Haes AlarmSense PLUS ASP-R-12 repeater panel Installation, Commissioning & Operating Manual
Below you will find brief information for repeater panel AlarmSense PLUS ASP-R-12. The AlarmSense PLUS ASP-R-12 is a 12 zone fully functional/passive repeater panel that supports up to 8 repeaters. The repeater panels are designed to be wired in a fault tolerant (fail safe) loop configuration, from Comms A +/- to Comms B +/- on the next repeater panel and so on until returning to Comms B +/- on the main panel again.
Advertisement
Advertisement
REPEATER PANEL
12 ZONE FULLY FUNCTIONAL/PASSIVE REPEATER PANEL
Installation, Commissioning &
Operating Manual
Approved Document UI-ASP-R-01 Issue 1.0
Haes Systems Ltd, Columbia House, Packet Boat Lane, Cowley Peachey, Uxbridge, UB8 2JP
Model Number
AlarmSense PLUS 12 zone repeater panel ASP-R-12
European Standard EN54-2 : 1997 + A1 : 2006
Control and indicating equipment for fi re detection and fi re alarm systems for buildings.
European Standard EN54-4 : 1997 + A1 : 2002 + A2 : 2006
Power supply equipment for fi re detection and fi re alarm systems for buildings.
IMPORTANT NOTE
PLEASE READ THIS MANUAL BEFORE HANDLING THE EQUIPMENT AND
OBSERVE ALL ADVICE GIVEN IN IT
THIS PARTICULARLY APPLIES TO THE PRECAUTIONS NECESSARY TO AVOID
E.S.D
!
IMPORTANT SAFETY NOTES
ATTENTION
ABOUT THIS PANEL
PRODUCT OVERVIEW
CABINET DETAILS
CIRCUIT BOARDS
MAIN PCB TERMINALS
COMMS PCB TERMINALS
TECHNICAL SPECIFICATION
POWER SUPPLY MODULE
INSTALLATION
SAFETY
ESD PRECAUTIONS
GENERAL
MOUNTING THE CABINET
MAINS CONNECTIONS
CONNECTING THE BATTERIES
CABLING
SETUP & PROGRAMMING
INSTALL COMMS PCB
SET NUMBER OF REPEATER PANELS
REPEATER PANEL ADDRESSING
PROGRAMMING REPEATER PANELS
OPERATING
PANEL CONTROLS & INDICATIONS
DISABLE MODE
TEST MODE
CONTENTS
8
8
9
9
9
10
11
12
14
14
16
16
17
18
18
20
21
Page
2
5
5
6
7
2
3
4
ASP-R Installation, Commissioning & Operating Manual
1
Approved Document Ref: UI-ASP-R-01 Issue 1.0
ABOUT THIS PANEL
PRODUCT OVERVIEW
Quiesecent and alarm current details for standby battery calculations
ASP-R-12 repeater panel
Standby Current
63mA
Alarm Current
85mA
ASP-R Installation, Commissioning & Operating Manual
2
Approved Document Ref: UI-ASP-R-01 Issue 1.0
CABINET
ABOUT THIS PANEL
57mm
80mm
260mm
308mm
250mm
300mm
ASP-R Installation, Commissioning & Operating Manual
3
Approved Document Ref: UI-ASP-R-01 Issue 1.0
ABOUT THIS PANEL
CIRCUIT BOARDS
AlarmSense PLUS repeater panels comprise of three circuit boards
TPCA01-R - Master PCB
PSU
@ + -
28V 0V
+
-
FIRE FAULT
C NC NO C NC NO
FR FLT CC PUL
-OP -OP -IP -IP
SNDR1 SNDR2 ZONE1 ZONE2 ZONE3 ZONE4
+ + + + + + -
TPCA05 - Comms PCB (with V3.0 software)
COMS A COMS B 28
+ -
+ -
V+
1
SW -ve OUTPUTS
2 3 4 5 6
ON
1 2 3 4
ADDRESS
+ -
BATTERY
• Piggy backs on Main PCB
• 6 programmable switch -ve outputs
TPCA03 - LED Display & Controls PCB
RESOUND SILENCE RESET
1 2 3 4
ENTER
ASP-R Installation, Commissioning & Operating Manual
4
Approved Document Ref: UI-ASP-R-01 Issue 1.0
ABOUT THIS PANEL
MAIN PCB TERMINALS
Switched -ve inputs
Switched -ve outputs
Max load 40mA
PSU
@ + -
28V 0V
+
-
FIRE FAULT
C NC NO C NC NO
FR FLT CC PUL
-OP -OP -IP -IP
SNDR1 SNDR2
+ -
ZONE1 ZONE2 ZONE3 ZONE4
+ + + + + -
COMMS PCB TERMINALS
+ -
BATTERY
Relay Coil
COMS A COMS B
+ -
+ -
28
V+ 1
SW -ve OUTPUTS
2 3 4 5 6
ON
1 2 3 4
ADDRESS
ASP-R Installation, Commissioning & Operating Manual
5
Approved Document Ref: UI-ASP-R-01 Issue 1.0
ABOUT THIS PANEL
TECHNICAL SPECIFICATION
Electrical Specifi cation Inputs & Outputs - TPCA01-R Main PCB
Terminal capacity 0.5mm
2
to 2.5mm
2
solid or stranded wire.
PSU @ output
PSU Input + -
Inputs; CC, PUL
Power supply voltage control line.
28vdc supply input. Diode protected for reversal and independent short circuit.
Max current 3 amps.
Switched -ve inputs, connect to 0v to trigger. Max input voltage = 28vdc. Non latching, max resistance 100R.
For temperature compensation control.
Max input current 3 amps. Input voltage
22vdc to 32vdc.
Protected via 10K Ohm impedance, 3v6 zener diode.
Electrical Specifi cation Inputs & Outputs - TPCA05 comms PCB
Comms A - B RS485 Repeater Comms, fused @ 20mA
28v Supply output Fused @ 500mA
Programmable outputs 1 - 6 Switched -ve outputs Overload voltage protected to 52vdc
Current limited 680R
Max load = 40mA
General Specifi cation
Enclosure
Cabling
Temperature range
Steel IP30. Epoxy powder coated Interpon Radon, silver grey
The use of fi re resistant screened cable, is recommended, FireBurn,
FP200 or equivalent. Minimum size 1mm
2
. Max cable length 1Km
Non fi re resistant cable can be used, BELDEN 9271 or BELDEN 9860.
Maximum cable length 1.2Km
-5 deg C to +40 deg C max RH 95%
ASP-R Installation, Commissioning & Operating Manual
6
Approved Document Ref: UI-ASP-R-01 Issue 1.0
ABOUT THIS PANEL
POWER SUPPLY MODULE
Power Supply Specifi cation
Mains supply
Mains supply fuse
Internal power supply rating
230vac +10% / -15% 50Hz max current
1A
2 Amp (T2A 250V) Not accessible for servicing. Internal to switch mode power unit
1.5 Amps total including battery charging Maximum load shared between outputs
= 900mA
ImaxA = 575mA ImaxB not specifi ed Maximum continuous load for battery standby (ImaxA)
Minimum current drawn by repeater panel
Maximum ripple
Min/max battery size and type
Battery charging voltage
Battery charging output current
I min = 63mA
250 millivolts
2 x 3.2Ahr 12volt VRLA
Use Yuasa NP range batteries
Supply and charger fault monitored
Other equivalent batteries may be used but have not been tested for the purposes of EN54 approval.
Temperature compensated
Battery high impedance fault (Batt Hi Z)
Max current drawn from batteries
27.3 vdc nominal at 20 deg C
1.5A PSU 630mA
Current limited 10 Ohms
Resistance > 1 Ohm
1.5 Amps with main power source disconnected. Battery fuse 3A LBC
20mm.
1 hour reporting time
ASP-R Installation, Commissioning & Operating Manual
7
Approved Document Ref: UI-ASP-R-01 Issue 1.0
INSTALLATION
SAFETY
(i) BS 7671 (IEE wiring regulations for electrical installations)
(ii) Codes of Practice
(iii) Statutory requirements
(iv) Any instructions specifi cally advised by the manufacturer
!
This equipment must only be installed and maintained by a suitably skilled and technically competent person.
THIS IS A PIECE OF CLASS 1 EQUIPMENT AND MUST BE EARTHED
Equipment Guarantee
This equipment is not guaranteed unless the complete system is installed and commissioned in accordance with the laid down national standards by an approved and competent person or organisation.
This product has been manufactured in conformance with the requirements of all applicable EU Council
Directives
ASP-R Installation, Commissioning & Operating Manual
8
Approved Document Ref: UI-ASP-R-01 Issue 1.0
INSTALLATION
ESD PRECAUTION
GENERAL
segregated away from mains voltage.
• Any junction boxes used should be clearly labelled FIRE ALARM.
• Any ancillary devices, e.g. door retaining magnets, must be powered from a separate power source.
• Any coils or solenoids used in the system must be suppressed, to avoid damage to the control equipment.
MOUNTING THE CABINET
Before mounting the cabinet remove the main PCB.
Remove the power supply module connecting wires from the main PCB, taking care to note where to reconnect them. The main PCB can then be carefully pulled off it’s mounting clips.
Secure the cabinet to the wall using the four indented holes in the back box. Ensure the box is mounted level and in a convenient location where it may be easily operated and serviced.
External cables should be glanded via preformed knockouts at the top and rear of the cabinet. Remove any knockouts and ensure the cabinet is clear of swarf etc prior to refi tting the PCB. Always ensure that if a knockout is removed, the hole is fi lled with a good quality cable gland. Any unused knockouts must be securely blanked off.
Knockouts should be removed with a sharp tap at the rim of the knockout using a fl at 6mm broad bladed screwdriver.
Use of excessive force will damage the enclosure around the knockout.
ASP-R Installation, Commissioning & Operating Manual
9
Approved Document Ref: UI-ASP-R-01 Issue 1.0
INSTALLATION
Typical panel layout
Incoming mains wiring
Comms loop wiring
PSU
@ + -
28V 0V
+ C
FIRE
NC NO C
FAULT
NC NO
FR FLT CC PUL
-OP -OP -IP -IP
SNDR1
+ -
SNDR2
+ -
ZONE1
+ -
ZONE2
+ -
ZONE3
+ -
ZONE4
+ -
COMS A
+ -
COMS B
+ -
28
V+ 1
SW -ve OUTPUTS
2 3 4 5 6
ON
1 2 3 4
ADDRESS
+ -
BATTERY
12V 3.2Ah VRLA BATTERY
12V 3.2Ah VRLA BATTERY
Drawing shows typical internal layout of a repeater panel with two 3.2Ah, 12v batteries fi tted
MAINS CONNECTIONS
Do not connect the mains supply to the panel until you are fully conversant with the layout and features of the equipment.
A rating plate is attached to the power supply module describing the nature of the supply permitted.
The incoming mains supply should be brought into the panel via one of the knockouts provided.
A suitable cable gland must be used to secure the outer sheath of the cable used. The earth must fi rst be connected to the primary earth stud (peg) marked with a symbol, using the ring crimp provided.
Suffi cient earth lead should be left to allow Live and Neutral connections to be accidentally pulled from the terminal block while leaving the earth connection intact.
ASP-R Installation, Commissioning & Operating Manual Approved Document Ref: UI-ASP-R-01 Issue 1.0
10
INSTALLATION
CONNECTING THE BATTERIES
Batteries of even very small capacity are capable of delivering very high currents which can cause fi re or injury, therefore battery connections should be done with caution.
The panel is supplied with battery leads already connected to the battery terminals on the main PCB.
These leads are coloured red for +ve and black for -ve.
2 x 12v batteries should be connected in series using the white jumper lead provided. See diagram.
ON
1 2 3
+ -
BATTERY
To optimise the service life of the batteries, the battery charger output voltage varies with temperature.
-ve +ve
N.B.
In the event of mains failure, the battery charger circuit will protect the batteries from full discharge by disconnecting them when they reach below
19v. When the mains supply is restored the batteries will be automatically reconnected.
12v SLA Battery 12v SLA Battery
NOTE:
If the mains is connected before the batteries, the panel will show a Power Supply fault for up to 1 minute until the monitoring cylce has fi nished polling. This is normal. If the fault doesn’t clear after 1 minute, check connections.
BATTERY CHARGING VOLTAGE CHECKS
The battery charging voltage is factory calibrated to 27.3vdc +/- 0.2v @ 20 o
C. This should not normally require adjustment. Where battery problems are experienced, the following information should be considered.
a) If a battery is disconnected from the charger, no voltage will appear on the output leads or terminals, due to intelligent battery controls.
b) Check the power supply voltage at the 28v & 0v supply output terminals. With the batteries disconnected the voltage should be 27.6vdc +/- 0.2v @ between 11 o
C - 40 o
C.
c) To test the batteries, turn off the mains and see if the system will run on the batteries. Check the battery voltage, should be 26.8v for a good battery or 22v for a fl at battery.
d) The power supply voltage can be adjusted using the potentiometer on the power supply module
(see page 7), checking at the 28v & 0v output terminals with a calibrated volt meter. Batteries should be disconnected. Carefully adjust the voltage to 27.6vdc +/- 0.2v. When completed, re-connect the batteries.
e) When the panel is re-charging a low battery, it should be possible to see the voltage across the batteries increase gradually. If this is not occurring, the batteries or the panel may be faulty.
ASP-R Installation, Commissioning & Operating Manual
11
Approved Document Ref: UI-ASP-R-01 Issue 1.0
INSTALLATION
CABLING
The repeater panels are designed to be wired in a fault tolerant (fail safe) loop confi guration, from Comms
A +/- to Comms B +/- on the next repeater panel and so on until returning to Comms B +/- on the main panel again (see diagram). This enables repeater panels to still work if there is a break in the cables. Up to 1Km of cable can be used between each repeater. 120R terminating resistors can be used to reduce interference between each leg of the loop.
Any suitable screened cable can be used or fi re resistant cable, ‘NoBurn’, FP200 etc.
If replacing an older system where the existing cabling cannot be confi gured in a loop as shown, it is possible to re-programme the panel back to legacy, radial circuit comms monitoring. This then allows any topology of comms cabling to be utilised.
To change the repeater comms monitoring type see over (page 13).
All repeater programming is done at the main control panel with Level 3 programming mode active, see main control panel instruction manual.
Fault Tolerant Loop Wiring
COMS A COMS B 28
+ + V+ 1
SW -ve OUTPUTS
2 3 4 5 6
ON
1 2 3 4
ADDRESS
Main Panel
COMS A COMS B 28
+ + V+ 1
SW -ve OUTPUTS
2 3 4 5 6
ON
1 2 3 4
ADDRESS
Repeater/Network Panel 1
COMS A COMS B 28
+ + V+ 1
SW -ve OUTPUTS
2 3 4 5 6
ON
1 2 3 4
ADDRESS
Repeater/Network Panel 2
ASP-R Installation, Commissioning & Operating Manual
12
Approved Document Ref: UI-ASP-R-01 Issue 1.0
INSTALLATION
To change the Comms monitoring type at the main control panel use:
2 1 2 3
Panel Wide Settings
RESOUND
There are 6 general, panel wide, settings available.
Enter the above code and press the ENTER button. The 6 programmable options are represented by fi re zone LEDs 1 - 6, Option 6 being the,
‘change repeater comms monitoring type’ setting.
1
Disable
Mode
2
Test
Mode
SILENCE
3
Mute
Buzzer
4
Test
Lamps
RESET
ENTER
Use button 1 to move to option 6
RESOUND SILENCE RESET
1
Disable
Mode
2
Test
Mode
3 4
Mute
Buzzer
Test
Lamps
ENTER
4
5
2
3
Fire LED Programming Option
1 Change / remove keypad access code
Set number of repeater panels on system
Set output delay time (1 - 10 minutes)
6
Turn off battery monitoring
Set up internal PCB confi guration (add extension zone card or repeater comms PCB)
Change repeater comms monitoring
6. Repeater Comms Monitoring Type
With the zone 6 fi re LED lit, the amber, fault / disabled / test LEDs will show the current setting.
LED 1 OFF = fault tolerant monitoring (default). LED 1 ON = legacy, radial circuit monitoring.
Press the ENTER button, zone 6 fi re LED will pulse to indicate ‘edit mode’.
Now use button 2 to change the setting (LED 1 ON or OFF).
When fi nished press the ENTER button again and the zone 6 fi re LED will return to steady ‘view mode’.
Press button 1 for 3 seconds to exit programming mode 2-1-2-3.
RESOUND SILENCE RESET
1
Disable
Mode
2
Test
Mode
3 4
Mute
Buzzer
Test
Lamps
ENTER
RESOUND SILENCE RESET
1
Disable
Mode
2
Test
Mode
3 4
Mute
Buzzer
Test
Lamps
ENTER
ASP-R Installation, Commissioning & Operating Manual
13
Approved Document Ref: UI-ASP-R-01 Issue 1.0
SETUP & PROGRAMMING
REPEATER PANEL SETUP & PROGRAMMING
The panels can support up to 8 repeaters. The repeater panels are fully functional with ‘Silence’ ‘Resound’ and ‘Reset’ controls, as well as Disable and Test Mode functions. It is possible to disable the controls of each or all repeater panels to make them passive.
Repeater Comms PCB
To run repeaters, a Comms PCB (TPCA05) must be fi tted to the main control panel. A Comms PCB for the control panel is supplied, as standard, with each repeater panel. The repeater panels themselves already have the comms board fi tted.
The Comms PCB fi ts into the control panel on top of the main circuit board where the ribbon cable from the display board is normally plugged.
To fi t the Comms PCB, power down the panel, un-plug the display board ribbon cable from the main circuit board and plug the Comms PCB into the socket instead.
A socket is provided on the top of the Comms PCB to re-connect the display board ribbon cable.
PSU
@ + -
28V 0V
+ -
FIRE
C NC NO
FAULT
C NC NO
FR FLT CC PUL
-OP -OP -IP -IP
SNDR1 SNDR2
+ + -
ZONE1 ZONE2 ZONE3 ZONE4
+ + + + -
Disconnect display board ribbon cable
+ -
BATTERY
PSU
@ + -
28V 0V
+ -
FIRE
C NC NO
FAULT
C NC NO
FR FLT CC PUL
-OP -OP -IP -IP
SNDR1 SNDR2
+ + -
ZONE1 ZONE2 ZONE3 ZONE4
+ + + + -
COMS A COMS B
+ + -
28
V+ 1
SW -ve OUTPUTS
2 3 4 5 6
ON
1 2 3 4
ADDRESS
ON
1 2 3 4 5 6 7
7 way DIL switch
Plug Comms PCB into the socket and re-connect dispay board ribbon cable to socket on top of Comms PCB
+ -
BATTERY
ON
1 2 3 4 5 6 7
Once the Comms PCB has been fi tted, the control panel will need to be programmed for the additional circuit board. To programme the main control panel for the additional PCB see over (page 15).
Next, the panel will need to be programmed for the number of repeater panels on the system. To set up the number of repeater panels on the system, see page 16.
All repeater programming is done at the main control panel with Level 3 programming mode active, see main control panel instruction manual.
ASP-R Installation, Commissioning & Operating Manual
14
Approved Document Ref: UI-ASP-R-01 Issue 1.0
SETUP & PROGRAMMING
To change the internal PCB confi guration at the main control panel use:
2 1 2 3
Panel Wide Settings
There are 6 general, panel wide, settings available.
RESOUND
Enter the above code and press the ENTER button. The 6 programmable options are represented by fi re zone LEDs 1 - 6, Option 5 being the, ‘set up internal PCB confi guration’ setting.
1
Disable
Mode
2
Test
Mode
SILENCE
3
Mute
Buzzer
4
Test
Lamps
RESET
ENTER
Use button 1 to move to option 5
RESOUND SILENCE RESET
1
Disable
Mode
2
Test
Mode
3 4
Mute
Buzzer
Test
Lamps
ENTER
3
4
5
Fire LED Programming Option
1 Change / remove keypad access code
2 Set number of repeater panels on system
6
Set output delay time (1 - 10 minutes)
Turn off battery monitoring
Set up internal PCB confi guration (add extension zone card or repeater comms PCB)
Change repeater comms monitoring
5. Setup Internal PCB Confi guration
With the zone 5 fi re LED lit, the amber, fault LEDs will show the current confi guration setting. Each of the
3 possible additional internal PCBs are represented by LEDs 1 - 3 as per table below.
LED 1 (ON)
Extension zone card 1
(zones 5 - 8)
LED 2 (ON)
Extension zone card 2
(zones 9 - 12)
LED 3 (ON)
Repeater Comms PCB
Press the ENTER button, zone 1 fi re LED will pulse to indicate editing of 1st additional PCB as per table above. Use button 1 to move to pulsing fi re LED 3.
Now use button 2 to change the setting (Amber LED ON = PCB included, OFF = not included).
When fi nished press the ENTER button again and the zone 5 fi re LED will return to steady ‘view mode’, with the amber, fault LEDs showing the new confi guration.
Press button 1 for 3 seconds to exit programming mode 2-1-2-3.
RESOUND SILENCE RESET
1
Disable
Mode
2
Test
Mode
3 4
Mute
Buzzer
Test
Lamps
ENTER
ASP-R Installation, Commissioning & Operating Manual
15
RESOUND SILENCE RESET
1
Disable
Mode
2
Test
Mode
3 4
Mute
Buzzer
Test
Lamps
ENTER
Approved Document Ref: UI-ASP-R-01 Issue 1.0
SETUP & PROGRAMMING
To set the number of repeater panels at the main control panel use:
2 1 2 3
Panel Wide Settings
RESOUND
There are 6 general, panel wide, settings available.
Enter the above code and press the ENTER button. The 6 programmable options are represented by fi re zone LEDs 1 - 6, Option 2 being the, ‘set number of repeater panels’ setting.
1
Disable
Mode
Use button 1 to move to option 2
2
Test
Mode
SILENCE
3
Mute
Buzzer
4
Test
Lamps
RESET
ENTER
1
RESOUND
Disable
Mode
2
Test
Mode
SILENCE
3 4
Mute
Buzzer
Test
Lamps
RESET
ENTER
4
5
2
3
Fire LED Programming Option
1 Change / remove keypad access code
Set number of repeater panels on system
Set output delay time (1 - 10 minutes)
6
Turn off battery monitoring
Set up internal PCB confi guration (add extension zone card or repeater comms PCB)
Change repeater comms monitoring
2. Set Number of Repeater Panels on System
With the zone 2 fi re LED lit, the amber, fault / disabled / test LEDs will show the current quantity of repeaters set 0 - 8. (1 LED lit = 1 repeater, 2 = 2 etc..).
Press the ENTER button, zone 2 fi re LED will pulse to indicate ‘edit mode’.
Now use buttons 1 & 3 to increase or decrease the quantity. Button 1 increases, button 3 decreases.
When fi nished press the ENTER button again and the zone 2 fi re LED will return to steady ‘view mode’.
Press button 1 for 3 seconds to exit programming mode 2-1-2-3.
Addressing
Each repeater panel needs to have a seperate address. The addressing is done using the 4 DIL switches on each of the Comms PCBs using binary code values, see diagram below.
The address should be set in sequence from 1 - 8, fi rst repeater address 01, next repeater address 02 etc.
The control panel should always be address 0 (all switches off).
ON
1 2 3 4
ADD 01
ON
1 2 3
ADD 02
4
ON
1 2 3 4
ADD 03
ON
1 2 3 4
ADD 04
ON
1 2 3 4
ADD 05
ON
1 2 3 4
ADD 06
ON
1 2 3 4
ADD 07
ON
1 2 3 4
ADD 08
ASP-R Installation, Commissioning & Operating Manual Approved Document Ref: UI-ASP-R-01 Issue 1.0
16
SETUP & PROGRAMMING
4 4 4 3
Programming Repeater Panels
All repeater programming is done at the main control panel with Level 3 programming mode active, see main control panel instruction manual.
The repeater panels have 2 inputs located on the main circuit board, Class Change (CC) and Alert (PUL).
Switching a negative voltage into these inputs will cause the alarm sounders to operate. The Class Change input (CC) will cause the alarms to sound continously and the Alert input (PUL) will cause the alarms to pulse.
There are also 6 switch -ve outputs located on the Comms PCB. By default o/p 1 is set to activate on common fi re and o/p 2 is set to activate for common fault.
There are 4 programming options available for the inputs and outputs in the repeater panels.
• Outputs 1 - 6 activate on common fi re
• Outputs 1 - 6 activate zonally for zones 1 - 6
• Outputs 1 - 6 activate zonally for zones 7 - 12
• Change inputs CC & PUL to power supply fault inputs.
It is also possible in this programming mode to disable the controls on repeater panels, making them passive instead of active and to disable the battery monitoring on the repeater panel if no battery backup is required.
Enter the above code and press ENTER. The zone 1 fi re LED will light. This indicates which repater panel is to be programmed 1 - 8. Use button 1 to move the fi re zone LED to the required repeater.
With the required repeater for editing LED lit, press the ENTER button to enter ‘editing mode’. The fi re zone
1 LED will now pulse to indicate setting of attribute 1 (outputs 1 - 6 common fi re) for that repeater.
Use button 1 to scroll to the attribute that requires editing, inidicated by a pulsing fi re LED 1 - 6 as per table below. Now use button 2 to change the setting indicated by the amber, fault LEDs, ON or OFF. Then use button 1 again to move to the next attribute if required.
Fire LED
(pulsing)
Attribute
LED 1
O/P 1 - 6
Common Fire
Default Setting OFF
LED 2
O/P 1 - 6 Zonal
(Zones 1 - 6)
OFF
LED 3
O/P 1 - 6 Zonal
(Zones 7 - 12)
OFF
LED 4 LED 5
Inputs For PSU
Fault
Controls
Passive
OFF OFF
Press button 1 for 3 seconds to exit programming mode 4-4-4-3.
Disable the controls and return DIL switch 6 to ‘OFF’ to exit Level 3 programming mode.
LED 6
Disable Battery
Monitoring
OFF
ASP-R Installation, Commissioning & Operating Manual
17
Approved Document Ref: UI-ASP-R-01 Issue 1.0
OPERATING
PANEL CONTROLS & INDICATIONS
Zonal Fire Indicator LEDs
Zones in Fire
Zones In Fault, Zones Disabled or
Zones In Test Indicator LEDs
RESOUND SILENCE RESET
1
Disable
Mode
2
Test
Mode
3
Mute
Buzzer
4
Test
Lamps
ENTER
Zone Fault / Disabled / Test
Supply Healthy
General Fire
General Fault
General Disablement
Test Mode
Sounder Status
Aux Output Status
Power Supply Fault
Delay Status
Repeater Fault
System Fault
Access Level
Off
Activate
Controls
On
Status Indicator LEDs
8 Button Keypad For Controls
And Programming
Activate Controls Key Switch
Activate Controls
In normal standby mode the keypad controls are inactive to protect from unauthorised operation. Controls can be activated by using the ‘Activate Controls’ key switch or by entering a four digit code using the keypad.
The use of a code entry to activate the controls is enabled by default but can be disabled in the Level 3 engineering functions.
To activate the controls using the key switch; turn the key clockwise to the ‘On’ position. The ‘Access
Level’ indicator LED will light and all buttons on the keypad will now be operational. To deactivate the controls, turn the key back to the ‘Off’ position and the ‘Access Level’ indicator LED will extinguish.
If the key switch is in the ‘On’ position the keypad will remain active.
NOTE : It is not possible to remove the key in the ‘On’ position.
To activate the controls using the keypad; fi rst push button 1 or button 2 to initialise the code entry
mode. The ‘Access Level’ indicator will pulse rapidly. After 30 seconds, if the code has not been entered, the panel will return to standby mode.
With the ‘Access Level’ indicator pulsing, enter the four digit code using buttons 1 - 4. The factory default code is 1-2-3-4 but can be changed in the engineering functions. After entering the four digit code press the ‘ENTER’ button. The ‘Access Level’ indicator LED will change to steady and all buttons on the keypad will now be operational.
If the wrong code has been entered the ‘Access Level’ indicator will continue to pulse. Enter the code again and press the ‘ENTER’ button. If after 30 seconds the correct code has still not been entered the panel will return to standby and button 1 or 2 will need to be pushed again to initialise code entry mode.
After activation by code entry, controls will automatically deactivate again after 2 minutes and the panel will return to standby mode.
The test lamps and mute buzzer functions are operational without the need to activate controls.
ASP-R Installation, Commissioning & Operating Manual
18
Approved Document Ref: UI-ASP-R-01 Issue 1.0
OPERATING
Status LED Indicators
Zones in Fire 1 - 12
Zone Fault/Disabled/Test
1 - 12
Supply Healthy:
General Fire:
General Fault:
General Disablement:
Test Mode:
Sounder Status:
Aux Output Status:
Power Supply Fault:
System Fault:
Access Level:
Repeater Fault:
Delay Status:
LED On
N/A
Indicates zone circuit is disabled or in test mode.
Indicates mains and/or battery supply is present.
N/A
N/A
Indicates one or more circuits have been disabled.
Indicates one or more circuits are in test mode
Indicates sounder circuits have been disabled or are in test mode
Indicates auxiliary outputs have been disabled.
N/A
Indicates a system failure, panel not functional.
Indicates controls are active (access level 2).
N/A
Delays are confi gured
LED Pulsing
Indicates alarm condition in zone.
Indicates a fault in the zone circuit.
N/A
Indicates panel is in alarm condition.
Indicates one or more faults are present.
Indicates disablement selection mode is active.
Indicates test mode selection is active.
Indicates a fault on one or more sounder circuits.
N/A
Indicates a power supply or battery fault.
Indicates the panel has recovered from a system fault.
Indicates panel is in confi guration mode
(access level 3).
Indicates a fault on one or more repeater panels
Delay is running
RESOUND SILENCE RESET
Keypad
RESOUND (red):
SILENCE (blue):
RESET (green):
1: (Disable Mode)
2: (Test Mode)
3: (Mute Buzzer)
4: (Test Lamps)
ENTER:
1
Disable
Mode
2
Test
Mode
3
Mute
Buzzer
4
Test
Lamps
ENTER
Use to resound the alarms after they have been silenced. Can also be used to invoke full evacuation.
Use to silence the sounders during an alarm condition.
Resets the panel back to standby mode.
With controls inactive, use to initialise code entry mode for activation of controls. With controls active, use to disable zones, sounder circuits or aux outputs (see DISABLE MODE section). Also has the numeric value 1 for code entry.
With controls inactive, use to initialise code entry mode for activation of controls. With controls active, use to put zones or sounders circuits into test mode (see TEST MODE section). Also has the numeric value 2 for code entry.
Mutes the panels internal fi re and fault buzzer. (The buzzer will still blip every 5-6 seconds during a fi re or fault condition). This function is operational without the need to activate controls. Also has the numeric value 3 for code entry.
Use this button to illuminate all LEDs to check that they are working correctly. This function is operational without the need to activate controls. Also has the numeric value 4 for code entry.
This button is used to confi rm code entries. It can also be used for fault diagnosis (see FAULT
DIAGNOSIS section).
ASP-R Installation, Commissioning & Operating Manual
19
Approved Document Ref: UI-ASP-R-01 Issue 1.0
OPERATING
DISABLE MODE
Disable Mode is used to disable or isolate individual zone circuits or all sounder circuits, all auxiliary outputs and any delays to outputs.
To initialise Disable Mode fi rstly activate the controls by turning the key switch or by entering the four digit code. Then press and hold the Disable Mode button (1) for 3 seconds.
After 3 seconds the panel will bleep and the General Disablement
LED and Zone 1 Fault/Disabled/Test LED will pulse slowly, indicating that Zone 1 is in disable selection mode.
1
RESOUND
Disable
Mode
2
Test
Mode
SILENCE
3
Mute
Buzzer
4
Test
Lamps
RESET
ENTER
Pressing the Disable Mode button again will move disable selection mode to Zone 2 and the Zone 2 Fault/
Disabled/Test LED will be pulsing instead. Subsequent presses will move the selection to Zones 3 - 12, dependant on the number of zones fi tted to the panel. I.e up to zone 4 on a 4 zone, 6 on a 6 zone, 8 on a
8 zone etc.
After the last available zone the next press will move the selection mode to the sounder circuits, indicated by the Sounder Status LED and then to the Aux outputs, indicated by the Aux Output Status LED and fi nally to the Delay LED. Pressing the button once more will move the selection back to Zone 1 again.
When the desired circuit, outputs or delays to be disabled is indicated by a slow pulsing LED, use the ENTER button to select it. Once selected the indicator LED will change to a rapid pulse. Pressing ENTER again will toggle the circuit between disabled and enabled. Then use Disable Mode button again to move to the next circuit. Any or all circuits, outputs or delays can be disabled simultaneously.
RESOUND
1
Disable
Mode
2
Test
Mode
SILENCE
3
Mute
Buzzer
4
Test
Lamps
RESET
ENTER
When all disablements have been set, press and hold the Disable Mode button for 3 seconds again.
This will exit the disable selection mode and the panel will return to standby. All disabled circuits and the
General Disablement will now be indicated by a steady LED.
To enable the circuits again, repeat the above process using the Disable Mode button to select the circuit and the ENTER button to remove the disablement.
Tip:
With the controls active, pressing the Disable Mode button briefl y will reveal which circuits are disabled (as opposed to in test mode). This is useful if using Disable Mode and Test Mode at the same time.
ASP-R Installation, Commissioning & Operating Manual
20
Approved Document Ref: UI-ASP-R-01 Issue 1.0
OPERATING
TEST MODE
Test Mode is used when testing the fi re alarm system. In test mode the devices in the zone(s) in test, detectors and call points etc, can be activated and the panel will automatically reset, enabling the system to be tested by one person. It is possible to test head removal monitoring and to test the system with or without the sounders.
RESOUND SILENCE RESET
To initialise Test Mode, fi rstly activate the controls by turning the key switch or by entering the four digit code. Then press and hold the Test
Mode button (2) for 3 seconds.
1 2 3 4
ENTER
After 3 seconds the panel will bleep and the Test Mode LED and Zone
1 Fault/Disabled/Test LED will pulse slowly, indicating that Zone 1 is in
Disable
Mode
Test
Mode
Mute
Buzzer
Test
Lamps test selection mode. The Sounder Status LED will also be pulsing rapidly, this indicates that the test will be
with sounders. (Test mode without sounders is explained below)
Pressing the Test Mode button again will move test selection mode to Zone 2 and the Zone 2 Fault/
Disabled/Test LED will be pulsing instead. Subsequent presses will move the selection to Zones 3 - 12, dependant on the number of zones fi tted to the panel. I.e up to zone 4 on a 4 zone, 6 on a 6 zone, 8 on a
8 zone etc..
After the last available zone the next press will move the selection mode to the sounder circuits, indicated by no Zone Fault/Disabled/Test LEDs on. This position selects whether or not the sounders will ring during test. Pressing the button once more will move the selection back to Zone 1 again.
When the desired zone to be tested is indicated by a slow pulsing LED, use the ENTER button to select it. Once selected the indicator LED will change to a rapid pulse. Pressing ENTER again will toggle the zone between in and out of test. Then use Test Mode button again to move to the next zone. Any or all zones can be in test mode simultaneously.
RESOUND
1
Disable
Mode
When at the sounder status position, use the ENTER button to toggle between testing with or without sounders. A rapid pulse = with sounders
(default), a slow pulse = without sounders.
SILENCE
2 3 4
Test
Mode
Mute
Buzzer
Test
Lamps
RESET
ENTER
When all zones to be tested have been selected, press and hold the Test Mode button for 3 seconds again.
This will exit the test selection mode. All zones in test and the Test Mode will now be indicated by a steady
LED.
To take zones out of test mode, repeat the above process using the Test Mode button to select the zone and the ENTER button to change the status.
Test Mode With Sounders
Activation of a call point or detector - sounders will pulse twice, device is automatically reset.
Removal of a detector - sounders will pulse once.
Test Mode Without Sounders
Activation of a call point or detector - panel buzzer and LED response only, device is automatically reset.
Tip:
With the controls active, pressing the Test Mode button briefl y will reveal which circuits are in test mode
(as opposed to disabled). This is useful if using Disable Mode and Test Mode at the same time.
ASP-R Installation, Commissioning & Operating Manual Approved Document Ref: UI-ASP-R-01 Issue 1.0
21
www.haes-systems.com

Public link updated
The public link to your chat has been updated.
Advertisement
Key features
- Fully functional repeater panel
- Supports up to 8 repeaters
- Fail safe loop configuration
- 12 zones
- Can be passive or active
- Easy to use controls and indications