Pelvac Manual
ENG
NBE
PELLETS SYSTEM
Version 7
CONTENT LIST:
Dear Customer. Thank you for choosing a NBE product. This product is designed and manufactured to the
highest standards in the EU. In order for you to get the most out of your product, we strongly recommend
that you carefully read this manual prior to installation and operation. In the event that you encounter any
difficulties during installation or operation, we recommend that you first refer to this manual or the
information provided in the support section found at www.nbe.dk.
Note: Help text on all menu items is displayed in the controller and is therefore not
described here in this manual. It is recommended to study the menus prior to initial
start.
Save this manual, so you always have it available when needed.
Page 3:
Page 4:
Page 5:
Page 6-8:
Page 9:
Page 10:
Page 11-12:
Page 13:
Page 14:
Page 15-18:
Page 19:
Page 20:
Page 21:
Page 22:
Page 23:
Page 24:
Page 25:
Page 26:
Page 27-35:
Page 36:
Page 37:
Page 38:
Comments on the Manual
Boiler Specifications
Burner Specifications
Boiler Room Design
Requirements for Chimney Height
Installation of the Boiler
Installation of the Burner
Wood Pellet Hopper
Vacuum Transport
Wiring Diagram
Electrical Connection Scheme
Optional Equipment
Internet Connection
Cloud Service
First Time Start-up
Cleaning the Burner/Boiler
Service and Maintenance
Flue gas condensation
Glossary controller
Warranty
CE Declaration of Conformity
Notes
2
COMMENTS ON THE
MANUAL:
!
Never handle the auger, blower, nor crawl in the hopper when the system is powered. There
will be no warning prior to the activation of these components. The boiler must not be
operated without the shield on the burner
The system is provided with an electrical current of 230V/50Hz. An improper installation or
improper repair can cause life-threatening electrical shock. Electrical connections must be
performed by the person who has the right skills and training. Performance of electrical
installation must be carried out in COMPLIANCE with the relevant rules. Always disconnect
the system from the electrical supply prior to starting maintenance work or servicing. The
system must be connected to a separate electrical circuit, which is equipped with the proper
circuit breaker and earth leakage breaker.
The boiler must be mounted to a functioning chimney. In the event that you smell smoke or
see any other indication of improper draft of the chimney, all operation of your system must
cease immediately and must remain so until a solution to the draft problem has been
resolved. Continuing operation may result in death or injury.
!
!
!
Always read the manual before system installation or repair. If in doubt, seek professional
help.
Open top covers etc. with extreme caution. When the boiler is in operation, there is a risk of
high temperature surrounding the top covers, which can result in injury. Avoid handling the
boiler while it is in operation. Never open the ash tray while the boiler is in operation
The system may be operated by skilled people. If you are in doubt as to the safe operational
use of the boiler, contact your dealer.
The menu structure etc. for the controller is supported by the help texts found in the control
box itself. Due to constant updates and new features, the menu structure of the controller
will not be described here in this manual. Instead, it is recommended to browse the
controller thoroughly prior to use and to receive an overview of all functions, etc. by your
installer.
This manual must be kept at the boiler!
3
BOILER SPECIFICATIONS:
Black Star
BS1016
BS1016
BS2030
BS4050
Height mm:
1017
1017
1017
1130
Width mm:
450
450
550
663
Depth mm:
715
715
778
883
Chimney mm:
130
130
150
150
Outlet:
1 1/4”
1 1/4”
1 1/4”
1 1/4”
Inlet:
1 1/4”
1 1/4”
1 1/4”
1 1/4”
Filling:
½”
½”
½”
½”
Efficiency:
93,3%
93,4%
94,7%
91,4%
EN Class:
5
5
5
5
Output:
10kW
14kW
24kW
48kW
300-ELAB-
1683
1700
1765
1859
Black Star
BS20
BS30
BS30
BS40
Height mm:
980
980
980
1084
Width mm:
430
530
530
628
Depth mm:
630
693
693
795
Chimney mm:
130
150
150
150
Outlet:
1 1/4”
1 1/4”
1 1/4”
1 1/4”
Inlet
1 1/4”
1 1/4”
1 1/4”
1 1/4”
Filling:
½”
½”
½”
½”
Efficiency:
91,7%
93,0%
92,0%
92,5%
EN Class
3
3
3
3
Output:
10 kW
16 kW
30 kW
40 kW
300-ELAB-
1398
1400
1407
1497
BS1016
BS20
4
BURNER SPECIFICATIONS:
10 kW burner:
Up to 60kg/day
40 watt/hour
Weight 10kg
16-24kW burner:
Up to 110kg/day
60 watt/hour
Weight 12kg
30kW burner:
Up to 150kg/day
80 watt/hour
Weight 15kg
40-60kW burner:
Up to 300kg/day
150 watt/hour
Weight 30kg
80-120kW burner:
Up to 600kg/day
200 watt/hour
Weight 40kg
150-200kW burner:
Up to 1000kg/day
250 watt/hour
Weight 60kg
5
BOILER ROOM DESIGN:
The boiler room for biomass boilers must be performed in accordance with the Danish
Institute of Fire "Fire Standard No. 32" BTV32. In addition, you must comply with the
rules set forth by your local building codes, environmental authorities, and labor
inspectorate. If you are in doubt on how to set up your boiler room, we recommend
that you contact your local chimney sweeper for guidance.
1. Wall and Ceiling
2. Distance to the Wall
3. Floor
4. Area and Lighting
5. Chimney
6. Air
7. Water Faucet
8. Fuel
9. Prohibited Liquids and Materials in Boiler Room.
10. Permit, Notification and Inspection
1. Wall and Ceiling. Ceiling surfaces must be constructed with at least Class 1 surface material. If the ceiling surface
happens to be the underside of the roof, the material must be made of noncombustible materials. Wall surfaces must be
constructed of at least a Class 2 surface material.
2. Distance to the Wall. Distance from the boiler or flue pipe to any combustible material should be large enough of a
distance to prevent temperatures from reaching an excess of 80 ° C. This requirement applies even if the combustible
material is covered with non-flammable material. If the distance is greater than 500 mm, the distance requirement is
typically satisfied.
3. Floor. Floors should consist of (or be covered with) non-combustible material under and around the boiler of a
distance of at least 300 mm from the boiler sides, and 500 mm from the boiler’s front (i.e. the side where the ash is
removed).
4. Area and Lighting. The boiler room and area around the heating system must be large enough to allow for easy
operation, cleaning, and maintenance of the heating system and boiler room. There must be adequate lighting so that
supervision and maintenance can be performed safely.
5. Chimney. The chimney must be of a design, aperture area, and height that provides
adequate draft conditions and sufficient exiting of flue gasses. The chimney draft
is created by negative pressure resulting from the buoyancy of the hot smoke rising
up through the chimney. If there is not enough draft in the chimney, the smoke will
not properly rise and will instead seep out through small cracks. This can result in
toxic smoke seeping into the house.
6
BOILER ROOM DESIGN:
The size of the chimney opening must match the amount of flue gases the chimney has to lead away. If the
opening in the chimney is too small, this will prevent the smoke from exiting fast enough due to the large
resistance in the chimney. This could cause the smoke to turn back; thus allowing for toxic fumes to enter into
the house. Simultaneously, the pellet fuel may not be completely burned, due to the lack of oxygen for
combustion. This can cause traces of soot to sit in the chimney and create what is called shining soot, which
increases the risk of chimney fire. The chimney opening must also not be too large since cold air can enter the
chimney from the top. When the chimney becomes cooled, condensation can occur and develop soot inside the
chimney. Soot is mostly a cosmetic problem, because it can penetrate through the chimney and cause ugly brown
splotches to appear on the walls inside the house. In addition, it is important that the chimney protrudes high
enough above the roof so the smoke does not bother the surrounding houses. Environmental authorities have
the possibility of prosecuting you if there are neighbors that complain about the smoke or odor.
What signs are there, if the chimney is not working?
• Light sensor is sooty or melted.
• Smoke in the hopper.
• Warm drop shaft.
• Smoke billows out of the fan or boiler during startup.
If you have any problems with your chimney, it is a good idea to keep a "diary“
of any draft problem; as draft problems are often associated with wind in certain
directions. Wind blowing on one side of the house can cause under pressure on
the other side of the house. Overpressure and under pressure will try to balance
out even through a chimney, if possible. It is a good idea to ask your chimney
sweeper about the size of the chimney and flues, the location of chimney
cleaning doors, and whether it is required to have steps on the roof. He will also
perform a fire prevention inspection
6. Air. The pellet boiler should be supplied with enough air for combustion. This
can be achieved if the pellet boiler is installed in a room which is equipped with a
sliding window with an adjustment bracket, an adjustable air vent from the outside,
or by providing the combustion chamber with air through a duct from the outside.
The area size of the fresh air valve should generally be the same as the internal diameter of the chimney. It
should also be mounted on the same side as the chimney to compensate for any pressure differences.
Note: drum dryers, range hoods, oil burner in the same room, all use high pressure blowers, that steal the air in
the room!
7. Water tap. There must be a tap in the boiler room. If the boiler output is less than
60 kW, a powder extinguisher (at least 5 kg) will suffice.
7
BOILER ROOM DESIGN:
8. Wood Pellets. The pellets must consist of pure wood, 6-8 mm max 8% water. Materials with glue, paint, wood
paint or plastics must not be burned. If the fuel storage is greater than 0.75 m3, the boiler system and fuel storage
must be located in a separate fire cell with at least one BD30 door to the other room. If the fuel storage or hopper
is placed in the open or under a shelter, there may be minimum distance to the building that should be observed.
Exposed fuel may not be in the boiler room, except logs. Do not exceed 4.75 m3 fuel in the boiler room, including
fuel storage and usage storage
9. Prohibited liquids and materials in boiler room. The boiler room must be kept clean and contain no combustible
materials nor flammable liquids (except oil for oil burners). The floor must be kept free of spilled fuel, dust and
combustible waste as well as waste from other activities in the room. Any burning embers
must be extinguished with water and transported to a secure storage location in the open.
!
10. Permit, notification and inspection.
Building permit:
You must obtain a building permit if the burner is situated in a building that is part of the Building Regulations 1995
(commercial buildings); though not for animals and farm buildings
Notification:
The heating system must be reported to the local council and registered with the chimney sweep.
Inspection:
The chimney sweeper will regularly supervise your biofuel boiler. If the chimney sweeper becomes aware of any
illegality under the rules for fireplaces and chimneys in the building code, he may notify the local council if the
owner does not change the illegal conduct.
Insurance:
You must notify your insurance company about your biomass system.
8
REQUIREMENTS FOR
CHIMNEY HEIGHTS:
Statutory air pollution requirements for solid fuel boilers up to 1MW.
(Only applicable for newly-built chimneys.)
Buildings with a roof slope that is less than 20 degrees.
Roofs with a slope of less than 20 degrees is counted as flat
20 o
Prohibited
area
Buildings with a double roof and roof slope that is less than 20
degrees.
20 o
Buildings with a roof slope that is less than 20 degrees and is
adjacent to another building.
20 o
Buildings with a slope greater than 20 degrees.
Prohibited
area
Buildings with a slope greater than 20 degrees and has an
adjacent building with a flat roof.
* Highest value selected
At least 10 m or 2xH
Prohibited
area
Gable window**
Property block or industrial building with an adjacent building.
* Highest value selected.
** At gable windows, the chimney must be at least 1 m above
the gable window's upper corner.
At least 10 m or 2xH
Prohibited
area
Property block or industrial building with two adjacent
buildings.
* Highest value selected.
H or at least 10 m
*Highest value is selected
9
INSTALLATION OF THE
BOILER:
A correctly executed installation ensures that the system functions properly.
Both national/local guidelines and requirements must always be observed.
The boiler can be installed on a pressurized system up to max 2.5 bar.
1. Standard.
DHW with mechanical flow control
2. DHW with 2 way valve.
Typically used when DHW is small or
when the surface coil is small.
Heat for the house is supplied while hot
water is being produced.
3. DHW with 3 way valve.
-Typically used when the water heater is large,
and when the surface coil is large
-The house is not supplied with heat while
producing hot water. The house must therefore
be able to manage without heat for short periods
during the winter .
4. Weather compensation.
Allows you to have a high temperature on the boiler.
Manage the supply temperature to the house in
relationship to the outside temperature and chill factor.
5. Weather compensation and solar heating
Do not go down on equipment 
10
INSTALLATION OF THE
BURNER:
General Guidelines:
Installing the burner on the boiler:
1. Check that the burner is not damaged during transport.
2. Check that the burning grate is inserted correctly in the burner (see image right).
3. Mount the burner and tighten the burner with the 2 wing nuts supplied.
Never use locknuts, as the seal between the boiler and the burner can leak over time.
4. Make sure that the burner is horizontal and that all connections are tight.
5. Mount the shield and the connector on the burner.
6. Install electricity for safety cut-off thermostat according to the wiring diagram. SAFETY THERMOSAT
MUST ALWAYS BE FUNCTION TESTED! The thermostat can be tested by using an electric kettle. The
thermostat must switch off when the temperature feeler is dipped into boiling water. If necessary, adjust
the switch-off temperature lower by turning the screw inward. Reset the thermostat by pressing hard on
the red button!
External auger:
7. Install the auger output over the burner.
8. Auger should be at an angle between 0 and 50 degrees.
9. The flexible hose should be angled enough as to allow for the free passage
of the wood pellets to the burner without getting stuck in the PVC hose.
11
INSTALLATION OF THE
BURNER:
Temperature sensor on the boiler:
Mount the sensor within a sufficiently long thermo well.
Use a fastening strip or similar to prevent accidental slippage.
Safety thermostat:
Mount on either the left or right side of the boiler as
displayed in image.
Note: Functional testing of the high limit safety thermostat
is required before starting up the boiler.
To test, press moderately on the disc (shown in A) in the
direction towards the temperature feeler. A small "click“
will occur, signaling that the connection between C and C2
is interrupted and that the high limit safety thermostat is
triggered. To re-activate the thermostat, press hard on the
red button marked (B) in the drawing. You will also hear
a "click", signaling that the connection between C, and C2
is restored and that the high limit safety thermostat is
activated and ready for use.
Semi cleaning on BS1016, BS2030 and BS4050:
The boiler cleaning system must be connected with 230V AC
through the socket located on the back of the boiler. In the
control box, make a connection to output (L5-L10). The cleaning
system will run every time the burner conducts a blower
cleaning sequence, ie. typically 5 sec. every 10 min. These
settings can be configured under the Cleaning menu in the
controller.
12
WOOD PELLET HOPPER:
There are several hopper solutions, examples include a steel hopper, fabric hopper and
mini hopper which is built together with the boiler. All hoppers can be extended for
bulk storage/feeding via the vacuum transport.
Steel Hopper:
Available in 4 different models
60x60cm
80x80cm
80x140cm ext.
100x100cm
=
=
=
=
200L
320L
500L
500L
= 140 kg
= 220 kg
= 350 kg
= 350 kg
Mini hopper, built together with boiler:
Available in 3 different models:
Can be mounted to the right or side of the boiler.
BS1016 mini, 150 kg
BS2030 mini, 200kg
BS4050 mini, 250kg
13
VACUUM TRANSPORT:
The Vacuum System for wood pellets makes it easy to customize various delivery forms for your system. Here are a
few examples of ways to configure your vacuum transport.
Cloth silo 3-5 tons with vacuum transport to BlackStar hopper.
Cloth silo 3-5 tons with vacuum transport to standard hopper.
Home build with vacuum transport to standard hopper.
14
WIRING DIAGRAM:
There may be factory installed wiring on the outputs L5-L10. L5 may be factory
fitted for the moving grate. L6 may be factory fitted for the compressor cleaning.
Remove these if there is a need for other equipment on the outputs
15
16
WIRING DIAGRAM:
17
18
ELECTRICAL
CONNECTION DIAGRAM:
Overview of connectivity
230
SAFETY THERMOSTAT
MOTOR
BRÆNDER
BRÆNDER
BRÆNDER
IN
PE-N-L
L-L
OUT
PE-N-L1
PE-N-L2
PE-N-L3
PE-N-L4
EKSTRA 1
PE-N-L5
EKSTRA 1
EKSTRA 2
EKSTRA 2
EKSTRA 3
EKSTRA 3
BUS
ILT
CONTACT
CONTACT
PULS
PULS
PULS
PULS
DISTANCE
LAN
TEMP.
TEMP.
TEMP.
TEMP.
TEMP.
TEMP.
TEMP.
EKS / FOTO
EKS / FOTO
PE-N-L6
PE-N-L7
PE-N-L8
PE-N-L9
PE-N-L10
GRD, TX, RX,
V1, V, V2
K-K1
K-K2
P-P1
P-P2
P-P3
P-P4
-, SIG, +
RJ45
T- T1
T – T2
T – T3
T – T4
T – T5
T – T6
T – T7
T – T9
T-T10
FUNCTION
230 Volt AC
Safety thermostat cutoff
External auger
Fan
Internal auger
Ignition
Circulation pump, can be set to other
equipment
Compressor cleaning, can be set to other
equipment..
Optional output for equipment.
Optional output for equipment.
Optional output for equipment
Optional output for equipment.
Expansion module
O2 controller
External ON/OFF
Free
Flow meter system
Flow meter solar heating
Free
Fan RPM
Distance sensor for hopper
Internet connection
Boiler temperature
Smoke temperature
Boiler return temperature
DHW temperature
External temperature
Free
Free
Temperature sensor burner
Photo sensor burner
19
OPTIONAL EQUIPMENT:
The controller supports the following equipment. Aids in performing adjustments, cleaning, and knowledge.
Smoke Temp. Sensor:
Reads the current smoke
temperature in the display.
Extension module:
Get additional 10 ouputs
for equipment.
Prepared for 02 control.
O2 Control Kit:
Regulates the amount of
oxygen in the flue gas.
Regulates the quantity of
wood pellet and air
according to the desired
O2%.
Hot Water Priority Kit:
Produces hot water only
when it is needed. Closes
hot water tank, when the
house is heated. Kits
available with either 2 or 3
way motorized valve.
Compressor Cleaning
System:
Cleans the burner head
efficiently with high
pressure. With this kit you
need to use your own
compressor.
Compressor Cleaning L:
Cleans the burner head
efficiently with high
pressure. “Low noise”
compressor included..
Solar Heating
Use the pellet burner
controller to run your solar
system.
External Temp. Sensor:
Stops burner through an
external temperature sensor.
Lambda sensor:
For the extension module.
Flow Sensor Kit:
Reads the system flow in the
display and calculates the
current power consumption
for the house
Distance Sensor for Hopper:
Monitors the pellet level in a
hopper and reports it in the
controller.
Exhaust Fan:
Need greater chimney draft?
The fan’s RPM can be
synched with the burner's
power output. Can be
connected to the burner
controller..
Weather Compensation:
Maintains a high boiler
temperature while adjusting
the house inlet temperature
in relation to the outdoor
temperature.
Wireless thermostat:
Stops the pellet burner with
thermostat. Gives a smooth
transition to summer time.
20
INTERNET CONNECTION:
The web-based controller can be updated automatically from the Internet. Operating data can also be uploaded to
www.stokercloud.dk
How to get the controller on the web:
1. Connect the controller to your router through an RJ45 cable. Since this is a direct cable connection no
passwords, etc. is required. Once connected, a small icon will appear on the screen indicating that the
controller is online.
If you do not have the possibility of a direct cable connection, these adapters
picture on right, can be used. They can establish a connection to your router
through your household power cables. This provides an easy PLUG and PLAY solution.
2. Find your control number and password under the "system" in the controller
Gå på www.stokercloud.dk og find styringen på scroll down i toppen af siden.
Alternativt tast din styrings nummer i søge feltet.
3. Go to www.stokercloud.dk and find your controller in the drop-down at the
top of the page. Or type your control number in the search box
4. LOG IN, and follow the instructions.
5. Enter your personal information. New user name and new password.
21
CLOUD SERVICE:
If your burner is online via our website www.stokercloud.dk we can help you keep an eye on your
system. If something unexpected happens, such as too many ignitions, unstable operation, improper
PI regulation etc., we will have the opportunity to help you ONLINE.
How it works:
NBE observes abnormalities on your graphs.
You will be contacted by E-mail, where we ask your
permission to make changes.
NBE will assess your graphs and the burner reaction
pattern, and make adjustments based on the
observations.
You can always see the changes in your LOG.
- After adjusting, it should look like this ...
NBE's Cloud Service ensures:
Fewest possible number of electrical ignitions.
Best possible PI regulation.
An optimized system for your house.
Lower wood pellet consumption.
Security in everyday life.
The latest updates to the controller.
22
FIRST TIME START UP:
Once the system is assembled, filled with water, and power is connected to the system a
few basic adjustments to the burner is required.
1.
Fill the auger with pellets by force starting the auger either through the
controller or directly via a 230V connection.
2.
When the augur appears full, run for an additional 15 min. to ensure
correct weighing later.
3.
Activate the 6 min. test run in the controller and collect the dispensed
pellets with a plastic bag.
4.
Using a kitchen scale, weigh the pellets from the test run and enter the amount into the controller under
"Auto calculation“. Repeat again after 7 days!
5.
Adjust minimum output as low as possible, typically 10% of the burner's rated output (i.e. if 20kW, set to
2.00kW). If the chimney draft is high, adjust the minimum output up until you have a stable flame at 10%
power.
6.
Once the burner is activated an ignition will be made. After approx. 20 minutes the burner will reach a nominal output
(100%). If necessary lock the burner output at 100%. Now you can perform an evaluation as to whether the fan is providing
suitable supply of air to the flame. If necessary, adjust in the fan menu
The flame at 100% should fill the entire width of the grate,
have redish spikes, and reach the opposite wall…
7.
Lock the burner to 50% power. Wait 5 minutes for the flame to stabilize.
Again, assess fan performance in relation to the flame
The flame at 50% should be approx. 10 cm out of the burner
and is yellowish in color.
8.
Lock the burner to 10% power. Wait 5 minutes for the flame to stabilize.
Assess fan performance in relationship to the flame.
The flame at 10% should be small and short
The photo sensor reading may fluctuate, however, it should not have a 0 LUX
reading for a period >10 sec. If the chimney draft is too high, increase the
minimum effect of the burner to increase flame size.
23
CLEANING THE
BURNER/BOILER:
Cleaning should be carried out regularly and/or as needed. There is a big difference in the
frequency of maintenance required from system to system. The setup, adjustment, and
wood pellet quality play an important role on how frequent maintenance should be
performed.
The table is only a suggestion and applies only to the BS1016, BS2030 and BS4050 boilers!
When
1/2
needed 7 Days 14 days 30 days annually annually
x
x
x
x
Cleaning cinders out of burner head.
x
Cleaning under the combustion grate for dust and cinders
x
x
x
Cleaning photo sensor from soot and dust.
x
x
x
x
x
Cleaning boilers, flues, and take semi cleaning out.
x
x
x
Cleaning burner fan from dust
Emptying the last smoke channel for ashes
Empty the ash pan, typically after 1,000-2,000 kg pellets
x
x
Check gaskets / replace worn gaskets.
Adjusting the burner. (weighing the pellets)
x
x
x
Filling the hopper.
x
x
Emptying the hopper, dust and fines removed.
x
Chimney sweeper
Turn off the burner in connection with cleaning.
Turn off the controller and allow to cool for approx. 5 min. Once the burner is completely turned off, it is ready for cleaning.
Unplug the burner, remove the shield, drop shaft, and detach the burner from the boiler so work can be easily performed.
Boiler.
All surfaces inside the boiler must be brushed clean from any deposits and the ash can must be emptied. When empting the
ash can, pay special attention to any build-up of ash in the rear smoke chamber and flue, since the Chimney Sweeper may not
always be removing the ash from the chimney flue
Never dispose of hot ashes in the trash, but let it cool in a metal bucket. Hot ashes can start burning when
it gets oxygen (air).
!
Burner head.
Remove any ash or cinders from the grate. Remove any pellet remnants under the burner grate. Wipe the photo sensor clean.
When re-inserting the photo sensor, ensure that the sensor points towards the combustion grate. Ensure that there is nothing
lodged in the fan and that it can rotate freely.
Hopper.
Since pellets naturally contain dust, you should periodically empty the hopper completely. The more dust that is present in
the hopper, the less the auger will dispense, and the more unstable the dosing. The boiler will go out of adjustment with
greater risk of downtime. How often one should empty the hopper depends greatly on the design and quality of the pellets
you use.
!
Put 1 dl cooking oil or similar into the hopper each time it is emptied (poured over the last pellets)
and the hopper will automatically empty the sawdust.
Start-up after cleaning.
Once the pellet boiler is reassembled, turn on the controller and the burner will start itself up.
!
Remember to reattach the shield so that the temperature reading on the burner is correct
24
TROUBLESHOOTING:
Problem
Mulig årsag
Mulig løsning
Alarm RPM
RPM sensor defective.
Change the fan.
Change to % regulation at the fan.
No power to the controller
The burner deactivate
residual current protection
Too high pellet
consumption
Too many electric ignitions
Unburnt pellets in the ash.
Cinders on the grate .
Defective fuse in the controller.
Skift sikringen til en ny.
Safety thermostat not active.
Genindkoble ved et hårdt tryk på den røde knap.
The controller has been
overvoltage. .
Send controller in for repair.
Electric ignition is faulty
Change the electric ignition to a new.
Current leak in a component..
Note when RCD deactivate, replace the component.
Cables exposed.
Check cables, insulate them if possible.
Lean burning.
Make a new adjustment of the burner.
Too high chimney draft.
Install draft stabilizer in the chimney.
Uninsulated pipes in the
installation.
Insulate with pipe insulation.
Flow in the system is fluctuating.
Set the pressure controlled circulation pump to fixed
pressure.
External thermostat unstable.
Set ”External wait” up in the controller.
Lean burning.
Make a new adjustment of the burner..
The grate is placed incorrectly.
Mount it correctly.
Too many pellets on the grate.
Make a new adjustment of the burner.
The fan is adjusted too high.
Make a new adjustment of the burner.
Too high chimney draft.
Install a draft stabilizer in the chimney.
Blower cleaning is not sufficient.
Adjust the fan % up to clean, and the time between the
down.
Clean the grate mechanical more frequently.
Poor quality pellets.
Change supplier.
Mount compressor cleaning.
Change the grate to a model that is more open.
Fat combustion.
Adjust the fan up at 10, 50 and 100 % power
Adjust the burner power down in ”auto calculation”.
The boiler condensates
Too low chimney temperature.
See page 27 about flue gas condensation.
25
FLUE GAS
CONDENSATION:
When a boiler has an extremely high efficiency (for example > 93%), the flue gas temperatures exiting the
boiler are very low. As a consequence of this high efficiency and low chimney temperature relationship, proper
precautions must be observed to avoid condensation from developing in the chimney. Leaving condensation
untreated will risk the development of soot in the chimney, corrosion in your boiler, as well as possible loss of
warranty.
Note: even if there is water in the boiler it may be due to condensation in the chimney.
Things that can prevent condensation in the boiler and chimney.
1. High chimney> 5m.
Provides a good draft in all conditions.
2. Small clearing in the chimney 125mm-150mm.
Provides better flow, and can "carry“ out more moisture.
3. Short un-insulated smoke pipe 70C degrees.
10 degrees up in the boiler temperature gives 10 degrees more smoke temperature.
6. Suitable return temperature> 55C degrees.
Hits the smoke boiler surfaces under 47C degrees, it starts condensing.
7. Open bypass in the boiler.
Release the smoke before the last smoke cooler, 15C degrees increase in
temperature of the smoke, only costs approx. 1% in efficiency.
8. Heated boiler room.
Lowers cooling of the boiler and smoke pipe and provides draft stabilizer more hot
air to work with.
9. More oxygen in combustion.
Increases air flow in the boiler, and carries more moisture, 1% more oxygen costs
approx. 0.5% in efficiency.
10. Remove the retarder.
The retarder decreases resistance of the boiler, and get a bad chimney to work
better. The gas temperature typically increases to approx. 100 degrees. The burner
should be basic readjusted after retarder is removed.
11. Keep the heat on the boiler continuously.
When using DHW priority on controller, and the boiler starts from cold each time it
starts The boiler is not to dried out between each start.
12. Mount electric exhaust fan to chimney.
Helps the flow the right way, from CHIP 6.82 can exhaust fan be connected directly
to the controller.
26
GLOSSARY:
for the controller from version 7.0594
Menus marked with are the additional parameters that appear when you enable Extended Setup
Menu 19.
!
MENU 1- BOILER
Boiler – in this menu everything regarding the boiler can be adjusted
Wanted temperature – Specify the desired boiler temperature. The burner will adjust its output to the setpoint can be held.
Difference Under – Specify the temperature difference under the wanted temperature before restarting the burner.
Difference Over – Specify the temperature difference over the wanted temperature before stopping the burner.
Night reduction – Specify the reduction of boiler temperature at night, when timer function is used for night reduction.
External Stop Temperature – Stops the burner when the external temperature sensor (T5) achieves this temperature (0 is disabled)
External Stop Difference – Starting difference, after stopping from external temperature (T5).
Timer Active – Specify whether timer function is active for heat production.
Timer periods – Specifying timer periods, where boiler heat production is OFF, ON, or lowered at night.
!
Alarm – Max. Drop shaft temperature – The max. permitted shaft temperature before the burner is stopped and cooled
down.
Alarm – Min. Boiler temperature – If the boiler is operating under this value and no temperature increases occur within
10 minutes, the burner will be stopped.
Alarm Output – Specify which output that is used for alarm.
External contact active – Is external contact active?
Reaction ON after – Minutes the external contact must be activated (ON), before the burner starts.
Reaction OFF after – Minutes the external contact must be deactivated (OFF), before the burner stops.
MENU 2- DHW
DHW – In this menu, everything concerning the domestic hot water tank can be adjusted
Wanted temperature – Specify the desired DHW temperature.
Difference under – Set the temperature drop from the desired DHW temperature at which the controller will switch to DHW priority to
reheat tank.
Remain in DHW production – The time the DHW valve remains in DHW position, after the DHW temperature has been reached. Only if heat is
needed in the tank.
!
Output DHW – Specify the output relay the controller will use for DHW operation.
Timer active – Specify whether timer function is active for DHW production.
Timer periods – Specifying timer periods, where DHW production is OFF or ON.
27
MENU 3 - REGULATION
Regulation – in this menu, everything concerning the PI regulation can be adjusted.
!
greater the
Temperature regulation gain P – Note: Responds to boiler temperature change. The higher the value, the greater the
response.
Temperature regulation gain I – Note: Responds to boiler temperature differences over time. The longer the time, the
response.
Power increase / minute – Specify the maximum output increase per minute after the start-up.
Min. power – Minimum power in percent. Not valid for DHW mode, which is set in the parameter Min. Power at DHW – see 3.6.
Max. power – Maximum power in percent. Not valid for DHW mode, which is set in the parameter Max. Power at DHW – see 3.6.
!
DHW regulation gain P – Response to DHW temperature change. The higher the value, the greater the response.
DHW regulation gain I – Response to DHW temperature difference over time. The higher the value, the greater the
response.
Setpoint boiler addition – Setpoint at DHW production is the wanted DHW temperature plus this addition.
Min. Power – Specifying min. output doing DHW, can be increased DHW production is too slow.
Max power at DHW – Specify the max. Burner output during DHW operation. This can be reduced if the boiler overheats doing DHW
operation.
28
MENU 4 – WEATHER
Weather – In this menu, everything concerning weather compensation can be adjusted. Ex. Operation via the outdoor temperature.
Active – Activate weather compensation?
Mean period temperature – The measured temperature used, is the average temperature over this period of time (hours).
Use T5 temperature sensor – Specify if the temperature is to be read from a local sensor or the internet.
Chill factor weight – Weight (%) of registered chill factor. Use for example if exposed to abnormal wind conditions.
Valve at DHW production – Valve reaction at DHW production. If the DHW is placed on the weather compensated circuit,
!
choose 100 open (open valve)
Outlet house pump – Specify which output is to be used for the house pump.
Regulating valve open – Specify which output on the controller to use for opening regulating valve.
Regulating valve close – Specify which output on the controller to use for closing regulating valve.
Gain P – Specify the response to house temperature changes. The higher the value, the greater the response.
Measured temperature 1 – Specify the temperature for regulation at point 1. At this temperature the burner will stop.
Measured temperature 2 – Specify the temperature for regulation at point 2. At this temperature the burner will stop.
Measured temperature 3 – Specify the temperature for regulation at point 3. At this temperature the burner will stop.
Measured temperature 4 – Specify the temperature for regulation at point 4. At this temperature the burner will stop.
Measured temperature 5 – Specify the temperature for regulation at point 5. At this temperature the burner will stop.
Measured temperature 6 – Specify the temperature for regulation at point 6. At this temperature the burner will stop.
Measured temperature 7 – Specify the temperature for regulation at point 7. At this temperature the burner will stop.
Forward temperature 1 – Enter the wanted temperature for regulation at point 1.
Forward temperature 2 – Enter the wanted temperature for regulation at point 2.
Forward temperature 3 – Enter the wanted temperature for regulation at point 3.
Forward temperature 4 – Enter the wanted temperature for regulation at point 4.
Forward temperature 5 – Enter the wanted temperature for regulation at point 5.
Forward temperature 6 – Enter the wanted temperature for regulation at point 6.
Forward temperature 7 – Enter the wanted temperature for regulation at point 7.
Max. Power 1 – Enter the wanted power for regulation at point 1.
Max. Power 2 – Enter the wanted power for regulation at point 2.
Max. Power 3 – Enter the wanted power for regulation at point 3.
Max. Power 4 – Enter the wanted power for regulation at point 4.
Max. Power 5 – Enter the wanted power for regulation at point 5.
Max. Power 6 – Enter the wanted power for regulation at point 6.
Max. Power 7 – Enter the wanted power for regulation at point 7.
29
MENU 5 - 02 CONTROL
O2 Control – In this menu, everything concerning the 02 control can be adjusted.
O2 control method – Specify if 02 control is active (ON), not active (OFF) or 02 is shown but not regulated (SHOW).
Wanted O2 at 10% power – Specify the desired % oxygen in the boiler at 10 % power.
Wanted 02 at 50 % power – Specify the desired % oxygen in the boiler at 50 % power.
Wanted 02 at 100 % power – Specify the desired % oxygen in the boiler at 100 % power.
O2 probe calibration – Start calibration of 02 probe
Wood pellet blocking time – Specify the number of minutes prior to blocking the pellet fuel when actual 02 % < 2 %
lower than the desired 02%
Updating time – Specify how often the 02 controller is allowed to make an adjustment on the flower speed and the fuel.
!
Regulation gain P – Specify how much the controller should respond to temperature changes.
Regulation gain I – Specify how much the controller should respond to time away from the desired oxygen content.
Correction fan 10 % - Specify how much the 02 controller can regulate the fan speed at 10 % power (plus, minus).
Correction fan 50 % - Specify how much the 02 controller can regulate the fan speed at 50 % power (plus, minus).
Correction fan 100 % - Specify how much the 02 controller can regulate the fan speed at 100 % power (plus, minus).
Regulation pellets gain P – Specifies gain for proportional oxygen regulation of wood pellets.
Regulation pellets gain I – Specifies gain for integrated oxygen regulation of wood pellets.
02 sensor type – Specify type of attached lambda sensor
02 sensor on expansion module – Is the oxygen sensor (lambda sensor) connected to an expansion module?
MENU 6 – CLEANING
Cleaning – In this menu, everything concerning cleaning can be adjusted.
Time between – Specify how often the fan should increase in speed to clean out the burner grate.
Time – Specify the duration of time desired for regular cleaning by the fan. Note: the fan will speed up to clean the grate.
Speed – Specify the fan speed to be used during regular cleaning.
Cleaning after – Specify the interval (lbs) between compressor cleaning. Note: A run period will always end with a cleaning.
Valve operating period – During this period, the air valve repeatedly opens for 0,2 sec and closes for 1,8 seconds.
Valve pulse length – Specify the air valve opening time of the total period of 2 seconds.
Stop pellets for – Specify the time desired to pause pellet dosing prior to cleaning. Note: ensures the wood pellets burn out.
Fan speed – Specify the fan speed desired when performing compressor cleaning.
Output valve – Specify the output relay in the controller that the valve is connected to.
!
Outlet boiler valve 1 – Specify the output for cleaning system valve 1. Activates half the time of compressor valve.
Outlet boiler valve 2 – Specify the output for cleaning system valve 2. Activates half the time of compressor valve.
Outlet ash auger – Activates the ash cleaning system. Runs 2 minutes for each 50 lbs pellets consumed.
Measure compressed air on T7 – Specifies if T7 is used for measuring of compressed air. If not, T7 can be used as
temperature sensor input.
30
30
MENU 7 – HOPPER
Hopper – In this menu, everything concerning the wood pellet hopper can be adjusted.
Distance top – Enter the distance from the sensor to the top of the pellets when the hopper is full. (minimum 2 in).
Distance bottom – Enter the distance from the sensor to the bottom of the pellets (cm) when the hopper is empty.
Automatic fill – Enter the number of lbs of pellets in the hopper when full. Note: values will be put into hopper content automatically.
Hopper content – Enter the hopper content (lbs). Note: this values is used for counting down the amount of pellets.
Minimum hopper content – Specify the minimum content of the hopper. An info-message is issued when this level is reached.
MENU 8 - FAN
Fan – In this menu, everything concerning the fan can be adjusted.
Speed at 10 % power – Fan speed at 10 % power must be adjusted according to the fuel, chimney draft, and back pressure in the boiler.
Speed at 50 % power – Fan speed at 50 % power must be adjusted according to the fuel, chimney draft, and back pressure in the boiler.
Speed at 100 % power – Fan speed at 100 % power must be adjusted according to the fuel, chimney draft, and back pressure in the boiler.
Use fan RPM – Select regulation of fan speed in Round Per Minute (RPM).
Use fan RPM alarm –
Exhaust fan: Speed at 10 % power – Wanted speed on exhaust fan, when the burner has 10 % output.
Exhaust fan: Speed at 50 % power – Wanted speed on exhaust fan, when the burner has 50 % output.
Exhaust fan: Speed at 100 % power – Wanted speed on exhaust fan, when the burner has 100 % output.
!
Controller output exhaust fan – Specify which output that is used for exhaust fan.
MENU 9 - AUGER
Auger – In this menu, everything concerning the external auger can be adjusted.
Force run external auger – Enter the number of seconds used for forced-running of the external auger. Use for auto calculation or for refilling
the auger.
Balancing – Do you want to measure external auger capacity for 6 minutes?
Auger capacity/6 min – Used to calculate the wood pellet quantity at 10 % and 100 % power.
Auto combustion – Choose if the controller calculates external auger time?
Auger feed time 10 % - Enter the auger running time at 10 % power (two decimals), only active if auto combustion is OFF.
Auger feed time 50 % - Enter the auger running time at 50 % (two decimals), only active if auto combustion is OFF
Auger feed time 100 % - Enter the auger running time at 100 % (two decimals), only active if auto combustion is OFF
Min. output at 10 % – Minimum output on the burner. Must be adjusted according to the size of the burner and the draft
!
in the chimney.
Max. Output Btu – Note: the nominal effect of the burner must match the boiler’s and burner’s rated output. Used in
auto combustion.
Auger feed times/minute – Specify number of times/minute you would like the internal auger to e dosing pellets. Note:
does not change the quantity.
Minimum pellets dose – Specify the minimum pellets dose each time the external auger feeds pellets.
31
Menu 10 - Ignition
Ignition – In this menu, everything concerning the ignition can be adjusted.
Pellets for ignition – Specify the amount of wood pellet to be used during ignition. Note: less quantity less smoke during start-up.
Ignition power – Specify the desired electrical load of the igniter. Note: the lower the load %, the longer the durability.
Fan speed start – Specify the desired fan speed at the start of an ignition cycle.
Fan speed middle – Specify the desired fan speed in the middle of an ignition cycle.
Fan speed end – Specify the desired fan speed at the end of an ignition cycle.
Max Time – Specifying the maximum time an electrical ignition can take. Note: the fan speed will change over this period of time.
Preheating – Specify the preheating time desired for the igniter. Note: specifies the time prior to the blower cycle.
Exhaust fan speed – Specify the amount of wood pellet to be used during ignition.
Number of ignitions – Specify the number of ignitions made. Can be cleared using the function - Reset ignition data
Reset ignition data – Reset the ignition counter. Ex. Use when replacing the igniter Note: A typical system should ignite 1000 times/year.
Menu 11 - Pump
Pump – In this menu, everything concerning the circulation pump can be adjusted.
Start temperature – Specify the pump’s start temperature. Note: only active if the burner is in operation.
Stop temperature – Specify the pump’s stop temperature. Note: only active if the burner is stopped.
!
Flowmeter liter/pulse – Specify how many liters the flowmeter provides per pulse.
Flowmeter pulse frequency – Pulse frequency from the flowmeter at a flow of 1 liter per minute. Only used if Flowmeter liters/pulse is set to 0.
!
Output pump – Specify which output that is used for boiler pump.
32
Menu 12 – Solar heating
Solar heating – In this menu, everything concerning solar heating can be adjusted.
Wanted sunpanel temperature – Specify the wanted sunpanel temperature. Regulated by regulation of pump speed.
Pumpstart temperature difference – Specify temperature difference between sunpanel and DHW, where the pump must run.
Pumpestop temperature difference - Specify temperature difference between sunpanel and DHW, where the pump must stop.
Pump minimum speed – Specify minimum pump speed. By specifying 100 %, the pump speed is not regulated.
DHW maximum temperature – Specify maximum DHW temperature. When this temperature is reached, the excess heat valve is opened.
Output sun pump – Specify the output for sunpanel pump. By specifying OFF, all solar heating is turned OFF.
Output sun excess heat – Specify the output for excess heat valve. By specifying OFF, excess heat is not used.
Start boilerpump at surplus - Specifies whether the boiler pump should run when solar heating is producing excess heat.
!
Input sun collector – Specify the input for suncollector temperature.
Input sun collector 2 – Specify the input for extra suncollector temperature. Only relevant for eat/west sun collectors.
Input DHW bottom temperature – Specify the input for DHW bottom temperature. By specifying OFF, the temperature
sensor at input T4 is used.
Input excess heat temperature – Specify the input for excess heat temperature. By specifying OFF, the temperature
sensor, the temperature sensor at input T3 is used.
Flow liter/pulse – Specify how many liters equals one pulse from the flowmeter.
Menu 13 – Chart view setup
Chart view setup – In this menu, charts of burner operation can be selected, including the color used. Choose whether the curve should be
shown by pressing the MENU bottom (change between NO and YES). Choose color by pressing the  bottom.
Boiler temperature
Power Btu
Smoke temperature
02 Reference
Return temperature
Boiler temperature reference
DHW temperature
Extern temperature
Extern temperature
DHW reference
House inlet temperature
House inlet reference
Sun collector temperature
!
Distance measure
Light
Shaft temperature
Power consumption mA
O2%
Flow 1
Flow 2
Flow 3
Flow 4
Power %
33
Menu 14 – Chart view
Chart view – In this menu, the burner’s operational charts can be viewed.
Menu 15 – Consumption
Consumption – In this menu, pellet consumption charts can be viewed.
Menu 16 – Download
Download – In this menu, you can check if there are any updates. Note: requires an internet connection.
Menu 17 – Event log
Event log – In this menu, you can check if there has been any changes made overthe past 48 hours.
Menu 18 – Setup
Setup – In this menu, everything concerning the settings can be adjusted. Ex. Internet connection, passwords etc.
Background picture – Select a picture to be background picture.
!
Shaft temperature sensor type – Specify the sensor type used for shaft temperature measurement. Select NTC or PTC.
Smoke temperature sensor type – Specify the sensor type used for smoke temperature measurement. Select NTC or
PT1000.
Sleep light level – Light level in sleep mode after 5 minutes inactivity. 5 means full light, 0 means light off.
!
Display color scheme – Specify the color scheme of the TFT display. Choose between 2011 and 2013 (written on the
display after Copyright)
RTC tod – specify current time.
RTC date – specify current date
RTC month – specify current month
RTC year – specify current year
Serial number – Here you can see the serial number of the controller, which also functions a user name when you connect the boiler to
StokerCloud the first time.
Password – This password is the password you need to connect the boiler to StokerCcloud.
IP Address – Here you can see the IP address of the controller.
MAC Address – Here you can see the Mac address of the controller.
Menu 19 – Extended setup
Extended setup – In this menu, special technical items can be adjusted.
Technical setup – In technical mode, all data can be changed. Otherwise, some critical data are not accible. 30 miuntes timeout.
!
Expansion module connected - If an expansion module is connected, another 10 outputs and 18 inputs are available.
Language – Change controller language. The program with the selected language is downloaded from the internet.
34
Menu 20 – Manual control
Manual control – In this menu, you can activate various outputs manually on the controller. Ex. Used when you want to test equipment.
L1 External auger
L2 Fan
L3 Internal auger
L4 Ignition
!
L5 Output pump
L6 Output valve
L7 Outlet ash auger
L8 ---------------------L9 Outlet boiler valve 1
L10 Outlet boiler valve 2
35
WARRANTY:
All products purchased from NBE is covered by the current Danish Purchasing Law. This includes 6 months warranty
on the products valid from the date of receipt. A 2 year warranty is granted with the completion of the Warranty
Registration.
Note: Electrical Igniters are not covered under the warranty as they are a wearable part.
The warranty only covers manufacturing and material defects. In case of product failure of the system when under
warranty, NBE will repair the spare part at no charge to the buyer. Buyer will be responsible for the installation or
replacement of the part. If NBE offers repair of the defective part, the purchaser shall send the part to NBE for repair.
NBE will return the part once repaired. Guarantee shall be invalid if product failure is due to circumstances caused by
the buyer; either by accident and/or abuse of the product, inadequate cleaning, chimney conditions, as well as
circumstances where NBE has no influence. In addition, the warranty is invalid due to misuse of the burner- fx. using
fuel that is not approved by NBE The warranty does not cover parts such as the electrical igniter. The buyer is
obligated to check the goods immediately upon receipt. If the buyer declares that the delivery was inadequate or
defective, the customer must immediately and without delay make a written claim with NBE. Returns are only made
by agreement with NBE. To the extent that NBE is liable to the purchaser, NBE's liability is limited only to direct loss
and not to damages incurred by connected equipment and/or indirect damage, loss of earnings, operating losses,
connection costs, etc.
Responsibilities: NBE assumes no responsibility as a result of the purchaser's legal relations with third parties. All
orders are accepted subject to force majeure, including war, civil unrest, natural disasters, strikes and lockouts,
failing supplies of raw materials, fire, damage of NBE or its supplier network, lack of transport opportunities, import /
export prohibitions or any other event which prevents or restricts NBE's ability to deliver. NBE has in cases of force
majeure, the right to cancel the transaction or any part thereof, or to deliver the agreed product as soon as the
obstacle to normal delivery has lapsed. In cases of force majeure, NBE will not be held responsible for any losses
incurred by the purchaser due to non-delivery. NBE will not be held responsible for any changes and/or faults related
to price changes, sold out items or changes to specifications in the product manual. It is the buyer's responsibility to
register the equipment to the appropriate authorities. If any disputes arise between the authorities and the
purchaser, NBE will be held harmless from any
The following can be delivered upon request:
• Exception of the expansion by Labor Inspectorate.
• Chimneys endorsements.
• Approval of Technology Institute (DTI).
• Print charts.
Material is also available on www.nbe.dk
36
CE DECLARATION OF
CONFORMITY
37
NOTES:
Date
Weighing
Date
g
Weighing
g
kW low
kW
kW low
kW
kW high
kW
kW high
kW
Fan low
%
Fan low
%
Fan middle
%
Fan middle
%
Fan high
%
Fan high
%
Note:
Note:
Date
Date
Weighing
g
Weighing
g
kW low
kW
kW low
kW
kW high
kW
kW high
kW
Fan low
%
Fan low
%
Fan middle
%
Fan middle
%
Fan high
%
Fan high
%
Note:
Note:
Date
Date
Weighing
g
Weighing
g
kW low
kW
kW low
kW
kW high
kW
kW high
kW
Fan low
%
Fan low
%
Fan middle
%
Fan middle
%
Fan high
%
Fan high
%
Note:
Note:
38
EN303-5 2012 Klasse 5
godkendt ved DTI .
Godkendt til trykekspansion.
Energi mærket AA.
Producent:
NBE Production A/S
Kjeldgårdsvj 2 9300 Sæby
Denmark
www.nbe.dk