Multi-Split Cassette Type Indoor Unit

Multi-Split Cassette Type Indoor Unit
Multi-Split Cassette Type
Indoor Unit
Owner's Manual
Air Conditioners
 Thank you for choosing Air Conditioners, please read this owner’s manual carefully before operation
and retain it for future reference.
User Notice
◆ When operating, the entire capacity of the cooperating indoor unit should be not
larger than 150% of outdoor unit. Otherwise, it will cause the shortage of cooling
(heating) capacity.
◆ A Breaker (or fuse) need to be installed in every indoor unit, and the capacity
should in according with indoor unit’s electrical parameter, all the indoor units are
required to be centralized controlled by a total Switch, this Switch can cut off the
electric power supply in case of emergency. The Breaker (or fuse) on each indoor
units have the function of short circuit prevention and abnormal overload avoiding,
it should be connected in normal situation. The total switch controlling the power
supply of all the indoor units. Before clearing and maintenance job being carried
out to the indoor units, it is very important to turn off the total power supply switch.
◆ In order to turn on the units successfully, the main power switch should be opened
8 hours before the operation.
◆ After receiving the turn off signal, every indoor unit will continue to work for
20-70sec to make use of the rest cool air or the rest heat air in the heat exchanger,
while preparing for the next operation. And this is normal.
◆ When the selected operating mode of the indoor unit are clash with the operating
mode of the outdoor unit, the malfunction light will blink after 5s on the indoor unit
or remote controller showing that the operation clash, then the indoor unit will stop.
At this time, change the operation mode of the indoor unit to the one that would
not clash with the outdoor operating mode to make the operation normal. The
cooling mode is not clash with the dry mode, while the fan mode is not clash with
any mode.
◆ The appliance shall not be installed in the laundry
◆ An all-pole disconnection switch having a contact separation of at least 3mm in all
poles should be connected in fixed wiring
◆ Information regarding transport/storage temperature (-25-55°C) is missing
◆ Main switch provided by end user: main switch handle should be black or gray, it
can be locked in “OFF” position with padlock
◆ The main disconnection device should be explained in user manual and the height
I
should be recommended at 0.6-1.7m. Over current protection is required (EN
60947-3, EN 60947-2)
◆ The cooling range of the unit is the outdoor environment temp.-5~48°C DB, the
heating range of the unit (only for the heat pump type unit) is the outdoor
environment temp. -15~27°C WB.
◆ This appliance can be used by children aged from 8 years and above and persons
with reduced physical, sensory or mental capabilities or lack of experience and
knowledge if they have been given supervision or instruction concerning use of
the appliance in a safe way and understand the hazards involved. Children shall
not play with the appliance. Cleaning and user maintenance shall not be made by
children without supervision.
◆ If the supply cord is damaged, it must be replaced by the manufacturer, its
service agent or similarly qualified persons in order to avoid a hazard.
◆ The appliance shall be installed in accordance with national wiring regulations.
Correct Disposal of this product
This marking indicates that this product should not be disposed
with other household wastes throughout the EU. To prevent possible
harm to the environment or human health from uncontrolled waste
disposal, recycle it responsibly to promote the sustainable reuse of
material resources. To return your used device, please use the
return and collection systems or contact the retailer where the
product
was
purchased.
environmental safe recycling.
R410A (R32/125:50/50): 2087.5
II
They
can
take
this
product
for
Contents
1 Safety Information ............................................................................ 1
2 Install Of The Cassette Type Indoor Unit .......................................... 2
2.1 Schematic diagram of installation spaces ............................................... 2
2.2 Select install location of the indoor unit................................................... 2
2.3 Important notice: ..................................................................................... 3
2.4 Dimension of ceiling opening and location of the hoisting screw (M10) . 3
2.5 Main body of hoisting air conditioner ...................................................... 4
2.6 Connection of the refrigerant pipe........................................................... 5
2.7 Drainage hose ......................................................................................... 6
2.8 Instruction ................................................................................................ 8
2.9 Electrical wiring ....................................................................................... 9
2.10 Install the panel ................................................................................... 10
3 Constitutes and Names of Parts of Cassette Type Indoor Unit ....... 13
4 Working Temperature Range .......................................................... 14
5 Operation Method When Meeting An Emergency ........................... 14
6 Malfunction Debarring .................................................................... 15
7 Maintenance Method ...................................................................... 17
7.1 Cleaning air filter ................................................................................... 17
7.2 Clean air inlet grille ............................................................................... 18
7.3 Install and change of air purifier ............................................................ 18
7.4 Clean Outlet vent and Surface Panel ................................................... 19
7.5 Maintenance before or after usage season .......................................... 20
III
Free Match Series Cassette Type Indoor Unit
1 Safety Information
Please read this manual carefully before use this unit, and operate it correctly
according to the guide in this manual.
