Remote alarm indicator for indoors
Contents
What is conventional fire detection?
2
Conventional central units
3
Power supply
4
Conventional detectors
5
Conventional pushbuttons
6
Extinguishing system signs
7
Sirens and bells
8
Indicators
9
Retainers
10
Extinguishing system control board, batteries and poles
11
Our commitment: services and guarantees
12
1
What is
conventional fire
detection?
The conventional fire
detection system is
suitable for small and
medium facilities
Conventional fire detection is the one whose
elements (detectors, manual call points, etc) are
grouped by areas. When a detection area is in
alarm state, an acoustic and light warning is
produced through the alarm devices: sounders,
beacons, indicators, etc.
This type of fire detection installations are the
most common ones in small premises or car
parks as, due to the small dimensions of the
premises or its open-plan design, the location of
the element in alarm state is not difficult, although
the control board only shows the area where the
alarm has been produced and each area has a
high number of detectors.
Conventional fire detection installations are
designed for being long-lasting installations and
easy to maintain.
Concept for conventional installation:
Zone 1
Zone 2
Zone 3
Detection is performed through areas of detection.
Signals: failure, pre-alarm and alarm.
2
centrals
2 detection zones
• 2 conventional detection zones
• Consumption: 50mA
• Mains supply: 230Vac + -10%
• They need one unique 12V / 7Ah battery.
• Sounder outputs 1&2: 24Vdc
• Auxiliary output: 24Vdc
• Working temperature: 0 to 40º C
• Storage temperature: -20 to 60º C
• Humidity: 0 – 95%
AE/C5-2M
AE/C5-2P
4 detection zones
Common
characteristics for
every control panel.
• 30 detectors per area as maximum.
• Unlimited number of pushbuttons per area.
• Manual activation of the evacuation alarm.
• Control of access levels per key.
• Individual disconnection of detection areas and
sounder.
• Test mode for areas per a single operator.
• Alarm relay with voltage free outlet.
• Failure relay with voltage free outlet
• 2 Sounder circuits supervised through a failure
indicator.
• End of line active.
• Certifications CE regarding EN 54 parts 2 and 4.
Certificates
• 4 conventional detection zones
• Consumption: 50mA
• Mains supply: 230Vac + -10%
• They need one unique 12V / 7Ah battery.
• Sounder outputs 1&2: 24Vdc
• Auxiliary output: 24Vdc
• Working temperature: 0 to 40º C
• Storage temperature: -20 to 60º C
• Humidity: 0 – 95%
• 2 models: ABS and metal.
AE/C5-4P
AE/C5-4M
8, 12 y 16 detection zones
• Modular capacity between 8, 12 and 16
zones of conventional detection.
• Active end of line.
• Monitored exits for evacuation.
• Fault and fire detector relay.
• Test monitored areas mode.
• Control keys and status indicating LEDs.
• Capacity for a 12V /18Ah battery.
• Dimensions: 462 X 345 X 120
AE/C5-8-16
CP
D
3
power supply
Switched Power Supply 2A/24Vcc
• Dual Voltage 230/115 VAC, 50/60Hz.
• 2 independent outputs protected against
short circuits.
• Equipped with luminous indications on
the general state of power supply, status
and battery charge.
• Capacity for 2 batteries 12V/7Ah.
• Dimensions: 272x320x125mm.
AE/FL-2A
Switched Power Supply 5A
• Dual voltage 230/115 VAC, 50/60Hz.
• 2 independent outputs protected against
short circuits.
• Equipped with luminous indications on
the general state of power supply, status
and battery charge.
• Capacity for 2 batteries 12V/17Ah.
• Dimensions: 440x390x100mm.
AE/FL-5A
High capacity power supply unit 8A
• 8A maximum output current.
• Two power supply outputs independently
protected.
• Real-time monitoring of the complete state
of the system.
• Temperature compensation.
• Capacity for batteries of up to 48Ah.
• Dimensions: 408x408x224mm
AE/FL-8A
High capacity power supply unit 12A
Certified
EN 54-4
CP
D
• 12A maximum output current.
• Two power supply outputs independently
protected.
• Real-time monitoring of the complete state
of the system.
• Temperature compensation.
• Capacity for batteries of up to 48Ah.
• Dimensions: 408x408x224mm
AE/FL-12A
4
detectors
Optical smoke detectors
• Base and dust protector, included.
• Connection to 2 wires.
• Power supply between 15 and 35 Vdc.
• Power consumption: 35 •A (stand by),
80 mA (alarm).
• Dimension: Ø 99 mm
• Height including the base: 46 mm.
• Dual LED
• LPCB certified
AE/C5-OP
Optical heat detector
• Socket and dust protector, included.
• Connection to 2 wires.
• Power supply between 15 and 35 VCC.
• Power consumption: 35 •A (at rest),
80 mA (alarm).
• Dimension: Ø 99 mm
• Height including the base: 61 mm.
• Dual LED
• LPCB certified
AE/C5-OPT
Rate and rise detector
Common
characteristics
for all detectors
According to model
AE002/OP
Rate and rise detector at 24V
Certified
CP
AE/C5-TV
Optical smoke detector at 24V
• Consisting of a dark chamber.
• Automatic operation monitoring.
• Voltage stabilizer.
• Power consumption: 180uA (stand by),
22 mA (alarm).
• Diameter: 105 mm.
• Height including the base: 68 mm.
• Smart Design
• Low profile
• LPCB approved
• SMD Technology
• CE marked under C.P.D.
• Dual LED for 360º visibility
• Remote output indicator
• Standard base compatible with tree
detectors.
EN 54-4
EN 54-7
• Socket and dust protector, included.
• Connection to 2 wires.
• Power supply between 15 and 35 Vdc.
• Power consumption: 35 •A (stand by),
80 mA (alarm).
• Dimension: Ø 99 mm
• Height including the base: 46 mm.
• Dual LED
• LPCB certified
D
• When it detects the 58°C degrees are reached,
it gives an alarm signal.
• Automatic operation monitoring.
• Voltage stabilizer.
• Automatic alarm output for connecting remote
action indicators.
• Power consumption: 50 •'ECA on stand by and
22 mA in alarm
• Diameter: 105 mm.
• Height: 45 mm.
AE085/TV
5
Manual call points
M.C.P. with self-test
Equipped with: micro-switch, alarm LED with a selftest LED, verification system with reset key,
calibrated plastic sheet, so that it locks and it will
not break.
• Push button protective cap.
• Mounted in an ABS case.
• CE Certificate issued by LPCB.
• Dimensions: 98 X 95X 39 mm
AE/V-PSAT
Hold M.P.C.
Push button designed in order to block the ignition
of a system of extinction, in blue color, for interior
use, serigraphically printed with the text: HOLD.
Equipped with: Micro-switch, verification, test
system with reset key, transparent methacrylate
protection cover, normally open contacts (NO),
common C, normally closed (NC) contacts and
calibrated plastic sheet, so that it locks and does
not break.
Introduced in an ABS box of 98X98X50 mm
AE/V-PB2
Release M.C.P.
Push button designed according to EN12094-3
norm, to trigger the ignition of an extinguishing
system, in yellow colour, for interior use,
serigraphically printed with the text: RELEASE.
Equipped with: Micro-switch, verification test system
with reset key, transparent methacrylate protection
cover, normally open contacts (NO), common C,
normally
closed (NC) contacts and calibrated plastic sheet,
so that it locks and does not break.
AE/V-PD2
Emergency M.P.C.
Evacuation push button, designed for its installation
in emergency exits. Green color. Interior use.
Equipped with: Microswitch, verification, test system
with reset key, transparent methacrylate protection
cover, normally open contacts (NO), common C,
normally closed (NC) contacts and calibrated plastic
sheet, so that it locks and does not break.
Introduced in an ABS box of 98X98X50 mm.
AE/V-PE
Certified
Waterproof protection case
CP
6
D
Manufactured from strong, transparent
polycarbonate that resists temperatures between
-40 º C and+49ºC.
Easy installation.
AE/V-SW5
M.C.P.
Outdoor M.C.P.
Conventional alarm manual call points suitable for
outdoor use, IP65 according to EN 54 -11 norm.
Equipped with a microswitch, with a load resistance
of 470 ohms or 680 ohms, verification system with
reset key and LED signal alarm. Allows the
assembly
of a calibrated plastic sheet, so that it locks and
will not break, or of a breakable glass sheet,
supplied both of them.
ABS case of 85x85x58 mm
CE certificate according to DPC.
LPCB certificate. Protection: IP 65
Outdoor M.C.P. IP67
Conventional alarm manual call points, water
resistant with an IP67 protection. It has two
independent switches with voltage free contacts,
valid for connecting the switch to conventional or
algorithmic systems through the corresponding
module. In its interior it can accommodate the
miniature module of 1 input. It incorporates
calibrated plastic sheet, so that it locks and does
not break, a verification system with a reset key
and a visible image of alarm, confirming its
activation.
Dimensions: 119mm x128mm x 62mm
Operating temperature: - 20ºC to + 65ºC
signs
AE/V-PSIP
AE/V-PSIP67
Optical / acoustic extinction signs, for
indoor use.
Suitable for indoor use, IP40.
Fixed sound can be selected, intermittent sound or
no sound at all, with steady or flashing light. ABS
material, power consumption: 95 mA /24 Vdc.
Resonant intensity: 108 dB /1m.
Dimensions: 365x180x50mm
AE/V-CE
Optical / acoustic sign, for outdoor use.
Suitable for outdoor use, IP65.
Fixed sound can be selected, intermittent sound or
no sound at all, with steady or flashing light. ABS
material, power consumption: 95 mA /24 Vdc.
Resonant intensity: 108 dB /1m.
Dimensions: 365x 180 x50mm.
AE/V-CEIP
Optical / acoustic sign CO
Suitable for indoor use, IP40. Supplied with an
adhesive sign: Carbon Monoxide. Fixed sound,
intermittent sound or no sound at all, can be
selected, with steady or flashing lights. ABS material.
Dimensions: 365mm x 180mm x 50mm
Power consumption: 95mA/24Vdc.
Resonant intensity: 108dB/ 1m.
AE/V-CECO
7
sounder and beacons
Certified
Bell of 6". Certified according to EN 54-3.
Equipped with a micro-motor to power the chime
mechanism and painted in red.
Sound level: 95 dB.
Protection: IP21
Power supply: 24 Vdc.
Weight: 0.45 Kg
Power consumption: 25mA
AE/V-B6
Electronic sounder with beacon
Sounder with multi-tone focus and certified
according to EN 54-3.
Dimensions: Ø 93 mm, height: 80 mm.
Sound level: 100 dB (tone 3).
Luminous intensity: > 0.5 Cd.
Power consumption: 25 mA
Protection: IP54 (with low base) IP65 (with high
base)
AE/V-ASF1SB
Electronic sounder
Sounder of multi-tone low power consumption,
certified according to EN 54-3. Power consumption
between 6 and 33 mA, depending on the tone.
Certified according to EN 54-3.
Dimensions: Ø 93 mm, height: 63 mm.
Sound level: 102 dB (tone 3).
Protection: IP54 (with low base)
IP65 (with high base)
AE/V-AS1SB
Flash
Low power consumption flash: 88 mA.
Luminous intensity: 10 Cd.
Dimensions: Ø 106 mm, height: 91 mm.
Protection: IP54 (with low base) IP65 (with high
base)
AE/V-AF1SB
Sounder and beacon
Sounder of a high powered sound with a LED focus
for indoor use.
It includes labels:FIRE, FUEGO, INCENDIO.
Certified according to EN 54-3.
Working voltage 24V CC.
Maximum power consumption:60mA
AE/V-ASF2
Outdoor sounder
CP
8
6" alarm bell
D
Outdoor sounder with luminous LED indication.
Dimensions: 210 X 230 X 60 mm
Weight: 1.10Kg
Power supply: 12 –'96 30 VCC
Power consumption: 90mA at 24VCC
Protection: IP65
AE/V-ASFE
indicators
Built-in remote alarm indicator
Designed to indicate in a visible place the state of
the alarm, out of one or more detectors, but installed
in a hidden place.
The standard place where is normally installed is
over the doors of the rooms, connected to the
detectors installed in its interior. It uses a flush
mounted box of a standard mechanism, a 2 Watt
lamp, red optical indicator lamp and a white ABS
trim.
Measurements: 85 x 85 mm.
Power consumption: 95 mA at 24 Vdc
AE/V-RP
Surface remote alarm indicator
For wall mounting, made out of white ABS equipped
with 2 high brightness leds.
Visible from both sides.
Measurements: 70x50x25 mm.
Power consumption: 35 mA at 24 Vdc.
AE/V-RSL
Remote alarm indicator for indoors
Surface alarm indicator with a wide viewing angle.
Specifications:
Power supply: 12 / 24 Vdc.
Maximum power consumption: 20 mA.
Measurements: 65x65x35mm
Certified
CP
D
extinguishing
control panel
AE/V-IAR
Extinguishing control panel
Developed and manufactured by Aguilera Electronica
under EN12094-1.
Characteristics:
• 2 monitored detection zones.
• Operating mode, programmable as:
• Double detection:Two alarms in one zone.
• Crossed detection: One alarm in every zone.
• Mixed: Two alarms in the panel.
• Monitored detection zone for trigger extinction
button.
• Monitored entry zone for extinction pause button.
• Buttons for extinguishing the fire and pausing
extinction built into the panel.
• 2 independent monitored inputs for pressure
monitoring or control of weighing and flow control.
• Monitored output for evacuation and for fire
extinguishing poster.
• Mode selection key: automatic, manual or unarmed.
• Display indicating the time remaining for the
discharge.
• Output time before extinction programmable
between 0 and 60 seconds.
• Optional relays in order to repeat the central unit
states.
• Dimensions: 320 x 272 x 125 mm.
• It can receive 2 batteries of 12V/7Ah.
AE/PX2
9
door retainers
Retainer of a wall mount
50 Kg/490N retainer to be mounted on a wall,
push button release, traction plate, 2 protection
diodes.
EN 1155 certified
Protection: IP40
Power consumption: 45mA 24Vdc
AE/V-R2450P
Retainer to build-in
50 Kg/490N retainer, in an aluminium box,
to be mounted on a wall, traction plate, 2
protection diodes.
EN 1155 certified.
Protection: IP40
Power consumption: 45mA 24Vdc
Retainer for the floor
Retainer of 50 Kg/490N for the floor, in an
aluminium case, with a traction plate, push
button release and 2 protection diodes.
EN 1155 certified
Protection: IP40
Power consumption: 45mA 24Vdc
AE/V-R2450E
AE/V-R2450F
Retainer of 50 Kg for the floor with a
extension arm
Retainer of 50 Kg/490N for the floor, with an
extendable arm with a traction plate, push
button release and 2 protection diodes.
EN 1155 certified
Protection: IP40
Power consumption: 45mA 24Vdc
AE/V-R2450B15/ AE/V-R2450B30
Retainer of 100 Kg for the floor with a
extension arm
Retainer of 100 Kg/980N for the floor with
an extendable arm with a traction plate, push
button release and 2 protection diodes.
EN 1155 certified.
Protection: IP40
Power consumption: 45mA 24Vdc
AE/V-R24100B15
Retainer of emergency doors to be built-in
Traction force: 300 Kg / 2490 N
Monitoring the status of the door.
Protection: IP40
Power consumption: 24V 250mA
Weight: 1.82 kg
AE/V-RPE300E
Retainer of emergency doors 300 or 500 Kg
10
Traction force: 300 or 500 Kg / 2490 N
It monitors the status of the door.
Protection: IP40
Power consumption: 24V 250mA
Weight: 2.02 Kg
AE/V-RPE300/ AE/V-RPE500
retainers
test batteries
Retainer for firewall doors for 100
and 50 Kg
Formed by an encapsulated electromagnet,
equipped with a central pivot point that
expels the door, when it must be closed and it
has a traction plate with an adaptation
ball-and-socket joint, which facilitates the proper
retention of the door.
Manufactured in aluminium, lacquered white,
equipped with manual push button that
cuts power to the electromagnet, releasing the
door leaf, which will be closed by the
spring's pressure. Certified by: EN 1155
AE/V-R2440
AE/V-R24100
Retainer with a selector
Retainer with a sheet selector, located in an
aluminum enclosure & with a traction plate,
release push button and 2 protection diodes.
EN 1155 Certified.
Traction force: 50 Kg / 490 N
Power consumption: 83 mA at 24 V.
AE/V-R2440S
Measurements: 95x95x30 mm.
Emergency batteries
Lead-acid type rechargeable batteries that are maintenance free.
De 12 V / 1,2 Ah
De 12 V / 2 Ah
De 12 V / 7 Ah
De 12 V / 17 Ah
De 12 V / 24 Ah
mod. B/12-1,2
mod. B/12-2
mod. B/12-6
mod. B/12-15
mod. B/12-24
Poles for the verification of detectors
• Smoke Detector Head AE/V-PT1.
It consists of a transparent, cylindrical chamber
that can be tilted on its hook and permits for
the detector’'92s operation to be seen. At the
bottom of the chamber there is a gap in which
the smoke canister is located. The gas
discharge is caused by a slight pressure in
the chamber against the ceiling.
• Bottle of synthetic smoke. AE/V-PTB1.
• Thermal and Thermovelocimetric detector
heads. AE/V-PT2 pole of a similar construction
as above, but with a heating element and a
ventilation motor. Working temperature 100
°C and nominal voltage of 220 V AC.
• Fibreglass extension section of 1.15 m
(AE/V-PTT1.15).
AE/V-PT1
AE/V-PTB1
AE/V-PT2
AE/V-PTT1.15
11
Our commitment: services and guarantees
Projects
Grupo Aguilera offers engineering companies its support
in the detection, control and extinguishing of fires advising
on systems and covering for each building. The project
department develops
The system design and dimensioning, hydraulic
calculations, diffusers calibration and installation isometric
advising on the effectiveness of the units in each risk and
setting out the operating capacity .
Trainig
Aware of the need to know and control what we are doing,
apart from the technical support provided to the installations
where our products are used, Grupo Aguilera offers
training courses on our equipment performance, installation
and programming.
Customer service
At Grupo Aguilera each customer is important, we are
aware of the different needs for each customer, this is
the reason why our team of experts offers customized
service meeting your requirements.
Mantenance
Grupo Aguilera commits itself to offering services on
repair, reprogramming and original spare part supply after
the guarantee period.
Technical support
With the aim of guaranteeing the correct operation of
the installations, Grupo Aguilera Technical department
carries out the operation and start-up test of the units,
apart from collaborating with the installer in all the steps.
Once the system is installed with the suitable power and
water supply, and the hydraulic test has been previously
carried out, Grupo Aguilera technical staff carries out
the operation test and the start-up of the units.
Equipment guarantee
Grupo Aguilera guarantees the correct performance of
the equipments for 2 years since the delivery date: we
are responsible for the replacement and repair of the
equipments where anomalies or manufacturing faults are
observed and are delivered from our factory in Madrid.
12
v e n ti o n
a
l
C
on
CENTRAL OFFICE
C/ Julián Camarillo, 26 - 2ª planta - 28037 MADRID • Tel: 91 754 55 11 - Fax: 91 754 50 98
GAS PROCESSING UNIT
Av. Alfonso Peña Boeuf, 6. P. I. Fin de Semana - 28022 MADRID • Tel: 91 312 16 56 - Fax: 91 329 58 20
GALICIA OFFICE
C/ José Luis Bugallal Marchesi Nº 9, 1º B - 15008 A CORUÑA • Tel: 98 114 02 42 - Fax: 98 114 24 62
CATALONIA OFFICE
C/ Rafael de Casanovas, 7 y 9 - SANT ADRIA DEL BESOS - 08930 BARCELONA
• Tel: 93 381 08 04 - Fax: 93 381 07 58
VALENCIA OFFICE
Avda. Mediterránea 46, San Juan de Enova - 46669 VALENCIA
• Tel: 628 92 70 56 - Fax: 91 754 50 98
ANDALUSIA OFFICE
C/ Industria, 5 - Edificio Metropol 3, 3ª Planta, Mod. 17. P.I.S.A. 41927 Mairena del Aljarafe - SEVILLA
• Tel: 95 465 65 88 - Fax: 95 465 71 71
www.aguilera.es • e-mail: comercial@aguilera.es
Edición 07/12
CANARIES OFFICE
C/ Sao Paulo, 17 - Pol. Ind, El Sebadal - 35008 LAS PALMAS DE GRAN CANARIA
• Tel: 928 24 45 80 - Fax: 928 24 65 72
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertising