Knick VariTrans P 27000 Universal Isolated Signal Conditioner Owner Manual

Add to My manuals
12 Pages

Knick VariTrans P 27000 is a universal isolator designed for galvanic isolation and conversion of input signals from 0 ... ±10 V to output signals from 0 ... ±20 mA, with linear signal transmission. The broad-range mains adapter allows powering the device with voltages from 20 to 253 V AC/DC. It features easily accessible pluggable screw clamp terminals for convenient wiring.

advertisement

Knick VariTrans P 27000 Universal Isolated Signal Conditioner Owner Manual | Manualzz

VariTrans® P 27000-S007

Universal Isolators

TA-251.103-KNE01 20120802

1. Safety Information

The warning symbol on the device (exclamation point in triangle) means: Observe instructions!

Warning! Protection against electric shock

For applications with high working voltages, take measures to prevent accidental contact and make sure that there is sufficient distance or insulation between adjacent devices!

Caution!

Be sure to take protective measures against electrostatic discharge

(ESD) when handling the devices!

Caution!

The VariTrans® P 27000 universal isolators must be installed only by qualified and specially trained personnel authorized by the operating company.

Do not connect the device to power supply before it is professionally installed.

Do not change the measuring range during operation. Observe the national codes and regulations during installation and selection of cables and lines.

Equipment shall be provided with a means for disconnecting it from each operating energy supply source. The disconnecting means shall disconnect all current-carrying conductors. (It must be easily accessible and clearly identifiable by the operator.)

Mains supply must be protected by a fuse of 20 A max.

2

Warning! EXPLOSION HAZARD

Do not connect/disconnect equipment unless power has been removed or the area is known to be non-hazardous.

Warning! EXPLOSION HAZARD

Substitution of components may impair suitability for Class I,

Division 2.

Conditions for safe use (Haz. Loc.)

For the use in hazardous locations, this equipment is to be installed into suitable enclosure, providing a degree of protection not less than IP 54.

Devices containing user accessible switches and/or potentiometers: the device must be installed into an end-use enclosure with tool removable cover.

3

2. Intended Use

The special models P 27000-S007 universal isolators are used for galvanic isolation and conversion of input signals from 0 ... ±10 V to output signals from

0 ... ±20 mA. Signal transmission is linear. By means of the broad-range mains adapter, the units can be powered by voltages from 20 to 253 V AC/DC.

Connection is made using pluggable screw clamp terminals.

Warning against misuse

Do not operate the device outside the conditions specified by the manufacturer, as this might result in hazards to operators or malfunction of the equipment.

3. Configuration

3.1 Tools

A screwdriver with a width of 2.5 mm is required to open and adjust the unit and to connect the wires to the screw clamp terminals.

4

3.2 Opening the unit

Disengage the top part of the housing on both sides using the screwdriver.

Pull out the top part of the housing and the electronics section until they lock.

3.3 Settings

Adjust the output range using DIP switches

S1, S2 and S3 as shown in the table below.

Caution!

The special model P 27000-S007 may be used in this range only!

P27000H1-S007

Input Output S1

1 2 3 4 5 6 7 8 9 10

0 ... ± 10 V 0 ... ± 20 mA ON ON ON OFF OFF OFF ON OFF OFF OFF

Input Output S2

1 2 3 4 5

S3

1 2 3

0 ... ± 10 V 0 ... ± 20 mA OFF ON OFF ON ON OFF OFF OFF

5

4. Mounting

The universal isolators are mounted on standard TS 35 rails.

5. Electrical Connection

Terminal assignments

1 Do not connect

2 Do not connect

3 Input +

4 Input –

5 Output +

6 Output –

7 Power supply

8 Power supply

Wire cross-section max. 2,5 mm 2

Multi-wire connection max. 1 mm 2

(two wires with same cross-section)

AWG 30-12, tightening torque 0.7 Nm

Wiring has to be suitable for a temperature of min. 75 °C

Warning!

For applications with high working voltages, take measures to prevent accidental contact and make sure that there is sufficient distance or insulation between adjacent devices!

5.1 Power supply

22 to 230 V AC/DC ± 10 %, 0.9 W, AC 48 to 62 Hz, 2.5 VA,

(overvoltage category II)

6

6. Dimensions

111

Fixed screw clamp terminals

Metal lock for fastening on top-hat rail

All dimensions in mm

7

7. Declarations, Certificates and Approvals

CE marking

The EU Declaration of Conformity is included in the documentation.

The Statement of Conformity for ATEX Zone 2 apparatus is included in the documentation.

Open-type Process Control Equipment also listed

Proc. Contr. Eq. for Use in Haz. Loc.

File: E340287, E308146, E340288

GL

Certificate No. 42 843 - 02 HH

Environmental Category: D

Test Standard: Regulations of the Performance of Type Tests, Part 1

EN 61010-1

8. Order Information

Device Order No.

Pluggable screw clamp terminals

P 27000 H1-S007

8

P 27000-S007 Universal Isolator

9. Technical Data

Input data

Input

Overload

Output data

Output

Load

Offset error

Residual ripple

General data

Gain error

Temperature coefficient 2)

Cutoff frequency

Test voltage

Working voltage 3)

(basic insulation)

0 ... ±10 V limited by 250 V suppressor diode, max. permissible continuous current ≤ 3 mA

0 ... ±20 mA

≤12 V 1) (600 Ω at 20 mA)

20 µA approx. 20 mV rms

0,08 % meas. value typical additional error for AC (45 ... 65 Hz sinus)

1 % meas. value

< 50 ppm/K full scale approx. 16 kHz

5 kV~ input against output

4 kV~ output against power supply

1 kV~for overvoltage category II and pollution degree 2 to EN 61010-1

For applications with high working voltages, take precautions to prevent accidental contact and make sure that there is sufficient distance to adjacent devices or sufficient insulation between them.

9

Protection against electric shock

Design

Protection

Weight

3)

EMC 4)

Surge withstand

Ambient temperature

Ambient conditions

Power supply

Protective separation to EN 61140 by reinforced insulation according to EN 61010-1 up to 600 V AC/DC across input and output for overvoltage category II and pollution degree 2, up to 300 V AC/DC across output and ower supply for overvoltage category II and pollution degree 2.

For applications with high working voltages, take measures to prevent accidental contact and make sure that there is sufficient distance to adjacent devices or sufficient insulation between them.

2004/108/EC

EN 61326

EN 61326/A1

5 kV, 1.2/50 μs, to IEC 255-4

Operation

Transport and storage

-10 to +70 °C

-40 to +85 °C

Stationary application, weather-protected

Relative air humidity 5 ... 95 %, no condensation

Barometric pressure: 70 ... 106 kPa, altitude up to 2000 m

Water or wind-driven precipitation (rain, snow, hail) excluded

22 to 230 V AC/DC ± 10 %, 0.9 W, AC 48 to 62 Hz; 2.5 VA,

(overvoltage category II)

Modular housing with pluggable screw clamp terminals, see dimension drawing

IP 20 approx. 150 g

10

Explosion protection Europe:

USA:

Canada:

II 3G Ex nA IIC T4 Gc X

Class I Div.2 GRP A,B,C,D T4

Class I Zone 2 AEx nA IIC T4

Class I Zone 2 Ex nA IIC T4 X

Class I Div.2 GRP A,B,C,D T4

1) Higher output load on request

2) Average TC in specified operating temperature range -10 ˚C ... +70 ˚C.

3) cULus certification: Working voltage (basic insulation) up to 600 V, working voltage (reinforced insulation) up to 300 V across input and output, each for overvoltage category II and pollution degree 2

4) Slight deviations are possible while there is interference

11

Knick Elektronische Messgeräte

GmbH & Co. KG

Beuckestraße 22

D-14163 Berlin

Phone: +49 (0)30 - 801 91 - 0

Fax: +49 (0)30 - 801 91 - 200

Internet: http://www.knick.de

Email: [email protected]