transmittal - Log into PIX (Phipps Information Exchange)

transmittal - Log into PIX (Phipps Information Exchange)
TRANSMITTAL
5995 Greenwood Plaza Blvd.
Suite 100
Greenwood Village, CO 80111-4710
303-571-5377
303-629-7467 (fax)
PROJECT:
TO:
ATTN:
No. 16J2060-0272
DATE: 03/27/2017
JCSD-Sierra Elementary Addition and Remodel
MOA Architectural
821 17th St Ste 400
Denver CO 80202
RE:
11 52 13-Default Submittal
Package Name 11 52 13
11 52 13 - 01
Jessica Blanford
JOB:
Ph/Fax:
WE ARE SENDING:
SUBMITTED FOR:
16J2060
ACTION TAKEN:
Shop Drawings
Approval
Approved as Submitted
Letter
Your Use
Approved as Noted
Prints
As Requested
Returned After Loan
Change Order
Review and Comment
Resubmit
Submit
Plans
SENT VIA:
Samples
Returned
Specifications / Product Data
Attached
Returned for Corrections
Other:
Separate Cover Via:
Due Date: 04/11/2017
NOTES:
Item
Package
Code
Submittal
11 52 13
11 52 13-01
Rev. Copies Date
1
1
03/27/2017
Description
Status
Projection Screens - Product Data
Architect Review
CC:
Signed:
Brian Hunsicker
Submittal Stamp Sheet
Project ID# : 16F40500A01
GH Phipps Job # : 16J2060
GH Phipps Submittal # : 11 52 13 - 01
Gerald H. Phipps, Inc.:
MOA Architecture
821 17th Street, Suite 400
Denver, CO - 80202
Architect:
SUBMITTED
GH Phipps
Construction Companies
GH Phipps has reviewed and herby submits
the attached in accordance with the Contract
Documents.
Note to Subcontractor/Material Supplier:
Subcontractor/Material Supplier remains
responsible for the confirmation and
correlation of dimensions at the jobsite;
fabrication processes and construction
techniques; coordination of the work with
the work of other trades; and satisfactory
performance of the work.
Engineer:
MOA - Jessica Blanford
jessica.blanford
03/30/2017
Other:
Based on the 120V, requirements identified
on page 3 of 13 in this document,
WE TAKE NO EXCEPTION to the electrical
requirements.
Ackerman Engineering, Inc. Don J Ackerman
Jan 29, 2017
NOTES:
Signed:
GH Phipps Representative
VCB Access/Series E
Ceiling recess case now.
Install background/roller
assembly later at job site by
Specifications—VCB Access/Series E
video conferencing backgrounds, size _______________________ h.
x _____________________ w., recessed ceiling mounting. Case back, top, and
front constructed of steel. Endcaps are steel. Bottom panel forms slot for passage of
viewing surface, easily removable for access. Symmetrical housing to allow for left
or right-hand motor location, and for viewing surface to unroll from the back or front
of the roller. Case to include bottom flange for trim around edges of ceiling opening.
Case may be mounted with 3/8" threaded rod, with lag screws through brackets, or
with wire in a grid ceiling. Mounting brackets slide in 18" long channels on top of
case, allowing brackets to be moved to avoid interference with conflicting building
structures. Brackets may be locked in position by tightening screws. Brackets may
also be angled to meet installation requirements.
Roller/background assembly may be installed in case at factory or job site.
Brackets supporting roller/background assembly to slide in track inside top of
case, allowing viewing surface to be centered in case regardless of size. Roller
of 3" (76 mm) dia. metal. Electrically operated 110-120V AC, 60 Hz. 3-wire
motor mounted inside screen roller, 1.1 amp current draw, instantly reversible,
lifetime lubricated, with internal thermal overload protector and electric brake,
standard motor with preset accessible switches. Optional Quiet Motor operates
at 44 Db (motor noise is approximately 30% less than standard tubular motors).
Housing to feature internal junction box, allowing it to be installed and wired
to building supply wires at an early stage of construction. Junction box to have
plug-in style connector, accepting the mating half of the connector from the
motorized roller/background assembly. 3-position control switch (or switches—
specify number) to stop or reverse unit at any point. Switch(es) furnished with
coverplate. Patented by Draper, Inc. (U.S. Patent Nos. 6,137,629; 6,421,175;
6,532,109; 6,816,308; 7,559,707).
Entire unit certified by Underwriters’ Laboratories for the U.S. and Canada.
Plenum rated case (UL approved “Suitable for Use in Environmental Air
Space”).
Specifications subject to change without notice.
Dimensions and Data
Size
H xW
(inches)
108" x 144"
144" x 144"
132" x 168"
168" x 168"
144" x 192"
Size
H x W
(cm)
274 x 366
366 x 366
335 x 427
427 x 427
366 x 488
Case
Length
(inches)
158"
158"
158"
182"
206"
Case Net Net
Length Weight Weight
(cm) (lbs) (kg) Qty
401
108
49
401
119
54
401
196
89
462
202
92
523
235
107
Custom Size
Please Mark Appropriate Selections
Select Shipping Option:
Case Now, Screen Assembly Later 1
Complete Unit Now
Coordinate with Andy Wildeman
(GHP - Superintendent)
303-901-8241
Select Background:
Printed (You will be required to provide additional information, including
artwork, properly sized and 150 dpi. Please contact Draper)
Neutral
Reef
Glacier
Beach
Savannah
Desert
Tundra
Chroma Key
Standard is acceptable.
Blue
MOA - Please Advise
See notes from EEI.
Green
Select Motor and Controls:
Standard Voltage Motor and Control Options:
110-120V AC (standard)
Optional Quiet Motor 2
Please Note: These motors come with one 110V-120V AC 3-position wall
switch (silver wall plate with black rocker)
1
Total number of 110-120V AC switches (operate independently)
Substitute white switch(es) for silver wall plate with black rocker
Optional Key Operated Switch
Power Supply Key Switch (On-off)
3-Position Key Control
3-Position Switch with Hinged Key-Locking Coverplate
Low Voltage Motor and Control Options:
Optional External LVC-IV Low Voltage Control Module
Optional Motor with Built-in Low Voltage Controller 1, 3
Optional Quiet Motor 2 with Built-in Low Voltage Controller 1, 3
Please Note: Select Control Options for Low Voltage from below.
24 Volt 3-Button Switch Number of 24V switches: ___________
Radio Frequency Remote Control (only with 24v)
Infrared Remote Control (only with 24v)
Optional Key Operated Switch
Power Supply Key Switch (On-off)
3-Position Switch with Hinged Key-Locking Coverplate
Select Motor Location:
Left end (standard)
Right end
Optional Accessories:
Additional set of mounting brackets for alternate mounting (see page 2)
1 Please
note: When ordering a motor with built-in Low Voltage Controller, if the case ships
separate from the "guts," the case includes the 25' cable and special low voltage switch.
120" H x 144" W
3
Quiet Motor with Built-inLow Voltage Controller Size Limitations
AV
AV
NTSCNTSC HDTVHDTV 16:1016:10
(inches) (cm) (inches)(cm) (inches)(cm) (inches)(cm)
108" x 144" 274 x 366
180"
457
184"
467
165" 419
2
Quiet Motor Size Limitations
AV
AV
NTSCNTSC HDTVHDTV 16:1016:10
(inches) (cm) (inches)(cm) (inches)(cm) (inches)(cm)
144" x 144" 366 x 366
200"
508
184"
467
189" 480
PROJECT:
ARCHITECT:
CONTRACTOR:
SUPPLIER:
Copyright © 2016 Draper Inc. Form VCBAccessE_Sub16 Printed in U.S.A.
DATE:
REVISED:
VCB Access/Series E by Draper
Page 2 of 2
Case Dimensions and Methods of Installation
91/8”
½”
7
11/8”
73/8”
7
5
2”
18”
/16”
/8”
/8”
7
67/8”
8”
613/16”
LEVELING BRACKET**
13/8”TYP
Center
of Case
/8”
4¾”
L*
11
5
18”
¾”
/8”
6½”
81/16”
L*
/16”
/16”
11
*L = Varies
For ceiling cutout subtract 1¼" from case length and width (measured from outer edge of flanges).
*There are several knock-outs in the screen housing to allow the Leveling Bracket to be adjusted laterally (up to 16" in either direction)
7
7
Mounting Bracket Dimensions
/"
8
ELECTRICAL
CUTOUT
7
/"
8
ELECTRICAL
CUTOUT
/16"
1
1
13/8"
R 3/16"
/2" 17/8"
1
/2"
/8" R /4"
1
/4"
1
TYP.
9
213/16"
/16"
TYP.
Alternate
Installation
(additional set of
brackets required
but not included)
Typical
Installation1
17/8"
/4 "
1
9
TYP.
/16"
TYP.
33/8"
7 7/8"
9 1/8"
With typical installation, brackets may be angled to meet installation requirements.
1
Wiring Diagrams2
11mm
110-120V Motor
110-120V Motor and Quiet Motor
110-120V Quiet Motor
Multiple Station Control
Single Station Control
Internal Screen Wiring
White (Common)
Black (Down)
Red (Up)
Internal Screen Wiring
White (Common)
Black (Down)
Red (Up)
Green (Ground)
Green (Ground)
Red
Blue
Single gang box by others
Min. 4" x 2 1/8" x 1 7/8" deep
Red
Black
Internal Screen Wiring
White (Neutral)
Black
Green/Yellow (Ground)
Dashed wiring
by electrician
Single gang box by others
Min. 4" x 2 1/8" x 1 7/8" deep.
3 shown. More or less equally
feasible.
Black
Location of key
operated on-off
switch if furnished
Data Cable
Data
Cables
RJ-9
connectors
To 110-120V Line
To 110-120V Line
For external low voltage (LVC-IV), serial (LVC-IV) and network (LVC-IV) wiring
diagrams, please consult instructions for those modules.
