UMG 96L / UMG 96 UMG 96L / UMG 96 – Universal measurement

UMG 96L / UMG 96 UMG 96L / UMG 96 – Universal measurement
UMG 96L / UMG 96
Threshold value
monitoring
Pulse outputs
UMG 96L / UMG 96 – Universal measurement device
Measuring accuracy
• Energy: Class 2
• Current .../1 A, .../5 A
• Voltage L - N: ± 1 %
Networks
• TN-, TT-Networks
2 digital outputs (UMG 96)
• Pulse output kWh / kvarh
• Switch output
1
UMG 96L / UMG 96
Areas of application
• Replaces analogue measurement devices
• Display and checking of electrical characteristics in energy distribution systems
• Limit value monitoring
Main features
Display selection and automatic display rotation
• Generous LCD display
• All measured values can be called up in factory setting
• Measured values that are not required can be hidden and displayed again
Operating hours counter
• The operating hours counter is active as soon as the device is switched on
• The time is measured with a resolution of 15 minutes
• Display in hours mode
Digital outputs for reactive or active energy
• Transmission of the reactive and active energy via digital outputs
• The active energy should be assigned to output 1 and the reactive energy
to output 2
2
Fig.: Effective power, all three phases at a glance
UMG 96L / UMG 96
Digital outputs for threshold values (UMG 96)
• Digital outputs also suitable for use as switch outputs
• Programming the digital outputs for threshold monitoring of
measurement data
• Assignment of a measured value (threshold value) per switch output
• The associated output reacts in response to the value exceeding or
dropping below the threshold value
• Transistor outputs
Fig.: Digital output for threshold value monitoring
Password
• 3-digit password protects against unauthorised changing
of the programming and configurations
• Changes in the following program menus can only be implemented after
entering the correct user password
• Password is not factory-programmed
Fig.: Password protection
3
UMG 96L / UMG 96
Dimension diagrams
96
All dimensions in mm
96
Side view UMG 96L / UMG 96
Cut out: 92
+0,8
x 92
+0,8
Rear view UMG 96L
Rear view UMG 96
mm
Typical connection
Loads
Loads
Digital outputs
UMG 96L
4
UMG 96 with 2 digital outputs
UMG 96L / UMG 96
Device overview and technical data
UMG 96L
Item number
UMG 96
52.14.001
52.14.005
52.09.001
Measured voltage
230 / 400 V AC
60 / 120 V AC
275 / 476 V AC
Operating voltage
196 ... 255 V AC
45 … 80 V AC
196 ... 275 V AC
Measured voltage input
Overvoltage category
300 V CAT III
150 V CAT III
300 V CAT III
Measured range, voltage L-N, AC (without potential transformer)
50 … 255 V AC
16 … 80 V AC
50 … 275 V AC
Measured range, voltage L-L, AC (without potential transformer)
87 … 442 V AC
28 …138 V AC
87 … 476 V AC
-
-
2
1%
1%
1%
Digital outputs
Number of digital outputs
General
Accuracy voltage measurement
General
Use in low and medium voltage networks
•
Accuracy current measurement
1%
Accuracy active energy (kWh, …/5 A)
Class 2
Number of measurement points per period
50
RMS - momentary value
Current, voltage, frequency
•
Active, reactive and apparent power / total and per phase
•
Power factor / total and per phase
•
Energy measurement
Active, reactive energy [∑ L1–L3]
•
Recording of the mean values
Voltage, current / actual and maximum
•
Active, reactive and apparent power / actual and maximum
•
Frequency / actual and maximum
•
Other measurements
Operating hours measurement
•
Technical data
Measurement in quadrants
4
Networks
TN, TT
Measured voltage input
Fig.: Example connection via three current transformers (UMG 96L)
Frequency measuring range
45 ... 65 Hz
Power consumption
approx. 0.1 VA / approx. 0.2 VA
Sampling frequency (50 Hz)
2.5 kHz / phase
Measured current input
Rated current
1/5A
Measurement range
0.02 ... 6 Arms
Overvoltage category
CAT III
Measurement surge voltage
4 kV
Power consumption
approx. 0.2 VA
Overload for 2 sec.
180 A (sinusoidal)
Sampling frequency (50/60 Hz)
2.5 / 3 kHz / Phase
Digital outputs*1
Switching voltage
max. 60 V DC, 5 – 24 V DC
Switching current
max. 50 mA Eff AC / DC
Pulse output (energy pulse)
max. 10 Hz
Maximum cable length
up to 30 m unscreened, from 30 m screened
Mechanical properties
Comment:
For detailed technical information please refer
to the operation manual and the Modbus address list.
• = included - = not included
*1 Refers exclusively to the UMG 96.
Weight
250 g
Device dimensions in mm (H x W x D)
96 x 96 x 48
Protection class per EN 60529
Front: IP50, Rear: IP20
Assembly per IEC EN 60999-1 / DIN EN 50022
Front panel installation
Connecting phase (U / I),
Single core, multi-core, fine-stranded
Terminal pins, core end sheath
0.08 to 2.5 mm²
1.5 mm²
5
UMG 96L / UMG 96
Environmental conditions
Temperature range
Operation: K55 (-10 ... +55 °C)
Relative humidity
Operation: 15 to 95 % (at 25 °C)
Operating height
0 ... 2,000 m above sea level
Degree of pollution
2
Installation position
user-defined
Electromagnetic compatibility
Electromagnetic compatibility of equipment
Directive 89/336/EEC
Electrical equipment for use within certain voltage limits
Directive 73/23/EEC
Equipment safety
Safety requirements for electrical
equipment for measurement, regulation, control
and laboratory use –
Part 1: General requirements
IEC/EN 61010-1
Part 2-030: Particular requirements for
testing and measuring circuits
IEC/EN 61010-2-030
Noise immunity
Industrial environment
IEC/EN 61326-1
Electrostatic discharge
IEC/EN 61000-4-2
Voltage dips
IEC/EN 61000-4-11
Emissions
Class B: Residential environment
IEC/EN 61326-1
Radio disturbanc voltage strength 30 – 1000 MHz
IEC/CISPR11/EN 55011
Radiated interference voltage 0.15 – 30 MHz
IEC/CISPR11/EN 55011
Safety
Europe
CE labelling
Comment:
For detailed technical information please refer to the operation manual and the Modbus address list.
• = included - = not included
6
Smart Energy &
Power Quality Solutions
Janitza electronics GmbH
Vor dem Polstück 1
D-35633 Lahnau
Germany
Sales partner
Tel.: +49 6441 9642-0
Fax: +49 6441 9642-30
[email protected]
www.janitza.com
Version 01/2015 • Subject to technical alterations.