TECHNICAL GUIDE R-410A ZV SERIES 3 - 5 TON

TECHNICAL GUIDE R-410A   ZV SERIES   3 - 5 TON
5123249-TTG-A-0515
TECHNICAL GUIDE
R-410A
ZV SERIES
3 - 5 TON
60 Hertz
Description
ASHRAE 90.1 COMPLIANT
TempMaster ZV units are convertible single packages with a
common footprint cabinet and common roof curb for all 3
through 5 ton models. The units were designed for light
commercial applications and can be easily installed on a roof
curb, slab, or frame.
All ZV units are self-contained and assembled on rigid full
perimeter base rails allowing for 3-way forklift access and
overhead rigging. Every unit is completely charged, wired,
piped, and tested at the factory to provide a quick and easy field
installation.
ZV units in all tonnage sizes are convertible between side
airflow and down airflow, with corresponding economizer if
economizer option is desired.
ZV units are available in the following configurations: cooling
only, cooling with electric heat and cooling with gas heat.
Electric heaters are available as factory-installed options or
field-installed accessories.
All units meet ASHRAE 90.1 single-zone variable supply air
volume standard. Featuring a variable frequency drive on 3
through 5 ton ZV models.
Tested in accordance with:
ZT 3 THROUGH 5 TON
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
5123249-TTG-A-0515
Table of Contents
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Table of Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Component Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Features and Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Guide Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Physical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Capacity Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Airflow Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Sound Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Typical Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Weights and Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Economizer Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
Component Location
Cooling With Gas Heat (3 Through 5 Ton)
High Efficiency
Filter access
SineWave
Fin Evaporator Coil (2" or 4”
“Simplicity®” 6(
w/IntelliSpeed™ Supply Fan Controls
filter options)
w/screw connectors for T-stat
Disconnect location
wiring and Network
(optional disconnect switch)
Connections
ECM Outdoor Fan motor
Micro-Channel Aluminum
Tube/Aluminum Fin
Condenser
Premium Efficiency
Belt-drive blower motor
Second model nameplate
inside hinged access
panel
Filter drier (solid core)
Base rails w/
forklift slots
(three sides)
and lifting
holes
Slide out motor and
blower assembly for
easy adjustment
and service
Power ventor
motor
Roof curbs in eight-and
fourteen-inch heights.
Roof curbs for transitioning
from 3-6 Ton footprint
to the ZV 3-5 Ton footprint
are available
(field-installed accessory)
Compressor access (HighEfficiency 2-Stage compressor)
2
VFD
20-gauge aluminized
steel tubular heat
exchanger for long life
(stainless steel option)
Side entry power
and control wiring
Slide-out drain pan
knockouts
with ¾" NPT
connection
Toolless door
latch
One or Two stage gas heating to
maintain warm, comfortable
temperature
Intelligent control board
for safe and efficient
operation
Johnson Controls Unitary Products
5123249-TTG-A-0515
Nomenclature
3-12.5 Ton Model Number Nomenclature
Z V TA5 N A5 A 2 A A C 2 1 B A 7
Product Category
Product Generation
7 = Seventh Generation
Z = A/C, Single Pkg., R-410A
Coated Coils
Product Identifier
A = Un-Coated
B = E-Coat Cond & Evap Coils
C = E-Coat Condenser Coil
D = E-Coat Evaporator Coil
V = 18 SEER Ultra High Eff. A/C
Nominal Cooling Capacity
TA3 = 3 Ton
TA4 = 4 Ton
TA5 = 5 Ton
Additional Options
A = No Options
B = Phase Monitor (PM)
C = Coil Guard (CG)
D = Dirty Filter Switch (DFS)
E = PM & CG
F = PM & DFS
G = CG & DFS
H = PM, CG, & DFS
Heat Type
C = Cooling Only. No heat installed
A = Alum Steel, Single Stage
B = Stainless Steel Single Stage
N = Alum Steel, Two Stage
S = Stainless Steel Two Stage
Configuration Options
1 = Bottom Drain Composite-STD
2 = Hot Gas Bypass
3 = SS Drain Pan No/HGB
4 = SS Drain Pan W/HGB
Nominal Heat Capacity (Unit Size Allowed)
Cooling
00 = Cooling Only
Filter Options
Natural Gas Heat Options
1 = 2" Throwaway Filters
2 = 2" Pleated Filters (Merv 7)
3 = 2" Cleanable Filters
4 = 4" Pleated Filters (Merv 13)
06 = 60 MBH Input (TA3, TA4)
08 = 80 MBH Input (TA3, TA4, TA5)
11 = 120 MBH Input (TA3, TA4, TA5)
16 = 160 MBH Input (TA5)
Electric Heat Options
VFD Options
03 = 3 KW (TA3)
06 = 6 KW (TA3, TA4, TA5)
08 = 9 KW (TA3, TA4, TA5)
15 = 15 KW (TA3, TA4, TA5)
20 = 20 KW (TA4, TA5)
23 = 24 KW (TA5)
A = None
B = VFD,VAV
C = VFD, w/Bypass, VAV
D = Cust Sup VFD,VAV
E = VFD, IntelliSpeed
F = VFD ,w/Bypass, Intellispeed
G = Cust Sup VFD, Intellispeed
Airflow
A = Std. Motor
D = Std. Motor/Motorized Damper (Downflow Only)
H = Std Motor/Low Leak Econ/Barometric Relief (Downflow
& Horizontal End Return Only)
J = Std Motor/Low Leak Econ/Power Exhaust (Downflow
& Horizontal End Return Only)
N = Hi Static
R = Hi Static/Motorized Damper (Downflow Only)
V = Hi Static Mtr/Low Leak Econ/Barometric Relief
(Downflow & Horizontal End Return Only)
W = Hi Static Mtr/Low Leak Econ/Power Exhaust
(Downflow & Horizontal End Return Only)
Control Options
A = None
C = BACnet MSTP,Modbus,N2 COM Card
F = FDD
H = Hnywll Excel 10 Ctrl, DFS, APS
N = Novar UCM Ctrl, DFS, APS
P = CPC Control, DFS, APS
R = Commercial Control System (CCS) Single Zone
S = Commercial Control System (CCS) Change over bypass
Installation Options
Voltage
2 = 208/230-3-60
4 = 460-3-60
5 = 575-3-60
A = No Options Installed
B = Option 1
C = Option 2
D = Options 1 & 2
E = Option 3
F = Option 4
G = Options 1 & 3
H = Options 1 & 4
J = Options 1, 2 & 3
K = Options 1, 2, & 4
L = Options 1,3 & 4
M = Options 1, 2, 3, & 4
N = Options 2 & 3
P = Options 2 & 4
Q = Options 2, 3, & 4
R = Options 3 & 4
S = Option 5
T = Options 1 & 5
U = Options 1, 3, & 5
V = Options 1, 4, & 5
W = Options 1, 3, 4, & 5
X = Options 3 & 5
Y = Options 4 & 5
Z = Options 3, 4 & 5
Options
1 = Disconnect
2 = Non-Pwr'd Conv. Outlet
3 = Smoke Detector S.A.
4 = Smoke Detector R.A.
5 = Pwr'd Conv. Outlet
Johnson Controls Unitary Products
3
5123249-TTG-A-0515
Features and Benefits
Standard Features for Ultra High Efficiency 3-5 Ton
Units
• Efficiency – High efficiency units reach as high as 18.1
SEER and 14.35 EER. Gas/electric units have electronic
spark ignition and power vented combustion with steady
state efficiencies of 80%. These efficiencies exceed all
legislated minimum levels and provide low operating costs.
• Service Friendly - The ZV Unit incorporates a number of
key features for ease of serviceability.
The motor and blower slide out of the unit as a common
assembly. This facilitates greater access to all the indoor
airflow components, thus simplifying maintenance and
adjustment.
Service time is reduced through the use of hinged,
toolless panels. Such panels provide access to frequently
inspected components and areas, including the control
box, compressors, filters, indoor motor & blower, and the
heating section. The panels are screwed in place at the
factory to prevent access by children or other
unauthorized persons. It is recommended that the panels
be secured with screws once service is complete.
Service windows have been placed in both condenser
section walls. Rotation of the cover allows easy access to
the condenser coils for cleaning or inspection.
The Simplicity® SE control board provides alarm
messages to help quickly identify any faults.
All units use four filters of the same standard size. This
standardization simplifies selections for filter replacement.
• Balanced Heating – The ZV two stage gas heating offers
“Ultimate Heating Comfort” with a balance between 1st and
2nd stage gas heating. The first stage of a gas heat ZV unit
provides 70% or 75% of the heating capacity.
• Convertible Airflow Design – The side duct openings
are covered when they leave the factory. If a side supply/
return is desired, the installer simply removes the two side
duct covers from the outside of the unit and installs them
over the down shot openings. No panel cutting is required.
Convertible airflow design allows maximum field flexibility
and minimum inventory.
• Advanced Controls - Simplicity® SE control boards have
standardized a number of features previously available only
as options or by utilizing additional controls.
The Simplicity® SE control board used in this
product will effectively operate the cooling system
down to 0°F when this product is applied in a comfort
cooling application for people. An economizer is
typically included in this type of application. When
applying this product for process cooling applications
(computer rooms, switchgear, etc.), please
reference applications bulletin AE-011-07 or call the
applications department for Unitary Products @ 1877-UPG-SERV for guidance. Additional
accessories may be needed for stable operation at
temperatures below 30°F.
The non-corrosive drain pan slides out of the unit to permit
easy cleaning. The drain pan is accessed by removing the
drain pan cover plate on the rear of the unit. Once the plate is
removed, the drain pan slides out through the rear of the unit.
All ZV units have a second model nameplate located
inside the control access door. This is to prevent
deterioration of the nameplate through weathering.
• Indoor Motors - Units come from the factory with
Premium Efficiency, Inverter rated, Indoor Motor. Both
motor and belt drive blower are mounted on a slide out
assembly for ease of service.
• VFD - These factory supplied Variable Frequency Drives
come with a 5 year warranty from the manufacturer. They
also provide ease of commissioning without the need of a
computer to program the motor. That also provide a soft
start which equates to longevity of motor and belt life.
• Outdoor motors - Units come from the factory with long
lasting, high efficiency ECM motors.
• Coil Technology – All ZT condensers utilize MicroChannel “all-aluminum” condensers which provide
improved heat transfer capabilities and reduced charge
volumes. All evaporators utilize a conventional copper
tube/aluminum fin design for proven reliability and
performance.
• Environmentally Aware - For improved Indoor Air
Quality, a combination of aluminum foil faced and
elastometric rubber insulations are used exclusively
throughout the units.
4
• Units will come with the new state of the art Simplicity
SE (Smart Equipment) control system. The new unit
control incorporates the best of the already proven
Simplicity™ unitary controls and creates a more robust,
intelligent control. The goal of this control is to utilize
cutting edge technology making the equipment easier to
install, operate, and service. All units are Factory
commissioned, configured, and run tested.
• Versatile - The Simplicity SE control can be configured to
use with a standard thermostat (easy to connect screw
Johnson Controls Unitary Products
5123249-TTG-A-0515
terminals), A zone sensor, or can be setup to
communicate with multiple BAS communication protocols
to integrate with building automation systems.
• Reduce field installed complexity - Each unit will comes
equipped with factory installed supply air, return air, and
outdoor air temperature sensors providing key
temperature readings thus reduce field installed
complexity.
• On-board USB Port - The new control comes with a long
list of features including data logging, current and
previous system faults and software update capabilities
using the on board USB port and common flash drive.
Energy use monitoring capabilities allow custom tailoring
to allow a system to work more efficiently at all times and
occupancy levels. Self test and start-up reports also
available from the board VIA the USB port.
• Embedded LCD Display - The board has a easy to read,
built-in LCD display and easy to use navigation joystick
and buttons allowing the user to quickly navigate the
menus displaying unit status, options, current function,
supply, return and outdoor temperatures, fault codes and
other information.
• Safety Monitoring - The control monitors the outdoor,
supply, and return air temperatures and the high and low
pressure switch status on the independent refrigerant
circuits. On units with heating the gas valve and high
temperature limit switches are monitored on gas and
electric heating units. The control also monitors the
voltage supplied to the unit and will protect the unit if low
voltage due to a brown out, or other electrical issue
occurs.
• Low Ambient - An integrated low-ambient control allows
units to operate in the cooling mode down to 0°F outdoor
ambient without additional components or intervention.
Optionally, the control board can be programmed to
lockout the compressors when the outdoor air
temperature is low or when free cooling is available.
• Anti-Short Cycle Protection - To aid compressor life, an
anti- short cycle delay is incorporated into the standard
control. Compressor reliability is further ensured by
programmable minimum run times. For testing, the antishort cycle delay can be temporarily overridden with the
push of a button.
• Fan Delays - Fan on and fan off delays are fully
programmable. Furthermore, the heating and cooling fan
delay times are independent of one another. All units are
programmed with default values based upon their
configuration of cooling and/or heating capacity.
• Nuisance Trip Protection and Three Strikes - To
prevent nuisance calls, the control board uses a three
times, you're out philosophy. The high, low-pressure
switch, anti-freeze protection, low voltage or heating high
limit must trip three times within two hours before the unit
control board will lock out the associated compressor.An
alarm message will be displayed on the LCD screen.
• Lead-Lag - An integrated Lead-Lag option allows equal
run time hours on all compressors, thereby extending the
life of all compressors. This option is selectable on the unit
control board.
Johnson Controls Unitary Products
• Low Limit Control (LLC) - To prevent the supply air from
dropping below a specified set point, when there is a
demand for cooling during cold outside conditions.
(Programmable Set point)
• Reliable - From the beginning - All units undergo
computer automated testing before they leave the factory.
Units are tested for refrigerant charge and pressure, unit
amperage, and 100% functionality. For the long term - All
units are painted with a long lasting, powder paint that
stands up over the life of the unit. The paint used has
been proven by a 1000 hour salt spray test.
• Full Perimeter Base Rails - The permanently attached
base rails provide a solid foundation for the entire unit and
protect the unit during shipment. The rails offer rigging
holes so that an overhead crane can be used to place the
units on a roof.
• Easy Installation - Gas and electric utility knockouts are
supplied in the unit underside as well as the side of the
unit. Utility connections can be made quickly and with a
minimum amount of field labor. All units are shipped with
2" throw-away filters installed.
• Wide Range of Indoor Airflows - All supply air blowers
are equipped with a belt drive that can be adjusted to
meet the exact requirements of the job. A high static drive
option is available for applications with a higher CFM and/
or static pressure requirement.
• Warranty - All models include a 1-year limited warranty
on the complete unit. Compressors and electric heater
elements each carry a 5-year warranty. Aluminized steel
(10 yr.) and stainless steel tubular heat exchangers carry
a 15- year warranty.
Factory Installed Options
TempMaster offers several equipment options factory installed,
for the ZVline.
• Optional Factory Installed Economizers - ZV units offer
a variety of optional factory installed economizers with low
leak dampers. The outdoor air dry bulb sensor enables
economizer operation if the outdoor air temperature is less
than the set point of the economizer logic module. See
economizer options section to determine the correct
economizer for your application.
• Down flow / End Return Economizers (with barometric
relief and fresh air hood) - All units offer a variety of
optional factory installed down flow economizers that are
shipped, installed and wired with low leak dampers
designed to meet ASHRAE 90.1-2010, AMCA 511 Class
1A damper, and the International Energy Conservation
Code (IECC) certification requirements by achieving
leakage rates of 3 cfm/sq. ft. at 1" of static pressure. Each
economizer goes through a rigorous 60,000 cycle test. Dry
bulb, single enthalpy, and dual enthalpy (with field installed
kit) can be selected. The economizer has spring return,
fully modulating damper actuators and is capable of
introducing up to 100% outdoor air. As the outdoor air
intake dampers open, the return air dampers close. The
changeover from mechanical refrigeration to economizer
operation is regulated by the outdoor air dry bulb
temperature or the outdoor air enthalpy input. The optional
(field installed) single or dual enthalpy kits provide
5
5123249-TTG-A-0515
•
•
•
•
•
•
•
•
•
•
•
additional inputs to monitor outdoor air/ or return air
humidity and temperature for true enthalpy control. The
installer needs only to assemble the outdoor air hood,
attach the enthalpy control the hood and mount the hood
to the unit (Hood and control are provided).
Power Exhaust - This factory option allows down flow or
horizontal end return economizer operation. The power
exhaust must be removed from the unit and mounted
in the horizontal end return duct work when applying
the product in the horizontal, end return
configuration.
Motorized Outdoor Air Damper - The motorized outdoor
air damper includes a slide-in/plug-in damper assembly
with an outdoor air hood and filters. The outdoor air
dampers open to the preset position when the indoor fan
motor is energized. The damper has a range of 0% to
100% outdoor air entry.
Alternate Indoor Blower Motor - For applications with
high static restrictions, units are offered with optional
indoor motors that provide higher static output and/or
higher airflow, depending upon the installer’s needs.
Aluminized Steel Gas Heat Exchanger - For
applications in non-corrosive environments.
Stainless Steel Gas Heat Exchanger - For applications
in corrosive environments, this option provides a full
stainless steel heat exchanger assembly.
Stainless Steel Drain Pan - An optional rust-proof
stainless steel drain pan is available to provide years of
trouble-free operation in corrosive environments.
Electric Heaters - The electric heaters range from 3kW to
24kW and are available in all the voltage options of the
base units. All heaters are intended for single point power
supply.
Disconnect Switch - For gas heat units and cooling units
with electric heat, a HACR breaker sized to the unit is
provided. For cooling only units, a switch sized to the
largest electric heat available for the particular unit is
provided. Factory installed option only.
Convenience Outlet - (Non-Powered/Powered) - This
option locates a 120V single-phase GFCI outlet with cover,
on the corner of the unit housing adjacent to the
compressors. The “Non-powered” option requires the
installer to provide the 120V single-phase power source and
wiring. The “Powered” option is powered by a stepdown
transformer in the unit. Factory installed option only.
Smoke Detectors - The smoke detectors stop operation
of the unit and provide a fault message to the control
board. Smoke detectors are available for both the supply
and/or return air configurations.
Filters - 2” Pleated MERV 7 or 4” Pleated MERV 13 are
available to meet LEED requirements. A 2” Throwaway is
shipped as standard.
Factory-installed smoke detectors may be subjected to
extreme temperatures during "off" times due to outside air
infiltration. These smoke detectors have an operational
limit of -4°F to 158°F. Smoke detectors installed in areas
that could be outside this range will have to be relocated to
prevent false alarms.
• Phase Monitors - Designed to prevent unit damage. The
phase monitor will shut the unit down in an out-of phase
condition. (Standard on units with Scroll Compressors.)
• Coil Guard - Customers can purchase a coil guard kit to
protect the condenser coil from damage. Additionally, this
kit stops animals and foreign objects from entering the
space between the inner condenser coil and the main
cabinet. This is not a hail guard kit.
• Dirty Filter Switch - This kit includes a differential
pressure switch that energizes the fault light on the unit
thermostat, indicating that there is an abnormally high
pressure drop across the filters. Factory installed option or
field installed accessory.
• Technicoat Condenser Coils - The condenser coils are
coated with a phenolic coating for protection against
corrosion due to harsh environments.
• Technicoat Evaporator Coil - The evaporator coils are
coated with a phenolic coating for protection against
corrosion due to harsh environments.
• E-coat Condenser Coils - The condenser coils are
coated with an epoxy polymer coating to protect against
corrosion.
• E-coat Evaporator Coils - The evaporator coils are
coated with an epoxy polymer coating to protect against
corrosion.
Control Options
• Simplicity® SE with Communication Option Control The TempMaster Simplicity® SE with Communication
Option Control is factory installed. It includes all the
features of the Simplicity® SE control with an additional
gateway to BACnet MS/TP (programmable to Modbus or
N2 protocols).
• Novar® BAS Control - The Novar® building automation
system controller is factory installed. Includes supply air
sensor, return air sensor, dirty filter indicator switch, and
air proving switch.
• CPC BAS Control - The Computer Process Controls
Model 810-3060 ARTC Advanced Rooftop building
automation system controller is factory installed. Includes
supply air sensor, return air sensor, with optional dirty
filter indicator switch and air proving switch.
• Honeywell BAS Control - The Honeywell W7750C
building automation system controller is factory installed.
Includes air supply sensor, return air sensor, with optional
dirty filter indicator switch, and air proving switch.
6
Johnson Controls Unitary Products
5123249-TTG-A-0515
Field Installed Accessories
TempMaster offers several equipment accessories for field
installation, for the ZV line.
• Down flow and End Return Economizers (with fresh air
hood and barometric relief) - All units offer a variety of
optional factory installed down flow economizers that are
shipped, installed and wired with low leak dampers designed
to meet ASHRAE 90.1-2010, AMCA 511 Class 1A damper,
and the International Energy Conservation Code (IECC)
certification requirements by achieving leakage rates of 3
cfm/sq. ft. at 1" of static pressure. Each economizer goes
through a rigorous 60,000 cycle test. Dry bulb, single
enthalpy, and dual enthalpy (with field installed kit) can be
selected. The economizer has spring return, fully modulating
damper actuators and is capable of introducing up to 100%
outdoor air. As the outdoor air intake dampers open, the
return air dampers close. The changeover from mechanical
refrigeration to economizer operation is regulated by the
outdoor air dry bulb temperature or the outdoor air enthalpy
input. The dual enthalpy kit provides a second input used to
monitor the return air (field installed). The installer needs only
to assemble the outdoor air hood, attach the enthalpy control
the hood and mount the hood to the unit (Hood and control
are provided).
• Single or Dual Enthalpy Control, Accessories - These
kits contain the required components to convert a dry bulb
economizer to a single enthalpy and/or dual enthalpy
economizer.
• Barometric Relief Damper - Zero to 100% capacity
barometric relief dampers for use with horizontal flow, or
field installed economizers.
• Power Exhaust - This accessory installs in the unit with a
down flow or horizontal end return economizer. Power
exhaust plugs into the connector in the unit bulkhead.
User must purchase the 1EH0408 barometric relief
and hood kit when applying the product in a
horizontal flow application. The power exhaust must
be mounted in the horizontal end return ductwork.
• Manual Outdoor Air Damper - Like the motorized
outdoor air damper, each manual outdoor air damper
includes a slide-in damper assembly with an outdoor air
hood and filters. Customers have a choice of dampers
with ranges of 0% to 100% or 0% to 35% outdoor air
entry.
• Motorized Outdoor Air Damper - The motorized outdoor
air damper includes a slide-in/plug-in damper assembly with
an outdoor air hood and filters. The outdoor air dampers
open to the preset position when the indoor fan motor is
energized. The damper has a range of 0% to 100% outdoor
air entry. Factory installed option or field installed accessory.
• Smoke Detectors - The smoke detectors stop operation
of the unit by interrupting power to the control board if
smoke is detected within the air compartment.
• CO2 Sensor - Senses CO2 levels and automatically
overrides the economizer when levels rise above the
preset limits.
Johnson Controls Unitary Products
• Dirty Filter Switch - This kit includes a differential
pressure switch that energizes the fault light on the unit
thermostat, indicating that there is an abnormally high
pressure drop across the filters.
• Coil Guard - Field installed decorative wire coil guard.
• Hail Guard - This kit includes a sloped hood which installs
over the outside condenser coil and prevents damage to
the coil fins from hail strikes. Field installed accessory only.
• Flue Exhaust Extension Kit - In locations with wind or
weather conditions which may interfere with proper
exhausting of furnace combustion products, this kit can be
installed to prevent the flue exhaust from entering nearby
fresh air intakes.
• -60°F Gas Heat Kit - For installations which require gas
heat units to perform in low ambient temperatures, a gas
section heating kit is available. This kit provides electric
heat in the gas heat controls section to ensure the gas
valve and controls will continue to function properly at
extremely low temperatures.
• Gas Heat High Altitude Kit - This kit converts a gas heat
unit to operate at high altitudes, 2,000 to 6,000 feet.
Conversion kits are available for natural gas and propane.
• Gas Heat Propane Conversion Kit - This kit converts a
gas-fired heater from natural gas to propane. It contains the
main burner orifices and gas valve replacement springs.
• Gas Piping Kit - Contains pipe nipples, fittings and gas cock
required for gas supply connection with external shut off.
• Electric Heaters - The electric heaters range from 3kW to
24kW and are available in all the voltage options of the
base units.
All heaters are dual staged. Cooling units include an
adapter panel for easy installation of the electric heaters.
Necessary hardware and connectors are included with the
heaters. All heaters are intended for single point power
supply.
• Metal Frame Filter Kit - Metal frame with polyester filter
medium.
• Permanent Filters - Permanent filters are available.
• Roof Curbs - Single Piece Adapter (10" High) - Roof curbs
for transitioning from 7.5 T thru 12.5T DHB/ DUC/DHC/DUS
to ZU/ZW/ZK 3- 12T units to TempMaster units. Fits 3 to 5
Ton roof curbs only.
• Roof Curb Transition - Single Piece Adapter (10” High) Roof curbs for transitioning from Sunline™ units to ZV
units. Fits 3 to 5 Sunline™ roof curbs only.
• Burglar Bars - Mount in the supply and return openings
to prevent entry into the duct work.
• Thermostat - The units are designed to operate with 24volt electronic and electro-mechanical thermostats. All
Ultra High Efficiency 3-5 Ton units (with or without an
economizer) operate with two-stage heat/two-stage cool
or two-stage cooling only thermostats, depending upon
unit configuration.
7
5123249-TTG-A-0515
Accessories
Field Installed Accessories - Non-Electrical
MODEL
1BD0408
1CG0427
1CG0428
1HG0415
1FE0412
1FF0415
1FL0423
1GP0405
1HA0450
1HA0451
1HA0452
1HA0453
1NP0454
1NP0455
1RC0470
1RC0471
VOLTAGE
All
All
All
All
All
All
All
All
All
All
All
All
All
All
All
All
1RC0472
All
1WC0412
1LN0407
1LN0408
All
All
All
8
DESCRIPTION
Burglar Bars, Downflow
Coil Guard
Coil Guard
Hail Guard Kit
Flue Exhaust Extension Kit
2" only Metal Filter Frame Kit
Permanent 2" only Filter Kit (Includes (4) four Filters)
Gas Piping Kit
High Altitude Kit for Natural Gas
High Altitude Kit for Natural Gas
High Altitude Kit for Propane
High Altitude Kit for Propane
Propane Conversion Kit
Propane Conversion Kit
Roof Curb, 8" Height
Roof Curb, 14" Height
Roof Curb, Transition (7.5 T thru 12.5T DHB/DUC/DHC/
DUS to ZU/ZW/ZK 3- 12T)
Wooden Crate for extra protection during shipping and
handling
Low NOx Kit
Low NOx Kit
WHERE USED
All Cabinets
(Electric / Electric Models), 42” Tall Cabinets
(Gas / Electric Models), 42" Tall Cabinets
All Short (42") Standard Cabinets
All Cabinets
All Tall 42" Cabinets
All Tall 42" Cabinets
All Cabinets
3 - 5T (80, 120 & 160 MBH Input)
3 - 4T (60 MBH Input)
3 - 5T (80, 120 & 160 MBH Input)
3 - 4T (60 MBH Input)
3 - 5T (80, 120 & 160 MBH Input)
3 - 4T (60 MBH Input)
All Cabinets
All Cabinets
All Cabinets
Standard Cabinets Only (not applicable to units 119" in
length)
3 - 5T (80, 120 & 160 MBH Input)
3 - 5T (60 MBH Input)
Johnson Controls Unitary Products
5123249-TTG-A-0515
Accessories (Continued)
Field Installed Accessories - Electric Heat
MODEL
2TP04510325
2TP04510346
2TP04510625
2TP04510646
2TP04510825
2TP04510846
2TP04510858
2TP04511525
2TP04511546
2TP04511558
2TP04512025
2TP04512046
2TP04512058
2TP04512325
2TP04512346
2TP04512358
VOLTAGE
230
460
230
460
230
460
575
230
460
575
230
460
575
230
460
575
DESCRIPTION
WHERE USED
3kW Electric Heat
All 42" Cabinet 3 Ton Models
6kW Electric Heat
All 42" Cabinet 3, 4 and 5 Ton Models
9kW Electric Heat
All 42" Cabinet 3, 4 and 5 Ton Models
15kW Electric Heat
All 42" Cabinet 3, 4 and 5 Ton Models
20kW Electric Heat
All 42" 4 and 5 Ton Models
24kW Electric Heat
All 42" Cabinet 5 Ton Models
Field Installed Accessories - Fresh Air
MODEL
1FA0413
1FA0414
1EH0408
2EC0401
2EC0402
2EE04707424
2EE04706924
2MD04703824
2MD04703924
2PE04704706
2PE04704746
2PE04704758
VOLTAGE DESCRIPTION
All
Manual Outside Air Damper 0-35%, Downflow
All
Manual Outside Air Damper 0-100%, Downflow
Barometric Relief Kit for Power Exhaust, Horizontal
All
Application
All
Single Enthalpy Control
All
Dual Enthalpy Control (Includes 2 Sensors)
Economizer for Downflow, End Return Horizontal, or
All
ERV Applications. Includes FA Hood, Exhaust Hood w/
Baro Relief
All
Horizontal Economizer without Barometric Relief
All
Motorized Damper, Downflow without Barometric Relief
All
Motorized Damper, Horizontal without Barometric Relief
230
Power Exhaust 230V Downflow or Horizontal
460
Power Exhaust 460V Downflow or Horizontal
575
Power Exhaust 575V Downflow or Horizontal
WHERE USED
All Cabinets
All Cabinets
All Cabinets
All Cabinets
All Cabinets
All 42" Cabinets
All Cabinets
All Cabinets
All Cabinets
All Cabinets
All Cabinets
All Cabinets
Field Installed Accessories - Controls
MODEL
2AP0401
2AQ04700324B
2AQ04700424C
2DF0402
VOLTAGE
All
All
All
All
2SH0401
All
2SD04700824
2SD04700924
2SD04701024
S1-YKMAP1810-0P
All
All
All
S1-MP-PRTKIT0P
All
All
DESCRIPTION
Air Proving Switch
CO² Space Accessory
CO² Unit Accessory
Dirty Air Switch
Wall Mounted humidity sensor-For use with MagnaDry
Reheat or space humidity input to Simplicity SE board.
Smoke Detector for Supply
Smoke Detector for Return
Smoke Detector for Supply and Return
MAP (Mobile Access Portal) Gateway- For use with
Simplicity SE Control.
MAP (Mobile Access Portal) Gateway Kit- Replacement
MAP gateway protective case, lanyard and
communication cable. Use only to replace worn or
damaged components.
WHERE USED
All Units
All Units
All Units
All Units
All Cabinets
All Gen 6 and greater units with 2" & 4" Filters
All Gen 6 and greater units with 2" & 4" Filters
All Gen 6 and greater units with 2" & 4" Filters
All Units
All Units
Field Installed Accessories - Electrical
MODEL
2BC04700106
2BC04700151
2BC04700154
VOLTAGE
230
460
575
DESCRIPTION
Gas heat kit, -60ºF
Gas heat kit, -60ºF
Gas heat kit, -60ºF
Johnson Controls Unitary Products
WHERE USED
All Units
All Units
All Units
9
5123249-TTG-A-0515
Guide Specifications
GENERAL
Units shall be manufactured by Johnson Controls in an ISO
9001 certified facility. TempMaster units are convertible single
packages with a common footprint cabinet and common roof
curb for all 3 through 5 ton models. The units were designed
for light commercial applications and can be easily installed on
a roof curb, slab, or frame. All TempMaster units are selfcontained and assembled on rigid full perimeter base rails
allowing for 3-way forklift access and overhead rigging. Every
unit is completely charged with R-410A, wired, piped, and
tested at the factory to provide a quick and easy field
installation. All units are convertible between side and down
airflow. Independent economizer designs are used on side and
down discharge applications, as well as all tonnage sizes.
TempMaster units are available in the following configurations:
cooling only, cooling with electric heat and cooling with gas
heat. Electric heaters are available as factory-installed options
or field-installed accessories.
DESCRIPTION
INDOOR (EVAPORATOR) FAN ASSEMBLY
Fan shall be a belt drive assembly and include an adjustable
pitch motor pulley. Job site selected brake horsepower shall not
exceed the motors nameplate horsepower rating plus the service factor. Units shall be designed to operate within the service
factor. Fan wheel shall be double inlet type with forward curve
blades, dynamically balanced to operate smoothly throughout
the entire range of operation. Design shall meet ASHRAE 90.1
single-zone variable supply air volume standard. Bearings shall
be sealed and permanently lubricated for longer life and no
maintenance. Entire blower assembly and motor shall be slide
out design.
OUTDOOR (CONDENSER) FAN ASSEMBLY
The outdoor fans shall be of the direct drive type, discharge air
vertically, have aluminum blades riveted to corrosion resistant
steel spider brackets and shall be dynamically balanced for
smooth operation. The outdoor fan motors shall have permanently
lubricated bearings internally protected against overload
conditions and staged independently. A cleaning window shall be
provided on two sides of the units for coil cleaning.
Units shall be factory assembled, single package, (Elec/Elec, Gas/
Elec), designed for outdoor installation. They shall have built in
field convertible duct connections for down discharge supply/return
or horizontal discharge supply/return and be available with factory
installed options or field installed accessories. The units shall be
factory wired, piped and charged with R-410A refrigerant and
factory tested prior to shipment. All unit wiring shall be both
numbered and color coded. The cooling performance shall be
rated in accordance with DOE and AHRI test procedures. Units
shall be CSA certified to ANSI Z21.47 and UL 1995/CAN/CSA No.
236-M90 standards.
REFRIGERANT COMPONENTS
UNIT CABINET
Coils:
Unit cabinet shall be constructed of galvanized steel with
exterior surfaces coated with a non-chalking, powder paint
finish, certified at 1000 hour salt spray test per ASTM-B117
standards. Indoor blower sections shall be insulated with up to
1” thick insulation coated on the airside. Either aluminum foil
faced or elastometric rubber insulation shall be used in the
unit’s compartments and be fastened to prevent insulation from
entering the air stream. Cabinet doors shall be hinged with
toolless access for easy servicing and maintenance. Full
perimeter base rails shall be provided to assure reliable transit
of equipment, overhead rigging, fork truck access and proper
sealing on roof curb applications. Disposable 2” filters shall be
furnished as standard and be accessible through hinged access
door. Fan performance measuring ports shall be provided on
the outside of the cabinet to allow accurate air measurements
of evaporator fan performance without removing panels or
creating bypass of the coils. Condensate pan shall be slide out
design, constructed of a non corrosive material, internally
sloped and conforming to ASHRAE 62-B9 standards.
Condensate connection shall be a minimum of ¾” I.D. female
and be rigid mount connection.
10
Compressors:
a. Shall be fully 2-stage, hermetic type, direct drive,
internally protected with internal high-pressure relief and
over temperature protection. The hermetic motor shall be
suction gas cooled and have a voltage range of + or –
10% of the unit nameplate voltage.
b. Shall have internal spring isolation and sound muffling to
minimize vibration and noise, and be externally isolated
on a dedicated, independent mounting.
a. Evaporator coils shall have aluminum plate fins
mechanically bonded to seamless internally enhanced
copper tubes with all joints brazed. Special Phenolic
coating shall be available as a factory option.
b. Evaporator coils shall be of the direct expansion, drawthru design.
c. Condenser coils shall have Micro-Channel aluminum
tube, aluminum fins.
d. Condenser coils shall be of the draw-thru design.
Refrigerant Circuit and Refrigerant Safety Components shall
include:
a. Independent fixed-orifice
expansion devices.
or
thermally
operated
b. Solid core filter drier/strainer to eliminate any moisture or
foreign matter.
c. Accessible service gage connections on both suction
and discharge lines to charge, evacuate, and measure
refrigerant pressure during any necessary servicing or
troubleshooting, without losing charge.
Johnson Controls Unitary Products
5123249-TTG-A-0515
Unit Controls:
a. Unit shall be complete with self-contained low-voltage
control circuit protected by a resettable circuit breaker on
the 24-volt transformer side.
b. Unit shall incorporate a lockout circuit which provides
reset capability at the space thermostat or base unit,
should any of the following standard safety devices trip
and shut off compressor.
1. Loss-of-charge/Low-pressure switch.
2. High-pressure switch.
3. Freeze condition sensor on evaporator coil. If any of
these safety devices trip, the LCD screen will display
the alarm message.
c. Unit shall incorporate "AUTO RESET" compressor over
temperature, over current protection.
d. Unit shall operate with conventional thermostat designs
and have a low voltage terminal strip for easy hook-up.
e. Unit control board shall have on-board diagnostics and
fault message display.
f. Standard controls shall include anti-short cycle and low
voltage protection, and permit cooling operation down to
a selectable value as low as 0 °F.
g. Control board shall monitor each refrigerant safety switch
independently.
GAS HEATING SECTION (IF EQUIPPED)
Heat exchanger and exhaust system shall be constructed of
aluminized steel and shall be designed with induced draft combustion with post purge logic, energy saving direct spark ignition, and redundant main gas valve. The heat exchanger shall
be of the tubular type, constructed of T1-40 aluminized steel for
corrosion resistance and allowing minimum mixed air entering
temperature of 40 ºF. Burners shall be of the in-shot type, constructed of aluminum-coated steel. All gas piping shall enter the
unit cabinet at a single location, through either the side or bottom, without any field modifications. An integrated control board
shall provide timed control of evaporator fan functioning and
burner ignition. Heating section shall be provided with the following minimum protection:
a. Primary and auxiliary high-temperature limit switches.
b. Induced draft pressure sensor.
c. Flame roll out switch (manual reset).
d. Flame proving controls.
e. All two stage gas units shall have two independent
stages of capacity (70% or 75% 1st stage, 100% 2nd
stage).
excessive temperature. The Heating Section assembly shall
slide out of the unit for easy maintenance and service. Units
with Electric Heating Sections shall be wired for a single point
power supply with branch circuit fusing (where required).
UNIT OPERATING CHARACTERISTICS
Unit shall be capable of starting and running at 125 ºF outdoor
temperature, exceeding maximum load criteria of AHRI Standard 340/360. The compressor, with standard controls, shall be
capable of operation down to 0 ºF outdoor temperature. Unit
shall be provided with fan time delay to prevent cold air delivery
before heat exchanger warms up. (Gas heat only)
ELECTRICAL REQUIREMENTS - All unit power wiring shall
enter unit cabinet at a single factory provided location and be
capable of side or bottom entry to minimize roof penetrations
and avoid unit field modifications. Separate side and bottom
openings shall be provided for the control wiring.
STANDARD LIMITED WARRANTIES - Compressor – 5 Years,
Heat Exchanger – 10 Years, Elect. Heat Elem. – 5 Years,
Parts – 1 Year
FACTORY INSTALLED OPTIONAL OUTDOOR AIR (Shall be
made available by either/or):
• DRY BULB AUTOMATIC ECONOMIZER - Outdoor and
return air dampers that are interlocked and positioned by
a fully-modulating, spring-return damper actuator. The
maximum leakage rate for the outdoor air intake dampers
shall be designed to meet ASHRAE 90.1-2010, AMCA
511 Class 1A damper, and the International Energy
Conservation Code (IECC) certification requirements by
achieving leakage rates of 3 cfm/sq. ft. at 1" of static
pressure. Changeover from compressor to economizer
operation shall be provided by an integral electronic
enthalpy control that feeds input into the basic module.
The outdoor intake opening shall be covered with a rain
hood that matches the exterior of the unit. Water
eliminator/filters shall be provided.
Simultaneous economizer/compressor operation is also
possible. Dampers shall fully close on power loss.
Available with barometric relief and power exhaust.
• MOTORIZED OUTDOOR AIR DAMPERS - Outdoor and
return air dampers that are interlocked and positioned by
a 2- position, spring-return damper actuator. A unitmounted potentiometer shall be provided to adjust the
outdoor and return air damper assembly to take in the
design CFM of outdoor air to meet the ventilation
requirements of the conditioned space during normal
operation. Whenever the indoor fan motor is energized,
the dampers open up to one of two pre-selected positions
- regardless of the outdoor air enthalpy. Dampers return to
the fully closed position when the indoor fan motor is deenergized. Dampers shall fully close on power loss.
ELECTRIC HEATING SECTION (IF EQUIPPED)
An electric heating section, with nickel chromium elements,
shall be provided in a range of 3 thru 24KW. The heating section shall have a primary limit control(s) (automatic reset) to prevent the heating element system from operating at an
Johnson Controls Unitary Products
ADDITIONAL FACTORY INSTALLED OPTIONS
• ALTERNATE INDOOR BLOWER MOTOR – For
applications with high restrictions, units are available with
11
5123249-TTG-A-0515
optional indoor blower motors that provide higher static
output and/or higher airflow.
• CONVENIENCE OUTLET (POWERED/NON-POWERED)–
Unit can be provided with an optional 120VAC GFCI outlet
with cover on the corner of the unit housing the compressors.
• ELECTRIC HEAT - Electric Heaters range from 3kW to
24kW and are available in all the voltage options of the
base unit.
• SMOKE DETECTOR – A smoke detector can be factory
mounted and wired in the supply and/or return air
compartments.
OTHER PRE-ENGINEERED ACCESSORIES AVAILABLE
• PHASE MONITOR - Designed to prevent damage in outof-phase condition.
• ROOF CURB - 14” and 8” high, full perimeter knockdown
curb, with hinged design for quick assembly.
• COIL GUARD - Designed to prevent condenser coil
damage.
• BAROMETRIC RELIEF DAMPER – (Unit mounted –
Downflow, Duct Mounted – Horizontal) – Contains a rain
hood, air inlet screen, exhaust damper and mounting
hardware. Used to relieve internal air pressure through
the unit during economizer operation.
• BAS CONTROLS HARDWARE - Include supply air
sensor, return air sensor, dirty filter indicator and air
proving switch.
• DIRTY FILTER SWITCH – This kit includes a differential
pressure switch that energizes the fault light on the unit
thermostat, indicating that there is an abnormally highpressure drop across the filters.
• BREAKER – An HACR breaker can be factory installed
on gas heat units or cooling units with electric heat.
• DISCONNECT SWITCH - A disconnect can be factory
installed on a cooling only units sized for the largest
electric heat available.
12
• STAINLESS STEEL HEAT EXCHANGER – For
applications in a corrosive environment, this option
provides a full stainless steel heat exchanger assembly.
• PROPANE CONVERSION KIT – Contains new orifices
and gas valve springs to convert from natural to L.P. gas.
• -60ºF GAS HEAT KIT – Provides an electric heat kit for
the gas compartment for use in extreme low ambient
conditions.
• ECONOMIZER (Downflow and Horizontal flow)
• POWER EXHAUST – (Unit mount – Downflow, Duct
mount – Horizontal flow)
• DUAL ENTHALPY KIT - Provides a second input to
economizer to monitor return air.
Johnson Controls Unitary Products
5123249-TTG-A-0515
Physical Data
ZVTA3 thru TA5 Single Stage Gas Physical Data
Models
Component
ZVTA3
ZVTA4
ZVTA5
3.0
4.0
5.0
Gross Capacity @ AHRI A point (MBh)
39000
54000
66000
AHRI net capacity (MBh)
38000
52000
64000
EER
14.15
14.35
13.85
SEER
18.1
18
17.5
IPLV
-
-
-
1200
1600
2000
Nominal Tonnage
AHRI COOLING PERFORMANCE
Nominal CFM
System power (KW)
2.70
3.64
4.62
R-410A
R-410A
R-410A
System 1
9-12
13-2
12-7
System 2
-
-
-
Refrigerant type
Refrigerant charge (lb-oz)
AHRI HEATING PERFORMANCE
Heating model
(A,B)06
(A,B)08
(A,B)11
(A,B)06
(A,B)08
(A,B)11
(A,B)08
(A,B)11
(A,B)16
Heat input (K Btu)
60
80
120
60
80
120
80
120
160
Heat output (K Btu)
49
65
97
49
65
97
65
97
129
-
-
-
-
81
81.5
81
81
81
80.5
AFUE %
-
Steady state efficiency (%)
81.5
81
81
-
No. burners
4
4
6
4
4
6
4
6
8
No. stages
1
1
1
1
1
1
1
1
1
Temperature Rise Range (ºF)
20-50°F 25-65°F 35-80°F 20-50°F 25-65°F 35-80°F 25-65°F 35-80°F 45-75°F
Gas Limit Setting (ºF)
200
235
290
200
235
290
235
290
240
Gas piping connection (in.)
3/4
3/4
3/4
3/4
3/4
3/4
3/4
3/4
3/4
DIMENSIONS (inches)
Length
89
89
89
Width
59
59
59
Height
OPERATING WT. (lbs.)
42
42
42
922
960
968
2-stage scroll
2-stage scroll
2-stage scroll
1
1
1
67/100
67/100
67/100
12.2
COMPRESSORS
Type
Quantity
Unit Capacity Steps (%)
CONDENSER COIL DATA
Face area (Sq. Ft.)
12.2
12.2
Rows
1
1
1
Fins per inch
23
23
23
Tube diameter (in./MM)
Circuitry Type
.98/25
.98/25
.98/25
2-pass Microchannel
2-pass Microchannel
2-pass Microchannel
10.56
EVAPORATOR COIL DATA
Face area (Sq. Ft.)
10.56
10.56
Rows
3
4
4
Fins per inch
15
15
15
Tube diameter
0.375
0.375
0.375
Refrigerant control
TXV
TXV
TXV
Johnson Controls Unitary Products
13
5123249-TTG-A-0515
ZVTA3 thru TA5 Single Stage Gas Physical Data (Continued)
Models
Component
Nominal Tonnage
ZVTA3
ZVTA4
ZVTA5
3.0
4.0
5.0
2
2
2
CONDENSER FAN DATA
Quantity of fans
Fan diameter (Inch)
24
24
24
Prop
Prop
Prop
Direct ECM
Direct ECM
Direct ECM
2
2
2
Motor HP each
1/3
1/3
1/3
No. speeds
Var.
Var.
Var.
RPM
850
850
850
Nominal total CFM
7000
7000
7000
Type
Drive type
Quantity of motors
BELT DRIVE EVAP FAN DATA
Quantity
Fan Size (Inch)
Type
1
1
1
12 x 9
12 x 9
12 x 9
Centrifugal
Centrifugal
Centrifugal
Motor Sheave
1VL40
1VL40
1VL34
1VL44
1VL40
1VM50
Blower Sheave
AK79
AK61
AK64
AK69
AK61
AK64
Belt
A47
A45
A47
A47
A45
A47
Motor HP each
1-1/2
1-1/2
1-1/2
1-1/2
1-1/2
2
RPM
1725
1725
1725
1725
1725
1725
56
56
56
56
56
56
Frame size
FILTERS
Quantity - Size
4 - (24 x 16 x 2)1,2
3
4 - (24 x 16 x 4)
4 - (24 x 16 x 2)1,2
3
4 - (24 x 16 x 4)
4 - (24 x 16 x 2)1,2
4 - (24 x 16 x 4)3
1. 2 In. Throwaway, Standard, MERV (Minimum Efficiency Reporting Value)
2. 2 In. Pleated, Optional, MERV 7.
3. 4 In. Pleated, Optional, MERV 13.
14
Johnson Controls Unitary Products
5123249-TTG-A-0515
ZVTA3 thru TA5 Two Stage Gas Physical Data
Models
Component
ZVTA3
ZVTA4
ZVTA5
3.0
4.0
5.0
Gross Capacity @ AHRI A point (MBh)
39000
54000
66000
AHRI net capacity (MBh)
38000
52000
64000
EER
14.15
14.35
13.85
SEER
18.1
18
17.5
IPLV
-
-
-
Nominal CFM
1200
1600
2000
System power (KW)
2.70
3.64
4.62
R-410A
R-410A
R-410A
System 1
9-12
13-2
12-7
System 2
-
-
-
Nominal Tonnage
AHRI COOLING PERFORMANCE
Refrigerant type
Refrigerant charge (lb-oz)
AHRI HEATING PERFORMANCE
Heating model
(N,S)06
(N,S)08
(N,S)11
(N,S)06
(N,S)08
(N,S)11
(N,S)08
(N,S)11
(N,S)16
Heat input (K Btu)
60
80
120
60
80
120
80
120
160
Heat output (K Btu)
49
65
97
49
65
97
65
97
129
-
-
-
-
81
81.5
81
81
81
80.5
AFUE %
-
Steady state efficiency (%)
81.5
81
81
-
No. burners
4
4
6
4
4
6
4
6
8
No. stages
21
22
22
21
22
22
22
22
22
Temperature Rise Range (ºF)
20-50°F 25-65°F 35-80°F 20-50°F 25-65°F 35-80°F 25-65°F 35-80°F 45-75°F
Gas Limit Setting (ºF)
200
235
290
200
235
290
235
290
240
Gas piping connection (in.)
3/4
3/4
3/4
3/4
3/4
3/4
3/4
3/4
3/4
DIMENSIONS (inches)
Length
89
89
89
Width
59
59
59
Height
OPERATING WT. (lbs.)
42
42
42
922
960
968
2-stage scroll
2-stage scroll
2-stage scroll
COMPRESSORS
Type
Quantity
Unit Capacity Steps (%)
1
1
1
67/100
67/100
67/100
12.2
CONDENSER COIL DATA
Face area (Sq. Ft.)
12.2
12.2
Rows
1
1
1
Fins per inch
23
23
23
Tube diameter (in./MM)
Circuitry Type
.98/25
.98/25
.98/25
2-pass Microchannel
2-pass Microchannel
2-pass Microchannel
10.56
EVAPORATOR COIL DATA
Face area (Sq. Ft.)
10.56
10.56
Rows
3
4
4
Fins per inch
15
15
15
Tube diameter
0.375
0.375
0.375
Refrigerant control
TXV
TXV
TXV
Johnson Controls Unitary Products
15
5123249-TTG-A-0515
ZVTA3 thru TA5 Two Stage Gas Physical Data (Continued)
Models
Component
Nominal Tonnage
ZVTA3
ZVTA4
ZVTA5
3.0
4.0
5.0
2
2
2
CONDENSER FAN DATA
Quantity of fans
Fan diameter (Inch)
24
24
24
Prop
Prop
Prop
Direct ECM
Direct ECM
Direct ECM
2
2
2
Motor HP each
1/3
1/3
1/3
No. speeds
Var.
Var.
Var.
RPM
850
850
850
Nominal total CFM
7000
7000
7000
Type
Drive type
Quantity of motors
BELT DRIVE EVAP FAN DATA
Quantity
Fan Size (Inch)
Type
1
1
1
12 x 9
12 x 9
12 x 9
Centrifugal
Centrifugal
Centrifugal
Motor Sheave
1VL40
1VL40
1VL34
1VL44
1VL40
1VM50
Blower Sheave
AK79
AK61
AK64
AK69
AK61
AK64
Belt
A47
A45
A47
A47
A45
A47
Motor HP each
1-1/2
1-1/2
1-1/2
1-1/2
1-1/2
2
RPM
1725
1725
1725
1725
1725
1725
56
56
56
56
56
56
Frame size
FILTERS
Quantity - Size
1.
2.
3.
4.
5.
16
4 - (24 x 16 x 2)3,4
5
4 - (24 x 16 x 4)
4 - (24 x 16 x 2)3,4
5
4 - (24 x 16 x 4)
4 - (24 x 16 x 2)3,4
4 - (24 x 16 x 4)5
1st Stage Capacity is 75% of Full Capacity.
1st Stage Capacity is 70% of Full Capacity.
2 In. Throwaway, Standard, MERV (Minimum Efficiency Reporting Value)
2 In. Pleated, Optional, MERV 7.
4 In. Pleated, Optional, MERV 13.
Johnson Controls Unitary Products
5123249-TTG-A-0515
ZVTA3 thru TA5 Unit Limitations
Unit Limitations
Size
(Tons)
TA3
(3)
TA4
(4)
TA5
(5)
Model
ZV
ZV
ZV
Johnson Controls Unitary Products
Unit Voltage
Applied Voltage
Outdoor DB Temp
Min
Max
Max (°F)
208/230-3-60
187
252
125
460-3-60
432
504
125
575-3-60
540
630
125
208/230-3-60
187
252
125
460-3-60
432
504
125
575-3-60
540
630
125
208/230-3-60
187
252
125
460-3-60
432
504
125
575-3-60
540
630
125
17
5123249-TTG-A-0515
Capacity Performance
ZVTA3 thru TA5 Cooling Capacities
ZVTA3 High Speed Compressor (3.0 Ton)
Air on
Evaporator Coil
CFM
750
900
1050
1200
1350
1500
750
900
1050
1200
1350
1500
18
WB
(°F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
49.3
43.4
37.4
35.5
49.8
44.7
39.6
37.5
35.4
50.4
46.0
41.7
39.5
37.2
50.9
47.4
43.8
41.4
39.0
48.7
46.0
43.4
40.8
50.0
48.1
45.3
42.5
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
2.0
1.9
1.9
1.9
1.9
2.0
1.9
1.9
1.9
1.9
2.0
2.0
1.9
1.9
2.0
2.0
1.9
1.9
25.0
28.1
31.2
35.4
26.8
30.6
34.3
37.4
35.4
28.6
33.0
37.4
39.4
37.2
30.4
35.5
40.6
41.3
39.0
37.9
43.7
43.3
40.8
40.4
46.8
45.3
42.5
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
41.7
38.3
34.8
32.4
42.6
39.6
36.5
34.1
31.8
43.6
40.9
38.2
35.9
33.5
44.6
42.3
40.0
37.6
35.2
43.6
41.7
39.3
37.0
44.9
43.4
41.0
38.7
2.4
2.3
2.3
2.3
2.4
2.4
2.3
2.3
2.3
2.4
2.4
2.4
2.3
2.3
2.4
2.4
2.4
2.4
2.3
2.4
2.4
2.4
2.3
2.4
2.4
2.4
2.3
19.2
25.2
31.2
32.2
22.6
27.9
33.3
34.0
31.8
26.0
30.7
35.4
35.7
33.5
29.4
33.4
37.4
37.4
35.2
36.1
39.5
39.2
37.0
38.8
41.5
40.9
38.7
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
75°F
20.9
16.7
45.5
2.2
24.1
20.2
16.2
40.8
2.1
27.4
23.6
19.5
15.9
36.1
2.1
31.2
27.1
22.6
19.5
15.7
34.0
2.1
21.8
16.8
46.2
2.2
25.9
21.3
16.6
42.1
2.1
30.0
25.7
20.9
16.4
38.0
2.1
33.8
30.2
25.0
20.9
16.2
35.8
2.1
35.4
34.7
30.0
25.3
20.6
33.6
2.1
22.7
16.8
47.0
2.2
27.7
22.3
17.0
43.5
2.2
32.7
27.9
22.3
17.0
40.0
2.1
36.4
33.4
27.4
22.2
16.7
37.7
2.1
37.2
36.9
33.2
27.5
21.8
35.3
2.1
23.6
16.8
47.7
2.2
29.4
23.4
17.4
44.8
2.2
35.3
30.0
23.7
17.5
41.9
2.2
39.0
36.6
29.8
23.6
17.1
39.5
2.1
39.0
39.0
36.5
29.7
23.0
37.1
2.1
31.2
24.5
17.8
46.1
2.2
37.9
32.1
25.0
18.0
43.8
2.2
41.5
39.8
32.2
25.0
17.6
41.3
2.1
40.8
40.8
39.7
32.0
24.3
38.9
2.1
33.0
25.6
18.2
47.5
2.2
40.5
34.3
26.4
18.6
45.7
2.2
44.1
42.9
34.7
26.4
18.1
43.2
2.2
42.5
42.5
42.5
34.2
25.5
40.6
2.1
95°F
17.1
15.0
39.3
2.7
21.8
18.4
15.0
35.4
2.7
26.5
21.8
18.0
14.2
31.7
2.7
28.7
25.2
21.0
16.8
12.6
30.3
2.7
18.8
15.0
39.5
2.7
23.6
19.3
15.0
36.5
2.7
28.5
23.6
19.0
14.5
33.5
2.7
31.0
28.0
23.1
18.2
13.4
31.8
2.7
31.8
31.8
27.2
22.0
16.9
30.2
2.7
20.4
14.9
39.8
2.7
25.4
20.2
15.0
37.7
2.7
30.4
25.5
20.1
14.7
35.3
2.7
33.2
30.7
25.2
19.7
14.2
33.4
2.7
33.5
33.5
30.3
24.7
19.0
31.6
2.7
22.1
14.9
40.1
2.7
27.2
21.1
14.9
38.8
2.7
32.3
27.3
21.1
15.0
37.0
2.7
35.4
33.5
27.3
21.1
15.0
35.0
2.7
35.2
35.2
33.5
27.3
21.1
32.9
2.7
29.0
22.0
14.9
40.0
2.7
34.3
29.1
22.1
15.2
38.8
2.7
37.7
36.2
29.4
22.6
15.8
36.6
2.7
37.0
37.0
36.6
30.0
23.3
34.3
2.7
30.8
22.9
14.9
41.1
2.7
36.2
30.9
23.2
15.4
40.6
2.8
39.9
39.0
31.5
24.0
16.6
38.1
2.7
38.7
38.7
38.7
32.6
25.4
35.7
2.7
90
22.1
26.7
31.2
33.8
24.7
29.2
33.8
35.7
33.6
27.3
31.8
36.4
37.5
35.3
29.9
34.4
39.0
39.4
37.1
37.0
41.6
41.2
38.9
39.6
44.1
43.1
40.6
18.9
24.0
29.2
30.0
22.1
26.6
31.1
31.6
30.2
25.3
29.2
33.0
33.2
31.6
28.6
31.7
34.9
34.8
32.9
34.3
36.8
36.4
34.3
36.9
38.7
38.0
35.7
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
85°F
19.0
15.9
23.0
19.3
15.6
27.0
22.7
18.8
15.0
30.0
26.1
21.8
18.1
20.3
15.9
24.8
20.3
15.8
29.3
24.7
20.0
15.4
32.4
29.1
24.0
19.5
33.6
33.5
28.6
23.7
21.6
15.9
26.5
21.3
16.0
31.5
26.7
21.2
15.8
34.8
32.1
26.3
21.0
35.3
35.3
31.8
26.1
22.9
15.9
28.3
22.2
16.2
33.8
28.6
22.4
16.2
37.2
35.0
28.6
22.4
37.1
37.1
35.0
28.5
30.1
23.2
16.3
36.1
30.6
23.6
16.6
39.6
38.0
30.8
23.8
38.9
38.9
38.2
31.0
31.9
24.2
16.5
38.4
32.6
24.8
17.0
42.0
40.9
33.1
25.2
40.6
40.6
40.6
33.4
105°F
16.8
14.8
20.8
17.5
14.2
24.7
20.2
16.7
13.1
26.5
22.9
19.1
15.3
18.3
14.5
22.4
18.2
14.0
26.5
21.9
17.6
13.2
28.6
25.6
21.1
16.6
30.2
29.4
24.7
20.0
19.8
14.2
24.0
18.9
13.8
28.3
23.6
18.5
13.3
30.8
28.4
23.1
17.9
31.6
31.6
27.8
22.5
21.2
13.9
25.7
19.6
13.6
30.1
25.4
19.4
13.4
33.0
31.1
25.2
19.2
32.9
32.9
31.0
25.1
27.3
20.3
13.3
31.9
27.1
20.3
13.5
35.1
33.9
27.2
20.5
34.3
34.3
34.1
27.6
29.0
21.0
13.1
33.8
28.8
21.2
13.5
37.3
36.6
29.2
21.9
35.7
35.7
35.7
30.2
65
14.1
14.8
18.7
15.4
20.4
16.1
22.1
16.7
23.8
17.3
25.4
11.5
12.1
15.3
12.7
17.2
13.3
19.2
13.9
21.1
14.5
23.1
Johnson Controls Unitary Products
5123249-TTG-A-0515
ZVTA3 High Speed Compressor (3.0 Ton) (Continued)
Air on
Evaporator Coil
CFM
750
900
1050
1200
1350
1500
WB
(°F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
36.9
32.4
28.6
28.1
36.4
33.4
30.4
29.5
28.6
36.0
34.4
32.3
31.0
29.6
35.6
35.4
34.1
32.4
30.6
36.4
36.0
33.8
31.6
37.4
37.8
35.2
32.6
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.1
3.0
3.0
3.0
3.1
3.0
3.0
3.1
3.1
3.0
3.0
18.6
22.8
27.1
27.8
21.6
25.2
28.8
29.3
28.6
24.7
27.7
30.6
30.7
29.6
27.8
30.1
32.3
32.1
30.6
32.5
34.1
33.6
31.6
34.9
35.8
35.0
32.6
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
115°F
16.5
14.5
34.4
3.3
19.7
16.6
13.4
29.5
3.3
22.8
18.6
15.3
12.0
25.4
3.4
24.2
20.6
17.2
13.8
10.3
26.0
3.3
17.8
14.0
33.3
3.3
21.2
17.1
13.0
30.4
3.4
24.5
20.2
16.1
11.9
27.4
3.4
26.3
23.3
19.1
14.9
10.7
27.2
3.3
28.1
26.4
22.2
17.9
13.7
27.1
3.3
19.1
13.4
32.2
3.3
22.6
17.6
12.6
31.2
3.4
26.2
21.8
16.8
11.9
29.3
3.4
28.4
26.1
21.1
16.1
11.2
28.5
3.3
29.6
29.6
25.3
20.4
15.5
27.7
3.3
20.3
12.8
31.1
3.3
24.1
18.2
12.2
32.0
3.4
27.9
23.5
17.6
11.8
31.2
3.4
30.5
28.8
23.1
17.3
11.6
29.8
3.3
30.6
30.6
28.5
22.8
17.2
28.3
3.3
25.6
18.7
11.8
32.8
3.4
29.6
25.1
18.4
11.7
33.1
3.4
32.6
31.5
25.0
18.5
12.0
31.0
3.4
31.6
31.6
31.6
25.3
19.0
28.9
3.3
27.1
19.2
11.4
33.6
3.4
31.3
26.7
19.2
11.6
35.1
3.4
34.6
34.3
27.0
19.7
12.4
32.3
3.4
32.6
32.6
32.6
27.8
20.7
29.6
3.3
90
18.2
21.6
25.0
25.7
21.2
23.9
26.6
26.9
27.1
24.1
26.2
28.2
28.2
27.7
27.0
28.4
29.8
29.5
28.3
30.7
31.4
30.8
28.9
-
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
125°F
16.3
14.3
18.6
15.6
12.6
21.0
16.9
13.9
10.9
22.0
18.3
15.2
12.2
17.3
13.5
19.9
16.0
12.0
22.5
18.5
14.6
10.7
24.0
21.0
17.1
13.3
25.4
23.5
19.7
15.9
18.4
12.6
21.2
16.3
11.4
24.1
20.0
15.2
10.4
26.0
23.7
19.0
14.3
27.7
27.4
22.8
18.3
19.4
11.8
22.6
16.7
10.8
25.7
21.6
15.9
10.2
28.0
26.5
20.9
15.4
28.3
28.3
26.0
20.6
23.9
17.1
10.3
27.3
23.1
16.5
10.0
30.0
29.2
22.8
16.5
28.9
28.9
28.9
23.0
25.2
17.4
9.7
28.8
24.7
17.2
9.7
32.0
31.9
24.7
17.5
29.6
29.6
29.6
25.3
65
9.2
9.4
12.1
9.7
13.7
9.9
15.3
10.1
16.8
10.3
18.4
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
Johnson Controls Unitary Products
19
5123249-TTG-A-0515
ZVTA3 Low Speed Compressor (3.0 Ton)
Air on
Evaporator Coil
CFM
750
900
1050
1200
1350
1500
750
900
1050
1200
1350
1500
20
WB
(°F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
38.7
34.6
30.5
29.6
39.0
35.7
32.4
31.3
30.2
39.4
36.9
34.3
33.0
31.6
39.7
38.0
36.2
34.6
33.0
39.1
38.1
36.3
34.4
40.2
40.0
37.9
35.9
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.1
1.1
19.8
24.6
29.3
29.1
23.1
27.1
31.1
30.9
30.2
26.5
29.7
32.9
32.6
31.6
29.8
32.2
34.6
34.4
33.0
34.8
36.4
36.1
34.4
-
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
31.4
29.0
26.7
25.6
32.2
30.2
28.2
27.1
25.9
32.9
31.3
29.7
28.5
27.4
33.7
32.5
31.2
30.0
28.8
33.6
32.8
31.5
30.2
34.8
34.3
33.0
31.7
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.5
1.5
1.5
1.5
1.5
1.5
17.3
21.5
25.7
25.4
20.7
23.9
27.2
26.9
25.9
24.0
26.3
28.6
28.4
27.4
27.4
28.7
30.0
29.9
28.8
31.1
31.5
31.4
30.2
-
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
75°F
16.4
13.1
35.0
1.4
20.6
16.6
12.7
31.8
1.4
24.8
20.2
16.3
12.5
28.6
1.4
26.4
23.7
18.6
16.3
12.7
27.6
1.4
18.3
13.4
35.6
1.4
22.4
17.8
13.1
33.0
1.4
26.6
22.1
17.5
13.0
30.3
1.4
28.7
26.5
20.9
17.6
13.1
29.2
1.4
30.2
30.2
26.4
22.1
17.8
28.0
1.4
20.1
13.8
36.2
1.4
24.3
18.9
13.6
34.1
1.4
28.5
24.1
18.8
13.5
32.0
1.4
30.9
29.2
23.1
18.8
13.5
30.7
1.4
31.6
31.6
29.2
24.0
18.9
29.5
1.4
22.0
14.2
36.7
1.4
26.2
20.1
14.0
35.2
1.4
30.3
26.0
20.0
14.0
33.7
1.4
33.2
32.0
25.4
20.0
13.9
32.3
1.4
33.0
33.0
31.9
26.0
20.0
30.9
1.4
28.0
21.3
14.5
36.4
1.4
32.2
28.0
21.2
14.5
35.4
1.4
35.4
34.8
27.7
21.2
14.4
33.9
1.4
34.4
34.4
34.4
27.9
21.1
32.3
1.3
29.9
22.4
15.0
37.5
1.3
34.0
30.0
22.5
14.9
37.1
1.3
37.7
37.5
29.9
22.4
14.8
35.5
1.3
35.9
35.9
35.9
29.8
22.2
33.8
1.3
95°F
13.6
9.9
27.8
1.9
17.8
14.0
10.2
26.1
1.9
21.9
18.1
14.1
10.0
24.6
1.9
23.8
22.2
17.9
13.7
9.4
24.1
1.9
15.3
9.9
28.4
1.9
19.4
14.9
10.4
27.2
1.9
23.5
19.9
15.2
10.4
26.0
1.9
25.9
24.9
19.9
14.8
9.8
25.3
1.9
25.9
25.9
24.6
19.3
14.0
24.6
1.9
17.0
10.0
29.1
1.9
21.1
15.9
10.7
28.3
1.9
25.2
21.8
16.2
10.7
27.4
1.9
28.0
27.6
21.8
16.0
10.2
26.5
1.8
27.4
27.4
27.4
21.3
15.2
25.6
1.8
18.7
10.0
29.7
1.9
22.8
16.8
10.9
29.5
1.8
26.8
23.6
17.3
11.1
28.8
1.8
29.9
29.9
23.8
17.2
10.6
27.7
1.8
28.8
28.8
28.8
23.4
16.5
26.6
1.8
24.4
17.8
11.1
30.6
1.8
28.5
25.4
18.4
11.4
30.2
1.8
31.4
31.4
25.7
18.4
11.1
28.9
1.8
30.2
30.2
30.2
25.4
17.7
27.7
1.8
26.1
18.7
11.3
31.7
1.8
30.1
27.3
19.5
11.8
31.6
1.8
32.9
32.9
27.7
19.6
11.5
30.1
1.8
31.7
31.7
31.7
27.4
18.9
28.7
1.8
90
18.5
23.0
27.5
27.3
21.9
25.5
29.1
28.9
28.0
25.2
28.0
30.7
30.5
29.5
28.6
30.5
32.3
32.1
30.9
32.9
33.9
33.8
32.3
18.0
20.7
23.5
23.3
20.5
22.7
24.8
24.7
24.5
23.0
24.6
26.1
26.0
25.6
25.6
26.5
27.4
27.3
26.6
28.4
28.7
28.6
27.7
-
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
85°F
15.0
11.5
19.2
15.3
11.4
23.3
19.1
15.2
11.3
25.1
22.9
18.3
15.0
16.8
11.7
20.9
16.4
11.8
25.1
21.0
16.3
11.7
27.3
25.7
20.4
16.2
28.0
28.0
25.5
20.7
18.6
11.9
22.7
17.4
12.1
26.8
22.9
17.5
12.1
29.5
28.4
22.5
17.4
29.5
29.5
28.3
22.7
20.3
12.1
24.5
18.5
12.5
28.6
24.8
18.7
12.5
31.7
31.2
24.6
18.6
30.9
30.9
30.9
24.7
26.2
19.5
12.8
30.3
26.7
19.8
12.9
33.8
33.8
26.7
19.8
32.3
32.3
32.3
26.6
28.0
20.6
13.1
32.1
28.6
21.0
13.4
35.4
35.4
28.8
21.0
33.8
33.8
33.8
28.6
105°F
13.9
9.9
17.0
13.3
9.6
20.1
16.7
12.7
8.8
21.7
20.1
15.9
11.8
14.9
9.3
18.2
13.8
9.3
21.5
18.3
13.7
9.0
23.7
22.8
18.0
13.2
24.5
24.5
22.3
17.4
15.8
8.6
19.4
14.2
9.0
23.0
19.8
14.6
9.3
25.7
25.5
20.1
14.7
25.6
25.6
25.3
19.5
16.8
7.9
20.6
14.7
8.8
24.4
21.4
15.5
9.5
27.3
27.3
22.1
16.1
26.6
26.6
26.6
21.6
21.8
15.2
8.5
25.8
23.0
16.4
9.7
28.6
28.6
24.2
17.5
27.7
27.7
27.7
23.7
23.0
15.6
8.3
27.3
24.6
17.3
9.9
30.0
30.0
26.3
18.9
28.7
28.7
28.7
25.9
65
11.0
11.5
15.9
11.9
17.0
12.3
18.2
12.7
19.4
13.1
20.5
7.6
8.4
12.5
9.2
13.7
10.0
15.0
10.8
16.2
11.6
17.5
Johnson Controls Unitary Products
5123249-TTG-A-0515
ZVTA3 Low Speed Compressor (3.0 Ton) (Continued)
Air on
Evaporator Coil
CFM
750
900
1050
1200
1350
1500
WB
(°F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
24.2
23.1
22.5
22.5
24.7
24.2
23.7
23.5
23.2
25.2
25.3
25.0
24.4
23.9
25.7
26.5
26.3
25.4
24.5
27.6
27.5
26.3
25.1
28.7
28.8
27.3
25.7
2.2
2.2
2.2
2.1
2.2
2.2
2.1
2.1
2.1
2.2
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
18.6
20.0
21.3
21.3
20.3
21.4
22.4
22.4
22.4
22.1
22.8
23.6
23.6
23.6
23.8
24.3
24.7
24.7
24.5
25.7
25.9
25.9
25.1
-
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
115°F
14.3
9.9
20.5
2.5
16.3
12.6
8.9
20.1
2.5
18.3
15.3
11.4
7.6
20.4
2.4
19.6
18.0
13.9
9.9
5.9
21.0
2.4
14.5
8.6
20.9
2.5
17.0
12.6
8.2
21.2
2.4
19.5
16.6
12.2
7.7
21.5
2.4
21.5
20.6
16.1
11.6
7.1
21.7
2.4
22.4
22.4
20.1
15.5
10.9
21.9
2.4
14.6
7.2
21.3
2.4
17.7
12.6
7.4
22.3
2.4
20.8
17.9
12.9
7.8
22.7
2.4
23.4
23.3
18.3
13.3
8.3
22.4
2.4
23.6
23.6
23.2
17.7
12.2
22.1
2.4
14.8
5.8
21.7
2.4
18.4
12.6
6.7
23.5
2.4
22.0
19.3
13.6
7.9
23.8
2.4
24.7
24.7
20.5
15.0
9.4
23.1
2.4
24.5
24.5
24.5
19.9
13.5
22.3
2.4
19.1
12.5
6.0
24.6
2.4
23.2
20.6
14.3
8.0
24.9
2.4
25.9
25.9
22.7
16.6
10.6
23.7
2.4
25.1
25.1
25.1
22.1
14.8
22.5
2.4
19.8
12.5
5.2
25.7
2.4
24.5
21.9
15.0
8.1
26.1
2.4
27.1
27.1
24.8
18.3
11.8
24.4
2.4
25.7
25.7
25.7
24.3
16.1
22.7
2.4
90
19.3
19.2
19.1
19.2
21.1
21.1
21.1
21.2
21.3
21.7
22.0
22.1
22.2
22.3
23.0
23.1
23.2
22.5
-
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
125°F
14.6
10.0
15.6
11.9
8.3
16.5
13.9
10.1
6.4
17.5
15.8
11.9
8.0
14.0
7.9
15.8
11.4
7.1
17.5
15.0
10.7
6.3
19.3
18.5
14.2
10.0
20.3
20.3
17.8
13.6
13.5
5.8
16.0
10.9
5.8
18.6
16.0
11.2
6.3
21.2
21.1
16.5
11.9
21.3
21.3
21.1
15.9
12.9
3.7
16.2
10.4
4.6
19.6
17.1
11.7
6.3
22.2
22.2
18.8
13.8
22.3
22.3
22.3
18.2
16.5
9.9
3.4
20.6
18.2
12.2
6.3
23.2
23.2
21.1
15.8
22.5
22.5
22.5
20.5
-
65
4.1
5.7
9.4
7.3
10.7
8.8
12.0
10.4
13.3
-
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
Johnson Controls Unitary Products
21
5123249-TTG-A-0515
ZVTA4 High Speed Compressor (4.0 Ton)
Air on
Evaporator Coil
CFM
1000
1200
1400
1600
1800
2000
1000
1200
1400
1600
1800
2000
22
WB
(°F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
67.2
60.1
53.1
49.5
67.6
61.3
54.9
52.1
49.2
68.0
62.4
56.8
54.7
52.6
68.4
63.5
58.6
57.3
56.0
64.6
60.4
59.9
59.4
65.7
62.2
62.5
62.8
2.6
2.5
2.5
2.5
2.6
2.6
2.5
2.5
2.5
2.6
2.6
2.5
2.5
2.5
2.7
2.6
2.6
2.6
2.5
2.7
2.6
2.6
2.6
2.7
2.6
2.6
2.6
32.6
38.7
44.8
49.4
35.7
42.0
48.2
52.0
49.2
38.8
45.2
51.7
54.5
52.6
41.9
48.5
55.1
57.1
56.0
51.8
58.5
59.7
59.2
55.1
61.9
62.2
62.5
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
61.1
54.0
46.8
45.3
60.3
54.5
48.7
47.6
46.5
59.6
55.1
50.5
49.9
49.2
58.9
55.6
52.4
52.2
52.0
56.2
54.3
54.5
54.8
56.8
56.1
56.8
57.5
3.2
3.1
3.1
3.1
3.2
3.2
3.1
3.1
3.1
3.2
3.2
3.1
3.1
3.1
3.2
3.2
3.2
3.1
3.1
3.2
3.2
3.2
3.1
3.2
3.2
3.2
3.2
26.5
34.5
42.5
45.2
31.4
38.3
45.1
47.4
46.5
36.4
42.0
47.7
49.6
49.2
41.3
45.8
50.3
51.8
52.0
49.6
52.9
54.0
54.8
55.5
56.2
56.9
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
75°F
27.0
21.4
64.1
2.9
33.3
27.9
22.5
57.1
2.8
39.6
34.5
27.9
22.6
50.0
2.8
45.2
41.0
32.4
28.1
21.7
47.4
2.8
28.7
21.7
64.0
2.9
35.6
29.3
22.9
57.9
2.9
42.5
36.8
29.4
23.1
51.8
2.8
48.1
44.3
35.3
29.7
22.5
49.8
2.8
49.2
49.2
44.1
36.3
28.6
47.9
2.8
30.5
22.1
63.8
2.9
37.9
30.6
23.3
58.7
2.9
45.4
39.1
30.9
23.6
53.7
2.8
51.0
47.6
38.2
31.3
23.2
52.3
2.8
52.6
52.6
47.5
39.0
30.5
50.9
2.8
32.2
22.5
63.7
2.9
40.2
31.9
23.6
59.6
2.9
48.2
41.4
32.5
24.1
55.5
2.9
54.0
50.8
41.0
32.9
24.0
54.7
2.8
56.0
56.0
51.0
41.7
32.5
54.0
2.8
42.5
33.2
24.0
60.4
2.9
51.1
43.7
34.0
24.6
57.3
2.9
56.9
54.1
43.9
34.5
24.7
57.2
2.9
59.2
59.2
54.5
44.4
34.4
57.1
2.8
44.8
34.6
24.3
61.2
2.9
54.0
46.0
35.5
25.1
59.2
2.9
59.8
57.4
46.8
36.1
25.5
59.6
2.9
62.5
62.5
58.0
47.2
36.3
60.1
2.9
95°F
22.4
18.3
55.6
3.6
29.5
24.5
19.5
49.9
3.6
36.6
30.7
25.3
19.9
44.2
3.5
41.1
36.9
31.1
25.3
19.6
42.9
3.6
25.0
18.6
55.2
3.6
32.0
25.8
19.6
50.5
3.6
39.1
33.0
26.6
20.1
45.9
3.6
43.8
40.3
33.5
26.8
20.1
45.0
3.6
46.5
46.5
40.5
33.5
26.5
44.0
3.6
27.6
18.9
54.7
3.6
34.6
27.2
19.7
51.2
3.6
41.5
35.4
27.8
20.3
47.6
3.6
46.6
43.6
35.9
28.3
20.6
47.1
3.6
49.2
49.2
44.0
36.2
28.4
46.6
3.6
30.3
19.2
54.3
3.6
37.1
28.5
19.8
51.8
3.6
44.0
37.7
29.1
20.4
49.3
3.6
49.4
47.0
38.3
29.7
21.1
49.2
3.6
52.0
52.0
47.6
39.0
30.4
49.1
3.6
39.7
29.8
19.9
52.5
3.6
46.5
40.1
30.3
20.6
51.0
3.6
52.2
50.3
40.8
31.2
21.6
51.3
3.6
54.8
54.8
51.2
41.7
32.3
51.6
3.6
42.2
31.1
20.1
53.1
3.6
48.9
42.4
31.6
20.8
52.7
3.6
54.9
53.7
43.2
32.6
22.1
53.4
3.6
56.9
56.9
54.7
44.5
34.2
54.2
3.6
90
29.5
36.6
43.6
47.3
33.6
40.1
46.7
49.7
47.9
37.6
43.6
49.7
52.1
50.9
41.6
47.1
52.7
54.4
54.0
50.7
55.7
56.8
57.1
54.2
58.7
59.2
59.7
25.0
33.1
41.3
42.8
29.8
36.6
43.4
44.8
44.0
34.6
40.0
45.5
46.7
46.6
39.4
43.5
47.7
48.7
49.1
47.0
49.8
50.7
51.6
50.4
51.9
52.6
53.4
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
85°F
24.7
19.8
31.4
26.2
21.0
38.1
32.6
26.6
21.3
43.1
39.0
31.8
26.7
26.9
20.2
33.8
27.5
21.3
40.8
34.9
28.0
21.6
46.0
42.3
34.4
28.3
47.9
47.9
42.3
34.9
29.1
20.5
36.3
28.9
21.5
43.4
37.2
29.4
22.0
48.8
45.6
37.0
29.8
50.9
50.9
45.8
37.6
31.2
20.9
38.7
30.2
21.7
46.1
39.6
30.8
22.3
51.7
48.9
39.7
31.3
54.0
54.0
49.3
40.4
41.1
31.5
22.0
48.8
41.9
32.2
22.6
54.5
52.2
42.3
32.9
57.1
57.1
52.8
43.1
43.5
32.9
22.2
51.5
44.2
33.6
23.0
57.4
55.5
45.0
34.4
59.7
59.7
56.3
45.8
105°F
21.0
17.1
28.1
23.0
18.0
35.1
28.9
23.6
18.2
38.8
34.9
29.2
23.5
23.4
17.1
30.4
24.2
18.0
37.3
31.3
24.8
18.3
41.6
38.3
31.6
24.9
44.0
44.0
38.5
31.5
25.8
17.1
32.7
25.3
17.9
39.6
33.6
26.0
18.5
44.3
41.8
34.1
26.3
46.6
46.6
42.2
34.2
28.2
17.0
35.0
26.5
17.9
41.8
35.9
27.2
18.6
47.0
45.3
36.5
27.8
49.1
49.1
45.8
36.9
37.3
27.6
17.9
44.0
38.2
28.5
18.7
49.7
48.8
39.0
29.2
51.6
51.6
49.5
39.6
39.6
28.8
17.9
46.2
40.5
29.7
18.8
52.4
52.2
41.4
30.6
53.4
53.4
53.1
42.3
65
20.6
21.3
27.5
21.9
29.5
22.5
31.4
23.2
33.3
23.8
35.3
17.9
18.2
24.6
18.6
26.3
19.0
28.0
19.4
29.7
19.7
31.4
Johnson Controls Unitary Products
5123249-TTG-A-0515
ZVTA4 High Speed Compressor (4.0 Ton) (Continued)
Air on
Evaporator Coil
CFM
1000
1200
1400
1600
1800
2000
WB
(°F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
50.2
45.9
41.6
40.4
50.0
46.6
43.1
42.4
41.6
49.9
47.3
44.7
44.3
43.9
49.7
48.0
46.2
46.2
46.2
48.7
47.7
48.1
48.5
49.5
49.3
50.1
50.9
4.1
4.0
4.0
4.0
4.1
4.0
4.0
4.0
4.1
4.1
4.0
4.0
4.0
4.1
4.1
4.1
4.0
4.0
4.1
4.1
4.1
4.1
4.1
4.1
4.1
4.1
4.0
23.4
31.8
40.1
40.4
28.1
34.9
41.8
42.1
41.6
32.7
38.1
43.4
43.9
43.9
37.4
41.2
45.0
45.6
46.2
44.4
46.7
47.3
48.0
47.5
48.3
49.1
49.9
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
115°F
19.6
15.9
44.7
4.5
26.6
21.5
16.4
41.8
4.5
33.7
27.2
21.9
16.5
39.0
4.4
36.6
32.9
27.3
21.7
16.2
38.0
4.5
21.8
15.5
44.9
4.5
28.7
22.5
16.3
42.6
4.5
35.6
29.5
23.0
16.6
40.4
4.4
39.3
36.4
29.8
23.1
16.4
39.7
4.5
41.6
41.6
36.5
29.6
22.7
39.1
4.6
24.0
15.2
45.0
4.5
30.8
23.5
16.2
43.4
4.5
37.6
31.8
24.2
16.7
41.7
4.5
41.9
40.0
32.2
24.4
16.6
41.5
4.5
43.9
43.9
40.3
32.2
24.2
41.2
4.6
26.1
14.9
45.2
4.5
32.8
24.4
16.1
44.2
4.5
39.5
34.0
25.4
16.7
43.1
4.5
44.6
43.6
34.7
25.8
16.9
43.2
4.5
46.2
46.2
44.0
34.9
25.7
43.3
4.5
34.9
25.4
15.9
45.0
4.5
41.5
36.3
26.6
16.8
44.5
4.5
47.3
47.2
37.2
27.1
17.1
45.0
4.5
48.0
48.0
47.8
37.5
27.2
45.4
4.5
37.0
26.4
15.8
45.8
4.5
43.4
38.6
27.7
16.9
45.9
4.5
49.1
49.1
39.6
28.5
17.4
46.7
4.5
49.9
49.9
49.9
40.1
28.7
47.6
4.5
90
21.9
30.4
38.9
37.9
26.4
33.2
40.1
39.5
38.8
30.9
36.1
41.2
41.0
40.7
35.5
38.9
42.4
42.5
42.6
41.8
43.5
44.0
44.5
-
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
125°F
18.3
14.6
25.2
20.0
14.9
32.2
25.4
20.1
14.8
34.4
30.8
25.4
19.9
20.2
14.0
27.0
20.8
14.6
33.9
27.7
21.3
14.8
37.0
34.5
27.9
21.2
38.8
38.8
34.5
27.6
22.1
13.3
28.9
21.6
14.4
35.6
29.9
22.4
14.9
39.6
38.2
30.4
22.5
40.7
40.7
38.4
30.2
24.1
12.7
30.7
22.4
14.2
37.3
32.2
23.5
14.9
42.2
41.9
32.9
23.8
42.6
42.6
42.3
32.8
32.5
23.2
13.9
39.0
34.4
24.7
14.9
44.0
44.0
35.4
25.1
44.5
44.5
44.5
35.4
34.3
24.0
13.7
40.7
36.7
25.8
14.9
45.5
45.5
37.9
26.4
46.4
46.4
46.4
38.0
65
14.5
14.6
20.8
14.7
22.1
14.8
23.3
14.9
24.6
15.0
25.9
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
Johnson Controls Unitary Products
23
5123249-TTG-A-0515
ZVTA4 Low Speed Compressor (4.0 Ton)
Air on
Evaporator Coil
CFM
1000
1200
1400
1600
1800
2000
1000
1200
1400
1600
1800
2000
24
WB
(°F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
53.1
46.5
39.9
40.1
52.8
47.4
41.9
42.1
42.3
52.5
48.2
44.0
44.2
44.3
52.2
49.1
46.1
46.2
46.3
50.0
48.1
48.2
48.3
50.9
50.2
50.3
50.4
1.6
1.6
1.7
1.7
1.6
1.6
1.6
1.6
1.7
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
27.6
33.7
39.9
40.0
31.9
36.9
41.9
42.0
42.2
36.3
40.1
43.8
44.1
44.3
40.6
43.2
45.8
46.1
46.3
46.4
47.7
48.1
48.3
-
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
43.5
39.5
35.6
35.2
43.4
40.3
37.1
37.0
36.9
43.4
41.0
38.6
38.7
38.9
43.4
41.7
40.0
40.5
41.0
42.4
41.5
42.3
43.1
43.2
43.0
44.1
45.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
36.9
36.8
36.7
33.9
36.2
38.4
38.5
38.6
37.0
38.5
39.9
40.2
40.5
40.8
41.4
41.9
42.4
-
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
75°F
22.9
18.3
48.3
1.9
28.4
23.1
17.8
43.0
1.9
34.0
28.0
22.3
17.6
37.7
1.9
36.4
32.9
25.3
22.6
17.5
37.6
1.9
24.7
17.5
48.1
1.9
30.5
24.0
17.6
43.8
1.9
36.2
30.5
23.7
17.6
39.5
1.9
39.5
37.0
28.6
24.1
17.7
39.5
1.9
42.2
42.2
37.1
30.6
24.2
39.6
1.9
26.5
16.8
47.9
1.9
32.5
24.9
17.3
44.6
1.9
38.4
33.0
25.1
17.7
41.3
1.9
42.6
41.1
32.0
25.7
18.0
41.5
1.9
44.3
44.3
41.5
33.6
25.8
41.6
1.9
28.4
16.1
47.8
1.9
34.5
25.8
17.1
45.4
1.9
40.7
35.6
26.5
17.8
43.0
1.9
45.7
45.3
35.3
27.2
18.2
43.4
1.9
46.3
46.3
45.8
36.7
27.5
43.7
1.9
36.5
26.7
16.9
46.2
1.9
42.9
38.1
27.9
17.9
44.8
1.9
48.1
48.1
38.6
28.8
18.5
45.3
1.9
48.3
48.3
48.3
39.7
29.1
45.7
1.9
38.6
27.6
16.6
47.0
1.9
45.1
40.6
29.3
18.0
46.6
1.9
50.1
50.1
42.0
30.3
18.7
47.2
1.9
50.4
50.4
50.4
42.7
30.7
47.8
1.9
95°F
21.8
15.7
38.6
2.6
26.1
20.5
15.0
35.9
2.6
30.4
25.3
19.9
14.6
33.2
2.6
32.6
30.1
24.9
19.8
14.6
32.8
2.6
22.6
14.4
39.0
2.6
27.5
21.0
14.6
36.7
2.6
32.3
27.7
21.2
14.7
34.5
2.6
35.6
34.4
27.8
21.2
14.6
34.4
2.6
36.7
36.7
34.4
27.7
21.1
34.3
2.6
23.5
13.0
39.3
2.6
28.9
21.6
14.3
37.5
2.6
34.3
30.1
22.5
14.8
35.8
2.6
38.5
38.5
30.7
22.7
14.7
36.0
2.6
38.6
38.6
38.6
30.5
22.2
36.3
2.6
24.3
11.7
39.6
2.6
30.3
22.1
13.9
38.3
2.6
36.2
32.6
23.8
14.9
37.1
2.6
40.2
40.2
33.6
24.1
14.7
37.7
2.6
40.5
40.5
40.5
33.3
23.3
38.2
2.6
31.7
22.6
13.6
39.1
2.5
38.2
35.0
25.0
15.1
38.5
2.5
41.9
41.9
36.5
25.6
14.7
39.3
2.5
42.4
42.4
42.4
36.1
24.3
40.1
2.5
33.1
23.2
13.3
39.9
2.5
40.2
37.4
26.3
15.2
39.8
2.5
43.6
43.6
39.4
27.1
14.7
40.9
2.5
44.3
44.3
44.3
38.9
25.4
42.1
2.5
90
27.7
32.7
37.7
37.6
31.4
35.4
39.4
39.4
39.5
35.1
38.1
41.1
41.3
41.4
38.8
40.8
42.9
43.1
43.4
43.6
44.6
45.0
45.4
34.3
34.2
34.2
32.8
34.2
35.6
35.7
35.8
35.1
36.1
37.0
37.2
37.5
37.9
38.3
38.7
39.2
-
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
85°F
22.3
17.0
27.2
21.8
16.4
32.2
26.6
21.1
16.1
34.5
31.5
25.1
21.2
23.7
16.0
29.0
22.5
16.1
34.3
29.1
22.5
16.2
37.6
35.7
28.2
22.7
39.5
39.5
35.7
29.2
25.0
14.9
30.7
23.2
15.8
36.4
31.6
23.8
16.3
40.6
39.9
31.3
24.2
41.4
41.4
40.2
32.1
26.3
13.9
32.4
24.0
15.5
38.5
34.1
25.1
16.4
43.1
43.1
34.4
25.7
43.4
43.4
43.4
35.0
34.1
24.7
15.2
40.6
36.5
26.5
16.5
45.0
45.0
37.5
27.2
45.4
45.4
45.4
37.9
35.8
25.4
14.9
42.7
39.0
27.8
16.6
46.8
46.8
40.7
28.7
47.4
47.4
47.4
40.8
105°F
21.3
14.4
24.9
19.3
13.6
28.6
24.1
18.6
13.0
30.9
29.0
23.5
18.1
21.7
13.0
26.0
19.5
13.1
30.2
26.1
19.6
13.1
33.5
32.7
26.1
19.5
34.2
34.2
32.6
26.0
22.2
11.5
27.0
19.8
12.6
31.9
28.1
20.7
13.2
35.7
35.7
28.7
21.0
35.8
35.8
35.8
28.7
22.6
10.1
28.1
20.1
12.1
33.6
30.2
21.7
13.3
37.2
37.2
31.3
22.4
37.5
37.5
37.5
31.5
29.1
20.4
11.6
35.2
32.2
22.8
13.4
38.7
38.7
33.9
23.8
39.2
39.2
39.2
34.3
30.2
20.7
11.1
36.9
34.2
23.8
13.4
40.2
40.2
36.5
25.3
40.8
40.8
40.8
37.1
65
16.0
16.2
22.6
16.3
24.0
16.5
25.4
16.6
26.7
16.7
28.1
12.7
13.0
19.3
13.2
20.7
13.5
22.2
13.8
23.6
14.0
25.0
Johnson Controls Unitary Products
5123249-TTG-A-0515
ZVTA4 Low Speed Compressor (4.0 Ton) (Continued)
Air on
Evaporator Coil
CFM
1000
1200
1400
1600
1800
2000
WB
(°F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
33.8
32.3
30.8
30.4
34.5
33.2
31.9
31.9
31.8
35.2
34.0
33.1
33.3
33.6
35.9
34.9
34.2
34.8
35.4
35.7
35.4
36.3
37.2
36.6
36.5
37.8
39.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
2.9
3.0
3.0
3.0
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
31.7
31.7
31.6
31.7
32.3
32.9
33.0
33.1
33.3
33.7
34.0
34.3
34.5
35.0
35.2
35.6
35.9
36.4
36.4
36.9
37.4
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
115°F
20.8
13.1
28.9
3.4
23.8
18.0
12.3
28.8
3.4
26.7
23.0
17.2
11.5
28.4
3.4
29.1
27.9
22.2
16.5
10.8
28.0
3.4
20.8
11.6
30.0
3.4
24.5
18.1
11.6
29.7
3.4
28.1
24.5
18.0
11.5
29.3
3.4
31.4
31.0
24.5
17.9
11.3
29.3
3.4
31.6
31.6
30.9
24.2
17.6
29.3
3.4
20.9
10.0
31.1
3.3
25.2
18.1
11.0
30.6
3.4
29.5
26.1
18.9
11.6
30.3
3.4
33.0
33.0
26.7
19.3
11.8
30.6
3.4
33.1
33.1
33.1
27.0
19.3
30.9
3.4
20.9
8.5
32.1
3.3
25.9
18.1
10.3
31.5
3.3
30.9
27.7
19.7
11.6
31.3
3.4
34.3
34.3
29.0
20.7
12.3
32.0
3.3
34.5
34.5
34.5
29.7
21.1
32.6
3.3
26.6
18.1
9.7
32.4
3.3
32.3
29.3
20.5
11.6
32.3
3.3
35.6
35.6
31.3
22.1
12.8
33.3
3.3
35.9
35.9
35.9
32.5
22.8
34.2
3.3
27.3
18.1
9.0
33.3
3.3
33.7
30.9
21.3
11.7
33.3
3.3
36.9
36.9
33.6
23.5
13.3
34.6
3.3
37.4
37.4
37.4
35.2
24.6
35.9
3.3
90
30.6
30.3
30.1
30.2
30.3
31.4
31.2
31.1
31.3
31.5
32.2
32.1
32.4
32.7
-
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
125°F
20.4
11.8
22.7
16.8
10.9
24.9
21.8
15.9
10.0
27.4
26.8
20.8
14.8
20.0
10.2
23.0
16.6
10.1
26.0
23.0
16.5
10.0
29.1
29.1
22.8
16.2
29.1
29.1
29.1
22.5
19.5
8.5
23.3
16.3
9.3
27.1
24.1
17.0
9.9
30.2
30.2
24.8
17.6
30.3
30.3
30.3
25.2
19.1
6.9
23.7
16.1
8.5
28.2
25.3
17.6
9.9
31.3
31.3
26.8
18.9
31.5
31.5
31.5
27.9
24.0
15.9
7.7
29.3
26.5
18.2
9.9
32.4
32.4
28.7
20.3
32.7
32.7
32.7
30.7
-
65
8.9
9.6
15.8
10.4
17.9
11.1
20.0
11.9
22.1
-
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
Johnson Controls Unitary Products
25
5123249-TTG-A-0515
ZVTA5 High Speed Compressor (5.0 Ton)
Air on
Evaporator Coil
CFM
1250
1500
1750
2000
2250
2500
1250
1500
1750
2000
2250
2500
26
WB
(°F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
84.7
75.5
66.4
61.3
84.6
76.3
67.9
63.9
60.0
84.6
77.0
69.4
66.5
63.7
84.6
77.7
70.9
69.2
67.4
78.5
72.4
71.8
71.1
79.2
74.0
74.4
74.7
3.4
3.4
3.3
3.2
3.4
3.4
3.3
3.3
3.2
3.4
3.4
3.3
3.3
3.2
3.4
3.4
3.3
3.3
3.3
3.4
3.3
3.3
3.3
3.4
3.3
3.3
3.3
41.4
49.5
57.6
61.0
44.6
52.7
60.8
63.5
60.0
47.8
55.9
64.0
66.0
63.7
50.9
59.1
67.3
68.5
67.4
62.3
70.5
71.0
70.3
65.5
73.7
73.5
73.2
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
77.0
67.6
58.2
56.9
75.6
67.8
59.9
58.8
57.6
74.2
67.9
61.6
60.6
59.5
72.8
68.1
63.3
62.4
61.5
68.2
65.1
64.2
63.4
68.4
66.8
66.1
65.4
4.2
4.1
4.1
4.0
4.2
4.1
4.1
4.0
4.0
4.2
4.1
4.1
4.0
4.0
4.1
4.1
4.1
4.1
4.0
4.1
4.1
4.1
4.1
4.1
4.1
4.1
4.1
36.8
45.6
54.3
56.0
40.6
48.6
56.7
57.9
57.6
44.3
51.7
59.1
59.8
59.5
48.1
54.8
61.4
61.7
61.5
57.8
63.8
63.6
63.4
60.9
66.1
65.5
64.8
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
75°F
36.0
30.6
80.9
3.8
43.0
36.5
30.0
71.6
3.7
50.0
42.4
36.2
29.8
62.3
3.7
54.6
48.3
40.7
36.0
29.9
59.1
3.6
37.2
29.7
80.1
3.8
45.1
37.4
29.8
72.0
3.7
53.0
45.1
37.6
29.8
63.9
3.7
58.1
52.8
44.0
37.5
29.9
61.4
3.6
60.0
60.0
52.9
45.2
37.6
58.8
3.6
38.3
28.8
79.4
3.8
47.1
38.3
29.6
72.5
3.7
55.9
47.8
39.0
29.9
65.5
3.7
61.6
57.3
47.3
39.0
29.9
63.6
3.7
63.7
63.7
57.5
48.2
38.8
61.6
3.6
39.4
28.0
78.7
3.8
49.2
39.3
29.3
72.9
3.7
58.9
50.6
40.3
30.0
67.1
3.7
65.2
61.9
50.6
40.5
29.9
65.8
3.7
67.4
67.4
62.1
51.1
40.1
64.4
3.7
51.2
40.2
29.1
73.4
3.7
61.9
53.3
41.7
30.1
68.7
3.7
68.7
66.4
53.9
42.0
29.9
68.0
3.7
70.3
70.3
66.8
54.0
41.3
67.3
3.7
53.3
41.1
28.9
73.8
3.7
64.9
56.0
43.1
30.1
70.4
3.7
72.2
70.9
57.2
43.6
29.9
70.2
3.7
73.2
73.2
71.4
57.0
42.5
70.1
3.7
95°F
32.1
27.3
70.3
4.8
39.4
33.1
26.9
62.8
4.7
46.6
38.9
32.6
26.2
55.3
4.6
50.4
44.7
38.3
31.8
25.3
53.6
4.6
33.4
26.2
69.0
4.8
41.2
33.8
26.4
62.9
4.7
49.1
41.5
33.8
26.1
56.8
4.6
53.5
49.1
41.1
33.2
25.2
55.3
4.6
57.6
56.7
48.5
40.2
32.0
53.8
4.5
34.7
25.0
67.7
4.7
43.1
34.5
25.9
63.0
4.7
51.5
44.0
35.0
26.0
58.3
4.6
56.6
53.5
44.0
34.6
25.1
57.0
4.6
59.5
59.5
53.0
43.2
33.3
55.7
4.5
36.0
23.9
66.5
4.7
45.0
35.2
25.4
63.1
4.7
54.0
46.5
36.2
25.8
59.8
4.6
59.8
57.8
46.9
36.0
25.0
58.7
4.6
61.5
61.5
57.6
46.1
34.6
57.6
4.6
46.9
35.9
24.9
63.3
4.6
56.4
49.0
37.4
25.7
61.3
4.6
62.9
62.2
49.8
37.3
24.9
60.4
4.6
63.4
63.4
62.2
49.0
35.9
59.5
4.6
48.7
36.6
24.4
63.4
4.6
58.9
51.6
38.5
25.5
62.7
4.6
65.5
65.5
52.6
38.7
24.8
62.1
4.6
64.8
64.8
64.8
51.9
37.2
61.5
4.6
90
39.1
47.5
56.0
58.5
42.6
50.7
58.8
60.7
58.8
46.0
53.8
61.5
62.9
61.6
49.5
56.9
64.3
65.1
64.4
60.1
67.1
67.3
66.8
63.2
69.9
69.5
69.0
34.7
43.5
52.2
52.5
38.6
46.4
54.2
54.3
53.8
42.4
49.3
56.1
56.0
55.7
46.2
52.2
58.1
57.8
57.5
55.0
60.0
59.6
59.1
57.9
61.9
61.3
60.7
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
85°F
34.1
29.0
41.2
34.8
28.5
48.3
40.7
34.4
28.0
52.5
46.5
39.5
33.9
35.3
28.0
43.1
35.6
28.1
51.0
43.3
35.7
28.0
55.8
50.9
42.6
35.4
58.8
58.6
50.7
42.7
36.5
26.9
45.1
36.4
27.7
53.7
45.9
37.0
27.9
59.1
55.4
45.7
36.8
61.6
61.6
55.3
45.7
37.7
25.9
47.1
37.2
27.4
56.4
48.5
38.2
27.9
62.5
59.8
48.8
38.2
64.4
64.4
59.9
48.6
49.0
38.0
27.0
59.2
51.2
39.5
27.9
65.8
64.3
51.8
39.7
66.8
66.8
64.5
51.5
51.0
38.8
26.7
61.9
53.8
40.8
27.8
69.1
68.7
54.9
41.1
69.0
69.0
69.0
54.5
105°F
29.7
24.6
37.1
30.7
24.4
44.5
36.8
30.4
24.0
47.7
42.9
36.5
30.0
31.0
23.5
38.9
31.4
23.9
46.7
39.3
31.6
23.8
50.8
47.3
39.3
31.3
53.8
53.8
46.9
38.7
32.4
22.3
40.7
32.1
23.5
49.0
41.8
32.7
23.7
53.8
51.6
42.0
32.5
55.7
55.7
51.3
41.3
33.7
21.2
42.4
32.7
23.0
51.2
44.3
33.9
23.5
56.8
55.9
44.8
33.7
57.5
57.5
55.7
43.9
44.2
33.4
22.6
53.4
46.8
35.1
23.4
59.6
59.6
47.6
35.0
59.1
59.1
59.1
46.6
46.0
34.1
22.1
55.6
49.3
36.2
23.2
61.3
61.3
50.4
36.2
60.7
60.7
60.7
49.2
65
27.6
27.6
34.8
27.5
36.1
27.4
37.3
27.4
38.6
27.3
39.8
23.5
23.3
30.4
23.0
31.3
22.7
32.2
22.4
33.1
22.1
34.0
Johnson Controls Unitary Products
5123249-TTG-A-0515
ZVTA5 High Speed Compressor (5.0 Ton) (Continued)
Air on
Evaporator Coil
CFM
1250
1500
1750
2000
2250
2500
WB
(°F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
63.5
57.9
52.3
50.2
62.3
58.0
53.6
51.8
50.0
61.2
58.1
54.9
53.4
51.9
60.1
58.2
56.2
55.0
53.8
58.3
57.5
56.6
55.7
58.4
58.7
58.1
57.5
5.4
5.3
5.2
5.1
5.4
5.3
5.2
5.1
5.0
5.3
5.2
5.2
5.1
5.1
5.3
5.2
5.1
5.1
5.1
5.2
5.1
5.1
5.1
5.1
5.1
5.1
5.1
32.6
41.4
50.1
49.0
36.6
44.1
51.6
50.6
49.6
40.5
46.8
53.2
52.3
51.3
44.4
49.6
54.7
53.9
53.1
52.3
56.2
55.5
54.8
55.0
57.8
57.2
56.6
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
115°F
27.3
21.9
56.7
6.1
34.9
28.3
21.8
53.0
5.9
42.4
34.7
28.3
21.8
49.4
5.8
45.1
41.1
34.7
28.2
21.8
46.8
5.7
28.7
20.8
55.7
6.0
36.5
29.0
21.4
53.1
5.9
44.4
37.2
29.4
21.6
50.5
5.8
48.0
45.4
37.4
29.3
21.3
48.3
5.7
49.6
49.6
45.4
37.1
28.8
46.2
5.6
30.0
19.6
54.7
5.9
38.2
29.6
21.0
53.2
5.8
46.4
39.6
30.5
21.4
51.5
5.7
51.0
49.7
40.0
30.4
20.8
49.8
5.7
51.3
51.3
49.6
39.4
29.3
48.0
5.6
31.4
18.4
53.7
5.8
39.9
30.3
20.6
53.3
5.7
48.4
42.1
31.7
21.2
52.6
5.7
53.9
53.9
42.7
31.5
20.3
51.2
5.6
53.1
53.1
53.1
41.8
29.8
49.9
5.6
41.6
30.9
20.2
53.3
5.7
50.4
44.5
32.8
21.1
53.7
5.6
55.5
55.5
45.4
32.6
19.8
52.7
5.6
54.8
54.8
54.8
44.1
30.3
51.8
5.6
43.3
31.5
19.8
53.4
5.6
52.4
47.0
33.9
20.9
54.7
5.6
57.2
57.2
48.1
33.7
19.3
54.2
5.6
56.6
56.6
56.6
46.5
30.8
53.6
5.6
90
30.5
39.3
48.0
45.5
34.5
41.8
49.1
47.0
44.8
38.6
44.4
50.2
48.5
46.7
42.6
47.0
51.3
50.0
48.6
49.5
52.4
51.5
50.5
-
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
125°F
24.9
19.2
32.6
25.9
19.3
40.3
32.6
26.1
19.5
42.4
39.4
32.9
26.5
26.3
18.0
34.2
26.6
18.9
42.1
35.1
27.2
19.3
45.3
43.6
35.5
27.4
44.8
44.8
43.8
35.5
27.7
16.9
35.8
27.2
18.5
43.8
37.5
28.3
19.1
48.1
47.8
38.1
28.4
46.7
46.7
46.7
37.6
29.1
15.7
37.4
27.8
18.2
45.6
39.9
29.4
18.9
50.0
50.0
40.6
29.3
48.6
48.6
48.6
39.6
38.9
28.4
17.8
47.4
42.3
30.5
18.7
51.5
51.5
43.2
30.2
50.5
50.5
50.5
41.7
40.5
29.0
17.5
49.1
44.7
31.6
18.6
53.0
53.0
45.8
31.2
52.4
52.4
52.4
43.8
65
20.0
19.3
27.2
18.6
27.3
17.9
27.4
17.2
27.5
16.5
27.6
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
Johnson Controls Unitary Products
27
5123249-TTG-A-0515
ZVTA5 Low Speed Compressor (5.0 Ton)
Air on
Evaporator Coil
CFM
1250
1500
1750
2000
2250
2500
1250
1500
1750
2000
2250
2500
28
WB
(°F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
62.4
56.5
50.7
49.2
62.4
57.3
52.3
51.1
49.8
62.4
58.1
53.9
53.0
52.0
62.4
58.9
55.5
54.9
54.2
59.7
57.1
56.7
56.4
60.5
58.7
58.6
58.6
2.0
2.1
2.1
2.1
2.0
2.0
2.1
2.1
2.1
2.0
2.0
2.1
2.1
2.1
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
33.2
41.8
50.3
48.8
38.2
45.1
52.0
50.7
49.5
43.2
48.4
53.6
52.7
51.8
48.1
51.7
55.3
54.6
54.0
55.0
56.9
56.6
56.2
-
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
55.1
50.5
45.9
45.3
54.7
50.9
47.1
46.6
46.1
54.2
51.3
48.3
47.9
47.5
53.8
51.6
49.5
49.2
48.9
52.0
50.7
50.5
50.4
52.4
51.9
51.8
51.8
2.8
2.8
2.8
2.7
2.8
2.8
2.8
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
35.9
40.5
45.2
44.6
39.0
42.7
46.4
45.9
45.4
42.0
44.8
47.7
47.3
46.9
45.1
47.0
48.9
48.6
48.4
49.1
50.1
50.0
49.8
-
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
75°F
27.2
21.2
58.7
2.4
35.0
28.3
21.5
53.5
2.4
42.8
35.3
27.9
21.8
48.3
2.4
45.8
42.9
31.7
28.9
22.1
47.2
2.4
29.6
21.0
58.5
2.4
37.4
29.6
21.9
54.1
2.4
45.1
38.3
29.7
22.3
49.7
2.4
48.8
46.9
35.5
30.4
22.1
48.8
2.4
49.5
49.5
47.0
38.5
30.0
48.0
2.4
32.0
20.8
58.3
2.4
39.7
31.0
22.3
54.7
2.4
47.4
41.2
31.6
22.8
51.1
2.4
51.8
50.9
39.3
31.9
22.2
50.4
2.4
51.8
51.8
50.6
41.1
30.8
49.8
2.4
34.4
20.7
58.1
2.4
42.0
32.4
22.7
55.3
2.4
49.7
44.1
33.4
23.3
52.5
2.4
54.6
54.6
43.1
33.4
22.2
52.0
2.4
54.0
54.0
54.0
43.6
31.6
51.6
2.4
44.4
33.8
23.2
55.9
2.4
52.0
47.1
35.3
23.8
53.9
2.4
56.6
56.6
46.9
35.0
22.3
53.6
2.4
56.2
56.2
56.2
46.2
32.5
53.4
2.4
46.7
35.1
23.6
56.4
2.4
54.3
50.0
37.1
24.2
55.3
2.3
58.5
58.5
50.7
36.5
22.3
55.2
2.4
58.5
58.5
58.5
48.8
33.3
55.2
2.4
95°F
28.3
20.7
50.1
3.3
33.5
26.4
19.3
46.6
3.3
38.6
32.0
25.5
19.0
43.1
3.2
41.1
37.7
31.7
25.7
19.8
42.7
3.2
29.1
19.3
49.9
3.3
34.9
27.0
19.2
47.0
3.2
40.6
34.8
27.0
19.2
44.1
3.2
44.2
42.5
34.8
27.0
19.2
43.8
3.2
45.4
45.4
42.5
34.8
27.0
43.5
3.2
29.9
17.9
49.7
3.2
36.3
27.7
19.1
47.4
3.2
42.6
37.6
28.5
19.4
45.1
3.2
47.3
47.3
37.8
28.2
18.6
45.0
3.2
46.9
46.9
46.9
37.0
26.9
44.8
3.2
30.7
16.4
49.4
3.2
37.7
28.4
19.1
47.8
3.2
44.6
40.3
30.0
19.6
46.2
3.2
48.6
48.6
40.9
29.4
18.0
46.1
3.2
48.4
48.4
48.4
39.3
26.8
46.1
3.2
39.1
29.0
19.0
48.3
3.2
46.6
43.1
31.5
19.8
47.2
3.2
50.0
50.0
43.9
30.7
17.4
47.3
3.2
49.8
49.8
49.8
41.5
26.7
47.3
3.2
40.5
29.7
18.9
48.7
3.2
48.6
45.9
32.9
20.0
48.3
3.1
51.3
51.3
47.0
31.9
16.8
48.4
3.2
51.3
51.3
51.3
43.8
26.6
48.6
3.2
90
34.6
41.2
47.8
46.7
38.6
43.9
49.2
48.3
47.5
42.6
46.6
50.6
50.0
49.3
46.6
49.3
52.1
51.6
51.2
52.1
53.5
53.3
53.0
36.1
39.1
42.2
41.8
38.4
40.8
43.3
43.0
42.7
40.7
42.5
44.3
44.2
44.0
43.0
44.2
45.4
45.3
45.3
45.9
46.5
46.5
46.6
-
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
85°F
27.8
21.0
34.2
27.3
20.4
40.7
33.7
26.7
20.4
43.5
40.3
31.7
27.3
29.4
20.2
36.1
28.3
20.6
42.9
36.5
28.4
20.7
46.5
44.7
35.1
28.7
47.5
47.5
44.8
36.6
31.0
19.3
38.0
29.4
20.7
45.0
39.4
30.0
21.1
49.6
49.1
38.5
30.1
49.3
49.3
48.9
39.0
32.6
18.5
39.9
30.4
20.9
47.2
42.2
31.7
21.4
51.6
51.6
42.0
31.4
51.2
51.2
51.2
41.4
41.7
31.4
21.1
49.3
45.1
33.4
21.8
53.3
53.3
45.4
32.8
53.0
53.0
53.0
43.9
43.6
32.4
21.2
51.4
47.9
35.0
22.1
54.9
54.9
48.8
34.2
54.9
54.9
54.9
46.3
105°F
27.6
19.2
32.0
24.8
17.6
36.3
30.4
23.8
17.1
38.9
36.1
29.9
23.7
27.9
17.3
33.0
25.1
17.3
38.1
33.0
25.1
17.2
41.9
40.8
32.9
25.0
42.7
42.7
40.7
32.8
28.1
15.5
34.0
25.5
17.0
39.9
35.5
26.4
17.4
44.2
44.2
35.9
26.3
44.0
44.0
44.0
35.2
28.3
13.6
35.0
25.8
16.6
41.7
38.0
27.8
17.5
45.3
45.3
38.9
27.6
45.3
45.3
45.3
37.7
36.0
26.2
16.3
43.5
40.5
29.1
17.7
46.5
46.5
41.9
28.9
46.6
46.6
46.6
40.1
37.0
26.5
16.0
45.3
43.1
30.4
17.8
47.7
47.7
44.9
30.2
47.9
47.9
47.9
42.6
65
20.9
20.7
28.5
20.4
28.8
20.1
29.2
19.9
29.6
19.6
29.9
17.5
17.1
24.9
16.7
25.1
16.3
25.3
15.9
25.5
15.5
25.7
Johnson Controls Unitary Products
5123249-TTG-A-0515
ZVTA5 Low Speed Compressor (5.0 Ton) (Continued)
Air on
Evaporator Coil
CFM
1250
1500
1750
2000
2250
2500
WB
(°F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
45.1
42.6
40.2
40.0
45.1
43.1
41.1
41.0
40.9
45.1
43.6
42.0
42.0
42.1
45.1
44.0
42.9
43.0
43.2
44.5
43.8
44.0
44.3
45.0
44.6
45.0
45.4
3.8
3.7
3.7
3.7
3.8
3.7
3.7
3.7
3.7
3.7
3.7
3.7
3.7
3.7
3.7
3.7
3.6
3.7
3.7
3.7
3.6
3.6
3.6
3.6
3.6
3.6
3.6
39.4
40.2
41.0
41.0
41.1
41.0
41.4
41.9
42.1
42.2
42.7
42.8
43.1
43.3
-
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
115°F
27.0
17.6
40.1
4.3
30.5
23.2
16.0
38.7
4.2
34.0
28.8
22.0
15.2
37.4
4.1
36.7
34.4
28.1
21.7
15.3
37.4
4.2
26.6
15.4
40.3
4.3
31.1
23.2
15.4
39.2
4.2
35.6
31.1
23.2
15.3
38.1
4.1
39.5
39.0
31.0
23.0
15.0
38.2
4.2
39.9
39.9
38.8
30.8
22.7
38.4
4.2
26.3
13.1
40.5
4.2
31.7
23.3
14.8
39.7
4.2
37.2
33.4
24.4
15.4
38.8
4.1
41.0
41.0
34.0
24.4
14.8
39.1
4.1
41.1
41.1
41.1
33.4
23.3
39.3
4.2
25.9
10.9
40.8
4.2
32.4
23.3
14.2
40.3
4.2
38.8
35.7
25.6
15.4
39.6
4.1
42.1
42.1
36.9
25.8
14.6
39.9
4.1
42.2
42.2
42.2
36.1
23.8
40.3
4.1
33.0
23.3
13.6
40.8
4.1
40.4
38.0
26.8
15.5
40.3
4.1
43.1
43.1
39.9
27.1
14.3
40.8
4.1
43.3
43.3
43.3
38.7
24.4
41.2
4.1
33.6
23.3
13.0
41.3
4.1
42.0
40.3
27.9
15.6
41.0
4.1
44.1
44.1
42.9
28.5
14.1
41.6
4.1
44.5
44.5
44.5
41.3
24.9
42.2
4.1
90
38.1
37.9
37.7
37.9
38.1
38.9
38.7
38.4
38.8
39.1
39.4
39.2
39.6
40.1
-
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
125°F
26.3
16.1
29.0
21.6
14.3
31.7
27.2
20.3
13.3
34.5
32.8
26.2
19.6
25.4
13.4
29.2
21.3
13.5
33.1
29.3
21.3
13.3
37.0
37.0
29.1
21.1
37.2
37.2
37.0
28.8
24.4
10.7
29.5
21.0
12.6
34.5
31.3
22.3
13.3
37.9
37.9
32.1
22.5
38.1
38.1
38.1
31.6
23.5
8.1
29.7
20.7
11.8
35.9
33.4
23.4
13.4
38.8
38.8
35.0
23.9
39.1
39.1
39.1
34.5
29.9
20.4
10.9
37.3
35.4
24.4
13.4
39.6
39.6
37.9
25.3
40.1
40.1
40.1
37.3
-
65
13.0
13.0
20.6
12.9
21.5
12.8
22.3
12.8
23.2
-
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
Johnson Controls Unitary Products
29
5123249-TTG-A-0515
Drive Selection
1.
Determine side or bottom supply duct Application.
2.
Determine desired airflow.
3.
Calculate or measure the amount of external static pressure.
• Add or deduct any additional static resistance from “Additional Static Resistance Table”.
4.
Using the operating point determined from steps 1, 2 & 3, locate this point on the appropriate supply air blower performance
table. (Linear interpolation may be necessary.)
5.
Noting the RPM and BHP from step 4, locate the appropriate motor and, or drive on the RPM selection table.
6.
Review the BHP compared to the motor options available. Select the appropriate motor and, or drive.
7.
Review the RPM range for the motor options available. Select the appropriate drive if multiple drives are available for the
chosen motor.
8.
Determine turns open to obtain the desired operation point.
Example
1.
2600 CFM
2.
1.6 iwg
3.
Using the supply air blower performance table below, the following data point was located: 1268 RPM & 1.95 BHP.
4.
Using the RPM selection table below, Size X and Model Y is found.
5.
1.95 BHP exceeds the maximum continuous BHP rating of the 1.5 HP motor. The 2 HP motor is required.
6.
1268 RPM is within the range of the 2 HP drives.
7.
Using the 2 HP motor and drive, .5 turns open will achieve 1268 RPM.
Airflow Performance
Example Supply Air Blower Performance
Air Flow
(CFM)
2200
2400
2600
2800
Available External Static Pressure - IWG
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
804
835
869
906
0.50
0.66
0.84
1.03
1.5 HP & Field Supplied Drive
866
0.71
925
0.90
982
897
0.87
956
1.06 1013
931
1.05
990
1.24 1047
968
1.25 1027 1.43 1084
1.06
1.22
1.40
1.60
1038
1069
1103
1139
Standard 1.5 HP & Drive
1.21 1092 1.35 1147
1.37 1124 1.51 1178
1.55 1158 1.69 1212
1.75 1194 1.89 1249
1.48
1.64
1.82
2.02
1203
1234
1268
1304
Alternate 2 HP & Drive
1.61 1259 1.73 1317
1.77 1290 1.90 1348
1.95 1324 2.07 1382
2.14 1361 2.27
-
1.87
2.03
2.21
-
Example RPM Selection
Size
(Tons)
Model
X
Y
Airflow
Option
Std.
H. Static
HP
1.5
2
Max
BHP
1.73
2.30
Motor
Sheave
1VM50
1VM50
Blower
Sheave
AK74
AK64
6 Turns
Open
N/A
N/A
5 Turns
Open
897
1039
4 Turns
Open
945
1094
3
6
0.00
0.00
0.01
0.01
0.01
0.00
0.00
0.01
0.01
0.01
3 Turns
Open
991
1150
2 Turns
Open
1035
1207
1 Turn
Open
1079
1256
Fully
Closed
1126
1308
Example Additional Static Resistance
Size
(Tons)
X
30
Model
Y
CFM Cooling Only
900
1000
1100
1200
1300
0.05
0.05
0.04
0.04
0.03
Economizer
4” Pleated Filter
-0.05
-0.03
-0.02
0.00
0.01
0.01
0.02
0.03
0.04
0.05
Electric Heat kW
9
15
0.00
0.00
0.01
0.01
0.01
0.01
0.02
0.02
0.02
0.03
20
24
0.01
0.02
0.02
0.02
0.03
0.01
0.02
0.02
0.02
0.03
Johnson Controls Unitary Products
5123249-TTG-A-0515
Altitude and Temperature Correction for CFM, Static Pressure and Power.
The information below should be used to assist in application of product when being applied at altitudes at or exceeding 1000 feet
above sea level.
The air flow rates listed in the standard blower performance tables are based on standard air at sea level. As the altitude or
temperature increases, the density of air decreases. In order to use the indoor blower tables for high altitude applications, certain
corrections are necessary.
A centrifugal fan is a "constant volume" device. This means that, if the rpm remains constant, the CFM delivered is the same
regardless of the density of the air. However, since the air at high altitude is less dense, less static pressure will be generated and
less power will be required than a similar application at sea level. Air density correction factors are shown in Table 14 and Figure 27.
Altitude/Temperature Correction Factors
Air
Temp.
40
50
60
70
80
90
100
0
1.060
1.039
1.019
1.000
0.982
0.964
0.946
1000
1.022
1.002
0.982
0.964
0.947
0.929
0.912
2000
0.986
0.966
0.948
0.930
0.913
0.897
0.880
3000
0.950
0.931
0.913
0.896
0.880
0.864
0.848
4000
0.916
0.898
0.880
0.864
0.848
0.833
0.817
Altitude (Ft.)
5000
0.882
0.864
0.848
0.832
0.817
0.802
0.787
6000
0.849
0.832
0.816
0.801
0.787
0.772
0.758
7000
0.818
0.802
0.787
0.772
0.758
0.744
0.730
8000
0.788
0.772
0.757
0.743
0.730
0.716
0.703
9000
0.758
0.743
0.729
0.715
0.702
0.689
0.676
10000
0.729
0.715
0.701
0.688
0.676
0.663
0.651
1.100
1.050
Correction Factor
1.000
Sea Level
0.950
1000 ft
0.900
2000 ft
3000 ft
0.850
4000 ft
0.800
5000 ft
0.750
6000 ft
7000 ft
8000 ft
0.700
9000 ft
10000 ft
0.650
0.600
40
50
60
70
80
90
100
Air Temperature (ºF)
The examples below will assist in determining the airflow performance of the product at altitude.
Example 1: What are the corrected CFM, static pressure, and BHP at an elevation of 5,000 ft. if the blower performance data is
6,000 CFM, 1.5 IWC and 4.0 BHP?
Solution: At an elevation of 5,000 ft. the indoor blower will still deliver 6,000 CFM if the rpm is unchanged. However, Table 13 must be
used to determine the static pressure and BHP. Since no temperature data is given, we will assume an air temperature of 70°F. Table
15 shows the correction factor to be 0.832.
Corrected static pressure = 1.5 x 0.832 = 1.248 IWC
Corrected BHP = 4.0 x 0.832 = 3.328
Example 2: A system, located at 5,000 feet of elevation, is to deliver 6,000 CFM at a static pressure of 1.5". Use the unit blower
tables to select the blower speed and the BHP requirement.
Solution: As in the example above, no temperature information is given so 70°F is assumed.
Johnson Controls Unitary Products
31
5123249-TTG-A-0515
The 1.5" static pressure given is at an elevation of 5,000 ft. The
first step is to convert this static pressure to equivalent sea level
conditions.
Sea level static pressure = 1.5 / .832 = 1.80"
Enter the blower table at 6000 sCFM and static pressure of
1.8". The rpm listed will be the same rpm needed at 5,000 ft.
Suppose that the corresponding BHP listed in the table is 3.2.
This value must be corrected for elevation.
BHP at 5,000 ft. = 3.2 x .832 = 2.66
Indoor Blower Specifications
Motor
Airflow
Size
Model
Option
(Tons)
TA3
(3)
TA4
(4)
TA5
(5)
Std.
H. Static
Std.
H. Static
Std.
H. Static
ZV
ZV
ZV
HP
RPM
Eff.
SF
1-1/2
1-1/2
1-1/2
1-1/2
1-1/2
2
1725
1725
1725
1725
1725
1725
0.86
0.86
0.86
0.86
0.86
0.86
1.15
1.15
1.15
1.15
1.15
1.15
Motor Sheave
Datum Dia.
Bore (in.)
Frame
(in.)
56
2.4 - 3.4
7/8
56
2.4 - 3.4
7/8
56
1.9 - 2.9
7/8
56
2.8 - 3.8
7/8
56
2.4 - 3.4
7/8
56
3.4 - 4.4
7/8
Blower Sheave
Datum Dia.
Bore (in.)
(in.)
7.5
1
5.7
1
6
1
6.5
1
5.7
1
6
1
Model
1VL40
1VL40
1VL34
1VL44
1VL40
1VM50
Model
AK79
AK61
AK64
AK69
AK61
AK64
Belt
A47
A45
A47
A47
A45
A47
Power Exhaust Specifications
Model
Voltage
2PE04703225
2PE04703246
2PE04703258
208/230-1-60
460-1-60
575-1-60
Motor
RPM1
1075
1075
1050
HP
3/4
3/4
3/4
QTY
1
1
1
LRA
7.8
3.4
2.9
Motor
FLA
5
2.2
1.5
CFM @
0.1 ESP
3800
3800
3800
Fuse Size
MCA
6.3
2.8
1.9
10
5
4
1. Motors are multi-tapped and factory wired for high speed.
RPM Selection
Size
Model Airflow Option
(Tons)
HP
Max
BHP
Motor
Sheave
Blower
Sheave
6 Turns
Open
5 Turns
Open
4 Turns
Open
3 Turns
Open
2 Turns
Open
1 Turn
Open
Fully
Closed
Field Supplied
1.5
1.5
1VL34
AK79
N/A
465
512
557
606
651
695
Std.
1.5
1.5
1VL40
AK79
N/A
612
661
707
752
799
844
H. Static
1.5
1.5
1VL40
AK61
N/A
782
846
906
968
1022
1085
Field Supplied
1.5
1.5
1VL40
AK54
N/A
896
960
1030
1090
166
1238
Std.
1.5
1.5
1VL34
AK64
N/A
576
631
688
747
800
859
H. Static
1.5
1.5
1VL44
AK69
N/A
792
844
892
944
996
1045
Field Supplied
1.5
1.5
1VL44
AK59
N/A
915
989
1050
1113
1173
1238
Field Supplied
1.5
1.5
1VL40
AK79
N/A
609
656
703
746
792
839
Std.
1.5
1.5
1VL40
AK61
N/A
782
846
906
968
1022
1085
Field Supplied
2
2
1VL40
AK54
N/A
896
960
1030
1090
1166
1238
H. Static
2
2
1VM50
AK64
N/A
1022
1079
1135
1190
1246
1297
TA3
(3)
TA4
(4)
TA5
(5)
32
ZV
ZV
ZV
Johnson Controls Unitary Products
5123249-TTG-A-0515
Additional Static Resistance
Size
(Tons)
Model
TA3 (3)
ZV
TA4 (4)
TA5 (5)
ZV
CFM Cooling Only1 Economizer2 3 4” Pleated Filter2
900
1000
1100
1200
1300
1400
1500
1200
1300
1400
1500
1600
1700
1800
1900
2000
2100
2200
2300
2400
2500
0.05
0.05
0.04
0.04
0.03
0.03
0.03
-0.01
-0.01
-0.01
-0.01
-0.01
-0.01
-0.02
-0.02
-0.02
-0.03
-0.03
-0.04
-0.04
-0.05
-0.05
-0.03
-0.02
0.00
0.01
0.03
0.04
0.10
0.11
0.12
0.13
0.14
0.15
0.16
0.17
0.18
0.19
0.20
0.21
0.22
0.23
0.01
0.02
0.03
0.04
0.05
0.07
0.08
0.05
0.06
0.06
0.07
0.08
0.08
0.09
0.10
0.10
0.11
0.12
0.12
0.13
0.14
3
6
0.00
0.00
0.01
0.01
0.01
0.02
0.02
0.01
0.01
0.02
0.02
0.02
0.03
0.03
0.04
0.04
0.05
0.06
0.06
0.07
0.08
0.00
0.00
0.01
0.01
0.01
0.02
0.02
0.01
0.01
0.02
0.02
0.02
0.03
0.03
0.04
0.04
0.05
0.06
0.06
0.07
0.08
Electric Heat kW2
9
15
0.00
0.00
0.01
0.01
0.01
0.02
0.02
0.01
0.01
0.02
0.02
0.02
0.03
0.03
0.04
0.04
0.05
0.06
0.06
0.07
0.08
0.01
0.02
0.02
0.02
0.03
0.03
0.04
0.02
0.03
0.03
0.04
0.04
0.05
0.05
0.06
0.07
0.07
0.08
0.09
0.10
0.11
20
24
0.01
0.02
0.02
0.02
0.03
0.03
0.04
0.02
0.03
0.03
0.04
0.04
0.05
0.05
0.06
0.07
0.07
0.08
0.09
0.10
0.11
0.01
0.02
0.02
0.02
0.03
0.03
0.04
0.02
0.03
0.03
0.04
0.04
0.05
0.05
0.06
0.07
0.07
0.08
0.09
0.10
0.11
1. Add these values to the available static resistance in the respective Blower Performance Tables.
2. Deduct these values from the available external static pressure shown in the respective Blower Performance Tables.
3. The pressure drop through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return air duct
is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.
Gas Heat Minimum Supply Air
Size
(Tons)
Model
TA3
(3)
ZV
TA4
(4)
ZV
TA5
(5)
ZV
Supply Air (CFM)
Heating
Min
Max
890
2220
915
2370
1130
1800
890
2220
915
2370
1290
2250
915
2370
1380
2570
1580
2630
Heat Size
(A,B)06 / (N,S)06
(A,B)08 / (N,S)08
(A,B)11 / (N,S)11
(A,B)06 / (N,S)06
(A,B)08 / (N,S)08
(A,B)11 / (N,S)11
(A,B)08 / (N,S)08
(A,B)11 / (N,S)11
(A,B)16 / (N,S)16
Electric Heat Minimum Supply Air
3 thru 5 Tons
Size
(Tons)
Model
TA3
(3)
ZV
TA4
(4)
ZV
TA5
(5)
ZV
Johnson Controls Unitary Products
Voltage
208/230-3-60
460-3-60
600-3-60
208/230-3-60
460-3-60
600-3-60
208/230-3-60
460-3-60
600-3-60
3
960
980
-
6
960
960
1280
1400
1600
1600
-
Minimum Supply Air (CFM)
Heater kW
9
15
1020
1020
960
960
960
960
1420
1420
1400
1400
1400
1400
1600
1600
1600
1600
1600
1600
20
1420
1400
1400
1600
1600
1600
24
1600
1600
1600
33
5123249-TTG-A-0515
Airflow Performance
ZVTA3 thru TA5 Side Duct Application
ZVTA3 (3.0 Ton) Side Duct
Air Flow
(CFM)
900
1000
1100
1200
1300
1400
1500
Available External Static Pressure - IWG1
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
468
479
494
509
524
540
562
FS4
0.24
563
0.25
578
0.27
594
0.28
608
0.30
623
0.32
639
0.34
660
0.27
0.29
0.31
0.37
0.39
0.41
0.44
652
670
688
701
716
732
753
Standard 1.5 Hp & Drive
0.36
736
0.46
814
0.38
756
0.47
837
0.40
775
0.49
856
0.46
788
0.55
870
0.48
804
0.58
886
0.51
819
0.61
901
0.54
840
0.65
921
0.56
0.57
0.59
0.65
0.68
0.71
0.75
887
911
931
945
961
977
998
High Static 1.5 Hp & Drive
0.67
955
0.76 1017
0.68
979
0.78 1041
0.69
999
0.79 1061
0.75 1015 0.85 1078
0.78 1032 0.88 1096
0.82 1048 0.92 1113
0.85 1069 0.96 1135
0.87
0.89
0.90
0.95
0.99
1.03
1.07
1074
1098
1117
1136
1154
1172
1195
FS4
1.01 1126
1.03 1148
1.04 1167
1.06 1188
1.09 1207
1.14 1226
1.18
-
1.09
1.11
1.13
1.17
1.20
1.26
-
1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
4. Field Supplied Drive
ZVTA4 (4.0 Ton) Side Duct
Air Flow
(CFM)
1200
1300
1400
1500
1600
1700
1800
1900
2000
1.
2.
3.
4.
Available External Static Pressure - IWG1
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
574
596
619
643
669
697
0.36
0.39
0.43
0.47
0.52
0.58
618
638
653
666
689
711
734
757
779
Standard 1.5 Hp & Drive
0.34
695
0.40
783
0.38
712
0.43
799
0.40
729
0.46
815
0.42
747
0.50
831
0.44
766
0.54
847
0.49
786
0.58
863
0.54
808
0.64
878
0.61
831
0.71
894
0.67
856
0.78
910
0.47
0.50
0.54
0.59
0.63
0.68
0.73
0.79
0.85
864
876
888
900
912
925
936
948
960
High Static 1.5 Hp & Drive
0.54
940
0.60
983
0.59
954
0.65
995
0.63
965
0.72 1007
0.68
975
0.78 1019
0.73
983
0.84 1031
0.79
991
0.89 1043
0.84
998
0.95 1055
0.91 1004 1.00 1067
0.98 1010 1.05 1079
0.69
0.74
0.78
0.83
0.88
0.94
1.00
1.06
1.13
1073
1080
1088
1096
1103
1112
1121
1130
1140
0.76
0.81
0.87
0.92
0.97
1.04
1.10
1.16
1.23
FS4
1119 0.88
1130 0.94
1140 1.00
1151 1.06
1162 1.13
1172 1.19
1183 1.27
1194 1.35
-
1178
1188
1198
1207
1217
1227
1237
-
0.94
1.00
1.06
1.11
1.18
1.25
1.33
-
Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
kW = BHP x 0.932.
Field Supplied Drive.
ZVTA5 (5.0 Ton) Side Duct
Air Flow
(CFM)
1500
1600
1700
1800
1900
2000
2100
2200
2300
2400
2500
1.
2.
3.
4.
34
Available External Static Pressure - IWG1
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
615
641
666
692
718
744
770
796
822
0.43
0.48
0.52
0.58
0.64
0.71
0.79
0.87
0.96
FS4
667
0.40
689
0.44
711
0.48
734
0.53
757
0.59
781
0.65
806
0.73
832
0.81
859
0.91
887
1.03
916
1.17
747
766
786
808
831
842
863
886
907
927
946
0.50
0.54
0.58
0.64
0.71
0.73
0.75
0.83
0.90
0.98
1.06
837
844
852
863
878
914
934
954
972
990
1006
0.58
0.60
0.64
0.68
0.76
0.82
0.88
0.95
1.02
1.09
1.17
Standard 1.5 Hp & Drive
904
0.59
972
0.73
917
0.65
982
0.79
931
0.73
994
0.86
945
0.80 1006 0.93
959
0.87 1018 0.99
973
0.94 1031 1.06
987
1.01 1044 1.14
1002 1.09 1059 1.22
1017 1.16 1074 1.31
1032 1.24 1091 1.40
1047 1.32 1112 1.52
1039
1047
1057
1067
1077
1089
1101
1116
1131
1150
1177
0.88
0.93
1.00
1.06
1.12
1.19
1.26
1.36
1.45
1.56
1.73
1096
1103
1112
1121
1130
1140
1151
1164
1178
1195
1219
High Static 2.0 Hp & Drive
0.92 1151 1.06 1207
0.97 1162 1.13 1217
1.04 1172 1.19 1227
1.10 1183 1.27 1237
1.16 1194 1.35 1246
1.23 1204 1.43 1256
1.31 1215 1.53 1266
1.40 1226 1.63 1276
1.50 1236 1.72 1286
1.62 1247 1.83 1295
1.79 1258 1.95
-
1.11
1.18
1.25
1.33
1.40
1.49
1.58
1.67
1.78
1.87
-
Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
kW = BHP x 0.932.
Field Supplied Drive.
Johnson Controls Unitary Products
5123249-TTG-A-0515
ZVTA3 thru TA5 Bottom Duct Application
ZVTA3 (3.0 Ton) Bottom Duct
Air Flow
(CFM)
900
1000
1100
1200
1300
1400
1500
1.
2.
3.
4.
Available External Static Pressure - IWG1
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
469
486
504
526
552
577
610
FS4
0.26
580
0.27
597
0.29
613
0.31
635
0.33
657
0.35
679
0.39
707
0.34
0.36
0.38
0.40
0.42
0.46
0.49
Standard 1.5 Hp & Drive
682
0.43
775
0.52
699
0.45
793
0.54
714
0.47
807
0.56
736
0.50
828
0.59
755
0.52
844
0.62
774
0.56
862
0.65
797
0.60
882
0.70
860
879
892
911
926
943
959
0.60
0.63
0.66
0.69
0.71
0.75
0.79
High Static 1.5 Hp & Drive
936
0.69 1004 0.78
956
0.72 1024 0.81
969
0.75 1037 0.84
986
0.78 1053 0.87
1001 0.81 1067 0.90
1017 0.84 1084 0.93
1031 0.89 1095 0.98
1063
1083
1098
1112
1126
1144
1154
0.87
0.91
0.93
0.97
0.99
1.02
1.07
1113
1135
1151
1162
1177
1198
1206
FS4
0.96 1155
1.00 1177
1.02 1196
1.06 1203
1.08 1220
1.11
1.15
-
1.05
1.10
1.12
1.15
1.17
-
Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
kW = BHP x 0.932.
Field Supplied Drive.
ZVTA4 (4.0 Ton) Bottom Duct
Air Flow
(CFM)
1200
1300
1400
1500
1600
1700
1800
1900
2000
1.
2.
3.
4.
Available External Static Pressure - IWG1
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
586
612
643
671
699
726
755
0.37
0.40
0.44
0.47
0.53
0.58
0.64
Standard 1.5 Hp & Drive
633
0.38
728
0.47
656
0.41
748
0.50
680
0.46
769
0.55
703
0.50
790
0.59
731
0.53
814
0.63
756
0.57
837
0.67
781
0.63
860
0.73
805
0.69
881
0.80
831
0.75
905
0.86
816
834
852
871
893
914
935
954
977
0.56
0.59
0.65
0.69
0.73
0.77
0.84
0.90
0.97
898
914
930
948
967
987
1006
1024
1046
High Static 1.5 Hp & Drive
0.65
973
0.75 1042
0.68
988
0.77 1056
0.74 1003 0.84 1070
0.78 1019 0.88 1086
0.82 1037 0.92 1103
0.87 1056 0.97 1121
0.94 1074 1.04 1139
1.01 1092 1.12 1157
1.08 1113 1.19 1178
0.85
0.87
0.93
0.97
1.01
1.07
1.14
1.22
1.3
1104
1118
1132
1148
1164
1183
1199
1218
-
0.95
0.96
1.02
1.07
1.11
1.17
1.24
1.33
-
FS4
1159 1.05
1174 1.07
1189 1.12
1205 1.17
1221 1.21
-
1208
1224
-
1.16
1.17
-
Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
kW = BHP x 0.932.
Field Supplied Drive.
ZVTA5 (5.0 Ton) Bottom Duct
Air Flow
(CFM)
1500
1600
1700
1800
1900
2000
2100
2200
2300
2400
2500
1.
2.
3.
4.
Available External Static Pressure - IWG1
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
616
643
671
698
725
753
782
809
837
865
893
FS4
0.39
696
0.43
719
0.47
746
0.52
771
0.57
796
0.62
822
0.68
849
0.74
874
0.82
900
0.89
925
0.98
952
0.50
0.54
0.58
0.62
0.67
0.73
0.79
0.85
0.93
1.01
1.09
771
791
817
840
864
888
913
936
960
984
1009
0.60
0.64
0.68
0.72
0.77
0.83
0.89
0.96
1.04
1.12
1.21
841
858
884
905
929
952
975
997
1019
1042
1065
0.71
0.74
0.78
0.83
0.88
0.94
1.00
1.07
1.15
1.23
1.33
Standard 1.5 Hp & Drive
907
0.81
968
0.91
921
0.85
980
0.95
947
0.88 1006 0.98
967
0.93 1025 1.03
990
0.98 1048 1.09
1012 1.04 1069 1.15
1033 1.11 1090 1.21
1055 1.18 1110 1.29
1076 1.26 1132 1.37
1098 1.35 1152 1.46
1120 1.44 1173 1.56
1024
1034
1062
1080
1102
1123
1143
1164
1185
1205
1226
1.02
1.06
1.09
1.13
1.19
1.25
1.32
1.39
1.48
1.57
1.67
1075
1084
1113
1131
1154
1174
1194
1215
1236
1256
1277
1.12
1.16
1.19
1.24
1.29
1.36
1.43
1.50
1.59
1.69
1.79
High Static 2.0 Hp & Drive
1122 1.23 1164 1.33
1130 1.26 1171 1.37
1160 1.29 1203 1.39
1178 1.34 1222 1.44
1202 1.40 1246 1.50
1222 1.46 1267 1.57
1243 1.54 1288 1.64
1264 1.61 1310 1.72
1285 1.70 1333 1.81
1306 1.80
1327 1.91
-
Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
kW = BHP x 0.932.
Field Supplied Drive.
Johnson Controls Unitary Products
35
5123249-TTG-A-0515
Sound Performance
Indoor Sound Power Levels (3 thru 5 Ton)
Indoor Sound Power Levels (Horizontal Ducted Inlet, Standard Static Belt Drive)
UNIT DESCRIPTION / MODEL
ZVTA3 / 3 Ton / Standard Static Belt Drive
TEST CONFIGURATION
Indoor Blower Speed (RPM)
Horizontal (Side Return) Ducted Inlet
612 - 3 Turns Open Equivalent
709 - 1 Turn Open Equivalent
External Static Pressure (IWG)
0.5
0.4
Airflow (CFM)
850
1300
Blower Motor BHP
0.37
0.40
Octave Center Freq. Hz
ID Blower Only (dB)
Cooling Operation1 (dB)
ID Blower Only (dB)
Cooling Operation1 (dB)
63
73
77
73
77
125
61
70
66
71
250
56
63
60
64
500
51
56
55
57
1000
44
48
51
52
2000
41
44
48
49
4000
44
47
47
48
8000
42
44
43
44
1. Cooling Operation – ID blower, compressor and outdoor fan operating at 230 VAC.
• Tested in accordance with AHRI Standard 260-2001. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning
Equipment.
• Testing datum includes effect of standard inlet air filters.
• Test duct dimension: 18 in. wide x 28 in. high x 8 ft. long, no elbows.
• Test duct termination is flush with reverberant room wall.
• Duct end (sound reflection) corrections included: (7.2, 3.4, 1.2, 0.4, 0.1, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 2k, 4k, 8k) Hz respectively.
UNIT DESCRIPTION / MODEL
ZVTA4 / 4 Ton / Standard Static Belt Drive
TEST CONFIGURATION
Indoor Blower Speed (RPM)
Horizontal (Side Return) Ducted Inlet
612 - 3 Turns Open Equivalent
709 - 1 Turn Open Equivalent
External Static Pressure (IWG)
0.5
0.4
Airflow (CFM)
850
1300
Blower Motor BHP
0.37
0.40
Octave Center Freq. Hz
ID Blower Only (dB)
Cooling Operation1 (dB)
ID Blower Only (dB)
Cooling Operation1 (dB)
63
73
77
73
77
125
61
70
66
71
250
56
63
60
64
500
51
56
55
57
1000
44
48
51
52
2000
41
44
48
49
4000
44
47
47
48
8000
42
44
43
44
1. Cooling Operation – ID blower, compressor and outdoor fan operating at 230 VAC.
• Tested in accordance with AHRI Standard 260-2001. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning
Equipment.
• Testing datum includes effect of standard inlet air filters.
• Test duct dimension: 18 in. wide x 28 in. high x 8 ft. long, no elbows.
• Test duct termination is flush with reverberant room wall.
• Duct end (sound reflection) corrections included: (7.2, 3.4, 1.2, 0.4, 0.1, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 2k, 4k, 8k) Hz respectively.
36
Johnson Controls Unitary Products
5123249-TTG-A-0515
UNIT DESCRIPTION / MODEL
ZVTA5 / 5 Ton / Standard Static Belt Drive
TEST CONFIGURATION
Horizontal (Side Return) Ducted Inlet
Indoor Blower Speed (RPM)
814 - 3 Turns Open Equivalent
External Static Pressure (IWG)
Airflow (CFM)
Blower Motor BHP
918 - 1 Turn Open Equivalent
0.6
0.8
1700
1950
0.42
0.88
Octave Center Freq. Hz
ID Blower Only (dB)
Cooling Operation1 (dB)
ID Blower Only (dB)
Cooling Operation1 (dB)
63
77
81
85
82
125
71
80
68
81
250
63
67
64
68
500
58
60
60
61
1000
56
57
58
59
2000
52
53
55
55
4000
51
51
54
54
8000
47
47
48
48
1. Cooling Operation – ID blower, compressor and outdoor fan operating at 230 VAC.
• Tested in accordance with AHRI Standard 260-2001. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning
Equipment.
• Testing datum includes effect of standard inlet air filters.
• Test duct dimension: 18 in. wide x 28 in. high x 8 ft. long, no elbows.
• Test duct termination is flush with reverberant room wall.
• Duct end (sound reflection) corrections included: (7.2, 3.4, 1.2, 0.4, 0.1, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 2k, 4k, 8k) Hz respectively.
Indoor Sound Power Levels (Horizontal Ducted Discharge, Standard Static Belt Drive)
UNIT DESCRIPTION / MODEL
ZVTA3 / 3 Ton / Standard Static Belt Drive
TEST CONFIGURATION
Horizontal (Side Supply) Ducted Discharge
Indoor Blower Speed (RPM)
610 - 3 Turns Open Equivalent
710 - 1 Turn Open Equivalent
0.5
0.6
External Static Pressure (IWG)
Airflow (CFM)
850
950
Blower Motor BHP
0.37
0.42
Octave Center Freq. Hz
ID Blower Only (dB)
Cooling Operation1 (dB)
ID Blower Only (dB)
Cooling Operation1 (dB)
63
77
78
79
79
125
74
75
75
76
250
66
68
70
70
500
61
61
65
64
1000
60
62
65
66
2000
52
52
58
58
4000
52
52
59
60
8000
44
44
50
50
1. Cooling Operation – ID blower, compressor and outdoor fan operating at 230 VAC.
• Tested in accordance with AHRI Standard 260-2001. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning
Equipment.
• Testing datum includes effect of standard inlet air filters.
• Test duct dimension: 18 in. wide x 28 in. high x 8 ft. long, no elbows.
• Test duct termination is flush with reverberant room wall.
• Duct end (sound reflection) corrections included: (7.2, 3.4, 1.2, 0.4, 0.1, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 2k, 4k, 8k) Hz respectively.
Johnson Controls Unitary Products
37
5123249-TTG-A-0515
UNIT DESCRIPTION / MODEL
ZVTA4 / 4 Ton / Standard Static Belt Drive
TEST CONFIGURATION
Horizontal (Side Supply) Ducted Discharge
Indoor Blower Speed (RPM)
610 - 3 Turns Open Equivalent
710 - 1 Turn Open Equivalent
0.5
0.6
External Static Pressure (IWG)
Airflow (CFM)
850
950
Blower Motor BHP
0.37
0.42
Octave Center Freq. Hz
ID Blower Only (dB)
Cooling Operation1 (dB)
ID Blower Only (dB)
Cooling Operation1 (dB)
63
77
78
79
79
125
74
75
75
76
250
66
68
70
70
500
61
61
65
64
1000
60
62
65
66
2000
52
52
58
58
4000
52
52
59
60
8000
44
44
50
50
1. Cooling Operation – ID blower, compressor and outdoor fan operating at 230 VAC.
• Tested in accordance with AHRI Standard 260-2001. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning
Equipment.
• Testing datum includes effect of standard inlet air filters.
• Test duct dimension: 18 in. wide x 28 in. high x 8 ft. long, no elbows.
• Test duct termination is flush with reverberant room wall.
• Duct end (sound reflection) corrections included: (7.2, 3.4, 1.2, 0.4, 0.1, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 2k, 4k, 8k) Hz respectively.
UNIT DESCRIPTION / MODEL
ZVTA5 / 5 Ton / Standard Static Belt Drive
TEST CONFIGURATION
Horizontal (Side Supply) Ducted Discharge
Indoor Blower Speed (RPM)
810 - 3 Turns Open Equivalent
External Static Pressure (IWG)
918 - 1 Turn Open Equivalent
0.4
0.8
Airflow (CFM)
2050
1950
Blower Motor BHP
0.73
0.88
1
Octave Center Freq. Hz
ID Blower Only (dB)
Cooling Operation (dB)
ID Blower Only (dB)
Cooling Operation1 (dB)
63
85
83
83
83
125
78
79
76
79
250
69
70
69
70
500
68
68
68
68
1000
64
64
65
65
2000
63
63
64
64
4000
64
64
64
64
8000
59
59
59
60
1. Cooling Operation – ID blower, compressor and outdoor fan operating at 230 VAC.
• Tested in accordance with AHRI Standard 260-2001. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning
Equipment.
• Testing datum includes effect of standard inlet air filters.
• Test duct dimension: 18 in. wide x 28 in. high x 8 ft. long, no elbows.
• Test duct termination is flush with reverberant room wall.
• Duct end (sound reflection) corrections included: (7.2, 3.4, 1.2, 0.4, 0.1, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 2k, 4k, 8k) Hz respectively.
38
Johnson Controls Unitary Products
5123249-TTG-A-0515
Indoor Sound Power Levels (Vertical Ducted Inlet, Standard Static Belt Drive)
UNIT DESCRIPTION / MODEL
ZVTA3 / 3 Ton / Standard Static Belt Drive
TEST CONFIGURATION
Vertical (Bottom Return) Ducted Inlet
Indoor Blower Speed (RPM)
609 - 3 Turns Open Equivalent
708 - 1 Turn Open Equivalent
0.4
0.4
Airflow (CFM)
850
1150
Blower Motor BHP
0.32
External Static Pressure (IWG)
0.38
Octave Center Freq. Hz
ID Blower Only (dB)
Cooling Operation1 (dB)
ID Blower Only (dB)
Cooling Operation1 (dB)
63
76
76
74
76
125
63
70
66
70
250
55
62
59
62
500
54
55
58
59
1000
48
48
53
53
2000
44
44
48
48
4000
41
44
45
46
8000
42
43
43
44
1. Differentials for Cooling Operation (IDB, COMP, & ODF) are logarithmically calculated from the horizontal flow sound test.
• Tested in accordance with AHRI Standard 260-2001. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning
Equipment.
• Testing datum includes effect of standard inlet air filters.
• Test duct dimension: 18 in. wide x 28 in. high x 8 ft. long, no elbows.
• Test duct termination is flush with reverberant room wall.
• Duct end (sound reflection) corrections included: (7.2, 3.4, 1.2, 0.4, 0.1, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 2k, 4k, 8k) Hz respectively.
UNIT DESCRIPTION / MODEL
ZVTA4 / 4 Ton / Standard Static Belt Drive
TEST CONFIGURATION
Vertical (Bottom Return) Ducted Inlet
609 - 3 Turns Open Equivalent
Indoor Blower Speed (RPM)
708 - 1 Turn Open Equivalent
External Static Pressure (IWG)
0.4
0.4
Airflow (CFM)
850
1150
Blower Motor BHP
0.32
Octave Center Freq. Hz
ID Blower Only (dB)
0.38
Cooling
Operation1
(dB)
ID Blower Only (dB)
Cooling Operation1 (dB)
63
76
76
74
76
125
63
70
66
70
250
55
62
59
62
500
54
55
58
59
1000
48
48
53
53
2000
44
44
48
48
4000
41
44
45
46
8000
42
43
43
44
1. Differentials for Cooling Operation (IDB, COMP, & ODF) are logarithmically calculated from the horizontal flow sound test.
• Tested in accordance with AHRI Standard 260-2001. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning
Equipment.
• Testing datum includes effect of standard inlet air filters.
• Test duct dimension: 18 in. wide x 28 in. high x 8 ft. long, no elbows.
• Test duct termination is flush with reverberant room wall.
• Duct end (sound reflection) corrections included: (7.2, 3.4, 1.2, 0.4, 0.1, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 2k, 4k, 8k) Hz respectively.
Johnson Controls Unitary Products
39
5123249-TTG-A-0515
UNIT DESCRIPTION / MODEL
ZVTA5 / 5 Ton / Standard Static Belt Drive
TEST CONFIGURATION
Indoor Blower Speed (RPM)
Vertical (Bottom Return) Ducted Inlet
812 - 3 Turns Open Equivalent
915- 1 Turn Open Equivalent
0.6
0.8
Airflow (CFM)
1575
1800
Blower Motor BHP
0.64
External Static Pressure (IWG)
Octave Center Freq. Hz
ID Blower Only (dB)
0.83
Cooling Operation1 (dB)
ID Blower Only (dB)
Cooling Operation1 (dB)
63
75
78
80
80
125
66
80
69
81
250
59
66
62
65
500
60
60
63
63
1000
57
57
60
60
2000
52
53
55
55
4000
49
50
53
53
8000
44
45
47
47
1. Differentials for Cooling Operation (IDB, COMP, & ODF) are logarithmically calculated from the horizontal flow sound test.
• Tested in accordance with AHRI Standard 260-2001. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning
Equipment.
• Testing datum includes effect of standard inlet air filters.
• Test duct dimension: 18 in. wide x 28 in. high x 8 ft. long, no elbows.
• Test duct termination is flush with reverberant room wall.
• Duct end (sound reflection) corrections included: (7.2, 3.4, 1.2, 0.4, 0.1, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 2k, 4k, 8k) Hz respectively.
Indoor Sound Power Levels (Vertical Ducted Discharge, Standard Static Belt Drive)
UNIT DESCRIPTION / MODEL
ZVTA3 / 3 Ton / Standard Static Belt Drive
TEST CONFIGURATION
Indoor Blower Speed (RPM)
Vertical (Bottom Supply) Ducted Discharge
609 - 3 Turns Open Equivalent
712 - 1 Turn Open Equivalent
External Static Pressure (IWG)
0.4
0.6
Airflow (CFM)
850
950
Blower Motor BHP
0.32
0.42
1
Octave Center Freq. Hz
ID Blower Only (dB)
Cooling Operation (dB)
ID Blower Only (dB)
Cooling Operation1 (dB)
63
76
77
81
81
125
68
68
72
72
250
55
65
57
57
500
56
57
57
57
1000
51
57
52
56
2000
49
49
50
50
4000
48
48
49
51
8000
46
46
47
48
1. Differentials for Cooling Operation (IDB, COMP, & ODF) are logarithmically calculated from the horizontal flow sound test.
• Tested in accordance with AHRI Standard 260-2001. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning
Equipment.
• Testing datum includes effect of standard inlet air filters.
• Test duct dimension: 18 in. wide x 28 in. high x 8 ft. long, no elbows.
• Test duct termination is flush with reverberant room wall.
• Duct end (sound reflection) corrections included: (7.2, 3.4, 1.2, 0.4, 0.1, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 2k, 4k, 8k) Hz respectively.
40
Johnson Controls Unitary Products
5123249-TTG-A-0515
UNIT DESCRIPTION / MODEL
ZVTA4 / 4 Ton / Standard Static Belt Drive
TEST CONFIGURATION
Vertical (Bottom Supply) Ducted Discharge
Indoor Blower Speed (RPM)
609 - 3 Turns Open Equivalent
712 - 1 Turn Open Equivalent
0.4
0.6
External Static Pressure (IWG)
Airflow (CFM)
850
950
Blower Motor BHP
0.32
0.42
Octave Center Freq. Hz
ID Blower Only (dB)
Cooling Operation1 (dB)
ID Blower Only (dB)
Cooling Operation1 (dB)
63
76
77
81
81
125
68
68
72
72
250
55
65
57
57
500
56
57
57
57
1000
51
57
52
56
2000
49
49
50
50
4000
48
48
49
51
8000
46
46
47
48
1. Differentials for Cooling Operation (IDB, COMP, & ODF) are logarithmically calculated from the horizontal flow sound test.
• Tested in accordance with AHRI Standard 260-2001. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning
Equipment.
• Testing datum includes effect of standard inlet air filters.
• Test duct dimension: 18 in. wide x 28 in. high x 8 ft. long, no elbows.
• Test duct termination is flush with reverberant room wall.
• Duct end (sound reflection) corrections included: (7.2, 3.4, 1.2, 0.4, 0.1, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 2k, 4k, 8k) Hz respectively.
UNIT DESCRIPTION / MODEL
ZVTA5 / 5 Ton / Standard Static Belt Drive
TEST CONFIGURATION
Vertical (Bottom Supply) Ducted Discharge
Indoor Blower Speed (RPM)
809 - 3 Turns Open Equivalent
External Static Pressure (IWG)
914 - 1 Turn Open Equivalent
0.5
0.8
Airflow (CFM)
1700
1800
Blower Motor BHP
0.64
0.83
1
Octave Center Freq. Hz
ID Blower Only (dB)
Cooling Operation (dB)
ID Blower Only (dB)
Cooling Operation1 (dB)
63
81
81
79
79
125
75
75
75
76
250
65
65
63
63
500
67
67
67
67
1000
63
63
63
63
2000
61
62
61
61
4000
62
62
61
61
8000
57
57
56
56
1. Differentials for Cooling Operation (IDB, COMP, & ODF) are logarithmically calculated from the horizontal flow sound test.
• Tested in accordance with AHRI Standard 260-2001. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning
Equipment.
• Testing datum includes effect of standard inlet air filters.
• Test duct dimension: 18 in. wide x 28 in. high x 8 ft. long, no elbows.
• Test duct termination is flush with reverberant room wall.
• Duct end (sound reflection) corrections included: (7.2, 3.4, 1.2, 0.4, 0.1, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 2k, 4k, 8k) Hz respectively.
Johnson Controls Unitary Products
41
5123249-TTG-A-0515
Indoor Sound Power Levels (Horizontal Ducted Inlet, High Static Belt Drive)
UNIT DESCRIPTION / MODEL
ZVTA3 / 3 Ton / High Static Belt Drive
TEST CONFIGURATION
Horizontal (Side Return) Ducted Inlet
876 - 4 Turns Open Equivalent
1,064 - 1/2 Turn Open Equivalent
1,190 - 2.5 Turns Open Equivalent1
1.0
1.6
2.0 1
Nominal Airflow (CFM)
1,200
1,100
1,000
Blower Motor BHP
0.64
0.93
Indoor Blower Speed (RPM)
External Static Pressure (IWG)
1.08
Octave Center Freq. Hz
ID Blower
Only (dB)
Cooling
Operation2 (dB)
ID Blower
Only (dB)
Cooling
Operation2 (dB)
ID Blower
Only (dB)
Cooling
Operation2 (dB)
63
75
80
81
81
81
83
125
69
71
71
73
73
75
250
62
68
66
71
68
70
500
54
56
57
59
59
60
1000
52
56
56
58
58
60
2000
47
49
52
52
54
56
4000
43
45
48
49
51
53
8000
43
45
45
46
47
48
1. Requires driven pulley #AK-56, normal high static pulley is an #AK-69.
2. Cooling Operation – ID blower, compressor and outdoor fan operating at 230 VAC.
• Tested in accordance with AHRI Standard 260-2001. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning
Equipment.
• Testing datum includes effect of standard inlet air filters.
• Test duct dimension: 18 in. wide x 28 in. high x 8 ft. long, no elbows.
• Test duct termination is flush with reverberant room wall.
• Duct end (sound reflection) corrections included: (7.2, 3.4, 1.2, 0.4, 0.1, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 2k, 4k, 8k) Hz respectively.
UNIT DESCRIPTION / MODEL
ZVTA4 / 4 Ton / High Static Belt Drive
TEST CONFIGURATION
Horizontal (Side Return) Ducted Inlet
Indoor Blower Speed (RPM)
965 - 5.5 Turns Open Equivalent
1,088 - 4 Turns Open Equivalent
1.0
1.6
2.0
Nominal Airflow (CFM)
1,600
1,400
1,200
Blower Motor BHP
0.86
1.03
1.13
External Static Pressure (IWG)
1,186 - 2.5 Turns Open Equivalent
Octave Center Freq. Hz
ID Blower
Only (dB)
Cooling
Operation1 (dB)
ID Blower
Only (dB)
Cooling
Operation1 (dB)
ID Blower
Only (dB)
Cooling
Operation1 (dB)
63
74
80
77
80
81
81
125
69
74
72
75
75
76
250
68
68
68
69
70
71
500
62
62
60
61
61
63
1000
60
61
58
58
59
60
2000
57
57
53
54
55
56
4000
56
56
49
50
51
52
8000
54
54
45
47
47
48
1. Cooling Operation – ID blower, compressor and outdoor fan operating at 230 VAC.
• Tested in accordance with AHRI Standard 260-2001. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning
Equipment.
• Testing datum includes effect of standard inlet air filters.
• Test duct dimension: 18 in. wide x 28 in. high x 8 ft. long, no elbows.
• Test duct termination is flush with reverberant room wall.
• Duct end (sound reflection) corrections included: (7.2, 3.4, 1.2, 0.4, 0.1, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 2k, 4k, 8k) Hz respectively.
42
Johnson Controls Unitary Products
5123249-TTG-A-0515
UNIT DESCRIPTION / MODEL
ZVTA5 / 5 Ton / High Static Belt Drive
TEST CONFIGURATION
Indoor Blower Speed (RPM)
Horizontal (Side Return) Ducted Inlet
1,012- 5.5 Turns Open Equivalent
1,134 - 3 Turns Open Equivalent
1,174 - 2 Turns Open Equivalent
1.0
1.6
2.0
Nominal Airflow (CFM)
2,000
1,800
1,600
Blower Motor BHP
1.04
1.25
External Static Pressure (IWG)
1.39
Octave Center Freq. Hz
ID Blower
Only (dB)
Cooling
Operation1 (dB)
ID Blower
Only (dB)
Cooling
Operation1 (dB)
ID Blower
Only (dB)
Cooling
Operation1 (dB)
63
76
78
78
79
79
81
125
70
73
73
76
74
77
250
68
70
68
69
69
70
500
61
62
61
62
60
62
1000
61
62
61
62
58
60
2000
57
58
57
58
54
56
4000
56
56
55
56
52
53
8000
50
50
50
50
47
48
1. Cooling Operation – ID blower, compressor and outdoor fan operating at 230 VAC.
• Tested in accordance with AHRI Standard 260-2001. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning
Equipment.
• Testing datum includes effect of standard inlet air filters.
• Test duct dimension: 18 in. wide x 28 in. high x 8 ft. long, no elbows.
• Test duct termination is flush with reverberant room wall.
• Duct end (sound reflection) corrections included: (7.2, 3.4, 1.2, 0.4, 0.1, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 2k, 4k, 8k) Hz respectively.
Indoor Sound Power Levels (Horizontal Ducted Discharge, High Static Belt Drive)
UNIT DESCRIPTION / MODEL
ZVTA3 / 3 Ton / High Static Belt Drive
Horizontal (Side Supply) Ducted Discharge
TEST CONFIGURATION
896 - 3.5 Turns Open Equivalent
1,072 - Fully Closed Equivalent
1,170 - 2.5 Turns Open Equivalent1
1.0
1.6
2.0 1
Nominal Airflow (CFM)
1,200
1,100
1,000
Blower Motor BHP
0.64
0.93
1.08
Indoor Blower Speed (RPM)
External Static Pressure (IWG)
Octave Center Freq. Hz
ID Blower
Only (dB)
Cooling
Operation2 (dB)
ID Blower
Only (dB)
Cooling
Operation2 (dB)
ID Blower
Only (dB)
Cooling
Operation2 (dB)
63
77
81
83
84
83
84
125
74
76
76
77
80
80
250
67
68
70
70
72
73
500
65
66
67
67
67
68
1000
61
62
67
67
66
69
2000
58
60
63
63
63
64
4000
57
59
62
62
62
63
8000
51
53
56
57
56
58
1. Requires driven pulley #AK-56, normal high static pulley is an #AK-69.
2. Cooling Operation – ID blower, compressor and outdoor fan operating at 230 VAC.
• Tested in accordance with AHRI Standard 260-2001. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning
Equipment.
• Testing datum includes effect of standard inlet air filters.
• Test duct dimension: 18 in. wide x 28 in. high x 8 ft. long, no elbows.
• Test duct termination is flush with reverberant room wall.
• Duct end (sound reflection) corrections included: (7.2, 3.4, 1.2, 0.4, 0.1, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 2k, 4k, 8k) Hz respectively.
Johnson Controls Unitary Products
43
5123249-TTG-A-0515
UNIT DESCRIPTION / MODEL
ZVTA4 / 4 Ton / High Static Belt Drive
TEST CONFIGURATION
Indoor Blower Speed (RPM)
Horizontal (Side Supply) Ducted Discharge
922 - 6 Turns Open Equivalent
1,069 - 4 Turns Open Equivalent
1,165 - 2.5 Turns Open Equivalent
1.0
1.6
2.0
Nominal Airflow (CFM)
1,600
1,400
1,200
Blower Motor BHP
0.86
1.03
External Static Pressure (IWG)
1.13
Octave Center Freq. Hz
ID Blower
Only (dB)
Cooling
Operation1 (dB)
ID Blower
Only (dB)
Cooling
Operation1 (dB)
ID Blower
Only (dB)
Cooling
Operation1 (dB)
63
80
82
82
83
84
84
125
76
77
76
77
78
79
250
71
72
72
72
74
74
500
69
69
69
69
70
70
1000
65
65
69
69
70
70
2000
64
64
64
64
65
65
4000
63
63
63
63
64
64
8000
58
58
58
58
59
59
1. Cooling Operation – ID blower, compressor and outdoor fan operating at 230 VAC.
• Tested in accordance with AHRI Standard 260-2001. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning
Equipment.
• Testing datum includes effect of standard inlet air filters.
• Test duct dimension: 18 in. wide x 28 in. high x 8 ft. long, no elbows.
• Test duct termination is flush with reverberant room wall.
• Duct end (sound reflection) corrections included: (7.2, 3.4, 1.2, 0.4, 0.1, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 2k, 4k, 8k) Hz respectively.
UNIT DESCRIPTION / MODEL
ZVTA5 / 5 Ton / High Static Belt Drive
Horizontal (Side Supply) Ducted Discharge
TEST CONFIGURATION
Indoor Blower Speed (RPM)
1,009- 5.5 Turns Open Equivalent
1,131 - 3 Turns Open Equivalent
1.0
1.6
2.0
2,000
1,800
1,600
External Static Pressure (IWG)
Nominal Airflow (CFM)
Blower Motor BHP
Octave Center Freq. Hz
1.04
ID Blower
Only (dB)
1,184 - 2 Turns Open Equivalent
1.25
Cooling
Operation1 (dB)
ID Blower
Only (dB)
1.39
Cooling
Operation1 (dB)
ID Blower
Only (dB)
Cooling
Operation1 (dB)
63
84
85
82
83
82
83
125
78
79
79
79
78
79
250
75
75
74
75
73
73
500
71
71
70
71
69
69
1000
69
69
71
71
71
72
2000
66
67
67
67
66
66
4000
66
66
66
67
66
66
8000
61
62
61
62
60
60
1. Cooling Operation – ID blower, compressor and outdoor fan operating at 230 VAC.
• Tested in accordance with AHRI Standard 260-2001. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning
Equipment.
• Testing datum includes effect of standard inlet air filters.
• Test duct dimension: 18 in. wide x 28 in. high x 8 ft. long, no elbows.
• Test duct termination is flush with reverberant room wall.
• Duct end (sound reflection) corrections included: (7.2, 3.4, 1.2, 0.4, 0.1, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 2k, 4k, 8k) Hz respectively.
44
Johnson Controls Unitary Products
5123249-TTG-A-0515
Indoor Sound Power Levels (Vertical Ducted Inlet, High Static Belt Drive)
UNIT DESCRIPTION / MODEL
ZVTA3 / 3 Ton / High Static Belt Drive
TEST CONFIGURATION
Vertical (Bottom Return) Ducted Inlet
927 - 3 Turns Open Equivalent
1,085 - 1/2 Turn Open Equivalent
1,190 - 2.5 Turns Open Equivalent1
1.0
1.6
2.01
Nominal Airflow (CFM)
1,200
1,100
1,000
Blower Motor BHP
0.68
0.93
1.09
Indoor Blower Speed (RPM)
External Static Pressure (IWG)
Octave Center Freq. Hz
ID Blower
Only (dB)
Cooling
Operation2 (dB)
ID Blower
Only (dB)
Cooling
Operation2 (dB)
ID Blower
Only (dB)
Cooling
Operation2 (dB)
63
77
79
82
83
79
81
125
68
69
70
71
72
73
250
60
67
62
69
64
67
500
58
58
63
63
62
63
1000
54
55
60
60
60
60
2000
48
49
56
56
55
55
4000
43
44
48
49
51
51
8000
44
44
45
46
47
47
1. Requires driven pulley #AK-56, normal high static pulley is an #AK-69.
2. Differentials for Cooling Operation (IDB, COMP, & ODF) are logarithmically calculated from the horizontal flow sound test.
• Tested in accordance with AHRI Standard 260-2001. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning
Equipment.
• Testing datum includes effect of standard inlet air filters.
• Test duct dimension: 18 in. wide x 28 in. high x 8 ft. long, no elbows.
• Test duct termination is flush with reverberant room wall.
• Duct end (sound reflection) corrections included: (7.2, 3.4, 1.2, 0.4, 0.1, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 2k, 4k, 8k) Hz respectively.
UNIT DESCRIPTION / MODEL
ZVTA4 / 4 Ton / High Static Belt Drive
TEST CONFIGURATION
Indoor Blower Speed (RPM)
Vertical (Bottom Return) Ducted Inlet
968 - 5.5 Turns Open Equivalent
1,120 - 3.5 Turns Open Equivalent
1,218 - 2.0 Turns Open Equivalent
1.0
1.6
2.0
Nominal Airflow (CFM)
1,600
1,400
1,200
Blower Motor BHP
0.86
1.03
1.13
External Static Pressure (IWG)
Octave Center Freq. Hz
ID Blower
Only (dB)
Cooling
Operation1 (dB)
ID Blower
Only (dB)
Cooling
Operation1 (dB)
ID Blower
Only (dB)
Cooling
Operation1 (dB)
63
77
79
78
78
81
81
125
69
73
71
73
73
74
250
63
63
63
64
66
66
500
63
64
62
63
64
64
1000
59
59
59
59
61
61
2000
54
54
53
54
56
56
4000
49
49
48
48
50
51
8000
45
46
45
46
47
47
1. Differentials for Cooling Operation (IDB, COMP, & ODF) are logarithmically calculated from the horizontal flow sound test.
• Tested in accordance with AHRI Standard 260-2001. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning
Equipment.
• Testing datum includes effect of standard inlet air filters.
• Test duct dimension: 18 in. wide x 28 in. high x 8 ft. long, no elbows.
• Test duct termination is flush with reverberant room wall.
• Duct end (sound reflection) corrections included: (7.2, 3.4, 1.2, 0.4, 0.1, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 2k, 4k, 8k) Hz respectively.
Johnson Controls Unitary Products
45
5123249-TTG-A-0515
UNIT DESCRIPTION / MODEL
ZVTA5 / 5 Ton / High Static Belt Drive
TEST CONFIGURATION
Indoor Blower Speed (RPM)
Vertical (Bottom Return) Ducted Inlet
1,039 - 5 Turns Open Equivalent
1,143 - 3 Turns Open Equivalent
1,201 - 2 Turns Open Equivalent
1.0
1.6
2.0
Nominal Airflow (CFM)
2,000
1,800
1,600
Blower Motor BHP
1.11
1.25
External Static Pressure (IWG)
1.39
Octave Center Freq. Hz
ID Blower
Only (dB)
Cooling
Operation1 (dB)
ID Blower
Only (dB)
Cooling
Operation1 (dB)
ID Blower
Only (dB)
Cooling
Operation1 (dB)
63
79
80
77
77
81
81
125
74
75
71
73
73
74
250
63
65
63
64
63
65
500
62
63
64
64
62
62
1000
61
61
61
61
59
59
2000
55
56
55
56
54
55
4000
52
52
50
51
50
50
8000
47
47
46
46
46
46
1. Differentials for Cooling Operation (IDB, COMP, & ODF) are logarithmically calculated from the horizontal flow sound test.
• Tested in accordance with AHRI Standard 260-2001. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning
Equipment.
• Testing datum includes effect of standard inlet air filters.
• Test duct dimension: 18 in. wide x 28 in. high x 8 ft. long, no elbows.
• Test duct termination is flush with reverberant room wall.
• Duct end (sound reflection) corrections included: (7.2, 3.4, 1.2, 0.4, 0.1, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 2k, 4k, 8k) Hz respectively.
Indoor Sound Power Levels (Vertical Ducted Discharge, High Static Belt Drive)
UNIT DESCRIPTION / MODEL
ZVTA3 / 3 Ton / High Static Belt Drive
TEST CONFIGURATION
Vertical (Bottom Supply) Ducted Discharge
920 - 3.0 Turns Open Equivalent
1,074 - Fully Closed Equivalent
1,189 - 2.0 Turns Open Equivalent1
1.0
1.6
2.01
Nominal Airflow (CFM)
1,200
1,100
1,000
Blower Motor BHP
0.68
0.93
1.09
Indoor Blower Speed (RPM)
External Static Pressure (IWG)
Octave Center Freq. Hz
ID Blower
Only (dB)
Cooling
Operation2 (dB)
ID Blower
Only (dB)
Cooling
Operation2 (dB)
ID Blower
Only (dB)
Cooling
Operation2 (dB)
63
81
82
81
81
82
82
125
78
78
78
78
81
81
250
69
70
70
71
74
74
500
67
68
68
69
71
71
1000
62
63
67
68
70
71
2000
60
61
62
63
65
66
4000
61
61
63
63
66
66
8000
54
55
57
57
60
61
1. Requires driven pulley #AK-56, normal high static pulley is an #AK-69.
2. Differentials for Cooling Operation (IDB, COMP, & ODF) are logarithmically calculated from the horizontal flow sound test.
• Tested in accordance with AHRI Standard 260-2001. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning
Equipment.
• Testing datum includes effect of standard inlet air filters.
• Test duct dimension: 18 in. wide x 28 in. high x 8 ft. long, no elbows.
• Test duct termination is flush with reverberant room wall.
• Duct end (sound reflection) corrections included: (7.2, 3.4, 1.2, 0.4, 0.1, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 2k, 4k, 8k) Hz respectively.
46
Johnson Controls Unitary Products
5123249-TTG-A-0515
UNIT DESCRIPTION / MODEL
ZVTA4 / 4 Ton / High Static Belt Drive
TEST CONFIGURATION
Vertical (Bottom Supply) Ducted Discharge
Indoor Blower Speed (RPM)
962 - 5.5 Turns Open Equivalent
1,092 - 3.5 Turns Open Equivalent
1.0
1.6
2.0
1,600
1,400
1,200
External Static Pressure (IWG)
Nominal Airflow (CFM)
0.86
Blower Motor BHP
1,190 - 2.0 Turns Open Equivalent
1.03
1.13
Octave Center Freq. Hz
ID Blower
Only (dB)
Cooling
Operation1 (dB)
ID Blower
Only (dB)
Cooling
Operation1 (dB)
ID Blower
Only (dB)
Cooling
Operation1 (dB)
63
83
84
82
82
83
83
125
80
81
79
80
80
81
250
75
75
74
75
75
75
500
71
72
70
71
71
72
1000
66
67
70
71
72
72
2000
63
64
64
64
65
65
4000
64
64
64
64
65
66
8000
58
59
59
59
60
60
1. Differentials for Cooling Operation (IDB, COMP, & ODF) are logarithmically calculated from the horizontal flow sound test.
• Tested in accordance with AHRI Standard 260-2001. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning
Equipment.
• Testing datum includes effect of standard inlet air filters.
• Test duct dimension: 18 in. wide x 28 in. high x 8 ft. long, no elbows.
• Test duct termination is flush with reverberant room wall.
• Duct end (sound reflection) corrections included: (7.2, 3.4, 1.2, 0.4, 0.1, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 2k, 4k, 8k) Hz respectively.
UNIT DESCRIPTION / MODEL
ZVTA5 / 5 Ton / High Static Belt Drive
TEST CONFIGURATION
Vertical (Bottom Supply) Ducted Discharge
1,033 - 5.5 Turns Open Equivalent
1,135 - 3 turns Open Equivalent
1.0
1.6
2.0
Nominal Airflow (CFM)
2,000
1,135
1,175
Blower Motor BHP
1.11
1.25
1.39
Indoor Blower Speed (RPM)
External Static Pressure (IWG)
1,175 - 2.5 Turns Open Equivalent
Octave Center Freq. Hz
ID Blower
Only (dB)
Cooling
Operation1 (dB)
ID Blower
Only (dB)
Cooling
Operation1 (dB)
ID Blower
Only (dB)
Cooling
Operation1 (dB)
63
83
83
83
83
85
86
125
84
84
82
82
79
81
250
79
80
77
78
66
66
500
73
73
70
71
65
66
1000
69
70
69
70
61
65
2000
67
67
65
66
60
61
4000
67
68
66
67
61
62
8000
62
63
60
61
54
54
1. Differentials for Cooling Operation (IDB, COMP, & ODF) are logarithmically calculated from the horizontal flow sound test.
• Tested in accordance with AHRI Standard 260-2001. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning
Equipment.
• Testing datum includes effect of standard inlet air filters.
• Test duct dimension: 18 in. wide x 28 in. high x 8 ft. long, no elbows.
• Test duct termination is flush with reverberant room wall.
• Duct end (sound reflection) corrections included: (7.2, 3.4, 1.2, 0.4, 0.1, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 2k, 4k, 8k) Hz respectively.
Outdoor Sound Power Levels ZVTA3 thru TA5
Size
(Tons)
TA3
(3)
TA4
(4)
TA5
(5)
Model
Sound Rating1
dB (A)
63
125
ZV
75
78.5
78.5
74.0
72.0
68.5
ZV
75
83.0
78.5
74.5
72.0
ZV
75
80.0
78.0
74.5
72.5
Octave Band Centerline Frequency (Hz)
250
500
1000
2000
4000
8000
65.0
60.5
53.0
69.5
63.0
58.0
55.5
69.0
63.0
57.5
52.0
1. Rated in accordance with AHRI 270 standard.
Johnson Controls Unitary Products
47
5123249-TTG-A-0515
Electrical Data
ZVTA3 thru TA5 Standard Indoor Blower - Without Powered Convenience Outlet
Size
(Tons)
Volt
Compressors
(each)
RLA LRA
MCC
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Exh
Motor
Pwr
Conv
Outlet
FLA
FLA
FLA
FLA
208
11.6
73.0
18.1
3.5
4.3
5.5
0.0
230
11.6
73.0
18.1
3.5
4.3
5.5
0.0
460
5.7
38.0
8.9
3.5
2.1
2.2
0.0
575
4.0
25.6
6.2
3.5
2.0
1.8
0.0
208
14.0
83.1
21.9
3.5
4.3
5.5
0.0
230
14.0
83.1
21.9
3.5
4.3
5.5
0.0
460
6.4
41.0
10.0
3.5
2.1
2.2
0.0
575
4.6
33.0
7.1
3.5
2.0
1.8
0.0
208
16.5 110.0 25.8
3.5
4.3
5.5
0.0
230
16.5 110.0 25.8
3.5
4.3
5.5
0.0
460
7.2
52.0
11.3
3.5
2.1
2.2
0.0
575
5.5
38.9
8.6
3.5
2.0
1.8
0.0
TA3
(3)
TA4
(4)
TA5
(5)
Electric Heat Option
MCA1
(Amps)
Model
kW
Stages
Amps
None
E03
E06
E08
E15
None
E03
E06
E08
E15
None
E03
E06
E08
E15
None
E08
E15
None
E06
E08
E15
E20
None
E06
E08
E15
E20
None
E06
E08
E15
E20
None
E08
E15
E20
None
E06
E08
E15
E20
E23
None
E06
E08
E15
E20
E23
None
E06
E08
E15
E20
E23
None
E08
E15
E20
E23
2.3
4.5
6.8
11.3
3.0
6.0
9.0
15.0
3.0
6.0
9.0
15.0
9.0
15.0
4.5
6.8
11.3
15.0
6.0
9.0
15.0
20.0
6.0
9.0
15.0
20.0
9.0
15.0
20.0
4.5
6.8
11.3
15.0
18.0
6.0
9.0
15.0
20.0
24.0
6.0
9.0
15.0
20.0
24.0
9.0
15.0
20.0
24.0
1
1
1
2
1
1
1
2
1
1
1
2
1
2
1
1
2
2
1
1
2
2
1
1
2
2
1
2
2
1
1
2
2
2
1
1
2
2
2
1
1
2
2
2
1
2
2
2
6.4
12.5
18.9
31.4
7.2
14.4
21.7
36.1
3.6
7.2
10.8
18.0
8.7
14.4
12.5
18.9
31.4
41.6
14.4
21.7
36.1
48.1
7.2
10.8
18.0
24.1
8.7
14.4
19.2
12.5
18.9
31.4
41.6
50.0
14.4
21.7
36.1
48.1
57.7
7.2
10.8
18.0
24.1
28.9
8.7
14.4
19.2
23.1
25.8
25.8
25.8
29.0
44.6
25.8
25.8
25.8
32.4
50.5
12.7
12.7
12.7
16.2
25.2
9.8
13.3
20.5
28.8
28.8
29.0
44.6
57.4
28.8
28.8
32.4
50.5
65.5
13.6
13.6
16.2
25.2
32.7
10.6
13.3
20.5
26.6
31.9
31.9
31.9
44.6
57.4
67.8
31.9
31.9
32.4
50.5
65.5
77.5
14.6
14.6
16.2
25.2
32.7
38.7
11.7
13.3
20.5
26.6
31.4
MCA1
w/Pwr
Exh
(Amps)
31.3
31.3
31.3
35.8
51.5
31.3
31.3
31.3
39.3
57.4
14.9
14.9
14.9
18.9
27.9
11.6
15.6
22.8
34.3
34.3
35.8
51.5
64.3
34.3
34.3
39.3
57.4
72.4
15.8
15.8
18.9
27.9
35.4
12.4
15.6
22.8
28.8
37.4
37.4
37.4
51.5
64.3
74.7
37.4
37.4
39.3
57.4
72.4
84.4
16.8
16.8
18.9
27.9
35.4
41.5
13.5
15.6
22.8
28.8
33.6
2
Max Fuse2/ Max Fuse3 /
Breaker3 Breaker
Size w/
Size
Pwr Exh
(Amps)
(Amps)
35
40
35
40
35
40
35
40
45
60
35
40
35
40
35
40
35
40
60
60
15
20
15
20
15
20
20
20
30
30
15
15
15
20
25
25
40
45
40
45
40
45
45
60
60
70
40
45
40
45
40
45
60
60
70
80
20
20
20
20
20
20
30
30
35
40
15
15
15
20
25
25
30
30
40
50
40
50
40
50
45
60
60
70
70
80
40
50
40
50
45
50
60
60
70
80
80
90
20
20
20
20
20
20
30
30
35
40
40
45
15
15
15
20
25
25
30
30
35
35
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
48
Johnson Controls Unitary Products
5123249-TTG-A-0515
ZVTA3 thru TA5 Hi Static Indoor Blower - Without Powered Convenience Outlet
Size
(Tons)
Volt
Compressors
(each)
RLA LRA
MCC
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Exh
Motor
Pwr
Conv
Outlet
FLA
FLA
FLA
FLA
208
11.6
73.0
18.1
3.5
4.3
5.5
0.0
230
11.6
73.0
18.1
3.5
4.3
5.5
0.0
460
5.7
38.0
8.9
3.5
2.1
2.2
0.0
575
4.0
25.6
6.2
3.5
2.0
1.8
0.0
208
14.0
83.1
21.9
3.5
4.3
5.5
0.0
230
14.0
83.1
21.9
3.5
4.3
5.5
0.0
460
6.4
41.0
10.0
3.5
2.1
2.2
0.0
575
4.6
33.0
7.1
3.5
2.0
1.8
0.0
208
16.5 110.0 25.8
3.5
6.8
5.5
0.0
230
16.5 110.0 25.8
3.5
6.8
5.5
0.0
460
7.2
52.0
11.3
3.5
3.2
2.2
0.0
575
5.5
38.9
8.6
3.5
2.6
1.8
0.0
TA3
(3)
TA4
(4)
TA5
(5)
Electric Heat Option
MCA
(Amps)
MCA1
w/Pwr
Exh
(Amps)
25.8
25.8
25.8
29.0
44.6
25.8
25.8
25.8
32.4
50.5
12.7
12.7
12.7
16.2
25.2
9.8
13.3
20.5
28.8
28.8
29.0
44.6
57.4
28.8
28.8
32.4
50.5
65.5
13.6
13.6
16.2
25.2
32.7
10.6
13.3
20.5
26.6
34.4
34.4
34.4
47.7
60.5
71.0
34.4
34.4
35.6
53.6
68.6
80.7
15.7
15.7
17.5
26.5
34.0
40.0
12.3
14.1
21.3
27.3
32.1
31.3
31.3
31.3
35.8
51.5
31.3
31.3
31.3
39.3
57.4
14.9
14.9
14.9
18.9
27.9
11.6
15.6
22.8
34.3
34.3
35.8
51.5
64.3
34.3
34.3
39.3
57.4
72.4
15.8
15.8
18.9
27.9
35.4
12.4
15.6
22.8
28.8
39.9
39.9
39.9
54.6
67.4
77.8
39.9
39.9
42.4
60.5
75.5
87.5
17.9
17.9
20.2
29.2
36.8
42.8
14.1
16.3
23.5
29.6
34.4
1
Model
kW
Stages
Amps
None
E03
E06
E08
E15
None
E03
E06
E08
E15
None
E03
E06
E08
E15
None
E08
E15
None
E06
E08
E15
E20
None
E06
E08
E15
E20
None
E06
E08
E15
E20
None
E08
E15
E20
None
E06
E08
E15
E20
E23
None
E06
E08
E15
E20
E23
None
E06
E08
E15
E20
E23
None
E08
E15
E20
E23
2.3
4.5
6.8
11.3
3.0
6.0
9.0
15.0
3.0
6.0
9.0
15.0
9.0
15.0
4.5
6.8
11.3
15.0
6.0
9.0
15.0
20.0
6.0
9.0
15.0
20.0
9.0
15.0
20.0
4.5
6.8
11.3
15.0
18.0
6.0
9.0
15.0
20.0
24.0
6.0
9.0
15.0
20.0
24.0
9.0
15.0
20.0
24.0
1
1
1
2
1
1
1
2
1
1
1
2
1
2
1
1
2
2
1
1
2
2
1
1
2
2
1
2
2
1
1
2
2
2
1
1
2
2
2
1
1
2
2
2
1
2
2
2
6.4
12.5
18.9
31.4
7.2
14.4
21.7
36.1
3.6
7.2
10.8
18.0
8.7
14.4
12.5
18.9
31.4
41.6
14.4
21.7
36.1
48.1
7.2
10.8
18.0
24.1
8.7
14.4
19.2
12.5
18.9
31.4
41.6
50.0
14.4
21.7
36.1
48.1
57.7
7.2
10.8
18.0
24.1
28.9
8.7
14.4
19.2
23.1
2
Max Fuse2/ Max Fuse3 /
Breaker3 Breaker
Size w/
Size
Pwr Exh
(Amps)
(Amps)
35
40
35
40
35
40
35
40
45
60
35
40
35
40
35
40
35
40
60
60
15
20
15
20
15
20
20
20
30
30
15
15
15
20
25
25
40
45
40
45
40
45
45
60
60
70
40
45
40
45
40
45
60
60
70
80
20
20
20
20
20
20
30
30
35
40
15
15
15
20
25
25
30
30
45
50
45
50
45
50
50
60
70
70
80
80
45
50
45
50
45
50
60
70
70
80
90
90
20
25
20
25
20
25
30
30
35
40
40
45
15
15
15
20
25
25
30
30
35
35
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
Johnson Controls Unitary Products
49
5123249-TTG-A-0515
ZVTA3 thru TA5 Standard Indoor Blower - With Powered Convenience Outlet
Size
(Tons)
Volt
Compressors
(each)
RLA LRA
MCC
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Exh
Motor
Pwr
Conv
Outlet
FLA
FLA
FLA
FLA
208
11.6
73.0
18.1
3.5
4.3
5.5
10.0
230
11.6
73.0
18.1
3.5
4.3
5.5
10.0
460
5.7
38.0
8.9
3.5
2.1
2.2
5.0
575
4.0
25.6
6.2
3.5
2.0
1.8
4.0
208
14.0
83.1
21.9
3.5
4.3
5.5
10.0
230
14.0
83.1
21.9
3.5
4.3
5.5
10.0
460
6.4
41.0
10.0
3.5
2.1
2.2
5.0
575
4.6
33.0
7.1
3.5
2.0
1.8
4.0
208
16.5 110.0 25.8
3.5
4.3
5.5
10.0
230
16.5 110.0 25.8
3.5
4.3
5.5
10.0
460
7.2
52.0
11.3
3.5
2.1
2.2
5.0
575
5.5
38.9
8.6
3.5
2.0
1.8
4.0
TA3
(3)
TA4
(4)
TA5
(5)
Electric Heat Option
MCA
(Amps)
MCA1
w/Pwr
Exh
(Amps)
35.8
35.8
35.8
41.5
57.1
35.8
35.8
35.9
44.9
63.0
17.7
17.7
17.9
22.4
31.4
13.8
18.3
25.5
38.8
38.8
41.5
57.1
69.9
38.8
38.8
44.9
63.0
78.0
18.6
18.6
22.4
31.4
38.9
14.6
18.3
25.5
31.6
41.9
41.9
41.9
57.1
69.9
80.3
41.9
41.9
44.9
63.0
78.0
90.0
19.6
19.6
22.4
31.4
38.9
45.0
15.7
18.3
25.5
31.6
36.4
41.3
41.3
41.3
48.3
64.0
41.3
41.3
42.8
51.8
69.9
19.9
19.9
20.6
25.2
34.2
15.6
20.6
27.8
44.3
44.3
48.3
64.0
76.8
44.3
44.3
51.8
69.9
84.9
20.8
20.8
25.2
34.2
41.7
16.4
20.6
27.8
33.8
47.4
47.4
48.3
64.0
76.8
87.2
47.4
47.4
51.8
69.9
84.9
96.9
21.8
21.8
25.2
34.2
41.7
47.7
17.5
20.6
27.8
33.8
38.6
1
Model
kW
Stages
Amps
None
E03
E06
E08
E15
None
E03
E06
E08
E15
None
E03
E06
E08
E15
None
E08
E15
None
E06
E08
E15
E20
None
E06
E08
E15
E20
None
E06
E08
E15
E20
None
E08
E15
E20
None
E06
E08
E15
E20
E23
None
E06
E08
E15
E20
E23
None
E06
E08
E15
E20
E23
None
E08
E15
E20
E23
2.3
4.5
6.8
11.3
3.0
6.0
9.0
15.0
3.0
6.0
9.0
15.0
9.0
15.0
4.5
6.8
11.3
15.0
6.0
9.0
15.0
20.0
6.0
9.0
15.0
20.0
9.0
15.0
20.0
4.5
6.8
11.3
15.0
18.0
6.0
9.0
15.0
20.0
24.0
6.0
9.0
15.0
20.0
24.0
9.0
15.0
20.0
24.0
1
1
1
2
1
1
1
2
1
1
1
2
1
2
1
1
2
2
1
1
2
2
1
1
2
2
1
2
2
1
1
2
2
2
1
1
2
2
2
1
1
2
2
2
1
2
2
2
6.4
12.5
18.9
31.4
7.2
14.4
21.7
36.1
3.6
7.2
10.8
18.0
8.7
14.4
12.5
18.9
31.4
41.6
14.4
21.7
36.1
48.1
7.2
10.8
18.0
24.1
8.7
14.4
19.2
12.5
18.9
31.4
41.6
50.0
14.4
21.7
36.1
48.1
57.7
7.2
10.8
18.0
24.1
28.9
8.7
14.4
19.2
23.1
2
Max Fuse2/ Max Fuse3 /
Breaker3 Breaker
Size w/
Size
Pwr Exh
(Amps)
(Amps)
45
50
45
50
45
50
45
50
60
70
45
50
45
50
45
50
45
60
70
70
20
25
20
25
20
25
25
30
35
35
15
20
20
25
30
30
50
50
50
50
50
50
60
70
70
80
50
50
50
50
50
60
70
70
80
90
25
25
25
25
25
30
35
35
40
45
15
20
20
25
30
30
35
35
50
60
50
60
50
60
60
70
70
80
90
90
50
60
50
60
50
60
70
70
80
90
90
100
25
25
25
25
25
30
35
35
40
45
45
50
20
20
20
25
30
30
35
35
40
40
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
50
Johnson Controls Unitary Products
5123249-TTG-A-0515
ZVTA3 thru TA5 Hi Static Indoor Blower - With Powered Convenience Outlet
Size
(Tons)
Volt
Compressors
(each)
RLA LRA
MCC
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Exh
Motor
Pwr
Conv
Outlet
FLA
FLA
FLA
FLA
208
11.6
73.0
18.1
3.5
4.3
5.5
10.0
230
11.6
73.0
18.1
3.5
4.3
5.5
10.0
460
5.7
38.0
8.9
3.5
2.1
2.2
5.0
575
4.0
25.6
6.2
3.5
2.0
1.8
4.0
208
14.0
83.1
21.9
3.5
4.3
5.5
10.0
230
14.0
83.1
21.9
3.5
4.3
5.5
10.0
460
6.4
41.0
10.0
3.5
2.1
2.2
5.0
575
4.6
33.0
7.1
3.5
2.0
1.8
4.0
208
16.5 110.0 25.8
3.5
6.8
5.5
10.0
230
16.5 110.0 25.8
3.5
6.8
5.5
10.0
460
7.2
52.0
11.3
3.5
3.2
2.2
5.0
575
5.5
38.9
8.6
3.5
2.6
1.8
4.0
TA3
(3)
TA4
(4)
TA5
(5)
Electric Heat Option
Model
kW
Stages
Amps
None
E03
E06
E08
E15
None
E03
E06
E08
E15
None
E03
E06
E08
E15
None
E08
E15
None
E06
E08
E15
E20
None
E06
E08
E15
E20
None
E06
E08
E15
E20
None
E08
E15
E20
None
E06
E08
E15
E20
E23
None
E06
E08
E15
E20
E23
None
E06
E08
E15
E20
E23
None
E08
E15
E20
E23
2.3
4.5
6.8
11.3
3.0
6.0
9.0
15.0
3.0
6.0
9.0
15.0
9.0
15.0
4.5
6.8
11.3
15.0
6.0
9.0
15.0
20.0
6.0
9.0
15.0
20.0
9.0
15.0
20.0
4.5
6.8
11.3
15.0
18.0
6.0
9.0
15.0
20.0
24.0
6.0
9.0
15.0
20.0
24.0
9.0
15.0
20.0
24.0
1
1
1
2
1
1
1
2
1
1
1
2
1
2
1
1
2
2
1
1
2
2
1
1
2
2
1
2
2
1
1
2
2
2
1
1
2
2
2
1
1
2
2
2
1
2
2
2
6.4
12.5
18.9
31.4
7.2
14.4
21.7
36.1
3.6
7.2
10.8
18.0
8.7
14.4
12.5
18.9
31.4
41.6
14.4
21.7
36.1
48.1
7.2
10.8
18.0
24.1
8.7
14.4
19.2
12.5
18.9
31.4
41.6
50.0
14.4
21.7
36.1
48.1
57.7
7.2
10.8
18.0
24.1
28.9
8.7
14.4
19.2
23.1
MCA1
(Amps)
MCA1
w/Pwr
Exh
(Amps)
35.8
35.8
35.8
41.5
57.1
35.8
35.8
35.9
44.9
63.0
17.7
17.7
17.9
22.4
31.4
13.8
18.3
25.5
38.8
38.8
41.5
57.1
69.9
38.8
38.8
44.9
63.0
78.0
18.6
18.6
22.4
31.4
38.9
14.6
18.3
25.5
31.6
44.4
44.4
44.6
60.2
73.0
83.5
44.4
44.4
48.1
66.1
81.1
93.2
20.7
20.7
23.7
32.7
40.3
46.3
16.3
19.1
26.3
32.3
37.1
41.3
41.3
41.3
48.3
64.0
41.3
41.3
42.8
51.8
69.9
19.9
19.9
20.6
25.2
34.2
15.6
20.6
27.8
44.3
44.3
48.3
64.0
76.8
44.3
44.3
51.8
69.9
84.9
20.8
20.8
25.2
34.2
41.7
16.4
20.6
27.8
33.8
49.9
49.9
51.5
67.1
79.9
90.3
49.9
49.9
54.9
73.0
88.0
100.0
22.9
22.9
26.5
35.5
43.0
49.0
18.1
21.3
28.5
34.6
39.4
2
Max Fuse2/ Max Fuse3 /
Breaker3 Breaker
Size w/
Size
Pwr Exh
(Amps)
(Amps)
45
50
45
50
45
50
45
50
60
70
45
50
45
50
45
50
45
60
70
70
20
25
20
25
20
25
25
30
35
35
15
20
20
25
30
30
50
50
50
50
50
50
60
70
70
80
50
50
50
50
50
60
70
70
80
90
25
25
25
25
25
30
35
35
40
45
15
20
20
25
30
30
35
35
60
60
60
60
60
60
70
70
80
80
90
100
60
60
60
60
60
60
70
80
90
90
100
100
25
30
25
30
25
30
35
40
45
45
50
50
20
20
20
25
30
30
35
35
40
40
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
Johnson Controls Unitary Products
51
5123249-TTG-A-0515
Electric Heat Multipliers
Voltage
Nominal
240
480
600
Applied
208
230
460
575
kW Capacity Multipliers1
0.75
0.92
0.92
0.92
1. Electric heaters are rated at nominal voltage. Use this table to determine the electric heat
capacity for heaters applied at lower voltages.
52
Johnson Controls Unitary Products
5123249-TTG-A-0515
Typical Wiring Diagrams
ZVTA3 thru TA5 Typical Wiring Diagrams
Typical ZVTA3 thru TA5 Cooling Unit with Gas Heat 208/230 Volt Wiring Diagram
Johnson Controls Unitary Products
53
5123249-TTG-A-0515
Typical ZVTA3 thru TA5 Cooling Unit with Gas Heat 208/230 Volt Unit (Options)
54
Johnson Controls Unitary Products
5123249-TTG-A-0515
Typical ZVTA3 thru TA5 Cooling Unit with Gas Heat 460/575 Volt Wiring Diagram
Johnson Controls Unitary Products
55
5123249-TTG-A-0515
Typical ZVTA3 thru TA5 Cooling Unit with Gas Heat 460/575 Volt Unit (Options)
56
Johnson Controls Unitary Products
5123249-TTG-A-0515
Typical ZVTA3 thru TA5 Cooling Unit with/without Electric Heat 208/230 Volt Wiring Diagram
Johnson Controls Unitary Products
57
5123249-TTG-A-0515
Typical ZVTA3 thru TA5 Cooling Unit with/without Electric Heat 208/230 Volt Unit
58
Johnson Controls Unitary Products
5123249-TTG-A-0515
Typical ZVTA3 thru TA5 Cooling Unit with/without Electric Heat 460/575 Volt Wiring Diagram
Johnson Controls Unitary Products
59
5123249-TTG-A-0515
Typical ZVTA3 thru TA5 Cooling Unit with/without Electric Heat 460/575 Volt Unit (Options)
60
Johnson Controls Unitary Products
5123249-TTG-A-0515
BAS Controls Typical Wiring Diagrams
Typical SURVEYOR BAS Control Wiring Diagram
Johnson Controls Unitary Products
61
5123249-TTG-A-0515
Typical CPC BAS Control Wiring Diagram
62
Johnson Controls Unitary Products
5123249-TTG-A-0515
Typical HONEYWELL BAS Control Wiring Diagram
Johnson Controls Unitary Products
63
5123249-TTG-A-0515
Typical HONEYWELL BAS Control Wiring Diagram
64
Johnson Controls Unitary Products
5123249-TTG-A-0515
Weights and Dimensions
ZVTA3 thru TA5 Unit Weights
Unit 4 Point Load Weight
FRONT
LEFT
B
C
X
Y
A
LEFT
D
Weight (lbs.)
Center of Gravity
Size
Model
(Tons)
Shipping Operating
X
Y
TA3
ZV
927
922
42.4
24.7
(3)
TA4
ZV
965
960
42.5
25.5
(4)
TA5
ZV
973
968
41.6
25.5
5)
Johnson Controls Unitary Products
FRONT
4 Point Load Location (lbs.)
A
B
C
D
202
184
255
281
217
198
260
285
223
196
257
293
65
5123249-TTG-A-0515
ZVTA3 thru TA5 Unit Accessory Weights
Unit Accessory
Economizer
Power Exhaust
Electric Heat1
Gas Heat2
Variable Frequency Drive3
Weight (lbs.)
Shipping
Operating
90
85
40
35
49
49
110
110
30
30
1. Weight given is for the maximum heater size available
(24KW).
2. Weight given is for the maximum number of tube heat
exchangers available (8 tube).
3. Weight includes mounting hardware, controls and manual
bypass option (3 to 5 ton only).
ZVTA3 thru TA5 Unit Dimensions
ZT037 - 061
29.69
15.25
15.38
59.00
15.38
2X Ø 24.38
B
SEE DETAIL A FOR GAS INLET
A
C
D
E
11.38
F
59.00
4.19
LEFT
27.31
SEE DETAIL B
FOR DRAIN LOCATION
21.19
89.00
FRONT
66
Johnson Controls Unitary Products
5123249-TTG-A-0515
ZVTA3 thru TA5 Unit Physical Dimensions
Unit Model Number
A
42
ZVTA3, TA4, TA5
Detail A
B
89
Dimension (in.)
C
D
22 1/8
18 3/16
E
15 3/16
F
6 3/16
Detail B
3.184
Gas Pipe Inlet
Ø 2.000
Gas Exhaust Vent
5-3/8
Ø 3.126
3/4” FPT
14.594
ZVTA3 thru TA5 Unit Clearances
7.705
4.727
42” CABINET
Johnson Controls Unitary Products
Direction
Top1
Front
Rear
Distance (in.)
72
36
36
Direction
Right
Left
Bottom2
Distance (in.)
12
36
0
1. Units must be installed outdoors. Over hanging structure or
shrubs should not obscure condenser air discharge outlet.
2. Units may be installed on combustible floors made from wood
or class A, B or C roof covering materials.
67
5123249-TTG-A-0515
ZVTA3 thru TA5 Unit Bottom Duct Openings
TOP VIEW
89
32 11/16
6 13/16
6 13/16
SUPPLY
AIR
RETURN
AIR
27 1/2
LEFT
18
24
RIGHT
21
20 1/8 19 1/8
17 1/8
12 5/16
Bottom condensate drain
14 1/2
25 9/16
Bottom gas
supply entry
16 3/8
18 1/16
FRONT
Bottom power, control
and convenience outlet
wiring entry
3X Ø 0.875
Ø 2.469
68
Johnson Controls Unitary Products
5123249-TTG-A-0515
ZVTA3 thru TA5 Unit Electrical Entry
Disconnect Swith Cover
Power Entry Ø 2-1/2
Control Entry Ø 7/8
Power Entry Ø 2-1/2
Convenience Outlet Cover
Convenience Outlet
Power Entry Ø 7/8
FRONT
ZVTA3 thru TA5 Unit Side Duct Openings
Dot Plugs
18-1/4
A
Return
Air
Supply Air
D
B
2-31/32
5-5/32
C
31-11/16
ZVTA3 thru TA5 Side Duct Dimensions
Unit Model Number
ZVTA3, TA4, TA5
Johnson Controls Unitary Products
A
27 3/4
Dimension (in.)
B
C
12 1/16
27 1/2
D
16
69
5123249-TTG-A-0515
ZVTA3 thru TA5 Unit Left Duct Opening
30-3/8
4-5/16
ZVTA3 thru TA5 Unit Accessory Dimensions
ZVTA3 thru TA5 Roof Curb
RIGHT
80-5/8
INSULATED DECK UNDER
CONDENSER SECTION
20
SUPPLY
20
6
RETURN
2 TYP.
30
INSULATED DECK UNDER
COMPRESSOR SECTION
50-1/2
8 or 14
70
FRONT
Johnson Controls Unitary Products
5123249-TTG-A-0515
ZVTA3 thru TA5 Transition Roof Curb
2 TYP
50-1/2
23 4
30-1/2
80-5/8
26
RETURN
SUPPLY
10
76-5/8
59-1/4
94
FRONT
64-1/4
RIGHT
ZVTA3 thru TA5 Roof Curb Cutaway
3/4” X 1-1/4” WIDE GASKETING FOR CURB
FRAME AND ALL DUCT SUPPORT SURFACES
2“
UNIT BASE
3.75”
WOOD NAILER
3.56”
UNIT BASE RAILS
14”
8“ MIN. ABOVE FINISHED ROOF
CURB FRAME
COUNTERFLASHING
CAN’T STRIP
INSULATION AND ROOFING MATERIAL
INSULATION
ROOF DECK AND SUPPORT STRUCTURE
Johnson Controls Unitary Products
71
5123249-TTG-A-0515
Economizer Options
Economizer Usage
Application
Cabinet Height
Description
Model
Side Return
All
Horizontal economizer without barometric relief
2EE047069241
Downflow, End Return
Horizontal or ERV
42"
Economizer, 42” tall cabinet
2EE047074242
1. Barometric relief must be ordered separately and installed in duct work.
2. Includes fresh air hood, exhaust hood and barometric relief.
Economizer Downflow W/Power Exhaust
Fresh Air Hood
Low Leak Economizer
Power Exhaust
Barometric
Relief Damper
72
Barometric Relief
Hood
Johnson Controls Unitary Products
Economizer End Return W/Power Exhaust
Fresh Air Hood
Field Installed
Duct Work
Low Leak
Economizer
Power Exhaust
Barometric Relief Damper
Barometric Relief Hood
Field Installed Horizontal Economizer W/Power Exhaust
Return Air Damper
Field Installed
Duct Work
Fresh Air Damper
Power Exhaust
Barometric
Relief Damper
Barometric
Relief Hood
Subject to change without notice. Printed in U.S.A.
Copyright © 2015 by Johnson Controls, Inc. All rights reserved.
York International Corporation
5005 York Drive
Norman, OK 73069
Fresh Air Hood
5123249-TTG-A-0515
Supersedes: Nothing