YORK Sunline 2000 DM036, DM048, DM060, DM072 Air Conditioners Technical Guide
Below you will find brief information for Sunline 2000 DM036, Sunline 2000 DM048, Sunline 2000 DM060, Sunline 2000 DM072. These YORK single-package air conditioners offer various capacities (3-6 tons), flexible installation options (roof, slab, etc.), and customizable features like bottom/side air discharge, economizers, and different heat types (gas/electric). They are designed for commercial applications and include robust warranties.
Advertisement
Advertisement
036-21502-002-A-0303
®
TECHNICAL GUIDE
SINGLE PACKAGE GAS/ELECTRIC UNITS
AND SINGLE PACKAGE
AIR CONDITIONERS
DM 036, 048, 060 & 072
3, 4, 5 & 6 NOMINAL TONS
10.0 SEER (3, 4 & 5 TONS), 9.0 EER (6 TONS)
DESCRIPTION
YORK Sunline 2000™ units are convertible single package air conditioners with a common cabinet and a common roof curb for the 3, 4, 5 and 6 ton sizes. The units were designed for light commercial and commercial applications. They can easily be installed on a roof curb, slab, roof jack or frame.
All units include:
• Powder Paint finish that meets ASTM-B-117 750 hour salt spray standards
• Permanently lubricated motors
• Bottom or side air discharge configuration capability
(field convertible)
•
• Manufactured under the quality standards of ISO9001
Simplicity
TM
Control Board
• Copper tube/aluminum fin coils
• Easy access to all components
• Rigging holes in base rails for lifting
• Fork lift slots on three sides
• Single point power connection
• Complete factory package - tested, charged and wired
• CSA agency listing on all units
WARRANTY
• Factory Limited Parts Warranty
• One-year parts warranty
• A Five-year parts warranty on the compressor and electric heat elements.
• Ten-year parts warranty on the gas-fired heat exchangers.
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
2
036-21502-002-A-0303
DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
PRODUCT NOMENCLATURE. . . . . . . . . . . . . . . . . . 3
FEATURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
FACTORY-INSTALLED OPTIONS . . . . . . . . . . . . . . 9
FIELD-INSTALLED ACCESSORIES . . . . . . . . . . . . 10
GUIDE SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . 38
Fig. #
1 UNIT CUTAWAY . . . . . . . . . . . . . . . . . . . . . . . . . . 9
2 TYPICAL FIELD POWER & CONTROL
WIRING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
3 UNIT DIMENSIONS (3 - 6 TON COOLING ONLY/
ELECTRIC HEAT) FRONT VIEW . . . . . . . . . . . . 32
4 UNIT DIMENSIONS (3 - 6 TON COOLING/GAS
HEAT) FRONT VIEW . . . . . . . . . . . . . . . . . . . . . 32
5 UNIT WITH ECONOMIZER RAINHOOD . . . . . . 33
6 UNIT WITH FIXED OUTDOOR AIR/MOTORIZED
DAMPER RAINHOOD. . . . . . . . . . . . . . . . . . . . . 33
7 UNIT DIMENSIONS (REAR VIEW). . . . . . . . . . . 34
8 DISCONNECT/BLOWER ACCESS LOCATION . 34
9 TYPICAL APPLICATIONS . . . . . . . . . . . . . . . . . 35
10 FOUR AND SIX POINT LOADING . . . . . . . . . . . 36
11 ROOF CURB DIMENSIONS . . . . . . . . . . . . . . . . 37
Tbl. #
LIST OF FIGURES
LIST OF TABLES
TABLE OF CONTENTS
Pg. #
Pg. #
1 SOUND POWER RATING . . . . . . . . . . . . . . . . . 11
2 CAPACITY RATINGS - (ARI 210/240) . . . . . . . . 11
3 GAS HEAT RATINGS . . . . . . . . . . . . . . . . . . . . . 11
4 DM036 COOLING CAPACITIES (3 TON). . . . . . 12
5 DM048 COOLING CAPACITIES (4 TON). . . . . . 13
6 DM060 COOLING CAPACITIES (5 TON). . . . . . 14
7 DM072 COOLING CAPACITIES (6 TON). . . . . . 15
8 SUPPLY AIR BLOWER PERFORMANCE (3 TON
BELT DRIVE) - SIDE DUCT APPLICATION . . . . 16
9 SUPPLY AIR BLOWER PERFORMANCE (4 TON
BELT DRIVE) - SIDE DUCT APPLICATION . . . . 17
10 SUPPLY AIR BLOWER PERFORMANCE (5 TON
BELT DRIVE) - SIDE DUCT APPLICATION . . . . 18
11 SUPPLY AIR BLOWER PERFORMANCE (6 TON
BELT DRIVE) - SIDE DUCT APPLICATION . . . . 19
12 SUPPLY AIR BLOWER PERFORMANCE (3 - 6
TON DIRECT DRIVE) . . . . . . . . . . . . . . . . . . . . 20
13 BELT DRIVE MOTOR AND DRIVE DATA . . . . . 20
14 STATIC RESISTANCES . . . . . . . . . . . . . . . . . . . 21
15 ELECTRIC HEATER CFM LIMITATIONS. . . . . . 21
16 ELECT DATA - DM036 & 048 DIRECT DRIVE
WITHOUT POWR’D CONVENIENCE OUTLET . 22
17 ELECT DATA - DM060 & 072 DIRECT DRIVE
WITHOUT POWR’D CONVENIENCE OUTLET . 23
18 ELECTRICAL DATA - DM036 & 048 BELT DRIVE
WITHOUT POWR’D CONVENIENCE OUTLET . 24
19 ELECTRICAL DATA - DM060 & 072 BELT DRIVE
WITHOUT POWR’D CONVENIENCE OUTLET . 25
20 ELECTRICAL DATA - DM036 & 048 DIRECT
DRIVE WITH POWR’D CONVENIENCE
OUTLET . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
21 ELECTRICAL DATA - DM060 & 072 DIRECT
DRIVE WITH POWR’D CONVENIENCE
OUTLET . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
22 ELECTRICAL DATA - DM036 & 048 BELT DRIVE
WITH POWR’D CONVENIENCE OUTLET . . . . . 28
23 ELECTRICAL DATA - DM060 & 072 BELT DRIVE
WITH POWR’D CONVENIENCE OUTLET . . . . . 29
24 PHYSICAL DATA . . . . . . . . . . . . . . . . . . . . . . . . 30
25 ELECTRIC HEAT CORRECTION FACTORS . . 30
26 VOLTAGE LIMITATIONS . . . . . . . . . . . . . . . . . . 30
27 UTILITIES ENTRY . . . . . . . . . . . . . . . . . . . . . . . 34
28 MINIMUM CLEARANCES . . . . . . . . . . . . . . . . . . 34
29 DM 4 POINT LOADS WEIGHT DISTRIBUTION . 36
30 DM 6 POINT LOADS WEIGHT DISTRIBUTION . 36
31 CENTER OF GRAVITY . . . . . . . . . . . . . . . . . . . . 36
32 OPERATING WEIGHTS (LBS.) . . . . . . . . . . . . . 37
Unitary Products Group
036-21502-002-A-0303
PRODUCT NOMENCLATURE
Product Catagory
D = Air Cond., Single Package
B = Heat Pump, Single Package
3-6 Ton Sunline Model Number Nomenclature
D M 048 N04 A 2 A AA 1
Product Generation
1 = First Generation
Product Identifier
M = R-22 Standard Efficiency (DCG/DCE)
F = R-22 Medium Efficiency (DEG/DEE)
H = R-22 High Efficiency (DHG/DHE)
Q = R-22 Std. Effic Heat Pump (BCH)
Nominal Cooling
Capacity - MBH
036 = 3 Ton
048 = 4 Ton
060 = 5 Ton
072 = 6 Ton
Voltage
1 = 208/230-1-60
2 = 208/230-3-60
4 = 460-3-60
5 = 575-3-60
Additional Options
(See Next Page)
Heat Type & Nominal Heat Capacity
C00 = Cooling Only. Suitable for field installed electric heat
Gas Heat Options
N04 = 40 MBH Output Aluminized Steel (036)
N06 = 60 MBH Output Aluminized Steel (048)
N08 = 79 MBH Output Aluminized Steel (036,060,072)
N10 = 99 MBH Output Aluminized Steel (048,060,072)
S04 = 40 MBH Output Stainless Steel (036)
S06 = 60 MBH Output Stainless Steel (048)
S08 = 79 MBH Output Stainless Steel (036,060,072)
S10 = 99 MBH Output Stainless Steel (048,060,072)
Electric Heat Options
E05 = 5 kW Electric Heat
E07 = 7 kW Electric Heat
E10 = 10 kW Electric Heat
E15 = 15 kW Electric Heat
E20 = 20 kW Electric Heat
E30 = 30 kW Electric Heat
Installation Options
A = No Options Installed
B = Option 1
C = Option 2
D = Options 1 & 2
E = Option 3
F = Option 4
G = Options 1 & 3
H = Options 1 & 4
J = Options 1, 2 & 3
K = Options 1, 2, & 4
L = Options 1,3 & 4
M = Options 1, 2, 3, & 4
N = Options 2 & 3
P = Options 2 & 4
Q = Options 2, 3, & 4
R = Options 3 & 4
S = Option 5
T = Options 1 & 5
U = Options 1, 3, & 5
V = Options 1, 4, & 5
W = Options 1, 3, 4, & 5
X = Options 3 & 5
Y = Options 4 & 5
Z = Options 3, 4, & 5
Options
1 = Disconnect
2 = Non-Pwr'd Conv Oultet
3 = Smoke Detector S.A.
4 = Smoke Detector R.A.
5 = Pwr'd Conv. Outlet
Airflow
A= Direct Drive
B = Direct Drive/Single Input Econo
D = Direct Drive/Motorized Damper
L = Direct Drive/BAS Ready Econ (No BAS Controller)/2" Pleated Filters/Extra xfrmr & circuit bkr.
N = Belt Drive
P = Belt Drive/Single Input Econo
R = Belt Drive/Motorized Damper
Y = Belt Drive/BAS Ready Econ (No BAS Controller) w/2" Pleated Filters
Unitary Products Group 3
4
036-21502-002-A-0303
PRODUCT NOMENCLATURE - Continued
3-6T Sunline Model Number Nomenclature
Additional Options
AA None
AB Phase Monitor
AC Coil Guard
AD Dirty Filter Switch
AE Phase Monitor & Coil Guard
AF Phase Monitor & Dirty Filter Switch
AG Coil Guard & Dirty Filter Switch
AH Phase Monitor, Coil Guard, & Dirty Filter Switch
AS Bottom Condensate Pan
BA Hinged Filter Door & Toolless Access Panels
BB Phase Monitor, Hinged Filter Door & Toolless Access Panels
BC Coil Guard, Hinged Filter Door & Toolless Access Panels
BD Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
BE Phase Monitor & Coil Guard, Hinged Filter Door & Toolless Access Panels
BF Phase Monitor & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
BG Coil Guard & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
BH Phase Monitor, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
CA CPC Controller with Dirty Filter Switch & Air Proving Switch
CB CPC Controller, DFS, APS & Phase Monitor
CC CPC Controller, DFS, APS & Coil Guard
CD CPC Controller, DFS, APS, Phase Monitor, & Coil Guard
CE CPC Controller, DFS, APS & Technicoat Cond. Coil
CF CPC Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor
CG CPC Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard
CH CPC Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard
CJ CPC Controller, DFS, APS & Technicoat Evap. Coil
CK CPC Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor
CL CPC Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard
CM CPC Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard
CN CPC Controller, DFS, APS & Technicoat Evap. & Cond Coils
CP CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor
CQ CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard
CR CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard
DA CPC Controller with Dirty Filter Switch & Air Proving Switch, Hinged Filter Door & Toolless Access Panels
DB CPC Controller, DFS, APS & Phase Monitor, Hinged Filter Door & Toolless Access Panels
DC CPC Controller, DFS, APS & Coil Guard, Hinged Filter Door & Toolless Access Panels
DD CPC Controller, DFS, APS, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
DE CPC Controller, DFS, APS & Technicoat Cond. Coil, Hinged Filter Door & Toolless Access Panels
DF CPC Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
DG CPC Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels
DH CPC Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
DJ CPC Controller, DFS, APS & Technicoat Evap. Coil, Hinged Filter Door & Toolless Access Panels
DK CPC Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
DL CPC Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels
DM CPC Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
DN CPC Controller, DFS, APS & Technicoat Evap. & Cond Coils, Hinged Filter Door & Toolless Access Panels
DP CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
DQ CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard, Hinged Filter Door & Toolless Access Panels
DR CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
Unitary Products Group
036-21502-002-A-0303
Additional Options
EA Johnson UNT Controller with Dirty Filter Switch & Air Proving Switch, Hinged Filter Door & Toolless Access Panels
EB Johnson UNT Controller, DFS, APS & Phase Monitor, Hinged Filter Door & Toolless Access Panels
EC Johnson UNT Controller, DFS, APS & Coil Guard, Hinged Filter Door & Toolless Access Panels
ED Johnson UNT Controller, DFS, APS, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
EE Johnson UNT Controller, DFS, APS & Technicoat Cond. Coil, Hinged Filter Door & Toolless Access Panels
EF Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
EG Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels
EH Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
EJ Johnson UNT Controller, DFS, APS & Technicoat Evap. Coil, Hinged Filter Door & Toolless Access Panels
EK Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
EL Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels
EM Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
EN Johnson UNT Controller, DFS, APS & Technicoat Evap. & Cond Coils, Hinged Filter Door & Toolless Access Panels
EP Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
EQ Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard, Hinged Filter Door & Toolless Access Panels
ER Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access
Panels
GA Honeywell Excel 10 Controller with Dirty Filter Switch & Air Proving Switch, Hinged Filter Door & Toolless Access Panels
GB Honeywell Excel 10 Controller, DFS, APS & Phase Monitor, Hinged Filter Door & Toolless Access Panels
GC Honeywell Excel 10 Controller, DFS, APS & Coil Guard, Hinged Filter Door & Toolless Access Panels
GD Honeywell Excel 10 Controller, DFS, APS, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
GE Honeywell Excel 10 Controller, DFS, APS & Technicoat Cond. Coil, Hinged Filter Door & Toolless Access Panels
GF Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
GG Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels
GH Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access
Panels
GJ Honeywell Excel 10 Controller, DFS, APS & Technicoat Evap. Coil, Hinged Filter Door & Toolless Access Panels
GK Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
GL Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels
GM Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access
Panels
GN Honeywell Excel 10 Controller, DFS, APS & Technicoat Evap. & Cond Coils, Hinged Filter Door & Toolless Access Panels
GP Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor, Hinged Filter Door & Toolless Access
Panels
GQ Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard, Hinged Filter Door & Toolless Access Panels
GR Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless
Access Panels
HA Honeywell Excel 10 Controller with Dirty Filter Switch & Air Proving Switch
HB Honeywell Excel 10 Controller, DFS, APS & Phase Monitor
HC Honeywell Excel 10 Controller, DFS, APS & Coil Guard
HD Honeywell Excel 10 Controller, DFS, APS, Phase Monitor, & Coil Guard
HE Honeywell Excel 10 Controller, DFS, APS & Technicoat Cond. Coil
HF Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor
HG Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard
HH Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard
HJ Honeywell Excel 10 Controller, DFS, APS & Technicoat Evap. Coil
HK Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor
HL Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard
HM Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard
HN Honeywell Excel 10 Controller, DFS, APS & Technicoat Evap. & Cond Coils
HP Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor
HQ Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard
HR Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard
Unitary Products Group 5
6
036-21502-002-A-0303
Additional Options
JA Johnson UNT Controller with Dirty Filter Switch & Air Proving Switch
JB Johnson UNT Controller, DFS, APS & Phase Monitor
JC Johnson UNT Controller, DFS, APS & Coil Guard
JD Johnson UNT Controller, DFS, APS, Phase Monitor, & Coil Guard
JE Johnson UNT Controller, DFS, APS & Technicoat Cond. Coil
JF Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor
JG Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard
JH Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard
JJ Johnson UNT Controller, DFS, APS & Technicoat Evap. Coil
JK Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor
JL Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard
JM Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard
JN Johnson UNT Controller, DFS, APS & Technicoat Evap. & Cond Coils
JP Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor
JQ Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard
JR Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard
NA Novar ETC-3 Controller with Dirty Filter Switch & Air Proving Switch
NB Novar ETC-3 Controller, DFS, APS & Phase Monitor
NC Novar ETC-3 Controller, DFS, APS & Coil Guard
ND Novar ETC-3 Controller, DFS, APS, Phase Monitor, & Coil Guard
NE Novar ETC-3 Controller, DFS, APS & Technicoat Cond. Coil
NF Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor
NG Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard
NH Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard
NJ Novar ETC-3 Controller, DFS, APS & Technicoat Evap. Coil
NK Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor
NL Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard
NM Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard
NN Novar ETC-3 Controller, DFS, APS & Technicoat Evap. & Cond Coils
NP Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor
NQ Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard
NR Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard
PA Novar ETC-3 Controller with Dirty Filter Switch & Air Proving Switch, Hinged Filter Door & Toolless Access Panels
PB Novar ETC-3 Controller, DFS, APS & Phase Monitor, Hinged Filter Door & Toolless Access Panels
PC Novar ETC-3 Controller, DFS, APS & Coil Guard, Hinged Filter Door & Toolless Access Panels
PD Novar ETC-3 Controller, DFS, APS, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
PE Novar ETC-3 Controller, DFS, APS & Technicoat Cond. Coil, Hinged Filter Door & Toolless Access Panels
PF Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
PG Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels
PH Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
PJ Novar ETC-3 Controller, DFS, APS & Technicoat Evap. Coil, Hinged Filter Door & Toolless Access Panels
PK Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
PL Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels
PM Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
PN Novar ETC-3 Controller, DFS, APS & Technicoat Evap. & Cond Coils, Hinged Filter Door & Toolless Access Panels
PP Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
PQ Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard, Hinged Filter Door & Toolless Access Panels
PR Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access
Panels
TA Technicoat Condenser Coil
TB Technicoat Condenser Coil & Phase Monitor
TC Technicoat Condenser Coil & Coil Guard
Unitary Products Group
036-21502-002-A-0303
Additional Options
TD Technicoat Condenser Coil & Dirty Filter Switch
TE Technicoat Condenser Coil, Phase Monitor, & Coil Guard
TF Technicoat Condenser Coil, Phase Monitor, & Dirty Filter Switch
TG Technicoat Condenser Coil, Coil Guard, & Dirty Filter Switch
TH Technicoat Condenser Coil, Phase Monitor, Coil Guard, & Dirty Filter Switch
TJ Technicoat Evaporator Coil
TK Technicoat Evaporator Coil & Phase Monitor
TL Technicoat Evaporator Coil & Coil Guard
TM Technicoat Evaporator Coil & Dirty Filter Switch
TN Technicoat Evaporator Coil, Phase Monitor, & Coil Guard
TP Technicoat Evaporator Coil, Phase Monitor, & Dirty Filter Switch
TQ Technicoat Evaporator Coil, Coil Guard, & Dirty Filter Switch
TR Technicoat Evaporator Coil, Phase Monitor, Coil Guard, & Dirty Filter Switch
TS Technicoat Evaporator & Condenser Coils
TT Technicoat Evaporator & Condenser Coils & Phase Monitor
TU Technicoat Evaporator & Condenser Coils & Coil Guard
TV Technicoat Evaporator & Condenser Coils & Dirty Filter Switch
TW Technicoat Evaporator & Condenser Coils, Phase Monitor, & Coil Guard
TX Technicoat Evaporator & Condenser Coils, Phase Monitor, & Dirty Filter Switch
TY Technicoat Evaporator & Condenser Coils, Coil Guard, & Dirty Filter Switch
TZ Technicoat Evaporator & Condenser Coils, Phase Monitor, Coil Guard, & Dirty Filter Switch
UA Technicoat Condenser Coil, Hinged Filter Door & Toolless Access Panels
UB Technicoat Condenser Coil & Phase Monitor, Hinged Filter Door & Toolless Access Panels
UC Technicoat Condenser Coil & Coil Guard, Hinged Filter Door & Toolless Access Panels
UD Technicoat Condenser Coil & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
UE Technicoat Condenser Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
UF Technicoat Condenser Coil, Phase Monitor, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
UG Technicoat Condenser Coil, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
UH Technicoat Condenser Coil, Phase Monitor, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
UJ Technicoat Evaporator Coil, Hinged Filter Door & Toolless Access Panels
UK Technicoat Evaporator Coil & Phase Monitor, Hinged Filter Door & Toolless Access Panels
UL Technicoat Evaporator Coil & Coil Guard, Hinged Filter Door & Toolless Access Panels
UM Technicoat Evaporator Coil & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
UN Technicoat Evaporator Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
UP Technicoat Evaporator Coil, Phase Monitor, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
UQ Technicoat Evaporator Coil, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
UR Technicoat Evaporator Coil, Phase Monitor, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
US Technicoat Evaporator & Condenser Coils, Hinged Filter Door & Toolless Access Panels
UT Technicoat Evaporator & Condenser Coils & Phase Monitor, Hinged Filter Door & Toolless Access Panels
UU Technicoat Evaporator & Condenser Coils & Coil Guard, Hinged Filter Door & Toolless Access Panels
UV Technicoat Evaporator & Condenser Coils & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
UW Technicoat Evaporator & Condenser Coils, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
UX Technicoat Evaporator & Condenser Coils, Phase Monitor, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
UY Technicoat Evaporator & Condenser Coils, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
UZ Technicoat Evaporator & Condenser Coils, Phase Monitor, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
Unitary Products Group 7
8
036-21502-002-A-0303
FEATURES
All models are available with a wide variety of factorymounted options such as stainless steel heat exchangers, phase monitor, dirty filter switch, and coil guard to make them suitable for almost every application.
All units are self-contained and assembled on full perimeter base rails with forklift holes on three sides and holes for overhead rigging. Every unit is completely piped, wired, charged and tested at the factory to simplify the field installation and to provide years of dependable operation.
All models (including those with an economizer) are suitable for either bottom or horizontal duct connections. For bottom duct, remove the sheet metal panels from the supply and return air openings through the base of the unit. For horizontal duct, remove the supply and return air panels on the rear of the unit.
All models are available with these “factory mounted” outdoor air damper options:
• Single enthalpy economizer
• Motorized outdoor air damper
Supply air blowers are equipped with either a direct drive or a belt drive that can be adjusted to meet the exact requirements of the job.
•
All compressors are equipped with internal pressure relief.
Every refrigerant circuit includes a liquid line filter-drier, a high pressure switch and a suction line with a freezestat and low pressure/loss of charge switch to protect all system components.
Simplicity
™ Controls -
Simplicity
™ control boards have standardized a number of features previously available only as options or by utilizing additional controls.
• Low Ambient - An integrated low-ambient control allows all units to operate in the cooling mode down to 0ºF outdoor ambient without additional assistance. Optionally, the control board can be programmed to lockout the compressors when the outdoor air temperature is low or when free cooling is available.
• Anti-Short Cycle Protection - To aid compressor life, an anti-short cycle delay is incorporated into the standard controls. Compressor reliability is further ensured by programmable minimum run times. For testing, the anti short cycle delay can be temporarily overridden with the push of a button.
• Fan Delays - Fan on and fan off delays are fully programmable and are independent of one another. All units are programmed with default values based upon their configuration of cooling and heat.
• Safety Monitoring - The control board monitors the high and low-pressure switches, the freezestats, the gas valve, if applicable, and the temperature limit switch on gas heat units. The unit control board will alarm on ignition failures, compressor lockouts and repeated limit switch trips.
• Nuisance Trip Protection- To prevent nuisance trouble calls, the control board uses a “three strikes, you’re out” philosophy. The high and low-pressure switches and the freezestats must trip three times within two hours before the unit control board will lock out the compressor.
• On Board Diagnostics - Each alarm will energize a trouble light on the thermostat, if so equipped, and flash an alarm code on the control board LED. Each high and low-pressure switch alarm as well as each freezestat alarm has its own flash code. The control board saves the five most recent alarms in memory, and these alarms can be reviewed at any time.
Alarms and programmed values are retained through the loss of power.
All units have long lasting powder paint cabinets with 750 hour salt spray test approval under ASTM-B117 procedures.
All models are CSA listed.
• Warranty - All models include a one-year limited parts warranty on the complete unit. Compressors and electric heater elements carry a five-year warranty. Gas heat exchangers carry a 10-year parts warranty.
• Gas Heat Operation - All gas heat units have a minimum AFUE of 80%. Each section includes a durable heat exchanger with aluminized steel or optional stainless steel tubes, a redundant gas valve, spark ignition, power venting, an ignition module for 100% shut-off and all of the safety controls required to meet the latest ANSI standards.
The gas supply piping can be routed into the heating compartment through a hole in the base pan of the unit or through a knockout in the piping panel on the front of the unit.
• Electric Heat Operation - All electric heat models are wired for a single power source and include a bank of nickel chromium elements mounted at the discharge of the supply air blower to provide a high velocity and uniform distribution of air across the heating elements.
Every element is fully protected against excessive temperature by thermal limit switches.
The power supply wiring can be routed into the control box through a threaded pipe connection (field supplied) in the base pan of the unit or through a knockout in the wiring panel on the side of the unit.
• BAS Controls - York’s Sunline™ series units offer factory mounted BAS controls such as Novar, Honeywell,
Johnson, and CPC.
Unitary Products Group
036-21502-002-A-0303
FIGURE 1: UNIT CUTAWAY
FACTORY-INSTALLED OPTIONS
• SINGLE INPUT ELECTRONIC ENTHALPY ECONO-
MIZERS - Includes a slide-in / plug-in damper assembly with fully modulating spring-return motor actuator capable of introducing up to 100% outdoor air with nominal
1% leakage type dampers.
The enthalpy system contains one sensor that monitors the outdoor air and determines when the air is cool enough and dry enough to provide free cooling.
The rainhood is painted to match the basic unit and must be field-assembled before installing.
• MOTORIZED OUTDOOR AIR INTAKE DAMPER -
Includes a slide-in / plug-in damper assembly with a 2position, spring return motor actuator which opens to a pre-set position whenever the supply air blower is operating and will drive fully closed when the blower unit shuts down.
The rain hood is painted to match the basic unit and must be field assembled before installing.
• PHENOLIC COATED EVAPORATOR AND CON-
DENSER COILS - Special coating process that utilizes
Technicoat 10-1
TM
processes. Coating is applied by total immersion of the complete coil for maximum protection.
• ELECTRIC HEATERS wired for single point power supply. These nickel chromium heater elements are provided with limit and automatic reset capability to prevent operation at excessive temperatures.
• FILTER OPTIONS - Standard units are shipped with 1” throw-away filters installed. 2” pleated filters are offered as a factory installed option.
• CONVENIENCE OUTLET - This 110 volt outlet can be
“powered” by the unit with a stepdown transformer or the unit may be ordered with a “non-powered” convenience outlet that can be wired in the field.
• DISCONNECT SWITCH - For gas heat units and cooling units with electric heat, a HACR breaker sized to the unit is provided. For cooling only units, a switch sized to the largest electric heat available for the particular unit is provided. Factory installed option only.
• BAS - See “Additional Options” section in the product nomenclature.
• SMOKE DETECTORS - (supply air & return air) The smoke detectors stop operation of the unit by interrupting power to the control board if smoke is detected within the air compartment.
Unitary Products Group 9
036-21502-002-A-0303
• COIL GUARD - Customers can purchase a coil guard kit to protect the condenser coil from damage. This is not a hail guard kit.
• STAINLESS STEEL HEAT EXCHANGER - For applications in corrosive environments, this option provides a full stainless steel heat exchanger assembly.
• PHASE MONITORS - Designed to prevent unit damage.
The phase monitor will shut the unit down in an out-ofphase condition.
• DIRTY FILTER SWITCH - This kit includes a differential pressure switch that energizes the fault light on the unit thermostat, indicating that there is an abnormally high pressure drop across the filters. Factory installed option or field installed accessory.
• HINGED FILTER DOOR/“TOOLLESS” BLOWER AND
ACCESS PANELS (not hinged) - This option allows for easy access and maintenance.
NOTE: Knobs are shipped inside the unit to prevent shipping damage. These must be field installed for tool-less operation.
FIELD-INSTALLED ACCESSORIES
• SINGLE INPUT ELECTRONIC ENTHALPY ECONO-
MIZERS - Includes a slide-in / plug-in damper assembly with fully modulating spring-return motor actuator capable of introducing up to 100% outdoor air with nominal
1% leakage type dampers.
The enthalpy system contains one sensor that monitors the outdoor air and determines when the air is cool enough and dry enough to provide free cooling.
The rainhood is painted to match the basic unit and must be field-assembled before installing.
• MOTORIZED OUTDOOR AIR INTAKE DAMPER -
Includes a slide-in / plug-in damper assembly with a 2position, spring return motor actuator which opens to some pre-set position whenever the supply air blower is operating and will drive fully closed when the blower unit shuts down.
The rain hood is painted to match the basic unit and must be field assembled before installing.
• ELECTRIC HEATERS wired for single point power supply. These nickel chromium heater elements are provided with limit and automatic reset capability to prevent operation at excessive temperatures.
• ROOF CURBS - Eight and fourteen-inch high roof curbs provide a water-tight seal between the unit and the finished roof. These full perimeter curbs meet the requirements of the National Roofing Contractors Association
(NRCA) and are shipped knocked-down for field assembly.
Roof curbs are designed to fit inside the base rails of the unit and include both a wood nailing strip and duct hanger supports.
• HIGH ALTITUDE NATURAL GAS - Burner orifices and pilot orifices are provided for proper furnace operation at altitudes up to 6,000 feet.
• PROPANE - Burner orifices, pilot orifices and gas valve parts are provided to convert a natural gas furnace to propane.
• HIGH ALTITUDE PROPANE - Burner orifices and pilot orifices are provided for proper furnace operation at altitudes up to 6,000 feet. This accessory supplements the basic propane conversion kit.
• LOW NOX KIT- Required to reduce the emission of nitrogen oxides below 40 nanograms per joule.
• POWER EXHAUST - Our single input economizer options are available with power exhaust. Whenever the outdoor air intake dampers are opened for free cooling, the exhaust fan will be energized to prevent the conditioned space from being over-pressurized during economizer operation.
The power exhaust option can only be used on bottom duct configurations.
• BAROMETRIC RELIEF DAMPER - This damper accessory can be used to relieve internal building air pressure on units with an economizer without power exhaust. This accessory includes a rain hood, a bird screen and a fully assembled damper. With bottom duct connections, the damper should be mounted over the opening in the return air panel. With horizontal ductwork, the accessory should be mounted on the return air duct.
• ENTHALPY ACCESSORY CONTROL KIT - This kit contains the required components to convert a single enthalpy economizer to dual enthalpy.
• BURGLAR BARS - Mount in the supply and return openings to prevent entry into the duct work.
• FLUE EXHAUST EXTENSION KIT - In locations with wind or weather conditions which may interfere with proper exhausting of furnace combustion products, this kit can be installed to prevent the flue exhaust from entering nearby fresh air intakes.
• CO
2
SENSOR - Senses CO
2
levels and automatically overrides the economizer when levels rise above the present limits.
• COIL GUARD - Customers can purchase a coil guard kit to protect the condenser coil from damage. This is not a hail guard kit.
10 Unitary Products Group
036-21502-002-A-0303
TABLE 1: SOUND POWER RATING
1
UNIT
SIZE
CFM
ESP
IWG
BLOWER
SPEED KW 63 125
SOUND POWER (db 10
-12
Watts)
Octave Band Centerline Frequency (Hz)
250 500 1,000 2,000 4,000 8,000
SWL dB(A)
036
048
060
072
1,200
1,600
2,000
2,200
0.6
0.55
0.45
0.3
LOW
HIGH
HIGH
HIGH
0.60
0.80
1.00
1.35
84
85
86
87
84
85
86
87
74
75
76
77
67
68
69
70
69
70
71
72
62
63
64
65
57
58
59
60
52
53
54
55
74
75
76
77
1. These values have been accessed using a model of sound propagation from a point source into the hemispheric\free field. The dBA values provided are to be used for reference only. Calculation of dBA values cover matters of system design and the fan manufacture has no way of knowing the details of each system. This constitutes and expectation to any specification or guarantee requiring a dBA value or sound data in any other form than sound power level ratings.
2. At a distance of 10 feet from the blower.
dB(A)
@
10Ft.
2
41
42
43
44
TABLE 2: CAPACITY RATINGS - (ARI 210/240)
1
MODEL MBH EER
2
SEER
3
DM036
DM048
DM060
DM072
36.0
47.4
59.0
72.0
9.1
9.0
9.1
9.0
10.0
10.0
10.0
-
1. 80/67°F Indoor and 95°F outdoor.
2. EER = Energy Efficiency Ratio at full load - the cooling capacity in Btu’s per hour (Btuh) divided by the power input in watts, expressed in Btuh per watt (Btuh/watt).
3. SEER = Seasonal Energy Efficiency Ratio.
TABLE 3: GAS HEAT RATINGS
1
MODEL
DM036N04
DM036N08
DM048N06
DM048N10
DM060N08
DM060N10
DM072N08
DM072N10
MBH
INPUT
50
100
75
125
100
125
100
125
MBH
OUTPUT
40
79
59
99
79
99
79
99
1. All units are single-stage heating.
AFUE
(%)
80.9
80.5
80.9
80.3
80.5
80.3
80.5
80.3
TEMP
RISE ºF
15 - 45
40 - 70
25 - 55
45 - 75
25 - 55
35 - 65
25 - 55
35 - 65
Unitary Products Group 11
036-21502-002-A-0303
TABLE 4: DM036 COOLING CAPACITIES (3 TON)
AIR ON
EVAPORATOR
COIL
CFM
1750
1475
1200
1050
900
WB °F
57
72
67
62
57
72
67
72
67
62
57
72
67
62
62
57
72
67
62
57
TOTAL
CAP.
1
MBH
39
42
40
36
37
41
38
45
43
39
40
44
41
38
35
36
39
37
34
34
POWER
INPUT
2
kW
2.9
3.1
3.0
3.0
2.9
3.1
3.0
3.1
3.0
3.0
2.9
3.1
3.0
3.0
3.0
2.9
3.1
3.0
3.0
2.9
86
39
28
35
36
37
26
32
35
43
39
40
31
39
38
35
36
24
30
34
34
83
39
25
32
36
37
23
30
30
38
39
40
28
35
38
35
36
21
27
33
34
TEMPERATURE OF AIR ON CONDENSER COIL
85°F
SENSIBLE CAPACITY
1
ENTERING DRY BULB, °F
TOTAL
CAP.
MBH
1
POWER
INPUT
2
kW
80
39
22
28
35
37
20
27
26
34
39
40
24
31
37
33
35
19
25
30
33
77
35
18
25
31
34
17
24
21
29
34
35
20
27
33
30
32
16
22
28
30
74
31
15
22
28
31
14
21
17
25
30
31
16
23
29
27
29
14
20
25
27
71
27
-
18
25
27
-
18
-
20
25
26
-
19
25
24
26
-
17
23
25
68
23
-
15
21
24
-
15
-
16
21
22
-
16
21
21
23
-
15
20
22
43
41
36
38
42
39
36
37
41
38
35
36
39
37
33
34
38
36
32
33
3.2
3.3
3.2
3.3
3.2
3.2
3.2
3.3
3.3
3.3
3.2
3.3
3.3
3.3
3.2
3.2
3.2
3.2
3.2
3.1
86
37
28
34
35
36
26
32
35
41
36
38
31
37
36
33
34
23
29
32
33
80
36
21
28
34
35
20
26
26
34
36
38
23
31
35
31
32
18
24
29
30
95°F
SENSIBLE CAPACITY
1
ENTERING DRY BULB, °F
83
37
24
31
35
36
23
29
30
38
36
38
27
35
36
33
34
21
26
31
33
77
32
18
25
30
32
17
23
21
29
32
33
20
27
31
28
30
16
21
26
27
74
28
14
21
27
28
14
20
17
25
27
29
16
23
27
25
27
13
19
24
25
71
25
-
18
24
25
-
17
-
21
23
24
-
19
23
22
24
-
16
21
22
AIR ON
EVAPORATOR
CFM
1750
1475
1200
1050
900
COIL
WB °F
67
62
57
72
67
62
57
72
67
62
57
72
72
67
62
57
72
67
62
57
TOTAL
CAP.
1
MBH
37
33
34
39
36
32
33
41
38
34
35
40
37
35
31
32
36
33
30
31
POWER
INPUT
2
kW
3.7
3.7
3.7
3.6
3.7
3.6
3.7
3.6
3.7
3.6
3.6
3.6
3.6
3.6
3.6
3.5
3.6
3.6
3.6
3.5
86
34
38
34
35
30
36
33
34
27
34
32
33
25
31
31
32
22
28
30
31
83
29
37
34
35
26
34
33
34
24
30
32
33
22
28
31
32
20
25
29
30
80
25
33
34
35
23
30
33
34
20
27
32
33
19
25
29
30
17
23
27
28
TEMPERATURE OF AIR ON CONDENSER COIL
105°F
SENSIBLE CAPACITY
1
ENTERING DRY BULB, °F
77
20
28
30
31
19
26
29
30
17
24
29
29
16
22
27
27
15
20
24
25
74
16
24
25
26
15
22
25
26
14
20
25
26
13
19
24
24
12
18
22
22
71
-
19
21
22
-
18
21
22
-
17
22
23
-
16
21
21
-
15
19
20
68
-
15
16
17
-
14
17
18
-
14
19
19
-
13
18
18
-
13
17
17
TOTAL
CAP.
1
MBH
39
36
32
33
38
35
31
32
37
34
30
31
36
32
29
30
34
31
28
28
POWER
INPUT
2
4.1
4.0
4.0
4.0
4.1
4.0
4.0
4.0
4.1
4.0
4.0
3.9
4.1
4.0
4.0
3.9
4.0
4.0
4.0
3.9
kW
86
33
36
32
33
30
34
31
32
26
33
30
31
24
30
29
30
21
27
28
28
115°F
ENTERING DRY BULB, °F
83
28
36
32
33
26
33
31
32
23
30
30
31
21
27
29
29
19
24
28
28
SENSIBLE CAPACITY
80
24
32
32
33
22
29
31
32
20
26
30
31
18
24
28
28
16
22
25
25
77
19
27
27
28
18
25
27
28
16
23
27
27
15
21
25
25
14
19
22
23
74
21
23
24
13
20
24
24
15
23
23
24
14
12
18
22
22
11
17
20
20
1
71
17
19
20
-
16
20
21
-
18
18
19
-
-
15
19
19
-
14
17
17
68
1. These capacities are gross ratings. For net capacity, determine the kW of the supply air blower motor from the SUPPLY AIR BLOWER PERFORMANCE
Table, multiply this value by 3.415 MBH/kW to determine the motor heat, and deduct this heat from the gross capacity of the unit.
2. These ratings include the compressor and the condenser fan motors but not the supply air blower motor. The total condenser fan motor power input
is 0.36kW. Refer to the SUPPLY AIR BLOWER PERFORMANCE Table for the kW of the supply air blower motor.
13
15
16
-
13
17
17
-
14
14
15
-
-
12
16
16
-
11
15
15
NOMINAL RATING
68
21
-
15
20
22
-
14
-
16
18
20
-
15
19
20
21
-
14
19
20
12 Unitary Products Group
036-21502-002-A-0303
TABLE 5: DM048 COOLING CAPACITIES (4 TON)
AIR ON
EVAPORATOR
COIL
CFM
2000
1800
1600
1400
1200
WB °F
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
72
67
62
57
TOTAL
CAP.
1
MBH
51
47
46
54
49
45
44
52
47
43
42
58
53
49
47
56
60
55
51
49
POWER
INPUT
2
kW
4.1
4.0
3.9
4.1
4.1
4.0
3.9
4.1
4.1
4.0
3.9
4.1
4.1
4.0
3.9
4.1
4.1
4.1
4.0
3.9
86
46
47
46
35
42
45
44
32
39
43
42
41
49
49
47
38
44
53
51
49
83
41
47
46
31
38
45
44
29
35
43
42
36
45
49
47
34
39
48
51
49
TEMPERATURE OF AIR ON CONDENSER COIL
85°F
SENSIBLE CAPACITY
1
ENTERING DRY BULB, °F
TOTAL
CAP.
MBH
1
POWER
INPUT
2
kW
80
37
45
46
27
34
42
43
25
32
39
39
31
40
48
47
29
33
42
51
49
77
32
41
41
23
30
38
39
22
28
36
36
26
35
43
43
25
28
37
45
44
74
28
36
37
19
26
34
35
18
25
32
32
21
30
38
38
20
23
32
40
39
71
24
32
32
-
22
30
31
-
21
29
29
-
25
33
33
-
-
26
34
33
68
19
27
28
-
19
26
27
-
18
25
25
-
20
28
28
-
-
21
29
28
60
52
48
47
57
50
46
45
55
48
44
44
53
47
43
42
51
45
41
41
4.5
4.4
4.4
4.5
4.5
4.4
4.3
4.5
4.4
4.3
4.3
4.5
4.5
4.4
4.3
4.6
4.5
4.5
4.4
4.3
86
45
44
44
35
41
43
42
32
38
41
41
41
49
46
45
38
44
52
48
47
80
36
44
44
27
34
41
41
25
31
38
38
31
39
46
45
29
33
42
48
47
95°F
SENSIBLE CAPACITY
1
ENTERING DRY BULB, °F
83
40
44
44
31
38
43
42
28
35
41
41
36
44
46
45
33
39
47
48
47
77
31
40
39
23
30
37
37
21
28
35
34
26
34
41
40
24
28
36
42
42
74
27
35
35
19
26
33
33
18
24
31
31
21
29
36
36
20
23
31
37
36
71
23
31
30
-
22
29
29
-
21
28
27
-
24
31
31
-
-
25
32
31
AIR ON
EVAPORATOR
CFM
2000
1800
1600
1400
1200
COIL
WB °F
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
TOTAL
CAP.
1
MBH
43
53
46
42
41
51
44
40
40
49
42
38
38
56
49
45
44
55
48
43
POWER
INPUT
2
kW
5.1
5.0
4.9
4.9
5.0
5.0
4.9
4.9
5.0
4.9
4.9
4.8
5.0
4.9
4.8
4.8
4.9
4.9
4.8
4.8
86
42
49
45
44
39
47
43
43
36
44
42
41
33
41
40
40
30
37
38
38
105°F
ENTERING DRY BULB, °F
83
37
46
45
44
34
43
43
43
32
40
42
41
29
37
40
40
27
34
38
38
SENSIBLE CAPACITY
1
80
29
38
43
43
28
35
42
31
40
45
44
41
26
33
39
38
23
30
36
35
TEMPERATURE OF AIR ON CONDENSER COIL
77
24
33
38
38
23
31
37
26
35
39
39
37
22
29
35
34
20
27
32
32
74
20
28
33
33
19
26
33
21
29
34
33
32
18
25
31
30
16
23
29
28
71
-
23
28
28
-
22
28
-
24
28
28
28
-
21
27
26
-
20
25
25
68
-
18
23
23
-
17
24
-
19
23
22
23
-
17
23
22
-
16
22
21
TOTAL
CAP.
MBH
52
45
40
40
51
44
39
53
46
41
41
39
48
42
37
37
46
39
35
35
1
POWER
INPUT
2
5.5
5.4
5.4
5.4
5.5
5.4
5.3
5.6
5.5
5.4
5.4
5.3
5.5
5.3
5.3
5.3
5.4
5.3
5.3
5.3
kW
86
38
45
40
40
35
44
39
40
46
41
41
39
32
40
37
37
29
36
35
35
115°F
83
40
31
39
39
39
28
36
37
37
26
33
35
35
35
44
41
41
33
42
40
SENSIBLE CAPACITY
ENTERING DRY BULB, °F
80
40
26
35
39
39
24
32
36
36
22
29
33
33
29
39
41
41
28
37
40
77
35
22
30
35
34
20
28
32
32
19
26
29
29
24
33
36
35
23
32
35
74
30
17
26
30
30
16
24
28
28
15
22
26
26
19
28
30
30
18
27
30
1
71
25
-
21
26
25
-
20
24
24
-
19
22
22
-
23
25
25
-
22
26
1. These capacities are gross ratings. For net capacity, determine the kW of the supply air blower motor from the SUPPLY AIR BLOWER PERFORMANCE
Table, multiply this value by 3.415 MBH/kW to determine the motor heat, and deduct this heat from the gross capacity of the unit.
2. These ratings include the compressor and the condenser fan motors but not the supply air blower motor. The total condenser fan motor power input
is 0.36kW. Refer to the SUPPLY AIR BLOWER PERFORMANCE Table for the kW of the supply air blower motor.
68
20
-
17
21
21
-
16
20
20
-
15
19
19
-
17
20
19
-
17
21
NOMINAL RATING
68
18
26
26
-
18
25
25
-
17
24
24
-
19
26
26
-
-
20
26
26
Unitary Products Group 13
036-21502-002-A-0303
TABLE 6: DM060 COOLING CAPACITIES (5 TON)
AIR ON
EVAPORATOR
COIL
CFM
2500
2250
2000
1750
1500
WB °F
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
72
67
62
57
TOTAL
CAP.
1
MBH
61
55
53
63
58
53
51
60
56
51
49
67
62
56
54
66
68
62
57
55
POWER
INPUT
2
kW
4.8
4.7
4.6
4.8
4.7
4.6
4.6
4.8
4.7
4.6
4.6
4.9
4.8
4.7
4.7
4.9
4.9
4.8
4.7
4.7
86
55
55
53
41
51
53
51
37
46
51
49
48
59
56
54
45
50
62
57
55
83
50
55
53
36
46
53
51
33
42
51
49
42
53
56
54
39
44
56
57
55
TEMPERATURE OF AIR ON CONDENSER COIL
85°F
SENSIBLE CAPACITY
1
ENTERING DRY BULB, °F
TOTAL
CAP.
MBH
1
POWER
INPUT
2
kW
80
44
55
53
31
41
51
49
29
38
47
45
36
47
56
54
34
38
50
57
55
77
39
50
48
27
36
47
44
25
34
43
41
30
41
50
48
29
32
43
51
48
74
34
45
42
22
32
42
40
21
30
39
37
24
35
45
42
23
25
37
44
42
71
28
39
37
-
27
37
35
-
26
35
33
-
30
39
36
-
-
31
38
36
68
23
34
32
-
22
32
30
-
21
31
29
-
24
33
31
-
-
24
32
29
65
60
53
51
65
59
53
50
64
58
52
50
61
56
50
47
58
53
47
45
5.1
5.1
5.2
5.4
5.1
5.2
5.2
5.4
5.2
5.2
5.3
5.4
5.2
5.2
5.3
5.3
5.6
5.3
5.3
5.4
86
54
52
50
40
49
50
47
36
44
47
45
47
57
53
50
44
50
60
53
51
80
43
52
50
31
39
48
46
28
36
44
42
35
45
53
50
33
37
48
53
51
95°F
SENSIBLE CAPACITY
1
ENTERING DRY BULB, °F
83
48
52
50
35
44
50
47
32
40
47
45
41
51
53
50
39
43
54
53
51
77
38
47
44
26
35
43
41
24
32
40
38
29
40
47
44
28
31
42
47
44
74
32
42
39
21
30
39
36
20
28
36
34
23
34
41
39
22
24
35
41
38
71
27
36
34
-
25
34
32
-
24
32
29
-
28
35
33
-
-
29
34
32
AIR ON
EVAPORATOR
CFM
2500
2250
2000
1750
1500
COIL
WB °F
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
TOTAL
CAP.
1
MBH
46
60
54
48
46
57
51
45
43
54
48
43
41
61
55
49
47
61
54
48
POWER
INPUT
2
kW
6.1
5.9
5.9
5.9
6.0
5.9
5.8
5.8
6.0
5.8
5.7
5.8
6.0
5.8
5.7
5.8
6.0
5.8
5.7
5.8
86
48
55
49
47
45
53
48
46
42
52
48
46
38
47
45
43
34
42
43
41
105°F
ENTERING DRY BULB, °F
83
41
52
49
47
39
49
48
46
37
47
48
46
34
42
45
43
30
38
43
41
SENSIBLE CAPACITY
1
80
33
44
48
46
32
41
48
35
46
49
47
46
29
38
44
42
26
34
39
38
TEMPERATURE OF AIR ON CONDENSER COIL
77
28
38
42
40
26
36
43
29
39
42
40
41
24
33
39
37
22
30
35
34
74
22
32
37
35
21
31
37
22
33
36
34
35
19
28
34
32
18
26
31
30
71
-
26
31
29
-
25
32
-
27
30
28
30
-
24
30
28
-
22
27
26
68
-
20
25
23
-
20
27
-
20
23
21
25
-
19
25
23
-
18
23
21
TOTAL
CAP.
MBH
57
50
44
42
57
50
44
57
50
44
42
42
53
46
41
39
49
43
38
37
1
POWER
INPUT
2
6.6
6.5
6.4
6.4
6.6
6.5
6.4
6.7
6.6
6.5
6.5
6.3
6.5
6.4
6.3
6.3
6.5
6.4
6.3
6.2
kW
86
43
50
44
42
41
50
44
46
50
44
42
42
37
45
41
39
33
40
38
37
115°F
83
42
36
45
44
42
32
41
41
39
28
36
38
37
39
50
44
42
38
47
44
SENSIBLE CAPACITY
ENTERING DRY BULB, °F
80
42
30
40
44
42
27
36
39
38
24
32
35
34
33
43
44
42
32
42
44
77
36
25
34
38
37
23
31
35
33
20
28
31
30
27
37
38
36
26
36
38
74
31
20
29
33
32
18
26
30
29
16
24
27
26
20
31
31
30
20
30
32
1
71
25
-
24
28
26
-
22
25
24
-
20
23
22
-
24
25
23
-
24
26
1. These capacities are gross ratings. For net capacity, determine the kW of the supply air blower motor from the SUPPLY AIR BLOWER PERFORMANCE
Table, multiply this value by 3.415 MBH/kW to determine the motor heat, and deduct this heat from the gross capacity of the unit.
2. These ratings include the compressor and the condenser fan motors but not the supply air blower motor. The total condenser fan motor power input
is 0.36kW. Refer to the SUPPLY AIR BLOWER PERFORMANCE Table for the kW of the supply air blower motor.
68
19
-
18
22
21
-
17
21
19
-
16
19
18
-
18
19
17
-
18
20
NOMINAL RATING
68
22
31
28
-
21
29
27
-
20
27
25
-
22
29
27
-
-
23
28
25
14 Unitary Products Group
036-21502-002-A-0303
TABLE 7: DM072 COOLING CAPACITIES (6 TON)
AIR ON
EVAPORATOR
COIL
CFM
2700
2550
2400
2100
1800
WB °F
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
72
67
62
57
TOTAL
CAP.
1
MBH
83
73
71
79
79
69
67
74
74
65
63
82
82
71
69
83
80
80
70
68
POWER
INPUT
2
kW
5.7
5.5
5.6
5.7
5.7
5.5
5.6
5.6
5.6
5.4
5.5
5.7
5.7
5.5
5.6
5.7
5.7
5.7
5.5
5.6
86
70
73
71
54
65
69
67
50
60
65
63
60
73
71
69
58
63
76
70
68
83
63
73
71
48
59
69
67
44
55
65
63
53
65
71
69
51
55
68
70
68
TEMPERATURE OF AIR ON CONDENSER COIL
85°F
SENSIBLE CAPACITY
1
ENTERING DRY BULB, °F
TOTAL
CAP.
MBH
1
POWER
INPUT
2
kW
80
56
70
71
41
53
66
67
39
50
62
63
46
58
70
69
44
47
60
70
68
77
49
63
64
35
47
60
61
34
44
57
58
38
51
62
62
37
40
53
62
60
74
42
56
57
29
40
54
54
28
39
51
52
31
43
55
55
30
32
45
55
52
71
35
49
50
-
34
47
48
-
34
46
47
-
36
48
47
-
-
37
47
45
68
28
42
43
-
28
41
42
-
28
41
42
-
29
41
40
-
-
30
39
37
77
77
71
71
76
76
70
70
75
75
69
69
73
73
67
67
71
71
65
65
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.2
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
86
70
69
69
53
65
67
67
49
59
65
65
60
73
70
70
58
63
75
71
71
80
57
68
68
41
52
63
63
38
48
58
58
46
58
69
70
44
47
60
71
71
95°F
SENSIBLE CAPACITY
1
ENTERING DRY BULB, °F
83
64
69
69
47
59
66
66
43
54
63
63
53
66
70
70
51
55
68
71
71
77
50
61
61
35
46
57
57
33
43
53
53
39
51
62
62
37
40
53
63
63
74
43
54
54
29
40
51
51
27
38
47
47
31
44
55
55
30
32
45
56
56
71
36
47
47
-
34
45
45
-
32
42
42
-
36
48
48
-
-
37
48
48
AIR ON
EVAPORATOR
CFM
2700
2550
2400
2100
1800
COIL
WB °F
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
TOTAL
CAP.
1
MBH
64
75
70
64
64
73
68
61
61
70
65
59
59
76
71
64
64
76
71
64
POWER
INPUT
2
kW
7.1
7.1
7.0
7.0
7.1
7.1
7.0
7.0
7.1
7.1
7.0
7.0
7.1
7.1
7.0
7.0
7.1
7.0
7.0
6.9
86
61
70
64
64
59
69
64
64
56
68
64
64
52
63
61
61
47
57
59
59
105°F
ENTERING DRY BULB, °F
83
53
66
64
64
51
64
64
64
49
61
64
64
45
56
61
61
41
51
58
58
SENSIBLE CAPACITY
1
80
44
56
64
64
43
54
63
45
58
64
64
63
39
50
58
58
36
46
54
53
TEMPERATURE OF AIR ON CONDENSER COIL
77
37
49
56
56
36
48
56
38
50
56
56
56
33
44
52
52
31
41
48
48
74
29
42
49
49
29
41
49
30
43
49
49
49
27
38
46
46
25
35
43
43
71
-
34
42
42
-
34
42
-
35
41
41
42
-
32
40
40
-
30
38
37
68
-
27
35
34
-
27
35
-
27
34
34
35
-
26
34
34
-
25
32
32
TOTAL
CAP.
MBH
76
66
58
58
76
66
59
75
65
57
57
59
73
63
56
56
69
60
53
53
1
POWER
INPUT
2
7.9
7.9
7.8
7.7
8.0
7.9
7.8
7.9
7.8
7.8
7.7
7.7
7.9
7.8
7.7
7.7
7.8
7.8
7.7
7.6
kW
86
57
66
58
58
55
66
59
59
65
57
57
59
50
61
56
56
45
55
53
53
115°F
83
58
48
59
59
59
44
54
56
56
40
49
53
53
51
64
57
57
49
61
58
SENSIBLE CAPACITY
ENTERING DRY BULB, °F
80
58
41
52
59
58
37
48
54
53
34
44
49
49
43
56
57
57
42
54
58
77
50
34
45
52
51
31
42
48
47
29
39
44
44
36
48
50
50
35
47
51
74
43
27
38
45
44
25
36
42
41
23
33
39
38
28
41
42
42
27
40
43
1
71
36
-
32
38
37
-
30
35
35
-
28
33
33
-
33
34
34
-
32
36
1. These capacities are gross ratings. For net capacity, determine the kW of the supply air blower motor from the SUPPLY AIR BLOWER PERFORMANCE
Table, multiply this value by 3.415 MBH/kW to determine the motor heat, and deduct this heat from the gross capacity of the unit.
2. These ratings include the compressor and the condenser fan motors but not the supply air blower motor. The total condenser fan motor power input
is 0.36kW. Refer to the SUPPLY AIR BLOWER PERFORMANCE Table for the kW of the supply air blower motor.
68
29
-
25
31
30
-
24
29
29
-
23
28
27
-
25
27
27
-
25
29
NOMINAL RATING
68
29
40
40
-
28
38
39
-
27
37
37
-
29
40
40
-
-
30
40
40
Unitary Products Group 15
036-21502-002-A-0303
TABLE 8: SUPPLY AIR BLOWER PERFORMANCE (3 TON BELT DRIVE) - SIDE DUCT APPLICATION
UNIT
SIZE
(MBH)
036
1 2
AIR
FLOW
CFM
1700
1600
1500
1400
1300
1200
1100
1000
900
0.20
0.30
AVAILABLE EXTERNAL STATIC PRESSURE-IWG
3
0.40
0.50
0.60
0.70
0.80
RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS
835 705 880 745 923 795 969 860 1013 970 -
811 655 854 695 898 740 942 790 986 840 1029 900 -
782
-
-
-
610
-
-
-
827
798
-
-
650
595
-
-
871
844
816
-
685
640
590
-
917
889
862
834
730
680
635
585
960
932
907
881
775
720
675
630
1003
975
951
927
825
765
715
665
1046
1018
995
970
905
790
750
705
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
809
782
-
550
510
-
855
829
797
590
545
500
900
872
843
625
858
540
942
919
890
665
625
580
UNIT
SIZE
(MBH)
036
1 2
AVAILABLE EXTERNAL STATIC PRESSURE-IWG
1.10
1.20
1.30
3
AIR
FLOW
CFM
0.90
1.00
1.40
1.50
1700
1600
1500
1400
1300
1200
1100
1000
900
RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS
-
-
-
1055
1036
1011
987
963
936
-
-
-
875
780
735
690
655
615
-
-
-
-
1066
1047
1028
1005
980
-
-
-
-
850
765
720
680
645
-
-
-
-
-
1075
1060
1040
1020
-
-
-
-
-
800
750
695
660
-
-
-
-
-
-
1084
1068
1050
-
-
-
-
-
-
775
715
670
-
-
-
-
-
-
-
1089
1053
-
-
-
-
-
-
-
735
680
-
-
-
-
-
-
-
-
1090
-
-
-
-
-
-
-
-
690
-
-
-
-
-
-
-
-
-
1. 230/460/575 Volts
2. For 208 Volts multiply values by 0.95.
3. Includes allowances for a wet evaporator coil, 1” filters, and the heat exchangers. Refer to ACCESSORY STATIC RESISTANCE Table
for resistance values on applications other than gas / electric units with side duct airflows.
-
-
-
-
-
-
-
-
-
16 Unitary Products Group
036-21502-002-A-0303
TABLE 9: SUPPLY AIR BLOWER PERFORMANCE (4 TON BELT DRIVE) - SIDE DUCT APPLICATION
UNIT
SIZE
(MBH)
0
48 1 2
AIR
FLOW
CFM
2000
1900
1800
1700
1600
1500
1400
1300
1200
0.20
0.30
AVAILABLE EXTERNAL STATIC PRESSURE-IWG
3
0.40
0.50
0.60
0.70
0.80
RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS
843 860 880 925 919 1005 956 1065 993 1145 1030 1195 1067 1235
817 775 854 850 893 920 930 995 970 1065 1008 1125 1046 1170
790
-
-
-
700
-
-
-
828
802
-
-
760
670
-
-
867
840
818
-
840
745
665
-
906
881
858
842
905
815
740
695
944
920
898
882
980
900
820
755
985
961
940
922
1040
970
890
835
1025
1001
980
962
1100
1030
950
895
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
833
-
-
650
-
-
867
858
847
705
665
640
904
893
880
765
725
680
942
932
916
820
785
730
UNIT
SIZE
(MBH)
048 1 2
AIR
FLOW
CFM
RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS
1103
1085
1270
1210
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
1064
1040
1020
1003
982
970
953
0.90
1145
1075
1005
945
880
835
780
1102
1081
1060
1044
1024
1010
992
1.00
1180
1115
1050
995
920
870
815
AVAILABLE EXTERNAL STATIC PRESSURE-IWG
3
1.10
1.20
1.30
-
1121
1100
1086
1067
1053
1034
-
1140
1085
1035
965
920
855
-
-
-
-
1107
1099
1080
-
-
-
-
1000
960
905
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
1.40
-
-
-
-
-
-
-
-
-
-
-
-
-
-
1.50
2000
1900
1800
1700
1600
1500
1400
1300
1200
1. 230/460/575 Volts
2. For 208 Volts multiply values by 0.95.
3. Includes allowances for a wet evaporator coil, 1” filters, and the heat exchangers. Refer to ACCESSORY STATIC RESISTANCE Table for
resistance values on applications other than gas / electric units with side duct airflows.
-
-
-
-
-
-
-
Unitary Products Group 17
036-21502-002-A-0303
TABLE 10: SUPPLY AIR BLOWER PERFORMANCE (5 TON BELT DRIVE) - SIDE DUCT APPLICATION
UNIT
SIZE
(MBH)
060
1 2
AIR
FLOW
CFM
2500
2400
2300
2200
2100
2000
1900
1800
1700
1600
1500
0.20
0.30
AVAILABLE EXTERNAL STATIC PRESSURE-IWG
3
0.40
0.50
0.60
0.70
0.80
-
-
-
-
-
RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS
1059 1560 1077 1590 1095 1630 1114 1650 1134 1660 1158 1685 1181 1720
1032 1405 1054 1470 1074 1525 1094 1560 1116 1595 1140 1620 1167 1640
1005
980
930
877
1260
1160
1060
950
1024
1002
957
908
1275
1170
1070
975
1049
1022
983
941
1370
1190
1080
1000
1069
1044
1010
976
1440
1250
1100
1020
1090
1066
1039
1009
1475
1350
1160
1050
1116
1090
1064
1040
1505
1410
1260
1100
1142
1117
1092
1070
1535
1440
1340
1225
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
894
855
-
-
-
885
815
-
-
-
940
903
884
864
-
940
860
815
770
-
980
950
925
908
882
980
905
850
805
740
1014
988
964
948
926
1020
940
880
835
780
1047
1022
1001
987
965
1095
970
910
870
830
UNIT
SIZE
(MBH)
060
1 2
AIR
FLOW
CFM
2500
2400
2300
2200
2100
2000
1900
1800
1700
1600
1500
1100
1079
1058
1035
1020
1004
0.90
1.00
AVAILABLE EXTERNAL STATIC PRESSURE-IWG
3
1.10
1.20
1.30
1.40
1.50
RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS
-
1193
1170
1148
1121
1665
1580
1480
1385
-
1202
1180
1155
-
1620
1530
1425
-
-
-
1190
-
-
-
1475
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
1285
1180
1060
960
900
860
1133
1110
1090
1071
1056
1038
1340
1240
1135
1030
965
880
1169
1143
1122
1103
1088
1070
1385
1280
1190
1100
1035
925
1205
1178
1158
1134
1118
1101
1445
1330
1240
1140
1065
980
-
1222
1196
1164
1145
1130
-
1375
1295
1175
1105
1045
-
-
-
1197
1170
1158
-
-
-
1205
1130
1075
-
-
-
-
1198
1184
1. 230/460/575 Volts
2. For 208 Volts multiply values by 0.95.
3. Includes allowances for a wet evaporator coil, 1” filters, and the heat exchangers. Refer to ACCESSORY STATIC RESISTANCE Table for
resistance values on applications other than gas / electric units with side duct airflows.
-
-
-
-
1150
1110
18 Unitary Products Group
036-21502-002-A-0303
TABLE 11: SUPPLY AIR BLOWER PERFORMANCE (6 TON BELT DRIVE) - SIDE DUCT APPLICATION
UNIT
SIZE
(MBH)
072
1 2
AIR
FLOW
CFM
3200
3000
2800
2600
2400
2200
2000
1800
0.20
0.30
AVAILABLE EXTERNAL STATIC PRESSURE-IWG
3
0.40
0.50
0.60
0.70
0.80
RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS
1150 2325 1182 2425 1212 2525 -
1100 2010 1129 2090 1157 2150 1185 2225 1215 2290 1242 2360 -
1045
985
930
-
-
-
1700
1425
1240
-
-
-
1074
1015
958
905
-
-
1780
1475
1300
1070
-
-
1102
1045
990
933
-
-
1850
1540
1350
1160
-
-
1131
1075
1020
965
919
-
1940
1630
1400
1210
1025
-
1160
1103
1051
997
950
909
2025
1715
1430
1250
1100
925
1190
1135
1081
1028
982
939
2075
1760
1490
1285
1130
1005
1217
1163
1111
1060
1014
968
2130
1825
1600
1325
1160
1030
UNIT
SIZE
(MBH)
072
1 2
AIR
FLOW
CFM
3200
3000
2800
2600
2400
2200
2000
1800
0.90
1.00
AVAILABLE EXTERNAL STATIC PRESSURE-IWG
3
1.10
1.20
1.30
1.40
1.50
RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS
-
-
1245
1193
1142
1090
1045
998
2190
1920
1675
1380
1175
1050
-
1222
1173
1124
1077
1028
-
1990
1730
1450
1200
1060
-
1250
1205
1155
1109
1058
-
2060
1800
1550
1275
1060
-
-
1234
1186
1140
1087
-
-
1885
1640
1360
1075
-
-
-
1217
1170
1118
-
-
-
1710
1460
1150
-
-
-
1249
1205
1148
-
-
-
1775
1545
1250
-
-
-
-
1235
1176
1. 230/460/575 Volts
2. For 208 Volts multiply values by 0.95.
3. Includes allowances for a wet evaporator coil, 1” filters, and the heat exchangers. Refer to ACCESSORY STATIC RESISTANCE Table for
resistance values on applications other than gas / electric units with side duct airflows.
-
-
-
-
1600
1360
Unitary Products Group 19
036-21502-002-A-0303
TABLE 12: SUPPLY AIR BLOWER PERFORMANCE (3 - 6 TON DIRECT DRIVE) - SIDE DUCT APPLICATION
UNIT SIZE
(MBH)
036
1
048
1
MOTOR SPEED
HI
MED
LOW
HI
MED
LOW
HI
MED
LOW
HI
CFM
-
0.20
WATTS
-
1684
1487
1996
1804
1681
2400
2290
2150
2461
800
710
960
838
760
1155
1105
1020
1480
CFM
-
AVAILABLE EXTERNAL STATIC PRESSURE-IWG
2
0.30
0.40
0.50
WATTS
-
CFM
1699
WATTS
825
CFM
1650
WATTS
785
1631
1464
1933
1765
1640
2338
2214
2100
2402
780
690
936
810
738
1125
1065
990
1440
1582
1421
1868
1714
1604
2274
2145
2029
2361
750
670
910
785
715
1095
1030
950
1395
1524
1367
1795
1650
1541
2167
2071
1965
2260
720
650
880
765
695
1045
990
910
1350
CFM
1570
0.60
WATTS
755
1410
1315
1722
1589
1490
2096
1990
1905
2178
690
620
845
735
670
1010
950
880
1305
060
1
072
1
UNIT SIZE
(MBH)
036
048
060
1
1
1
MOTOR SPEED
HI
MED
LOW
HI
MED
LOW
HI
MED
LOW
HI
CFM
1430
1324
1246
1635
1508
1416
1990
1911
1816
2101
0.70
WATTS
725
650
605
820
705
645
980
920
838
1260
AVAILABLE EXTERNAL STATIC PRESSURE-IWG
2
0.80
0.90
CFM
1360
1260
1185
1544
1407
1337
1887
1828
1724
2000
WATTS
700
630
590
790
675
620
945
885
800
1205
CFM
1280
1185
1110
1419
1306
1230
1771
1724
1644
1914
WATTS
680
610
570
765
645
595
905
835
770
1155
CFM
1180
1100
1020
1300
1195
1120
1629
1604
1531
1830
1.00
WATTS
655
590
545
740
625
575
855
798
710
1110 072
1
1. Side Duct application (230/460/575 Volts)
2. Includes allowances for a wet evaporator coil, 1” filters, and the heat exchangers. Refer to STATIC RESISTANCES Table for resistance values
TABLE 13: BELT DRIVE BLOWER MOTOR AND DRIVE DATA
MODEL
SIZE
3 TON
4 TON
5 TON
6 TON
BLOWER
RANGE
(RPM)
790/1120
MOTOR
1
HP
1 1/2
790/1120 1 1/2
850/1220 1 1/2
900/1250 1 1/2
FRAME
56
56
56
56
ADJUSTABLE MOTOR PULLEY
DESIG-
NATION
1VL40
1VL40
1VL40
1VL44
OUTSIDE
DIA.
(IN.)
2.7-3.7
2.7-3.7
2.7-3.7
3.1-4.1
PITCH
DIA.
(IN.)
2.4-3.4
2.4-3.4
2.4-3.4
2.8-3.8
BORE
(IN.)
5/8
5/8
5/8
7/8
FIXED BLOWER PULLEY
DESIG-
NATION
AK61
AK61
AK56
AK56
OUTSIDE
DIA.
(IN.)
5.9
5.9
5.4
5.4
PITCH
DIA.
(IN.)
5.7
5.7
5.2
5.2
BORE
(IN.)
1
1
1
1
DESIG-
NATION
A36
A36
A36
A36
BELT
(NOTCHED)
PITCH
LENGTH
(IN.)
37.3
37.3
37.3
37.3
1. All motors have solid bases and are inherently protected. these motors can be selected to operate into their service factor because they are located in the moving air, upstream of any heating device.
QTY.
1
1
1
1
20 Unitary Products Group
036-21502-002-A-0303
TABLE 14: STATIC RESISTANCES
DESCRIPTION
ECON OMIZER
ELECTRIC
HEATERS
3
1 2
5-15KW
20-30KW
BOTTOM DUCT CONNECTIONS
1
COOLING ONLY
2
1000
0.07
0.04
0.06
0.06
0.08
1200
0.08
0.05
0.07
0.07
0.10
1400
0.09
0.06
0.08
0.08
0.12
1600
0.11
0.07
0.09
0.09
0.14
RESISTANCE, IWG
1800
CFM
2000 2200
0.13
0.08
0.11
0.10
0.16
0.15
0.10
0.13
0.11
0.18
0.17
0.12
0.15
0.12
0.20
2400
0.20
0.14
0.17
0.14
0.23
2600
0.23
0.16
0.20
0.16
0.26
2800
0.26
0.19
0.23
0.19
0.29
1. Deduct these resistance values from the available external static pressure shown in SUPPLY AIR BLOWER PERFORMANCE Tables.
2. The pressure through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return air
duct system is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.
3. Add these resistance values to the available static resistance values on SUPPLY AIR BLOWER PERFORMANCE Tables.
3000
0.30
0.22
0.26
0.22
0.32
TABLE 15: ELECTRIC HEATER CFM LIMITATIONS
UNIT MODEL SIZE NOMINAL
TONS
3
4
5
6
VOLTAGE
208/230-1-60
208/230-3-60
460-3-60
575-3-60
208/230-1-60
208/230-3-60
460-3-60
575-3-60
208/230-1-60
208/230-3-60
460-3-60
575-3-60
208/230-1-60
208/230-3-60
460-3-60
575-3-60
1300
1300
-
-
1600
1600
-
5
1100
1100
-
-
-
1800
1800
-
-
1300
1300
1300
-
1600
1600
1600
7
1100
1100
1100
-
-
1800
1800
1800
-
MINIMUM SUPPLY AIR CFM
HEATER SIZE NOMINAL KW
1300
1300
1300
1300
1600
1600
1600
10
1200
1200
1200
1200
1600
1800
1800
1800
1800
1600
1800
1800
1800
1800
1300
1300
1300
1300
1600
1600
1600
15
1200
1200
1200
1200
1300
1300
1300
1400
1600
1600
1600
20
1300
1300
1300
1300
1600
1800
1800
1800
1800
-
-
-
-
1600
1600
1600
30
-
-
-
-
1800
1800
1800
1800
1800
Unitary Products Group 21
036-21502-002-A-0303
TABLE 16: ELECTRICAL DATA - DM036 & 048 DIRECT DRIVE WITHOUT POWR’D CONVENIENCE OUTLET
Model
Tonnage
3
4
Voltage
Compressors
RLA
Each
LRA
Each
OD Fan
Motor
FLA
ID Blower
Motor
FLA
Conv
Outlet
Amps
Electric Heater
Model No.
Heater kW
Heater
Amps
Minimum
Circuit
Ampacity
Amps
208-1-60
230-1-60
208-3-60
230-3-60
460-3-60
575-3-60
208-1-60
230-1-60
208-3-60
230-3-60
460-3-60
575-3-60
19.2
19.2
14.1
14.1
7.1
5.8
25.0
25.0
14.7
14.7
7.7
6.4
87
87
110
110
54
44
135
135
130
130
64
52
2.3
2.3
2.3
2.3
1.3
1.3
2.3
2.3
2.3
2.3
1.3
1.3
4.4
4.4
4.4
4.4
2.2
2.2
5.0
5.0
5.0
5.0
2.2
2.2
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
2CE04511058
2CE04511558
2CE04512058
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
NONE
2CE04510525
2
2CE04510725
2
2CE04511025
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
NONE
2CE04510525
2
2CE04510725
2
2CE04511025
2CE04511525
2CE04512025
NONE
2CE04510525
2CE04510525
2
2CE04510725
2
2CE04511525
2CE04512025
NONE
2CE04510746
2
2CE04511046
2
2CE04511546
2
2CE04512046
2
NONE
2CE04511525
2CE04512025
NONE
2CE04510525
2
2CE04510725
2
2CE04511025
2CE04511525
2CE04512025
NONE
2CE04510746
2
2CE04511046
2
2CE04511546
2
2CE04512046
2
NONE
2CE04511058
2CE04511558
2CE04512058
21.2
0.0
6.8
10.1
13.6
19.5
0.0
10.6
15.9
21.2
8.0
11.9
15.9
0.0
5.3
7.5
10.6
15.9
5.3
7.5
10.6
15.9
21.2
0.0
4.0
5.6
21.2
0.0
4.0
5.6
8.0
11.9
15.9
0.0
0.0
6.8
10.1
13.6
19.5
0.0
10.6
15.9
11.9
15.9
0.0
5.3
7.5
10.6
15.9
21.2
7.5
10.6
15.9
21.2
0.0
4.0
5.6
8.0
0.0
4.0
5.6
8.0
11.9
15.9
0.0
5.3
51.0
0.0
8.2
12.1
16.4
23.5
0.0
10.2
15.3
20.4
22.2
33.0
44.1
0.0
12.7
18.0
25.5
38.2
22.1
31.3
44.2
66.3
88.3
0.0
11.1
15.5
20.4
0.0
19.2
26.9
38.5
57.2
76.4
0.0
0.0
8.2
12.1
16.4
23.5
0.0
10.2
15.3
33.0
44.1
0.0
12.7
18.0
25.5
38.2
51.0
31.3
44.2
66.3
88.3
0.0
11.1
15.5
22.2
0.0
19.2
26.9
38.5
57.2
76.4
0.0
22.1
70.0
13.1
13.1
17.9
23.2
32.1
10.8
14.9
21.3
27.7
34.0
47.5
61.4
25.7
25.7
28.8
38.1
54.1
38.5
45.3
61.5
89.1
116.7
25.7
25.7
25.7
27.7
38.5
38.5
39.9
54.3
77.8
101.8
38.5
12.4
13.0
17.9
23.2
32.1
10.1
14.9
21.3
46.8
60.7
24.3
24.3
28.1
37.4
53.3
69.2
44.6
60.7
88.3
115.9
24.3
24.3
24.9
33.3
30.7
30.7
39.2
53.6
77.0
101.1
30.7
33.1
1. HACR Type per NEC.
2. These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block accessories
2FB04700825 and 2FB04700846 are available for field installation.
Max Fuse /
BRKR
1
Size
Amps
25
35
15
15
70
20
20
20
25
30
40
40
40
60
40
50
70
40
60
60
70
90
125
40
40
40
30
60
60
60
60
80
110
60
35
15
15
25
15
15
20
25
35
40
60
70
50
70
35
35
35
35
35
35
45
70
90
125
45
45
45
60
80
110
45
45
22 Unitary Products Group
036-21502-002-A-0303
TABLE 17: ELECTRICAL DATA - DM060 & 072 DIRECT DRIVE WITHOUT POWR’D CONVENIENCE OUTLET
Model
Tonnage
5
6
Voltage
Compressors
RLA
Each
LRA
Each
OD Fan
Motor
FLA
ID Blower
Motor
FLA
Conv
Outlet
Amps
Electric Heater
Model No.
Heater kW
Heater
Amps
208-1-60
230-1-60
208-3-60
230-3-60
460-3-60
575-3-60
208-3-60
230-3-60
460-3-60
575-3-60
28.9
28.9
16.0
16.0
8.0
6.4
18.9
18.9
9.5
7.6
165
165
125
125
66.5
50
146
146
73
58.4
1.3
1.3
1.3
1.3
0.8
0.8
1.3
1.3
0.8
0.8
6.6
6.6
6.6
6.6
3.3
3.3
6.8
6.8
3.6
3.6
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
2CE04513006
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
2CE04513006
NONE
2CE04510525
2
2CE04510725
2
2CE04511025
2CE04511525
2CE04512025
2CE04513025
NONE
2CE04510525
2
2CE04510725
2
2CE04511025
2CE04511525
2CE04512025
2CE04513025
NONE
2CE04510746
2
2CE04511046
2
2CE04511546
2
2CE04512046
2
2CE04513046
2
NONE
2CE04511058
2CE04511558
2CE04512058
2CE04513058
NONE
2CE04510525
2
2CE04510725
2
2CE04511025
2CE04511525
2CE04512025
2CE04513025
NONE
2CE04510525
2
2CE04510725
2
2CE04511025
2CE04511525
2CE04512025
2CE04513025
NONE
2CE04510746
2
2CE04511046
2
2CE04511546
2
2CE04512046
2
2CE04513046
2
NONE
2CE04511058
2CE04511558
2CE04512058
2CE04513058
28.8
0.0
10.6
15.9
21.2
30.4
15.9
21.2
29.6
0.0
6.8
10.1
13.6
19.5
8.0
11.9
15.9
22.2
0.0
5.3
7.5
10.6
19.5
28.8
0.0
10.6
15.9
21.2
30.4
0.0
4.0
5.6
10.6
15.9
21.2
29.6
0.0
6.8
10.1
13.6
5.6
8.0
11.9
15.9
22.2
0.0
5.3
7.5
5.3
7.5
10.6
15.9
21.2
29.6
0.0
4.0
0.0
4.0
5.6
8.0
11.9
15.9
22.2
0.0
34.6
0.0
10.2
15.3
20.4
29.3
38.2
51.0
71.2
0.0
8.2
12.1
16.4
23.5
22.2
33.0
44.1
61.6
0.0
12.7
18.0
25.5
23.5
34.6
0.0
10.2
15.3
20.4
29.3
0.0
11.1
15.5
25.5
38.2
51.0
71.2
0.0
8.2
12.1
16.4
15.5
22.2
33.0
44.1
61.6
0.0
12.7
18.0
22.1
31.3
44.2
66.3
88.3
123.3
0.0
11.1
0.0
19.2
26.9
38.5
57.2
76.4
106.7
0.0
1. HACR Type per NEC.
2. These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block accessories
2FB04700825 and 2FB04700846 are available for field installation.
50
15
20
25
30
40
60
80
100
25
25
25
25
35
50
50
50
50
50
50
70
90
40
50
50
50
35
50
15
20
25
30
45
60
80
100
20
20
20
25
90
40
40
40
40
40
50
70
70
70
70
100
125
175
40
40
80
110
150
70
70
70
70
70
Minimum
Circuit
Ampacity
Amps
47.8
13.0
16.3
22.7
29.1
40.2
56.3
72.2
97.5
16.3
16.3
19.7
24.9
33.8
36.3
49.8
63.7
85.5
31.7
31.7
31.7
40.4
33.4
47.4
11.3
16.0
22.4
28.8
39.9
31.7
31.7
31.7
40.1
56.1
72.0
97.3
14.1
14.3
19.3
24.6
27.9
36.0
49.5
63.4
85.3
27.9
27.9
30.8
44.0
47.3
63.5
91.1
118.7
162.4
27.9
27.9
44.0
44.0
44.0
56.3
79.8
103.8
141.7
44.0
Max Fuse /
BRKR
1
Size
Amps
Unitary Products Group 23
036-21502-002-A-0303
TABLE 18: ELECTRICAL DATA - DM036 & 048 BELT DRIVE WITHOUT POWR’D CONVENIENCE OUTLET
Model
Tonnage
3
4
Voltage
Compressors
RLA
Each
LRA
Each
OD Fan
Motor
FLA
ID Blower
Motor
FLA
Conv
Outlet
Amps
Electric Heater
Model No.
Heater kW
Heater
Amps
Minimum
Circuit
Ampacity
Amps
208-1-60
230-1-60
208-3-60
230-3-60
460-3-60
575-3-60
208-1-60
230-1-60
208-3-60
230-3-60
460-3-60
575-3-60
18.0
18.0
11.4
11.4
6.2
5.0
24.4
24.4
14.1
14.1
7.1
5.8
105
105
90
90
45
36
140
140
105
105
55
44
1.3
1.3
1.3
1.3
0.8
0.8
1.3
1.3
1.3
1.3
0.8
0.8
7.6
7.6
5.2
5.2
2.6
2
7.6
7.6
5.2
5.2
2.6
2
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
2CE04511525
2CE04512025
NONE
2CE04510746
2
2CE04511046
2
2CE04511546
2
2CE04512046
2
NONE
2CE04511058
2CE04511558
2CE04512058
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
NONE
2CE04510525
2
2CE04510725
2
2CE04511025
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
NONE
2CE04510525
2
2CE04510725
2
2CE04511025
2CE04511525
2CE04512025
NONE
2CE04510525
2
2CE04510725
2
2CE04511025
2CE04511525
2CE04512025
NONE
2CE04510525
2
2CE04510725
2
2CE04511025
2CE04511525
2CE04512025
NONE
2CE04510746
2
2CE04511046
2
2CE04511546
2
2CE04512046
2
NONE
2CE04511058
2CE04511558
2CE04512058
21.2
0.0
6.8
10.1
13.6
19.5
0.0
10.6
15.9
21.2
8.0
11.9
15.9
0.0
5.3
7.5
10.6
15.9
5.3
7.5
10.6
15.9
21.2
0.0
4.0
5.6
21.2
0.0
4.0
5.6
8.0
11.9
15.9
0.0
0.0
6.8
10.1
13.6
19.5
0.0
10.6
15.9
11.9
15.9
0.0
5.3
7.5
10.6
15.9
21.2
7.5
10.6
15.9
21.2
0.0
4.0
5.6
8.0
0.0
4.0
5.6
8.0
11.9
15.9
0.0
5.3
51.0
0.0
8.2
12.1
16.4
23.5
0.0
10.2
15.3
20.4
22.2
33.0
44.1
0.0
12.7
18.0
25.5
38.2
22.1
31.3
44.2
66.3
88.3
0.0
11.1
15.5
20.4
0.0
19.2
26.9
38.5
57.2
76.4
0.0
0.0
8.2
12.1
16.4
23.5
0.0
10.2
15.3
33.0
44.1
0.0
12.7
18.0
25.5
38.2
51.0
31.3
44.2
66.3
88.3
0.0
11.1
15.5
22.2
0.0
19.2
26.9
38.5
57.2
76.4
0.0
22.1
70.2
12.3
13.5
18.4
23.7
32.6
9.5
14.7
21.1
27.5
34.3
47.8
61.7
24.1
24.1
29.1
38.4
54.3
39.4
48.6
64.7
92.3
119.9
24.1
24.1
25.9
27.5
39.4
39.4
43.2
57.6
81.0
105.1
39.4
11.1
13.5
18.4
23.7
32.6
8.5
14.7
21.1
47.8
61.7
20.8
22.4
29.1
38.4
54.3
70.2
48.6
64.7
92.3
119.9
20.8
20.8
25.9
34.3
31.4
33.5
43.2
57.6
81.0
105.1
31.4
37.1
1. HACR Type per NEC.
2. These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block accessories
2FB04700825 and 2FB04700846 are available for field installation.
Max Fuse /
BRKR
1
Size
Amps
25
35
15
15
80
15
15
20
25
30
35
35
40
60
35
50
70
35
60
60
70
100
125
35
35
35
60
90
110
60
30
60
60
60
35
15
15
25
15
15
20
25
30
40
60
80
50
70
30
30
50
70
100
125
30
30
30
35
90
110
45
45
45
45
45
60
24 Unitary Products Group
036-21502-002-A-0303
TABLE 19: ELECTRICAL DATA - DM060 & 072 BELT DRIVE WITHOUT POWR’D CONVENIENCE OUTLET
Model
Tonnage
5
6
Voltage
Compressors
RLA
Each
LRA
Each
OD Fan
Motor
FLA
ID Blower
Motor
FLA
Conv
Outlet
Amps
Electric Heater
Model No.
Heater kW
Heater
Amps
Minimum
Circuit
Ampacity
Amps
208-1-60
230-1-60
208-3-60
230-3-60
460-3-60
575-3-60
208-3-60
230-3-60
460-3-60
575-3-60
28.9
28.9
16.0
16.0
8.0
6.4
18.9
18.9
9.5
7.6
165
165
125
125
66.5
50
146
146
73
58.4
1.3
1.3
1.3
1.3
0.8
0.8
1.3
1.3
0.8
0.8
7.6
7.6
5.2
5.2
2.6
2
5.0
5.0
2.5
2
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
2CE04513025
NONE
2CE04510746
2
2CE04511046
2
2CE04511546
2
2CE04512046
2
2CE04513046
2
NONE
2CE04511058
2CE04511558
2CE04512058
2CE04513058
NONE
2CE04510525
2
2CE04510725
2
2CE04511025
2CE04511525
2CE04512025
2CE04513025
NONE
2CE04510525
2
2CE04510725
2
2CE04511025
2CE04511525
2CE04512025
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
2CE04513006
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
2CE04513006
NONE
2CE04510525
2
2CE04510725
2
2CE04511025
2CE04511525
2CE04512025
2CE04513025
NONE
2CE04510525
2
2CE04510725
2
2CE04511025
2CE04511525
2CE04512025
2CE04513025
NONE
2CE04510746
2
2CE04511046
2
2CE04511546
2
2CE04512046
2
2CE04513046
2
NONE
2CE04511058
2CE04511558
2CE04512058
2CE04513058
10.1
13.6
19.5
28.8
0.0
10.6
15.9
21.2
30.4
5.3
7.5
10.6
15.9
21.2
29.6
0.0
6.8
0.0
4.0
5.6
8.0
11.9
15.9
22.2
0.0
13.6
19.5
28.8
0.0
10.6
15.9
21.2
30.4
10.6
15.9
21.2
29.6
0.0
6.8
10.1
5.6
8.0
11.9
15.9
22.2
0.0
5.3
7.5
5.3
7.5
10.6
15.9
21.2
29.6
0.0
4.0
0.0
4.0
5.6
8.0
11.9
15.9
22.2
0.0
12.1
16.4
23.5
34.6
0.0
10.2
15.3
20.4
29.3
12.7
18.0
25.5
38.2
51.0
71.2
0.0
8.2
0.0
11.1
15.5
22.2
33.0
44.1
61.6
0.0
16.4
23.5
34.6
0.0
10.2
15.3
20.4
29.3
25.5
38.2
51.0
71.2
0.0
8.2
12.1
15.5
22.2
33.0
44.1
61.6
0.0
12.7
18.0
22.1
31.3
44.2
66.3
88.3
123.3
0.0
11.1
0.0
19.2
26.9
38.5
57.2
76.4
106.7
0.0
18.3
23.6
32.4
46.4
11.7
14.7
21.1
27.5
38.6
29.9
29.9
38.1
54.1
70.0
95.3
15.2
15.2
29.9
29.9
29.9
34.0
47.5
61.4
83.3
29.9
23.7
32.6
46.6
10.2
14.7
21.1
27.5
38.6
38.4
54.3
70.2
95.5
13.4
13.5
18.4
26.5
34.3
47.8
61.7
83.5
26.5
26.5
29.1
45.0
48.6
64.7
92.3
119.9
163.7
26.5
26.5
45.0
45.0
45.0
57.6
81.0
105.1
142.9
45.0
1. HACR Type per NEC.
2. These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block accessories
2FB04700825 and 2FB04700846 are available for field installation.
Max Fuse /
BRKR
1
Size
Amps
15
15
25
30
40
20
25
35
50
70
100
20
20
45
45
45
60
50
70
90
45
45
45
45
45
15
25
30
40
25
35
50
15
40
60
80
100
20
20
20
90
40
40
40
40
40
50
70
70
70
70
100
125
175
40
40
90
110
150
70
70
70
70
70
Unitary Products Group 25
036-21502-002-A-0303
TABLE 20: ELECTRICAL DATA - DM036 & 048 DIRECT DRIVE WITH POWR’D CONVENIENCE OUTLET
Model
Tonnage
3
4
Voltage
Compressors
RLA
Each
LRA
Each
OD Fan
Motor
FLA
ID Blower
Motor
FLA
Conv
Outlet
Amps
Electric Heater
Model No.
Heater kW
Heater
Amps
208-1-60
230-1-60
208-3-60
230-3-60
460-3-60
575-3-60
208-1-60
230-1-60
208-3-60
230-3-60
460-3-60
575-3-60
18.0
18.0
11.4
11.4
6.2
5.0
24.4
24.4
14.1
14.1
7.1
5.8
105
105
90
90
45
36
140
140
105
105
55
44
1.3
1.3
1.3
1.3
0.8
0.8
1.3
1.3
1.3
1.3
0.8
0.8
4.4
4.4
4.4
4.4
2.2
2.2
5.0
5.0
5.0
5.0
2.2
2.2
10.0
10.0
10.0
10.0
5.0
4.0
10.0
10.0
10.0
10.0
5.0
4.0
2CE04511525
2CE04512025
NONE
2CE04510746
2
2CE04511046
2
2CE04511546
2
2CE04512046
2
NONE
2CE04511058
2CE04511558
2CE04512058
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
NONE
2CE04510525
2
2CE04510725
2
2CE04511025
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
NONE
2CE04510525
2
2CE04510725
2
2CE04511025
2CE04511525
2CE04512025
NONE
2CE04510525
2
2CE04510725
2
2CE04511025
2CE04511525
2CE04512025
NONE
2CE04510525
2
2CE04510725
2
2CE04511025
2CE04511525
2CE04512025
NONE
2CE04510746
2
2CE04511046
2
2CE04511546
2
2CE04512046
2
NONE
2CE04511058
2CE04511558
2CE04512058
21.2
0.0
6.8
10.1
13.6
19.5
0.0
10.6
15.9
8.0
11.9
15.9
0.0
5.3
7.5
10.6
15.9
5.3
7.5
10.6
15.9
21.2
0.0
4.0
5.6
21.2
0.0
4.0
5.6
8.0
11.9
15.9
0.0
0.0
6.8
10.1
13.6
19.5
0.0
10.6
15.9
11.9
15.9
0.0
5.3
7.5
10.6
15.9
21.2
7.5
10.6
15.9
21.2
0.0
4.0
5.6
8.0
0.0
4.0
5.6
8.0
11.9
15.9
0.0
5.3
21.2
51.0
0.0
8.2
12.1
16.4
23.5
0.0
10.2
15.3
22.2
33.0
44.1
0.0
12.7
18.0
25.5
38.2
22.1
31.3
44.2
66.3
88.3
0.0
11.1
15.5
20.4
0.0
19.2
26.9
38.5
57.2
76.4
0.0
0.0
8.2
12.1
16.4
23.5
0.0
10.2
15.3
33.0
44.1
0.0
12.7
18.0
25.5
38.2
51.0
31.3
44.2
66.3
88.3
0.0
11.1
15.5
22.2
0.0
19.2
26.9
38.5
57.2
76.4
0.0
22.1
20.4
1. HACR Type per NEC.
2. These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block accessories
2FB04700825 and 2FB04700846 are available for field installation.
30
40
15
20
30
90
20
20
25
45
45
60
70
50
70
80
45
70
70
80
110
150
45
45
45
70
100
125
70
35
70
70
70
40
15
20
30
20
20
25
30
45
50
70
90
60
80
40
40
60
80
110
150
40
40
40
50
90
125
50
50
50
50
60
70
35
Minimum
Circuit
Ampacity
Amps
82.5
16.9
19.2
24.2
29.4
38.3
13.7
19.9
26.3
46.5
60.0
73.9
33.9
34.7
41.3
50.6
66.6
46.8
57.8
74.0
101.6
129.2
33.9
33.9
38.2
32.7
46.8
46.8
52.4
66.8
90.3
114.3
46.8
15.8
19.2
24.2
29.4
38.3
12.7
19.9
26.3
59.3
73.2
29.9
33.9
40.6
49.9
65.8
81.7
57.1
73.2
100.8
128.4
29.9
31.9
37.4
45.8
38.2
42.0
51.7
66.1
89.5
113.6
38.2
45.6
32.7
Max Fuse /
BRKR
1
Size
Amps
26 Unitary Products Group
036-21502-002-A-0303
TABLE 21: ELECTRICAL DATA - DM060 & 072 DIRECT DRIVE WITH POWR’D CONVENIENCE OUTLET
Model
Tonnage
5
6
Voltage
Compressors
RLA
Each
LRA
Each
OD Fan
Motor
FLA
ID Blower
Motor
FLA
Conv
Outlet
Amps
Electric Heater
Model No.
Heater kW
Heater
Amps
Minimum
Circuit
Ampacity
Amps
208-1-60
230-1-60
208-3-60
230-3-60
460-3-60
575-3-60
208-3-60
230-3-60
460-3-60
575-3-60
28.9
28.9
16.0
16.0
8.0
6.4
18.9
18.9
9.5
7.6
165
165
125
125
66.5
50
146
146
73
58.4
1.3
1.3
1.3
1.3
0.8
0.8
1.3
1.3
0.8
0.8
6.6
6.6
6.6
6.6
3.3
3.3
6.8
6.8
3.6
3.6
10.0
10.0
10.0
10.0
5.0
4.0
10.0
10.0
5.0
4.0
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
2CE04513006
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
2CE04513006
NONE
2CE04510525
2
2CE04510725
2
2CE04511025
2CE04511525
2CE04512025
2CE04513025
NONE
2CE04510525
2
2CE04510725
2
2CE04511025
2CE04511525
2CE04512025
2CE04513025
NONE
2CE04510746
2
2CE04511046
2
2CE04511546
2
2CE04512046
2
2CE04513046
2
NONE
2CE04511058
2CE04511558
2CE04512058
2CE04513058
NONE
2CE04510525
2
2CE04510725
2
2CE04511025
2CE04511525
2CE04512025
2CE04513025
NONE
2CE04510525
2
2CE04510725
2
2CE04511025
2CE04511525
2CE04512025
2CE04513025
NONE
2CE04510746
2
2CE04511046
2
2CE04511546
2
2CE04512046
2
2CE04513046
2
NONE
2CE04511058
2CE04511558
2CE04512058
2CE04513058
28.8
0.0
10.6
15.9
21.2
30.4
15.9
21.2
29.6
0.0
6.8
10.1
13.6
19.5
8.0
11.9
15.9
22.2
0.0
5.3
7.5
10.6
19.5
28.8
0.0
10.6
15.9
21.2
30.4
0.0
4.0
5.6
10.6
15.9
21.2
29.6
0.0
6.8
10.1
13.6
5.6
8.0
11.9
15.9
22.2
0.0
5.3
7.5
5.3
7.5
10.6
15.9
21.2
29.6
0.0
4.0
0.0
4.0
5.6
8.0
11.9
15.9
22.2
0.0
34.6
0.0
10.2
15.3
20.4
29.3
38.2
51.0
71.2
0.0
8.2
12.1
16.4
23.5
22.2
33.0
44.1
61.6
0.0
12.7
18.0
25.5
23.5
34.6
0.0
10.2
15.3
20.4
29.3
0.0
11.1
15.5
25.5
38.2
51.0
71.2
0.0
8.2
12.1
16.4
15.5
22.2
33.0
44.1
61.6
0.0
12.7
18.0
22.1
31.3
44.2
66.3
88.3
123.3
0.0
11.1
0.0
19.2
26.9
38.5
57.2
76.4
106.7
0.0
68.8
84.7
110.0
21.3
21.3
25.9
31.2
40.1
54.1
17.0
21.3
27.7
34.1
45.2
48.8
62.3
76.2
98.0
41.7
41.7
43.6
52.9
39.7
53.7
15.3
21.0
27.4
33.8
44.9
41.7
41.7
41.7
52.6
68.6
84.5
109.8
19.1
20.6
25.6
30.8
40.2
48.5
62.0
75.9
97.8
37.9
37.9
43.3
54.0
59.8
76.0
103.6
131.2
174.9
37.9
37.9
54.0
54.0
54.4
68.8
92.3
116.3
154.2
54.0
1. HACR Type per NEC.
2. These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block accessories
2FB04700825 and 2FB04700846 are available for field installation.
Max Fuse /
BRKR
1
Size
Amps
60
20
25
30
35
45
70
90
125
30
30
30
35
45
60
70
80
100
60
60
60
60
45
60
60
60
40
60
20
25
30
35
60
70
90
110
25
25
30
35
100
50
50
50
50
50
70
80
80
80
80
110
150
175
50
50
100
125
175
80
80
80
80
80
Unitary Products Group 27
036-21502-002-A-0303
TABLE 22: ELECTRICAL DATA - DM036 & 048 BELT DRIVE WITH POWR’D CONVENIENCE OUTLET
Model
Tonnage
3
4
Voltage
Compressors
RLA
Each
LRA
Each
OD Fan
Motor
FLA
ID Blower
Motor
FLA
Conv
Outlet
Amps
Electric Heater
Model No.
Heater kW
Heater
Amps
Minimum
Circuit
Ampacity
Amps
208-1-60
230-1-60
208-3-60
230-3-60
460-3-60
575-3-60
208-1-60
230-1-60
208-3-60
230-3-60
460-3-60
575-3-60
18.0
18.0
11.4
11.4
6.2
5.0
24.4
24.4
14.1
14.1
7.1
5.8
105
105
90
90
45
36
140
140
105
105
55
44
1.3
1.3
1.3
1.3
0.8
0.8
1.3
1.3
1.3
1.3
0.8
0.8
7.6
7.6
5.2
5.2
2.6
2
7.6
7.6
5.2
5.2
2.6
2
10.0
10.0
10.0
10.0
5.0
4.0
10.0
10.0
10.0
10.0
5.0
4.0
2CE04511525
2CE04512025
NONE
2CE04510746
2
2CE04511046
2
2CE04511546
2
2CE04512046
2
NONE
2CE04511058
2CE04511558
2CE04512058
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
NONE
2CE04510525
2
2CE04510725
2
2CE04511025
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
NONE
2CE04510525
2
2CE04510725
2
2CE04511025
2CE04511525
2CE04512025
NONE
2CE04510525
2
2CE04510725
2
2CE04511025
2CE04511525
2CE04512025
NONE
2CE04510525
2
2CE04510725
2
2CE04511025
2CE04511525
2CE04512025
NONE
2CE04510746
2
2CE04511046
2
2CE04511546
2
2CE04512046
2
NONE
2CE04511058
2CE04511558
2CE04512058
21.2
0.0
6.8
10.1
13.6
19.5
0.0
10.6
15.9
21.2
8.0
11.9
15.9
0.0
5.3
7.5
10.6
15.9
5.3
7.5
10.6
15.9
21.2
0.0
4.0
5.6
21.2
0.0
4.0
5.6
8.0
11.9
15.9
0.0
0.0
6.8
10.1
13.6
19.5
0.0
10.6
15.9
11.9
15.9
0.0
5.3
7.5
10.6
15.9
21.2
7.5
10.6
15.9
21.2
0.0
4.0
5.6
8.0
0.0
4.0
5.6
8.0
11.9
15.9
0.0
5.3
51.0
0.0
8.2
12.1
16.4
23.5
0.0
10.2
15.3
20.4
22.2
33.0
44.1
0.0
12.7
18.0
25.5
38.2
22.1
31.3
44.2
66.3
88.3
0.0
11.1
15.5
20.4
0.0
19.2
26.9
38.5
57.2
76.4
0.0
0.0
8.2
12.1
16.4
23.5
0.0
10.2
15.3
33.0
44.1
0.0
12.7
18.0
25.5
38.2
51.0
31.3
44.2
66.3
88.3
0.0
11.1
15.5
22.2
0.0
19.2
26.9
38.5
57.2
76.4
0.0
22.1
82.7
17.3
19.7
24.7
29.9
38.8
13.5
19.7
26.1
32.5
46.8
60.3
74.2
34.1
34.9
41.6
50.9
66.8
49.6
61.1
77.2
104.8
132.4
34.1
34.1
38.4
32.5
49.4
49.4
55.7
70.1
93.5
117.6
49.4
16.1
19.7
24.7
29.9
38.8
12.5
19.7
26.1
60.3
74.2
30.8
34.9
41.6
50.9
66.8
82.7
61.1
77.2
104.8
132.4
30.8
32.9
38.4
46.8
41.4
46.0
55.7
70.1
93.5
117.6
41.4
49.6
1. HACR Type per NEC.
2. These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block accessories
2FB04700825 and 2FB04700846 are available for field installation.
Max Fuse /
BRKR
1
Size
Amps
30
40
15
20
90
20
20
25
30
35
45
45
60
70
50
70
80
45
70
70
80
110
150
45
45
45
80
100
125
70
35
70
70
70
40
15
20
30
20
20
25
30
45
60
70
90
70
80
40
40
70
80
110
150
40
40
40
50
100
125
50
50
50
50
60
80
28 Unitary Products Group
036-21502-002-A-0303
TABLE 23: ELECTRICAL DATA - DM060 & 072 BELT DRIVE WITH POWR’D CONVENIENCE OUTLET
Model
Tonnage
5
6
Voltage
Compressors
RLA
Each
LRA
Each
OD Fan
Motor
FLA
ID Blower
Motor
FLA
Conv
Outlet
Amps
Electric Heater
Model No.
Heater kW
Heater
Amps
Minimum
Circuit
Ampacity
Amps
208-1-60
230-1-60
208-3-60
230-3-60
460-3-60
575-3-60
208-3-60
230-3-60
460-3-60
575-3-60
28.9
28.9
16.0
16.0
8.0
6.4
18.9
18.9
9.5
7.6
165
165
125
125
66.5
50
146
146
73
58.4
1.3
1.3
1.3
1.3
0.8
0.8
1.3
1.3
0.8
0.8
7.6
7.6
5.2
5.2
2.6
2
5.0
5.0
2.5
2
10.0
10.0
10.0
10.0
5.0
4.0
10.0
10.0
5.0
4.0
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
2CE04513006
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
2CE04513006
NONE
2CE04510525
2
2CE04510725
2
2CE04511025
2CE04511525
2CE04512025
2CE04513025
NONE
2CE04510525
2
2CE04510725
2
2CE04511025
2CE04511525
2CE04512025
2CE04513025
NONE
2CE04510746
2
2CE04511046
2
2CE04511546
2
2CE04512046
2
2CE04513046
2
NONE
2CE04511058
2CE04511558
2CE04512058
2CE04513058
NONE
2CE04510525
2
2CE04510725
2
2CE04511025
2CE04511525
2CE04512025
2CE04513025
NONE
2CE04510525
2
2CE04510725
2
2CE04511025
2CE04511525
2CE04512025
2CE04513025
NONE
2CE04510746
2
2CE04511046
2
2CE04511546
2
2CE04512046
2
2CE04513046
2
NONE
2CE04511058
2CE04511558
2CE04512058
2CE04513058
28.8
0.0
10.6
15.9
21.2
30.4
15.9
21.2
29.6
0.0
6.8
10.1
13.6
19.5
8.0
11.9
15.9
22.2
0.0
5.3
7.5
10.6
19.5
28.8
0.0
10.6
15.9
21.2
30.4
0.0
4.0
5.6
10.6
15.9
21.2
29.6
0.0
6.8
10.1
13.6
5.6
8.0
11.9
15.9
22.2
0.0
5.3
7.5
5.3
7.5
10.6
15.9
21.2
29.6
0.0
4.0
0.0
4.0
5.6
8.0
11.9
15.9
22.2
0.0
34.6
0.0
10.2
15.3
20.4
29.3
38.2
51.0
71.2
0.0
8.2
12.1
16.4
23.5
22.2
33.0
44.1
61.6
0.0
12.7
18.0
25.5
23.5
34.6
0.0
10.2
15.3
20.4
29.3
0.0
11.1
15.5
25.5
38.2
51.0
71.2
0.0
8.2
12.1
16.4
15.5
22.2
33.0
44.1
61.6
0.0
12.7
18.0
22.1
31.3
44.2
66.3
88.3
123.3
0.0
11.1
0.0
19.2
26.9
38.5
57.2
76.4
106.7
0.0
66.6
82.5
107.8
20.2
20.2
24.6
29.8
38.7
52.7
15.7
19.7
26.1
32.5
43.6
46.5
60.0
73.9
95.8
39.9
39.9
41.3
50.6
38.8
52.8
14.2
19.7
26.1
32.5
43.6
39.9
39.9
39.9
50.9
66.8
82.7
108.0
18.4
19.7
24.7
29.9
38.4
46.8
60.3
74.2
96.0
36.5
36.5
41.6
55.0
61.1
77.2
104.8
132.4
176.2
36.5
36.5
55.0
55.0
55.7
70.1
93.5
117.6
155.4
55.0
1. HACR Type per NEC.
2. These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block accessories
2FB04700825 and 2FB04700846 are available for field installation.
Max Fuse /
BRKR
1
Size
Amps
60
20
20
30
35
45
70
90
110
25
25
25
30
40
50
70
80
100
50
50
50
60
45
50
50
50
40
60
20
20
30
35
60
70
90
110
25
25
25
30
100
50
50
50
50
50
70
80
80
80
80
110
150
200
50
50
100
125
175
80
80
80
80
80
Unitary Products Group 29
036-21502-002-A-0303
TABLE 24: PHYSICAL DATA
EVAPORATOR
BLOWER
EVAPORATOR
COIL
CONDENSER
FANS
CONDENSER
COILS
COMPRESSOR
(Qty. Per Unit)
AIR
FILTERS
CHARGE
MODELS
Centrifugal Blower (Dia. x Wd. in.)
Fan Motor HP (Direct Drive)
Fan Motor HP (Belt Drive)
Rows Deep
Fins Per Inch
Face Area (Sq. Ft.)
Propeller Dia. (in.)
Fan Motor Hp
Nom. CFM
Rows Deep
Fins Per Inch
Face Area (Sq. Ft.)
Scroll Type
Quantity Per Unit (15” X 20” X 1” or 2“)
Quantity Per Unit (14” X 25” X 1” or 2“)
Total Face Area (sq. ft.)
Refrigerant 22
(lbs./oz.)
TABLE 25: ELECTRIC HEAT CORRECTION FACTORS
NOMINAL VOLTAGE VOLTAGE kW CAP. MULTI-
PLIER
208
240
480
600
208
230
460
575
1.00
0.92
0.92
0.92
036
12 X 10
1/2
1 1/2
3
13
3.6
24
1/4
3400
1
16
17.1
1
2
1
6.3
5/8
048
12 X 10
3/4
1 1/2
3
13
4.3
24
1/4
3400
1
16
17.1
DM
060
12 X 10
1
1 1/2
3
13
5.1
24
1/4
3400
1
22
17.1
1
2
1
6.3
6/8
1
2
1
6.3
6/8
TABLE 26: VOLTAGE LIMITATIONS
1
VOLTAGE
POWER SUPPLY
MIN.
208/230-3-60
460-3-60
575-3-60
187
414
518
MAX.
253
506
506
1. Utilization Range “A” in accordance with ARI Standard
110.
072
12 X 11
1
1 1/2
4
13
5.1
24
1/4
3400
2
16
16.7
1
2
1
6.3
10/0
30 Unitary Products Group
036-21502-002-A-0303
TYPICAL POWER WIRING
REFER TO THE ELECTRICAL DATA
TABLES TO SIZE THE DISCONNECT
SWITCH, OVERCURRENT PROTEC-
TION AND WIRING.
COOLING ONLY (24 VOLT THERMOSTAT)
THERMOSTAT 1
TERMINALS
RV
UNIT TERMINAL
STRIP TB1
TYPICAL CONTROL WIRING
COOLING / HEATING (24 VOLT THERMOSTAT)
THERMOSTAT 1
TERMINALS
RH
UNIT TERMINAL
STRIP TB1
ADD
JUMPER
RC R
24 VOLT
TRANSFORMER
YC
R
Y1 Y Y1 24 VOLT
TRANSFORMER
Y2
Y2
W1
GF G
W
W2
C
G G
1 24 VOLT THERMOSTAT 2TH07701024. TO CONTROL THE ECONOMIZER
ON SECOND STAGE COOLING, USE THE THERMOSTAT 2TH0401224.
C
1 24 VOLT THEROMSTAT 2ET07701024. TO CONTROL THE ECONOMIZER ON THE SECOND
STAGE COOLING OR TO HAVE AN ELECTRIC HEAT ACCESSORY WITH TWO STAGES OF
HEAT, USE THERMOSTAT 2TH0471024.
COOLING / HEATING (ELECTRONIC THEROMSTAT)
MULTI STAGE
ADD
JUMPER
THERMOSTAT 1
TERMINALS
RC
RH
4
Y1
Y2
W1
W2
G
ADD
JUMPER
B
LED 1
LED 2
COM
A1
A2
NOT
USED
4
2
UNIT TERMINAL
STRIP TB1
R
24 VOLT
TRANSFORMER
Y1
Y2
W1
3 W2
G
C
X
OCC
T
T
TO REMOTE SENSOR
2TH040702224 IF USED
1 ELECTRONIC PROGRAMMABLE THEROMSTAT 2TH04700224 (INCLUDES SUBBASE).
2 SECOND STAGE COOLING IS NOT REQUIRED ON UNITS LESS ECONOMIZER.
3 SECOND STAGE HEATING IS ONLY REQUIRED ON UNITS WITH A TWO STAGE
ELECTRIC HEATER.
FIGURE 2: TYPICAL FIELD POWER & CONTROL WIRING
COOLING / HEATING (ELECTRONIC THEROMSTAT)
SINGLE STAGE
THERMOSTAT 1
TERMINALS
RH
UNIT TERMINAL
STRIP TB1
R
ADD
JUMPER
RC
Y
W
G
Y1
W1
G
C
24 VOLT
TRANSFORMER
1 ELECTRONIC PROGRAMMABLE THEROMSTAT 2ET07701024 (INCLUDES SUBBASE).
TO CONTROL THE ECONOMIZER ON SECOND STAGE COOLING, USE THERMOSTAT
2TH04700224.
Unitary Products Group 31
036-21502-002-A-0303
FIGURE 3: UNIT DIMENSIONS (3 - 6 TON COOLING ONLY/ELECTRIC HEAT) FRONT VIEW
FIGURE 4: UNIT DIMENSIONS (3 - 6 TON COOLING/GAS HEAT) FRONT VIEW
32 Unitary Products Group
036-21502-002-A-0303
FIGURE 5: UNIT WITH ECONOMIZER RAINHOOD
DETAIL “A”
DETAIL “B”
FIGURE 6: UNIT WITH FIXED OUTDOOR AIR/MOTORIZED DAMPER RAINHOOD
Unitary Products Group 33
036-21502-002-A-0303
FIGURE 7: UNIT DIMENSIONS (REAR VIEW)
FILTER
ACCESS
BLOWER MOTOR
ACCESS
FIELD-SUPPLIED
DISCONNECT SWITCH
LOCATION
MOUNTING BRACKET
FOR DICONNECT SWITCH
(Shipped attached to the blower housing inside the blower compartment) A,B
WIRING ENTRY
(See Detail “B”)
DISCONNECT SWITCH LOCATION
AND MOTOR ACCESS PANEL FOR
UNIT WITH “BELT-DRIVE” OPTION
CONTROL BOX
ACCESS
FIGURE 8: DISCONNECT/BLOWER ACCESS
LOCATION
TABLE 27: UTILITIES ENTRY
HOLE
A
B
C
D
OPENING SIZE (DIA.)
7/8” KO
1
2” KO
1
1-5/8” KO
1-1/2” KO
USED FOR
Control Wiring
Power Wiring
2
Side
Bottom
Side
Bottom
Gas Piping (Front)
Gas Piping (Bottom)
1. Opening in the bottom to the unit can be located by the side in the insulation.
2. Do not remove the 2” knockout ring.
TABLE 28: MINIMUM CLEARANCES
LOCATION CLEARANCE
Front
24” (Cooling/Electric Heat)
32” (Gas Heat)
Back
Left Side (Filter Access)
Right Side (Cond. Coil)
Below Unit
1
12” (Less Economizer)
36” (With Economizer or Fixed
Air/Motorized Damper)
24” (Less Economizer)
36” (With Economizer)
24”
0”
Above Unit
2
72” (For
Condenser Air Discharge)
1. Units may be installed on combustible floors made from wood or class A, B, or C roof covering material.
2. Units must be installed outdoors. Overhanging structures or shrubs should not obstruct condenser air discharge outlet.
34 Unitary Products Group
036-21502-002-A-0303
FIGURE 9: TYPICAL APPLICATIONS
Unitary Products Group 35
036-21502-002-A-0303
44 7 /
8
D
A
X
APPROXIMATE
CENTER OF GRAVITY
FRONT OF UNIT
BACK OF UNIT
82 1 /
4
C
Y
B
CONDENSER COIL
END OF UNIT
44 7 /
8
A
F
X
APPROXIMATE
CENTER OF GRAVITY
FRONT OF UNIT
E
FIGURE 10: FOUR AND SIX POINT LOADING
TABLE 29: DM 4 POINT LOADS WEIGHT DISTRIBUTION
UNIT TOTAL A
DM036 Cooling/ Electric
DM036N04
DM036N08
DM048 Cooling/ Electric
DM048N06
DM048N10
DM060 Cooling/ Electric
DM060N08
DM060N10
DM072 Cooling/ Electric
DM072N08
DM072N10
565
685
640
700
710
625
635
615
675
720
775
785
125
152
143
158
158
140
140
137
152
164
179
179
TABLE 30: DM 6 POINT LOADS WEIGHT DISTRIBUTION
UNIT TOTAL A B
DM036 Cooling/ Electric
DM036N04
DM036N08
DM048 Cooling/ Electric
DM048N06
DM048N10
DM060 Cooling/ Electric
DM060N08
DM060N10
DM072 Cooling/ Electric
DM072N08
DM072N10
565
685
640
700
710
625
635
615
675
720
775
785
84
102
95
104
105
93
94
91
100
107
115
117
83
100
94
103
104
92
93
90
99
117
126
128
TABLE 31: CENTER OF GRAVITY
DIMENSION 3 - 5 TON
X
Y
40-¾”
19-¾”
6 TON
44”
22”
B
123
150
140
150
155
133
138
135
145
189
201
206
C
82
99
93
101
103
91
92
89
98
129
139
141
D
104
126
118
129
131
115
117
113
124
134
144
146
C
157
190
177
192
197
172
177
170
185
196
209
214
B
BACK OF UNIT
82 1 /
4
D
Y
C
CONDENSER COIL
END OF UNIT
E
105
128
119
131
133
117
119
115
126
122
131
133
D
160
193
180
200
200
180
180
173
193
171
186
186
F
107
129
121
132
134
118
120
116
128
111
120
121
36 Unitary Products Group
036-21502-002-A-0303
TABLE 32: OPERATING WEIGHTS (LBS.)
MODEL SIZE
DM (Cooling Only)
BASIC
UNIT
OPTIONS
ACCY.
DM
(Gas/Electric)
N04
N06
N08
N10
Economizer
Motorized Damper
Electric Heater
5 - 7 kW
10 - 15 kW
20 - 30 kW
Roof Curb
Barometric Relief / Fixed Air Damper
Belt-Drive Blower
3 TON
565
625
-
635
-
4 TON
615
-
675
-
685
28
92
10
5
50
26
18
23
5 TON
640
-
-
700
710
6 TON
720
-
-
775
785
FIGURE 11: ROOF CURB DIMENSIONS
Unitary Products Group 37
036-21502-002-A-0303
GUIDE SPECIFICATIONS
GENERAL
Units shall be manufactured by York International Unitary
Products Group in an ISO 9001 certified facility.
York's Sunline 2000
TM
units are convertible single packageunits. Although the units are primarily designed for curb mounting on a roof, they can also be slab-mounted at ground level or set on steel beams above a finished roof. Cooling only, cooling with gas heat and cooling with electric heat models are available with a wide variety of factory-mounted options and field-installed accessories to make them suitable for almost every application. All units are self-contained and assembled on full perimeter base rails with holes in the four corners for overhead rigging. Every unit is completely piped, wired, charged and tested at the factory to simplify the field installation and to provide years of dependable operation. All models (including those with an economizer) are suitable for either bottom or horizontal duct connections. Models with power exhaust are suitable for bottom duct connections only.
For bottom duct, remove the sheet metal panels from the supply and return air openings through the base of the unit.
For horizontal duct, remove the supply and return air panels on the rear of the unit.
All non-Scroll compressors include crankcase heaters and all compressors have internal pressure relief. Every refrigerant circuit includes a liquid line filter-drier, a discharge line high pressure switch and a suction line with a freezestat and low pressure/loss of charge switch.The unit control circuit includes a 75 VA transformer, a 24-volt circuit breaker and a relay board with a compressor lockout circuit, a terminal strip for thermostat wiring, plus an additional set of pin connectors to simplify the interface of additional field controls. All units have long lasting powder paint cabinets with 750 hour salt spray test approval under ASTMB117 procedures. All models are CSA listed. All models include a 1-year limited warranty on the complete unit. Compressors and electric heater elements carry a 5-year warranty. Aluminized steel and Stainless steel tubular heat exchangers carry a 10-year warranty.
DESCRIPTION
Units shall be factory-assembled, single packaged, Electric
Cooling/Gas Heat, Electric Cooling/Optional Electric Heat and designed for outdoor mounted installation.
The 3 thru 5 ton units shall have minimum SEER ratings of
10.0 and the 6 ton units shall have minimum EER ratings of
9.0. They shall have built-in field convertible duct connections for down discharge supply/return or horizontal discharge supply/return, and be available with factory installed options or field installed accessories. The units shall be factory wired, piped, charged with R-22 refrigerant and factory tested prior to shipment. All unit wiring shall be both numbered and color coded. All units the cooling performance shall be rated in accordance with DOE and ARI test procedures. Units shall be
CSA listed, classified to ANSI Z21.47, UL 1995/CSA No. 236 standards.
UNIT CABINET
Unit cabinet shall be constructed of G90 galvanized steel, with exterior surfaces coated with a non-chalking, powdered paint finish, certified at 750 hours salt spray test per
ASTMB117 standards. Indoor blower section shall be insulated with a minimum 1/2” thick insulation, coated on the airside. Aluminum foil faced insulation shall be used in the furnace compartment and be fastened with ridged fasteners to prevent insulation from entering the air stream. Cabinet panels shall be “large” size, easily removable for servicing and maintenance. Full perimeter base rails shall be provided to assure reliable transit of equipment, overhead rigging and proper sealing on roof curb applications. Disposable 1" filters shall be furnished and be accessible through a removable access door, sealed airtight. Units filter track shall be designed to accommodate either 1” or 2” filters. Fan performance measuring ports shall be provided on the outside of the cabinet to allow accurate air measurements of evaporator fan performance without removing panels or creating air bypass of the coils. Condensate pan shall be internally sloped and conform to ASHRAE 62-89 self-draining standards. Condensate connection shall be a minimum of 3/4” I.D. female and be a ridged mount connection.
INDOOR (EVAPORATOR) FAN ASSEMBLY
The indoor fan shall be direct drive, multi-speed, or a factory installed belt drive assembly that includes an adjustable pitch motor pulley. Job site selected (B.H.P.) brake horsepower shall not exceed the motors nameplate horsepower rating, plus the service factor. Units shall be designed not to operate above service factor. Fan wheel shall be double-inlet type with forward-curved blades, dynamically balanced to operate smoothly throughout the entire range of operation. Airflow design shall be constant air volume. Bearings shall be sealed and permanently lubricated for longer life and no maintenance.
OUTDOOR (CONDENSER) FAN ASSEMBLY
The outdoor fan shall be of the direct-driven propeller type, discharge air vertically, have aluminum blades riveted to a corrosion resistant steel spider bracket and shall be dynamically balanced for smooth operation. The outdoor fan motor shall be totally enclosed with permanently lubricated bearings, internally protected against overload conditions and staged independently.
REFRIGERANT COMPONENTS
Compressor: a.
Shall be internally protected with internal high-pressure relief and over temperature protection.
b.
Shall have internal spring isolation and sound muffling to minimize vibration and noise, and be externally isolated on a dedicated, independent mounting.
Coils: a.
Evaporator and condenser coils shall have aluminum plate fins mechanically bonded to seamless
38 Unitary Products Group
036-21502-002-A-0303 internally enhanced copper tubes with all joints brazed. Special Phenolic coating shall be available as a factory option.
b.
Evaporator and Condenser coils shall be of the direct expansion, draw-thru, design.
Refrigerant Circuit and Refrigerant Safety Components shall include: a.
Independent fixed-orifice expansion devices.
b.
Filter drier/strainer to eliminate any moisture or foreign matter.
c.
Accessible service gage connections on both suction and liquid lines to charge, evacuate, and measure refrigerant pressure during any necessary servicing or troubleshooting without losing charge.
d.
The refrigeration system shall provide at least 15°F of sub-cooling at design conditions.
UNIT CONTROLS a.
Unit shall be complete with self-contained low-voltage control circuit protected by a resetable circuit breaker on the 24-volt transformer side.
b.
Unit shall incorporate a lockout circuit which provides reset capability at the space thermostat or base unit, should any of the following standard safety devices trip and shut off compressor.
c.
Loss-of-charge/Low-pressure switch.
d.
High-pressure switch.
e.
Freeze-protection thermostat, evaporator coil. f.
If any of the above safety devices trip, a LED (lightemitting diode) indicator shall flash a diagnostic code that indicates which safety switch has tripped.
g.
Unit shall incorporate “AUTO RESET” compressor over temperature, over current protection.
h.
Unit shall operate with conventional thermostat designs and have a low voltage terminal strip for easy hook-up.
i.
Unit control board shall have on-board diagnostics and fault code display.
j.
Standard controls shall include anti-short cycle and low voltage protection, and permit cooling operation down to 0°F.
k.
Control board shall monitor each refrigerant safety switch independently.
l.
Control board shall retain last 5 fault codes in non volatile memory, which will not be lost in the event of a power loss.
GAS HEATING SECTION
Shall be designed with induced draft combustion with post purge logic, energy saving direct spark ignition, and redundant main gas valve. Venter wheel shall be constructed of stainless steel for corrosion resistance. The heat exchanger shall be of the tubular type, constructed of T1-40 aluminized steel for corrosion resistance and allowing minimum mixed air entering temperature of 25°F. Burners shall be of the inshot type, constructed of aluminum coated steel and contain air mixture adjustments. All gas piping shall enter the unit cabinet at a single location through either the side or curb, without any field modifications. An integrated control board shall provide timed control of evaporator fan functioning and burner ignition. Heating section shall be provided with the following minimum protection: a.
Primary and auxiliary high-temperature limit switches.
b.
Induced draft motor speed sensor.
c.
Flame roll out switch (manual reset).
d.
Flame proving controls.
ELECTRIC HEATING SECTION
An electric heating section, with nickel chromium elements, shall be provided in a range of 5 thru 30 KW, offering two stages of capacity - 16 KW and above on 208/230 volt heaters and 20 KW and above on 460 and 575 volt heaters. The heating section shall have a primary limit control(s) and automatic reset to prevent the heating element system from operating at an excessive temperature. The heating section assembly shall slide out of the unit for easy maintenance and service. Units with Electric Heating shall be wired for a single point power supply with branch circuit fusing (where required).
UNIT OPERATING CHARACTERISTICS a.
Unit shall be capable of starting and running at
125°F outdoor temperature, exceeding maximum load criteria of ARI Standard 210/240. The compressor, with standard controls, shall be capable of operation down to 0°F outdoor temperature. Unit shall be provided with fan time delay to prevent cold air delivery before heat exchanger warms up (Gas heat only).
ELECTRICAL REQUIREMENTS
All unit power wiring shall enter unit cabinet at a single factory provided location and be capable of side or bottom entry, to minimize roof penetrations and avoid unit field modifications.
Separate side and bottom openings shall be provided for the control wiring.
STANDARD LIMITED WARRANTIES
• Compressor 5 Years
• Heat Exchanger 10 Years
• Electric Heat Element 5 Years
• Other Parts 1 Year
Unitary Products Group 39
OPTIONAL OUTDOOR AIR (Shall be made available by either/or):
• ELECTRONIC ENTHALPY AUTOMATIC ECONO-
MIZER- Outdoor and return air dampers that are interlocked and positioned by a fully-modulating, spring return damper actuator. The maximum leakage rate for the outdoor air intake dampers shall not exceed 2% when dampers are fully closed and operating against a pressure differential of 0.5 IWG. A unit-mounted potentiometer shall be provided to adjust the outdoor and return air damper assembly to take in CFM of outdoor air to meet the minimum ventilation requirement of the conditioned space during normal operation. During economizer operation, a mixed-air temperature control shall modulate the outdoor and return air damper assembly to prevent the supply air temperature from dropping below
55°F. Changeover from compressor to economizer operation shall be provided by an integral electronic enthalpy control that feeds input into the basic module. The outdoor intake opening shall be covered with a rain hood that matches the exterior of the unit. Water eliminator/filters shall be provided. Simultaneous economizer/compressor operation is also possible. Dampers shall fully close on power loss.
• MOTORIZED OUTDOOR AIR DAMPERS - Outdoor air dampers are positioned by a 2-position, spring-return damper actuator. The maximum leakage rate for the outdoor air intake dampers shall not exceed 2% when dampers are fully closed and operating against a pressure differential of 0.5 IWG. A unit-mounted potentiometer shall be provided to adjust the outdoor damper assembly to take in the design CFM of outdoor air to meet the ventilation requirements of the conditioned space during normal operation. Whenever the indoor fan motor is energized, the dampers open up to one of two pre-selected positions - regardless of the outdoor air enthalpy. Dampers return to the fully closed position when the indoor fan motor is de-energized. Dampers shall fully close on power loss.
OTHER PRE-ENGINEERED ACCESSORIES AVAILABLE
• ROOF CURB - 14"and 8” high, full perimeter curb with wood nailer (shipped knocked-down).
• BAROMETRIC RELIEF DAMPER - Contains a rain hood, air inlet screen, exhaust damper and mounting hardware. Used to relieve internal air pressure through the unit.
• PROPANE CONVERSION KIT - Contains new orifices and gas valve parts to convert from natural to L.P. gas.
One per unit required.
• HIGH ALTITUDE - NATURAL GAS - Contains orifices required for applications between 2000 and 6000 feet altitude.
Subject to change without notice. Printed in U.S.A.
Copyright © by Unitary Products 2003. All rights reserved.
Unitary
Products
Group
5005
York
Drive
• HIGH ALTITUDE - PROPANE GAS - Contains orifices required for applications between 2000 and 6000 feet altitude. Must be used with propane conversion kit.
• LOW NOX - Required to reduce the emission of nitrogen oxides below 40 nanograms per joule.
• GAS PIPING - Contains 1/2” pipe nipples, fittings and gas cock (including panel assess gaskets) required for bottom gas supply connection with external shut off.
• POWER EXHAUST OPTION - To work in conjunction with economizers.
• ELECTRIC HEATERS
• ECONOMIZER/MOTORIZED DAMPER RAIN HOOD -
Contains all hood panels and the hardware for assembling.
• MANUAL OUTDOOR AIR DAMPER
• COIL GUARD KIT - Guard for cooling coil.
• HAIL GUARD
• FLUE EXHAUST EXTENSION
OTHER FACTORY INSTALLED OPTIONS
• POWER EXHAUST OPTION - To work in conjunction with economizers.
• STAINLESS STEEL HEAT EXCHANGER
• TECHNICOAT PHENOLIC COATED CONDENSER
AND EVAPORATOR COIL
• ELECTRONIC SINGLE ENTHALPY ECONOMIZER
• DIRTY FILTER SWITCH
• PHASE MONITOR
• COIL GUARD
• POWERED GFI CONVENIENCE OUTLET
• NON-POWERED GFI CONVENIENCE OUTLET
• BAS CONTROLS (CPC, JOHNSON, HONEYWELL,
NOVAR)
• BAS READY ECONOMIZER (BELIMO ACTUATOR
WITHOUT A CONTROLLER)
• HINGED FILTER DOOR ACCESS AND TOOLESS
ACCESS PANELS
• 2" PLEATED FILTERS
• DISCONNECT SWITCH
• SUPPLY AIR SMOKE DETECTOR
• RETURN AIR SMOKE DETECTOR
036-21502-002-A-0303
Supersedes: 036-21502-001-A-0103
Norman
OK
73069

Public link updated