Install Guide - IGBT dimmer modules

Install Guide - IGBT dimmer modules
OPT20HP - Dual 120VAC / 2000VA
OPT15HP - Dual 120VAC / 1800VA
OPT41000HP - Quad 120VAC / 1000VA
OPT41000HP15 - Quad 120VAC / 1000VA
OPT20HP7 - Dual 277VAC / 2000 VA
OPT41000HP7 - Quad 277VAC / 1000VA
Optio
Install Guide - IGBT dimmer modules
Description
Installation
The Optio IGBT Dimmer Modules offer high performance dimming
of various load types, while operating at increased efficiency and
reducing lamp noise on incandescent lamp types. IGBT Dimming
Technology provides precise control over inrush current without the
use of chokes, and resists damage from short circuits.
Any combination of Optio dimming and relay modules may be
installed in the panel. Blank covers MUST be installed in any unused
spaces. Pull the jumper (shorting plugs) before installing.
To install modules:
1. Unpack module and recycle or properly discard packaging
materials. (Be sure to keep this instruction sheet for
future use.) Inspect dimming module for signs of damage
during transit.
All Optio Dimmer Modules have identical mounting dimensions,
allowing them to be easily swapped within any of the Optio Lighting
Control Panels. (Use caution to ensure that quad dimmer modules
are not installed into module spaces wired for dual dimmer modules.)
2. Disconnect main power to Optio Lighting Control Panel.
Warning
3. Open dimmer module side of panel front cover.
• Installing the module with power applied to the cabinet may expose you to
dangerous voltage and damage the device. Remove power before installing. A
qualified electrician should perform this installation.
4. If present, remove blank cover from location where module is
to be installed (Figure 1). When possible, lower modules should
be installed first.
5. Remove shorting plugs from the load terminal block. The
shorting plug is the red tab protruding from the green load
terminal block. To remove, grasp the shorting plug and
gently pull.
120V Modules for use in Optio Panel models
OPT3120, OPT6120, OPT9120
OPT20HP
OPT15HP
OPT41000HP
OPT41000HP15
Note
• The dimmer module will not operate properly if the shorting plug is left in circuit.
277V Modules for use in Optio Panel models
OPT3277, OPT6277, OPT9277
6. Gently insert module into lighting control panel, heatsink first.
Secure module using four screws (provided). Dimmer Module
should be installed with the heatsink facing away from you.
OPT20HP7
OPT41000HP7
7. Close panel front cover.
Figure 1: Installing modules and blank covers
Important Safety Information
Important Safeguards
When using electrical equipment, basic safety precautions should
always be followed including the following:
a. READ AND FOLLOW ALL SAFETY INSTRUCTIONS.
b. Do not use outdoors.
c. Do not mount near gas or electric heaters.
d. Equipment should be mounted in locations and at heights where it
will not readily be subjected to tampering by unauthorized
personnel.
e. The use of accessory equipment not recommended by the
manufacturer may cause an unsafe condition.
f. Do not use this equipment for other than intended use.
g. Refer service to qualified personnel.
SAVE THESE INSTRUCTIONS.
Note: The Optio 9-Module
Panel is used to illustrate in
Figure 1. However, the module
installation is identical for all
Optio Panel models.
Warning
• Before installation, disconnect power at circuit breakers or remove fuse to avoid
electrical shock or damage to the unit. It is recommended that an electrician
perform this installation.
2
Operation
Warranty
Focus button
Three Year Limited Warranty
Optio Dimmer Modules are equipped with a "Focus Button" on each
circuit (Figure 1). Tapping the focus button quickly will turn the circuit
on to full, tapping it quickly again will turn the circuit off. Pressing and
holding the focus button will ramp the dimmer up to full intensity. If
the focus button is released before reaching full intensity, the dimmer
will stop at that relative output.
This Philips Lighting device, when properly installed and under normal
conditions of use (without overload, abuse or alteration), is warranted
to you, the original user, for a period of three years from the date of
original retail purchase, to be free from defects in materials and
workmanship. If during the warranty period you believe the purchased
product or any part thereof has such a defect, you must return the
product (or part) at your cost during such period, with proof of
purchase (or if installed by a third-party a written explanation of
installation transaction with proof of date), to Philips Lighting, 10275
West Higgins Rd., Rosemont, IL 60018, for repair or replacement (or
to an authorized Philips Lighting supplier which agrees in advance to
handle the return and replacement by factory authorization). If the
product or part is found by Philips Lighting to have been defective in
material or workmanship it will be repaired or replaced (as deemed
necessary by Philips Lighting), and the replacement will be returned to
you free of charge. The original user is solely responsible for any costs
associated with removal and re-installation of the product and
shipping to Philips Lighting or its authorized supplier.
LED status indications
Red LED
Green LED
Condition
Off
Off
Normal
Off
Flashing
No Load
Off
On
Focus Mode
(controlled at dimmer)
Slow Flashing
Off
Overload
Fast Flashing
Off
Over Temperature
On
Off
Communication Error
Flashing
Flashing
Miswire to Line
PHILIPS LIGHTING LIMITS THE DURATION OF THE IMPLIED
WARRANTY OF MERCHANTABILITY WITH RESPECT TO THE
PRODUCT TO THE LIMITED WARRANTY PERIOD SET FORTH
ABOVE, AND OTHERWISE DISCLAIMS ALL IMPLIED
WARRANTIES WITH RESPECT TO THE PRODUCT AND ITS
PARTS. Some states disallow certain limitations on implied warranties
so you should consult your state law if you have a question regarding
this limitation and disclaimer.
Specifications
Operating Voltage: 120VAC, 50/60Hz
Number of Circuits:
OPT20HP / OPT15HP: 2
OPT41000HP / OPT41000HP15: 4
Min Rated Load (Per circuit): 0.5W
Max Rated Load (Per circuit):
OPT20HP: 2000VA
OPT15HP: 1800VA
OPT41000HP / OPT41000HP15: 1000VA
Philips Lighting disclaims any and all liability for incidental,
consequential, special or indirect damage arising out of any claimed
breach of warranty or otherwise. However, some states do not allow
exclusion or limitation of such damages, so this disclaimer may not
apply to you.
The remedy provided in this Limited Warranty for defective products
is the user’s sole and exclusive remedy, subject to your state law.
Further, this Warranty gives the user specific legal rights, and the user
may also have other rights which may vary from state to state.
Operating Voltage: 277VAC, 50/60Hz
Number of Circuits:
OPT20HP7: 2
OPT41000HP7: 4
Min Rated Load (Per circuit): 0.5W
Max Rated Load (Per circuit):
OPT20HP7: 2000VA
OPT41000HP7: 1000VA
Contact Information
Philips Lighting
Customer Support +1-800-526-2731
www.philips.com/lightingcontrolsna
Supported Load Types: Incandescent, Inductive, Magnetic Low
Voltage, Electronic Low Voltage
Transition Time (Rise or Fall): 800uS independent of load size
Cooling: Natural convection
Ambient Operating Temp: 0 to 40 degrees C
Relative Humidity: 5 to 95% non-condensing
Made in U.S.A.
3
Field Service / Commissioning Request
From:
Company:
Phone:
Fax:
Please fill out, sign and date, and fax back to 972-389-6175
Allow Minimum two weeks advance notice.
Job Name:
Sales Order Number:
Site Address:
City: State: Zip Code:
Electrical Contractor:
Phone:
IMPORTANT: At NO time shall the system be energized prior to Philips Lighting authorized personnel checkout. Philips Lighting will not be liable for
any damage that may occur and the system warranty may be voided. System commissioning will be contingent on Philips Lighting Credit Department
approval. Please see Philips Lighting Terms and Conditions for further details.
Requested Checkout Date:
Please check the boxes below to confirm that:
 Arrangements have been made for access to ALL equipment.
 ALL control stations and receptacle stations have been installed.
 ALL system inter-wiring is complete between dimmer cabinets and control stations, and has been checked for accuracy and continuity.
 ALL load lamps have been installed and ALL load circuits have been checked with the associated power feed for correct wiring.
 The system has been cleaned for customer acceptance and ALL dimmers have been installed in the appropriate dimmer rack(s).
 ALL necessary owners, representatives, and staff will be present for demonstrating and training at time of commissioning. Please see
specifications for requirements.
I hereby certify that the above conditions have been met and that the installation is complete. I understand that a PURCHASE ORDER will be required
for additional visits resulting from an INCOMPLETE INSTALLATION.
Print name:
Signature:
Position:
Date:
Phone Number:
Fax Number:
Email:
©2012 Philips Lighting Electronics N.A.
A Division of Philips Electronics North America Corporation.
All rights reserved.
Published and printed in USA
October 2012
Form number: IG.OPTIOIGBT.2.10032012
Philips Lighting Controls, Systems & Services N.A.
10275 West Higgins Road
Rosemont, IL 60018
Customer Support: +1-855-512-8791
www.philips.com/lightingcontrolsna
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertisement