AutroSafe Power Module - BSS-310

Features

Provides 24V DC and 5V DC regulated voltage to all panel mounted I/O modules.

Easily plugged onto a standard mounting rail.

Designed to meet EN-54 and LPCB requirements and conforms to CE standards.

Application / Description

The Power Module BSS-310 converts unregulated battery voltage to 24V DC and 5V DC regulated voltage to all I/O modules mounted in the Fire Alarm Control Panel

(BS-310/320) or the Controller (BC-320).

The power can be increased by connecting several modules in parallel.

Mounting

The Power Module is always delivered with the Fire Alarm

Control Panel (BS-310/320) or the Controller (BC-320).

The module is easily plugged onto a mounting rail - as the first module placed at the bottom of the rail - inside the Fire

Alarm Control Panel (BS-310/320) or the Contro ller

(BC-320).

Cabling

Two wires are used for the internal connection between the connection block on the Power Module BSS-310 and the terminals on the Connection Module BSF-310A.

Refer to connection drawing / schematics on the other side of this data sheet.

Connections / Indicators

Front view when mounted on rail

Green indicator

H2 (5V)

Screw terminal 10

Green indicator

H1 (24V)

Screw terminal 1

The module has two green indicators;

Right green indicator (H1) - the presence of 24V DC

Left green indicator (H2) - the presence of 5V DC

The I/O module has the following connections:

Screw Terminal no.

1

2

3

4

7

8

5

6

9

10

Signal

+24 V Input

+24 V Input

0 V Input

0 V Input

Chassis

Chassis

Not in use

Not in use

Not in use

Not in use

P-BSS310/CE-Rev. B, 000315 Protecting environment, life and property...

Power Module, BSS-310

Technical Specifications

Dimensions (mm)

Weight (g)

Materials

Electrical connection

Mounting

Current Consumption (idle)

Maximum output power,

24V regulated

Maximum output power,

5V

Input voltage

24V Output

5V Output

95x89x32

81

Top and bottom: Zytel FR7200

Snap-on mounting device: Zytel 7335S

Internal system: plug-in connection

Removable screw terminals (maximum cable dimension 2,5mm

2

)

Onto a standard 35 mm mounting rail inside the Fire Alarm Control Panel or

Controller.

40mA

840mA

100mA

18-32 V DC

24V +/- 5%

5V +/- 5%

Order Numbers

Order number

BSS-310

Description

Power Module

Ship Weight metric/imperial

Installation Overview

BSF-310A

5

4

-

-

+

+

1

2

3

4

5

6

BSS-310

Chassis

I/O Modules

Schematics

24V DC input

1

0V

3 BSS-310

Chassis

5

Internal

+ 24V reg

Internal

+ 5V reg

Internal

0V

Autronica Fire and Security AS

Fire and Security, Trondheim, Norway. Phone: + 47 73 58 10 00, fax: + 47 73 91 93 00.

Oil & Gas, Stavanger, Norway. Phone: + 47 51 84 09 00, fax: + 47 51 84 09 49.

Autronica Industrial Ltd., Watford, United Kingdom. Phone: 1923 23 37 68, fax: 1923 22 55 77.

Autronica AS, Marine Sales, Oslo, Norway. Phone: + 47 22 55 34 10, fax: + 47 22 55 30 46.

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals

Download PDF

advertisement