SUPPLIER:
DATE:
www.draperinc.com
Wall Switches,
RF or IR
Receivers,
or integrated
control systems
For more information and wiring diagrams for serial and network
communication, please see wiring diagrams supplied with individual items.
2
PROJECT:
To 110-120V Line
Black
Green/Yellow (Ground)
Dashed wiring
by electrician
Wall Switch,
RF or IR
Receiver,
or integrated
control system
Blue
Red
86mm
200mm
RJ-9
connector
Black
To 110-120V Line
Internal Screen Wiring
White (Neutral)
232mm
Blue
Location of key
operated on-off
switch if furnished
47mm
R 3mm
Dashed wiring
by electrician
Black
R 4mm
13mm
110-120V Quiet 6mm
Motor with Internal Low72mm
Voltage Controller 6mm
Single Low Voltage Control 14mm
Multiple Low
Voltage Controls
14mm
Blue
Red
Please Note:
47mm
110-120V
Motor and Quiet Motor
R 6mm
110-120V
Motor
with Internal Low Voltage Controller
3mm
35mm
(Internal Low Voltage Controller)
Cap off with wire
nut and tape
Dashed wiring
by electrician
Control
switch
Mounting Bracket Dimensions
13mm
(765) 987-7999
REVISED:
Installation/Operating Instructions
Ultimate Access Series E & V Electric Projection Screen by Draper
Electrical Connections
Caution
1 Read instructions through completely before proceeding.
2 Follow instructions carefully. Installation contrary to instructions
invalidates warranty.
3 Entire bottom of screen case should be unobstructed to permit
access to bottom panel for electrical connections or servicing.
4 Screen should be installed level (using a carpenter’s level).
5 Nothing should be fastened to screen dowel or viewing surface.
6 Operating switch(es) and mounting brackets are packed separately
in screen carton. Do not discard with packing material.
7 Screen operates on 110-120V, 60 Hz. AC, 1.1 amp current draw.
NOTE: Screen has been thoroughly inspected and tested at factory
and found to be operating properly prior to shipment.
These instructions are meant as a guide only. They do not imply any responsibility on the
part of the manufacturer for improper installation or faulty workmanship at the jobsite.
Hanging Screen
When locating viewing surface and checking clearance for screen operation,
remember surface is centered in the length of the case. Regardless of
mounting method used, the following points apply:
1 Mounting brackets are shipped attached to the case. Engage each bracket
with top of housing as shown below and tighten set screws (see fig 1).
2 Screen should be positively and securely supported so that vibration or
even abusive pulling on viewing surface will not weaken installation.
Please Note: A Hoisting Bracket is included on each end of the case to
aid in overhead installation of the Ultimate Access case.
Figure
HOISTING
BRACKET
HOISTING
BRACKET
CASE
MOUNTING
BRACKET
CASE
MOUNTING
BRACKET
7
/”
8
ELECTRICAL
CUTOUT
With typical installation, brackets may be angled to meet installation requirements.
3 Installer must insure that fasteners used are of adequate strength and
suitable for the mounting surface chosen. Supporting hardware (chains,
cables, 3/8" rods, etc.) must be essentially vertical.
Screen operates on 110-120V, 60 Hz., 1.1 amp current draw.
Junction box is located just above the bottom access panel at the left end of
the screen.
Open the access panel/trap door for access to the junction box cover. (See
bottom access panel/trap door opening and closing instructions below).
Remove two (2) hex head screws that secure the cover to the junction box to
expose the red, black, and white pigtail leads and the green ground wire per
wiring diagram on page 3.
If optional low voltage control or video interface control is specified and factory
installed, please refer to wiring diagrams on page 4.
Screen is shipped with internal wiring complete and control switch(es) fully
boxed. Wire to connect screen to switch(es) and switch(es) to power supply
should be furnished by installer. Connections should be made in accordance
with attached wiring diagram, and wiring should comply with national and
local electrical codes.
All operating switches should be “off” before power is connected.
Bottom Access Panel/Trap Door Opening & Closing
Figure
A spring latch near the center
of the case and at each end ACCESS DOOR
SE
of the trap door holds this
SUPPORT
CARIOR
BRACKET
assembly closed. The center
TE
IN
latch must be disengaged first.
E
ID
OR
To gain access to inside of screen
SL
DOon)
AP iti
case, disengage spring latch at
TR pos
p
(u
center, followed by the latches at
each end. To disengage, slide the
latch lever towards the center of
screen case (see Fig. 2), then pull
ACCESS
DOOR
down slightly on the trap door assembly.
LATCH
The latch levers are somewhat concealed
from view. Locate these with the trap door
open by feeling for the vertical latch lever above the door about 3" from case
endcaps and near the center of the case.
The assembly will swing down, opening about 135°. Pivot the prop arms at
each end of the trap door assembly towards the ends of screen case. Prop
arms engage with a hole in each endcap to hold the trap door assembly fully
open. To close the trap door assembly disengage prop arms from endcaps
and pivot these over the access panel. Swing the trap door assembly upward,
stopping just before the latch levers hit the bottom flanges of the endcaps
(and center of case where appropriate). Pull levers of latches towards center
of screen case to allow the trap door assembly to be pivoted to its closed
position. Make sure that the spring latch levers engage fully with case
endcaps (and center of case where appropriate).
4 Entire bottom of case must be readily accessible after installation is complete.
5 Front, back and top of case must be straight—not forced to warp or bow.
Figure
6 If case is painted on location, slot on bottom of case should be shielded to
protect viewing surface from paint splatters/overspray.
7 Do not seal unit in ceiling until electricalconnections have been made and
screen has been operated successfully.
Suitable for use in environmental air space in accordance with Section
300-22(c) of the National Electrical Code, and Sections 2-128, 12-010(3)
and 12-100 of the Canadian Electrical Code, Part 1, CSA C22.1.
Caution: Beware of pinch
points along closure
Copyright © 2016 Draper Inc. Form UltimateAccess_Inst16
Printed in U.S.A.
If you encounter any difficulties installing or servicing your Ultimate Access screen, call
your dealer or Draper, Inc., in Spiceland, Indiana, 765/987-7999 or fax 765/987-7142.
Ultimate Access Series E & V by Draper
Motorized Roller/Fabric Installation
Figure
1 The bottom access panel and trap door must be removed first.
Idler end roller
2 The motor end mounting bracket has a metal bracket
mounting bracket
with snap ring for accepting motor head. Back out the
two set screws in bracket until they are flush with top Washer
side of bracket.
3 To engage the motor end bracket flange above the
two channels in the top of the screen housing, rotate
the bracket approximately 45° counterclockwise to
allow the top surface of the motor bracket to rest flat Retaining
Clip
against the top inside of the housing.
4 Rotating the bracket clockwise until it is engaged with
Roller Assembly
the channels, slide it along the length of the housing
against the electrical junction box.
Motor End
Set Screws
Mounting
5 Engage idler end bracket (rectangular
Bracket
mounting pad) in the same manner as
motor end bracket and slide it toward the
opposite end of the screen housing.
Motor End
Retaining Clip
Do not tighten set screws on this bracket
until the roller/fabric assembly is
Figure
installed, and centered in case.
Note: Step 6 requires two people to perform safely.
6 Locate the black washer and retaining clips attached to the instruction sheet.
Raise the roller/fabric assembly up into the screen housing and engage the
head of the motor completely into the motor mounting
bracket, making sure the limit switch adjusting knobs are
visible from the bottom of the screen housing (see fig. 6).
If snap ring is provided, make sure the snap ring engages with
the motor. If retaining clip is provided instead, install to lock
motor end in place.
7 While supporting the idler end of the roller, slide the idler end
mounting bracket toward the roller. Insert the roller pin into the
nylon bushing on the idler end mounting bracket.
8 The roller idler pin needs to go through the idler bracket far
enough to allow the washer and retaining clip to be reinstalled
on the pin.
CAUTION: Failure to replace the washer and retaining clip could
result in the separation of the roller from the brackets.
Figure
9 The roller/fabric assembly and roller brackets may need to be slid left or right in
the mounting channel of case to center fabric within screen case.
10 Securely tighten the set screws on roller mounting brackets.
11 Connect the electrical plug from the motor to the mating socket on the junction box.
12 Reinstall the bottom access panel as previously described.
Motorized Roller/Fabric Removal
Reverse the instructions above “Motorized Roller/Fabric Installation” for removal of
the unit.
Operation
CAUTION: Always be prepared to shut screen off manually when new
adjustment is being tested. Screen may be severely damaged if viewing
surface is allowed to run too far up or too far down.
CAUTION: Be sure all switches are in “off” position before adjusting
limit switches.
The motor limit screws are normally located on the audience left of screen roller.
"DOWN" LIMIT ADJUSTMENT
To Reduce Screen Drop
1 Raise screen surface about 1' above desired setting and turn off.
2 Turn the WHITE/DOWN limit screw clockwise (three screw turns = ½ roller
revolution).
3 Test by running screen down and repeat steps 1 and 2 until desired position
is reached.
To Increase Screen Drop
1 Run screen to the down limit.
2 With the down switch on, turn the WHITE/DOWN limit screw counterclockwise (3 turns of screw equals ½ roller revolution) to increase drop.
3 Test by running screen up about 1' and back down to new down limit.
4 Repeat steps 2 and 3 until desired position is reached.
"UP" LIMIT ADJUSTMENT
Screen is Running Too Far Up
1 Lower screen surface about 1' below desired setting and turn off.
2 Turn the YELLOW/UP limit screw clockwise (three screw turns = ½ roller
revolution).
3 Test by running screen up.
4 Repeat steps 1 through 3 until desired position is reached.
Screen Needs to Run Up More
1 Run screen down about 1' and turn off.
2 With the up switch on, turn the YELLOW/UP limit screw counterclockwise
(three turns of screw = ½ roller revolution).
3 Repeat steps 1 and 2 until desired position is reached.
CAUTION: Do NOT allow the dowel to wrap up over the roller when
the screen is running up! This could damage the screen.
Tab-Tension Adjustment Procedure for Ultimate Access/Series V
Draper’s Tab-Tensioning System is factory-set, and under normal circumstances
will not require field adjustment. If, however, you notice wrinkles, waves or other
indications that the tensioning cables need to be adjusted, follow the procedure below.
1 Determine which side requires adjustment.
2 Secure dowel with one hand.
3 Using Phillips-head screwdriver, depress spring-loaded adjustment screw
and slowly turn CLOCKWISE TO INCREASE tension, or
COUNTER-CLOCKWISE TO RELEASE tension. The screw adjusts in
60° turn increments. Adjust only one increment (60° turn) at a time.
TENSIONING
CABLE
TENSIONING
CABLE
Figure
ADJUSTMENT
SCREW
TO
IN C
ADJUSTMENT
SCREW
REASE TE
O
RN
IS E
TU
KW
URN
E
DOWEL
4 If problem is not corrected, leave screen in position for 24 hours to allow
surface material to stretch into position.
5 If problem still is not corrected, repeat steps 2 and 3.
(765) 987-7999
N
IS
DOWEL
LEASE T
R E N T E R- C E N S
LO I
TO CO U
C
N
CLOCKW S
NT
www.draperinc.com
Limit Adjustments
Please Note: Screen limits are factory set for optimum performance of
the screen. A procedure is outlined below for minor tweaks, but any
adjustment of these limits may negatively affect the flatness of the
screen surface and could also void the warranty. Please check with
Draper prior to resetting screen limits.
IO
When screen is first operated, be cautious! Cycle unit down and up several times
to confirm satisfactory operation. Be prepared to cut POWER if necessary.
110-120V SINGLE STATION CONTROL—3-position UP-OFF-DOWN switch
permits operation to be stopped at any point. Factory adjusted limit switches
automatically stop screen when fully down or fully up.
110-120V MULTIPLE STATION CONTROL—Switches are similar in appearance
to 110-120V Single Station Control. Screen stops when switch is released and
may be restarted in either direction. Factory adjusted limit switches stop screen
automatically when fully up or fully down.
24V CONTROL—Three-button UP-STOP-DOWN switches stop at any point
desired, operate in any sequence. Factory adjusted limit switches automatically
stop screen when fully up or fully down. Installer should incorporate an all-pole
disconnect in the fixed wiring available with RF or IR remote.
110-120V & 12V VIDEO INTERFACE CONTROL—Allows screen to be controlled
by trigger signal—when the signal comes on, the screen descends automatically.
Two versions: Model VIC115 integrates screen operation with a Draper video
projector lift or a video projector or tuner with a 110-120V switched outlet. Model
VIC12 interfaces with a 12V switched outlet. Both available with an override switch
(VIC–OS), permitting independent operation. VIC–OS not available with factory
installed VIC115 & VIC12.
KEY OPERATED SWITCHING—Two kinds of key-operated switches are
optionally available with this unit. 1 The key-operated power supply switch controls
power to the screen and switches. When it is “off”, the switches will not operate
screen. Key may be removed from the switch in either “on” or “off” position.
2 A three-position key switch permits the screen to be operated directly by key.
In this case, the screen’s operator must always have a key.
RS232/ETHERNET—Serial communication and network communication optionally
available with wall switches, RF or IR remote.
Page 2 of 4
Ultimate Access Series E & V by Draper
Page 3 of 4
Case Dimensions
91/8”
211/16”
OVERALL CASE LENGTH
91/8”
211/16”
2”
OVERALL CASE LENGTH
2”
18”
18”
2”
2”
1
n
n1
11//88””
n5/8” n /8”
n7/88””
n
5
7
7
9 /8” 9 /8”
7
7 /8”
3
977/16”
9 /16”
73/8”
31/8”
31/8”
25/8”
25/8”
6¾”
6¾”
73/8”
73/8”8”
¾”
¾”
¾”
Series E
Viewing Surface
Varies
Varies
8”
Series V
Viewing Surface
Series E
Viewing Surface
Series V
Viewing Surface
For ceiling cutout subtract ½" from case length and width (measured from outer edge of flanges).
INTERNAL SCREEN WIRING
Internal LVC-IV - Single or Multiple
Projection Screen Wiring Diagram
Green/Yellow
(Motor Ground)
Green/Yellow (Ground)
Red (Up)
Black (Down)
White (Common)
Receiver
Button
Red-to screen (directional)
Brown-to screen (directional)
White -Common to screen & 110V-220V AC Neutral
FUSE - 3.15 AMP
250 VAC 5x20mm
Yellow-to 110V-220V AC-Hot
Black-to 110V-220V AC-Hot
GND
N
Location of key
operated on-off
switch if furnished.
