Data Sheet K85001-0606 -- Smoke Detectors with Auxiliary Functions

Data Sheet K85001-0606 -- Smoke Detectors with Auxiliary Functions
Kidde Catalog u Conventional Initiating
Technology that saves lives
Smoke Detectors
with Auxiliary
Functions
500 Series
S1125
Overview
Standard Features
500 Series two-wire conventional photoelectric smoke detectors
bring together trusted technology and a full line of features that
meet the demands of every type of application. The 500 offers
sounders in two-wire applications, specifically to meet residential
code requirements.
• Remote maintenance (CleanMe®) reporting and builtin drift compensation reduces false alarms
Kidde is also proud to offer proven technology like CleanMe®,
dust compensation, field replaceable optical chambers, and selfdiagnostics. CleanMe® is only available on the 500 2-wire models
and will communicate with compatible FACPs when servicing is
required.
500 Series detectors work on a light-scattering principle. A pulsed
infrared light-emitting diode serves as the light source, and a highspeed photo diode as the sensing element. This design has superior protection against nuisance alarms caused by dust, insects,
RF interference, and ambient light.
The proprietary optical chamber is field replaceable. In the event of
a confirmed alarm the LED will light continuously. The unit indicates trouble by flashing the LED every second. This meets the
NFPA 72 field sensitivity testing requirements.
7272-1657:
0277
• Self-diagnostics meets NFPA 72 sensitivity testing requirements without the need for external meters
• Field-replaceable optical chamber makes service fast and
simple
• Large SEMS screw terminals accept 12-18 AWG wire
• Small, low profile design blends with any environment
• Optional auxiliary functions include:
•Integral sounder with optional tandem interconnection
•Auxiliary relay Listed for applications such as elevator recall
•Fire system isolated heat integrated with nonlatching single station smoke alarm
•Integral fixed/ROR heat detectors
•Adaptor plate enables replacing 500 Series
with legacy 400 Series smoke detectors
Additional diagnostic information is activated by applying a magnet
near the detector’s integral reed switch. This initiates a self-diagnostic
routine and provides visual indication of sensitivity level, or if service
is required. The magnet test causes the LED to blink. The number of
blink counts corresponds to a smoke detector sensitivity range.
Models with a built-in 85dB sounders emit the temporal 3 pattern and can be easily tandemly interconnected using the 405-05
polarity reversal relay. This enables all detectors to sound when
the initiating detector sounds and meets the requirement of the
International Residential Building Code (IRC).
Page 1 of 4
K85001-0606
D ATA S H E E T
Not to be used for installation purposes. Issue 1
Application
Assembly
500 Series detectors are ideal for both retrofit applications and
new installations alike. They are particularly well-suited for installations where detector reliability is essential, but where typical analog/addressable devices may not be appropriate or feasible. With
their replaceable optical chambers, these detectors are equally
well-suited to dusty environments where detectors require frequent
cleaning.
Optional fixed temperature sensor
Diagnostic LED
Optional rate-of-rise sensor
Photoelectric sensor
Replaceable optical chamber
and bug screen
Detector cap
Mounting and Installation
500 Series detector bases mount directly to standard single-gang
electrical boxes, three-inch round, or four-inch octagonal boxes.
Detector heads simply twist onto the base. Heads are equipped
with a break-away locking tab, which prevents unauthorized removal. SEMS terminals accept 24 to 12 AWG field wiring.
Dimensions
2" (5cm)
5" (12cm)
Typical Wiring
Specifications
Electrical
Power Supply
Maximum ripple pk-pk (6/12/24V)
Typical average standby current
Typical alarm current (6/12/24V)
Auxiliary relay contacts
(521NCRXT only)
Photoelectric sensitivity
Environment
Operating temperature
Operating humidity range
RFI immunity
Page 2 of 4
8.5-33VDC (12/24 V operation)
polarity sensitive
10% (Vpk-pk)
70 μA
up to 60 mA max if not limited by
control panel
1.0 A @ 30 VDC; Form C
3.1% + 0.5 - 1.0%
32° to 100° F (0° to 37° C)
0 to 95% non-condensing
20 V/m min; 0-1000 MHz
Physical
Color
Field wiring size
Heat detector specifications
UL 2-wire compatibility identifiers
Sounder output (521NCSXT only)
Drift compensation adjustment
Detector head dimensions
Mounting dimensions
Regulations
Reset time
Listings
500N Series:
521B, 521BXT:
White
12-18 AWG (16-22 recommended)
Rate-of-Rise:
15° F/min and >105° F
(8.3° C/min and >40.6° C)
Fixed Threshold: 135° F (57.2° C)
S09A, S10A, S11A
85dB @ 10 feet
1.0% ft. max
5.5 D x 2" H (14.0 x 5 cm)
5.25" (13.3 cm) diameter;
0.3" (0.8 cm) height
1 second min
UL 268 cUL, CSFM
UL 268, CSFM
K85001-0606
D ATA S H E E T
Not to be used for installation purposes. Issue 1
Ordering Information
Model
Description
521B
521BXT
2-wire, photoelectric, 8.5-33VDC; UL 268, CSFM Listed
2-wire, photoelectric, 8.5-33VDC, fixed temp and rate-of-rise heat;
UL 268, CSFM Listed
2-wire, photoelectric, 8.5-33VDC, fixed temp and
rate-of-rise heat, aux. relay; UL 268, cUL, CSFM Listed
2-wire, photoelectric, 8.5-33VDC, fixed temp and rate-of-rise heat,
temporal 3 sounder; UL 268, cUL, CSFM Listed
521NCRXT
521NCSXT
Compatibility
S09A/S10A
S09A/S10A
Alarm Current
(mA)
5 min. - 60 max.
5 min. - 60 max.
S11A
15 min. - 60 max.
S10A
10 min. - 60 max
Reverse
polarity (mA)
10
Note: Only 500 Series 2-wire smoke detectors are CleanMe compatible.
Accessories
405-05
SM200-12PKG
SM-EXT1
211-10PKG
Page 3 of 4
Polarity reversal module enables sounder interconnection of all 4-wire smoke detectors, when initiating detector sounds all smokes
sound.
Smoke! in a Can® canned smoke for functional testing
Smoke! in a Can® extension tube
Replacement optical chambers (set of 10)
K85001-0606
D ATA S H E E T
Not to be used for installation purposes. Issue 1
Technology that saves lives
Contact us...
Email: kidde.fire@fs.utc.com
Web: Kidde.com/EngineeredSystems
Kidde is a UTC brand.
1016 Corporate Park Drive
Mebane, NC 27302
© 2016 United Technologies Corporation.
All rights reserved.
K85001-0606
D ATA S H E E T
Not to be used for installation purposes. Issue 1
10-27-16
Page 4 of 4