AutroSafe Power Module - BSS-310
Features
•
Provides 24V DC and 5V DC regulated voltage to all panel mounted I/O modules.
•
Easily plugged onto a standard mounting rail.
•
Designed to meet EN-54 and LPCB requirements and conforms to CE standards.
Application / Description
The Power Module BSS-310 converts unregulated battery voltage to 24V DC and 5V DC regulated voltage to all I/O modules mounted in the Fire Alarm Control Panel
(BS-310/320) or the Controller (BC-320).
The power can be increased by connecting several modules in parallel.
Mounting
The Power Module is always delivered with the Fire Alarm
Control Panel (BS-310/320) or the Controller (BC-320).
The module is easily plugged onto a mounting rail - as the first module placed at the bottom of the rail - inside the Fire
Alarm Control Panel (BS-310/320) or the Contro ller
(BC-320).
Cabling
Two wires are used for the internal connection between the connection block on the Power Module BSS-310 and the terminals on the Connection Module BSF-310A.
Refer to connection drawing / schematics on the other side of this data sheet.
Connections / Indicators
Front view when mounted on rail
Green indicator
H2 (5V)
Screw terminal 10
Green indicator
H1 (24V)
Screw terminal 1
The module has two green indicators;
•
Right green indicator (H1) - the presence of 24V DC
•
Left green indicator (H2) - the presence of 5V DC
The I/O module has the following connections:
Screw Terminal no.
1
2
3
4
7
8
5
6
9
10
Signal
+24 V Input
+24 V Input
0 V Input
0 V Input
Chassis
Chassis
Not in use
Not in use
Not in use
Not in use
P-BSS310/CE-Rev. B, 000315 Protecting environment, life and property...
Power Module, BSS-310
Technical Specifications
Dimensions (mm)
Weight (g)
Materials
Electrical connection
Mounting
Current Consumption (idle)
Maximum output power,
24V regulated
Maximum output power,
5V
Input voltage
24V Output
5V Output
95x89x32
81
Top and bottom: Zytel FR7200
Snap-on mounting device: Zytel 7335S
Internal system: plug-in connection
Removable screw terminals (maximum cable dimension 2,5mm
2
)
Onto a standard 35 mm mounting rail inside the Fire Alarm Control Panel or
Controller.
40mA
840mA
100mA
18-32 V DC
24V +/- 5%
5V +/- 5%
Order Numbers
Order number
BSS-310
Description
Power Module
Ship Weight metric/imperial
Installation Overview
BSF-310A
5
4
-
-
+
+
1
2
3
4
5
6
BSS-310
Chassis
I/O Modules
Schematics
24V DC input
1
0V
3 BSS-310
Chassis
5
Internal
+ 24V reg
Internal
+ 5V reg
Internal
0V
Autronica Fire and Security AS
Fire and Security, Trondheim, Norway. Phone: + 47 73 58 10 00, fax: + 47 73 91 93 00.
Oil & Gas, Stavanger, Norway. Phone: + 47 51 84 09 00, fax: + 47 51 84 09 49.
Autronica Industrial Ltd., Watford, United Kingdom. Phone: 1923 23 37 68, fax: 1923 22 55 77.
Autronica AS, Marine Sales, Oslo, Norway. Phone: + 47 22 55 34 10, fax: + 47 22 55 30 46.
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project