www.nemko.com TEST REPORT IEC 60950-1: 2005 (2nd

www.nemko.com TEST REPORT IEC 60950-1: 2005 (2nd
Test Report issued under the responsibility of:
www.nemko.com
TEST REPORT
IEC 60950-1: 2005 (2nd Edition)
Information technology equipment – Safety –
Part 1: General requirements
Report Reference No. ..................... :
180488B
Date of issue..................................... :
2011-10-21
Total number of pages ......................
45 + pages as indicated in part “List of attachments”
CB/CCA Testing Laboratory .......... :
Nemko Oy
Address ............................................ :
Perkkaantie 11, FI-02601 Espoo, Finland
Applicant’s name ............................ :
Satel Oy
Address ............................................ :
Meriniitynkatu 17, FI-24100 Salo, Finland
Manufacturer’s name ..................... :
Same as applicant
Address ............................................ :
Factory’s name ............................... :
Same as applicant
Address ............................................ :
Test specification:
Standard ........................................... :
Test procedure ................................. :
IEC 60950-1:2005 (2nd Edition) + A1:2009
CB
CCA
National
Non-standard test method…………..:
N/A
Test Report Form No...................... :
IECEN60950_1C
Test Report Form(s) Originator ........ :
SGS Fimko Ltd (edited by Nemko Oy)
Master TRF ...................................... :
Dated 2009-09 (2010-02)
Copyright © 2009 IEC System for Conformity Testing and Certification of Electrical Equipment (IECEE), Geneva, Switzerland.
All rights reserved.
This publication may be reproduced in whole or in part for non-commercial purposes as long as the IECEE is acknowledged as
copyright owner and source of the material. IECEE takes no responsibility for and will not assume liability for damages resulting from
the reader's interpretation of the reproduced material due to its placement and context.
If this Test Report Form is used by non-IECEE members, the IECEE/IEC logo and the reference to the CB Scheme procedure shall
be removed.
This report is not valid as a CB Test Report unless signed by an approved CB Testing Laboratory and appended to a CB Test
Certificate issued by an NCB in accordance with IECEE 02.
Test item description .....................:
Radio modem receiver for building-in
Trade Mark ....................................... :
SATEL-TA21
Manufacturer .................................... :
Satel Oy
Model/Type reference....................... :
CGR10 and CGR15
Ratings ............................................. :
No electrical ratings (the EUT is not connected to a mains supply)
This Test Report , when bearing the Nemko name and logo is only valid when issued by a Nemko laboratory,
or by a laboratory having special agreement with Nemko.
Page 2 of 49
Testing procedure and testing location:
CB/CCA Testing Laboratory:
Testing location/ address ...................... :
See page 1.
Tested by (name + signature) ..... :
Erja Hägert
Approved by (name + signature) . :
Timo Leismala
Testing procedure: TMP
Tested by (name + signature) ..... :
Approved by (name + signature) .. :
Testing location/ address ...................... :
Testing procedure: WMT
Tested by (name + signature) ..... :
Witnessed by (name + signature) :
Approved by (name + signature) . :
Testing location/ address ...................... :
Testing procedure: SMT
Tested by (name + signature) ..... :
Approved by (name + signature) .. :
Supervised by (name + signature):
Testing location/ address ................ :
Testing procedure: RMT
Tested by (name + signature) ..... :
Approved by (name + signature) .. :
Supervised by (name + signature):
Testing location/ address ...................... :
TRF No. IEC60950_1A
Report No. 180488B
Page 3 of 49
Report No. 180488B
Summary of testing (SOT):
The receiver CGR10 is working inside the Leica Viva CS10/15 unit. During the test the transmitter is
sending continuously the text to the CGR10 receiver. The numbers of receiver data can be seen in the
display of Leica Viva unit. The receiver frequencies are 403-473 MHz.
Clause 4.7; The equipment is for building-in. The flammability properties of the end product enclosure have
not been evaluated. Fire enclosure requirements have to be considered in end product.
The product
fulfils /
does not fulfill the requirements of EN 60950-1:2006 + A11:2009.
Tests performed (name of test and test clause):
Testing location:
All tests as indicated in the test report:
See page 1.
Summary of compliance with National Differences:
The product
fulfils /
does not fulfill the requirements of EN 60950-1:2006 + A11:2009 (+ A1:2010):
CENELEC common modifications
NO
SE
FI
DK
UK
IE
DE
CH
ES
US
CA
KR
other: According to Online CB-Bulletin dated 2011-10-21 no SNC have been informed for the following countries:
China, Japan.
SNC for Germany: Manuals have to be provided in German language before marketing in Germany.
Copy of marking plates
Receiver model CGR10
TRF No. IEC60950_1A
Receiver model CGR15
Page 4 of 49
Name and address of production-sites (Factories):
Satel Oy
Meriniitynkatu 17
P.O. Box 142
FI-24101
Finland
List of attachments:
The test report includes following additional documentation:
Technical Annex: 13 pages
Photographs: 5 pages
TRF No. IEC60950_1A
Report No. 180488B
Page 5 of 49
Report No. 180488B
Test item particulars (TIP):
Equipment mobility .................................................... :
Supply(s) ................................................................... :
movable
stationary
hand-held
for building-in
transportable
direct plug-in
a.c. mains
d.c. mains
SELV
TNV
battery operated
LPS
secondary hazardous voltage ?
other:
Connections per IEC 62102:
Connection to the supply .......................................... :
pluggable equipment:
type A
permanent connection
detachable power supply cord
non-detachable power supply cord
not directly connected to the mains
Operating condition .................................................. :
continuous
rated operating / resting time:
Access area .............................................................. :
operator access area
restricted access location
service access area
Overvoltage category (OVC) .................................... :
OVC I
other:
OVC II
OVC III
type B
OVC IV
Mains supply tolerance (%) or absolute mains supply Not connected to mains.
values (V) ................................................................. :
Tested power systems .............................................. :
TN-S, TN-C, TN-C-S, TT (not corner earthed,
figure V.1, V.2, V.3, V.5)
TN-S, TT (corner earthed, figures V.1, V.6)
TN-C (middle point earthed, figure V.4)
IT (not corner earthed, figure V.7)
IT (corner earthed, figure V.8), simulated
impedance (MΩ):
IT testing, phase-phase voltage (V) .......................... : N/A
Class of equipment ................................................... :
Class I
Class II
Not classified
Class III
PD 1
PD 3
Considered current rating (A) ................................... :
Pollution degree (PD) ............................................... :
PD 2
IP protection class .................................................... : IP20
Max. altitude during operation (m) ............................ : 2000 m
Altitude of test laboratory (m) ................................... : approx. 3 m
Mass of equipment (kg) ............................................ :
0,053kg
Ambient temperature during operation (°C) ........ ..... : Max. +60°C
Additional requirements as per cl. 1.1.2 ................... :
Radiation(s) and special hazards .............................. :
Output(s) and other connections .............................. :
TRF No. IEC60950_1A
Laser
UV
Ionizing
CRT
Energy
batteries
moving parts
dust, powder, gases, liquids, oil, grease
heating elements
thermostats
sound pressure
audio amplifier
other:
none
SELV
LPS
secondary hazardous voltage
other:
Connections per IEC 62102:
TNV
mains
Page 6 of 49
Report No. 180488B
Possible test case verdicts:
- test case does not apply to the test object.................. : N/A
- test object does meet the requirement ....................... : P (Pass)
- test object does not meet the requirement ................. : F (Fail)
Testing:
Date of receipt of test item ............................................ : 08.08.2011
Date(s) of performance of tests .................................... : 11.10.2011-18.10.2011
General remarks:
The test results presented in this report relate only to the object tested.
This report shall not be reproduced, except in full, without the written approval of the Issuing testing laboratory.
"(See Enclosure #)" refers to additional information appended to the report.
"(See appended table)" refers to a table appended to the report.
Note: This TRF includes EN Group Differences together with National Differences and Special National
Conditions, if any. All Differences are located in the Appendix to the main body of this TRF.
Throughout this report a
comma /
point is used as the decimal separator.
General product information (GPI):
CGR10/15 is a 4-level FSK/GMSK UHF radio modem receiver, which provides a transparent data received
from SATELLINE compatible radio modems manufactured by Satel Oy.
It has been designed especially for use in Leica Viva CS10/15 series controllers.
The CGR10/15 gets the 5V operating voltage inside from the Leica Viva CS10/15 unit.
TRF No. IEC60950_1A
Page 7 of 49
Report No.180488B
IEC 60950-1
Clause
Requirement + Test
1
GENERAL
P
1.4
General conditions for test
P
1.4.1
Application of tests
P
1.4.2
Type tests
P
1.4.3
Test samples ......................................................... :
1.4.4
Operating parameters for test ............................... :
1.4.5
Supply voltage for test ........................................... :
5VDC
1.4.6
Supply frequency for test ....................................... :
DC equipment
1.4.7
Electrical measuring instruments
P
1.4.8
Normal operating voltages
P
1.4.9
Measurement of voltage to earth
DC equipment
1.4.10
Loading configuration of the EUT .......................... :
The transmitter is sending
continuously the text to the
CGR10 receiver.
1.4.11
Power from a telecommunication network
1.4.12
Temperature measurement conditions
P
1.4.12.1
General
P
1.4.12.2
Temperature dependent equipment ...................... :
1.4.12.3
Non-temperature dependent equipment ............... :
Measurements carried out
with 60 °C.
P
1.4.13
Temperature measurement methods
Thermocouple method
P
1.4.14
Simulated faults and abnormal operating conditions
P
1.4.15
Compliance by inspection of relevant data
P
1.5
Components
P
1.5.1
General
P
Comply with IEC 60950-1 or relevant component
standard
TRF No. IEC60950_1A
Result – Remark
As user would receive.
Verdict
P
P
P
N/A
N/A
P
N/A
N/A
(see appended table 1.5.1)
P
Page 8 of 49
Report No.180488B
IEC 60950-1
Clause
Requirement + Test
Result – Remark
1.5.2
Evaluation and testing of components
Certified components are
used in accordance with their
ratings, certifications and/or
they comply with applicable
parts of this standard.
Verdict
P
Components not certified are
used in accordance with their
ratings and they comply with
applicable parts of IEC 609501 and/or the relevant
component standard.
Components, for which no
relevant IEC-standard exists,
have been tested under the
conditions occurring in the
equipment, using applicable
parts of IEC 60950-1.
1.5.3
Thermal controls
1.5.4
Transformers
N/A
1.5.5
Interconnecting cables
N/A
1.5.6
Capacitors bridging insulation
No primary circuits in the
equipment. The equipment
contains SELV circuits only.
1.5.7
Resistors bridging insulation
Refer below:
P
1.5.7.1
Resistors bridging functional, basic or
supplementary insulation
Resistors are bridging
functional insulation only.
P
1.5.7.2
Resistors bridging double or reinforced insulation
between a.c. mains supply and other circuits
No primary circuits in the
equipment.
N/A
1.5.7.3
Resistors bridging double or reinforced insulation
between a.c. mains and antenna or coaxial cable
No primary circuits in the
equipment.
N/A
1.5.8
Components in equipment for IT power systems
The equipment is for DC only.
N/A
1.5.9
Surge suppressors
VDRs have not been used in
the equipment.
N/A
1.5.9.1
General
N/A
1.5.9.2
Protection of VDRs
N/A
1.5.9.3
Bridging of functional insulation by a VDR
N/A
1.5.9.4
Bridging of basic insulation by a VDR
N/A
1.5.9.5
Bridging of supplementary, double or reinforced
insulation by a VDR
N/A
1.6
Power interface
1.6.1
AC power distribution systems
1.6.2
Input current
1.6.3
Voltage limit of hand-held equipment
TRF No. IEC60950_1A
No thermal controls.
N/A
N/A
P
The equipment is for DC only.
N/A
N/A
5VDC
P
Page 9 of 49
Report No.180488B
IEC 60950-1
Clause
Requirement + Test
Result – Remark
Verdict
1.6.4
Neutral conductor
The equipment is for DC only.
Equipment
Inv. no.
Date(s)
-
-
-
1.7
Marking and instructions
1.7.1
Power rating and identification markings
1.7.1.1
Power rating markings
Rated voltage(s) or voltage range(s) (V) ............... :
1.7.1.2
N/A
P
The equipment is building-in
type for use in Leica Viva
CS10/15 series controllers.
P
N/A
The 5V operating voltage is
taken from the Leica Viva
CS10/15 unit. No rating
provided, since the equipment
is not connected to a mains
supply.
N/A
Symbol for nature of supply, for d.c. only ............... :
N/A
Rated frequency or rated frequency range (Hz) .... :
N/A
Rated current (mA or A) ........................................ :
N/A
Identification markings
Refer below;
P
Manufacturer’s name or trade-mark or identification SATEL-TA21
mark ...................................................................... :
P
Model identification or type reference ................... :
CGR-10 and CGR-15
P
Symbol for Class II equipment only ....................... :
The equipment is class III.
Other markings and symbols ................................ :
N/A
N/A
1.7.2
Safety instructions and marking
1.7.2.1
General
N/A
1.7.2.2
Disconnect devices
N/A
1.7.2.3
Overcurrent protective device
N/A
1.7.2.4
IT power distribution systems
1.7.2.5
Operator access with a tool
1.7.2.6
Ozone
EUT does not produce ozone.
N/A
1.7.3
Short duty cycles
The equipment is intended for
continuous operation.
N/A
1.7.4
Supply voltage adjustment ................................... :
N/A
Methods and means of adjustment; reference to
installation instructions ......................................... :
N/A
1.7.5
Power outlets on the equipment ........................... :
TRF No. IEC60950_1A
No precautions regarding
connection to earthed mains
socket-outlet are necessary.
The equipment is for DC
supply only.
N/A
N/A
N/A
No standard power outlet.
N/A
Page 10 of 49
Report No.180488B
IEC 60950-1
Clause
Requirement + Test
1.7.6
Fuse identification (marking, special fusing
characteristics, cross-reference) .......................... :
1.7.7
Wiring terminals
1.7.7.1
Protective earthing and bonding terminals ........... :
N/A
1.7.7.2
Terminals for a.c. mains supply conductors
N/A
1.7.7.3
Terminals for d.c. mains supply conductors
N/A
1.7.8
Controls and indicators
1.7.8.1
Identification, location and marking ...................... :
N/A
1.7.8.2
Colours ................................................................ :
N/A
1.7.8.3
Symbols according to IEC 60417 ......................... :
N/A
1.7.8.4
Markings using figures ....................................... :
N/A
1.7.9
Isolation of multiple power sources ..................... :
Single power source only.
N/A
1.7.10
Thermostats and other regulating devices .......... :
No thermostats or other
regulating devices.
N/A
1.7.11
Durability
Marking withstands rubbing by
water (15 s) and petroleum
spirit (15 s).
P
1.7.12
Removable parts
No marking is placed on
removable parts such that the
marking could become
misleading.
P
1.7.13
Replaceable batteries .......................................... :
No batteries in the equipment.
N/A
1.7.14
Result – Remark
Verdict
N/A
No wiring terminals provided.
No controls or indicators.
N/A
N/A
Language(s) ........................................................ :

Equipment for restricted access locations ........... :
N/A
Equipment
Inv. no.
Date(s)
Water
-
11.10.2011
Spirit
-
11.10.2011
TRF No. IEC60950_1A
Page 11 of 49
Report No.180488B
IEC 60950-1
Clause
Requirement + Test
Result – Remark
Verdict
2
PROTECTION FROM HAZARDS
P
2.1
Protection from electric shock and energy hazards
P
2.1.1
Protection in operator access areas
2.1.1.1
Access to energized parts
P
Test by inspection ................................................. :
P
Test with test finger (Figure 2A) ............................ :
P
Test with test pin (Figure 2B) ................................ :
N/A
Test with test probe (Figure 2C) ........................... :
N/A
2.1.1.2
Battery compartments
N/A
2.1.1.3
Access to ELV wiring
For building-in equipment
with +5VDC input voltage
No ELV.
N/A

Working voltage (Vpeak or Vrms); minimum
distance through insulation (mm)
2.1.1.4
Access to hazardous voltage circuit wiring
No hazardous voltages in
operator access area.
2.1.1.5
Energy hazards ..................................................... :
No energy hazard in operator
access area.
2.1.1.6
Manual controls
No shafts of knobs etc.
2.1.1.7
Discharge of capacitors in equipment
Energy hazards – d.c. mains supply
N/A
P
N/A
N/A

Measured voltage (V); time-constant (s) ................ :
2.1.1.8
P
Not connected to d.c. mains
supply.
N/A
a) Capacitor connected to the d.c. mains supply .. :
N/A
b) Internal battery connected to the d.c. mains
supply .................................................................... :
N/A
2.1.1.9
Audio amplifiers .................................................... :
No audio amplifiers.
N/A
2.1.2
Protection in service access areas
N/A
2.1.3
Protection in restricted access locations
N/A
Equipment
Inv. no.
Date(s)
-
-
-
2.2
SELV circuits
2.2.1
General requirements
SELV limits are not exceeded
under normal condition and
after a single fault.
P
2.2.2
Voltages under normal conditions (V) ................... :
+5VDC
P
2.2.3
Voltages under fault conditions (V) ....................... :
+5VDC
P
TRF No. IEC60950_1A
P
Page 12 of 49
Report No.180488B
IEC 60950-1
Clause
Requirement + Test
Result – Remark
Verdict
2.2.4
Connection of SELV circuits to other circuits ...... :
SELV circuits are connected
to other SELV circuits.
Equipment
Inv. no.
Date(s)
Multimetr Fluke 289
682
18.10.2011
P
2.3
TNV circuits
N/A
2.3.1
Limits
N/A
Type of TNV circuits ............................................... :

2.3.2
Separation from other circuits and from accessible
parts
N/A
2.3.2.1
General requirements
N/A
2.3.2.2
Protection by basic insulation
N/A
2.3.2.3
Protection by earthing
N/A
2.3.2.4
Protection by other constructions .......................... :
N/A
2.3.3
Separation from hazardous voltages
N/A

Insulation employed ............................................... :
2.3.4
Connection of TNV circuits to other circuits
N/A

Insulation employed ............................................... :
2.3.5
Test for operating voltages generated externally
N/A
Equipment
Inv. no.
Date(s)
-
-
-
2.4
Limited current circuits
2.4.1
General requirements
2.4.2
Limit values
2.4.3
N/A
2.4.1 – 2.4.3; No limited
current circuits.
N/A
N/A
Frequency (Hz) ...................................................... :

Measured current (mA) .......................................... :

Measured voltage (V) ............................................. :

Measured circuit capacitance (nF or µF) ............... :

Connection of limited current circuits to other
circuits
N/A
Equipment
Inv. no.
Date(s)
-
-
-
TRF No. IEC60950_1A
Page 13 of 49
Report No.180488B
IEC 60950-1
Clause
Requirement + Test
Result – Remark
Verdict
2.5
Limited power sources
(See appended table 2.5)
N/A
a) Inherently limited output
No limited power sources.
N/A
b) Impedance limited output
N/A
c) Regulating network limited output under normal
operating and single fault condition
N/A
d) Overcurrent protective device limited output
N/A
Equipment
Inv. no.
Date(s)
-
-
-
2.6
Provisions for earthing and bonding
N/A
2.6.1
Protective earthing
2.6.2
Functional earthing
N/A
2.6.3
Protective earthing and protective bonding
conductors
N/A
2.6.3.1
General
N/A
2.6.3.2
Size of protective earthing conductors
Not connected to mains. No
parts required to be
connected to protective earth.
N/A
2
Rated current (A), cross-sectional area (mm ),
AWG ...................................................................... :
2.6.3.3
N/A
Size of protective bonding conductors

N/A
2
Rated current (A), cross-sectional area (mm ),
AWG ...................................................................... :

Protective current rating (A), cross-sectional area
2
(mm ), AWG........................................................... :

2.6.3.4
Resistance of earthing conductors and their
terminations; resistance (Ω), voltage drop (V), test
current (A), duration (min) ...................................... :
N/A
2.6.3.5
Colour of insulation ................................................ :
N/A
2.6.4
Terminals
N/A
2.6.4.1
General
N/A
2.6.4.2
Protective earthing and bonding terminals
N/A
Rated current (A), type, nominal thread diameter
(mm) ....................................................................... :

2.6.4.3
Separation of the protective earthing conductor from
protective bonding conductors
N/A
2.6.5
Integrity of protective earthing
N/A
2.6.5.1
Interconnection of equipment
N/A
2.6.5.2
Components in protective earthing conductors and
protective bonding conductors
N/A
TRF No. IEC60950_1A
Page 14 of 49
Report No.180488B
IEC 60950-1
Clause
Requirement + Test
Result – Remark
Verdict
2.6.5.3
Disconnection of protective earth
N/A
2.6.5.4
Parts that can be removed by an operator
N/A
2.6.5.5
Parts removed during servicing
N/A
2.6.5.6
Corrosion resistance
N/A
2.6.5.7
Screws for protective bonding
N/A
2.6.5.8
Reliance on telecommunication network or cable
distribution system
N/A
Equipment
Inv. no.
Date(s)
-
-
-
2.7
Overcurrent and earth fault protection in primary circuits
N/A
2.7.1
Basic requirements
N/A
2.7.1 – 2.7.6; No primary
circuits.
Instructions when protection relies on building
installation
N/A
2.7.2
Faults not simulated in 5.3.7
N/A
2.7.3
Short-circuit backup protection
N/A
2.7.4
Number and location of protective devices ........... :
N/A
2.7.5
Protection by several devices
N/A
2.7.6
Warning to service personnel ................................ :
N/A
2.8
Safety interlocks
N/A
2.8.1
General principles
2.8.2
Protection requirements
N/A
2.8.3
Inadvertent reactivation
N/A
2.8.4
Fail-safe operation
N/A
2.8.5
Moving parts
N/A
2.8.6
Overriding
N/A
2.8.7
Switches, relays and their related circuits
N/A
2.8.7.1
Separation distances for contact gaps and their
related circuits
N/A
2.8.7.2
Overload test
N/A
2.8.7.3
Endurance test
N/A
2.8.7.4
Electric strength test
N/A
2.8.8
Mechanical actuators
N/A
Equipment
TRF No. IEC60950_1A
2.8.1 – 2.8.8; No safety
interlocks.
Inv. no.
Date(s)
N/A
Page 15 of 49
Report No.180488B
IEC 60950-1
Clause
Requirement + Test
-
Result – Remark
-
Verdict
-
2.9
Electrical insulation
P
2.9.1
Properties of insulating materials
P
2.9.2
Humidity conditioning
Non hygroscopic insulation
materials used (PCB only).
P
Relative humidity (%), temperature (°C) ......... ...... :
-

2.9.3
Grade of insulation
Functional.
P
2.9.4
Separation from hazardous voltages
Supplied by SELV.
N/A

Method(s) used ..................................................... :
Equipment
Inv. no.
Date(s)
-
-
-
2.10
Clearances, creepage distances and distances through insulation
P
2.10.1
General
P
2.10.1.1
Frequency .............................................................. :
DC supply.
P
2.10.1.2
Pollution degrees ................................................... :
2
P
2.10.1.3
Reduced values for functional insulation
See 5.3.4.
P
2.10.1.4
Intervening unconnected conductive parts
N/A
2.10.1.5
Insulation with varying dimensions
N/A
2.10.1.6
Special separation requirements
N/A
2.10.1.7
Insulation in circuits generating starting pulses
N/A
2.10.2
Determination of working voltage
P
2.10.2.1
General
P
2.10.2.2
RMS working voltage
P
2.10.2.3
Peak working voltage
P
2.10.3
Clearances
N/A
2.10.3.1
General
N/A
2.10.3.2
Mains transient voltages
Not connected to mains
supply.
N/A
a) AC mains supply ............................................... :
N/A
b) Earthed d.c. mains supplies .............................. :
N/A
c) Unearthed d.c. mains supplies .......................... :
N/A
d) Battery operation ............................................... :
N/A
2.10.3.3
Clearances in primary circuits
No primary circuits.
N/A
2.10.3.4
Clearances in secondary circuits
Functional insulation complies
with 5.3.4 c).
N/A
TRF No. IEC60950_1A
Page 16 of 49
Report No.180488B
IEC 60950-1
Clause
Requirement + Test
Result – Remark
2.10.3.5
Clearances in circuits having starting pulses
N/A
2.10.3.6
Transients from a.c. mains supply ........................ :
N/A
2.10.3.7
Transients from d.c. mains supply ........................ :
N/A
2.10.3.8
Transients from telecommunication networks and
cable distribution systems ..................................... :
N/A
2.10.3.9
Measurement of transient voltage levels
N/A
a) Transients from a mains suplply
N/A
For an a.c. mains supply ....................................... :
N/A
For a d.c. mains supply ......................................... :
N/A
b) Transients from a telecommunication network :
N/A
2.10.4
Creepage distances
2.10.4.1
General
N/A
2.10.4.2
Material group and comparative tracking index
N/A
CTI tests ................................................................. :
Functional insulation complies
with 5.3.4 c).
Verdict
Material group IIIb is
assumed to be used.
N/A

2.10.4.3
Minimum creepage distances
2.10.5
Solid insulation
P
2.10.5.1
General
P
2.10.5.2
Distances through insulation
N/A
2.10.5.3
Insulating compound as solid insulation
N/A
2.10.5.4
Semiconductor devices
N/A
2.10.5.5
Cemented joints
N/A
2.10.5.6
Thin sheet material – General
N/A
2.10.5.7
Separable thin sheet material
N/A
Number of layers (pcs) ........................................... :
N/A

2.10.5.8
Non-separable thin sheet material
N/A
2.10.5.9
Thin sheet material – standard test procedure
N/A
Electric strength test
2.10.5.10
Thin sheet material – alternative test procedure
Electric strength test

N/A

2.10.5.11
Insulation in wound components
N/A
2.10.5.12
Wire in wound components
N/A
Working voltage .................................................... :
N/A
a) Basic insulation not under stress ...................... :
N/A
b) Basic, supplementary, reinforced insulation ...... :
N/A
c) Compliance with Annex U ................................. :
N/A
TRF No. IEC60950_1A
Page 17 of 49
Report No.180488B
IEC 60950-1
Clause
2.10.5.13
Requirement + Test
Verdict
Two wires in contact inside wound component;
angle between 45° and 90° ................................... :
N/A
Wire with solvent-based enamel in wound
components
N/A
Electric strength test
2.10.5.14
Result – Remark
(see appended table 2.10.5)

Routine test
N/A
Additional insulation in wound components
N/A
Working voltage .................................................... :
N/A
- Basic insulation not under stress ........................ :
N/A
- Supplementary, reinforced insulation .................. :
N/A
2.10.6
Construction of printed boards
P
2.10.6.1
Uncoated printed boards
P
2.10.6.2
Coated printed boards
N/A
2.10.6.3
Insulation between conductors on the same inner
surface of a printed board
N/A
2.10.6.4
Insulation between conductors on different layers of
a printed board
N/A
Distance through insulation
N/A
Number of insulation layers (pcs) ........................... :
N/A
2.10.7
Component external terminations
N/A
2.10.8
Tests on coated printed boards and coated
components
N/A
2.10.8.1
Sample preparation and preliminary inspection
N/A
2.10.8.2
Thermal conditioning
N/A
2.10.8.3
Electric strength test
N/A
2.10.8.4
Abrasion resistance test
N/A
2.10.9
Thermal cycling
N/A
2.10.10
Test for Pollution Degree 1 environment and
insulating compound
N/A
2.10.11
Tests for semiconductor devices and cemented
joints
N/A
2.10.12
Enclosed and sealed parts
N/A
Equipment
Inv. no.
Date(s)
-
-
-
TRF No. IEC60950_1A
Page 18 of 49
Report No.180488B
IEC 60950-1
Clause
Requirement + Test
3
WIRING, CONNECTIONS AND SUPPLY
P
3.1
General
P
3.1.1
Current rating and overcurrent protection
3.1.2
Protection against mechanical damage
3.1.3
Securing of internal wiring
N/A
3.1.4
Insulation of conductors
N/A
3.1.5
Beads and ceramic insulators
N/A
3.1.6
Screws for electrical contact pressure
N/A
3.1.7
Insulating materials in electrical connections
N/A
3.1.8
Self-tapping and spaced thread screws
N/A
3.1.9
Termination of conductors
N/A
10 N pull test
N/A
Sleeving on wiring
N/A
3.1.10
Result – Remark
Verdict
No over-current protection.
P
Equipment
Inv. no.
Date(s)
-
-
-
3.2
P
Connection to a mains supply
N/A
Not connected to mains. Sub-clauses deleted.
3.3
Wiring terminals for connection of external conductors
N/A
Not connected to mains. Sub-clauses deleted.
3.4
Disconnection from the mains supply
N/A
Not connected to mains. Sub-clauses deleted.
3.5
Interconnection of equipment
P
3.5.1
General requirements
P
3.5.2
Types of interconnection circuits ........................... :
3.5.3
ELV circuits as interconnection circuits
N/A
3.5.4
Data ports for additional equipment
N/A
SELV- SELV
P
Equipment
Inv. no.
Date(s)
-
-
-
TRF No. IEC60950_1A
Page 19 of 49
Report No.180488B
IEC 60950-1
Clause
Requirement + Test
4
PHYSICAL REQUIREMENTS
4.1
Stability
Angle of 10°
Result – Remark
Verdict
P
N/A
For building-in.
N/A
Test force (N) ........................................................ :
N/A
Equipment
Inv. no.
Date(s)
-
-
-
4.2
Mechanical strength
N/A
4.2.1
General
4.2.2
Steady force test, 10 N
N/A
4.2.3
Steady force test, 30 N
N/A
4.2.4
Steady force test, 250 N
N/A
4.2.5
Impact test
N/A
Fall test
N/A
Swing test
N/A
4.2.6
Drop test; height (mm) .......................................... :
N/A
4.2.7
Stress relief test (°C) .................... ......................... :
N/A
4.2.8
Cathode ray tubes
4.2.1 – 4.2.7; No
requirements from clauses
2.1.1, 2.6.1, 2.10, 3.2.6 and
4.4.1. No tests considered
necessary.
No CRTs in the equipment.
Picture tube separately certified ............................ :
N/A
N/A
N/A
4.2.9
High pressure lamps
No high pressure lamps in the
equipment.
N/A
4.2.10
Wall or ceiling mounted equipment; force (N) ....... :
The equipment is hand-held.
N/A
4.2.11
Rotating solid media
The equipment does not
contain devices that would
use solid media rotating at a
speed higher than 8 000
r/min.
N/A
Equipment
Inv. no.
Date(s)
-
-
-
4.3
Design and construction
4.3.1
Edges and corners
TRF No. IEC60950_1A
P
All edges and corners are free
from sharp edges.
P
Page 20 of 49
Report No.180488B
IEC 60950-1
Clause
Requirement + Test
Result – Remark
Verdict
4.3.2
Handles and manual controls; force (N)..............:
No handles and manual
controls.
N/A
4.3.3
Adjustable controls
No hazardous adjustable
controls.
N/A
4.3.4
Securing of parts
No loosening of parts
impairing creepage distances
or clearances likely to occur.
P
4.3.5
Connection by plugs and sockets
SELV connector at the back
of the equipment does not
comply with IEC 60320 or
IEC 60083.
P
4.3.6
Direct plug-in equipment
Not intended to plug directly
into a wall socket-outlet.
N/A
Torque .................................................................. :

Compliance with the relevant mains plug standard
.............................................................................. :
N/A
4.3.7
Heating elements in earthed equipment
No heating elements
provided.
N/A
4.3.8
Batteries
No batteries in the equipment.
N/A
- Overcharging of a rechargeable battery
N/A
- Unintentional charging of a non-rechargeable
battery
N/A
- Reverse charging of a rechargeable battery
N/A
- Excessive discharging rate for any battery
N/A
4.3.9
Oil and grease
Insulation is not exposed to
oil, grease etc.
N/A
4.3.10
Dust, powders, liquids and gases
The equipment does not
generate dust or use
powders, and does not
contain flammable liquids or
gases.
N/A
4.3.11
Containers for liquids or gases
No containers for liquids or
gases in the equipment.
N/A
4.3.12
Flammable liquids ................................................ :
The equipment does not
contain flammable liquid.
N/A
Quantity of liquid (l) .............................................. :
N/A
Flash point (°C) .................................................... :
N/A
4.3.13
Radiation
N/A
4.3.13.1
General
Refer below:
N/A
4.3.13.2
Ionizing radiation
The equipment does not
generate ionizing radiation.
N/A
Measured radiation (pA/kg) .................................. :

Measured high-voltage (kV) ................................. :

TRF No. IEC60950_1A
Page 21 of 49
Report No.180488B
IEC 60950-1
Clause
4.3.13.3
Requirement + Test
Result – Remark
Verdict
Measured focus voltage (kV) ............................... :

CRT markings ...................................................... :

Effect of ultraviolet (UV) radiation on materials
The equipment does not
produce UV radiation.
Part, property, retention after test, flammability
classification ......................................................... :
N/A
N/A
4.3.13.4
Human exposure to ultraviolet (UV) radiation ...... :
The equipment does not
produce UV radiation.
N/A
4.3.13.5
Lasers (including laser diodes) and LEDs
Refer below:
N/A
4.3.13.5.1
Lasers (including laser diodes)
No lasers in the equipment.
N/A

Laser class ........................................................... :
4.3.13.5.2
Light emitting diodes (LEDs)
No LEDs.
4.3.13.6
Other types ........................................................... :
The equipment is a receiver
only.
Equipment
Inv. no.
Date(s)
-
-
-
TRF No. IEC60950_1A
N/A
Page 22 of 49
Report No.180488B
IEC 60950-1
Clause
Requirement + Test
4.4
Protection against hazardous moving parts
Result – Remark
Verdict
N/A
No moving parts. Sub-clauses deleted.
4.5
Thermal requirements
P
4.5.1
General
4.5.2
Temperature tests
P
Normal load condition per Annex L ...................... :

Refer below:
P
4.5.3
Temperature limits for materials
(see appended table 4.5)
P
4.5.4
Touch temperature limits
(see appended table 4.5)
P
4.5.5
Resistance to abnormal heat ............................... :
Class III equipment. No
thermoplastic parts carrying
hazardous voltages.
Equipment
Inv. no.
Date(s)
Datalogger Agilent 34970A
600
14.10.2011
4.6
Openings in enclosures
4.6.1
Top and side openings
P
No openings.
P

Dimensions (mm) ................................................. :
4.6.2
Bottoms of fire enclosures
No openings.
P

Construction of the bottom, dimensions (mm) ..... :
4.6.3
Doors or covers in fire enclosures
4.6.4
Openings in transportable equipment
4.6.4.1
Constructional design measures
N/A
N/A
No openings.
P
N/A

Dimensions (mm) ................................................. :
4.6.4.2
Evaluation measures for larger openings
N/A
4.6.4.3
Use of metallized parts
N/A
4.6.5
Adhesives for constructional purposes
No barrier secured by
adhesive inside enclosure.

Conditioning temperature (°C), time (weeks) ........ :
Equipment
Inv. no.
Date(s)
-
-
-
4.7
Resistance to fire
4.7.1
Reducing the risk of ignition and spread of flame
TRF No. IEC60950_1A
N/A
P
Method 1 has been used.
P
Page 23 of 49
Report No.180488B
IEC 60950-1
Clause
Requirement + Test
Result – Remark
Verdict
Method 1, selection and application of components
wiring and materials
(see appended table 4.7)
P
Method 2, application of all of simulated fault
condition tests
Method 1 has been used.
N/A
4.7.2
Conditions for a fire enclosure
For building-in. Fire enclosure
requirements has to be
considered in end product.
N/A
4.7.2.1
Parts requiring a fire enclosure
N/A
4.7.2.2
Parts not requiring a fire enclosure
N/A
4.7.3
Materials
4.7.3.1
General
See table 4.7.
4.7.3.2
Materials for fire enclosures
For building-in. Fire enclosure
requirements has to be
considered in end product.
4.7.3.3
Materials for components and other parts outside
fire enclosures
4.7.3.4
Materials for components and other parts inside fire See tables 1.5.1 and 4.7.
enclosures
4.7.3.5
Materials for air filter assemblies
No air filters in the equipment.
N/A
4.7.3.6
Materials used in high-voltage components
No high-voltage components
in the equipment.
N/A
P
P
N/A
N/A
Equipment
Inv. no.
Date(s)
-
-
-
P
5
ELECTRICAL REQUIREMENTS AND SIMULATED ABNORMAL CONDITIONS
N/A
5.1
Touch current and protective conductor current
N/A
Touch current and protective conductor current not applicable.
Sub-clauses deleted.
5.2
Electric strength
5.2.1
General
5.2.2
Test procedure
N/A
Functional insulation complies
with 5.3.4 c).
N/A
N/A
Equipment
Inv. no.
-
-
Date(s)
-
5.3
Abnormal operating and fault conditions
P
5.3.1
Protection against overload and abnormal operation (see appended table 5.3)
P
TRF No. IEC60950_1A
Page 24 of 49
Report No.180488B
IEC 60950-1
Clause
Requirement + Test
Result – Remark
Verdict
5.3.2
Motors
No motors / fans in the
equipment.
N/A
5.3.3
Transformers
No safety isolating
transformers in the
equipment.
N/A
5.3.4
Functional insulation .............................................. :
Functional insulation complies
with 5.3.4 c).
N/A
5.3.5
Electromechanical components
No electromechanical
components in the equipment.
N/A
5.3.6
Audio amplifiers in ITE ......................................... :
No audio amplifiers in the
equipment.
N/A
5.3.7
Simulation of faults
See the enclosed fault
condition tests, Table 5.3.
P
5.3.8
Unattended equipment
No thermostats, temperature
limiters or thermal cut-outs.
5.3.9
Compliance criteria for abnormal operating and
fault conditions
Refer below:
P
5.3.9.1
During the tests
No fire or molten metal
occurred and no deformation
of enclosure during the tests.
P
5.3.9.2
After the tests
Functional insulation only.
P
Equipment
Inv. no.
Date(s)
Datalogger Agilent 34970A
600
18.10.2011
6
CONNECTION TO TELECOMMUNICATION NETWORKS
N/A
N/A
Not connected to telecommunication networks.
Sub-clauses deleted.
7
CONNECTION TO CABLE DISTRIBUTION SYSTEMS
Not connected to cable distribution systems.
Sub-clauses deleted.
TRF No. IEC60950_1A
N/A
Page 25 of 49
Report No.180488B
IEC 60950-1
Clause
Requirement + Test
Result – Remark
A
ANNEX A, TESTS FOR RESISTANCE TO HEAT AND FIRE
Verdict
N/A
PCB material V-0.
Sub-clauses deleted.
B
ANNEX B, MOTOR TESTS UNDER ABNORMAL CONDITIONS (see 4.7.2.2 and
5.3.2)
N/A
No motors. Sub-clauses deleted.
C
ANNEX C, TRANSFORMERS (see 1.5.4 and 5.3.3)
N/A
No transformers. Sub-clauses deleted.
D
ANNEX D, MEASURING INSTRUMENTS FOR TOUCH-CURRENT TESTS
(see 5.1.4)
N/A
D.1
Measuring instrument
N/A
D.2
Alternative measuring instrument
N/A
E
ANNEX E, TEMPERATURE RISE OF A WINDING (see 1.4.13)
N/A
F
ANNEX F, MEASUREMENT OF CLEARANCES AND CREEPAGE DISTANCES
(see 2.10 and Annex G)
N/A
G
ANNEX G, ALTERNATIVE METHOD FOR DETERMINING MINIMUM
CLEARANCES
N/A
See 2.10.1.3. Sub-clauses deleted.
H
ANNEX H, IONIZING RADIATION (see 4.3.13)
N/A
J
ANNEX J, TABLE OF ELECTROCHEMICAL POTENTIALS (see 2.6.5.6)
N/A
Metal(s) used ....................................................... :
K
ANNEX K, THERMAL CONTROLS (see 1.5.3 and 5.3.8)

N/A
No thermal controls. Sub-clauses deleted.
L
ANNEX L, NORMAL LOAD CONDITIONS FOR SOME TYPES OF ELECTRICAL
BUSINESS EQUIPMENT (see 1.2.2.1 and 4.5.2)
N/A
L.1
Typewriters
N/A
L.2
Adding machines and cash registers
N/A
L.3
Erasers
N/A
L.4
Pencil sharpeners
N/A
TRF No. IEC60950_1A
Page 26 of 49
Report No.180488B
IEC 60950-1
Clause
Requirement + Test
Result – Remark
Verdict
L.5
Duplicators and copy machines
N/A
L.6
Motor-operated files
N/A
L.7
Other business equipment
N/A
M
ANNEX M, CRITERIA FOR TELEPHONE RINGING SIGNALS (see 2.3.1)
N/A
No telephone ringing signals. Sub-clauses deleted.
N
ANNEX N, IMPULSE TEST GENERATORS (see 1.5.7.2, 1.5.7.3, 2.10.3.9, 6.2.2.1,
7.3.2, 7.4.3 and Clause G.5)
N/A
N.1
ITU-T impulse test generators
N/A
N.2
IEC 60065 impulse test generator
N/A
P
ANNEX P, NORMATIVE REFERENCES
Q
ANNEX Q, Voltage dependent resistors (VDRs) (see 1.5.9.1)

N/A
No VDRs used. Sub-clauses deleted.
R
ANNEX R, EXAMPLES OF REQUIREMENTS FOR QUALITY CONTROL
PROGRAMMES
N/A
R.1
Minimum separation distances for unpopulated
coated printed boards (see 2.10.6.2)
N/A
R.2
Reduced clearances (see 2.10.3)
N/A
S
ANNEX S, PROCEDURE FOR IMPULSE TESTING (see 6.2.2.3)
N/A
S.1
Test equipment
N/A
S.2
Test procedure
N/A
S.3
Examples of waveforms during impulse testing
N/A
T
ANNEX T, GUIDANCE ON PROTECTION AGAINST INGRESS OF WATER
(see 1.1.2)
N/A

U
ANNEX U, INSULATED WINDING WIRES FOR USE WITHOUT INTERLEAVED
INSULATION (see 2.10.5.4)
N/A

V
ANNEX V, AC POWER DISTRIBUTION SYSTEMS (see 1.6.1)
N/A
V.1
Introduction
N/A
V.2
TN power distribution systems
N/A
TRF No. IEC60950_1A
Page 27 of 49
Report No.180488B
IEC 60950-1
Clause
Requirement + Test
Result – Remark
Verdict
V.3
TT power distribution systems
N/A
V.4
IT power distribution systems
N/A
W
ANNEX W, SUMMATION OF TOUCH CURRENTS
N/A
No touch currents in this equipment. Sub-clauses deleted.
X
ANNEX X, MAXIMUM HEATING EFFECT IN TRANSFORMER TESTS (see clause
C.1)
N/A
X.1
Determination of maximum input current
N/A
X.2
Overload test procedure
N/A
Y
ANNEX Y, ULTRAVIOLET LIGHT CONDITIONING TEST (see 4.3.13.3)
N/A
Y.1
Test apparatus ..................................................... :
N/A
Y.2
Mounting of test samples ..................................... :
N/A
Y.3
Carbon-arc light-exposure apparatus ................... :
N/A
Y.4
Xenon-arc light exposure apparatus .................... :
N/A
Z
ANNEX Z, OVERVOLTAGE CATEGORIES (see 2.10.3.2 and Clause G.2)
N/A
AA
ANNEX AA, MANDREL TEST (see 2.10.5.8)
N/A
BB
ANNEX BB, CHANGES IN THE SECOND EDITION
CC
ANNEX CC, EVALUATION OF INTEGRATED CIRCUIT (IC) CURRENT LIMITERS
N/A
CC.1
Integrated circuit (IC) current limiters
N/A
CC.2
Test program 1
N/A
CC.3
Test program 2
N/A
DD
ANNEX DD, REQUIREMENTS FOR THE MOUNTING MEANS OF RACKMOUNTED EQUIPMENT
N/A
DD.1
General
N/A
DD.2
Mechanical strength test, variable N
N/A
DD.3
Mechanical strength test, 250 N, including end
stops
N/A
DD.4
Compliance
N/A
EE
ANNEX EE, HOUSEHOLD AND HOME/OFFICE DOCUMENT/MEDIA
SHREDDERS
N/A
TRF No. IEC60950_1A

The equipment is not for rack
mounting.
Page 28 of 49
Report No.180488B
IEC 60950-1
Clause
Requirement + Test
EE.1
General
N/A
EE.2
Markings and instructions
N/A
EE.3
Inadvertent reactivation
N/A
EE.4
Disconnection of power to hazardous moving parts
N/A
EE.5
Protection against hazardous moving parts
N/A
TRF No. IEC60950_1A
Result – Remark
Verdict
Page 29 of 49
Report No.180488B
IEC 60950-1
Clause
Requirement + Test
1.5.1
TABLE: List of critical components
Object/part No.
Manufacturer/
trademark
Result – Remark
Type/model
Verdict
P
Technical data
Standard
(Edition / year)
Mark(s) of
1
conformity )
General
PCB
AT&S
MX3
94V-0
UL94
UL (E67138)
Functional insulation
Basic insulation
Supplementary insulation
Reinforced insulation
1
) An asterisk indicates a mark which assures the agreed level of surveillance
Supplementary information:
1.6.2
U (V)
TABLE: Electrical data (in normal conditions)
I (A)
Irated (A)
P (W)
N/A
Fuse #
Ifuse (A)
Condition/status
Supplementary information:
2.5
TABLE: limited power sources
Circuit
Fault
Uoc (V)
Measured
Supplementary information:
TRF No. IEC60950_1A
N/A
Limit
Isc (A)
Measured
Limit
P (VA)
Measured
Limit
Fuse (A)
Value
Limit
Page 30 of 49
Report No.180488B
IEC 60950-1
Requirement + Test
2.10.3 and
2.10.4
TABLE: Working voltage measurements for clearance and creepage distances
Condition #
Clause
Result – Remark
TN-S, TN-C,
TN-S, TT
TN-CS, TT (not (corner earthed)
corner earthed)
Between
Figures V.1,
V.2, V.3, V.5
peak
peak
Rms
-
TN-C (middle
point earthed
IT (not corner
earthed)
IT (corner
earthed)
Figure V.4
Figure V.7
Figure V.8
Figures V.1, V.6
rms
Verdict
peak
rms
peak
rms
peak
Rms
`
Supplementary information:
2.10.3 and
2.10.4
TABLE: Clearance and creepage distance measurements
Clearance (cl) and creepage
distance (cr) at/of/between:
Upeak
(V)
Urms
(V)
Req. cl.
(mm)
N/A
Meas. cl.
(mm)
Req. cr.
(mm)
Meas. cr.
(mm)
Functional insulation:
Basic/supplementary insulation:
Reinforced insulation:
Supplementary information:
2.10.5
TABLE: Distance through insulation measurements
Distance through insulation (DTI) at/of:
Basic insulation:
Supplementary insulation:
Reinforced insulation:
Supplementary information:
TRF No. IEC60950_1A
Upeak
(V)
N/A
Urms
(V)
Test
voltage
(V)
Req. DTI
(mm)
DTI
(mm)
Page 31 of 49
Report No.180488B
IEC 60950-1
Clause
Requirement + Test
4.3.8
TABLE: Batteries
Result – Remark
Verdict
N/A
The tests of 4.3.8 are applicable only when appropriate battery
data is not available
No batteries.
N/A
Is it possible to install the battery in a reverse polarity position?
Non-rechargeable batteries
Discharging
Meas.
current
Manuf.
Specs.
Unintentional
charging
N/A
Rechargeable batteries
Charging
Meas.
current
Manuf.
Specs.
Discharging
Meas.
current
Manuf.
Specs.
Reversed
charging
Meas.
current
Manuf.
Specs.
Max.
current
during
normal
condition
Max.
current
during
fault
condition
Test results:
- Chemical leaks
Verdict
No batteries.
N/A
- Explosion of the battery
N/A
- Emission of flame or expulsion of molten metal
N/A
- Electric strength tests of equipment after completion of tests
N/A
Supplementary information:
TRF No. IEC60950_1A
Page 32 of 49
Report No.180488B
IEC 60950-1
Clause
Requirement + Test
Result – Remark
4.5
TABLE: Thermal requirements
Verdict
P
Supply voltage (V) ........................... :

5VDC

Ambient Tmin (°C) ............................. :
Ambient Tmax (°C) ............................ :
60
1)

Maximum measured temperature T of part/at::
Allowed
Tmax
(°C)
T (°C)
Top of MIX1
78,7
105
Top of IC28
80,2
105
Top of IC2
79,4
105
Top of cover
67,7
85
Supplementary information:
Temperature T of winding:
t1 (°C)
R1 (Ω)
t2 (°C)
R2 (Ω)
T (°C)
Allowed Insulation
class
Tmax (°C)
Supplementary information:
1)
Temperatures indicated are extrapolated to Tamb = 60 °C.
Worst case temperature of assemblies in horizontal and vertical are informed.
4.5.5
TABLE: Ball pressure test of thermoplastic parts
N/A
Allowed impression diameter (mm) ..................... : ≤ 2 mm
Part

Test temperature Impression diameter
(mm)
(°C)
Supplementary information:
4.7
TABLE: Resistance to fire
Part
PCB
Manufacturer of
material
AT&S
Supplementary information:
TRF No. IEC60950_1A
P
Type of material
MX3 LE
Thickness Flammability
(mm)
class
Various
94V-0
Evidence
UL
Page 33 of 49
Report No.180488B
IEC 60950-1
Clause
Requirement + Test
Result – Remark
5.1.6
TABLE: Touch current measurements (single phase equipment)
Verdict
N/A
Supply voltage (V) ........................................... :

Supply frequency (Hz) ..................................... :

From
L–N
L–L
L–L
L–N
L–N
L–L
L–L
TN-S,
TN-C,
TN-CS,
TT
TN-C,
TT
TN, TT
IT
IT
IT
IT
Measurement
limit
Not
Middle
Not
Not
Not
Corner
Corner
corner
point
corner corner
corner
earthed
earthed
earthed earthed earthed earthed
earthed
Fault
Figure 6 Figure 7 Figure 8 Figure 9 Figure 9
(mA)
Equipment
main
protective
earthing
terminal
(mA)
(mA)
(mA)
(mA)
Figure
10
Figure
10
(mA)
(mA)
(mA)
3,5 /
0,75 /
Earth
5 % of rated
current
None
Accessible Earth
parts and Neutral
circuits not
Line
connected
to
Line to
protective
earth
earth
Component
-
Supplementary information:
-
TRF No. IEC60950_1A
-
-
-
-
-
0,25
-
Page 34 of 49
Report No.180488B
IEC 60950-1
Clause
Requirement + Test
5.2
TABLE: Electric strength tests, impulse tests and voltage surge tests
Test voltage applied between:
Functional insulation:
Basic/supplementary insulation:
Reinforced insulation:
Supplementary information:
Functional insulation complies with 5.3.4 c).
TRF No. IEC60950_1A
Result – Remark
Verdict
N/A
Voltage shape Test voltage Breakdown
(AC, DC,
(V)
Yes / No
impulse, surge)
Page 35 of 49
Report No.180488B
IEC 60950-1
Clause
Requirement + Test
Result – Remark
5.3
TABLE: Fault condition tests
Verdict
P
Ambient temperature (°C) .................................... :
23,5

Power source for EUT: Manufacturer, model/type,
output rating ......................................................... :
+5VDC

Component
No.
Fault
Supply
voltage
(V)
Test
time
Fuse #
Fuse
current
(A)
Observation
D9
s-c
+5VDC
2min
-
-
No remarks.
C120
s-c
+5VDC
2min
-
-
The receiver shut off. It works
normal after the test.
Supplementary information:
TRF No. IEC60950_1A
Page 36 of 49
Report No.180488B
IEC 60950-1
Clause
Requirement + Test
Result – Remark
Verdict
ATTACHMENT TO TEST REPORT IEC 60950-1
EUROPEAN GROUP DIFFERENCES AND NATIONAL DIFFERENCES
Information technology equipment – Safety –
Part 1: General requirements
Differences according to ............... : EN 60950-1:2006/A11:2009/A1:2010
Attachment Form No. ..................... : EU_GD_IEC60950_1B
Attachment Originator ................... : SGS Fimko Ltd (edited by Nemko Oy 2010-07)
Master Attachment ......................... : Date (2010-04)
Copyright © 2010 IEC System for Conformity Testing and Certification of Electrical Equipment
(IECEE), Geneva, Switzerland. All rights reserved.
IEC 60950-1, GROUP DIFFERENCES (CENELEC common modifications EN)
Contents

Add the following annexes:
Annex ZA (normative)
Normative references to international publications
with their corresponding European publications
Annex ZB (normative)
Special national conditions
Annex ZC (informative)
A-deviations
General
Delete all the “country” notes in the reference
document according to the following list:
1.4.8
Note 2
1.5.7.1 Note
1.5.9.4 Note
2.2.3
Note
2.3.2
Note
2.3.4
Note 2
2.7.1
Note
2.10.5.13 Note 3
3.2.4
Note 3
4.3.6
Note 1 & 2
4.7.2.2 Note
5.1.7.1 Note 3 & 4
6
Note 2 & 5
6.1.2.2 Note
6.2.2.1 Note 2
7.1
Note 3
7.3
Note 1 & 2
Annex H Note 2
General
1.5.1
1.5.8
1.7.2.1
2.2.4
2.3.2.1
2.6.3.3
2.10.3.2
3.2.1.1
2.5.1
4.7
4.7.3.1
5.3.7
6.1.2.1
6.2.2
6.2.2.2
7.2
G.2.1
Note 2 & 3
Note 2
Note 4, 5 & 6
Note
Note 2
Note 2 & 3
Note 2
Note
Note 2
Note 4
Note 2
Note 1
Note 2
Note
Note
Note
Note 2
EN 60950-1 + A1:2010:
In IEC 60950-1:2005/A1 delete all the “country” notes according to the following list:
- 1.5.7.1:
Note
- 6.1.2.1:
Note 2
- 6.2.2.1:
Note 2
- EE.3: Note
TRF No. IEC60950_1A


Page 37 of 49
Report No.180488B
IEC 60950-1
Clause
Requirement + Test
Result – Remark
Verdict
1.1.1
EN 60950-1 + A1:2010:
Not a multimedia equipment.
N/A
The equipment is not a
portable sound system.
N/A
No headphones or earphones
provided.
N/A
Replace the text of NOTE 3 by the following:
NOTE 3
The requirements of EN 60065 may also
be used to meet safety requirements for multimedia
equipment. See IEC Guide 112, Guide on the safety of
multimedia equipment. For television sets EN 60065
applies.
1.2.3
EN 60950-1 + A1:2010:
Add the following definition:
1.2.3.Z1
PORTABLE SOUND SYSTEM
small battery powered audio equipment:
− whose prime purpose is to listen to recorded or
broadcasted sound; and
− that uses headphones or earphones that can be
worn in or on or around the ears; and
− that allows the user to walk around
NOTE
Examples are mini-disk or CD players; MP3
audio players or similar equipment.
1.3.Z1
Add the following subclause:
1.3.Z1 Exposure to excessive sound pressure
The apparatus shall be so designed and
constructed as to present no danger when used for
its intended purpose, either in normal operating
conditions or under fault conditions, particularly
providing protection against exposure to excessive
sound pressures from headphones or earphones.
NOTE Z1 A new method of measurement is described in
EN 50332-1, Sound system equipment:
Headphones and earphones associated with portable
audio equipment - Maximum sound pressure level
measurement methodology and limit considerations Part 1: General method for “one package equipment”,
and in EN 50332-2, Sound system equipment:
Headphones and earphones associated with portable
audio equipment - Maximum sound pressure level
measurement methodology and limit considerations Part 2: Guidelines to associate sets with headphones
coming from different manufacturers.
1.5.1
Add the following NOTE:
Considered.
P
NOTE Z1 The use of certain substances in electrical and
electronic equipment is restricted within the EU: see
Directive 2002/95/EC
1.7.2.1
Add the following NOTE:
NOTE Z1 In addition, the instructions shall include, as
far as applicable, a warning that excessive sound
pressure from earphones and headphones can cause
hearing loss
TRF No. IEC60950_1A
No headphones or earphones
provided
N/A
Page 38 of 49
Report No.180488B
IEC 60950-1
Clause
Requirement + Test
Result – Remark
1.7.2.1
EN 60950-1 + A1:2010:
No headphones or earphones
provided.
N/A
The equipment is DC
powered (SELV). No primary
circuits.
N/A
Delete NOTE Z1.
Verdict
Add the following paragraph at the end of the
subclause:
In addition, for a PORTABLE SOUND SYSTEM,
the instructions shall include a warning that
excessive sound pressure from earphones and
headphones can cause hearing loss.
2.7.1
Replace the subclause as follows:
Basic requirements
To protect against excessive current, short-circuits
and earth faults in PRIMARY CIRCUITS, protective
devices shall be included either as integral parts of
the equipment or as parts of the building
installation, subject to the following, a), b) and c):
a) except as detailed in b) and c), protective
devices necessary to comply with the requirements
of 5.3 shall be included as parts of the equipment;
b) for components in series with the mains input to
the equipment such as the supply cord, appliance
coupler, r.f.i. filter and switch, short-circuit and earth
fault protection may be provided by protective
devices in the building installation;
c) it is permitted for PLUGGABLE EQUIPMENT
TYPE B or PERMANENTLY CONNECTED
EQUIPMENT, to rely on dedicated overcurrent and
short-circuit protection in the building installation,
provided that the means of protection, e.g. fuses or
circuit breakers, is fully specified in the installation
instructions.
If reliance is placed on protection in the building
installation, the installation instructions shall so
state, except that for PLUGGABLE EQUIPMENT
TYPE A the building installation shall be regarded
as providing protection in accordance with the
rating of the wall socket outlet.
2.7.2
This subclause has been declared ‘void’.
Considered.
N/A
3.2.3
Delete the NOTE in Table 3A, and delete also in
this table the conduit sizes in parentheses.
Considered.
N/A
TRF No. IEC60950_1A
Page 39 of 49
Report No.180488B
IEC 60950-1
Clause
Requirement + Test
Result – Remark
Verdict
3.2.5.1
Replace
“60245 IEC 53” by “H05 RR-F”;
“60227 IEC 52” by “H03 VV-F or H03 VVH2-F”;
“60227 IEC 53” by “H05 VV-F or H05 VVH2-F2”.
Considered.
N/A
The equipment is class III.
N/A
Considered.
N/A
Considered.
N/A
The unit does not emit X-ray
radiation.
N/A
In Table 3B, replace the first four lines by the
following:
Up to and including 6
0,75
Over 6 up to and including 10
Over 10 up to and including 16
b
(0,75)
(1,0)
c
a
1,0
1,5
In the conditions applicable to Table 3B delete the
a
words “in some countries” in condition .
In NOTE 1, applicable to Table 3B, delete the
second sentence.
3.3.4
In Table 3D, delete the fourth line: conductor sizes
for 10 to 13 A, and replace with the following:
Over 10 up to and
including 16
1,5 to 2,5
1,5 to 4
Delete the fifth line: conductor sizes for 13 to 16 A.
4.3.13.6
Add the following NOTE:
NOTE Z1 Attention is drawn to 1999/519/EC: Council
Recommendation on the limitation of exposure of the
general public to electromagnetic fields 0 Hz to 300
GHz. Standards taking into account this
Recommendation which demonstrate compliance with
the applicable EU Directive are indicated in the OJEC.
4.3.13.6
EN 60950-1 + A1:2010:
Replace the existing NOTE by the following:
NOTE Z1 Attention is drawn to :
1999/519/EC: Council Recommendation on the limitation
of exposure of the general public to electromagnetic
fields 0 Hz to 300 GHz, and 2006/25/EC: Directive on
the minimum health and safety requirements regarding
the exposure of workers to risks arising from physical
agents (artificial optical radiation).
Standards taking into account mentioned
Recommendation and Directive which demonstrate
compliance with the applicable EU Directive are
indicated in the OJEC.
Annex H
Replace the last paragraph of this annex by:
At any point 10 cm from the surface of the
OPERATOR ACCESS AREA, the dose rate shall
not exceed 1 µSv/h (0,1 mR/h) (see NOTE).
Account is taken of the background level.
Replace the notes as follows:
NOTE These values appear in Directive 96/29/Euratom.
Delete NOTE 2.
TRF No. IEC60950_1A
Page 40 of 49
Report No.180488B
IEC 60950-1
Clause
Requirement + Test
Bibliography
Additional EN standards.

ZA
NORMATIVE REFERENCES TO INTERNATIONAL PUBLICATIONS WITH THEIR
CORRESPONDING EUROPEAN PUBLICATIONS

ZB
SPECIAL NATIONAL CONDITIONS
P
1.2.4.1
In Denmark, certain types of Class I appliances
(see 3.2.1.1) may be provided with a plug not
establishing earthing conditions when inserted into
Danish socket-outlets.
The equipment is class III.
N/A
1.2.13.14
In Norway and Sweden, for requirements see
1.7.2.1 and 7.3 of this annex.
The equipment is not
connected to a cable
distribution system.
N/A
1.5.7.1
In Finland, Norway and Sweden, resistors
bridging BASIC INSULATION in CLASS I
PLUGGABLE EQUIPMENT TYPE A must comply
with the requirements in 1.5.7.1. In addition when a
single resistor is used, the resistor must withstand
the resistor test in 1.5.7.2.
The equipment is not
pluggable equipment type A.
The equipment is class III.
N/A
1.5.8
In Norway, due to the IT power system used (see
annex V, Figure V.7), capacitors are required to be
rated for the applicable line-to-line voltage (230 V).
The equipment is class III and
DC powered (5V).
N/A
1.5.9.4
In Finland, Norway and Sweden, the third dashed No VDRs in the equipment.
sentence is applicable only to equipment as defined
in 6.1.2.2 of this annex.
1.7.2.1
In Finland, Norway and Sweden, CLASS I
PLUGGABLE EQUIPMENT TYPE A intended for
connection to other equipment or a network shall, if
safety relies on connection to protective earth or if
surge suppressors are connected between the
network terminals and accessible parts, have a
marking stating that the equipment must be
connected to an earthed mains socket-outlet.
The marking text in the applicable countries shall
be as follows:
In Finland: "Laite on liitettävä
suojamaadoituskoskettimilla varustettuun
pistorasiaan"
In Norway: “Apparatet må tilkoples jordet
stikkontakt”
In Sweden: “Apparaten skall anslutas till jordat
uttag”
TRF No. IEC60950_1A
Result – Remark
The equipment is not
pluggable equipment type A.
The equipment is class III.
Verdict
N/A
N/A
Page 41 of 49
Report No.180488B
IEC 60950-1
Clause
Requirement + Test
1.7.2.1
The equipment is not
In Norway and Sweden, the screen of the cable
connected to a cable
distribution system is normally not earthed at the
distribution system.
entrance of the building and there is normally no
equipotential bonding system within the building.
Therefore the protective earthing of the building
installation need to be isolated from the screen of a
cable distribution system.
It is however accepted to provide the insulation
external to the equipment by an adapter or an
interconnection cable with galvanic isolator, which
may be provided by e.g. a retailer.
The user manual shall then have the following or
similar information in Norwegian and Swedish
language respectively, depending on in what
country the equipment is intended to be used in:
“Equipment connected to the protective earthing of
the building installation through the mains
connection or through other equipment with a
connection to protective earthing – and to a cable
distribution system using coaxial cable, may in
some circumstances create a fire hazard.
Connection to a cable distribution system has
therefore to be provided through a device providing
electrical isolation below a certain frequency range
(galvanic isolator, see EN 60728-11).”
NOTE In Norway, due to regulation for installations of
cable distribution systems, and in Sweden, a galvanic
isolator shall provide electrical insulation below 5 MHz.
The insulation shall withstand a dielectric strength of 1,5
kV r.m.s., 50 Hz or 60 Hz, for 1 min.
Translation to Norwegian (the Swedish text will also
be accepted in Norway):
“Utstyr som er koplet til beskyttelsesjord via
nettplugg og/eller via annet jordtilkoplet utstyr – og
er tilkoplet et kabel-TV nett, kan forårsake
brannfare. For å unngå dette skal det ved tilkopling
av utstyret til kabel-TV nettet installeres en
galvanisk isolator mellom utstyret og kabel- TV
nettet.”
Translation to Swedish:
”Utrustning som är kopplad till skyddsjord via jordat
vägguttag och/eller via annan utrustning och
samtidigt är kopplad till kabel-TV nät kan i vissa fall
medfőra risk főr brand. Főr att undvika detta skall
vid anslutning av utrustningen till kabel-TV nät
galvanisk isolator finnas mellan utrustningen och
kabel-TV nätet.”
TRF No. IEC60950_1A
Result – Remark
Verdict
N/A
Page 42 of 49
Report No.180488B
IEC 60950-1
Clause
Requirement + Test
Result – Remark
1.7.5
In Denmark, socket-outlets for providing power to
other equipment shall be in accordance with the
Heavy Current Regulations, Section 107-2-D1,
Standard Sheet DK 1-3a, DK 1-5a or DK 1-7a,
when used on Class I equipment. For
STATIONARY EQUIPMENT the socket-outlet shall
be in accordance with Standard Sheet DK 1-1b or
DK 1-5a. For CLASS II EQUIPMENT the socket
outlet shall be in accordance with Standard Sheet
DKA 1-4a.
There are no socket outlets
providing power to other
equipment.
N/A
2.2.4
In Norway, for requirements see 1.7.2.1, 6.1.2.1
and 6.1.2.2 of this annex.
No TNV circuits in the
equipment.
N/A
2.3.2
In Finland, Norway and Sweden there are
additional requirements for the insulation. See
6.1.2.1 and 6.1.2.2 of this annex.
No TNV circuits in the
equipment.
N/A
2.3.4
In Norway, for requirements see 1.7.2.1, 6.1.2.1
and 6.1.2.2 of this annex.
No TNV circuits in the
equipment.
N/A
2.6.3.3
In the United Kingdom, the current rating of the
circuit shall be taken as 13 A, not 16 A.
The equipment is class III and
not for connection to a.c.
mains supply.
N/A
2.7.1
In the United Kingdom, to protect against
excessive currents and short-circuits in the
PRIMARY CIRCUIT of DIRECT PLUG-IN
EQUIPMENT, tests according to 5.3 shall be
conducted, using an external protective device
rated 30 A or 32 A. If these tests fail, suitable
protective devices shall be included as integral
parts of the DIRECT PLUG-IN EQUIPMENT, so
that the requirements of 5.3 are met.
The equipment is not a direct
plug-in equipment.
N/A
2.10.5.13
In Finland, Norway and Sweden, there are
additional requirements for the insulation, see
6.1.2.1 and 6.1.2.2 of this annex.
No TNV circuits in the
equipment.
N/A
TRF No. IEC60950_1A
Verdict
Page 43 of 49
Report No.180488B
IEC 60950-1
Clause
Requirement + Test
Result – Remark
3.2.1.1
In Switzerland, supply cords of equipment having
a RATED CURRENT not exceeding 10 A shall be
provided with a plug complying with SEV 1011 or
IEC 60884-1 and one of the following dimension
sheets:
The equipment is class III and
not connected to a mains
supply.
N/A
The equipment is class III and
not connected to a mains
supply.
N/A
SEV 6532-2.1991
Plug Type 15
3P+N+PE
250/400 V, 10 A
SEV 6533-2.1991
Plug Type 11
L+N
250 V, 10 A
SEV 6534-2.1991
Plug Type 12
L+N+PE
250 V, 10 A
Verdict
In general, EN 60309 applies for plugs for currents
exceeding 10 A. However, a 16 A plug and socketoutlet system is being introduced in Switzerland,
the plugs of which are according to the following
dimension sheets, published in February 1998:
3.2.1.1
SEV 5932-2.1998
Plug Type 25
3L+N+PE
230/400 V, 16 A
SEV 5933-2.1998
Plug Type 21
L+N
250 V, 16 A
SEV 5934-2.1998
Plug Type 23
L+N+PE
250 V, 16 A
In Denmark, supply cords of single-phase
equipment having a rated current not exceeding13
A shall be provided with a plug according to the
Heavy Current Regulations, Section 107-2-D1.
CLASS I EQUIPMENT provided with socket-outlets
with earth contacts or which are intended to be
used in locations where protection against indirect
contact is required according to the wiring rules
shall be provided with a plug in accordance with
standard sheet DK 2-1a or DK 2-5a.
If poly-phase equipment and single-phase
equipment having a RATED CURRENT exceeding
13 A is provided with a supply cord with a plug, this
plug shall be in accordance with the Heavy Current
Regulations, Section 107-2-D1 or EN 60309-2.
TRF No. IEC60950_1A
Page 44 of 49
Report No.180488B
IEC 60950-1
Clause
Requirement + Test
Result – Remark
3.2.1.1
The equipment is class III and
In Spain, supply cords of single-phase equipment
having a rated current not exceeding 10 A shall be not connected to a mains
provided with a plug according to UNE 20315:1994. supply.
Verdict
N/A
Supply cords of single-phase equipment having a
rated current not exceeding 2,5 A shall be provided
with a plug according to UNE-EN 50075:1993.
CLASS I EQUIPMENT provided with socket-outlets
with earth contacts or which are intended to be
used in locations where protection against indirect
contact is required according to the wiring rules,
shall be provided with a plug in accordance with
standard UNE 20315:1994.
If poly-phase equipment is provided with a supply
cord with a plug, this plug shall be in accordance
with UNE-EN 60309-2.
3.2.1.1
The equipment is class III and
not connected to a mains
supply.
N/A
3.2.1.1
The equipment is class III and
In Ireland, apparatus which is fitted with a flexible
cable or cord and is designed to be connected to a not connected to a mains
supply.
mains socket conforming to I.S. 411 by means of
that flexible cable or cord and plug, shall be fitted
with a 13 A plug in accordance with Statutory
Instrument 525:1997 - National Standards Authority
of Ireland (section 28) (13 A Plugs and Conversion
Adaptors for Domestic Use) Regulations 1997.
N/A
3.2.4
In Switzerland, for requirements see 3.2.1.1 of this The equipment is class III and
not connected to a mains
annex.
supply.
N/A
3.2.5.1
In the United Kingdom, a power supply cord with
conductor of 1,25 mm2 is allowed for equipment
with a rated current over 10 A and up to and
including 13 A.
The equipment is class III and
not connected to a mains
supply.
N/A
3.3.4
In the United Kingdom, the range of conductor
sizes of flexible cords to be accepted by terminals
for equipment with a RATED CURRENT of over 10
A up to and including 13 A is:
The equipment is class III.
Terminals are not used for
connection of DC to the
equipment.
N/A
In the United Kingdom, apparatus which is fitted
with a flexible cable or cord and is designed to be
connected to a mains socket conforming to BS
1363 by means of that flexible cable or cord and
plug, shall be fitted with a ‘standard plug’ in
accordance with Statutory Instrument 1768:1994 The Plugs and Sockets etc. (Safety) Regulations
1994, unless exempted by those regulations.
NOTE ‘Standard plug’ is defined in SI 1768:1994 and
essentially means an approved plug conforming to BS
1363 or an approved conversion plug.
2
2
• 1,25 mm to 1,5 mm nominal cross-sectional
area.
TRF No. IEC60950_1A
Page 45 of 49
Report No.180488B
IEC 60950-1
Clause
Requirement + Test
Result – Remark
4.3.6
In the United Kingdom, the torque test is
performed using a socket outlet complying with BS
1363 part 1:1995, including Amendment 1:1997
and Amendment 2:2003 and the plug part of
DIRECT PLUG-IN EQUIPMENT shall be assessed
to BS 1363: Part 1, 12.1, 12.2, 12.3, 12.9, 12.11,
12.12, 12.13, 12.16 and 12.17, except that the test
of 12.17 is performed at not less than 125 °C.
Where the metal earth pin is replaced by an
Insulated Shutter Opening Device (ISOD), the
requirements of clauses 22.2 and 23 also apply.
The equipment is not a direct
plug-in equipment.
N/A
4.3.6
The equipment is not a direct
In Ireland, DIRECT PLUG-IN EQUIPMENT is
plug-in equipment.
known as plug similar devices. Such devices shall
comply with Statutory Instrument 526:1997 National Standards Authority of Ireland (Section 28)
(Electrical plugs, plug similar devices and sockets
for domestic use) Regulations, 1997.
N/A
5.1.7.1
The equipment is class III and
In Finland, Norway and Sweden TOUCH
CURRENT measurement results exceeding 3,5 mA contains no TNV circuits.
r.m.s. are permitted only for the following
equipment:
N/A
• STATIONARY PLUGGABLE EQUIPMENT TYPE
A that
○ is intended to be used in a RESTRICTED
ACCESS LOCATION where equipotential
bonding has been applied, for example, in a
telecommunication centre; and
○ has provision for a permanently connected
PROTECTIVE EARTHING CONDUCTOR; and
○ is provided with instructions for the installation
of that conductor by a SERVICE PERSON;
• STATIONARY PLUGGABLE EQUIPMENT TYPE
B;
• STATIONARY PERMANENTLY CONNECTED
EQUIPMENT.
TRF No. IEC60950_1A
Verdict
Page 46 of 49
Report No.180488B
IEC 60950-1
Clause
Requirement + Test
6.1.2.1
In Finland, Norway and Sweden, add the following No TNV circuits.
text between the first and second paragraph of the
compliance clause:
If this insulation is solid, including insulation forming
part of a component, it shall at least consist of
either
- two layers of thin sheet material, each of which
shall pass the electric strength test below, or
- one layer having a distance through insulation of
at least 0,4 mm, which shall pass the electric
strength test below.
If this insulation forms part of a semiconductor
component (e.g. an optocoupler), there is no
distance through insulation requirement for the
insulation consisting of an insulating compound
completely filling the casing, so that CLEARANCES
and CREEPAGE DISTANCES do not exist, if the
component passes the electric strength test in
accordance with the compliance clause below and
in addition
- passes the tests and inspection criteria of 2.10.11
with an electric strength test of 1,5 kV multiplied
by 1,6 (the electric strength test of 2.10.10 shall
be performed using 1,5 kV), and
- is subject to ROUTINE TESTING for electric
strength during manufacturing, using a test
voltage of 1,5 kV.
It is permitted to bridge this insulation with a
capacitor complying with EN 132400:1994,
subclass Y2.
A capacitor classified Y3 according to EN
132400:1994, may bridge this insulation under the
following conditions:
- the insulation requirements are satisfied by
having a capacitor classified Y3 as defined by
EN 132400, which in addition to the Y3 testing, is
tested with an impulse test of 2,5 kV defined in
EN 60950-1:2006, 6.2.2.1;
- the additional testing shall be performed on all
the test specimens as described in EN 132400;
- the impulse test of 2,5 kV is to be performed
before the endurance test in EN 132400, in the
sequence of tests as described in EN 132400.
TRF No. IEC60950_1A
Result – Remark
Verdict
N/A
Page 47 of 49
Report No.180488B
IEC 60950-1
Clause
Requirement + Test
Result – Remark
Verdict
6.1.2.1
EN 60950-1 + A1:2010:
No TNV circuits.
N/A
In Finland, Norway and Sweden, add the following
text between the first and second paragraph of the
compliance clause:
If this insulation is solid, including insulation forming
part of a component, it shall at least consist of
either
- two layers of thin sheet material, each of which
shall pass the electric strength test below, or
- one layer having a distance through insulation of
at least 0,4 mm, which shall pass the electric
strength test below.
Alternatively for components, there is no distance
through insulation requirement for the insulation
consisting of an insulating compound completely
filling the casing, so that CLEARANCES and
CREEPAGE DISTANCES do not exist, if the
component passes the electric strength test in
accordance with the compliance clause below and
in addition
- passes the tests and inspection criteria of
2.10.11 with an electric strength test of 1,5 kV
multiplied by 1,6 (the electric strength test of
2.10.10 shall be performed using 1,5 kV), and
- is subject to ROUTINE TESTING for electric
strength during manufacturing, using a test voltage
of 1,5 kV.
It is permitted to bridge this insulation with an
optocoupler complying with 2.10.5.4 b).
It is permitted to bridge this insulation with a
capacitor complying with EN 60384-14:2005,
subclass Y2.
A capacitor classified Y3 according to EN 6038414:2005, may bridge this insulation under the
following conditions:
- the insulation requirements are satisfied by
having a capacitor classified Y3 as defined by EN
60384-14, which in addition to the Y3 testing, is
tested with an impulse test of 2,5 kV defined in EN
60950-1:2006, 6.2.2.1;
- the additional testing shall be performed on all
the test specimens as described in EN 60384-14;
- the impulse test of 2,5 kV is to be performed
before the endurance test in EN 60384-14, in the
sequence of tests as described in EN 60384-14.
TRF No. IEC60950_1A
Page 48 of 49
Report No.180488B
IEC 60950-1
Clause
Requirement + Test
Result – Remark
Verdict
6.1.2.2
No TNV circuits.
In Finland, Norway and Sweden, the exclusions
are applicable for PERMANENTLY CONNECTED
EQUIPMENT, PLUGGABLE EQUIPMENT TYPE B
and equipment intended to be used in a
RESTRICTED ACCESS LOCATION where
equipotential bonding has been applied, e.g. in a
telecommunication centre, and which has provision
for a permanently connected PROTECTIVE
EARTHING CONDUCTOR and is provided with
instructions for the installation of that conductor by
a SERVICE PERSON.
N/A
7.2
In Finland, Norway and Sweden, for requirements Not connected to cable
distribution systems.
see 6.1.2.1 and 6.1.2.2 of this annex.
N/A
The term TELECOMMUNICATION NETWORK in
6.1.2 being replaced by the term CABLE
DISTRIBUTION SYSTEM.
7.3
In Norway and Sweden, for requirements see
1.2.13.14 and 1.7.2.1 of this annex.
Not connected to cable
distribution systems.
N/A
7.3
In Norway, for installation conditions see EN
60728-11:2005.
Not connected to cable
distribution systems.
N/A
ZC
A-DEVIATIONS (informative)
1.5.1
Switzerland (Ordinance on environmentally
hazardous substances SR 814.081, Annex 1.7,
Mercury - Annex 1.7 of SR 814.81 applies for
mercury.)
P
There are no components
containing mercury in the
equipment.
P
Add the following:
NOTE In Switzerland, switches containing mercury such
as thermostats, relays and level controllers are not
allowed.
1.7.2.1
Must be considered before
Germany (Gesetz über technische Arbeitsmittel
marketing in Germany.
und Verbraucherprodukte (Geräte- und
Produktsicherheitsgesetz – GPSG) [Law on
technical labour equipment and consumer
products], of 6th January 2004, Section 2, Article 4,
Clause (4), Item 2).
−
If for the assurance of safety and health certain
rules during use, amending or maintenance of a
technical labour equipment or readymade
consumer product are to be followed, a manual in
German language has to be delivered when placing
the product on the market.
Of this requirement, rules for use even only by
SERVICE PERSONS are not exempted.
1.7.13
Switzerland (Ordinance on chemical hazardous
risk reduction SR 814.81, Annex 2.15 Batteries)
Annex 2.15 of SR 814.81 applies for batteries.
TRF No. IEC60950_1A
No batteries in the equipment.
N/A
Page 49 of 49
Report No.180488B
IEC 60950-1
Clause
Requirement + Test
Result – Remark
Verdict
List of measurement and test equipment:
Inv.
no.
Equipment
Manufacturer /
model / type
Range and accuracy based
on calibration data
Used
682
Multimeter
Fluke 289 (true rms)
VDC ± 0,1 %
VAC (20 Hz – 10 kHz) ± 1 %
VAC (10 kHz – 100 kHz) ± 5 %
ADC ± 0,1 %
AAC ± 0,5 %
R ± 0,5 %
f ± 0,1 %
x
600
Datalogger
Datalogger Agilent
34970A
-100 °C – 1200 °C (± 1 °C)
609
Scale
Precisa XT 6200D
0 – 6 kg (0,1 g), ± 0,1 g
TRF No. IEC60950_1A
x
x
- Page 1 of 13 -
Technical Annex
Report No. 180488B
- Page 2 of 13 -
Technical Annex
Report No. 180488B
- Page 3 of 13 -
Technical Annex
Report No. 180488B
- Page 4 of 13 -
Technical Annex
Report No. 180488B
- Page 5 of 13 -
Technical Annex
Report No. 180488B
- Page 6 of 13 -
Technical Annex
Report No. 180488B
- Page 7 of 13 -
Technical Annex
Report No. 180488B
- Page 8 of 13 -
Technical Annex
Report No. 180488B
- Page 9 of 13 -
Technical Annex
Report No. 180488B
- Page 10 of 13 -
Technical Annex
Report No. 180488B
- Page 11 of 13 -
Technical Annex
Report No. 180488B
- Page 12 of 13 -
Technical Annex
Report No. 180488B
BOTTOM OF LAYOUT:
- Page 13 of 13 -
Technical Annex
Report No. 180488B
TOP OF LAYOUT:
- Page 1 of 5 -
Photographic
documentation
Report No. 180488B
TOP OF RECEIVER
BOTTOM OF RECEIVER
- Page 2 of 5 -
Photographic
documentation
Report No. 180488B
TESTED WITH THIS UNIT
TOP OF CONSTRUCTION
- Page 3 of 5 -
Photographic
documentation
Report No. 180488B
BOTTOM OF CONSTRUCTION
DC CONNECTOR
- Page 4 of 5 -
Photographic
documentation
Report No. 180488B
TOP OF RECEIVER
- Page 5 of 5 -
Photographic
documentation
Report No. 180488B
BOTTOM OF RECEIVER
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertisement