FINESSE/STANDESSE ComForT (VCF.../VCS4
EN
Esc
Auto
Man
SET TIME
CLEAN RESET
SET TIME SWITCH
FINESSE/STANDESSE Comfort
(VCF.../VCS4..)
with DA Control module (VCS-R-DA-..)
VCS-R-DA-E, VCS-R-DA-V
FULL MANUAL
OPERATION AND MAINTENANCE
2
1. BEFORE YOU BEGIN
Symbols are used in the user’s manual to improve your orientation.
The following table includes their graphical images and meanings:
SYMBOL
MEANING
ATTENTION!
Warning/caution
DO NOT OVERLOOK!
Important instructions
YOU WILL NEED
NOTE
Practical tips and information
TECHNICAL INFORMATION
More detailed technical information
LINK
Refer to other parts/sections
of the manual
Declaration of conformity
Declatarion of confortmity for DA control modules is part of declaration of conformity for air
curtains FINESSE/STANDESSE Comfort . Declaration of conformity is located at www.2vv.cz
2
1. MODULE
1.1 DESCRIPTION OF THE DA CONTROL MODULES
DA control modules are suitable with electric or water heated FINESSE/STANDESSE Comfort air
curtains (VCF-x-xxx-E-.../VCS4x-xxE-…, VCF-x-xxx-V-.../VCS4x-xxV-… )
There are two types of DA control modules:
- VCS-R-DA-V (Suitable with air curtains with water coil VCF-x-xxx-V-.../VCS4-x-xxV-…)
- VCS-R-DA-E (Suitable with air curtain with electric heater VCF-x-xxx-E-.../VCS4-x-xxE-…)
Each type of DA control module can be use for all FINESSE/STANDESSE Comfort output series
(A,B,C)
- Air curtains FINESSE/STANDESSE Comfort are produced with universal connection interface.
- Air curtains FINESSE/STANDESSE Comfort can be controlled by one of following control modules.
- Control modules (SM, DM or DA) are required accessories for FINESSE/STANDESSE Comfort
air curtains (VCF.../VCS4…) and has to be ordered separatelly.
3
2. CONTROLS
2.1 CONTROL PANELS OVERVIEW
LCD
manual / automatic
fan speed
ON/OFF
Esc
Auto
Man
heating
SET TIME
CLEAN RESET
SET TIME SWITCH
Function buttons:
time settings
time switch settings,
service menu settings
Regulation of water coil is provided by mixing valve (MV-3). Regulation of water coil (mixing) is provided from control panel.
Mixing valve (MV-3) is an required accessorie for DA control module (VCS-R-DA-V) and has
to be ordered separately.
4
3. CONTROLS
3.1 MANUAL MODE
3.1-1 Turning the air curtain ON and OFF
ON/OFF
manual / automatic
Esc
Esc
Auto
Man
Auto
Man
SET TIME
CLEAN RESET
SET TIME SWITCH
SET TIME
CLEAN RESET
SET TIME SWITCH
3.1-2 Setting of the fan speed
MAN
Heat:
Fan:
MAN
Heat:
Fan:
MAN
Heat:
Fan:
MAN
Heat:
Fan:
MAN
Heat:
Fan:
MAN
Heat:
Fan:
MAN
Heat:
Fan:
MAN
Heat:
Fan:
Esc
Auto
Man
SET TIME
CLEAN RESET
SET TIME SWITCH
3.1-3 Setting the electric heater
Esc
Auto
Man
SET TIME
CLEAN RESET
SET TIME SWITCH
5
3. CONTROLS
3.1-4 Setting the heating ouput of water coil
MAN
Heat:
Fan:
MAN
Heat:
Fan:
MAN
Heat:
Fan:
MAN
Heat:
Fan:
Esc
Auto
Man
SET TIME
CLEAN RESET
SET TIME SWITCH
Regulation of water coil is provided by mixing valve (MV-3) .
Regulation of water coil is provided from control panel (3 levels – manual mode or fluently
– automatic mode).
The external temperature sensor (included in delivery) has to be connected with VCS-R-DAV module for correct function of automatic mode.
Mixing valve (MV-3) is an required accessorie for DA control module (VCS-R-DA-V) and has
to be ordered separately.
3.2 AUTOMATIC MODE
External temperature sensor (delivered with DA control module) has to be connected for
correct function of automatic mode.
External temperature sensor must be leaded out of building. Placed close to the door opening and away from sunlight!
3.2-1 Choose Automatic/Manual mode
manual / automatic
Esc
Auto
Man
SET TIME
CLEAN RESET
SET TIME SWITCH
6
3. CONTROLS
3.2-2 Set the required temperature (room temperature)
Esc
Auto
Man
AUT
Tem. room: 20°C
Request tem.: 24°C
AUT
Tem. room: 20°C
Request tem.: off
SET TIME
CLEAN RESET
SET TIME SWITCH
Air curtain with DA control module in automatic mode is trying to reach required room
temperature. Electronics calculate outside air temperature, inside air temperature and air
temperature on the outlet from the air curtain. According its calculations is automatically
regulated speed of the fan and heating output of the air curtain.
3.3 TIME SWITCH
- The DA control module has integrated time switch. Time switch is switching ON/OFF air curtain
in preset time period. Setting of time switch is made from control panel.
- There is a week time regime available.
- There are 4 time periods per day available.
- For correct function of time switch it is necessary to set correct time.
3.3-1 Time setting
Mo 15:45
OFF
Esc
Esc
Auto
Man
SET TIME
CLEAN RESET
SET TIME SWITCH
Esc
Auto
Man
Auto
Man
SET TIME
CLEAN RESET
SET TIME SWITCH
SET TIME
CLEAN RESET
SET TIME SWITCH
EXIT
POSITION
VALUE
7
3. CONTROLS
MO - SU
1-4
Time
3.3-2 Time switch settings
MO
1
START_XX:XX
STOP_XX:XX
OFF
Esc
Esc
Auto
Man
SET TIME
CLEAN RESET
SET TIME SWITCH
Esc
Auto
Man
Auto
Man
SET TIME
CLEAN RESET
SET TIME SWITCH
SET TIME
CLEAN RESET
SET TIME SWITCH
EXIT
POSITION
8
VALUE
4. OPERATION WITH EXTERNAL ACCESSORIES
4.1 ACCESSORIE OVERVIEW
Air curtain FINESSE/STANDESSE Comfort with DA control module can be connected with:
Door contact (DK-1)
- Air curtain is switching ON/OFF or is set to “Door contact function” according
to OPEN/CLOSED doors.
Door contact (DK) is suitable with all DA control modules. Behaviour
and setting of air curtain with door contact is described in:
5.1-3 Door contact function
Mixing valve (MV-3)
- It is use for mixing regulation of water for air curtains with water coil.
Mixing valve (MV-3) is suitable for VCS-R-DA-V control module and
VCF-x-xxx-V-.../VCS4x-xxV-... air curtains only.
9
SERVICE MODE
5. SERVICE MODE
The service mode serves for setting-up periods of signaling, the interval of curtain cleaning,
and setup of the behavior of the curtain fan when using a door switch with closed doors.
In „SERVICE MODE“ you be set:
- Door contact function
- Cleaning interval signalization
- Aftercooling of electric heater
5.1 SERVICE MODE SETTINGS
5.1-1 Service mode activation:
OFF
Esc
Esc
Auto
Man
SET TIME
CLEAN RESET
SET TIME SWITCH
Auto
Man
SET TIME
CLEAN RESET
SET TIME SWITCH
5 sec.
5.1-2 Cleaning interval signalization
This function is accessible with activation of the service mode. After activation, the notice SET
TIME TO CLEAN FILTER will appear on the control panel. obr.set time to clean filter
Set time to
clean filter:
Set time to
clean filter:
Set time to
clean filter:
Auto
Man
Set time to
clean filter:
Esc
SET TIME
CLEAN RESET
SET TIME SWITCH
Set time to
clean filter:
10
SERVICE MODE
Symbol
Meaning
Time
Set time to
clean filter:
Without indication interval of
curtain cleaning
---
Set time to
clean filter:
Long-term interval of curtain
cleaning
3000/6000*
Set time to
clean filter:
Medium-term interval of curtain cleaning
1900/2800*
Set time to
clean filter:
Short-term interval of curtain
cleaning
800/1600*
*values for VCS-R-DA-V / VCS-R-DA-E
The selected setup is stored either:
a) automatically after 15 seconds of non-activity
b) by pressing the button
Set time to
clean filter:
Esc
Auto
Man
SET TIME
CLEAN RESET
SET TIME SWITCH
Is displayed on the display:
OFF
Esc
Auto
Man
SET TIME
CLEAN RESET
SET TIME SWITCH
All setup parameters apply for manual as well as automatic mode.
11
SERVICE MODE
5.1-3 Door switch function
Set time to
clean filter:
OFF
Esc
Esc
Auto
Man
Esc
Auto
Man
SET TIME
CLEAN RESET
SET TIME SWITCH
Auto
Man
SET TIME
CLEAN RESET
SET TIME SWITCH
SET TIME
CLEAN RESET
SET TIME SWITCH
5 sec.
1x
Mode door switch
fan level 1
After activation Mode door switch appears on the display.
Esc
Auto
Man
SET TIME
CLEAN RESET
SET TIME SWITCH
With the push of a button[obr. tlačítko ohřevu ] three modes
of operation of the curtain can be set when the doors are
closed:
Mode door switch
fan level 1
Mode door switch
fan level 1
Mode door switch
fan level 2
Esc
Auto
Man
SET TIME
CLEAN RESET
SET TIME SWITCH
12
Mode door switch
off
Symbol
Meaning
Mode door switch
fan level 1
"When doors are closed, the curtain will go to the first speed
of the fan (Default setting from the manufacturer)."
Mode door switch
fan level 2
When doors are closed, the curtain will go to
the second speed of the fan
Mode door switch
off
The curtain will be turned off when the doors are closed
SERVICE MODE
The selected setup is stored either:
a) automatically after 15 seconds of non-activity
b) by pressing the button obr.save
Mode door switch
fan level 1
Esc
Auto
Man
SET TIME
CLEAN RESET
SET TIME SWITCH
Is displayed on the display:
OFF
Esc
Auto
Man
SET TIME
CLEAN RESET
SET TIME SWITCH
All setup parameters apply for manual as well as automatic mode.
5.1-4 Aftercooling function (VCS-R-DA-E only)
Set time to
clean filter:
OFF
Esc
Esc
Auto
Man
Esc
Auto
Man
SET TIME
CLEAN RESET
SET TIME SWITCH
Auto
Man
SET TIME
CLEAN RESET
SET TIME SWITCH
SET TIME
CLEAN RESET
SET TIME SWITCH
5 sec.
2x
After activation After-cooling appears on the display.
after-cooling
30s
after-cooling
30s
Esc
Auto
Man
SET TIME
CLEAN RESET
SET TIME SWITCH
after-cooling
60s
13
SERVICE MODE
5.1-5 Mod BUS (adress setting)
MODBUS address
OFF
Esc
Esc
Auto
Man
Esc
Auto
Man
SET TIME
CLEAN RESET
SET TIME SWITCH
Auto
Man
SET TIME
CLEAN RESET
SET TIME SWITCH
SET TIME
CLEAN RESET
SET TIME SWITCH
5 sec.
VCF-x-.../
VCS4x-..
x press to select
Address is
sending ...
MODBUS address
1-6
Esc
Esc
Auto
Man
SET TIME
CLEAN RESET
SET TIME SWITCH
Power supply OFF
save address
(tone beep confirm)
VCS-R-DA-..
Auto
Man
RF
SET TIME
CLEAN RESET
SET TIME SWITCH
select MODBUS address
1-6
VCF-x-.../
VCS4x-..
MASTER
MODBUS RTU
Power supply ON
Each control module must has its own unique Modbus adress. DA control module allows maximum 6 unique Modbus adresses to be set.
For air curtains controlled by modbus is control panel used only for Modbus adress setting
14
6. DA CONTROL MODULE FUNCTIONS OVERVIEW
Air curtains execution
With electric heater
(VCF-x-xxx-E-.../VCS4x-xxE...)
With water coil
(VCF-x-xxx-V-.../VCS4x-xxV...)
DA
DA
(VCS-R-DA-E)
(VCS-R-DA-V)
Manual/Automatic
Manual/Automatic
Speed of the fan
1/2/3
1/2/3
Electric heater regulation
3 steps / Fluently
x
Control module
Type of control
Water heater regulation
x
Mixing valve
Control panel connection
Radio signal
Radio signal
Number of quick connection sockets
4
2
Door switch behavior
OFF/1st speed / 2nd speed
OFF/1st speed / 2nd speed
Timer
Day/ Week
Day/ Week
Temperature measurement
" 2 internal sensors
1 external sensor"
" 2 internal sensors
1 external sensor"
Operation state indication
LCD
LCD
Radio signal indication
BEEP sound
BEEP sound
Cleaning interval indication
Time interval
Time interval
Water heater anti-frezze protection
x
Automatic
Aftercooling of electric heater
30sec/1min
x
Chaining of the air curtains
In radio signal range
In radio signal range
7. MAINTAINING THE AIR CURTAIN
Before any work is done, the main electrical supply to the air curtain must be shut off!
We recommend that a service inspection be done at least twice a year (in autumn and spring), or
even more often, depending on local conditions. This involves removing dust from the suction
cover and interior areas of the air curtain.
Use a vacuum cleaner to remove dirt from the suction cover and wipe it with a damp cloth.
Also use a vacuum cleaner and damp cloth to remove dirt from the inside and surface of the air
curtain.
Failure to maintain the air curtain may decrease its efficiency and shorten its life!
15
8. TROUBLESHOOTING
8.1 SAFETY ELEMENTS
8.1-1 Preventing the electric heater from overheating
If the electric heater overheats, the safety thermostat will shut it off. Each heating element is
equipped with its own safety thermostat. The electric heater will go back on automatically after
cooling.
If the safety thermostat fails or malfunctions, the emergency thermostat will go on and turn the
heater off permanently. Emergency thermostat is equipped with manual RESET.
• There is no signal when the thermostats are activated. A failure can be recognised by reduced
heater output when the settings panel indicates it should be working.
• When the emergency thermostat activates, it is necessary to determine the cause of the overheating!
• Never reach inside the air curtain unless the main electrical supply has been turned off!
8.1-2 Preventing the fan from overheating
If any motor is overheated and the heat safety fuse shuts it off, the other motors remain in operation. After cooling, the motor will automatically go back on.
16
8. TROUBLESHOOTING
• There is no signal when an overheated motor shuts off. A failure can be recognised by decreased
air flow volume.
• When a motor shuts off, it is necessary to determine the cause of the failure!
• Never reach inside the air curtain unless the main electrical supply has been turned off!
• Whenever an air curtain’s motor or heater overheats, it is necessary to detect and eliminate the
cause.
• If the cause is any sort of internal failure in the air curtain, it is absolutely necessary to contact the
appropriate authorised service centre.
9. CONCLUSION
If you have any doubts or questions, do not hesitate to contact our sales or technical support department.
Before operation and maintanance, thoroughly read the section “Safe use of air curtains”. It contains all instructions on the safe and correct use of the product.
CONTACT
Address
2VV, s.r.o.,
Poděbradská 289,
530 09 Pardubice,
Czech Republic
Internet: http://www.2vv.cz/contact.distribution.php
17