Intelligent IPM - Installation and Operations Manual

Add to my manuals
120 Pages

advertisement

Intelligent IPM - Installation and Operations Manual | Manualzz

Intelligent IPM

Firmware Release 7.0

Installation and Operations Manual

Instructions

This symbol is intended to alert the user to the presence of important operating and maintenance (servicing) instructions in the literature accompanying the appliance.

Dangerous Voltage

This symbol is intended to alert the user to the presence of un-insulated dangerous voltage within the product’s enclosure that may be of sufficient magnitude to constitute a risk of electric shock to persons.

Protective Grounding Terminal

This symbol indicates a terminal that must be connected to earth ground prior to making any other connections to the equipment.

Life-Support Policy

As a general policy, Server Technology

does not recommend the use of any of its products in the following situations:

 life-support applications where failure or malfunction of the Server Technology product can be reasonably expected to cause failure of the lifesupport device or to significantly affect its safety or effectiveness.

 direct patient care.

Server Technology will not knowingly sell its products for use in such applications unless it receives in writing assurances satisfactory to Server

Technology that:

 the risks of injury or damage have been minimized,

 the customer assumes all such risks, and

 the liability of Server Technology is adequately protected under the circumstances.

The term life-support device includes but is not limited to neonatal oxygen analyzers, nerve stimulators (whether used for anesthesia, pain relief or other purposes), auto-transfusion devices, blood pumps, defibrillators, arrhythmia detectors and alarms, pacemakers, hemodialysis systems, peritoneal dialysis systems, neonatal ventilator incubators, ventilators (for adults or infants), anesthesia ventilators, infusion pumps, and any other devices designated as

“critical” by the U.S. FDA.

Notices

301-0113-1 Rev K (052016)

Copyright © 2005-2016 Server Technology, Inc. All rights reserved.

1040 Sandhill Drive

Reno, Nevada 89521 USA

All Rights Reserved

This publication is protected by copyright and all rights are reserved. No part of it may be reproduced or transmitted by any means or in any form, without prior consent in writing from Server Technology.

The information in this document has been carefully checked and is believed to be accurate. However, changes are made periodically. These changes are incorporated in newer publication editions. Server Technology may improve and/or change products described in this publication at any time. Due to continuing system improvements, Server Technology is not responsible for inaccurate information which may appear in this manual. For the latest product updates, consult the Server Technology web site at www.servertech.com

. In no event will Server Technology be liable for direct, indirect, special, exemplary, incidental, or consequential damages resulting from any defect or omission in this document, even if advised of the possibility of such damages.

In the interest of continued product development, Server Technology reserves the right to make improvements in this document and the products it describes at any time, without notices or obligation.

The Globe logo is a trademark of Server Technology, Inc., registered in the US. Use of the logos for commercial purposes without the prior written consent of Server Technology may constitute trademark infringement and unfair competition in violation of federal and state laws.

Server Technology, the Globe logo, Sentry, Switched CDU, CDU, PRO2, PIPS, POPS, PDU Power Pivot, and StartUp Stick are trademarks of Server

Technology, Inc., registered in the US. EZip is a trademark of Server Technology.

Other trademarks and trade names may be used in this document to refer to either the entities claiming the marks and names or their products. Server

Technology, Inc. disclaims any proprietary interest in trademarks and trade names other than its own.

Please Recycle

Shipping materials are recyclable. Please save them for later use, or dispose of them appropriately.

Table of Contents

C

HAPTER

1: I

NTRODUCTION

Quick Installation Checklist ............................................................................................................. 4

Technical Support ............................................................................................................................ 4

PDU Power Pivot

.......................................................................................................................... 5

Equipment Overview ....................................................................................................................... 6

IPv6 and Sentry Products ................................................................................................................. 7

Installation ..................................................................................................................................... 10

Standard Accessories ..................................................................................................................... 10

Optional Accessories ..................................................................................................................... 10

Safety Precautions .......................................................................................................................... 11

Installing the Power Input Retention Bracket ................................................................................ 12

Attaching Safety Earth Ground Connection .................................................................................. 13

Connecting to the Power Source .................................................................................................... 14

Connecting Devices ....................................................................................................................... 14

Connecting the Sensors .................................................................................................................. 14

Connecting to the Unit ................................................................................................................... 14

4

C

HAPTER

2: O

PERATIONS

Interfaces ........................................................................................................................................ 16

Web Interface ................................................................................................................................. 17

Command Line Interface ............................................................................................................... 41

15

C

HAPTER

3: A

DVANCED

O

PERATIONS

SSL ................................................................................................................................................ 76

SSH ................................................................................................................................................ 78

SNMP/Thresholds .......................................................................................................................... 79

LDAP ............................................................................................................................................. 91

TACACS+ ................................................................................................................................... 101

Logging ........................................................................................................................................ 106

Upload/Download ........................................................................................................................ 110

75

C

HAPTER

4: A

PPENDICES

112

Appendix A: Resetting to Factory Defaults ................................................................................. 112

Appendix B: Uploading Firmware ............................................................................................... 113

Appendix C: Technical Specifications ......................................................................................... 114

Appendix D: Product Support Information .................................................................................. 119

Chapter 1: Introduction

Quick Installation Checklist

The following steps are recommended to quickly install and configure the Intelligent IPM for use in your data center equipment cabinet.

1. Mount the Intelligent IPM.

2. Connect to the power source.

3. Connect the devices.

4. Connect the sensors.

5. Connect to the PDU.

6. Configure the PDU.

 Login as the predefined Administrator (admn/admn).

 Configure the network settings.

 Create new administrative user account.

 Configure location and PDU names.

 Configure sensor names.

 Configure new user account(s).

 Remove the predefined Administrator.

7. Connect the PDU to the network.

Technical Support

Experience Server Technology's FREE Technical Support

Server Technology understands

that there are often questions when installing and/or using a new product. Free Technical

Support is provided from 8 a.m. to 5 p.m. PST, Monday through Friday. After-hours service is provided to ensure your requests are handled quickly no matter what time zone or country you are located in.

Server Technology, Inc.

1040 Sandhill Drive Tel: 1-800-835-1515 Web: www.servertech.com

Reno, Nevada 89521 USA Fax: 775-284-2065 Email: [email protected]

4  Introduction

Intelligent IPM

Installation and Operations Manual

PDU Power Pivot

Server Technology’s PDU Power Pivot

flexible infeed provides a simplified power cord routing to the PDU with a design that eliminates bend radius issues.

As illustrated below, the PDU Power Pivot capability can deliver a solution for several types of PDU installations and mountings, setting the correct cord angle for overhead power, offset overhead power, concrete floor, raised floor, and intra-rack power.

PDU Power Pivot – Flexible Cord Design

To learn more about PDU Power Pivot and watch a brief video that animates the PDU Power Pivot mounting angles in the equipment rack, see the Server Technology website at:

http://info.servertech.com/PDUpowerpivot

Intelligent IPM

Installation and Operations Manual

Introduction

5

Equipment Overview

1. The power inlet/cord(s) connects the Intelligent IPM to the electrical power source.

2. Two RJ45 connectors for Serial (RS-232) and Ethernet connection.

3. Two mini RJ11 connectors for Temperature/Humidity sensors.

A number is printed above each outlet, and these numbers can be used in commands that require an outlet name.

2

3

1

Intelligent IPM Views

6  Introduction

Intelligent IPM

Installation and Operations Manual

IPv6 and Sentry Products

Server Technology is introducing IPv6 “dual stack” support to the PDU product line. IPv6 has been designed to succeed

IPv4 as the dominant communications protocol for internet traffic, to avoid depletions of the IPv4 address space, and to allow more IP address growth. Many devices already in use support IPv6.

IPv6 has several new operational methods:

 Static IPv6 Address: The IPv6 equivalent of Static IPv4.

 DHCPv6 Address: The IPv6 equivalent of a DHCP IPv4 address, also known as a “stateful” auto-configuration of DHCPv6.

 IPv6 Stateless Auto-Configured Address – (RFC 4862): An automatically-generated unique link-local IPv6 address used for client based configurations. This address is always present in the Server Technology dual stack and cannot be disabled.

 DHCPv6 Stateless Auto-Configured Address – (RFC 3736): A “stateless” Dynamic Host Configuration Protocol

(DHCP) service for IPv6 (DHCPv6). This address is used by nodes to obtain configuration information, such as addresses of DNS recursive name servers that do not require the maintenance of any dynamic state for individual clients.

Firmware

– Protocol Support

IPv6 and IPv4 Protocols:

The firmware supports the following network IPv6 and IPv4 protocols:

 DNS Ping

 FTP (or SFTP) Server SNMPv1/2/3

 FTP (or SFTP) Updates SNTP

 HTTP or HTTPS

 SMTP

 Static IPv6 DHCPv6 (stateless and stateful)

 Syslog SNMPv1/2/3 Traps

 Telnet SSH

IPv4-Only Protocols:

The firmware supports the following network IPv4-only protocols:

 Cisco EnergyWise

 LDAP

 Load Shedding *

 RADIUS *

 TACACS+

* = may work with IPv6 addresses, but not tested.

Intelligent IPM

Installation and Operations Manual

Introduction

7

Network-Enabled Modes

NOTES:

 For all network-enabled modes described below, the PDU will set an auto-configured IPv6 address, and if IPv6 router

announcements are active, a stateless DHCP IPv6 address will also be set. Further, in all network-enabled modes, at

least one IPv4 or one IPv6 address will be active.

 For maximum backward compatibility, the default network mode is “IPv4 only”.

 Network disabled – No IPv4 or IPv6 addresses available.

 IPv4 only, DHCP disabled (static IPv4) – If the IPv4 Static Address and Net Mask of the PDU are valid, they will be set.

 IPv4 only, DHCP enabled (DHCP IPv4) – The PDU will try to resolve an IPv4 DHCP address. If a DHCP address cannot be obtained after 90 seconds, the PDU can: (1) optionally fall back to its static IPv4 settings, or

(2) indefinitely wait to acquire an address based on DHCP configuration settings. This setting is the default.

 Dual IPv6/IPv4, DHCP disabled (static IPv6/IPv4) – If the IPv6 Static Address and prefix of the PDU are valid, they will be set. Otherwise, the PDU will attempt to use DHCPv6 to obtain an IPv6 address.

In addition, if the IPv4 Static Address and Net Mask of the PDU are valid, they will be set.

 Dual IPv6/IPv4, DHCP enabled (DHCP IPv6/IPv4) – The PDU will try to resolve both its IPv6 and IPv4 addresses by DHCP. If both DHCP requests are answered, the primary DNS server of the PDU will become the primary IPv6 DNS server, and the secondary DNS server of the PDU will become the primary IPv4 DNS server.

If only one of the DHCP requests is answered, the DNS servers of the PDU will map to the primary and secondary DNS server from that request.

If a DHCP address cannot be obtained after 90 seconds, the PDU can: (1) optionally fall back to its static IPv4 and/or IPv6 settings, or (2) indefinitely wait to acquire an address based on DHCP configuration settings.

8  Introduction

Intelligent IPM

Installation and Operations Manual

Viewing Network Status

You can obtain the IPv6 network status through the firmware Web Interface or Command Line Interface (CLI). For the

CLI, use the show network command as follows:

Switched CDU: show network

Network Settings

State: DHCP IPv6/IPv4 Network: Dual IPv6/IPv4

Link: Up Negotiation: Auto

Speed: 100 Mbps Duplex: Full

AutoCfg IPv6: FE80::20A:9CFF:FE52:4104/64

IPv6 Address: FD01::1:B51A:E03C/64

IPv4 Address: 10.1.6.230 Subnet Mask: 255.255.0.0

IPv4 Gateway: 10.1.1.1

DNS1: FD01::A01:585

DNS2: 10.1.5.133

Static IPv4/IPv6 Settings

IPv6 Address: FD01::A01:353/64

IPv6 Gateway: ::

IPv4 Address: 10.1.2.253 Subnet Mask: 255.255.0.0

IPv4 Gateway: 10.1.1.1

DNS1: 10.1.5.133

DNS2: 10.1.5.134

DHCP Settings

DHCP: Enabled

FQDN: Enabled [sentry3-524104]

Boot Delay: Enabled

Static Fallback: Enabled

Network Services

Telnet: Enabled Port: 23

SSH: Enabled Port: 22 Auth: Password, Kb-Int

HTTP: Enabled Port: 80

SSL: Enabled Port: 443 Installed Cert: User Encrypted

Access: Optional Stored Files: Cert & Key

User Cert: Enabled User Passphrase: <set>

SNMPv1/2: Enabled Port: 161 TrapPort: 162

SNMPv3: Disabled Port: 161 TrapPort: 162

FTP Server: Enabled Port: 21

SPM Access: Enabled

Command successful

NOTE: The fields IPv4 Address, IPv4 Subnet Mask, IPv4 Gateway, DNS1, and DNS2 are equivalent to existing PDU IPv4 settings except that current network settings and static settings are displayed separately. This allows you to view both static configuration settings and active network settings that can be obtained using DHCP. The DNS addresses may be in IPv4 or IPv6 (based on RFC4291) format at this time.

Intelligent IPM

Installation and Operations Manual

Introduction

9

Installation

Before installing your Intelligent IPM, refer to the following lists to ensure that you have all the items shipped with the unit as well as all other items required for proper installation.

Standard Accessories

 RJ45 to RJ45 crossover cable.

 RJ45 to DB9F serial port adapter (for connection to standard DB9M DTE serial port).

 Outlet retention clips (208-240V models).

 Separate power input cord.

 Power input retention bracket hardware (can be installed):

Two removable T-brackets with two 40mm screws.

Optional Accessories

 Temperature/Humidity sensors

 Rack mounting hardware

10  Introduction

Intelligent IPM

Installation and Operations Manual

Safety Precautions

This section contains important safety and regulatory information that must be reviewed before installing and using the

Intelligent IPM.

Only for installation and use in a

Restricted Access Location in accordance with the following installation and use instructions.

This equipment should only be

installed by trained personnel.

This equipment is designed to be installed on a dedicated circuit.

The power supply cord shall be a minimum of 1.5m (4.9ft) and a maximum of 4.5m (15ft). If using an extension power cord, the total length shall also be no more than the maximum allowed. The plug is considered the disconnect device and must be easily accessible.

The dedicated circuit must have circuit breaker or fuse protection.

PDUs have been designed without a master circuit breaker or fuse to avoid becoming a single point of failure. It is the customer’s responsibility to provide adequate protection for the dedicated power circuit. Protection of capacity equal to the current rating of the PDU must be provided and must meet all applicable codes and regulations. In North America, protection must have a 10,000A interrupt capacity.

Models with unterminated power cords: Input connector must be installed by qualified service personnel. Input connector rating must meet all applicable codes and regulations.

Destiné à l'installation et l'utilisation dans le cadre de Restricted Access Location selon les instructions d'installation et d'utilisation.

Cet équipement est uniquement destiné

à être installé par personnel qualifié.

Cet équipement a été conçu pour être installé que un circuit dédié. Le cordon d’alimentation doit être d’au moins 1,5M et un maximum de 4,5m. Si vous utilisez un cordon de rallonge, la longueur totale est

également plus que le maximum autorise.

La prise est considérée comme un dispositif de coupure et doit être facilement accessible.

Le circuit spécialisé doit avoir un disjoncteur ou une protection de fusible. PDUs ont été conçus sans disjoncteur général ni fusible pour éviter que cela devient un seul endroit de panne. C’est la responsabilité du client de fournir une protection adéquate pour le circuit-alimentation spécialisé. Protection de capacité équivalant à la puissance de l'équipement, et respectant tous les codes et normes applicables. Les disjoncteurs ou fusibles destinés à l'installation en Amérique du Nord doivent avoir une capacité d'interruption de 10.000 A.

Modèles avec cordons d'alimentation non terminées: Le connecteur d’entrée doit être installé par un personnel qualifié. Entrée cote de raccordement doit respecter tous les codes et règlements électriques applicables.

Do not block venting holes when installing this product. Allow for maximum airflow at all times.

Installation Orientation: Vertical units are designed to be installed in vertical orientation.

Always disconnect the power supply cord before servicing to avoid electrical shock. For products with two input power cords, both must be disconnected before servicing.

WARNING! High leakage current!

Earth connection is essential before connecting supply!

WARNING! Cx-xxE-x units double pole/neutral fusing

ATTENTION! Observe precautions for handling Electrostatic Sensitive

Devices.

Products rated for 240/415VAC may be fitted with a plug that is rated for a higher voltage. Caution must be taken to assure that the rating of the unit and the supply voltage match.

Ne bloquez pas les orifices d'aération lors de l'installation de ce produit. Permettre une circulation d'air maximale à tout moment.

Installation Orientation: Les unités vertical sont conçues pour être installées dans une orientation verticale.

Toujours débrancher le cordon d'alimentation avant de l'ouverture pour

éviter un choc électrique . Pour les produits avec deux cordons d'alimentation d'entrée, les deux doivent être déconnectés avant l'entretien.

ATTENTION! Haut fuite très possible! Une connection de masse est essentielle avant d e connecter l’alimentation !

ATTENTION! Les unités Cx-xxE-x Double

Pôle/Fusible sur le Neutre

Attention ! Respecter les mesures de sécurité en manipulant des dispositifs sensibles aux décharges électrostatiques.

Les produits prévus pour 240/415VAC peut

être équipé d'un bouchon qui est conçu pour une tension plus élevée. Des précautions doivent être prises pour assurer que la cote de l’unité et la tension d’alimentation correspond.

Nur für Installation und Gebrauch in eingeschränkten Betriebszonen gemäß der folgenden Installations-und

Gebrauchsanweisungen.

Dieses Gerät ist nur für den Einbau

durch Personal vorgesehen.

Die Geräte sind für eine Installation an einer fest zugeordneten Leitung ausgelegt.

Die Stromzuleitung hat eine Mindestlänge von 1,5m, und hochstens 4,5m. Sollten Sie ein Verlangerrungsnetzkabel, der

Gesamtlange auch nicht mehr als die maximal zulassige sein. Der Stecker dient zur Trennung vom Netz und muss einfach erreichbar sein.

Der feste Stromkreis muss mit einem

Schutzschalter oder einem

Sicherungsschutz versehen sein. PDUs verfügt über keinen Hauptschutzschalter bzw. über keine Sicherung, damit kein einzelner Fehlerpunkt entstehen kann. Der

Kunde ist dafür verantwortlich, den

Stromkreis sachgemäß zu schützen. Der

Kapazitätsschutz entspricht der aktuellen

Stromstärke der Geräte und muss alle relevanten Codes und Bestimmungen erfüllen. Für Installation in Nordamerika müssen Ausschalter bzw. Sicherung über

10.000 A Unterbrechungskapazität verfügen.

Modelle mit nicht abgeschlossenen

Netzkabel : Der Eingangsstecker darf nur von qualifiziertem Wartungspersonal installiert werden. Eingangsanschluss

Bewertung müssen alle geltenden und verbindlichen Normen und Vorschriften entsprechen.

Achten Sie darauf, dass keine

Belüftungslöcher bei der Installation dieses

Produkts. Damit für maximalen Luftstrom zu allen Zeiten.

Installationsausrichtung: Vertical Einheiten sind zur vertikalen Installation vorgesehen.

Trennen Sie das Netzkabel, bevor Sie

Wartungsarbeiten Öffnung einen elektrischen Schlag zu vermeiden . Für

Produkte mit zwei Eingangsstromkabel, sowohl, müssen vor der Wartung abgeschaltet werden.

ACHTUNG! Hoher Ableitstrom! Ein

Erdungsanschluss ist vor dem Einschalten der Stromzufuhr erforderlich!

ACHTUNG!: Cx-xxE-x Zweipolige bzw.

Neutralleiter-Sicherung

Achtung! Vorsichtshinweise zur

Handhabung elektrostatisch empfindlicher

Geräte beachten.

Produkte die für 240/415VAC zugelassen sind können mit einem Stecker der für eine höhere Spannung ausgestattet sein.

Vorsicht ist geboten, um sicherzustellen, dass die erlaubten Betriebswerte des

Gerätes und der Versorgungsspannung zueinander passen.

Intelligent IPM

Installation and Operations Manual

Introduction  11

Installing the Power Input Retention Bracket

To install the power input retention bracket:

1. Remove the two screws attaching the IEC 60320 C19 inlet to the enclosure.

2. Assemble and attach the retention bracket to the enclosure as shown.

Retention Bracket Assembly

12  Introduction

Intelligent IPM

Installation and Operations Manual

Attaching Safety Earth Ground Connection

Server Technology PDUs are supplied with an external safety ground connection to provide an alternate ground path for fault currents, and to maintain the same ground reference between it and the equipment rack.

NOTE: The auxiliary external ground location may vary. Most PDUs will have it located near the power cord entry located near the symbol.

User-supplied materials:

 One 5 mm internal (or external) tooth star washer;

 One 4.0 mm

2

(10 AWG) wire with 5 mm ring terminal;

 One metric M5 x 6 mm coarse pitch screw.

Instructions:

1. Connect one end of the ground wire to the equipment cabinet or local ground.

2. Locate the PDU external ground near the symbol.

3. Connect the other end with a ring terminal and a M5 screw to the PDU external ground. To ensure proper grounding to the chassis, use a star washer between the ring terminal and the PDU.

Intelligent IPM

Installation and Operations Manual

Introduction  13

Connecting to the Power Source

To attach a power cord to the unit:

1. Plug the female end of the power cord firmly into its connector at the base.

2. Use a screwdriver to tighten the two screws on the retention bracket.

To connect to the power source:

Plug the male end of the power cord into the AC power source.

Connecting Devices

1. Keep the device’s on/off switch in the off position until after it is plugged into the outlet.

2. Connect devices to the Intelligent IPM outlets.

NOTE: Server Technology recommends even distribution of attached devices across all available outlets to avoid exceeding the outlet, branch or phase limitations.

Always disconnect ALL power supply cords before opening to avoid electrical shock.

Afin d’éviter les chocs électriques, débranchez TOUTES les cables électrique avant d’ouvrir.

Immer ALLE Netzleitungen auskuppeln vor den Aufmachen um elektrischen Schlag zu vermeiden.

Connecting the Sensors

The Intelligent IPM is equipped with two mini RJ11 T/H ports for attachment of the Temperature/Humidity sensors.

Attach the mini RJ11 plug of the sensor(s) to the appropriate T/H port.

Connecting to the Unit

Serial (RS232) port

The Intelligent IPM is equipped with an RJ45 Serial RS-232 port for attachment to a PC or networked terminal server using the supplied RJ45 to RJ45 crossover cable and RJ45 to DB9F serial port adapter as required.

Ethernet port

The Intelligent IPM is equipped with an RJ45 10/100Base-T Ethernet port for attachment to an existing network. This connection allows access to the Intelligent IPM via Telnet or Web.

The Intelligent IPM is configured with the following network defaults to allow unit configuration out-of-the-box through either Telnet or Web:

 IP address:

192.168.1.254

 Subnet Mask:

255.255.255.0

 Gateway:

192.168.1.1

The local PC network connection must be configured as noted below:

NOTE: Contact your system administrator for instructions in reconfiguring the network connection. Reconfiguration of your network connection may require a restart to take effect.

 IP address:

 Subnet Mask:

192.168.1.x (where x is 2-253)

255.255.255.0

14  Introduction

Intelligent IPM

Installation and Operations Manual

Chapter 2: Operations

I

NTERFACES

Outlet Naming and Grouping

Usernames and Passwords

W

EB

I

NTERFACE

Logging In

System Summary

Outlet Control

Individual ............................................................................................................................. 21

Group ................................................................................................................................... 21

Environmental Monitoring

Sensors ................................................................................................................................. 22

Configuration

System................................................................................................................................... 22

Network ................................................................................................................................ 25

Telnet/SSH ............................................................................................................................ 26

HTTP/SSL............................................................................................................................. 26

Serial Ports .......................................................................................................................... 28

Groups .................................................................................................................................. 29

Users .................................................................................................................................... 29

FTP ...................................................................................................................................... 31

SNTP/Syslog ......................................................................................................................... 32

SNMP/Thresholds ................................................................................................................ 33

LDAP .................................................................................................................................... 35

TACACS+............................................................................................................................. 37

RADIUS ................................................................................................................................ 38

SMTP/Email ......................................................................................................................... 39

Features

Tools

Ping ...................................................................................................................................... 40

Change Password................................................................................................................. 40

Firmware .............................................................................................................................. 40

View Log .............................................................................................................................. 40

Restart .................................................................................................................................. 40

C

OMMAND

L

INE

I

NTERFACE

Logging In

Operations Commands

Administration Commands

User Administration ............................................................................................................. 49

Outlet Administration ........................................................................................................... 53

Group Administration .......................................................................................................... 55

Environmental Monitor Administration ............................................................................... 56

Serial Port Administration ................................................................................................... 56

System Administration .......................................................................................................... 58

Feature Administration ........................................................................................................ 60

TCP/IP Administration ......................................................................................................... 67

HTTP Administration ........................................................................................................... 70

Sentry Power Manager (SPM) Administration .................................................................... 70

Telnet Administration ........................................................................................................... 71

FTP Administration .............................................................................................................. 71

SNTP Administration ........................................................................................................... 73

16

16

16

17

17

18

21

22

22

40

40

41

45

49

41

Interfaces

The Intelligent IPM has two interfaces: the Web interface accessed via the HTTP enabled Ethernet connections, and the command line for serial and Telnet connections.

Outlet Naming and Grouping

For commands requiring an outlet name, you can specify it in one of two ways: a predefined absolute name or a descriptive name assigned by an administrator.

Absolute names are specified by a period (.) followed by a tower letter and outlet number. The tower letter for the

Intelligent IPM is A.

Outlets can also be included in one or more named groups of outlets, enabling you to issue a command that affects all outlets in a named group.

Usernames and Passwords

The Intelligent IPM has one predefined administrative user account (username/password: admn/admn), and supports a maximum of 128 defined user accounts.

NOTE: For security, Server Technology recommends removal of the predefined administrative user account after a new account with administrative rights has been created.

Only an administrative-level user can perform operations such as creating/removing user accounts and command privileges, changing passwords and displaying user information. An administrator can also view the status of all sensors and power inputs.

Usernames can contain from 1-16 characters and are not case sensitive; spaces are not allowed. Passwords can contain up to 16 characters, and are case sensitive.

16  Operations

Intelligent IPM

Installation and Operations Manual

Web Interface

The Web Interface provides web-based access to the Firmware. The interface is designed with three major sections, illustrated below.

1. System Header: Shows PDU description and location, IP address, and user/access.

2. Navigation Bar: Provides access to PDU configuration, control action, or status page.

3. Details Window: Current control/status information based on the page selected from the navigation bar.

NOTE: The blinking of the PDU location string (IP address) in the System Header section may not work with all web browsers.

This example shows the Outlet Control > Individual page:

Example of Firmware Web Interface

Logging In

Logging in through the Web interface requires directing the Web client to the configured IP address of the unit.

To log in by the Web interface:

In the login window, enter a valid username and password and press OK.

If you enter an invalid username or password, you will be prompted again.

You are given three attempts to enter a valid username and password combination. If all three fail, the session ends and a protected page will be displayed.

NOTE: The default PDU username/password is admn/admn.

Intelligent IPM

Installation and Operations Manual

Operations  17

System Summary

The System Summary is typically displayed as the default page at user login to the firmware Web Interface. If you do not have environmental monitor access for a PDU, your default page at login will be the Outlet Control page (shown in Figure

3 above).

Both the System Summary page and the Outlet Control page display automatically at login and do not require enabling.

The System Summary page contains general system, line, humidity, and temperature status information. The color-coded sensor graphs shown in the example below provide a quick and efficient real-time view for monitoring environmental conditions in your PDU network.

Example of System Summary Page

The System Summary page displays precise current and system power consumption in your PDU network. Dynamic updates (without a full page refresh) allow you to assess critical system statistics with close to instantaneous feedback.

This performance is useful for monitoring new installation or power distribution changes in high-density computing environments. Power system administrators can also quickly identify thermal and humidity concerns that might otherwise escalate into costly infrastructure repairs if left unchecked.

As long as the System Summary page is active, the sensor graphs are continually updating system statistics and threshold values. The data with the most impact on the system is displayed to reduce your analysis and troubleshooting time. You can quickly analyze and correct a PDU if a sudden operating condition affects your device network.

NOTE: Because the System Summary page continually requests updated status information from the PDU, the page does not time-out. You will need to navigate to another page or manually log off.

System Information

Uptime: Displays the cumulative time the PDU has been up and running since the last unit restarted. Uptime shows

continuous, real-time system updates with an approximate 5-second automatic refresh. A manual refresh of the System

Summary page is not required.

Firmware Version: Shows the current firmware version.

Ethernet NIC S/N: Displays the PDU serial number derived from the Ethernet NIC.

18  Operations

Intelligent IPM

Installation and Operations Manual

Active Users: Displays the number of active user sessions accessing the firmware. These sessions include serial,

TELNET, SSH, and Web sessions. Active Users also shows sessions that an unauthorized user may be attempting to access. The number shown in Active Users changes instantly as the number of active user sessions change. A total of 4 concurrent web user sessions are allowed (HTTP or HTTPS).

NOTE: Depending on your web browser, multiple web accesses from the same machine are often treated as one user.

Total Power Consumption: Displays the total system power (in Watts) being distributed by the current PDU

configuration.

Line Status

The Line Status graph displays a blinking warning (yellow), whenever the total input load on an infeed exceeds the present user set threshold. If an overload occurs, a blinking error condition (red) is displayed. The unit continues to display these yellow and red states until the condition changes or the problem has been resolved.

The default input feed high load threshold is 80% of the input feed maximum load capacity.

NOTE: The input feed high threshold is user-defined. You must configure this threshold value on the SNMP/Thresholds page or the Command

Line Interface (CLI).

Temperature Status

The Temperature Status graph displays a blinking error whenever temperature exceeds the low or high threshold. The

PDU will continue to display this state until the condition changes or the problem has been resolved.

For the temperature sensor, the default range of low/high temperature values is 5º-45º C (41º-115º F).

Up to four sets of dual temperature/humidity sensors can be displayed in this graph for a total of eight possible temperature sensor graphs. A thin blue line separates each set based on the tower or environmental monitor.

NOTE: The temperature threshold values are user-defined. You must configure these threshold values on the SNMP/Thresholds page or the

Command Line Interface (CLI).

Humidity Status

The Humidity Status graph displays a blinking error whenever humidity exceeds the low or high threshold. The PDU will continue to display this state until the condition changes or the problem has been resolved.

For the humidity sensor, the default range of low/high humidity percentage is 0-100% (relative humidity).

Up to four sets of dual temperature/humidity sensors can be displayed in this graph for a total of eight possible humidity sensor graphs. A thin blue line separates each set based on the tower or environmental monitor.

NOTE: The humidity threshold values are user-defined. You must configure these threshold values on the SNMP/Thresholds page or the

Command Line Interface (CLI).

Field Descriptions

The following fields and icons are viewed left to right for Line Status, Temperature Status, and Humidity Status:

Icon: Provides quick viewing of current operational state: Information

, Warning and Critical .

ID: Device input feed or sensor identifier.

Name: Descriptive, user-defined name for each input infeed or sensor.

Load, Temp, Humidity: Current state of the reported input load (in amps), current temperature, or current percentage of

relative humidity.

Low Limit: Displays the user-defined low limit of the load, temperature, or humidity graph. These values depend on the

sensor limited and cannot be set by the user. For example, a 0ºC low limit would be displayed as sensor graph in Celsius.

for a temperature

Sensor Graph and Level Indicator: The horizontal sensor graph shows current operating conditions in color-coded

segments. See the section below, “Sensor Graph Color Coding” for details. The level indicator

appears across the graph to indicate the relative position of the current data value with respect to the minimum (low limit) and maximum

(high limit) values displayed at the left and right of the graph.

Intelligent IPM

Installation and Operations Manual

Operations  19

High Limit: Displays the high limit of the load, temperature, or humidity graph. These values depend on the sensor limits

are cannot be set by the user. For example, a 100ºC high limit would be displayed as in Celsius.

for a temperature sensor graph

Status: One of several operating conditions:

System Summary

– Status Descriptions

Icon Status Description

Reading

Normal

Load High

Over Load

Temp Low

Temp High

Humid Low

Humid High

Unit is reading a new or restored sensor.

Indicates normal operation.

Infeed current load exceeds present High threshold.

Infeed current load exceeds the measurable range for the infeed.

Current temperature falls below present Low threshold.

Current temperature exceeds present High threshold.

Current percentage of relative humidity falls below present Low threshold.

Current percentage of relative humidity exceeds present High threshold.

Lost The connection was lost to a sensor that was previously detected and the sensor is pulled from the original environment monitoring statistics. There is no data to report, the graph is meaningless, and the threshold settings remain displayed but are grayed.

Sensor Graph Color-Coding

The following colors change dynamically on the sensor graphs to communicate operating conditions:

Line (Load) Status:

Green = Normal

Yellow = High load (load configured by user)

Red = Overload (based on device characteristics)

User configures load capacity at Configuration > SNMP/Thresholds > Input Feed Traps and Thresholds

Temperature Status:

Blue = cold; low temperature (threshold configured by user)

Green = acceptable temperature range

Red = hot; high temperature (threshold configured by user)

User configures low/high temperature thresholds at Configuration > SNMP/Thresholds > Sensor Traps and

Thresholds

Humidity Status:

Blue = wet; high humidity (threshold configured by user)

Green = acceptable percentage of relative humidity

Yellow = dry; low humidity (threshold configured by user)

User configures low/high relative humidity thresholds at Configuration > SNMP/Thresholds > Sensor Traps and

Thresholds

20  Operations

Intelligent IPM

Installation and Operations Manual

Logical Group Separators

Logical groups are separated by a thin blue line on the System Summary page as shown in the following example between

Tower A_InfeedA and Tower B_InfeedA:

This grouping includes master/link units in addition to some branched units.

Up to three blue line dividers can be displayed on the System Summary page between all sensor groups.

Outlet Control

The Outlet Control section offers access to the Individual and Group outlet control pages. From the Individual and Group pages, the user can review and manipulate power control functions for all outlets and groups assigned to the current user.

Both pages include the outlet’s absolute and descriptive names, the Outlet Status reported to the PDU by the outlet, the current Control State being applied by the PDU, and the outlet load in amperes.

Available outlet and group power states can be set to on, off, or reboot.

Individual

The Individual outlet control page displays all outlets assigned to the current user. The user can apply on, off, or reboot actions to individual, multiple, or all accessible outlets.

To apply actions to individual or multiple outlets:

In the Individual Outlet Control section, select the desired action from the Control Action drop-down menu for each individual outlet to be changed, and click Apply.

To apply an action to all outlets:

In the Global Control section, select the desired action from the Control Action drop-down menu and click Apply.

Group

The Group outlet control page displays all groups assigned to the current user, as well as the outlets for each group.

To select a group:

Select the group name from the drop-down menu and click Select. The page will refresh to display all outlets associated to the selected group name.

To apply an action to a group:

Select the desired action from the drop-down menu and click Apply.

Intelligent IPM

Installation and Operations Manual

Operations  21

Outlet State/Control State Field Values

Outlet State Control State Description

On On Outlet is on

Off

Off

Off

Pend On

Outlet is off

Outlet is off and about to turn on in response to a sequence timer

Off

On

Off

On

Off

On/Wait

Off/Wait

On/Error

Off/Error

Off/Fuse

On/Fuse

Reboot

Idle On

Idle Off

Wake On

Wake Off

Off

On varies varies

On

On

Outlet is off and a Reboot action has been initiated

A restart has occurred

– Last Control State has been maintained

A restart has occurred

– Last Control State has been maintained

A power-loss has occurred

– Wakeup State has been applied

A power-loss has occurred

– Wakeup State has been applied

Outlet state in transition

– Re-query of outlet status required

Outlet state in transition

– Re-query of outlet status required

Error State

– Outlet should be off, but current is sensed at the outlet

Error State

– Outlet should be on, but no current is sensed at the outlet

Outlet should be on, but a blown fuse has been detected

Outlet should be on, but a blown fuse has been detected downstream

No Comm varies Communication to the outlet has been lost. Control state will be applied when communication is

re-established.

Environmental Monitoring

Sensors

The Sensors page displays:

 Absolute and descriptive names of the temperature/humidity sensor

 Temperature/humidity sensor readings and percentage of relative humidity

Monitor pages (like the Sensors page) refresh occasionally to reflect current PDU status.

Temperature/Humidity Sensor Status

Status

Found

Not Found

Lost

Description

The PDU found the sensor and connection is established.

On a fresh reboot, the PDU does not find a sensor.

The connection to a previously found sensor is now lost.

No Comm Communication loss occurred due to a hardware issue (not loss of communication with the probes).

1

1

= The ENV part of the sensor supports two Temperature/Humidity (T/H) probes as part of the master unit, two T/H probes as part of the link unit, and the optional EMCU-1-1 (which can support two T/H probes, four contact-closure monitoring points, and one water sensor). The “No Comm” sensor status is not loss of communication with probes themselves.

Configuration

The Configuration section offers access to all unit configuration options. This section is available to administrative level users only.

System

The System configuration page is used for reference of system information such as Ethernet NIC Serial Number, Ethernet

MAC address and system firmware and hardware revisions as well as assignment and maintenance of other system wide configurations.

For descriptive names, up to 24 alphanumeric and other typed characters (ASCII 33 to 126 decimal) are allowed. Spaces are not allowed.

NOTE: Spaces can be used for the location description only.

22  Operations

Intelligent IPM

Installation and Operations Manual

Creating a pre-login banner:

Click the Login Banner link. On the subsequent Login Banner page, type pre-login banner text and click Apply.

NOTES:

 The pre-login banner can be up to 2069 characters in length and is displayed prior to the login prompt. If left blank, a system banner will

not be displayed prior to the login prompt.

 For an SSH connection, the banner length is truncated to 1500 bytes in SSH packets to avoid failure of the SSH connection when

configured with a long login banner.

The Login Banner displays the following Characters Remaining box to show you in real-time as you type how many of the

2069 maximum characters are still available for you to complete your banner. The box adjusts dynamically as you type or delete characters.

If you reach the maximum 2069 characters, the box displays “-1”. To clear your entry and start over, click Cancel.

Creating a descriptive system location name:

Enter a descriptive name and press Apply.

Configuring the Input Current LED display orientation:

Select Normal or Inverted from the drop-down menu and click Apply.

Configuring the LED display orientation:

From the Display Orientation drop-down list, select Normal or Inverted, and click Apply.

NOTES:

 Only specific PDU models are equipped with an accelerometer chip that senses device orientation. If equipped, your PDU automatically

aligns the LED display orientation (depending on its current direction), and the option “Auto” displays in the Display Orientation

drop-down list by default. In addition, the actual mounting of the unit, such as “<Normal> or <Inverted>”, appears to the right of

the "Auto" option. However, even if your PDU model does have the sensor for device orientation, you can still select the Normal or

Inverted option from the list to override the capability of the hardware.

 If your PDU model does not have the accelerometer chip, you will need to configure the LED display orientation by selecting Normal or

Inverted.

Enabling or disabling strong password requirements:

Sentry supports enforcement of strong passwords for enhanced security. When enabled, all new passwords must be a minimum of 8 characters in length with at least one uppercase letter, one lowercase letter, one number and one special character.

Acceptable strong passwords:

n0tOnmyw@tch john2STI?

H3reUgo!

NOTE: Strong password requirements also enforce a minimum change of four character positions when defining new strong passwords.

Select Enabled or Disabled from the Strong Passwords drop-down menu and press Apply.

NOTE: The strong password requirement is applied against all new passwords.

Enabling or disabling the configuration reset button:

Select Enabled or Disabled from the Configuration Reset Button drop-down menu and press Apply.

Setting the temperature scale:

Select Celsius or Fahrenheit from the Temperature Scale drop-down menu and press Apply.

Creating a descriptive unit name:

Click on the Tower Names link.

On the subsequent Tower Names page, enter a descriptive name and press Apply.

Intelligent IPM

Installation and Operations Manual

Operations  23

Creating a descriptive input feed name:

Click on the Input Feed Names link.

On the subsequent Input Feed Names page, enter a descriptive name and press Apply.

Setting the temperature scale:

Select Celsius or Fahrenheit from the Temperature Scale drop-down menu and click Apply.

Setting the system area (footprint):

Enter a system area value in the Area (Footprint) field and click Apply.

Setting the system area unit of measure:

Select Square Feet or Square Meters from the Area (Footprint) drop-down menu and click Apply.

Setting the power factor:

The Power Factor value calculates the power usage displayed in the Power Monitoring pages.

Type a numeric value in the Power Factor field (from 0.50 to 1.00) and click Apply.

Setting the 3-phase load out-of-balance threshold:

The threshold (percentage) specified determines when the current on the lines of a 3-phase system are out-of-balance between the three phases of power. If the alerting feature is enabled, an alert will be sent when an out-of-balance condition occurs.

In the 3-Phase Load Out-of-Balance Threshold field, type a value from 0 to 100%, and click Apply.

Setting the 3-phase load out-of-balance alerting:

This setting enables/disables the sending of an alert when the current on the lines of a 3-phase system are past a pre-set threshold (percentage) and are out-of-balance between the three phases of power.

From the 3-Phase Load Out-of-Balance Alerting drop-down menu, select Enabled or Disabled, and click Apply.

NOTES:

 When a device with 3-phase input voltage is out-of-balance, efficiency is reduced and the unit is prevented from reaching maximum

capacity. When an alert for the out-of-balance condition is received (if the alerting feature is enabled), it may be necessary to adjust

distribution of the loads.

 For 3-phase systems, if the Out-of-Balance Alerting feature is enabled, and the system goes into a load out-of-balance condition, the

Tower Status field on the “Power Monitoring – System” web page will display the alert “3ph Out-of-Balance”, unless there is a higher

priority tower error state to report.

Configuring the Command Line Interface (CLI) session timeout:

Enter a timeout period (in minutes) in the CLI Session Timeout field, and click Apply.

The valid timeout range is 1 to 1440 minutes (24 hours); the default is 5 minutes.

Configuring the web session (Web Interface) timeout:

Enter a timeout period (in minutes) in the Web Session Timeout field.

The valid timeout range is 1 to 1440 minutes (24 hours); the default is 5 minutes.

Creating a descriptive outlet name:

Click on the Outlet Names link which will open the Outlets configuration page.

Creating a descriptive serial port name:

Click on the Serial Port Names link which will open the Serial Ports configuration page.

Creating a descriptive environmental monitor name:

Click on the Environmental Monitor Names link.

On the subsequent Environmental Monitor Names page, enter a descriptive name and press Apply.

Creating descriptive sensor names:

Click on the Sensor Names link.

On the subsequent Sensor Names page, enter a descriptive name and press Apply.

24  Operations

Intelligent IPM

Installation and Operations Manual

Network

The Network configuration page is used for maintenance of the network interface. From this page an administrator can configure the IP address, subnet mask, gateway address, DNS addresses as well as view the link status, speed and duplex value.

The PDU is configured with the following network defaults to allow unit configuration out-of-the-box through either

Telnet or Web:

 IP address:

192.168.1.254

 Subnet Mask:

255.255.255.0

 Gateway:

192.168.1.1

The initial local PC network connection must be configured as noted below:

NOTE: Contact your system administrator for instructions in reconfiguring the network connection. Reconfiguration of your network connection may require a restart to take effect.

 IP address:

 Subnet Mask:

192.168.1.x (where x is 2-253)

255.255.255.0

NOTE: The unit must be restarted after network configuration changes.

Enabling or disabling Dynamic Host Configuration Protocol (DHCP) support:

To enable DHCP, check the Enable checkbox. To disable DHCP, uncheck the checkbox. Click Apply.

Enabling Dynamic Host Configuration Protocol (DHCP):

To enable DHCP, check the Enable checkbox. To disable DHCP, uncheck (clear) the checkbox.

Click Apply.

Setting the Fully-Qualified Domain Name (FQDN):

To enable FQDN, check the Enable checkbox and accept the default name “sentry3-521384” (or type a different name).

To disable FQDN, uncheck (clear) the checkbox.

Click Apply.

Enabling the DHCP boot delay:

To enable the boot delay, check the Enable checkbox. To disable the boot delay, uncheck (clear) the checkbox.

Click Apply.

 Enabling the Boot Delay option gives the PDU approximately 100-seconds to establish a connection through a

DHCP server. This interval allows various network component activities to occur as the CDU powers up (such as obtaining SNTP time stamps for logging). This is the default state.

 Disabling the Boot Delay option forces the CDU to boot after approximately 5-seconds regardless of the DHCP acquisition state. This speeds up a boot when a DHCP server is connected to one of the outlets in the CDU. In this configuration, SNMP traps, SNTP, and other protocols will not be available until a DHCP address has been resolved.

NOTES:

 The Boot Delay option executes only when DHCP is enabled.

 The firmware can detect network link integrity and will wait for network connection. This means that if the network is not currently

connected, the enabled Boot Delay option will be ignored.

Enabling static address fallback:

NOTE: The Static Address Fallback option executes only when DHCP is enabled.

To enable static address fallback, check the Enable checkbox. To disable, uncheck (clear) the checkbox.

Click Apply.

 Enabling the Static Address Fallback option informs the PDU to automatically fall back to a static address if a

DHCP server does not respond after 100-seconds. This is the default state.

 Disabling the Static Address Fallback option generates DHCP server requests until the PDU obtains a dynamic address.

NOTE: If the DHCP server boot time is excessive, you may need to disable the DHCP Static Address Fallback option.

Intelligent IPM

Installation and Operations Manual

Operations  25

Setting the IP address, subnet mask, gateway or DNS address:

In the appropriate field, enter the IP address, subnet mask, gateway address or DNS address and press Apply.

Telnet/SSH

The Telnet/SSH configuration page enables or disables Telnet and SSH support and configures the port number that the

Telnet or SSH server watches.

Enabling or disabling Telnet or SSH support:

Select Enabled or Disabled from the appropriate Server drop-down menu and click Apply.

Changing the Telnet or SSH server port number:

In the appropriate Port field, enter the port number and click Apply.

Enabling or disabling SSH server authentication methods:

The SSH server supports the Password and the Keyboard-Interactive authentication methods for security.

Password is an authentication method in which the SSH client gathers username/password credentials and makes the authentication request to the SSH sever with the credentials. The Password method is controlled by the SSH client.

Keyboard-Interactive is an authentication method in which the SSH server controls an information field followed by one or more prompts requesting credential information from the SSH client. The client gathers credential information keyed-in by the user and sends it back to the server. The Keyboard-Interactive method is controlled by the SSH server.

Individual enabling and disabling of the Password and Keyboard-Interactive authentication methods are supported to allow an

SSH client to be forced to use a specific method. Although both methods are available, by enabling the Keyboard-Interactive method and disabling the Password method, the SSH client is forced to used Keyboard-Interactive, which is required to display the login banner.

NOTE: At least one authentication method must be enabled.

Select the Password checkbox and/or the Keyboard-Interactive checkbox and click Apply.

HTTP/SSL

The HTTP/SSL page configures HTTP server options, SSL options (including user-defined certificates), and determines settings for the PDU Power Manager (SPM) enterprise software product.

Enabling or disabling HTTP or SSL support:

From the HTTP or SSL Server drop-down menu, select Enabled or Disabled, and click Apply.

NOTE: SSL-encrypted (HTTPS) must be used for secure website connections.

Setting SSL secure access:

SSL allows either optional or required connections. The default secure access is optional.

 Optional: Both non-secure (HTTP) and SSL-encrypted connections (HTTPS) are allowed access.

 Required: Only SSL-encrypted connections (HTTPS) are allowed access.

From the Secure Access drop-down menu, select Optional or Required, and click Apply.

Changing the HTTP server or SSL port number:

In the HTTP or SSL section of the page, in the Port field, type the port number, and click Apply. The HTTP default port number is 80; the SSL default port number is 443.

Uploading a custom user certificate:

Enabling and disabling user certificates:

In the User Certificate drop-down menu, select Enabled. Provide a passphrase

(0-47 characters)

for the new certificate. To change the passphrase, type a new passphrase and check the Change checkbox. Click Apply.

The Stored Files section displays a message to confirm the upload status of the user certificate and its related public key.

26  Operations

Intelligent IPM

Installation and Operations Manual

Custom User Certificate Messages

Message

Cert & Key

Cert

No Cert

Factory Encrypted

None

Uploading the certificate:

Description and Valid Values/Range

Both the user certificate and its key were uploaded successfully.

User certificate was uploaded without a key.

User certificate was not uploaded.

User certificate was encrypted and uploaded at product assembly.

Neither the user certificate nor its key were uploaded.

NOTE: You can enable user certificates and provide a passphrase using either the firmware Web interface or the Command Line Interface (CLI).

However, the uploading of a custom user certificate can only be done using the Web interface – there are no equivalent commands for uploading user certificates.

To upload a user certificate, click the Upload link. The Upload window displays. Type the certificate filename (or key filename) and click the Upload button. The upload status is displayed in the Stored Files section as described above.

Removing a certificate:

To remove a user certificate, click the Remove link. A message displays to confirm the removal of the certificate.

Setting the PDU Power Manager (SPM) options:

The PDU Power Manager (SPM) is Server Technology’s enterprise management software product for the data center. The configuration options provided allow you to enable/disable SPM and reset the SPM password to its default.

NOTE: The SPM options apply only if you are currently using Server Technology’s SPM software.

SPM Secure Access:

If your operation does not currently use SPM software, you can disable SPM Secure Access. However, if disabled, the

PDU will not be able to use the SPM suite of secure network capabilities or the advanced remote configuration.

Select Enabled or Disabled from the SPM Secure Access drop-down menu and click Apply.

NOTE: Both HTTP and SSL must be enabled or the SPM Secure Access option will not be permitted. When SPM Secure Access is permitted, the default is Enabled.

SPM Password:

Each PDU has a default unique SPM password that is used to communicate between SPM and the PDU. When SPM discovers a PDU in the network, SPM changes this password into a different unique password for added security. The

SPM then continues to manage or alter these passwords as required for system security.

If a PDU is relocated or swapped from the system after a password was generated, SPM may not be able to re-establish a connection to the unit. The Set SPM Reset Password command allows you to reset to the internal default password of the

PDU so SPM can re-discover the device and add it to the system. Once the unit has been acquired by SPM, no further action is necessary.

To reset the password, check SPM Password and click Apply.

NOTE: Do not reset the password if SPM communication has already been established.

Intelligent IPM

Installation and Operations Manual

Operations  27

Serial Ports

The Serial Ports configuration page allows maintenance to the serial port.

NOTE: Pass-Thru connections can only be initiated from the command line interface via a Telnet/SSH session.

Setting the data-rate for all serial ports:

Select the serial port data-rate from the drop-down menu and click Apply.

Setting the serial port timeout value:

The Serial Port Timeout Value sets the serial port inactivity timeout period for individual ports. The timeout period defines the maximum period of inactivity before automatically closing the Pass-Thru session.

The valid range for the timeout is 0 to 60 (in minutes). The default timeout is 5 minutes. Setting the timeout value to “0” disables the timeout.

Click the Edit link in the Action column next to the individual port to be configured.

Type the timeout minutes in the Connection Timeout field and click Apply.

Creating a descriptive serial port name:

Click the Edit link in the Action column next to the port to be configured.

On the following Serial Ports Edit page, enter a descriptive name up to 24 alphanumeric and other typed characters - (ASCII 33 to

126 decimal) are allowed; spaces are not allowed. Press Apply.

Enabling or disabling serial port active signal checking:

Click on the Edit link in the Action column next to the port to be configured.

On the following Serial Ports Edit page, select On or Off from the DSR Check drop-down menu and click Apply.

Enabling or disabling the Command Line Interface (CLI):

This option enables or disables availability of the CLI for issuing action commands to the PDU. If disabled, only the

Firmware Web user interface will be available.

Click on the Edit link in the Action column next to the port to be configured.

On the following Serial Ports Edit page, select Enabled or Disabled from the CLI drop-down menu and click Apply.

Enabling or disabling the Serial Command Protocol (SCP):

This option allows SCP functions to be enabled or disabled for a specific serial port.

Click on the Edit link in the Action column next to the port to be configured.

On the following Serial Ports Edit page, select Enabled or Disabled from the SCP drop-down menu and click Apply.

NOTES:

 Upon a coldboot of the system, if the Coldboot Alert feature is enabled, the system will send a ½ second RS-232 break out to any

SCP-enabled serial ports.

 The SCP option must be enabled to use the Bluetooth Android solution.

Enabling or disabling the Serial Command Protocol (SCP) emulation:

This option notifies SCP of an MRV device on a specific serial port.

Click on the Edit link in the Action column next to the port to be configured.

On the following Serial Ports Edit page, select None or MRV from the SCP Emulation drop-down menu and click Apply.

Enabling or disabling the RFTAG option:

This option makes RF Code sensor tags available for the Server Technology wireless monitoring solution.

Click on the Edit link in the Action column next to the port to be configured.

On the following Serial Ports Edit page, select Enabled or Disabled from the RFTAG drop-down menu and click Apply.

28  Operations

Intelligent IPM

Installation and Operations Manual

Configuring the Bluetooth™ options:

If the PDU has been equipped for the mobile monitoring solution using Bluetooth

® technology, several Bluetooth parameters will be available for editing on the Serial Ports configuration page.

Click the Edit link in the Action column to configure the following parameters.

Provide a value as described for each parameter field, and click Apply.

Firmware Bluetooth Parameters

Parameter

Bluetooth Name

Description and Valid Values/Range

Descriptive name of the Bluetooth module that displays in the list of discovered modules on the

Android device. The default module name is “ST Eye”. The name cannot be blank; maximum

Valid range is 1-31 characters.

Bluetooth Discoverability Settings that determine the current status of the pushbutton on the Bluetooth module.

 Always – The Bluetooth module is discoverable, even without pressing the pushbutton.

 Limited – (Default). The pushbutton on the Bluetooth module must be pressed to make

the module discoverable for 60-seconds.

 Never – The Bluetooth module is never in discoverable mode.

Bluetooth Pin Code The pin code is available for legacy Bluetooth modules that require a pin to pair the module.

Although not used in current Bluetooth modules, the pin code is supported if needed.

Default is 9611; must be 4-digits; range is 0000 to 9999.

Bluetooth Transmission Power Designated transmission power (dbm) for the Bluetooth module. Note that lowering the

transmission power reduces the effective range of the module. Default is 0;

range is -6 to 4 dbm.

Groups

The Groups configuration page allows you to create and delete groups and to assign outlets to groups.

Creating a group:

Enter a descriptive group name in the Group Name field. Up to 24 alphanumeric and other typed characters (ASCII 33 to

126 decimal) are allowed; spaces are not allowed. Press Apply.

Removing a group:

Click on the Remove link in the Action column for the group to be removed and click Yes on the subsequent confirmation window.

Adding and Deleting outlets from a group:

Press the Edit link in the Action column for the associated group.

On the subsequent Group Edit page, select or deselect outlets to be included in that group. Press Apply.

Users

The Users configuration page is used for creation and removal of usernames, assignment of accessible outlets and group, assignment of privilege levels, and the changing of user passwords.

Creating a new user:

Enter a user name in the Username field. Up to 16 alphanumeric and other typed characters (ASCII 33 to 126 decimal) are allowed; spaces are not allowed.

Enter a password for the new user and verify in the Password and Verify Password fields. For security, password characters are not displayed. Press Apply.

Removing a user:

Click on the Remove link in the Action column for the user to be removed and click Yes on the subsequent confirmation window.

Changing a user password:

Click on the Edit link in the Action column for the associated user.

On the subsequent User Edit page, enter a password and verify the new password for the new user in the Password and

Verify Password fields. For security, password characters are not displayed. Press Apply.

Intelligent IPM

Installation and Operations Manual

Operations  29

Changing a user’s access privilege level:

The PDU has the following defined privilege levels:

 Admin:

Full-access for all configuration, control (On, Off, Reboot), status and serial/Pass-Thru ports.

 Power User:

Full-access for all control (On, Off, Reboot), status and serial/Pass-Thru ports.

 User:

Partial-access for control (On, Off, Reboot), status and Pass-Thru of assigned outlets, groups and serial/Pass-Thru ports.

 Reboot-Only: Partial-access for control (Reboot), status and Pass-Thru of assigned outlets, groups and serial/Pass-Thru ports.

 On-Only:

Partial-access for control (On), status and Pass-Thru of assigned outlets, groups and serial/Pass-

Thru ports.

 View-Only:

Partial-access for status and Pass-Thru of assigned outlets, groups and serial/Pass-Thru ports.

The administrator can also grant administrative privileges to other user accounts allowing the unit to have more than one administrative-level user.

NOTE: You cannot remove administrative privileges from the default admn user unless you have already granted administrative access to another user account.

Click on the Edit link in the Action column for the associated user.

On the subsequent User Edit page, select Admin, Power-User, User, Reboot-only, On-only or View-only from the Access Level drop-down menu and click Apply.

Granting or removing environmental monitoring access:

Click on the Edit link in the Action column for the associated user.

On the subsequent User Edit page, select Yes or No from the Environmental Monitoring drop-down menu and click

Apply.

NOTE: Granting access to environmental monitoring (temperature/humidity/sensors) to a non-admin user also grants that user access to power monitoring (outlets, infeeds, towers – all the environmental data of the PDU).

Adding and deleting outlet access:

Click on the Outlets link in the Access column for the associated user.

On the subsequent User Outlets page, select or deselect outlets to be accessed by the user and click Apply.

Adding and deleting group access:

Click on the Groups link in the Access column for the associated user.

On the subsequent User Groups page, select or deselect group to be accessed by the user and click Apply.

Adding and deleting serial port access:

Click on the Ports link in the Access column for the associated user.

On the subsequent User Ports page, select or deselect ports to be accessed by the user and click Apply.

30  Operations

Intelligent IPM

Installation and Operations Manual

FTP

The FTP configuration page allows you to set up and maintain all settings required to perform an FTP firmware upload, configure automatic FTP updates, or system configuration uploads/downloads.

NOTES:

The FTP page accepts both IPv4 and IPv6 formats in the Host field.

 Secure File Transport Protocol (SFTP) is also supported for encrypted SSH transport over the network.

Setting the FTP Host Address:

Enter the IP address or hostname in the Host field and press Apply.

Setting the FTP username:

Enter the FTP server username in the Username field, and press Apply.

Setting the FTP password:

Enter the FTP server password in the Password field, and press Apply.

Setting the filepath:

Enter the path of the file to be uploaded in the Directory field, and press Apply.

Setting the filename for upload:

Enter the filename of the file to be uploaded in the Filename field, and press Apply.

Testing the FTP upload configuration:

This test validates that the unit is able to contact and log onto the specified FTP server, download the firmware file and verify that the firmware file is valid for this unit.

Press Test.

Enabling or disabling automatic updates:

The PDU features the ability to schedule automatic firmware updates. When enabled and configured, the PDU will regularly check the FTP server for a new firmware image and upload it.

Select Enabled or Disabled from the drop-down menu and press Apply.

Setting the automatic update scheduled day:

Select the desired day for the automatic update from the drop-down menu and press Apply.

Setting the automatic update scheduled hour:

Select the desired hour for the automatic update from the drop-down menu and press Apply.

Enabling or disabling the FTP server:

The PDU features the ability to upload and download system configuration files to ease implementation across multiple

Sentry devices.

Select Enabled or Disabled from the drop-down menu and press Apply.

NOTE: The FTP server must be enabled for configuration upload or download.

Intelligent IPM

Installation and Operations Manual

Operations  31

SNTP/Syslog

The SNTP/Syslog page sets the options for the SNTP server, time zone, Daylight Saving Time (DST) automatic clock adjustment, and Syslog server.

About Daylight Saving Time(DST)

Support for DST is disabled by default. When enabled, the date and time are automatically adjusted forward one hour between the starting and ending dates and times (which can be configured).

NOTE: If Daylight Saving Time (DST) is enabled, all system time displays will be shown with the current DST start/end date/time settings.

The default time zone is set for the United Stated until at least 2015.

The time zone format is: mo.w.d/h:m:s, as follows:

mo = month from January to December (1-12)

w = week number (1-4) or the last week (5)

d = day of week from Sunday to Saturday (0-6)

h = hour (0-23)

m = minute (0-59)

s = second (0-59)

Setting the local date/time:

The Date/Time (Local) field shows the current DST settings. To increment the settings – based on updates to the start/end day/time options – click Update.

Setting the SNTP primary/secondary server address:

The Primary/Secondary Host fields contact the SNTP server; the fields are populated with the external NTP pool time zones “2.pool.ntp.org” and “1.pool.ntp.org” as default for new PDUs that have not yet been time set.

Enter the IP address or hostname in the Primary Host and/or Secondary Host field and click Apply.

Setting the Local GMT offset (hours/minutes):

The GMT offset supports all standard international time zones from -12:59 to +14.59. The GMT offset can be set in minutes to accommodate partial-hour time zones.

Select the local offset from GMT value from the drop-down menu and click Apply.

Enabling or disabling Daylight Saving Time (DST):

Select Enabled or Disabled from the SNMPv3 Agent drop-down menu and click Apply.

Setting Daylight Saving Time (DST) start/end date/time options:

Select the week/day/month and hour/minute/second for the start date/time and end date/time from the drop-down menus and click Apply.

Setting the Syslog server address:

Enter the IP address or hostname in the Primary and/or Secondary Host field, and click Apply.

NOTE: Both IPv4 and IPv6 formats are accepted in the Primary/Secondary Host fields.

Changing the Syslog server port number:

In the Syslog Port field, enter the port number and click Apply.

32  Operations

Intelligent IPM

Installation and Operations Manual

SNMP/Thresholds

The SNMP/Thresholds configuration page allows setup and maintenance of all SNMP agent settings required to enable

SNMP. The page also provides access to the trap configuration pages for towers, input feed, environmental monitor, and sensors.

NOTE: Traps are generated according to a hierarchical architecture; for example, if a tower status enters a trap condition, only the tower status trap is generated. Infeed and outlet status traps are suppressed until the tower status returns to normal.

About SNMP versions:

The firmware supports SNMP versions 1, 2, and 3.

SNMP version 3 supports authentication and encryption on a per user basis. Authentication types are None and MD5.

Encryption types are None and DES. If you use authentication, you must use encryption.

Two SNMPv3 users are supported: one user with read-write (RW) access, and one user with read-only (RO) access Both users have the same configuration parameters, and you can configure each user independently.

SNMPv2 and SNMPv3 can be enabled or disabled independently. You can have SNMPv2 and/or SNMPv3, or none.

Enabling or disabling SNMP v3 support:

Select Enabled or Disabled from the SNMPv3 Agent drop-down menu and click Apply.

NOTE: The default for SNMP support is Enabled. When Server Technology products are shipped, the default SNMP configuration for the GET community string is set to “public” and the SET community string is left blank.

Setting the SNMPv3 read-write (RW) user or read-only (RO) user:

Enter the Read-Write User or Read-Only User username and click Apply. A valid username can be set to any value between 1-31 characters.

Configuring the SNMPv3 read-write (RW) user or read-only (RO) user authentication type:

From the Read-Write User or Read-Only User Authentication Type drop-down menu, select None or MD5, and click

Apply. To clear the password, check Change Password.

Setting the SNMPv3 read-write (RW) user or read-only (RO) user authentication password:

Enter the Read-Write (RW) User or Read-Only (RO) User Password and, and click Apply. To clear the password, check

Change Password. A valid authentication password can be set to any value between 1-39 characters. A blank password

will clear the string.

Configuring the SNMPv3 read-write (RW) user or read-only (RO) user privacy type:

From the Read-Write User or Read-Only User Privacy Type drop-down menu, select None or DES, and click Apply. To clear the password, check Change Password.

Setting the SNMPv3 read-write (RW) user or read-only (RO) user privacy password:

Enter the Read-Write User or Read-Only User privacy password and, and click Apply. To clear the password, check

Change Password. A valid password can be set to any value between 1-31 characters

Setting the SNMPv3 trap username:

The optional trap username displays on SNMP activity logs to identify user actions.

Type a name in the Trap Username field and click Apply. The trap username can be 1-31 alphanumeric characters; spaces are allowed; and the name is case sensitive.

Intelligent IPM

Installation and Operations Manual

Operations  33

Configuring general parameters for any SNMP version:

Setting trap destinations:

Type an IP address or hostname as necessary in the trap destination field(s) and click Apply.

NOTE: Both IPv4 and IPv6 formats are accepted in the “Trap Destination 1” and “Trap Destination 2” fields.

Setting the error trap repeat time:

Type a time value in the Error Trap Repeat Time field and click Apply. The valid range is 1 to 65535 (in seconds).

Setting the trap format version:

The SNMP Trap Format configures the SNMP trap format version. The trap format can be SNMP v1, v2, or v3. The default is v1, regardless of the versions that are enabled for the agent.

From the Trap Format drop-down menu, select the v1, v2, or v3 option and click Apply.

Setting IP restrictions:

From the IP Restrictions drop-down menu, select the No Restrictions or Trap Destinations Only option and click Apply.

NOTE: When the Trap Destinations Only option is selected, SNMP Manager Get and Set requests are allowed only from the IP address of the defined trap destinations.

Setting the SNMP SysName, SysLocation or SysContact objects:

In the appropriate field, enter the SysName, SysLocation or SysContact objects and click Apply.

Enabling or disabling tower traps:

Click on the Tower Traps link.

On the subsequent Tower Traps page, select or deselect the desired traps and click Apply.

Configuring input feed traps and thresholds:

Click on the Input Feed Traps and Thresholds link.

On the subsequent Input Feed Traps page, select or deselect the desired traps and click Apply.

For Load traps, enter a maximum load value for the infeed in the High Load Threshold field and click Apply.

The default input feed high load threshold is 80% of the input feed maximum load capacity.

Configuring outlet traps:

Click on the Outlet Traps and Thresholds link.

On the subsequent Outlet Traps and Thresholds page, select or deselect the desired traps and click Apply.

Enabling or disabling Environmental Monitor traps:

Click on the Environmental Monitor Traps link.

On the subsequent page, select or deselect the desired traps and click Apply.

Configuring Temperature and Humidity Recovery Delta (Hysteresis):

Click the Sensor Traps and Thresholds link.

The Recovery Delta field allows configuration of the number of degrees of change needed to recover from a temperature alarm. After exceeding the high-temperature threshold, the temperature value must fall below the high-temperature threshold by the number of degrees specified in the Recovery Delta field before the sensor recovers.

For example, if the High Temp value is 80 degrees Fahrenheit, and the Recovery Delta field is 2 degrees Fahrenheit, the sensor will not recover until a temperature value of 78 degrees Fahrenheit is reported.

To configure a temperature recovery delta (hysteresis), in the Recovery Delta field for “Temp”, type a value

(in degrees) and click Apply. Valid range is

0-30 Celsius or 0-54 Fahrenheit.

To configure a humidity recovery delta (hysteresis), in the Recovery Delta field for “Humid”, type a value

(in percent) and click Apply.

Valid range is 0-20%.

NOTE: The default value for the Recovery Delta field is 1 degree Celsius and 2 degrees Fahrenheit.

34  Operations

Intelligent IPM

Installation and Operations Manual

Configuring Temperature Recovery Delta:

Click the Sensor Traps and Thresholds link.

The Recovery Delta field allows configuration of the number of degrees of change needed to recover from a temperature alarm. After exceeding the high-temperature threshold, the temperature value must fall below the high-temperature threshold by the number of degrees specified in the Recovery Delta field before the sensor recovers.

For example, if the High Temp value is 80 degrees Fahrenheit, and the Recovery Delta field is 2 degrees Fahrenheit, the sensor will not recover until a temperature value of 78 degrees Fahrenheit is reported.

To configure a temperature recovery delta, type a value (in degrees) in the Recovery Delta field and click Apply.

NOTE: The acceptable value range for the Recovery Delta field is 0-10 degrees for Celsius and 0-18 degrees for Fahrenheit. The default value for the Recovery Delta field is 1 degree Celsius and 2 degrees Fahrenheit.

LDAP

The LDAP configuration page is used for setup and maintenance of all settings required to enable LDAP support.

Enabling or disabling LDAP support:

Select Enabled or Disabled from the LDAP drop-down menu and click Apply.

Configuring the authentication order:

Select Remote -> Local or Remote Only from the drop-down menu and click Apply.

NOTE: Server Technology recommends not setting the authentication order to Remote Only until LDAP has been configured and tested.

Setting the LDAP server address:

Enter the IP address or hostname in the Primary and/or Secondary Host field and click Apply.

NOTE: Both IPv4 and IPv6 formats are accepted in the Primary/Secondary Host fields.

Changing the LDAP server port:

Enter the port number in the LDAP Port field and click Apply.

Setting the LDAP bind type:

The PDU supports three standard LDAP bind methods:

Simple: Uses unencrypted delivery of username-password over the network to the LDAP server for authentication,

showing user credentials in plain text.

TLS/SSL: (LDAP over TLS/SSL) Uses a trusted authority certificate to provide encryption of LDAP authentication.

MD5: Provides strong protection using 1-way hash encoding that does not transmit the username-password over the

network.

From the Bind Type drop-down menu, select Simple, TLS/SSL, or MD5, and click Apply.

NOTE: If LDAP over TLS/SSL is enabled, MD5 binding is disabled.

Setting the search bind Distinguished Name (DN):

Enter the fully-qualified distinguished name (FQDN) in the Search Bind field and click Apply.

Setting the search bind password for Distinguished Name (DN):

Enter the Search Bind Password in the Search Bind Password field and click Apply.

Setting the user search base Distinguished Name (DN):

Enter the User Search Base DN in the User Search Base DN field and click Apply.

Setting the user search filter:

Enter the User Search Filter in the User Search Filter field and click Apply.

Setting the group membership attribute:

Enter the group membership attribute in the Group Membership Attribute field and click Apply.

Intelligent IPM

Installation and Operations Manual

Operations  35

Enabling or disabling group search:

Select Enabled or Disabled from the Group Search drop-down menu and click Apply.

Setting the group search base Distinguished Name (DN):

The Group Search Base DN indicates where the LDAP group search will start.

Enter the Base DN in the Group Search Base DN field and click Apply.

Setting the user membership attribute name:

The User Membership Attribute is a comma-delimited string of up to two attribute names whose values in the search results are the users that are members of the group. Maximum numbers of characters is 61.

Enter the user membership attribute name(s) in the User Membership Attribute field and click Apply.

NOTE: The user membership option allows the searching of directory entries of groups for a user membership attribute to find the groups for which the user is a member.

Setting the DNS IP address:

For information about how to set the DNS IP address, see the Network section.

Configuring LDAP groups:

Click on the LDAP Groups link at the bottom of the page.

Creating an LDAP group:

Enter a descriptive group name in the LDAP Group Name field. Up to 24 alphanumeric and other typed characters

(ASCII 33 to 126 decimal) are allowed; spaces are not allowed. Press Apply.

Removing an LDAP group:

Click on the Remove link in the Action column for the group to be removed and click OK on the subsequent confirmation window.

Changing an LDAP group’s access privilege level:

Click on the Edit link in the Action column for the associated LDAP Group.

On the subsequent LDAP Group - Edit page, select Admin, User, On-only or View-only from the Access Level dropdown menu and click Apply.

Granting or removing environmental monitoring viewing privileges:

Click on the Edit link in the Action column for the associated LDAP Group.

On the subsequent LDAP Group - Edit page, select Yes or No from the Environmental Monitoring drop-down menu and click Apply.

NOTE: Granting access to environmental monitoring (temperature/humidity/sensors) to a non-admin user also grants that user access to power monitoring (outlets, infeeds, towers – all the environmental data of the PDU).

Adding and deleting outlet access:

Click on the Outlets link in the Access column for the associated LDAP Group.

On the subsequent LDAP Group - Outlets page, select or deselect outlets to be accessed by the LDAP Group and click

Apply.

Adding and deleting outlet group access:

Click on the Groups link in the Access column for the associated LDAP Group.

On the subsequent LDAP Group - Groups page, select or deselect outlet groups to be accessed by the LDAP Group and click Apply.

Adding and deleting serial port access:

Click on the Ports link in the Access column for the associated LDAP Group.

On the subsequent LDAP Group - Ports page, select or deselect ports to be accessed by the LDAP Group and click Apply.

36  Operations

Intelligent IPM

Installation and Operations Manual

TACACS+

The TACACS+ configuration page is used for setup and maintenance of all settings required to enable TACACS+ support.

Enabling or disabling TACACS+ support:

Select Enabled or Disabled from the TACACS+ drop-down menu and click Apply.

Setting the TACACS+ server address:

Enter the IP address or hostname in the Primary and/or Secondary Host field and click Apply.

NOTE: Both IPv4 and IPv6 formats are accepted in the Primary/Secondary Host fields.

Changing the TACACS+ server port:

Enter the port number in the Port field and click Apply.

Configuring the authentication order:

Select Remote > Local or Remote Only from the drop-down menu and click Apply.

For more information about remote authentication order, see the “Setting the authentication order” section.

NOTE: Server Technology recommends not setting the authentication order to Remote Only until TACACS has been fully configured and tested.

Setting the TACACS+ encryption key:

Enter a key and verify the new key the Encryption Key and Verify Encryption Key fields. Press Apply.

For security, key characters are not displayed.

Configuring TACACS+ privilege levels:

Click on the TACACS+ Privilege Levels link at the bottom of the page.

Changing an TACACS+ Privilege Level’s access privilege level:

Click on the Edit link in the Action column for the associated TACACS+ Privilege Level.

On the subsequent TACACS+ Privilege Level - Edit page, select Admin, User, On-only or View-only from the Access

Level drop-down menu and click Apply.

Granting or removing environmental monitoring viewing privileges:

Click on the Edit link in the Action column for the associated TACACS+ privilege level.

On the subsequent TACACS+ Privilege Level - Edit page, select Yes or No from the Environmental Monitoring dropdown menu and click Apply.

NOTE: Granting access to environmental monitoring (temperature/humidity/sensors) to a non-admin user also grants that user access to power monitoring (outlets, infeeds, towers – all the environmental data of the PDU).

Adding and deleting outlet access:

Click on the Outlets link in the Access column for the associated TACACS+ Privilege Level.

On the subsequent LDAP Group - Outlets page, select or deselect outlets to be accessed by the TACACS+ Privilege Level and click Apply.

Adding and deleting outlet group access:

Click on the Groups link in the Access column for the associated TACACS+ Privilege Level.

On the subsequent LDAP Group - Groups page, select or deselect outlet groups to be accessed by the TACACS+ Privilege

Level and click Apply.

Adding and deleting serial port access:

Click on the Ports link in the Access column for the associated TACACS+ Privilege Level.

On the subsequent LDAP Group - Ports page, select or deselect ports to be accessed by the TACACS+ Privilege Level and click Apply.

Intelligent IPM

Installation and Operations Manual

Operations  37

RADIUS

The Remote Authentication Dial-in User Service (RADIUS) configuration allows you to set up and maintain the settings required to enable RADIUS support.

Enabling or disabling RADIUS support:

Select Enabled or Disabled from the RADIUS drop-down menu and click Apply.

Configuring the authentication order:

Select Remote > Local or Remote Only from the drop-down menu and click Apply.

For more information about remote authentication order, see the “Setting the authentication order” section.

NOTE: Server Technology recommends not setting the authentication order to Remote Only until the RADIUS has been fully configured and tested.

Changing the RADIUS server address:

Enter the IP address or hostname in the Primary and/or Secondary Server field and click Apply.

NOTE: Both IPv4 and IPv6 formats are accepted in the Primary/Secondary Host fields.

Setting the RADIUS shared secret:

The shared secret is the RADIUS authentication key.

Enter the shared secret in the Primary and Secondary Shared Secret field. Up to 48 upper and lowercase alphanumeric and other typed characters (ASCII 33 to 126 decimal) and spaces are allowed; control characters are not allowed. Press Apply.

To change the shared secret, check the Change checkbox to clear the Shared Secret field, enter the new shared secret, and click Apply.

Changing the RADIUS server port:

This field specifies the port number used by the RADIUS server for incoming RADIUS authentication requests.

Enter the port number in the Primary and/or Secondary Port field and click Apply.

The valid port number range is 1-65535; default is 1812.

Setting the RADIUS server timeout value:

The Timeout field specifies the time interval (in seconds) to wait for a reply from the RADIUS server before resending an authentication request.

Type the timeout value (in seconds) in the Primary and/or Secondary Timeout field and click Apply.

The valid timeout range is 1-30 seconds; default is 5 seconds.

Setting the number of RADIUS server retries:

The Set RADIUS Retries command specifies the number of times an authentication request is sent to the RADIUS server.

The PDU will attempt authentication with the primary server until the number of retries is reached, then will attempt authentication with the secondary server. If the PDU does not receive a response from these attempts, the authentication request will be rejected.

Setting the number of retries:

Type the number of retries in the Primary and/or Secondary Retries field and click Apply.

The valid retries range is 0-10; default is 2.

38  Operations

Intelligent IPM

Installation and Operations Manual

SMTP/Email

The SMTP/Email page allows the configuration of Simple Mail Transfer Protocol (SMTP) and Email options.

Enabling or disabling Email support:

Select Enabled or Disabled from the Email Notifications drop-down menu and click Apply.

Setting the SMTP server address:

Enter the IP address or hostname in the SMTP Host field and click Apply.

NOTE: Both IPv4 and IPv6 formats are accepted in the Host field.

Changing the SMTP server port:

Enter the port number in the SMTP Port field and click Apply.

Setting the SMTP authentication type:

NOTES:

 SMTP authentication allows the mail client in the PDU to login to the mail server during the process of sending a mail. The mail server may require this login to relay mail to another mail server.

 Supported SMTP authentication types are: None (default, no SMTP authentication); Digest-MD5; CRAM-MD5; Login; and Plain. SMTP authentication occurs with a configured username and password, or you can use the address in the ‘From’ Address field in place of the username.

From the SMTP Authentication drop-down menu, select an authentication method. From the “with” drop-down menu, select “SMTP Username” or “From Address”. Click Apply.

Setting the Email SMTP authentication username:

In the Username field, type the desired Email SMTP username and click Apply. Spaces are not allowed.

Setting the Email SMTP authentication password:

The Set Email SMTP Password command sets the password for SMTP authentication with the username.

In the Password field, type a password of 1-16 alphanumeric and other characters (ASCII 33 to 126 decimal) are allowed; passwords are case sensitive. Click Apply.

To change the password, type over it, check the Change checkbox, and click Apply.

Setting the ‘From’ email address:

Enter the ‘from’ email address in the ‘From’ Address field and click Apply.

Setting the ‘Send To’ email address:

Enter the ‘send to’ email address in the Primary or Secondary ‘Send To’ Address field and click Apply.

If the primary ‘send to’ address fails, the system then attempts to send the email to the secondary ‘send to’ address.

Setting the subject ID:

From the Subject ID drop-down menu, select the default “Sentry3_524640” option or the “Location” option to specify the email subject line. Click Apply.

Enabling or disabling event type notifications:

Check the type of event message to enable, and click Apply. Options are Event Messages, Authentication Messages, power

Messages, and Configuration Messages.

Sending a test email:

After providing information in the Email/SMTP web page, click the Test button to send a test email to the target email destinations.

Intelligent IPM

Installation and Operations Manual

Operations  39

Features

The Features configuration page allows you to activate and maintain the special features purchased from Server

Technology. From this page you can review all activated features and activate new purchased features.

To activate a special feature:

In the Feature Key Value field, enter the activation key provided by Server Technology and click Apply.

NOTE: A restart of the PDU is required after activating new special features.

Tools

The Tools section contains access to rebooting the unit, uploading new firmware as well as resetting the unit to factory defaults.

This section is available to administrative level users only.

Ping

The Ping feature tests the ability of the PDU to contact an IP address for another Ethernet-enabled device. For LDAP support, Ping tests the configuration of the Domain Name Server (DNS) IP address by testing for proper name resolution.

NOTE: Both IPv4 and IPv6 formats are accepted in the Ping Host Name/IP Address field.

Change Password

The Change Password feature allows users to change their own password.

NOTE: An administrator can always assign a new password.

Changing a password:

Enter the current password, enter a new password and verify the new password. Press Apply.

Firmware

The Firmware page allows the uploading of a system firmware (.bin) file. Click Browse to locate the .bin firmware file, and then click Upload. A confirmation message is displayed.

View Log

The View Log feature enables viewing of the internal system log. This features logs all authentication attempts, power actions, configuration changes and other system events. The system memory stores more than 4000 entries in a continuously aging log.

For permanent off-system log storage, the Syslog protocol is supported. For more information about configuration requirements, see the “Logging” section.

NOTE: Only system administrators can view the system log.

Reviewing the system log:

Click on the Previous 100 entries or Next 100 entries link to navigate through the log.

Restart

Performing a warm boot:

Select the Restart from the Action drop-down menu and click Apply.

NOTE: System user/outlet/group configuration or outlet states are NOT changed or reset with this command.

Resetting to factory defaults:

For more information about resetting a PDU to factory defaults from the Web interface, see Appendix A.

Uploading new firmware:

For more information about uploading new firmware from the Web interface, see Appendix B.

Generating a new SSL X.509 certificate:

Select the Restart and generate a new X.509 certificate from the Action drop-down menu and click Apply.

Computing new SSH security keys:

Select the Restart and compute new SSH keys from the Action drop-down menu and click Apply.

40  Operations

Intelligent IPM

Installation and Operations Manual

Command Line Interface

IMPORTANT: The Command Line Interface (CLI) was modified to allow both IPv4 and IPv6 settings.

Logging In

Logging in through Telnet requires directing the Telnet client to the configured IP address of the unit.

Logging in through the Console (RS232) port requires the use of a terminal or terminal emulation software configured to support ANSI or VT100 and a supported data rate (300, 1200, 2400, 4800, 9600, 19200, 38400, 57600, or 115200 BPS) -

8 data bits-no parity-one stop bit and Device Ready output signal (DTR or DSR). The default data rate is 9600.

To log in by RS-232 or Telnet:

1. Press Enter. The following appears, where x.xx is the firmware version:

Sentry Version x.xx

Username:

NOTE: Logging in by Telnet will automatically open a session. It is not necessary to press Enter.

2. At the Username: and Password: prompts, enter a valid username and password. And press Enter.

You are given three attempts to enter a valid username and password combination. If all three fail, the session ends.

NOTE: The default username/password is admn/admn.

When you enter a valid username and password, the command prompt (Switched CDU:) appears. If a location identifier was defined, it will be displayed before the Switched CDU: prompt. For more information, see the “Creating a location description” section.

You can enter commands in any combination of uppercase and lowercase. All command characters must be entered correctly; there are no command abbreviations. A user must have administrative privileges to use the administration commands. The following tables list and briefly describe each command.

Operations Command Summary

Command Description

Connect

Envmon

IStat

List Group

List Groups

Connects to a serial/Pass-Thru port

Displays the status of the integrated Environmental Monitor

Displays the status of the infeeds

Lists all assigned outlets for a group name

Lists all accessible groups for the current user

List Outlets

List Ports

Login

Logout

Off

On

Password

Quit

Reboot

Status

UPSStat

Add Grouptouser

Add Outlettogroup

Add Outlettouser

Add Porttouser

Create Group

Create UPS

Lists all accessible outlets for the current user

Lists all accessible serial/Pass-Thru ports for the current user

Ends the current session and brings up the Username: prompt

Ends a session

Turns one or more outlets off

Turns one or more outlets on

Changes the password for the current user

Ends a session

Reboots one or more outlets

Displays the on/off status of one or more outlets

Displays the status of the associated UPSs

Grants a user access to one or more groups

Adds an outlet to a group name

Grants a user access to one or all outlets

Grants a user access to one or all serial/Pass-Thru ports

Adds a group name

Adds a UPS association

Intelligent IPM

Installation and Operations Manual

Operations  41

Administrative Command Summary

Create User Adds a user account

Delete Groupfromuser

Delete Outletfromgroup

Delete Outletfromuser

Delete Portfromuser

List User

List Users

Remove Group

Remove UPS

Removes access to one or more groups for a user

Deletes an outlet from a group name

Removes access to one or all outlets for a user

Removes access to one or all serial/Pass-Thru ports

Displays all accessible outlets/groups/ports for a user

Displays privilege levels for all users

Deletes a group name

Deletes a UPS association

Remove User

Restart

Set Banner

Set Bluetooth Discover

Set Bluetooth Name

Set Bluetooth Pincode

Set Bluetooth Transpwr

Set DHCP

Deletes a user account

Performs a warm boot

Set the pre-login banner text

Determines the current status of the pushbutton on the Bluetooth module

Configures the name of the discovered Bluetooth module on the Android device

Pin code value for legacy Bluetooth modules that require a pin to pair the module

Designated transmission power (dbm) for the Bluetooth module.

Enables or disables DHCP support

Set DHCP Boot Delay Enables or disables a 100-second boot delay between PDU and DHCP server

Set DHCP Static Address Fallback Enables or disables DHCP fallback to a static IP address

Set DNS

Set EnergyWise

Set EnergyWise Domain

Set EnergyWise Port

Set EnergyWise Refresh

Set EnergyWise Secret

Set Envmon Name

Set Envmon THS Name

Set FTP Autoupdate Day

Set FTP Autoupdate Hour

Set FTP Autoupdate

Set FTP Directory

Set FTP Filename

Set FTP Host

Set FTP Password

Set FTP Test

Set FTP Server

Set FTP Username

Set Gateway

Set HTTP

Set HTTP Port

Set Infeed Loadmax

Set Infeed Name

Set Infeed Voltage

Set IP Address

Set LDAP UseTLS

Sets the IP address of the Domain Name server

Enables or disables the Cisco EnergyWise network

Sets the Cisco EnergyWise domain name

Sets the Cisco EnergyWise port number

Rate (in seconds) at which information is pushed to the EnergyWise manager

Sets the Cisco EnergyWise secret

Specifies a descriptive field fro the integrated Environmental Monitor

Specifies a descriptive field for a temperature-humidity sensor

Sets the automatic FTP update day

Sets the automatic FTP update hour

Enables or disables automatic FTP update support

Specifies the directory for the file to be uploaded

Specifies the file to be uploaded via FTP

Sets the FTP Host IP address or hostname

Sets the password for the FTP Host

Validates that the PDU can login to the FTP server and verify/download the firmware file

Enables or disables the FTP server

Sets the username for the FTP Host

Sets the gateway of the PDU

Enables or disables HTTP access and sets the HTTP target port.

Specifies the target port for HTTP access

Specifies the maximum load capacity for the infeed

Specifies a descriptive field for the infeed

Specifies the nominal input voltage for the infeed

Sets the IP address of the PDU

Enables or disables LDAP over TLS/SSL support

42  Operations

Intelligent IPM

Installation and Operations Manual

Administrative Command Summary (continued…)

Set Location Specifies a descriptive field for the Web control screen and login banner

Set Net

Set Option Button

Set Option Coldboot Alert

Set Option Display

Set Option More

Set Option Outlet Sequence

Set Option Prompt

Set Option StrongPasswords

Set Option Tempscale

Set Option CLI Timeout

Set Option Web Timeout

Set Outlet Locked

Set Outlet Name

Set Outlet PostOnDelay

Set Outlet RebootDelay

Set Outlet SeqInterval

Set Outlet Wakeup

Set Port CLI

Set Port DSR Check

Set Port Name

Set Port SCP

Set Port SCP Emulate

Set Port Speed

Set Port Timeout

Set Port RFTag

Set SCPAuth

Set SCPAuth User

Set SNMP IP Restrict

Set SNTP

Set SNTP DST

Set SNTP DST End

Set SNTP DST Start

Set SNTP GMTOffset

Set SPM

Set SPM Reset Password

Set Subnet

Set System Area

Set System Area Unit

Set System Balance

Set System Balance Alert

Set System PF

Set Telnet Port

Set Telnet

Set Tower 3Phase

Set Tower Model

Set Tower Name

Determines the acquisition method for the protocol stack and IPv4/IPv6 addresses

Enables or disables the external configuration reset button

Enables or disables the Coldboot Alert feature using a serial protocol

Sets the LED orientation for external Current displays

Enables or disables the ‘more’ prompt

Configures outlet power-on sequence order as normal or reversed

Configures a custom CLI prompt

Enables or disables strong password requirements

Sets the Environmental Monitor temperature scale

Sets the Command Line Interface (CLI) session timeout period

Sets the web session (Web Interface) timeout period

Locks or unlocks a single outlet (no control) in its current state

Specifies a descriptive field for a device attached to an outlet

Sets the Post-On delay for an outlet

Sets the reboot delay for all outlets

Sets the sequencing interval for all outlets

Sets the wakeup state for an outlet

Enables or disables availability of the Command Line Interface (CLI)

Sets the DSR active signal checking for a serial/Pass-Thru port

Specifies a descriptive field for a serial/Pass-Thru port

Enables or disables Serial Command Protocol (SCP) functions

Notifies the Serial Command Protocol (SCP) of an MRV device on a specific serial port

Set the connection speed for all serial/Pass-Thru ports

Sets the inactivity timeout period for a serial port before closing the pass-thru session

Enables or disables RF Code sensor tags for the wireless monitoring solution

Enables or disables Serial Command Protocol (SCP) authentication

Sets the username and password for Serial Command Protocol (SCP) authentication

Allows SNMP Get and Set requests only from defined trap destinations

Sets the IP address or hostname of the SNTP servers

Enables or disables Daylight Saving Time (DST)

Specifies the settings for DST day/time end parameters

Specifies the settings for DST day/time start parameters

Sets the local GMT offset applied to the SNTP date/time

Enables/disables secure access of Sentry Power Manager (SPM)

Resets the SPM password on the PDU to its internal default password

Sets the subnet mask of the PDU

Specifies to total system area for the system

Specifies the system area (footprint) unit of measure

Sets the percentage as load out-of-balance threshold for 3-phase systems

Enables/disables alert when load out-of-balance threshold is reached for 3-phase systems

Sets the power factor used in the total system power calculation

Sets the Telnet server port number

Enables or disables Telnet access

Specifies the AC voltage type for the tower

Specifies the model number for the tower

Specifies a descriptive field for the tower

Intelligent IPM

Installation and Operations Manual

Operations  43

Administrative Command Summary (continued…)

Set Tower ProdSN Specifies the serial number for the tower

Set Tower

Set UPS AddInfeed

Set UPS DelInfeed

Set UPS GETComm

Set UPS Host

Set UPS Port

Set UPS Type

Set UPS VPoll

Set User Access

Set User Envmon

Set User Password

Show EnergyWise

Show FTP

Show Infeeds

Show Network

Show Options

Show Outlets

Show Ports

Show SNTP

Show System

Show System Status

Show Towers

Show UPS

Version

Specifies the AC or DC voltage type for the tower

Adds an infeed association to a UPS

Deletes an infeed association from a UPS

Sets the UPS ‘get’ community string

Sets the UPS Host IP address or hostname

Specifies the target port for a UPS

Sets the UPS type

Enables or disables UPS voltage polling

Sets the access level for a user

Grants or removes user access to environmental monitoring

Changes the password for a user

Displays Cisco EnergyWise network configuration information

Displays FTP configuration information

Displays infeed configuration information

Displays network configuration information for all IPv4 and IPv6 settings

Displays system option information

Displays configuration information for all outlets

Displays serial/Pass-Thru port configuration information

Displays SNTP configuration information

Displays system configuration information

Displays system power and tower configuration information

Displays tower configuration information

Displays UPS configuration information

Displays the firmware version

To display the names of commands that you can execute:

At the command prompt, press Enter. A list of valid commands for the current user appears.

44  Operations

Intelligent IPM

Installation and Operations Manual

Operations Commands

Operations commands manage outlet states, provide information about the PDU environment and control session operations.

Turning outlets on:

The On command turns on one or more outlets. When the command completes, a display indicating all outlets affected and their current states will be displayed.

To turn outlets on:

At the Sentry: prompt, type on, followed by an outlet name, and press Enter, or

Type on, followed by a group name, and press Enter, or

Type on all and press Enter.

Examples

The following command turns the second outlet on, using the outlet’s absolute name:

Sentry: on .a2<Enter>

The following command turns on all the outlets in the group named ServerGroup_1:

Sentry: on ServerGroup_1<Enter>

Turning outlets off:

The Off command turns off one or more outlets. When the command completes, a display indicating all outlets affected and their current states will be displayed.

To turn outlets off:

At the Sentry: prompt, type off, followed by an outlet name, and press Enter, or

Type off, followed by a group name, and press Enter, or

Type off all and press Enter

Examples

The following command turns off the outlet named FileServer_1:

Sentry: off FileServer_1<Enter>

The following command turns off all outlets:

Sentry: off all<Enter>

Rebooting outlets:

The Reboot command reboots one or more outlets. This operation turns the outlet(s) off, delays for a user configurable period and then turns the outlet(s) on. When the command completes, a display indicating all outlets affected and their current states will be displayed.

NOTE: It is necessary to reissue the Status command to verify that the outlets have rebooted.

To reboot one or more outlets:

At the Sentry: prompt, type reboot, followed by an outlet name, and press Enter, or

Type reboot, followed by a group name, and press Enter, or

Type reboot all and press Enter.

Example

The following command reboots all the outlets in the group named ServerGroup_1:

Sentry: reboot ServerGroup_1<Enter>

Intelligent IPM

Installation and Operations Manual

Operations  45

Displaying outlet status:

The Status command displays the on/off status of one or more outlets. The command displays the status of only those outlets for which the current username has power control access.

This display includes the outlet absolute and descriptive names, the Outlet State reported to the PDU by the outlet and the current Control State being applied by the PDU. If you do not specify any parameter with this command, the status of all accessible outlets is displayed.

NOTE: If the user has access to more than 16 total outlets, the Status command will display the first 16 outlets with a prompt to view the remaining outlets.

To display on/off status of one or more outlets:

At the Sentry: prompt, type status, followed by an outlet name, and press Enter, or

Type status, followed by a group name, and press Enter, or

Type status and press Enter.

Examples

The following command displays the on/off status of the outlet named FileServer_1:

Sentry: status WebServer_1<Enter>

Outlet Outlet Outlet Control

ID Name State State

.A2 WebServer_1 On On

The following command displays the on/off status of all accessible outlets:

Sentry: status<Enter>

Outlet Outlet Outlet Control

ID Name State State

.A1 DataServer_1 On On

.A2 WebServer_1 On On

The following command displays the on/off status for outlets in the group ServerGroup_1:

Sentry: status ServerGroup_1<Enter>

Group: ServerGroup_1

Outlet Outlet Outlet Control

ID Name State State

.A1 DataServer_1 On On

.A2 WebServer_1 On On

Displaying accessible outlets:

The List Outlets command displays accessible outlets for the current user. The display includes the absolute and descriptive name of all outlets assigned to the current user.

To display accessible outlets:

At the Sentry: prompt, type list outlets and press Enter.

Example

The follow command displays all accessible outlets for the current user:

Sentry: list outlets<Enter>

Outlet Outlet

ID Name

.A1 DataServer_1

.A2 WebServer_1

46  Operations

Intelligent IPM

Installation and Operations Manual

Displaying accessible groups:

The List Groups command displays accessible groups for the current user.

To display accessible groups:

At the Sentry: prompt, type list groups and press Enter.

Example

The follow command displays all accessible groups for the current user:

Sentry: list groups<Enter>

Groups:

ServerGroup_1

RouterGroup_1

Displaying outlets assigned to a group:

The List Group command displays outlets assigned to the specified group name.

To display outlets assigned to a group:

At the Sentry: prompt, type list group, followed by the group name and press Enter.

Example

The follow command displays the outlets assigned to the group ServerGroup_1:

Sentry: list group ServerGroup_1<Enter>

Group: ServerGroup_1

Outlet Outlet

ID Name

.A1 DataServer_1

.A2 WebServer_1

Displaying accessible serial ports:

The List Ports command displays accessible serial ports for the current user.

To display accessible serial ports:

At the Sentry: prompt, type list ports and press Enter.

Example

The follow command displays all accessible serial ports for the current user:

Sentry: list ports<Enter>

Port Port

ID Name

Console Console

Displaying infeed status:

The Istat command displays the status of one or more infeeds.

This display includes the infeed absolute and descriptive names and the Input Status.

To display status of one or more infeeds:

Type istat and press Enter.

Example

The following command displays the infeed status:

Sentry: istat

Input Input Input

Feed ID Feed Name Status

.AA HQ_1_Infeed_A On

Intelligent IPM

Installation and Operations Manual

Operations  47

Connecting to a serial device:

The Connect command allows Pass-Thru serial connection to devices attached to the standard serial port (Console).

To connect to a serial device:

At the Switched CDU: prompt, type connect console and press Enter.

NOTE: The Connect command will not immediately disconnect when issued from an SSH session that was established while another Telnet or

SSH session already existed.

To disconnect from a serial device:

Type !*break and press Enter.

Displaying the status of the environmental monitor:

The Envmon command displays the status of the integrated Environmental Monitor.

By default, only administrative user accounts are allowed access to the Envmon command. An administrator can user the

Set User Envmon command to enable and disable access for other user accounts.

To display the status of the Environmental Monitor:

At the Sentry: prompt, type envmon and press Enter.

Example

The following command displays the status of the Environmental Monitor.

Sentry: envmon<Enter>

Environmental Monitor .A

Name: Florida_HQ_1 Status: Normal

Temperature/Humidity Sensors

ID Name Temperature Humidity

.A1 Temp_Humid_Sensor_A1 Not Found Not Found

.A2 T/H2_Florida_HQ_1 23.5 Deg. C 22 % RH

Changing a password:

The Password command changes the current user’s password. For security, when you type a password, the characters are not displayed on the screen.

To change a password:

At the Sentry: prompt, type password and press Enter.

At the Enter Current Password: prompt, type the current password and press Enter.

At the Enter New Password: prompt, type the new password and press Enter. Passwords can contain 1-16 characters.

At the Verify Password: prompt, retype the new password and press Enter.

Starting a new session:

The Login command activates the Username: prompt. The current session ends, allowing a user to log in and start a new session under a different username.

To start a new session:

At the Sentry: prompt, type login and press Enter. The Username: prompt appears.

48  Operations

Intelligent IPM

Installation and Operations Manual

Ending a session:

The Quit or Logout commands ends a session. A session ends automatically when no activity is detected for five minutes, or upon loss of connection.

To end a session:

At the Sentry: prompt, type quit and press Enter, or

Type logout and press Enter.

Displaying UPS status:

The UPSStat command displays the status of one or more UPS devices associated with the PDU.

The display includes UPS index number, type, line/battery status, and reported voltage.

NOTE: Access to this command requires enabling user privileges for environmental monitoring using the Set User Envmon command.

Administration Commands

Administration commands can only be issued by a user with administrative privileges, such as the predefined Admn user or another user who has been granted administrative privileges with the Set User Admnpriv command.

User Administration

Creating a user account:

The Create User command creates a user account with the specified username and password.

To create a user account:

At the Sentry: prompt, type create user, optionally followed by a 1-16 character username (Spaces are not allowed, and usernames are not case sensitive). Press Enter.

At the Password: prompt, type a password of 1-16 alphanumeric and other typed characters - (ASCII 32 to 126 decimal) are allowed; passwords are case sensitive. Press Enter.

At the Verify Password: prompt, retype the password. Press Enter.

Example

The following command creates the user account JaneDoe:

Sentry: create user JaneDoe<Enter>

Password: <Enter>

Verify New Password: <Enter>

For security, password characters are not displayed.

Removing a user account:

The Remove User command removes a user account.

NOTE: You can remove the default user account admn only if you have already granted administrative access to another user account using the

Set User Admnpriv command.

To remove a user account:

At the Sentry: prompt, type remove user, optionally followed by a username. Press Enter.

Intelligent IPM

Installation and Operations Manual

Operations  49

Changing a password:

The Set User Password command changes a user’s password. For security, when you type a password, the characters are not displayed on the screen.

To change a password:

At the Sentry: prompt, type set user password, followed by a username and press Enter.

At the Password: prompt, type the new password and press Enter. Passwords can contain 1-16 characters.

At the Verify Password: prompt, retype the new password and press Enter.

Example

The following command changes the password for the user JohnDoe:

Sentry: set user password johndoe<Enter>

Password: <Enter>

Verify Password: <Enter>

For security, password characters are not displayed.

Setting user access level privileges:

The Set User Access command sets the access level privileges for a user. The PDU has the following defined access privilege levels; Admin, Power User, User, Reboot-Only, On-Only and View-Only.

The administrator can also grant administrative privileges to other user accounts allowing the PDU to have more than one administrative-level user.

NOTE: You cannot remove administrative privileges from the Admn user unless another user has already been given administrative access level privileges created.

To set the access level privilege for a user:

At the Sentry: prompt, type set user access, followed by admin, poweruser, user, rebootonly, ononly or viewonly, optionally followed by a username and press Enter.

Examples

The following command sets the user access level for JohnDoe to Admin:

Sentry: set user access admin johndoe<Enter>

The following command sets the user access level for JaneDoe to User:

Sentry: set user access user janedoe<Enter>

Granting and removing environmental monitoring viewing privileges:

The Set User Envmon command grants or removes Environmental Monitoring viewing privileges to/from a user.

To grant or remove environmental monitoring viewing privileges for a user:

At the Sentry: prompt, type set user envmon followed by on or off, optionally followed by a username and press Enter.

Example

The following command grants input load privileges to the user JohnDoe:

Sentry: set user envmon on johndoe<Enter>

50  Operations

Intelligent IPM

Installation and Operations Manual

Displaying user access level:

The List Users command displays all defined users with their access level.

To display user access privilege levels:

At the Sentry: prompt, type list users and press Enter.

Example

The following command displays all users with their access privilege level:

Sentry: list users<Enter>

User Privilege Environmental

Name Level Monitoring

JOHNDOE Admin Allowed

JILLDOE Power-User Allowed

JANEDOE User Allowed

JAKEDOE Reboot-Only Not Allowed

JOSEYDOE On-Only Not Allowed

JOEDOE View-Only Not Allowed

Adding outlet access to a user:

The Add OutletToUser command grants a user access to one or all outlets. To grant access for more than one outlet, but not all outlets, you must use multiple Add OutletToUser commands.

To grant outlet access to a user:

At the Sentry: prompt, type add outlettouser, optionally followed by an outlet name and a username. Press Enter, or

Type add outlettouser all, followed by a username and press Enter.

Examples

The following commands grant the user JaneDoe access to outlets A1 and Webserver_1:

Sentry:add outlettouser .a1 janedoe<Enter>

Sentry:add outlettouser WebServer_1 janedoe<Enter>

Deleting outlet access for a user:

The Delete OutletFromUser command removes a user’s access to one or all outlets. You cannot remove access to any outlet for an administrative level user.

To delete outlet access for a user:

At the Sentry: prompt, type delete outletfromuser, optionally followed by an outlet name and a username. Press Enter, or

Type delete outletfromuser all, followed by a username and press Enter.

Adding group access to a user:

The Add GroupToUser command grants a user access to a group. To grant access for more than one group, you must use multiple Add GroupToUser commands.

To grant group access to a user:

At the Sentry: prompt, type add grouptouser, optionally followed by a group name and a username. Press Enter.

Examples

The following commands grants to user JaneDoe access to the groups ServerGroup_1 and ServerGroup_2:

Sentry:add GroupToUser ServerGroup_1 janedoe<Enter>

Sentry:add GroupToUser ServerGroup_2 janedoe<Enter>

Deleting group access for a user:

The Delete GroupFromUser command removes a user’s access to a group. You cannot remove access to any group for an administrative level user.

To delete group access for a user:

At the Sentry: prompt, type delete GroupFromUser, optionally followed by a group name and a username. Press Enter.

Intelligent IPM

Installation and Operations Manual

Operations  51

Adding serial port access to a user:

The Add PortToUser command grants a user access to the serial port.

To grant serial port access to a user:

At the Sentry: prompt, type add porttouser console and a username. Press Enter.

Deleting serial port access for a user:

The Delete PortFromUser command removes a user’s access to the serial port. You cannot remove access to the serial port for an administrative level user.

To delete serial port access for a user:

At the Sentry: prompt, type delete portfromuser console and a username. Press Enter.

Displaying user outlet, group and serial port access:

The List User command displays all accessible outlets, groups and serial ports for a user.

To display user outlet, group and serial port access:

At the Sentry: prompt, type list user, optionally followed by a username. Press Enter.

Example

The following command displays information about the user JaneDoe:

Sentry: list user janedoe<Enter>

Username: JANEDOE

Outlet Outlet

ID Name

.A1 DataServer_1

.A2 WebServer_1

Groups:

ServerGroup_1

ServerGroup_2

More (Y/es N/o): Y

Ports:

Port Port

ID Name

Console Console

JaneDoe can access the following outlets, groups and serial ports: outlet A1 which has a descriptive name of

DataServer_1, outlet A2 which has a descriptive name of WebServer_1, group ServerGroup_1 group ServerGroup_2, and

Console serial port.

52  Operations

Intelligent IPM

Installation and Operations Manual

Outlet Administration

Setting the sequencing interval:

The Set Outlet SeqInterval commands sets the power on sequencing interval for all outlets.

To set the sequencing interval:

At the Sentry: prompt, type set outlet seqinterval all, followed by a value from 0 to 15 (in seconds) and press Enter.

Setting the reboot delay:

The Set Outlet RebootDelay commands sets the reboot delay for all outlets.

To set the sequencing interval:

At the Sentry: prompt, type set outlet rebootdelay all, followed by a value from 5 to 60 (in seconds) and press Enter.

Creating a descriptive outlet name:

The Set Outlet Name command assigns a descriptive name to an outlet. You can use this name in commands that require an outlet name as an alternative to using the outlet’s absolute name.

To create an outlet name:

At the Sentry: prompt, type set outlet name followed by the absolute outlet name, then a descriptive name of up to 24 alphanumeric and other typed characters - (ASCII 33 to 126 decimal) are allowed; spaces are not allowed; outlet names are not case sensitive. Press Enter.

Example

The following command adds the descriptive name DataServer_1 to outlet .a1:

Sentry: set outlet name .a1 DataServer_1<Enter>

Setting the outlet wakeup state:

The Set Outlet Wakeup command set the default wakeup state for that outlet. In the event of a system-wide power loss, this state will be applied to the outlet when power is restored.

The wakeup state can be set to On, Off or Last. Upon restoration of system power; If set to On, the PDU will apply power to that outlet. If set to Off, the PDU will not apply power to that outlet. If set to Last, the PDU will apply the last known power state.

To set the wakeup state:

At the Sentry: prompt, type set outlet wakeup, followed by on, off or last and the outlet name. Press Enter.

Example

The following command sets the wakeup state for outlet .a1 to off:

Sentry: set outlet wakeup off .a1<Enter>

Setting the outlet post-on delay:

The Set Outlet PostOnDelay command is used set the Post-On delay for an outlet. This feature allows the administrator to manage boot dependencies during power-on sequencing or group commands by delaying the sequencing of subsequent outlets after an outlet has been powered on.

NOTE: This delay is applied in addition to the general sequencing interval.

To set the outlet post-on delay

At the Sentry: prompt, type set outlet postondelay, followed by a value from 0 to 900 (in seconds) and press Enter.

Example

The following command set the Post-On delay for outlet .a2 to 90 seconds:

Sentry: set outlet postondelay .a2 90<Enter>

Intelligent IPM

Installation and Operations Manual

Operations  53

Displaying outlet information:

The Show Outlets command displays information about all outlets. This information includes:

 Sequencing and reboot timer values

 Descriptive outlet name, if applicable

 Outlet wakeup state and Post-On settings

To display outlet information:

At the Sentry: prompt, type show outlets and press Enter.

Example

The following command displays all outlet information:

Sentry: show outlets<Enter>

Outlet Outlet Wakeup Post-On

ID Name State Delay (seconds)

.A1 TowerA_Outlet1 Off 0

.A2 TowerA_Outlet2 On 90

More (Y/es N/o):

Outlet Options:

Sequence Interval: 2 seconds

Reboot Delay: 15 seconds

54  Operations

Intelligent IPM

Installation and Operations Manual

Group Administration

Creating a group name:

The Create Group command creates a new group name.

To create a group name:

At the Sentry: prompt, type create group optionally followed by a descriptive name of up to 24 alphanumeric and other typed characters - (ASCII 33 to 126 decimal) are allowed; spaces are not allowed; group names are not case sensitive. Press

Enter.

Example

The following command creates group name ServerGroup_1:

Sentry: create group ServerGroup_1<Enter>

Removing a group name:

The Remove Group command removes a group name.

To remove a group name:

At the Sentry: prompt, type remove group, optionally followed by a username. Press Enter.

Example

The following command removes group name ServerGroup_1:

Sentry: remove group ServerGroup_1<Enter>

Adding an outlet to a group:

The Add OutletToGroup command adds an outlet to a group. To add more than one outlet, but not all outlets, you must use multiple Add OutletToGroup commands.

To add an outlet to a group:

At the Sentry: prompt, type add outlettogroup, optionally followed by an outlet name and group name. Press Enter, or

Type add OutletToGroup, followed by all and the group name. Press Enter.

Examples

The following commands uses absolute outlet names to add outlets A1 and A2 to group name ServerGroup_1:

Sentry:add OutletToGroup .a1 ServerGroup_1<Enter>

Sentry:add OutletToGroup .a2 ServerGroup_1<Enter>

The following commands uses the outlets’ descriptive names to add outlets DataServer_1 and WebServer_1 to group name

ServerGroup_1:

Sentry:add OutletToGroup DataServer_1 ServerGroup_1<Enter>

Sentry:add OutletToGroup WebServer_1 ServerGroup_1<Enter>

The following command add all outlets to group name ServerGroup_1:

Sentry: add OutletToGroup<Enter>

Outletname: all<Enter>

Groupname: ServerGroup_1<Enter>

Deleting an outlet from a group:

The Delete OutletFromGroup command deletes an outlet from a group. To delete more than one outlet, but not all outlets, you must use multiple Delete OutletToGroup commands.

To delete an outlet from a group:

At the Sentry: prompt, type delete outletfromgroup, optionally followed by an outlet name and a group name. Press

Enter, or

Type delete outletfromgroup, followed by all then the group name. Press Enter.

Intelligent IPM

Installation and Operations Manual

Operations  55

Environmental Monitor Administration

Creating a descriptive Environmental Monitor name:

The Set Envmon Name command assigns a descriptive name to the integrated Environmental Monitor. This descriptive name is displayed when the Evnmon command is issued.

To create an Environmental Monitor name:

At the Sentry: prompt, type set envmon name followed by the absolute Environmental Monitor name, then a descriptive name of up to 24 alphanumeric and other typed characters - (ASCII 33 to 126 decimal) are allowed; spaces are not allowed. Press Enter.

Example

The following command adds the descriptive name Florida_HQ_1to the Environmental Monitor:

Sentry: set envmon name .a Florida_HQ_1<Enter>

Creating a descriptive temperature/humidity sensor name:

The Set Envmon THS Name command assigns a descriptive name to a temperature/humidity sensor. This descriptive name is displayed when the Evnmon command is issued.

To create an temperature/humidity sensor name:

At the Sentry: prompt, type set envmon ths name followed by the absolute name of the temperature/humidity sensor, then a descriptive name of up to 24 alphanumeric and other typed characters - (ASCII 33 to 126 decimal) are allowed; spaces are not allowed. Press Enter.

Example

The following command adds the descriptive name T/H2_Florida_HQ_1 to the second temperature/humidity sensor:

Sentry: set envmon ths name .a2 T/H2_Florida_HQ_1<Enter>

Serial Port Administration

Creating a descriptive serial port name:

The Set Port Name command assigns a descriptive name to a serial port. You can use this name in commands that require a port name as an alternative to using the port’s absolute name.

To create an port name:

At the Sentry: prompt, type set port name followed by the absolute outlet name, then a descriptive name of up to 24 alphanumeric and other typed characters - (ASCII 33 to 126 decimal) are allowed; spaces are not allowed; port names are not case sensitive. Press Enter.

Example

The following command adds the descriptive name Rack1 to Console port:

Sentry: set port name console Rack1<Enter>

Setting the serial ports data-rate:

The Set Port Speed command sets the default data-rate for the serial port.

Valid data-rates are 1200, 2400, 4800, 9600, 19200, 38400, 57600 and 115200.

To set the serial port data-rate:

At the Sentry: prompt, type set port speed, follow by the data-rate and press Enter.

Example

The following command sets the serial ports data-rate to 38400 BPS:

Sentry: set port speed 38400<Enter>

Enabling or disabling active signal checking for serial connections:

The Set Port DSR Check command enables or disables active signal checking for serial connections to devices attached to any of the available serial ports.

To enable or disable active signal checking for serial connections:

At the Sentry: prompt, type set port dsrcheck console, on or off, and press Enter.

56  Operations

Intelligent IPM

Installation and Operations Manual

Setting the serial port timeout value:

The Set Port Timeout command sets the serial port inactivity timeout period. The timeout period defines the maximum period of inactivity before automatically closing the Pass-Thru session.

The valid range for the timeout is 0 to 60 (in minutes). The default timeout is 5 minutes. The command can be used to set individual ports by ID or name.

NOTES:

 Setting the timeout value to “0” disables the timer.

 Only a numeric value is accepted.

To set the serial port timeout value for an individual port:

At the Switched CDU: prompt, type set port timeout, followed by the port ID or name, followed by a timeout value from

0 to 60 (in minutes), and press Enter.

Configuring the Bluetooth™ options:

If the PDU has been equipped for the mobile monitoring solution using Bluetooth

® technology, several Bluetooth parameters will be available for editing on the Serial Ports configuration page.

To set the Bluetooth™ module name:

The Bluetooth™ module name displays in the list of discovered modules on the Android device. The default is “ST Eye”, and the module name cannot be blank.

At the Switched CDU: prompt, type set bluetooth name, followed by 1-31 characters of a descriptive name for the module, and press Enter.

To set the Bluetooth™ discoverability:

Three discoverability settings determine the current status of the pushbutton on the Bluetooth module:

 Always - The Bluetooth module is discoverable, even without pressing the pushbutton.

 Limited (Default) - The pushbutton on the Bluetooth module must be pressed to make the module discoverable for 60-seconds.

 Never - The Bluetooth module is never in discoverable mode.

At the Switched CDU: prompt, type set bluetooth discover, followed by always, limited, or never, and press Enter.

To set the Bluetooth™ pin code:

The pin code is available for legacy Bluetooth modules that require a pin to pair the module. Although not used in current

Bluetooth modules, the pin code is supported if needed. The default is 9611.

At the Switched CDU: prompt, type set bluetooth pincode, followed by 4-digits from 0000 to 9999, and press Enter.

To set the Bluetooth™ transmission power:

This setting is the designated transmission power (dbm) for the Bluetooth module. Note that lowering the transmission power reduces the effective range of the module. Default is 0

At the Switched CDU: prompt, type set bluetooth transpwr, followed by a value from -6 to 4 (dbm), and press Enter.

Intelligent IPM

Installation and Operations Manual

Operations  57

Displaying serial port information:

The Show Ports command displays information about all serial ports. This information includes:

 Serial port data rate

 Descriptive port name, if applicable

 DSR signal checking settings

 Bluetooth™ parameter settings settings, if applicable

To display serial port information:

At the Sentry: prompt, type show ports and press Enter.

Example

The following command displays all serial port information:

Switched CDU: show ports<Enter>

Serial Port Configuration

Port ID: Console

DSR Check: ON

Port Name: CONSOLE

CLI: Enabled SCP: Disabled RFTAG: Enabled

Data Rate: 9600 Connection Timeout: 5 minute<s>

Port ID: Aux

DSR Check: ON

Port Name: AUX

CLI: Enabled SCP: Enabled

Data Rate: 115200 Connection Timeout: 5 minute<s>

Bluetooth Settings:

Name: ST Eye – 10.1.2.77

Discoverability: LIMITED

Pin code: 9611

Transmission pwr: 0 <dbm>

System Administration

Creating a pre-login banner:

The Set Banner command specifies text that appears prior to the login authentication. This feature allows administrators to configure a message up to 2069 characters for display of legal, disclaimer or other text as required by application. If left blank, the user will be taken directly to the login prompt.

NOTES:

For SSH sessions only:

 The “keyboard-interactive” authentication method must be used for the banner to display.

 Banner length is truncated to 1500 bytes in SSH packets to avoid failure of SSH connection when configured with a long login banner.

To create a pre-login banner:

At the Switched CDU: prompt, type set banner and press Enter. Type the desired pre-login banner text and when finished type Ctrl-z.

Setting the system area:

The Set System Area command is used to set the total area for the system. This value is used for total system power calculations.

To set the system area:

At the Switched CDU: prompt, type set system area, followed by the system area (in square feet) and press Enter.

Example

The following command sets the total system area to 6.3 square feet:

Switched CDU: set system area 6.3<Enter>

Setting the system area unit of measure:

The Set System Area Unit command sets the value for the system area footprint in either square meters or square feet.

The default unit of area is a square meter.

To set the system area unit of measure:

At the Switched CDU: prompt, type set system areaunit, followed by squaremeter or squarefoot, and press Enter.

58  Operations

Intelligent IPM

Installation and Operations Manual

Setting the power factor:

The Set System PF command sets the power factor used in the total system power calculation. The valid range is .50 to

1.00.

To set the power factor:

At the Switched CDU: prompt type set system pf, followed by the power factor, and press Enter.

Setting the 3-phase load out-of-balance threshold:

The Set System Balance command determines when the current on the lines of a 3-phase system are out-of-balance between the three phases of power.

To set the 3-phase load out-of-balance threshold:

At the Switched CDU: prompt, type set system balance, followed by the load out-of-balance threshold (in percent), and press Enter.

Example:

The following command sets the 3-phase load out-of-balance threshold to 20%.

Switched CDU: set system balance 20<Enter>

Setting the 3-phase load out-of-balance alert:

The Set System Balance Alert command enables or disables the sending of an alert when the current on the lines of a 3phase system are past a pre-set threshold (percentage) and are out-of-balance between the three phases of power.

At the Switched CDU: prompt, type set system balancealert, followed by enabled or disabled, and press Enter.

Example:

The following command enables the load out-of-balance alert:

Switched CDU: set system balancealert enabled<Enter>

NOTES:

When a device with 3-phase input voltage is out-of-balance, efficiency is reduced and the unit is prevented from reaching maximum

capacity. When an alert for the out-of-balance condition is received (if the alerting feature is enabled), it may be necessary to adjust

distribution of the loads.

For 3-phase systems, if the Out-of-Balance Alerting feature is enabled, and the system goes into a load out-of-balance condition, the

System Status command will display the alert “3ph Out-of-Balance” in the Tower Status section, unless there is a higher priority tower

error state to report.

Creating a location description:

The Set Location command specifies text that appears in the Web control screen’s Location field. The text is also appended to a Welcome to banner that appears when a user successfully logs in serially or through a Telnet session.

If you do not issue this command, or if you issue this command without specifying any text, the control screen’s Location field will be blank and no Welcome to banner will be displayed.

To create a location description:

At the Sentry: prompt, type set location followed by a descriptive name of up to 24 alphanumeric and other typed characters - (ASCII 33 to 126 decimal) are allowed; spaces are allowed. Press Enter.

Omitting any characters after typing ‘set location’ deletes any previously specified text.

Examples

The following command specifies Florida HQ as the descriptive location for the control screen and the login banner:

Sentry: set location Florida HQ<Enter>

The following command deletes any previously specified location description:

Sentry: set location<Enter>

In this case, the control screen’s Location field is blank, and no welcome banner is displayed after a successful login.

Intelligent IPM

Installation and Operations Manual

Operations  59

Feature Administration

Displaying activated special features:

The Show Features command displays all activated special features for the device.

To display activated special features:

At the Switched CDU: prompt, type show features and press Enter.

Example

The following command displays all activated special features:

Switched CDU: show features<Enter>

Activated Features:

Smart Load Shedding

NOTE: A restart of the IPM is required after activating new special features.

Enabling or disabling strong passwords:

The Set Option Strong Password command is used to enable or disable the requirements for strong passwords. When enabled, all new passwords must be a minimum of 8 characters in length with at least one uppercase letter, one lowercase letter, one number and one special character.

To enable or disable strong passwords:

At the Sentry: prompt, type set option strong password, followed by enabled or disabled and press Enter.

Displaying system power status:

The System Status command displays system power and tower information.

To display system power status:

At the Switched CDU: prompt, type sysstat and press Enter.

Example

Switched CDU: sysstat

System Power Status

Total Power Consumption: 170 Watts

Area <Footprint>: 100.0 Square Meters

Watts Per Area Unit: 2 Watts Per Square Meter

Tower Status

Tower Tower Tower

ID Name Status

.A TowerA Normal

.B TowerB Normal

Command successful

NOTE: For 3-phase systems, if the Out-of-Balance Alerting feature is enabled, and the system goes into a load out-of-balance condition, the

System Status command will display the alert “3ph Out-of-Balance” in the Tower Status section, unless there is a higher priority tower error state to report.

60  Operations

Intelligent IPM

Installation and Operations Manual

Enabling or disabling the external configuration reset button:

The Set Option Button command enables or disables the external configuration reset button. This feature can enhance system security by protecting the PDU configurations from being reset locally.

NOTE: If this feature has been enabled and the administrative account username/password has been lost, then the PDU must be returned to the factory for non-warranty reset of the configuration.

To enable or disable the configuration reset button:

At the Sentry: prompt, type set option button, followed by enabled or disabled and press Enter.

Enabling or disabling the ‘more’ prompt:

The Set Option More command enables or disables the ‘more’ prompt for display of data larger than the terminal window.

To enable or disable ‘more’:

At the Sentry: prompt, type set option more, followed by enabled or disabled and press Enter.

Setting the temperature scale:

The Set Option TempScale command sets the temperature scale that the PDU will report in.

To set the temperature scale:

At the Sentry: prompt, type set option tempscale, followed by celsius or fahrenheit and press Enter.

Creating a descriptive tower name:

The Set Tower Name command assigns a descriptive name to a tower. This descriptive name is displayed when the Show

Traps command is issued.

To create a tower name:

At the Sentry: prompt, type set tower name, followed by the absolute tower name, then the descriptive name of up to 24 alphanumeric and other keyboard characters (ASCII 33 to 126 decimal - spaces are not allowed). Press Enter.

Example

The following command adds the descriptive name Florida_HQ_1 to tower .a:

Sentry: set tower name .a Florida_HQ_1<Enter>

Intelligent IPM

Installation and Operations Manual

Operations  61

Displaying tower information:

The Show Towers command displays information about the PDU. This information includes the absolute and descriptive unit names.

To display tower information:

At the Sentry: prompt, type show towers and press Enter.

Example

Sentry: show towers<Enter>

Tower Tower

ID Name

.A Florida_HQ_1

Creating a descriptive infeed name:

The Set Infeed Name command assigns a descriptive name to an infeed. This descriptive name is displayed when the

Show Traps command is issued

To create a infeed name:

At the Sentry: prompt, type set infeed name, followed by the absolute infeed name, then the descriptive name of up to 24 alphanumeric and other keyboard characters (ASCII 33 to 126 decimal - spaces are not allowed). Press Enter.

Example

The following command adds the descriptive name HQ_1_Infeed_A to the infeed on the PDU:

Sentry: set infeed name .aa HQ_1_Infeed_A<Enter>

Displaying infeed information:

The Show Infeeds command displays information about all infeeds. This information includes the absolute and descriptive infeed names.

To display tower information:

At the Sentry: prompt, type show infeeds and press Enter.

Example

Sentry: show infeeds<Enter>

Input Input

Feed ID Feed Name

.AA HQ_1_Infeed_A

62  Operations

Intelligent IPM

Installation and Operations Manual

Configuring the Command Line Interface (CLI) session timeout:

The Set Option CLI Timeout command configures the CLI session timeout in minutes.

The valid timeout range is 1 to 1440 minutes (24 hours). The default session timeout is 5 minutes.

To configure the CLI Session Timeout:

At the Switched CDU: prompt, type set option clitimeout, followed by the session timeout (in minutes), and press Enter.

Example:

The following command sets the CLI session timeout to 15 minutes:

Switched CDU: set option clitimeout 15<Enter>

Configuring the web session (Web Interface) timeout:

The Set Option Web Timeout command configures the Web session timeout in minutes.

The valid timeout range is 1 to 1440 minutes (24 hours). The default session timeout is 5 minutes.

To configure the web session timeout:

At the Switched CDU: prompt, type set option webtimeout, followed by the session timeout (in minutes), and press

Enter.

Example:

The following command sets the web session (Web Interface) timeout to 10 minutes:

Switched CDU: set option webtimeout 10<Enter>

Customizing the CLI prompt:

The Set Option Prompt command customizes the CLI prompt.

To customize the CLI prompt:

At the Switched CDU: prompt, type set option prompt and press Enter. Then type the custom prompt and press Enter.

To reset the custom prompt to the default prompt, type set option prompt and press Enter. When prompted, leave blank and press Enter.

The maximum length of the custom prompt is 31 characters. Spaces and special characters are allowed.

Example:

The following command sets the default CLI prompt to “My Prompt”:

Switched CDU: set option prompt<Enter>

Custom prompt <blank for default>: My Prompt:

Command successful

My Prompt:

Enabling or Disabling StartUp Stick

:

The Set Option Startupstick command enables or disables the StartUp Stick tool for PDU mass configuration of operating parameters.

To enable or disable StartUp Stick:

At the Switched CDU: prompt, type set option startupstick, followed by enabled or disabled and press Enter.

To enable or disable coldboot alert:

Upon a coldboot of the system (if the Coldboot Alert feature is enabled), the system sends a ½ second RS-232 break out on any serial ports that are also enabled.

The Set Option Coldboot Alert command enables or disables the Coldboot Alert feature.

To enable or disable coldboot alert:

At the Switched CDU: prompt, type set option cbalert, followed by enabled or disabled, and press Enter.

Intelligent IPM

Installation and Operations Manual

Operations  63

To enable or disable the Serial Command Protocol (SCP) authentication:

The Set SCP Authentication command enables or disables SCP Authentication.

To enable or disable SCP:

At the Switched CDU: prompt, type set scpauth, followed by enabled or disabled, and press Enter.

To set the Serial Command Protocol (SCP) authentication user:

The Set SCPAuth User command sets the username and password for SCPAuthentication.

To set SCP username:

At the Switched CDU: prompt, type set scpauth user, followed by user name, and press Enter. You will be prompted to enter and verify a password.

Displaying the Firmware version:

The Version command displays the Firmware version.

To display the firmware version:

At the Sentry: prompt, type version and press Enter.

Performing a warm boot:

The Restart command performs a warm boot of the PDU.

NOTE: System user/outlet/group/port configuration or outlet states are NOT changed or reset with this command.

To perform a warm boot:

At the Sentry: prompt, type restart and press Enter.

Displaying system options:

The Show Options command displays settings for all system options.

To display system option information:

At the Switched CDU: prompt, type show options and press Enter.

Example

Sentry: show options

System Options

Display Orientation: AUTO <Normal>

Outlet Sequence Order: NORMAL

Strong Passwords: DISABLED

Configuration Reset Button: ENABLED

More Prompt: ENABLED

Temperature Scale: CELSIUS

CLI Custom Prompt: <none>

CLI Session Timeout: 10 minutes

Web Session Timeout: 10 minutes

Coldboot Alert <SCP>: ENABLED

NOTE: The display of “<SCP>” after the Coldboot Alert parameter in the Show Options command (as indicated above) shows a relationship between the Serial Command Protocol (SCP) and the Coldboot Alert feature. Upon a coldboot of the system, if the Coldboot Alert feature is enabled, the system will send a ½ second RS-232 break out to to any SCP-enabled serial ports.

64  Operations

Intelligent IPM

Installation and Operations Manual

Enabling or disabling the Cisco EnergyWise network:

NOTE: Only commands through the CLI are supported for the Cisco EnergyWise network. There is no firmware web-based interface for

EnergyWise. Enabling EnergyWise requires a system restart.

The Set EnergyWise command enables or disables the EnergyWise network support:

To enable or disable EnergyWise:

At the Switched CDU: prompt, type set energywise, followed by enabled or disabled, and press Enter.

Example

Switched CDU: set energywise enabled

Command successful –- restart required

Setting up PDUs in the Cisco EnergyWise network:

NOTE: To use EnergyWise, you must first configure domain name, port, and secret.

The Set EnergyWise Domain command configures the EnergyWise domain the PDU belongs to. The limit of the Domain Name is 64 characters.

To set the EnergyWise domain name:

At the Switched CDU: prompt, type set energywise domain, followed by the domain name, and press Enter.

Example

Switched CDU: set energywise domain 10.1.2.120

Command successful

To set the EnergyWise port:

The default port number is 43440; the valid range for port numbers is 1-65535.

At the Switched CDU: prompt, type set energywise port, followed by the port number, and press Enter.

Example

Switched CDU: set energywise port

Port [666]: 700

Command successful

To set the EnergyWise secret:

The limit of the Secret field is 64 characters. A blank secret is also acceptable.

At the Switched CDU: prompt, type set energywise secret, then verify the secret, and press Enter.

Example

Switched CDU: set energywise secret

Secret: ********

VerifySecret: ********

Command successful

Intelligent IPM

Installation and Operations Manual

Operations  65

To set a blank EnergyWise secret:

A blank secret is acceptable.

At the Switched CDU: prompt, type set energywise secret, do not type in the Secret field, and press Enter twice (to bypass the Secret field and then VerifySecret field.)

Example of a blank secret

Switched CDU: show energywise

EnergyWise Configuration

Endpoint: Enabled *

Port: 666

Domain: (undefined)

Refresh Rate: 60

Secret: (Blank)

Command successful

To set the EnergyWise refresh rate:

The EnergyWise refresh rate is the rate (in seconds) at which new information is pushed to the EnergyWise manager.

Valid range is 30-600 seconds; default is new data sent to the EnergyWise manager every 3 minutes.

At the Switched CDU: prompt, type set energywise refresh, followed by a rate (in seconds) from 30-600, and press

Enter.

Viewing Cisco EnergyWise network parameters:

NOTE: A change in any value (shown in the example below) requires a restart of the system.

To view EnergyWise network parameters:

At the Switched CDU: prompt, type show energywise, and press Enter.

Example

Switched CDU: show energywise

EnergyWise Configuration

Endpoint: Enabled*

Port: 666

Domain: <undefined>

Refresh Rate: 55

Secret: ********

Command successful

66  Operations

Intelligent IPM

Installation and Operations Manual

TCP/IP Administration

The Set DHCP command enables or disables DHCP support.

To enable or disable DHCP support:

At the Switched CDU: prompt, type set dhcp, followed by enabled or disabled, and press Enter.

Enabling or disabling DHCP boot delay:

The Set DHCP Boot Delay command enables or disables the DHCP boot delay option.

 Enabling the Boot Delay option gives the PDU approximately 100-seconds to establish a connection through a

DHCP server This interval allows various network component activities to occur as the PDU powers up (such as obtaining SNTP time stamps for logging or allowing SNMP traps to be sent as switched outlets power up). This is the default state.

 Disabling the Boot Delay option forces the PDU to boot after approximately 5-seconds regardless of the DHCP acquisition state. This speeds up a boot when a DHCP server is connected to one of the PDU’s outlets. In this configuration, SNMP traps, SNTP and other protocols will not be available until a DHCP address has been resolved.

To enable the boot delay:

At the Switched CDU: prompt, type set dhcp, followed by bootdelay, followed by enabled or disabled, and press

Enter.

NOTES:

 The Boot Delay option executes only when DHCP is enabled.

 The firmware can detect network link integrity and will wait for network connection. This means that if the network is not currently

connected, the enabled Boot Delay option will be ignored.

Enabling or disabling DHCP static address fallback:

NOTE: DHCP must be enabled to activate the DHCP Static Address Fallback option.

The Set DHCP Static Address Fallback command enables or disables the DHCP static address fallback option.

Enabling the Static Address Fallback option informs the PDU to automatically fall back to a static address if a DHCP server does not respond after 100-seconds. This is the default state.

Disabling the Static Address Fallback option generates periodic DHCP server requests until the PDU obtains a dynamic address.

To enable the static address fallback:

At the Switched CDU: prompt, type set dhcp, followed by staticfallback, followed by enabled or disabled, and press

Enter.

NOTE: If the DHCP server boot time is excessive, you may need to disable the DHCP Static Address Fallback option.

Setting the IP address:

The Set Ipaddress command sets the TCP/IP address of the network interface controller.

To set the IP address:

At the Sentry: prompt, type set ipaddress, followed by the IP address and press Enter.

NOTE: Both IPv4 and IPv6 IP address formats are accepted.

Example

The following command sets the IP address to 12.34.56.78:

Sentry: set ipaddress 12.34.56.78<Enter>

Intelligent IPM

Installation and Operations Manual

Operations  67

Setting the subnet mask:

The Set Subnet command sets the subnet mask for the network the PT40 will be attached to.

To set the subnet mask:

At the Sentry: prompt, type set subnet, followed by the subnet mask and press Enter.

Example

The following command sets the subnet mask to 255.0.0.0

Sentry: set subnet 255.0.0.0<Enter>

Setting the gateway:

The Set Gateway command sets the IP address of the default gateway the PDU uses to access external networks.

To set the gateway IP address:

At the Sentry: prompt, type set gateway, followed by the gateway IP address and press Enter.

Example

The following command set the gateway IP address to 12.34.56.1:

Sentry: set gateway 12.34.56.1<Enter>

Setting the DNS IP address:

The Set DNS command sets the TCP/IP address of the Domain Name server (DNS).

To set the DNS IP address:

At the Sentry: prompt, type set, followed by dns1 or dns2 and the Domain Name server’s IP address. Press Enter.

NOTE: Both IPv4 and IPv6 formats are accepted for DNS IP address.

Example

The following command sets the primary Domain Name server IP address to 98.76.54.254:

Sentry: set dns1 98.76.54.254<Enter>

68  Operations

Intelligent IPM

Installation and Operations Manual

Displaying network configuration information:

The Show Network command displays TCP/IP, Telnet, SSH, Web, SSL, SNMP, and DHCP options (when DHCP is enabled) configuration information. The Show Network command also displays all IPv4 and IPv6 settings.

 Network configuration: IP address, subnet mask, gateway and DNS IP addresses (both IPv4 and IPv6 formats are displayed). (both IPv4 and IPv6 formats are displayed).

 Enabled-disabled status and port numbers for Telnet, SSH, HTTP, SSL, SNMP, and FTP Server support.

 Network status: Link, speed, duplex, and negotiation.

 DHCP boot delay and DHCP static address fallback options (when DHCP is enabled).

 Enabled-disabled status of Sentry Power Manager (SPM).

To display network configuration information:

At the Sentry: prompt, type show network and press Enter.

Example

The following command displays the network configuration information:

Switched CDU: show network

Network Settings

State: DHCP IPv6/IPv4 Network: Dual IPv6/IPv4

Link: Up

Speed: 100 Mbps

Negotiation: Auto

Duplex: Full

AutoCfg IPv6: FE80::20A:9CFF:FE52:4104/64

IPv6 Address: FD01::1:B51A:E03C/64

IPv4 Address: 10.1.6.230 Subnet Mask: 255.255.0.0

IPv4 Gateway: 10.1.1.1

DNS1: FD01::A01:585

DNS2: 10.1.5.133

Static IPv4/IPv6 Settings

IPv6 Address: FD01::A01:353/64

IPv6 Gateway: ::

IPv4 Address: 10.1.2.253 Subnet Mask: 255.255.0.0

IPv4 Gateway: 10.1.1.1

DNS1: 10.1.5.133

DNS2: 10.1.5.134

DHCP Settings

DHCP: Enabled

FQDN: Enabled [sentry3-524104]

Boot Delay: Enabled

Static Fallback: Enabled

Network Services

Telnet: Enabled Port: 23

SSH: Enabled Port: 22 Auth: Password, Kb-Int

HTTP: Enabled Port: 80

SSL: Enabled Port: 443 Installed Cert: User Encrypted

Access: Optional Stored Files: Cert & Key

User Cert: Enabled User Passphrase: <set>

SNMPv1/2: Enabled Port: 161 TrapPort: 162

SNMPv3: Disabled Port: 161 TrapPort: 162

FTP Server: Enabled Port: 21

SPM Access: Enabled

Command successful

NOTE: The fields IPv4 Address, IPv4 Subnet Mask, IPv4 Gateway, DNS1, and DNS2 are equivalent to existing PDU IPv4 settings except that current network settings and static settings are displayed separately. This allows you to view both static configuration settings and active network settings that can be obtained using DHCP. The DNS addresses can be in IPv4 or IPv6 (based on RFC4291) format at this time.

Intelligent IPM

Installation and Operations Manual

Operations  69

HTTP Administration

NOTE: A restart is required after setting or changing any Telnet/Web configurations.

Enabling and disabling HTTP support:

The Set HTTP command is used to enable or disable HTTP support.

To enable or disable HTTP support:

At the Sentry: prompt, type set http, followed by enabled or disabled and press Enter.

Changing the HTTP server port:

With HTTP support enabled, the HTTP server watches and responds to requests on the default HTTP port number 80. This port number can be changed using the Set HTTP Port command.

To change the HTTP port:

At the Sentry: prompt, type set http port, followed by the port number and press Enter.

Example

The following changes the HTTP port number to 2048:

Sentry: set HTTP port 2048<Enter>

Setting the HTTP authentication method:

The Set HTTP Security command is used to set the method of authentication. The PDU HTTP server supports two authentication methods for security and validation of the username-password – Basic and MD5 digest.

To set the HTTP authentication method:

At the Sentry: prompt, type set http security, followed by basic or md5 and press Enter.

Sentry Power Manager (SPM) Administration

The PDU Power Manager (SPM) is Server Technology’s enterprise management software product for the data center. The configuration options provided allow you to enable/disable SPM and reset the SPM password to its default.

NOTE: The SPM options apply only if you are currently using Server Technology’s SPM software product.

Enabling and disabling SPM Secure Access:

The Set SPM command enables or disables support for Sentry Power Manager (SPM). If your operation does not currently use SPM software, you can disable SPM Secure Access. However, if disabled, the PDU will not be able to use the SPM suite of secure network capabilities or the advanced remote configuration.

To enable or disable SPM support:

At the Switched CDU: prompt, type set spm, followed by enabled or disabled and press Enter.

NOTE: Both HTTP and SSL must be enabled or the SPM Secure Access option will not be permitted. When SPM Secure Access is permitted, the default is Enabled.

Resetting the SPM Password:

The Set SPM Reset Password command resets the SPM password on the PDU to its internal default password.

Each PDU has a default unique SPM password that is used to communicate between SPM and the PDU. When SPM discovers a PDU in the network, SPM changes this password into a different unique password for added security. The

SPM then continues to manage or alter these passwords as required for system security.

If a PDU is relocated or swapped from the system after a password was generated, SPM may not be able to re-establish a connection to the unit. The Set SPM Reset Password command allows you to reset to the internal default password of the

PDU so SPM can re-discover the device and add it to the system. Once the unit has been acquired by SPM, no further action is necessary.

To reset the SPM password:

At the Switched CDU: prompt, type set spm, followed by resetpw and press Enter.

NOTE: Do not reset the password if SPM communication has already been established.

70  Operations

Intelligent IPM

Installation and Operations Manual

Telnet Administration

NOTE: A restart of the IPM is required after setting or changing any Telnet/Web configurations.

Enabling and disabling Telnet support:

The Set Telnet command is used to enable or disable Telnet support.

To enable or disable Telnet support:

At the Sentry: prompt, type set telnet, followed by enabled or disabled and press Enter.

Changing the Telnet port:

With Telnet support enabled, the Telnet server watches and responds to requests on the default Telnet port number 23. This port number can be changed using the Set Telnet Port command.

To change the Telnet socket:

At the Sentry: prompt, type set telnet port, followed by the port number and press Enter.

Example

The following changes the Telnet port number to 7001:

Sentry: set telnet port 7001<Enter>

FTP Administration

You can upload new versions of firmware into the PDU using File Transfer Protocol (FTP). This allows access to new firmware releases for firmware improvements and new features additions. The following commands are used to configure the PDU for an FTP firmware upload.

NOTE: Secure File Transport Protocol (SFTP) is also supported for encrypted SSH transport over the network.

Setting the FTP host address:

The Set FTP Host command sets the FTP host IP address or hostname allowing for firmware file uploads.

To set the FTP Host address:

At the Sentry: prompt, type set ftp host, followed by the IP address or hostname and press Enter.

NOTE: Both IPv4 and IPv6 formats are accepted for IP address or hostname.

Examples

The following command sets the FTP host IP address to 12.34.56.99:

Sentry: set ftp host 12.34.56.99<Enter>

The following command sets the FTP hostname to ftp.servertech.com:

Sentry: set ftp host ftp.servertech.com<Enter>

Setting the FTP username:

The Set FTP Username command sets the username as required by the FTP Host.

To set the FTP username:

At the Sentry: prompt, type set ftp username, followed by the FTP username and press Enter.

Example

The following command sets the FTP username to Guest:

Sentry: set ftp username guest<Enter>

Intelligent IPM

Installation and Operations Manual

Operations  71

Setting the FTP Password:

The Set FTP Password command sets the password as required by the FTP Host.

To set the FTP password:

At the Sentry: prompt, type set ftp password, followed by the FTP password and press Enter.

Example

The following command sets the FTP password to OpenSesame:

Sentry: set ftp password OpenSesame<Enter>

Setting the filename to be uploaded:

The Set FTP Filename command sets the filename of the firmware file to be uploaded.

To set the FTP filename:

At the Sentry: prompt, type set ftp filename, followed by the firmware filename and press Enter.

Example

The following command sets the FTP filename to snb_s50a.bin:

Sentry: set ftp filename snb_s50a.bin<Enter>

Setting the directory for the file to be uploaded:

The Set FTP Directory command sets the directory for the firmware file to be uploaded.

To set the FTP directory:

At the Sentry: prompt, type set ftp directory, followed by the directory and press Enter.

Example

The following command sets the FTP directory to ftp://Sentry:

Sentry: set ftp directory ftp://sentry<Enter>

Enabling or disabling automatic updates:

The Set FTP Autoupdate command is used to enable or disable automatic firmware update support.

To enable or disable automatic updates:

At the Sentry: prompt, type set ftp autoupdate, followed by enabled or disabled and press Enter.

Setting the automatic update scheduled day:

The Set FTP Autoupdate Day command is used to set the day when automatic updates occur.

To set the automatic update day:

At the Sentry: prompt, type set ftp autoupdate day, followed by a day of the week or everyday and press Enter.

Example

The following command sets the automatic update day to Sunday:

Sentry: set ftp autoupdate day sunday<Enter>

Setting the automatic update scheduled hour:

The Set FTP Autoupdate Hour command is used to hour of the day when automatic updates occur.

To set the automatic update hour:

At the Sentry: prompt, type set ftp autoupdate hour, followed by an hour of the day and press Enter.

Examples

The following command sets the automatic update hour to 12 AM:

Sentry: set ftp autoupdate hour 12am<Enter>

The following command sets the automatic update hour to 3 PM:

Sentry: set ftp autoupdate hour 3pm<Enter>

72  Operations

Intelligent IPM

Installation and Operations Manual

Displaying FTP configuration information:

The Show FTP command displays all FTP configuration information.

 FTP Host IP address

 FTP Host username and password

 Firmware filepath and filename

To display FTP configuration information:

At the Sentry: prompt, type show ftp and press Enter.

Example

The following command displays the FTP configuration information:

Sentry: show ftp<Enter>

FTP Configuration

Host: ftp.servertech.com

Username: guest

Password: OpenSesame

Directory: ftp://sentry

Filename: snb_s52a.bin

FTP Automatic Updates Configuration

Automatic Updates: 12.34.56.99

Scheduled Day: Sunday

Scheduled Hour: 3 PM

SNTP Administration

The firmware supports the use of a network time service to provide a synchronized time reference.

About Daylight Saving Time(DST)

Support for DST is disabled by default. When enabled, the date and time are automatically adjusted forward one hour between the starting and ending dates and times (which can be configured).

NOTE: If Daylight Saving Time (DST) is enabled, all system time displays will be shown with the current DST start/end date/time settings.

The default time zone is set for the United Stated until at least 2015.

The time zone format is: mo.w.d/h:m:s, as follows:

mo = month from January to December (1-12)

w = week number (1-4) or the last week (5)

d = day of week from Sunday to Saturday (0-6)

h = hour (0-23)

m = minute (0-59)

s = second (0-59)

Setting the SNTP server address:

The Set SNTP command is used to set the primary and secondary SNTP server addresses.

To set the SNTP server address:

At the Switched CDU: prompt, type set sntp, followed by primary or secondary, and the SNTP server IP address or hostname. Press Enter.

NOTES:

 The primary/secondary IP addresses contact the SNTP server; these addresses are populated with the external NTP pool time zones

“2.pool.ntp.org” and “1.pool.ntp.org” as default for new PDUs that have not yet been time set.

 Both IPv4 and IPv6 formats are accepted for primary/secondary IP address or hostname.

Examples

The following command sets the primary SNTP server address to 204.152.184.72:

Switched CDU: set sntp primary 204.152.184.72<Enter>

The following command sets the secondary SNTP server address to cuckoo.nevada.edu:

Switched CDU: set sntp secondary cuckoo.nevada.edu<Enter>

Intelligent IPM

Installation and Operations Manual

Operations  73

Setting the local GMT offset (hours/minutes):

The Set SNTP GMToffset command is used to set the offset from GMT for the date/time returned by SNTP.

The GMT offset supports all standard international time zones from -12:59 to +14.59. The GMT offset can be set in minutes to accommodate partial-hour time zones.

NOTE: The IPM does not support automatic adjustment for Daylight Saving Time (DST).

To set the local GMT offset:

At the Sentry: prompt, type set sntp gmtoffset, followed by the offset value, and press Enter.

Examples

The following command sets the local GMT offset to -12:

Sentry: set sntp gmtoffset -12<Enter>

Displaying SNTP configuration information:

The Show SNTP command displays all SNTP configuration information.

To display SNTP configuration information

At the Sentry: prompt, type show sntp and press Enter.

Example

The following command displays the SNTP configuration information:

Switched CDU: show sntp <Enter>

Date/Time: 2013-04-13 15:21:18

Primary Host: 204.152.184.72

Secondary Host: 1.pool.ntp.org

Local GMT Offset: -8

Use DST: Enabled

Start Date: 1 st Wednesday in April

Start Time: 04:18:06

End Date: 1 st Sunday in November

End Time: 02:00:00

Feature Administration

Displaying activated special features:

The Show Features command displays all activated special features for the device.

To display activated special features:

At the Switched CDU: prompt, type show features and press Enter.

Example

The following command displays all activated special features:

Switched CDU: show features<Enter>

Activated Features:

Smart Load Shedding

NOTE: A restart of the IPM is required after activating new special features.

74  Operations

Intelligent IPM

Installation and Operations Manual

Chapter 3: Advanced Operations

SSL

Enabling and Setting up SSL Support

SSL Technical Specifications

SSH

Enabling and Setting up SSH Support

SSH Technical Specifications

SNMP

MIB, OID and Support

Enabling and Setting up SNMP Support

SNMP Traps

Configuring Traps

LDAP

Enabling and Setting up LDAP Support

Configuring LDAP Groups

LDAP Technical Specifications

TACACS+

Enabling and Setting up TACACS+ Support

Configuring TACACS+ Privilege Levels

TACACS+ Technical Specifications

L

OGGING

Internal System Log

Syslog

Email

U

PLOAD

/D

OWNLOAD

Sentry Integrated FTP Server

FTP Configuration Files

Upload/Download Process

76

5

76

5

76 5

78

78

78

79

81

85

87

79

91

97

100

91

101

101

103

105

106

106

106

107

110

110

110

111

Intelligent IPM

Installation and Operations Manual

Advanced Operations  75

SSL

Secure Socket Layers (SSL) enables secure Web sessions between a Sentry Remote Power Manager and a remote user.

SSL provides two chief features designed to make TCP/IP (Internet) transmitted data more secure:

 Authentication – The connecting client is assured of the identity of the server.

 Encryption – All data transmitted between the client and the server is encrypted rendering any intercepted data unintelligible to any third party.

SSL uses the public-and-private key encryption system by RSA, which also requires the use of digital certificates. An

SSL Certificate is an electronic file uniquely identifying individuals or websites and enables encrypted communication;

SSL Certificates serve as a kind of digital passport or credential. The PDU’s SSL Certificate enables the client to verify the PDU’s authenticity and to communicate with the PDU securely via an encrypted session, protecting confidential information from interception and hacking.

SSL Command Summary

Command

Set SSL

Set SSL Access

Set SSL Port

Description

Enables/disables SSL support

Sets SSL access as optional or required

Configures the SSL port number

Set SSL User Certificate Enables/disables custom user certificates

Set SSL User Passphrase Passphrase to control login access for user certificates

Enabling and Setting up SSL Support

NOTE: A restart of the IPM is required after setting or changing any SSL configurations.

Enabling or disabling SSL support:

The Set SSL command is used to enable or disable SSL support.

To enable or disable SSL support:

At the Sentry: prompt, type set ssl, followed by enabled or disabled and press Enter.

Setting SSL access level:

The Set SSL Access command is used to assign use of SSL as optional or required. The default access level is set to optional.

To change the access level:

At the Sentry: prompt, type set ssl access, followed optional or required, and press Enter.

Example

The following changes the access level to required:

Sentry: set ssl access required<Enter>

Enabling or disabling custom user certificates:

The Set SSL User Certificate command enables or disables uploading of custom user certificates.

To enable or disable user certificates:

At the Switched CDU: prompt, type set ssl usercert, followed by enabled or disabled, and press Enter.

Setting the custom user certificate passphrase:

The Set SSL User Passphrase command sets the user-defined passphrase for authentication of uploaded custom user certificates.

To set the user certificate passphrase:

At the Switched CDU: prompt, type set ssl userpass and press Enter. You will be prompted to provide the passphrase. Press

Enter.

NOTE: A restart of the PDU is required after setting the user certificate passphrase.

76  Advanced Operations

Intelligent IPM

Installation and Operations Manual

SSL Technical Specifications

Secure Socket Layer (SSL)

Transport Layer Security (TLS) version 1 (RFC 2246)

SSL/TLS-enabled HTTPS server (RFC 2818)

Self-Signed X.509 Certificate version 3 (RFC 2459)

Asymmetric Cryptography:

1024-bit RSA Key Exchange

Symmetric Cryptography Ciphers:

TLS_RSA_WITH_AES_256_CBC_SHA

TLS_RSA_WITH_AES_128_CBC_SHA

TLS_RSA_WITH_3DES_EDE_CBC_SHA

TLS_RSA_WITH_DES_CBC_SHA

Intelligent IPM

Installation and Operations Manual

Advanced Operations  77

SSH

Secure Shell (SSH) version 2 enables secure network terminal sessions between a Remote Power Manager and a remote user over insecure network. SSH provides an encrypted terminal sessions with strong authentication of both the server and client, using public-key cryptography and is typically used as a replacement for unencrypted Telnet. In addition to enabling secure network terminal sessions to the PDU for configuration and power management, the SSH session can be used for secure Pass-Thru connections to attached devices.

SSH requires the configuration and use of a client agent on the client PC. There are many freeware, shareware or forpurchase SSH clients available. Two examples are the freeware client PuTTY and the for-purchase client SecureCRT by

VanDyke Software. For configuration and use of these clients, please refer to the applicable software documentation.

SSH Command Summary

Command

Set SSH

Set SSH Port

Description

Enables/disables SSH support

Sets the SSH server port number

Enabling and Setting up SSH Support

NOTE: A restart of the PDU is required after setting or changing any SSH configuration

Enabling or disabling SSH support:

The Set SSH command is used to enable or disable SSH support.

To enable or disable SSH support:

At the Sentry: prompt, type set ssh, followed by enabled or disabled and press Enter.

Changing the SSH server port:

With SSH support enabled, the SSH server watches and responds to requests on the default SSH port number 22. This port number can be changed using the Set SSH Port command.

To change the SSH port:

At the Sentry: prompt, type set ssh port, followed by the port number and press Enter.

Example

The following changes the SSH port number to 65535:

Sentry: set ssh port 65535<Enter>

SSH Technical Specifications

Secure Shell (SSH) version 2

Asymmetric Cryptography:

Diffie-Hellman DSA/DSS 512-1024 (random) bits per NIST specification

Symmetric Cryptography:

AES256-CBC

AES192-CBC

AES128-CBC

RIJNDAEL256-CBC

RIJNDAEL192-CBC

RIJNDAEL128-CBC

Message Integrity:

HMAC-SHA1-160

HMAC-MD5-128

Authentication:

Username/Password

Session Channel Break Extension (for RS232 Break)

3DES-192-CBC

78  Advanced Operations

Intelligent IPM

Installation and Operations Manual

SNMP/Thresholds

The PDU supports the Simple Network Management Protocol (SNMP). This allows network management systems to use

SNMP requests to retrieve information and control power for the individual outlets.

The unit includes an SNMP v2c agent supporting standard MIB 1 and MIB 2 objects. A private enterprise MIB extension

(Sentry3 MIB) is also supported to provide remote power control.

About SNMP Versions

The firmware supports SNMP versions 1, 2, and 3.

SNMP version 3 supports authentication and encryption on a per user basis. Authentication types are None and MD5.

Encryption types are None and DES. If you use authentication, you must use encryption.

Two SNMPv3 users are supported: one user with read-write (RW) access, and one user with read-only (RO) access Both users have the same configuration parameters, and you can configure each user independently.

SNMPv2 and SNMPv3 can be enabled or disabled independently. You can have SNMPv2 and/or SNMPv3, or none.

SNMP CLI Commands:

 All SNMP v3 specific configuration settings use the CLI command SET SNMP V3.

 All SNMP v1/v2 specific configuration settings use the CLI command SET SNMP V2.

 All SNMP configuration settings common to any SNMP version use the CLI command SET SNMP.

NOTES:

 If you use SNMP v1 or SNMP v2, all SET SNMP CLI commands (and the SHOW command) require the “V2” keyword.

 SNMP v1/v2 CLI commands are documented immediately below in this section showing the required “V2” keyword. All CLI commands

that follow the SNMP v1/v2 section in this manual assume SNMP v3.

SNMP v1/v2 Command Summary

Command

Set SNMP IP Restrict

Set SNMP Trap Format

Set SNMP V2

Set SNMP V2 Getcomm

Set SNMP V2 Setcomm

Show SNMP

Description

Allows SNMP Get and Set requests only from defined trap destinations

Configures the SNMP trap format version

Enables or disables SNMP v1/v2 support

Sets the ‘get’ community string

Sets the ‘set’ community string

Displays all SNMP configuration information

Enabling and Setting Up SNMP v1/v2 Support

SNMP v1/v2 support must be enabled and configured for access to Sentry3 MIB objects and generation of all Sentry3 traps.

Enabling/disabling SNMP support:

The SNMP Set command is used to enable or disable SNMP v1/v2 support.

To enable SNMP v1/v2 support:

At the Switched CDU: prompt, type set snmp v2, followed by enabled or disabled and press Enter.

NOTE: A restart of the IPM is required after enabling or disabling SNMP support.

Intelligent IPM

Installation and Operations Manual

Advanced Operations  79

Setting the Get/Set community strings:

NOTE: The default for SNMP support is Enabled. When Server Technology products are shipped, the default SNMP configuration for the Get community string is set to “public” and the Set community string is left blank.

The PDU supports two SNMP community strings (Set and Get) that provide varying levels of access to objects defined in the PDU3 MIB. Valid community strings are 1 to 24 characters.

Set Community String:

The Setcomm string provides read-write access to sentry3 MIB objects. The default Setcomm string is blank.

To set the Setcomm community string:

At the Switched CDU: prompt, type set snmp v2 setcomm, followed by the string, and press Enter.

Get Community String:

The Getcomm string provides read-only access to sentry3 MIB objects. The default Getcomm string is public.

To set the Getcomm community string:

At the Switched CDU: prompt, type set snmp v2 getcomm, followed by the string, and press Enter.

Displaying SNMP v1/v2 configuration information:

The Show SNMP V2 command displays all SNMP v1/v2configuration information, including:.

 SNMP support status

 SNMP community strings

 Trap timer value

 Trap destinations (both IPv4 and IPv6 formats can be displayed.)

To display SNMP v1/v2 configuration information:

At the Switched CDU: prompt, type show snmp v2 and press Enter.

Example

The following command displays the SNMP configuration information:

Switched CDU: show snmp v2<Enter>

SNMP Configuration

SNMPv2 Agent: Enabled

GET Community <RO>: public

SET Community <RW>: <undefined>

TRAP Community: trap

SNMPv3 Agent: Disabled

Engine ID 800006B602000000000000000000000FFFF0A010249

RW Username: <undefined>

RW Auth Type: None <password not set>

RW Privacy Type: None <password not set>

RO Username: <undefined>

RO Auth Type: None <password not set>

RW Privacy Type: None <password not set>

Trap Username <undefined>

Trap Destination 1: <undefined>

Trap Destination 2: <undefined>

Trap format: v3

IP Restrictions: No Restrictions

Error Trap Repeat Time: 60 second<s>

SysName: Sentry3_524640

SysLocation: No Location

SysContact: No Contact

Command successful

80  Advanced Operations

Intelligent IPM

Installation and Operations Manual

SNMP v3 Command Summary

Command

Set SNMP IP Restrict

Description

Allows SNMP Get and Set requests from defined trap destinations only

Set SNMP Trap Format Configures the SNMP trap format version

Set SNMP V3 Enables or disables SNMP v3 support

Set SNMP V3 RO Username

Set SNMP V3 RO Auth Type

Sets the SNMP V3 read-only username.

Sets the SNMP V3 read-only authentication type

Set SNMP V3 RO Auth Password Sets the SNMP V3 read-only authentication password

Set SNMP V3 RO Priv Type Sets the SNMP V3 read-only privacy type

Set SNMP V3 RO Priv Password Sets the SNMP V3 ready-only privacy password

Set SNMP V3 RW Username Sets the SNMP V3 read-write username

Set SNMP V3 RW Auth Type Sets the SNMP V3 read-write authentication type

Set SNMP V3 RW Auth Password Sets the SNMP V3 read-write authentication password

Set SNMP V3 Trap Username

Set SNMP V3 RW Priv Type

Sets the SNMP V3 trap username for display on SNMP activity logs

Sets the SNMP V3 read-write privacy type

Set SNMP V3 RW Priv Password Sets the SNMP V3 ready-write privacy password

Show SNMP Displays all SNMP configuration information

MIB, OID and Support

The PDU SNMP MIB and OID are available on the Server Technology website: ftp://ftp.servertech.com/pub/SNMP/sentry3

Technical support is available 8:00AM to 5:00 PM Pacific Time, Monday-Friday.

For SNMP Support, email: [email protected]

Enabling and Setting up SNMP Support

SNMP support must be enabled and configured for access to Sentry3 MIB objects and generation of all Sentry3 traps.

Enabling/disabling SNMP support:

The SNMP command is used to enable or disable SNMP support.

To enable SNMP support:

At the Sentry: prompt, type set snmp, followed by enabled or disabled and press Enter.

NOTE: A restart of the IPM is required after enabling or disabling SNMP support.

SNMPv3 Engine ID:

The local engine ID is the unique identifier for the SNMPv3 engine and is displayed for viewing.

Setting the SNMP v3 read-only (RO) username :

The Set SNMP RO Username command sets the read-only username for SNMP v3. A valid username can be set to any value between 1-32 characters.

To set the RO username:

At the Switched CDU: prompt, type set snmp v3 rousername, and press Enter.

NOTE: You can set a blank username but doing so will clear the string and disallow any read-only user access.

Setting the SNMP v3 read-only (RO) authentication type :

The Set SNMP RO Auth Type command sets the SNMP v3 RO authentication type.

To set the RO authentication type:

At the Switched CDU: prompt, type set snmp v3 roauthtype, followed by none or md5, and press Enter.

Intelligent IPM

Installation and Operations Manual

Advanced Operations  81

Setting the SNMP v3 read-only (RO) authentication password:

The Set SNMP RO Auth Password command sets the SNMP v3 RO authentication password. A valid authentication password can be set to any value between 1-40 characters. A blank password will clear the string.

To set the RO authentication password:

At the Switched CDU: prompt, type set snmp v3 roauthpass, and press Enter.

Setting the SNMP v3 read-only (RO) privacy type :

The Set SNMP RO Priv Type command sets the SNMP v3 RO privacy type.

To set the RO privacy type:

At the Switched CDU: prompt, type set snmp v3 roprivtype, followed by none or des, and press Enter.

Setting the SNMP v3 read-only (RO) privacy password:

The Set SNMP RO Priv Password command sets the SNMP v3 RO privacy password. A valid privacy password can be set to any value between 1-32 characters. A blank password will clear the string

To set the RO privacy password:

At the Switched CDU: prompt, type set snmp v3 roprivpass, and press Enter

Setting the SNMP v3 read-write (RW) username :

The Set SNMP RW Username command sets the read-write username for SNMP v3. A valid username can be set to any value between 1-32 characters.

To set the RW username:

At the Switched CDU: prompt, type set snmpv3 rwusername, and press Enter.

NOTE: You can set a blank username but doing so will clear the string and disallow any read-write user access.

Setting the SNMP v3 read-write (RW) authentication type :

The Set SNMP RW Auth Type command sets the SNMP v3 RW authentication type.

To set the RW authentication type:

At the Switched CDU: prompt, type set snmp v3 rwauthtype, followed by none or md5, and press Enter.

Setting the SNMP v3 read-write (RW) authentication password:

The Set SNMP RW Auth Password command sets the SNMP v3 RW authentication password. A valid authentication password can be set to any value between 1-40 characters. A blank password will clear the string

To set the RW authentication password:

At the Switched CDU: prompt, type set snmp v3 rwauthpass, and press Enter.

Setting the SNMP v3 read-write (RW) privacy type :

The Set SNMP RW Priv Type command sets the SNMP v3 RW privacy type. A valid password can be set to any value between 1-40 characters.

To set the RW privacy type:

At the Switched CDU: prompt, type set snmp v3 rwprivtype, followed by none or des, and press Enter.

Setting the SNMP v3 read-write (RW) privacy password:

The Set SNMP RW Priv Password command sets the SNMP v3 RW privacy password. A valid privacy password can be set to any value between 1-32 characters. A blank password will clear the string

To set the RW privacy password:

At the Switched CDU: prompt, type set snmp v3 rwprivpass, and press Enter.

82  Advanced Operations

Intelligent IPM

Installation and Operations Manual

Setting the SNMP v3 trap username:

The Set SNMP Trap Username command sets an optional username for display on SNMP activity logs to identify user actions.

At the Switched CDU: prompt, type set snmp v3 trapusername, and press Enter. The trap username can be 1-31 alphanumeric characters; spaces are allowed; and the name is case sensitive.

Setting the error trap repeat timer:

The Set SNMP Traptime command sets the timer period between repeated error condition traps.

The valid range is 1 to 65535 (in seconds). The default is 60 seconds.

To set the error trap repeat timer:

At the Switched CDU: prompt, type set snmp traptime, followed by the timer period, and press Enter.

Example

The following sets the timer period to 180 seconds:

Switched PDU: set snmp traptime 180<Enter>

Setting the SNMP trap format version:

The SNMP Trap Format configures the SNMP trap format version. The trap format can be SNMP v1, v2, or v3.

To set the trap format version:

At the Switched CDU: prompt, type set snmp trapformat, followed by 1, 2, or 3, and press Enter. The default is v1, regardless of the versions that are enabled for the agent.

Example

The following sets the trap format version to SNMP v3:

Switched CDU: set snmp trapformat 3<Enter>

Setting IP restrictions:

The Set SNMP IP Restrictions command supports SNMP Manager Get and Set requests to only be allowed from the IP address of the defined trap destinations.

To set SNMP IP restrictions:

At the Switched CDU: prompt, type set snmp iprestrict trapdests and press Enter.

To remove SNMP IP restrictions:

At the Switched CDU: prompt, type set snmp iprestrict none and press Enter.

Setting trap destinations:

The Set SNMP Trapdest1 and Trapdest2 commands are used to set the IP addresses or hostname of SNMP management stations receiving all traps. The PDU supports a maximum of two trap destinations; one must be defined to enable trap generation.

To set the trap destination:

At the Sentry: prompt, type set snmp, trapdest1 or trapdest2, the Ipaddress or hostname and press Enter.

Examples

The following sets the trap destination 1 to 64.42.31.208:

Sentry: set snmp trapdest1 64.42.31.208<Enter>

The following sets the trap destination 2 to snmp.servertech.com:

Sentry: set snmp trapdest2 snmp.servertech.com<Enter>

To reset the trap destination:

At the Sentry: prompt, type set snmp, trapdest1 or trapdest2, 0.0.0.0 and press Enter.

Intelligent IPM

Installation and Operations Manual

Advanced Operations  83

Setting the trap timer:

The Set Traptime command sets the timer period between repeated error-condition traps. The valid range for the timer period is 1 to 65535 (in seconds). The default value for the timer period is 60 seconds.

To set the trap timer:

At the Sentry: prompt, type set traptime, followed by the timer period and press Enter.

Example

The following sets the timer period to 180 seconds:

Sentry: set traptime 180<Enter>

Setting the Get/Set community strings:

The Switched CDU supports two SNMP community strings that provide varying levels of access to objects defined in the

PDU3 MIB.

Community strings can be 1 to 24 characters.

Setcomm:

The Setcomm string provides read-write access to sentry3 MIB objects. The default Setcomm string is blank.

To set the Setcomm community string:

At the Switched CDU: prompt, type set snmp setcomm, followed by the string and press Enter.

Getcomm:

The Getcomm string provides read-only access to sentry3 MIB objects. The default Getcomm string is public.

To set the Getcomm community string:

At the Switched CDU: prompt, type set snmp getcomm, followed by the string and press Enter.

Setting the SNMP SysName:

The Set SNMP SysName command is used to set the SNMP MIB-II SysName object.

To set the SysName object:

At the Switched CDU: prompt, type set snmp sysname, followed by the object name and press Enter.

Setting the SNMP SysLocation:

The Set SNMP SysLocation command is used to set the SNMP MIB-II SysLocation object.

To set the SysLocation object:

At the Switched CDU: prompt, type set snmp syslocation, followed by the object location and press Enter.

Setting the SNMP SysContact:

The Set SNMP SysContact command is used to set the SNMP MIB-II SysContact object.

To set the SysContact object:

At the Switched CDU: prompt, type set snmp syscontact, followed by the object contact and press Enter.

84  Advanced Operations

Intelligent IPM

Installation and Operations Manual

Displaying SNMP configuration information:

The Show SNMP command displays all SNMP configuration information.

 SNMP version (v2/v3) support status (enabled/disabled)

 SNMP community strings

 Read-Only (RO) or Read-Write (RW) username, authentication type, privacy type (if SNMPv3)

 Trap username

 Trap destination(s)

 IP restrictions setting

 Error trap repeat time (in seconds)

 Sysname, syslocation, and syscontact

To display SNMP configuration information:

At the Switched CDU: prompt, type show snmp and press Enter.

Example

The following command displays the SNMP configuration information:

Switched CDU: show snmp<Enter>

SNMP Configuration

SNMPv2 Agent: Enabled

GET Community <RO>: public

SET Community <RW>: <undefined>

TRAP Community: trap

SNMPv3 Agent: Disabled

Engine ID 800006B602000000000000000000000FFFF0A010249

RW Username: <undefined>

RW Auth Type: None <password not set>

RW Privacy Type: None <password not set>

RO Username: <undefined>

RO Auth Type: None <password not set>

RW Privacy Type: None <password not set>

Trap Username <undefined>

Trap Destination 1: <undefined>

Trap Destination 2: <undefined>

Trap format: v3

IP Restrictions: No Restrictions

Error Trap Repeat Time: 60 second<s>

SysName: Sentry3_524640

SysLocation: No Location

SysContact: No Contact

Command successful

SNMP Traps

The Intelligent IPM supports four types of SNMP traps. Traps are enabled at the Tower (T), Infeed (I), outlet (O),

Environmental Monitor (E) or sensor (S) level.

Trap Summary

Name Level(s) Description

Status T, I, O, E, S Operational status change

Change

Temp

Humid

O

S

S

Control status change

Temperature is out of range

Relative Humidity is out of range

All traps include the Location of the PDU as defined with the Set Location command.

Intelligent IPM

Installation and Operations Manual

Advanced Operations  85

Status Trap

A Status trap is generated when an error condition occurs on a tower, infeed, Environmental Monitor or individual sensor.

Status traps include the reported Status, the Location of the PDU and identifier and name of the affected tower, infeed, outlet, environmental monitor or sensor.

Any error state generates a Status trap and triggers the trap timer. A new trap is generated at the end of every timer period until the Status returns to a non-error status. All status traps are enabled by default.

Tower Status traps

Status

Normal

NoComm

Error

x

Description

Tower is working correctly

Communication to the tower has been lost

Infeed Status traps

Status

On

OffError

NoComm

Error

x x

Description

Infeed is on

Infeed should be on but no current is sensed at the infeed

Communication to the infeed has been lost

Outlet Status traps

Status

On

Off

OnWait

OffWait

OnError

OffError

OffFuse

NoComm x x x x

Error Description

Outlet is on

Outlet is off

Outlet Status in transition

Outlet Status in transition

Outlet should be off but current is sensed at the outlet

Outlet should be on but no current is sensed at the outlet

Outlet should be on but a blown fuse has been detected

Communication to the outlet has been lost

Environmental Monitor Status traps

Status

Normal

NoComm

Error

x

Description

Environmental Monitor is working correctly

Communication to the Environmental Monitor has been lost

Temperature/Humidity Sensor Status traps

Status

Found

NotFound

Lost

Error

x

Description

The sensor has been detected

No sensor has been detected

Sensor initially detected but communication to the sensor has been lost

NoComm x Communication to the sensor has been lost

NOTE: Traps are generated according to a hierarchical architecture, for example, if an Tower Status enters a trap condition, only the Tower

Status trap will be generated. Infeed, Outlet, Environmental Monitor or Sensor Status and Temp and Humid traps will be suppressed until the

Tower Status returns to Normal.

Change Trap

The Change trap is generated for all outlet status changes between any on/off conditions. Change traps include the outlet status, Location of the PDU, and identifier and name of the affected outlet. For descriptions of the outlet status types, see the previous table.

86  Advanced Operations

Intelligent IPM

Installation and Operations Manual

Temp Trap

The Temp trap is generated whenever the temperature on a temperature/humidity sensor is beyond preset thresholds.

Temp traps include the reported temperature, temp status, Location of the PDU, and identifier and name of the affected sensor.

Any error state generates a Temp trap and triggers the trap timer. A new trap is generated at the end of every timer period until the Temp returns to a non-error status.

Temp Traps

Status

Normal

NotFound

Reading

Error

TempLow x

TempHigh x

ReadError x

Lost x

NoComm x

Description

The sensor is working correctly and the temperature is within preset thresholds

No sensor has been detected

Temp status currently being read

Temperature at the sensor below preset low threshold

Temperature at the sensor exceeds preset high threshold

Unable to read Temp status

Sensor initially detected but communication to the sensor has been lost

Communication to the sensor has been lost

Humidity Trap

The Humidity trap is generated whenever the humidity on a temperature/humidity sensor is beyond preset thresholds.

Humidity traps include the reported relative humidity, humidity status, Location of the PDU, and identifier and name of the affected sensor.

Any error state generates a Humidity trap and triggers the trap timer. A new trap is generated at the end of every timer period until the Humidity returns to a non-error status.

Humidity Traps

Status

Normal

NotFound

Reading

Error

HumidLow x

HumidHigh x

ReadError x

Lost x

Description

The sensor is working correctly and the relative humidity is within preset thresholds

No sensor has been detected

Humidity status currently being read

Relative humidity at the sensor below preset low threshold

Relative humidity at the sensor exceeds preset high threshold

Unable to read Humidity status

Sensor initially detected but communication to the sensor has been lost

NoComm x

Configuring Traps

Communication to the sensor has been lost

SNMP Trap Command Summary

Command

Set Trap Tower Status

Set Trap Infeed Status

Set Trap Outlet Change

Set Trap Outlet Status

Set Trap EM Status

Set Trap THS Status

Set Trap THS Temp

Set Trap THS Temphigh

Set Trap THS Templow

Set Trap THS Humid

Set Trap THS Humidhigh

Set Trap THS Humidlow

Show Traps

Description

Enables or disables the Tower Status trap

Enables or disables the Infeed Status trap off

Enables or disables the Outlet Change trap

Enables or disables the Outlet Status trap

Enables or disables the Environmental Monitor Status trap

Enables or disables a temperature/humidity sensor Status trap

Enables or disables a temperature/humidity sensor Temp trap

Sets a temperature/humidity sensor Temp trap high limit

Sets a temperature/humidity sensor Temp trap low limit

Enables or disables a temperature/humidity sensor Humid trap

Sets a temperature/humidity sensor Humid trap high limit

Sets a temperature/humidity sensor Humid trap low limit

Displays trap configurations

Intelligent IPM

Installation and Operations Manual

Advanced Operations  87

Enabling or Disabling a Status Trap:

The Set Trap … Status command is used to enable or disable Status traps for a Tower, Infeed or Outlet.

To Enable or Disable a Status trap:

At the Sentry: prompt, type set trap (tower, infeed, outlet, em or ths) status, followed by the tower, infeed or outlet name, and on or off. Press Enter, or\

Type set trap (tower, infeed, outlet, em or ths) Status all, followed by on or off and press Enter.

Examples

The following command enables the Status trap for the first tower, using the tower’s absolute name:

Sentry: set trap tower status .a on<Enter>

The following command enables the Status trap for the tower named Florida_HQ_1:

Sentry: set trap tower status Florida_HQ_1 on<Enter>

NOTE: Enabling lower hierarchical traps automatically enables traps of higher hierarchical value: i.e. enabling an Outlet Status trap automatically enables the Infeed and Tower Status traps for that outlet. Conversely, if a Tower Status trap is disabled, all associated Infeed Status

& Load and Outlet Status traps will be disabled.

Enabling or Disabling a Change Trap:

The Set Trap Outlet Change command is used to enable or disable an Outlet Change trap.

To Enable or Disable a Change trap:

At the Sentry: prompt, type set trap outlet change, followed by the outlet name and on or off. Press Enter, or

Type set trap outlet change all, followed by on or off and press Enter.

Example

The following command enables the Change trap for the third outlet on the first infeed of the second tower, using the outlet’s absolute name:

Sentry: set trap outlet change .ba3 on<Enter>

Enabling or Disabling the Temp Trap:

The Set Trap THS Temp command is used to enable or disable the Temp trap.

To Enable or Disable the Temp trap:

At the Sentry: prompt, type set trap ths temp, followed by the sensor name and on or off. Press Enter.

Example

The following command enables the Temp trap for the first temperature-humidity sensor:

Sentry: set trap ths temp .a1 on<Enter>

Setting the Temperature Sensor Threshold Limits:

The Set Trap THS Templow and Set Trap THS Temphigh commands are used to set the lower and upper threshold limits for the Temperature sensor.

To set the Temperature threshold limits:

At the Sentry: prompt, type set trap ths, templow or temphigh, followed by the sensor name and a value from 0 to 127 in degrees Celsius. Press Enter.

Example

The following command sets the second temperature high threshold limit to 95:

Sentry: set trap ths temphigh .a2 95<Enter>

88  Advanced Operations

Intelligent IPM

Installation and Operations Manual

Enabling or Disabling the Humid Trap:

The Set Trap THS Humid command is used to enable or disable the Humid trap.

To Enable or Disable the Humid trap:

At the Sentry: prompt, type set trap ths humid, followed by the sensor name and on or off. Press Enter.

Example

The following command enables the Humid trap for the first temperature-humidity sensor:

Sentry: set traps ths humid .a1 on<Enter>

Setting the Humidity Sensor Threshold Limits:

The Set Trap THS Humidlow and Set Trap THS Humidhigh commands are used to set the lower and upper threshold limits for the Humidity sensor.

To set the Humidity threshold limits:

At the Sentry: prompt, type set trap ths, humidlow or humidhigh, followed by the sensor name and a value from 0 to

100 in percent relative humidity. Press Enter.

Example

The following command sets the first humidity sensor low threshold limit to 5:

Sentry: set trap ths humidlow .a1 5<Enter>

Configuring Temperature Recovery Delta (Hysteresis):

The Temperature Recovery Delta command allows configuration of the number of degrees of change needed to recover from a temperature alarm.

To configure the temperature recovery delta:

At the Switched CDU: prompt, type set trap ths tempdelta, followed by the sensor name, the number of degrees for the recovery delta, and press Enter.

Valid range is 0-30 C or 0-54 F.

Example

The following command configures the recovery delta at 2 degrees Fahrenheit for temperature/humidity sensor .A1:

Switched CDU: set trap ths tempdelta temp_humid_sensor_A1 2<Enter>

Intelligent IPM

Installation and Operations Manual

Advanced Operations  89

Configuring Humidity Recovery Delta (Hysteresis):

The Humidity Recovery Delta command allows configuration of the percentage of change needed to recover from a humidity alarm.

NOTE: After exceeding a low or high humidity threshold (thus entering an error condition), the humidity value must return past the threshold by the configured recovery delta amount to clear the error condition. Default of humidity recovery delta is 2% relative humidity.

To configure the humidity recovery delta:

At the Switched CDU: prompt, type set trap ths humiddelta, followed by the sensor name, the percentage for the recovery delta, and press Enter. Valid range is 0-20%.

Example

The following command configures the recovery delta at 2 relative humidity for temperature/humidity sensor .A1:

Switched CDU: set trap ths humiddelta temp_humid_sensor_A1 2<Enter>

Displaying Trap Configuration Information:

The Show Traps command displays information about all traps.

To display trap information:

At the Sentry: prompt, type show traps and press Enter.

Example

The following command requests trap configuration information:

Sentry: show traps <Enter>

Tower trap configuration:

Tower Tower Status

ID Name Trap

.A Florida_HQ_1 ON

More (Y/es N/o): y

Input feed trap configuration:

Input Input Status

Feed ID Feed Name Trap

.AA HQ_1_Infeed_A ON

More (Y/es N/o): y

Outlet trap configuration:

Outlet Outlet Change Status

ID Name Trap Trap

.AA1 DataServer_1 OFF ON

.AA2 WebServer_1 OFF ON

More (Y/es N/o): y

Environmental Monitor .A trap configuration:

Name: Florida_HQ_1

Status Trap: ON

Temperature/Humidity Sensor .A1 Temperature/Humidity Sensor .A2

Name: Temp_Humid_Sensor_A1 Name: T/H2_Florida_HQ_1

Status Trap: ON Status Trap: ON

Temp Trap: ON Temp Trap: ON

Low: 0 Deg.C Low: 0 Deg.C

High: 127 Deg.C High: 95 Deg.C

Humid Trap: ON Humid Trap: ON

Low: 5 % RH Low: 0 % RH

High: 100 % RH High: 100 % RH

90  Advanced Operations

Intelligent IPM

Installation and Operations Manual

LDAP

The PDU family of products supports Lightweight Directory Access Protocol (LDAP) Version 3. This support enables authentication with LDAP servers; user accounts do not need to be individually created locally on each Sentry device.

This allows administrators to pre-define and configure (in each Sentry product, and in the LDAP server) a set of necessary

LDAP Groups, and access rights for each. User’s access rights can then be assigned or revoked simply by making the user a member of one-or-more pre-defined Sentry LDAP Groups. User accounts can be added, deleted, or changed in the

LDAP server without any changes needed on individual Sentry products.

Sentry LDAP support has been tested in the following environments:

 Microsoft Active Directory (MSAD)

 Novell eDirectory (eDir)

 OpenLDAP

LDAP Command Summary

Command

Add GrouptoLDAP

Add OutlettoLDAP

Add PorttoLDAP

Create LDAPGroup

Delete GroupfromLDAP

Delete OutlettoLDAP

Description

Grants an LDAP group access to one or more groups

Grants an LDAP group access to one or more outlets

Grants an LDAP group access to one or more serial ports

Adds an LDAP group name

Removes access to one or more groups for an LDAP group

Removes access to one or more outlets for an LDAP group

Delete PortfromLDAP

List LDAPGroup

List LDAPGroups

Ping

Remove LDAPGroup

Set Authorder

Set DNS

Set LDAP Bind

Set LDAP BindDN

Set LDAP BindPW

Set LDAP GroupAttr

Set LDAP GroupType

Set LDAP Host

Set LDAP Port

Set LDAP UserBaseDN

Set LDAP UserFilter

Set LDAP UseTLS

Set LDAP

Set LDAPGroup Access

Set LDAPGroup Envmon

Show LDAP

Show Network

Removes access to one or more serial ports for an LDAP group

Displays all accessible outlet/groups/ports for an LDAP group

Displays privilege levels for all LDAP groups

Verifies proper DNS configuration by name resolution

Deletes an LDAP group name

Specifies the authentication order for each new session attempt

Sets the IP address of the Domain Name server

Specifies the LDAP bind request

Specifies the user account Fully-Qualified Distinguished Name (FQDN) for binds

Specifies the user account password for binds

Specifies the user class distinguished name (DN) or names of groups a user is a member of

Specifies the data type for the Set LDAP GroupAttr command

Sets the IP address or hostname of the Directory Services server

Sets the LDAP server port number

Sets the base distinguished name (DN) for the username search at login

Sets the filter used for the username search at login

Enables/disables LDAP over TLS/SSL support

Enables/disables LDAP support

Sets the access level for an LDAP group

Grants or removes access to environmental monitoring

Displays LDAP configurations

Displays network configuration information for all IPv4 and IPv6 settings

Intelligent IPM

Installation and Operations Manual

Advanced Operations  91

Enabling and Setting Up LDAP Support

There are a few configuration requirements for properly enabling and setting up LDAP support. Below is an overview of the minimum requirements.

Directory Services server configuration requirements:

1. Define at least one LDAP group.

2. Assign users to that LDAP group.

Sentry configuration requirements:

1. Enable LDAP support.

2. Define the IP address and domain component of at least one Directory Services server.

3. Set the LDAP bind request method being utilized by the Directory Services server.

4. Define the IP address of at least one DNS server.

5. Test DNS server configuration using Sentry ‘ping’ support.

6. Define at least one LDAP group and assign access rights for that group.

NOTE: LDAP group names on the Directory Service server and the IPM must match.

Enabling and disabling LDAP support:

The Set LDAP command is used to enable or disable LDAP support.

To enable or disable LDAP support:

At the Sentry: prompt, type set ldap, followed by enabled or disabled and press Enter.

Setting the LDAP host address:

The Set LDAP Host command sets the TCP/IP address of the Directory Services server.

NOTE: Both IPv4 and IPv6 formats are accepted for hostname.

To set the LDAP host address:

At the Sentry: prompt, type set ldap, followed by host1 or host2 and the Directory Services server’s IP address or hostname. Press Enter.

Examples

The following command sets the primary Directory Services server IP address to 98.76.54.32:

Sentry: set ldap host1 98.76.54.32<Enter>

The following command sets the secondary Directory Services server hostname to ldap.servertech.com:

Sentry: set ldap host2 ldap.servertech.com<Enter>

Changing the LDAP server port:

The Set LDAP port command sets the port to which the PDU sends LDAP requests to on the previously defined LDAP server. The default port is 389.

To change the LDAP server port:

At the Sentry: prompt, type set ldap port, followed by the port number and press Enter.

Example

The following command sets the LDAP server port number to 8888:

Sentry: set ldap port 8888<Enter>

Enabling and disabling LDAP over TLS/SSL support:

The Set LDAP UseTLS command is used to enable or disable LDAP over TLS/SSL support.

To enable or disable LDAP over TLS/SSL support:

At the Switched CDU: prompt, type set ldap usetls, followed by yes or no and press Enter.

NOTE: When LDAP Over TLS/SSL is enabled, MD5 binding is disabled.

92  Advanced Operations

Intelligent IPM

Installation and Operations Manual

Setting the LDAP bind type:

The Set LDAP Bind command specifies the LDAP bind request that authenticates a client with the LDAP server.

The PDU supports three standard LDAP bind methods:

Simple: Uses unencrypted delivery of username-password over the network to the LDAP server for authentication,

showing user credentials in plain text.

LDAP over TLS/SSL: Uses a trusted authority certificate to provide encryption of LDAP authentication.

MD5: Provides strong protection using 1-way hash encoding that does not transmit the username-password over the

network.

To set the bind type:

At the Switched CDU: prompt, type set ldap bind, followed by simple, TLS, or md5, and press Enter.

NOTE: If MD5 binding is enabled, LDAP over TLS/SSL is disabled.

Setting the search bind Distinguished Name (DN):

The Set LDAP BindDN command is used to set the fully-qualified distinguished name (FQDN) for user accounts to bind with. This is required for directory services that do not support anonymous binds. This field is used ONLY with Simple

Binds. Maximum string length is 124 characters.

NOTE: If left blank, then an anonymous bind will be attempted. This field is used only with Simple binds.

To set the search bind DN:

At the Sentry: prompt, type set ldap binddn, and press Enter. At the following prompt, type the FQDN and press Enter.

Example

The following sets the FQDN for MSAD to ‘cn=guest,cn=Users,dc=servertech,dc=com’:

Sentry: set ldap binddn<Enter>

Enter Search Bind DN (Max characters 124): cn=guest,cn=Users,dc=servertech,dc=com<Enter>

The User Membership Attribute is a comma-delimited string of up to two attribute names whose values in the search results are the users that are members of the LDAP group. Maximum number of characters is 61.

NOTE: The user membership attribute option allows the searching of group directory names by a user membership attribute to find the groups for which the user is a member.

To set user membership attribute:

At the Switched CDU: prompt, type set ldap groupsearch userattr and press Enter.

Then at the following prompt, type the group membership attribute and press Enter.

Example

The following sets the user membership attribute to Test

Switched CDU: set ldap groupsearch userattr<Enter>

Enter Group Member Attribute <61 character max>

Test<Enter>

Setting the search bind Distinguished Name (DN) password:

The Set LDAP BindPW command is used to set the password for the user account specified in the Search Bind DN.

Maximum password size is 20 characters.

To set the Bind Password DN:

At the Sentry: prompt, type set ldap bindpw and press Enter. At the following prompt, type the bind password and press

Enter.

Intelligent IPM

Installation and Operations Manual

Advanced Operations  93

Setting the group membership attribute:

The Set LDAP GroupAttr command is used to specify the name of user class attributes that lists distinguished names

(DN), or names of groups that a user is a member of. Maximum string length is 30 characters.

To set Group Membership Attribute:

At the Sentry: prompt, type set ldap groupattr and press Enter. At the following prompt, type the group membership attribute and press Enter.

Example

The following sets the group membership attribute for MSAD to ‘memberof’:

Sentry: set ldap groupattr<Enter>

Enter Group Member Attr (Max character 30): memberof<Enter>

Setting the group membership value type:

The Set LDAP GroupType command is used to specify whether the values of Group Membership Attribute represent the

Distinguished Name (DN) of a group or just the name of the group.

To set group membership value type:

At the Sentry: prompt, type set ldap grouptype followed by DN or Name and press Enter.

Example

The following sets group membership value to DN

Sentry: set ldap grouptype DN<Enter>

Setting the user search base Distinguished Name (DN):

The Set LDAP UserBaseDN command is used to set the base (DN) for the login username search. This is where the search will start, and will include all subtrees. Maximum size is 100 characters.

To set the user search base DN:

At the Sentry: prompt, type set ldap userbasedn and press Enter. At the following prompt, type the search base DN and press Enter.

Example

The following sets the DN user search base for MSAD to ‘cn=Users,dc=servertech,dc=com’:

Sentry: set ldap userbasedn<Enter>

Enter User Search Base DN (Max characters 100): cn=Users,dc=servertech,dc=com<Enter>

Setting the user search filter:

The Set LDAP UserFilter command is used to set the search filter for the username entered at the login prompt.

The search filter must be entered within parenthesis and adhere to the following format:

(searchfilter=%s)

where ‘searchfilter’ is the name of the attribute in the user class which has a value that represents the user’s login name. In this string, the ‘%s’ will be replaced by the entered username. Maximum string length is 100 characters.

To set the user search filter:

At the Sentry: prompt, type set ldap userfilter and press Enter. At the following prompt, type the User Search Filter and press Enter.

Example

The following sets the user search filter for MSAD to ‘samaccountname’:

Sentry: set ldap userfilter<Enter>

Enter User Search Filter (Max characters 100):

(samaccountname=%s)<Enter>

94  Advanced Operations

Intelligent IPM

Installation and Operations Manual

Setting the authentication order:

The Set Authorder command sets the authentication order for remote authentication sessions. The PDU supports two methods for authentication order - Remote > Local and Remote Only.

The Remote > Local method first attempts authentication with the Active Directory server and if unsuccessful with the local user database on the PDU device.

The Remote Only method attempts authentication only with the Active Directory server and if unsuccessful, access is denied.

NOTE: With the Remote Only method, if authentication fails due to a communication failure with the Active Directory server automatic authentication fallback will occur to authenticate with the local user data base on the PDU device.

To set the authentication order:

At the Sentry: prompt, type set authorder, followed by remotelocal or remoteonly and press Enter.

NOTE: Server Technology recommends not setting the authentication order to Remote Only until the LDAP has been configured and tested.

Intelligent IPM

Installation and Operations Manual

Advanced Operations  95

Displaying LDAP configuration information:

The Show LDAP command displays LDAP configuration information.

 Enabled-disabled status of LDAP support

 Directory Services server IP address and port

 Bind request password type and remote authentication order

 Search bind distinguished name and password

 User search base distinguished name and filter

 Group membership attribute and type

To display the LDAP configuration information:

At the Sentry: prompt, type show ldap and press Enter.

Example

The following command displays the LDAP configuration information:

Sentry: show ldap

LDAP Configuration

LDAP: Enabled

Host 1: 98.76.54.32

Host 2: ldap.servertech.com

Port: 8888

TLS/SSL: Yes

Bind Type: MD5

Auth Order: Remote->Local

Search Bind

DN: cd=guest,cn=Users,dc=servertech,dc=com

Password: OpenSesame

User Search

Base DN: cn=Users,dc=servertech,dc=com

Filter: (samaccountname=%s)

Group Membership

Attribute: memberof

Value Type: DN

Setting the DNS IP address:

The Set DNS command sets the TCP/IP address of the Domain Name server (DNS).

NOTE: LDAP requires the definition of at least one Domain Name server.

To display the DNS configuration information, use the Show Network command as described on page 68.

To set the DNS IP address:

At the Sentry: prompt, type set, followed by dns1 or dns2 and the Domain Name server’s IP address. Press Enter.

NOTE: Both IPv4 and IPv6 formats are accepted for DNS IP address.

Example

The following command sets the primary Domain Name server IP address to 98.76.54.254:

Sentry: set dns1 98.76.54.254<Enter>

Verifying the DNS configuration:

The Ping command can be used to verify the configuration of the DNS IP address.

To verify the DNS configuration:

At the Sentry: prompt, type ping, followed by the domain component of the Directory Services server previously configured and press Enter.

Example

The following command verifies the DNS configuration:

Sentry: ping servertech.com

Pinging servertech.com [98.76.54.32] with 64 bytes of data:

Reply from 98.76.54.32: bytes=64 pseq=0 triptime=0

Reply from 98.76.54.32: bytes=64 pseq=1 triptime=0

Reply from 98.76.54.32: bytes=64 pseq=2 triptime=0

Reply from 98.76.54.32: bytes=64 pseq=3 triptime=0

Reply from 98.76.54.32: bytes=64 pseq=4 triptime=0

96  Advanced Operations

Intelligent IPM

Installation and Operations Manual

Configuring LDAP Groups

Creating an LDAP group:

The Create LDAPGroup command creates an LDAP group.

To create an LDAP group:

At the Sentry: prompt, type create ldapgroup, optionally followed by a 1-16 character group name (Spaces are not allowed, and LDAP group names are not case sensitive). Press Enter.

Example

The following command creates the LDAP group PowerUser:

Sentry: create ldapgroup PowerUser<Enter>

Removing an LDAP group:

The Remove LDAPGroup command removes an LDAP group.

To remove an LDAP group:

At the Sentry: prompt, type remove ldapgroup, optionally followed by a group name. Press Enter.

Setting LDAP group access level privileges:

The Set LDAPGroup Access command sets the access level privileges for an LDAP group. The PDU has four defined access privilege levels; Admin, User, On-Only and View-Only.

To set the access level privilege for an LDAP group :

At the Sentry: prompt, type set ldapgroup access, followed by admin, user, ononly or viewonly, optionally followed by a LDAP group name and press Enter.

Examples

The following command sets the LDAP group access level for LDAPAdmin to Admin:

Sentry: set ldapgroup access admin ldapadmin<Enter>

The following command sets the LDAP group access level for PowerUser to User:

Sentry: set ldapgroup access user poweruser<Enter>

Granting and removing input status viewing privileges :

The Set LDAPGroup Envmon command grants or removes input status viewing privileges to/from an LDAP group.

To grant or remove input status viewing privileges for an LDAP group:

At the Sentry: prompt, type set ldapgroup envmon followed by on or off, optionally followed by a group name and press

Enter.

Example

The following command grants input status viewing privileges to the LDAP group PowerUser:

Sentry: set ldapgroup envmon on poweruser<Enter>

Displaying the LDAP access privilege levels:

The List LDAPGroups command displays all defined LDAP group with their access privilege level.

To display LDAP group access privilege levels:

At the Sentry: prompt, type list ldapgroups and press Enter.

Example

The following command displays all LDAP groups with their access privilege level:

Sentry: list ldapgroups<Enter>

LDAP Access Environmental

Group Name Level Monitoring

LDAPAdmin Admin Allowed

PowerUser User Allowed

User On-Only Not Allowed

Guest View-Only Not Allowed

Intelligent IPM

Installation and Operations Manual

Advanced Operations  97

Adding outlet access to an LDAP group:

The Add OutletToLDAP command grants an LDAP group access to one or all outlets. To grant access for more than one outlet, but not all outlets, you must use multiple Add OutletToLDAP commands.

To grant outlet access to an LDAP group:

At the Sentry: prompt, type add outlettoldap, optionally followed by an outlet name and a group name. Press Enter, or

Type add outlettoldap all, followed by a group name and press Enter.

Examples

The following commands grant the LDAP group PowerUser access to outlets A1 and Webserver_1:

Sentry:add outlettoldap .a1 poweruser<Enter>

Sentry:add outlettoldap WebServer_1 poweruser<Enter>

Deleting outlet access for an LDAP group:

The Delete OutletFromLDAP command removes an LDAP group’s access to one or all outlets. You cannot remove access to any outlet for an administrative level group.

To delete outlet access for an LDAP group:

At the Sentry: prompt, type delete outletfromldap, optionally followed by an outlet name and a group name. Press Enter, or

Type delete outletfromldap all, followed by a group name and press Enter.

Adding outlet group access to an LDAP group:

The Add GroupToLDAP command grants an LDAP group access to a outlet group. To grant access for more than one outlet group, you must use multiple Add GroupToLDAP commands.

To grant outlet group access to an LDAP Group:

At the Sentry: prompt, type add grouptoldap, optionally followed by an outlet group name and an LDAP group name.

Press Enter.

Examples

The following commands grants to LDAP group PowerUser access to the outlet groups ServerGroup_1 and

ServerGroup_2:

Sentry:add grouptoldap servergroup_1 poweruser<Enter>

Sentry:add grouptoldap servergroup_2 poweruser<Enter>

Deleting outlet group access for an LDAP group:

The Delete GroupFromLDAP command removes an LDAP group’s access to a outlet group. You cannot remove access to any group for an administrative level group.

To delete outlet group access for an LDAP group:

At the Sentry: prompt, type delete groupfromldap, optionally followed by a outlet group name and an LDAP group name. Press Enter.

Adding serial port access to an LDAP group:

The Add PortToLDAP command grants an LDAP group access to the serial port.

To grant serial port access to an LDAP group:

At the Sentry: prompt, type add porttoldap console and a group name. Press Enter.

Deleting serial port access for an LDAP group:

The Delete PortFromLDAP command removes an LDAP group’s access to the serial port. You cannot remove access to the serial port for an administrative level group.

To delete serial port access for a user:

At the Sentry: prompt, type delete portfromldap console and a group name. Press Enter.

98  Advanced Operations

Intelligent IPM

Installation and Operations Manual

Granting and removing access to environmental monitoring :

The Set LDAPGroup Envmon command grants or removes input status viewing privileges to/from an LDAP group.

To grant or remove input status viewing privileges for an LDAP group:

At the Switched CDU: prompt, type set ldapgroup envmon followed by on or off, optionally followed by a group name and press Enter.

Example

The following command grants input status viewing privileges to the LDAP group PowerUser:

Switched CDU: set ldapgroup envmon on poweruser<Enter>

NOTE: Granting access to environmental monitoring (temperature/humidity/sensors) to a non-admin user also grants that user access to power monitoring (outlets, infeeds, towers – all the environmental data of the PDU).

Displaying LDAP Group access:

The List LDAPGroup command displays all access rights for an LDAP group.

To display LDAP Group access:

At the Sentry: prompt, type list ldapgroup, optionally followed by a group name. Press Enter.

Example

The following command displays information about the LDAP group PowerUser:

Sentry: list ldapgroup poweruser<Enter>

Username: PowerUser

Outlet Outlet

ID Name

.A1 DataServer_1

.A2 WebServer_1

Groups:

ServerGroup_1

ServerGroup_2

More (Y/es N/o): Y

Ports:

Port Port

ID Name

Console Console

Members of the PowerUser LDAP group can access the following outlets, outlet groups and serial ports: outlet A1 which has a descriptive name of DataServer_1, outlet A2 which has a descriptive name of WebServer_1, group ServerGroup_1 group ServerGroup_2 and Console serial port.

Intelligent IPM

Installation and Operations Manual

Advanced Operations  99

LDAP Technical Specifications

Simple Bind Authentication Process

Client LDAP Server Sentry

MD5 Bind Authentication Process

Client LDAP Server

Initiate Sentry session

Authentication request with

Usename/

Password

Successful

Bind?

Username found?

Prompt for login credentials

Simple bind using

Search Bind

DN & Password

Subtree search starting from

User Search Base

DN with User

Search Filter

Simple Bind using

User FQDN and login password

Initiate Sentry session

Authentication request with

Usename/

Password

Access Denied

Successful

Bind?

Username found?

Successful

Bind?

Subtree search starting from

User Search Base

DN with User

Search Filter

Attribute match?

Access Denied

Username found?

Attribute match?

Group

match?

Attribute name compared to

Group

Membership

Attribute

Username groups access rights compared against

Sentry LDAP groups

Access Granted

Group

match?

Access Granted

LDAPS (LDAP-over-TLS/SSL) Client Specifications

Secure Sockets Layer (SSL)

Transport Layer Security (TLS) version 1 (RFC 2246) x.509 version 3 Server Certificates (RFC 2459) with RSA key sizes up to 4096 bits

Symmetric Cryptography Ciphers:

TLS_RSA_WITH_3DES_EDE_CBC_SHA (168-bit)

TLS_RSA_WITH_DEX_CBC_SHA (56-bit)

TLS_RSA_WITH_AES_128_CBC_SHA (128-bit)

TLS_RSA_WITH_AES_256_CBC_SHA (256-bit)

Server certificates are accepted and used on –the-fly

A NULL client certificate is sent to the server if a client certificate is requested.

Sentry

Prompt for login credentials

SASL Digest-MD5 bind using uppercase username & entered password

Subtree search starting from

User Search Base

DN with User

Search Filter

Attribute name compared to

Group

Membership

Attribute

Username groups access rights compared against

Sentry LDAP groups

100  Advanced Operations

Intelligent IPM

Installation and Operations Manual

TACACS+

The PDU family of products supports the Terminal Access Controller Access Control System (TACACS+) protocol. This enables authentication and authorization with a central TACACS+ server; user accounts do not need to be individually created locally on each Sentry device.

This allows administrators to pre-define and configure (in each Sentry product, and in the TACACS+ server) a set of necessary TACACS+ privilege levels, and user’s access rights for each. User’s access rights can then be assigned or revoked simply by making the user a member of one-or-more pre-defined Sentry TACACS+ privilege levels. User account rights can be added, deleted, or changed within TACACS+ without any changes needed on individual Sentry products.

The PDU supports 16 different TACACS+ privilege levels; 15 are entirely configurable by the system administrator (1 is reserved for default Admin level access to all Sentry resources).

TACAC+ Command Summary

Command

Set Authorder

Set TACACS

Set TACACS Host

Set TACACS Key

Set TACACS Port

Show TACACS

Description

Specifies the authentication order for each new session attempt

Enables/disables SSL support

Sets the IP address or hostname of the TACACS server

Sets the TACACS encryption key

Sets the TACACS server port number

Displays TACACS configurations

Add GrouptoTACACS

Add OutlettoTACACS

Grants a TACACS account access to one or more groups

Grants a TACACS account access to one or all outlets

Add PorttoTACACS Grants a TACACS account access to one or serial ports

Delete GroupfromTACACS Removes access to one or more groups for a TACACS account

Delete OutlettoTACACS

Delete PortfromTACACS

Removes access to one or more outlets for a TACACS account

Removes access to one or more serial ports for a TACACS account

Set TacPriv Access

Set TacPriv Envmon

List TacPrivs

List TacPriv

Sets the access level for a TACACS account

Grants or removes privileges to view input and environmental monitoring status

Displays access levels for all TACACS accounts

Displays all accessible outlet/groups/ports for a TACACS account

Enabling and Setting up TACACS+ Support

There are a few configuration requirements for properly enabling and setting up TACACS+ support. Below is an overview of the minimum requirements:

1. Enable TACACS+ support.

2. Define the IP address and domain component of at least one TACACS+server.

3. Set the TACACS+ key configured on the supporting TACACS+server.

Enabling and disabling TACACS+ support:

The Set TACACS command is used to enable or disable TACACS+ support.

To enable or disable TACACS+ support:

At the Sentry: prompt, type set tacacs, followed by enabled or disabled and press Enter.

Intelligent IPM

Installation and Operations Manual

Advanced Operations  101

Setting the TACACS+ server address:

The Set TACACS Host command sets the IP address or hostname of the TACACS+ server.

NOTE: Both IPv4 and IPv6 formats are accepted for IP address or hostname.

To set the TACACS+ server address:

At the Sentry: prompt, type set tacacs, followed by host1 or host2 and the TACACS+ server’s IP address or hostname.

Press Enter.

Examples

The following command sets the primary TACACS+ server address to 98.76.54.32:

Sentry: set tacacs host1 98.76.54.32<Enter>

The following command sets the secondary TACACS+ server address to tacacs.servertech.com:

Sentry: set tacacs host2 tacacs.servertech.com<Enter>

Setting the TACACS+ encryption key:

The Set TACACS Key command sets the encryption key used to encrypt all data packets between the PDU and the

TACACS+ server. This key must match the key configured on the TACACS+ server.

To set the encryption key:

At the Sentry: prompt, type set tacacs key and press Enter.

At the TACACS+ Key: prompt, type a key of up to 60 alphanumeric and other keyboard characters (ASCII 32 to 126 decimal). Keys are case sensitive. Press Enter. To specify no password, press Enter.

At the Verify TACACS+ Key: prompt, retype the key. Press Enter. To verify no password, press Enter at the prompt.

Example

Sentry: set tacacs key<Enter>

TACACS+ Key: <Enter>

Verify TACACS+ Key: <Enter>

For security, key characters are not displayed.

NOTE: A key size of zero results in no encryption being applied which may not be supported by the TACACS+ server and is not recommended for a production environment.

Changing the TACACS port:

With TACACS support enabled, the PDU sends TACACS requests to the default TACACS port number 49. This port number can be changed using the Set TACACS Port command.

To change the TACACS port:

At the Sentry: prompt, type set tacacs port, followed by the port number and press Enter.

Example

The following changes the TACACS port number to 50:

Sentry: set tacacs port 50<Enter>

Setting the authentication order:

The Set Authorder command sets the authentication order for remote authentication sessions. The PDU supports two methods for authentication order - Remote -> Local and Remote Only.

The Remote -> Local method first attempts authentication with the TACACS+ server and if unsuccessful with the local user database on the PDU device.

The Remote Only method attempts authentication only with the TACACS+ server and if unsuccessful, access is denied.

NOTE: With the Remote Only method, if authentication fails due to a communication failure with the TACACS+ server automatic authentication fallback will occur to authenticate with the local user data base on the PDU device.

To set the authentication order:

At the Sentry: prompt, type set authorder, followed by remotelocal or remoteonly and press Enter.

NOTE: Server Technology recommends not setting the authentication order to Remote Only until TACACS+ has been configured and tested.

102  Advanced Operations

Intelligent IPM

Installation and Operations Manual

Displaying TACACS+ configuration information:

The Show TACACS command displays TACACS+ configuration information.

To display the TACACS configuration information:

At the Sentry: prompt, type show tacacs and press Enter.

Example

The following command displays the TACACS configuration information:

Sentry: show tacacs<Enter>

TACACS+ Configuration

TACACS+: Enabled

Host 1: 98.76.54.32

Host 2: tacacs.servertech.com

Port: 50

TACACS+ Key: (Set)

Auth Order: Remote->Local

Configuring TACACS+ Privilege Levels

Setting TACACS+ account access level privileges:

The Set TacPriv Access command sets the access level privileges for a TACACS+ account. The PDU has four defined access privilege levels; Admin, User, On-Only and View-Only.

To set the access level privilege for a TACACS+ account :

At the Sentry: prompt, type set tacpriv access, followed by admin, user, ononly or viewonly, optionally followed by a

TACACS+ account number and press Enter.

Examples

The following command sets the TACACS+ account access level for account 14 to Admin:

Sentry: set tacpriv access admin 14<Enter>

The following command sets the TACACS+ account access level for account 5 to User:

Sentry: set tacpriv access user 5<Enter>

Granting and removing input status viewing privileges:

The Set TacPriv Envmon command grants or removes input status viewing privileges to/from a TACACS+ account.

To grant or remove input status viewing privileges for a TACACS+ account:

At the Sentry: prompt, type set tacpriv envmon, followed by on or off, optionally followed by a TACACS+ account number and press Enter.

Example

The following command grants input status viewing privileges to the TACACS+ account 5:

Sentry: set tacpriv envmon on 5<Enter>

Displaying the TACACS+ access privilege levels:

The List TacPrivs command displays all TACACS+ accounts with their access privilege levels.

To display TACACS+ account access privilege levels:

At the Sentry: prompt, type list tacprivs and press Enter.

Example

The following command displays all TACACS+ account with their access privilege level:

Sentry: list tacprivs<Enter>

TACACS Access Environmental

Account Name Level Monitoring

TACAdmin Admin Allowed

PowerUser User Allowed

User On-Only Not Allowed

Guest View-Only Not Allowed

Intelligent IPM

Installation and Operations Manual

Advanced Operations  103

Adding outlet access to a TACACS+ account:

The Add OutletToTACACS command grants a TACACS+ account access to one or all outlets. To grant access for more than one outlet, but not all outlets, you must use multiple Add OutletToTACACS commands.

To grant outlet access to a TACACS+ account:

At the Sentry: prompt, type add outlettotacacs, optionally followed by an outlet name and a TACACS+ account number.

Press Enter, or

Type add outlettotacacs all, followed by a TACACS+ account number and press Enter.

Examples

The following commands grant the a TACACS+ account 5 access to outlets A1 and Webserver_1:

Sentry:add outlettotacacs .a1 5<Enter>

Sentry:add outlettotacacs WebServer_1 5<Enter>

Deleting outlet access for a TACACS+ account:

The Delete OutletFromTACACS command removes a TACACS+ account’s access to one or all outlets. You cannot remove access to any outlet for an administrative level account.

To delete outlet access for a TACACS+ account:

At the Sentry: prompt, type delete outletfromtacacs, optionally followed by an outlet name and a TACACS+ account number. Press Enter, or

Type delete outletfromtacacs all, followed by a TACACS+ account number and press Enter.

Adding outlet group access to a TACACS+ account:

The Add GroupToTACACS command grants a TACACS+ account access to an outlet group. To grant access for more than one outlet group, you must use multiple Add GroupToTACACS commands.

To grant outlet group access to a TACACS+ account:

At the Sentry: prompt, type add grouptotacacs, optionally followed by an outlet group name and a TACACS+ account number. Press Enter.

Examples

The following commands grants to a TACACS+ account number 5 access to the outlet groups ServerGroup_1 and

ServerGroup_2:

Sentry:add grouptotacacs servergroup_1 5<Enter>

Sentry:add grouptotacacs servergroup_2 5<Enter>

Deleting outlet group access for a TACACS+ account:

The Delete GroupFromTACACS command removes a TACACS+ account’s access to an outlet group. You cannot remove access to any group for an administrative level account.

To delete outlet group access for a TACACS+ account:

At the Sentry: prompt, type delete groupfromtacacs, optionally followed by a outlet group name and a TACACS+ account number. Press Enter.

Adding serial port access to a TACACS+ account:

The Add PortToTACACS command grants a TACACS+ account access to the serial port.

To grant serial port access to a TACACS+ account:

At the Sentry: prompt, type add porttotacacs console and a TACACS+ account number. Press Enter.

Deleting serial port access for a TACACS+ account:

The Delete PortFromTACACS command removes a TACACS+ account’s access to the serial port. You cannot remove access to the serial port for an administrative level account.

To delete serial port access for a TACACS+ account:

At the Sentry: prompt, type delete portfromtacacs console and a TACACS+ account number. Press Enter.

104  Advanced Operations

Intelligent IPM

Installation and Operations Manual

Displaying TACACS account access:

The List TacPriv command displays all access rights for a TACACS+ account.

To display TACACS account access:

At the Sentry: prompt, type list tacpriv, optionally followed by a TACACS+ account. Press Enter.

Example

The following command displays information about the TACACS+ account 1:

Sentry: list tacpriv 1<Enter>

TACACS+ Privilege Level: 1

Outlet Outlet

ID Name

.A1 DataServer_1

.A2 WebServer_1

Groups:

ServerGroup_1

ServerGroup_2

More (Y/es N/o): Y

Ports:

Port ID Port Name

Console Console

Members of the TACACS privilege level 1 account can access the following outlets, outlet groups and serial ports: outlet

A1 which has a descriptive name of DataServer_1, outlet A2 which has a descriptive name of WebServer_1, group

ServerGroup_1 group ServerGroup_2 and Console serial port.

TACACS+ Technical Specifications

Authentication START Packet includes: action = 1 (TAC_PLUS_AUTHEN_LOGIN) priv_lvl = 0 (TAC_PLUS_PRIV_LVL_MIN) authen_type = 1 (TAC_PLUS_AUTHEN_TYPE_ASCII) service = 1 (TAC_PLUS_AUTHEN_SVC_LOGIN) user = (entered username) port = (access path into the PDU) rem_addr = ‘Sentry3_xxxxxx’ (xxxxxx is last six digits of MAC address) data = ‘‘ (null)

NOTE: The password is sent in a CONTINUE packet.

Authorization REQUEST Packet includes: authen_method = 6 (TAC_PLUS_AUTHEN_METH_TACACSPLUS) priv_lvl = 0 (TAC_PLUS_PRIV_LVL_MIN) authen_type = 1 (TAC_PLUS_AUTHEN_TYPE_ASCII) authen_service = 1 (TAC_PLUS_AUTHEN_SVC_LOGIN) user = (entered username) port = (access path into the PDU) rem_addr = ‘Sentry3_xxxxxx’ (xxxxxx is last six digits of Ethernet MAC address) service = ‘shell’ (for exec) cmd = ‘‘ (null)

NOTE: The access paths into the PDU which support TACACS+ are ‘Console’, ‘Telnet’, ‘SSH’, ‘HTTP’ and ‘HTTPS’. In the case of

‘Console’ and ‘Modem’, an administrator is allowed to rename these ports in which case the assigned name is used.

Intelligent IPM

Installation and Operations Manual

Advanced Operations  105

Logging

The PDU family of products supports logging of system events both internally and externally. An internal log of more than 4000 events is automatically maintained and is reviewable by administrative users. For permanent/long-term log storage, Sentry supports the Syslog protocol. And for immediate notification, Sentry supports Email notifications.

Log entries include a sequential entry number, a date/time stamp and an event message. The event message is preceded with a message ‘type’ heading and if the event is tied to a user, the username will be included.

NOTE: For date/time stamp support, SNTP server support must be configured.

The PDU supports the following event message headers:

 AUTH:

 POWER:

 CONFIG:

 EVENT:

All authentication attempts.

All power state change requests.

All system configuration changes.

All general system events. Example: over/under threshold event.

Internal System Log

The internal system log is stored in the local memory and has support for up to 4097 continuously aging entries. The internal system log is only available to administrative users.

Syslog

The PDU’s Syslog support is RFC3164-compliant and enables off-Sentry viewing and storage of log messages. The PDU supports external logging to up to two Syslog servers.

Syslog Command Summary

Command

Set Syslog HostIP

Set Syslog Port

Show Syslog

Description

Sets the IP address of the Syslog server

Sets the Syslog server port number

Displays all Syslog configuration information

Setting the Syslog server IP address:

The Set Syslog HostIP command sets the TCP/IP address of the Syslog server.

To set the Syslog server IP address:

At the Sentry: prompt, type set syslog, followed by hostip1 or hostip2 and the Syslog server’s IP address. Press Enter.

Example

The following command sets the primary Syslog server IP address to 56.47.38.29:

Sentry: set syslog hostip1 56.47.38.29<Enter>

Changing the Syslog server port:

With Syslog support enabled, the Syslog server watches and responds to requests on the default Syslog port number 514.

This port number can be changed using the Set Syslog Port command.

To change the Syslog port:

At the Sentry: prompt, type set syslog port, followed by the port number and press Enter.

Example

The following changes the Syslog port number to 411:

Sentry: set syslog port 411<Enter>

106  Advanced Operations

Intelligent IPM

Installation and Operations Manual

Displaying Syslog configuration information:

The Show Syslog command displays Syslog configuration information.

To display the Syslog configuration information:

At the Sentry: prompt, type show syslog and press Enter.

Example

The following command displays the Syslog configuration information:

Sentry: show syslog<Enter>

SYSLOG Configuration

Primary Syslog Server IP Address: 56.47.38.29

Secondary Syslog Server IP Address: 0.0.0.0

Syslog Server Port: 411

Email

Email Command Summary

Command

Set Email

Set Email SMTP Host

Set Email SMTP Port

Set Email From

Description

Enables or disables Email notification support

Sets the SMTP Host IP address or hostname

Sets the SMTP server port number

Sets the email ‘From’ address

Set Email PrimaryTo

Set Email SecondaryTo

Set Email Event

Set Email Auth

Set Email Power

Set Email Config

Show Email

Sets the primary recipient email address

Sets the secondary recipient email address

Enables or disables notification of general system events

Enables or disables notification of all authentication attempts

Enables or disables notification of power state change requests

Enables or disables notification of configuration changes

Displays all Email configuration information

Enabling or disabling Email notification support:

The Set Email command enables or disables Email notification support.

To enable or disable Email notification support:

At the Sentry: prompt, type set email, followed by enabled or disabled and press Enter.

Setting the SMTP server address:

The Set Email Host command sets the IP address or hostname of the SMTP server.

NOTE: Both IPv4 and IPv6 formats are accepted for IP address or hostname.

To set the SMTP server address:

At the Sentry: prompt, type set email smtp host, followed by the SMTP server’s IP address or hostname and press Enter.

Examples

The following command sets the SMTP server address to 55.55.55.55:

Sentry: set email smtp 55.55.55.55<Enter>

The following command sets the SMTP server address to email.servertech.com:

Sentry: set email smtp email.servertech.com<Enter>

Intelligent IPM

Installation and Operations Manual

Advanced Operations  107

Changing the SMTP server port:

With SMTP support enabled, the PDU sends SMTP requests to the default SMTP port number 25. This port number can be changed using the Set Email SMTP Port command.

To change the TACACS port:

At the Sentry: prompt, type set email smtp port, followed by the port number and press Enter.

Example

The following changes the SMTP port number to 5555:

Sentry: set email smtp port 5555<Enter>

Setting the ‘From’ email address:

The Set Email From command sets the ‘from’ email address. By default, this is set to ‘Sentry3_’ plus the last three octets of the unit’s MAC address. Example: ‘Sentry3_510c90@’

To set the ‘From’ email address:

At the Sentry: prompt, type set email from, followed by the originating email address and press Enter.

Example

The following command sets the ‘from’ email address to [email protected]:

Sentry: set email from [email protected]<Enter>

Setting the ‘To’ email address:

The Set Email PrimaryTo and Set Email SecondaryTo commands set the recipient email addresses.

To set the ‘To’ email address:

At the Sentry: prompt, type set email, followed by primaryto or secondaryto and the destination email address. Press

Enter.

Examples

The following command sets the primary ‘to’ email address to [email protected]:

Sentry: set email primaryto [email protected]<Enter>

The following command sets the secondary ‘to’ email address to [email protected]:

Sentry: set email secondaryto [email protected]<Enter>

Enabling or disabling event notification types:

The Set Email Event, Set Email Auth, Set Email Power and Set Email Config commands enable or disable email

notification of the event types as described on page 106.

To enable or disable event notification types:

At the Sentry: prompt, type set email, followed by event, auth, power or config and enabled or disabled. Press Enter.

Examples

The following command sets the enables email notification general system events:

Sentry: set email event enabled<Enter>

The following command sets the disables email notification authentications attempts:

Sentry: set email auth disable<Enter>

108  Advanced Operations

Intelligent IPM

Installation and Operations Manual

Displaying Email configuration information:

The Show Email command displays Email configuration information.

To display the Email configuration information:

At the Sentry: prompt, type show email and press Enter.

Example

The following command displays the Email configuration information:

Sentry: show email

Email Configuration

Email Notifications: Enabled

SMTP Host: email.servertech.com

SMTP Port: 5555

'From' Address: [email protected]

Primary 'Send To' Address: [email protected]

Secondary 'Send To' Address: [email protected]

Include EVENT Messages: Enabled

Include AUTH Messages: Disabled

Include POWER Messages: Disabled

Include CONFIG Messages: Disabled

Intelligent IPM

Installation and Operations Manual

Advanced Operations  109

Upload/Download

The PDU family of product supports the ability to upload and download system configurations using a standard FTP client. This feature enables for backup and restoration of system configuration as well as upload of ‘template’ configurations to ease large initial equipment deployments.

Upload/Download Command Summary

Command

Set FTP Server

Show FTP

Description

Enables or disables the FTP server

Displays FTP configuration information

Sentry Integrated FTP Server

The PDU supports an integrated FTP Server which must be enabled for Upload/Download support. The PDU FTP Server supports a single user at a time. Once an administrative user has authenticated with the PDU FTP Server, standard FTP client commands can be used to upload or download Sentry configurations.

NOTE: The integrated FTP Server does NOT support web browser FTP file transfers.

A non-web-browser is required for all Upload/Download requests.

Enabling and disabling the FTP server:

The Set FTP Server command is used to enable or disable the integrated FTP server.

To enable or disable the FTP server:

At the Sentry: prompt, type set ftp server, followed by enabled or disabled and press Enter.

FTP Configuration Files

The PDU FTP server supports upload/download of two configuration files: CONFIG.BIN and NETWORK.INI. These files can be uploaded or downloaded using FTP PUT and GET operations.

 CONFIG.BIN

This file contains the entire configuration of the PDU excluding TCP/IP settings, serial/factory-only configurations, the x.509 certificate (SSL) and SSH keys. This file in encoded to keep all data (including usernames, passwords etc.) out of plain view. This file is

NOT editable.

 FTP.INI

This file contains only the FTP settings (FTP Host, username, password, filepath, filename and automatic updates support). This file is user readable and editable ‘plain text’ file.

 NETWORK.INI This file contains only the TCP/IP settings (IP address, subnet mask, gateway, DNS1 and

DNS2). This file is user readable and editable ‘plain text’ file.

 SNTP.INI

This file contains only the SNTP settings (SNTP Hosts and GMT offset). This file is user readable and editable ‘plain text’ file.

NOTE: The CONFIG.BIN file while encoded is not encrypted and susceptible to decoding using simple tools.

Server Technology recommends the secure storage of CONFIG.BIN backup images.

110  Advanced Operations

Intelligent IPM

Installation and Operations Manual

Upload/Download Process

GETting a configuration file (Download):

1. Open the FTP client.

In a Windows environment, in the Run window type ftp and press Enter.

2. At the prompt, type open, followed by the IP address of the PDU and press Enter.

FTP> open 12.34.56.78<Enter>

3. Authenticate with the appropriate administrative username and password.

4. At the prompt, type get, followed by the filename and press Enter.

FTP> get config.bin<Enter>

5. At the prompt, type close to close the connection to the PDU.

FTP> close

PUTting a configuration file (Upload):

NOTE: Uploading the CONFIG.BIN file takes considerably longer than the NETWORK.INI file.

When uploading both, Server Technology recommends uploading the NETWORK.INI file first.

1. Open the FTP client.

In a Windows environment, in the Run window type ftp and press Enter.

2. At the prompt, type open, followed by the IP address of the PDU and press Enter.

FTP> open 12.34.56.78<Enter>

3. Authenticate with the appropriate administrative username and password.

4. At the prompt, type put, followed by the filename and press Enter.

FTP> put network.ini<Enter>

5. At the prompt, type close to close the connection to the PDU and force a restart of the device.

FTP> close

Intelligent IPM

Installation and Operations Manual

Advanced Operations  111

Chapter 4: Appendices

Appendix A: Resetting to Factory Defaults

You can reset the non-volatile RAM that stores all configurable options. This clears all administrator –editable fields and reset all command line configurable options to their default values, including all user accounts.

You can reset the unit to factory defaults from the command line or the web interface, or by pressing the Reset button.

You must have administrator-level privileges to issue the command. Using the Reset button can be necessary when a forgotten password prevents administrator login. Each of the methods updates the current working configuration to the factory defaults.

Reset to factory defaults

NOTE: Resetting the unit resets all TCP/IP and Telnet/Web configurations. Reconfiguring the TCP/IP and Telnet/web settings will be required.

From the Web interface

On the Restart page in the Tools section of the Web interface, select Restart and reset to factory defaults from the dropdown menu and click Apply.

From the command line

At the Switched CDU: prompt, type restart factory and press Enter.

Using the reset button

Locate the recessed Reset button directly beside the Serial & Ethernet ports. You will need a non-conductive, nonmetallic tool that fits inside the recess.

NOTE: This method will not work if you disable the Reset button.

Insert the tool in the recess, then depress and hold the reset button for at least ten seconds.

NOTE: If you press and hold the Reset button for more than 15 seconds, the reset will terminate.

Reset to factory defaults, except network settings

From the Web interface

On the Restart page in the Tools section of the Web interface, select Restart and reset to factory defaults, except

network from the drop-down menu and click Apply.

From the command line

At the Switched CDU: prompt, type restart factory keepnet and press Enter.

112  Appendices

Intelligent IPM

Installation and Operations Manual

Appendix B: Uploading Firmware

You can upload new versions of firmware using File Transfer Protocol (FTP). This allows access to new firmware releases for firmware improvements and new features additions.

NOTE: To begin an FTP upload session, you must first configure the FTP Host address, username/password, filename and filepath.

You can initiate an FTP upload session by issuing a command or from the Web interface. You must have administratorlevel privileges to initiate an upload.

Initiate an FTP upload session from the Web interface

On the Restart page in the Tools section of the Web interface, select Restart and upload firmware via FTP from the drop-down menu and press Apply.

Upon issuing this command the unit will restart and upload the firmware file specified with the FTP Filename command from the previously configured FTP Host.

Initiate an FTP upload session from the command line

The Restart FTPLoad command initiates an upload of firmware. Upon issuing this command the unit will restart and upload the firmware file specified with the FTP Filename command from the previously configured FTP Host.

To initiate an FTP firmware upload session:

At the Sentry: prompt, type restart ftpload and press Enter.

Intelligent IPM

Installation and Operations Manual

Appendices  113

Appendix C: Technical Specifications

Branch Circuit Protection

Server Technology PDUs are equipped with one of several types of Branch Circuit Protection, including internal fuses, retractable fuse holders, and circuit breakers, as illustrated below.

These fuses and circuit breakers meet the strict safety requirements of UL 60950-1 and EN 60950-1 for Branch Circuit

Protection.

Circuit Breaker

If a circuit breaker is tripped, it can be reset by pressing or switching it back ON once the cause of the overload or short circuit has been identified, removed, or resolved. Intelligent PDUs with branch circuit sensing will display a flashing FE on the input current LED(s) to indicate Fuse Error.

Alternatively, the circuit breaker can be turned OFF manually by inserting a slotted or flat-blade tool into the OFF switch as shown in the illustration on the left.

It is not necessary to disconnect the AC power source to perform this operation.

NOTE:

This circuit breaker contains no user-serviceable parts. Do not open or disassemble this part.

114  Appendices

Intelligent IPM

Installation and Operations Manual

Compact Fuse Holder

The Compact Fuse Holder is a UL 98 listed Fused Disconnect Switch that allows the user to turn OFF the branch circuit and safely service the fuse without having to disconnect the PDU AC power source prior to performing this operation.

To help identify which fuse is open, blown, or missing, the Open Fuse Indicator

Light glows

orange

when the PDU is powered and the Switch Handle is in the ON position.

Additionally, intelligent PDUs with branch circuit sensing will display a flashing

FE on the input current LEDs to indicate Fuse Error.

To service the fuse or turn OFF the branch, rotate the Switch Handle toward the Fuse Access Door.

Next, rotate the Fuse Access Door counter clock-wise until it opens.

Only replace the fuse with the same size, type, and ratings as the original fuse.

Reverse these steps after the new fuse(s) is installed.

CAUTION:

 Failure to replace the fuse with the same size, type, and ratings will damage the PDU and the connected and nearby

equipment, and will cause electrical shock, fire, explosion, or injury/death.

 Do not attempt to open the Fuse Access Door without first setting the Switch Handle in the OFF position. Forcibly

rotating the Fuse Access Door will damage the fused holder.

Intelligent IPM

Installation and Operations Manual

Appendices  115

Fuse Retractor, Fuse Access Window, and Fuse Access Cover

The PDU AC power source must be disconnected prior to servicing a unit with the Fuse Retractor,

Fuse Access Window, and Fuse Access Cover

.

Intelligent PDUs with branch circuit sensing will display a flashing FE on the input current LEDs to indicate

Fault Error.

For the fuse retractor, rotate the fuse holder exposing the fuse.

For the fuse access window or cover, remove the screws that secure the plastic cover.

Once the fuses are exposed, carefully remove and replace with a new one of the same size, type, and ratings as the original. A fuse puller may be needed for fuse access windows and covers.

Reverse these steps after the new fuse(s) is installed.

CAUTION:

 Failure to replace the fuse with the same size, type, and ratings will damage the PDU and the connected and nearby

equipment, and will cause electrical shock, fire, explosion, or injury/death.

Time-Delay Fuses

– Class G

NOTE: Server Technology PDUs ship with Bussman SC-20 fuses.

Ampere Rating Voltage Interrupting Rating

20 A 600 Vac 100,000 A RMS Sym. AC

* Cooper Bussman Technical Data Sheet 1024

Bussman Part No.

*

SC-20

Server Technology Part No.

FUSE-SC20G

For technical support or service with time-delay fuses, contact Server Technology as follows:

Experience Server Technology's FREE Technical Support

Server Technology understands that there are often questions when installing and/or using a new product. Free Technical

Support is provided from 8 a.m. to 5 p.m. PST, Monday through Friday. After-hours service is provided to ensure your requests are handled quickly no matter what time zone or country you are located in.

Server Technology, Inc.

1040 Sandhill Drive Tel: 1-800-835-1515 Web: www.servertech.com

Reno, Nevada 89521 USA Fax: 775-284-2065 Email: [email protected]

116  Appendices

Intelligent IPM

Installation and Operations Manual

Data Connections

RS-232 port

Intelligent IPMs are equipped standard with an RJ45 DTE RS-232c serial port. This connector can be used for direct local access or from other serial devices such as a terminal server. An RJ45 crossover cable is provided for connection to an

RJ45 DCE serial port.

4

5

6

7

8

Pin DTE Signal Name

1 Request to Send RTS

2

3

Data Terminal Ready DTR

Transmit Data TD

Signal Ground

Signal Ground

Receive Data

Data Set Ready

Clear to Send

RD

DSR

CTS

Input/Output

Output

Output

Output

Input

Input

Input

8 7 54321

RJ45 to DB9F serial port adapter

Additionally, an RJ45 to DB9F serial port adapter is provided for use in conjunction with the RJ45 crossover cable to connect to a PC DB9M DCE serial port. The adapter pin-outs below reflect use of the adapter with the provided RJ45 crossover cable.

Input/Output

3

4

5

6

7

8

Pin DCE Signal Name

1

2 Receive Data RD

Transmit Data TD

Data Terminal Ready DTR

Signal Ground

Data Set Ready

Request to Send

Clear to Send

DSR

RTS

CTS

Output

Input

Input

Output

Input

Output

5

9

4

8

3

7

2

6

1

LED Indicators

Outlets

Units are equipped with a status LED for each power receptacle. A lit/on LED indicates that power is being supplied at the port and a darkened/off LED indicates that there is no power at the port.

Intelligent IPM

Installation and Operations Manual

Appendices  117

Regulatory Compliance

Product Safety

Units have been safety tested and certified to the following standards:

 USA/Canada

UL 60950-1:2007 and CAN/CSA 22.2 No. 60950-1-07

 European Union EN 60950-1:2006 + A11 +A1 + A12

This product is also designed for Norwegian IT power system with phase-to phase voltage 230V.

USA Notification

NOTE: This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part

15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at the user’s own expense.

Modifications not expressly approved by the manufacturer could void the user's authority to operated the equipment under

FCC rules.

Canadian Notification

This Class A digital apparatus complies meets all requirements of the Canadian Interference-Causing Equipment

Regulations.

Cet appareil numérique de la classe A respecte toutes les exigencies du Règlement sur le matériel brouilleur du Canada.

European Union Notification

Products with the CE Marking comply with both the EMC Directive (89/336/EEC) and the Low Voltage Directive

(73/23/EEC) issued by the Commission of the European Community.

Compliance with these directives implies conformity to the following European Norms:

 EN55022

Electromagnetic Interference

 EN55024

Electromagnetic Immunity

 EN60950-1 Product Safety

 EN61000-3 Harmonics and Flicker

Products with the following mark comply with the RoHS Directive (2002/95/EC) issued by the Commission of the

European Community.

Japanese Notification

この装置は、情報処理装置等電波障害自主規制協議会(VCCI)の基準に基づくクラスA情報技術装置

です。この装置を家庭環境で使用すると電波妨害を引き起こすことがあります。この場合には使用者が

適切な対策を講ずるよう要求されることがあります。

Recycling

Server Technology Inc. encourages the recycling of its products. Disposal facilities, environmental conditions and regulations vary across local, state and country jurisdictions, so Server Technology encourages consultation with qualified professional and applicable regulations and authorities within your region to ensure proper disposal.

Waste Electrical and Electronic Equipment (WEEE)

In the European Union, this label indicates that this product should not be disposed of with household waste. It should be deposited at an appropriate facility to enable recovery and recycling.

118  Appendices

Intelligent IPM

Installation and Operations Manual

Appendix D: Product Support Information

Warranty

For Server Technology warranty information, visit our website: www.servertech.com

Technical Support

Experience Server Technology's FREE Technical Support

Server Technology understands that there are often questions when installing and/or using a new product. Free Technical

Support is provided from 8 a.m. to 5 p.m. PST, Monday through Friday. After-hours service is provided to ensure your requests are handled quickly no matter what time zone or country you are located in.

Server Technology, Inc

1040 Sandhill Drive Tel: 1-800-835-1515

Reno, Nevada 89521 USA Fax: 775-284-2065

Return Merchandise Authorization

Web:

Email: www.servertech.com

[email protected]

If you have a product that is not functioning properly and needs technical assistance or repair, see the Server Technology

Return Merchandise Authorization process at:

www.servertech.com

Intelligent IPM

Installation and Operations Manual

Appendices  119