ProData® data logger
Smart Energy &
Power Quality Solutions
✔
ProData® data logger
Data collection and recording
ProData®
ProData® data logger
Data collection and recording
ProData® data loggers are used for the collection of any
physical measurement data (temperature, pressure, ...)
or any consumption values (electricity, water, gas,
coolant...). ProData® data loggers consist of a programmable microprocessor, storage media, several
interfaces and 16 channels for connecting sensors or
pulse generators. External sensors are used to collect
the measurement data and convert it with analoguedigital converters into “memory-safe” data in order
to be able to be stored by the ProData® storage media.
The collected data is read out through an interface and
is analysed with suitable software. The ProData® can also
be configured for the application through one of these
interfaces (e.g. measurement intervals etc). Data loggers
are indispensable for energy management systems e.g.
for cost centre management. ProData® data loggers are
also indispensable in the field of status monitoring.
Areas of application
• Data collection and recording of meter values
•E
lectricity cost data collection and cost centre
management
• Analysis of process data
• Condition monitoring
1
Data collection instrument ProData®
ProData® data logger
The ProData® data logger is suitable for collecting data
and recording meter values.
Data recording
The analogue measurement values can be recorded in
set time intervals (1 sec ...12h) as minimum, average and
maximum values. In the set time intervals (1 sec ...12h),
the difference between the overall meter readings and
the meter reading at the last recording time is shown. The
ring buffer for the values ​​storage consists of 430KB and is
sufficient for 3 months if the digital counters are recorded
every 15 minutes.
Main features
• The collection and recording of meter values
• 16 digital inputs (Connection of 15 meters; one input
reserved as tariff input)
• 64 bit counter
• RS232, RS485, Modbus
• 1 analogue input
• 1 temperature input
• Including GridVis software
Application example – photovoltaic
UMG 96
S0-Output
PT100
UMG 96
UMG 96
S0-Output
S0-Output
LiYcY 4x0,5
Maximal 100m
PSTN
2
UMG 96
S0-Output
Data collection instrument ProData®
Analogue inputs
• 1 analogue input 0 (4) – 20mA, -20/20mA programmable
• 1 input for temperature sensor: PT100, PT200, PT500,
PT1000, NTC10k oder KTY83
The measurement values can be read through Modbus.
Digital inputs
16 digital inputs can be used as:
• An overall pulse counter at each input – maximum
frequency 50Hz, 64 bit counter
• Frequency measurement on each input for monitoring
flow quantities, power etc.
The stated measurement values can be read through the
Modbus. The digital inputs (4x4) can be set as pulse (S0
interface) or as signal inputs using jumpers.
3
Application options ProData®
Dimensional drawing
Typical application
Modbus
Gas consumption
Process signal 0 (4) - 20mA
PT 100/200/500/1000
Temperature monitoring
Effective/reactive
energy consumption
Water consumption
4
Compressed
air/steam
Effective energy
consumption
Application options ProData®
Overview of product variants
Description
Type
Item number
Data logger
ProData
External power supply
24VDC
16.05.002
External power supply is necessary
24VDC (+15/-35%)
®
52.11.001
General technical data
Supply voltage
Overvoltage category
CAT II
Weight
660g
Dimensions
W=174mm x H=110mm x D=57mm
Mounting
DIN rail
Working temperature
-10…55 °C
Storage temperature
Protection class
-20…60°C
According EN60529
IP 20
Effective energy (kWh) purchase/supply
Through the pulse input
yes
Reactive energy (Karh), inductive/capacitive
Through the pulse input
yes
Apparent energy
Through the pulse input
yes
Temperature measurement input
-150…400°C
Accuracy: ± 1°C
Analogue input
4…20mA
Accuracy: ± 0.3mA
Measurement range
Features
Consumption data collection
Memory size
430kB
Clock
± 1 minute per month
Event recording
yes
Periphery
Digital inputs
As status or pulse input
16 (max. 50Hz, 64 bit counter)
Temperature measurement input
Pt100, Pt200, Pt500, Pt1000, NTC10k, KTY83
1
Analogue input
4…20mA, scaleable
1
yes
Software GridVis
Communication
Interfaces
RS 232
9.6, 19.2, 38.4, 115.2 kbps
yes
RS 485
9.6, 19.2, 38.4, 115.2 kbps
yes
Protocols
Modbus RTU
yes
5
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF