Important: Read and save these instructions. This guide to be left with equipment.
OnLine
GSTC/SETC
B+ Models
Installation and
Operation Manual
Includes installation, operation maintenance and troubleshooting information for your GSTC/SETC B+
Nortec OnLine Options.
2553429-B | 21 JUN 2010
Thank you for choosing NORTEC.
INSTALLATION DATE (MM/DD/YYYY)
MODEL #
SERIAL #
Proprietary Notice
This document and the information disclosed herein are proprietary data of WALTER MEIER LTD. Neither this document nor the information contained herein shall be reproduced used, or disclosed to others without the written authorization of WALTER MEIER LTD., except to the extent required for installation or maintenance of recipient’s equipment. All references to the NORTEC name should be taken as referring to WALTER MEIER LTD.
Liability Notice
NORTEC does not accept any liability for installations of humidity equipment installed by unqualified personnel or the use of parts/components/equipment that are not authorized or approved by NORTEC.
Copyright Notice
Copyright 2010, WALTER MEIER LTD. All rights reserved.
Contents
1 Overview
1 Offerings
1 Humidifier Wiring
4 GPRS or Dial-up Connection
10 Configuration Screen
14 Nortec OnLine Start-Up Checklist
15 Troubleshooting
15 Gateway Indicator Lights
16 Spare Parts
17 Wiring Diagrams
Overview
The Nortec OnLine Option provides a web-based remote monitoring capability to equipped GSTC
(sold after March 2009) or SETC (sold after March 2010) series humidifiers. The Nortec OnLine option operates in conjunction with a centralized server based at Nortec 's facilities. This server allows the user to monitor and control various aspects of the humidifier operation. If a fault or service warning is detected the Nortec server will send an email response to three userspecified personnel. Nortec OnLine also provides Nortec with the ability to diagnose the humidifier's performance remotely, ensuring quick response to customer inquiries.
Nortec OnLine provides the advantages of immediate notification and quick diagnosis of humidifier fault conditions, should they arise. Nortec OnLine also provides a user-friendly BMSlike interface, even when a dedicated Building Management System is not available or unfeasible. All that is required for Nortec OnLine’s operation is either an internet connection, an external phone line or a wireless network connection.
Offerings
Nortec OnLine supports three types of connections to the internet: Ethernet, Dialup modem, and
GPRS modem. Both static IP and DHCP addressing is available for ethernet connections. Simply specify at the time of order, which type of connection type would be preferable and any details that may apply (refer to the configuration form at the back of the manual). Once in the field, a user can differentiate between the different connection types by inspecting a tag present on the
OnLine module. This identifier tag will provide details such as connection type and part number information.
For sites where LAN/internet connections are available, the OnLine module may be plugged into the network through an ethernet port present on the control board. NORTEC OnLine is capable of operating with either a Static IP address or a Dynamic IP address. Wide area network (WAN) port 5222 must be opened to TCP traffic for the units to communicate with the NORTEC OnLine
Service.
The Nortec OnLine module also comes equipped with a serial port which allows a dial-up modem or a wireless GPRS modem to be connected. All the necessary programming for the connection details will be pre-programmed at the factory.
Humidifier Wiring
It is possible to network up to a maximum of 8 units to a single Nortec OnLine module. This
OnLine module is located internally to the GSTC or SETC unit. When multiple humidifiers are present, only a single module is required and will be installed inside a 'lead' unit, which can be specified by the user. Since each unit is separately addressed, it is possible to monitor and control each unit independently.
Installation | 1
Figure 1: Networking Layout
2 | Installation
Figure 2: Networking for 2009 Models and Newer
The necessary internal wiring for the gateway is already present except for the network connection that can be made internally to the unit. To network multiple units to a single
Gateway, the units may be daisy-chained to each other using the network link terminals at the
OnLine terminal strip, see Figure 2 and 3.
B+
Figure 3: Connecting Multiple Humidifiers to a Lead Humidifier
Table 1 refers to the recommended wire types and maximum recommended lengths from the
Nortec OnLine module in the lead unit. Since communication between the humidifiers and
Nortec OnLine will always occur via a EIA-485 signal type, Nortec recommends using 18-24
AWG shielded (120 Ω impedance), twisted pair wire between the lead humidifier and each of the secondary humidifiers. Cable runs between the Nortec OnLine module and the furthest
“slave” humidifier should not exceed 2,600 feet. Signal boosters or repeaters may be necessary for longer wire runs. The shield wire(s) should be connected at one end only.
The Nortec OnLine module has been designed and tested to operate with a variety of third-party manufacturers equipment that promote wireless connectivity. Should a user desire to connect the OnLine module to the internet via a wireless connection such as 802.11b or g class network, Nortec can provide recommendations on which equipment to use.
Installation | 3
Ethernet Connections
To connect Nortec OnLine to the internet via a local area network, insert the ethernet cable into the port on the Nortec OnLine module inside the lead humidifier. The serial port is not used in this configuration. The option for Static IP or DHCP addressing is specified at time of order, the units should be visible on the network after being connected. In order to connuicate with the
Nortec OnLine service Lan Port 5222 must be opened (”forwarded or triggered”) for TCP traffic.
GPRS or Dial-up Connections
The Nortec OnLine module is also able to connect with the Nortec Server via a dial-up connection to a local Internet Service Provider or even through a GPRS connection. Should such a connection be desirable Nortec can recommend a variety of third party manufacturers equipment that the Nortec OnLine module has been proven to work well with.
If a dial-up or GPRS connection is desired it will be necessary to contact Nortec at the time of order to provide information on the required settings.
These modems are connected to the serial port on the OnLine module. The ethernet port is not used in this case.
Signal Type
EIA-485, 2-wire
Table 1: Recommended Wire Types and Lengths
A
Polarity
B
Recommended Cable
Net + Net - 18-24 AWG Shielded, Twisted Pair
120 Ω impedance
Maximum Recommended
Distance from NORTEC Module
2,600 ft
User Webpage Interface
The Nortec OnLine web page can be accessed via the internet address www.Norteconline.com.
After initially logging into the Nortec OnLine server the user will be presented with a list of humidifiers currently registered with the Server program. Each serial number and an address descriptor.
By clicking on the humidifier name, the user will then be brought to a status screen with an image of the selected humidifier. Refer to Figure 5.
The status screen, refer to Figure 6 provides the user with a quick reference to the unit’s operation.
Several key status values can be gathered at a glance. Refer to Table 2 for a description of the variables displayed on the status screen.
4 | Installation
Figure 4: NORTEC OnLine Homepage
Figure 5: List of Humidifiers
Installation | 5
Figure 6: Status Screen
6 | Installation
Variable Name
Table 2: Status Screen Variables
Displayed Information Description
3 Day Drain
Burner 1 Status
Burner 2 Status
Burner 3 Status
Burner 4 Status
Burner 5 Status
Burner 6 Status
Steam Exchanger
Status
Capacity Limit
Channel 1
Demand%RH
Channel 1 Setpoint
Channel 2
Demand/%RH
Channel 2 Setpoint
Drain Valve Status
Fault Indicator
Fill Valve Status
Full Tank Blowdown
Keep WarmKeep
Warn used on status screen not
Keep Warm.
Operational Hours
Remaining Service
Hours. Hours to next Service.
Serial Number
On/Off Chart Item
On/Off Animated
On/Off Lamp Indicator
On/Off Lamp Indicator
On/Off Lamp Indicator
On/Off Lamp Indicator
On/Off Lamp Indicator
On/Off Animated
0-100% Chart Item
Indicates if the three day tank drain feature is enabled. 0=disabled, 1=enabled.
Indicates if Burner 1 is on.
Indicates if Burner 2 is on (if equipped)
Indicates if Burner 3 is on (if equipped)
Indicates if Burner 4 is on (if equipped)
Indicates if Burner 5 is on (if equipped)
Indicates if Burner 6 is on (if equipped)
Indicates if steam is flowing through the heat exchanger.
Indicates the current value for the capacity limit set point (adjustment) on the humidifier.
0-100% Chart Item
0-100% Chart Item
0-100% Chart Item
0-100% Chart Item
Indicates the current Demand or %RH signal being supplied to Channel 1 of the humidifier from a connected sensor.
Shows current value for the setpoint of channel
1. This value is only applicable when unit is set to respond to a %RH signal.
Indicates the current Demand or %RH signal supplied to Channel 2 of the humidifier from a connected sensor.
Shows current value for the setpoint of channel
2. This value is only applicable when unit is set to respond to a %RH signal and configured for dual channel.
On/Off Animated
On/Off Lamp
Indicator
Provides current fault status. The red fault light is lit when a fault is detected.
On/Off Animated
Indicates when the tank drain has been activated and the unit is draining water.
On/Off Chart Item
Indicates if the humidifier is filling the water tank.
Indicates if the full tank blowdown feature is enabled or disabled. Feature is toggled by dipswitch on mainboard.
On/Off Chart Item Indicates if the water tank keepwarm feature is enabled or disabled. Feature is toggled by dipswitch on mainboard.
Hours Chart Item
Hours Chart Item
Alpha-Numeric String
Displays the amount of the time the humidifier has been in operation.
Displays the number of operational hours left until the next suggested service period is due.
Indicates the Humidifiers Serial Number for quick reference.
Product Line
GSTC SETC
X X
X
X
X
X
X
X
X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
Installation | 7
Variable Name
Service Indicator
Software Version
Steam Production
System Demand
Correct Output
Unit Address
Unit Model
Unit Status
Water Level High
Water Level Mid-
Range
Water Level Low
Weighted Hours
Manual Drain
Pre-Clean
Power Reset
Multimode
Table 2: Status Screen Variables - CONTINUED
Displayed Information Description
On/Off Lamp
Indicator
Numerical Chart Item
On/Off Animated
Provides current service status. The yellow service light is lit when service is due.
Indicates the software version installed on the
Humidifiers mainboard.
Indicates that the humidifier is producing steam in response to a demand signal.
0-100% Numerical Data Displays the humidifier's current demand output
Provides details on the Humidifier's location. Mailing Address Chart
Item
Unit Identifier Chart Item Indicates the model type & size of the selected humidifier.
On/Off Lamp
Indicator
On/Off Lamp
Indicator
Yellow light is on if water is at a high level. Light combinations are possible for mid-state water levels.
On/Off Lamp Indicator Green light is on if water is at optimal level.
Light combinations are possible for mid-state water levels
On/Off Lamp Indicator
Indicates if unit has responded to a demand signal. The green LED is on when a demand signal is present.
Hours Chart Item
Red light is on if water is at a low level. Light combinations are possible for mid-state water levels.
Equivalent operating hours convoluted to 100% steam production. Ex. Weighted hours = 2 hours at 50% demand.
On/Off Chart Item
On/Off Chart Item
On/Off Chart Item
Status Item
Drain unit when “on”.
Initiates a pre-clean cycle.
Performs a software reset similar to turning the unit off and then on again.
0: Standalone unit (default setting)
1: Unit is Master
2: Unit is Slave
Lists current signal type the unit is configured for
0: 0-5Vdc
1: 1-5Vdc
2: 0-10Vdc
3: 2-10Vdc
4: 0-16Vdc
5: 3.2-16Vdc
6: 0-10mA
Product LIne
GSTC SETC
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
8 | Installation
Variable Name
Limit Type
3 Day Drain Delay
Limit Signal Type
Time Proportioning
Active
Float Check Active
Table 2: Status Screen Variables - CONTINUED
Displayed
Information
Description
Status Item
Time Status Item
Status Item
On/Off Chart Item
On/Off Chart Item
7: 4-20mA
Displays idle time remaining before tank drains.
Lists current signal type the unit is configured for
0: 0-5Vdc
1: 1-5Vdc
2: 0-10Vdc
3: 2-10Vdc
4: 0-16Vdc
5: 3.2-16Vdc
6: 0-10mA
7: 4-20mA
Displays that unit has received demand such that time proportioning has activated.
Active when unit is currently performing a 23 hour float check.
Product Line
GSTC SETC
X X
X X
X X
X X
X X
Installation | 9
Configuration Screen
By selecting the configuration button, see Figure 7 & Figure 8, located near the top of the webpage, the user is able to adjust control parameters for the humidifier.
Table 3 provides a description of the control variables provided to the user.
Figure 7: Configuration Button
10 | Installation
Figure 8: Configuration Screen
Variable Name
Capacity Limit
Channel 1 Setpoint
Channel 2 Setpoint
Disable Humidifier
Table 3: Screen Status Variable
Setting Range Description
0-100%
10-95%
10-95%
Allows the user to adjust the total steam output the unit will be able to produce at
100% demand.
Sets the Channel 1 Setpoint. This feature is only enabled when the humidifier is set to operate with an RH signal.
Sets the Channel 2 Setpoint. This feature is only enabled when the humidifier is set to operate with an RH signal.
Enabled/Disabled Forces the humidifier into a lockout state where steam production is halted and the unit will not respond to any demand input.
Product Line
GSTC SETC
X X
X X
X X
X X
Installation | 11
At the top of the screen the user is presented with options for three different screens, see
Figure 9. One option will provide a trending graph, see Figure 10, that monitors points such as
%RH/Demand and setpoint settings for channel 1 and channel 2 as well as the current humidifier’s output. This trend graph is capable of keeping historical data for each particular unit.
Figure 9: Three Screen Options
12 | Installation
Figure 10: Trend Data
Figure 11: Fault and Service History Table, provides a list of up to 18 fault or service errors that the humidifier has experienced . This can provide valuable troubleshooting information when faced with a recurring problem.
Figure 12: Parameter Table, provides an in-depth view of all the variables available through
Nortec OnLine. From the parameter listings a user can determine if a certain gas burner has been disabled, the proportional coefficient for the PI band on channel 1, or even what version of the GSTC software the unit is currently operating with.
Figure 11: Fault and Service History Table
Figure 12: Parameter Table
Installation | 13
Nortec OnLine Start-Up Checklist
Wiring
Humidifier-to-humidifier connection:
Each individual humidifier linked to lead unit.
Connection can be direct or daisy-chained to other units.
Shield connected to lead unit only (wire should not be connected at other end).
Network Connection
Lead unit wired to local network (Ethernet, GPRS, Dial-up).
Network activity verified.
Port 5222 open to TCP traffic.
Start-Up Procedure
Ensure power is being supplied to the humidifier and NORTEC OnLine module.
Verify power to OnLine module (Power LED should be lit).
After power-up, verify network communication.
Verify variable operation after mapping is complete.
Perform regular humidifier start-up check.
14 | Installation
Troubleshooting
Gateway Indicator Lights
The OnLine module has four status indicator LEDs that provide a quick-reference for troubleshooting communication faults with the Nortec OnLine option. Table 4 provides a description of each LEDs function.
Table 5 details common problems and solutions.
LED Name
Module Status
Serial Link Status
Ethernet Activity /
Collision
Network Link
Table 4: OnLIne Module Status LED Description
Color Function
Off
Green
Indicates that the OnLine module is not receiving power.
Indicates the OnLine is operating normally.
Orange Indicates that the OnLine is loading the firmware installed on the module.
Flashing Green Indicates that the OnLine is receiving a network packet from an serial connection.
Flashing Red
Orange
Indicates that the OnLine is transmitting a network packet on a serial connection.
Displayed when the OnLine is booting.
Flashing Green Indicates that the OnLine is receiving a network packet from an
Ethernet connection.
Flashing Red Indicates that the OnLine is transmitting a network packet on a
Ethernet connection.
Off
Green
Orange
No network connection is present.
The OnLine has detected the presence of a 10Mbps network.
The OnLine has detected the presence of a 100Mbps network.
Troubleshooting | 15
Problem
The NORTEC server cannot read/write any information to any of the networked humidifiers.
The NORTEC server network can see some of the networked humidifiers but not others.
Table 5: Troubleshooting Communication Problems
Solution
Verify that the network connection is made and is connected properly.
Verify that firewall port 5222 is open to TCP traffic.
Verify that the correct network settings are being used. The OnLine module may need to be restarted to load the new settings.
Check the ethernet link (if ethernet enabled) or serial link (if modem enabled) communication LED's to determine if there is any network traffic being sent or received by the OnLine module from the NORTEC server. Verify proper connections to networked humidifiers.
Turn the OnLine module off for several seconds then switch it back on to reload the control program. Allow for some time for the network variables to be polled.
Ensure proper connections to the humidifiers.
Disconnect all of the humidifiers from the NORTEC OnLine module except for the unit that is not responding to the network. Disconnect power to the OnLine module, wait a moment, then reconnect power. Check Serial Link LED transmit/receive lights to see if the module can talk to the humidifier.
Verify that each unit has a unique modbus address (no conflicts).
Spare Parts
Table 6: Spare Parts
Part Number Item
1509602
1509603
NORTEC Online Module - Dial-up
Configuration.
Description
Spare part for On-Line module with dial-up settings.
NORTEC Online Module - GPRS Configuration. Spare part for On-Line module with dial-up settings.
1509604
1509605
1509349
NORTEC Online Module - Static IP
Configuration.
Spare part for On-Line module with wired ethernet and static IP settings.
NORTEC Online Module - DHCP Configuration. Spare part for On-Line module with wired ethernet and dynamic IP settings.
Communication Cable for OnLine module. Cable with RS-12 plug for On-Line module.
16 | Troubleshooting
Troubleshooting | 17
18 | Troubleshooting
Warranty
Walter Meier Inc. and/or Walter Meier Ltd. (hereinafter collectively referred to as THE
COMPANY), warrant for a period of two years after installation or 30 months from manufacturer’s ship date, whichever date is earlier, that THE COMPANY’s manufactured and assembled products, not otherwise expressly warranted (with the exception of the cylinder), are free from defects in material and workmanship. No warranty is made against corrosion, deterioration, or suitability of substituted materials used as a result of compliance with government regulations.
THE COMPANY’s obligations and liabilities under this warranty are limited to furnishing replacement parts to the customer, F.O.B. THE COMPANY’s factory, providing the defective part(s) is returned freight prepaid by the customer. Parts used for repairs are warranted for the balance of the term of the warranty on the original humidifier or 90 days, whichever is longer.
The warranties set forth herein are in lieu of all other warranties expressed or implied by law. No liability whatsoever shall be attached to THE COMPANY until said products have been paid for in full and then said liability shall be limited to the original purchase price for the product. Any further warranty must be in writing, signed by an officer of THE COMPANY.
THE COMPANY’s limited warranty on accessories, not of the companies manufacture, such as controls, humidistats, pumps, etc. is limited to the warranty of the original equipment manufacturer from date of original shipment of humidifier.
THE COMPANY makes no warranty and assumes no liability unless the equipment is installed in strict accordance with a copy of the catalog and installation manual in effect at the date of purchase and by a contractor approved by THE COMPANY to install such equipment.
THE COMPANY makes no warranty and assumes no liability whatsoever for consequential damage or damage resulting directly from misapplication, incorrect sizing or lack of proper maintenance of the equipment.
THE COMPANY makes no warranty and assumes no liability whatsoever for damage resulting from freezing of the humidifier, supply lines, drain lines, or steam distribution systems.
THE COMPANY makes no warranty and assumes no liability whatsoever for equipment that has failed due to ambient conditions when installed in locations having climates below 14°F (-
10°C) during January or above 104°F (40°C) during July.
THE COMPANY retains the right to change the design, specification and performance criteria of its products without notice or obligation.
U.S.A.
Walter Meier (Climate USA) Inc.
826 Proctor Avenue
Ogdensburg, NY 13669
CANADA
Walter Meier (Climate Canada) Ltd.
2740 Fenton Road
Ottawa, Ontario K1T 3T7
TEL: 1.866.NORTEC1
FAX: 613.822.7964
EMAIL: [email protected]
WEBSITE: www.humidity.com www.norteconline.com
Certificate No. 002419
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project