Instruction Manual for Microwave Motion Sensor
Tri-level Version, Model No.:HC404VRC-KD
Technical Specifications
Microwave Motion Sensor
OPERATING VOLTAGE: 120-277VAC 50/60Hz
HF SYSTEM: 5.8GHz CW radar
RATED LOAD: 120V~ / 1.5A / 200W
230V~ / 1.5A / 350W
277V~ / 1.5A / 400W
DETECTION ANGLE: 30 O
RJ12 (sensor antenna)
1-10V-
1-10V+
~ 150 O
POWER CONSUMPTION: <1W
DETECTION RANGE (DxH): Max. 12 x 6m (SAM5)
Max. 16 x 15m (SAM6)
TIME SETTING: 2s, 30s~30min.
DAYLIGHT SENSOR: 2~50Lux; disable
STAND-BY PERIOD: 0s, 10s ~ 30min, +∞
STAND-BY DIMMING LEVEL: 10% ~ 50%
MOUNTING: Indoors, ceiling&wall mounted
WORKING TEMP.: -20 O C ~ +60 O C
The sensor is an active motion detector; it emits a high-frequency electro-magnetic wave at 5.8GHz and receives its echo.The sensor detects the change in echo from movement in its detection zone.
A microprocessor then triggers the switch light ON command. Detection is possible through doors, panes of glass and thin walls.
Note: the high-frequency output of this sensor is <0.2mW; approximately just 0.2‰ of the transmission power of a mobile telephone.
SAM5
Infrared remote receiver
35.9
Cable side entry
SAM6
Daylight sensor
HC404VRC-KD
Infrared remote receiver
Slots for T8 tube
Daylight sensor
30.7
40.4
11.2
Slots for T5 tube
32.2
Cable back entry
Push
L’
N
L
N
ON/
OFF
Auto Mode
Reset
SC1 SC2
Scene mode
SC3 SC4
Detection range
+
100% 50% 10%
10%
Stand-by dimming level
20% 30%
Daylight Sensor
2Lux
Test
2s
30s
Hold-time
1min
5min
10min 30min 50Lux
0s
10min
10s
Stand-by period
1min
30min M/A
HRC-05
15
12
IMPORTANT
PLEASE READ THESE INSTRUCTIONS CAREFULLY PRIOR TO INSTALLATION AND RETAIN THIS LEAFLET IN A KNOWN
AND SAFE PLACE FOR FUTURE REFERENCE.
SECTION 1 INSTALLATION AND WIRING
1.1 Ensure that the electricity supply is switched off before installing or servicing this product.
1.2 Wiring diagram
SECTION 2 REMOTE CONTROL
1 ON/
OFF
Auto Mode Reset
2
3
5
4
6
7
8
11
SC1 SC2
Scene mode
SC3 SC4
Detection range
Power
100%
Power
80%
100% 50% 10%
10%
Stand-by dimming level
20% 30%
+
Dim
-
Daylight Sensor
2Lux
5min
30s
Hold-time
10min
1min
30min 50Lux
9
10
13
12
0s 10s
Stand-by period
1min
10min 30min M/A
14
15
HRC-05
Note: the buzzer beeps one time when RC
receives signal successfully
Permanent ON/OFF [ ]
1
2 3 4 button 1
1. Press button , to select permanent ON or permanent OFF mode.
2. Press button to resume automatic operation. (Please refer to explanation below)
Auto Mode [ ]
Press button to in initiate automatic mode. The sensor starts working and all settings remain as before the light was switched ON/OFF.
RESET [ ]
Press button , all settings go back to the value of DIP switch settings.
Test 2s function [ ]
8
3 button 8
1.Press button ,the sensor goes into testmode (hold time2s). N.B. the stand-by period and daylight sensor settings are disabled in test mode.
4 11 button 10
Press button , the latest surrounding lux value overwrites previous lux value learned, and is set as the daylight threshold. This feature enables the fixture to function well in any environment.
button 5
Press button , the output shifts between 80% and 100%, for energy saving purposes.
Dim +/- [ ]
Press button to adjust the light brightness between 10%~100% during hold-time.“+” increases the light level, “-” will decrease the light level.
Lux disable [ ]
Press button , the built-in daylight sensor is disabled, the light will always operate upon detection regardless of ambient light level.
Note: The buzzer beeps twice if it is in manual override mode, and beeps once if shifts to semi-auto mode.
Detection range [ ]
Press buttons in zone to set detection range at 100% / 50% / 10%.
zone 11
Press buttons in zone to set hold time at 30s / 1min / 5min / 10min / 30min.
zone 12
Press buttons in zone to set the stand-by period at 0s / 10s / 1min / 10min / 30min / +∞.
Note: “0s” means on/off control; “+∞” means bi-leve of dimming control, the light will never switch off.
(i.e. the light remains at the stand-by dimming level until motion is detected.) zone 7
Press buttons in zone to set the stand-by dimming level at 10% / 20% / 30% .
zone 13
Press buttons in zone to set daylight sensor at 2lux / 10lux / 50lux.
There are 4 scene modes built into the remote control for different applications:
Scene options Detection range Hold time Stand-by period Stand-by dimming leve
SC1 100% 1min 10min 10%
SC2 100% 5min 10min 10%
SC3 100% 10min 30min 10%
SC4 100% 10min + 10%
Daylight sensor
2Lux
2Lux
10Lux
50Lux
Note: the end-user can fine tune the settings by pressing buttons of detection range / hold time / stand-by period / stand-by dimming level
/daylight sensor , the last setting will over-write that feature of the pre-set scene.
6 11 12 7
Section 3 Functions
3.1 Zero-cross Relay Operation
Designed in the software, the sensor switches on/off the load right at the zero-cross point, to ensure the in-rush current is minimised, enabling the maximum life-time of the relay.
3.2 Daylight Monitoring Function
Hytronik specially designed this function in software for deep energy-saving purpose. A built-in daylight sensor is designed to provide “smart photocell” function. This function can only be activated when stand-by period is set to “+∞”. In this mode the lamp will automatically illuminate at the dim level setting when the natural light goes below the threshold setting. The fixture will also switch off as the natural light returns.
3.3 Manual Override
This sensor maybe over-ridden by the end-users to switch on/off the lights manually, or adjust the maximum brightness during motion hold-time with the push-switch. This makes the product more user-friendly and offers more options to fit for extra-ordinary demands.
* Short push (<1s): on/off function;
ON → OFF: the light turns off immediately and cannot be lighten for a certain time (equals to hold time preset) even there is movement is detected. After
this period, the sensor goes back to auto sensor mode.
OFF → ON: the light turns on 100% and goes to auto sensor mode, even when ambient Lux level exceeds the daylight threshold.
* Long push (>1s): adjust the maximum brightness (between 10% and 100%) during hold-time. Both the settings on DIP switch and manual override can
overwrite each other, the latest action controls.
*Rapidly turn off/on the power supply three times within 3 seconds, the sensor goes to manual override or semi-auto function.
The buzzer beeps twice if it is in manual override mode, and beeps once if shifts to semi-auto mode.
* If no end-user adjustment is desired, simply leave this terminal disconnected.
The light will not come on
The lamp is always on
The lamp is on without any identifiable movement
The lamp will not work despite movement
SECTION 4 TROUBLE SHOOTING
MALFUNCTION CAUSE REMEDY
The sensor is not mounted for reliably detecting movement
CAUSE
Incorrect light-control setting selected
Faulty lamp
No power supply
Continuous movement in the detection zone
Movement occurred, but not identified by the sensor (Movement behind wall, movement of small object in immediate lamp vicinity etc.)
REMEDY
Adjust daylight threshold setting
Replace lamp
Check power to sensor
Check detection area setting
Securely mount enclosure
1. Reduce sensitivity.
2. Check the movement behind
walls to avoid facilities such as
water pipe, fan, which may
mis-trigger the sensor.
Rapid movements are being suppressed to minimize malfunctioning or the detection radius is too small.
Check detection area setting