to a single zone sensor
• Cut jumper wires (W4) on all slave units. If jumper is not cut it will give erroneous temperature value.
Auxiliary C0
2
Sensor Failure Procedures
In the event that the UCM reports an incorrect or failed
Auxiliary C0
2 sensor input temperature, properly inspect the following:
1.
Check configuration of the VAV unit
• Auxiliary sensor needs to be configured as C0
2
2. Check jumper position on C0
2 sensor
Figure 41.
Jumper position
2. Actual auxiliary temperature is higher or lower than what the UCM reads
• Check the location and installation of the Auxiliary zone sensor. Change the calibration factor in the
UCM setup screens.
Note: If Auxiliary sensor is off more than ± 2 degrees continue to number 3.
3. Auxiliary sensor wired incorrectly
• Check wiring for the correct connections. See
4.2 Installation and Wiring,” p. 11
for further details on Auxiliary sensor wiring.
4. Defective Auxiliary sensor
• Disconnect the zone sensor terminal plug from the
UCM and using an Ohmmeter, measure the resistance across the auxiliary sensor wires.
Compare the resistance to temperature using
Table 3, p. 10 . The resistance should shown value
should be within ± 2 degrees near those measured with an accurate temperature measuring device. If not, the Auxiliary sensor needs to be replaced.
5. Defective wiring or UCM
• See if the VAV UCM is outputting 5VDC.This can be done by disconnecting the wires on the VAV UCM on terminals TB3-5 and TB3-6 and measure the
VDC. It should be 5VDC. If the meter does not read
5VDC at the UCM the wires going to the zone have an open. If 5VDC is not present check incoming power to the UCM board on TB1-1 and TB1-2.
VAV-SVX01D-EN
• Needs to be set up as 0-10VDC
• Check voltage between J3-6 and J3-5 with the sensor connected
• Should be between 1-10VDC. If it is not check incoming power
• Check voltage input to C0
2
Sensor with voltmeter
• Voltage needs to be between 20 to 26 VAC; nominal
24 VAC
3. If proper voltage is measured at incoming power and you have no VDC output at J3-6 and J3-5, replace sensor. If no voltage, check up stream of controller to see were voltage has been interrupted. See
to
for correct unit diagrams.
VAV Damper Failure Procedures
In the event that the air valve is not modulating, properly inspect the following:
1. Tracer Summit or Rover has enabled an override function in VAV UCM
• The overrides are Open, Closed, Min, or Max.
Disable all overrides.
Note: See UCM programming and operation chapter to be able to release override with Rover
53
Troubleshooting
• UCM is going through a recalibrate (reset) command. This is shown in the diagnostic log in
Rover
• Wait for calibration to finish.
2. Zone temperature is greater than the heat set point or less than the cool set point
• Change the heat and/or cool set points.
3. Actuator not driving full drive time
• Drive time in advanced configuration not set at 90 seconds on current VariTrane units or 60 seconds for varitrac units
• Adjust to correct damper travel time using Rover software. See Operation and Programming chapter.
• Damper actuator loose on shaft
• Tighten damper actuator set screw to damper shaft
• Measure the power input toTB1-1 (power) andTB1-
2 (ground) of the UCM board. The supply voltage should be between 20 and 28 VAC (24 VAC cataloged). However, voltages at either extreme may result in system instability and cause damper to not be driven its full range.
• If no voltage, check up stream of controller to see were voltage has been interrupted. See
to
for correct unit diagrams.
4. Actuator motor has failed
• Check voltage at J1-6 toTB1-2, should have 24 VAC.
If 24VAC is not present check incoming power to the
UCM board onTB1-1 andTB1-2. Should measure 24
VAC ± 10%. If proper voltage is measured at TB1-1 andTB1-2 and no voltage at J1-6 andTB1-2, replace
UCM.
• Check motor by applying 24 VAC directly to common (blue) and jumper open (black) wire to a ground to drive damper open.
• Damper should drive open
• Check motor by applying 24 VAC directly to common (blue) and jumper closed (red) wire to a ground to drive damper closed
• Damper should drive closed
• If damper actuator does not open or close replace actuator
VAV Series Fan Failure Procedures
In the event that the fan output is not energizing, properly inspect the following:
1. Verify the output configuration in the UCM setup menu.
• Unit needs to be configured as Series fan
2. Outputs on the UCM are configured as normally closed
• Verify the output configuration in the UCM setup menu.
Note: Series fan powered units in the occupied mode has the fan continuously energized. See operation Chapter for details
3. Tracer Summit has the fan output disabled
• Check group, global, and/or Tracer overrides to make sure they are not inhibiting fan operation.
4. A flow override exists locking out the fan output
• Check to make sureTracer or Rover has released fan disable override.
5. If VAV UCM is calling in the status menu for the Fan to be on and it is not then check UCMTriac output wiring; and Relay output.
• Override damper open
• See if fan cycles on
• Check J8 toTB1-2. Should have 24 VAC; if it does not, measure the power input to TB1-1 (power) and TB1-2 (ground) of the UCM board. The supply voltage should be between 20 and 28
VAC (24 VAC cataloged). However, voltages at either extreme may result in system instability.
• Triac can be checked with purchasing a 24 VAC
LED and see if it lights up on call for fan UCM if
LED does not light up replace UCM
• Remove fan wires from UCM and apply 24 VAC directly to fan relay wires.
• Fan relay should energize. If it does not check wiring. If wiring is OK replace fan relay.
NOTICE:
Equipment Damage!
UCM Outputs are switched to ground. Do not jumper
24 VAC to J9, J10, or J11 because damage will occur.
6. After all checks have been completed, check motor fan winding integrity and bearing failure.
VAV Parallel Fan Failure Procedures
In the event that the fan output is not energizing, properly inspect the following:
1. Verify the output configuration in the UCM setup menu.
• Unit needs to be configured as parallel fan
2. Outputs on the UCM are configured as normally closed
• Verify the output configuration in the UCM setup menu.
Note: Parallel fan can be enabled by either a differential temperature above the heating setpoint or CFM flow. See
“UCM Programming and Operation,” p. 24
for details.
54 VAV-SVX01D-EN
Figure 42.
3. Tracer Summit has the fan output disabled
• Check group, global, and/or Tracer overrides to make sure they are not inhibiting fan operation.
4. A flow override exists locking out the fan output
• Check to make sureTracer or Rover has released fan disable override.
Note: If fan cycling is based on temperature go to step
5 and if it is based on flow go to step 6.
5. If fan control is based on temperature and Zone temperature is at or above the heating set point plus heating offset on units configured as temperature control. A factory set differential of 0.5°F (0.3°C) exists to prevent short cycling.
• Increase the UCM heating set point causing fan to be cycled on.
• Lower the Heating setpoint by .6° and the fan should cycle off.
6. If the fan control is based on flow, the unit fan will be energized whenever primary airflow is below this set point. For this parallel fan configuration, the fan control point, if specified in a percentage of unit airflow, must be set between 15% and 30% of the units cataloged airflow to assure proper operation. A differential of 5% exists to avoid excessive fan cycling.
• Override damper closed until CFM is below enabled flow setpoint
• See if fan cycles on
• Override damper open until CFM is above enabled flow setpoint fan should cycle off
7.
If VAV UCM is calling in the status menu for the Fan to be on and it is not then check UCMTriac output, wiring, and Relay output.
• Check J8 toTB1-2. Should have 24VAC; if it does not if not measure the power input toTB1-1 (power) and
VAV-SVX01D-EN
Troubleshooting
TB1-2 (ground) of the UCM board. The supply voltage should be between 20 and 28 VAC (24 VAC cataloged). However, voltages at either extreme may result in system instability.
• Triac can be checked with purchasing a 24 VAC LED and see if it lights up on call for fan UCM if LED does not light up replace UCM.
• Remove fan wires from UCM and apply 24 VAC directly.
• Fan relay should energize. If it does not check wiring. If wiring is OK replace fan relay
Note: UCM Outputs are switched to ground. Do not jumper 24 VAC to J9, J10, or J11 because damage will occur.
8. After all checks have been completed, check motor fan winding integrity and bearing failure.
PSC Variable Speed Motor Check Out
If PSCVariable speed motor control not changing speed of the motor inspect the following:
• Wires connected improperly
• Check wiring to make sure speed control is wired correctly. See
and
for wiring schematic.
• Check voltage selection switch on side of variable speed motor control.
• Should be set for motor voltage.
• To check speed control
• Turn voltage selection switch fully CCW
• Turn Motor speed control potentiometer fully
CCW
• Motor should remain off
• Turn voltage selection switch fully CW
• Motor speed control potentiometer still fully
CCW
• Measure motor voltage. Should be no more than
8VAC lower than line voltage
• With voltage selection switch still fully CW
• Turn Motor speed control potentiometer slowly fully CW (HI)
• Should go to full speed smoothly
If it fails any of these tests replace PSC motor speed controller.
Testing ECM-DCU and ECM-VCU Fan Control
If ECM is not controlling Fan Motor properly inspect the following:
Note: The ECM controller has 4 wire pin connector that has an enable binary output and a Variable speed analog output.
1.
Incorrect supply voltage/No voltage
55
Troubleshooting
• Measure the power input to 24 VAC terminal and
Common/ground terminal of the ECM board. The supply voltage should be between 19.2 and 28.2
VAC (24 VAC cataloged). However, voltages at either extreme may result in system instability.
• If low or no voltage, check up stream of controller to see how voltage has been interrupted. See complete wiring diagrams (
and
2. Testing Binary Output
• Measure voltage from White to Green wire on connector
• Should be between 9 to 30VDC. If not replace ECM
3. Testing Analog variable speed output
• On ECM-DCU change board selector switches to 0 on each one of the switches to give a 100% output signal. On ECM-VCU adjust potentiometer until
LED's read a 100% output.
• Measure voltage from green to red wires on 4 pin connector and document. See
and
for correct unit wiring diagram.
• Should measure above 9VDC
• Change ECM-DCU board selector switches to 9 on tens digit an 9 on units digit to give a 99% output signal. On ECM-VCU adjust potentiometer until
LED's read a 99% output
• Measure voltage from green to red wires on 4 pin connector and document. See
and
for correct unit wiring diagram.
• Should measure less than previous reading
• Continue process until all selector switch positions have been checked to find any dead spots in selector switches
• If unit ECM board fails any of these tests replace board. If ECM is found to be good but motor still does note operate contact VAV technical support.
Figure 43.
ECM
VAV Electric Heat Stage(s) Failure
Procedures
In the event that the heat outputs are not energizing, properly inspect the following:
1.
Zone temperature is at or above the heating set point
• Increase the UCM heating set point.
56
2. Verify the output configuration in the UCM setup menu.
• Unit needs to be configured as 3 stage Electric heat
3. Tracer Summit has the electric heat output disabled
• Check group, global, and/or Tracer overrides to make sure they are not inhibiting heat operation.
4. Minimum heating CFM is not being met, airflow is too low
• Increase the airflow or lower the minimum heating flow.
5. Heat relays have failed
• If VAV UCM is calling in the status menu for the electric heat to be on and it is not then check UCM
Triac output; wiring; and Relay output.
• Check J8 toTB1-2. Should have 24VAC; if it does not measure the power input toTB1-1 (power) andTB1-
2 (ground) of the UCM board. The supply voltage should be between 20 and 28 VAC (24 VAC cataloged). However, voltages at either extreme may result in system instability.
• Heat Triac(s) can be checked with purchasing a 24
VAC LED and see if it lights up on call for Heat stage
UCM. If LED does not light up replace UCM.
NOTICE:
Equipment Damage!
UCM Outputs are switched to ground. Do not jumper
24 VAC to J9, J10, or J11 because damage will occur.
• Move electric heat relay wires from UCM and apply
24 VAC directly.
• Electric heat stage should energize. If it does not; check wiring, safeties and electric heat contactor.
Replace components as necessary.
VAV Proportional Hot water failure
Check binary outputs
In the event that the heat outputs are not energizing, properly inspect the following:
1.
Zone temperature is at or above the heating set point
• Increase the UCM heating set point.
2. Verify the output configuration in the UCM setup menu
• Unit needs to be configured as proportional hot water
3. Tracer Summit has the heat output disabled
• Check group, global, and/or Tracer overrides to make sure they are not inhibiting heat operation.
4. Heat relays have failed
• If VAV UCM is calling in the status menu for the valve to be open and it is not then check UCMTriac output; wiring; and Relay output.
VAV-SVX01D-EN
• Check J8 toTB1-2. Should have 24VAC; if it does not if not measure the power input toTB1-1 (power) and
TB1-2 (ground) of the UCM board. The supply voltage should be between 20 and 28 VAC (24 VAC cataloged). However, voltages at either extreme may result in system instability.
• Heat Triac(s) can be checked with purchasing a 24
VAC LED and see if it lights up on call for Heat output to be open or closed by UCM. If LED does not light up replace UCM.
NOTICE:
Equipment Damage!
UCM Outputs are switched to ground. Do not jumper
24 VAC to J9, J10, or J11 because damage will occur.
Check controller proportional hot water logic
• Reconfigure controller setup from a VariTrane F unit into a VariTrac unit with proportional hot water heat.
• Recalibrate unit.
• Drive time configured in rover should be 120 seconds.
• Raise the temp 4° above the space temp (4 degrees offset must be maintained during test) it should take
3.2 min. from close to open. The temperature from space to setpoint must remain 4 degrees over the length of the test. If unit does not pass test check actuator and valve. After valve and actuator are found to be ok, repeat test and if it is still failing replace controller.
Note: If the controller is not reconfigured as a varitrac unit and remains configured as a varitrane unit with proportional hot water it would take 1.1 hrs to move from completely closed to completely open.
• Put original configuration back in controller
Trane/Honeywell Proportional valve check out procedures
Two problems can occur with the cartridge/ actuator or both that can result in over conditioning the space.
Cartridge Failure
• If the actuator is driven closed but there is 1/8" or more play in the indicator (move with your finger), or the piston has not returned up past the A port or has
"frozen". In either case, the cartridge is not closed off completely. This will result in over heating (or over cooling) in the space.
Actuator Failure
• If the actuator has stopped moving to the closed position when commanded to, and there is no play in the lever, the actuator has failed.
Troubleshooting
• Remove the actuator and work the cartridge stem manually. If the stem moves freely, then only the actuator has failed. If the stem is sluggish or stuck, the actuator and the cartridge have failed.
Note: Actuator indicator on the side of the actuator should be positioned at the top of the actuator when valve is closed.
VAV Two Position Hot water failure
Check binary outputs
In the event that the heat outputs are not energizing, properly inspect the following:
1.
Zone temperature is at or above the heating set point
• Increase the UCM heating set point
2. Verify the output configuration in the UCM setup menu
• Unit needs to be configured as two position hot water
3. Tracer Summit has the heat output disabled
• Check group, global, and/or Tracer overrides to make sure they are not inhibiting heat operation.
4. Heat relays have failed
• If VAV UCM is calling in the status menu for the valve to be open and it is not then check UCMTriac output, wiring, and Relay output.
• Check J6 to TB1-2. Should have 24 VAC; if it does not, measure the power input toTB1-1 (power) and
TB1-2 (ground) of the UCM board. The supply voltage should be between 20 and 28 VAC (24 VAC cataloged). However, voltages at either extreme may result in system instability.
NOTICE:
Equipment Damage!
UCM Outputs are switched to ground. Do not jumper
24 VAC to J9, J10, or J11 because damage will occur.
• Heat Triac(s) can be checked with purchasing a 24
VAC LED and see if it lights up on call for heat output to be open by UCM. If LED does not light up replace
UCM.
VAV-SVX01D-EN 57
Troubleshooting
Wiring Diagrams
Figure 44.
Wiring diagram for single duct unit that is either cooling only, hot water, or field installed reheat
TO J8
TO J9
TO J10
W (HOT)
BK (CLOSE)
R (OPEN)
PROP.
WATER
VALVE
24VAC
12VA MAX
OPTIONAL FIELD INSTALLED
PROPORTIONAL WATER VALVE
DAMPER
ACTUATOR
WIRING
24VAC 60HZ
NEC CLASS-2
CONTROL CIRCUIT
LOAD= 12VA
(WITHOUT HEAT)
8.
OPTIONAL
FACTORY
INSTALLED
WIRELESS
24VAC
BL
Y
Y
BL
OPTIONAL
FUSE, DISCONNECT
& TRANSFORMER
GND
UCM or EI Board
24V
OPTIONAL POWER
TRANSFORMER
(50VA)
GREEN
GROUND
SCREW
BK
BK
BL
OPTIONAL
DISCONNECT
SWITCH
OPTIONAL
FUSE
Y
ADDRESS
SWITCH
J1 1
ACT
BIP GND 24V
D.D.C.\U.C.M.
CONTROL BOARD
J3
+ + + -
YEL GRN
ZONE GND SET A/CO2 GND
1
7.
R
BK
G
PRESSURE
TRANSDUCER
+
VOUT
-
GND
UCM or EI Board
24V
5.
R (HOT)
O (COMMON)
GR (NC CONTACT)
BK (RETURN)
Y
(TB1-1) 24VAC
(TB4-1) BIP
(TB1-1) 24VAC
(TB1-2) GND
NOT CONNECTED
OPTIONAL FIELD INSTALLED
OCCUPANCY SENSOR
TB1-1
TB1-2
TB2-6
TB2-5
TB3-3
TB3-2
TB3-1
D.D.C.\U.C.M.
CONTROL BOX
SHIELDED TWISTED PAIR
COMMUNICATIONS WIRING
OPTIONAL FACTORY INSTALLED
WIRELESS
6.
TB3-5 TB3-6
TB2-6
TB2-5 TB3-2
TB3-1
TB3-3
24V
CO2
SENSOR GND
OUT
+
0
V
(TB1-1) 24V
(TB3-6) GND
(TB3-5) A/CO2
OPTIONAL FIELD INSTALLED
CO2 SENSOR
NOTE:
1.
6.
OPTIONAL
AUX TEMP SENSOR
2(+) 1(-) 3 2
ZONE SENSOR
W/ COMM. JACK
REMOTE MTD.
3.
4.
1
FACTORY WIRING
FIELD WIRING
OPTIONAL OR ALTERNATE WIRING
OPTIONAL FIELD
INSTALLED ZONE SENSOR
2. 1/4" QUICK CONNECT REQUIRED FOR ALL FIELD CONNECTIONS.
3.
ZONE SENSOR TERMINALS 1 (-) AND 2 (+) REQUIRE SHIELDED TWISTED PAIR
WIRING FOR COMMUNICATIONS JACK EQUIPPED ZONE SENSOR OPTION.
4.
NO ADDITIONAL WIRING REQUIRED FOR NIGHT SETBACK OVERRIDE (ON/CANCEL).
5.
6.
7.
THE OPTIONAL BINARY INPUT CONNECTS BETWEEN TB4-1 (BIP) AND 24VAC (HOT) FROM
TRANSFORMER. THE BINARY INPUT CAN BE RECONFIGURED AS AN OCCUPANCY INPUT VIA THE
COMMUNICATIONS INTERFACE.
AS SHIPPED, THE AUX INPUT IS CONFIGURED AS AN AUX TEMP INPUT. THE AUX INPUT CAN BE
RECONFIGURED AS A CO2 SENSOR INPUT VIA THE COMMUNICATIONS INTERFACE.
S TERMINAL NOT TO BE USED WITH VARITRANE.
TO J10
TO J9
TO J8
2ND STG.
1ST STG.
HOT
HEATER STAGE
CONTACTOR(S)
24VAC, 12VA
MAX/COIL
OPTIONAL FIELD INSTALLED
ELECTRIC HEATER
TO J9
TO J8
ON - OFF
WATER VALVE
24 VAC
12VA MAX
OPTIONAL FIELD INSTALLED
0N-OFF WATER VALVE
8.
9.
IF UNIT MOUNTED TRANFORMER IS NOT PROVIDED, POLARITY FROM UNIT TO UNIT MUST BE
MAINTAINED TO PREVENT PERMANENT DAMAGE TO CONTROL BOARD. IF ONE LEG OF 24VAC
SUPPLY IS GROUNDED, THEN GROUND LEG MUST BE CONNECTED TO TB1-2.
OPTIONAL FUSE, DISCONNECT SWITCH & TRANSFORMER WIRING. WIRINGS GOES THRU TO
NEXT COMPONENT WHEN OPTIONS ARE NOT CHOSEN/
10.
TRANSFORMER WIRE COLORS: 120V - W, 208V - R, 240V - O, 277V - BR, 480V - R/BK
575V -R, 190V - R, 220V - R, 347V - R.
11.
ZONE SENSOR TERMINALS 6 AND 7 REQUIRE SHIELDED TWISTED PAIR
WIRING FOR OPTIONAL USE OF COMMUNICATIONS JACK.
11 10 7 6 3 2 1
DIGITAL DISPLAY ZONE SENSOR
W/ COMM. JACK
REMOTE MTD.
4.
11.
OPTIONAL FIELD INSTALLED
DIGITAL DISPLAY ZONE SENSOR
WARNING
HAZARDOUS VOLTAGE!
DISCONNECT ALL ELECTRIC POWER
INCLUDING REMOTE DISCONNECTS AND
FOLLOW LOCK OUT AND TAG PROCEDURES
BEFORE SERVICING. INSURE THAT ALL
MOTOR CAPACITORS HAVE DISCHARGED
STORED VOLTAGE. UNITS WITH VARIABLE
SPEED DRIVE, REFER TO DRIVE
INSTRUCTIONS FOR CAPACITOR DISCHARGE.
FAILURE TO DO THE ABOVE COULD RESULT
IN DEATH OR SERIOUS INJURY.
AVERTISSEMENT
TENSION DANGEREUSE!
COUPER TOUTES LES TENSIONS ET
OUVRIR LES SECTIONNEURS À DISTANCE,
PUIS SUIVRE LES PROCÉDURES DE
VERROUILLAGE ET DES ÉTIQUETTES AVANT
TOUTE INTERVENTION. VÉRIFIER QUE TOUS
LES CONDENSATEURS DES MOTEURS SONT
DÉCHARGÉS. DANS LE CAS D'UNITÉS
COMPORTANT DES ENTRAÎNEMENTS À
VITESSE VARIABLE, SE REPORTER AUX
INSTRUCTIONS DE L'ENTRAÃŽNEMENT POUR
DÉCHARGER LES CONDENSATEURS.
NE PAS RESPECTER CES MESURES DE
PRÉCAUTION PEUT ENTRAÎNER DES
BLESSURES GRAVES POUVANT ÊTRE
MORTELLES.
ADVERTENCIA iVOLTAJE PELIGROSO!
DESCONECTE TODA LA ENERGà A ELÉCTRICA,
INCLUSO LAS DESCONEXIONES REMOTAS Y
SIGA LOS PROCEDIMIENTOS DE CIERRE Y
ETIQUETADO ANTES DE PROCEDER AL
SERVICIO. ASEGÚRESE DE QUE TODOS
LOS CAPACITORES DEL MOTOR HAYAN
DESCARGADO EL VOLTAJE ALMACENADO.
PARA LAS UNIDADES CON TRANSMISIÓN
DE VELOCIDAD VARIABLE, CONSULTE LAS
INSTRUCCIONES PARA LA DESCARGA
DEL CONDENSADOR.
EL NO REALIZAR LO ANTERIORMENTE
INDICADO, PODRÃ A OCASIONAR LA MUERTE
O SERIAS LESIONES PERSONALES.
58 VAV-SVX01D-EN
Troubleshooting
Figure 45.
Wiring diagram for fan powered unit that is either cooling only, hot water, or field installed reheat
TO J8
TO J9
TO J10
W (HOT)
BK (CLOSE)
R (OPEN)
PROP.
WATER
VALVE
24VAC
12VA MAX
OPTIONAL FIELD INSTALLED
PROPORTIONAL WATER VALVE
DAMPER
ACTUATOR
WIRING
FAN CONTROL
BOX WIRING
OPTIONAL
FACTORY
INSTALLED
WIRELESS
24VAC
BL
Y
Y
BL
GND
UCM or EI Board
24V
TB1-1
TB1-2
TB2-6
TB2-5
TB3-3
TB3-2
TB3-1
R-FAN
24 VAC
BR
Y
BL
ADDRESS
SWITCH
+ + -
J1
+ -
ACT
YEL
1
BIP GND 24V
D.D.C.\U.C.M.
CONTROL BOARD
J3
GRN
ZONE GND SET A/CO2 GND
1
S
7.
R
BK
G
PRESSURE
TRANSDUCER
+
VOUT
-
11 10 7 6 3 2 1
DIGITAL DISPLAY ZONE SENSOR
W/ COMM. JACK
REMOTE MTD.
4.
8.
OPTIONAL FIELD INSTALLED
DIGITAL DISPLAY ZONE SENSOR
TB2-6
TB2-5 TB3-2
TB3-1
TB3-3
D.D.C.\U.C.M.
CONTROL BOX
SHIELDED
TWISTED PAIR
COMMUNICATIONS
WIRING
OPTIONAL FACTORY INSTALLED
WIRELESS
TO J10
TO J9
TO J8
2ND STG.
1ST STG.
HOT
HEATER STAGE
CONTACTOR(S)
24VAC, 12VA
MAX/COIL
OPTIONAL FIELD INSTALLED
ELECTRIC HEATER
5.
R (HOT)
O (COMMON)
GR (NC CONTACT)
BK (RETURN)
Y
(TB1-1) 24VAC
(TB4-1) BIP
(TB1-1) 24VAC
(TB1-2) GND
NOT CONNECTED
OPTIONAL FIELD INSTALLED
OCCUPANCY SENSOR
TB3-5
6.
NOTE:
1.
FACTORY WIRING
FIELD WIRING
OPTIONAL OR ALTERNATE WIRING
2. 1/4" QUICK CONNECT REQUIRED FOR ALL FIELD CONNECTIONS.
TB3-6
OPTIONAL
AUX TEMP SENSOR
6.
24V
CO2
SENSOR GND
OUT
+
0
V
(TB1-1) 24V
(TB3-6) GND
(TB3-5) A/CO2
OPTIONAL FIELD INSTALLED
CO2 SENSOR
4.
5.
3.
ZONE SENSOR TERMINALS 1 (-) AND 2 (+) REQUIRE SHIELDED TWISTED PAIR WIRING FOR COMMUNICATIONS
JACK EQUIPPED ZONE SENSOR OPTION.
NO ADDITIONAL WIRING REQUIRED FOR NIGHT SETBACK OVERRIDE (ON/CANCEL).
6.
7.
THE OPTIONAL BINARY INPUT CONNECTS BETWEEN TB4-1 (BIP) AND 24VAC (HOT) FROM TRANSFORMER.
THE BINARY INPUT CAN BE RECONFIGURED AS AN OCCUPANCY INPUT VIA THE COMMUNICATIONS
INTERFACE.
AS SHIPPED, THE AUX INPUT IS CONFIGURED AS AN AUX TEMP INPUT. THE AUX INPUT CAN BE
RECONFIGURED AS A CO2 SENSOR INPUT VIA THE COMMUNICATIONS INTERFACE.
S TERMINAL NOT TO BE USED WITH VARITRANE.
8.
ZONE SENSOR TERMINALS 6 AND 7 REQUIRE SHIELDED TWISTED PAIR WIRING FOR COMMUNICATIONS
JACK EQUIPPED ZONE SENSOR OPTION.
2(+) 1(-) 3 2
ZONE SENSOR
W/ COMM. JACK
REMOTE MTD.
3.
4.
1
OPTIONAL FIELD
INSTALLED ZONE SENSOR
TO J9
TO J8
ON - OFF
WATER VALVE
24 VAC
12VA MAX
OPTIONAL FIELD INSTALLED
0N-OFF WATER VALVE
WARNING
HAZARDOUS VOLTAGE!
DISCONNECT ALL ELECTRIC POWER
INCLUDING REMOTE DISCONNECTS AND
FOLLOW LOCK OUT AND TAG PROCEDURES
BEFORE SERVICING. INSURE THAT ALL
MOTOR CAPACITORS HAVE DISCHARGED
STORED VOLTAGE. UNITS WITH VARIABLE
SPEED DRIVE, REFER TO DRIVE
INSTRUCTIONS FOR CAPACITOR DISCHARGE.
FAILURE TO DO THE ABOVE COULD RESULT
IN DEATH OR SERIOUS INJURY.
AVERTISSEMENT
TENSION DANGEREUSE!
COUPER TOUTES LES TENSIONS ET
OUVRIR LES SECTIONNEURS À DISTANCE,
PUIS SUIVRE LES PROCÉDURES DE
VERROUILLAGE ET DES ÉTIQUETTES AVANT
TOUTE INTERVENTION. VÉRIFIER QUE TOUS
LES CONDENSATEURS DES MOTEURS SONT
DÉCHARGÉS. DANS LE CAS D'UNITÉS
COMPORTANT DES ENTRAÎNEMENTS À
VITESSE VARIABLE, SE REPORTER AUX
INSTRUCTIONS DE L'ENTRAÃŽNEMENT POUR
DÉCHARGER LES CONDENSATEURS.
NE PAS RESPECTER CES MESURES DE
PRÉCAUTION PEUT ENTRAÎNER DES
BLESSURES GRAVES POUVANT ÊTRE
MORTELLES.
ADVERTENCIA iVOLTAJE PELIGROSO!
DESCONECTE TODA LA ENERGà A ELÉCTRICA,
INCLUSO LAS DESCONEXIONES REMOTAS Y
SIGA LOS PROCEDIMIENTOS DE CIERRE Y
ETIQUETADO ANTES DE PROCEDER AL
SERVICIO. ASEGÚRESE DE QUE TODOS
LOS CAPACITORES DEL MOTOR HAYAN
DESCARGADO EL VOLTAJE ALMACENADO.
PARA LAS UNIDADES CON TRANSMISIÓN
DE VELOCIDAD VARIABLE, CONSULTE LAS
INSTRUCCIONES PARA LA DESCARGA
DEL CONDENSADOR.
EL NO REALIZAR LO ANTERIORMENTE
INDICADO, PODRÃ A OCASIONAR LA MUERTE
O SERIAS LESIONES PERSONALES.
VAV-SVX01D-EN 59
Troubleshooting
Figure 46.
Single duct with single phase voltage electric heat
60 VAV-SVX01D-EN
Figure 47.
Single duct with three phase voltage electric heat
Troubleshooting
VAV-SVX01D-EN 61
Troubleshooting
Figure 48.
SCR/PSC fan powered with single phase voltage electric heat
62 VAV-SVX01D-EN
Figure 49.
SCR/PSC fan powered with three phase voltage electric heat
Troubleshooting
VAV-SVX01D-EN 63
Troubleshooting
Figure 50.
ECM fan powered with single phase voltage electric heat
64 VAV-SVX01D-EN
Figure 51.
ECM fan powered with three phase voltage electric heat
Troubleshooting
VAV-SVX01D-EN 65
Appendix
66
RTD
SAP
SAT
TB
TOV
TR
UCM
UL
VA
VAC
VAV
ZSM
LED
MAX
MIN
NEC
PPM
PROM
PWM
RSSI
CU
DDC
DEG
DP
EEPROM o F
Hz
ICS
I/O
IOP
BIP
BMS
BOP o C
CCP
CFM
CMS
CO
2
COM
CPL
AC
AHU
AIP
AOP
AVG
AWG
BCU
Alternating Current
Air Handling Unit
Analog Input
Analog Output
Average
American Wire Gauge
Building Control Unit
Binary Input
Building Management System
Binary Output
Celsius
Central Control Panel
Cubic Feet per Minute
Cubic Meters per Second
Carbon Dioxide
Communication
Custom Program Language
Command Unit
Direct Digital Control
Degree
Differential Pressure
Electrically Erasable Programmable Read Only Memory
Fahrenheit
Hertz
Integrated Comfort™ System
Input/Output
Installation, Operation, and Programming
Light Emitting Diode
Maximum
Minimum
National Electric Code
Parts Per Million
Programmable Read Only Memory
Pulse Width Modulation
Receiver Signal Strength Indicator
Resistance Temperature Detector
Supply Air Pressure
Supply Air Temperature
Terminal Block
Timed Override
Time since last transmission was received
Unit Control Module
Underwriter's Laboratories
Voltage Ampere
Voltage Alternating Current
Variable Air Volume
Zone Sensor Module
VAV-SVX01D-EN
Trane optimizes the performance of homes and buildings around the world. A business of Ingersoll Rand, the leader in creating and sustaining safe, comfortable and energy efficient environments, Trane offers a broad portfolio of advanced controls and HVAC systems, comprehensive building services, and parts. For more information, visit www.Trane.com.
Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice.
© 2014 Trane All rights reserved
VAV-SVX01D-EN 13 Mar 2014
Supersedes VAV-SVX01C-EN (May 2010)
We are committed to using environmentally conscious print practices that reduce waste.
advertisement
Related manuals
advertisement
Table of contents
- 2 Introduction
- 2 Warnings, Cautions, and Notices
- 2 Important Environmental Concerns
- 2 Important Responsible Refrigerant Practices
- 6 General Information
- 6 Overview of Manual
- 6 Chapter Overview
- 6 Unit Control Module 4.2 (UCM 4.2)
- 6 Specifications
- 6 UCM 4.2 Enhancements
- 7 UCM 4.2 Features
- 8 Shipping
- 8 Storage
- 9 VAV Start Up/Check Out Procedure
- 9 Chapter Overview
- 9 UCM 4.2 Pre-Power Check-Out
- 9 Light Emitting Diode (LED) Operations
- 10 Zone Sensor Check-out
- 11 UCM 4.2 Installation and Wiring
- 11 Chapter Overview
- 11 UCM 4.2 Power Wiring
- 11 Power Requirements
- 11 Zone Sensor Wiring
- 11 Location and Mounting
- 11 Wiring
- 12 Multiple UCM’s Per Zone Sensor
- 12 Multiple UCM’s per Auxiliary Duct Temperature Sensor
- 12 Zone Sensor Hardwired Option
- 12 Zone Sensor Wireless Option
- 12 Communication Wiring
- 12 Communication Link Wiring
- 13 DIP Switch Settings
- 17 Wireless Zone Sensor
- 17 Overview
- 17 Dimensional Diagrams
- 18 Setting the Address, Mounting, Wiring, and Associating the Receiver and Sensor
- 18 Choosing a Location for Mounting the Sensor
- 19 Setting the Rotary Address Switches on the Receiver and the Sensor
- 20 Factory Wiring of the Receiver to the VAV UCM
- 22 Replacing and Securing the Receiver Cover
- 22 Applying Power to the Receiver
- 23 Powering the Sensor and Associating the Sensor to the Receiver
- 23 Testing Signal and Battery Strength
- 23 Disassociation
- 24 UCM Programming and Operation
- 24 Chapter Overview
- 24 Accessing Rover/Comm4
- 24 Rover Overview
- 24 Laptop Requirements and Complete Connection Instructions
- 26 UCM Home Tabs: At a Glance
- 27 Status Tab
- 27 Setpoints Tab
- 28 Wireless Tab
- 28 Advanced Configuration Tab
- 28 UCM Home Tabs: Instructions
- 28 Configuration
- 28 Setpoints Tab
- 30 Setup Tab
- 33 Wireless Tab
- 34 Advanced Configuration Tab
- 35 Entering and Exiting the Service Mode
- 35 Overriding VAVs
- 35 Resetting Diagnostics
- 35 Saving VAV Program
- 36 Downloading Program Files from PC to DDC UCM 4.2
- 38 Sequence of Operations
- 38 Chapter Overview
- 38 Single Duct Units
- 38 Override Conditions (Single Duct)
- 39 Fan-Powered Units
- 39 Parallel Fan-Powered Units
- 39 Occupied Units
- 39 Override Conditions (Parallel Fans)
- 40 Series Fan-Powered Units
- 40 Occupied Units
- 40 Override Conditions (Series Fan)
- 40 Zone Sensor Functions
- 41 Flow Sensor
- 41 Failure Modes
- 42 Air and Water Balancing
- 42 Chapter Overview
- 42 Air Balancing
- 42 System Checkout
- 42 System Setup
- 42 VAV Single Duct Unit Air Balancing
- 44 Water Balancing
- 45 Troubleshooting
- 45 Chapter Overview
- 45 Diagnostic Log
- 46 Diagnostic Table
- 46 UCM Failure Procedures
- 47 UCM Communication Loss Procedures
- 47 Wired Zone Sensor Failure Procedures
- 48 Wired Zone Setpoint Failure Procedures
- 49 Wireless Zone Sensor Failure Procedures
- 51 Airflow Failure Procedures
- 53 Auxiliary Temperature Sensor Failure Procedures
- 53 Auxiliary C02 Sensor Failure Procedures
- 53 VAV Damper Failure Procedures
- 54 VAV Series Fan Failure Procedures
- 54 VAV Parallel Fan Failure Procedures
- 56 VAV Electric Heat Stage(s) Failure Procedures
- 56 VAV Proportional Hot water failure
- 57 Trane/Honeywell Proportional valve check out procedures
- 57 Cartridge Failure
- 57 Actuator Failure
- 57 VAV Two Position Hot water failure
- 58 Wiring Diagrams
- 66 Appendix