- Industrial & lab equipment
- Personal safety & protection
- Fire protection
- Honeywell
- PowerBoost3 F
- User manual
PowerBoost3 B | User manual | Honeywell PowerBoost3 F, B PowerBoost Installation and Setup Guide
Add to My manuals12 Pages
PowerBoost3 F and PowerBoost3 B are two supervised outputs that can be used for bells/sirens to meet certain UL requirements, or can serve as an auxiliary power source for remote devices such as door strikes, latches, keypads, etc. The PowerBoost3 F mounts inside its own cabinet and includes a self-contained 18VAC, 72VA transformer with enclosure (SA5110TFR). The PowerBoost3 B mounts inside a large attack-resistant cabinet with room for two batteries and includes a self-contained 18VAC, 72VA transformer with enclosure (SA1451).
advertisement
INSTALLATION AND SETUP GUIDE
About the PowerBoost3
The PowerBoost3 (herein referred to as the Module) provides two supervised outputs that can be used for bells/sirens to meet certain UL requirements, or can serve as an auxiliary power source for remote devices such as door strikes, latches, keypads, etc. The module mounts inside its own cabinet.
PowerBoost3-F
PowerBoost3-B
For bell output usage (ECP mode), the control activates the outputs and receives output status via the control’s ECP terminals. Can also report various trouble conditions to the control via on-board triggers.
ON
For auxiliary power usage (stand-alone mode), the outputs provide steady power to an attached device, and the module reports various trouble conditions to the control via on-board triggers.
PowerBoost3 Configurations
VSM-002-V0
Model Configuration
PowerBoost3-F
• Intended for Fire applications where supervised bell outputs (ECP mode) or additional auxiliary power outputs (stand-alone mode) are needed.
PowerBoost3-B
• Module mounts on a backplate inside a red cabinet.
• Includes self-contained 18VAC, 72VA transformer with enclosure (SA5110TFR) that mounts inside the cabinet.
• Intended for Commercial Burglary applications where supervised bell outputs and
72-hour battery backup is needed.
• Module mounts inside a large attack-resistant cabinet with room for two batteries.
• Includes self-contained 18VAC, 72VA transformer with enclosure (SA1451) that mounts outside the cabinet.
Module Features
ECP Mode
When used in ECP mode, the Module provides two supervised bell outputs (12VDC, 3A pool, 2A max on any one output).
The Module reports supervised conditions to the control panel via trigger output and ECP connections. These trouble conditions are reported as alarms on assigned zones (similar to zones on a 4204CF Relay Module). The Module and zones need to be programmed into the control. See Programming for ECP section for detailed information. The Module must be set for an appropriate device address via its DIP switches.
The Module supervises the following conditions when used in ECP mode:
Via ECP Connection
• Output 1 Supervision (see note 1)
• Output 2 Supervision (see note 1)
Via Trigger Output Connection
• Trouble (see note 2)
• AC Loss
• Low Battery (see note 3)
NOTES
1. Output supervision trouble activates upon EOLR open or short
2. Trouble trigger activates upon output overload, output supervision, and earth ground fault (VISTA-FBP series only)
3. Low battery trigger activates upon low battery (voltage below 11.5VDC), battery missing, or battery charger supervision conditions
Stand-Alone Mode
When used in Stand-Alone mode, the Module provides steady power of 12VDC, 2.2A total (3A alarm, 2A max on any one output) to the two outputs.
To use stand-alone mode, connect the outputs to the devices to be powered and set the module’s DIP switch to address 0 (all switches OFF).
Trigger Outputs
For control’s that do not fully support ECP communication, the Module provides three trigger outputs that can be connected to the control’s zone inputs to report the following conditions:
Trigger Action
AC Loss
Low Battery
Trouble on steady = loss of AC on steady = low battery or missing battery on steady for any of the following conditions:
- output 1 or 2 overload - ground fault
- output 1 or 2 supervision - battery charger failure
AC Loss Detection and Battery Monitoring
The Module is powered by an 18VAC 72VA wire-in transformer connected to a 120VAC source. Loss of AC power results in a fault condition reported to the control via ECP or the AC Loss trigger. The size of the battery the Module can charge is dependent upon the maximum output current of the system and the system load. This output is protected against shorts and against battery lead reversal.
The Module supervises the following battery conditions:
• Battery charger failure (reports to control via ECP or the Trouble trigger)
• Missing battery indication within 60 seconds (90 seconds for UL) of the disconnection of the battery leads (reports to control via ECP or Battery trigger).
• Low battery when the battery voltage falls below 11.5V (reports to control via ECP or Battery trigger).
Earth Ground Fault Detection
The Module supports built-in Earth Ground Fault detection that complies with UL864 Fire. A ground fault occurs upon a short through TB1-3 from any other terminal. Ground faults report to the control via ECP or the Trouble trigger
Module Shutdown
If the Module loses AC power and the battery voltage drops below 9.8VDC, the system will disconnect the battery. This feature helps prevent total discharge of the battery cells that would otherwise result in battery replacement. When AC power is restored, the battery automatically reconnects back into the system.
LED Indications
The Module has three LEDs that indicate the following conditions:
AC
ECP Bus
Low Battery
Trouble green green yellow yellow on = AC power available single flashing = communicating with control
3 flashes = loss of communication with control on = missing or low battery condition on = one or more trouble conditions exist (bell overload, output supervision, ground fault, charger fail)
- 2 -
PowerBoost3-F Mounting Procedure
Mounting the PC Board and Backplate
The PowerBoost3-F mounts in its own cabinet and includes a backplate, hardware, and Transformer.
Refer to the diagram below to mount the PC Board, backplate and transformer in the cabinet.
SECURE MOUNTING PLATE
TO CABINET WITH 4 SCREWS
TO MOUNT PC BOARD
SNAP THE UPPER CORNERS OF THE
PC BOARD ONTO PLASTIC STANDOFFS,
THEN USE SCREWS AND SPACERS TO
SECURE BOTTOM EDGE. DO NOT
OVERTIGHTEN.
IMPORTANT!
REMOVE APPROPRIATE WIRE
KNOCKOUTS BEFORE INSTALLING
MOUNTING PLATE
SNAP PLASTIC STANDOFFS
INTO MOUNTING PLATE
(SEE DETAIL A)
DIP
5
4
3
2
1
DETAIL A
PLASTIC STANDOFF (2)
(C)
INSTALL 3 SCREWS AND SPACERS
INTO MOUNTING PLATE
(SEE DETAIL B)
SA5110TFR ENCLOSED TRANSFORMER
SECURE TO CABINET WITH
4 SCREWS (C).
REPLACE COVER AFTER WIRING.
DETAIL B
SCREW AND SPACER (3)
PB3-005-V0
(C)
Mounting and Wiring the SA5110TFR Transformer
The PowerBoost3-F uses the SA5110TFR Transformer, which is an enclosed AC power transformer with manually resettable circuit breaker protection. It mounts in the lower left-hand corner of the cabinet.
UL:
• A dedicated 120VAC circuit must be used for fire applications.
• Wires must be rated for 90 degrees C or higher operation.
IMPORTANT: Make sure that the dedicated AC circuit is not powered at this time. Apply AC power only after all other wiring, except the backup battery wiring, has been completed.
Connect the transformer to the control as follows:
1. Remove the cover from the transformer's enclosure.
2. Remove the lower knockout on the left-hand side of the cabinet. Run 120VAC power wires into the transformer enclosure via this knockout.
3. Use wire nuts (not supplied) to splice the 120VAC wires to the transformer's black and white flying leads. Push the mated wires back into the transformer enclosure.
4. Connect the transformer's 18VAC blue flying leads which emerge from the top of the enclosure to the PowerBoost3 AC terminals.
- 3 -
PowerBoost3-B Mounting Procedure
Mounting the PC Board
The PowerBoost3-B mounts in its own cabinet and includes the module PC board and SA1451 transformer.
CABINET
PowerBoost3
DIP
5
4
3
1
CIRCUIT
BOARD
DETAIL A
SIDE VIEW OF
BOARD-SUPPORTING
SLOTS
DETAIL B
SIDE VIEW OF
MOUNTING CLIP
TRANSFORMER SA1451
MOUNTS EXTERNALLY TO CABINET
(REPLACE COVER AFTER WIRING)
PB3-006-V1
Mounting and Wiring the SA1451 Transformer
The PowerBoost3-B uses the SA1451 Transformer, which is an enclosed AC power transformer with manually resettable circuit breaker protection. The transformer provides 18VAC/72VA secondary winding for powering the control and mounts outside the cabinet.
To connect the SA1451 transformer to the control, perform the following steps:
1. Remove the front cover of the enclosure.
2. Mount the enclosure to the wall near the PowerBoost3 cabinet. The enclosure has four mounting holes on its back surface for this purpose.
3. Run 120VAC wiring to the enclosure in conduit. A dedicated circuit must be used.
4. Use wire nuts to splice the 120VAC wires to the transformer’s white and black primary leads.
5. Connect the earth ground post on the back of the enclosure to a good earth ground.
6. Run 16AWG wire in conduit from the enclosure to the control panel.
7. Use wire nuts to splice the transformer blue 18VAC secondary leads to the 16AWG wire. Connect the 16AWG wire at the control panel to terminals 1 and 2.
8. Replace the front cover of the enclosure and fasten it with the screws supplied.
NOTES:
• Use wires having insulation rated for at least 90°C operation and suitable for non-power limited applications
• Use care to keep 18VAC wiring separated from all other wiring inside the control panel’s enclosure. This must be done by running non-power-limited 18VAC wiring into the control panel’s enclosure via one of the knockouts on the left-hand side, and then tie-wrapping these wires to the tie-wrap loops located near the knockout.
- 4 -
Wiring Connections for the PowerBoost3 Module
Wiring for both the Powerboost3-B and PowerBoost3-F is the same.
Connection Summary
Connection Procedure
AC Connect the 18 VAC 72VA wire-in transformer to the Module’s AC Input terminals.
ECP Connects the ground, data in, and data out terminals to the control’s ECP terminals.
(control’s ECP red +12VDC connection not used)
OUTPUT For ECP operation: Connect to bell/siren respective +/– terminals. Connect 2k EOLR (EOL20) at terminals DC+ and OUT– for Class A supervision, or across the last sounder for Class B supervision.
Each of the Module’s outputs is rated 13.65 VDC, 2.0A (total combined alarm output current is 3A max).
For Stand-Alone operation: Connect the device to be powered +Input to DC+, –Input to DC–.
Connect battery terminals to battery. The charge output voltage is 13.65VDC ±1%. BATTERY
(12AH min)
TRIGGERS Connect each desired trigger to a zone + input on the control. Refer to the Zone Event Worksheet in the Programming For ECP Mode section for information on control panel zones and trigger connections.
NOTE: If used, Tamper trigger must be connected to ECP Ground (–) as shown in the Trigger Detail in the wiring diagram.
Refer to the diagram below when making connections.
ACTIVE
PowerBoost3
AC
LED
LED
TROUBLE LED
DIP
LOW
BATT
LED
TRIGGER OUTPUTS
5
4
3
2
1
SET APPROPRIATE
MODULE ADDRESS
TRIGGERS
TROUBLE: ON = TROUBLE CONDITION
AC LOSS: ON = AC LOSS
BATTERY: ON = LOW/MISSING BATTERY
TAMPER: ECP MODE ONLY.
SENDS TROUBLE IF OPENED
EARTH GROUND
DETECT JUMPER
ON = ENABLE
AC INPUT
ECP
TERMINALS
ERTH
GND GND TX RX
OUTPUT 1
†
OUT DC OUT DC
BATTERY
N/U
OUTPUT 2
†
OUT DC OUT DC
N/U
NON POWER LIMITED.
MAINTAIN MINIMUM
1/4" SPACING TO OTHER
WIRING.
POLARIZED
SUPERVISED
BELL
POLARIZED
SUPERVISED
BELL
TAMPER
TO CONTROL'S
ZONE TERMINALS
SEE TYPICAL TRIGGER
CONNECTIONS BELOW
CONNECT TO
A DEDICATED
CIRCUIT
120VAC, 60Hz,
600mA MAX
TO ECP GND
TRANSFORMERS
SA5110TFR (PowerBoost3-F)
SA1451 (PowerBoost3-B)
18VAC, 72VA
ENCLOSED TRANSFORMER
REPLACE COVER AFTER WIRING
2A CIRCUIT
BREAKER
BLK BLUE
WHT BLUE
SEE
EARTH
GROUND
NOTE
BELOW
NON POWER LIMITED.
MAINTAIN MINIMUM
1/4" SPACING
TO OTHER WIRING.
CONNECT TO
PROPER EARTH
GROUND.
GRN
NOTE: USE WIRES HAVING
INSULATION RATED FOR
90 C OR HIGHER
GRN
(13.65 VDC, 2A) (13.65 VDC, 2A)
2K EOLR
(EOL20)
2K EOLR
(EOL20)
TYPICAL CLASS B CONNECTIONS
BATTERY
CHARGING VOLTAGE: 13.65 VDC
MINIMUM BATTERY SIZE = 12AH
†
OUTPUT NOTE
FOR APPROVED SPECIAL
APPLICATION NOTIFICATION
APPLIANCE CIRCUITS, THE
MAXIMUM LINE IMPEDANCE
ALLOWED WHEN THE SYSTEM IS
FULLY LOADED TO 3A FOR DEVICES
THAT CAN OPERATE AT A MINIMUM
OF 8VDC IS 0.85 OHMS. FOR
DEVICES THAT CAN OPERATE AT A
MINIMUM OF 9VDC THE MAXIMUM
LINE IMPEDANCE IS 0.35 OHMS.
TYPICAL
STAND-ALONE
POWER
SUPPLY MODE
OUT DC OUT DC
TYPICAL TRIGGER CONNECTIONS
AC INPUT
ECP
GND
EARTH GROUND NOTE
SEE INSTRUCTIONS FOR
PROPER EARTH GROUND
CONNECTIONS
THE IMPEDANCE AT WHICH A
GROUND FAULT IS
ANNUNCIATED IS 1,000 OHMS
TYPICAL
CLASS A
CONNECTIONS
2K EOLR
(EOL20)
OUT DC OUT DC
DEVICE
TAMPER
SWITCH
ZONE ZONE
CONTROL PANEL
AUX GND (KEYPAD )
CONTROL PANEL
CONTROL PANEL
AUX
GND
DATA
IN
DATA
OUT
FOR COMMERCIAL FIRE LISTING, BOTH SPECIAL
APPLICATION OUTPUTS 1 AND 2 MUST BE USED
IN THE SAME NOTIFICATION ZONE.
PB3-003-V1
- 5 -
Programming For ECP Mode
For ECP compatible controls, the PowerBoost3 appears to the control as a 4204CF Relay module. The various output trouble conditions report to the control as alarms on specific zone numbers based on zones associated with the 4204CF
Relay module (i.e. zones 601-696). Each zone must be programmed in the control accordingly. When programming the control, set each of the reporting zones for 24hr trouble zone type.
To use ECP mode, set the DIP switch to an appropriate address for the control being used (refer to the DIP Switch Table for the switch settings for each address).
UL: If more than one PowerBoost3 module is to be used in a fire application, an ECP-ISO module must be used for each additional PowerBoost3 module.
The following table lists the trouble events that can be reported.
Zone Event Worksheet
Trigger
TRBL
(trouble)
LED
Trouble
Events Reported
Output Overload
Output Supervision
Earth Ground Fault
Connection/Programming at the Control
Overload: Trouble trigger to a control panel zone
Supervision: VISTA- “BP and FBP” series
Earth Ground Fault: VISTA- “FBP” series only
Zone Number
Overload: Any (ZT 05 or
19 recommended)
Supervision: 601-632
(based on output no.)
Earth Ground Fault: 972
AC
LOSS
AC AC Loss
LO BATT Low Batt Battery Charger
Supervision
Missing Battery
TAMPER N/A
AC Loss trigger connected to a control panel zone Any (ZT 05 or 19
Low Battery trigger connected to a control panel zone
Charger Overload/Low
Battery
Cabinet Tamper Tamper trigger connected through a N.C switch to module’s ECP Ground (term 4) recommended)
Any (ZT 05 or 19 recommended)
801-815 (based on module’s address)
DIP SWITCH SETTINGS
Use the DIP switches to set the module’s ECP address (or, if applicable, set to Stand-Alone mode) and set the desired power-up state.
Module Address
(ECP Mode = addr. 1-15)
1
ECP addr.
DIP Switch Position
2
ECP addr.
3
ECP addr.
(“–“ = ON)
4
ECP addr.
5
Power-Up State
Stand Alone Mode
†
OFF OFF OFF OFF
††
1 – OFF OFF OFF
††
3
5
7
–
– OFF
††
– OFF
††
OFF ††
– OFF – OFF
††
– OFF
††
– – – OFF
††
ON
DIP
OFF
5
4
3
2
1
9
††
††
11 – –
OFF
OFF
–
–
–
††
††
††
TRIGGER OUTPUTS
13 – OFF –
–
–
–
††
††
15 – – – –
††
† Default setting is for Stand Alone Mode (sw 1-4 = OFF) with Power Up State set to ON (sw 5 = ON).
†† SW 5 is used to determine if the module powers up with the outputs ON or OFF.
POWER UP STATE
ECP ADDRESS
- 6 -
Notes on Installing Sounders
The PowerBoost3 provides two Notification Appliance Circuits (Class A or B, Style Y supervision) for operating fire or burglary alarm notification appliances. Each circuit is rated as follows: 10VDC – 14VDC, 2A max. power limited.
NOTE: The total alarm current drawn from outputs 1 and 2 cannot exceed 2.9A for battery-independent operation.
UL:
• Burglary Notification Appliance Circuits must be programmed for a timeout of 16 minutes or longer.
• Commercial fire alarm systems require Notification Appliance Circuits to be supervised.
Notification Appliance Circuit Supervision
The PowerBoost3 monitors the Notification Appliance Circuits wiring for open and short circuit faults while the output is inactive. The system provides a trouble indication when an open occurs. When a short occurs between the Bell (+) and
Bell (–) terminal wiring, or between the Bell (+) terminal wiring and earth ground the system provides a trouble indication.
UL:
• Use only UL Listed sounding devices for UL installations.
• In Commercial Fire installations, the PoweBoost3 cannot be used to drive sounders in the same physical area as sounders connected to other alarm outputs.
Compatible Alarm Indicating Devices
Alarm Indicating Device Type
RX7 UL Indoor Sounder, 12V
Chime, 12/24V, Selectable Tone & Volume, Red
Chime, 12/24V, Selectable Tone & Volume, White
Chime/Strobe, 12/24V, Selectable Candela, Tone & Volume, Red
Chime/Strobe, 12/24V, Selectable Candela, Tone & Volume, White
Horn, 12/24V, Red
Horn, 12/24V, White
Horn, 12/24V, Outdoor, Red
2-Wire Wall Mount Horn/Strobe, 12/24V, Standard Candela, Red
2-Wire Wall Mount Horn/Strobe, 12/24V, High Candela, Red
2-Wire Wall Mount Horn/Strobe, 12/24V, Standard Candela, Red, Outdoor
2-Wire Wall Mount Horn/Strobe, 12/24V, High Candela, Red, Outdoor
2-Wire Wall Mount Horn/Strobe, 12/24V, Standard Candela, White
2-Wire Wall Mount Horn/Strobe, 12/24V, High Candela, White
4-Wire Wall Mount Horn/Strobe, 12/24V, Standard Candela, Red
4-Wire Wall Mount Horn/Strobe, 12/24V, High Candela, Red
4-Wire Wall Mount Horn/Strobe, 12/24V, Standard Candela, Red, Outdoor
4-Wire Wall Mount Horn/Strobe, 12/24V, High Candela, Red, Outdoor
4-Wire Wall Mount Horn/Strobe, 12/24V, Standard Candela, White
4-Wire Wall Mount Horn/Strobe, 12/24V, High Candela, White
2-Wire Ceiling Mount Horn/Strobe, 12/24V, Standard Candela, Red
2-Wire Ceiling Mount Horn/Strobe, 12/24V, High Candela, Red
2-Wire Ceiling Mount Horn/Strobe, 12/24V, Standard Candela, Red, Outdoor
2-Wire Ceiling Mount Horn/Strobe, 12/24V, High Candela, Red, Outdoor
2-Wire Ceiling Mount Horn/Strobe, 12/24V, Standard Candela, White
2-Wire Ceiling Mount Horn/Strobe, 12/24V, High Candela, Red
4-Wire Ceiling Mount Horn/Strobe, 12/24V, Standard Candela, Red
4-Wire Ceiling Mount Horn/Strobe, 12/24V, High Candela, Red
4-Wire Ceiling Mount Horn/Strobe, 12/24V, Standard Candela, Red, Outdoor
4-Wire Ceiling Mount Horn/Strobe, 12/24V, High Candela, Red, Outdoor
4-Wire Ceiling Mount Horn/Strobe, 12/24V, Standard Candela, White
4-Wire Ceiling Mount Horn/Strobe, 12/24V, High Candela, White
2-Wire Wall Mount Strobe, 12/24V, Standard Candela, Red
2-Wire Wall Mount Strobe, 12/24V, High Candela, Red
Wall Mount Strobe, 12/24V, Standard Candela, Red, Outdoor
Wall Mount Strobe, 12/24V, High Candela, Red, Outdoor
Wall Mount Strobe, 12/24V, Standard Candela, White
Wall Mount Strobe, 12/24V, High Candela, White
Ceiling Mount Strobe, 12/24V, Standard Candela, Red
Ceiling Mount Strobe, 12/24V, High Candela, Red
Ceiling Mount Strobe, 12/24V, Standard Candela, Red, Outdoor
Ceiling Mount Strobe, 12/24V, High Candela, Red, Outdoor
Ceiling Mount Strobe, 12/24V, Standard Candela, White
Ceiling Mount Strobe, 12/24V, High Candela, White
Manufacturer
ADT
SYSTEM SENSOR
SYSTEM SENSOR
SYSTEM SENSOR
SYSTEM SENSOR
SYSTEM SENSOR
SYSTEM SENSOR
SYSTEM SENSOR
SYSTEM SENSOR
SYSTEM SENSOR
SYSTEM SENSOR
SYSTEM SENSOR
SYSTEM SENSOR
SYSTEM SENSOR
SYSTEM SENSOR
SYSTEM SENSOR
SYSTEM SENSOR
SYSTEM SENSOR
SYSTEM SENSOR
SYSTEM SENSOR
SYSTEM SENSOR
SYSTEM SENSOR
SYSTEM SENSOR
SYSTEM SENSOR
SYSTEM SENSOR
SYSTEM SENSOR
SYSTEM SENSOR
SYSTEM SENSOR
SYSTEM SENSOR
SYSTEM SENSOR
SYSTEM SENSOR
SYSTEM SENSOR
SYSTEM SENSOR
SYSTEM SENSOR
SYSTEM SENSOR
SYSTEM SENSOR
SYSTEM SENSOR
SYSTEM SENSOR
SYSTEM SENSOR
SYSTEM SENSOR
SYSTEM SENSOR
SYSTEM SENSOR
SYSTEM SENSOR
SYSTEM SENSOR
Model #
P4WH
PC2R
PC2RH
PC2RK
PC2RHK
PC2W
PC2WH
PC4R
PC4RH
PC4RK
PC4RHK
PC4W
PC4WH
SR
SRH
SRK
SRHK
SW
SWH
SCR
SCRH
SCRK
SCRHK
SCW
SCWH
875936B
CHR
CHW
CHSR
CHSW
HR
HW
HRK
P2R
P2RH
P2RK
P2RHK
P2W
P2WH
P4R
P4RH
P4RK
P4RHK
P4W
- 7 -
Alarm Indicating Device Type
Ceiling Mount Evacuation Speaker, Dual Voltage, 7” Round, White
Wall Mount Evacuation Speaker, Dual Voltage, 5” Square, Red
Wall Mount Evacuation Speaker, Dual Voltage, 5” Square, White
Wall Mount Speaker/Strobe, 12/24V, Selectable Candela, Red
Manufacturer
SYSTEM SENSOR
SYSTEM SENSOR
SYSTEM SENSOR
SYSTEM SENSOR
Model #
SP200W
SP201R
SP201W
SP2R1224M
Wiring Instructions for the Synchronization Module for UL864
Follow the instructions provided with the Synchronization Module. The Maximum Device Rating table lists the maximum number of devices that can be used on the combined PowerBoost3 outputs.
UL:
•••• All visual notification appliances within the same physical area must be synchronized.
•••• The bell outputs are listed as Special Application Notification Appliance Circuits.
Compatible Synchronization Module: System Sensor model MDLW Sync-Circuit Module
Maximum Device Rating Table
NOTE: To use this table, the device Candela Setting and Horn Setting MUST match what is listed in the Table.
Candela
System Sensor
System Sensor
System Sensor
System Sensor
System Sensor
System Sensor
System Sensor
System Sensor
System Sensor
System Sensor
System Sensor
System Sensor
System Sensor
Wheelock
Wheelock
Wheelock
Wheelock
Wheelock
Wheelock
Wheelock
Wheelock
Mfg
Gentex
Gentex
Gentex
Gentex
System Sensor
System Sensor
System Sensor
System Sensor
System Sensor
System Sensor
System Sensor
System Sensor
System Sensor
System Sensor
System Sensor
System Sensor
System Sensor
System Sensor
System Sensor
System Sensor
System Sensor
System Sensor
System Sensor
System Sensor
System Sensor
System Sensor
System Sensor
System Sensor
System Sensor
System Sensor
Alarm Indicating
Device Type
Horn Strobe 12V, 2w
Horn Strobe 12V, 2w
Horn Strobe 12V, 4w
Horn Strobe 12V, 4w
Horn, Strobe12/24V
Horn, Strobe12/24V
Horn, Strobe12/24V
Horn, Strobe12/24V
Horn, Strobe12/24V
Horn, Strobe12/24V
Horn, Strobe12/24V
Horn, Strobe12/24V
Horn, Strobe12/24V
Horn, Strobe12/24V
Horn, Strobe12/24V
Horn, Strobe12/24V
Horn, Strobe12/24V
Horn, Strobe12/24V
Horn, Strobe12/24V
Horn, Strobe12/24V
Horn, Strobe12/24V
Horn, Strobe12/24V
Horn, Strobe12/24V
Horn, Strobe12/24V
Horn, Strobe12/24V
Horn, Strobe12/24V
Horn, Strobe12/24V
Horn, Strobe12/24V
Horn, Strobe12/24V
Horn, Strobe12/24V
P4RK
P4RHK
P4W
P4WH
PC2R
PC2RH
PC2RK
PC2RHK
PC2W
PC2WH
PC4R
PC4RH
PC4RK
PC4RHK
PC4W
Model
GEC3-12,GES3-12,GEH-12
GEC3-12,GES3-12,GEH-12
GEC3-12,GES3-12,GEH-12
GEC3-12,GES3-12,GEH-12
HR
HW
HRK
P2R
P2RH
P2RK
P2RHK
P2W
P2WH
P4R
P4RH
Horn, Strobe12/24V
Strobe12/24V
Strobe12/24V
Strobe12/24V
Strobe12/24V
Strobe12/24V
Strobe12/24V
PC4WH
SR
SRH
SRK
SRHK
SW
SWH
Strobe12/24V
Strobe12/24V
Strobe12/24V
Strobe12/24V
SCR
SCRH
SCRK
SCRHK
Strobe12/24V
Strobe12/24V
SCW
SCWH
Horn Strobe 12V, 4W MT-121575W
Horn Strobe 12V, 2W AS-121575W
Strobe 12V RSS-121575W
Horn Strobe 12V, 2W
Horn 12V/24V
Horn 12V
NS-121575W
NH-12/24
AH-12
Horn 12V/24V
Bell 12V
MT-12/24,MT4-12/24
MB-G6-12,MB-G10-12
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15 na na na na
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
-
15
15
15
15
15
15
15
15
15
75
15
75
-
-
12
12
12
12
12
12
5
12
12
12
12
12
12
12
7
8
9
95
10
11
11
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
Max # of
Devices
7
3
7
3
45
45
45
12
12
12
12
12
12
12
12
Mech-Temporal
Mech-Temporal
Continuous Mech
Continuous Mech
-
-
-
Temporal - High
Temporal - High
Temporal - High
Temporal - High
Temporal - High
Temporal - High
Temporal - High
Temporal - High
Temporal - High
Temporal - High
Temporal - High
Temporal - High
Temporal - High
Temporal - High
Temporal - High
Temporal - High
Temporal - High
Temporal - High
Temporal - High
Temporal - High
Temporal - High
Temporal - High
Temporal - High
Temporal - High
Temporal - High
Temporal - High
Temporal - High
Temporal - High
Temporal - High
Temporal - High
Temporal - High
Temporal - High
Temporal - High
Temporal - High
Temporal - High
Temporal - High
Continuous/Hi
Continuous/Hi na
Hi
Hi
Hi
Continuous Horn na
- 8 -
Supervising the Notification Appliance Circuits
To wire the NAC using the supervision feature, perform the following:
Install a 2K EOL resistor (Model 2EOL, supplied) across the last notification appliance on each Notification Appliance
Circuit to be supervised.
Earth Ground Connections
In order for the lightning transient protective devices in this product to be effective, the designated earth ground terminal
(terminal 3) must be terminated in a good earth ground. Recommended wire gauge for the ground connection is #16
AWG, run no farther than 30 feet.
IMPORTANT: The panel requires the earth ground connection for its lightning transient protection devices and in order to detect Ground Fault conditions.
PowerBoost3-B
To connect the earth ground, perform the following steps:
1. Connect the earth ground post inside the 1451 enclosure to a good earth ground (use grounding methods specified in the National Electric Code).
2. Use a green nut (supplied) to secure the wire to the ground post. Ground wire should be the only wire under this nut.
3. Run a 16AWG wire from the ground post to the panel’s earth ground terminal (30). Use a second green nut (supplied) to secure this wire to the ground post.
This connection avoids ground loops that may occur when the 1451 and panel are connected to different earth ground systems.
PowerBoost3-F
To connect the transformer to the control, perform the following steps:
1. Remove the front cover of the enclosure.
2. Mount the enclosure to the wall near the control panel. The enclosure has four mounting holes on its back surface for this purpose.
3. Run 120VAC wiring to the enclosure in conduit. A dedicated circuit must be used.
4. Use wire nuts to splice the 120VAC wires to the transformer’s white and black primary leads.
5. Connect the earth ground post on the back of the enclosure to a good earth ground.
6. Run 16AWG wire in conduit from the enclosure to the control panel.
7. Use wire nuts to splice the transformer blue 18VAC secondary leads to the 16AWG wire. Connect the 16AWG wire at the control panel to terminals 1 and 2.
8. Replace the front cover of the enclosure and fasten it with the screws supplied.
NOTES:
• Use wires having insulation rated for at least 90°C operation and suitable for non-power limited applications.
• Use care to keep 18VAC wiring separated from all other wiring inside the control panel’s enclosure. This must be done by running, non-power-limited 18VAC wiring into the control panel’s enclosure via one of the knockouts on the left-hand side, and then tie-wrapping these wires to the tie-wrap loops located near the knockout.
- 9 -
Determining the Control’s Power Supply Load
In the event of an AC power loss the PowerBoost3 must be supported by backup, rechargeable batteries. When the system is used, a 12AH to 34.4AH battery must be connected the control panel.
The battery’s capacity must be sized to provide the required hours of standby time followed by the required minutes of alarm time.
Use the worksheets that follow to calculate the total current for auxiliary power 1 or bell power 1 and auxiliary power 2 or bell power 2 total current load. In each worksheet, multiply each device’s standby and/or alarm current by the number of units used.
Fill out the Battery Capacity Calculation Worksheet, following the other worksheets below, to determine the required capacity for the backup battery. Select a battery from the Battery Selection Table (found later in this section) that have a capacity greater than or equal to the calculated capacity.
1. In Worksheet 1A, enter devices used on Auxiliary Power 1. Calculate standby and alarm currents, then add to get
Auxiliary Power 1 current subtotal.
In Worksheet 1B, enter devices connected to the Bell 1 Output. Calculate alarm currents, then add to get the Bell 1
Output current subtotal.
Worksheet 1A: Auxiliary Power 1 Current Load
Worksheet 1B: Bell 1 Output Current Load
Device
Model #
Device Current X
# of Units
Standby Alarm
Device
Model #
Device Current X
# of Units
Total Current
Alarm
Bell 1 Output Subtotal
(2A max.)
Auxiliary Power 1 Subtotal see table 2A max.
- 10 -
2. In Worksheet 2A, enter devices used on Auxiliary Power 2. Calculate standby and alarm currents, then add to get
Auxiliary Power 2 current subtotal.
In Worksheet 2B, enter devices connected to the Bell 2 Output. Calculate alarm currents, then add to get the Bell 2
Output current subtotal.
Worksheet 2A: Auxiliary Power 2 Current Load
Worksheet 2B: Bell 2 Output Current Load
Device
Model #
Device Current X
# of Units
Standby Alarm
Device
Model #
Device Current X
# of Units
Total Current
Alarm
Bell 2 Output Subtotal
(2A max.)
Auxiliary Power 2 Subtotal
2A max.
3. In Worksheet 3, enter the total calculated subtotals of all listed outputs from Worksheets 1 and 2, then add to get the combined current.
Worksheet 3: Total Current Load
Auxiliary Power 1A Subtotal
Total Current
Standby Alarm
Auxiliary Power 2A Subtotal
Bell 1B Output Subtotal n/a
Bell 2B Output Subtotal n/a
PowerBoost3 Current 100mA 100mA
Total Current Load
(see UL Listing Requirements Table for max. standby; 2.3A max. alarm)
Determining the Size of the Standby Battery
Select the battery size based upon the UL Listing Requirements Table and calculated standby load.
IMPORTANT: DO NOT use Gates batteries (sealed lead-acid type). These batteries require a different charging voltage than is supplied by the PowerBoost3
Module
.
UL Listing Requirements Table
Duration Requirement Minimum Battery AH
Listing
Standby Alarm Recharge
UL365/609 Mercantile
UL1023 House Burglary
UL365 Police Station Bank
UL365 Police Station Mercantile
4 hr
4 hr
4 hr
8 hr
15 min 24 hr
4 min 48 hr
15 min 72 hr
15 min 24 hr
UL985 Household Fire
UL864/1481 CS Signaling
24 hr
24 hr
4 min
5 min
48 hr
48 hr
UL864/1481 Remote Station Signaling 60 hr
UL365/609 Bank Vault 72 hr
5 min
15 min
48 hr
72 hr
ULC 24 hr 30 min 48 hr
(2x7AH) (2x17.2AH)
Standby Current Rating (alarm = 3A)
1.9
2
1.9
1
0.35
0.35
0
0
0.3
2.25
2.3
2.25
1.3
0.42
0.4
0.1
0
0.37
2.3
2.3
2.3
1.6
0.54
0.5.
0.15
0.11
0.5
2.3
2.3
2.3
2.1
1.2
1.2
0.4
0.33
1
- 11 -
Use battery capacity and the Battery Selection Table to determine the appropriate battery model number. A dual battery harness is supplied that allows two batteries to be wired in parallel for increased capacity.
Battery Selection Table
12AH
14AH
17.2AH
Yuasa NP12-12
Yuasa NP7-12
Yuasa NPG18-12
Fits in large mercantile cabinet only.
Connect two in parallel.
Fits in large mercantile cabinet only.
Connect the battery, referring to the diagram below.
NOTE: The standby battery is automatically tested for 10 minutes every 4 hours
.
The
PowerBoost3
also runs a 5-second battery test every 60 seconds to check if the battery is connected.
NOTE: WHEN CONNECTING BATTERIES IN PARALLEL:
- USE BATTERIES FROM THE SAME MANUFACTURER AND
WITH THE SAME VOLTAGE AND CAPACITY RATING.
- USE BATTERIES WITH APPROXIMATELY SAME AGE AND
STATE OF CHARGE.
- USE CABLES PROVIDED AND OBSERVE POLARITY!
- IT IS RECOMMENDED THAT ALL BATTERIES BE REPLACED
AT SAME TIME, EVEN IF ONLY ONE BATTERY HAS BECOME
WEAK.
- AS LONG AS ONE GOOD BATTERY REMAINS CONNECTED,
THE ONCE PER 60 SECOND BATTERY TEST WILL NOT
DETECT THE DISCONNECTION OF REMAINING BATTERIES.
PowerBoost3
RED
BATTERY
TABS
BLK
DUAL
BATTERY
HARNESS
BLK
RED
RED
BLK
OBSERVE
POLARITY!
+
12V
BATTERY
+
12V
BATTERY
(IF REQUIRED)
PB3-007-V0
Specifications
Board Dimensions 2.7” W x 8” L x 1.5” D
Input Voltage
Special Application
Notification Appliance
Output Voltages
18VAC, 72VA
12VDC 3A alarm pool, 2.2A standby,
2A max on any one output
Battery Charging Voltage 13.65VDC, 3A - 600mA
Current Drain 100mA @ 12V
ECP Input Voltage 8-14VDC
Earth Ground Impedance 1000 ohms
Max. Bell Impedance
Wire Run Length
0.85 ohms for 8VDC min. operation
0.35 ohms for 9VDC min. operation
2000ft max. unshielded; 1000ft shielded;
#14-32 gauge (see control’s instructions for wire length limitations)
32°F (0°C) to 120°F (49°C)
Temperature Range
Agency Listings
• UL 864 NFPA 72 Commercial Fire
• UL 1481 Power Supplies for Fire Alarm
System (stand-alone mode)
• UL bank listing (80-hr standby)
• California State Fire Marshal
Residential and Commercial
• New York City MEA
• Factory Mutual
REFER TO THE INSTALLATION AND SETUP GUIDE FOR THE CONTROL WITH WHICH THIS DEVICE IS
USED FOR WARRANTY INFORMATION AND LIMITATIONS OF THE ENTIRE SYSTEM.
ÊK14963RŠ
K14963 8/09 Rev. A
2 Corporate Center Drive, Suite 100
P.O. Box 9040, Melville, NY 11747
Copyright © 2009 Honeywell International Inc.
www.honeywell.com/security
advertisement
Key Features
- Two supervised outputs
- UL requirements
- Auxiliary power source
- ECP mode
- Stand-alone mode
- Trigger outputs
- AC loss detection
- Battery monitoring
- Earth ground fault detection
- Module shutdown