With growing demand for power supply to distribution cabinets, manufacturers of power distribution units should offer a very wide range of products in order to meet the
growing requirements of the market.
Innovative solutions, development of products providing modern power supply to server rooms and continuous expansion of the offer are the means of BKT Elektronik to
meet all the needs of our Customers.
Power distribution units from our offer have numerous applications in information technology and telecommunications.
They were designed for small hanging cabinets, as well as for standing 19” distribution cabinets.
You can now choose the right model thanks to our rich and diverse offer of input connectors, outlets, control and protection modules used in 19” power distribution units.
We expanded our offer concerning server rooms, adding three-phase power distribution units, whose modular and multifunctional structure has enabled us to sell ready-touse products from our offer, as well as to create one- or three-phase distribution units with current-carrying capacity of 32 A with a Customer to fulfill particular requirements
of Investors.
Building a power distribution unit from scratch, we can adopt the existing electric infrastructure, adjust the number and type of outlets for particular devices and add
protection units and ammeters in configuration that is in line with the current requirements of Data Center market.
Development and unlimited access to network infrastructure has forced a natural development of power distribution units. Thanks to it, NPM units have now the feature of
remote monitoring of voltage [V], current [A], power [kW] and total power usage [kWh], including the monitoring of an individual outlet of a power distribution unit.
We can now improve the safety through monitoring of distribution cabinets and server rooms environment and determining alarm thresholds for installed sensors with the
feature of remote reporting (E-mail, SNMP trap).
The latest generation of maintainable power distribution units can be controlled through Ethernet, WiFi, Web interface (http, https), Telnet, SSH, SNMP (V1, V2c, V3). What is
more, you can also remotely authorize users through RADIUS server.
If a bigger number of power distribution units is installed, they can be series connected (Master-Slave), which significantly reduces the need for IP network resources.
Network Power Manager units allow the management of one- and three-phase power supply from 16 to 32 A. They increase the security, monitoring the conditions in server
cabinet in case there are unwanted physical and chemical environmental factors, such as temperature, humidity, water and smoke. They also inform the maintainers through
TCP/IP protocol about unauthorized access to the equipment inside a cabinet.
BKT Elektronik has also launched a product that provides redundancy and uninterruptable operation of network devices. Automatic Transfer Switch (ATS) is a device that
switches between power lines in less than 16 ms at current-load of 16 and 32 A and does not interrupt the operation of equipment connected to it.
Contents
19” Power Distribution Units
1-4
Vertical (0U) Power Distribution Units
Single-phase Vertical Power Distribution Units
Three-phase Vertical Power Distribution Units
Power Cables
5-7
5
6-7
7
Monitoring and Management Power Distribution Unit
Management IP-PDU
Management PCDS Units
Monitoring Managament and Controlling PDUs
Managament MS-PDU
NPM V - Network Power Management
Enviroment Monitoring System Conditions
EMS-Environment Monitoring System
Automatic Transfer Switch
ATS-Automatic Transfer Switch
8-15
8-11
12-15
16-27
16-19
20-27
28-32
28-32
33-35
33-35
19” Power Distribution Units
Power Distribution Units offered by BKT Elektronik has been specially designed for 19” distribution cabinets. Their modular, multifunctional structure will meet the needs of
every Customer. You can choose between many standards of input connectors, outlets, and control and protection modules. Their casing is made of white aluminum. PDUs are
panel-mounted in 19” standard.
19” PDUs with NF C61-314 Outlets
19” PDUs with NF C61-314 Outlets
Index
1134L010.05-1
Index
1134L030.09-1
Input Connector
DIN 49441 (unischuko)/ 16A, 250V
Input Connector
DIN 49441 (unischuko)/16A, 250V
Cable
1,8 m H05VV-F 3 x 1,5 mm2
Cable
2,3 m H05VV-F 3 x 1,5 mm2
Outlets
5 x NF C61-314 (PL, FR Standard)/16A, 250V
Outlets
9 x NF C 61-314 (PL, FR Standard)/16A, 250V
Additional Elements
Lighted switch
Additional Elements
LED indicator
Maximum Current-load
16A (3500W)
Maximum Current-load
16A (4000W)
Size L x W x H [mm]
482.6 x 44.4 x 44.4
Size L x W x H [mm]
482.6 x 44.4 x 44.4
Casing
1U, 19”, black plastic, fixed holders
Casing
1U, 19”, anodized aluminum, fixed holders
19” PDUs with NF C61-314 Outlets
19” PDUs with NF C61-314 Outlets
Index
1134L010.09-1
Index
1134L230.09-1
Input Connector
DIN 49441 (unischuko)/16A, 250V
Input Connector
IEC320 C14/10A, 250V
Cable
2,3 m H05VV-F 3 x 1,5 mm2
Cable
2,3 m H05VV-F3 x 1,5mm2
Outlets
9 x NF C 61-314 (PL, FR Standard)/ 16A, 250V
Outlets
9 x NF C61-314 (PL, FR Standard)
Additional Elements
Lighted switch with a cover
Additional Elements
LED indicator
Maximum Current-load
16A (4000W)
Maximum Current-load
10 A (2500W)
Size L x W x H [mm]
482.6 x 44.4 x 44.4
Size L x W x H [mm]
482.6 x 44.4 x 44.4
Casing
1U, 19”, anodized aluminum, fixed holder
Casing
1U, 19”, anodized aluminum, fixed holders
19” PDUs with NF C61-314 Outlets
19” PDUs with NF C61-314 Outlets
Index
1134L012.07-1
Index
1134L016.06-1
Input Connector
DIN 49441 (unischuko)/16A, 250V
Input Connector
DIN 49441 (unischuko)/16A, 250V
Cable
2,3 m H05VV-F 3 x 1,5 mm2
Cable
2,3 m H05VV-F 3 x 1,5 mm2
Outlets
7 x NF C61-314 (PL, FR Standard)/16A, 250V
Outlets
6 x NF C61-314 (PL, FR Standard)/16A, 250V
Additional Elements
Lighted switch with a cover
Additional Elements
Lighted switch with a cover
Additional Elements
LED indicator
Un: 250 V~ 50/60 Hz IL: 16A
Uc: 320V~
In (8/20 µS): 3 kA
Surge Protection with
a Filter
3 x LED indicator
UN: 250V ~ 50/60Hz IL: 16A
Uc: 320V ~
In (8/20) µs: 5kA
Maximum Current-load
16A (4000W)
Maximum Current-load
16A (4000W)
Size L x W x H [mm]
482.6 x 44.4 x 44.4
Size L x W x H [mm]
482.6 x 44.4 x 44.4
Casing
1U, 19”, anodized aluminum, fixed holders
Casing
1U, 19”, anodized aluminum, fixed holders
1
Imax (8/20)
Mp: L-N, L-PE, N-PE
Imax (8/20) µs: 10kA
Up: <1 kV tA: < 25 ns
EN type: T3
19” Power Distribution Units
19” PDUs with NF C61-314 Outlets
19” PDUs with DIN 49440 Outlets
Index
1134L630.09-1
Index
1134L030.09-0
Input Connector
IEC320 C20/16A, 250V
Input Connector
DIN 49441 (unischuko)/16A, 250V
Cable
2,3 m H05VV-F3 x 1,5mm2
Cable
2,3 m H05VV-F 3 x 1,5 mm2
Outlets
9 x NF C61-314 (PL, FR Standard)/16A, 250V
Outlets
9 x DIN 49440 (schuko)/16A, 250V
Additional Elements
LED indicator
Additional Elements
LED indicator
Maximum Current-load
16A (4000W)
Maximum Current-load
16A (4000W)
Size L x W x H [mm]
482.6 x 44.4 x 44.4
Size L x W x H [mm]
482.6 x 44.4 x 44.4
Casing
1U, 19”, anodized aluminum, fixed holders
Casing
1U, 19” , anodized aluminum, fixed holders
19” PDUs with DIN 49440 Outlets
19” PDUs with DIN 49440 Outlets
Index
1134L010.09-0
Index
1134L210.09-0
Input Connector
DIN 49441 (unischuko)/16A, 250V
Input Connector
IEC320 C14/10A, 250V
Cable
2,3 m H05VV-F 3 x 1,5 mm2
Cable
2,3 m H05VV-F 3 x 1,5 mm2
Outlets
9 x DIN 49440 (schuko)/16A, 250V
Outlets
9 x DIN 49440 (schuko)/16A, 250V
Additional Elements
Lighted switch with a cover
Additional Elements
Lighted switch with a cover
Maximum Current-load
16A (4000W)
Maximum Current-load
10A (2500W)
Size L x W x H [mm]
482.6 x 44.4 x 44.4
Size L x W x H [mm]
482.6 x 44.4 x 44.4
Casing
1U, 19”, anodized aluminum, fixed holders
Casing
1U, 19”, anodized aluminum, fixed holders
19” PDUs with DIN 49440 Outlets
19” PDUs with DIN 49440 Outlets
Index
1134L012.07-0
Index
1134L016.06-0
Input Connector
DIN 49441 (unischuko)/16A, 250V
Input Connector
DIN 49441 (unischuko)/16A, 250V
Cable
2,3 m H05VV-F 3 x 1,5 mm2
Cable
2,3 m H05VV-F 3 x 1,5 mm2
Outlets
7 x DIN 49440 (schuko)/16A, 250V
Outlets
6 x DIN 49440 (schuko)/16A, 250V
Additional Elements
Lighted switch with a cover
Additional Elements
Lighted switch with a cover
Surge Protection
LED indicator
UN: 250V ~ 50/60Hz IL: 16A
Uc: 320V ~
In (8/20)µs: 3kA
Imax (8/20) µs: 5kA
Surge Protection
3 x LED indicator
UN: 250V ~ 50/60Hz IL: 16 A
Uc: 320V ~
In (8/20) µs: 5kA
Imax (8/20) µs: 10kA
Maximum Current-load
16A (4000W)
Maximum Current-load
16A (4000W)
Size L x W x H [mm]
482.6 x 44.4 x 44.4
Size L x W x H [mm]
482.6 x 44.4 x 44.4
Casing
1U, 19” , anodized aluminum, fixed holders
Casing
1U, 19” , anodized aluminum, fixed holders
Uoc: 4 kV
Up: <1 kV tA: < 25 ns
EN type: T3
Mp: L-N L-PE N-PE
Up: <1 kV tA: < 25 ns
EN type: T3
2
19” Power Distribution Units
19” PDUs with IEC320 C13 Outlets
19” PDUs with IEC320 C13 Outlets
Index
1134L010.08-2
Index
1134L230.09-2
Input Connector
DIN 49441 (unischuko)/16A, 250V
Input Connector
IEC320 C14/10A, 250V
Cable
2,3 m H05VV-F 3 x 1,5 mm2
Cable
2,3 m H05VV-F 3 x 1,5 mm2
Outlets
8 x IEC320 C13/10A, 250V
Outlets
9 x IEC320 C13/ 10A, 250V
Additional Elements
Lighted switch
Additional Elements
LED indicator
Maximum Current-load
10A (2500W)
Maximum Current-load
10A (2500W)
Size L x W x H [mm]
482.6 x 44.4 x 62
Size L x W x H [mm]
482.6 x 60 x 44.4
Casing
1U, 19” , anodized aluminum, fixed holders
Casing
1U, 19” , anodized aluminum, fixed holders
19” PDUs with IEC320 C13 Outlets
19” PDUs with IEC320 C13 Outlets
Index
11341004.08-2,08-2
Index
11341704.08-2,06-6
Input Connector
DIN 49441 (unischuko)/16 A, 250V
Input Connector
IEC 60309/16A, 250V
Cable
3 m H05VV-F 3 x 1,5 mm2
Cable
3 m H05VV-F 3 x 2,5 mm2
Outlets
Front 8 x IEC320 C13/10A, back 8 x IEC320 C13/10A, 250 V
Outlets
Front 8 x IEC320 C13/10A, back 6 x IEC320 C19/16A, 250V
Additional Elements
Ammeter with an overload sound alarm
Additional Elements
Ammeter with an overload sound alarm
Maximum Current-load
16A (4000W)
Maximum Current-load
16A (4000W)
Size L x W x H [mm]
482.6 x 116 x 44,4
Size L x W x H [mm]
482.6 x 116 x 44,4
Casing
1U, 19”, black aluminum, fixed holders
Casing
1U, 19”, black aluminum, fixed holders
19” PDUs with IEC320 C13 Outlets
19” PDUs with IEC320 C13 Outlets
Index
11341804.08-2,06-6
Index
11341704.04-2,06-6
Input Connector
IEC 60309/32A, 250V
Input Connector
IEC 60309/16A, 250V
Cable
3 m H05VV-F 3 x 6.0 mm2
Cable
3 m H05VV-F 3 x 2,5 mm2
Outlets
Front 8 x IEC320 C13/10A, back 6 x IEC320 C19/16A, 250V
Outlets
Front 4 x IEC320 C13/10A, back 6 x IEC320 C19/16A, 250V
Additional Elements
Ammeter with an overload sound alarm
Additional Elements
Ammeter with an overload sound alarm
Maximum Current-load
32A (8000W)
Maximum Current-load
16A (4000W)
Size L x W x H [mm]
482.6 x 116 x 44,4
Size L x W x H [mm]
482.6 x 116 x 44,4
Casing
1U, 19”, black aluminum, fixed holders
Casing
1U, 19”, black aluminum, fixed holders
Available 19” PDU models with IEC320 C13 outlets, without the ammeter
Model
Input Connector
Outlets
Index
BKT 19" Power Distribution Unit DIN49441(unischuko) front 8xIEC320 C13 back 8xIEC320 C13 11341000.08-2,08-2
BKT 19" Power Distribution Unit IEC 60309/16A, 250V
front 8xIEC320 C13 back 6xIEC320 C19 11341700.08-2,06-6
BKT 19" Power Distribution Unit IEC 60309/32A, 250V
front 8xIEC320 C13 back 6xIEC320 C19 11341800.08-2,06-6
BKT 19" Power Distribution Unit IEC 60309/16A, 250V
front 4xIEC320 C13 back 6xIEC320 C19 11341700.04-2,06-6
3
19” Power Distribution Units
19” PDUs with IEC320 C19 Outlets
19” PDUs with IEC320 C19 Outlets
Index
11341704.08-2,06-6
Index
11341804.08-2,06-6
Input Connector
IEC 60309/16A, 250V
Input Connector
IEC 60309/32A, 250V
Cable
3 m H05VV-F 3 x 2,5 mm2
Cable
3 m H05VV-F 3 x 6.0 mm2
Outlets
Front 8 x IEC320 C13/10A, back 6 x IEC320 C19/16A, 250V
Outlets
Front 8 x IEC320 C13/10A, back 6 x IEC320 C19/16A, 250V
Additional Elements
Ammeter with an overload sound alarm
Additional Elements
Ammeter with an overload sound alarm
Maximum Current-load
16A (4000W)
Maximum Current-load
32A (8000W)
Size L x W x H [mm]
482.6 x 116 x 44,4
Size L x W x H [mm]
482.6 x 116 x 44,4
Casing
1U, 19”, black aluminum, fixed holders
Casing
1U, 19”, black aluminum, fixed holders
19” PDUs with IEC320 C19 Outlets
Index
11341704.04-2,06-6
Input Connector
IEC 60309/16A, 250V
Cable
3 m H05VV-F 3 x 2,5 mm2
Outlets
Front 4 x IEC320 C13/10A, back 6 x IEC320 C19/16A, 250V
Additional Elements
Ammeter with an overload sound alarm
Maximum Current-load
16A (4000W)
Size L x W x H [mm]
482.6 x 116 x 44,4
Casing
1U, 19”, black aluminum, fixed holders
Available 19” PDU models with IEC320 C19 outlets, without the ammeter
Model
Input Connector
Outlets
Index
BKT 19" Power Distribution Unit IEC 60309/16A, 250V Front 8xIEC320 C13; back 6xIEC320 C19 11341700.08-2,06-6
BKT 19" Power Distribution Unit IEC 60309/16A, 250V Front 8xIEC320 C13; back 6xIEC320 C19 11341800.08-2,06-6
BKT 19" Power Distribution Unit IEC 60309/16A, 250V Front 4xIEC320 C13; back 6xIEC320 C19 11341700.04-2,06-6
4
Vertical (0U) Power Distribution Units
Single-phase Vertical Power Distribution Units
Index
11340040
Input Connector
DIN49441 (universal)/16A, 250V
Cable
2,3 m H05VV-F 3 x 1,5 mm2
Outlets
12 x NF C61-314 (PL, FR Standard)/16A, 250V
Additional Elements
LED indicator
Maximum Current-load
16A (4000W)
Size L x W x H [mm]
705 x 62x 44,4
Casing
0U, anodized aluminum, fixed holders
Index
11340844.24-2
Input Connector
IEC 60309/32A, 250V
Cable
3 m H05VV-F 3 x 6.0 mm2
Outlets
24 x IEC320 C13/10A, 250V
Additional Elements
Ammeter with an overload sound alarm 2 automatic circuit
breakers with LED indicator
Maximum Current-load
32A (8000W)
Size L x W x H [mm]
1237 X 68 X 44,4
Casing
0U, anodized aluminum, fixed holders
Index
11341630.20-3,04-6
Input Connector
IEC 60320 C20/16A, 250V
Cable
3 m H05VV-F 3 x 2.5 mm2
Outlets
20 x IEC320 C13/10A, 250V + 4 x IEC320/C19/16A, 250V
Additional Elements
LED indicator
Maximum Current-load
16A (4000W)
Size L x W x H [mm]
1139 x 62 x 44.4
Casing
0U, anodized aluminum, fixed holders
Index
11341730.24-1
Input Connector
IEC 60309/16A, 250V
Cable
3 m H05VV-F 3 x 2.5 mm2
Outlets
24 x NF C61-314/16A, 250V
Additional Elements
LED indicator
Maximum Current-load
16A (4000W)
Size L x W x H [mm]
1210 X 68 X 44.4
Casing
0U, anodized aluminum, fixed holders
5
Vertical (0U) Power Distribution Units
Three-phase Vertical Power Distribution Units
Index
11341B30.24-1
Input Connector
IEC 60309/32A, 400V
Cable
3 m, 5 x 6.0 mm2
Outlets
24 x NF C61-314 (PL, FR Standard)/16A, 250V
Additional Elements
3 x LED indicator
Maximum Current-load
12160W
Size L x W x H [mm]
1469 x 62 x 44,4
Casing
0U, black aluminum, adjustable holders
Index
11341B30.24-2
Input Connector
IEC 60309/32A, 400V
Cable
3 m, 5 x 6.0 mm2
Outlets
24 x IEC320 C13/10A, 250V
Additional Elements
3 x LED indicator
Maximum Current-load
12160W
Size L x W x H [mm]
1313 x 62 x 44,4
Casing
0U, black aluminum, adjustable holders
Index
11341B30.21-2,03-6
Input Connector
IEC 60309/32A, 400V
Cable
3 m, 5 x 6.0 mm2
Outlets
21 x IEC320 C13/10A, 250V, 3 x IEC320 C19/16A, 250V
Additional Elements
3 x LED indicator
Maximum Current-load
12160W
Size L x W x H [mm]
1313 x 62 x 44,4
Casing
0U, black aluminum, adjustable holders
Index
11342B03.24-0
Input Connector
IEC 60309/32A, 400V
Cable
3 m, 5 x 6.0 mm2
Outlets
24 x DIN49440 (schuko)/16A, 250V
Additional Elements
3 over-current circuit breakers
Maximum Current-load
12160W
Size L x W x H [mm]
1635 x 68 x 44,4
Casing
0U, black aluminum, adjustable holders
Index
11341B61.24-0
Input Connector
IEC 60309/32A, 400V
Cable
3 m, 5 x 6.0 mm2
Outlets
24 x DIN49440 (schuko)/16A, 250V
Additional Elements
3 surge protection units
3 over-current circuit breakers
Maximum Current-load
12160W
Size L x W x H [mm]
1827.5 x 68 x 44,4
Casing
0U, black aluminum, adjustable holders
6
Vertical (0U) Power Distribution Units
Three-phase Vertical Power Distribution Units
Index
11341B65.18-2,06-6
Index
11341B65.24-0
Input Connector
IEC 60309/32A, 400V
Input Connector
IEC 60309/32A, 400V
Cable
3 m, 5 x 6.0 mm2
Cable
3 m, 5 x 6.0 mm2
Outlets
18 x IEC320 C13/10A, 250V,
6 x IEC320 C19/16A, 250V
Outlets
24 x DIN49440 (schuko)/16 A, 250V
Additional Elements
3 ammeters
3 over-current circuit breakers
Additional Elements
Three-phase ammeter
3 over-current circuit breaker
Maximum Current-load
12160W
Maximum Current-load
12160W
Size L x W x H [mm]
1938 x 68 x 44,4
Size L x W x H [mm]
1801 x 62 x 44.4
Casing
0U, black aluminum, adjustable holders
Casing
0U, black aluminum, adjustable holders
Power Cables
Available Models
7
Model
Input Connector
Outlets
BKT Power Cable - 3 x 1mm2 black 2m
DIN49441 (unischuko)/16A, 250V
IEC320 C13/10A, 250V
11480784.2
Index
BKT Power Cable - 3 x 1mm2 black 3m
DIN49441 (unischuko)/16A, 250V
IEC320 C13/10A, 250V
11480784.3
BKT Power Cable - 3 x 1mm2 black 5m
DIN49441 (unischuko)/16A, 250V
IEC320 C13/10A, 250V
11480784.5
BKT Power Cable - 3 x 1mm2 black 3m
IEC320 C14/10A, 250V
IEC320 C13/10A, 250V
11480785.3
BKT Power Cable - 3 x 1mm2 black 5m
IEC320 C14/10A, 250V
IEC320 C13/10A, 250V
11480785.5
BKT Power Cable - 3 x 1mm2 black 5m
DIN49441 (unischuko)/16A, 250V
IEC320 C19/16A, 250V
11480796.3
BKT Power Cable - 3 x 1,5mm2 black 3m
IEC 320 C20/16A, 250V
IEC320 C19/16A, 250V
11480797.3
BKT Power Cable - 3 x 1,5mm2 black 5m
IEC 320 C20/16A, 250V
IEC320 C19/16A, 250V
11480797.5
Monitoring and Management Power Distribution Unit
Management IP-PDU
PDUs offered by BKT Elektronik have been extended and now can monitor basic parameters, such as supply voltage [V], total current-load of a unit [A], total power [kW], total
energy consumption [kWh]. This has created a new set of products: IP-PDU (IP - Power Distribution Unit).
IP-PDUs are widely applicable in information technology and telecommunications. They have been designed to be used in small hanging cabinets, as well as in 19” standing
distribution cabinets.
The IP-PDUs have been fitted with a new generation hot-swappable measuring module with a built-in LCD display. It displays information on supply voltage [V], current [A],
power [kW] and energy consumption [kWh].
SNMP and MODBUS RTU protocols allow complete integration of IP-PDU with external management software.
Features:
?
Input voltage 250 V/400 V; IEC 60309/16A/32A connector
?
Output voltage 250 V
?
Maximum current-load for outlets: IEC320 C13/10A, IEC320 C19/16A, DIN49440/16A, NF C61-314/16A
?
Possible use of outlets: IEC320 C13, IEC320 C19, DIN49440, NF C61-314
?
Can operate in Master/Slave system (max: 5)
?
Vertical mounting
?
Remote monitoring of IP-PDU’s parameters over Ethernet
?
Sending alarm information to defined e-mail addresses
?
Hot-swappable LCD display
?
Internal built-in alarm (buzzer)
?
Connection with the IP-PDU through Web interface and SNMP(V1) and MODBUS RTU protocols
?
Size of the vertical IP-PDU: (0U) LxWxH [mm]: X x 62 x 44.4
8
Monitoring and Management Power Distribution Unit
Management IP-PDU
Web interface
IP-PDU can be monitored through Web interface with most of the available web browsers. This enables the User to manage, monitor and control the state of devices
connected to the unit using not only a computer, but even a smart phone or a tablet.
It allows:
?
Verification of supply voltage of IP-PDU [V]
?
Current total current-load [A]
?
Total energy consumption [kWh]
?
Total power of IP-PDU [kW]
?
Setting up alarm threshold for supply voltage [V]
?
Setting up alarm threshold for total current-load of IP-PDU [A]
It includes:
?
Master/Slave work model config
?
Ethernet settings
?
SNMP settings
?
SMTP settings
?
E-mails and user accounts settings
Monitoring
IP-PDUs monitor the following parameters:
Settings
IP-PDUs allow the setup of the following parameters:
?
Total current-load of the IP-PDU [A]
?
Total current-load of the IP-PDU [A]
?
Work model: Master/Slave
?
Ethernet interface (IP address, gate, mask, DNS)
?
SNMP interface
?
HTTP interface
?
SMTP parameters
?
E-mail addresses
?
User accounts
?
Supply voltage [V]
?
Total energy consumption [kWh]
?
Total power of the IP-PDU [kW]
?
System state
?
Active alarms
9
Monitoring and Management Power Distribution Unit
Management IP-PDU
Control and communication
IP-PDUs have been fitted with a replaceable module with a built-in LCD allowing a communication between users
and the IP-PDU.
?
LCD display can show supply voltage [V], total current-load of the IP-PDU [A],
total power [kW], total energy consumption [kWh]
?
Web interface available through Internet Explorer web browser
?
Network – Ethernet 10/100 Mbit/s
?
IP-PDU connection with external applications and devices through SNMP (V1) and MODBUS RTU
protocols
Alarms
IP-PDUs allow monitoring of and alarming about parameters that have significant influence
on proper operation of devices connected to the IP-PDU.
?
IP-PDU alarms about:
?
Min and max total current-load [A]
?
Min and max supply voltage [V]
Ways and alarming
IP-PDUs offer several ways of notifying the User about a current alarm, which includes:
?
Internal built-in alarm (buzzer)
?
Displaying alarm information on LCD display
?
Alarm at external port – RJ11 socket, NO-NC contact for connecting external alarming devices, such as sound or visual alarm
?
Alarm notification over the Web interface
?
Sending alarm information to e-mail address
?
Sending SNMP Traps
System structure
IP-PDUs can be cascade-connected in a chain of up to 4 devices that use a single IP address.
Available outlets
Special order outlets
Technical Parameters of the Hot-swappable Module
Item
Parameter
Value
Ethernet Port
RJ45
Output
2 x Serial Port
RS485
Alarm Port
RJ11
Supply Voltage
IP-PDU Working Voltage
110/250 VAC 50/60Hz
Digital Voltmeter
Digital Ammeter
Power
Electrical Energy
Meter
Casing
Operating
Environment
Maximum
255V
Accuracy
± 1% +2
Resolution
1V
Maximum
32A
Accuracy
± 1% +1
Resolution
100mA
Resolution
0,1kW
Pulse Rate
1600imp/kWh
Level
1
Resolution
0,1 kWh
Size
144 ×44.4×44.4mm
Color
Black
Temperature
0°C~55°C
Humidity
10%~90%
10
Monitoring and Management Power Distribution Unit
Vertical Single-phase IP-PDUs
Available Models
Model
Input Connector
Outlets
Index
BKT IP Power Distribution Unit
IEC 60309/16A, 250V
24 x IEC320 C13/10A, 250V
1134IP7V1.24-2
BKT IP Power Distribution Unit
IEC 60309/32A, 250V
24 x IEC320 C13/10A, 250V
1134IP8V1.24-2
BKT IP Power Distribution Unit
IEC 60309/16A, 250V
30 x IEC320 C13/10A, 250V
1134IP7V1.30-2
BKT IP Power Distribution Unit
IEC 60309/32A, 250V
30 x IEC320 C13/10A, 250V
1134IP8V1.30-2
BKT IP Power Distribution Unit
IEC 60309/16A, 250V
18 x IEC320 C13/10A, 250V + 6 x IEC320 C19/16A, 250V
1134IPAV1.18-2,06-6
BKT IP Power Distribution Unit
IEC 60309/32A, 250V
18 x IEC320 C13/10A, 250V + 6 x IEC320 C19/16A, 250V
1134IPBV1.18-2,06-6
BKT IP Power Distribution Unit
IEC 60309/16A, 250V
20 x IEC320 C13/10A, 250V + 4 x IEC320 C19/16A, 250V
1134IP7V1.20-2,04-6
BKT IP Power Distribution Unit
IEC 60309/32A, 250V
20 x IEC320 C13/10A, 250V + 4 x IEC320 C19/16A, 250V
1134IP8V1.20-2,04-6
BKT IP Power Distribution Unit
IEC 60309/16A, 250V
21 x IEC320 C13/10A, 250V + 3 x IEC320 C19/16A, 250V
1134IPAV1.21-2,03-6
BKT IP Power Distribution Unit
IEC 60309/32A, 250V
21 x IEC320 C13/10A, 250V + 3 x IEC320 C19/16A, 250V
1134IPBV1.21-2,03-6
Vertical Three-phase IP-PDUs
Available Models
Model
Input Connector
BKT IP Power Distribution Unit
IEC 60309/16A, 400V
Outlets
24 x IEC320 C13/10A, 250V
Index
1134IPAV1.24-2
BKT IP Power Distribution Unit
IEC 60309/32A, 400V
24 x IEC320 C13/10A, 250V
1134IPBV1.24-2
BKT IP Power Distribution Unit
IEC 60309/16A, 400V
18 x IEC320 C13/10A, 250V + 6 x IEC320 C19/16A, 250V
1134IPAV1.18-2,06-6
BKT IP Power Distribution Unit
IEC 60309/32A, 400V
18 x IEC320 C13/10A, 250V + 6 x IEC320 C19/16A, 250V
1134IPBV1.18-2,06-6
BKT IP Power Distribution Unit
IEC 60309/16A, 400V
20 x IEC320 C13/10A, 250V + 4 x IEC320 C19/16A, 250V
1134IPAV1.20-2,04-6
BKT IP Power Distribution Unit
IEC 60309/32A, 400V
20 x IEC320 C13/10A, 250V + 4 x IEC320 C19/16A, 250V
1134IPBV1.20-2,04-6
BKT IP Power Distribution Unit
IEC 60309/16A, 400V
21 x IEC320 C13/10A, 250V + 3 x IEC320 C19/16A, 250V
1134IPAV1.21-2,03-6
BKT IP Power Distribution Unit
IEC 60309/32A, 400V
21 x IEC320 C13/10A, 250V + 3 x IEC320 C19/16A, 250V
1134IPBV1.21-2,03-6
11
Monitoring and Management Power Distribution Unit
Management PCDS
Maintainable monitoring PCDS units (Power Controlling Distribution System) offered by BKT Elektronik make up a new group of modular three-phase PDUs. It enables the
User to randomly reconfigure the outlets and fully monitor the PDU operation along with its environment conditions thanks to connected external sensors.
Modular and multifunctional structure allows the assembly of three-phase PDUs with current-load of 32 A with a Customer according to particular investment requirements.
Creating a PDU from scratch, we can adopt the existing electrical infrastructure, adjust the number and type of outlets to particular devices and fit it with protection modules
and ammeters in configuration that is in line with particular requirements of the Data Center market.
Hot-swappable outlets modules allow reconfiguring PDU online i.e. without disconnecting it from power supply.
PCDS units are a perfect solution for Users, for whom security of powered devices and easy reconfiguration are the priorities.
Features:
?
Input voltage 250V/400V, IEC 60309/16A/32A connector
?
Output voltage 250V
?
Maximum current-load for outlets: IEC320 C13/10A, IEC320 C19/16A, DIN49440/16A, NF C61-314/16A
?
Possible use of outlets: IEC320 C13, IEC320 C19, DIN49440, NF C61-314
?
PGDS rail current-load: up to 3x32A
?
Can operate in Master/Slave system (max: 5)
?
Vertical mounting
?
Intelligent management or remote monitoring
?
Sending alarm information to defined e-mail addresses
?
Internal built-in alarm (buzzer)
?
Connection with the PCDS unit through Web interface and SNMP(V1, V2c, V3) protocols
?
Large LED display
?
Hot-swappable modules
?
High protection rate of switched modules
?
Up to 6 PDUM modules can be installed
?
Over-current protection of PCSM modules
?
Size of the vertical PDU: LxWxH [mm]: 1692 x 71.5 x 38.6
12
Monitoring and Management Power Distribution Unit
Management PCDS
Web interface
The PCDS can be monitored through multi-user Web interface, which includes monitoring, management and administration.
It allows:
?
Current monitoring of total current-load [A]
?
Monitoring the state of connected temperature, humidity, water and smoke sensors
It includes:
?
Indications and status of connected sensors
?
Device operating system state
?
State of alarms and alarm values
?
Adding, removing and modifying users
Web interface is compatible with most of the available web browsers and enables the User to manage, monitor or control the state of devices connected to a PDU using not
only a computer, but even a smart phone or a tablet.
13
Monitoring and Management Power Distribution Unit
Management PCDS
PCDS Functionality
Monitoring
PCDS units monitor the following parameters:
?
Total current-load of the unit [A]
?
State of connected sensors
?
System state
?
Active alarms
?
Alarm logs
?
Temperature, humidity, presence of smoke and water
Environment conditions monitoring
PCDS units monitor environment conditions depending on sensors installed:
?
Temperature, humidity, smoke, water
Settings
PCDS units allow the setup of the following parameters:
?
Total current-load of the PCDS [A]
?
Work model: Master/Slave
?
Ethernet interface (IP address, gate, mask, DNS)
?
SNMP interface
?
HTTP interface
?
Telnet and SSH interfaces
?
SMTP parameters
?
E-mail addresses
?
Accounts and permissions of users and administrators
?
SYSLOG server parameters
?
Temperature range [min/max]
?
Humidity range [min/max]
Control and communication
PCDS units have been fitted with modules that provide communication with the unit through various protocols, through various communication media and at various
levels.
?
Large LED display can show supply voltage and the PDU current-load and monitor connected sensors
?
Web interface through Internet Explorer, Opera, Chrome, Firefox web browsers
?
Network - Ethernet 10/100 Mbit/s
?
Serial communication interface - RS232, RS485
?
Communication protocols (command line) – Telnet, SSH
?
PCDS connection with external applications and devices through SNMP (V1, V2c, V3) protocol
Alarms
PCDS units allow monitoring of and alarming about parameters that have significant influence on proper operation of devices connected to the unit and the installed sensors.
PCDS alarms about:
?
Total current-load [A]
?
Minimum and maximum temperature
?
Minimum and maximum humidity
?
Presence of water
?
Presence of smoke
Ways of alarming
PCDS units offer several ways of notifying the User about a current alarm, which includes:
?
Internal built-in alarm (buzzer)
?
Displaying alarm information on LCD display
?
Alarm notification over the Web interface
?
Sending alarm information to e-mail address
?
Sending SNMP Traps
System structure
PCDS can be cascade-connected in a chain of up to 10 devices that use a single IP address.
Available outlets
Special order outlets
14
Monitoring and Management Power Distribution Unit
Management PCDS Units
Types of modules for PCDS
?
PGDS - Power Generatrix Distribution System (rail for modules)
?
PCSM - Power Controlling System Module
?
PDUM - Power Distribution Unit Module
Detailed List of PCDS Features
Features
Description
Total current-load of PCDS [A]
Temperature
Monitoring
Humidity
Water
Smoke
Work model: Master/Slave
Ethernet interface (IP address, gate, mask, DNS)
SMTP parameters
E-mail addresses
Settings
Accounts and permissions of users and administrators
HTTP interface
Telnet and SSH interfaces
Temperature range [min/max]
Humidity range [min/max]
Total current-load of PCDS [A]
System
Alarms
Temperature/humidity sensors
Alarm
Threshold
Config
Total current-load [A]
Smoke sensor
Water sensor
Alarms
Temperature
Humidity
Internal built-in alarm (buzzer)
Ways
of Alarming
Alarm notification over the Web interface
Sending alarm information to e-mail address
Sending SNMP Traps
Web interface (HTTP) access through Internet Explorer, Opera,
Chrome and Firefox web browsers
Communication
Ethernet 10/100 Mbit/s
SNMP (V1, V2c, V3)
Telnet and SSH communications protocol
Available Sensors
Temperature/humidity (hybrid), water and smoke sensors
Cascade Connection
Possible to connect up to 10 units in Master/Slave configuration
Sensors for PCDS
?
Temperature and humidity sensor (1134CTH01)
?
Water sensor (1134CWS01)
?
Smoke sensor (1134CSS01)
Vertical Single-phase PGDS Rails
Input Connector
Index
BKT PGDS Module Rail for 6 PDUMs
Model
IEC 60309/16A, 250V
1134PC7PG.06
BKT PGDS Module Rail for 6 PDUMs
IEC 60309/32A, 250V
1134PC8PG.06
Vertical Three-phase PGDS Rails
Input Connector
Index
BKT PGDS Module Rail for 6 PDUMs
Model
IEC 60309/16A, 400V
1134PCAPG.06
BKT PGDS Module Rail for 6 PDUMs
IEC 60309/32A, 400V
1134PCBPG.06
PCSMs to Be Mounted in Rails
Model
Index
BKT NPM Type A Module (factory configuration only) 1134PCNPM.A
PDUMs to Be Mounted in Rails
Model
Index
BKT Module for PGDS Rails 5 x IEC320 C13, LED indicator & fuse
1134PCPDA.05-3
BKT Module for PGDS Rails 4 x IEC320 C19, LED indicator & fuse
1134PCPDC.04-6
BKT Module for PGDS Rails 4 x DIN49440, LED indicator & fuse
1134PCPDD.04-0
BKT Module for PGDS Rails 4 x NFC61 (pin), LED indicator & fuse
1134PCPDE.04-0
15
Monitoring Managament and Controlling PDUs
Managament MS-PDU
MS-PDUs (Metered and Switched Power Distribution Units) offered by BKT Elektronik make up another group of power distribution units, which have been expanded with
remote monitoring and management features. They are characterized by a new casing in comparison to PDUs and IP-PDUs and complex controlling and metering module.
They can be applied in large institutions, as well as small companies providing the highest quality of uninterrupted power supply and control over devices.
Features:
?
Input voltage 250V, IEC 60309/32A and DIN 49441/16A connectors
?
Output voltage 250V
?
Maximum current-load for outlets: IEC320 C13/10A, IEC320 C19/16A, DIN49440/16A and NFC 61-314/16A
?
Possible to use outlets: IEC320 C13, IEC320 C19, DIN49440 and NF C61-314
?
Horizontal and vertical mounting
?
Remote monitoring and management over Ethernet
?
Sending alarm information to defined e-mail addresses
?
Internal built-in alarm (buzzer)
?
Connection with the MS-PDUs through Web interface and SNMP(V1) protocol
?
LED display for MS-PDU’s supply voltage verification
?
Built-in over-current circuit breaker (in 19” version)
?
19” MS-PDU size LxWxH [mm]: 482.6 x 216 x 44.4
?
The vertical PDU size (0U) LxWxH [mm]: X x 66.6 x 44.4
16
Monitoring Managament and Controlling PDUs
Managament MS-PDU
Web interface
MS-PDU can be monitored through multi-user Web interface, which includes monitoring, management and administration.
It allows:
?
Current verification of total current-load of MS-PDU [A]
?
Current verification of current-load of each outlet with alarm threshold config
?
State control (on/off) of every outlet
It includes:
?
Sequential start-up programs of the entire PDU
?
Time programmator of each output
?
Indications and status of connected sensors
?
Device operating system state
?
State of alarms and alarm values
?
Adding, removing and modifying users
Web interface is compatible with most of the available web browsers and enables the User to control the state of devices connected to the PDU using not only a
computer, but even a smart phone or a tablet.
17
Monitoring Managament and Controlling PDUs
Managament MS-PDU
MS-PDU Functionality
Monitoring
MS-PDUs monitor the following parameters:
?
Total current-load of the MS-PDU [A]
?
Current-load of each outlet [A]
?
Supply voltage [V]
?
Outlet state ON/OFF
?
System state
?
Active alarms
?
Alarm logs
Environment conditions monitoring
MS-PDUs monitor environment conditions using one T/H sensor
Settings
?
MS-PDUs allow the setup of the following parameters:
?
Total current-load of the MS-PDU [A]
?
Current-load of each outlet [A]
?
Delays in sequential start-up/shutdown of each outlet
?
Work model: Master/Slave
?
Ethernet interface (IP address, gate, mask, DNS)
?
SNMP interface
?
HTTP interface
?
SMTP parameters
?
E-mail addresses
?
User accounts
?
Temperature range [min/max]
?
Humidity range [min/max]
Control and communication
MS-PDUs allow communication with the User through the following interfaces and protocols:
?
LED display showing supply voltage and total current-load of the MS-PDU
?
Web interface through Internet Explorer, Firefox and Chrome web browsers
?
Network - Ethernet 10/100 Mbit/s
?
MS-PDU connection with external applications and devices through SNMP (V1) protocol
Alarms
MS-PDUs allow monitoring of and alarming about parameters that have significant influence on proper operation of devices connected to the unit and the installed sensors.
MS-PDUS alarm about:
?
Total current-load [A]
?
Minimum and maximum current-load of each outlet [A]
?
Supply voltage [V]
?
Minimum and maximum temperature
?
Minimum and maximum humidity
Ways of alarming
MS-PDUs offer several ways of notifying the User about a current alarm, which includes:
?
Internal built-in alarm (buzzer)
?
Alarm notification over the Web interface
?
Sending alarm information to e-mail address
?
Sending SNMP Traps
Keeping settings
MS-PDUs allow keeping settings between their start-ups. You do not need to worry about losing the current configuration of the active outlets.
Available outlets
Special order outlets
18
Monitoring Managament and Controlling PDUs
Managament MS-PDU
Detailed List of MS-PDU Features Depending on a Model
Type
Features
Monitoring
Control
Settings
Control
A
B
C
D
Total current-load of MS-PDU [A]
A
x
Bx
C
x
D
x
Supply voltage of MS-PDU [V]
A
x
Bx
C
x
D
x
Current-load of each outlet [A]
A
Bx
C
D
x
Outlet state ON/OFF
A
B
C
x
D
x
Temperature/humidity sensor
A
x
B
x
C
x
D
x
Outlet state ON/OFF
A
B
C
x
D
x
Total current-load of MS-PDU [A]
A
x
Bx
C
x
D
x
Current-load of each outlet [A]
A
x
Bx
C
x
D
x
Delays in sequential start-up/
shutdown of each outlet
A
B
C
x
D
x
Temperature/humidity thresholds
A
x
Bx
C
x
D
x
Keeping outlets state between MS-PDU start-ups
A
B
C
x
D
x
System
Alarms
Total current-load of MS-PDU
A
x
Bx
C
x
D
x
Alarm
Threshold
Config
Total current-load of MS-PDU [A]
A
x
Bx
C
x
D
x
Exceeded current-load of each outlet [A]
A
Bx
C
D
x
Temperature/humidity
A
C
x
B
D
x
C
x
D
x
Keeping Settings
Alarms
Monitoring
Descroption
Sensor for MS-PDUs
?
Temperature and humidity sensor (1134CTH01)
19” Metered and Switched Power Distribution Units
Available models
Model
19" BKT MS- PDU Type A
Input Connector
Outlets
Index
DIN49441(unischuko)/16A, 250V 8xIEC320 C13/10A, 250V
1134MS0H1.A.08-2
19" BKT MS- PDU Type B
DIN49441(unischuko)/16A, 250V 8xIEC320 C13/10A, 250V
1134MS0H1.B.08-2
19" BKT MS- PDU Type C
DIN49441(unischuko)/16A, 250V 8xIEC320 C13/10A, 250V
1134MS0H1.C.08-2
19" BKT MS- PDU Type D
DIN49441(unischuko)/16A, 250V 8xIEC320 C13/10A, 250V
1134MS0H1.D.08-2
Vertical (0U) Single-phase Metered and Switched Power Distribution Units
Available MS-PDU Type A Models
Model
Input Connector
Outlets
Index
BKT Vertical MS-PDU Type A
18 x IEC320 C13/10A, 250V
IEC 60309/32A, 250V
+6 x IEC320 C19/16A, 250V 1134MS8V1.A.18-2,06-6
BKT Vertical MS-PDU Type A
IEC 60309/32A, 250V 24 x IEC320 C13/10A, 250V
1134MS8V1.A.24-2
BKT Vertical MS-PDU Type A
IEC 60309/32A, 250V 36 x IEC320 C13/10A, 250V
1134MS8V1.A.36-2
BKT Vertical MS-PDU Type A
21 x IEC320 C13/10A, 250V
IEC 60309/32A, 250V
+3 x IEC320 C19/16A, 250V 1134MS8V1.A.21-2,03-6
Available MS-PDU Type B Models
Model
Input Connector
Outlets
Index
BKT Vertical MS-PDU Type B
18 x IEC320 C13/10A, 250V
IEC 60309/32A, 250V
+6 x IEC320 C19/16A, 250V 1134MS8V1.B.18-2,06-6
BKT Vertical MS-PDU Type B
IEC 60309/32A, 250V
BKT Vertical MS-PDU Type B
IEC 60309/32A, 250V 36 x IEC320 C13/10A, 250V
24xIEC320 C13/10A, 250V
1134MS8V1.B.24-2
BKT Vertical MS-PDU Type B
21 x IEC320 C13/10A, 250V
IEC 60309/32A, 250V
+3 x IEC320 C19/16A, 250V 1134MS8V1.B.21-2,03-6
1134MS8V1.B.36-2
Available MS-PDU Type C Models
Model
Input Connector
Outlets
Index
BKT Vertical MS-PDU Type C
18 x IEC320 C13/10A, 250V
IEC 60309/32A, 250V
+6 x IEC320 C19/16A, 250V 1134MS8V1.C.18-2,06-6
BKT Vertical MS-PDU Type C
IEC 60309/32A, 250V 24 x IEC320 C13/10A, 250V
1134MS8V1.C.24-2
BKT Vertical MS-PDU Type C
IEC 60309/32A, 250V 36 x IEC320 C13/10A, 250V
1134MS8V1.C.36-2
BKT Vertical MS-PDU Type C
21 x IEC320 C13/10A, 250V
IEC 60309/32A, 250V
+3 x IEC320 C19/16A, 250V 1134MS8V1.C.21-2,03-6
Available MS-PDU Type D Models
Model
Input Connector
Outlets
Index
BKT Vertical MS-PDU Type D
18 x IEC320 C13/10A, 250V
IEC 60309/32A, 250V
+6 x IEC320 C19/16A, 250V 1134MS8V1.D.18-2,06-6
BKT Vertical MS-PDU Type D
IEC 60309/32A, 250V 24 x IEC320 C13/10A, 250V
1134MS8V1.D.24-2
BKT Vertical MS-PDU Type D
IEC 60309/32A, 250V 36 x IEC320 C13/10A, 250V
1134MS8V1.D.36-2
BKT Vertical MS-PDU Type D
21 x IEC320 C13/10A, 250V
IEC 60309/32A, 250V
+3 x IEC320 C19/16A, 250V 1134MS8V1.D.21-2,03-6
19
Monitoring Managament and Controlling PDUs
NPM V - Network Power Manager
NPM V (Network Power Manager) power distribution units offered by BKT Elektronik allow the management of single- and three-phase power supply from 16 to 32 A. They
increase safety by monitoring conditions inside a server cabinet in case there are unwanted physical and chemical environment conditions, such as temperature, humidity,
water and smoke, and protect against them. They also inform the maintainers of the telecommunications infrastructure about unauthorized access to the inside of a cabinet.
NPM V units allow remote monitoring of voltage [V], current [A], power [kW] and total energy consumption [kWh], also in a single outlet of the power distribution unit.
The installed devices in server cabinets are now much safer thanks to monitoring of environment conditions in distribution cabinets and server rooms, and defining alarm
thresholds for the installed sensors with remote reporting (E-mail, SNMP Trap).
Features:
?
Input voltage 250V/400V, IEC 60309/16A/32A and DIN 49441/16A connectors
?
Output voltage 250V
?
Maximum current-load for outlets: IEC320 C13/10A, IEC320 C19/16A, DIN49440/16A and NF C61-314/16A
?
Possible use of outlets: IEC320 C13, IEC320 C19, DIN49440 and NFC 61-314
?
Horizontal and vertical mounting
?
Remote monitoring and management through Ethernet/WiFi
?
Sending alarm information to defined e-mail addresses
?
Internal built-in alarm (buzzer)
?
Connection with the NMP V unit through Web interface and SNMP(V1,V2c,V3), Telnet and SSH protocols
?
User authorization through RADIUS server
?
Possibility of having up to 20 users logged up with selected permissions
?
Can operate in Master/Slave system (max: 5)
?
Built-in energy meters for each outlet
?
Built-in over-current circuit breaker (in 19’’ version)
?
Large LCD graphic display (128x64) for vertical version and LED display for 19’’ versions to verify NPM V unit’s
operation parameters and alarms
?
19” NPM V unit size LxWxH [mm]: 482.6 x 216 x 44.4
?
Vertical (0U) NPM V unit size LxWxH [mm]: X x 66.6 x 44.4
20
Monitoring Managament and Controlling PDUs
NPM V - Network Power Management
Web interface
NPM V unit can be monitored through multi-user Web interface, which includes monitoring, management and administration. Current verification of total current-load of
NPM unit [A]. Current verification of current-load of each outlet with alarm threshold config, state control of each outlet (on/off) and the memory of the last state in case of the
device restart.
It includes:
?
Sequential start-up program of the entire unit
?
Time programmator for each outlet
?
Indications and status of connected sensors
?
Device operating system state
?
State of alarms and alarm values
?
Adding, removing and modifying users
?
Diagrams of current-load, voltage, temperature and humidity
21
Monitoring Managament and Controlling PDUs
NPM V - Network Power Manager
Web interface is compatible with most of the available web browsers and enables the User to manage, monitor or control the state of devices connected to a PDU, as well as
energy consumption for the entire PDU and for each outlet, using not only a computer, but even a smart phone or a tablet.
Setting up such network parameters as IP addresses, RADIUS, SMTP and NTP (and many more) allow, from the side of the management, random configuration of NPM V unit
according to the User’s or Administrator’s needs.
22
Monitoring Managament and Controlling PDUs
NPM V - Network Power Manager
NPM-V functionality
Monitoring
NPM-V units monitor the following parameters:
?
Total current-load of the NPM-V [A]
?
Current-load of each outlet [A]
?
Supply voltage of the NPM-V [V]
?
Total energy consumption [kWh]
?
Energy consumption of each outlet [kWh]
?
Power Factor
?
Power of the entire NPM-V [kW]
?
Power of each outlet [kW]
?
Outlet state ON/OFF
?
Active alarms
?
Alarm logs
Energy consumption monitoring
NPM-V units have been fitted with energy meters which monitor and record:
?
Total energy consumption of the entire NPM-V [kWh]
?
Energy consumption of each outlet [kWh]
Environment conditions monitoring
NPM-V units allow monitoring various environment conditions depending on the selected model (vertical/horizontal). They monitor temperature, humidity, presence of
smoke, door (access control) and presence of water.
?
19‘’ models monitor temperature and humidity using two T/H sensors
?
Vertical (0U) models in basic configuration monitor temperature and humidity using two T/H sensors
?
Vertical (0U) models in extended configuration (selected at the order) – two additional sensor modules that allow monitoring:
- water, presence of smoke, temperature and humidity (1xWater, 1xSmoke, 1xT/H)
- door, temperature and humidity (2xDoor, 1xT/H)
Parameters settings
In NPM-V units we can set up the following parameters:
?
Total current-load of the NPM-V [A]
?
Current-load of each outlet [A]
?
Delays in sequential start-up/shutdown of each outlet [s]
?
Work model: Master/Slave
?
Delays of OFF/ON or ON/OFF/ON cycles in each outlet
?
Ethernet interface (IP address, gate, mask, DNS) or DHCP
?
SNMP interface
?
HTTP and HTTPS interface
?
Telnet and SSH interface
?
SYSLOG server interface
?
WiFi interface
?
NTP time server parameters
?
RADIUS server parameters
?
SMTP server parameters
?
E-mail addresses
?
Accounts and permissions of users and administrators
?
Temperature range [min/max]
?
Humidity range [min/max]
Control and communication
NPM-V units have been fitted with modules allowing communication with the unit through various protocols,
various communication media and at various level.
?
LED & LCD Displays
- 19” versions have LED displays
- Vertical (0U) versions have LCD displays
?
Web interface available through: Internet Explorer, Opera, Chrome or Firefox
?
Communication protocols (command line) – Telnet, SSH
?
INetwork - Ethernet 10/100 Mbit/s, WiFi
?
RJ45/RS232 serial communication interface
?
Communication with external applications and devices through SNMP (V1, V2c, V3) protocols
23
Monitoring Managament and Controlling PDUs
NPM V - Network Power Manager
Alarms
Extended functionality of NPM-V allows monitoring of and alarming about many parameters that have significant influence on proper operation of devices connected to
the unit and the installed sensors.
NPM-V unit alarms about:
?
Total current-load [A]
?
Minimum and maximum current-load of each outlet [A]
?
Minimum and maximum temperature
?
Minimum and maximum humidity
?
Presence of water
?
Presence of smoke
?
Opened door or side covers of a cabinet
Ways of alarming
NPM-V offer several ways of notifying the User about a current alarm, which includes:
?
Internal built-in alarm (buzzer)
?
Displaying alarm information on LCD display
?
Alarm at external RJ11 (NO-NC) port
?
Alarm notification over the Web interface
?
Sending alarm information to e-mail address
?
Sending SNMP Traps
?
Through SYSLOG server
System structure
NPM-V can be cascade-connected in a chain of up to 5 devices that use a single IP address.
Keepings settings
NPM-V units allow keeping settings between their start-ups. You do not need to worry about losing the current configuration of the active outlets.
Available outlets
Device 1
Device 2
Device 3
Device 4
Internet
Router
Switch
NPM 1
Device n
NPM 2
NPM 3
PC (1)
PC (2)
NPM 5
24
Monitoring Managament and Controlling PDUs
NPM V - Network Power Manager
Detailed List of NPM-V Features Depending on the Model
Type
Features
Monitoring
Monitoring
Control
A
B
C
D
Total current-load of the NPM-V [A]
A
x
Bx
C
x
D
x
Supply voltage of the NPM-V [V]
A
x
Bx
C
x
D
x
Total energy consumption [kWh]
A
x
Bx
C
x
D
x
Energy consumption of each outlet [kWh]
A
B
x
C
D
x
Power Factor
A
x
B
x
C
x
D
x
Total power for entire NPM-V [kW]
A
x
Bx
C
x
D
x
Power of each outlet [kW]
A
Bx
C
D
x
Current-load of each outlet [A]
A
Bx
C
D
x
Outlet state ON/OFF
A
B
C
x
D
x
Temperature
A
x
A
x
B
x
C
x
D
x
Bx
C
x
D
x
Bx
Bx
C
x
D
x
Smoke (additional module)
A
x
A
x
C
x
D
x
Door (additional module)
A
x
B
x
C
x
D
x
Energy meter for the entire NPM-V [kWh]
A
x
B
x
C
x
D
x
Energy meter for each outlet [kWh]
A
B
x
C
D
x
Outlet state ON/OFF
A
B
C
x
D
x
Total current-load of the NPM-V [A]
A
x
Bx
C
x
D
x
Description
Humidity
Water (additional module)
Control
Settings
Keeping Settings
System
Alarms
Alarms
Alarm
Threshold
Config
Ways
of Alarming
Current-load of each outlet [A]
A
Bx
C
D
x
Delays of OFF/ON or ON/OFF/ON cycle of each outlet
A
B
C
x
D
x
Delays in sequential start-up/shutdown of each outlet
A
B
C
x
D
x
Work model selection: Master/Slave
A
x
B
x
C
x
D
x
Ethernet (IP address, gate, mask, DNS) or DHCP
A
x
Bx
C
x
D
x
WiFi
A
x
Bx
C
x
D
x
NTP time server parameters
A
x
Bx
C
x
D
x
RADIUS server parameters
Bx
B
x
C
x
D
x
SYSLOG server parameters
A
x
A
x
C
x
D
x
SMTP server interface
A
x
Bx
C
x
D
x
SNMP interface
Bx
Bx
C
x
D
x
E-mail addresses
A
x
A
x
C
x
D
x
Accounts and permissions of users and administrators
A
x
B
x
C
x
D
x
HTTP and HTTPS interfaces
A
x
Bx
C
x
D
x
Telnet and SSH interfaces
Bx
Bx
C
x
D
x
Temperature range [min/max]
A
x
A
x
C
x
D
x
Humidity range [min/max]
A
x
B
x
C
x
D
x
Outlets state memory during the unit restart
A
B
C
x
D
x
Total current-load of the NPM-V [A]
A
x
Bx
C
x
D
x
Exceeded current-load of each outlet [A]
A
Bx
C
D
x
Temperature/humidity sensor
A
x
C
x
D
x
Smoke sensor
A
x
B
x
B
x
C
x
D
x
Door sensor
A
x
B
x
C
x
D
x
Water sensor
A
x
Bx
C
x
D
x
Total current-load of the NPM-V [A]
A
x
Bx
C
x
D
x
Exceeded current-load of each outlet [A]
A
Bx
C
D
x
Temperature
Bx
B
x
C
x
D
x
Humidity
A
x
A
x
C
x
D
x
Internal built-in alarm (buzzer)
A
x
Bx
C
x
D
x
Displaying alarm information on LCD display
Bx
Bx
C
x
D
x
Alarm at external port – RJ11 (NO-NC)
A
x
A
x
C
x
D
x
Alarm notification over Web interface
A
x
B
x
C
x
D
x
Sending alarm information to an e-mail address
A
x
Bx
C
x
D
x
Sending SNMP Traps
A
x
A
x
Bx
Bx
C
x
D
x
C
x
D
x
Web interface (HTTP and HTTPS) through IE, OPERA, CHROME
and FIREFOX web browsers
A
B
C
x
D
x
Through SYSLOGS protocols
Communication
Ethernet, WiFi
A
x
Bx
C
x
D
x
SNMP (V1, V2c, V3)
A
x
Bx
C
x
D
x
RADIUS user authorization protocol
A
x
Bx
C
x
D
x
Telnet and SSH communication protocols
A
x
Bx
C
x
D
x
RS232 serial data transmission protocol
Bx
C
x
D
x
Bx
x
C
x
D
Bx
C
x
D
x
Available Sensors
Temperature/humidity (hybrid), door, water and smoke sensors
A
x
x
A
Cascade Connections
Possible to connect up to 5 units in Master/Slave system
A
x
25
Monitoring Managament and Controlling PDUs
NPM V - Network Power Manager
Sensors for NPM-V units
?
Temperature and humidity sensor (1134CTH01)
?
Water sensor (1134CWS01)
?
Smoke sensor (1134CSS01)
?
Door sensor (1134CBS01)
19’’ NPM-V Units
Available Type A Models
Model
Input Connector
Outlets
19" BKT Network Power Manager V Type A DIN 49441 (unischuko)/16A, 250V
19" BKT Network Power Manager V Type A
IEC 60309/32A, 250V
Index
8xIEC320 C13/10A, 250V
1134N06V.A.08-2
8 x IEC320 C13/10A, 250V
+4 x IEC320 C19/16A, 250V
1134N86V.A.08-2,04-6
Available Type B Models
Model
Input Connector
Outlets
19" BKT Network Power Manager V Type B DIN 49441 (unischuko)/16A, 250V
19" BKT Network Power Manager V Type B
IEC 60309/32A, 250V
Index
8xIEC320 C13/10A, 250V
1134N06V.B.08-2
8 x IEC320 C13/10A, 250V
+4 x IEC320 C19/16A, 250V
1134N86V.B.08-2,04-6
Available Type C Models
Model
Input Connector
Outlets
19" BKT Network Power Manager V Type C DIN 49441 (unischuko)/16A, 250V
19" BKT Network Power Manager V Type C
Index
8 x IEC320 C13/10A, 250V
1134N06V.C.08-2
8 x IEC320 C13/10A, 250V
1134N86V.C.08-2,04-6
+4 x IEC320 C19/16A, 250V
IEC 60309/32A, 250V
Available Type D Models
Model
Input Connector
Outlets
19" BKT Network Power Manager V Type D DIN 49441 (unischuko)/16A, 250V
19" BKT Network Power Manager V Type D
IEC 60309/32A, 250V
Index
8 x IEC320 C13/10A, 250V
1134N06V.D.08-2
8 x IEC320 C13/10A, 250V
1134N86V.D.08-2,04-6
+4 x IEC320 C19/16A, 250V
Vertical (0U) Single-phase NPM-V Units
Available Type A Models
Model
Input Connector
Vertical BKT Network Power Manager V Type A
IEC 60309/16A, 250V
Vertical BKT Network Power Manager V Type A
Outlets
Index
24 x IEC320 C13/10A, 250V
1134N77V.A.24-2
IEC 60309/32A, 250V
24 x IEC320 C13/10A, 250V
1134N87V.A.24-2
Vertical BKT Network Power Manager V Type A
IEC 60309/32A, 250V
21 x IEC320 C13/10A, 250V
1134N87V.A.21-2,03-6
+3 x IEC320 C19/16A, 250V
Vertical BKT Network Power Manager V Type A
IEC 60309/32A, 250V
18 x IEC320 C13/10A, 250V
1134N87V.A.18-2,06-6
+6 x IEC320 C19/16A, 250V
Vertical BKT Network Power Manager V Type A
IEC 60309/32A, 250V
36 x IEC320 C13/10A, 250V
1134N87V.A.36-2
Available Type B Models
Model
Input Connector
Vertical BKT Network Power Manager V Type B
IEC 60309/16A, 250V
Vertical BKT Network Power Manager V Type B
Outlets
Index
24 x IEC320 C13/10A, 250V
1134N77V.B.24-2
IEC 60309/32A, 250V
24 x IEC320 C13/10A, 250V
1134N87V.B.24-2
Vertical BKT Network Power Manager V Type B
IEC 60309/32A, 250V
21 x IEC320 C13/10A, 250V
1134N87V.B.21-2,03-6
+3 x IEC320 C19/16A, 250V
Vertical BKT Network Power Manager V Type B
IEC 60309/32A, 250V
18 x IEC320 C13/10A, 250V
1134N87V.B.18-2,06-6
+6 x IEC320 C19/16A, 250V
Available Type C Models
Model
Input Connector
Vertical BKT Network Power Manager V Type C
IEC 60309/16A, 250V
Vertical BKT Network Power Manager V Type C
Outlets
Index
24 x IEC320 C13/10A, 250V
1134N77V.C.24-2
IEC 60309/32A, 250V
24 x IEC320 C13/10A, 250V
1134N87V.C.24-2
Vertical BKT Network Power Manager V Type C
IEC 60309/32A, 250V
21 x IEC320 C13/10A, 250V
1134N87V.C.21-2,03-6
+3 x IEC320 C19/16A, 250V
Vertical BKT Network Power Manager V Type C
IEC 60309/32A, 250V
18 x IEC320 C13/10A, 250V
1134N87V.C.18-2,06-6
+6 x IEC320 C19/16A, 250V
Available Type D Models
Model
Input Connector
Vertical BKT Network Power Manager V Type D
IIEC 60309/16A, 250V
Vertical BKT Network Power Manager V Type D
Outlets
Index
24 x IEC320 C13/10A, 250V
1134N77V.D.24-2
IEC 60309/32A, 250V
24 x IEC320 C13/10A, 250V
1134N87V.D.24-2
Vertical BKT Network Power Manager V Type D
IEC 60309/32A, 250V
21 x IEC320 C13/10A, 250V
1134N87V.D.21-2,03-6
+3 x IEC320 C19/16A, 250V
Vertical BKT Network Power Manager V Type D
IEC 60309/32A, 250V
18 x IEC320 C13/10A, 250V
1134N87V.D.18-2,06-6
+6 x IEC320 C19/16A, 250V
26
Monitoring and Controlling Metered PDUs
NPM V - Network Power Manager
Vertical (0U) Three-phase NPM-V Units
Available Type A Models
Model
Input Connector
Vertical BKT Network Power Manager V Type A
IEC 60309/32A, 400V
24 x IEC320 C13/10A, 250V
Outlets
Index
Vertical BKT Network Power Manager V Type A
IEC 60309/32A, 400V
21 x IEC320 C13/10A, 250V
1134NB8V.A.21-2,03-6
+3 x IEC320 C19/16A, 250V
Vertical BKT Network Power Manager V Type A
IEC 60309/32A, 400V
18 x IEC320 C13/10A, 250V
1134NB8V.A.18-2,06-6
+6 x IEC320 C19/16A, 250V
Vertical BKT Network Power Manager V Type A
IEC 60309/32A, 400V
36 x IEC320 C13/10A, 250V
1134NB8V.A.24-2
1134NB8V.A.36-2
Available Type B Models
Model
Input Connector
Outlets
Vertical BKT Network Power Manager V Type B
IEC 60309/32A, 400V
24 x IEC320 C13/10A, 250V
Index
Vertical BKT Network Power Manager V Type B
IEC 60309/32A, 400V
21 x IEC320 C13/10A, 250V
1134NB8V.B.21-2,03-6
+3 x IEC320 C19/16A, 250V
Vertical BKT Network Power Manager V Type B
IEC 60309/32A, 400V
18 x IEC320 C13/10A, 250V
1134NB8V.B.18-2,06-6
+6 x IEC320 C19/16A, 250V
1134NB8V.B.24-2
Available Type C Models
Input Connector
Outlets
Vertical BKT Network Power Manager V Type C
Model
IEC 60309/32A, 400V
24 x IEC320 C13/10A, 250V
Index
Vertical BKT Network Power Manager V Type C
IEC 60309/32A, 400V
21 x IEC320 C13/10A, 250V
1134NB8V.C.21-2,03-6
+3 x IEC320 C19/16A, 250V
Vertical BKT Network Power Manager V Type C
IEC 60309/32A, 400V
18 x IEC320 C13/10A, 250V
1134NB8V.C.18-2,06-6
+6 x IEC320 C19/16A, 250V
1134NB8V.C.24-2
Available Type D Models
Model
Input Connector
Outlets
Vertical BKT Network Power Manager V Type D
IEC 60309/32A, 400V
24 x IEC320 C13/10A, 250V
Vertical BKT Network Power Manager V Type D
IEC 60309/32A, 400V
21 x IEC320 C13/10A, 250V
1134NB8V.D.21-2,03-6
+3 x IEC320 C19/16A, 250V
Vertical BKT Network Power Manager V Type D
IEC 60309/32A, 400V
18 x IEC320 C13/10A, 250V
1134NB8V.D.18-2,06-6
+6 x IEC320 C19/16A, 250V
27
Index
1134NB8V.D.24-2
Enviroment Monitoring System Conditions
EMS-Environment Monitoring System
Environment Monitoring System is an intelligent system for monitoring environment and power supply in one or several distribution cabinets. Based on advanced
technologies, it provides effectiveness, reliability and safety of installed and working devices. EMS can be applied in server rooms, telecommunications, computer networks,
although it is most frequently used in small or medium Data Centers.
You can easily monitor the environment and power supply in a cabinet over Ethernet using this system. It consists of a main unit (Master), subunit (Slave) and a Hub.
EMS can also monitor the status of PDUs, thanks to replaceable MPD module with LCD display.
Features
• Supply voltage of Master and Slave – 250V, IEC320 C14/10A connector
• Supply voltage of Hub – 12VDC/RJ45
• Horizontal mounting
• Remote monitoring and management of environment in one or several cabinets through Ethernet
• Sending alarm information to defined e-mail addresses
• Internal built-in alarm (buzzer)
• Communication with a PDU through Web interface and SNMP(V2), Telnet and SSH protocols
• Can operate in Master/Slave/Hub system; maximum 11 Slave units with a use of Hub
• Possible to connect and control the status of up to 4 PDUs connected to the Master unit and up to 4 PDUs connected to a Slave unit
• Possible to control sensors connected to the Master and Slave units
• LCD display in the Master unit to verify the parameters of installed devices and reported alarms
• LED indicators in the Master and Slave units informing about connected sensors
• Master, Slave, Hub unit size LxWxH [mm]: 482.6 x 131.8 x 44.4
28
System for Monitoring Environmental Conditions
EMS-Environment Monitoring System
Web interface
WEB INTERFACE of devices connected to a PDU using not only a computer, but also a smart phone or a tablet.
It allows:
?
Supply voltage monitoring [V] of the Master
?
Current-load monitoring [A] of the Master
?
Power monitoring [kW] of PDUs with MPD modules
?
EMS may be monitored through Web interface compatible with most of the available web browsers that enables you to manage, monitor and control the status
connected to the Master
?
Energy consumption monitoring [kWh] of PDUs with MPD modules connected to the Master
?
Monitoring of the status of connected temperature/humidity, water, smoke and door sensors in Master and Slave units
?
Operating system status control in Master/Slave units
?
Adding, removing and modifying users
?
Controlling state of alarms and alarm values
?
Alarm threshold config for temperature and humidity sensors
?
Ethernet config
?
SMTP server config
EMS functionality
EMS consists of a main unit (Master) and up to 11 Slave units connected with a use of Hub. Such a system enables you to monitor environment in 12 cabinets.
The system also includes PDUs with hot-swappable LCD display. Parameters monitored in each unit: voltage and current of PDUs (max 4), temperature, humidity, smoke,
water and door. Alarms are sent in the case of exceeded defined thresholds or the occurrence of controlled events. Every event is saved in a log. There is a possibility of
assigning user permissions to particular units.
Monitoring
EMS can monitor the following parameters:
?
Total current-load [A] for PDUs connected to EMS
?
Energy consumption [kWh] for PDUs connected to EMS
?
Supply voltage [V] for PDUs connected to EMS
?
Master/Slave units status
?
Active alarms
?
Alarm logs
Energy consumtion monitoring
EMS can monitor energy consumption thanks to the installation of MPD modules in PDUs.
Energy consumption may be controlled through Web interface and LED display in MPD modules.
29
System for Monitoring Environmental Conditions
EMS-Environment Monitoring System
Environment conditions monitoring
EMS allows monitoring various environment conditions depending on the installed sensors. These include: temperature, humidity, smoke, door (access control) and water
sensors.
?
You can connect the following sensors to the Master unit and monitor them:
- two temperature and humidity sensors: T/H1 and T/H2
- two door sensors: Door1 and Door2
- one smoke sensor
- one water sensor
?
You can connect the following sensors to a Slave unit:
- two temperature and humidity sensors: T/H1 and T/H2
- two door sensors: Door1 and Door2
- one smoke sensor
- one water sensor
Settings
You can set up the following parameters in EMS:
?
Minimum and maximum current-load [A] of connected PDUs
?
Minimum and maximum supply voltage [V] of connected PDUs
?
Ethernet (IP address, gate, mask, DNS)
?
Telnet and SSH interfaces
?
SNMP interface
?
HTTP interface
?
SMTP server parameters
?
E-mail addresses
?
User accounts
?
Temperature range [min/max]
?
Humidity range [min/max]
T/H Sensor 1
T/H Sensor 2
Smog sensor
Door sensor 1
Door sensor 2
Water-logging sensor
Internet
EMS Master
Router
Switch
Metered PDU-1 (current, voltage, power)
Metered PDU-2 (current, voltage, power)
Metered PDU-3 (current, voltage, power)
PC
Metered PDU-4 (current, voltage, power)
EMS-HUB
T/H Sensor 1
T/H Sensor 2
Smog sensor
Door sensor 1
Door sensor 2
EMS Slave
Metered PDU-1 (current, voltage, power)
Water-logging sensor
Metered PDU-1 (current, voltage, power)
Metered PDU-2 (current, voltage, power)
Metered PDU-2 (current, voltage, power)
Metered PDU-3 (current, voltage, power)
Metered PDU-3 (current, voltage, power)
Metered PDU-4 (current, voltage, power)
Metered PDU-4 (current, voltage, power)
30
System for Monitoring Environmental Conditions
EMS-Environment Monitoring System
Control and communication
?
LCD display & LED indicator
- Master unit has been fitted with LCD display and LED indicators.
- LCD display provides the view of system status, supply voltage, current-load and energy consumption of connected PDUs. You can also verify the sate of connected
temperature and humidity, door, water and smoke sensors.
- LED indicators in the Master unit inform about a number and type of installed sensors and PDUs, as well as ports they are connected to. You can also check how
many Slave units there are in the EMS.
- Slave unit has been fitted with LED indicators, which inform about a number and type of installed sensors and PDUs, as well as ports they are connected to.
?
Web interface accessible through Internet Explorer, Opera, Chrome and Firefox web browsers
?
Ethernet 10/100 Mbit/s
?
PDU connection to external applications and devices through SNMP (V1) protocol
?
Communication between Master/Slave/Hub units through RS485/RJ45 protocol
Alarms
EMS allows monitoring of and alarming about parameters that have significant influence on proper operation of devices connected to a PDU and installed sensors.
EMS can alarm about the following parameters:
?
Minimum and maximum current-load [A] of connected PDUs
?
Minimum and maximum supply voltage [V] of connected PDUs
?
Minimum and maximum temperature
?
Minimum and maximum humidity
Ways of alarming
EMS offers several ways of notifying a user about a current alarm, which includes:
?
Internal built-in alarm (buzzer)
?
Displaying alarm information on LCD display
?
Alarm notification over the Web interface
?
Sending alarm information to e-mail address
?
Sending SNMP Traps
MPD Metering Module
Replaceable MPD metering modules inform about PDU’s parameters with a possibility of sending this information through RJ45 port to Master and Slave units of EMS.
MPD metering module is the latest designed and patented hot-swappable device with a multipurpose modular structure.
Its LCD display informs you about supply voltage [V] and current of a PDU and sends this information through RJ45 port (RS485) to EMS. It also displays information
about the current power [kW] and has built-in energy meter [kWh].
Basic Features
The modules are hot-swappable, and their failure does not influence the operation of a PDU, which increases reliability of the power distribution system.
Hot-swappable Module Technical Parameters
Item
Parameter
Value
Supply Voltage
PDU Working Voltage
110/250 VAC, 50/60Hz
Output
Digital
Voltmeter
Digital
Ammeter
Power
Electrical
Energy Meter
Casing
Operation
Environment
31
Output Port
RJ45
Communication Protocol
RS485
Maximum
255V
Accuracy
±1% +3
Resolution
1V
Maximum
32V
Accuracy
±1% +1
Resolution
100mA
Resolution
0,1kW
Pulse Rate
1000imp/kWh
Level
1
Resolution
0,1 kWh
Size
110 x 41 x 56mm
Colour
Czarny
Temperature
0°C~55°C
Humidity
10%~90%
System for Monitoring Environmental Conditions
EMS-Environment Monitoring System
Sensors for EMS
?
Temperature and humidity sensor (1134CTH01)
• Water sensor (1134CWS01)
• Smoke sensor (1134CSS01)
• Door sensor (1134CBS01)
Available EMS Models
Model
Index
EMS (Master)
1134EM01
EMS (Slave)
1134ES01
EMS (HUB)
1134EH01
19” MPD Metering Power Distribution Units for EMS with a Socket for an MPD Metering Module
Model
Input Connector
Outlets
Index
19" MPD Unit with a Socket
for an MPD Module
6 x NF C61-314
11342050.06-1
DIN49441 (unischuko)/16A, 250V
(PL, FR standard)/ 16A, 250V
19" MPD Unit with a Socket
for an MPD Module
DIN49441 (unischuko)/16A, 250V
6 x DIN 49440
(schuko)/16A, 250V
MPD module for MPD units of EMS metering voltage, current and energy consumption, with a built-in
meter and LCD display.
11342050.06-0
11342050.06-0
We can adjust the number and type of outlets in MPD unit to the Customer requirements.
32
Automatic Transfer Switch
ATS-Automatic Transfer Switch
BKT Elektronik has launched a product that provides redundancy and uninterrupted operation of network devices. ATS switches between power lines in no more than 16 ms at
16A and 32A current, not interrupting the operation of connected devices. When there is a power cut at Input A, the ATS automatically switches to power supply from Input B.
ATS can be applied in server rooms, data centers, telecommunication and many other areas where uninterrupted power supply is a must.
ATS offered by BKT Elektronik is highly reliable and stable and switches between power sources very quickly.
Features
?
Supply voltage 250V; IEC320 C20/16A, 250V and IEC60309 /16A, 250V connectors
?
Output supply voltage 250V
?
Maximum time of switching between power sources: ? 16 ms
?
Maximum current-load for outlets: IEC320 C13/10A, IEC320 C19/16A
?
Possible to use outlets: IEC320 C13, IEC320 C19
?
Horizontal mounting
?
Hot-swappable SNMP card allowing monitoring and remote management through Ethernet
?
Sending alarm information to defined e-mail addresses
?
Internal built-in alarm (buzzer)
?
Communication with a PDU through Web interface, SNMP(V1), Ethernet and Telnet
?
Quick and easy power source switch
?
Available in 19” 1U or 2U casing
?
Size [mm]: 482.6 x 220 x 44.4/88.8
33
Automatic Transfer Switch
ATS-Automatic Transfer Switch
Web interface
ATS unit can be monitored through multi-user Web interface, which includes monitoring, management and administration.
It iallows:
?
Verification of input and output supply voltage
?
Verification of current-load of each power source
?
Power source control
?
Changing power sources switching time
?
Power source switch lock of the power source available at the front panel
?
Changing names of power sources
?
Min and max supply voltage [V] config
?
Min and max current-load [V] config
?
State of alarms and alarm values
?
SNMP and Ethernet config
Web interface is compatible with most of the available web browsers and enables you to manage, monitor or control the state of devices connected to the PDU, as well
as energy consumption for the PDU and for each outlet, using not only a computer, but even a smart phone or a tablet.
34
Automatic Transfer Switch
ATS-Automatic Transfer Switch
ATS Functionality
Monitoring
ATS can monitor the following parameters:
?
Total current-load [A] of Input A and Input B
?
Output total current-load [A]
?
Supply voltage [V] of Input A and Input B
?
Output supply voltage [V]
?
Current status of power source
?
Power supply failure
?
Active alarms
?
Alarm logs
Settings
In ATS you can set up the following parameters:
?
Minimum and maximum current-load [A]
?
Minimum and maximum supply voltage [V]
?
Power source switch time for each power source [sec]
?
Ethernet (IP address, gate, mask, DNS)
?
SNMP interface
?
HTTP interface
?
SMTP server parameters
?
E-mail addresses
?
User accounts
Control and communication
?
LED 3-digit display allows the control of supply voltage and current-load for active power source and IP addresses
?
Web interface through Internet Explorer, Opera, Chrome, Firefox
?
Network – Ethernet 10/100 Mbit/s using SNMP Card
?
Serial communication interface (Telnet) – RJ45/RS232
?
ATS connection to external applications and devices through SNMP (V1) protocol
Alarms
ATS allows monitoring of and alarming about parameters that have significant influence on proper operation of connected devices.
ATS can alarm about the following parameters:
?
Minimum and maximum current-load [A]
?
Minimum and maximum supply voltage [V]
?
Power supply failure at one of the inputs
Ways of alarming
EMS offers several ways of notifying a user about a current alarm, which includes:
?
Internal built-in alarm (buzzer)
?
Displaying alarm information on LCD display
?
Alarm notification over the Web interface
?
Sending alarm information to e-mail address
?
Sending SNMP Traps
Available output sockets
?
19” 1U version – IEC320 C13, C19 – built-in, IEC60309/16A, 250V – cable
?
19” 2U version – IEC320 C13, C19 – built-in, IEC60309/32A, 250V – cable
Available models
Model
Input Socket
Output Socket
Indeks
ATS Basic BKT 1U 19"
2 x IEC320 C20/16A, 250V
(built-in), no cables included
6 x IEC320 C13/10A
2 x IEC320 C16/16A
1134A4.06-2,02-6S
ATS Basic BKT 1U 19"
2 x IEC60309/16A, 250V (cable)
1 x IEC 60309/16A, 250V
(cable)
1134A5.01-7S
ATS Basic BKT 2U 19"
2 x IEC 60309/32A, 250V (cable)
12 x IEC320 C13/10A
4 x IEC320 C19/16A
1134A9.12-2,04-6S
2 x IEC 60309/32A, 250V (cable)
1 x IEC 60309/32A, 250V
(cable)
1134A9.01-8S
ATS Basic BKT 2U 19"
BKT Hot-swappable SNMP/WEB Card, for ATS expansion
35
1134A.SNMP