To
110-120 VAC L1
Line
3 Button Wall Switch
DOWN - Black
COM - White
UP - Red
Electrically Straight
Data Cable to more
LVC-IV modules*
RS232/485
Inputs/Outputs
Wall Switch
IR Eye Input
*A maximum of six (6)
LVC-IV modules can be
linked together.
Low Voltage
Trigger
3-28 VDC
Dashed wiring by electrician
Low voltage wiring by others
External LVC-IV - Single or Multiple
Projection Screen Wiring Diagram
INTERNAL SCREEN WIRING
White (Common)
Red (Up)
Black (Down)
Green/Yellow
(Motor Ground)
To
110-120 VAC L1
Line
GND
Receiver
Button
Red-to screen (directional)
Brown-to screen (directional)
Yellow-to 110V-220V AC-Hot
Black-to 110V-220V AC-Hot
White -Common to screen & 110V-220V AC Neutral
Green/Yellow (Ground)
FUSE - 3.15 AMP
250 VAC 5x20mm
TO: MOTOR LEADS
TO: MOTOR LEADS
Standard Wiring Diagrams
Location of key
operated on-off
switch if furnished.
N
3 Button Wall Switch
DOWN - Black
COM - White
UP - Red
Electrically Straight
Data Cable to more
LVC-IV modules*
RS232/485
Inputs/Outputs
IR Eye Input
Low Voltage
Trigger
3-28 VDC
Dashed wiring by electrician
Low voltage wiring by others
www.draperinc.com
(765) 987-7999
Wall Switch
*A maximum of six (6)
LVC-IV modules can
be linked together.
Ultimate Access Series E & V by Draper
Page 4 of 4
Wiring Diagrams with Built-In Controls
Multiple Station Control
Single Station Control
Multiple Station Control
Single Station Control
Internal Screen Wiring
White (Common)
Black (Down)
Red (Up)
Internal Screen Wiring
White (Common)
Black (Down)
Red (Up)
Green (Ground)
Green (Ground)
Blue
Control
switch
Control
Single gang box by others
switch
Min. 4" x 2 1/8" x 1 7Blue
/8" deep
Red
Red
Single gang box by others
Min. 4" x 2 1/8Red
" x 1 7/8" deep Blue
Red
Black
Dashed wiring
by electrician
Red
Black
Red
Blue
Dashed wiring
by electrician
Black
Blue
Blue
Location of key
operated on-off
Black
Black
switch if furnished
Please Note:
Do not wire
To 110-120V
motors
in Line
parallel.
To 110-120V Line
Cap off with wire
nut and tape
Cap off with wire
nut and tape
Black
Location of key
operated on-off
switch if furnished
Green (Ground)
Green (Ground)
Dashed wiring
by electrician
Dashed wiring
by electrician
Internal Screen Wiring
White (Common)
Black (Down)
Red (Up)
Internal Screen Wiring
White (Common)
Black (Down)
Red (Up)
Blue
Red
Black
Location of key
operated on-off
switch if furnished
Blue
Red
Black
Single gang box by others
Min. 4" x 2 1/8" x 1 7/8" deep.
3 shown. More or less equally
feasible.
Location of key
operated on-off
switch if furnished
Single gang box by others
Min. 4" x 2 1/8" x 1 7/8" deep.
3 shown. More or less equally
feasible.
To 110-120V Line
To 110-120V Line
Built-In VIC-12*
Built-In VIC-115*
115 Volt Relay
12 Volt Relay
Ring Terminal on each Ground Wire
with Star Washer screwed to Spine
Wire soldered to terminal
Wire connected with Quick Disconnect
www.draperinc.com
Red
(765) 987-7999
3
1
Black
Green
Red
Black
White
Ground
#2 Up
#1 Down
Common
110-120 VAC
Screen Motor
Jacketed Motor Cable
White
Green
Black
HSG. Cap
Green
HSG. Plug
: : ::
7
5
White Lead
HSG. Cap
HSG. Plug
:: : :
Black Lead
Black
110-120 VAC
Screen Motor
Jacketed Motor Cable
White
Green
Orange (+)
Brown (-)
White
6
4
2
: : ::
Black
Ground
#2 Up
#1 Down
Common
: : ::
Red
Green
Red
Black
: : ::
8
Green
14 13
9 :: : :
5 :: : :
1 :: : :
: : ::
Ring Terminal on ground wire
riveted to J-Box with Star Washer
:: : :
Wire connected with Quick Disconnect
hite-Common to screen & 110 VAC Neutral
Red-to screen (directional)
Brown-to screen (directional)
Yellow-to 110 VAC-Hot
Black-to 110 VAC-Hot
Green/Yellow (Ground)
LVC-IV Low Voltage Control Wiring Diagrams for All Draper Products
Location of key
operated 0n-off
switch if furnished.
Technical Specifications:
Notes:
To 110V AC-Hot
Dashed wiring by electrician
Low voltage wiring by others
Power Supply:
110V-120V / 60Hz
Temperature:
-40° C – 85° C
Frequency:
433 MHz
Power:<300W
Transmit Power: <10mW
Sensitivity:-110dBm
Fuse:
3.15 Amp
Figure 1
To screen/lift. See
individual product
wiring diagrams
for details.
3 Button Wall Switch
DOWN - Black
COM - White
UP - Red
RS232/485
or connection
to next LVC-IV
(universal-either jack)
(supplied by others)
Low Voltage
RF Remote
Trigger 5-28 VDC Antenna
Signal Light
-Don't let the RF receiver touch metal objects; this could affect the maximum distance the transmitter can be from the RF receiver.
-Disconnect the power supply before installing the RF receiver.
-Avoid electrostatic interference: Static electricity will damage
the electronic components.
-Make sure there is more than 5 feet between the RF receiver
and ground.
-Make sure there is more than 1 foot between the RF receiver
and ceiling.
-Make sure there is more than 1 foot between the RF receiver
and transmitter.
-If using more than one receiver, make sure they are separated
by more than 8 inches.
Optional
IR Eye
Radio Frequency (RF) Remote Control
Receiver
Button
The LVC-IV comes with built-in Radio Frequency Remote control capability (optional handheld transmitter NOT included).
To "Learn" a remote
Signal
1 Press receiver button on LVC-IV (see Fig. 2A).
Light
2 Signal light will flash slowly.
3 Press transmitter's Up button within 10 seconds (see Fig. 2B).
4 Signal light flashes three times quickly.
Receiver
Button
To "Un-Learn" a remote
1 Press receiver button on LVC-IV (see Fig. 2A).
2 Signal light will flash slowly.
3 Press transmitter's Down button within 10 seconds (see Fig. 2C).
4 Signal light flashes three times quickly.
.
A
3 Button Wall Switch
DOWN - Black
COM - White
UP - Red
Electrically Straight
Data Cable to more
LVC-IV modules*
RS232/485 Inputs/Outputs
Low Voltage Trigger
3-28 VAC
IR Eye Input
To "Un-Learn" all remotes
1 Press receiver button on LVC-IV until signal light flashes quickly, then release.
2 Press receiver button once while signal light is flashing.
3 Signal light will stop flashing.
B
C
Figure 2
Please Note: Operating range is 250ft (open distance). RF Signal will degrade significantly with each wall it is required to penetrate.
If you are experiencing issues with RF signal strength, the RF antenna can be threaded out one of the knockouts for better reception.
InfraRed (IR) Remote Control
*A maximum of six (6)
LVC-IV modules can be
linked together.
1 Plug Optional IR Eye into mini plug input provided on LVC-IV (see Figs. 1 and 3).
2 IR Remote Control transmitter does not need to be "learned" by the LVC-IV. Simply point and operate.
3 Maximum IR Eye cable length is 42".
Please Note: IR Transmitter Range is 26ft.
Figure 3
DC Low Voltage Trigger
Wall Switch
The LVC-IV comes with built-in connection for sending a DC trigger (5-28 VDC) from the projector to the projection screen.
1 Connect remote trigger voltage from projector to the low voltage trigger cable.
2 Plug the mini-jack plug of the low voltage trigger cable to the LVC-IV (Figure 1 & 4).
3 When projector is 'ON' the low voltage output of the projector will cause LVC-IV to deploy projection screen.
When projector 'OFF' the low voltage is removed from LVC-IV and projection screen will retract into case.
Figure 4
Wiring Diagrams
Screens.......................... Page 2
RS-232/485..................................... Page 3
Positive Lead
RedProjection
24 AWG
Form LVC-IV-Wiring_Inst17
Printed in the U.S.A.
If you encounter
anyLead
difficulties installing or servicing your LVC-IV, call your dealer
Negative
or contact Draper,
Black 24Inc.,
AWG Spiceland, Indiana, 765-987-7999, or fax 765-987-7142.
.60" Max.
Copyright ©2017 Draper Inc.
www.draperinc.com
(765) 987-7999
GND
To
110-120 VAC L1
Line
N
Green/Yellow
(Motor Ground)
White (Common)
Red (Down)
Black (Up)
Dashed wiring by electrician
Low voltage wiring by others
Location of key
operated on-off
switch if furnished.
Red-to screen (directional)
Brown-to screen (directional)
Yellow-to 110V-220V AC-Hot
Black-to 110V-220V AC-Hot
White -Common to screen & 110V-220V AC Neutral
Green/Yellow (Ground)
Receiver
Button
Low Voltage
Trigger
5-28 VDC
IR Eye Input
RS232/485
Inputs/Outputs
Wall Switch
*A maximum of six (6)
LVC-IV modules can be
linked together.
Electrically Straight
Data Cable to more
LVC-IV modules*
3 Button Wall Switch
DOWN - Black
COM - White
UP - Red
External LVC-IV—Single or Multiple
Projection Screen Wiring Diagram
FUSE - 3.15 AMP
250 VAC 5x20mm
INTERNAL SCREEN WIRING
External LVC-IV - Single or Multiple
Wiring Diagram for Ambassador and Rolleramic
LVC-IV by Draper
Page 2 of 3
External LVC-IV—Single or Multiple Wiring
Diagram for Ambassador and Rolleramic
LVC-IV by Draper
Page 3 of 3
RS232 / RS485 Information
123456
RS232 / RS485 CommPort Parameters:
1 Frequency (BAUD Rate): 2400
2 Data long code : 8
3 Parity Check : N
4 Start bit : 1
5 Stop bit : 1
6 Flow Control : NONE
Please Note:
Connections using modular cable
must be made using electrically
straight 6-conductor modular cable
(RJ25). This means colors do not
cross over: blue leads to blue, green
to green, etc. (see diagram at right)
COMMAND
COMMAND STRINGS
REMARK
UP
9A 01 01 00 0A DD D7
ID No. : 1 / Channel : 01
PIN 2 - Down
STOP
9A 01 01 00 0A CC C6
ID No. : 1 / Channel : 01
PIN 3 - Up
DOWN
9A 01 01 00 0A EE E4
ID No. : 1 / Channel : 01
PIN 1 - 5VDC Output
PIN 4 - Ground
PIN 5 - RS485-A or RS232-GND
For more detailed programming instructions or group control go to:
http://www.draperinc.com/DraperPro
(registration required)
PIN 6 - RS485-B or RS232-Tx
LVC-IV—Dimensions
4.5"
Use the appropriate
screws and hardware
to mount the enclosure
through the four key
holes provided. Use
largest size fastener
that will fit in key holes.
2.214"
FUSE - 3.15 AMP
250 VAC 5x20mm
10.39"
2.214"
For AC supply wires attach appropriate ½" Trade Size connector
to route wiring through knockouts. For low voltage wires attach
with appropriate connector to route wiring through knockouts.
Knockouts are provided on all fours sides of the enclosure.
www.draperinc.com
(765) 987-7999
ULTIMATE ACCESS/SERIES E
MOTORIZED CEILING-RECESSED PROJECTION SCREEN
The ULTIMATE ACCESS/SERIES E is a ceiling-recessed electric projection
screen. It has an independently motorized ceiling closure that forms a solid
bottom panel giving the ceiling a clean appearance when closed. The door
opens into the case before the viewing surface descends into the room.
And the entire closure extends down as required for screen installation or
adjustment. The Access Series is designed to allow installation of the folded
steel headbox during construction and the screen later, to avoid damage to
the screen.
FEATURES
—— INCLUDES: One 110V, 3-position
switch.
—— CASE DIMENSIONS: 9-7/8" H X 8"
D (25 cm X 20 cm) (includes flange).
Mounting brackets are adjustable.
Built-in controls may increase length.
—— BLACK BORDERS: NTSC, HDTV and
16:10 formats have black borders on
all four sides. Available on AV format
upon request.
—— WARRANTY: One year against defects
in materials and workmanship.
—— US PATENTS:
http://www.draperinc.com/legal/patents/
OPTIONS
—— VIEWING SURFACE: Available with
viewing surfaces from the OptiView (free
hanging), ClearSound (acoustically
transparent) and Chroma
Key families.
—— CONTROLS: Can be furnished with
standard control options.
—— MOTORS: Also available with
Quiet Motor or 220V motor.
—— EXTRA DROP: Available upon
request, specify color.
—— 16:10 FORMAT: from 94" (239 cm)
to 165" (419 cm) dia.
—— 16:9 HDTV FORMAT: from 92" (234 cm)
to 161" (409 cm) dia.
—— 4:3 NTSC/PAL FORMAT: 72"
(183 cm) to 180" (457 cm) dia.
—— AV FORMAT: from 50" x 50"
(127 cm x 127 cm) to 12' x 12'
(366 cm x 366 cm)
—— CUSTOM SIZES AVAILABLE: For
larger sizes see the Ultimate Access
XL/Series E.
SUPPORTING DOCUMENTS
All instructions, technical drawings and other supporting
documents are located at:
www.draperinc.com/Documents.aspx
DraperInc.com
SIZES
For more information on this product visit:
www.draperinc.com/go/UltAccE.htm
Draper, Inc. © 2016 All Rights Reserved • Updated 9.7.16
TECHNICAL DATA SHEET
Chroma Key
VIDEO PRODUCTION surfaces
Chroma Key Green
The perfect surface for video production where you need the background to “disappear.” Offers excellent uniformity
and consistent surface color edge to edge. Works effectively throughout 180° viewable range. Blue Chroma Key is also
available.
Chroma Key Surfaces
Chroma Key surfaces are ideal for video production and recording.
Surface Characteristics
•Maximum Height Without Seams: 70”
•Weight (g/sm): 510
•Thickness (mm): 0.32
•Cleaning: Mild soap and water
•Composition: Flexible PVC
•Excellent Opacity
•Matte Finish
•Flame Retardant
•Tear Resistant
•Wrinkle Resistant
Draper, Inc. 411 S. Pearl St. Spiceland, IN 765-987-7999 www.draperinc.com Form: 11-334_8-12
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertisement