advertisement
▼
Scroll to page 2
of 47
Assembly Instructions P4 Pellet 8 - 105 English version of the assembly instructions for technicians. Read and follow the instructions and safety instructions! Subject to technical change. Fröling Heizkessel- und Behälterbau Ges.m.b.H, Industriestraße 12, A-4710 Grieskirchen Tel +43 (0) 7248 606-0 Fax +43 (0) 7248 606-600 [email protected] www.froeling.com I Introduction Dear customer, The FROLING P4 Pellet is a state-of-the-art design that conforms to all currently applicable standards and testing guidelines. Please read and follow the assembly instructions. They contain safety instructions and comprehensive information relating to transporting, setting up and assembling the boiler. The constant further development of our products means that there may be minor differences from the pictures and content. If you discover any errors, please let us know. Subject to technical change. Delivery certificate Keeping a record that the delivery was received correctly and collecting customer-specific data relating to the system allows us to respond quickly should problems arise. We would therefore ask you to confirm that you have received the product in good condition. Please send Froling a copy of the delivery certificate, filled in and signed by the customer. Guarantee conditions Our sale and delivery conditions generally apply. These conditions have been made available to customers, and customers have been made aware of them at the time of order completion. You can also find the guarantee conditions on the enclosed guarantee certificate. Address of manufacturer FRÖLING Heizkessel- und Behälterbau GesmbH Industriestraße 12 A-4710 Grieskirchen AUSTRIA TEL +43 (0)7248 606 0 FAX +43 (0)7248 606 600 E-MAIL [email protected] WEBSITE www.froeling.com Page 2 M0930811 v Contents 1 General Information C 5 1.1 Standards 5 1.2 Qualification of assembly staff 5 1.3 Protective equipment for assembly staff 6 1.4 Design information 6 1.4.1 Installation and approval of the heating system ....................................................6 1.4.2 Information on the installation room (boiler room) ................................................6 Boiler room characteristics ................................................................................6 Ventilation of the boiler room.............................................................................7 1.4.3 Heating water requirements ...............................................................................7 1.4.4 Combination with storage tank ...........................................................................7 1.4.5 Chimney connection/chimney system ..................................................................8 Draught limiter ................................................................................................8 Boiler data relating to design of the flue gas system P4 Pellet 8/15/20/25/32/38 ......8 Boiler data relating to design of the flue gas system P4 Pellet 48/60/80/100/105 ......9 1.4.6 Room air-independent operation .........................................................................9 Minimum specification of connection lines .......................................................... 10 1.4.7 Notes on boiler ventilation ............................................................................... 10 2 Technology 2.1 Components and Connections 11 11 2.2 Dimensions 12 2.2.1 Supply air connections for room air-independent operation ................................... 13 2.2.2 Flue gas pipe position ...................................................................................... 13 2.3 Technical specifications 14 2.3.1 P4 Pellet 8/15/20/25 ....................................................................................... 14 2.3.2 P4 Pellet 32/38/48/60 ..................................................................................... 15 2.3.3 P4 Pellet 80/100/105 ...................................................................................... 16 2.3.4 Airborne sound level ....................................................................................... 17 3 Assembly 18 3.1 Transportation 18 3.1.1 Positioning..................................................................................................... 18 3.1.2 Temporary storage ......................................................................................... 18 3.2 Set-up in the boiler room 19 3.2.1 Removing the boiler from the pallet................................................................... 19 3.2.2 Moving the boiler in the boiler room .................................................................. 20 3.2.3 Minimum distances in the boiler room................................................................ 20 3.3 Dismantling for location where positioning is difficult 21 3.3.1 Dismantling the stoker assembly and insulation .................................................. 21 3.3.2 Remove the door and ash drawer (P4 Pellet 8/15/20/25)...................................... 23 3.3.3 Dismantling the suction cyclone cover................................................................ 24 3.3.4 Dismantling the stoker unit .............................................................................. 25 3.3.5 Positioning dimensions after dismantling ............................................................ 28 3.3.6 Notes on reassembly ....................................................................................... 29 Fröling Heizkessel- und Behälterbau Ges.m.b.H, Industriestraße 12, A-4710 Grieskirchen, Austria Tel +43 (0) 7248 606-0 Fax +43 (0) 7248 606-600 [email protected] www.froeling.com Page 3 M0930811 C Contents 3.4 Assembling the Pellet Boiler 30 3.4.1 Installing the induced draught fan..................................................................... 30 3.4.2 Fit the ash container and doors (P4 Pellet 32/38/48/60/80/100/105) ..................... 31 3.5 Installing the discharge system 32 3.5.1 General installation information ........................................................................ 32 3.5.2 Hose Lines..................................................................................................... 32 Potential Equalisation ..................................................................................... 33 3.5.3 Universal suction system ................................................................................. 34 Variant 1 – Komfort pellet box ......................................................................... 35 Variant 2 – Eco pellet box ............................................................................... 36 Installing the suction probes and lines .............................................................. 37 3.5.4 Suction screw system...................................................................................... 38 3.5.5 Bag silo discharge system................................................................................ 41 3.5.6 Pellet storage area.......................................................................................... 43 Size of store ................................................................................................. 43 Sloping floor ................................................................................................. 44 Impact cushion.............................................................................................. 44 3.6 Electrical Connection 45 3.6.1 Connecting the Komfort pellet box .................................................................... 46 4 Initial Start-up 47 4.1 Configuring the Boiler 47 4.2 Setting the “Max level and min level” sensor 47 Page 4 M0930811 v 1 General Standards, personnel, design 1 General Information 1.1 Standards The installation and commissioning of the boiler must be carried out in accordance with local fire and building regulations. The following standards and regulations should be observed in any case: ÖNORM/DIN EN 303-5 Boilers for solid fuels, manually and automatically fed combustion systems; rated heat output up to 300 kW; ÖNORM M 7510-1 Guidelines for checking heating systems Part 1: General requirements and one-off inspection ÖNORM M 7510-4 Guidelines for checking heating systems Part 4: Simple check for heating plants for solid fuels EN 12828 Heating systems in buildings - design of water-based heating systems EN 13384-1 Chimneys serving one appliance TRVB H 118 Technical directives for fire protection/prevention (Austria only) ÖNORM H 5170 Construction and fire protection requirements ÖNORM M 7135 Compressed untreated wood or bark – pellets and briquettes – Requirements and test DIN 51731 Testing solid fuels – compressed untreated wood – Requirements and testing ÖNORM H 5195-1 Prevention of damage by corrosion and scale formation in closed warm-waterheating systems at operating temperatures up to 100 °C (Austria only). VDI 2035 Prevention of damage in water heating installations - Scale formation in domestic hot water supply installations and water heating installations (Germany only) SWKI 97-1 Lime scale and corrosion protection in heating systems (Switzerland only) 1.BImSchV First Ordinance on Implementation of the Federal Emissions Control Act 1.2 Qualification of assembly staff CAUTION Assembly and installation by untrained personnel: Risk of injury and damage to equipment! The instructions and information provided in the instructions should be observed! Only allow trained staff to carry out assembly and installation! Assembly, installation, initial startup and servicing must only be carried out by qualified people: - Heating technicians / building technicians - Electrical installation technicians - Froling customer services The assembly staff must have read and understood the instructions in the documentation. Fröling Heizkessel- und Behälterbau Ges.m.b.H, Industriestraße 12, A-4710 Grieskirchen, Austria Tel +43 (0) 7248 606-0 Fax +43 (0) 7248 606-600 [email protected] www.froeling.com Page 5 M0930811 1 General Standards, personnel, design 1.3 Protective equipment for assembly staff You must ensure that staff have the protective equipment specified by accident prevention regulations. y During transportation, set-up and assembly of the boiler: - Work clothing - Safety shoes - Protective gloves 1.4 Design information It is forbidden to carry out modifications to the boiler or to change or deactivate safety equipment. Always comply with all fire, building, and electrical regulations when installing or operating the boiler system, and follow the operating instructions and mandatory regulations that apply in the country in which the boiler is operated. 1.4.1 Installation and approval of the heating system The boiler should be operated in a closed heating system. The following standards govern the installation: Applicable standard: ÖNORM / DIN EN 12828 Heating systems in buildings § Each heating system must be officially approved. The appropriate supervisory authority (inspection agency) must always be informed when installing or modifying a heating system, and authorisation must be obtained from the building authorities: - Austria: Report to the construction authorities of the community or magistrate - Germany: Report new installations to an approved chimney sweeper / the building authorities. 1.4.2 Information on the installation room (boiler room) Boiler room characteristics There must not be a potentially explosive atmosphere in the boiler room as the boiler is not suitable for use in potentially explosive environments. The boiler room must be frost-free. The boiler does not provide any light, so the customer must provide sufficient lighting in the boiler room in accordance with national workplace design regulations. When using the boiler above 2000 metres above sea level you should consult the manufacturer. Page 6 M0930811 v 1 General Standards, personnel, design Ventilation of the boiler room Ventilation air for the boiler room should be taken from and expelled directly outside, and the openings and air ducts should be designed to prevent weather conditions (foliage, snowdrifts, ...) from having any effect on the air flow. Unless otherwise specified in the applicable building regulations for the boiler room, the following standards apply for the design and dimensions of the air ducts: § Applicable standards: - TRVB H 118 - ÖNORM H 5170 - UNI 10683 1.4.3 Heating water requirements There are no special requirements for the filling water of the heating system. The following standards and guidelines apply: Applicable standards and guidelines: Austria: Germany: Switzerland: Italy: ÖNORM H 5195-1 VDI 2035 SWKI 97-1 D.P.R. no. 412 § Notice on filling with make-up water: Always bleed the filling hose before connecting, in order to prevent air from entering the system. 1.4.4 Combination with storage tank NOTICE It is not generally necessary to use a storage tank for the system to run smoothly. However we recommend that you use it with a storage tank, as this allows you to achieve continuous reduction within the ideal performance range of the boiler. For the correct dimensions of the storage tank and the line insulation (in accordance with ÖNORM M 7510 or guideline UZ37) please consult your installer or Froling. Fröling Heizkessel- und Behälterbau Ges.m.b.H, Industriestraße 12, A-4710 Grieskirchen, Austria Tel +43 (0) 7248 606-0 Fax +43 (0) 7248 606-600 [email protected] www.froeling.com Page 7 M0930811 1 General Standards, personnel, design 1.4.5 Chimney connection/chimney system EN 303-5 specifies that the entire flue gas system must be designed to prevent, wherever possible, damage caused by seepage, insufficient feed pressure and condensation. It should be noted here that flue gas temperatures of less than 160 K above room temperature can occur within the permitted operating range of the boiler. The flue gas temperatures (for clean systems) and additional flue gas values can be found in the technical specification sheets. À See “Boiler data relating to design of the flue gas system” Connect to the chimney via the shortest path, preferably with a vertical gradient of less than 30–45°. Insulate the connecting piece. The entire flue gas system (chimney and connection) must be calculated as per ÖNORM/DIN EN 13384-1 or prior standards ÖNORM M 7515/DIN 4705-1. 