192 Maximum Switching Capacity Relay Contact Rating Electrical Ratings: Cat. No. 700-HK36___ ➋ Rated Thermal Current (Ith) 1-pole, 1 CO, SPDT - 16 A ➊ Rated Thermal Current (UI) 250V IEC, 300V UL/CSA ➊ Electrical Ratings of Contacts 120VAC Inductive VAC Inductive VDC Resistive Make, Break, and Continuous Minimum Permissible Contact Rating AC-15, 6.2 A B300 Pilot duty, 3 A 1/3 Hp (0.24 kW) 1-phase 240VAC AC-15, 3.1 A B300 Pilot duty, 1.5A 3/4 Hp (0.55 kW) 1-phase 230VAC 0.55 kW 1-phase 24VDC DC-13, 5.0 A 125VDC DC-13, 0.2 A R300 Pilot Duty, 0.22 A 250VDC DC-13, 0.1 A R300 Pilot duty, 0.11 A 23VAC AC-1, 16 A ➊ 277VAC 16A General use ➊ 30VDC DC-1, 12 A 10 A, Resistive 300 mW (5V/60 mA or 60V/5 mA) for silver contacts ➊ Maximum module current: -10 Amp per relay output -12 Amps per 2 adjacent relay outputs ➋ Replacement relays: -24V DC control (coil) voltage (Cat. No. 700-HK36Z24) -120V AC control (coil) voltage (Cat. No. 700-HK36A1) Cycles Bul. 700-HK36 SPDT Electrical Life (AC Loads) vs. Contact Life Publication 1492-TD008D-EN-P - January 2009 Resistive load - cos = 1 Inductive load - cos = 0.4