Please take specially note to the meaning of these two marks:
Warning! : This mark means that it may cause casualty or badly heart if the
operation is incorrect.
Note! : This mark means that it may cause casualty or property loss if the
operation is incorrect.
Warning:
①. Do not adopt fuse with unsuitable capacity or adopt iron thread instead of fuse,
otherwise malfunction or fire may happened.
②. Cut down the main power switch immediately if malfunction (such as smell the
burning odor etc.) happened.
③. Maintain ventilation to prevent oxygen leakage in room.
④. Don’t insert finger or stick like things into discharge vent or outlet grill.
⑤. Please make sure that the unit is installed in the place that can bear the weight
of it adequately. If the place is not strong enough, the air conditioner may drop
and cause casualty event.
⑥. Don’t spray or smear any oil paint or insecticide on the surface of unit,
otherwise, fire may be leaded.
⑦. Do not refit the conditioner. Please contact the agency or prefect ional
personnel to repair or move the conditioner.
⑧. An all-pole disconnection switch having a contact separation of at least 3mm
in all poles should be connected in fixed wiring.
Note! :
①. Please check and make sure that the cord, drainage pipe and tubes are
connected in the correct way to prevent leakage of water, refrigerant, electric
shock or fire.
②. The main power must connectable to the earth in order to assure the
conditioner earthing effectively and to prevent electric shock. Please don’t
connect the earthing line with the gas pipe, water pipe, lightening rod or the
connecting line of telephone.
③. The air conditioner should be turned off at least after 5 mins’ operation,
otherwise it would affect the duration of the unit.
④. Don’t let the children operate the air conditioner.
⑤. Please don’t operate the unit by wet hand.
1
Unitary Duct Split Unitary Duct Split
⑥. Please turn off the main power of the unit before cleaning the conditioner or
change the filter.
⑦. Please cut off the main power if the conditioner will be used for a long time.
2 Install Of The Cassette Type Indoor Unit
2.1 Schematic diagram of installation spaces
Fig.1
2.2 Select install location of the indoor unit
1). Obstruct should put away from the intake or outlet vent of the indoor unit so
that the airflow can be blown though all the room.
2). Make sure that the installation had accord with the requirement of the
schematic diagram of installation spaces.
3). Select the place where can stand 4 times of the weight of the indoor unit and
would not increase the operating noise and oscillate.
4). The horizontally of the installation place should be guaranteed.
5). Select the place where easy drain condensated coagulated water, and easy
connect with outdoor unit.
6). Make sure that there are enough space for care and maintenance. Make sure
that the weight between the indoor unit and ground is above 2500mm.
7). When installing the steeve bolt, check if the install place can stand the weight
4 times of the unit’s. If not, reinforce before installation. (Refer to the install
cardboard and find where should be reinforced).
2
Free Match Series Cassette Type Indoor Unit
Note! :
There will be lots of lampblack and dust stick on the acentric, heat exchanger and
water pump in dining room and kitchen, which would reduce the capacity of heat
exchanger, lead water leakage and abnormal operation of the water pump. The
following treatment should be taken under this circumstance:
①. Ensure that the smoke trap above cooker has enough capacity to obviate
lampblack to prevent the indraft of the lampblack by the air conditioner.
②. Keep the air conditioner far from the kitchen so that the lampblack would not
be indraft by the air conditioner.
2.3 Important notice:
1). To guarantee the good performance, the unit must be installed by professional
personnel according with this instruction.
2). Please contact the local ALPICAIR special nominated repair department before
installation. Any malfunction caused by the unit that is installed by the
department that is not special nominated by ALPICAIR would not deal with on time
by the inconvenience of the business contact.
2.4 Dimension of ceiling opening and location of the
hoisting screw (M10)
Fig.2 Install dimension of mode
3
Unitary Duct Split Unitary Duct Split
The drilling of holes in the ceiling must be done by the professional personnel.
Fig.3
Notes :
The dimension for the ceiling openings with * marks can be as large as 910mm.
But the overlapping sections of the ceiling and the decorated surface boards should be
maintained at no less than 20mm.
2.5 Main body of hoisting air conditioner
1). The primary step for install the indoor unit.
When attach the hoisting stand on hoisting screw, do use nut and gasket
individually at the upper and lower of the hoisting stand to fix it. The use of gasket
anchor board can prevent gasket break off.
2). Use install cardboard
a) Please refer to the install cardboard about the dimension of ceiling opening.
b) The central mark of the ceiling opening is marked on the install cardboard.
c) Install the install cardboard on the unit by bolt (3 piece), and fix the angle of
the drainage pipe at the outlet vent by bolt.
3). Adjust the unit to the suitable install place. (Refer to the fig.3)
4). Check if the unit is horizontal.
Inner drainage pump and bobber switch are included in the indoor unit, check if 4
angle of every unit are horizontal by water lever. (If the unit is slant toward the opposite
of the coagulate water flow, there may be malfunction of the bobber switch and lead
water drop.)
5). Backout the gasket anchor board used to prevent gasket break off and tighten
the nut on it.
6). Backout the install cardboard.
4
Free Match Series Cassette Type Indoor Unit
Fig.4
Note! :
Please do tighten the nuts and bolts to prevent air conditioner break off.
2.6 Connection of the refrigerant pipe
1). When connect the pipe to the unit or backout it from the unit, please do use
both spanner and torque wrench. As shown in fig.5.
2). When connect, smear both inside and outside of the flare nut with freeze
motor oil, screw it by hand and then tighten it with spanner.
3). Refer to form 1 to check if the wrench had been tightened (too tight would
mangle the nut and lead leakage).
4). Examine the connection pipe to see if it had gas leakage, then take the
treatment of heat insulation, as shown in the fig.5.
5). Only use median sponge to entwine the wiring interface of the gas pipe and
heat preservation sheath of the gas collection tube.
5
Unitary Duct Split Unitary Duct Split
Fig.5
Form 1: The tightening torque needed for tightening nut
Diameter(Inch)
Surface thickness(mm)
Tightening torque (N·m)
Φ1/4’’
≥0.5
15-30 (N·m)
Φ3/8’’
≥0.71
30-40 (N·m)
Φ1/2’’
≥1
45-50 (N··m)
Φ5/8’’
≥1
60-65 (N·m)
Φ3/4’’
≥1
70-75 (N··m)
2.7 Drainage hose
1). Install the drain hose
a) The diameter of the drain hose should be equal or bigger than the
connection pipe’s. ( The diameter of polythene pipe: Outer diameter 25mm
Surface thickness ≥1.5mm)
b) Drain hose should be short and drooping gradient should at less 1/100 to
prevent the formation of air bubble.
c) If drain hose cannot has enough drooping gradient, drain raising pipe should
be added.
d) To prevent bent of the drain hose, the distance between hoisting stand
should is 1 to 1.5m.
6
Free Match Series Cassette Type Indoor Unit
Fig.6
e) Use the drain hose and clamp attached. Insert the drain hose to the drain
vent, and then tighten the clamp.
f) Entwine the big sponge on the clamp of drain hose to insulate heat.
g) Heat insulation should be done to indoor drain hose.
Fig.7
2). Drain stepup pipe note
a) The install height of the drain raising pipe should less than 280mm.
b) The drain raising pipe should form a right angle with the unit, and distance to
unit should not beyond 300mm.
Fig.8
7
Unitary Duct Split Unitary Duct Split
2.8 Instruction
1). The slant gradient of the attached drain hose should be within 75mm so that
the drain hole doesn’t has to endure the unnecessary outside force.
Fig.9
2). Please install the drain hose according to the following process if several drain
hoses join together.
Fig.10
3). Check the smoothness of drain after installation.
a) Check the drain state by immitting 600cc water slowly from the outlet vent or
test hole.
b) Check the drain in the state of refrigerating after installation of the electric
circuit.
8
Free Match Series Cassette Type Indoor Unit
Fig.11
2.9 Electrical wiring
Note: The power of the entire indoor unit must be connected in outdoor unit.
①. About the electrical wiring, please see the circuit diagram attached with the
unit.
②. All the installation of electrical wiring must be done by professional personnel.
③. Please do take the earthing treatment.
Wiring method of connection unit and controller
1). Connection wiring (communication):
a) Open electric box cover (1), drag the wiring (communication) from the rubber
plug A, and impact them well individually by impact fastener.
b) Wiring according to the indoor side circuit diagram.
2). Fix the impact fastener after connection.
3). Entwine the small sponge on the electric wire ( do entwine it to prevent
condensation)
4). Impact tightly by impact fastener after connection and then fit on the electric
box (1) and (2).
5). Connect the wiring (communication) through the piping hole of the chassis
and the bottom of the appliance upward, then connect the brown wire to the
Terminal board “3”, black wire(the communication wire) to the Terminal
board“2”, blue wire to the Terminal board“N(1)”.and connect the earthing wire
to the screw terminal on the electric box.
9
Unitary Duct Split Unitary Duct Split
Fig.12
2.10 Install the panel
1). Set the panel to the indoor unit body by matching the position of the swing flap
motor of the panel to the piping position of the panel to the piping position of
the indoor unit as shown by fig.13.
2). Install the panel
①. Install the panel on the indoor unit temporarily. When install, hang the latch on
the hook that is located on the opposite side of the swing flap on the panel of
the indoor unit. (2 positions)
②. Hang the remaining 2 latches to the hooks on the sides of the indoor unit. (Be
careful not to let the swing motor lead wire get caught in the sealing material.)
③. Screw the 4 hexagon head screws under the latches in about 15mm. (The
panel would rise)
④. Adjust the panel by turning it toward the direction pointed by the arrow as
shown in fig.13, so that the adjust board connect the ceiling well.
⑤. Tighten the screws until the thickness of the sealing material between panel
and indoor unit reduced to 5-8mm.
10
Free Match Series Cassette Type Indoor Unit
Fig.13
Notes:
①. Improper screwing of the screws may cause the troubles shown in fig.14.
Fig.14
②. If gap still exist between ceiling and decoration panel after tightening the
screws, readjust the height of the indoor unit. (As shown in fig.15).
11
Unitary Duct Split Unitary Duct Split
Fig.15
※ After fixing, be sure no gap left between the ceiling and the panel.
③. Wiring of the decoration panel (Fig.16)
Connect the joints for swing flap motor lead wire (at 2 places) installed on the
panel.
Fig.16
12
Free Match Series Cassette Type Indoor Unit
3 Constitutes and Names of Parts of Cassette Type
Indoor Unit
13
Unitary Duct Split Unitary Duct Split
4 Working Temperature Range
Working Temperature Range
Indoor side state
Outdoor side stae
Dry bulb temp.℃
Wet bulb temp.℃
Dry bulb temp.℃
Wet bulb temp.℃
Rated Cooling
27
19
35
24
Max. cooling
32
23
48
26
Min. cooling
21
15
18
—
Rated Heating
20
15
7
6
Max. heating
27
—
24
18
Min. heating
20
15
-15
-16
5 Operation Method When Meeting An Emergency
When wireless remote controller is lost or damaged, the following method could be
adopted to control cassette type indoor unit:
(1). When the unit is turned off, press AUTO button on corner outer coverⅡ, then
the unit begin operate in cooling with the fan run in high speed. The temp. will
be set to 26 ℃ automatically.
(2). When the unit is turned off, press TEST button on the corner outer coverⅡ,
then the unit begin running in heating and the fan is running in high speed.
The temp. will be set to 20 ℃automatically.
(3). When the unit is running, press AUTO button on corner outer coverⅡ, then
the unit stops running; under the running state of heating, press TEST button
on corner outer cover Ⅱ, then the unit stops running.
Note!
Prevent using the operating method for meeting an emergency when the wireless
remote controller could be used in normal. There are 3 lights on corner outer cover Ⅱ,
red for power, green for running, and yellow for timer.
Fig.17
14
Free Match Series Cassette Type Indoor Unit
6 Malfunction Debarring
Warning!
①. Cut down the main power switch immediately if malfunction (such as smell the
burning odor etc.) happened, and then contact service center. If the abnormal
state is maintained, the unit may be damaged or electric shock or fire may be
happened.
②. Do not refit the conditioner. Please contact service center to repair or move
the conditioner.
(1). Check the following items before contacting maintenance center
Phenomena
Air conditioner
doesn’t run at all
Air conditioner runs
but stops immediately
Abnormal cooling or
heating
Reason
Remedial Measures
Blow of fuse or breaker
Change fuse or close breaker
Power cut
Restart when there is power
supply
Don’t connect with power
Connect power well
Low batteries of wireless remote
controller
Change new batteries
Wireless remote controller
exceed remote control area
Signal could be received within
8m
Blockage in inlet or outlet vent of
indoor or outdoor unit
Clean out blockage
Blockage in inlet or outlet vent of
indoor or outdoor unit
Clean out blockage
Improper of temp. setting
Adjust settings in wireless
remote controller
Low setting of fan speed
Adjust settings in wireless
remote controller
Incorrect of wind direction
Adjust settings in wireless
remote controller
Door or window opened
Close
Direct sun burn
Hang curtain or jalousie before
windows
Too many people in room
Too many heater in room
Filter blocked by dirt
15
Clean filter
Unitary Duct Split Unitary Duct Split
(2). Instruction
If problem still cannot found out after above checking, please contact service
center and instruct phenomena and model.
(3). The following circumstance are not malfunction
Reason
“Malfunction”
Start up unit immediately after
turned off
Air conditioner
doesn’t run
When opening power
Mist is blown from air
When cooling
conditioner
Slight click sound heard once
Noise is heard from
air conditioner
The overload protects switch
makes it run after 3 minutes
delay.
Run for about 1 minute without
other actions
The high humidity air in room is
cooled rapidly
Sound of initialization for electric
begin running
expand valve
Hissing sound heard continuously
The sound for gas refrigerant
when cooling
flowing in the unit
Hissing sound heard when staring
The sound for gas refrigerant
or stopping
stops flow
Slight hissing sound heard when
Sound for running of drainage
running or after running
system
Creak sound heard when running
or after running
Dust be blown for air
Started up after long time’s
conditioner
doesn’t runs
The grating sound caused by
expands of panel and other parts
for the change of temperature
Dust in indoor unit be blown out
This is because when air
Odor gives out from
air conditioner
When running
conditioning, odors or cigarette
smoke from the room that was
sucked in is discharged again.
(4). After-sales Service
When having quality or other problems when purchasing air conditioner, please
contact the local service center.
16
Free Match Series Cassette Type Indoor Unit
7 Maintenance Method
When air conditioner won’t be used for a long time, please cut off the main power
supply of air conditioner.
Warning!
①. Do turn off the unit and cut off the main power supply when cleaning the air
conditioner, otherwise electric shock or harm may happen.
②. It is forbidden to wash air conditioner by water rinsing, otherwise electric shock
may happen.
7.1 Cleaning air filter
When the usage environment has lots of dust, air filter should be cleaned more
frequently (about once 6 months).
1). Open air inlet grille
Pull the 2 handle on air inlet grille at the same time with the direction showed by
arrow in fig. 18, pull down slowly. (Reverse when closing)
2). Disassembly air filter
As shown in fig. 19, pull the handle behind air inlet grille, raise it and disassembly.
Then discharge the 3 purifier fixed on filter.
Fig. 18
Fig. 19
3). Clean
Adopts cleaner or water to wash filter; if the filter is too dirty ( like oil stain on it ),
adopts warm water ( lower than 45℃) with neutral scourer to clean it, then dry it in the
shade.
17
Unitary Duct Split Unitary Duct Split
Note!
①. Do not clean the filter by hot water whose temp. is higher than 45℃to prevent
fade or deformation.
②. Do not burn it on fire or the filter would catches fire or deformation.
4). Install air filter
Fix the 3 purifiers on filter, install filter on the several bulges on top of air inlet grille,
pull the handle behind air inlet grille toward inside to fix filter. As shown in fig. 20.
5). Close air inlet grille (Refer to the 1st step)
Maintenance Method
Fig. 20
Fig. 21
7.2 Clean air inlet grille
1). Open air inlet grille (the same with the 1st step of Clean Air Filter)
2). Take out air filter (the same with the 2nd step of Clean Air Filter)
3). Take out air inlet grille
4). Open air inlet grille for an angle of 45°, as shown in fig. 21, rise it.
5). Clean
Clean it by pubescence brush, water and neutral cleaning, then throw water or dry
it.
Note!:
Do not use water above 45℃ to wash the panel to prevent fade or deformation.
6). Install air inlet grille (refer to 3rd step)
7). Install air filter (refer to the 4th step of Clean Air Filter)
8). Close air inlet grille (refer to the 1st step)
7.3 Install and change of air purifier
1). Open air inlet grille (the same the 1st step of Clean Air Filter)
2). Disassembly purifier
18
Free Match Series Cassette Type Indoor Unit
As shown in fig 22, disassembly air filter, screw out fixing bolts fixed on purifier on
filter, then purifier could be disassembly.
3). Take out the package sack of static fiber net filter, then install the filter in stand
of purifier, and fix purifier on air filter.
4). Install air filter (the same with the 4th step of Clean Air Filter)
Fig. 22
Function and usage period for air purifying
 Could adsorb CO, CO2, benzene, aldehydes and odor of gasoline etc..
 Could adsorb deleterious material that is smaller than 1μm in air, as dust, pollen,
bacteria, and virus.
 Usage period is 6 months to 1 year. If it is necessary to be changed, purchase
new purifier in the nearest ALPICAIR special engaged maintenance center.
7.4 Clean Outlet vent and Surface Panel
 Clean the surface panel by soft dry cloth or wet cloth with neutral scourer.
 It is forbidden to clean surface panel by gasoline, benzene, diluents, cleansing
powder etc..
 If the guide louver is too dirty, it may be removed to be cleaned. (As narrated
below)
Disassembly and install of guide louver
1). Disassembly guide louver
Screw bolts in both end of guide louver to loose.
Note!
Do not wipe guide louver powerfully when cleaning, otherwise fluff on surface
would fall off.
2). Install guide louver
19
Unitary Duct Split Unitary Duct Split
Rotate guide louver slightly could install the protruding edge of both end into
grooves on both end of guide louver, and then tighten bolts.
7.5 Maintenance before or after usage season
Check before the usage season
 Check if there is blockage in inlet or outlet vent of air conditioner.
 Check if the earthing wire had earthed reliably.
 Check if the air filter had been installed well.
 In order to start up the air conditioner smoothly after long time’s turned off, turn
on the main power supply 8 hours before turning on the air conditioner.
Maintenance after usage season
 Clean filter and body of air conditioner.
 Cut off the main power supply of air conditioner.
 The cooling or heating capacity and sound level are tested before leaving
factory.
 If the parameter changed, refer to the data offered on nameplate.
Following items:
1). For the safe operation of this unit, please read and follow the instructions
carefully.
2). During operation, total capacity of indoor units should not exceed the total
capacity of outdoor units. Otherwise, poor effect of cooling or heating may
result.
3). Direct operators or maintainers should well keep this manual.
4). If this unit fails to operate normally, please contact our service center as soon
as possible and provide the following information:
 Content on the nameplate (model number, cooling capacity, production code,
ex-factory date).
 Malfunction details (before and after the malfunction occurs).
Each unit has been strictly tested and proved to be qualified before ex-factory. In
order to prevent units from being damaged or operating normally because of improper
disassembly, please do not disassemble the unit by yourself. If you need to
disassemble and check units, please contact our service center. We will send
specialists to guide the disassembly.
All graphics in this manual is only for your reference. For sales or production
reasons, these graphics are subject to change by manufacturer without prior notice.
20
Was this manual useful for you? yes no
Thank you for your participation!