1 Local regulations and other statutory regulations also apply. The chimney must be approved by a smoke trap sweeper or chimney sweep! As per TRVB H 118 (only in Austria) an explosion flap must be installed in the flue pipe or in the chimney. Draught limiter Recommended: Installing a draught limiter 1 Install the draught limiter directly under the mouth of the flue line, as the pressure is lower at this location. Boiler data relating to design of the flue gas system P4 Pellet 8/15/20/25/32/38 P4 Pellet Description Units 8 15 20 25 32 38 Flue gas temperature RL °C 140 150 150 150 160 160 Flue gas mass flow RL PL kg/h 25 11 36 15 52 20 65 25 78 32 92 41 Flue gas mass flow RL PL kg/s 0.007 0.003 0.010 0.004 0.014 0.006 0.018 0.007 0.022 0.009 0.025 0.011 Necessary Feed pressure RL PL Pa 8 6 8 6 8 6 8 6 8 6 8 6 Necessary Feed pressure RL PL mbar 0.08 0.06 0.08 0.06 0.08 0.06 0.08 0.06 0.08 0.06 0.08 0.06 mm 130 130 130 130 150 150 Flue pipe diameter RL = Rated Load, PL = Partial Load Page 8 M0930811 v 1 General Standards, personnel, design Boiler data relating to design of the flue gas system P4 Pellet 48/60/80/100/105 P4 Pellet Description Units 48 60 80 100 105 Flue gas temperature RL °C 160 170 160 170 170 Flue gas mass flow RL PL kg/h 140 60 155 70 215 75 275 95 285 100 Flue gas mass flow RL PL kg/s 0,039 0,017 0,043 0,019 0,060 0,021 0,0760,02 6 0,079 0,028 Necessary Feed pressure RL PL Pa 8 6 8 6 8 6 8 6 8 6 Necessary Feed pressure RL PL mbar 0,08 0,06 0,08 0,06 0,08 0,06 0.08 0.06 0,08 0,06 mm 150 150 200 200 200 Flue pipe diameter RL = Rated Load, PL = Partial Load 1.4.6 Room air-independent operation The P4 Pellet boiler has a central air connection on the back of the boiler. If appropriate supply air and flue gas connections are installed, the boiler can be operated independently of room air as a type C42 or type C82 in the sense of EN 15035. Definition of type C4 as per EN 15035: Boiler that is connected via its combustion air supply and flue gas outlet, with a connecting piece that may be supplied, to a shared chimney with a shaft for combustion air supply and a shaft for flue gas outlet. The mouths of the air and flue gas chimney are either concentric or so close to each other that similar wind conditions apply. Air is supplied by an air and flue gas system. Definition of type C8 as per EN 15035: A boiler that is connected via its combustion air supply and flue gas outlet, with a connecting piece, to a wind protection device and a single or shared chimney. Air supply via an air supply line that is independent from the chimney system. This design requires a wind protection device. If a protective grating is fitted, you must ensure that the mesh size is sufficiently large to prevent a significant loss of pressure and/or seal from dirt. The second index “2” (C42 / C82) indicates type C boilers with a blower fan behind the combustion chamber or the heat exchanger. Fröling Heizkessel- und Behälterbau Ges.m.b.H, Industriestraße 12, A-4710 Grieskirchen, Austria Tel +43 (0) 7248 606-0 Fax +43 (0) 7248 606-600 [email protected] www.froeling.com Page 9 M0930811 1 General Standards, personnel, design When dimensioning pipe bends in the supply air line you should note that: The ratio of the radius of curvature (r) to pipe diameter (d) should be greater than 1: r:d ≥ 1 For example P4 Pellet 8/15: - Diameter of supply air connection = 80 mm - Minimum radius of pipe bends = 80 mm Install the supply air line in as straight a line as possible and over the shortest path. The number of pipe bends should be kept to a minimum (ideally a maximum of 4 bends). Also: The resistance of the supply air line can be a maximum of 20 Pa. You can find the necessary dimensions of the supply air connections in the boiler in the technical data sheets. À See 2.2.1 Supply air connections for room air-independent operation Minimum specification of connection lines Connecting piece for the combustion air supply as per EN 1856-2: EN 1856-2 - T080 - N2 - D Connecting piece for the flue gas outlet as per EN 1856-2: EN 1856-2 - T200 - P1 - W TXXX N2 P1 D W ... ... ... ... ... Temperature class (specified in °C) Pressure class with test pressure = 20 Pa Pressure class with test pressure = 200 Pa Condensation resistance not required (dry) Condensation resistance required (damp) 1.4.7 Notes on boiler ventilation The boiler system should be set up rising slightly towards the back left, so the ventilation connection is the highest point of the boiler. Fitting a functioning, automatic ventilating valve ensures constant removal of air in the boiler. This prevents malfunctions due to air in the boiler system. Fit an automatic ventilating valve! Tip: Fit a vertical pipe before the automatic ventilating valve as a calming section, to ensure it is positioned above the level of the boiler water. A microbubble separator can also optionally be fitted in the lines to the boiler. Page 10 M0930811 v 2 Technology Components, connections, and dimensions 2 Technology 2.1 Components and Connections 4 5 6 1 G E F 3 D B 2 C A Pos. Description Units A Boiler flow connection B Boiler return connection C Drain D Air vent E Pellet suction line F Return-air line G Flue gas pipe connection 1 Lambdatronic P 3200 control 2 Switch box 3 Induced draught fan 4 Safety temperature limiter - STL 5 Main switch 6 Service interface Inch mm 8 / 15 20 / 25 32 / 38 48/60 80/100/105 1 6/4 6/4 6/4 2 1 6/4 6/4 6/4 2 1/2 1/2 1/2 1/2 1 1/2 1/2 1/2 1 1 DA 60 DA 60 DA 60 DA 60 DA 60 130 130 150 150 200 Fröling Heizkessel- und Behälterbau Ges.m.b.H, Industriestraße 12, A-4710 Grieskirchen, Austria Tel +43 (0) 7248 606-0 Fax +43 (0) 7248 606-600 [email protected] www.froeling.com Page 11 M0930811 2 Technology Components, connections, and dimensions 2.2 Dimensions Dimension Description L Length, boiler L* Length, boiler L1 Total length inc. induced draught fan L1* Total length inc. induced draught fan B * B W1 H Units mm Width of boiler Width, boiler, inc. support for positioning unit 1) mm Total width, inc. suction cyclone Height, boiler 2) 8 / 15 20 / 25 740 740 940 32 / 38 48 / 60 80/100/105 820 900 1000 1020 1100 1070 940 600 770 860 1030 1235 705 875 965 1275 1480 1185 1355 1445 1790 2085 1280 1280 1430 1585 1710 H1 Total height, inc. suction cyclone 1660 1660 1900 1900 1900 H2 Height, flue pipe connection 1350 1350 1530 1685 1785 H3 Height, flow connection 460 460 460 515 520 H4 Height, return connection 940 955 1085 1240 1360 H5 Height, drainage connection 460 460 460 515 520 H6 Height, ventilation connection 1030 1030 1155 1310 1430 H8 Height, induced draught fan connection 1090 1090 1215 1375 1495 Height, suction system connection 1480 1480 1720 1720 1720 130 130 150 150 200 H15 Flue pipe diameter mm mm 1) Corresponds to the minimum positioning width after removing the stoker assembly, suction cyclone and positioning unit. 2) Corresponds to the minimum positioning height after removing the stoker assembly, suction cyclone and positioning unit. Page 12 M0930811 v 2 Technology Technical specifications 2.2.1 Supply air connections for room air-independent operation 315 215 230 100 P4 Pellet 80 / 100 P4 Pellet 48 / 60 P4 Pellet 32 / 38 305 P4 Pellet 20 / 25 235 P4 Pellet 8 / 15 115 115 170 190 P4 Pellet Description Units 8/15 20/25 32/38 48/60 80/100/105 Supply air connection pipe (external diameter) mm 80 100 125 160 200 2.2.2 Flue gas pipe position P4 Pellet Description Units 8/15 20/25 32/38 48/60 80/100/105 A – Lateral distance mm 420 585 650 815 1000 B – Depth distance mm 90 90 85 90 80 Fröling Heizkessel- und Behälterbau Ges.m.b.H, Industriestraße 12, A-4710 Grieskirchen, Austria Tel +43 (0) 7248 606-0 Fax +43 (0) 7248 606-600 [email protected] www.froeling.com Page 13 M0930811 2 Technology Technical specifications 2.3 Technical specifications 2.3.1 P4 Pellet 8/15/20/25 P4 Pellet Description Rated heat output Heating efficiency range Units kW 8 15 20 25 10,5 14,9 20,0 25,0 3.1-10.5 3.1-14.9 6.0-20.0 7.5-25.0 Mains connection 230V / 50Hz fused 16A Output W 96 123 110 110 Boiler weight kg 350 350 430 430 L 70 70 80 80 mbar 4.3 6.1 4.5 2.9 Boiler capacity (water) Upstream resistance (ΔT=20°C) Min. boiler return temperature Maximum boiler temperature setting Minimum boiler temperature setting Permitted operating pressure Not applicable due to internal return temperature control °C bar Boiler class Permitted fuel 80 80 80 80 40 40 40 40 3 3 3 3 3 3 3 3 Wood pellets Ø 6mm as per ÖNORM M 7135 / DIN 51731 Test report data TÜV Austria1) Testing institute Test report no. 06-UWC Wels-EX295/2 2) 3) 2) 4) 06-UWC Wels-EX295/1 Test data at rated load Carbon monoxide (CO) [mg/MJ] 24 39 35 30 Nitrogen oxide (NOx) [mg/MJ] 74 74 76 78 Organic Hydrocarbons (OGC) [mg/MJ] < 1.0 0.6 0.7 0.9 Dust [mg/MJ] 14 12 11 11 91.6 90.9 91.9 92.9 Boiler efficiency rating [%] Test data at partial load Carbon monoxide (CO) [mg/MJ] 77 77 72 66 Nitrogen oxide (NOx) [mg/MJ] 69 69 71 73 Organic Hydrocarbons (OGC) [mg/MJ] 1.4 1.4 1.3 1.1 Dust [mg/MJ] 11 11 11 10 92.0 92.0 93.3 94.5 Boiler efficiency rating [%] 1) TÜV Austria, Environment and Chemistry Division, Am Thalbach 15, A-4600 Thalheim/Wels 2) In accordance with ÖNORM / DIN EN 303-5, chapter 5.1.3 type test: for a boiler from a range with a consistent structure it is sufficient, if the ratio of rated heat output from the largest to the smallest boiler ≤ 2 : 1, to carry out the tests with the smallest and the largest boilers. The boiler manufacturer must ensure that all boilers, including those that have not been tested in a range, whose values have been determined depending on rated heat output by interpolation, fulfil the requirements of the norm. 3) Values of the type P4 Pellet 20 are interpolated between the test protocol 06-UWC/Wels-EX-295/1 and K44302/2. 4) Values of the type P4 Pellet 25 are interpolated between the test protocol 06-UWC/Wels-EX-295/1 and K44302/2. Page 14 M0930811 v 2 Technology Technical specifications 2.3.2 P4 Pellet 32/38/48/60 P4 Pellet Description Rated heat output Heating efficiency range Units kW 32 38 48 60 32,0 38,0 48,0 58,5 8.9-32.0 8.9-38.0 14.4-48 17.3-58.5 Mains connection 230V / 50Hz fused 16A Output W 110 110 120 120 Boiler weight kg 530 530 760 760 L 125 125 170 170 mbar 1.5 2.1 3.6 5.3 Boiler capacity (water) Upstream resistance (ΔT=20°C) Min. boiler return temperature Maximum boiler temperature setting Minimum boiler temperature setting Permitted operating pressure Not applicable due to internal return temperature control °C bar Boiler class Permitted fuel 80 80 80 80 40 40 40 40 3 3 3 3 3 3 3 3 Wood pellets Ø 6mm as per ÖNORM M 7135 / DIN 51731 Test report data TÜV SÜD SZA1) Testing institute Test report no. K44302/6 3) 4) K44302/4 - TÜV2) 08-UWC/ Wels-EX-337 Test data at rated load Carbon monoxide (CO) [mg/MJ] 31 45 25 5 Nitrogen oxide (NOx) [mg/MJ] 79 77 77 77 Organic Hydrocarbons (OGC) [mg/MJ] 1.0 1.0 1.5 <2 Dust [mg/MJ] 10 9 10 11 93.5 92.6 92.4 92.1 Boiler efficiency rating [%] Test data at partial load Carbon monoxide (CO) [mg/MJ] 61 61 36 10 Nitrogen oxide (NOx) [mg/MJ] 75 75 71 66 Organic Hydrocarbons (OGC) [mg/MJ] 1.0 1.0 1.5 <2 Dust [mg/MJ] 10 10 10 10 95.7 95.7 94.0 92.3 Boiler efficiency rating [%] 1) TÜV SÜD SZA Austria, Technische Prüf-GmbH, accredited initial and boiler inspection body in accordance with BGBl. no. 211/92 Arsenal, Object 207, A-1030 Wien 2) TÜV Austria, Environment and Chemistry Division, Am Thalbach 15, A-4600 Thalheim/Wels 3) In accordance with ÖNORM / DIN EN 303-5, chapter 5.1.3 type test: for a boiler from a range with a consistent structure it is sufficient, if the ratio of rated heat output from the largest to the smallest boiler ≤ 2 : 1, to carry out the tests with the smallest and the largest boilers. The boiler manufacturer must ensure that all boilers, including those that have not been tested in a range, whose values have been determined depending on rated heat output by interpolation, fulfil the requirements of the norm. 4) Values of the model, P4 Pellet 48, are interpolated between the test protocol K44302/4 and 08-UWC/Wels-EX-337. Fröling Heizkessel- und Behälterbau Ges.m.b.H, Industriestraße 12, A-4710 Grieskirchen, Austria Tel +43 (0) 7248 606-0 Fax +43 (0) 7248 606-600 [email protected] www.froeling.com Page 15 M0930811 2 Technology Technical specifications 2.3.3 P4 Pellet 80/100/105 P4 Pellet Description Rated heat output Heating efficiency range Units kW 80 100 105 80,0 100,0 105,0 24,0-80,0 30-100,0 24,0-105,0 Mains connection 230V / 50Hz fused 16A Output W 115 112 112 Boiler weight kg 1090 1100 1100 L 280 280 280 mbar 4,3 4,3 4,3 Boiler capacity (water) Upstream resistance (ΔT=20°C) Min. boiler return temperature Maximum boiler temperature setting Minimum boiler temperature setting Permitted operating pressure Not applicable due to internal return temperature control °C bar Boiler class Permitted fuel 80 80 80 40 40 40 3 3 3 3 3 3 Wood pellets Ø 6mm as per ÖNORM M 7135 / DIN 51731 Test report data TÜV1) Testing institute TÜV2)3) Test report no. 10-UW/WelsEX-242/1 Test data at rated load Carbon monoxide (CO) [mg/MJ] 6 6 6 Nitrogen oxide (NOx) [mg/MJ] 80 83 83 Organic Hydrocarbons (OGC) [mg/MJ] <1,5 <1 <1 Dust [mg/MJ] 12 13 13 93,2 94,3 94,3 Boiler efficiency rating [%] Test data at partial load Carbon monoxide (CO) [mg/MJ] 29 29 29 Nitrogen oxide (NOx) [mg/MJ] 62 62 62 Organic Hydrocarbons (OGC) [mg/MJ] <1 <1 <1 Dust [mg/MJ] 10 10 10 93,7 93,7 93,7 Boiler efficiency rating [%] 1) TÜV Austria, Environment and Chemistry Division, Am Thalbach 15, A-4600 Thalheim/Wels 2) In accordance with ÖNORM / DIN EN 303-5, chapter 5.1.3 type test: for a boiler from a range with a consistent structure it is sufficient, if the ratio of rated heat output from the largest to the smallest boiler ≤ 2 : 1, to carry out the tests with the smallest and the largest boilers. The boiler manufacturer must ensure that all boilers, including those that have not been tested in a range, whose values have been determined depending on rated heat output by interpolation, fulfil the requirements of the norm. 3) Values of the model, P4 Pellet 80, are interpolated between the test protocol 08-UW/Wels-EX-337 and 10-UW/Wels-EX242/1. Partial load data from test protocol 10-UW/Wels-EX242/1 Page 16 M0930811 v 2 Technology Technical specifications 2.3.4 Airborne sound level The sound level specified in the following table is based on sound measurements on a P4 Pellet 15. (measuring device: Omega HHSL 1) The sound level of the individual units was plotted at a distance of 1 m from the sound source. Ambient level for measurement: 32 dBA Unit Measurement Units in continuous operation: Induced draught fan (activation: 50%) 41 dBA Induced draught fan (activation: 65%) 44 dBA Induced draught fan (activation: 90%) 50 dBA Units in non-continuous operation: Suction turbine 68 dBA Grate motor 42 dBA Stoker motor / Stoker screw 33 dBA Ignition fan 53 dBA WOS motor / WOS system 60 dBA Burn back slide valve actuator (open) 34 dBA Burn back slide valve actuator (close) 50 dBA Please note that all the measurements were taken in-house and do not come from a certified test station. This data should therefore be viewed as individual measurements to be used as guidelines. Please also note the sound levels required in the standards listed below, which must be fulfilled by planning and construction measures: ÖNORM B 8115-2 Sound insulation and room acoustics in building construction - Requirements for sound insulation ÖNORM H 5190 Heating systems - Acoustic insulation Fröling Heizkessel- und Behälterbau Ges.m.b.H, Industriestraße 12, A-4710 Grieskirchen, Austria Tel +43 (0) 7248 606-0 Fax +43 (0) 7248 606-600 [email protected] www.froeling.com Page 17 M0930811 3 Installation Transport and Setup 3 Assembly 3.1 Transportation Do NOT use forklifts for this task! The boiler is delivered packed in cardboard and on a pallet. Move without jarring or jolting Protect the packaging against damp Consult the delivery information on the packaging. Observe the centre of gravity of the pallet! The boiler is marked opposite the lifting side with a sticker. 3.1.1 Positioning U Position a lifting truck or similar lifting device at the pallet and position the boiler If it is not possible to position the boiler on the pallet: U Remove the cardboard and remove the boiler from the pallet À See 3.2.1 Removing the boiler from the pallet If the boiler must be dismantled for positioning: U Dismantle the components of the boiler until it can be brought into position À See 3.3 Dismantling for location where positioning is difficult For positioning using a crane: Remove the insulating cover, the WOS cover and the heat exchanger cover The hoisting point for the crane eye is below the cover. U 3.1.2 Temporary storage If the system is to be installed at a later date: Store the boiler, insulation and control unit in a safe, dust-free, and dry location Moisture and frost reduce the effectiveness of insulation and can destroy electronic components. U Page 18 M0930811 v 3 Installation Transport and Setup 3.2 Set-up in the boiler room 3.2.1 Removing the boiler from the pallet U U Remove packing bands with an appropriate tool Pull off the cardboard from above 1 2 U U 1 Remove the transport covers (1) of the ash drawers (P4 Pellet 8-25) or insulated door(s) and ash bucket (P4 Pellet 32-105) and cleaning devices (2) Remove the protective casing On the front of the boiler, P4 Pellet 8/15/20/25: U Open the insulating door U Remove securing devices used during transportation on the left and right side of the base. U Pull out the lock bolt of the door hinge (1) and remove it from the guide U Remove the insulated door and pull out the floor insulation On the front of the boiler, P4 Pellet 32/38/48/60/80/100/105: Remove securing devices used during transportation on the left and right side of the base. U Remove 2 screws each on the left and right of the ash collecting plate and remove the collecting plate U Pull out the floor insulation behind U At the back of the boiler: Remove securing devices used during transportation on the left and right side of the base. U Fröling Heizkessel- und Behälterbau Ges.m.b.H, Industriestraße 12, A-4710 Grieskirchen, Austria Tel +43 (0) 7248 606-0 Fax +43 (0) 7248 606-600 [email protected] www.froeling.com Page 19 M0930811 3 Installation Transport and Setup 3.2.2 Moving the boiler in the boiler room U U Position a lifting truck or similar lifting device with an appropriate load-bearing capacity at the base frame of the boiler and move to the specified place Set up boiler at intended location Put red boiler underlays under the frame. Observe the minimum distances in the boiler room. 3.2.3 Minimum distances in the boiler room P4 Pellet Description Units 8/15 20/25 32/38 48/60 80/100/105 A Minimum distance to suction cyclone assembly 300 300 300 300 300 B Induced draught fan maintenance area 300 300 300 300 300 C Space for insulated door 550 720 830 490 590 Space requirement with plug-in insulated door 400 400 300 - - Minimum distance to side of boiler 200 200 200 200 200 D Page 20 M0930811 mm v 3 Installation Transport and Setup 3.3 Dismantling for location where positioning is difficult If the boiler cannot be brought into position because the space is confined, it is possible to dismantle individual components. The following steps show the maximum possible dismantling steps. You should only carry out the steps that are necessary for positioning. 3.3.1 Dismantling the stoker assembly and insulation U U U U Remove the locking screws on the sound insulation hood of the stoker assembly and remove the sound insulation hood. Lift the front part of the stoker assembly upwards and remove. Lift the back part of the stoker assembly upwards and remove Remove insulating cover Fröling Heizkessel- und Behälterbau Ges.m.b.H, Industriestraße 12, A-4710 Grieskirchen, Austria Tel +43 (0) 7248 606-0 Fax +43 (0) 7248 606-600 [email protected] www.froeling.com Page 21 M0930811 3 Installation Transport and Setup U U U U Page 22 M0930811 Unscrew the screws under the insulated cover with the contact washers at the flaps of the controller cover. Open insulated door (only for P4 Pellet 8/15/20/25) Unscrew the screw together with the contact washer on the bottom side of the controller cover Remove the controller cover v 3 Installation Transport and Setup 3.3.2 Remove the door and ash drawer (P4 Pellet 8/15/20/25) U U Fold out the hinge pins at the top of the insulated door and pull down Lift the insulated door from the lower hinge and remove U Open both ash doors and remove the ash drawer together with accessories U You can optionally remove the upper cover of the settling chamber and the inner cover Fröling Heizkessel- und Behälterbau Ges.m.b.H, Industriestraße 12, A-4710 Grieskirchen, Austria Tel +43 (0) 7248 606-0 Fax +43 (0) 7248 606-600 [email protected] www.froeling.com Page 23 M0930811 3 Installation Transport and Setup 3.3.3 Dismantling the suction cyclone cover U Remove the covering of the middle cable duct At the pellet module: U Unplug the relevant plugs: - “Suction unit M3” - “Max level S1” - “Gate valve M8” U U Page 24 M0930811 Separate the cable tie at the cable leadthrough Unthread the cables that have been unplugged v 3 Installation Transport and Setup U U Wind up the unplugged cables at the units Open the clamps and take off the cover 3.3.4 Dismantling the stoker unit U Remove the covering of the cable duct At the pellet module: U Unplug the relevant plugs: - “Grate drive M6” - “Burn back flap M7” - “Stoker motor M1” - “Ignition E1” U Unthread the cables of the unplugged units Fröling Heizkessel- und Behälterbau Ges.m.b.H, Industriestraße 12, A-4710 Grieskirchen, Austria Tel +43 (0) 7248 606-0 Fax +43 (0) 7248 606-600 [email protected] www.froeling.com Page 25 M0930811 3 Installation Transport and Setup U U U Remove the back and front locking split pin of the grate drive and pull out the bolt CAUTION! Secure the grate motor so it cannot fall down when the bolt is removed. U Push the bushing back at the grate rod Remove the grate motor U Page 26 M0930811 Loosen the locking screw on the ignition fan Take out the ignition fan v 3 Installation Transport and Setup U Depending on the design, cut open the aluminium band from the heat insulation mat below the stoker duct and remove U Remove two screw connections on the right and left at the stoker unit flange The screws can be removed completely as the stoker unit is hung on the boiler on two hooks. The following assembly step requires two people: Weight of stoker unit P4 Pellet 8/15/20/25: approx. 32 kg Weight of stoker unit P4 Pellet 32/38: approx. 36 kg Weight of stoker unit P4 Pellet 48/60: approx. 46 kg Weight of stoker unit P4 Pellet 80/100/105: approx. 68 kg U Pull the stoker unit up slightly until the hooks come out of the stoker flange U Tip the unit back slightly and lift away The P4 Pellet is fully dismantled and can now be brought into position. Fröling Heizkessel- und Behälterbau Ges.m.b.H, Industriestraße 12, A-4710 Grieskirchen, Austria Tel +43 (0) 7248 606-0 Fax +43 (0) 7248 606-600 [email protected] www.froeling.com Page 27 M0930811 3 Installation Transport and Setup 3.3.5 Positioning dimensions after dismantling P4 Pellet Dimension Description L Length, boiler B Width of boiler H Height of boiler Units mm 8/15 20/25 32/38 48/60 1) 80/100/105 740 740 740 820 9102) 705 875 965 1275 1480 1280 1280 1430 1585 1710 1) If the control unit is dismantled, the dimension can be reduced to 780 mm (e.g. for bringing into position through doors with a clearance of 800 mm) 2) If the control unit is dismantled, the dimension can be reduced to 880 mm (e.g. for bringing into position through doors with a clearance of 900 mm) Dismantling the control unit: U U U U Page 28 M0930811 Remove the lateral plexiglass covers and secure the nuts of the screw connection so they cannot turn Remove the screws on the left and right on the underside Remove the cable marked “Display” and pull up and out Remove the control unit v 3 Installation Transport and Setup 3.3.6 Notes on reassembly U After positioning the boiler, assemble in reverse order It is particularly important to observe the following points during assembly: U Depending on the design of the insulation, after fitting the stoker unit and the insulating material it may be necessary to stick a new aluminium band on top of the aluminium band that was previously cut. When fitting the grate motor, check that it is in the correct position on the back support: - Top position = P4 Pellet 8/15/20/25 Bottom position = P4 Pellet 32/38 A position = P4 Pellet 48/60/80/100/105 Observe the installation position of the actuating sleeve between the grate motor and the slide rod U Carefully screw in the locking screw finger-tight You must not carry on tightening to the extent that the ignition fan pipe is deformed Fix the cable with the cable ties supplied. There must not be any loose cables in the area of the igniter. Only connect the power supply after completing assembly. The individual units should be checked by the qualified technician and adjusted if necessary during initial start-up. Fröling Heizkessel- und Behälterbau Ges.m.b.H, Industriestraße 12, A-4710 Grieskirchen, Austria Tel +43 (0) 7248 606-0 Fax +43 (0) 7248 606-600 [email protected] www.froeling.com Page 29 M0930811 3 Installation Assembling the Pellet Boiler 3.4 Assembling the Pellet Boiler 3.4.1 Installing the induced draught fan U U Remove the locking screws on the sound insulation hood of the stoker assembly and remove the sound insulation hood. Open the clamps on the suction cyclone container and lift the cover ´ The induced draught set is in the suction cyclone container U Remove the induced draught fan from the suction cyclone container U Remove pre-installed cover plate Unscrew pre-installed nuts and spacer washers Attach and fix the ID fan as illustrated The straight edge of the tube flange must be at the top. U U 1 U U Page 30 M0930811 Join both cables of the ID fan with the pre-installed cables Ensure that the locking device (1) clicks into place. Push the cable behind the cladding and put back the cover plate. v 3 Installation Assembling the Pellet Boiler 3.4.2 Fit the ash container and doors (P4 Pellet 32/38/48/60/80/100/105) U Remove the insulating cover and unscrew the two top retaining screws with the contact washers of the controller cover Caution: Do not lose the contact washers! U Unscrew the lower retaining screw with contact washer and remove the controller cover U Put the insulated door in the boiler base and secure at the top with bolts Take the two cover caps for the ash containers from the ash containers and position them in the open flaps U U Put in the ash containers and secure with the locking lever Fröling Heizkessel- und Behälterbau Ges.m.b.H, Industriestraße 12, A-4710 Grieskirchen, Austria Tel +43 (0) 7248 606-0 Fax +43 (0) 7248 606-600 [email protected] www.froeling.com Page 31 M0930811 3 Installation Install discharge system 3.5 Installing the discharge system 3.5.1 General installation information NOTICE Water lines should not be located in close proximity to the pellet store and the feeder units due to the dangers posed by condensation and bursting water pipes! Check the delivered items for foreign objects in the individual components In the pellet store room an impact cushion must be installed on the opposite side to the filler pipes. This reduces wear on the pellets when they are blown in and stops the finish being worn off. Broken pieces of masonry or finish and other foreign bodies (small stones, pieces of wood, screws, etc.) can block the discharge system or the pellet feed into the boiler and cause the system to fail. In case of faults due to such foreign bodies, the guarantee is void. In time pellets leave dust on the ground; this can impair the process of moving them from the pellet storage area. For this reason you should check and clean if necessary before refilling. 3.5.2 Hose Lines For the hose lines used with the suction device, the universal suction system, and the bag silo discharge unit, observe the following: Do not kink the hose lines! Minimum bending radius = 30cm Lay the hose lines as straight as possible! If the lines are sagging, it can lead to so-called “pockets.” Problem-free pellet feeding can not be guaranteed. Lay the hose lines in short segments away from walking areas! Hose lines are not UV-proof! Therefore: do not lay the hose lines outdoors! Hose lines are suitable for temperatures up to 60°C! Therefore: Hose lines must not come into contact with flue gas pipes or uninsulated heating pipes! Hose lines must be grounded on both ends, to ensure that no static charge builds up as a result of transporting the pellets! The suction line must be a single piece! The return-air line can be made up of several pieces, but potential equalization must be established throughout the line! Page 32 M0930811 v 3 Installation Install discharge system Potential Equalisation When connecting the hose lines to the individual connection pipes, ensure there is potential equalization throughout the line! U Expose approximately 3 cm of the grounding strap on the end of the hose line TIP: Slit the insulation open along the wire with a knife U Bend the earth wire inwards in a loop ´ This prevents the earth wire from being damaged by the feed of pellets. U Install a hose clamp on the hose line Put the hose line on the connection U Ensure that contact is established between the grounding strap and the connection! U Tighten the hose clamp Fröling Heizkessel- und Behälterbau Ges.m.b.H, Industriestraße 12, A-4710 Grieskirchen, Austria Tel +43 (0) 7248 606-0 Fax +43 (0) 7248 606-600 [email protected] www.froeling.com Page 33 M0930811 3 Installation Install discharge system 3.5.3 Universal suction system F J A G B H D G A B I K E Variant 2 Eco pellet box B C Variant 1 Komfort pellet box A 25 m Suction hose G Manual re-arranging unit (Variant 2) B Hose clamps 50-65 mm H 2 x Blind plates (Variant 2) C 2 x Fire protection choke collars (only in Austria) I 6 x Star-shaped screw knobs (Variant 2) D Komfort pellet box (Variant 1) J Cover plate for wall E Support for fire protection choke collar (Variant 1) K Suction probe F Installation module for wall 50 50 250 250 A Page 34 M0930811 280 280 Before installation: U Prepare a wall penetration for the pellet box (width: 28cm, height: 25cm) Maintain a distance of at least 5 cm from the finished floor. Dimensions in mm v 3 Installation Install discharge system Variant 1 – Komfort pellet box U Position Komfort pellet box (D) at the wall penetration The distance from the wall on the board side of the pellet box should be at least 10 cm for maintenance purposes. 10 cm U Fix Pellet box to the wall with 4 M8x50 frame screws and 10 mm dowels U Fill the space in the wall penetration with a nonflammable material The partition must be insulated as per ÖNORM B 3836 or DIN 4102-11! D J Put the cover plate for the wall (J) onto the pipes of the pellet box U Secure the cover plate to the wall using 4 M8x50 frame screws and 10 mm dowels U U Mount the bracket (E) for fire protection choke collars on the pellet box Fire protection choke collars only in Austria. E Fröling Heizkessel- und Behälterbau Ges.m.b.H, Industriestraße 12, A-4710 Grieskirchen, Austria Tel +43 (0) 7248 606-0 Fax +43 (0) 7248 606-600 [email protected] www.froeling.com Page 35 M0930811 3 Installation Install discharge system Variant 2 – Eco pellet box U F U U Fill the space in the wall penetration with a nonflammable material The partition should be insulated in accordance with ÖNORM B 3836 or DIN 4102-11. U Place the wall cover plate (J) on the insertion module pipes Secure the cover plate to the wall using 4 M8x50 frame screws and 10 mm dowels J U H I G Page 36 M0930811 Place the wall insertion module (F) at the wall penetration Secure the insertion module to the wall using 4 M8x50 frame screws and 10 mm dowels U Install 2 blind plates (H) on the insertion module using 2 star-shaped screw knobs (I) U Install interchange unit (G) using 2 star-shaped screw knobs No position is specified for the interchange unit! v 3 Installation Install discharge system Installing the suction probes and lines A B K Position the suction probes (K) at equal distances in the pellet supply bin U Secure the suction probes to the bottom using frame screws U Fix hose lines (A) to the suction probe using hose clips (B) U Lay the hose lines to the pellet box and secure them using hose clips U B A B CAUTION! Read the label on the suction probe or pellet box about the suction line and return-air line! Ensure correct connection! CAUTION! When connecting the hose lines, beware of potential equalisation! À Page 33, Potential Equalisation À For information on store layout see 3.5.6 Pellet storage area C A Thread the fire protection choke collar (C) on to the hose line (A) Fire protection choke collars only in Austria. U Attach the hose lines to the pellet box pipes using hose clips (B) U U B CAUTION! Read the label on the suction probe or pellet box about the suction line and return-air line! Ensure correct connection! C A 1 2 Lay the hose lines to the boiler, through identified openings at the back plate and install with hose clamps to the identified connections Suction line: hose line to left connection (1) on the back of the boiler Return-air line: hose line to right connection (2) on the back of the boiler CAUTION! When connecting the hose lines, beware of potential equalisation! À Page 33, Potential Equalisation Fröling Heizkessel- und Behälterbau Ges.m.b.H, Industriestraße 12, A-4710 Grieskirchen, Austria Tel +43 (0) 7248 606-0 Fax +43 (0) 7248 606-600 [email protected] www.froeling.com Page 37 M0930811 3 Installation Install discharge system 3.5.4 Suction screw system G J H I N M K F D E L C B A A Flange bearing H Gearbox flange B Ejector flange I Drive flange seal C Trough mount with rubber pad J Geared motor D Bearing flange K 2 x Cover plates for wall penetration E Open trough L Main worm F Suction intake with integrated support M Shaft end for main worm G Proximity switch N Worm extension (if needed) Before installation: Prepare wall penetration for suction piece (width: 34cm, height: 20cm) Ensure that the channel in the wall penetration is positioned off centre. U Page 38 M0930811 v 3 Installation Install discharge system U H1 U J U I U L Thread the basic screw (H1) into the penetration The key-way must be toward the boiler! Thread the closed trough (J) onto the basic screw on the store side The quadratic flange points out of the store! Thread the open trough (I) onto the basic screw Secure together using 4 M10x30 hexagonal bolts and nuts Depending on the length of the discharge unit, a screw extension may be necessary: U Place the screw extension (N) on the basic screw (L) and secure it using spring dowels N The screw blade must always be rising. L If no additional screw is used: U Put the the end of the basic screw shaft (M) on the basic screw shaft (L) and secure it using spring dowels M J U U U G I U H U G Secure the gearing flange (I) and the gearing flange seal (H) to the suction piece using 4 hexagonal M10 x 40 mm bolts and nuts - 17 mm hexagonal nut Lubricate the screw stub shaft Put on the geared motor (J) Take care when inserting the key-way into the groove of the shaft! Attach the geared motor on the gearing flange (l) using 4 M8 x 16 mm hexagonal bolts with spacer washers - Hexagonal nut dimension 13 mm Install the proximity switch (G) on the inspection cover of the suction piece The proximity switch should project approx. 1cm into the suction piece Adjusting the sensitivity during the initial start-up À Page 47, 4.2 Setting the “Max level and min level” sensor Fröling Heizkessel- und Behälterbau Ges.m.b.H, Industriestraße 12, A-4710 Grieskirchen, Austria Tel +43 (0) 7248 606-0 Fax +43 (0) 7248 606-600 [email protected] www.froeling.com Page 39 M0930811 3 Installation Install discharge system U U D B C A U U U U K U U D 1 Page 40 M0930811 B Secure the bearing flange (D) and the trough mount (C) to the trough using 4 hexagonal M10 x 40 mm bolts and nuts - Hexagonal nut SW 17 mm Place the flange bearing unit (A) and the ejecting flange (B) on the shaft and secure them to the bearing flange using 2 M14 x 35 mm hexagonal bolts and spacer washers - 21 mm socket spanner Do not lubricate! The flange bearing is permanently lubricated and is maintenance free! Arrange the trough parallel to the store wall Secure the trough mount and suction piece to the floor using 2 10 mm dowels and 8 x 70 mm frame screws Fill the space in the wall penetration with a nonflammable material The partition must be insulated as per ÖNORM B 3836 or DIN 4102-11! Secure the wall penetration cover plates (K) to the external store wall using 3 10 mm dowels and 8 x 50 mm frame screws Finally, the inclined bottom is installed The plates of the inclined bottom must not be placed on the trough! À Page 44, Sloping floor Lay both hose lines in the boiler room to the suction intake On the left and right of the suction intake: U Secure the suction hose (B) to the suction connecting piece using a hose clamp (D) No connection side specified for suction or return-air line! U Put the supplied fire protection choke collar (1) on the hose and secure it to the suction piece using 2 self-tapping screws Fire protection choke collars only in Austria. v 3 Installation Install discharge system U 1 2 Lay the hose lines to the boiler, through identified openings at the back plate and install with hose clamps to the identified connections Suction line: hose line to left connection (1) on the back of the boiler Return-air line: hose line to right connection (2) on the back of the boiler CAUTION! When connecting the hose lines, beware of potential equalisation! À Page 33, Potential Equalisation 3.5.5 Bag silo discharge system U Fit frame with bag silo À See assembly instructions “Pellet bag silo Type I - V” Observe the height of the boiler room during planning. H H1 H2 Bag silo frame height Height including filler coupling 1) Required minimum room height Ideal store room height 2) Type I, II Type III - V [cm] 185 190 [cm] 205 210 [cm] [cm] 215 230 220 230 1) Minimum room height for connection to filler pipe in installation room. 2) When full, the bag silo has a heap shape. Optimum height is for use of the whole capacity. Fröling Heizkessel- und Behälterbau Ges.m.b.H, Industriestraße 12, A-4710 Grieskirchen, Austria Tel +43 (0) 7248 606-0 Fax +43 (0) 7248 606-600 [email protected] www.froeling.com Page 41 M0930811 3 Installation Install discharge system U Fit the bag silo in accordance with the assembly instructions supplied U Put the flange ring (1) onto the bag silo Put the bag silo and flange ring onto the probe at the threaded bolts and screw them together 1 U U D U U Thread one fire protection choke collar each (B) onto the suction and return-air lines Fire protection choke collars only in Austria. Run hose lines through the openings in the wall into the pellet store Secure the hose lines to the silo suction probe using hose clamps (D) Read the label on the silo suction probe! Suction line: The hose line to the cover of the suction unit Return-air line: The hose line to the suction motor B U 1 2 Lay the hose lines to the boiler, through identified openings at the back plate and install with hose clamps to the identified connections CAUTION! Observe the label for the suction line and the return-air line on the silo suction probe and boiler. Ensure correct connection! Suction line: hose line to left connection (1) on the back of the boiler Return-air line: hose line to right connection (2) on the back of the boiler CAUTION! When connecting the hose lines, beware of potential equalisation! À Page 33, Potential Equalisation Page 42 M0930811 v 3 Installation Install discharge system 3.5.6 Pellet storage area For the universal suction system, the pellet store must be built with an inclined floor! The following picture shows the most important components: B A C D E F A 2 x Filler pipes B Earth wire C Planking on the store door D Sloping floor E Impact cushion F Under-floor structure for sloping floor Size of store The storage area should be able to hold approximately 1.5 times the annual requirement. The exact amount of required space depends on the system’s heating load. Rule of thumb formula: 1m³ store / kW heating burden Fröling Heizkessel- und Behälterbau Ges.m.b.H, Industriestraße 12, A-4710 Grieskirchen, Austria Tel +43 (0) 7248 606-0 Fax +43 (0) 7248 606-600 [email protected] www.froeling.com Page 43 M0930811 3 Installation Install discharge system Sloping floor Fig.1: Store for a discharge unit with a suction probe Fig.2: Store for a discharge unit with a screw The under-floor structure should be dimensioned so that the sloping floor is not deformed when subjected to static load. You should ensure that the pellets can slide down smoothly. This means the sloped floor should be at an angle of at least 45° and have a smooth surface (we recommend laminate). When planning the under-floor structure, note: 1 m³ of pellets roughly corresponds to a weight of 650 kg! Ideally the suction probes should already be fitted before the sloped floor is constructed. A distance of 20 cm should be maintained between the cross-pieces and the suction probe should be centrally positioned. (see Fig. 1) The weight of the pellets must not be borne by the trough! (see Fig. 2) Impact cushion The baffle plate is made of rubber and is positioned opposite the filling nozzles at a distance of approximately 20 cm from the wall. It prevents pellets from striking the wall and knocking off pieces of the finish when filling. Pieces of the finish, screws, and other foreign objects can clog the suction probe! CAUTION! Damage caused by foreign objects is not covered by the guarantee! NOTICE In time pellets leave dust on the ground; this can impair the process of moving them from the storage area. Check the storage area before re-filling and clean if necessary Regular complete emptying and cleaning of the storage area ensures consistent readiness for operation! Page 44 M0930811 v 3 Installation Connecting the pellet boiler 3.6 Electrical Connection DANGER When working on electric components: Risk of serious injuries from electric shocks U Work on electrical components should only be carried out by authorised technicians Wiring should be installed using flexible sheathed cable and dimensioned in compliance with the locally applicable standards and guidelines The power supply line (mains connection) must be fitted with a C16 A fuse by the customer. U U U U Remove insulating cover 2 pieces Unscrew the retaining screws with contact washers behind the control unit Open the insulated door and remove the centrally positioned retaining screw and contact from below Remove the front insulating cover and wire the connections in accordance with the circuit diagram À Schematic diagrams: See operating instructions “Lambdatronic P 3200” CAUTION When using energy-efficient pumps on the speed-regulated pump outputs: Malfunctions of the boiler and the hydraulic system are possible! Take the following precautions: You must not connect any EC motor pumps at the speedregulated pump outputs of the boards. Observe the additional instructions and information on board outputs in the operation instructions of the boiler controller. Fröling Heizkessel- und Behälterbau Ges.m.b.H, Industriestraße 12, A-4710 Grieskirchen, Austria Tel +43 (0) 7248 606-0 Fax +43 (0) 7248 606-600 [email protected] www.froeling.com Page 45 M0930811 3 Installation Connecting the pellet boiler 3.6.1 Connecting the Komfort pellet box The connection of the Comfort pellet box to the pellet module board is established using a flexible cable (5x0.75mm², e.g. YMM as per ÖVEK41-5 or H05VV-F as per DIN VDE 0281-5). This is a 24V control line. The previous figure shows the plugged-in 5-pin connecting plug of the Komfort pellet box and the accompanying connection layout of the Lambdatronic P3200 control system. To check the plug arrangement: U Detach the protective plate (1) from the board U Perform check using the board’s labels The actuators (2) of the pellet box must be switched to the “R” position! 2 1 The actuators are ready to plug in and are connected to the board. All necessary plug clips are included with the pellet box in delivery Page 46 M0930811 v 4 Commissioning 4 Initial Start-up 4.1 Configuring the Boiler The boiler must be adjusted to the requirements of the heating system during commissioning NOTICE Optimum performance and efficient operation with low emissions can only be guaranteed if the system is set up by a qualified technician and the specified factory settings are observed. Take the following precautions: U We recommend that the system is commissioned by Froling customer services or an authorised installer. Before heating up the boiler for the first time: U Set the controller to match your heating system. The keypad layout and necessary control steps for modifying the parameters can be found in the accompanying operating instructions for the “Lambdatronic P 3200”. 4.2 Setting the “Max level and min level” sensor In delivery configuration, the factory settings of the sensor are secured with a seal. Changes to the settings should only be carried out by qualified technicians. Depending on the design, a min level sensor may also be installed. 2 1 The monitoring LED (1) should only illuminate when identifying materials! U If the monitoring LED stays on permanently, the sensitivity is set too high! ´ Reduce the sensitivity by turning the adjusting screw (2) to the left U If the monitoring LED does not react when pellets are being fed in, the sensitivity is set too low! ´ Increase the sensitivity of the adjusting screw by turning to the right Fröling Heizkessel- und Behälterbau Ges.m.b.H, Industriestraße 12, A-4710 Grieskirchen, Austria Tel +43 (0) 7248 606-0 Fax +43 (0) 7248 606-600 [email protected] www.froeling.com Page 47 M0930811
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement