PowerBoost3 B | User manual | Honeywell PowerBoost3 F, B PowerBoost Installation and Setup Guide

Add to My manuals
12 Pages

PowerBoost3 F and PowerBoost3 B are two supervised outputs that can be used for bells/sirens to meet certain UL requirements, or can serve as an auxiliary power source for remote devices such as door strikes, latches, keypads, etc. The PowerBoost3 F mounts inside its own cabinet and includes a self-contained 18VAC, 72VA transformer with enclosure (SA5110TFR). The PowerBoost3 B mounts inside a large attack-resistant cabinet with room for two batteries and includes a self-contained 18VAC, 72VA transformer with enclosure (SA1451).

advertisement

Honeywell PowerBoost3 F and B Installation and Setup Guide | Manualzz

INSTALLATION AND SETUP GUIDE

About the PowerBoost3

The PowerBoost3 (herein referred to as the Module) provides two supervised outputs that can be used for bells/sirens to meet certain UL requirements, or can serve as an auxiliary power source for remote devices such as door strikes, latches, keypads, etc. The module mounts inside its own cabinet.

PowerBoost3-F

PowerBoost3-B

For bell output usage (ECP mode), the control activates the outputs and receives output status via the control’s ECP terminals. Can also report various trouble conditions to the control via on-board triggers.

ON

For auxiliary power usage (stand-alone mode), the outputs provide steady power to an attached device, and the module reports various trouble conditions to the control via on-board triggers.

PowerBoost3 Configurations

VSM-002-V0

Model Configuration

PowerBoost3-F

• Intended for Fire applications where supervised bell outputs (ECP mode) or additional auxiliary power outputs (stand-alone mode) are needed.

PowerBoost3-B

• Module mounts on a backplate inside a red cabinet.

• Includes self-contained 18VAC, 72VA transformer with enclosure (SA5110TFR) that mounts inside the cabinet.

• Intended for Commercial Burglary applications where supervised bell outputs and

72-hour battery backup is needed.

• Module mounts inside a large attack-resistant cabinet with room for two batteries.

• Includes self-contained 18VAC, 72VA transformer with enclosure (SA1451) that mounts outside the cabinet.

Module Features

ECP Mode

When used in ECP mode, the Module provides two supervised bell outputs (12VDC, 3A pool, 2A max on any one output).

The Module reports supervised conditions to the control panel via trigger output and ECP connections. These trouble conditions are reported as alarms on assigned zones (similar to zones on a 4204CF Relay Module). The Module and zones need to be programmed into the control. See Programming for ECP section for detailed information. The Module must be set for an appropriate device address via its DIP switches.

The Module supervises the following conditions when used in ECP mode:

Via ECP Connection

• Output 1 Supervision (see note 1)

• Output 2 Supervision (see note 1)

Via Trigger Output Connection

• Trouble (see note 2)

• AC Loss

• Low Battery (see note 3)

NOTES

1. Output supervision trouble activates upon EOLR open or short

2. Trouble trigger activates upon output overload, output supervision, and earth ground fault (VISTA-FBP series only)

3. Low battery trigger activates upon low battery (voltage below 11.5VDC), battery missing, or battery charger supervision conditions

Stand-Alone Mode

When used in Stand-Alone mode, the Module provides steady power of 12VDC, 2.2A total (3A alarm, 2A max on any one output) to the two outputs.

To use stand-alone mode, connect the outputs to the devices to be powered and set the module’s DIP switch to address 0 (all switches OFF).

Trigger Outputs

For control’s that do not fully support ECP communication, the Module provides three trigger outputs that can be connected to the control’s zone inputs to report the following conditions:

Trigger Action

AC Loss

Low Battery

Trouble on steady = loss of AC on steady = low battery or missing battery on steady for any of the following conditions:

- output 1 or 2 overload - ground fault

- output 1 or 2 supervision - battery charger failure

AC Loss Detection and Battery Monitoring

The Module is powered by an 18VAC 72VA wire-in transformer connected to a 120VAC source. Loss of AC power results in a fault condition reported to the control via ECP or the AC Loss trigger. The size of the battery the Module can charge is dependent upon the maximum output current of the system and the system load. This output is protected against shorts and against battery lead reversal.

The Module supervises the following battery conditions:

• Battery charger failure (reports to control via ECP or the Trouble trigger)

• Missing battery indication within 60 seconds (90 seconds for UL) of the disconnection of the battery leads (reports to control via ECP or Battery trigger).

• Low battery when the battery voltage falls below 11.5V (reports to control via ECP or Battery trigger).

Earth Ground Fault Detection

The Module supports built-in Earth Ground Fault detection that complies with UL864 Fire. A ground fault occurs upon a short through TB1-3 from any other terminal. Ground faults report to the control via ECP or the Trouble trigger

Module Shutdown

If the Module loses AC power and the battery voltage drops below 9.8VDC, the system will disconnect the battery. This feature helps prevent total discharge of the battery cells that would otherwise result in battery replacement. When AC power is restored, the battery automatically reconnects back into the system.

LED Indications

The Module has three LEDs that indicate the following conditions:

AC

ECP Bus

Low Battery

Trouble green green yellow yellow on = AC power available single flashing = communicating with control

3 flashes = loss of communication with control on = missing or low battery condition on = one or more trouble conditions exist (bell overload, output supervision, ground fault, charger fail)

- 2 -

PowerBoost3-F Mounting Procedure

Mounting the PC Board and Backplate

The PowerBoost3-F mounts in its own cabinet and includes a backplate, hardware, and Transformer.

Refer to the diagram below to mount the PC Board, backplate and transformer in the cabinet.

SECURE MOUNTING PLATE

TO CABINET WITH 4 SCREWS

TO MOUNT PC BOARD

SNAP THE UPPER CORNERS OF THE

PC BOARD ONTO PLASTIC STANDOFFS,

THEN USE SCREWS AND SPACERS TO

SECURE BOTTOM EDGE. DO NOT

OVERTIGHTEN.

IMPORTANT!

REMOVE APPROPRIATE WIRE

KNOCKOUTS BEFORE INSTALLING

MOUNTING PLATE

SNAP PLASTIC STANDOFFS

INTO MOUNTING PLATE

(SEE DETAIL A)

DIP

5

4

3

2

1

DETAIL A

PLASTIC STANDOFF (2)

(C)

INSTALL 3 SCREWS AND SPACERS

INTO MOUNTING PLATE

(SEE DETAIL B)

SA5110TFR ENCLOSED TRANSFORMER

SECURE TO CABINET WITH

4 SCREWS (C).

REPLACE COVER AFTER WIRING.

DETAIL B

SCREW AND SPACER (3)

PB3-005-V0

(C)

Mounting and Wiring the SA5110TFR Transformer

The PowerBoost3-F uses the SA5110TFR Transformer, which is an enclosed AC power transformer with manually resettable circuit breaker protection. It mounts in the lower left-hand corner of the cabinet.

UL:

• A dedicated 120VAC circuit must be used for fire applications.

• Wires must be rated for 90 degrees C or higher operation.

IMPORTANT: Make sure that the dedicated AC circuit is not powered at this time. Apply AC power only after all other wiring, except the backup battery wiring, has been completed.

Connect the transformer to the control as follows:

1. Remove the cover from the transformer's enclosure.

2. Remove the lower knockout on the left-hand side of the cabinet. Run 120VAC power wires into the transformer enclosure via this knockout.

3. Use wire nuts (not supplied) to splice the 120VAC wires to the transformer's black and white flying leads. Push the mated wires back into the transformer enclosure.

4. Connect the transformer's 18VAC blue flying leads which emerge from the top of the enclosure to the PowerBoost3 AC terminals.

- 3 -

PowerBoost3-B Mounting Procedure

Mounting the PC Board

The PowerBoost3-B mounts in its own cabinet and includes the module PC board and SA1451 transformer.

CABINET

PowerBoost3

DIP

5

4

3

1

CIRCUIT

BOARD

DETAIL A

SIDE VIEW OF

BOARD-SUPPORTING

SLOTS

DETAIL B

SIDE VIEW OF

MOUNTING CLIP

TRANSFORMER SA1451

MOUNTS EXTERNALLY TO CABINET

(REPLACE COVER AFTER WIRING)

PB3-006-V1

Mounting and Wiring the SA1451 Transformer

The PowerBoost3-B uses the SA1451 Transformer, which is an enclosed AC power transformer with manually resettable circuit breaker protection. The transformer provides 18VAC/72VA secondary winding for powering the control and mounts outside the cabinet.

To connect the SA1451 transformer to the control, perform the following steps:

1. Remove the front cover of the enclosure.

2. Mount the enclosure to the wall near the PowerBoost3 cabinet. The enclosure has four mounting holes on its back surface for this purpose.

3. Run 120VAC wiring to the enclosure in conduit. A dedicated circuit must be used.

4. Use wire nuts to splice the 120VAC wires to the transformer’s white and black primary leads.

5. Connect the earth ground post on the back of the enclosure to a good earth ground.

6. Run 16AWG wire in conduit from the enclosure to the control panel.

7. Use wire nuts to splice the transformer blue 18VAC secondary leads to the 16AWG wire. Connect the 16AWG wire at the control panel to terminals 1 and 2.

8. Replace the front cover of the enclosure and fasten it with the screws supplied.

NOTES:

• Use wires having insulation rated for at least 90°C operation and suitable for non-power limited applications

• Use care to keep 18VAC wiring separated from all other wiring inside the control panel’s enclosure. This must be done by running non-power-limited 18VAC wiring into the control panel’s enclosure via one of the knockouts on the left-hand side, and then tie-wrapping these wires to the tie-wrap loops located near the knockout.

- 4 -

Wiring Connections for the PowerBoost3 Module

Wiring for both the Powerboost3-B and PowerBoost3-F is the same.

Connection Summary

Connection Procedure

AC Connect the 18 VAC 72VA wire-in transformer to the Module’s AC Input terminals.

ECP Connects the ground, data in, and data out terminals to the control’s ECP terminals.

(control’s ECP red +12VDC connection not used)

OUTPUT For ECP operation: Connect to bell/siren respective +/– terminals. Connect 2k EOLR (EOL20) at terminals DC+ and OUT– for Class A supervision, or across the last sounder for Class B supervision.

Each of the Module’s outputs is rated 13.65 VDC, 2.0A (total combined alarm output current is 3A max).

For Stand-Alone operation: Connect the device to be powered +Input to DC+, –Input to DC–.

Connect battery terminals to battery. The charge output voltage is 13.65VDC ±1%. BATTERY

(12AH min)

TRIGGERS Connect each desired trigger to a zone + input on the control. Refer to the Zone Event Worksheet in the Programming For ECP Mode section for information on control panel zones and trigger connections.

NOTE: If used, Tamper trigger must be connected to ECP Ground (–) as shown in the Trigger Detail in the wiring diagram.

Refer to the diagram below when making connections.

ACTIVE

PowerBoost3

AC

LED

LED

TROUBLE LED

DIP

LOW

BATT

LED

TRIGGER OUTPUTS

5

4

3

2

1

SET APPROPRIATE

MODULE ADDRESS

TRIGGERS

TROUBLE: ON = TROUBLE CONDITION

AC LOSS: ON = AC LOSS

BATTERY: ON = LOW/MISSING BATTERY

TAMPER: ECP MODE ONLY.

SENDS TROUBLE IF OPENED

EARTH GROUND

DETECT JUMPER

ON = ENABLE

AC INPUT

ECP

TERMINALS

ERTH

GND GND TX RX

OUTPUT 1

OUT DC OUT DC

BATTERY

N/U

OUTPUT 2

OUT DC OUT DC

N/U

NON POWER LIMITED.

MAINTAIN MINIMUM

1/4" SPACING TO OTHER

WIRING.

POLARIZED

SUPERVISED

BELL

POLARIZED

SUPERVISED

BELL

TAMPER

TO CONTROL'S

ZONE TERMINALS

SEE TYPICAL TRIGGER

CONNECTIONS BELOW

CONNECT TO

A DEDICATED

CIRCUIT

120VAC, 60Hz,

600mA MAX

TO ECP GND

TRANSFORMERS

SA5110TFR (PowerBoost3-F)

SA1451 (PowerBoost3-B)

18VAC, 72VA

ENCLOSED TRANSFORMER

REPLACE COVER AFTER WIRING

2A CIRCUIT

BREAKER

BLK BLUE

WHT BLUE

SEE

EARTH

GROUND

NOTE

BELOW

NON POWER LIMITED.

MAINTAIN MINIMUM

1/4" SPACING

TO OTHER WIRING.

CONNECT TO

PROPER EARTH

GROUND.

GRN

NOTE: USE WIRES HAVING

INSULATION RATED FOR

90 C OR HIGHER

GRN

(13.65 VDC, 2A) (13.65 VDC, 2A)

2K EOLR

(EOL20)

2K EOLR

(EOL20)

TYPICAL CLASS B CONNECTIONS

BATTERY

CHARGING VOLTAGE: 13.65 VDC

MINIMUM BATTERY SIZE = 12AH

OUTPUT NOTE

FOR APPROVED SPECIAL

APPLICATION NOTIFICATION

APPLIANCE CIRCUITS, THE

MAXIMUM LINE IMPEDANCE

ALLOWED WHEN THE SYSTEM IS

FULLY LOADED TO 3A FOR DEVICES

THAT CAN OPERATE AT A MINIMUM

OF 8VDC IS 0.85 OHMS. FOR

DEVICES THAT CAN OPERATE AT A

MINIMUM OF 9VDC THE MAXIMUM

LINE IMPEDANCE IS 0.35 OHMS.

TYPICAL

STAND-ALONE

POWER

SUPPLY MODE

OUT DC OUT DC

TYPICAL TRIGGER CONNECTIONS

AC INPUT

ECP

GND

EARTH GROUND NOTE

SEE INSTRUCTIONS FOR

PROPER EARTH GROUND

CONNECTIONS

THE IMPEDANCE AT WHICH A

GROUND FAULT IS

ANNUNCIATED IS 1,000 OHMS

TYPICAL

CLASS A

CONNECTIONS

2K EOLR

(EOL20)

OUT DC OUT DC

DEVICE

TAMPER

SWITCH

ZONE ZONE

CONTROL PANEL

AUX GND (KEYPAD )

CONTROL PANEL

CONTROL PANEL

AUX

GND

DATA

IN

DATA

OUT

FOR COMMERCIAL FIRE LISTING, BOTH SPECIAL

APPLICATION OUTPUTS 1 AND 2 MUST BE USED

IN THE SAME NOTIFICATION ZONE.

PB3-003-V1

- 5 -

Programming For ECP Mode

For ECP compatible controls, the PowerBoost3 appears to the control as a 4204CF Relay module. The various output trouble conditions report to the control as alarms on specific zone numbers based on zones associated with the 4204CF

Relay module (i.e. zones 601-696). Each zone must be programmed in the control accordingly. When programming the control, set each of the reporting zones for 24hr trouble zone type.

To use ECP mode, set the DIP switch to an appropriate address for the control being used (refer to the DIP Switch Table for the switch settings for each address).

UL: If more than one PowerBoost3 module is to be used in a fire application, an ECP-ISO module must be used for each additional PowerBoost3 module.

The following table lists the trouble events that can be reported.

Zone Event Worksheet

Trigger

TRBL

(trouble)

LED

Trouble

Events Reported

Output Overload

Output Supervision

Earth Ground Fault

Connection/Programming at the Control

Overload: Trouble trigger to a control panel zone

Supervision: VISTA- “BP and FBP” series

Earth Ground Fault: VISTA- “FBP” series only

Zone Number

Overload: Any (ZT 05 or

19 recommended)

Supervision: 601-632

(based on output no.)

Earth Ground Fault: 972

AC

LOSS

AC AC Loss

LO BATT Low Batt Battery Charger

Supervision

Missing Battery

TAMPER N/A

AC Loss trigger connected to a control panel zone Any (ZT 05 or 19

Low Battery trigger connected to a control panel zone

Charger Overload/Low

Battery

Cabinet Tamper Tamper trigger connected through a N.C switch to module’s ECP Ground (term 4) recommended)

Any (ZT 05 or 19 recommended)

801-815 (based on module’s address)

DIP SWITCH SETTINGS

Use the DIP switches to set the module’s ECP address (or, if applicable, set to Stand-Alone mode) and set the desired power-up state.

Module Address

(ECP Mode = addr. 1-15)

1

ECP addr.

DIP Switch Position

2

ECP addr.

3

ECP addr.

(“–“ = ON)

4

ECP addr.

5

Power-Up State

Stand Alone Mode

OFF OFF OFF OFF

††

1 – OFF OFF OFF

††

3

5

7

– OFF

††

– OFF

††

OFF ††

– OFF – OFF

††

– OFF

††

– – – OFF

††

ON

DIP

OFF

5

4

3

2

1

9

††

††

11 – –

OFF

OFF

††

††

††

TRIGGER OUTPUTS

13 – OFF –

††

††

15 – – – –

††

† Default setting is for Stand Alone Mode (sw 1-4 = OFF) with Power Up State set to ON (sw 5 = ON).

†† SW 5 is used to determine if the module powers up with the outputs ON or OFF.

POWER UP STATE

ECP ADDRESS

- 6 -

Notes on Installing Sounders

The PowerBoost3 provides two Notification Appliance Circuits (Class A or B, Style Y supervision) for operating fire or burglary alarm notification appliances. Each circuit is rated as follows: 10VDC – 14VDC, 2A max. power limited.

NOTE: The total alarm current drawn from outputs 1 and 2 cannot exceed 2.9A for battery-independent operation.

UL:

• Burglary Notification Appliance Circuits must be programmed for a timeout of 16 minutes or longer.

• Commercial fire alarm systems require Notification Appliance Circuits to be supervised.

Notification Appliance Circuit Supervision

The PowerBoost3 monitors the Notification Appliance Circuits wiring for open and short circuit faults while the output is inactive. The system provides a trouble indication when an open occurs. When a short occurs between the Bell (+) and

Bell (–) terminal wiring, or between the Bell (+) terminal wiring and earth ground the system provides a trouble indication.

UL:

• Use only UL Listed sounding devices for UL installations.

• In Commercial Fire installations, the PoweBoost3 cannot be used to drive sounders in the same physical area as sounders connected to other alarm outputs.

Compatible Alarm Indicating Devices

Alarm Indicating Device Type

RX7 UL Indoor Sounder, 12V

Chime, 12/24V, Selectable Tone & Volume, Red

Chime, 12/24V, Selectable Tone & Volume, White

Chime/Strobe, 12/24V, Selectable Candela, Tone & Volume, Red

Chime/Strobe, 12/24V, Selectable Candela, Tone & Volume, White

Horn, 12/24V, Red

Horn, 12/24V, White

Horn, 12/24V, Outdoor, Red

2-Wire Wall Mount Horn/Strobe, 12/24V, Standard Candela, Red

2-Wire Wall Mount Horn/Strobe, 12/24V, High Candela, Red

2-Wire Wall Mount Horn/Strobe, 12/24V, Standard Candela, Red, Outdoor

2-Wire Wall Mount Horn/Strobe, 12/24V, High Candela, Red, Outdoor

2-Wire Wall Mount Horn/Strobe, 12/24V, Standard Candela, White

2-Wire Wall Mount Horn/Strobe, 12/24V, High Candela, White

4-Wire Wall Mount Horn/Strobe, 12/24V, Standard Candela, Red

4-Wire Wall Mount Horn/Strobe, 12/24V, High Candela, Red

4-Wire Wall Mount Horn/Strobe, 12/24V, Standard Candela, Red, Outdoor

4-Wire Wall Mount Horn/Strobe, 12/24V, High Candela, Red, Outdoor

4-Wire Wall Mount Horn/Strobe, 12/24V, Standard Candela, White

4-Wire Wall Mount Horn/Strobe, 12/24V, High Candela, White

2-Wire Ceiling Mount Horn/Strobe, 12/24V, Standard Candela, Red

2-Wire Ceiling Mount Horn/Strobe, 12/24V, High Candela, Red

2-Wire Ceiling Mount Horn/Strobe, 12/24V, Standard Candela, Red, Outdoor

2-Wire Ceiling Mount Horn/Strobe, 12/24V, High Candela, Red, Outdoor

2-Wire Ceiling Mount Horn/Strobe, 12/24V, Standard Candela, White

2-Wire Ceiling Mount Horn/Strobe, 12/24V, High Candela, Red

4-Wire Ceiling Mount Horn/Strobe, 12/24V, Standard Candela, Red

4-Wire Ceiling Mount Horn/Strobe, 12/24V, High Candela, Red

4-Wire Ceiling Mount Horn/Strobe, 12/24V, Standard Candela, Red, Outdoor

4-Wire Ceiling Mount Horn/Strobe, 12/24V, High Candela, Red, Outdoor

4-Wire Ceiling Mount Horn/Strobe, 12/24V, Standard Candela, White

4-Wire Ceiling Mount Horn/Strobe, 12/24V, High Candela, White

2-Wire Wall Mount Strobe, 12/24V, Standard Candela, Red

2-Wire Wall Mount Strobe, 12/24V, High Candela, Red

Wall Mount Strobe, 12/24V, Standard Candela, Red, Outdoor

Wall Mount Strobe, 12/24V, High Candela, Red, Outdoor

Wall Mount Strobe, 12/24V, Standard Candela, White

Wall Mount Strobe, 12/24V, High Candela, White

Ceiling Mount Strobe, 12/24V, Standard Candela, Red

Ceiling Mount Strobe, 12/24V, High Candela, Red

Ceiling Mount Strobe, 12/24V, Standard Candela, Red, Outdoor

Ceiling Mount Strobe, 12/24V, High Candela, Red, Outdoor

Ceiling Mount Strobe, 12/24V, Standard Candela, White

Ceiling Mount Strobe, 12/24V, High Candela, White

Manufacturer

ADT

SYSTEM SENSOR

SYSTEM SENSOR

SYSTEM SENSOR

SYSTEM SENSOR

SYSTEM SENSOR

SYSTEM SENSOR

SYSTEM SENSOR

SYSTEM SENSOR

SYSTEM SENSOR

SYSTEM SENSOR

SYSTEM SENSOR

SYSTEM SENSOR

SYSTEM SENSOR

SYSTEM SENSOR

SYSTEM SENSOR

SYSTEM SENSOR

SYSTEM SENSOR

SYSTEM SENSOR

SYSTEM SENSOR

SYSTEM SENSOR

SYSTEM SENSOR

SYSTEM SENSOR

SYSTEM SENSOR

SYSTEM SENSOR

SYSTEM SENSOR

SYSTEM SENSOR

SYSTEM SENSOR

SYSTEM SENSOR

SYSTEM SENSOR

SYSTEM SENSOR

SYSTEM SENSOR

SYSTEM SENSOR

SYSTEM SENSOR

SYSTEM SENSOR

SYSTEM SENSOR

SYSTEM SENSOR

SYSTEM SENSOR

SYSTEM SENSOR

SYSTEM SENSOR

SYSTEM SENSOR

SYSTEM SENSOR

SYSTEM SENSOR

SYSTEM SENSOR

Model #

P4WH

PC2R

PC2RH

PC2RK

PC2RHK

PC2W

PC2WH

PC4R

PC4RH

PC4RK

PC4RHK

PC4W

PC4WH

SR

SRH

SRK

SRHK

SW

SWH

SCR

SCRH

SCRK

SCRHK

SCW

SCWH

875936B

CHR

CHW

CHSR

CHSW

HR

HW

HRK

P2R

P2RH

P2RK

P2RHK

P2W

P2WH

P4R

P4RH

P4RK

P4RHK

P4W

- 7 -

Alarm Indicating Device Type

Ceiling Mount Evacuation Speaker, Dual Voltage, 7” Round, White

Wall Mount Evacuation Speaker, Dual Voltage, 5” Square, Red

Wall Mount Evacuation Speaker, Dual Voltage, 5” Square, White

Wall Mount Speaker/Strobe, 12/24V, Selectable Candela, Red

Manufacturer

SYSTEM SENSOR

SYSTEM SENSOR

SYSTEM SENSOR

SYSTEM SENSOR

Model #

SP200W

SP201R

SP201W

SP2R1224M

Wiring Instructions for the Synchronization Module for UL864

Follow the instructions provided with the Synchronization Module. The Maximum Device Rating table lists the maximum number of devices that can be used on the combined PowerBoost3 outputs.

UL:

•••• All visual notification appliances within the same physical area must be synchronized.

•••• The bell outputs are listed as Special Application Notification Appliance Circuits.

Compatible Synchronization Module: System Sensor model MDLW Sync-Circuit Module

Maximum Device Rating Table

NOTE: To use this table, the device Candela Setting and Horn Setting MUST match what is listed in the Table.

Candela

System Sensor

System Sensor

System Sensor

System Sensor

System Sensor

System Sensor

System Sensor

System Sensor

System Sensor

System Sensor

System Sensor

System Sensor

System Sensor

Wheelock

Wheelock

Wheelock

Wheelock

Wheelock

Wheelock

Wheelock

Wheelock

Mfg

Gentex

Gentex

Gentex

Gentex

System Sensor

System Sensor

System Sensor

System Sensor

System Sensor

System Sensor

System Sensor

System Sensor

System Sensor

System Sensor

System Sensor

System Sensor

System Sensor

System Sensor

System Sensor

System Sensor

System Sensor

System Sensor

System Sensor

System Sensor

System Sensor

System Sensor

System Sensor

System Sensor

System Sensor

System Sensor

Alarm Indicating

Device Type

Horn Strobe 12V, 2w

Horn Strobe 12V, 2w

Horn Strobe 12V, 4w

Horn Strobe 12V, 4w

Horn, Strobe12/24V

Horn, Strobe12/24V

Horn, Strobe12/24V

Horn, Strobe12/24V

Horn, Strobe12/24V

Horn, Strobe12/24V

Horn, Strobe12/24V

Horn, Strobe12/24V

Horn, Strobe12/24V

Horn, Strobe12/24V

Horn, Strobe12/24V

Horn, Strobe12/24V

Horn, Strobe12/24V

Horn, Strobe12/24V

Horn, Strobe12/24V

Horn, Strobe12/24V

Horn, Strobe12/24V

Horn, Strobe12/24V

Horn, Strobe12/24V

Horn, Strobe12/24V

Horn, Strobe12/24V

Horn, Strobe12/24V

Horn, Strobe12/24V

Horn, Strobe12/24V

Horn, Strobe12/24V

Horn, Strobe12/24V

P4RK

P4RHK

P4W

P4WH

PC2R

PC2RH

PC2RK

PC2RHK

PC2W

PC2WH

PC4R

PC4RH

PC4RK

PC4RHK

PC4W

Model

GEC3-12,GES3-12,GEH-12

GEC3-12,GES3-12,GEH-12

GEC3-12,GES3-12,GEH-12

GEC3-12,GES3-12,GEH-12

HR

HW

HRK

P2R

P2RH

P2RK

P2RHK

P2W

P2WH

P4R

P4RH

Horn, Strobe12/24V

Strobe12/24V

Strobe12/24V

Strobe12/24V

Strobe12/24V

Strobe12/24V

Strobe12/24V

PC4WH

SR

SRH

SRK

SRHK

SW

SWH

Strobe12/24V

Strobe12/24V

Strobe12/24V

Strobe12/24V

SCR

SCRH

SCRK

SCRHK

Strobe12/24V

Strobe12/24V

SCW

SCWH

Horn Strobe 12V, 4W MT-121575W

Horn Strobe 12V, 2W AS-121575W

Strobe 12V RSS-121575W

Horn Strobe 12V, 2W

Horn 12V/24V

Horn 12V

NS-121575W

NH-12/24

AH-12

Horn 12V/24V

Bell 12V

MT-12/24,MT4-12/24

MB-G6-12,MB-G10-12

15

15

15

15

15

15

15

15

15

15

15

15

15

15

15

15

15 na na na na

15

15

15

15

15

15

15

15

15

15

15

15

15

15

15

-

15

15

15

15

15

15

15

15

15

75

15

75

-

-

12

12

12

12

12

12

5

12

12

12

12

12

12

12

7

8

9

95

10

11

11

12

12

12

12

12

12

12

12

12

12

12

12

12

12

12

Max # of

Devices

7

3

7

3

45

45

45

12

12

12

12

12

12

12

12

Mech-Temporal

Mech-Temporal

Continuous Mech

Continuous Mech

-

-

-

Temporal - High

Temporal - High

Temporal - High

Temporal - High

Temporal - High

Temporal - High

Temporal - High

Temporal - High

Temporal - High

Temporal - High

Temporal - High

Temporal - High

Temporal - High

Temporal - High

Temporal - High

Temporal - High

Temporal - High

Temporal - High

Temporal - High

Temporal - High

Temporal - High

Temporal - High

Temporal - High

Temporal - High

Temporal - High

Temporal - High

Temporal - High

Temporal - High

Temporal - High

Temporal - High

Temporal - High

Temporal - High

Temporal - High

Temporal - High

Temporal - High

Temporal - High

Continuous/Hi

Continuous/Hi na

Hi

Hi

Hi

Continuous Horn na

- 8 -

Supervising the Notification Appliance Circuits

To wire the NAC using the supervision feature, perform the following:

Install a 2K EOL resistor (Model 2EOL, supplied) across the last notification appliance on each Notification Appliance

Circuit to be supervised.

Earth Ground Connections

In order for the lightning transient protective devices in this product to be effective, the designated earth ground terminal

(terminal 3) must be terminated in a good earth ground. Recommended wire gauge for the ground connection is #16

AWG, run no farther than 30 feet.

IMPORTANT: The panel requires the earth ground connection for its lightning transient protection devices and in order to detect Ground Fault conditions.

PowerBoost3-B

To connect the earth ground, perform the following steps:

1. Connect the earth ground post inside the 1451 enclosure to a good earth ground (use grounding methods specified in the National Electric Code).

2. Use a green nut (supplied) to secure the wire to the ground post. Ground wire should be the only wire under this nut.

3. Run a 16AWG wire from the ground post to the panel’s earth ground terminal (30). Use a second green nut (supplied) to secure this wire to the ground post.

This connection avoids ground loops that may occur when the 1451 and panel are connected to different earth ground systems.

PowerBoost3-F

To connect the transformer to the control, perform the following steps:

1. Remove the front cover of the enclosure.

2. Mount the enclosure to the wall near the control panel. The enclosure has four mounting holes on its back surface for this purpose.

3. Run 120VAC wiring to the enclosure in conduit. A dedicated circuit must be used.

4. Use wire nuts to splice the 120VAC wires to the transformer’s white and black primary leads.

5. Connect the earth ground post on the back of the enclosure to a good earth ground.

6. Run 16AWG wire in conduit from the enclosure to the control panel.

7. Use wire nuts to splice the transformer blue 18VAC secondary leads to the 16AWG wire. Connect the 16AWG wire at the control panel to terminals 1 and 2.

8. Replace the front cover of the enclosure and fasten it with the screws supplied.

NOTES:

• Use wires having insulation rated for at least 90°C operation and suitable for non-power limited applications.

• Use care to keep 18VAC wiring separated from all other wiring inside the control panel’s enclosure. This must be done by running, non-power-limited 18VAC wiring into the control panel’s enclosure via one of the knockouts on the left-hand side, and then tie-wrapping these wires to the tie-wrap loops located near the knockout.

- 9 -

Determining the Control’s Power Supply Load

In the event of an AC power loss the PowerBoost3 must be supported by backup, rechargeable batteries. When the system is used, a 12AH to 34.4AH battery must be connected the control panel.

The battery’s capacity must be sized to provide the required hours of standby time followed by the required minutes of alarm time.

Use the worksheets that follow to calculate the total current for auxiliary power 1 or bell power 1 and auxiliary power 2 or bell power 2 total current load. In each worksheet, multiply each device’s standby and/or alarm current by the number of units used.

Fill out the Battery Capacity Calculation Worksheet, following the other worksheets below, to determine the required capacity for the backup battery. Select a battery from the Battery Selection Table (found later in this section) that have a capacity greater than or equal to the calculated capacity.

1. In Worksheet 1A, enter devices used on Auxiliary Power 1. Calculate standby and alarm currents, then add to get

Auxiliary Power 1 current subtotal.

In Worksheet 1B, enter devices connected to the Bell 1 Output. Calculate alarm currents, then add to get the Bell 1

Output current subtotal.

Worksheet 1A: Auxiliary Power 1 Current Load

Worksheet 1B: Bell 1 Output Current Load

Device

Model #

Device Current X

# of Units

Standby Alarm

Device

Model #

Device Current X

# of Units

Total Current

Alarm

Bell 1 Output Subtotal

(2A max.)

Auxiliary Power 1 Subtotal see table 2A max.

- 10 -

2. In Worksheet 2A, enter devices used on Auxiliary Power 2. Calculate standby and alarm currents, then add to get

Auxiliary Power 2 current subtotal.

In Worksheet 2B, enter devices connected to the Bell 2 Output. Calculate alarm currents, then add to get the Bell 2

Output current subtotal.

Worksheet 2A: Auxiliary Power 2 Current Load

Worksheet 2B: Bell 2 Output Current Load

Device

Model #

Device Current X

# of Units

Standby Alarm

Device

Model #

Device Current X

# of Units

Total Current

Alarm

Bell 2 Output Subtotal

(2A max.)

Auxiliary Power 2 Subtotal

2A max.

3. In Worksheet 3, enter the total calculated subtotals of all listed outputs from Worksheets 1 and 2, then add to get the combined current.

Worksheet 3: Total Current Load

Auxiliary Power 1A Subtotal

Total Current

Standby Alarm

Auxiliary Power 2A Subtotal

Bell 1B Output Subtotal n/a

Bell 2B Output Subtotal n/a

PowerBoost3 Current 100mA 100mA

Total Current Load

(see UL Listing Requirements Table for max. standby; 2.3A max. alarm)

Determining the Size of the Standby Battery

Select the battery size based upon the UL Listing Requirements Table and calculated standby load.

IMPORTANT: DO NOT use Gates batteries (sealed lead-acid type). These batteries require a different charging voltage than is supplied by the PowerBoost3

Module

.

UL Listing Requirements Table

Duration Requirement Minimum Battery AH

Listing

Standby Alarm Recharge

UL365/609 Mercantile

UL1023 House Burglary

UL365 Police Station Bank

UL365 Police Station Mercantile

4 hr

4 hr

4 hr

8 hr

15 min 24 hr

4 min 48 hr

15 min 72 hr

15 min 24 hr

UL985 Household Fire

UL864/1481 CS Signaling

24 hr

24 hr

4 min

5 min

48 hr

48 hr

UL864/1481 Remote Station Signaling 60 hr

UL365/609 Bank Vault 72 hr

5 min

15 min

48 hr

72 hr

ULC 24 hr 30 min 48 hr

(2x7AH) (2x17.2AH)

Standby Current Rating (alarm = 3A)

1.9

2

1.9

1

0.35

0.35

0

0

0.3

2.25

2.3

2.25

1.3

0.42

0.4

0.1

0

0.37

2.3

2.3

2.3

1.6

0.54

0.5.

0.15

0.11

0.5

2.3

2.3

2.3

2.1

1.2

1.2

0.4

0.33

1

- 11 -

Use battery capacity and the Battery Selection Table to determine the appropriate battery model number. A dual battery harness is supplied that allows two batteries to be wired in parallel for increased capacity.

Battery Selection Table

12AH

14AH

17.2AH

Yuasa NP12-12

Yuasa NP7-12

Yuasa NPG18-12

Fits in large mercantile cabinet only.

Connect two in parallel.

Fits in large mercantile cabinet only.

Connect the battery, referring to the diagram below.

NOTE: The standby battery is automatically tested for 10 minutes every 4 hours

.

The

PowerBoost3

also runs a 5-second battery test every 60 seconds to check if the battery is connected.

NOTE: WHEN CONNECTING BATTERIES IN PARALLEL:

- USE BATTERIES FROM THE SAME MANUFACTURER AND

WITH THE SAME VOLTAGE AND CAPACITY RATING.

- USE BATTERIES WITH APPROXIMATELY SAME AGE AND

STATE OF CHARGE.

- USE CABLES PROVIDED AND OBSERVE POLARITY!

- IT IS RECOMMENDED THAT ALL BATTERIES BE REPLACED

AT SAME TIME, EVEN IF ONLY ONE BATTERY HAS BECOME

WEAK.

- AS LONG AS ONE GOOD BATTERY REMAINS CONNECTED,

THE ONCE PER 60 SECOND BATTERY TEST WILL NOT

DETECT THE DISCONNECTION OF REMAINING BATTERIES.

PowerBoost3

RED

BATTERY

TABS

BLK

DUAL

BATTERY

HARNESS

BLK

RED

RED

BLK

OBSERVE

POLARITY!

+

12V

BATTERY

+

12V

BATTERY

(IF REQUIRED)

PB3-007-V0

Specifications

Board Dimensions 2.7” W x 8” L x 1.5” D

Input Voltage

Special Application

Notification Appliance

Output Voltages

18VAC, 72VA

12VDC 3A alarm pool, 2.2A standby,

2A max on any one output

Battery Charging Voltage 13.65VDC, 3A - 600mA

Current Drain 100mA @ 12V

ECP Input Voltage 8-14VDC

Earth Ground Impedance 1000 ohms

Max. Bell Impedance

Wire Run Length

0.85 ohms for 8VDC min. operation

0.35 ohms for 9VDC min. operation

2000ft max. unshielded; 1000ft shielded;

#14-32 gauge (see control’s instructions for wire length limitations)

32°F (0°C) to 120°F (49°C)

Temperature Range

Agency Listings

• UL 864 NFPA 72 Commercial Fire

• UL 1481 Power Supplies for Fire Alarm

System (stand-alone mode)

• UL bank listing (80-hr standby)

• California State Fire Marshal

Residential and Commercial

• New York City MEA

• Factory Mutual

REFER TO THE INSTALLATION AND SETUP GUIDE FOR THE CONTROL WITH WHICH THIS DEVICE IS

USED FOR WARRANTY INFORMATION AND LIMITATIONS OF THE ENTIRE SYSTEM.

ÊK14963RŠ

K14963 8/09 Rev. A

2 Corporate Center Drive, Suite 100

P.O. Box 9040, Melville, NY 11747

Copyright © 2009 Honeywell International Inc.

www.honeywell.com/security

advertisement

Key Features

  • Two supervised outputs
  • UL requirements
  • Auxiliary power source
  • ECP mode
  • Stand-alone mode
  • Trigger outputs
  • AC loss detection
  • Battery monitoring
  • Earth ground fault detection
  • Module shutdown

Related manuals

Frequently Answers and Questions

What does the 'ECP mode' do?
In ECP mode, the PowerBoost3 module provides two supervised bell outputs (12VDC, 3A pool, 2A max on any one output) and reports supervised conditions to the control panel via trigger output and ECP connections. These trouble conditions are reported as alarms on assigned zones (similar to zones on a 4204CF Relay Module). The Module and zones need to be programmed into the control.
What is 'Stand-alone mode'?
In Stand-Alone mode, the PowerBoost3 module provides steady power of 12VDC, 2.2A total (3A alarm, 2A max on any one output) to the two outputs. To use stand-alone mode, connect the outputs to the devices to be powered and set the module’s DIP switch to address 0 (all switches OFF).
How does the PowerBoost3 module handle AC loss?
The PowerBoost3 is powered by an 18VAC 72VA wire-in transformer connected to a 120VAC source. Loss of AC power results in a fault condition reported to the control via ECP or the AC Loss trigger. The Module supervises the following battery conditions: Battery charger failure, missing battery indication, and low battery.
What is the maximum output current for the PowerBoost3?
The total alarm current drawn from outputs 1 and 2 cannot exceed 2.9A for battery-independent operation.
How do I connect the battery to the PowerBoost3?
The battery must be sized to provide the required hours of standby time followed by the required minutes of alarm time. You should connect a 12AH to 34.4AH battery to the control panel.
Download PDF

advertisement