1 | Overview
The B925F/B926F keypad is an SDI2 bus compatible device.
Each keypad has an LCD display that shows two-line system messages, and user adjustable options such as volume and backlight.
The keypad connects to the SDI2 bus on the control panel using terminal wiring. You can connect more than one keypad to the control panel by wiring them in parallel.
You can program, diagnose, and troubleshoot the system from the control panel keypad as well as remotely through RPS.
1 3 6 2 1
2.1 | Access the address switches
1. Unlock the keypad by turning the lock counter-clockwise.
Refer to Figure 2.1.
2. Hold the keypad by the base in one hand. With the other hand, gently push down on the keypad to remove it from the base. Refer to Figure 2.2.
3. Look at the back of the keypad, and locate the switches.
Refer to Figure 2.3
GAS
10
5 7
4
R Y G B
7
10
5
9
10
8
Figure 2.1: Unlocking the keypad
1
GAS
6 1
Figure 1.1: Keypad base overview
Callout ― Description
1 ― Wall mount holes
2 ― Single gang box holes
3 ― Double gang box holes
4 ― Wire opening
5 ― Surface mount wire openings
6 ― Gang box holes (3-4 in)
7 ― Surface mount wire channel
8 ― Bubble level
9 ― SDI2 wiring terminal block
10 ― Wire tie posts
2 3 6 5
2 | SDI2 address switches
Two switches determine the address for the keypad. The control panel uses the address for communications. Use a slotted screwdriver to set the switches.
Figure 2.2: Removing the keypad from base
1
2
Figure 2.3: Switches location
Callout ― Description
1 ― Address switches
2.2 | Set the address switches
Set the address switches per the control panel confi guration.
If multiple SDI2 keypads reside on the same system, each
SDI2 keypad must have a unique address. For single-digit addresses 1 through 9, set the tens switch to 0. Figure 2.4 shows the address switch setting for address 1.
3 | Installation
After you set the address switches for the proper address, mount the keypad base, wire to the control panel, and attach the keypad to the base.
Caution!
Remove all power (AC and battery) before making any connections. Failure to do so might result in personal injury and/or equipment damage.
3.1 | Mount the keypad
You can surface mount the keypad, or mount it to standard electrical boxes, including single gang boxes.
Mounting the keypad:
1. Use the base as a template to mark the desired mounting surface. Refer to Figure 1.1 for mounting hole and wiring locations.
2. Pull the wiring through the desired wire opening in the base.
3. Use the appropriate mounting hardware (supplied) to mount the base to the desired mounting surface. Refer to Figure 1.1 for mounting hole and wiring locations .
3.2 | Wire to the control panel
When you wire the keypad to a control panel, use the control panel SDI2 terminals labeled R, Y, G, B (PWR, A, B, COM).
Connect them to the keypad terminals labeled R, Y, G, B.
Refer to Figure 3.1.
You can connect keypads to the SDI2 data bus by parallel wire run from the control panel to each keypad, wire from keypad to keypad, or a combination of the two techniques.
Refer to Figure 3.2.
1
2
R
Y
G
B
3
R
Y
G
B
Figure 3.2: Installing multiple keypads using the SDI2 terminals
Reconnect the keypad to the base by sliding the keypad onto the base (reverse of Step 2). The keypad automatically locks onto the base. Apply power to the system.
4 | Display
You can adjust the keypad’s display brightness level, and you can turn the keypad’s nightlight feature on or off.
Adjusting the keypad display brightness:
1. Press [MENU] or press [CMD][8] to open the Main menu.
2. Use [NEXT] to go to the Press 5 for Settings Menu option, or simply press [5].
3. Use [NEXT] to go to the Press 4 for Keypad Confi g option, or simply press [4].
4. Press [1] to adjust the brightness.
5. Use [PREV] or [NEXT] to adjust the brightness level. The changes apply immediately.
6. Press [ESC] to exit the menu.
Turning the keypad nightlight on or off (control panel version
2.1 or higher):
1. Press [MENU] or press [CMD][8] to open the Main menu.
2. Use [NEXT] to go to the Press 5 for Settings Menu option, or simply press [5].
3. Use [NEXT] to go to the Press 4 for Keypad Confi g option, or simply press [4].
4. Use [NEXT] to go to the Press 4 for Nightlight option, or simply press [4].
5. Use [PREV] or [NEXT] to toggle between the Yes and No options.
6. Press [ENTER] while viewing the desired option to save the programming.
7. Press [ESC] to exit the menu.
Figure 3.1: Wiring the keypad to the SDI2 bus connection
(B9512 shown)
Callout ― Description
1 ― Control panel
2 ― Terminal wiring
3 ― Keypad’s wiring terminal block
.
Figure 2.4: Address switches
5 | Status indicators
You can diagnose and troubleshoot the system using the keypad’s status indicators. Refer to Table 5.1 and Table 5.2.
Status indicator
Function
Ready to turn on (arm). (24 hour points, such as fi re points, are always monitored.)
Turned on (armed)
GAS Gas alarm
AC (Mains) power present
Table 5.1: Keypad status indicators
Fire keypad indicator
Function
Fire alarm
Silenced
Supervisory condition
System trouble
Table 5.2: Keypad Fire status indicators
6 | Audible tones
The keypad has a built-in speaker that produces several distinct warning tones. The keypad backlight illuminates when it emits an audible tone.
Tone
Fire alarm
Gas alarm
User alarm
Description
When an area is in fi re alarm, the keypad emits a pulsed, high-pitched bell tone.
When a gas point activates, the keypad emits a unique high pitched tone.
When a user alarm (such as panic and medical alarms) occurs, the tone sounds for the programmed amount of time.
Burglary alarm When an area is in alarm, the keypad emits a steady, high pitched bell tone.
Entry delay The keypad emits an intermittent beep tone during entry delay periods to remind the user to disarm the area.
Exit delay
Invalid button buzz
The keypad emits an intermittent beep tone during exit delay.
When an invalid button, or sequence of buttons, is pressed, the keypad emits a fl at buzz tone.
Keypress
Trouble
The keypad emits a muted beep tone as each button is pressed to indicate that the entry was accepted.
When a trouble event occurs, such as a service alert, the keypad emits a two-tone warble until you enter a programmed passcode with the appropriate authority.
Watch point fault
A single clean tweedle tone alerts the user anytime a watch point is faulted.
Table 6.1: Keypad audible tones
7 | Supervision
The control panel supervises all keypads on the SDI2 bus.
If a supervised keypad fails to respond to the control panel, the control panel declares a Missing Keypad Trouble. When the control panel can again communicate with the keypad, it restores the Missing Keypad Trouble.
During a Missing Keypad Trouble, any connected keypad that maintained contact with the control panel shows the Missing
Keypad Trouble as its idle text, and shows the missing keypad’s address. The communicating keypads also sound a trouble tone. Users can silence the trouble tone. If no other troubles exist, the tone silences when the missing keypad restores.
8 | Show the fi rmware version
Showing the keypad fi rmware version:
1. Remove the keypad from the base to remove power to the keypad. Refer to Figures 2.1 and 2.2.
2. Return the keypad to the base to restore power.
The keypad shows the model number, keypad address, and fi rmware version for 10 seconds.
NOTICE!
You can also view a keypad’s fi rmware version in RPS.
9 | Keypad cleaning
Use a soft cloth and non-abrasive cleaning solution to clean your keypad (for example, microfi ber cloth and eyeglass cleaner).
Spray the cleaner onto the cloth. Do not spray cleaners directly onto the keypad.
10 | Certifi cations
Region Certifi cation
US UL 365 - Police Station Connected Burglar Alarm
Units and Systems
UL 609 - Local Burglar Alarm Units and Systems
UL 636 - Holdup Alarm Units and Systems
UL 864 - Control Units and Accessories for Fire
Alarm Systems
UL 985 - Household Fire Warning System Units
UL 1023 - Household Burglar-Alarm System Units
UL 1076 - Proprietary Burglar Alarm Units and
Systems
UL 1610 - Central Station Burglar Alarm Units
CSFM - California Offi ce of The State Fire
Marshal
FCC Part 15 Class B
Region Certifi cation
CA Canada CAN/ULC S303 - Local Burglar Alarm
Units and Systems
CAN/ULC S304 - Signal Receiving Centre and
Premise Alarm Control Units
CAN/ULC S545 - Residential Fire Warning System
Control
Units
ULC-ORD C1023 - Household Burglar Alarm
System Units
ULC-ORD C1076 - Proprietary Burglar Alarm
Units and Systems
ICES-003 - Digital Apparatus
11 | Specifi cations
Dimensions
Voltage (input)
Current (maximum)
6.2 in x 4.7 in x 1 in (158 mm x
120 mm x 26 mm)
12 VDC nominal
Operating temperature 0°C to +50°C (+32°F to +122°F)
Relative humidity 5% to 93% at +32°C (+90°F) non-condensing
Terminal wire size
Standby: 35 mA
Alarm: 70 mA
SDI2 wiring
12 AWG to 22 AWG (2 mm to
0.65 mm)
Maximum distance - wire size
(unshielded wire only):
1000 ft (305 m) - 22 AWG (0.65 mm)
Compatibility B9512G/B9512G-E
B8512G/B8512G-E
(Refer to the compatible control panel installation document for device capacity.)
Copyright
This document is the intellectual property of Bosch Security
Systems, Inc. and is protected by copyright. All rights reserved.
Trademarks
All hardware and software product names used in this document are likely to be registered trademarks and must be treated accordingly.
Bosch Security Systems, Inc. product manufacturing dates
Use the serial number located on the product label and refer to the Bosch Security Systems, Inc. website at http://www.boschsecurity.com/datecodes/.
Fire Keypad
B925F/B926F
en Installation Guide
Bosch Security Systems, Inc.
130 Perinton Parkway
Fairport, NY 14450
USA www.boschsecurity.com
Bosch Sicherheitssysteme GmbH
Robert-Bosch-Ring 5
85630 Grasbrunn
Germany
© 2015 Bosch Security Systems, Inc. F.01U.305.193 | 03 | 2015.01