SmartPro 120V 2.2kVA 1.92kW Line-Interactive Sine
Wave UPS, 2U Rack/Tower, Extended Run,
Pre-installed SNMPWEBCARD, LCD Display, USB,
DB9 Serial
MODEL NUMBER: SMART2200RMXLN
Highlights
2.2kVA / 2200VA / 1920W line interactive 2U rack / tower UPS;
0.9 power factor
120V nominal output during brownouts to 83V and overvoltages to 145V
Interactive LCD provides UPS status information and advanced configuration options
USB, RS232, EPO and
Pre-installed SNMPWEBCARD interface
Expandable runtime, Hot-swap batteries, 96% efficiency, Sine wave output
2 independently switchable output load banks
NEMA 5-20P input; 4 NEMA
5-15/20R & 4 5-15R outlets
Description
Tripp Lite SmartPro Line Interactive UPS with enhanced LCD interface offers network-grade power protection for
Applications
Distributed Server Rooms critical server, network and telecommunications equipment. Line Interactive Uninterruptible Power Supply (UPS) with built-in Auto-Voltage Regulation (AVR) actively corrects brownouts and overvoltages back to usable levels while maintaining a full battery charge in case of power failure. Tripp Lite's unique configuration excels in exceptionally poor-power environments with two separate levels of voltage boost to correct both slight
Network Closets
Small Business Networks
Voice over IP (VoIP) Phone
Systems undervoltages and severe brownout conditions. Interactive LCD interface reports UPS operating mode, detailed
UPS and site-power data, plus enables a variety of UPS setup and configuration options. Super-fast switchover from line to battery power occurs within milliseconds to maintain operation of connected equipment without interruption or reboot. 96% line-mode efficiency offers reduced heat emissions and operating costs. Network
Package Includes
SMART2200RMXLN UPS management interfaces support communications via USB, RS-232 and pre-installed SNMPWEBCARD network interface. HID-compliant USB interface enables integration with built-in power management and auto shutdown features of Windows and Mac OS X. Network communications ports enable detailed monitoring of equipment load levels, self-test data and utility power conditions. Includes PowerAlert monitoring software and complete system with Pre-installed
SNMPWEBCARD
PowerAlert software with USB,
Serial & EPO cabling
4 post installation kit
Owner's manual cabling. Switched output load banks enable scheduled and real-time remote reboot and load shedding of select outlets. Emergency Power Off (EPO) interface. LCD display panel easily rotates for viewing in rackmount or tower configurations. Audible alarm with push-button momentary alarm-cancel and silent-mode configuration options. Programmable self-test.
Field-replaceable, hot-swappable battery modules.
Features
Tripp Lite SMART2200RMXLN line interactive 2U rack/tower UPS with 2200VA / 2.2kVA / 1920W capacity and extended runtime options
Line interactive UPS with Automatic Voltage Regulation (AVR) corrects brownouts and overvoltages from 83 to 145V
NEMA 5-20P input plug; 4 NEMA 5-15/20R and 4 5-15R output receptacles, Two independently switched output load banks
Maintains uninterrupted operation of connected networking equipment during blackouts, surges, brownouts and overvoltages
1 / 5
High 96% efficiency rating in line-power mode offers reduced power consumption and BTU emisssions
Internal batteries offer 12 minutes at 50% load (960W) and 4.5 minutes at 100% load (1920W)
Extended runtime is available with optional BP48V24-2U (limit 1), BP48V60RT-3U (multi-pack compatible) and BP48V27-2US (multi-pack compatible);
Output is reduced to 1600 watts maximum with external battery packs
External battery configurations require the use of Tripp Lite's External Battery Configuration Software (see manual)
Hot-swappable, user-replaceable internal batteries and external battery packs can be replaced with no disruption to connected equipment
Front panel LCD monitoring screen with MODE and ENTER buttons reports operating mode with 5-bar battery charge graphic, plus 7 selectable screens of detailed UPS and site power information
LCD interface also supports a number of advanced user setup and operating preferences
Ships with 4 post rackmount installation hardware; Optional 2POSTRMKITWM enables 2 post rackmount/wallmount installation; Optional 2-9USTAND enables tower placement
Built-in USB, RS-232 and pre-installed SNMPWEBCARD accessory
HID-compliant USB interface enables integration with built-in power management and auto shutdown features of Windows and Mac OS X
Included PowerAlert UPS monitoring software; Built-in Emergency Power Off (EPO) interface with cable
Specifications
OUTPUT
Output Capacity Details
Output Volt Amp Capacity (VA)
Output kVA Capacity (kVA)
Output Watt Capacity (Watts)
Output kW Capacity (kW)
Nominal Output Voltage(s)
Supported
Frequency Compatibility
Output Voltage Regulation (Line
Mode)
Output derates to 1600 watts in all external battery pack configurations
2200
2.2
1920
1.92
120V
60 Hz
-14%, +6%
Output Voltage Regulation (Battery
Mode)
Output Receptacles
Load Management Receptacles
+/- 5%
(4) 5-15R; (4) 5-15/20R
Two switched single outlet load banks (1 5-15/20R & 1 5-15R)
Output AC Waveform (AC Mode) Pure Sine wave
Output AC Waveform (Battery Mode) Pure Sine wave
INPUT
Rated input current (Maximum Load) 16.0A
Nominal Input Voltage(s) Supported 120V AC
UPS Input Connection Type 5-20P
UPS Input Cord Length (ft.) 10
2 / 5
UPS Input Cord Length (m)
Recommended Electrical Service
Input Phase
VOLTAGE REGULATION
Voltage Regulation Description
Overvoltage Correction
Undervoltage Correction
Severe Undervoltage Correction
3
20A 120V
Single-Phase
BATTERY
Full Load Runtime (min.)
Half Load Runtime (min.)
Expandable Battery Runtime
External Battery Pack Compatibility
DC System Voltage (VDC)
Battery Recharge Rate (Included
Batteries)
Internal UPS Replacement Battery
Cartridge
Battery Access
Battery Replacement Description
Expandable Runtime
4.5 min. (1920w)
12 min. (960w)
Extended runtime supported via optional external battery packs
BP48V24-2U (limit 1); BP48V60RT-3U (multi-pack compatible); BP48V27-2US (multi-pack compatible)
48
Less than 4.5 hours from 10% to 90% (typical, full load discharge)
RBC94-2U
Front panel battery access door
Hot-swappable, user replaceable batteries
Yes
Automatic voltage regulation (AVR) maintains line power operation with an input voltage range of 83 to 145
Voltage reduction of 12% applies when input is between 127 and 145
Voltage boost of 12% applies when input voltage is between 96 and 108
Voltage boost of 24% applies when input voltage is between 83 and 95
USER INTERFACE, ALERTS & CONTROLS
Front Panel LCD Display
Front panel LCD information and configuration screen offers detailed UPS and site power status and operating data, plus configuration of voltage, operating mode, alarm function and a variety of additional options (see manual for detailed LCD configuration and monitoring options)
Switches
Alarm Cancel Operation
Audible Alarm
Front Panel LCD
3 pushbutton switches control OFF / ON power status, MODE selection and MUTE / ENTER control functions
Power-fail alarm can be temporarily silenced using alarm-cancel switch; silent mode alarm configuration option available
Audible alarm indicates UPS startup, power-failure, low-battery, overload, UPS fault and remote shutdown conditions
Yes
SURGE / NOISE SUPPRESSION
UPS AC Suppression Joule Rating
UPS AC Suppression Response
Time
EMI / RFI AC Noise Suppression
570
Instantaneous
Yes
3 / 5
PHYSICAL
Included Mounting Accessory
Description
Installation Form Factors Supported with Optional Accessories
Primary Form Factor
4 post rackmount installation accessories included
2 post rackmount (2POSTRMKITWM); Wallmount (2POSTRMKITWM); Tower (2-9USTAND)
Rackmount
UPS Power Module Dimensions
(hwd, in.)
UPS Power Module Dimensions
(hwd, cm)
3.43 x 17.32 x 19.46
8.7 x 44 x 49.4
Rack Height (U Spaces)
UPS Power Module Weight (lbs.)
2
57.6
UPS Power Module Weight (kg) 26.2
UPS Shipping Dimensions (hwd / in.) 7.9 x 21.7 x 24.2
UPS Shipping Dimensions (hwd / cm)
20.1 x 55.1 x 61.5
Shipping Weight (lbs.)
Shipping Weight (kg)
Cooling Method
UPS Housing Material
68.8
31.2
Fan
Steel
ENVIRONMENTAL
Operating Temperature Range
Storage Temperature Range
Relative Humidity
AC Mode BTU / Hr. (Full Load)
AC Mode Efficiency Rating (100%
Load)
+32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius
+5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius
0 to 95%, non-condensing
306
96%
COMMUNICATIONS
Communications Interface
DB9 Serial; EPO (emergency power off); Pre-installed network card; Slot for SNMP/Web interface; USB (HID enabled)
Network Monitoring Port Description Pre-installed SNMPWEBCARD network interface; Supports detailed monitoring of UPS and site power conditions
PowerAlert Software Included
Communications Cable
WatchDog Compatibility
USB and DB9 cabling included
Supports Watchdog application, OS and hard-reboot restart options for remote applications
LINE / BATTERY TRANSFER
Transfer Time 5 milliseconds (line to battery mode); 1 millisecond (battery to line mode)
4 / 5
Low Voltage Transfer to Battery
Power (Setpoint)
High Voltage Transfer to Battery
Power (Setpoint)
83
145
SPECIAL FEATURES
Grounding Lug
Cold Start (Startup in Battery Mode
During a Power Failure)
High Availability UPS Features
Green Energy-Saving Features
Back panel grounding lug
Cold-start operation supported
Hot swappable batteries
Greater than 95% efficiency - GREEN UPS; Individually controllable load banks
CERTIFICATIONS
UPS Certifications Tested to UL1778 (USA); Tested to CSA (Canada); Tested to NOM (Mexico); Meets FCC Part 15 Category A (EMI)
WARRANTY
Product Warranty Period (Worldwide) 2-year warranty, 3 year with registration. Note: Registration is required for 3-year warranty.
Connected Equipment Insurance
(U.S., Canada & Puerto Rico)
$250,000 Ultimate Lifetime Insurance
© 2015 Tripp Lite. All rights reserved. All trademarks are the sole property of their respective owners. Tripp Lite has a policy of continuous improvement.
Specifications are subject to change without notice. Photos may differ slightly from final products.
5 / 5
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project