Universal switch insert 1gang

Universal switch insert 1gang
Universal switch insert 1gang/ Universal switch insert 2gang
Universal switch insert 1gang/
Universal switch insert 2gang
Order no.: 8512 11 0x, 8512 22 0x
Operating instructions
1. Safety instructions
Electrical equipment may only be installed and assembled by a qualified electrician in
accordance with the relevant installation standards, guidelines, regulations, directives,
safety and accident prevention regulations of the country.
Failure to comply with these instructions may result in damage to the device, fire or other
hazards.
Hazard due to electric shock. Do not operate device without application module.
Hazard due to electric shock. The device is not suited for safe disconnection of the
mains supply. Even when the device is switched off, the load is not galvanically separated from the mains supply.
Do not connect any non-dimmable lamps, their transformers or operating devices.
Observe manufacturer's data.
Hazard of fire. During operation with conventional transformers, fuse each transformer
on the primary side according to manufacturer's data. Use safety transformers that comply with EN 61558-2-6 (VDE 0570 Part 2-6) only.
These instructions are an integral component of the product and must be retained by the
end user.
2. Design and layout of the device
(3)
(1)
(6)
(4)
(8)
(7)
Figure 1: Universal switch insert 1gang
6W-5833D
Page 1/6
08-2013
Universal switch insert 1gang/Universal switch insert 2gang
(3)
(2)
(6)
(8)
(5)
(7)
Figure 2: Universal switch insert 2gang
(1) Universal switch insert
(2) Universal switch insert 2gang
(3) Frames
(4) Application module
(5) Application module 2gang
(6) Screw for dismantling protection (not R.1/R.3)
(7) Button design cover
(8) Connecting terminals
3. Function
Correct use
–– Only suitable for use in indoor areas with no drip and no spray water.
–– Switching of incandescent lamps, HV halogen lamps, dimmable energy-saving and 230 V
retrofit LED lamps; electronic and dual-mode transformers or conventional transformers
with low voltage halogen lamps
–– Suitable for mixed loads up to the specified total capacity (see "Technical Data")
–– Installation into wall box according to DIN 49073 (recommended for touch switch insert
2gang, deep box)
–– Operate with suitable aplication module (see "Accessories")
No mixed load operation of capacitive and inductive loads possible at the output.
Product characteristics
–– Power extension via universal power boosters (except for switch insert 2gang, see
catalogue)
–– automatic setting of load-dependent switching principle and additional, optional settings via
the application module e.g. for energy-saving lamps and 230 V retrofit LED lamps
–– Soft start for bulb protection
–– Electronic short circuit protection
–– Electronic overload and overheating protection
–– Electronic interference signal suppression e.g. for ripple control impulses (tariff signals)
–– Connection of extension unit push-button (NO contact)
6W-5833D
Page 2/6
08-2013
Universal switch insert 1gang/Universal switch insert 2gang
Additional product characteristics, switch insert 2gang
–– Different load types at each output possible
–– Output wattage ratings independent from each other
–– Possible to operate output 1only
–– Connection of extension unit push-button (NO contact) per each output possible
Switching process (table 1)
Do only use dimmable loads.
Flickering of connected lamps possible due to falling below of the indicated minimum load,
ripple control impulses (tariff signals) of power station or illuminant exchange of energysavings lamps or 230 V retrofit LED lamps.
Short term flickering during load detection of ohmic loads possible. No operation is possible
during load detection. These are not defects of the device.
If the switching performance of energy-saving lamps and 230 V LED lamps is unsatisfactory in factory setting, a load setting must be carried out. The load setting is described in
the instructions of the respective application module.
When circuiting several loads to one output (parallel circuiting ) optimise switching performance via load setting if necessary.
4. Operation
These instructions describe the installation of the switch inserts. The operation is to be taken
from the instructions of the respective application module.
The operation of extension units is only possible if a cover is attached to the main unit.
5. Information for electricians
5.1 Installation and electrical connection
DANGER!
Touching live parts can result in an electric shock.
An electric shock can be lethal.
Disconnect the connecting cables before working on the device and cover all live
parts in the area!
CAUTION!
Do not interconnect the outputs of universal switch insert 2gang.
Operating both outputs on a joint load will destroy the device.
For capacity extension, use universal power boosters (except for universal
switch insert 2gang, see catalogue).
Circuiting and mounting the switch insert
A MCB max. 16 A has been installed as device protection.
Circuit switch insert and optional extension units according to the connection diagram
(Figure 3 to 6).
Mount the switch insert into a wall box. The connecting terminals must be at the bottom.
Attach frame and application module (see instructions for application module).
A deep wall box is recommended for switch insert 2gang.
Illuminated mechanical push-buttons must be equipped with a separate N-terminal.
6W-5833D
Page 3/6
08-2013
Universal switch insert 1gang/Universal switch insert 2gang
Motion detector extension units can only be used when the switch insert is operated with a
motion detector application module.
Motion detector extension units are not suitable for the switch insert 2gang.
For power supply, a load must be connected to output 1 of the switch insert 2gang.
6. Appendix
6.1 Technical data
Rated voltage
230 V~, + 10%/- -15%
Mains frequency
50/60 Hz
MCB
max. 16 A
Standby power consumption
< 0.3 W
Degree of protection
IP 20
Relative humidity
0 ... 65 % (no condensation)
Operating temperature
-5°C … +45°C
Storage/transport temperature
-20°C … +60°C
Number of extension units
unlimited
Extension unit cable length
max. 50 m
Number of motion detector extension units unlimited
Cable length motion detector extension units
max. 50 m
Load cable length
max. 100 m
Connecting terminals
1 x 2.5 mm² or 2 x 1.5 mm²
Mounting orientation
connecting terminals downwards
Installation depth
32 mm
Performance reduction per 5°C above 25°C:
–– Incandescent lamps, HV halogen lamps, LV halogen lamps
with electronic transformers or dual-mode transformers,
NV halogen lamps with conventional transformers
-25 %
–– Dimmable 230 V retrofit LED lamps, dimmable energy-savings lamps
-30 %
Installation in wood or drywallas well as in multiple combinations
-25 %
Performance data including transformer power dissipation
–– Conventional transformers 20 %
–– Electronic transformers, dual-mode transformers 10 %
Universal switch insert 1gang
Standby power consumption
< 0.3 W
Incandescent lamps
25 ... 400 W
HV halogen lamps 25 ... 400 W
LV halogen lamps with electronic transformers or dual-mode transformers 25 ... 400 VA
LV halogen lamps with conventional transformers 25 ... 400 VA
Dimmable 230 V retrofit LED lamps
5 ... 70 W
Dimmable energy-savings lamps
13 ... 80 W
Mixed loads
possible to lowest maximum load
6W-5833D
Page 4/6
08-2013
Universal switch insert 1gang/Universal switch insert 2gang
Universal switch insert 2gang per output
Standby power consumption
0.3 W channel 1 / 0.7 W channel 2
Incandescent lamps
35 ... 300 W
HV halogen lamps 35 ... 300 W
LV halogen lamps with electronic transformers or dual-mode transformers
35 ... 300 VA
LV halogen lamps with conventional transformers 35 ... 300 VA
Dimmable 230 V retrofit LED lamps
12 ... 40 W
Dimmable energy-savings lamps 15 ... 54 W
Mixed loads
possible to lowest maximum load
Conventional transformers should be operated with at least 25 % nominal load. Nonetheless, 75 % is recommended because in individual cases, depending on the transformer,
unstable switching performance may occur.
Carry out loading of conventional, electronic and dual-mode transformers according to
manufacturer's instructions.
Do not use non-dimmable energy-saving lamps or 230 V retrofit LED lamps.
For 230 V retrofit LED lamps, the power supply of the switch insert via the lamp, even when
switched off, may cause weakened illumination of the lamp.
6.2 Troubleshooting
Device switches off and can no longer be switched on after a certain time.
Electronic overheating protection has triggered.
Reduce connected load.
Check the installation situation.
Device briefly switches off and on again.
Short circuit protection has triggered, but in the meantime there is no longer a fault.
Switch insert 2gang switches both outputs off.
Load at output 1 is defective and interrupts the power supply of the joint switch insert.
Repair load at output 1.
6.3 Accessories
Universal switch insert 1gang
Push-button 1gang
KNX radio button 1gang quicklink
KNX radio button 4gang quicklink
Motion detector 1.1 m
Motion detector 2.2 m
IR Motion detector comfort 1.1 m
IR Motion detector comfort 2.2 m
KNX radio motion detector
comfort 1.1 m quicklink
KNX radio motion detector
comfort 2.2 m quicklink
6W-5833D
8514 51 xx
8514 51 xx
8564 81 xx
8534 11 xx
8534 21 xx
8534 12 xx
8534 22 xx
8534 21 xx
8534 21 xx
Page 5/6
08-2013
Universal switch insert 1gang/Universal switch insert 2gang
Universal switch insert 2gang
Push-button 2gang
KNX radio button 2gang quicklink
KNX radio button 4gang quicklink
8514 21 xx
8514 61 xx
8564 81 xx
6.4 Warranty
We reserve the right to realise technical and formal changes to the product in the interest of
technical progress.
Our products are under guarantee within the scope of the statutory provisions.
If you have a warranty claim, please contact the point of sale.
6W-5833D
Page 6/6