FLOW METER

SPP-N118

Firmware: v.6.01 or higher

Input type: 0/4-20 mA

Batching and totalizer function

Assisting the automation industry since 1986

2017.05.18

Read the user's manual carefully before starting to use the unit or software.

Producer reserves the right to implement changes without prior notice.

SPP-N118_INSSXEN_v.2.09.002

User manual - FLOW METER SPP-N118

CONTENTS

1. BASIC REQUIREMENTS AND USER SAFETY........................................................................................

3

2. GENERAL CHARACTERISTICS................................................................................................................

4

3. TECHNICAL DATA......................................................................................................................................

5

4. DEVICE INSTALLATION............................................................................................................................

7

4.1. UNPACKING.......................................................................................................................................

7

4.2. ASSEMBLY........................................................................................................................................

8

4.3. CONNECTION METHOD...................................................................................................................

8

4.4. MAINTENANCE................................................................................................................................

17

5. FRONT PANEL DESCRIPTION................................................................................................................

18

6. PRINCIPLE OF OPERATION...................................................................................................................

19

6.1. MEASUREMENT MODE..................................................................................................................

19

6.2. DETECTION OF THE PEAK VALUES............................................................................................

22

6.3. CONTROL OF THE RELAY OUTPUTS..........................................................................................

23

6.3.1. One threshold mode................................................................................................................

25

6.3.2. Two thresholds mode..............................................................................................................

26

6.3.3. Batcher mode and „PrE r1” mode...........................................................................................

27

6.3.4. Use of the batcher counter as a marker.................................................................................

28

7. DEVICE PROGRAMMING.........................................................................................................................

29

7.1. PROGRAMMING MENU..................................................................................................................

29

7.2. PARAMETERS EDITION.................................................................................................................

30

7.2.1. Numeric parameters (digit change mode)...............................................................................

30

7.2.2. Numeric parameters (slide change mode)..............................................................................

30

7.2.3. Switch parameters (“LIST” type).............................................................................................

31

7.3. MENU DESCRIPTION.....................................................................................................................

31

7.3.1. “rELAy1” menu........................................................................................................................

31

7.3.2. “FLouu” menu..........................................................................................................................

34

7.3.3. “bAtCH” menu.........................................................................................................................

38

7.3.4. “totAL” menu............................................................................................................................

40

7.3.5. “Pr inP” menu..........................................................................................................................

41

7.3.6. “Init d” parameter.....................................................................................................................

42

7.3.7. “FiLtEr” menu..........................................................................................................................

42

7.3.8. ”OutP” menu............................................................................................................................

42

7.3.9. ”briGHt” parameter..................................................................................................................

45

7.3.10. ”HOLd” menu.........................................................................................................................

45

7.3.11. ”SECU” menu........................................................................................................................

46

7.3.12. ”rS-485” menu.......................................................................................................................

46

7.3.13. ”Edit t” parameter..................................................................................................................

47

7.3.14. ”dEFS” parameter..................................................................................................................

48

7.3.15. ”SErv” menu..........................................................................................................................

48

7.4. UNITS CALCULATIONS EXAMPLES.............................................................................................

48

7.4.1. Units recalculating examples..................................................................................................

49

7.5. MENU STRUCTURE........................................................................................................................

50

8. OVER-CURRENT PROTECTION.............................................................................................................

52

9. DISPLAYED VALUES CALCULATION....................................................................................................

52

9.1. ADDITIONAL CALCULATIONS (USED CONVERSION CHARACTERISTIC)...............................

52

9.1.1. Linear characteristic................................................................................................................

52

9.1.2. Square characteristic..............................................................................................................

53

9.1.3. Square root characteristic.......................................................................................................

54

9.1.4. User defined characteristic.....................................................................................................

54

9.2. EXAMPLES OF CALCULATIONS...................................................................................................

55

10. THE MODBUS PROTOCOL HANDLING...............................................................................................

59

10.1. LIST OF REGISTERS....................................................................................................................

59

10.2. TRANSMISSION ERRORS DESCRIPTION..................................................................................

66

10.3. EXAMPLES OF QUERY/ANSWER FRAMES...............................................................................

66

11. DEFAULT AND USER'S SETTINGS LIST.............................................................................................

69

2

User manual - FLOW METER SPP-N118

Explanation of symbols used in the manual:

!

- This symbol denotes especially important guidelines concerning the installation and operation of the device. Not complying with the guidelines denoted by this symbol may cause an accident, damage or equipment destruction.

i

IF THE DEVICE IS NOT USED ACCORDING TO THE MANUAL THE USER IS

RESPONSIBLE FOR POSSIBLE DAMAGES.

- This symbol denotes especially important characteristics of the unit.

Read any information regarding this symbol carefully

!

- The manufacturer is not responsible for any damages caused by

inappropriate installation, not maintaining the proper environmental conditions and using the unit contrary to its assignment.

- Installation should be conducted by qualified personnel . During installation all available safety requirements should be considered. The fitter is responsible for executing the installation according to this manual, local safety and EMC regulations.

- If the device is equipped with PE connector, it should be connected to PE wire.

Otherwise PE wire should be connected to GND connector.

- The unit must be properly set-up, according to the application. Incorrect configuration can cause defective operation, which can lead to unit damage or an accident.

- If in the case of a unit malfunction there is a risk of a serious threat to the

safety of people or property additional, independent systems and solutions to prevent such a threat must be used.

- The unit uses dangerous voltage that can cause a lethal accident. The unit

must be switched off and disconnected from the power supply prior to starting installation of troubleshooting (in the case of malfunction).

- Neighbouring and connected equipment must meet the appropriate standards and regulations concerning safety and be equipped with adequate overvoltage and interference filters.

- Do not attempt to disassemble, repair or modify the unit yourself. The unit

has no user serviceable parts. Defective units must be disconnected and submitted for repairs at an authorized service centre.

3

4

!

!

User manual - FLOW METER SPP-N118

- Do not use the unit in areas threatened with excessive shocks, vibrations, dust, humidity, corrosive gasses and oils.

- Do not use the unit in areas where there is risk of explosions.

- Do not use the unit in areas with significant temperature variations, exposure to condensation or ice.

- Do not use the unit in areas exposed to direct sunlight.

- Make sure that the ambient temperature (e.g. inside the control box) does not exceed the recommended values. In such cases forced cooling of the unit must be considered (e.g. by using a ventilator).

The unit is designed for operation in an industrial environment and must not be used in a household environment or similar.

Main task of SPP-N118 is measurement of instantaneous flow (flow rate), and counting of

total flow (e.g. passage of fluid or gas ), The device can be used as regulator, to control industrial process. Measurement of instantaneous flow can be indicated in range: 0 to 9999

(plus decimal point) and can be expressed in any scalable user units of flow and three time measures (second, minute, hour). Total flow can be indicated in range from 0.000 to

4294967295 user units with maximum resolution of 0.00001 units.

SPP-N118 can cooperate with flow sensors with current output (0-20mA or 4-20mA).

Sensors can be powered from sensor supply output (stabilized, 24VDC +5%, -10% 100mA).

The device is equipped in 1 or 2 relay outputs or OC-type outputs, which can be driven

due to instantaneous flow, total flow or batcher counter value. Optionally SPP-N118 with one

relay output (or OC-type output) can be equipped with active current output, passive isolated current output or active voltage output. Build in RS 485 interface enables access to all internal registers, and supports MODBUS RTU communication protocol. The controller can be ordered in two power supply versions.

The device has 5 buttons being used for main presets programming. To get high protection level, the keyboard is mounted under transparent cover. To allow user to change presets without opening the cover, an IR sensor is mounted. Remote controller contains basic

functions to handle menu of the device (note, that remote controller is not a part of the SPP-

N118 set – it is an additional equipment).

Additional features:

• alarm preset; alarm signal is released when measurement exceeds measurement range

• direct access to relays thresholds settings, without password,

• batcher mode.

User manual - FLOW METER SPP-N118

Power supply voltage

(depending on version)

External fuse (required)

Power consumption

85...230...260V AC/DC; 50 ÷ 60 Hz (separated) or 19...24...50V DC and 16...24...35V AC (separated)

T - type, max. 2 A max. 5 VA @ 85 ÷ 260V AC/DC max. 5 VA @ 16V ÷ 35V AC max. 5 W @ 19V ÷ 50V DC

Current input

0÷20 mA, 4÷20 mA overload protected, maximum input current about 40 mA

Current measurement accuracy

Measurement input resistance:

± 0,1% @ 25°C; ± one digit (for 0÷20 mA range)

50

W

Accepted prolonged input overload: 20%

Programmable input

low level: high level: not separated

0V ÷ 1V

10V ÷ 30V (about. 12 mA @ 24V)

Sensor power supply output

24V +5%, -10% / max. 100 mA, stabilized

Relay output

OC-type output

0, 1 or 2 NO, 5A/250V AC (resistance)

3A/250V AC (reactance)

0, 1 or 2; 30mA / 30VDC / 100mW

Active current output

(optional, for one relay or one

OC-type output version only)

Load resistance max.

range max. 0 ÷ 24 mA

700

W

Passive isolated current output

(optional, for one relay or one

OC-type output version only)

Supply voltage

Load resistance max.

range max. 2.8 ÷ 24 mA

Us = 9.5 ÷ 36V

(Us – 9.5V) / 24mA [k

W]

5

6

Active voltage output

(optional, for one relay or one

OC-type output version only)

Load resistance min.

User manual - FLOW METER SPP-N118

range max. 0 ÷ 11V

2000

W

Instantaneous flow range

Temperature stability

Instantaneous flow precision

Instantaneous flow unit

Total flow range

Total flow precision

0 ÷ 9999, plus decimal point

50 ppm / °C

Selected from range: 0 ÷ 0.000

User unit per min. or sec. or hour

4 294 967 295. 999 999 units

Selected from range: 0 ÷ 0.000

Total flow unit

Batcher counter range

Batcher counter precision

Batcher counter unit

Any, with precision, settable by user

65535.999999 units

Selected from range: 0 ÷ 0.000

Any, with precision, settable by user

Number of batches counter range 0 ÷ 999999

Communication interface RS 485, 8N1 and 8N2, Modbus RTU, not separated

Baud rate

Display

Data memory

Protection level

Housing type

Housing material

Housing dimensions without glands : with glands:

Operating temperature

Storage temperature

1200 bit/s ÷ 115200 bit/s

LED, 6 digit, 13mm height, red non-volatile memory, EEPROM type

IP 67 wall mounted

ABS (lower part) + PC (upper part)

110 x 80 x 67 mm

110 x 105 x 67 mm

0°C to +50°C or -20°C to +50°C

-10°C to +70°C or -20°C to +70°C

Humidity

Altitude

5 to 90% no condensation up to 2000 meters above sea level

Screws tightening max. torque 0,5 Nm

Max. connection leads cross section 3 mm

2

(for connectors 1÷6) or

2 mm

2

(for connectors 7÷16)

User manual - FLOW METER SPP-N118

Safety requirements

EMC

!

according to: PN-EN 61010-1 installation category: II pollution degree: 2 voltage in relation to ground: 300V AC insulation resistance : >20M

W insulation strength between power supply and input/output terminal: 1min. @ 2300V insulation strength between relays terminal:

1min. @ 1350V according to: PN-EN 61326-1

This equipment is not intended for use in residential environments and may not provide adequate protection to radio reception in such environments.

The unit has been designed and manufactured in a way assuring a high level of user safety and resistance to interference occurring in a typical industrial environment. In order to take full advantage of these characteristics installation of the unit must be conducted correctly and according to the local regulations.

!

- Read the basic safety requirements on page 3 prior to starting the installation.

- Ensure that the power supply network voltage corresponds to the nominal voltage stated on the unit’s identification label.

- The load must correspond to the requirements listed in the technical data.

- All installation works must be conducted with a disconnected power supply.

- Protecting the power supply clamps against unauthorized persons must be taken into consideration.

4.1. UNPACKING

After removing the unit from the protective packaging, check for transportation damage. Any transportation damage must be immediately reported to the carrier. Also, write down the unit serial number on the housing and report the damage to the manufacturer.

Attached with the unit please find:

- user’s manual,

- warranty,

7

User manual - FLOW METER SPP-N118

4.2. ASSEMBLY

!

- Disconnect the power supply prior to starting assembly.

- Check the connections are wired correctly prior to switching the unit on.

!

To install device on the wall, a pinholes should be made. Figure 4.1 presents

dimensions of the device and distances between holes. The back side of the device has four mounting holes. This part of the case should be mounted to a wall by screws.

110 mm

90 mm

67 mm

ø4

.4

ø8

.4

8

Figure 4.1. Device and assembly dimensions

4.3. CONNECTION METHOD

Caution

!

- Installation should be conducted by qualified personnel . During installation all available safety requirements should be considered. The fitter is responsible for executing the installation according to this manual, local safety and EMC regulations.

- The unit is not equipped with an internal fuse or power supply circuit breaker.

Because of this an external time-delay cut-out fuse with minimal possible nominal current value must be used (recommended bipolar, max. 2A) and a power supply circuit-breaker located near the unit. In the case of using a monopolar fuse it must be mounted on the phase cable (L).

- The power supply network cable diameter must be selected in such a way that in the case of a short circuit of the cable from the side of the unit the cable shall be protected against destruction with an electrical installation fuse.

- Wiring must meet appropriate standards and local regulations and laws.

User manual - FLOW METER SPP-N118

!

- In order to secure against accidental short circuit the connection cables must be terminated with appropriate insulated cable tips.

- Tighten the clamping screws. The recommended tightening torque is 0.5 Nm.

Loose screws can cause fire or defective operation. Over tightening can lead to damaging the connections inside the units and breaking the thread.

- In the case of the unit being fitted with separable clamps they should be inserted into appropriate connectors in the unit, even if they are not used for any connections.

- Unused clamps (marked as n.c.) must not be used for connecting any connecting cables (e.g. as bridges), because this can cause damage to the equipment or electric shock.

- If the unit is equipped with housing, covers and sealing packing, protecting against water intrusion, pay special attention to their correct tightening or clamping.

In the case of any doubt consider using additional preventive measures (covers, roofing, seals, etc.). Carelessly executed assembly can increase the risk of electric shock.

- After the installation is completed do not touch the unit’s connections when it is switched on, because it carries the risk of electrical shock.

Due to possible significant interference in industrial installations appropriate measures assuring correct operation of the unit must be applied. To avoid the unit of improper indications keep recommendations listed below.

Avoid common (parallel) leading of signal cables and transmission cables together with power supply cables and cables controlling induction loads (e.g. contactors). Such cables should cross at a right angle.

Contactor coils and induction loads should be equipped with anti-interference protection systems, e.g. RC-type.

Use of screened signal cables is recommended. Signal cable screens should be connected to the earthing only at one of the ends of the screened cable.

In the case of magnetically induced interference the use of twisted couples of signal cables (so-called “spirals”) is recommended. The spiral (best if shielded) must be used with RS-485 serial transmission connections.

In the case of measurement or control signals are longer than 30m or go outside of the building then additional safety circuits are required.

In the case of interference from the power supply side the use of appropriate antiinterference filters is recommended. Bear in mind that the connection between the filter and the unit should be as short as possible and the metal housing of the filter must be connected to the earthing with largest possible surface. The cables connected to the filter output must not run in parallel with cables with interference (e.g. circuits controlling relays or contactors).

9

User manual - FLOW METER SPP-N118

Connections of power supply voltage and measurement signals are executed using the clamping connectors inside of the unit’s housing.

a) b)

6 mm

5 mm

Figure 4.2. Recommended dimensions of cable stripping

a) for big connectors (1 to 6), b) for small connectors (7 to 16)

10

!

Figure 4.3. Method of connecting cables to the clamping connectors

• All connections must be made while power supply is disconnected !

• Flow sensor connected to current input of flow meter should be installed accordingly to local regulations, and recommendations of the producer.

• Correct installation and application of flow sensor is essential for correct

operation of flow meter type SPP-N118.

User manual - FLOW METER SPP-N118

RS - 485

16 15 14

R1

(option)

R2

(option) programmable input

13 12 11 10 9 8 7

GND

+

0/4 - 20mA

+

Uo

-

24V

(+5%, -10%)

Imax = 100 mA

6 5 4 3 2 1

RS - 485

16 15 14

Figure 4.4. Terminals description (relay outputs)

OC1, OC2: U max = 30V DC,

I max = 30mA,

P max = 100mW

programmable input

13 12 11 10 9 8 7

GND

+

0/4 - 20mA

+

Uo

-

24V

(+5%, -10%)

Imax = 100 mA

OC1

(option)

- +

6 5

OC2

(option)

- +

4 3 2 1

Figure 4.5. Terminals description (OC-type outputs)

11

12

User manual - FLOW METER SPP-N118

RS - 485

16 15 14 programmable input

13 12 11 10 9 8 7

GND

+

0/4 - 20mA

+

Uo

-

24V

(+5%, -10%)

Imax = 100 mA

R1

(option)

ACTIVE current output

(option)

6 5

- +

4 3 2 1

Figure 4.6. Terminals description (relay and active current outputs)

RS - 485

16 15 14

R1

(option)

Passive, isolated current output

4÷20mA

(option) programmable input

13 12 11 10 9 8 7

GND

+

0/4 - 20mA

+

Uo

-

24V

(+5%, -10%)

Imax = 100 mA

6 5 4 3 2 1

Figure 4.7. Terminals description (relay and passive current outputs)

User manual - FLOW METER SPP-N118

RS - 485

16 15 14 programmable input

13 12 11 10 9 8 7

GND

+

0/4 - 20mA

+

Uo

-

24V

(+5%, -10%)

Imax = 100 mA

R1

(option)

ACTIVE voltage output

(option)

6 5

- +

4 3 2 1

Figure 4.8. Terminals description (relay and active voltage outputs)

RS - 485

16 15 14

OC1: U max = 30V DC,

I max = 30mA,

P max = 100mW

programmable input

13 12 11 10 9 8 7

GND

+

0/4 - 20mA

+

Uo

-

24V

(+5%, -10%)

Imax = 100 mA

OC1

(option)

ACTIVE current output

(option)

- +

6 5

- +

4 3 2 1

Figure 4.9. Terminals description (OC-type and active current outputs)

13

14

User manual - FLOW METER SPP-N118

RS - 485

16 15 14 programmable input

OC1: U max = 30V DC,

I max = 30mA,

P max = 100mW

OC1

(option)

Passive, isolated current output

4÷20mA

(option)

- +

13 12 11 10 9 8 7

6 5 4 3 2

GND

+

0/4 - 20mA

+

Uo

-

24V

(+5%, -10%)

Imax = 100 mA

1

Figure 4.10. Terminals description (OC-type and passive current outputs)

RS - 485

16 15 14 programmable input

OC1: U max = 30V DC,

I max = 30mA,

P max = 100mW

13 12 11 10 9 8 7

OC1

(option)

ACTIVE voltage output

(option)

- +

6 5

- +

4 3 2

GND

+

0/4 - 20mA

+

Uo

-

24V

(+5%, -10%)

Imax = 100 mA

1

Figure 4.11. Terminals description (OC-type and active voltage outputs)

User manual - FLOW METER SPP-N118

R1

R2

6 5 4 3

FUSE

N L

2 1

FUSE

!

Depending on version:

85...230...260V AC/DC; 50 ÷ 60 Hz or

19...24...50V DC and 16...24...35V AC

N L

Figure 4.12. Connection of power supply and relays

Contacts of relay outputs are not equipped with spark suppressors. While use the relay outputs for switching of inductive loads (coils, contactors, power relays, electromagnets, motors etc.) it is required to use additional suppression circuit (typically capacitor 47nF/ min. 250VAC in series with

100R/5W resistor), connected in parallel to relay terminals or (better) directly on the load. In consequence of using the suppression circuit, the level of generated electromagnetic disturbances is lower, and the life of relay contacts rises.

a) b)

L

L

6 5

6 5

!

!

N N

Figure 4.13. Examples of suppression circuit connection: a) to relay terminals; b) to the inductive load

15

16

Uo

8 7

+ -

Logic controller

- +

voltage input

24V

User manual - FLOW METER SPP-N118

OC1

6 5

- +

Uo

8 7

+ -

R

2k2

LED 10 mA

OC1

6 5

- +

Figure 4.14. Example of OC-type outputs connection

ACTIVE current output

- +

4 3

Logic controller

+

Current input

-

0-20 mA

Figure 4.15. Example of active current outputs connection

(for device with active current output only)

Uo

8 7

+ -

PASSIVE

Current output

4 3

Logic controller

+

Current input

4-20mA

-

!

Isolation loss

Figure 4.16. Example of passive current outputs connection

(for device with passive current output only)

User manual - FLOW METER SPP-N118

ACTIVE voltage output

- +

4 3

Logic controller

+

voltage input

0 - 10V

-

Figure 4.17. Example of active voltage outputs connection

(for device with active voltage output only)

4.4. MAINTENANCE

The unit does not have any internal replaceable or adjustable components available to the user. Pay attention to the ambient temperature in the room where the unit is operating.

Excessively high temperatures cause faster ageing of the internal components and shorten the fault-free time of unit operation.

In cases where the unit gets dirty do not clean with solvents. For cleaning use warm water with small amount of detergent or in the case of more significant contamination ethyl or isopropyl alcohol.

!

Using any other agents can cause permanent damage to the housing.

Product marked with this symbol should not be placed in municipal waste. Please check local regulations for disposal and electronic products.

17

User manual - FLOW METER SPP-N118

infrared receiver

Thresholds exceeding LED indicators (R)

R1 R2 Σ

total flow mode and batching mode

LED indicator (

S)

display

ESC

MENU

ENTER

PAUSE

Σ

RESET

programming pushbuttons

Symbols and functions of push-buttons:

ESC

MENU

ENTER

PAUSE

Symbol used in the manual: [ESC/MENU]

Functions:

• Enter to main menu ( press and hold by at least 2 sec.)

• Exit the current level and Enter to previous menu (or measure mode)

• Cancel the changes made in parameter being edited

Symbol used in the manual: [ENTER/PAUSE]

Functions :

• Start to edit the parameter

• Enter to the sub-menu,

• Confirmation of changes made in parameter being edited

• While batcher mode: pause/start batching.

Symbol used in the manual: [^] [v]

Functions :

• Change of the present menu,

• Modification of the parameter value,

• Switching of the display between relay thresholds and number of batches counter

Σ

RESET

Symbol used in the manual: [

S /RESET]

Functions :

• Switching of the display between total and instantaneous measurements or batcher counter (while batcher mode only)

• Zeroing the currently displayed counter (press and hold by at least 2 sec.), the zeroing must be confirmed by [ENTER] button.

18

User manual - FLOW METER SPP-N118

After turning the power supply on, device ID and software version are showed on the display, next the controller goes to the measurement mode.

6.1. MEASUREMENT MODE

In the measure mode, device displays instantaneous measurement (flow value or time per one unit of flow, depending on „F or P” parameter value) equivalent to input current, total flow or batcher counter value.

Displayed value presentation is defined by parameters “F unit”, “t unit” and “b unit” with resolution defined by parameters “F PrEc”, “t PrEc” and “b PrEc”.

... 879 876 543 . 219

“F unit” “F PrEc”

... 876 543 . 219

“F unit” “F PrEc”

Instantaneous flow (flow rate) is displayed in units defined by parameter “F unit” and

“Ftunit” (min., sec. or h), with resolution defined by

Point

(max. 3 digits after decimal point). Device converts measured current to selected units accordingly to conversion characteristic selected by user. The measurement range equal to the nominal range is called:

nominal measurement range, and the measurement range equal to the extended nominal

range is called: permissible measurement range (Figure 6.1, 6.2).

Lo r” parameter

Hi r” parameter nominal measurement range

4 mA

20 mA permissible measurement range

Figure 6.1. Definitions of measurement ranges in mode 4 ÷ 20 mA

If the result of measurement exceeds the permissible measurement range, warning ”-Hi-” or

”-Lo-” is displayed rather than input signal, depends on exceeded value (see description of

“Lo r” or “Hi r” parameters, paragraph ”FLouu” menu).

19

User manual - FLOW METER SPP-N118

Hi r” parameter

0 mA 20 mA permissible measurement range

Figure 6.2. Definitions of measurement ranges in mode 0 ÷ 20 mA

i

– If input current range is strongly overloaded, device can display improper results

– While time per one unit of flow is displayed (parameter “F or P” = “PEriod”):

• If flow value equals 0, then message “-STOP-” is displayed.

• If value of period is too high to be fitted on 6 digits, message “-OvLd-”

(Overload) is displayed instead of the result.

• If flow value is different than 0 but value of period is too small to be fitted on 6 digits, message “-UnLd-” (Underload) is displayed instead of the result.

Total flow is displayed in units defined by parameter “t unit” with resolution defined by parameter “t PrEc” (max 3 digits after decimal point). If total flow counter overflows, warning

“tot ov” is displayed alternatively with maximum counter value. Total flow counter can be

zeroed using “Clrtot” option of “totAL” submenu, using [

S ] button (press and hold by at

least 2 sec.), electrically via programmable input or via RS-485 interface by writing of value

0000h to any of total flow counter result registers.

i

Zeroing by [

S ] button can be activated using „m CLr” option of “totAL” submenu.

Zeroing via programmable input can be activated using „Func” option of “Pr inP” submenu.

Parameter “CutoFF”, allows to define input current value, below which total amount of flow is not counted (incremented).

i

If “CutoFF” is set to value different than zero and if input current is lower than this value, then instantaneous flow (flow rate) is displayed, but TOTAL

COUNTER IS NOT INCREMENTED.

“Cutoff” Threshold “CT” is defined by formulas below:

CT =

" CutoFF" × 20mA

100

for 0 ÷ 20 mA

input

CT =

" CutoFF" × 16mA

100

4 mA for 4 ÷ 20 mA input

20

nominal measurement range

User manual - FLOW METER SPP-N118

Batching counter value is displayed in units defined by parameter “b unit” with resolution defined by parameter “b PrEc” (max 3 digits after decimal point). If batcher counter overflows, warning “bAt ov” is displayed alternatively with maximum counter value. Batching counter can

be zeroed using “CLrbAt” option of “bAtCH” submenu, using [

S ] button (press and hold by

at least 2 sec.), electrically via programmable input or via RS-485 interface by writing of value

0000h to any of batcher counter result registers.

i

Zeroing by [

S ] button can be activated using „m CLr” option of “bAtCH” submenu.

Zeroing via programmable input can be activated using „Funct” option of “Pr inP” submenu.

Switching between current flow rate, total flow counter and batcher counter can be

done by pressing [

S ] button. Kind of displayed value is signalised by S LED. It lights,

while total flow is displayed. If batcher counter is displayed then

S LED is pulsing.

i

Batching counter can be displayed while batcher mode only (set „SourCE”=”bAt” in

„rELAy1” submenu).

Functions of [^] and [v] buttons depend on kind of presently displayed value:

• If instantaneous flow (flow rate) is displayed ( LED marked

S is off) or batcher counter value (

S LED is pulsing), user can check main threshold values and

number of batches counter

(which indicates how many times batcher was started). After pressing [^] or [v] buttons, name of the threshold (e.g. ”rELPr1”) and its value or ”bAtCnt” label and

number of batches counter

will be displayed on the display in alternating mode.

If [^] or [v] will be pressed in 5 sec again, the next threshold will be displayed, else the device comes back to the measurement mode. If a free access is enabled (see description of ”SECu” menu), user can change the value of particular threshold pressing button

[ENTER] (see: PARAMETERS EDITION). Using [

S ] button while

number of batches counter

is displayed and confirm „CLEAr?” message by [ENTER] button causes zeroing

number of batches counter

.

i

• If particular parameter has been changed and confirmed in quick view mode, its new value is displayed in alternating mode with parameter name by few seconds. Confirmed changes may be checked or user can switch viewed parameter pressing [^] or [v] button.

Number of batches counter is incremented after each start of batching process

(every first start after batcher counter zeroing).

• If batcher counter value is displayed (

S LED is pulsing) and counter value exceeds 6 digits, then decimal point of the most left digit is pulsing. To view most significant digits, it is required to decrease resolution or/and change unit..

• If total flow counter value is displayed ( LED marked

S is on), and its length exceeds 6 digits, buttons [^] and [v] enable switching between more and less significant digits.

Positions of currently displayed digits are signalized by flashing decimal points (see example below).

21

User manual - FLOW METER SPP-N118

Example of switchin g between less and more significant digits of total flow result .

Let, total counter result be equal 1236789876543.21:

– while less significant 6 digits are displayed, flashing most left decimal point signalizes that result is longer than 6 digits, to show more significant digits press [^],

– while medium digits are displayed both most left and most right decimal points are

flashing (Figure 6.3). Most right decimal point signalizes than result has less significant

digits – to see these digits press [v] button. Most left decimal point signalizes additional more significant digits. Press [^] button to see these digits.

– while most significant digits are displayed, most right decimal point is flashing, and signalising that result has less significant digits, to see these digits press [v].

[

S ]

to instantaneous flow display mode

[

S ]

to instantaneous flow display mode

[

S ]

to instantaneous flow display mode

Figure 6.3. Switching between digits (screens) of total flow result.

All accessible parameters (e.g. pulse input settings, decimal point position) can be changed by entering the menu (see: DEVICE PROGRAMMING). Use the local keyboard or the remote controller to do it. (Note: all parameters can be remote changed via RS-485 interface).

i

Counting of pulses and controlling or relays is realised regardless of operation mode

(after entering to menu mode counting and controlling is continued in “background”.

6.2. DETECTION OF THE PEAK VALUES

The SPP-N118 flow meter is equipped with peaks detection function. It can detect a

peaks of the input signal and display their values. Presets connected with this function are placed in ”HOLd” menu (see description of ”HOLd” menu). The detection of the peak can be done if the measured signal raises and drops of value at least equal to parameter ”PEA”.

Detected peaks are displayed during the time defined by parameter ”timE”. If a new peak will be detected while one is displayed, this new peak will be displayed and display time counter

will be cleared (Figure 6.4). If no peaks are detected while time ”timE” elapses, device starts

to show the current value of input signal again. If „HdiS”=”HOLD” then setting parameter

"timE"=0.0 causes holding peak value until [ESC] button is pressed. If „HdiS”=”rEAL” then value "timE"=0.0 means no holding. Displaying peak value is signalized by flashing most right decimal point.

The relays/LEDs and the analogue output can be controlled depend on the current value of input signal or the peak value (see ”HOLd” menu).

22

User manual - FLOW METER SPP-N118

measure

”timE”

”timE”

”PEA”

”PEA”

time real measurement result display value

Figure 6.4. Process of peaks detection

6.3. CONTROL OF THE RELAY OUTPUTS

The control of the object (measured signal) is done due to instantaneous flow value

(current flow rate), total flow counter value or batcher counter value , and is realized via relay outputs. Front panel LEDs named „R” indicates the state of particular relay output.

i

If device is not equipped with one or more relay outputs, menus refer to this relays are available, but apply to LED indicators only. In such case LEDs indicates exceeding of particular thresholds.

Modes of the control can be changed depend on the values of parameters “SourCE”,

“SEt P”, “SEt P2”, “HYSt ”, “modE”, “t on”, “t oFF”, “unit” and “ALArmS” (available in

rELAy1” ÷ ”rELAy2” menu). If relay is controlled due to total flow counter value

(“SourCE” = ”tot”), additional parameters are available in menu. Parameters “t PrEC” and

“t unit” defining the unit and resolution of displayed thresholds and hysteresis of selected relay. If relay is controlled due to batcher counter value (“SourCE” = ”bAt”), in addition

“b PrEC”, “b coEF” and “b unit” parameters are available in menu but parameters:

“SEt P2”, “HYSt ”, “modE”, “t on”, “t oFF”, “unit” are unavailable. Parameters “b PrEC” and “b unit” define the resolution and unit of displayed thresholds and hysteresis of selected relay. Depend on “modE” parameter, relays can be not used or controlled over one or two thresholds values.

If one threshold is used (Figure 6.5) the relay can be turned on (“modE” = ”on”) or off

(“modE” = ”oFF”) when the input signal value is contained in zone A. If two thresholds are

used (Figure 6.6) the relay will be turned on when value of input signal is contained in zone A

(“modE” = ”in”) or zone B (“modE” = ”out”) and turned off if the signal is contained in the second one.

23

24

state of relay/LED

User manual - FLOW METER SPP-N118

”SEt P” parameter zone B zone A

”HYSt” parameter measure

Figure 6.5. One threshold control of the relay/LED outputs

state of relay/LED

”SEt P” or ”SEt P2” parameter

i

zone B zone A zone B measure

”HYSt” parameter

Figure 6.6. Two threshold control of the relay/LED outputs

The relay outputs and LEDs (named R) can be controlled depend on both - the current value and the peak value (when peak detection is active, for flow rate only) of the input signal.

User manual - FLOW METER SPP-N118

6.3.1. One threshold mode

Figure 6.7 presents the principle of relay outputs operation for one threshold mode, and

an example values of other parameters.

a) displayed value zone A

A t

A

B t

B

B

OFF

B

ON t

C

measured signal

t

D

“SEt P” parameter

(expected signal value) zone B

C D D

OFF

“HYSt” parameter

(allowed signal deviation)

D

ON

b) closed open time relay state

(modE = on

t on = 0

t oFF = 0) c) d) e) open closed time relay state

(modE = oFF

t on = 0

t oFF = 0) open closed time relay state

(modE = on

t on > 0

t oFF > 0)

“t on”

parameter open time relay state

(modE = oFF

t on > 0

t oFF > 0) closed

“t oFF”

parameter time

“t oFF”

parameter

“t on”

parameter

Description:

A, B, C, D

B

ON

,B

OFF

,D

ON

,D

OFF t

A

, t

B

, t

C

, t

D

- points where measured signal exceeds border values (expected value ± allowed deviation)

- relays state changes moments: (for “t on” > 0, “t oFF” > 0)

- time periods while input signal is in zone A or zone B

Figure 6.7. Principle of LED/relay output operation for one threshold mode

Parameter “SEt P” sets a threshold of the relay, and parameter “HYSt” sets a

hysteresis of the relay (Figure 6.7 a). The relay can change its state only when input value

exceeds (over or under) border value and t

A

,t

B

,t

C

,t

D times (

Figure 6.7

) are bigger than the

time defined by parameters “t on”, “t oFF” and “unit”.

Border values means values equal

threshold+hysteresis and threshold-hysteresis respectively.

If “t on” and “t oFF” parameters are set to “0”, then the relay state will be changed

as soon as input value exceeds any of the border values (see points A and C, Figure 6.7 a,

b, c).

If values of “t on” or/and “t oFF” are positive, then relay state will be turned on if the input value exceeds the border values and stay bigger (or lower) during at least

“t on” (see points B

“t oFF” elapse since the input signal value exceeds any of the border values (see points

B

OFF

, D

OFF

ON

, D

ON

, Figure 6.7 a, d, e). Similarly, the relay will be turned off if time

, Figure 6.7 a, d, e).

25

User manual - FLOW METER SPP-N118

If t

A

,t

B

,t

C

or t

D

(when input signal stay in zone A or zone B) are lower than parameters

“t on” or “t oFF”, the relay will not change its state (see points A and C, Figure 6.7 a, d, e).

The state of relay output while the input value exceeds the border values (points A, B, C,

D) is described by parameter “modE”. The relay can be turned on (“modE” = ”on”), or

turned off (“modE” = ”oFF”) when input signal value is contained in zone A (Figure 6.7 a).

The parameter “ALArmS” allow user to set the relay output behaviour in critical situations (e.g. Input values exceeds permissible input range). User can select that the relays will be turned on, turned off,or not changed in critical situations.

All parameters connected with relay outputs are described in paragraph ”rELAy1” menu.

6.3.2. Two thresholds mode

displayed value zone B

t

A t

B

C

C

OFF t

C

C

ON

measure d signal

t

D t

E

“HYSt” parameter a) zone A

A

B

B

OFF

B

ON

D

E

E

OFF

E

ON

“SEt P” or “SEt P2” parameter

“HYSt” parameter zone B b) c) d) e) relay state

(modE = in

t on = 0

t oFF = 0) relay state

(modE = out

t on = 0

t oFF = 0) relay state

(modE = in

t on > 0

t oFF > 0) relay state

(modE = out

t on > 0

t oFF > 0) closed open

“t on” parameter

“t oFF” parameter open closed closed open open

“t oFF” parameter closed

“t on” parameter time time time time time

“t on” parameter “t oFF” parameter

Description:

A, B, C, D, E

B

ON

,B

OFF

,C

ON

,C

OFF

,E

ON

,E

- points where measured signal exceeds border values (expected value ± allowed deviation)

OFF

- relays state changes moments: (for “t on” > 0, “t oFF” > 0)

t

A

, t

B

, t

C

, t

D

, t

E

- time periods while input signal is in zone A or zone B

Figure 6.8. Principle of LED/relay output operation for two thresholds mode

26

User manual - FLOW METER SPP-N118

Figure 6.8 presents the principle of relay outputs operation for two thresholds mode, and

an example values of other parameters. In this mode parameter “SEt P2” is accessible in common with “SEt P2”, this parameter describes a second threshold of the relay output. The parameters “HYSt”, “modE”, “t on”, “t oFF”, “unit” and “ALArmS” are connected with both

“SEt P” and “SEt P2” thresholds. While the controlling process, the relay output changes its state depends of both “SEt P” and “SEt P2” thresholds in similar way as it was described in one threshold mode.

If two threshold mode is used, “modE” parameter defines state of the relay output when the input value occurs in a particular zone defined by border values of both thresholds. The relay can be turned on if the input value is contained in zone A (“modE” = ”in”) or zone B

(“modE” = ”out”) and turned off if it is contained in the second one (Figure 6.8).

i

The sequence of thresholds “SEt P” and “SEt P2” can be set in any order, due to the control of relay outputs is done depend on difference between thresholds values

(zone A ) and outside of threshold values (zone B).

6.3.3. Batcher mode and „PrE r1” mode

To switch the device into a batcher mode in submenu „rELay1” user should set

„SourCE”=„bAt”. There are following parameters related to R1 in this mode: “SourCE”,

“SEt P”, “b PrEC”, “b unit” and “ALArmS”. Parameters “SEt P”, “b PrEC”, “b unit” define quantity of batched medium, displaying precision and the unit respectively. Parameter

“ALArmS” allows to set behaviour of relay output in critical situations.

Pressing [ENTER] button while device is in batcher mode causes start of batching and set of relay R1. Successive pressings of [ENTER] button cause pause/restart of batching and switching R1 relay off/on. When batcher counter reaches value equal to “SEt P” then relay

R1 is switched off.

i

If batcher counter is overloaded then its maximal value is displayed alternatively with “bAt ov” message. Overload of this counter do not change state of relays.

To start another pouring cycle, batcher counter must be cleared and next new cycle initiated by pressing [ENTER] button. Batcher counter can be zeroed using “CLrbAt” option of

“bAtCH” submenu, using [

S ] button (press and hold by at least 2 sec.), electrically via

programmable input or via RS-485 interface by writing of value 0000h to any of batcher counter result registers. After zeroing of batcher counter, currently realized pouring is stopped and relays switched off.

i

Zeroing electrically via programmable input causes start of the next batching automatically. In other cases to start of the next batching it is required to use

[ENTER] button or write of value 0001h to any of batcher counter result registers using RS-485 interface. To stop batching it is required to use [ENTER] button or write of value 0002h to any of batcher counter result registers using RS-485 interface.

Due to delays while closing/opening the valves decreasing of “SEt P” parameter

(defining volume of batched medium) can be necessary. Fact that zeroing of the batcher

counter using [

S ] stops the batching process and switches off the relays can be used for

calculating desired value of “SEt P”. Note, that if relay which is controlled by batcher counter is used for driving the valve, then value counted after zeroing of the batcher counter tells how much of medium flows through valve during closing.

27

User manual - FLOW METER SPP-N118

Number of batches is counted by another counter (number of batches counter) and stored into the non-volatile memory. To display the value of this counter use [^] or [v] button.

After that message ”bAtCnt” and content of number of batches counter are displayed

alternatively. To clear this counter press [

S ] button while device displays it and confirm by

pressing [ETNER] button. Every initialisation of batcher (start of batching) causes incrementation of number of batches counter.

If parameter „SourCE” of relay (other than R1) is set to „PrE r1” then parameters

SEt P” and „SEt P2” of particular relay means control advance of this relay in relation to threshold of relay R1 („SEt P” parameter in „rELAy1” submenu). In other words, first threshold of relay R2 equals

SEt P

R1

SEt P

R2

and value of its second threshold equals

SEt P

R1

SEt P2

R2

. Thresholds of other relays (if available) are calculated in the same way.

Relays working in this mode can be used to control additional valve of the batcher.

i

If relay other than R1 should change its state at the end of batching (simultaneously at turning relay R1 off), it is required to set „modE”=”in” or ”out” and set zero value for one of its thresholds („SEt P” or „SEt P2”).

The clearing and starting of next batching can be run automatically, with defined delay between successive doses. To enable this feature it is necessary to set parameters: „A rES”

(autoreset function), „A dLy” and „Atunit” (desired delay and unit of time) of “bAtCH” menu.

6.3.4. Use of the batcher counter as a marker

This feature allows to use the batcher counter for cyclic control of relays (except R1) by volume of flowing medium (e.g. switching relay on after counter reaches 9 litres and switch it off after counter reaches -10 litres, in other words generate one pulse every 10 litres. For example to use R2 as marker it is required to set counter as follow:

1.

Set relay R1 to batcher mode („SourCE”=”bAt”).

2.

Set „SEt P” of relay R1 to desired cyclic volume (e.g. 10 litres). This value defines cycle duration expressed in units of flow (not a time) because cycle time depends on flow speed.

3.

Set relay R2 as batcher pre-trig (“SourCE”=“PrE R1”).

4.

Set “modE” of R2 according to desired mode of operation (in this example “modE”

= “on”, however it can be also set to other modes). Depending on this parametrer, relay will be no or off in desired phase of the cycle.

5.

Set

SEt P

(and

SEt P2

if “modE” = “in” or “modE” =“out”) of relay R2 according to desired phase within it should be on (and off). These values must be lower than threshold of R1. Note, that time of active state of R2 depends on flow speed. It is recommended to set

SEt P

of R2 to half of R1 threshold but it is not necessary (in this example set “1”, what causes that R2 will be activated when batcher counter reaches 9 litres ).

6.

Switch on autoreset of batcher counter

(„A rES”=„on”) and set „A dLy” to 0.

Note that R1 is switched off for a short period every time batcher counter is cleared, what can be used to any purpose.

28

User manual - FLOW METER SPP-N118

The device menu allow user to set all parameters connected to operation of measurement input, control modes, critical situations behaviour, communication via RS-485 and access settings. The meaning of the particular parameters is described in paragraph

MENU DESCRIPTION.

Some of the parameters can be accessed without menu entering (quick view mode).

If current flow is displayed (LED named

S is off) or batcher counter value (LED named S is pulsing) user can check main thresholds values and

number of batches

(which indicates how many times batcher was started). After pressing [^] or [v] button, name of the threshold (e.g.

”rELPr1”) and its value or ”bAtCnt” label and

number of batches

will be displayed on the display in alternating mode. If [^] or [v] will be pressed in 5 sec again, the next threshold will be displayed, else the device comes back to the measurement mode. If a free access is enabled (see description of ”SECU” menu), user can change the value of particular threshold pressing button [ENTER] (see: PARAMETERS EDITION).

i

If particular parameter has been changed and confirmed in quick view mode, its new value is displayed in alternating mode with parameter name by few seconds.

Confirmed changes may be checked or user can switch viewed parameter pressing

[^] or [v] button.

7.1. PROGRAMMING MENU

To enter main menu (being in the measurement mode) operator must to press and hold at least 2 sec. [ESC/MENU] button.

If the user password is defined (see parameter “SEtcod“, menu ”SECU”), operator have to enter correct one before proceeding to menu options . Entering of the passwords is similar to the edition of numeric parameters (see:

PARAMETERS EDITION

)

,

however presently editing digit is showed only on the display, other digits are replaced by “-” sign.

After entering of last digit of the password first menu position will be displayed (if the password is correct) or warning ”Error” in other case.

!

Pay attention when device parameters are being changed. If it is possible, turn off controlled installation (machine).

29

User manual - FLOW METER SPP-N118

Functions of the buttons while sub-menu and parameters choice:

Selection of sub-menu or parameter for editing. Name of selected item (submenu or parameter) is displayed.

or

ENTER

ENTER

PAUSE

Operation of [ENTER] button depend on present menu position:

• if the name of some sub-menu is displayed - enter this sub-menu; name of the first parameter (or next level sub-menu) is displayed,

• if the name of some parameter is displayed - enter the edition of this parameter; present value of the parameter is displayed,

ESC

MENU

[ESC/MENU] button allow user to exit present menu level and goes to upper level menu (or measurement mode).

i

After about 1 min. since last use of the buttons, device exits the menu mode and returns to the measurement mode (only if no parameters are in editing mode).

7.2. PARAMETERS EDITION

To start edition of any parameter user should select name of desired one using [^] [v] buttons and then press [ENTER].

7.2.1. Numeric parameters (digit change mode)

Numerical parameters are displayed as decimal numbers. The mode of its new value entering depends on chosen edit method ( see parameter „Edit”).

In mode “by digit” („Edit”=”dig”) pressing one of the keys [^] or [v] causes change of current position (flashing digit) or the sign (+/-). Short pressing of the [ENTER] button causes change of the position (digit).

Press [ENTER] at least 2 seconds to accept the changes, after that question ”SEt?” is displayed, and user must to confirm (or cancel) the changes. To conform changes (and story it in EEPROM) press [ENTER] button shortly after ”SEt?” is displayed. To cancel the changes press [ESC] button shortly after ”SEt?” is displayed. After that device returns to the menu.

7.2.2. Numeric parameters (slide change mode)

In “slide change” mode („Edit”=”Slid”), buttons [^] and [v] has different functions. To increase edited value press (or press and hold) [^] button only, the increasing became quickest as long as button [^] is pressed. To slow down the increasing, button [v] can be used. If [v] is pressed shortly (and button [^] is still pressed), increasing slow down for a moment only, if [v] is pressed and held while button [^] is still pressed the increasing slow down and will be kept on lower speed.

To decrease edited value press (or press and hold ) [v] button only. The decreasing became quickest as long as button [v] is pressed. To slow down the decreasing, button [^] can be used. If [^] is pressed shortly (and button [v] is still pressed), decreasing slow down for a moment only, if [^] is pressed and held while button [v] is still pressed the decreasing slow down and will be kept on lower speed.

Press [ENTER] at least 2 seconds to accept the changes, after that question ”SEt?” is displayed, and user must to confirm (or cancel) the changes. To conform changes (and story it in EEPROM) press [ENTER] button shortly after ”SEt?” is displayed. To cancel the changes press [ESC] button shortly after ”SEt?” is displayed. After that device returns to the menu.

30

User manual - FLOW METER SPP-N118

7.2.3. Switch parameters (“LIST” type)

Switch parameters can be described as a sets of values (a lists) out of which only one of the options available on the list can be selected for the given parameter. Options of switching parameter are selected using

[^], [v] keys.

Short pressing of [ENTER] causes in displaying of the acknowledge question (”SEt?”). If key [ENTER] is pressed again, the changes are accepted, stored in EEPROM end the edition process finished. Pressing the key [ESC] after ”SEt?” causes in cancelling of made changes and returning to menu.

Functions of buttons when editing numeric and switching parameters:

While editing numeric parameter:

• change of current (flashing) digit

• slide change of value (acceleration, deceleration, direction change)

While editing switch parameter - selection of switch parameter.

or

ENTER

ENTER

PAUSE

If numerical parameter is being edited, a short press of [ENTER] button change edited position. A long press of [ENTER] button (at lest 2 sec.) causes of display a ”SEt?” ask, which allow user to make sure if change of the parameter value is correct. If switch parameter is being edited, a short press of [ENTER] button causes of display a ”SEt?” ask. When [ENTER] button is pressed again (while ”SEt?” is displayed) the new value of the parameter is stored in EEPROM memory.

ESC

MENU

Pressing this button operator can cancel the changes done up to now (if they were not approved by [ENTER] button after the ”SEt?” ask) and come back to menu

7.3. MENU DESCRIPTION

“- - - -”

- password checking. If some password different from „0000” is set, then every enter to main menu follows the entering of password. If entered password is correct then first menu position will be displayed else warning ”Error”, and unit returns to measurement mode.

i

Due to problem with direct displaying of “m” letter, it is exchanged with special sign

“ “. Independently in user manual letter „m” is used to make it more readable

(example: “modE”).

7.3.1. “rELAy1” menu

This menu allows to configure the operation mode of relays and LEDs marked „R” (e.g. „R1”).

If there are few relay outputs available, then every output has its own configuration menu (e.g.

menu „rELAy2” for relay (LED) „R2”). Principle of the relays operation is described in paragraph CONTROL OF THE RELAY OUTPUTS.

i

• The relay outputs and LEDs (named R) can be controlled by due to current flow rate, stored peak value, total flow counter or batcher counter,

• If device is not equipped with one or more relay outputs, menus refer to this relays are available, but apply to LED indicators only. In such case LEDs indicates exceeding of particular thresholds.

31

User manual - FLOW METER SPP-N118

“SourCE”

“Flo”

“bAt”

“tot”

- parameter defining kind of result using to control state of this relay.

It can be set to one of three values:

- relay is controlled due to current flow rate value or stored peak of flow rate

(see “Hold” menu),

- relay is controlled due to batcher counter value,

- relay is controlled due to total counter result.

i

“bAt” option is available for relay R1 only. For the rest of relays „PrE r1” option is available. „PrE r1” option means controlling in relation to „SEt P” of relay R1 (see

CONTROL OF THE RELAY OUTPUTS).

“SEt P”

- first threshold of the relay (range 0 ÷ 999999). Threshold is the medium value of

relay hysteresis. While batcher mode („SourCE”=„bAt”) „SEt P” value means the quantity of pouring matter.

“SEt P2” - second threshold of the relay (range 0 ÷ 999999). This threshold is accessible when ”modE” parameter is set to „in” or „out” value. Threshold is the medium

value of relay hysteresis.

“HYSt” - hysteresis of relay (range 0 ÷ 99999). Full hysteresis of the relay is equal to 2x

“HYSt” parameter. The relay state can change when an input signal is out of

threshold-hysteresis to threshold+hysteresis zone.

i

Presented parameters should be set to ensure that ”SEt P” + ”HYSt”,

”SEt P2” + ”HYSt”, ”SEt P” - ”HYSt” or ”SEt P2” - ”HYSt” do not exceeds the measure range. Additionally, in two threshold mode (“modE”= „in” or „out”), the hysteresis for both thresholds must not cover each other (in other case relay can't change its state).

“b PrEc” - decimal point position (displaying precision of the relay thresholds ) when relay is controlled due to batcher counter result. It can be set to:

“ 0“

“ 0.0“

“ 0.00“

“0.000“

Decimal point position is changed by [^], [v] buttons.

“b unit” - the unit of relay thresholds when relay is controlled due to batcher counter result. It can be set to:

“unit”

“1000un”

- units

- thousands of units

32

User manual - FLOW METER SPP-N118

i

Parameters ”b PrEc” and ”b unit” are available only for relay R1 while batcher mode (“SourCE” = bAt”) is set. When current flow rate is used to control relays, the unit and precision of the thresholds and hysteresis are defined by parameters

“F unit”, “Ftunit” and “F PrEc” of menu ”Flouu”. When relay (other than R1) is controlled in relation to „SEt P” threshold of relay R1 (“SourCE” = PrE r1”), the unit and precision of the thresholds and hysteresis of relay (other than R1) are defined by parameters „b unit” and „b PrEC” parameters available in submenu of relay R1.

“t PrEc” - decimal point position (displaying precision of the relay thresholds ) when relay is controlled due to total flow counter result. It can be set to:

“ 0“

“ 0.0“

“ 0.00“

“0.000“

Decimal point position is changed by [^], [v] buttons.

“t unit”

- the unit of relay thresholds and hysteresis when relay is controlled due to total flow counter result. It can be set to:

“unit”

“1000un”

- units

- thousands of units

i

Parameters ”t PrEc” and ”t unit” are available only if total flow counter is used to control relay output (“SourCE” = tot”). When current flow rate is used to control relays, the unit and precision of the thresholds and hysteresis are defined by parameters “F unit”, “Ftunit” and “F PrEc” of menu ”Flouu”. When relay (other than R1) is controlled in relation to „SEt P” threshold of relay R1

(“SourCE” = PrE r1”), the unit and precision of the thresholds and hysteresis of relay (other than R1) are defined by parameters „b unit” and „b PrEC” parameters available in submenu of relay R1.

“modE” - relay operation mode:

“noACt” - the relay is not active (permanent turned off)

“on”

- one threshold mode, the relay is turned ON when input signal exceeds

SEt P + HYSt value, and is turned off back when the input signal became lower than SEt P - HYSt,

“oFF” - one threshold mode, the relay is turned OFF when input signal exceeds

SEt P + HYSt value, and is turned on back when the input signal became lower than SEt P - HYSt,

“in”

- two threshold mode, the relay is turned ON when the input signal is bigger than “lower threshold + HYSt and lower than “bigger

threshold - HYSt”, and turned off when the input signal is contained in the second zone. The bigger threshold means bigger one of “SEt P” and “SEt P2” thresholds, the lower threshold” means lower one of

“SEt P” and “SEt P2” thresholds.

33

User manual - FLOW METER SPP-N118

“Out” - two threshold mode, relay is turned OFF when the input value is bigger than “bigger threshold + HYSt and lower than “lower threshold

HYSt”, and turned on when the input signal is contained in the second zone. The bigger threshold means bigger one of “SEt P” and “SEt P2” thresholds, the lower threshold means lower one of “SEt P” and

“SEt P2” thresholds.

“modbuS” - the relay is controlled via RS-485 interface, independently on the input signal.

i

“t on”

LEDs light when relays are closed, independently of relays' mode.

• When power supply fail, unit do not store relays state selected by RS-485 interface.

- turn on delay time, the relay is turned on with delay equal “t on” if the input value exceeds appropriate border value (defined with threshold and hysteresis), at least “t on” time. “t on” range 0 ÷ 99.9, defined with 0.1 sec. resolution. Unit of this parameter is set by “unit” parameter.

“t oFF” - turn off delay time, the relay is turned off with delay equal “t oFF” if the input value exceeds appropriate border value (defined with threshold and hysteresis), at least “t oFF” time. “t oFF” range 0 ÷ 99.9, defined with 0.1 sec. resolution. Unit of this parameter is set by “unit” parameter.

i

If time when the input signal exceeds some border value is shorter than “t on” or

“t oFF” time, the relay do not change its state (see paragraph: CONTROL OF

THE RELAY OUTPUTS).

“unit”

- unit of time for “t on” i “t oFF” parameters. Can be set on one of two values:

“min”

“SEC”

- minutes,

- seconds.

“ALArmS”

“noCHAn”

“on”

- this parameter defines the relay reaction when some critical situations occurs:

“oFF”

- relay do not change its state,

- relay will be turned on,

- relay will be turned off.

If parameter “modE” is set to “on” , “oFF”, “in” or “Out” the “critical situation” means that permissible input frequency is exceeded.

If parameter “modE” is set to “modbuS”, the “critical situation” means communication delay (when no data is received) longer than “mbtimE” parameter

(see description: “rS-485” menu).

7.3.2. “FLouu” menu

This menu presets the measurement input and allows configuration of current flow rate displaying mode:

34

User manual - FLOW METER SPP-N118

“I tyPE“ - type of the input / sensor. This parameter can be set to values:

0-20”, 4-20

- current inputs of 0÷20mA or 4÷20mA of measurement range respectively. Displayed values are defined by parameters

“Lo CAL”,”Hi CAL” (or by user defined characteristic points) and parameter ”Point”.

“I CHAr“ - this option sets type of the conversion characteristic.

This preset is essential when meter cooperates with flow sensor, which changes it's output current accordingly to characteristic other than linear. It can be set to:

”LinEAr” - linear

“Square” - square

“Sqroot” - square root

When one of those characteristics is chosen display range is defined by “Lo CAL” and “Hi CAL”.

“USEr”

User defined characteristic. Maximal length 20 points. Every point is defined by user. Adding, Editing and Deleting of points is done by options

AddPnt”, „EdtPnt”, „dELPnt” („FLouu” menu) respectively.

i

If user defined characteristic is selected, and if number of defined points is lower than 2 then warning ”Errc” is displayed in measurement mode.

The process of displayed result calculation is described in details in DISPLAY VALUES

CALCULATION paragraph.

“Point“

- decimal point position (precision of flow rate displaying). It can be set to:

“ 0“

“ 0.0“

“ 0.00“

“0.000“

Decimal point position is changed by [^], [v] buttons.

i

Change of displaying precision can require appropriate correction of relays thresholds and hysteresis. These parameters are not updated automatically, due to settings of “Point” parameter.

“F unit” - the unit of volume used for flow rate displaying . It can be set to: (”unit.“ - units, or “1000un” - thousands of units). Units expressed by “F unit” are conventional, and can be exchanged to any other pair of units e.g. for powders it can be kilogram and tonne, for liquids it can be litre or cubic meter.

“Ftunit” - time unit used for flow rate displaying .It can be set to:

(”SEC“ - seconds, ”min” - minutes or “hour” - hours).

i

The unit used to displaying the flow rate, depends simultaneously on parameters:

“F coEF”, “F unit” and “Ftunit”, for example: unit/min or 1000un/h etc.

“F or P” - type of value displayed on the display:

“FL vAL” - flow value,

“PEriod” - time per one unit of flow,

35

User manual - FLOW METER SPP-N118

“Lo CAL”

“Hi CAL”

These parameters describe the values displayed for minimum and maximum input signal value for selected input type. If input type is set to 4-20 mA (0-20 mA) “Lo CAL” parameter defines the value displayed when input current is equal 4 mA (0mA), and “Hi CAL” parameter defines the value displayed for 20 mA of input current. Available range for these parameters: 0 ÷ 9999.

i

If user defined characteristic is selected (parameter “I CHAr” = ”USEr”) the parameters „Lo CAL” and „Hi CAL” are not available for modification, due to their values are calculated from defined characteristic.

“F coEF” - conversion coefficient. Changes analogue input unit to any unit used to calculate flow by multiplying current flow measurement value (after calculating user characteristics in “I CHAr” parameter) by value in “F coEF” parameter. Firstly, parameter editing requires to enter a value (by entering a digit in each blinking display separately), secondly to select decimal point position (blinking dot on selected position). There are following decimal point position options:

000000. - integer value, no decimal places,

00000.0 - one decimal place,

0000.00 - two decimal places,

000.000 - three decimal places,

00.0000 - four decimal places,

0.00000 - five decimal places,

000000 - six decimal places,

For example: 1 [ l ] = 0,264172 [US gallon], so F coEF = 264172 (no decimal places)

i

Decimal point position in “Piont” and “F coEF” parameters does not affect on each other.

“AddPnt” - this option allow user to add single point to the user defined characteristic.

After selection of this option device waits for „X” and „Y” coordinates of new point.

Modification of the coordinates is done accordingly to numerical parameters edition.

Coordinate „X” defines the percentage ratio of input current to selected current range. The „X” range: -99,9 ÷ 199,9. Coordinate „Y” defines displayed value for particular „X” value. The „Y” value can be changed in range: 0 ÷ 9999, decimal point position depend on „Point” parameter (”FLouu ” menu) .

i

• User can not enter two points with the same value of „ X ” coordinate. If user trays to do it, ”Err” warning is displayed. To modify any defined point use ”EdtPnt” option.

• To distinguish „X” and „Y” coordinates, if „X” coordinate is displayed an additional decimal point on utmost right position is displayed.

• If user defined characteristic is selected, and if number of defined points is lower than 2 then warning ”Errc” is displayed in measurement mode.

36

User manual - FLOW METER SPP-N118

“dELPnt” - this option allows user to delete any of the points of the user defined characteristic. After selection current number of points of the user defined characteristic is displayed for about approx. 1,5 sec. After that device waits for selection of point being deleted (by [^], [v] buttons). The short pressing of [ENTER] button causes by switching between X and Y value of the displayed point. The long press (press and hold at least 2 sec) of [ENTER] button causes by displaying

„dEL?” ask. If [ENTER] button is pressed again, current point is deleted and new updated number of points of the user defined characteristic is displayed.

“EdtPnt” - this option allows user to modify of particular point of the user defined characteristic. After selection current number of points of the user defined characteristic is displayed for about approx. 1,5 sec. After that device waits for selection of point being edited (by [^], [v] buttons). The short pressing of [ENTER] button causes by switching between X and Y value of the displayed point. The long press (press and hold at least 2 sec) of [ENTER] button causes by entering to edit the selected coordinate of the point. Modification of the coordinates is done accordingly to numerical parameters edition.

i

“AddPnt”, ”dELPnt” and “EdtPnt” options are available only if the user defined characteristic is used (it means when parameter “I CHAr” = ”USEr”).

“CutoFF” - this parameter, allows to define input current value, below which total amount of flow is not counted (incremented), but current flow rate is displayed. Parameter

“Cutoff” is expressed as percentage value of input current nominal range (0-20mA or 4-20mA), and can be set in range 0 ÷ 9.9 %,

i

If “CutoFF” is set to value different than zero and if input current is lower than this value, then instantaneous flow (flow rate) is displayed, but TOTAL

COUNTER IS NOT INCREMENTED.

Cutoff Threshold “CT” is defined by formulas below:

CT =

" CutoFF" × 20mA

100

for 0 ÷ 20 mA

output

CT =

" CutoFF" × 16mA

100

4 mA for 4 ÷ 20 mA output

“Lo r”, ”Hi r” - These parameters define the expansion of nominal range in percent. They

determine the permissible range of input currents (Figure7.1).

The permissible range allow user to exceed the nominal range of input current.

If input value is contained in the permissible range a proper result is displayed.

If input current exceeds this range (defined by “Lo r” and “Hi r”), “-Lo-” or “-

Hi-” warning is displayed depend on input current value.

37

User manual - FLOW METER SPP-N118

Lo r” = 75,0% (3 mA)

Hi r” = 5,0 % (1 mA)

I min nominal measurement range (4-20mA)

I max

[ mA ]

0 1

4

20 21 22 display message ”-Lo-

i

permissible measurement range measurement result is displayed regardless on nominal range exceeding display message ”-Hi-

Figure 7.1 Example of definition of permissible range of input currents -

Lo r” and “Hi r” parameters (“4-20” mode)

The “Lo r” parameter is important if input is set to “4-20” mode only, and determines lower border of the permissible range. If input is set to “0-20” mode, lower border of the permissible range is always 0mA.

If input is set to “4-20” mode, the lower border is calculated due to expression:

I min

= 4 mA - 4 mA × “Lo r” %.

The “Lo r” value can be set from 0 to 99.9%.

Parameter “Hi r” determines the upper border of the permissible range accordingly to the expression (for both “0-20”i “4-20”modes):

I max

= 20 mA + 20 mA × “Hi r” %.

The value of “Hi r” can be set from 0 to 19.9%

In example no 1 of the DISPLAY VALUES CALCULATION paragraph the procedure of the permissible input range determining is presented in details.

If the measurement value do not exceeds permissible measurement range but displayed value exceeds range (-99999 ÷ 999999), the warning

-Ov-

is displayed rather than the calculated result.

7.3.3. “bAtCH” menu

This menu allows to configure batcher counter displaying mode.

“b PrEc” - decimal point position (precision of batcher counter). It can be set to:

“ 0“

“ 0.0“

“ 0.00“

“0.000“

Decimal point position is changed by [^], [v] buttons.

38

User manual - FLOW METER SPP-N118

“b coEF” - conversion coefficient. Changes analogue input unit to any unit used to calculate batcher by multiplying current flow measurement value (after calculating user characteristics in “I CHAr” parameter) by value in “b coEF” parameter. Firstly, parameter editing requires to enter a value (by entering a digit in each blinking display separately), secondly to select decimal point position (blinking dot on selected position). There are following decimal point position options:

000000. - integer value, no decimal places,

00000.0 - one decimal place,

0000.00 - two decimal places,

000.000 - three decimal places,

00.0000 - four decimal places,

0.00000 - five decimal places,

000000 - six decimal places,

For example: 1 [ l ] = 0,264172 [US gallon], so b coEF = 264172 (no decimal places)

i

Decimal point position in “Piont” and “b coEF” parameters does not affect on each other.

“b unit” - the unit of volume used for batcher counter displaying . It can be set to: (”unit.“ units, or “1000un” - thousands of user units). Units expressed by “b unit” are conventional, and can be exchanged to any other pair of units e.g. for powders it can be kilogram and tonne, for liquids it can be litre or cubic meter.

“CLrbAt” - this option allows zeroing of batcher counter. After selection of this option ask

“CLEAr?” is displayed. If user press [ENTER] batcher counter is cleared, else action is cancelled.

Zeroing of batcher counter is possible via RS-485 interface too. It can be done as write of 0000h to any one of registers referred to batcher counter (0Dh ÷ 0Fh) using RS 485 interface.

i

To protect batcher counter of unauthorised zeroing, it is recommended to set password to menu access (see menu “SECU”).

“m CLr” - this parameter allows to activate manual zeroing of batcher counter using [

S ]

button:

”oFF”

”on”

- manual zeroing disabled,

- manual zeroing enabled.

“A rES” - this parameter allows to activate autoreset function (automatic batcher counter zeroing and start next batching):

”oFF”

”on”

- autoreset disabled,

- autoreset enabled.

“Atunit” - time unit of autoreset delay:

”SEC“ - seconds,

”min”

- minutes.

39

User manual - FLOW METER SPP-N118

“A dLy” - autoreset delay - it defines delay between last finished batching and execution of batcher autoreset function. Parameter “A dLy” is expressed with precision 0.1 of sec. or minutes depend on “Atunit” parameter.

i

Due to delays during valves closing, too small value of “A dLy ” can cause counting error while next batching cycle. It is recommended to set parameter “A dLy ” as much as valve closing time (or more), to preserve complete close of valves before start of next batching cycle.

7.3.4. “totAL” menu

This menu allows to configure total flow counter displaying mode.

“t PrEc” - decimal point position (precision of total flow counter). It can be set to:

“ 0“

“ 0.0“

“ 0.00“

“0.000“

Decimal point position is changed by [^], [v] buttons.

“t coEF” - conversion coefficient. Changes analogue input unit to any unit used to calculate total flow by multiplying current flow measurement value (after calculating user characteristics in “I CHAr” parameter) by value in “t coEF” parameter. Firstly, parameter editing requires to enter a value (by entering a digit in each blinking display separately), secondly to select decimal point position (blinking dot on selected position). There are following decimal point position options:

000000. - integer value, no decimal places,

00000.0 - one decimal place,

0000.00 - two decimal places,

000.000 - three decimal places,

00.0000 - four decimal places,

0.00000 - five decimal places,

000000 - six decimal places,

For example: 1 [ l ] = 0,264172 [US gallon], so t coEF = 264172 (no decimal places)

i

Decimal point position in “Piont” and “t coEF” parameters does not affect on each other.

“t unit”

- the unit of volume used for total flow counter displaying . It can be set to: (”unit“ units, or “1000un” - thousands of units). Units expressed by “t unit” are conventional, and can be exchanged to any other pair of units e.g. for powders it can be kilogram and tonne, for liquids it can be litre or cubic meter.

40

User manual - FLOW METER SPP-N118

“CLrtot” - this option allows zeroing of total flow counter. After selection of this option ask

“CLEAr?” is displayed. If user press [ENTER] total flow counter is cleared, else action is cancelled

Zeroing of total flow counter is possible via RS-485 interface too. It can be done as write of 0000h to any one of registers referred to total flow counter (09h ÷ 0Ch) using RS 485 interface.

i

To protect total flow counter of unauthorised zeroing, it is recommended to set password to menu access (see menu “SECU”).

“m CLr” - this parameter allows to activate manual zeroing of total flow counter using [

S ]

button:

”oFF”

”on”

- manual zeroing disabled,

- manual zeroing enabled.

7.3.5.

This menu allows to configure programmable input.

“Funct” - this parameter defines the function of the programmable input. When active state is delivered to programmable input, it causes of the activating of particular function.

This parameter can be set to one of the values:

“diSAbL”

“CLrtot”

“CLrbAt”

“inhibi”

- programmable input is disabled,

-

- zeroing of total flow counter zeroing of batcher counter

,

and automatic start of next batching cycle, if input is controlled by edge of the logical signal („mode” =

„LO-HI” or „HI-LO”). While input is controlled according to the logical signal level („mode” = „HI” or „LO”), active level causes zeroing of the counter (and stops batching) and inactive level starts/enables batching .

- programmable input stops the counting by total flow counter and

batcher counter while input is controlled according to the logical signal level („mode” = „HI” or „LO”) . If input is controlled by edge of the logical signal („mode” = „LO-HI” or „HI-LO”), successive active edges start/stop counting alternately.

“modE” - this parameter allows selection of active level/edge of programmable input. It can be set to one of following:

“HI”

“LO”

- executing function while high level on the input

- executing function while low level on the input

“LO-HI” - executing function while rising edge on the input

“HI-LO” - executing function while falling edge on the input

i

For settings “executing function while high/low level” the selected level must be longer than 5ms.

41

User manual - FLOW METER SPP-N118

7.3.6. “ Init d ” parameter

This parameter defines type of the value displayed after power on the meter. It is possible to set it to:

“Flo”

“bAt”

“tot”

“tot2”

“tot3”

- current flow rate (instantaneous flow),

- batcher counter,

- lowest part of total flow counter (less significant digits),

- medium part of total flow counter,

- highest part of total flow counter (most significant digits).

i

If value “tot2” or “tot3” is selected, meter automatically switches display to nonzero part of total counter result. Flashing (or not, if result is shorter than 6 digits) decimal points indicates which one part is actually displayed.

7.3.7. “FiLtEr” menu

This menu contains parameters referred to additional data (result) filtration.

“vALUE” - this parameter sets filtration rate. It can be set to values from 0

(no filtration ) to 5 (strongest filtration – time window about 3.5 sec.).

“droP” - this parameter defines minimum percentage change of measured value which turns off (temporally) data filtration. Value of this parameter can be changed in range:

0 ÷ 199,9%. Main purpose of this parameter is acceleration of displaying data changes, when sudden changes of instantaneous measurements value occur (while parameter “vALUE” is set to high values).

7.3.8. ”OutP” menu

This menu contains parameters of analogue output control. Menu is available if the device is equipped witch analogue output.

i

“OUtmod”

Analogue output can be controlled depend on both present measured value and peak value (if peak detection is enabled).

- analogue output mode. Depending on version of the device there are following options:

For active current output:

oFF

0-20

4-20

modbuS

- current output disabled ,

- current output enabled with 0 ÷ 20 mA mode ,

- current output enabled with 4 ÷ 20 mA mode,

- current output controlled via RS-485 interface.

For passive current output:

oFF

- current output disabled ,

4-20

modbuS

- current output enabled with 4 ÷ 20 mA mode,

- current output controlled via RS-485 interface.

For active voltage output:

oFF

- voltage output disabled ,

42

0-5

1-5

0-10

2-10

modbuS

User manual - FLOW METER SPP-N118

- voltage output enabled with 0 ÷ 5V mode ,

- voltage output enabled with 1 ÷ 5V mode ,

- voltage output enabled with 0 ÷ 10V mode ,

- voltage output enabled with 2 ÷ 10 V mode,

- voltage output controlled via RS-485 interface.

43

User manual - FLOW METER SPP-N118

“SourCE”

“Flo”

“bAt”

“tot”

- this parameter defines kind of analogue output controlling parameter, and can be set to one of three values:

- analogue output is controlled due to instantaneous flow (flow rate),

- analogue output is controlled due to batcher counter result,

- analogue output is controlled due to total flow counter result.

i

If parameter „SourCE”=„bAt” and batcher mode is disabled, then analogue output will be set to its alarm state defined by „AL” parameter in „OutPUt” menu.

”OUt LO” - this parameter determines the input value for which the output signal is minimal

(depend of output mode „OUtmod”).

“OUt HI” - this parameter determines the input value for which the output signal is maximal

(depend of output mode „OUtmod”).

The analogue output value is calculated due to formula given below:

Out=

W " OUt LO"

"OUt HI" "OUt LO"

× 

BAA

i

where:

W – displayed value,

Out – analogue output value,

B

– higher range limit (20mA / 5V / 10V),

A – lower range limit (0mA / 4mA / 0V / 1V / 2v),

Out LO” parameter can be greater than “Out HI”. In this case the conversion characteristic is reversed, it means that if input value raises the output value falls.

“b Prec” - decimal point position (displaying precision of parameters ”OUt LO” and

”OUt HI”) when analogue output is controlled due to batcher counter result. It can be set to:

“ 0“

“ 0.0“

“ 0.00“

“0.000“

Decimal point position is changed by [^], [v] buttons.

“b unit” - the unit of parameters ”OUt LO” and ”OUt HI”, while analogue output is controlled due to batcher counter result. It can be set to one of two values :

“unit”

“1000un”

- units

- thousands of units

i

Parameters ”b PrEc” and ”b unit” are available only if batcher counter is used to control current output (“SourCE” = tot”). When current flow rate is used to control it, the unit and precision of ”OUt LO” and ”OUt HI” parameters are defined by parameters “F unit”, “Ftunit” and “Point” of menu ”Flouu”.

44

User manual - FLOW METER SPP-N118

“t PrEc” - decimal point position (displaying precision of parameters ”OUt LO” and

”OUt HI”) when analogue output is controlled due to total flow counter result. It can be set to:

“ 0“

“ 0.0“

“ 0.00“

“0.000“

Decimal point position is changed by [^], [v] buttons.

“t unit”

- the unit of parameters

”OUt LO” and ”OUt HI”, while analogue output is controlled due to total flow counter result. It can be set to one of two values :

“unit”

“1000un”

- units

- thousands of units

i

Parameters ”t PrEc” and ”t unit” are available only if total flow counter is used to control current output (“SourCE” = tot”). When current flow rate is used to control it, the unit and precision of ”OUt LO” and ”OUt HI” parameters are defined by parameters “F unit”, “Ftunit” and “Point” of menu ”Flouu”.

Lo r”, ”Hi r” - this parameters define the output value range. If calculated output value Out exceeds defined range then analogue output generates signal equal to upper or lower border of the defined range. These parameters defines the percentage extension of nominal analogue range (with 0,1% resolution).

Parameter “Lo r” defines lower border of the range due to formula:

Out

min

= A - (A × “Lo r” %), where:

A – lower signal value range limit.

This parameter can be set from 0 to 99.9% (for active current output and active voltage output) or from 0 to 29.9% (for passive current output).

Parameter “Hi r” defines higher border of the range due to formula:

Out

max

= B + (B × “Hi r” %), where:

B – higher signal value range limit.

This parameter can be set from 0 to 19.9% (for active and passive current output) or from 0 to 9.9% (for active voltage output).

In example on page 58 of the DISPLAY VALUES CALCULATION paragraph

the procedure of the analogue outputs determining is presented in details.

AL” - this parameter determines the behaviour of analogue output if any critical situation occurs. According to version of the device, this parameter can be set:

For active current output:

“noCHAn”

“22.1”

- current will not change,

- current will be set to 22.1 mA,

“3.4”

“0.0”

- current will be set to 3.4 mA,

- current will be set to 0 mA.

45

User manual - FLOW METER SPP-N118

For passive current output:

“noCHAn”

“22.1”

“3.4”

- current will not change,

- current will be set to 22.1 mA,

- current will be set to 3.4 mA,

For active voltage output:

“noCHAn”

“11.0”

“5.5”

“1.2”

“0.6”

“0.0”

- voltage will not change,

- voltage will be set to 11 V,

- voltage will be set to 5.5 V,

- voltage will be set to 1.2 V.

- voltage will be set to 0.6 V,

- voltage will be set to 0 V.

When the critical situation goes, the output signal will be set to value calculated due to formulas given above.

i

If parameter “OUtmod” is set to “oFF”, “4-20”, “0-20”, “0-5”, “1-5”, “0-10” or “2-10” the “critical situation” means that permissible measurement range is exceeded.

If parameter “OUtmod” is set to “modbuS”, the “critical situation” means communication delay (when no data is received) longer than “mbtimE” parameter (see description: “rS-485” menu).

Before turning off the device it is recommended to first disable the current output's power supply, and then the device itself. If the current output is supplied while the device itself is turned off, the output current will be about 27.5 mA.

7.3.9. ”briGHt” parameter

This parameter allows user to set bright of the LED display, bright can be set to conventional values from 1 to 8.

7.3.10. ”HOLd” menu

This menu contains parameters connected with peak detection function. See also full description of the peak detection function in paragraph: DETECTION OF THE PEAK VALUES

“modE” - the type of detected changes of the input signal, can be set to values:

”norm” - peaks , peak and next drop of the input signal of value equal at least “PEA”,

”inv”

- drops, drop and next peak of the input signal of value equal at least “PEA”,

46

User manual - FLOW METER SPP-N118

“PEA”

- minimal detected signal change classified as peak or drop (see Figure 6.4)

“timE” - maximum time of displaying of the peak (drop) value, can be set from 0.0 to 19.9 sec, with 0.1 sec. resolution. If „HdiS”=”HOLD” then setting parameter "timE"=0.0 causes holding peak value until [ESC] button is pressed. If „HdiS”=”rEAL” then value "timE"=0.0 means no holding.

“HdiS” - type of displayed values:

”rEAL”

- current value is displayed,

”HOLd” - peak (drop) value is displayed,

“H r1”, “H r2” - relay/LED outputs ( R1, R2) operation mode:

”rEAL”

- relay/LED operates depend on the current value,

”HOLd” - relay/LED operates depend on the peak (drop) value.

”HOUt”

- current output operation mode:

”rEAL”

- current output operates depend on the current value,

”HOLd” - current output operates depend on the peak (drop) value.

7.3.11. ”SECU” menu

This menu contains presets connected with availability of other parameters:

“SEtcod” - user password (4-digits number). If this parameter is set at value “0000”, user password is turned off.

If the user do not remember his password, the access to the menu is possible by the “one-use password”. To get this password please contact with

Marketing Division. “Single use password” can be used only one time, after that it is destroyed. Entering this password causes in clearing of user password, it means sets the user password to „0000”.

i

The “one-use password” can be used ONE TIME ONLY , it is impossible to use it again! The “one-use password” can be restored by Service Division only.

“Acc r1 ÷ Acc r2” - this option permits user (”on”) or prohibits (”oFF”) to modify the thresholds of the relays/LEDs R1 ÷ R2 without knowledge about user password.

7.3.12. ”rS-485” menu

This menu is connected with RS-485 interface, and sets his properties:

”Addr”

- this parameter defines the address of the device, accordingly to Modbus protocol.

It can be set in range from 0 to 199. If the value 0 is set then device, responds to frames with address 255 (FFh).

47

User manual - FLOW METER SPP-N118

”bAud” - this parameter determines RS-485 interface baud rate. It can be set to one of 8 possible values: ”1200”, ”2400”,”4800”, ”9600”, ”19200”, ”38400”, ”57600”,

”115200”.

”mbAccE”

- this parameter sets the access to the configuration registers of the device.

Possible values:

”on”

”oFF”

- configuration registers can be set via RS-485 interface,

- configuration registers can not be set via RS-485 interface.

i

The access to registers no 04h i 05h cant be denied by ”mbAccE” parameter (see:

LIST OF REGISTERS).

”mbtimE” - this parameter defines maximal time (sec) between following frames received by the device. If the delay will be greater than the value of ”mbtimE” parameter, the relays and the analogue output which are controlled via RS-485 interface, will set to alert state (see "OUtPUt" menu and “rELAy1” menu description). Parameter

mbtimE” can be set to values from 0 to 99 seconds. The value 0 means that the time will be not controlled.

”rESP”

- this parameter defines minimal (additional) delay between the Modbus message and the answer of the device (received and sent via RS-485 interface). This additional delay allows the device to work with poor RS-converters which do not works properly on baud rates higher than 19200. This parameter can be set to one of values:

- answer as quick as possible, no additional delay

”Std”

” 10c”

” 20c”

” 50c”

”100c”

”200c”

- answer delayed of 10, 20, 50, 100 of 200 chars respectively, where one character time depends on selected baud rate

i

In the most cases parameter ”rESP” should be set to ”Std” (no additional delay).

Unfortunately for some third party RS-converters ”rESP” should be adjusted

experimentally. Table 7.1 contains most frequently used values.

”bAud” parameter

”rESP” parameter

“38.4”

“ 10c”

“57.6”

“ 20c”

Tab.7.1. Settings of ”rESP” parameter

7.3.13. ”Edit t” paramet er

This parameter allows to change the edition mode of numerical parameters:

”dig”

- the change to “by digit” mode,

”Slid”

- slide change mode.

“115.2”

“ 50c”

48

User manual - FLOW METER SPP-N118

7.3.14. ”dEFS” parameter

This setting allows to restore the factory settings of the device. To get the access to this option special password is required: „5465”, next the device displays acknowledge question

„SEt?”. Press [ENTER] to acknowledge the restoring of factory settings or [ESC] to cancel.

7.3.15. ”SErv” menu

This menu contains the parameters for authorized service only. To enter this menu proper service password must be entered. Improper settings can causes of damage of the device.

7.4. UNITS CALCULATIONS EXAMPLES

During work with the device, there could be a need to recalculate measured value in a unit into another. In the device there is a possibility to do so independently for flow, total flow

and batcher using parameters “F coEF”, “t coEF”, “b coEF” respectively. Examples of

recalculations for some measurement units are shown below.

Input: litre

[ l ]

US gallon

[ gallon ]

Flow, Tot, Bat: litre

[ l ]

1

3,78541

4,54608

UK gallon

[ gallon ]

US ounce

[ US fl oz ]

UK ounce

[ UK fl oz ]

0,029574

0,028413

US beer barrel

[ bbl ]

UK beer barrel

[ imp. bl. ]

158,987

163,659

US gallon

[ gallon ]

0,264172

1

1,20094

0,007812

0,007506

42

43,2341

UK gallon

[ gallon ]

0,219969

0,832675

1

0,006505

0,00625

34,9723

36

US ounce

[ US fl oz ]

33,814

128

153,721

1

0,960742

5376

5533,98

UK ounce

[ UK fl oz ]

35,1957

133,23

160,003

1,04086

5595,68

5760,11

Tab.7.2. Coefficients for volume units

1

US beer barrel

[ bbl ]

0,00629

UK beer barrel

[ imp. bl. ]

0,00611

0,02381

0,028594

0,000186

0,000179

1

1,02938

0,02313

0,027778

0,000181

0,000174

0,971454

1

49

User manual - FLOW METER SPP-N118

stone

[ st ] gran

[ gr ]

UK ton

[ t ]

US ton

[ t ]

Input: kilogram

[ kg ]

Flow, Tot, Bat: kilogram

[ kg ]

1

0,02835

ounce

[ oz ] pound

[ lb ]

0,453592

6,35029

0,000065

1016,04

907,184

1

16

224

ounce

[ oz ]

35,2739

0,002286

35840

32000

pound

[ lb ]

2,20462

0,0625

1

14

0,000143

2240

2000

stone

[ st ]

0,157473

0,004464

0,071429

1

0,00001

160

142,857 -

-

1

gran

[ gr ]

15432,3

437,5

7000

98000

Tab.7.3. Coefficients for weight units

UK ton

[ t ]

0,000984

0,000028

0,000446

0,00625

-

1

0,892857

-

1,12

1

US ton

[ t ]

0,001102

0,000031

0,0005

0,007

7.4.1. Units recalculating examples

Task:

Lets assume that we have a device which woks with sensor scaled in litres. We want, that flow measurement is displayed in US ounces, total flow in hundreds of US gallons and batcher in US gallons.

Solution:

Using Tab.7.2 (number value in table corresponds to number of input units – left column,

in one output unit – upper row) set:

F coEF” parameter as: 33,814,

t coEF” parameter as: 0,002641,

and “b coEF” parameter as: 0,264172.

50

User manual - FLOW METER SPP-N118

7.5. MENU STRUCTURE

ESC

MENU

ESC

MENU

Measurement mode

ESC

MENU

Press and hold at least 2 seconds

0 _ _ _

ENTER

PAUSE

4-digit user password entering (if it is different from „0000”)

rELAy1

ESC

MENU

ESC

MENU

ESC

MENU

ESC

MENU

ESC

MENU

ESC

MENU rELAy2

FLouu bAtCH b PrEc b unit

CLrbAt m CLr

A rES

Atunit

A dLy

ENTER

PAUSE totAL

Pr inP init d

ENTER

PAUSE

Funct

ESC

MENU modE

ENTER

PAUSE

ENTER

PAUSE

ESC

MENU

Parameter edition

ENTER

PAUSE

ENTER

PAUSE

ESC

MENU

ESC

MENU

Parameter edition

See next page

ENTER

PAUSE

ESC

MENU

Options similar to „rELAy1” menu

ENTER

PAUSE

ESC

MENU

ENTER

PAUSE

ENTER

PAUSE

ESC

MENU

Parameter edition

ENTER

PAUSE

CLEAr?

ESC

MENU

ENTER

PAUSE

Batching counter clearing

t PrEc t unit

CLrtot

ENTER

PAUSE

ENTER

PAUSE

ESC

MENU

Parameter edition

m CLr

ENTER

PAUSE

CLEAr?

ESC

MENU

ENTER

PAUSE

Balance counter clearing

ENTER

PAUSE

ESC

MENU

ENTER

PAUSE

ESC

MENU

I tyPE

I CHAr

Point

F unit

Ftunit

F or P

Lo CAL

Hi CAL

AddPnt dELPnt

EdtPnt

CutoFF

Lo r

Hi r

SourCE

SEt P

SEt P2

ENTER

PAUSE

ENTER

PAUSE

ESC

MENU

Parameter edition

HYSt b PrEc b unit t PrEc t unit

Visible only if

SourCE”=”bAt

Visible only if

SourCE”=”tot

modE t on t oFF unit

ALArmS

ENTER

PAUSE

ENTER

PAUSE

ESC

MENU

Parameter edition

51

52

User manual - FLOW METER SPP-N118

See previous page

ESC

MENU

FiLtEr

ESC

MENU

OUtPUt

ESC

MENU briGHt

ENTER

PAUSE

ENTER

PAUSE

ESC

MENU

Parameter edition

ESC

MENU

HOLd

ESC

MENU

SECU

ESC

MENU rS-485

ESC

MENU

Edit t

ESC

MENU dEFS

ENTER

PAUSE

ESC

MENU

ENTER

PAUSE

ESC

MENU

Parameter edition

ENTER

PAUSE

ESC

MENU

ENTER

PAUSE

ESC

MENU vALUE

ENTER

PAUSE

ENTER

PAUSE

ESC

MENU

Parameter edition

droP

OUtmod

ENTER

PAUSE

ENTER

PAUSE

ESC

MENU

Parameter edition

SourCE

OUt LO

OUt HI b PrEc b unit t PrEc t unit

Lo r

Hi r

AL

option

ENTER

PAUSE

ESC

MENU

ENTER

PAUSE

ESC

MENU

SEtcod

ENTER

PAUSE

ENTER

PAUSE

ESC

MENU

Parameter edition

Acc r1

Acc r2

Addr

ENTER

PAUSE

ENTER

PAUSE

ESC

MENU

Parameter edition

bAud mbAccE mbtimE rESP

4-digit special password entering

0 _ _ _

ESC

MENU

ENTER

PAUSE

SEt?

ENTER

PAUSE

ESC

MENU modE

PEA timE

H dis

H r1

H r2

HOut

ENTER

PAUSE

Default settings restoring

ENTER

PAUSE

ENTER

PAUSE

ESC

MENU

Parameter edition

option

ESC

MENU

SErv

User manual - FLOW METER SPP-N118

The input of the device is equipped with over-current protection circuit. This circuit protects the standard resistor to damage. Maximum input current is set to 40mA.

When temperature of the standard resistor falls, the protection circuit will turn off himself automatically, and the device will measure the input current again. Due to thermal phenomenon in the standard resistor, precision of the measurement may be lower, during few minutes (up to the standard resistor temperature will falls to the environment temperature).

The first step to compute the result of measure is the calculation of the normalized result

(it means result of 0-1 range). To do it, the begin of the input range (0 mA for 0-20mA range, and 4mA for 4-20mA range) must be subtracted from measured value. Next, received result must be divided by the width of the input range ( it means 20mA for 0-20mA range, and 16mA for 4-20mA range). So normalized result can be expressed by expressions:

i

I n

=

I n

=

I inp.

4

16

I inp.

20

for

4 ÷ 20 mA range

for 0 ÷ 20 mA range where I inp.

Means input current (in mA), and I n –

normalized result.

If measured value exceeds the nominal input range (0-20mA or 4-20mA), and do not exceed the permissible input range, then received normalized I n

result will exceed 0-1 range, e.g. input range 4-20 mA, input current = 3 mA – the normalized result is equal -0,0625, and for input current = 22 mA, the normalized result is equal

1,125. In such cases presented expressions are still correct.

9.1. ADDITIONAL CALCULATIONS (USED CONVERSION CHARACTERISTIC)

The manner of the additional computation of the displayed result depends on selected conversion characteristic. All presented charts are connected with the input range 4 - 20 mA.

9.1.1. Linear characteristic

The normalized result is converted by fixed coefficients determined by “Lo CAL” and

“Hi CAL” parameters (when the normalized results is equal 0, then value “Lo CAL” is displayed, and when the normalized results is equal 1, then value “Hi CAL” is displayed).

Expression presented below shows the manner of result calculation:

W =I

n

× 

"Hi CAL""Lo CAL"   "Lo CAL" , where W means the displayed value.

i

The value of the “Lo CAL” parameter can be higher than the value of “Hi CAL” parameter. In such a case, for an increasing value of input current the displayed value decreases.

53

User manual - FLOW METER SPP-N118

Lo CAL Hi CAL

Lo CAL Hi CAL

0 4 8 12

Input current [mA]

16 20 0 4 8 12

Input current [mA]

16 20

Figure. 9.1 Normal („Lo CAL” < ”Hi CAL”) and inverted („Lo CAL” > ”Hi CAL”) characteristic

9.1.2. Square characteristic

The normalized result is squared and further conversion is done as for linear characteristic.

Conversion is made accordingly with the expression:

W =I

2

n

× 

"Hi CAL""Lo CAL"   "Lo CAL" ,

where W means the displayed value.

Hi CAL Lo CAL

Lo CAL Hi CAL

0 4 8 12 16

Input current [mA]

20 0 4 8 12 16

Input current [mA]

20

Figure. 9.2 Normal („Lo CAL” < ”Hi CAL”) and inverted („Lo CAL” > ”Hi CAL”) characteristic

54

User manual - FLOW METER SPP-N118

9.1.3. Square root characteristic

The normalized result is rooted and further conversion is done as for linear characteristic.

Conversion is made accordingly with the expression:

W =

I

n

× 

"Hi CAL" "Lo CAL"   "Lo CAL" ,

where W means the displayed value.

i

Showed above expression is not valid when normalized result is negative. It is possible for 4-20 mode only. In this case (I n

<0) the displayed result is equal

“Lo CAL” (see graphs below).

Lo CAL

Hi CAL

Lo CAL

0 4 8 12 16

Input current [mA]

20

Hi CAL

0 4 8 12 16

Input current [mA]

20

Figure. 9.3 Normal („Lo CAL” < ”Hi CAL”) and inverted („Lo CAL” > ”Hi CAL”) characteristic

9.1.4. User defined characteristic

User defined characteristic is defined as set of X-Y points. Number of the points is variable and may be set from 2 to 20 points which make linear segments (see graph and see ”FLouu”

menu).

Due to the normalized result I from figure below, and I n be chosen. n

, the device computes specific segment, e.g. for characteristic

= 0,65 the segment between points X = ”50.0.” and X = ”70.0.” will

Let's mark those points as PL (point low) i PH (point high) - in this example PL= “50.0,” and

PH = “70.0.”, and the normalized result I n

for the point PL as I p

(in this example I

0,5). The displayed result is calculated accordingly to the expression: p

= I n

(PL) =

W = I

n

I p

 ×

[

Y PH −Y PL]

[

X PH −X PL]

×

100  Y PL where Y(PH), X(PH), Y(PL), X(PL) mean values of X and Y coordinates of PH i PL points.

i

If the normalized result exceeds the user defined characteristic values, then specific utmost segment, defined by two next points, is used for calculations. If characteristic from figure below is used, and if I n

>1 then segment defined by points

X(PL) = “90.0.”, X(PH) = “100.0.” will be used.

55

User manual - FLOW METER SPP-N118

0

Normalized measurement I n

(for 0-20 mA range)

0,2 0,35

0,5 0,7 0,9

5-elements characteristic

X (PH) = „70.0.”

1

Y (PH)

X = „35.0.”

X (PL) = „50.0.”

X = „20.0.”

Prąd wejściowy [mA]

Y (PL)

X = „90.0.”

X = „100.0.”

0 4 8 12

Input current [mA]

16 20

Figure. 9.4 Example of user defined characteristic

9.2. EXAMPLES OF CALCULATIONS

Example 1 : Selection of the permissible input range (“4-20” mode)

If in “4-20” mode the user sets “Lo r” = 20,0% and “Hi r” = 10,0%, then permissible input currents range will be equal: 3,2 mA ÷ 22 mA. Lower border of the range is the result of calculations: 4 mA - 4 mA × 20%, and the higher : 20 mA + 20 mA × 10%.

Example : The normalized I n result calculation

Let the input mode = 4-20 mA. The normalized I

expression on page 53, so if I

n

result is calculated accordingly to the in

= 10 mA then 10 mA - 4 mA = 6 mA, and this result should be divided by the width of input range (16 mA). Finally the normalized result: I n

= 6/16 = 0,375.

In case when input current exceeds nominal measurement range, calculations are similar. For example if input current is equal 2,5 mA then I equal 20,5 mA then I n

= (20,5 - 4)/16

@ 1,0313.

n

= (2,5 - 4)/16

@ -0,0938, and if input current is

Example

Let the input mode = 4-20 mA, and parameters “Lo CAL” and “Hi CAL” equal to 300 and 1200 respectively. The calculations will be done for three different input currents from example 2.

56

User manual - FLOW METER SPP-N118

a) I in

=10 mA and I n

= 0,375

Accordingly to expression on page 53 for linear characteristic:

0,375 × [1200 - 300]

@ 337 and next, the “Lo CAL” value is added to the result , so the displayed value:

W

@ 337 + 300 = 637 b) I in

= 2,5 mA and

W

@ 216.

I n

= -0,0938.

c) I in

= 20,5 mA and

W

@ 1228.

I n

= 1,0313.

Example

Let the input mode = 4-20 mA, and parameters “Lo CAL” and “Hi CAL” equal to 300 and 1200 respectively. The calculations will be done for there different input currents from example 2.

a) I in

=10 mA and I n

= 0,375

Accordingly to expression on page 54 for square characteristic: (0,375)

and next, the “Lo CAL” value is added to the result , so the displayed value:

W

@ 127 + 300 = 427

2 × [1200 - 300]

@ 127.

b) I in

= 2,5 mA and

W

@ 308.

I n

= -0,0938.

c) I in

= 20,5 mA and

W

@ 1257.

I n

= 1,0313.

Example

Let the input mode = 4-20 mA, and parameters “Lo CAL” and “Hi CAL” equal to 300 and 1200 respectively. The calculations will be done for there different input currents from example 2.

a) I in

=10 mA and I n

= 0,375

Accordingly to expression on page 55 for square root characteristic:

0,375 × [1200 - 300]

@ 551.

and next, the “Lo CAL” value is added to the result , so the displayed value:

W

@ 551 + 300 = 851 b) I in

= 2,5 mA and I n

= -0,0938 , normalized result is negative , so the displayed value is equal to “Lo CAL” parameter: W

@ “Lo CAL” = 300.

c) I in

= 20,5 mA and I n

W

@ 1214.

= 1,0313.

57

User manual - FLOW METER SPP-N118

Example

Let the input mode = 4-20 mA, and the user selected the 10 segment characteristic. To do this it is necessary to enter X and Y coordinates of 11 points (see Menu ”FLouu”).

The calculations will be done for three different input currents from example 2, so in calculations some of the segments will be used only.

Let the following points will be given:

X1 = “00.0.”, Y1 = “10.0”,

X2= “10.0.”, Y2 = “20.0”,

....

X6 = “30.0.”, Y6 = “30.0”,

X7 = “40.0.”, Y7 = “80.0”,

....

X10 = “90.0.”, Y10 = “900.0”,

X11 = “100.0.”, Y11 = “820.0”,

Additionally all other points must to be defined and stored in the device memory.

a) I in

=10 mA and I n

= 0,375

The segment defined by X6 = “30.0.” i X7 = “40.0.” for this I n will be selected. Accordingly to

expressions given for user defined characteristic (see page 55) X6(PL) = 30, Y6(PL) = 30,

X7(PH) = 40, Y7(PH) = 80 and I p

= 0,3 , the displayed value :

W = I

n

I p

 ×

[

Y PH −Y PL]

[

X PH −X PL]

×

100  Y PL=

=

0,375−0,3 ×

[

80−30]

[

40−30]

×

100  30 ≃ 67 b) I in

= 2,5 mA and I n

= -0,0938, because of the normalized I n

value is lower than 0, the segment defined by X1 and X2 will be selected. X1(PL) = 0, Y1(PL) = 10, X2(PH) = 10,

Y2(PH) = 20 and I p

= 0. For these values the displayed value W

@ 1. c) I in

= 20,5 mA and I n

= 1,0313. , because of the normalized I n

value is higher than 1, the segment defined by X10 and X11 will be selected, and X10(PL) = 90, Y10(PL) = 900,

X11(PH) = 100, Y11(PH) = 820 and I p

= 0,9 for these values the displayed value W

@ 795.

Example 7 Current output value calculation

Lets assume that we have active current output and its parameters are:

“OUtmod” = “4-20”, “OUt LO” = 100, “OUt HI” = 200, “Lo r” = 5.0, “Hi r” = 5.0

Parameters “Lo r” and “Hi r” define working range of current output to 3.8 ÷ 21 mA.

Output current will be calculated for three displayed values „D”: a) D = „17.5”

According to formula from page 44:

I out

= (17.5-10.0) / (20.0-10.0) × 16 mA + 4 mA = 0.75 ·16 + 4 = 16 mA

Calculated I out

does not exceed the output working range (3.8 - 21 mA).

58

User manual - FLOW METER SPP-N118

b) D = „20.5”

According to formula from page 44:

I out

= (20.5-10.0) / (20.0-10.0) × 16 mA + 4 mA = 1.05 ·16 + 4 = 20.08 mA

Calculated I out

does not exceed the output working range (3.8 - 21 mA).

c) D = „30.0”

According to formula from page 44:

I out

= (30.0-10.0) / (20.0-10.0) × 16 mA + 4 mA = 2 ·16 + 4 = 36 mA.

Calculated I out exceeds the output working range (3.8 - 21 mA), so current output will generate current equal to the upper border of range defined by parameter “Lo r” i “Hi r” (it means 21 mA).

Example

It is necessary to measure the pipeline flow using orifice plate (flange), which makes a pressure difference 25 kPa, at flow rate 10 m 3 /h. Measurement can be done using differential pressure sensor with range 25kPa, and current output signal 4-20mA. The sensor output

should be connected to SPP-N118 terminals, and proper configuration of input and

recalculation is required.

Let meter measures with precision 0,1 m

3

/h, parameters of “Flouu” menu should be set as below:

“I tyPE“ = “4-20mA” - current input type

“I CHAr“ = “Sqroot”

- input characteristic – square-root. It is necessary to obtain flow rate readings direct proportional to pressure difference (using

“Point” = “0.0” differential pressure sensor proposed in example).

- decimal point position, it allows to obtain displaying precision

0,1 m

3

/h

“F unit” = “m 3”

“Ftunit” = “hour”

- parameters defining the unit flow as m 3 /h

“Lo CAL” = “000.0”

“Hi CAL” = “010.0”

- value displayed when input current is equal 4mA - 0,0 m 3 /h

- value displayed when input current is equal 20mA - 10,0 m

3

/h

Parameter “FiLtEr” and “CutoFF” should be set if necessary. If it is necessary to input current lower than 1% (it means 4.16mA) stop total flow counter incrementation then

“CutoFF” parameter should be set to value “1.0”.

If user would like to protect input signal from the noise (to stabilize measurements), then parameter “FiLtEr” should be set to value allowing easy readings.

59

User manual - FLOW METER SPP-N118

10. THE MODBUS PRO TOCOL HANDLING

Transmission parameters: 1 start bit, 8 data bits, 1 or 2 stop bit (2 bits are send, 1 and 2 bits are accepted when receive), no parity control

Baud rate: selectable from: 1200 to 115200 bits/second

Transmission protocol: MODBUS RTU compatible

The device parameters and display value are available via RS-485 interface, as HOLDINGtype registers (numeric values are given in U2 code) of Modbus RTU protocol. The registers

(or groups of the registers) can be read by 03h function, and wrote by 06h (single registers) or

10h (group of the registers) accordingly to Modbus RTU specification. Maximum group size for

03h and 10h functions can not exceeds 16 registers (for single frame).

i

The device interprets the broadcast messages, but then do not sends the answers.

10.1. LIST OF REGISTERS

Some parameters are located on two registers (higher word in first register, and lower word in next one). After writing of one of them device controls result of their 32-bit value, and if it is necessary corrects value of second register automatically. If appropriate modification is impossible, both registers stay unaffected and device responds with error code 03h

(see: TRANSMISSION ERRORS DESCRIPTION).

Register Write

01h 1

02h 1

No

03h

04h

05h

06h 2

Range

0 ÷ 999999

Register description

Measurement value (no decimal point)

No

Yes

Yes

Yes

Yes 2CCh÷1800h

Yes

0h, A0h, 60h

0 ÷ 3 see descr.

0h ÷ 1800h

0h ÷ 1600h

The status of the current measurement; 0h - data valid; A0h - top border of the measurement range is exceeded; 60h - bottom border of the measurement range is exceeded;

Point ” parameter in “FLouu” menu (precision of flow rate displaying). Identical as reg. 12h

State of the relays and alarm LED (binary format)

(1 - on, 0 - off): 00000000 000e00ba

a - relay R1; b - relay R2; e - alarm state indicator; If written, only

a, b bits are important (others are ignored) these bits allows user to control the relays via RS-485 interface

State of active current output, expressed in 1/256 mA units – it means that high byte express integer part, and low byte fractional part of desired output current.

State of passive current output, expressed in 1/256 mA units – it means that high byte express integer part, and low byte fractional part of desired output current.

State of active voltage output, expressed in 1/512 V units – it means that high byte express integer part, and low byte fractional part of desired output voltage.

07h 1

08h 1

No 0 ÷ 999999 Peak (drop) value (no decimal point)

60

User manual - FLOW METER SPP-N118

Register Write

09h 1

0Ah

1

No

0Bh 1 No

0Ch

0Dh

0Eh

0Fh

10h

11h

12h

13h

14h

15h

16h

17h

18h

19h

1Ah

1Bh

1Ch

1Dh

1Eh

1Fh

20h

21h

1

1

1

1

3

No

No

No

No

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

No

Range

0÷FFFFFFFFh

0÷999

0÷999

0÷FFFFh

0÷999

0÷999

0 ÷ 1

0 ÷ 3

0 ÷ 3

0 ÷ 2

0 ÷ 1

0÷99

0 ÷ 9999

0 ÷ 9999

0 ÷ 999

0 ÷ 199

0 ÷ 199

0 ÷ 1999

0 ÷ 1

0 ÷ 3

0 ÷ 1

0 ÷ 3

0 ÷ 199

205Eh

Register description

Total flow component expressed in thousands of units e.g.:

999999999 999 . 999

Total flow component expressed in units e.g.:

999999999 999 . 999

Total flow component expressed in thousandths of units e.g.:

999999999 999 . 999

Batcher component expressed in thousands of units e.g.:

65535 999 . 999

Batcher component expressed in units e.g.:

65535 999 . 999

Batcher component expressed in thousandths of units e.g.:

65535 999 . 999

I tyPE” parameter in “FLouu” menu (nominal input range).

0 - 0-20 mA range; 1 - 4-20 mA range

I CHAr” parameter in “FLouu” menu (characteristic type)

0 - linear ; 1 - square; 2 - square root; 3 - user defined

Point ”parameter in “FLouu” menu (precision of flow rate displaying): 0 - “ 0”; 1 - “ 0.0”; 2 - “ 0.00”; 3 - “0.000

“Ftunit” parameter in “FLouu” menu (the unit of time while flow rate displaying): 0 - SEC; 1 - min; 2 - hour;

“F unit” parameter in “FLouu” menu (the unit of volume while flow rate displaying): 0 - unit; 1 - 1000un;

“CutoFF” parameter in “Flouu” menu (cut-off threshold), in 0,1%

Lo CAL” parameter in “Flouu” menu, no decimal point included

Hi CAL” parameter in “Flouu” menu, no decimal point included

Lo r” parameter in “Flouu” menu, in 0,1%

Hi r” parameter in “Flouu” menu, in 0,1%

“vALUE” parameter in “FiLtEr” menu (measurement filtering rate)

“droP” parameter in “FiLtEr” menu expressed in tenth of percent

“t unit” parameter in “totAL” menu (the unit of volume while total flow counter result displaying): 0 - unit; 1 - 1000un;

“t PrEc” parameter in “totAL” (precision of total flow counter result displaying):

0 - “ 0”; 1 - “ 0.0”; 2 - “ 0.00”; 3 - “0.000”

„m CLr” parameter in „totAL” menu: 0 - „oFF”, 1 - „on”

“init d” parameter (kind of value displayed after power on):

0 - “FLo”; 1 - “tot”; 2 - “tot2”; 3 - “tot3”

Device address

Device identification code (ID)

61

62

User manual - FLOW METER SPP-N118

Register Write

22h

23h

24h

25h

27h

2Dh

2Fh

30h

31h

32h

33h

4

5

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Range

0 ÷ 7

0 ÷ 1 see descr.

0 ÷ 5

0 ÷ 99

1 ÷ 8

0 ÷ 1

Register description

“bAud” parameter in “rS-485” menu (baud rate);

0 - 1200 baud; 1 - 2400 baud; 2 - 4800 baud; 3 - 9600 baud;

4 - 19200 baud; 5 - 38400 baud; 6 - 57600 baud; 7 - 115200 baud

“mbAccE” parameter in “rS-485” menu (permission to write registers via RS-485 interface); 0 - write denied ; 1 - write allowed

Parameters of “SECU” menu (binary format (0 - „oFF”, 1 - „on”):

bit 0 - “Acc r1” parameter;bit 1 - “Acc r2” parameter;

“rESP” parameter in “rS-485” menu (additional response delay);

0 - no additional delay; 1 - ”10c” option; 2 - ”20c” option;

3 - ”50c” option; 4 - ”100c” option; 5 - ”200c” option;

“mbtimE” parameter in “rS-485” menu (maximum delay between received frames); 0 - no delay checking;

1 ÷ 99 - maximum delay expressed in seconds

briGHt” parameter (display brightness);

1 - the lowest brightness; 8 - the highest brightness

Edit” parameter (numerical parameters edit mode);

0 - „dig” mode; 1 - „SLid” mode

Parameters of relay R1 operation

0 ÷ 999999 “SEt P” parameter in “rELAy1” menu, no decimal point included

34h

35h

36h

37h

38h

39h

3Ah

3Bh

3Ch

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

0 ÷ 99999

0 ÷ 2

0 ÷ 3

HySt” parameter in “rELAy1” menu, no decimal point included

0 ÷ 5

0 ÷ 999

0 ÷ 999

0 ÷ 1

0 ÷ 2

modE” parameter in “rELAy1” menu:

0 - “noACt” mode; 1 - “on” mode; 2 - “oFF” mode; 3 - “in” mode;

4 - “out” mode; 5 - “modbuS” mode

“t on” parameter in “rELAy1” menu, expressed in tenth of seconds or tenth of minutes depend on “unit” parameter

“t oFF” parameter in “rELAy1” menu, expressed in tenth of seconds or tenth of minutes depend on “unit” parameter

“unit” parameter in “rELAy1” menu:

0 - seconds; 1 - minutes

“ALArmS” parameter in “rELAy1” menu:

0 - no changes; 1 - on; 2 - off

0 ÷ 999999 “SEt P2” parameter in “rELAy1” menu, no decimal point included

“SourCE” parameter in “rELAy1” menu (kind of value controlled relay): 0 - “FLo”; 1 - “bAt”;2 - “tot”;

“t PrEc” parameter in “rELAy1” menu (precision of thresholds and hysteresis while relay is controlled due to total flow counter value):

0 - “ 0”; 1 - “ 0.0”; 2 - “ 0.00”; 3 - “0.000”

User manual - FLOW METER SPP-N118

Register Write

3Dh

3Eh

3Fh

40h

41h

42h

43h

44h

45h

46h

47h

48h

49h

4Ah

4Bh

4Ch

4Dh

70h

71h

6

6

Yes

Yes

Yes

Range

0 ÷ 1

0 ÷ 3

0 ÷ 1

Register description

“t unit” parameter in “rELAy1” menu (the unit of thresholds and hysteresis while relay is controlled due to total flow counter value):

0 - unit; 1 - 1000un;

“b PrEc” parameter in “rELAy1” menu (precision of thresholds while relay is controlled due to batcher counter value):

0 - “ 0”; 1 - “ 0.0”; 2 - “ 0.00”; 3 - “0.000”

“b unit” parameter in “rELAy1” menu (the unit of thresholds while relay is controlled due to batcher counter value):

0 - unit; 1 - 1000un;

Parameters of relay R2 operation

0 ÷ 999999 “SEt P” parameter in “rELAy2” menu, no decimal point included

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

0 ÷ 99999

0 ÷ 5

0 ÷ 999

0 ÷ 999

0 ÷ 1

0 ÷ 2

HySt” parameter in “rELAy2” menu, no decimal point included

modE” parameter in “rELAy2” menu:

0 - “noACt” mode; 1 - “on” mode; 2 - “oFF” mode; 3 - “in” mode;

4 - “out” mode; 5 - “modbuS” mode

“t on” parameter in “rELAy2” menu, expressed in tenth of seconds or tenth of minutes depend on “unit” parameter

“t oFF” parameter in “rELAy2” menu, expressed in tenth of seconds or tenth of minutes depend on “unit” parameter

“unit” parameter in “rELAy2” menu:

0 - seconds; 1 - minutes

“ALArmS” parameter in “rELAy2” menu:

0 - no changes; 1 - on; 2 - off

0 ÷ 999999 “SEt P2” parameter in “rELAy2” menu, no decimal point included

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

72h

6

÷ 95h

6

0 ÷ 2

0 ÷ 3

0 ÷ 1

-999 ÷ 1999

0 ÷ 9999

“SourCE” parameter in “rELAy2” menu (kind of value controlled relay): 0 - “FLo”; 1 - “bAt”;2 - “tot”;

“t PrEc” parameter in “rELAy2” menu (precision of thresholds and hysteresis while relay is controlled due to total flow counter value):

0 - “ 0”; 1 - “ 0.0”; 2 - “ 0.00”; 3 - “0.000”

“t unit” parameter in “rELAy2” menu (the unit of thresholds and hysteresis while relay is controlled due to total flow counter value):

0 - unit; 1 - 1000un;

The value of „X” coordinate of point no. 1 of the user defined characteristic, expressed in 0,1%

The value of „Y” coordinate of point no. 1 of the user defined characteristic, no decimal point included

Further pairs of „X” - „Y” coordinates of points no. 2 ÷ 19 of the user defined characteristic

63

User manual - FLOW METER SPP-N118

64

Register Write

96h 6

Range

Yes -999 ÷ 1999

97h

A0h

A1h

A2h

6

A3h

A4h

2

2

2

2

2

Yes

Yes

Yes

Yes

Yes

Yes

0 ÷ 9999

0 ÷ 3

0 ÷ 2

0 ÷ 5

0 ÷ 999999

0 ÷ 999999

Register description

The value of „X” coordinate of point no. 20 of the user defined characteristic, expressed in 0,1%

The value of „Y” coordinate of point no. 20 of the user defined characteristic, no decimal point included

OUtmod” parameter in “OUtPUt” menu (active current output mode)

0 - current output disabled ; 1 - current output enabled with

4 ÷

20mA mode; 2 - current output enabled with 0÷20mA mode ;

3 - current output controlled via RS-485 interface

OUtmod” parameter in “OUtPUt” menu (passive current output mode)

0 - current output disabled ; 1 - current output enabled with

4 ÷

20mA mode; 2 - current output controlled via RS-485 interface

OUtmod” parameter in “OUtPUt” menu (active voltege output mode)

0 - voltage output disabled ; 1 - voltage output enabled with 0

÷5V

mode; 2 - voltage output enabled with 1÷5V mode ; 3 - voltage output enabled with 0÷10V mode ; 4 - voltage output enabled with

2÷10V mode ; 5 - voltage output controlled via RS-485 interface

OUt LO” parameter in “OUtPUt” menu, no decimal point included

OUt HI” parameter in “OUtPUt” menu, no decimal point included

A5h

A6h

A7h

A8h

A9h

2

2

2

2

2

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

0 ÷ 999

0 ÷ 299

0 ÷ 199

0 ÷ 99

0 ÷ 3

0 ÷ 2

0 ÷ 5

0 ÷ 2

0 ÷ 3

Lo r” parameter in “OUtPUt” menu, for active current output and active voltage output, expressed in 0.1%

Lo r” parameter in “OUtPUt” menu for passive current output, expressed in 0.1%

Hi r” parameter in “OUtPUt” menu for active and passive current output, expressed in 0.1%

Hi r” parameter in “OUtPUt” menu for active voltage output, expressed in 0.1%

AL” parameter in “OUtPUt” menu (active current output value on critical exception): 0 - no change; 1 - 22.1 mA; 2 - 3.4 mA; 3 - 0 mA

AL” parameter in “OUtPUt” menu (passive current output value on critical exception): 0 - no change; 1 - 22.1 mA; 2 - 3.4 mA

AL” parameter in “OUtPUt” menu (active voltage output value on critical exception): 0 - no change; 1 - 11 V; 2 - 5.5; 3 - 1.2 V;

4 - 0.6 V; 5 - 0 V

“SourCE” parameter in “OUtPUt” menu (kind of value controlled current output): 0 - “FLo”; 1 - “bAt”; 2 - “tot”;

“t PrEc” parameter in “OUtPUt” menu (precision of “OUt LO” and “OUt HI” parameters displaying, while current output is controlled due to total flow counter value): 0 - “ 0”; 1 - “ 0.0”; 2 - “

0.00”; 3 - “0.000”

Register Write

AAh 2 Yes

ABh 2 Yes

ACh 2 Yes

C0h

C1h

C2h

C3h

C4h

C5h

C8h 2

D0h

Yes

Yes

D1h

D2h

D3h 1

D4h 1

D5h

D6h

Yes

Yes

Yes

Yes

Yes

D7h

Yes

Yes

Yes

Yes

Yes

Yes

Yes

User manual - FLOW METER SPP-N118

Range

0 ÷ 1

0 ÷ 3

0 ÷ 1

0 ÷ 1

0 ÷ 9999

0 ÷ 199

0 ÷ 1

0 ÷ 1

0 ÷ 1

0 ÷ 1

0 ÷ 1

0 ÷ 3

0 ÷ 1

0÷999999

0 ÷ 1

0 ÷ 1

0 ÷ 999

Register description

“t unit” parameter in “OUtPUt” menu (the unit of “OUt LO” and

OUt HI” parameters displaying, while current output is controlled due to total flow counter value): 0 - unit; 1 - 1000un;

“b PrEc” parameter in “OUtPUt” menu (precision of “OUt LO” and “OUt HI” parameters displaying, while current output is controlled due to batcher counter value): 0 - “ 0”; 1 - “ 0.0”; 2 - “

0.00”; 3 - “0.000”

“b unit” parameter in “OUtPUt” menu (the unit of “OUt LO” and

OUt HI” parameters displaying, while current output is controlled due to batcher counter value): 0 - unit; 1 - 1000un;

modE” parameter in “HOLd” menu (type of detected changes):

0 - peaks; 1 - drops

PEA” parameter in “HOLd” menu (minimum detectable change, no decimal point included)

timE” parameter in “HOLd” menu, maximum peaks' (or drops') display time expressed in seconds

HdiS” parameter in “HOLd” menu (the type of values displayed on the display ):

0 - current measurement value; 1 - peaks (or drops) values

H r1” parameter in “HOLd” menu (the control mode of relay R1 and LED R1) :

0 - control depends on current measurement values;

1 - control depends on peaks (or drops) values;

H r2” parameter in “HOLd” menu (the control mode of relay R2 and LED R2) :

0 - control depends on current measurement values;

1 - control depends on peaks (or drops) values;

HOut” parameter in “HOLd” menu:

0 - “rEAL” mode ; 1 - “HOLd” mode

“b unit” parameter in “bAtCH” menu (the unit of volume while batcher counter result displaying): 0 - unit; 1 - 1000un;

“b PrEc” parameter in “bAtCH” (precision of batcher counter result displaying):

0 - “ 0”; 1 - “ 0.0”; 2 - “ 0.00”; 3 - “0.000”

„m CLr” parameter in „bAtCH” menu: 0 - „oFF”, 1 - „on”

Number of batches counter

“A rES” parameter in “bAtCH” menu (batcher autoreset):

0 - disabled, 1 - enabled

“Atunit” parameter in “bAtCH” menu (time unit of autoreset delay): 0 - „SEC”, 1 - „min”

“A dLy” parameter in “bAtCH” menu (autoreset delay) expressed in tenth of seconds or tenth of minutes depend on “Atunit” parameter)

65

66

Register Write

D8h

D9h

DAh

Yes

Yes

Yes

Range

0 ÷ 1

0 ÷ 3

0 ÷ 3

User manual - FLOW METER SPP-N118

Register description

“F or P” parameter in “FLouu” submenu (type of value displayed on the display): 0 - flow value; 1 - time per one unit of flow ;

“Funct” parameter in “Pr inP” menu (programmable input operation mode):

0 - mode “diSAbL”, disabled

1 - mode “CLrtot”, zeroing of total flow counter,

2 - mode “CLrbAt”, zeroing of batcher counter and start next batching

3 - mode “inhibi”, holding of the total flow counter and batcher counter,

“modE” parameter in “Pr inP” menu (active level/edge of programmable input):

0 - “HI”; 1 - “LO”; 2 - “LO-HI”; 3 - “HI-LO”

E0h

E1h

E2h

E3h

E4h

E5h

E6h

E7h

E8h

E9h

EAh

EBh

ECh

EDh

EEh

Yes

Yes

Yes

0 ÷ 999999

0 ÷ 6

0 ÷ 999999

Value of “F coEF” parameter in “Flouu” submenu, without decimal point. Value of 0 in interpreted as 1 000 000.

Decimal point of “F coEF” parameter in “Flouu” submenu

0 - “ 0”; 1 - “ 0.0”; 2 - “ 0.00”; 3 - “0.000”; 4 - “0.0000”;

5 - “0.00000”, 6 - “0.000000”;

Value of “F coEF” parameter in “totAL” submenu, without decimal point. Value of 0 in interpreted as 1 000 000.

Yes

Yes

Yes

No

0 ÷ 6

0 ÷ 999999

0 ÷ 6

0 ÷ 999999

No 0 ÷ 999999999

No

No

0 ÷ 999

0 ÷ 999

Decimal point of “F coEF” parameter in “totAL” submenu

0 - “ 0”; 1 - “ 0.0”; 2 - “ 0.00”; 3 - “0.000”; 4 - “0.0000”;

5 - “0.00000”, 6 - “0.000000”;

Value of “b coEF” parameter in “bAtCH” submenu, without decimal point. Value of 0 in interpreted as 1 000 000.

Decimal point of “b coEF” parameter in “bAtCH” submenu

0 - “ 0”; 1 - “ 0.0”; 2 - “ 0.00”; 3 - “0.000”; 4 - “0.0000”;

5 - “0.00000”, 6 - “0.000000”;

Calculated flow (multiplied “PuLSEL” and “F coEF” values) expressed in user units (value without decimal point)

Calculated total flow component (multiplied “PuLSEL” and

“t coEF” values) expressed in thousands of user units (value without decimal point):

999999999 999 . 999

Calculated total flow component (multiplied “PuLSEL” and

“t coEF” values) expressed in user units (value without decimal point):

999999999 999 . 999

Calculated total flow component (multiplied “PuLSEL” and

“t coEF” values) expressed in thousandths of user units (value without decimal point):

999999999 999 . 999

User manual - FLOW METER SPP-N118

Register Write

EFh

F0h

F1h

No

No

No

Range

0 ÷ FFFFh

0 ÷ 999

0 ÷ 999

Register description

Calculated batcher component (multiplied “PuLSEL” and

“b coEF” values) expressed in thousands of user units (value without decimal point):

65535 999 . 999

Calculated batcher component (multiplied “PuLSEL” and

“b coEF” values) expressed in user units (value without decimal point):

65535 999 . 999

Calculated batcher component (multiplied “PuLSEL” and

“b coEF” values) expressed in thousandths of user units (value without decimal point):

65535 999 . 999

1

6

- it is recommended to read these registers simultaneously – (1,2) and (7,8), (D3h,D4h) in 2-registers frames, and registers (9h,Ah,Bh,Ch) in 4-registers frames. If single registers are read, data errors are possible because of changes of read value between successive registers readings. Zeroing of total flow counter is possible by preset of

0000h to any one of it's registers (09h ÷ 0Ch). Controlling of batcher counter is possible by writing appropriate value (0 - zeroing, 1 - start/continue, 2 - pause) into one of the batcher counter registers (0Dh ÷ 0Fh). Zeroing of

number of batches counter is possible by preset of 0000h to any one of it's registers (D3h ÷ D4h).

2 - these registers are active only if device is equipped with current or voltage output

3 - after writing to register no 20h the device responds with an “old” address in the message.

4

5

- after writing to register no 22h the device responds with the new baud rate.

- the value of the “mbAccE” parameter is also connected to write to this register, so it is possible to block a writes, but impossible to unblock writes via RS-485 interface, The unblocking of the writes is possible from menu level only.

- the pairs of „X -Y” coordinates may be defined for any free point. The pair is “free” (it means that particular point is not defined) if „X” coordinate of this point is equal 8000h. After writing both X and Y coordinate the point is defined and used in calculation of result. The coordinates of any point can be changed at any time.

10.2. TRANSMISSION ERRORS DESCRIPTION

If an error occurs while write or read of single register, then the device sends an error code according to Modbus RTU specifications (example message no 5).

Error codes:

01h - illegal function (only functions 03h, 06h and 10h are available),

02h - illegal register address

03h - illegal data value

08h - no write permission ( see: “mbAccE” parameter)

10.3. EXAMPLES OF QUERY/ANSWER FRAMES

Examples apply for device with address 1. All values are represent hexadecimal.

Field description:

ADDR

Device address on modbus network

FUNC

REG H,L

Function code

COUNT H,L

No. of registers to read/write (Hi and Lo byte)

BYTE C

Starting address (address of first register to read/write, Hi and Lo byte)

Data byte count in answer frame

DATA H,L

CRC L,H

Data byte (Hi and Lo byte)

CRC error check (Hi and Lo byte)

67

User manual - FLOW METER SPP-N118

1. Read of the displayed value (measurement) and status, the device address = 01h:

ADDR FUNC

01 03

REG H,L

00 01

The answer :

ADDR

01

i

FUNC BYTE C

03 06

DATA H1,L1

00 01

DATA H2, L2 DATA H3.L3

CRC L,H

86 A0 00 00 2A B4

DATA H1, L1 - reg. 01h (1 - high word of measurement value)

DATA H2, L2 - reg. 02h (86A0h - low word of measurement value ),

DATA H3, L3 - reg. 03h (0 - measurement status).

In this example measurement value is equal 186A0h (100 000 in decimal format).

Decimal point position is not included in measurement value (reg. 01h and 02h).

Decimal point position can be read from reg. 04h (

Point

parameter).

2. Read of device ID code

COUNT H,L

00 03

CRC L,H

54 0B

ADDR FUNC

01 03

REG H,L

00 21

COUNT H,L

00 01

CRC L,H

D4 00

The answer:

ADDR

01

FUNC

03

BYTE C

02

DATA H,L

20 5E

CRC L,H

20 7C

DATA - identification code (205Eh)

3. Change of the device address from 1 to 2 (write to reg. 20h)

ADDR FUNC

01 06

REG H,L

00 20

DATA H - 0

DATA L - new device address (2)

DATA H,L

00 02

CRC L,H

09 C1

68

User manual - FLOW METER SPP-N118

The answer (the same as the message):

ADDR FUNC

01 06

REG H,L

00 20

DATA H,L

00 02

CRC L,H

09 C1

4. Change of baud rate of all devices connected to the net (BROADCAST message).

ADDR FUNC

00 06

REG H,L

00 22

COUNT H,L

00 04

CRC L,H

29 D2

i

DATA H - 0

DATA L - 4, new baud rate 19200 baud

Device do not reply to BROADCAST-type messages.

5. Try to write improper data to register (register 04h):

ADDR FUNC

01 06

REG H,L

00 04

DATA H,L

00 10

CRC L,H

C9 C7

DATA H, L written value (10h = 16) out of allowable range (0 ÷ 5)

Device response ( with exception code 03h):

ADDR FUNC

01 86

ERR

03

CRC L,H

09 C1

i

There is no full implementation of the Modbus Protocol in the device. The functions presented above are available only.

69

User manual - FLOW METER SPP-N118

11. DEFAULT AND USER'S SETTINGS LIST

70

Parameter Description Default value

SourCE

SEt P

SEt P2

HYSt b PrEc b unit t PrEc t unit modE t on t oFF

Parameters of relay R1 operation (“rELAy1” menu)

Kind of value controlled relay state FLo

Relay first threshold

Relay second threshold

20.0

30.0

0.0

Hysteresis of relay

Precision of thresholds displaying (while relay is controlled due to batcher counter value)

The unit of thresholds displaying (while relay is controlled due to batcher counter value)

Precision of thresholds and hysteresis displaying

(while relay is controlled due to total flow counter value)

The unit of thresholds and hysteresis displaying

(while relay is controlled due to total flow counter value)

Operation mode of relay

Turn on delay of relay

Turn off delay of relay unit Unit of “t on”, “toFF” parameters of relay

ALArmS Reaction for critical situation of relay

0 unit

0 unit

„in”

0.0 (sec.)

0.0 (sec.)

„SEC”

„oFF”

SourCE

SEt P

SEt P2

HYSt t PrEc

Parameters of relay R2 operation (“rELAy2” menu)

Kind of value controlled relay state FLo

Relay first threshold

Relay second threshold

40.0

50.0

Hysteresis of relay

Precision of thresholds and hysteresis displaying

(while relay is controlled due to total flow counter value)

0.0

0 t unit modE t on t oFF unit

The unit of thresholds and hysteresis displaying

(while relay is controlled due to total flow counter value)

Operation mode of relay

Turn on delay of relay

Turn off delay of relay

Unit of “t on”, “toFF” parameters of relay unit

„in”

0.0 (sec.)

0.0 (sec.)

„SEC”

User's value

Desc.

page

32

33

33

33

33

32

32

32

32

33

34

34

34

33

34

34

34

34

32

32

32

32

32

User manual - FLOW METER SPP-N118

Parameter Description Default value User's value

Ftunit

F or P

Lo CAL

Hi CAL

F coEF

CutoFF

Lo r

Hi r

ALArmS Reaction for critical situation of relay

I tyPE

I CHAr

Point

F unit

„oFF”

Configuration of current flow display (“FLouu” menu)

Input mode „4-20”

LinEAr Conversion characteristic mode

Decimal point position (precision of flow rate displaying)

The unit of volume (Cubic measure) for flow rate displaying

0.0

unit

The unit of time for flow rate displaying

Kind of value visible on the display

Minimum displayed value (for nominal range)

Maximum displayed value (for nominal range)

Flow calculation coeffitient

Cutoff threshold min

„FL vAL”

000.0

100.0

1.000

1.0 (%)

Extension of the bottom of the nominal input range

Extension of the top of the nominal input range

5.0 (%)

5.0 (%)

Configuration of Batcher Counter reset and displaying mode (”bAtCH” menu)

b PrEc b coEF b unit m CLr

A rES

Atunit

A dLy

Decimal point position ( precision of batcher counter displaying)

Batch calculation coeffitient

The unit of batcher counter displaying

0.0

1.000

unit

Manual zeroing of total flow counter

Batcher autoreset function

Time unit of autoreset delay

Batcher autoreset delay oFF oFF

SEC

0

Configuration of Total Flow Counter reset and displaying mode (”totAL” menu)

t PrEc t coEF t unit m CLr

Funct modE

Decimal point position ( precision of total flow counter displaying)

0.000

Total flow calculation coeffitient

The unit of total flow counter displaying

Manual zeroing of total flow counter

1.000

unit oFF

Programmable input configuration („Pr inP” menu)

Programmable input function

Active level/edge of programmable input diSAbL

Power on initialization configuration

HI

Desc.

page

34

38

40

40

40

41

41

41

39

39

39

39

39

40

35

35

35

35

36

37

37

37

35

35

36

36

71

User manual - FLOW METER SPP-N118

72

Parameter Description Default value

Init d Kind of value displayed after device power on FLo vALUE droP

OUtmod Active current output mode

SourCE

OUt LO

OUt HI

Filtering ratio

Configuration of data filtration (”FiLtEr” menu)

0

Measured value change causing of temporal filtering deactivation

10.0 (%)

Active current output configuration (“OUtPUt” menu)

Kind of value controlled active current output

Display value for 0 mA or 4 mA current output

Display value for 20 mA current output

„0-20” (mA)

FLo

000.0

200.0

b PrEc b unit t PrEc t unit

Precision of “OUt LO” and “OUt HI” parameters displaying, while active current output is controlled due to batcher counter value.

The unit of “OUt LO” and “OUt HI” parameters displaying, while active current output is controlled due to batcher counter value.

Precision of “OUt LO” and “OUt HI” parameters displaying, while active current output is controlled due to total flow counter value.

The unit of “OUt LO” and “OUt HI” parameters displaying, while active current output is controlled due to total flow counter value.

Extension of the bottom of the nominal output range

Extension of the top of the nominal output range

Current output value on critical exception

0 unit

0 unit

Lo r

Hi r

AL

5.0 (%)

5.0 (%)

22.1 (mA)

Passive current output configuration (“OUtPUt” menu)

OUtmod Passive current output mode „4-20” (mA)

SourCE

OUt LO

OUt HI b PrEc

Kind of value controlled active current output

Display value for 4 mA current output

Display value for 20 mA current output

Precision of “OUt LO” and “OUt HI” parameters displaying, while active current output is controlled due to batcher counter value.

FLo

000.0

200.0

0 b unit t PrEc

The unit of “OUt LO” and “OUt HI” parameters displaying, while active current output is controlled due to batcher counter value.

Precision of “OUt LO” and “OUt HI” parameters displaying, while active current output is controlled due to total flow counter value.

unit

0

User's value

Desc.

page

42

42

42

42

44

44

44

44

44

45

45

42

44

44

44

45

45

45

44

44

45

User manual - FLOW METER SPP-N118

Parameter Description Default value User's value

modE

PEA timE

HdiS

H r1

H r2

HOUt t unit

Lo r

Hi r

AL

The unit of “OUt LO” and “OUt HI” parameters displaying, while active current output is controlled due to total flow counter value.

Extension of the bottom of the nominal output range

Extension of the top of the nominal output range

Current output value on critical exception unit

5.0 (%)

5.0 (%)

22.1 (mA)

Active voltage output configuration (“OUtPUt” menu)

OUtmod Active voltage output mode

SourCE Kind of value controlled active current output

„0-10” (V)

FLo

OUt LO

OUt HI

000.0

200.0

b PrEc b unit t PrEc t unit

Display value for 0 V, 1 V or 2 V voltage output

Display value for 5 V or 10 V voltage output

Precision of “OUt LO” and “OUt HI” parameters displaying, while active current output is controlled due to batcher counter value.

The unit of “OUt LO” and “OUt HI” parameters displaying, while active current output is controlled due to batcher counter value.

Precision of “OUt LO” and “OUt HI” parameters displaying, while active current output is controlled due to total flow counter value.

The unit of “OUt LO” and “OUt HI” parameters displaying, while active current output is controlled due to total flow counter value.

0 unit

0 unit

Lo r

Hi r

AL briGHt

Extension of the bottom of the nominal output range

Extension of the top of the nominal output range

Voltage output value on critical exception

Display parameters

5.0 (%)

5.0 (%)

11.0 (V)

Display brightness

„bri 6

Configuration of peaks detection function (“HOLd” menu)

Kind of detected changes

Minimum detected change

Maximum time of peak displaying

The type of displayed value

Source of relay R1, and LED R1 control

Source of relay R2, and LED R2 control

Source of current output control

„norm

000.0

0.0

(sec.)

„rEAL”

„rEAL”

„rEAL”

„rEAL”

Settings of access to the configuration parameters (“SECU” menu)

Desc.

page

45

45

45

45

45

45

45

44

44

45

45

46

42

44

44

44

46

47

47

47

47

47

47

73

74

User manual - FLOW METER SPP-N118

Parameter Description Default value

Acc r1

Acc r2

Edit t

Permission to changes of relay R1 threshold without of the user password knowledge

Permission to changes of relay R2 threshold without of the user password knowledge on on

Addr bAud

RS 485 interface configuration (“rS-485” menu)

Device address 0

Baud rate

9600

(b./sec.) mbAccE Permission to changes of configuration registers mbtimE Maximum delay between received messages rESP Additional delay of answer transmission

„on”

0

„Std”

Configuration of numerical parameters edition

Numerical parameters edit mode dig

User's value

Desc.

page

47

47

48

47

48

48

48

48

SIMEX Sp. z o.o.

ul. Wielopole 11

80-556 Gdańsk

Poland