HP StorageWorks Disk Array XP1024: Site Preparation Guide

HP StorageWorks Disk Array XP1024: Site Preparation Guide

HP StorageWorks

Disk Array XP1024 site preparation guide

fourth edition (May 2005)

part number: A7906-96011

This guide describes how to prepare a site for the installation of an HP Disk Array XP1024.

© Copyright 2002-2005 Hewlett-Packard Development Company, L.P., all rights reserved

Hewlett-Packard Company makes no warranty of any kind with regard to this material, including, but not limited to, the implied warranties of merchantability and fitness for a particular purpose. Hewlett-Packard shall not be liable for errors contained herein or for incidental or consequential damages in connection with the furnishing, performance, or use of this material.

This document contains proprietary information, which is protected by copyright. No part of this document may be photocopied, reproduced, or translated into another language without the prior written consent of Hewlett-Packard.

The information contained in this document is subject to change without notice.

HP-UX is a registered trademark of Hewlett-Packard Company.

All other product names mentioned herein may be trademarks of their respective companies.

Hewlett-Packard Company shall not be liable for technical or editorial errors or omissions contained herein. The information is provided “as is” without warranty of any kind and is subject to change without notice. The warranties for Hewlett-Packard Company products are set forth in the express limited warranty statements accompanying such products. Nothing herein should be construed as constituting an additional warranty.

Printed in the U.S.A.

HP StorageWorks Disk Array XP1024: Site Preparation Guide fourth edition (May 2005) part number: A7906-96011

2

HP StorageWorks Disk Array XP1024: Site Preparation Guide

Contents

Contents

About this guide 5

Intended audience 5

Related documentation 5

Conventions 5

Getting help 6

HP technical support 6

HP storage website 7

HP authorized reseller 7

Revision history 8

Warranty statement 9

1 Introduction 11

2 Site prep team and tasks 13

The site prep team 14

Site prep technical tasks 16

Site planning timetable 18

3 Preparing for installation 19

Safety requirements 20

General computer room requirements 21

Physical requirements 24

HP Disk Array XP512 DKU physical requirements 27

Service and cable routing space requirements 29

Data comm requirements 36

Phone Home with Continuous Track 36

HP StorageWorks Command View XP and your public Intranet 37

Outside phone line 37

3

4

Electrical requirements 38

Line voltage 38

Branch Circuit Breakers 39

Frequency 39

AC line voltage requirements for the HP Disk Array XP1024 DKC 40

AC line voltage requirements for the HP Disk Array XP1024 DKU 43

Safety and dedicated ground 48

Grounding requirements 48

Receptacles 49

Power line transients 51

Maximum peak inrush and crest factor 52

Sources of electrical interference 53

Three-phase AC cabling for the USA (60 Hz) 55

Connecting the external power supply cords 55

Branch circuit requirements 57

Three-phase AC cabling for Europe (50 Hz) 58

Connecting the power supply cords 58

Branch circuit requirements 59

Single-phase AC cabling for USA 61

Connecting the power-supply cords 61

Branch circuit requirements 64

Single-phase cabling for europe 65

Connecting the power supply cords 65

Branch circuit requirements 66

Uninterruptible Power Supply (UPS) 67

UPS features 67

UPS limitations 67

Power requirements: single secondary input (primary offline) 68

Reference supplier information 68

Environmental requirements 69

Heat dissipation and power consumption 74

Altitude 75

Acoustics 76

Delivery space requirements 77

4 Receiving your HP Disk Array XP1024 79

Checking for shipping shortage and damage 80

Unpacking the cartons 81

Glossary 83

Index 95

HP StorageWorks Disk Array XP1024: Site Preparation Guide

About this guide

This guide describes how to prepare a physical site for the installation of an

HP Disk Array XP1024. For information about the operation of the HP

Disk Array XP1024, refer to the owner’s guide.

Intended audience

This guide is intended for use by anyone participating in preparing a site for

HP Disk Array XP1024 installation. Your purchase of an HP Disk Array

XP1024 includes an onsite consultation visit by your HP support representative. Address your questions to the HP support representative at the consultation.

Related documentation

HP provides the following related documentation:

HP StorageWorks Disk Array XP1024: Owner’s Guide

HP StorageWorks Command View XP for XP Disk Arrays: User Guide

For information about operating system commands and third-party products, refer to the manufacturer’s documentation.

Conventions

This guide uses the following text conventions.

Figure 1

Blue text represents a cross-reference. For the online version of this guide, the reference is linked to the target.

www.hp.com

Underlined, blue text represents a website on the

Internet. For the online version of this guide, the reference is linked to the target.

About this guide

5

| literal variable input/output

Example

[ ]

{ }

Bold text represents literal values that you type exactly as shown, as well as key and field names, menu items, buttons, file names, application names, and dialog box titles.

Italics indicates that you must supply a value. Italics is also used for manual titles.

Monospace font denotes user input and system responses, such as output and messages.

Denotes an example of input or output. The display shown in this guide may not match your configuration exactly.

Indicates an optional parameter.

Indicates that you must specify at least one of the listed options.

Separates alternatives in a list of options.

Getting help

If you still have a question after reading this guide, contact an HP authorized service provider or access our website: www.hp.com

HP technical support

In North America, call technical support at 1-800-652-6672, available 24 hours a day, 7 days a week.

Outside North America, call technical support at the nearest location.

Telephone numbers for worldwide technical support are listed on the HP website under support: http://h18006.www1.hp.com/storage/arraysystems.html

6

HP StorageWorks Disk Array XP1024: Site Preparation Guide

Be sure to have the following information available before calling:

• technical support registration number (if applicable)

• product serial numbers

• product model names and numbers

• applicable error messages

• operating system type and revision level

• detailed, specific questions

For continuous quality improvement, calls may be recorded or monitored.

HP storage website

For the most current information about HP StorageWorks XP products, visit the support website. Select the appropriate product or solution from this website: http://h18006.www1.hp.com/storage/arraysystems.html

For information about product availability, configuration, and connectivity, consult your HP account representative.

HP authorized reseller

For the name of your nearest HP authorized reseller, you can obtain information by telephone:

United States

Canada

Or contact:

1-800-345-1518

1-800-263-5868 www.hp.com

About this guide

7

Revision history

May 2002

October 2002

April 2004

May 2005

First edition

Second edition

Third edition

Fourth edition

8

HP StorageWorks Disk Array XP1024: Site Preparation Guide

Warranty statement

HP warrants that for a period of ninety calendar days from the date of purchase, as evidenced by a copy of the invoice , the media on which the

Software is furnished (if any) will be free of defects in materials and workmanship under normal use.

DISCLAIMER. EXCEPT FOR THE FOREGOING AND TO THE

EXTENT ALLOWED BY LOCAL LAW, THIS SOFTWARE IS

PROVIDED TO YOU “AS IS” WITHOUT WARRANTIES OF ANY

KIND, WHETHER ORAL OR WRITTEN, EXPRESS OR IMPLIED.

HP SPECIFICALLY DISCLAIMS ANY IMPLIED WARRANTIES

OR CONDITIONS OF MERCHANTABILITY, SATISFACTORY

QUALITY, NON-INFRINGEMENT, TITLE, ACCURACY OF

INFORMATIONAL CONTENT, AND FITNESS FOR A

PARTICULAR PURPOSE. Some jurisdictions do not allow exclusions of implied warranties or conditions, so the above exclusion may not apply to you to the extent prohibited by such local laws. You may have other rights that vary from country to country, state to state, or province to province.

WARNING! YOU EXPRESSLY ACKNOWLEDGE AND AGREE

THAT USE OF THE SOFTWARE IS AT YOUR SOLE RISK. HP

DOES NOT WARRANT THAT THE FUNCTIONS CONTAINED IN

THE SOFTWARE WILL MEET YOUR REQUIREMENTS, OR THAT

THE OPERATION OF THE SOFTWARE WILL BE UNINTERRUPTED,

VIRUS-FREE OR ERROR-FREE, OR THAT DEFECTS IN THE

SOFTWARE WILL BE CORRECTED. THE ENTIRE RISK AS TO THE

RESULTS AND PERFORMANCE OF THE SOFTWARE IS ASSUMED

BY YOU. HP DOES NOT WARRANT OR MAKE ANY

REPRESENTATIONS REGARDING THE USE OR THE RESULTS OF

THE USE OF THE SOFTWARE OR RELATED DOCUMENTATION IN

TERMS OF THEIR CORRECTNESS, ACCURACY, RELIABILITY,

CURRENTNESS, OR OTHERWISE. NO ORAL OR WRITTEN

INFORMATION OR ADVICE GIVEN BY HP OR HP’S AUTHORIZED

REPRESENTATIVES SHALL CREATE A WARRANTY.

About this guide

9

LIMITATION OF LIABILITY. EXCEPT TO THE EXTENT

PROHIBITED BY LOCAL LAW, IN NO EVENT INCLUDING

NEGLIGENCE WILL HP OR ITS SUBSIDIARIES, AFFILIATES,

DIRECTORS, OFFICERS, EMPLOYEES, AGENTS OR

SUPPLIERS BE LIABLE FOR DIRECT, INDIRECT, SPECIAL,

INCIDENTAL, CONSEQUENTIAL, PUNITIVE OR OTHER

DAMAGES (INCLUDING LOST PROFIT, LOST DATA, OR

DOWNTIME COSTS), ARISING OUT OF THE USE, INABILITY

TO USE, OR THE RESULTS OF USE OF THE SOFTWARE,

WHETHER BASED IN WARRANTY, CONTRACT, TORT OR

OTHER LEGAL THEORY, AND WHETHER OR NOT ADVISED

OF THE POSSIBILITY OF SUCH DAMAGES. Your use of the

Software is entirely at your own risk. Should the Software prove defective, you assume the entire cost of all service, repair or correction. Some jurisdictions do not allow the exclusion or limitation of liability for incidental or consequential damages, so the above limitation may not apply to you to the extent prohibited by such local laws.

NOTE. EXCEPT TO THE EXTENT ALLOWED BY LOCAL LAW,

THESE WARRANTY TERMS DO NOT EXCLUDE, RESTRICT OR

MODIFY, AND ARE IN ADDITION TO, THE MANDATORY

STATUTORY RIGHTS APPLICABLE TO THE LICENSE OF THE

SOFTWARE TO YOU; PROVIDED, HOWEVER, THAT THE

CONVENTION ON CONTRACTS FOR THE INTERNATIONAL

SALE OF GOODS IS SPECIFICALLY DISCLAIMED AND SHALL

NOT GOVERN OR APPLY TO THE SOFTWARE PROVIDED IN

CONNECTION WITH THIS WARRANTY STATEMENT.

10

HP StorageWorks Disk Array XP1024: Site Preparation Guide

Introduction

1

Introduction

The objective of a site prep is to prepare your site for the successful and timely installation of your HP Disk Array XP1024. Proper site preparation and maintenance is vital to the reliability of your HP Disk Array XP1024.

A site prep is a delicate balance of equipment design criteria, site environmental variables, your business needs, and your budget constraints.

This guide contains site preparation information for the HP Disk Array

XP1024. Other site preparation resources may also be available to you.

Consult your HP representative specializing in the HP Disk Array XP1024.

11

12

HP StorageWorks Disk Array XP1024: Site Preparation Guide

Site prep team and tasks

2

Site prep team and tasks

The HP service organization is committed to making sure you receive the maximum benefits of your HP Disk Array XP1024. Brief descriptions of the HP team and how they can assist you are included in this chapter. You are also an integral part of the site prep team. Your responsibilities are also described here. The table on

page 16

provides a site inspection checklist and includes a reference for pertinent information.

13

The site prep team

The site prep planning team is responsible for determining site location and location size, ensuring that construction requirements and local codes are met, and scheduling all events related to site completion to prepare for the successful installation and maintenance of the HP Disk Array XP1024. The site prep team consists of the following personnel:

The HP Sales Representative (SR)

The sales representative is your primary point of contact. A sales representative coordinates all the HP resources to ensure successful delivery and installation of your disk array.

The HP Customer Engineer (CE)

The HP CE is trained and experienced in the installation of your disk array.

He or she has have the tools, parts, and knowledge to install and maintain your HP Disk Array XP1024. The CE also assists you in determining your site prep requirements.

The HP Application Software Engineer (ASE)

The HP ASE is a software technical specialist trained in configuring your

HP Disk Array XP1024. The ASE can install and configure all software applications for your disk array.

The Customer

As part of the site prep planning team, your responsibilities include scheduling, planning, and preparing a suitable environment for the HP Disk

Array XP1024. Your site team may include a site specialist for your computer room, a site electrician, and other site personnel specializing in your site computer room. Responsibilities include proper:

• Physical space necessary for proper disk array function and maintenance activity, including space and weight limitations and system accessibility

14

HP StorageWorks Disk Array XP1024: Site Preparation Guide

Site prep team and tasks

• Electrical power input including adherence to: local building codes local electrical codes local safety codes

• Connectors and receptacles, including hardware or cables network links telephone equipment equipment supplied by companies other than HP

• Environmental requirements including: temperature requirements humidity limitations

• Floor ventilation areas

• Cable access holes

• RJ-11 analog telephone lines for Phone Home capabilities

15

Site prep technical tasks

Use the following table as an action item checklist.

Customer Summary

Customer:

Contact: Telephone:

Address: HP CE:

Date: Time:

Safety

9 when completed

‰

Is there a fire protection system in the computer room?

‰ Are there any equipment servicing hazards?

Computer Room

9when completed

‰ Is there a copy of the existing floor plan?

‰ Is there a copy of the newly developed floor plan?

‰ Is there adequate space for airflow and maintenance needs?

‰ Is the computer room structurally complete?

‰ Is the raised floor adequate for equipment loading?

‰ Are there channels or cut-outs for cable routing?

‰ Is antistatic flooring installed?

‰ Is there a telephone jack for Phone Home configuration?

‰ Is there a telephone line for customer engineer use?

‰ Is there a private LAN available?

Yes No Reference

‰ ‰

page 20

‰ ‰

page 20

Yes No Reference

‰ ‰

page 21

‰ ‰

page 29

‰ ‰

page 21

‰ ‰

page 21

‰ ‰

page 29

‰ ‰

page 29

‰ ‰

page 29

‰ ‰

page 36

‰ ‰

page 37

‰ ‰

page 37

16

HP StorageWorks Disk Array XP1024: Site Preparation Guide

Electrical Yes No Reference

9when completed

‰ Are two AC outlets (on different lines) available for the proposed equipment?

‰ Does the input voltage correspond to equipment specifications?

‰ ‰

page 38

‰ ‰

page 38

‰ Are the input circuit breakers adequate for equipment loads?

‰ ‰

page 38

‰ Does the input frequency correspond to equipment specifications?

‰ ‰

page 38

‰ Are lightning arresters installed?

‰ Have all sources of electrical interferences been corrected?

‰ ‰

page 53

‰ ‰

page 53

Air-Conditioning Yes No Reference

9 when completed

‰ Can the temperature be maintained between 16

°

and 32

°

C?

‰ Can temperature changes be held to less that 10

°

C per hour?

‰

‰

‰

‰

page 69

page 71

‰ Can humidity level be maintained between 20% and 80% percent?

‰ ‰

page 71

Building Access and Security Yes No Reference

9 when completed

‰ Is there access control to the computer room?

‰ Is there access control for the customer site?

‰ Are any stair-walkers, lifts, ramps, floor coverings, or ladders required to install the equipment?

Define: _________________________________________

‰ Will the equipment fit through all doors, corridors, and in lifts, both in size and weight?

‰ Does the building have a loading dock?

Maximum access height is _____m.

‰ ‰

page 29

‰ ‰

page 29

‰ ‰

page 29

‰

‰

‰

‰

page 29 page 29

Site prep team and tasks

17

Site planning timetable

The following guidelines can be used to monitor the progress of your preinstallation preparation. The time between placing an order to actual arrival can vary, and we recommend conferring with your HP representative to determine the best estimated delivery dates for preparation of your site.

The following are items that may require several weeks of lead time to complete:

• Acquiring required power connectors

• Arranging for an electrician

• Adding or modifying air conditioning

• Building alterations

• Placing an order for data comm equipment

Due to potential delays, we recommend that the suppliers of the listed services be contacted as soon as you have placed your order:

• Schedule the site planning visit with your HP CE to discuss questions concerning site planning.

• Select an appropriate location for the disk array and create a plan outlining the physical arrangement of the equipment, including related furniture.

18

HP StorageWorks Disk Array XP1024: Site Preparation Guide

Preparing for installation

3

Preparing for installation

This chapter provides information for planning and preparing your site before and during installation of your HP Disk Array XP1024.

Before installing your HP Disk Array XP1024, your site data center computer room must meet the requirements described in this chapter.

19

Safety requirements

The following sections contain information to help you properly prepare your facility for the arrival of your disk array.

Site safety consideration

When making decisions concerning site safety, your first concern should be the safety of your personnel and then the safety of your equipment. Two major safety considerations for any computer site are fire safety and emergency power-off. If you have any questions on site safety, consult your

HP CE, your insurance carrier, and local building inspectors for safety recommendations.

Fire safety

When considering fire safety, consult your insurance carrier and fire department for suggestions and recommendations. They can analyze your existing fire control systems, and advise you of any changes that may be needed. If you are building a new site, or modifying an old site, consult your local building codes for fire prevention and protection guidelines. You can also consult your local HP CE and local fire inspectors for additional information.

Equipment servicing hazards

You, your HP CEs and HP ASEs require safe access to the disk array.

Along with the specifications listed in “General computer room requirements” (page 21) , ensure that electrical or data communication

cables do not create a safety hazard.

20

HP StorageWorks Disk Array XP1024: Site Preparation Guide

General computer room requirements

The goal of a computer room is to maintain an ideal environment for your computer equipment, including your HP Disk Array XP1024. The following guidelines are recommended:

• Locate the computer room away from exterior walls of the building to avoid the heat gain from windows and exterior wall surfaces.

• When locating near exterior windows is unavoidable, use windows that are double or tripled glazed and shaded to prevent direct sunlight from entering the computer room.

• Maintain the computer room at a positive pressure relative to the surrounding spaces to reduce introduction of contaminants.

• Use a vapor barrier installed around the entire computer room envelope to restrain moisture migration.

• Caulk and vapor-seal all pipes and cables that penetrate the envelope.

• Use a 10-inch to 12-inch raised floor system for the most favorable room air distribution system if the under floor area is being used as an as part of the air circulation system.

Space planning

A site prep begins with your existing floor plan. The location of the new equipment should be selected and a new floor plan should be developed.

You can use this section to satisfy the disk array physical requirements, ensuring that your site is ready when the disk array arrives. Your floor plan should include the location of:

• Walls

• Cable paths, including lengths

• All equipment in your computer room, including furniture, cabinets, racks, data comm equipment, and systems

• Electrical outlets

• Immovable objects

• Floor vents

Preparing for installation

21

The HP Disk Array XP1024

Your HP Disk Array XP1024 is a high-performance disk array system. It is used to store large quantities of data in an efficient and secure manner. The components of the HP Disk Array XP1024 are contained in one of two types of cabinets.

Each HP Disk Array XP1024 has one disk controller cabinet (DKC), which contains the controller electronics for the disk array, and one to five disk-cabinet units (DKUs), which contain the hard disk drives.

When only XP1024 DKUs are used, the disk array can have one to four

XP1024 DKUs. The figure below shows a Disk Array XP1024 with four

XP1024 DKUs.When both XP1024 and XP512 DKUs are used, the DKU types cannot be mixed on the same side of the DKC.

Minimum Disk Subsystem

22

DKU frame

(L2)

4th DKU

DKU frame

(L1)

3rd DKU

DKC frame

DKU frame

(R1)

1st DKU

DKU frame

(R2)

2nd DKU

HP StorageWorks Disk Array XP1024: Site Preparation Guide

Preparing for installation

When both XP1024 and XP512 DKUs are used, the disk array can have one or two XP1024 DKUs (on one side of the DKC) and one to three XP512

DKUs (on the other side of the DKC) as shown in the figure below.

XP1024 and XP512 DKUs cannot be mixed on the same side of the DKC.

Minimum Disk Subsystem

DKU frame DKU frame

(L3)

5th DKU

(L2)

4th DKU

DKU frame

(L1)

3rd DKU

DKC frame

DKU frame

(R1)

1st DKU

DKU frame

(R2)

2nd DKU

23

Physical requirements

Dimensions

An HP Disk Array XP1024 consists of a single DKC cabinet and one to four DKU cabinets with the approximate dimensions listed in the table below.

Minimum

Dimensions DKC mm DKC in DKU mm DKU in

Height 1860

Width 782*

Depth 800

73.6

30.8

31.5

1860

750

800

* The width of the DKC includes the side panels.

73.6

29.5

31.5

Weight

An HP Disk Array XP1024 consists of a single DKC cabinet and one to four DKU cabinets. The table below provides the approximate weights for a minimum and maximum configuration. The main factor that increases weight is the number of hard disk drives (HDDs) in a DKU cabinet:

Weight

Minimum configuration

Maximum configuration

DKC kg DKC lb DKU kg DKU lb

478 1051 492 1082

586 1290 755 1661

Specific component dimensions and weights

The values listed in these tables are approximate and should be used for general reference only; use these values to estimate the hallway and door clearances as well as floor strength for moving the disk array cabinets.

24

HP StorageWorks Disk Array XP1024: Site Preparation Guide

Preparing for installation

Component Width

DKC Cabinet alone 782 mm

30.8 in

DKC Cabinet packaged*

890 mm

35 in

DKU Cabinet alone 750 mm

29.5 in

A7925A DKU

Cabinet packaged*

890 mm

35 in

A7925U DKU

Cabinet packaged*

890 mm

35 in

Depth

800 mm

31.5 in

1000 mm

39.37 in

800 mm

31.5 in

1000 mm

39.37 in

1000 mm

39.37 in

Height

1860 mm

73.6 in.

2020 mm

79.58 in

1860 mm

73.6 in

2020 mm

79.58 in

2020 mm

79.58 in

*For shipments to locations outside the United States, Canada, and

Germany, add 88 kg (194 lb) for an international shipping crate.

Weight

Fully

Loaded

586 kg

1290 lb

674 kg

1484 lb

755 kg

1661 lb

823 kg

1811 lb

843 kg

1855 lb

The table below lists HP Disk Array XP1024 component product weights.

Product Description kg lb

A7907A SVP High Reliability Kit 5.5

12.1

A7909A 8-Port ExSA Channel Adapter Pair 4.2

9.2

A7909B 8-Port ExSA Channel Adapter Pair - Enhanced 4.2

9.2

A7910A 8-Port 1 Gbps FC/CA Adapter Pair 4.2

9.2

A7911A 4-Port 1-2 Gbps Autosensing FC/CA CHIP Pair 4.2

9.2

A7912A 8-Port 1-2 Gbps Autosensing FC/CA CHIP Pair 4.2

9.2

A7912B 8-Port 1-2 Gbps Enhanced FC CHIP Pair 4.2

9.2

A7913B 16-Port 1-2 Gbps Enhanced FC CHIP Pair

A7914A 8-Port 1 Gbps FICON - SW CHIP Pair

A7915A 8-Port 1 Gbps FICON - LW CHIP Pair

4.3

9.25

4.0

8.8

4.0

8.8

25

26

Product Description kg lb

A7916B 8-Port 1-2 Gbps Enhanced FC - LW CHIP Pair 4.2

9.2

A7917A Additional CHIP/ACP Power Supply

A7918A 2GB Cache Memory Module

8.8

0.2

19.4

0.4

A7919A

A7920A

Cache Platform Board

Additional Battery for Cache Memory

A7921A 512MB Shared Memory Module

A7922A Array Control Processor (ACP) pair - High

Performance

A7924A FC Cable Set for L1 DKU

5.6

12.3

42.2 92.8

0.05 0.1

3.6

7.9

A7926A FC Cable Set for R2 and L2 DKU

A7928A 36 GB 15k rpm FC Array Group - 4 disks

A7928S

A7929A

A7930S

A7931A

A7931S 73 GB 15k rpm FC Spare Disk Drive

A7933A 300 GB 10k rpm FC Array Group - 4 disks

A7933S

A7934A

36 GB 15k rpm FC Spare Disk Drive

73 GB 10k rpm FC Array Group - 4 disks

A7929S 73 GB 10k rpm FC Spare Disk Drive

A7930A 146 GB 10k rpm FC Array Group - 4 disks

146 GB 10k rpm FC Spare Disk Drive

73 GB 15k rpm FC Array Group - 4 disks

300 GB 10k rpm FC Spare Disk Drive

4GB Cache Memory Module

3.0

6.6

3.0

4.0

6.6

8.8

1.0

2.2

4.0

8.8

1.0

4.0

2.2

8.8

1.0

2.2

4.4

9.7

1.1

4.0

2.4

8.8

1.0

2.2

0.2

0.4

A7935A 1GB Shared Memory Module 0.05 0.1

A7938A 8-Port Gigabit Ethernet iSCSI - SW CHIP Pair 4.6

10.1

A7939A 4-Port Gigabit Ethernet NAS - SW CHIP Pair 4.5

9.9

HP StorageWorks Disk Array XP1024: Site Preparation Guide

HP Disk Array XP512 DKU physical requirements

Dimensions

The approximate dimensions of an HP StorageWorks Disk Array XP512

DKU are listed in the table and diagrammed in the figure below.

Minimum

Dimensions DKU mm

Height 1790

Width 600

Depth 800

DKU in

70.5

23.6

31.5

Preparing for installation

27

28

Weight

The values listed in these tables are approximate and should be used for general reference only. Use these values to estimate the hallway and door clearances as well as floor strength for moving the subsystem frames.

The table below lists the physical dimensions for each HP StorageWorks

Disk Array XP512 DKU frame component.

Component

A5965A DKU

Cabinet alone

DKU Cabinet packaged*

Width

600 mm

23.62 in

890 mm

35 in

Depth

600 mm

23.62 in

1000 mm

39.37 in

Height

1790 mm

70.53 in.

2020 mm

79.58 in

Weight

Fully

Loaded

480 kg

1056 lb

539 kg

1185.5 lb

*For shipments to locations outside the United States, Canada, and

Germany, add 88 kg (194 lb) for an international shipping crate.

The table below lists the weights for each HP StorageWorks Disk Array

XP512 DKU frame component.

Product Description kg lb

All Options Disk Array frame

A5966A

A5966S

18GB array group, 4 drives per group

18GB spare drive

A5967A

A5967S

A5968A

A5968S

47GB array group, 4 drives per group

47GB spare drive

73 GB array group

73 GB spare drive

A5969A

A5969S

A5974A

A5975A

300 661

5.6

12.3

1.4

3.1

7.2

15.9

1.8

4.0

7.2

15.9

1.8

4.0

181 GB array group

181 GB spare drive

FC cable set for DKC frame to L1 (frame #4) 2

FC cable set for frame R2, R3, L2, or L3 3

7.2

15.9

1.8

4.0

4.4

6.6

HP StorageWorks Disk Array XP1024: Site Preparation Guide

Service and cable routing space requirements

This section contains information about space requirements for the HP Disk

Array XP1024. This data should be used as a guideline for space planning development.

The service clearance is the additional flooring space required to access your HP Disk Array XP1024. This space should be reserved for the disk array; never use this space for storage.

HP recommends that you prepare a revised floor plan showing the overall location and arrangement of your computer room, including the addition of your disk array. Enough room and lighting should be provided for people to work effectively on a daily basis and for periodic servicing of equipment.

Select a location that can accommodate the addition of more DKU cabinets as your requirements increase. Be sure to consider interconnecting cables and power cord lengths when planning your layout. Identify the location of all power outlets on the floor plan. Plan to keep cables away from traffic areas to help prevent accidents and equipment failures. Prior to installation, consult your site specialist responsible for your computer room.

HP strongly discourages the use of carpeting, including anti-static varieties, within 6.0 m (20 ft.) of the disk array. If this advice is not followed, you should place static discharge mats where personnel must walk across before touching any part of the array. Failure to comply with this precaution can result in equipment damage through static discharge.

If you are planning to construct a new computer room or modify an existing site, first consult with your HP representatives and local contractors. It is important to plan the site with future expansion in mind so that equipment can be added without disturbing the computer operation.

The computer room floor must be able to support the total weight of the equipment as well as localized weight at each caster or foot of the equipment cabinets. A common method of preparing an adequate floor for a computer room is to construct a raised floor over the building floor. The weight should be spread evenly and the flooring should provide an area

Preparing for installation

29

30 through which interconnecting cables can be run conveniently and unobtrusively. It should allow for optimum distribution of conditioned air.

Raised floor access ramps must not exceed a 10

°

slope

.

To estimate floor strength, the following items should be considered:

• The total weight of the equipment (the unpacked and packaged weights are listed in this chapter)

• The total weight of furniture such as desks, chairs, and storage cabinets

• Total approximate weight of computer room personnel

• Weight of moving equipment such as forklifts, dollies, and so on.

Any questions regarding the adequacy of airflow construction should be referred to and evaluated by a qualified structural engineer.

Caution

In addition to determining the adequacy of the computer site floor, ensure that all floors, stairs, and elevators which might be used when the disk array is moved to its destination can support the weight and size of the equipment. Failure to comply can result in damage to the equipment.

The minimum service access is:

• Rear: 800 mm (31.5 in)

• Side:: 0 mm

• Front: 800 mm (31.5 in)

Maximum point floor loading is 500 kg (1102.3 lb).

HP StorageWorks Disk Array XP1024: Site Preparation Guide

Preparing for installation

The figure below shows the recommended service clearance and floor cutout recommendations for the XP1024 DKC. Measurements are in millimeters.

782

Recommended dimension : 400

( 300 – 602 ) *1

(Unit : mm)

191

*2

76

598

191

2*

800

G

55 113

Recommended dimension : 300

( 250 - 400 ) *1

250

*2

*3

680 564

2400

254

250

*2

65 123 105

G

300

166

86

16

450

610

750

166

86

16

800

Front

Floor cutout area for cables

Screw jack

Caster

Service clearance

G

Grid panel (over 450mm

Opening on the bottom of the frame

(for external cable entry) x450mm)

*1 Values of parenthesis show allowable range of the floor cutout dimension.

The floor cutout should be planned in the center of the DKC. In case that the floor cutout is planned

may be off-center.

In this case,check the relation between the positions of the cutout and the opening on the bottom of

the frame.

If the floor cutout width is planned more than 520 mm,be careful about the restriction of the movable

direction because there is a possibility that the caster wheels fall down into the cutout.

*2 These dimensions vary with the floor cutout dimension.

*3 The thickness of the front door (35 mm) is different from the rear door (25 mm).

*4 The overhang of the front door panel insert (7 mm) is not included.

31

32

The figure below shows the recommended service clearance and floor cutout recommendations for the XP1024 DKU.

750

(Unit: mm)

G

300 225

45

200

225

110 55

800

570 680 800 2400

555

165

85

G

420

580

120 65

165

85

800

Front

Floor cutout area for cables

Screw jack

Caster

Service clearance

G

Grid panel (over 450mm x 450mm)

HP StorageWorks Disk Array XP1024: Site Preparation Guide

The figure below shows the minimum service access and cutouts for the

XP1024.

680 564

191

55 113 253

300

*3 a *1

400

*3

1532

225 300

G G b *1

241

(Unit: mm)

800

45 110 55

200

555

570 680 800

2400

65 123 250

*3

G G

120 65

166

86

16

*2 d

450

610

750

FRONT

420

580

750

181

101

16

800 c *1

DKC DKU

Floor cutout area for cables

Screw jack

Caster

Service clearance

G Grid panel (over 450mm x 450mm)

1. Clearance (a+b) depends on the floor load rating and clearance (c). Floor load rating and clearances are listed in the table on

(page 34) .

2. Front clearance (d) of 0.3 m is required for unobstructed opening of the front door.

Preparing for installation

33

The table below shows the floor load rating for service clearances

(minimum configuration).

Required clearance (a+b) m

Floor load rating

(kg/sq. m)

Clearance (c) m

C = 0 C = 0.2

C = 0.4

C = 0.6

C = 1.0

500

450

400

0.6

0.9

1.4

0.4

0.7

1.0

0.2

0.4

0.8

0

0.3

0.6

0

0

0.3

350

300

2.0

3.0

1.6

2.5

1.3

2.1

1.0

1.8

0.7

1.3

Actual clearances for installation should be decided after consulting with construction specialist responsible for installation building, as they could vary depending on the size/layout of the system and building conditions.

When various configurations of subsystems are arranged in a row, clearance values based on the largest subsystem should be used.

From the viewpoint of maintenance operations, it is suggested that clearance (c) be made as large possible.

34

HP StorageWorks Disk Array XP1024: Site Preparation Guide

The figure below shows the maximum service access and cutouts for the

XP1024.

(Unit: mm) a *1

3782 b *1

800

G G G G G

16

750

G

750

G

750

G

Front

750

G

750

G

800

2400

16

800

C *1

DKU DKU DKC DKU DKU

Preparing for installation

Screw jack

Caster

G

Floor cutout area for cables

Service clearance

Grid panel (over 450mm x 450mm)

Clearance (a+b) depends on the floor load rating and clearance (c). The following table lists floor load ratings.

Floor Load Rating

(kg/m

2

)

Clearance (C) (m)

C = 0 C = 0.2 C = 0.4 C = 0.6 C = 1.0

500

450

400

350

300

1.9

2.7

3.9

5.6

8.3

1.2

2.0

3.1

4.6

6.9

0.8

1.4

2.4

3.7

3.9

0.3

1.0

1.8

3.1

5.0

0

0.7

1.0

2.0

3.7

If your installation will include one or more XP512 DKUs, see the HP

StorageWorks Disk Array XP512 Site Preparation Guide for XP512 clearance requirements.

35

Data comm requirements

Route data comm cables away from areas of high static electric fields created by power transformers and heavy foot traffic. Use shielded data comm cables that meet approved industrial standards to reduce the effects of external fields.

Phone Home with Continuous Track

The HP Disk Array XP1024 Phone Home capabilities detect and report problems even before they are noticed by operators and users. Continuous

Track, a program that resides in the DKC, phones “home” to the HP

Storage Technology Center (STC) and provides:

Periodic “well” checkups

Every 24 hours, Continuous Track calls the HP Storage Technology

Center. When a successful connection is made, status and/or configuration information is transferred from the DKC to the HP

Storage Technology Center. Your HP CE sets the time of the call. This checkup records the health of your disk array on a daily basis.

Incidental “sick” calls

When an error occurs, a service information message (SIM) is generated. The SIM is stored in the DKC for use by your HP service representative. The Continuous Track remote maintenance tool also reports the SIMs to the STC. SIMs are classified according to severity, and many SIMs do not require immediate attention. These SIMs are often addressed during routine maintenance, and are corrected before a failure occurs. Serious-level and acute-level SIMs are reported to the

STC immediately to ensure that the problem is addressed as soon as possible.

To activate Phone Home, these requirements are necessary:

• Dedicated analog phone line

• An HP CE to configure Continuous Track

36

HP StorageWorks Disk Array XP1024: Site Preparation Guide

HP StorageWorks Command View XP and your public Intranet

HP StorageWorks Command View XP is a web-based software application that permits you to connect to, monitor, and manage disk arrays. You can remotely manage your HP Disk Array XP1024.

Local Area Network (LAN)

To connect to your Intranet (public LAN), your CE directly connects your

HP Disk Array XP1024 to an available Ethernet port on your public LAN.

To ensure network security, consult with your HP CE and your network administrator before selecting the location of your LAN drop.

Network Hardware Needed:

• One twisted pair (Cat 5) cable

• Ane available LAN drop on your Intranet

Outside phone line

Recommendation

Install a public voice phone line near your disk array. This phone line is used by you and your HP CE for voice communication in and outside of your facility.

Preparing for installation

37

Electrical requirements

Power requirements are one of the most important considerations prior to installing your disk array. For disk array cabinets with two connections to

AC power, if one input fails, the second input must be capable of supporting the entire current demand nominally shared by the two power connections. For disk array cabinets with four connections to AC power, the two connections to AC Box 1 or the two power connections to AC Box

2 must be capable of supporting the entire current demand nominally shared by the four power connections. The figure below shows two examples of the disk array’s fault-tolerant operation.

Disk Array Cabinet

(DKU or DKC)

(2 AC Power connections)

AC Power

Input Box

#1

AC Power

Input Box

#2

Disk Array Cabinet

(DKU or DKC)

(4 AC Power connections)

AC Power

Input Box

#1

AC Power

Input Box

#2

Line voltage

The Disk Array can tolerate the loss of connection to AC Box 1 or AC Box 2.

The Disk Array can tolerate the loss of connections to AC Box 1 or AC Box 2, but no other combinations are allowed.

The line voltage (AC) at the wall power outlet is a function of the local power utility and your building power distribution network. Voltages outside the operating range of the disk array can cause intermittent system errors or a complete system shutdown. If required, the HP CE, along with

38

HP StorageWorks Disk Array XP1024: Site Preparation Guide

Branch Circuit Breakers

See “Branch Circuit Requirements”

(page 39)

for the specific branch circuit requirements for your power situation.

Three-phase branch circuit breakers

The power cords supplied with each HP Disk Array XP1024 DKU configured for three-phase power are sized for connection to a 30 or

60-amp circuit. There are no external power cords for the DKC when the

HP Disk Array XP1024 is configured for 60-amp, three-phase power.

Single-phase branch circuit breakers

The power cords supplied with each HP Disk Array XP1024 DKU configured for single-phase power are sized for connection to a 30 or

50-amp circuit. The power cords supplied with each HP Disk Array

XP1024 DKC configured for single-phase power are sized for connection to a 30 or 40-amp circuit.

30-amp, single-phase power is available by special order only.

Frequency

your electrician can determine the current line voltage and make recommendations. Avoid the use of a line voltage conditioner.

Make sure that a power distribution unit (if used) supports the correct voltage to support your entire system.

AC line frequency is normally determined by your local power providers.

In some cases, electrical power is supplied by motor-generators. Shifts in

AC line frequency can cause system errors. Your HP CE can monitor the frequency of the input AC line power and make recommendations, if necessary. The HP Disk Array XP1024 requires that the line frequency be within 0.5 Hz of the rated line frequency (50 Hz or 60 Hz).

Preparing for installation

39

The following tables reflect the line voltage for each power cable when the cabinets are cabled with functioning, redundant power cables.

AC line voltage requirements for the HP Disk Array XP1024 DKC

The table below lists the basic AC power requirements for a 40-amp, single-phase XP1024 DKC.

Nominal Rated Voltage (Vac)

Parameter 200 208* 220 230 240

Minimum operating voltage (Vac) 184 191 202 212 221

Maximum operating voltage (Vac) 212 220 233 244 254

Rated line current per power cord

(Arms)

8.0

7.7

7.2

7.0

6.6

Number of power cords

Recommended circuit breakers

Number of circuit breakers

Dropout carry-through time at minimum line voltage (ms)

* 60 Hz only.

2 2 2 2 2

40 A 40 A 40 A 40 A 40 A

2

30

2

30

2

30

2

30

2

30

40

HP StorageWorks Disk Array XP1024: Site Preparation Guide

Preparing for installation

The table below lists the basic AC power requirements for a 30-amp, single-phase, XP1024 DKC.

Nominal Rated Voltage (Vac)

Parameter 200 208

*

220 230 240

Minimum operating voltage (Vac) 184 191 202 212 221

Maximum operating voltage (Vac) 212 220 233 244 254

Rated line current per power cord

(Arms)

4.0

3.9

3.6

3.5

3.3

Number of power cords 4 4 4 4 4

Recommended circuit breakers

Number of circuit breakers

Dropout carry-through time at minimum line voltage (ms)

* 60 Hz only.

30 A 30 A 30 A 30 A 30 A

4 4 4 4 4

30 30 30 30 30

41

42

The table below lists the basic AC power requirements for a 30-amp, three-phase XP1024 DKC.

Nominal Rated Voltage (Vac)

Parameter 200 208

*

220 230 240 380 400 415

Minimum operating voltage (Vac)

184 191 202 212 221 350 368 382

212 220 233 244 254 403 424 440 Maximum operating voltage

(Vac)

Rated line current per power cord

(Arms)

5.2

5.0

4.7

4.6

4.3

2.7

2.6

2.5

2 2 2 2 2 2 2 2 Number of power cords

Recommended circuit breakers

Number of circuit breakers

Dropout carry-through time at minimum line voltage (ms)

* 60 Hz only.

30 A 30 A 30 A 30 A 30 A 30 A 30 A 30 A

2

30

2

30

2

30

2

30

2

30

2

30

2

30

2

30

HP StorageWorks Disk Array XP1024: Site Preparation Guide

AC line voltage requirements for the HP Disk Array XP1024 DKU

The table below lists the basic AC power requirements for a 50-amp, single-phase, XP1024 DKU.

Nominal Rated Voltage (Vac)

Parameter 200 208

*

220 230 240

Nominal rated voltage (Vac) 200 208 220 230 240

Minimum operating voltage (Vac) 184 191 202 212 221

Maximum operating voltage (Vac) 212 220 233 244 254

Rated line current per power cord

(Arms)

22.3

21.6

20.3

19.4

18.6

Number of power cords 2 2 2 2 2

Recommended circuit breakers

Number of circuit breakers

Dropout carry-through time at minimum line voltage (ms)

* 60 Hz only.

50 A 50 A 50 A 50 A 50 A

2 2 2 2 2

30 30 30 30 30

Preparing for installation

43

The table below lists the basic AC power requirements for a 30-amp, single-phase XP1024 DKU.

Nominal Rated Voltage (Vac)

Parameter 200 208

*

220 230 240

Minimum operating voltage (Vac) 184 191 202 212 221

Maximum operating voltage (Vac) 212 220 233 244 254

Rated line current per power cord

(Arms)

13.5

13.0

12.3

11.7

11.2

Number of power cords 4 4 4 4 4

Recommended circuit breakers

Number of circuit breakers

Dropout carry-through time at minimum line voltage (ms)

* 60 Hz only.

30 A 30 A 30 A 30 A 30 A

4 4 4 4 4

30 30 30 30 30

44

HP StorageWorks Disk Array XP1024: Site Preparation Guide

Preparing for installation

The table below lists the basic AC power requirements for a 60-amp, three-phase XP1024 R1 DKU.

Nominal Rated Voltage (Vac)

Parameter 200 208

1

220 230 240 380 400 415

Minimum operating voltage (Vac)

184 191 202 212 221 350 368 382

Maximum operating voltage (Vac)

212 220 233 244 254 403 424 440

Rated line current per power cord (Arms)

19.0 18.2 17.2 16.6 15.7 10.7 10.2 9.8

Number of power cords

Recommended circuit breakers

Number of circuit breakers

2 2 2 2 2 2

60 A 60 A 60 A 60 A 60 A 30 A

2 2 2 2 2 min.

2

2

2

30 A min.

2

2

2

30 A min.

2

2

Dropout carry-through time at minimum line voltage

(ms)

30 30 30 30 30 30 30 30

1. 60 Hz only.

2. 30-amp breakers are adequate at 380, 400, and 415 Vac, because the current drawn at these voltages is considerably less than at the lower voltages.

45

46

The table below lists the basic AC power requirements for 60-amp, three-phase, R2, L1, and L2 XP1024 DKUs. Unlike the first DKU (R1),

DKUs R2, L1, and L2 do not provide AC power to the DKC.

Nominal Rated Voltage (Vac)

Parameter 200 208

1

220 230 240 380 400 415

Minimum operating voltage (Vac)

Maximum operating voltage (Vac)

184 191

212 220

202 212 221 350 368 382

233 244 254 403 424 440

Rated line current per power cord (Arms)

19.0 18.2 17.2 16.6 15.7 10.7 10.2 9.8

Number of power cords

Recommended circuit breakers

2 2 2 2 2 2

60 A 60 A 60 A 60 A 60 A 30 A min.

2

2

30 A min.

2

2

30 A min.

2

Number of circuit breakers

2 2 2 2 2 2 2 2

Dropout carry-through time at minimum line voltage

(ms)

30 30 30 30 30 30 30 30

1. 60 Hz only.

2. 30-amp breakers are adequate at 380, 400, and 415 Vac, because the current drawn at these voltages is considerably less than at the lower voltages.

HP StorageWorks Disk Array XP1024: Site Preparation Guide

Preparing for installation

The table below lists the basic AC power requirements for a 30-amp, three-phase XP1024 DKU.

Nominal Rated Voltage (Vac)

Parameter 200 208* 220 230 240 380 400 415

Minimum operating voltage (Vac)

184 191 202 212 221 350 368 382

Maximum operating voltage (Vac)

Rated line current per power cord

(Arms)

212

15.0

220

14.4

233

13.6

244

13.0

254

12.5

403

8.8

424

8.4

440

8.1

Number of power cords

2 2 2 2 2 2 2 2

Recommended circuit breakers

30 A 30 A 30 A 30 A 30 A 30 A 30 A 30 A

Number of circuit breakers

2

Dropout carry-through time at minimum line voltage (ms)

2 2 2 2 2 2 2

30 30 30 30 30 30 30 30

* 60 Hz only.

If you intend to use HP Disk Array XP512 DKUs with your HP XP1024

Disk Array, see the HP StorageWorks Disk Array XP512 Site Preparation

Guide for power-requirements information for these DKUs.

47

Safety and dedicated ground

The primary reason for grounding electrical systems is safety. The safety ground is required by the National Electric Code (USA) and most other local, regional, and national codes. In addition to safety ground, HP requires that a dedicated (earth reference) ground be installed as a common reference point for all system components. You should consult with your

HP CE and your electrician to ensure that your electrical system meets all local and national safety codes.

Grounding requirements

Your subsystem must meet all of the following conditions:

• An insulated grounding conductor that is identical in size and insulation material and thickness to the ungrounded branch-circuit supply conductors. It should be green, with or without yellow stripes, and is to be installed as a part of the branch circuit that supplies the unit or system. This means the ground conductor must be run in the same conduit, armored cable, or other cable bundle as the phase wires.

• Grounding as prescribed by your local country codes.

• The grounding conductor mentioned above should be grounded to earth at the service equipment or other acceptable building earth ground such as the building frames (in the case of a high rise steel frame structure).

• IT configured grounding systems are not certified for use with the

XP1024 as these grounding systems may not have solidly conductor-connected grounded power systems and/or they may have resistive impedance inserted in ground and/or neutral lines. The

XP1024 requires a solidly conductor-connected ground and may require a separate neutral in the case of WYE or STAR connections.

48

HP StorageWorks Disk Array XP1024: Site Preparation Guide

Receptacles

When receptacles are used to connect your disk array components to AC power, they must include a dedicated ground connection that is insulated from the receptacle. It is important that the receptacle box be grounded with an additional ground connection that is separate from the dedicated ground.

The additional ground can be hard conduit.

Each disk array cabinet has two or four separate connections to AC power

(except the 60-amp, three-phase DKC, which has no external power connection). For disk array cabinets with two connections to AC power, each input must be capable of supporting the entire current demand for the cabinet. For disk array cabinets with four connections to AC power, the two inputs to AC Box 1 or the two inputs to AC Box 2 must be capable of supporting the entire current demand for the cabinet. The figure below shows two examples of the disk array’s fault-tolerant operation.

Disk Array Cabinet

(DKU or DKC)

(2 AC Power connections)

AC Power

Input Box

#1

AC Power

Input Box

#2

Disk Array Cabinet

(DKU or DKC)

(4 AC Power connections)

AC Power

Input Box

#1

AC Power

Input Box

#2

The Disk Array can tolerate the loss of connection to AC Box 1 or AC Box 2.

The Disk Array can tolerate the loss of connections to AC Box 1 or AC Box 2, but no other combinations are allowed.

Preparing for installation

49

50

Specific power plugs and receptacles are required for the XP1024 DKC and

DKUs, depending on the power option you specify when ordering the HP

Disk Array XP1024. The power cords on 60 Hz cabinets are shipped with plugs attached and connected. The power cords on 50 Hz cabinets are shipped without plugs. Customers are responsible for having the correct plugs and receptacles installed by an electrician in compliance with local electrical requirements and practices.

Caution

When installing the receptacles, the electrician must ensure that each receptacle has its own neutral (if required) and ground. Using the same neutral/ground for more than one circuit causes voltage loss and heat problems. It can create a fire hazard. A shared neutral conductor that fails open-circuit can cause overvoltage damage to equipment.

The table below lists the plug and connector part numbers for 60 Hz configurations of the HP Disk Array XP1024.

Power Source Frequency

Breaker

Rating

Single-phase 60 Hz 30 A

Plug

Russellstoll

3750DP

Three-phase 60 Hz

40/50 A

30 A

60 A

Russellstoll

9P53U2

Russellstoll

3760PDG

Russellstoll

RS460P9W

Connector

Russellstoll

3933

(Alt. 9C33U0) or 3753

(Alt. 9R33U0W)

Russellstoll

9C53U2 or 9R53U2W

Russellstoll

3934 (Alt.

9C34U0) or 3754

(Alt. 9R34U0W)

Russellstoll

RS460C9W or

RS460R9W

HP StorageWorks Disk Array XP1024: Site Preparation Guide

The Russelstoll connectors are available through most industrial electrical distributors. HP has arranged for these connectors to also be available in stock from the distributors listed below. These distributors are able to ship worldwide and ship via customer preference.

Beck Electrical Supply

2775 Goodrick Avenue

Richmond, CA 94801 USA

Telephone: (800) 466-4395

Fax: (800) 466-5442

Contact: Ken Mogan [email protected]

Source Research, Inc. (SRI)

2160 Sunnydale Boulevard

Clearwater, FL 33765-2108 USA

Telephone: (800) 356-0259

Contact: Erik Peterson, telephone extension 302 http://www.sourceresearch.com/index.cfm

Power line transients

Heavy electrical loads from nearby machinery or equipment (elevators, electric welders, etc.) can cause intermittent system problems with sophisticated electronic equipment, even if that equipment is on a separate circuit breaker. When faced with these conditions, you should provide a separate, completely independent power panel with an isolated ground and circuit breaker coming directly from the main building power source or secondary power source.

If necessary, your HP CE can measure your power line noise level and make appropriate recommendations concerning the use of line treatment devices.

Preparing for installation

51

Maximum peak inrush and crest factor

The table below shows the maximum peak inrush currents for the HP Disk

Array XP1024 DKC and DKUs.

Cabinet

DKC

DKU

Power

30-amp

40-amp

30-amp

50-amp

60-amp

Single-Phase Three-Phase

25 A

67 A

33 A

53 A

N/A

3

30 A

N/A

1

79 A

N/A

2

99 A

4

40 A

5

1. The 40-amp power configuration is single-phase only.

2. The 50-amp power configuration is single-phase only.

3. The 60-amp power configuration is three-phase only.

4. First DKU (R1) only. This value includes the current drawn by the

DKC in this configuration.

5. R2, L1, and L2 DKUs.

The table below shows the crest factors for the HP Disk Array XP1024.

Cabinet

DKC

DKU

Single-Phase Three-Phase

2.02

1.65

1.88

1.54

If you intend to use HP Disk Array XP512 DKUs with your HP XP1024

Disk Array, see the HP StorageWorks Disk Array XP512 Site Preparation

Guide for peak-inrush and crest-factor information for these DKUs.

52

HP StorageWorks Disk Array XP1024: Site Preparation Guide

Sources of electrical interference

Ensure that the disk array is protected from sources of electrical interference: wall outlets Convenience power outlets for building maintenance equipment (vacuum cleaners, floor buffers, etc.) must be wired from circuit breakers on a power panel separate from the computer system panel. The ground wires from these outlets must be connected to the normal building distribution panel and not to the system ground.

If a separate power source and separate ground are not provided, operation of janitorial equipment can induce electrical noise and cause abnormal operation of the computer system. Your electrician can verify whether or not maintenance outlets are on separate panels.

lightning vibration

In some geographical areas it may by advisable to install lightning protection for both personnel and computer systems.

The principles of lightning protection and personnel safety are outlined in detail in the lightning protection code contained in the National Fire Protection

Association (NFPA) Handbook.

Continuous vibration can cause a slow degradation of mechanical parts and, when severe, can cause data errors in disk drives. Mechanical connections such as printed circuit assembly (PCA) conductors, cable connectors, and processor backplane wiring can also be affected by vibrations.

Preparing for installation

53

54 electromagnetic interference metal flammable materials airborne contaminants

The disk array is specifically designed to reduce its susceptibility to radiated and conducted interference.

Electromagnetic interference can cause a variety of system problems. Your HP CE can advise you about many of the most common causes of electromagnetic interference.

If metal is used in the construction of the raised floor, ensure that there is a common ground connection between the raised floor and main floor to avoid possible build up of different voltage potentials.

Failure to comply can result in serious injury to personnel and damage to equipment.

Fundamental safeguards for disk arrays should include a site well away from any sources of potential damage.

The system should not be installed or operated in an environment where there is a risk of fire or explosion due to the presence of highly flammable gases, volatile liquids, or combustible dust.

Airborne contaminants and particles of a certain size and hardness can damage your disk arrays. Some of the most common contaminants are dust, smoke, ash, eraser debris, food crumbs, and salty air.

Your HP CE can assist you in determining whether or not you need be concerned about airborne contaminants.

Also, see Dust and Pollution Control (page 70) and

Metallic Particulate Contamination

(page 70) .

HP StorageWorks Disk Array XP1024: Site Preparation Guide

Three-phase AC cabling for the USA (60 Hz)

Each three-phase HP Disk Array XP1024 DKU has two main disconnect devices (two main breakers for dual power lines) so that AC power to the unit can be supplied from separate power distribution panels with two power-supply cords.

Caution

Trained service personnel should be present whenever the disk array is being connected to a new power source for the first time.

If you intend to use HP Disk Array XP512 DKUs with your

HP XP1024 Disk Array, see the HP StorageWorks Disk Array XP512 Site

Preparation Guide for cabling information for these DKUs.

Connecting the external power supply cords

The HP Disk Array XP1024 can be factory-configured for 60-amp or

30-amp, three-phase power.

60-amp, three-phase power

When the disk array uses 60-amp, three-phase input power, HP Disk Array

XP1024 DKUs have two power cords, but the DKC has no external power cords as shown in the figure below.

DKC DKU

Breaker l Box

#1

Breaker l Box

#2

AC Power

Input Box

#1

AC Power

Input Box

#2

60 A 60 A

Preparing for installation

55

56

In this configuration, an internal cable from the first (R1) DKU provides power to the DKC. If one power source malfunctions, the other power source assumes the total load, providing uninterrupted operation. HP recommends that each power cord have a separate electrical circuit as its source in case of a circuit failure. Each power-supply cord is supplied with an attachment plug type Russellstoll RS460P9W. Be sure to install

Russellstoll RS460C9W or RS460R9W socket receptacles between the power distribution panel of the building and the attachment plugs for the unit.

The power cords provided with your disk array are non-shielded, type ST or equivalent with four #4 AWG (minimum) conductors terminated at one end with an assembled plug connector.

30-amp, three-phase power

When the disk array uses 30-amp, three-phase input power, HP Disk Array

XP1024 DKCs and DKUs have two power cords each as shown in the figure below.

DKC DKU

AC Power

Input Box

#1

AC Power

Input Box

#2

AC Power

Input Box

#1

AC Power

Input Box

#2

30 A 30 A

30 A 30 A

If one power source malfunctions, the other power source assumes the total load, providing uninterrupted operation. HP recommends that each power cord have a separate electrical circuit as its source, in case of a circuit failure. Each power-supply cord is supplied with an attachment plug type

Russellstoll 3760PDG. Be sure to install Russellstoll 3934 (alternate,

HP StorageWorks Disk Array XP1024: Site Preparation Guide

9C34U0) or 3754 (alternate, 39R34U0W) socket receptacles between the power distribution panel of the building and the power plugs for the units.

The power cords provided with your disk array are non-shielded, type ST or equivalent with four #8 AWG (minimum) conductors terminated at one end with an assembled plug connector.

Branch circuit requirements

To protect your disk array, your building must be wired correctly. Each supply (“hot”) conductor must be protected by a short-circuit protective device and by an overcurrent protective device. The following tables list the current specifications for the overcurrent protective devices required for three-phase operation:

• 30-Amp, 50 or 60 Hz, three-phase DKC

(page 42)

• 60-Amp, 50 or 60 Hz, three-phase R1 DKU

(page 45)

All protective devices must comply with national standards of the country where the units are to be installed. If a protective device interrupts any supply conductor, it must also interrupt all other supply conductors.

Overcurrent protection is not required for the neutral conductor of this unit.

Only 50 Hz, three-phase configurations have a neutral conductor.

Preparing for installation

57

Three-phase AC cabling for Europe (50 Hz)

Each three-phase HP Disk Array XP1024 DKU has two main disconnect devices (two main breakers for dual power lines) so that AC power to the unit can be supplied from separate power distribution panels with two power-supply cords.

Caution

Trained service personnel should be present whenever the disk array is being connected to a new power source for the first time.

If you intend to use HP Disk Array XP512 DKUs with your HP XP1024

Disk Array, see the HP StorageWorks Disk Array XP512 Site Preparation

Guide for cabling information for these DKUs.

Connecting the power supply cords

All 50 Hz, European HP Disk Array XP1024 cabinets are shipped with unterminated power cords. Your electrician must select and install the correct power plug. Be sure to prepare the following socket receptacles and power cords between the power distribution board of the building and the attachment plugs for the unit:

60-amp power cords

Power cords of type H07RN-F or equivalent, with five 10 mm

2

conductors per cord, are provided with the unit.

Caution

Be sure to connect the power cords to the distribution panel as shown below. Improper wiring of the neutral conductor may cause damage to your disk array. To reduce the risk of a wrong connection, you should use a plug and socket that is approved for this disk array. It is your electrician’s responsibility to select and install the proper plug.

58

HP StorageWorks Disk Array XP1024: Site Preparation Guide

XP1024

Power Cord

Black

Brown

Black

Blue

Green/Yellow

N

G

L1

L2

L3

Line

Line

Line

Neutral

Safety Ground

To Power

Distribution

Panel

30-amp power cords

Power cords of type H07RN-F or equivalent, with five 6 mm

2

conductors per cord, are provided with the unit.

Caution

Be sure to connect the power cords to the distribution panel as shown in the figure above. Improper wiring of the neutral conductor may cause damage to your disk array. To reduce the risk of a wrong connection, you should use a plug and socket that is approved for this disk array. It is your electrician’s responsibility to select and install the proper plug.

When connecting to 380 to 415-volt service, a WYE configuration with neutral and ground conductors (in addition to the three-phase wires — a total of five wires) is required.

High leakage current can occur between the power supply and the unit. To avoid electrical shock, ensure that the protective earth connection is made before the supply connections.

Branch circuit requirements

When the supplied line to line voltage is in the 380 to 415-volt range, the connection must be a five-wire WYE or STAR connection.

To protect your disk array, your building must be wired correctly. Each supply (“hot”) conductor should be protected by a short-circuit protective device and by an overcurrent protective device. The following tables list

Preparing for installation

59

the current specifications for the overcurrent protective devices required for three-phase operation:

• 30-Amp, 50 or 60 Hz, three-phase DKC

(page 42)

• 60-Amp, 50 or 60 Hz, three-phase R1 DKU

(page 45)

The protective device must comply with national standards of the country where the units are to be installed. If a protective device interrupts a supply conductor, it must also interrupt all other supply conductors.

Overcurrent protection is not required for the neutral conductor.

60

HP StorageWorks Disk Array XP1024: Site Preparation Guide

Single-phase AC cabling for USA

When configured for 40/50-amp, single-phase power, each HP Disk Array

XP1024 cabinet (both the 50-amp DKC and the 40-amp DKUs) has two power cords and two main disconnect devices so that AC power can be supplied from separate power distribution panels. When configured for

30-amp, single-phase power, each HP Disk Array XP1024 cabinet has four power cords and four main disconnect devices.

Caution

Trained service personnel should be present whenever the disk array is being connected to a new power source for the first time.

If you intend to use HP Disk Array XP512 DKUs with your HP XP1024

Disk Array, see the HP StorageWorks Disk Array XP512 Site Preparation

Guide for cabling information for these DKUs.

Connecting the power-supply cords

The HP Disk Array XP1024 can be factory-configured for 40/50-amp or

30-amp, single-phase power.

Preparing for installation

61

40/50-amp, single-phase power

Each 40/50-amp HP Disk Array XP1024 cabinet has two power-supply cords with attachment plug type Russellstoll 9P53U2 as shown below.

DKC DKU

AC Power

Input Box

#1

AC Power

Input Box

#2

AC Power

Input Box

#1

AC Power

Input Box

#2

40 A 40 A 50 A 50 A

Be sure to install Russellstoll 9C53U2 or Russellstoll 9R53U2W socket receptacles between the power distribution panel of the building and the attachment plugs for the unit.

The power cords provided with your disk array are non-shielded, type ST or equivalent with three #6 AWG (minimum) conductors terminated at one end with an assembled 9C53U2 plug connector.

62

HP StorageWorks Disk Array XP1024: Site Preparation Guide

Preparing for installation

30-amp, single-phase power

Each 30-amp HP Disk Array XP1024 cabinet has four power-supply cords with attachment plug type Russellstoll 3750DP as shown below.

DKC DKU

AC Power

Input Box

#1

AC Power

Input Box

#2

AC Power

Input Box

#1

AC Power

Input Box

#2

30 A 30 A 30 A 30 A 30 A 30 A 30 A 30 A

Be sure to install Russellstoll 3933 (alternate, 9C33U0) or 3753 (alternate,

39R33U0W) socket receptacles between the power distribution panel of the building and the attachment plugs for each unit.

The power cords that are provided with your disk array are nonshielded, type SJT or equivalent with three #10 AWG (minimum) conductors that are terminated at one end with an assembled plug connector.

63

Branch circuit requirements

To protect your disk array, your building must be wired correctly. Each supply (“hot”) conductor must be protected by a short-circuit protective device and by an overcurrent protective device. The following tables list the current specifications for the overcurrent protective devices required for single-phase operation:

• 40-Amp, 50 or 60 Hz, single-phase DKC (page 40)

• 30-Amp, 50 or 60 Hz, single-phase DKC (page 41)

• 50-Amp, 50 or 60 Hz, single-phase DKU

(page 43)

• 30-Amp, 50 or 60 Hz, single-phase DKU

(page 44)

The protective device must comply with national standards of the country where the units is to be installed (USA). If a protective device interrupts a supply conductor, it must also interrupt all other supply conductors.

Note

In many cases, local codes do not allow a branch circuit fitted with a

50-amp receptacle or connector to be protected by an overcurrent-protection device with a rating lower than 50 amps. You can order your HP Disk Array XP1024 with the 30-amp power option to comply with these local codes. Your electrician knows the appropriate code requirements for your location/site.

64

HP StorageWorks Disk Array XP1024: Site Preparation Guide

Single-phase cabling for europe

When configured for 40/50-amp, single-phase power, each HP Disk Array

XP1024 cabinet (both the 40-amp DKC and the 50-amp DKUs) has two power cords and two main disconnect devices so that AC power can be supplied from separate power distribution panels. When configured for

30-amp, single-phase power, each HP Disk Array XP1024 cabinet has four power cords and four main disconnect devices.

Caution

Trained service personnel should be present whenever the disk array is being connected to a new power source for the first time.

If you intend to use HP Disk Array XP512 DKUs with your HP XP1024

Disk Array, see the HP StorageWorks Disk Array XP512 Site Preparation

Guide for cabling information for these DKUs.

Connecting the power supply cords

50-amp power cords

Each 50-amp HP Disk Array XP1024 cabinet has two power-supply cords.

The power cords included with the unit are type H07RN-F or equivalent with three 10 mm

2

conductors.

Caution

Be sure to connect the power cords to the distribution panel as shown below. Improper wiring of the neutral conductor may cause damage to your disk array. To reduce the risk of a wrong connection, you should use a plug and socket that is approved for this disk array. It is your electrician’s responsibility to select and install the proper plug.

XP1024

Power Cord

Black

Blue

Green/Yellow

L1

N

G

Line

Neutral

Safety Ground

To Power

Distribution

Panel

Preparing for installation

65

30-amp power cords

Each 30-amp HP Disk Array XP1024 cabinet has four power-supply cords.

The power cords included with the unit are type H07RN-F or equivalent with three 6 mm

2

conductors.

High leakage current may occur between the power supply and the unit. To avoid an electrical shock, be sure the protective earth connection is made before the supply connections.

Branch circuit requirements

To protect your disk array, your building must be wired correctly. Each supply (“hot”) conductor must be protected by a short-circuit protective device and by an overcurrent protective device. The following tables list the current specifications for the overcurrent protective devices required for single-phase operation:

• 40-Amp, 50 or 60 Hz, single-phase DKC (page 40)

• 30-Amp, 50 or 60 Hz, single-phase DKC (page 41)

• 50-Amp, 50 or 60 Hz, single-phase DKU

(page 43)

• 30-Amp, 50 or 60 Hz, single-phase DKU

(page 44)

The protective device must comply with national standards of the country where the units is to be installed. If a protective device interrupts a supply conductor, it must also interrupt all other supply conductors.

Note

In many cases, local codes do not allow a branch circuit fitted with a

50-amp receptacle or connector to be protected by an overcurrent- protection device with a rating lower than 50 amps. You can order your HP

Disk Array XP1024 with the 30-amp power option to comply with these local codes. Your electrician knows the appropriate code requirements for your location/site.

66

HP StorageWorks Disk Array XP1024: Site Preparation Guide

Uninterruptible Power Supply (UPS)

Caution

This uninterruptible power system (UPS) reference is for a product UPS situation. If you are planning or already have a site wide UPS,

Hewlett-Packard recommends against a product UPS powered by a site-wide UPS for the XP1024

Most HP Disk Array XP1024 units are installed in data centers where a

UPS strategy is already in place. However, if you are making your first large disk array purchase, you may need a separate UPS solution. HP references the Silcon DP300 series UPS solution, a product of American

Power Conversion Corp (APC), manufacturers of uninterruptible power systems.

UPS features

The APC UPS, Silcon DP300 series, provides the following feature set:

• Protection against short line transients

• Continued availability during short duration power failures (a minimum of 30 minutes for a fully-configured system)

• Stable AC output voltage

• LCD display unit with ability to display key AC input/output parameters, alarm log, events log and programming functions

• Communications interface option for communicating a remote UPS shutdown through the serial port connection

UPS limitations

While the UPS provides uninterrupted power to the XP array in the event of a power failure, once the battery runtime is exceeded, it shuts down, resulting in a loss of AC power to the array. The UPS does have the ability to communicate an oncoming shutdown to the host via the Silcon Triple

Chassis. The host can then pass this message in-band to the XP array using the “xppf” program.

Preparing for installation

67

Power requirements: single secondary input (primary offline)

The values in the table below are based on a worst-case voltage (rated voltage –10%) and a maximum configuration for disk control and disk array frames. A phase imbalance of 15% is also included in the calculation.

Input (Vac) Single-Phase

208

400

DKC Each

DKU

Three-Phase

First DKU

13.1 A 36.8 A 31 A

N/A N/A 17.4 A

Each Additional

DKU

24.6 A

14.4 A

In a maximum XP1024 configuration (1 DKC and 4 XP1024 DKUs) the array requires 31 kVA.

If you intend to use HP Disk Array XP512 DKUs with your

HP Disk Array XP1024, see the HP StorageWorks Disk Array XP512 Site

Preparation Guide for power requirements for these DKUs.

Reference supplier information

American Power Conversion

32 Fairgrounds Road

West Kingston, RI 0289

Phone Numbers:

Technical Support & Product Info.

1-800-800-4272

Corporate

1-800-788-2208

1-401-789-5735

To find out more about the recommended American Power Conversion

UPS, travel to the APC web site: www.apcc.com

You can also contact your HP service representatives for specific configuration needs for your area.

68

HP StorageWorks Disk Array XP1024: Site Preparation Guide

Environmental requirements

The environmental specifications for operating your disk array must be satisfied prior to installation.

If you intend to use HP Disk Array XP512 DKUs with your HP XP1024

Disk Array, see the HP StorageWorks Disk Array XP512 Site Preparation

Guide for environmental requirements for these DKUs.

Air conditioning ducts

Use separate computer room air conditioning duct work. If it is not separate from the rest of the building, it might be difficult to control cooling and air pressure levels. Duct work seals are important for maintaining a balanced air conditioning system and high static air pressure. Adequate cooling capacity means little if the direction humidity levels increase when the ducts are exposed to warm air.

Humidity

Maintain proper humidity levels. High humidity levels cause galvanic actions to occur between some dissimilar metals. This eventually causes a high resistance between connections, leading to equipment failure.

Caution

Low humidity contributes to undesirably high levels of electrostatic charges. This increases the electrostatic discharge (ESD) voltage potential.

ESD can cause component damage during servicing operations.

Static charges (voltage levels) occur when objects are separated or rubbed together. The voltage level of a static charge is determined by the following factors:

• Types of materials

• Relative humidity

• Rate of change or separation

Preparing for installation

69

70

Follow these precautions to minimize possible ESD-induced failures in your computer room:

• Install conductive flooring (conductive adhesive must be used when laying tiles).

• Use conductive wax if waxed floors are installed.

• Ensure that all equipment and flooring are properly grounded and are at the same ground potential.

• Use conductive tables and chairs.

• Store spare electric parts in antistatic containers.

• Maintain recommended humidity level an airflow rates.

Low humidity levels are often the result of the facility heating system and occur during the cold season. Most heating systems provide air with a low humidity level, unless the system has a built-in humidifier.

Dust and pollution control

For trouble free operation, disk drives require a dust-free environment. The

HP Disk Array XP1024 disk drives are protected from dust particles by mechanical air filters designed to trap large dust particles. Smaller particles can pass through some filters, and, over a period of time, can cause problems in mechanical parts. Small dust particles can be prevented from entering the computer room by maintaining its air conditioning system at a high static air pressure level.

Metallic particulate contamination

Metallic particulates can be especially harmful around electronic equipment. This type of contamination may enter the data center environment from a variety of source, including but not limited to raised floor tiles, worn air conditioning part, heating ducts, rotor brushes in vacuum cleaners, or print component wear. Because metallic particulates conduct electricity, they have an increased potential for creating short circuits in electronic equipment.This problem is aggravated by the increasingly dense circuitry of electronic equipment.

Over time, very fine whiskers of pure metal can form on electroplated zinc, cadmium, or tin surfaces. If these whiskers are disturbed, they may break

HP StorageWorks Disk Array XP1024: Site Preparation Guide

off and become airborne, possibly causing failures or operational interruptions. For over 50 years, the electronics industry has been aware of the relatively rare but possible threat posed by metallic particulate contamination. During recent years, a growing concern has developed in computer rooms where these conductive contaminants are formed on the bottom of some raised floor tiles.

Although this problem is relatively rare, it may be an issue within your computer room. Since metallic contamination can cause permanent or intermittent failures on your electronic equipment, Hewlett-Packard strongly recommends that your site be evaluated for metallic particulate contamination before the installation of electronic equipment.

Temperature and humidity specifications

When the disk array is operating, the recommended temperature range is

21

°

C to 24

°

C and recommended relative humidity range is (at 22

°

C) between 40 to 55 percent. The table below lists the full range of temperature, humidity, and vibration specifications for the HP Disk Array

XP1024. The vibration and shock specifications apply to all three axes.

Caution

No condensation in or around the HP Disk Array XP1024 should be observed under any conditions.

Preparing for installation

71

72

Specification

Temperature deviation

(

°

C/hour)

Vibration

5

Shock

Operating

1

Temperature (

°

C)

Relative humidity (%)

4

Max wet bulb (

°

C)

16 to 32

20-80

26

10

0.25 mm,

5-10 Hz

0.05 G,

10-300 Hz

Nonoperating

2

–10 to +43

8-90

27

10

2.5 mm,

5-10 Hz

0.5 G,

10-70 Hz

0.05 mm,

70-99 Hz

1.0 G,

99-300 Hz

8 G, 15 ms

Shipping and

Storage

3

–25 to +60

5-95

29

20

0.5, 15 min.

at four most severe resonances between

5-200 Hz

6

Horizontal:

7

incline impact: 1.22 m/s

Vertical:

8

rotational edge:

0.15 m

1. Environmental specification for operating condition should be satisfied before the disk subsystem is powered on. Maximum temperature of 32ºC should be strictly satisfied at the air inlet portion. The recommended temperature range is 21~24ºC.

2. Nonoperating condition includes both packing and unpacking conditions unless otherwise specified.

3. On shipping/storage condition, the product should be packed with factory packing.

4. No condensation in and around the drive should be observed under any conditions.

5. The specifications apply to all three axes.

6. See ASTM D999-86, Standard Methods for Vibration Testing of Shipping Containers.

HP StorageWorks Disk Array XP1024: Site Preparation Guide

7. See ASTM D880-86, Standard Methods of Incline Impact Test for Shipping Containers.

8. See ASTM D775-80, Standard Methods for Drop Test for Loaded Boxes.

Preparing for installation

73

Heat dissipation and power consumption

The table below describes the heat dissipation and power consumption of the HP Disk Array XP1024 in a maximum configuration:

Parameter DKC

Power consumption (kVA) 3.09

Heat dissipation (kW) 2.94

BTUs per hour kcal per hour

10034

2528

Each DKU

6.94

6.40

21843

5504

Full Array

(4 DKUs &

1 DKC)

30.85

28.53

97373

24536

If you intend to use HP Disk Array XP512 DKUs with your HP XP1024

Disk Array, see the HP StorageWorks Disk Array XP512 Site Preparation

Guide for heat dissipation and power consumption information for these

DKUs.

74

HP StorageWorks Disk Array XP1024: Site Preparation Guide

Altitude

When operating the HP Disk Array XP1024, the maximum altitude is 3,000 meters. For nonoperational situations, the maximum altitude is 4,000 meters.

If you intend to use HP Disk Array XP512 DKUs with your HP XP1024

Disk Array, see the HP StorageWorks Disk Array XP512 Site Preparation

Guide for altitude specifications for these DKUs.

Preparing for installation

75

Acoustics

Computer equipment and air conditioning blowers cause computer rooms to be noisy. Ambient noise level in a computer room can be reduced as follows: dropped ceiling Cover with a commercial-grade fire-resistant, acoustic rated, fiberglass ceiling tile.

sound deadening Cover the walls with sound-deadening material.

removable partitionsTo be most effective, use foam rubber models.

The acoustic emission specifications for the HP XP1024 Disk Array are:

• 8.27 Bels (A) sound power

• 64 dB (A) sound pressure, operator position

If you intend to use HP Disk Array XP512 DKUs with your HP XP1024

Disk Array, see the HP StorageWorks Disk Array XP512 Site Preparation

Guide for acoustic-emission specifications for these DKUs.

76

HP StorageWorks Disk Array XP1024: Site Preparation Guide

Delivery space requirements

There should be enough clearance to move equipment safely from the receiving area to the computer room. Permanent obstructions, such as pillars or narrow doorways, can cause equipment damage.

Delivery plans should include the possible removal of walls or doors. The

physical dimensions are summarized on page 24 .

Preparing for installation

77

78

HP StorageWorks Disk Array XP1024: Site Preparation Guide

4

Receiving your HP Disk Array XP1024

Your HP Disk Array XP1024 is shipped directly from HP. If your disk array is part of a system order, HP coordinates the shipment of equipment from all locations so that it arrives at your site at approximately the same time.

In some cases, factors beyond the control of HP can cause delivery delays.

If you have not received your equipment within a two week period, notify your HP sales representative. The HP sales representative traces your order and expedites delivery.

Caution

Be sure to allow for size and weight in regards to placing the disk array at

its installation site. Refer to “Dimensions” (page 24) for specific size and

weight values.

Receiving your HP Disk Array XP1024

79

Checking for shipping shortage and damage

As your disk array arrives, check the carrier’s bill of lading carefully to ensure that all items shipped by HP are delivered. Notify the carrier immediately if there are any discrepancies or items missing.

Inspect all of the shipping containers for signs of damage before actually unpacking the equipment. Some typical signs of shipping damage are dents, scratches, cuts, or water marks. If any damage is found, note on the bill of lading that there is apparent damage subject to inspection. Arrange for the carrier’s representative and a representative from Hewlett-Packard to be present when the item in question is unpacked.

Regardless of the circumstances, the HP CE takes immediate action to replace any damaged components without waiting for the settlement of claims.

80

HP StorageWorks Disk Array XP1024: Site Preparation Guide

Unpacking the cartons

The equipment cartons can be unpacked at your convenience; it is your responsibility to have the equipment unpacked and moved to its proper installation location prior to the day of installation.

The DKC and DKU frames are very heavy. In a maximum configuration, the DKU weighs more than 1600 lb. It is recommended that three (3) people unpack and move this equipment to avoid injury.

Retain the packing list (invoice) for each carton that is to be unpacked and ensure that each item on the list can be accounted for. Contact your HP sales representative immediately if there are any missing items, or if the items are not the same as you ordered.

Leave the sealed cartons or packages of CDs, cables, and any other installation hardware intact for the HP CE. Your HP CE and HP ASE install and configure your disk array.

Receiving your HP Disk Array XP1024

81

82

HP StorageWorks Disk Array XP1024: Site Preparation Guide

BC

BS

BTU

Glossary

ACP

AL

AL-PA allocation array group

Glossary

Array control processor. The ACP handles the passing of data between the cache and the physical drives held in the DKUs. ACPs work in pairs, providing a total of eight SCSI buses. Each SCSI bus associated with one

ACP is paired with a SCSI bus on the other ACP pair element. In the event of an ACP failure, the redundant ACP takes control. Both ACPs work together sharing the load.

Arbitrated loop.

Arbitrated loop physical address.

The ratio of allocated storage capacity versus total capacity as a percentage.

“Allocated storage” refers to those LDEVs that have paths assigned to them. The allocated storage capacity is the sum of the storage of these

LDEVs. Total capacity refers to the sum of the capacity of all LDEVs on the disk array.

A group of 4 or 8 physical hard disk drives (HDDs) installed in an XP disk array and assigned a common RAID level. RAID1 2d+2d array groups are made up of 4 HDDs. A RAID1 4d+4d group is two 4 HDD array groups concatenated together. RAID5 array groups are made up of 4 or 8 HDDs, depending on whether they are RAID5 3d+1p or RAID5 7d+1p, respectively. All RAID6 array groups are made up of 8 HDDs.

The HP StorageWorks Business Copy XP software program, which enables you to maintain up to nine internal copies of logical volumes on the disk array.

Basic supply.

British thermal unit.

83

<Symbol font>×C

C-Track

CA ca cache

CDE

CE

CFW

CH channel adapter

(CHA) channel host interface processor

(CHIP) channel processor

(CHP)

Degrees centigrade/Celsius.

The HP StorageWorks Continuous Track XP software program, which detects internal hardware component problems on a disk array and automatically reports them to the HP STC.

The HP StorageWorks Continuous Access XP software program, which enables you to create and maintain duplicate copies of the data store on a local disk array.

Cache.

Very high speed memory that is used to speed I/O transaction time. All reads and writes to the XP array family are sent to the cache. The data is buffered there until the transfer to/from physical disks (with slower data throughput) is complete.

The benefit of cache memory is that it speeds I/O throughput to the application. The larger the cache size, the greater amount of data buffering can occur and the greater throughput to the applications.

XP arrays support a range of cache memory. In the event of power loss, battery power allows the contents of the cache boards to survive for up to

48 hours.

Common desktop environment.

Customer engineer.

Cache fast write.

Channel.

The channel adapter (CHA) provides the interface between the disk array and the external host system. Occasionally this term is used synonymously with the term channel host interface processor (CHIP).

Synonymous with the term channel adapter (CHA).

The processors located on the channel adapter (CHA).

84

HP StorageWorks Disk Array XP1024: Site Preparation Guide

CHPID

CKD

CL command device configuration file consistency group ID

(CTGID) control unit

CSA

CU

CVS daemon

DASD

DCR

DE

DFDSS

DFSMS

DFW disk adapter (DKA)

Channel path identifier.

Count key data.

Cluster.

A volume on the disk array that accepts CA or BC control operations which are then executed by the disk array.

A file that defines the pair configurations.

The group identifier for which the disk array guarantees the sequence of asynchronous data transfer for the asynchronous CA volume group.

To organize the storage space attached to the DKC, you can group similarly configured logical devices (LDEVs) with unique control unit images

(CUs). CUs are numbered sequentially. The disk array supports a certain number of CUs, depending on the disk array model. Each CU can manage multiple LDEVs. Therefore, to uniquely identify a particular LDEV requires both the CU number and the LDEV number.

Canadian Standards Association.

Control unit.

Custom volume size (also called virtual LVI).

A process that runs in the background and performs a specific operation at predefined times in response to certain events.

Direct access storage device.

Dynamic cache residency.

HP StorageWorks Data Exchange XP.

Data Facility Dataset Services.

Data Facility System Managed Storage.

DASD fast write.

Synonymous with the term ACP.

Glossary

85

disk control frame

(DKC) disk array frame

(DKU) disk recovery and restore unit (DRR) disk group disk type

DMP dr

DSF

DW

DWL

ECKD

EFS emulation modes

EOF

The disk control frame (DKC) refers to the array hardware that houses the channel adapters and service processor (SVP).

The disk array frame (DKU) refers to the array hardware that houses the physical disks in the array.

The unit located on the ACP that is responsible for data recovery and restoration in the event of a cache failure.

The physical disk locations associated with a parity group.

The manufacturing label burned into the physical disk controller firmware.

In most cases, the disk type is identical to the disk model number.

Dynamic multipathing.

Drive.

Device support facilities.

Duplex write.

Duplex write line.

Extended count key data.

The IRIX standard file system.

The logical devices (LDEVs) associated with each RAID group can have one of the following emulation modes. These modes change the behavior of the disks and determine their size.

OPEN-3:

OPEN-8:

OPEN-9:

OPEN-E:

OPEN-K:

OPEN-L:

OPEN-M

OPEN-V:

End of field.

2.46 GB

7.38 GB

7.42 GB

13.56 GB

Not available on XP12000

36 GB

Not available on XP12000

User-defined custom size

86

HP StorageWorks Disk Array XP1024: Site Preparation Guide

EPO

EREP

ESA

ESCON expanded LUN

ExSA failover

<Symbol font>×F

FAL

FBA

FC

FC-AL

FCC

FCP

FCU

FDR fence level

F/M ft.

FWD

Emergency power-off.

Error reporting.

Enterprise Systems Architecture.

Enterprise System Connection (the IBM trademark for optical channels).

A LUN is normally associated with only a single LDEV. The LUSE feature allows a LUN to be associated with 1 to 36 LDEVs. Essentially, LUSE makes it possible for applications to access a single large pool of storage.

The LUSE feature is available when the HP StorageWorks LUN

Configuration Manager product is installed.

Extended serial adapter.

Disconnecting a failed portion and replacing it with another normal portion or alternative portion in order to continue functioning.

Degrees Fahrenheit.

File access library (part of the Data Exchange software).

Fixed-block architecture.

Fibre Channel.

Fibre Channel arbitrated loop.

Federal Communications Commission.

Fibre Channel Protocol.

File conversion utility (part of the Data Exchange software).

Fast dump/restore.

A level for selecting rejection of a write I/O request from the host according to the condition of mirroring consistency.

Format/message.

Foot or feet.

Fast wide differential.

Glossary

87

hot standby

HP

H/W

Hz

ICKDSF

IDCAMS

IML in.

88

fx

GB

GLM

HA

HBA

HCD

HORCM_CMD

HORCM_DEV

HORCM_INST

HORCM_MON host mode

The IRIX disk utility.

Gigabytes.

Gigabyte link module.

High availability.

Host bus adapter.

Hardware configuration definition.

A section of the RAID Manager instance configuration file that defines the disk devices used by RAID Manager to communicate with the disk array.

A section of the RAID Manager instance configuration file that defines the volumes of the instance.

A section of the RAID Manager instance configuration file that defines how RAID Manager groups link to remote RAID Manager instances.

A section of the RAID Manager instance configuration file that defines the instance you are configuring.

Each port can be configured with various options referred to as host modes.

These modes are represented as two-digit hexadecimal numbers. The first digit, usually 0, represents different things on different arrays. The second hex digit represents the host system type. For example, the 8 in mode 08 represents an HP-UX host.

Using two or more servers as a standby in case of a primary server failure.

Hewlett-Packard Company.

Hardware.

Hertz.

A DSF command used to perform media maintenance.

Access method services (a component of Data Facility Product).

Initial microprogram load.

Inches.

HP StorageWorks Disk Array XP1024: Site Preparation Guide

I/O

IOCP instance km kVA kW

LAN

JCL

KB kcal kg lb.

LCP

LD, LDEV

LED local disk local instance

LPAR

LCP

LRU

Glossary

Input/output (applies to an operation or device).

Input/output configuration program

An independent copy of RAID Manager. Instances are local or remote and can run on the same host.

Job control language.

Kilobyte.

Kilocalorie.

Kilogram.

Kilometer.

Kilovolt-ampere.

Kilowatt.

Local area network.

Pound.

Local control port.

Logical device. An LDEV is created when a RAID group is carved into pieces according to the selected host emulation mode (that is, OPEN-3,

OPEN-8, OPEN-9). The number of resulting LDEVs depends on the selected emulation mode. The term LDEV is often used synonymously with the term volume.

Light emitting diode.

A local disk in the host.

The instance currently being configured or the instance to which commands are issued.

Logical partition.

Link control processor or local control port.

Least recently used.

89

LU

LUN

LUSE

LVI

LVM

LVM mirror m

MB

MCU mirroring consistency mm

MP

MPLF

MR ms, msec mutual hot standby system

MVS

NHAS node

Logical unit.

Logical unit number. A LUN results from mapping a SCSI logical unit number, port ID, and LDEV ID to a RAID group. The size of the LUN is determined by the emulation mode of the LDEV, and the number of LDEVs associated with the LUN. For example, a LUN associated with two OPEN-

3 LDEVs has a size of 4,693 MB.

Logical unit size expansion.

Logical volume image.

Logical Volume Manager.

A disk duplicating function provided by Logical Volume Manager (LVM)

(capable of triplicating disks).

Meters.

Megabytes.

Main control unit.

The consistency (usability) of data in a volume (for example, S-VOL).

Millimeters.

Microprocessor.

Multipath Locking Facility.

Magnetoresistive.

Milliseconds.

Two servers that are poised to cover for each other if necessary.

Multiple Virtual Storage (including MVS/370, MVS/ESA, MVS/XA).

Novell High Availability Server.

Logically speaking, an environment where instances can be executed.

Physically, a processor, which is an element of a cluster system.

90

HP StorageWorks Disk Array XP1024: Site Preparation Guide

P-P

PPRC

PS

Glossary

path

PCI

PM port

NVS

OFC

OLM

ORM

OS

P/DAS

PA parity group partition

Nonvolatile storage.

Open Fibre Control.

Optical link module.

Online read margin.

Operating system.

PPRC/dynamic address switching.

Physical address.

A parity group is a mode of disk operation and configuration. It is synonymous with the term “array group.”

Dividing a specific physical disk according to the HP-UX kernel or device driver layer into two or more areas as if there are two or more physical disks.

Paths are created by associating a port, a target, and a LUN ID to one or more LDEVs.

Power control interface or peripheral component interconnect.

HP StorageWorks Performance Manager XP software.

The number of supported ports on an XP disk array depends on the number of supported I/O slots and the number of ports available per I/O adapter.

The XP family of disk arrays supports SCSI, Fibre Channel (FC/AL),

ESCON, and FICON I/O interfaces. I/O support can vary with the selected

disk array.

Ports are named based upon their port group and port letter. Examples of port names include CL1-A through CL1-R and CL2-A through CL2-R

(letters I and O are skipped).

Point-to-point.

Peer-to-peer remote copy.

Power supply.

91

P-VOL

RS

RAID

RAID group

RAID level

RAM remote instance

RISC

RM

RM instance configuration file

R-SIM

R/W, r/w

S/390

SAM script file

SCSI sec.

seq.

92

The primary or main volume that contains the data to be copied.

Russellstoll

®

, a brand of electrical plugs and receptacles manufactured by

Thomas & Betts Corporation.

Redundant array of inexpensive disks.

See “array group.”

A RAID Level is one of the ways that disk drives are grouped together in a

RAID to improve performance, data availability/reliability or both. RAID levels are defined from RAID0 to RAID6. HP StorageWorks Disk Arrays in the XP product family support RAID1, RAID5 and RAID6. Not all of these RAID levels are supported by all XP family members. Consult the owner's guide or your HP representative for the details of which RAID levels are supported by your specific XP disk array.

Random access memory.

The instance to which the local instance communicates as configured in the

HORCM_INST section of the RAID Manager instance configuration file.

Reduced instruction set computer.

HP StorageWorks RAID Manager XP.

A file that defines the link between a volume and a RAID Manager instance. This file consists of four sections: HORCM_MON,

HORCM_CMD, HORCM_DEV, and HORCM_INST.

Remote service information message.

Read/write.

IBM System/390 architecture.

System Administration Manager.

A file containing a shell script.

Small computer system interface.

Second.

Sequential.

HP StorageWorks Disk Array XP1024: Site Preparation Guide

SGI shell script

Sidefile

SIM

SMI-S

SMIT

SMS

SNMP special files

SSID

STC

SVP

S-VOL takeover

TB

TCP/IP

TID

TPF

TSO

Glossary

Silicon Graphics Incorporated.

A command sequence executed by a UNIX shell.

An area of cache used to store the data sequence number, record location, record length, and queued control information before transmit over the

ESCON link.

Service information message.

Storage Management Initiative Specification.

System Management Interface Tool.

System managed storage.

Simple Network Management Protocol.

Files that indicate physical devices and are different from regular files in the UNIX system. The functions of the device drivers (that is, access to system peripherals) become available through these special files.

Storage subsystem identification.

HP Storage Technology Center.

Service processor, which is the laptop PC that is built into the DKC. The

SVP provides a direct interface into the disk array. SVP use is reserved for

HP support representatives only.

Secondary or remote volume. The copy volume that receives the data from the primary volume.

The actions of a standby server that takes over processing from the previously active server.

Terabyte.

Transmission control protocol/Internet protocol

Target ID.

Transaction processing facility.

Time-sharing option (an IBM System/370 operating system option).

93

VSE

VTOC

XA

XDF

XF

XLV

UCB

UL

VDE

VM

VOLID volser

Volume

XRC

Unit control block.

Underwriters’ Laboratories.

Verband Deutscher Elektrotechniker.

Virtual machine (an IBM S/390 system control program).

Volume ID.

Volume serial number.

Synonymous with LDEV.

Extended Remote Copy.

Virtual Storage Extension (an IBM S/390 operating system).

Volume table of contents.

System/370 Extended Architecture.

Extended distance feature (for ExSA channels).

IRIX extended file system.

Extended logical volume manager.

94

HP StorageWorks Disk Array XP1024: Site Preparation Guide

Index

A acoustics

XP512

76

altitude

XP512

75

American Power Conversion (APC) supplier information

68

application software engineer (ASE) site preparation team

14

audience intended

5

authorized reseller, HP

7

C cables

XP512 routing space

29

clearance

XP512 service

31

computer room

XP512 requirements

21

conventions documentation

5

customer site preparation responsibilities

14

customer engineer (CE) site preparation team

14

Index

D damage, shipping

XP512

80

data communications

XP512 requirements

36

delivery

XP512

77

dimensions

XP512

24

,

27

disk arrays supported

5

documentation conventions

5

related

5

E electrical interference sources of

53

electrical requirements

XP512

38

environmental requirements

XP512

69

F floor

XP512 load

30

95

H heat dissipation

XP512

74

help obtaining

6

HP authorized reseller

7

technical support

6

I installation

XP512

19

P power cord

3-phase AC (Europe)

58

3-phase AC (USA)

55

single-phase (Europe)

65

single-phase AC (USA)

61

power supply

XP512

67

R related documentation list of

5

S safety

XP512

20

sales representative (SR) site preparation team

14

site preparation checklist

16

physical requirements

24

,

27

preparations before delivery

18

team

14

system administrator required knowledge

5

96

T technical support

W

X

HP weight

XP512

6

XP512

24

unpacking

81

HP StorageWorks Disk Arrays XP128/XP1024: Owner’s Guide

Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertisement