a810 in termounta in hea lt hcarecreeks id e

a810 in termounta in hea lt hcarecreeks id e
1
2
3
4
5
6
8" METAL STUD WALL
MECHANICAL DUCT, SEE MECHANICAL
SHEETS FOR SIZE
5/8" TYPE 'X' GYP. BOARD BOTH SIDES
E
E
VCBO ARCHITECTURE
524 SOUTH 600 EAST
SALT LAKE CITY, UT 84102
Phone: (801) 575-8800
(801) 531-9850
Fax:
WWW: www.vcbo.com
1
1
SCHEDULED QUARTZ QZ1
SCALE: 1 1/2" = 1'-0"
5/8" GYP. BOARD, BOTH SIDES AND
TOP
0'
B2
4' - 0" U.N.O.
5/8" GYP. BOARD, BOTH SIDES AND
TOP
PROVIDE (1) 1 1/4" DIA. OPENING IN
TUBE STEEL FOR ELECTRICAL
CONDUIT, TYP.
5'-0" TO FLOOR
3 1/2"X6"X3/16" PLATE ANCHOR INTO
FLOOR WITH (2) 1/2" DIA. ANCHORS, FULL
PAN WELD AT HSS SUPPORTS
SCHEDULED FLOORING OVER CONCRETE
SLAB
3"X3"X1/4" HSS, FULL HEIGHT OF WALL, AT
ENDS AND MIDPOINT OF WALL, 3/8" BOLTS
@ 6" O.C. VERTICALLY
B2
A810
SEMI-RECESSED FIRE
EXTINGUISHER
CABINET
HAND HELD FIRE
EXTINGUISHER
5'-0" TO FLOOR
3 5/8" METAL STUD FRAMING @ 16" O.C., 1
STUD EACH SIDE OF TUBE STEEL
SCHEDULED METAL
STUD W/ 5/8" GYP.
BOARD BOTH SIDES
AND IN RECESS
SEE MANUFACTURER FOR ROUGH OPENING
4' - 0" U.N.O.
PROVIDE (1) 1 1/4" DIA. OPENING IN
TUBE STEAK FOR ELECTRICAL
CONDUIT, TYP.
CABINET DOOR
6"
1'-0"
1'-6"
COMPOSITE FLOOR DECK OR
STEEL ROOF DECK. REFER TO
STRUCTURAL DRAWINGS
SCHEDULED METAL
STUD W/ 5/8" GYP.
BOARD BOTH SIDES
AND IN RECESS
METAL DEFLECTION TRACK.
GAUGE TO MATCH GAUGE OF
WALL STUD. FASTEN TO DECK
WITH POWDER-DRIVEN
FASTENERS AT COMPOSITE DECK
AND SHEET METAL SCREWS AT
METAL DECK ONLY
RECESSED FIRE
EXTINGUISHER CABINET
HAND HELD FIRE
EXTINGUISHER
ACOUSTICAL INSULATION
IN DECK FLUTES
1/2"
3"X3"X1/4" HSS, FULL HEIGHT OF WALL, AT
ENDS AND MIDPOINT OF WALL, 3/8" BOLTS
@ 6" O.C. VERTICALLY
A810
NOTE:
COORDINATE MODEL
W/ DEPTH OF STUDS
NOTE:
COORDINATE MODEL
W/ DEPTH OF STUDS
1/2"
REVEAL
SEE MANUFACTURER FOR ROUGH OPENING
SCHEDULED QUARTZ QZ1
D
SHAFT DETAIL
E5
REVEAL
CONTINUOUS 16 GAUGE METAL
PLATE
CABINET DOOR
CONTINUOUS 16 GAUGE
METAL PLATE. REFER TO
DETAIL 'A' FOR ATTACHMENT
ACOUSTICAL SEALANT BOTH SIDES
CONTINUOUS
SEALANT AT
PERIMETER
1' - 0"
ATTACH GYPSUM BOARD TO
METAL STUDS AND NOT TO METAL
DEFLECTION TRACK
ACOUSTICAL SEALANT BOTHD
SIDES
METAL RUNNER TRACK NESTED INTO
DEFLECTION TRACK TO MAINTAIN MIN
1 1/2" GAP. GAUGE TO MATCH GAUGE
OF WALL STUDS
3 5/8" METAL STUD FRAMING @ 16" O.C., 1
STUD EACH SIDE OF TUBE STEEL
ACOUSTICAL INSULATION
PARTITION TYPE AS INDICATED ON
THE FLOOR PLANS
STEEL BEAM, SEE
STRUCTURAL DETAILS
WELD TUBE TO FLOOR ANGLE
SEE MANUF.
ACOUSTICAL INSULATION ADDITIONAL
COMPONENT NO X
SEE MANUFACTURER
SEE MANUFACTURER
SEE MANUF.
FOR ROUGH OPENING
FOR ROUGH OPENING
A
FOR R.O.
FOR R.O.
FOR ADDITIONAL SIMILAR NOTES
NOT SHOWN HERE, REFER TO
DETAIL 'A' TO THE LEFT
PERPENDICULAR TO METAL DECK FLUTES
B
PARALLEL TO METAL DECK FLUTES
SCHEDULED BASE, BOTH SIDES
SCHEDULED FLOORING OVER CONCRETE
SLAB
E6
LOW WALL SECTION1
D3
SCALE: 1 1/2" = 1'-0"
FLOOR INFILL AREA
FIRE EXTINGUISHER CABINET
D4
SCALE: 1 1/2" = 1'-0"
0'
6"
1'-0"
FIRE EXTINGUISHER CABINET
NON-RATED ACOUSTICAL PARTITION HEAD DETAILS
D5
SCALE: 1 1/2" = 1'-0"
1'-6"
0'
6"
1'-0"
SCALE: 3" = 1'-0"
1'-6"
0'
6"
1'-0"
1'-6"
0'
1"
3"
6"
9"
CONDUIT OR PIPING
NOTES:
CROSS BRACING
2" MAX.
METAL STUDS AT TYPE
'A' BACKING PLATES
METAL STUDS AT TYPE
'B' BACKING PLATES
SIMILAR TO UL CAJ8101
C
(3) 3/4" #10 LOW PROFILE
PAN HEAD SHEET METAL
SCREWS AT EACH STUD,
TYP.
TYPE 'A' BACKING PLATES:
C1
LOW WALL SECTION
C2
SCALE: 1 1/2" = 1'-0"
CONDUIT PENETRATION DETAIL
C3
SCALE: 3" = 1'-0"
0'
6"
1'-0"
(3) 3/4" #10 LOW PROFILE
PAN HEAD SHEET METAL
SCREWS AT EACH STUD,
TYP.
TYPE 'B' BACKING PLATES:
0'
1"
3"
6"
FOR ADDITIONAL SIMILAR NOTES
NOT SHOWN HERE, REFER TO
DETAIL 'A' TO THE LEFT
PARTITION TYPE AS INDICATED ON
THE FLOOR PLANS
A
BACKING PLATE SCHEDULE
PERPENDICULAR TO METAL DECK FLUTES
B
SCALE: 3" = 1'-0"
9"
0'
SCHEDULED ROOF
1
METAL FURRING @ JOIST WEB
W/ 5/8" GYP. BOARD EACH SIDE
A810
A1
3"X3"X1/4" TUBE STEEL, FULL HEIGHT OF
WALL, AT ENDS AND MIDPOINT OF WALL,
3/8" BOLTS @ 6" O.C. VERTICALLY
A810
STEEL BEAM, PAINTED
WHEN EXPOSED
SCHEDULED CEILING
SYSTEM, SEE CEILING
PLANS
1/2" MAX.
5/8" TYPE 'X' GYP. BOARD
16 GA. METAL TRACK, PAINTED
1"
CONTROL JOINT @
30'-0" MAX SPACING
3 5/8" METAL STUD FRAMING @ 16" O.C.,
1 STUD EACH SIDE OF TUBE STEEL
BATT INSULATION
1"
SCHEDULED WALL
SCALE: 6" = 1'-0"
0'
6"
1'-0"
2"
STUD FRAMED CONTROL JOINT
0'
1"
2"
0'
1"
TO
WHEN DIMENSION
EXCEEDS 3" INSTALL
CRIPPLE STUDS IN
CORNER
4"
1"
3"
6"
0'
1. ALL FIRE DAMPERS TO BE
INSIDE WALL.
2. CUT GYP. BOARD TIGHT TO
DUCT. (MAX. GAP OF 1/4")
SEAL AS REQUIRED.
3. IF DUCT IS TO BE INSULATED,
DO NOT RUN INSULATION
THROUGH WALL. FLARE
INSULATION ONTO FACE OF
WALL AROUND DUCT ON
BOTH SIDES OF WALL AND
SEAL TO FACE OF WALL WITH
INSULATION MASTIC.
DISTANCE TO FIRST
SCREW IN GYP. BOARD
1' - 7 1/2"
CONCRETE FLOOR SLAB - REFER TO
STRUCTURAL DRAWINGS
A3
SCALE: 3" = 1'-0"
TYP. DUCT OPENING IN RATED WALL
SCALE: NOT TO SCALE
6"
9"
B
A5
A810
RECESSED A/V
MOUNTING
BRACKET, SEE
ELECTRICAL
3 5/8" METAL STUD @
EACH SIDE OF
MONITOR BRACKET
NON-RATED PARTITION BASE DETAIL1
1'-6"
0'
1"
3"
6"
1/2"
9"
METAL CORNER
BEAD, TYP.
METAL STUD FRAMING,
SEE SCHEDULED WALL
3 5/8" METAL STUD @ EACH
SIDE OF MONITOR BRACKET
A6
A810
2
A5
SCALE: 3" = 1'-0"
3
RECESSED A/V
MOUNTING
BRACKET, SEE
ELECTRICAL
0'
1"
3"
6"
3 5/8" METAL STUD
FRAMED WALLS
A
1/2"
5/8" TYPE 'X' GYPSUM
WALLBOARD (TYP.)
5/8" GYPSUM WALLBOARD
3 5/8" METAL STUD
FRAMED WALLS
9"
Job # 13375
CAD File
Drawn Author Checked Checker
Date OCTOBER 28, 2013
Owner #
Ins. #
TYPICAL INTERIOR
FRAMING DETAILS
SCHEDULED BASE
SOUND BATT INSULATION
DIGITAL SIGN DISPLAY MOUNT PLAN
SCALE: 1 1/2" = 1'-0"
4
Description
ADDENDUM 01
EDGE OF WALL (BEYOND)
METAL STUD FRAMING, SEE
SCHEDULED WALL
TYPICAL ELECTRICAL DEVICE DETAIL
Date
11.01.13
MONITOR, SEE ELECTRICAL
PLANS FOR SIZE
5/8" TYPE 'X' GYPSUM
BOARD (TYP.)
NOTE:
ILLUSTRATION DOES NOT SHOW
WALL FINISHES, TILE, PLASTIC
LAMINATE, OR OTHER FINISHES
A4
Rev #
1
VINYL WALL GRAPHIC
TO WRAP WALL
FIRE SAFING MATERIALS
PARTITION SLIP JOINT TYPICAL
3"
1'-0"
LOCATE 'J' BOXES ON OPPOSITE
SIDES OF STUD AND FILL CAVITIES
W/ BATT INSULATION TO PREVENT
SOUND TRANSMISSION
SIMILAR TO UL CAJ8101
1"
6"
ISOLATE BACK-TO-BACK 'J' BOXES
W/ 1 1/2" X 16" X CONT. POLYISO
RIGID INSULATION BOARD TO
PREVENT SOUND TRANSMISSION
METAL STUDS
0'
EDGE OF WALL
(BEYOND)
SCALE: 3" = 1'-0"
9"
NOTES:
2"
DO NOT OVER TIGHTEN SCREWS,
GENERAL CONTRACTOR TO ENSURE
TOP CHANNEL SLIPPAGE
1
B5
FOR STEEL STUD WALLS USE
FC-8019 1 HR. APPLICATION
5/8" GYP. BOARD ON
METAL STUD, DO NOT
FASTEN INTO TOP
CHANNEL
A1
9"
METAL CORNER
BEAD, TYP.
18 GA. METAL SLOTTED
OVERSIZED CHANNEL
11/6/2013 2:16:23 PM
WALL"Y" BRACING DETAIL1
SCALE: 1 1/2" = 1'-0"
4"
METAL DECK
A
B4
SCALE: 3" = 1'-0"
1'-6"
FIRE SAFING REQUIRED
AT ALL RATED WALLS,
FILL IN DECK FLUTES,
SOUND BATT
INSULATION AT ALL
OTHERS
3"
NOTE:
FIRE SEAL STUD
WALL AROUND STEEL
JOISTS AND BEAMS
B3
6"
SCALE: 1 1/2" = 1'-0"
LOW WALL REINFORCEMENT
1' - 0"
B2
1' - 0"
SLIP JOINT AT BEAM / JOIST
6"
B1
ACOUSTIC SEALANT FULL DEPTH OF
GYPSUM BOARD. BOTH SIDES OF WALL
AT OPEN WEB JOIST
3' - 0" (VERIFY W/MONITOR)
AT STEEL BEAM
SCHEDULED WALL
1 HOUR
OR NON-RATED
3/4"
METAL RUNNER TRACK. ATTACH TO
DECK WITH POWDER-DRIVEN
FASTENERS AT 24" OC AND 2" FROM
EACH END
1' - 7 1/2"
B
6"
A1
ACOUSTIC INSULATION AS REQUIRED
BY PARTITION TYPE
3 5/8" 22 GA. STUD
DIAGONAL BRACING @ 48"
O.C. STAGGERED. ANGLED
APPROXIMATELY 45° FROM
TOP OF WALL
45.0
0°
R-13 BATT INSULATION BOTH
SIDES OF JOIST/BEAM
5/8" GAP
SEE WALL TYPE
3 1/2"X6"X3/16" PLATE, ANCHOR INTO
FLOOR WITH (2) 1/2" DIA. OFFSET
ANCHORS, FULL PAN WELD AT TUBE
STEEL SUPPORTS
OPEN WEB STEEL JOIST
6"
MONITOR, SEE
ELECTRICAL PLANS
FOR SIZE.
FOR PARTITION TYPE
3' - 3" (VERIFY W/MONITOR)
3 5/8" METAL STUD FRAMING @ CORNER
3"
SEE FLOOR PLAN
1 5/8" TYPE 'S' SCREWS
@ 24" O.C.
SCHEDULED STEEL STUD
1/4" MIN - 1/2" MAX
METAL CORNER BEAD, TYP. OVER
5/8" GYP. BOARD
1"
WALL EXTENDS TO
METAL DECK
FLOOR OR ROOF
STRUCTURE
FIRE SAFING @ DECK FLUTES @
FIRE RATED WALLS, SOUND
BATT INSULATION AT ALL OTHER
LOCATIONS
PARALLEL TO METAL DECK FLUTES
NON-RATED PARTITION HEAD DETAILS1
C5
SCALE: NOT TO SCALE
1'-6"
C
METAL RUNNER TRACK NESTED
INTO DEFLECTION TRACK TO
MAINTAIN MIN 1 1/2" GAP. GAUGE TO
MATCH GAUGE OF WALL STUDS
TYPE 'B' BACKING PLATE SHALL SUPPORT THE SAME ITEMS AS TYPE 'A'
BACKING PLATE BUT USE WHERE APPEARANCE IS THE MAIN CONCERN
SUCH AS LOBBIES AND OTHER HIGH DESIGN AREAS.
- AT DOOR STOPS AND BUMPER RAILS
- AT TOILET ACCESSORIES, MIRRORS, COAT HOOKS, ETC.
- AT ALL UPPER WALL HUNG CABINETS
- AT ALL BASE CABINETS
- AT ALL FULL HEIGHT CABINETS
- AT WALL MOUNTED ADJUSTABLE SHELVING
- AT ALL WALL MOUNTED HANDRAILS
PACK WITH FIRE
SAFING MATERIALS
AND FIRE CAULK
CONTINUOUS 16 GA. METAL
PLATE. REFER TO DETAIL 'A' FOR
ATTACHMENT
ATTACH GYPSUM BOARD TO
METAL STUDS AND NOT TO METAL
DEFLECTION TRACK
5' - 0"
6"
METAL STUDS
BEHIND GYP.
BOARD
NOTCH STUD RETURN TO
ALLOW PLATE TO PASS
INSIDE STUD FLANGE
METAL DEFLECTION TRACK.
GAUGE TO MATCH GAUGE OF
WALL STUD. FASTEN TO DECK
WITH POWDER-DRIVEN
FASTENERS AT COMPOSITE
DECK AND SHEET METAL
SCREWS AT METAL DECK ONLY
2" MAX
3' - 0"
1. CUT GYP. BOARD TIGHT TO
DUCT. (MAX. GAP OF 1/4")
SEAL AS REQUIRED.
2. THROUGH CONCRETE WALLS
USE W-J-1116.
3. THROUGH GYP. BOARD WALL
USE W-L-1018.
COMPOSITE FLOOR DECK OR
STEEL ROOF DECK. REFER TO
STRUCTURAL DRAWINGS
TYPE 'B' BACKING PLATE:
16 GAUGE X 6" HIGH BENT METAL
PLATE ATTACHED TO WEB PORTION
OF METAL STUDS
TYPE 'B' BACKING PLATE
TYPE 'A' BACKING PLATE:
16 GAUGE X 6" HIGH
CONTINUOUS METAL PLATE
3930 WEST PARKWAY BLVD. WEST VALLEY, UTAH
CONSTRUCTION DOCUMENTS - BID SET
TYPE 'A' BACKING PLATE
INTERMOUNTAIN HEALTHCARE
WIDE FLANGE BEAM
INTERMOUNTAIN HEALTHCARE CREEKSIDE
PROVIDE BACKING PLATES AS INDICATED ON THE DRAWINGS OR WHERE NOT INDICATED, ACCORDING TO THE FOLLOWING SCHEDULE. REFER TO DETAILS ELSEWHERE IN THE SET OF DRAWINGS
FOR THE SUPPORT OF WALL MOUNTED ITEMS IN EXCESS OF 200 POUNDS
A6
DIGITAL SIGN DISPLAY MOUNT SECTION
SCALE: 1 1/2" = 1'-0"
5
6
A810