HydroLevel HydroStat 3150 Temperature Limit Control Installation Instructions and Operating Manual
Below you will find brief information for Temperature Limit Control HydroStat 3150. The HydroStat 3150 is a combination low water cut-off and universal temperature limit control for oil-fired boilers. It features a digital display for easy temperature monitoring and adjustment. The HydroStat 3150 also has a thermal pre-purge feature to conserve fuel and meet DOE regulations.
PDF
Download
Document
Advertisement
Advertisement
Page 1 MODEL 3150 Combination Low Water Cut-Off & Universal Temperature Limit Control for Oil-Fired Boilers INSTALLATION INSTRUCTIONS and OPERATING MANUAL • Replaces Common Aquastat* Models – Can be installed on existing immersion wells to replace both cold-start and triple-action Aquastats®. Industry standard wiring designations make change-outs quick and easy. • Digital Display – Easy to read LED continually displays boiler temperature. Also displays temperature limit and differential settings during adjustment. 120 VAC Operating Voltage • Easy to Set – Dials for setting temperature limits and differentials eliminate complicated programming. PATENT NOS. 7,891,572; 8,931,708 • Thermal Pre-Purge Feature – Conserves fuel and meets 2012 DOE regulations by circulating latent heat in the boiler to the heating zone before firing the burner. • *Aquastat is a registered trademark of Honeywell International, Inc. Dual Function Design Temperature Limit Control Designed for cold start and tankless coil boilers. Low Water Cut-Off Provides protection against potentially dangerous low water conditions when installed with the Hydrolevel Electro-Well™ (see page 2 for details). Electrical shock hazard. To prevent electrical shock, death or WARNING equipment damage, disconnect power supply before installing or servicing control. Only qualified personnel may install or service this control in To prevent serious CAUTION burns, boiler should be thoroughly cooled before installing or accordance with local codes and ordinances. Read instructions completely before proceeding. servicing control. Frozen pipes/water damage. Central heating systems are prone to shut down as a result of power or fuel outages, WARNING safety related fault conditions or equipment failure. Installation of freeze protection monitoring or other precautions is recommended for unattended dwellings in climates subject to sustain below-freezing temperatures. 126 Bailey Road, North Haven, CT 06473 • Phone (203) 776-0473 • FAX (203) 764-1711 • www.hydrolevel.com Page 2 IMMERSION WELLS Fuel Smart HydroStat can be installed on a Hydrolevel Electro-Well™ or on an existing immersion well already in the boiler. IMPORTANT: The control will only provide low water cut-off protection when installed on an Electro-Well™. Installing HydroStat with Hydrolevel Electro-Well™ Installing HydroStat with Standard Immersion Well When installed on an Electro-Well™ (sold separately), the Low Water Cut-Off function is automatically activated. Heat transfer grease should not be used. NOTE: For proper operation, there must be 1/2" clearance between the copper well tube and any furnace within the boiler. NOTE: When installed on a standard immersion well, the “LWCO Active” LED will not illuminate. See Electro-Well™ models on page 11. MOUNTING THE CONTROL IMPORTANT Make sure that the immersion well or Electro-Well™ is installed in the boiler manufacturer’s designated temperature limit control tapping. NOTE: If installing an Electro-Well, pipe sealing compound should be used. Teflon tape is not recommended. STEP 1 Two mounting positions are available on the back of the control (Fig. 1). Select which of the two positions (2 knockouts) is best for the location of the control. Remove the knockout. STEP 2 Place control on the well. While holding box against well nut, tighten well clamp screw. (Fig. 2) STEP 3 Insert sensor ALL THE WAY into well through the knockout (A or B) you have chosen. (Fig. 3) BACK OF HYDROSTAT BOX FIG. 1 FIG. 2 FIG. 3 IMPORTANT – Sensor must be inserted all the way into the well for proper operation. CORRECT INCORRECT NOTE: In the case of space restrictions, the Fuel Smart HydroStat control may be mounted in a horizontal orientation without any loss of function. Hydrolevel recommends vertical mounting, when possible, for proper orientation of LED display. REMOTE MOUNTING KITS are available separately for mounting the Fuel Smart HydroStat control box in a remote location. Each kit includes mounting hardware and a remote sensor. See page 12 for kit options. 2 Page 3 WIRING shock hazard. To prevent electrical shock, death or equipment damage, disconnect power supply before WARNING Electrical installing or servicing this control. STEP 1 Connect 120 VAC Hot to terminal L1. Connect 120 VAC Neutral to terminal L2. Disconnect means and overload protection as required (provided by others). STEP 4 Connect the thermostat to STEP 2 Connect the circulator to C1 and C2. (C2 is neutral.) Multi-Zones T and T. SCHEMATIC/LADDER DIAGRAM 3 STEP 3 Connect the burner circuit to B1 and B2. (B2 is neutral.) Adding additional zones. Page 4 SETTING THE CONTROL Diagnostic LEDs Test/Settings Button Dynamic Display Water Temperature and Real Time Verification of Setting Adjustments. Low Temperature Limit Setting (OFF or 110°-200°F) Jumper Factory OFF Low Temperature Differential Setting (10°-30°F) High Temperature Limit Setting (100°-220°F) Factory 190°F Factory 10°F High Temperature Differential Setting (10°-30°F) Factory 10°F To set COLD START operation Operates on call for heat only. Low Temperature Limit Make sure Low Temperature Limit is turned fully counter-clockwise (OFF position). Low Temperature Differential No change is required. High Temperature Limit (factory setting = 190°F) Adjust setting until desired temperature is displayed. High Temperature Differential (factory setting = 10°F) Using a small screwdriver, adjust setting until desired differential is displayed. To set WARM START operation NOTE: Be careful not to select overlapping temperature settings. For example: If the HIGH TEMPERATURE LIMIT is set at 190°F with a HIGH TEMPERATURE DIFFERENTIAL set at 20°F, then the LOW TEMPERATURE LIMIT needs to be set at 170°F (190°F - 20°F = 170°F) or below. IMPORTANT: To prevent flue gas condensation and reduce fatigue caused by thermal cycling on conventional (non-condensing) boilers, both HIGH and LOW LIMIT set points should be 150°F or above (Limit Setting - Differential Setting ≥ 150°F). Boiler manufacturer’s temperature requirements supercede these recommendations. OPERATION 4 Maintains temperature for domestic hot water. Low Temperature Limit Adjust setting until desired temperature is displayed. Prior to adjusting, remove the jumper located at the top right corner of the circuit board (not equipped on all units). IMPORTANT: If low limit temperature cannot be set above 140°F, remove jumper. Low Temperature Differential Using a small screwdriver, adjust setting until desired differential is displayed. High Temperature Limit (factory setting = 190°F) Adjust setting until desired temperature is displayed. High Temperature Differential (factory setting = 10°F) Using a small screwdriver, adjust setting until desired differential is displayed. Page 5 OPTIONAL FEATURES NOTE: The Program Mode – – is accessed by turning the LO TEMP dial to a position just above OFF. Thermal Pre-Purge Thermal Pre-Purge is designed to maximize boiler efficiency. When activated, the control will supply latent heat that may remain in the boiler from a previous run cycle to the heating zone that is now calling. The control monitors how quickly the boiler temperature is declining and activates the burner only when it determines that the latent heat is insufficient to satisfy the call. During the purge cycle the display will indicate . This feature works with single-zone and multi-zone heating systems utilizing circulators or zone valves. No change in wiring is needed. To activate Thermal Pre-Purge 1. Turn the LO TEMP dial to access the Program Mode – indicated in the display as 2. Turn the HI TEMP dial to select feature 3. Push the Test/Settings Button to turn Thermal Pre-Purge or 4. Reset LO TEMP and HI TEMP settings to desired temperatures (see page 4) Degrees Fahrenheit or Celsius The control has the ability to operate in degrees Fahrenheit or Celsius. When operating in Celsius, a play next to the temperature whenever the temperature is below 100 degrees. will appear in the dis- To change between degrees Fahrenheit and degrees Celsius 1. Turn the LO TEMP dial to access the Program Mode – indicated in the display as 2. Turn the HI TEMP dial to select feature 3. Push the Test/Settings Button to for Celsius or for Fahrenheit 4. Reset LO TEMP and HI TEMP settings to desired temperatures (see page 4) Manual Reset Low Water Cut-Off The low water cut-off operation on the HydroStat can be set to operate in automatic (default) or manual reset mode. When in manual reset mode, the control will shut-down the burner immediately when a low water condition is detected. If the low water condition is sustained for 30 seconds, the low water light will blink, indicating that the control has locked out the burner. The control can only be reset by pushing the Test/Settings button on the top of the control. The manual reset feature meets CSD-1 code requirements. IMPORTANT: The system must be checked by a qualified heating professional prior to resuming operation. WARNING: DO NOT ADD WATER UNTIL THE BOILER HAS FULLY COOLED. To activate Manual Reset LWCO mode 1. Turn the LO TEMP dial to access the Program Mode – indicated in the display as 2. Turn the HI TEMP dial to select feature 3. Push the Test/Settings Button to for Automatic Reset Mode or for Manual Reset Mode 4. Reset LO TEMP and HI TEMP settings to desired temperatures (see page 4) To Test the Manual Reset Feature: Press and hold the Test/Settings button located on the top of the control for 30 seconds to simulate a low water condition. After 30 seconds, the Low Water light will blink indicating that the control is locked out. To reset the lock-out condition, press the Test/Settings button momentarily. MORE OPTIONAL FEATURES ON NEXT PAGE 5 Page 6 Circulator Activation Options When in the default mode, the HydroStat activates the circulator (C1/C2 contacts) on calls to TT. The control can be programmed to activate the circulator on calls to ZC/ZR in place of, or in addition to, calls to TT. To change how the Circulator is activated 1. Turn the LO TEMP dial to access the Program Mode – indicated in the display as 2. Turn the HI TEMP dial to select feature 3. Push the Test/Settings Button to select between the following options: - Circulator on TT call only - Circulator on ZC/ZR call only - Circulator on both TT & ZC/ZR calls 4. Reset LO TEMP and HI TEMP settings to desired temperatures (see page 4) Restore Factory Default Settings To restore all features to the factory default settings (see following chart for default settings) 1. Turn the LO TEMP dial to access the Program Mode – indicated in the display as 2. Turn the HI TEMP dial to select feature 3. Push the Test/Settings Button to to reset all features to the default settings. 4. Reset LO TEMP and HI TEMP settings to desired temperatures (see page 4) Dial Setting Feature Options Thermal Pre-Purge Fahrenheit or Celsius Description Purge Inactive Purge Active Degrees Fahrenheit Degrees Celsius LWCO Manual or Automatic Reset Automatic Reset Manual Reset Circulator Options Circulator operation on TT call only Circulator operation on ZC/ZR call only Circulator operation on call from either Not available on this control Not available on this control Not available on this control Not available on this control Restore Factory Defaults Restore Defaults Do Not Restore Defaults SEE PAGE 4 FOR ADDITIONAL SETTINGS 6 Default Setting Page 7 LED LEGEND TEST/SETTINGS Button TEMP ACTIVE Indicates that the HydroStat control is powered and that the temperature function is active. To Test Low Water Cut-Off: Press and hold the Test/Settings button for 5 seconds. The display will read LCO. TEMP HIGH TEMP Illuminates when the boiler water temperature reaches the high limit setting. It will remain lit until the water temperature falls below the high limit setting less the differential setting. The HydroStat control will prevent burner operation while this LED is on. NOTE: This LED illuminates regularly during normal boiler operation. LWCO TEST 0000 The red Low Water light should illuminate and the burner circuit (B1 and B2) should de-energize. NOTE: The control must be installed with a Hydrolevel Electro-Well for low water cut-off functionality (see page 1 for more details). LWCO ACTIVE Indicates that the low water cut-off To View Current Settings: Press and release the Test/Settings Button in short intervals to sequentially display the following settings: (LWCO) function of the HydroStat control is active. When the control is installed with a Hydrolevel Electro-Well, this LED will be on at all times when the control is powered. NOTE: If the control was installed with a well other than the Electro-Well, this LED will not illuminate. This indicates that the control is providing temperature function only. HIGH LIMIT SETTING 00 HIGH DIFFERENTIAL SETTING LWCO LOW WATER Indicates that the boiler is in a LOW LIMIT SETTING low water condition. The HydroStat control will prevent burner operation during this condition. If the LOW WATER light is blinking, the control has been programmed to provide lockout protection in the event a low water condition is detected (see Manual Reset Low Water Cut-Off on page 5). Pressing the TEST/SETTINGS button will reset the control. 00 00 LOW DIFFERENTIAL SETTING 00 The display will return to boiler temperature (default) if Test/Settings Button in not pressed for 5 seconds. IMPORTANT: The system must be checked by a qualified heating professional prior to resuming operation. WARNING: ALLOW THE BOILER TO FULLY COOL BEFORE ADDING WATER. 7 Page 8 TROUBLESHOOTING Burner Will Not Fire See Flow Chart 1, page 9 Burner Will Not Shut Down See Flow Chart 2, page 10 Temperature Display Exceeds High Limit Setting Under normal operation, boiler temperature will continue to rise after the control shuts off the burner. This condition, known as “thermal stacking”, results from hot boiler surfaces continuing to release heat into the boiler water. No or Insufficient Domestic Hot Water If the boiler has a tankless coil make sure the low limit setting on the HydroStat is set properly. NOTE: If the low limit setting is dialed fully counter clockwise, it will shut off the low temperature maintenance feature and will function as a cold start control. Faster hot water response may also be achieved by turning off the Thermal Pre-Purge Feature (see page 4). If boiler is operating in conjunction with an indirect water heater, check to be sure the temperature control on the indirect tank is set properly. Make sure any valves in between domestic hot water heating device, boiler, and hot water taps are open. Boiler Will Not Maintain Low Limit Temperature Check for overlapping high temperature setting. If the high limit setting is set below the low limit setting, the control will default to the high limit setting and the corresponding high limit differential setting. Temperature Display Differs from Boiler T&P Gauge Temperature Reading Temperature variances can result from differing water temperatures within the boiler or different reaction times of the two devices. If the HydroStat temperature is significantly below the T&P gauge temperature, make sure the thermistor is inserted all the way to the end of the well. LWCO “Active” Light (Green LED) Is Not On The HydroStat will only provide low water cut-off functionality when used in conjunction with an insulated Electro-Well™. When attached to a standard immersion well, the LWCO “Active” light will remain off and the HydroStat will provide temperature functionality only. Low Water Light (Red LED) Is On or Blinking WARNING: A low water condition is a serious and potentially dangerous condition. Do not attempt to add water to a hot boiler. Allow the boiler to fully cool before adding water. When Installed on an Electro-Well™ When the LOW WATER light is on, this indicates that the control is not detecting water in the boiler. When the LOW WATER light is blinking, this indicates that the control has been programmed to provide low water lock-out protection and is currently locked out (see Manual Reset Low Water Cut-Off on page 5). Pressing the TEST/SETTINGS button after the low water condition is resolved will reset the lock-out condition. 1. If the light is on and the heating system is filled with water, pull the sensor out of the well and inspect it. Make sure that the metal clip is protruding enough to come in contact with the inside of the well tube. Check that the well does not have excessive build-up of heat transfer grease that may interfere with the clip contacting the well. 2. Remove well and examine for excessive residue build-up. Clean and re-install. When Installed on a Standard Immersion Well If either LWCO LED lights are illuminated and the control is installed on a standard immersion well, this is a false reading caused by a loss of continuity between the sensor and the inside of the well tube. Follow steps 1 and 2 (above) to ensure that the metal sensor head is making good contact with the inside surface of the copper well. 8 Page 9 Troubleshooting Flow Chart 1 – Burner Will Not Fire Does the Display Read YES The Control is Purging Latent Heat from the Boiler. NO The Control is Not Powered. ? The Thermal Pre-Purge feature holds off the burner until the control determines if the latent heat in the boiler can satisfy the heat call. NO Is the Green LED (TEMP ACTIVE) On? The Temp Active LED will be on at all times when the control is powered. Check for 120 VAC on terminals L1 and L2. YES CAUTION – ALWAYS ALLOW A BOILER TO COOL BEFORE ADDING WATER Is the Red LED On? YES The Control is Sensing Low Water. YES The Control is Sensing High Temperature. The burner will not fire until the low water condition is satisfied. Check that the system is filled with water. Check that the sensor is inserted fully into the well and contact between its spring clip and the copper well tube is made. Check that the control is tightly clamped to the well. Also see page 8 for additional troubleshooting information. NO Is the Yellow LED On? The burner will not fire until the boiler water has dropped to the high limit differential set-point. See HydroStat Settings chart. Check that the high temperature setting is correct. NO Is the Thermostat (T-T) Calling for Heat? NO YES Is There 120 VAC Between B1 and B2? Is the External Zone (ZC-ZR) Calling for Heat? NO Is the Low Limit Dial Set to OFF? YES YES The Control is Operating Properly. YES NO HydroStat is supplying 120 VAC to the burner circuit. Recheck wiring and operation of burner and other limit controls. NO Replace Control When the low temperature setting is set to OFF, the HydroStat will act as a cold start control. The burner will not fire unless there is a call from the thermostat (T-T) or an external zone (ZC-ZR). Set thermostat to call for heat. Burner should fire. If the boiler has a tankless coil, set the Low Temperature Limit to maintain temperature. If both the red and yellow LEDs are off and there is a call to fire the burner, there will be 120 VAC on terminals B1 and B2. If 120 VAC is not present, the control should be replaced. 9 Page 10 Troubleshooting Flow Chart 2 – Burner Will Not Shut Down Is the Red LED On? YES The Control is Sensing Low Water. WARNING! TURN OFF POWER TO BURNER IMMEDIATELY! CAUTION – ALWAYS ALLOW A BOILER TO FULLY COOL BEFORE ADDING WATER. NO Is the Yellow LED On? YES The Control is Sensing High Temperature. YES The Control is Operating Normally. Recheck wiring. Make sure that burner is wired to B1. Burner should never fire when red or yellow LED is lit. NO Is the Thermostat (T-T) Calling for Heat? NO Is the External Zone (ZC-ZR) Calling for Heat? The burner will continue to fire when there is a call from the thermostat or external zone. YES The Control is Operating Normally. NO Check temperature display. When the Low Limit is set, the HydroStat will fire the burner until the temperature reaches the Low Limit Setting. NO Is the Low Limit Dial Set to OFF? YES Is there 120 VAC between B1 and B2? NO When there is no call to fire the burner, the voltage should be 0 volts between B1 and B2. Recheck Wiring. Make sure the burner is wired to B1. YES Replace Control. If there is no call for heat (from T-T, ZC-ZR or Low Limit), there should be 0 VAC between B1-B2. If there is voltage between B1-B2, the control should be replaced. 10 Page 11 ELECTRO-WELLS HydroStat installed with Electro-Well™ When installed with the Hydrolevel Electro-Well, HydroStat will provide both temperature and low water cut-off functionality. If the control was supplied by the boiler manufacturer, it was installed with an ElectroWell. The Electro-Well is available separately for field installations. 1/2" CLEARANCE 1/2" CLEARANCE 1/2" CLEARANCE Electro-Well™ Models 11 IMPORTANT: For proper operation of the low water cut-off function, there must be a minimum of ½" clearance between the copper well tube and any surface within the boiler. Page 12 MAINTENANCE Remove the Electro-Well from the heating system every five years and clean any scale or sediment deposits from all parts that are exposed to the boiler water. After cleaning, reinstall the well using pipe sealing compound. Teflon tape is not recommended. REMOTE MOUNTING KITS Part No. Description Part No. Description 48-101 48-102 HydroStat Remote Mount Kit with 24" sensor HydroStat Remote Mount Kit with 48" sensor 48-103 48-104 48-121 HydroStat Remote Mount Kit with 10' sensor HydroStat Remote Mount Kit with 20' sensor HydroStat Pipe Mounting Kit with 48" sensor DIMENSIONS SPECIFICATIONS HYDROSTAT MODEL 3150 Input voltage Burner contacts Circulator contacts Operating range – low limit Operating range – high limit Operating range – differential Thermostat heat anticipator setting 120 VAC, 60 HZ 7.4 FLA, 44.4 LRA@120 VAC 5.8 FLA, 34.8 LRA@120 VAC Off or 110°F (43°C) - 200°F (93°C) 100°F (38°C) - 220°F (104°C) 10°F (6°C) - 30°F (17°C) 0.2A LIMITED MANUFACTURER’S WARRANTY We warrant products manufactured by Hydrolevel Company to be free from defects in material and workmanship for a period of two years from the date of manufacture or one year from the date of installation, whichever occurs first. In the event of any claim under this warranty or otherwise with respect to our products which is made within such period, we will, at our option, repair or replace such products or refund the purchase price paid to us by you for such products. In no event shall Hydrolevel Company be liable for any other loss or damage, whether direct, indirect, incidental or consequential. This warranty is your EXCLUSIVE remedy and shall be IN PLACE OF any other warranty or guarantee, express or implied, including, without limitation, any warranty of MERCHANTABILITY or fitness for a particular purpose. This warranty may not be assigned or transferred and any unauthorized transfer or assignment thereof shall be void and of no force or effect. 126 Bailey Road, North Haven, CT 06473 • Phone (203) 776-0473 • FAX (203) 764-1711 • www.hydrolevel.com 12 082517 ">
Advertisement
Key features
- Digital display for boiler temperature
- Easy to set temperature limits and differentials
- Thermal pre-purge feature
- Low water cut-off protection
- Dual function design for cold start and tankless coil boilers
Frequently asked questions
The HydroStat 3150 operates on 120 VAC.
The thermal pre-purge feature conserves fuel and meets DOE regulations by circulating latent heat in the boiler to the heating zone before firing the burner.
The low water cut-off function provides protection against potentially dangerous low water conditions when installed with the Hydrolevel Electro-Well. It will shut down the burner if a low water condition is detected.
The low limit setting ranges from Off to 200°F (93°C), the high limit setting ranges from 100°F (38°C) to 220°F (104°C), and the differential setting ranges from 10°F (6°C) to 30°F (17°C).