YOKOGAWA General Specifications


Add to my manuals
19 Pages

advertisement

YOKOGAWA General Specifications | Manualzz

<<Contents>> <<Index>>

General

Specifications

GS 33J64E10-01EN

Models A2FV70S/A2FV70D

Field Control Unit,

Model A2CUKT3

Cabinet Utility Kit (For RIO System Upgrade)

[Release 6]

This document describes the hardware specifications of A2FV70S/A2FV70D field control unit (FCU) and A2CUKT3 cabinet utility kit, as well as the specifications of the field control station (for RIO System Upgrade).

Note: “RIO” stands for Remote I/O.

1. A2FV70S/A2FV70D Field Control Unit (for RIO System Upgrade)

GENERAL

A2FV70S and A2FV70D FCU are to replace the existing FCU for RIO System Upgrade.

HARDWARE SPECIFICATIONS

Applicable products

The following models of FCU can be upgraded by the

RIO System Upgrade.

Model

Field Control Unit (19-inch rack mountable)

AFE10S AFM10S AFH10S AFS10S AFG10S

AFE10D AFM10D AFH10D AFS10D AFG10D

Model

Field Control Unit (with cabinet) (*1)

AFE20S AFM20S AFH20S AFS20S AFG20S

AFE20D AFM20D AFH20D AFS20D AFG20D

*1: Place an order of A2CUKT3-C separately for upgrading the existing FCU (with cabinet).

Processor

VR5532 (350 MHz)

Main Memory Capacity

128 MB

Memory protection during power failure

Battery

Battery Backup for Main Memory: Max. 72 hours

Battery Recharge Time: 48 hours or longer

READY contact output

2 terminals (NC and C),

Contact points open during FCU failure

Contact rating: 30 V DC, 0.3 A or less

Note: When the option code of “/HKU” is specified, the house keeping unit (HKU) outputs failures of the FCU by opening the READY contact of the

A2CUKT3.

Communication interface

Vnet/IP interface: Dual-redundant

F01E.ai

Connectable nodes

The following nodes can be connected to the FCU for

RIO system upgrade.

Model Description

A2NN30D Node interface unit (for N-IO) (*1)

ANB10S/D ESB bus node units

ANB11S/D Optical ESB bus node units

*1: A2NN30D can be used only with A2BN4D and

A2BN5D. (A2BN3D can not be used for RIO

System Upgrade.)

HKU interface unit (option)

When the option code of “/HKU” is specified, the HKU outputs failures of FCU by opening the READY contact.

The HKU also monitors the environmental status of the cabinet via the N-ESB bus or the optical ESB bus, which enables to display the HKU’s operation status on the HIS as well as to generate system alarms.

Yokogawa Electric Corporation

2-9-32, Nakacho, Musashino-shi, Tokyo, 180-8750 Japan

Tel.: 81-422-52-5634 Fax.: 81-422-52-9802

GS 33J64E10-01EN

©Copyright June 2016 (YK)

5th Edition June 1, 2017 (YK)

<<Contents>> <<Index>>

Module Configuration

Power Supply Module (PW481, PW482, or PW484): 2 modules for dual-redundant configuration

Processor Module (CP461 style S2 or later):

I/O Module (*1):

2 modules for dual redundant configuration

2 modules each for dual redundant configuration (*2) and max. 8 in total.

*1: The following modules can be installed in an FCU. For details, refer to the GS of each module.

[Communication modules (ALR111, ALR121, ALE111, ALF111, and ALP121), ESB bus coupler modules (EC401 and

EC402), N-ESB bus coupler modules (A2EN402 and A2EN404), and Optical ESB bus repeater modules (ANT401 and

ANT411)]

*2: ESB bus coupler modules (EC401/EC402), N-ESB bus coupler modules (A2EN402/A2EN404), and Optical ESB Bus

Coupler Modules (ANT401/ANT411) are used always in a dual-redundant configuration. A single configuration or dualredundant configuration can be selected for the communication modules (ALR111, ALR121, ALE111, ALF111, and

ALP121).

2

Module installation restrictions

When using EC401 or EC402 ESB bus coupler module, install them in slots 7 and 8 of the FCU.

A pair of ANT401 or ANT411 optical ESB bus repeater master modules is to be installed in an odd-number slot and the one on the right of the slots 1 to 6 according to the number of branches.

A pair of A2EN402 or A2EN404 N-ESB bus coupler modules is to be installed in an odd-number slot and the one on the right of the slots 1 to 8 according to the number of branches. Note that the pair of A2EN402/A2EN404 cannot be installed in slots 7 and 8 of the FCU when EC401/EC402 are installed (as these modules occupy slots 7 and 8).

For remarks on installation of the communication modules and the bus interface modules, refer to the GS “N-IO

System Overview” (GS 33J62A10-01EN).

Node unit installation restriction

An N-IO node can be connected to EC41, A2EN40, and ANT41 installed in the A2FV70 via an N-ESB bus or an optical ESB bus.

An FIO node can be connected only to EC41 and ANT41 installed in the A2FV70 via an ESB bus or an optical

ESB bus.

Mounting restrictions by application capacity limitations

The number of nodes that can be connected to an FCU is as shown below. The node expansion license does not limit the number of nodes, but limited by the VP6F1900 software license.

Basic Control Functions (VP6F1900)

Number of N-IO nodes (*1)

Number of N-IO I/O Units (*2)

Sum of ANB11D/ANB10D units

Sum of ALR111/ALR121/ALE111/ALP121 modules

Sum of ALF111 modules

Sum of Communication Modules to be mounted (*3)

Max. 8 nodes per FCU

Max. 40 units per FCU

Max. 8 units per FCU

Max. 32 modules (16 pairs in dual-redundant configuration) per FCU

Max. 64 modules (32 pairs in dual-redundant configuration) per FCU

Max. 64 modules (*1) per FCU

*1: An N-IO node consists of a node interface unit and N-IO I/O units. For details refer to the GS “N-IO Node (for RIO System

Upgrade)” (GS 33J64F10-01EN)

*2: An N-IO I/O unit consists of I/O modules and I/O adaptors. For details refer to the GS “N-IO Node (for RIO System

Upgrade)” (GS 33J64F10-01EN)

*3: This is the sum of ALR111, ALR121, ALE111, ALF111, and ALP121 modules.

For details, refer to the GS “VP6F1900 Control Function for Field Control Station (for A2FV70)”

GS 33J15C20-01EN) and the GS “VP6F3100 Project I/O License” (GS 33J15A10-01EN).

All Rights Reserved. Copyright © 2016, Yokogawa Electric Corporation GS 33J64E10-01EN June 1, 2016-00

<<Contents>> <<Index>>

Power Supply

Voltage: 100-120 V AC, Frequency: 50/60 Hz

Voltage: 220-240 V AC, Frequency: 50/60 Hz

Voltage: 24 V DC

To be specified by the Suffix Code.

Power Consumption

For 100-120 V AC: 200 VA

For 220-240 V AC: 230 VA

For 24 V DC: 5.5 A

Weight

Approx. 6.9 kg (Model A2FV70S)

Approx. 7.7 kg (Model A2FV70D)

Mounting

19-inch Rack Mounting (M5x8 screws)

With insulation bush (accessory)

Connection

Power supply: M4 screw terminal connection

Grounding: M4 screw terminal connection

READY contact output: M4 screw terminal connection

Vnet/IP interface: UTP cable (CAT5e or superior) to connect Layer 2 switch.

SYSTEM CONFIGURATION

The figure below shows an example of the RIO System Upgrade configured by A2FV70, N-IO and FIO nodes.

Vnet/IP

3

A2FV70D

ESB Bus

Optical ESB Bus

N-IO Node

NIU

N-ESB Bus

NIU

N-ESB Bus

Optical ESB Bus

NIU

N-IO Node

NIU

TM1

READY

FUSE RL1 CN1 (PSU-L)

CN2 (PSU-R)

TM2 100-120V AC

ESB Bus

ANT10U

N-IO N-IO

N-IO N-IO

ANB10D

N-IO N-IO

ANB11D

Optical ESB Bus

ANB10D

ESB Bus

Optical ESB Bus

N-IO

Node

NIU

ESB Bus

N-IO

NIU: Node interface unit (A2NN10D, A2NN20D or A2NN30D)

N-IO: N-IO I/O unit

ANT41: ANT41-E, -F

ANT52: AMT52-E, -F

Figure Configuration of the RIO System Upgrade

All Rights Reserved. Copyright © 2016, Yokogawa Electric Corporation

F02E.ai

GS 33J64E10-01EN Mar. 20, 2017-00

<<Contents>> <<Index>>

EXTERNAL DIMENSIONS

Unit: mm

4

8.75

21.3

482.6

465.1

440

207

150.6

20.4

221.3

146

265.9

44.5

31.75

5.9

Hole for mounting on a 19-inch rack

8 holes for M5 screws

When option code “/HKU” specified

F1-03E.ai

Nominal tolerance:

Nominal tolerance is ± 0.8 mm for the dimensions of 0.5 mm or more and 120 mm or less, and the combined nominal tolerance is ± 1.5 mm.

The nominal tolerance is in accordance with JEM 1459 for the dimensions over 120 mm.

SOFTWARE REQUIREMENT

The A2FV70 is supported by CENTUM VP R6.03 or later.

A software license is required to use the A2FV70. For details, refer to the GS “VP6F1900 Control Function for Field

Control Station (for A2FV70)” (GS 33J15C20-01EN) and “VP6F3100 Project I/O License” (GS 33J15A10-01EN).

STANDARD ACCESSORIES

The A2FV70 FCU is delivered with the following standard accessories.

Part Name

Insulating bush

Part No.

S9049PM

Quantity

8

Remarks

Accessory

All Rights Reserved. Copyright © 2016, Yokogawa Electric Corporation GS 33J64E10-01EN Mar. 20, 2017-00

<<Contents>> <<Index>>

MODEL AND SUFFIX CODES

Field control unit

Field Control Unit (for RIO System Upgrade, 19-inch Rack Mountable)

Standard type

Dual-redundant Vnet/IP, single power supply

Dual-redundant Vnet/IP, dual-redundant power supply

Always 1

100 - 120 V AC power supply (*1)

220 - 240 V AC power supply (*1)

24 V DC power supply (*1)

With no explosion protection

Basic type

With ISA Standard G3 option

Always 0

Description

Model

A2FV70S

-S

3

Suffix

Codes

4

1

1

2

4

0

0

1

0

Option

Code

/HKU With HKU Interface (*2)

*1: To meet the safety standards and EMC standards, the unit must be installed in a keyed metallic cabinet.

*2: When used in combination with A2CUKT3 for upgrading the current field control unit (AFE20, AFM20, AFH20,

AFS20, or AFG20), specify the option code oh “/HKU.”

Duplexed field control unit

Model

A2FV70D

-S

4

Suffix

Codes

1

1

2

4

0

0

1

0

Option

Code

/HKU

Description

Duplexed Field Control Unit (for RIO System Upgrade, 19-inch Rack Mountable)

Standard type

Dual-redundant Vnet/IP, dual-redundant power supply

Always 1

100 - 120 V AC power supply (*1)

220 - 240 V AC power supply (*1)

24 V DC power supply (*1)

With no explosion protection

Basic type

With ISA Standard G3 option

Always 0

With HKU interface (*2)

*1: To meet the safety standards and EMC standards, the unit must be installed in a keyed metallic cabinet.

*2: When used in combination with A2CUKT3 for upgrading the current field control unit (AFE20, AFM20, AFH20,

AFS20, or AFG20), specify the option code of “/HKU.”

ORDERING INFORMATION

Specify models, suffix codes, and option codes when ordering.

5

All Rights Reserved. Copyright © 2016, Yokogawa Electric Corporation GS 33J64E10-01EN Mar. 20, 2017-00

<<Contents>> <<Index>>

6

2. A2CUKT3 Cabinet utility kit (for RIO System Upgrade)

GENERAL

A2CUKT3 is a kit for upgrading existing FCU cabinets, distribution boards of I/O expansion cabinets, and temperature monitoring functions of cabinets when upgrading the RIO system. The A2CUKT3 kit as well as FCU for the RIO

System Upgrade and N-IO node units enables to utilize the existing assets when upgrading the control system. The hardware specifications of the A2CUKT3 are described in this section. Installation of the A2CUKT3 shall be performed by Yokogawa or its affiliate.

STANDARD SPECIFICATIONS

Applicable Cabinet

For A2CUKT3-C (For FCU with Cabinet)

Category

AFE20S

AFE20D

Field Control Unit (for V net and RIO, with Cabinet)

AFM20S AFH20S AFS20S

Model

AFM20D AFH20D AFS20D

Note: Ordering of the A2FV70/HKU is required for upgrading the field control unit.

AFG20S

AFG20D

For A2CUKT3-N (For I/O expansion cabinet)

Category

Model

*1: Except for ACB21-S3000

I/O Expansion Cabinet

ACB21 (*1)

Components of the cabinet utility kit

Table Main parts of A2CUKT3 (1/2)

Parts Classfication

Parts Names Parts No.

supplementation

Quantity

L;Left :Qty

R;Right :Qty

Power supply voltage

A2CUKT3

-C

(FCU with cabinet)

A2CUKT3

-N

(For I/O expansion cabinet)

Power distribution

Main power distribution board

L:1

R:1(When a dual power supply suffix seledted)

100 VAC

220 V AC

24 V DC

S9100FE

S9121FE

S9101FE

FCU power distribution board

For front side

L:1

R:1

100 V AC

220 V AC

24 V DC

S9106FE

S9107FE

S9108FE

Node power distribution board

For front side

For rear side

L:1

R:1

L:1

R:1

100 V AC

220 V AC

24 V DC

100 V AC

220 V AC

24 V DC

S9122FE

S9123FE

S9104FE

S9105FE

Grounding cable

Between grounding bars 1 / 1

Between main power distribution board and grounding bar

1 / 1

Note: “HKU” stands for a House Keeping Unit.

S9997UV / S9998UV

S9995UV /

S9996UV (When Dual power supply suffix seledted)

All Rights Reserved. Copyright © 2016, Yokogawa Electric Corporation

Remarks

GS 33J64E10-01EN June 1, 2016-00

<<Contents>> <<Index>>

7

Table Main parts of A2CUKT3 (2/2)

Parts Classfication

Parts Names Parts No.

supplementation

Quantity

L;Left :Qty

R;Right :Qty

Power supply voltage

A2CUKT3

-C

(FCU with cabinet)

A2CUKT3

-N

(For I/O expansion cabinet)

House Keeping

HKU interface unit

1 — S9102FE

HKU

(for I/O expansion cabinet)

1 — —

FCU fan unit

(with a built-in HKU)

1

100 V AC

220 V AC

24 V DC

S9109FE

S9110FE

Door fan frame

For Front side

For Rear side

Door fan cable

For Front side

For Rear side

Fan power supply unit

Junction adaptor

1

1

1

1

1

1

100 V AC

220 V AC

24 V DC

100 V AC

220 V AC

24 V DC

S9320UK

S9327UK

S9898UV

S9899UV

Thermistor

Thermistor cable

1

1

S9090UG

S9999UV

Note: “HKU” stands for a House Keeping Unit.

*1: Use 9124FE when option code of “/NHKU” is selected and S9103FE for other cases.

S9124FE or

S9103FE (*1)

S9113FE

S9111FE

S9112FE

S9114FE

S9115FE

Remarks

Not provided when

“/NHKU” is selected.

4 units of fan unit for FCU fan unit is included.

Relays the power line between the main power distribution board and fan power supply unit.

READY Contact Output

A2CUKT3-C (FCU with Cabinet): 3 terminals

(NC, NO, and C)

Contact Rating:

Rated voltage:

Rated current:

Rated power:

250 V AC/30 V DC or less

2 A

125 VA or less

Power supply voltage

100-120 V AC, Frequency: 50/60 Hz

220-240 V AC, Frequency: 50/60 Hz

24 V DC

Specify with the Suffix Code.

Power Consumption

A2CUKT3-C

(With FCU and the maximum number of front and rear nodes are installed)

For 100-120 V AC: 1700 VA

For 220-240 V AC: 2000 VA

For 24 V DC: 50 A

A2CUKT3-N

(When the maximum number of front and rear nodes is installed)

For 100-120 V AC: 1600 VA

For 220-240 V AC: 1700 VA

For 24 V DC: 42 A

Connection terminal

Power Supply: M6 screw terminal connection

Contact Output: M4 screw terminal connection

Weight

A2CUKT3-C

A2CUKT3-N

Approx. 24 kg

Approx. 16 kg

All Rights Reserved. Copyright © 2016, Yokogawa Electric Corporation GS 33J64E10-01EN June 23, 2016-00

<<Contents>> <<Index>>

EXAMPLE OF UPGRADING CABINET

A2CUKT3-C (For FCU with Cabinet)

Front

Order separately

FCU (A2FV70/HKU)

FCU power distribution board

Rear

Node power distribution board

8

FCU Fan Unit

Order separately

NIU (A2NN20D)

Thermistor

Thermistor cable

HKU interface unit

(For A2CUKT3-C)

Order separately

NIU (A2NN20D)

Door fan cable

Main power distributi on board

(Front)

Grounding cable

: For A2CUKT3

Door fan cable Door fan frame

(For front door)

Main power distribution board (Rear)

Door fan frame

(For rear door)

F2-01E.ai

Figure Upgrading FCU with cabinet using A2CUKT3-C

All Rights Reserved. Copyright © 2016, Yokogawa Electric Corporation GS 33J64E10-01EN June 1, 2016-00

<<Contents>> <<Index>>

A2CUKT3-N (For I/O Expansion Cabinet)

Front

Node power distribution board

Rear

Node power distribution board

9

Thermistor

Thermistor cable

Order separately

NIU (A2NN20D)

Main power distributi on board

(Front)

HKU interface unit

(For A2CUKT3-C)

Order separately

NIU (A2NN20D)

Junction adaptor

FCU power supply unit

Door fan cable

Grounding cable

: Parts for A2CUKT3

Door fan cable

Door fan frame

(For front door)

HKU for I/O expansion cabinet

Main power distribution board (Rear)

Door fan frame

(For rear door)

F2-02E.ai

Figure Upgrading I/O expansion cabinet with A2CUKT3-N

All Rights Reserved. Copyright © 2016, Yokogawa Electric Corporation GS 33J64E10-01EN June 1, 2016-00

<<Contents>> <<Index>>

EXTERNAL DIMENSIONS

Main power distribution board

AC

Unit: mm

DC

119

T9089KH

296.7

F2-03E.ai

Unit: mm

HKU interface unit

119

T9089KH

Figure Main power distribution board

296.7

F2-04E.ai

Unit: mm

10

73 45.5

73 30.5

For A2CUKT3-C

For A2CUKT3-N

F2-05E.ai

Figure HKU interface unit

Nominal tolerance:

Nominal tolerance is ± 0.8 mm for the dimensions of 0.5 mm or more and 120 mm or less, and the combined nominal tolerance is ± 1.5 mm.

The nominal tolerance is in accordance with JEM 1459 for the dimensions over 120 mm.

All Rights Reserved. Copyright © 2016, Yokogawa Electric Corporation GS 33J64E10-01EN Aug. 1, 2016-00

<<Contents>> <<Index>>

Node power distribution board

Unit: mm

FCU power distribution board

AC

49.6

135.6

F2-06E.ai

Figure Node power distribution board

DC

Unit: mm

11

49.6

135.6

49.6

141.9

F2-07E.ai

Figure FCU power distribution board (for A2CUKT3-C only)

Nominal tolerance:

Nominal tolerance is ± 0.8 mm for the dimensions of 0.5 mm or more and 120 mm or less, and the combined nominal tolerance is ± 1.5 mm.

The nominal tolerance is in accordance with JEM 1459 for the dimensions over 120 mm.

All Rights Reserved. Copyright © 2016, Yokogawa Electric Corporation GS 33J64E10-01EN June 1, 2016-00

<<Contents>> <<Index>>

FCU fan unit (with a built-in HKU)

Unit: mm

12

482.6

Figure FCU fan unit (with a built-in HKU) (for A2CUKT3-C only)

Fan power supply unit

Unit: mm

F2-08E.ai

45.2

170

Figure Fan power supply unit (for A2CUKT3-N only)

F2-09E.ai

Nominal tolerance:

Nominal tolerance is ± 0.8 mm for the dimensions of 0.5 mm or more and 120 mm or less, and the combined nominal tolerance is ± 1.5 mm.

The nominal tolerance is in accordance with JEM 1459 for the dimensions over 120 mm.

All Rights Reserved. Copyright © 2016, Yokogawa Electric Corporation GS 33J64E10-01EN June 1, 2016-00

<<Contents>> <<Index>>

HKU (for I/O expansion cabinet)

24.1

110.0

Unit: mm

13

F2-10E.ai

Figure HKU for I/O expansion cabinet (for A2CUKT3-N only)

Door fan flame (for I/O expansion cabinet)

Unit: mm

481 52

F2-11E.ai

Figure Door fan flame

Nominal tolerance:

Nominal tolerance is ± 0.8 mm for the dimensions of 0.5 mm or more and 120 mm or less, and the combined nominal tolerance is ± 1.5 mm.

The nominal tolerance is in accordance with JEM 1459 for the dimensions over 120 mm.

All Rights Reserved. Copyright © 2016, Yokogawa Electric Corporation GS 33J64E10-01EN June 1, 2016-00

<<Contents>> <<Index>>

Junction adaptor (for I/O expansion cabinet)

102.45

184.4

Unit: mm

14

F2-12E.ai

Figure Junction adaptor (for A2CUKT3-N only)

Nominal tolerance:

Nominal tolerance is ± 0.8 mm for the dimensions of 0.5 mm or more and 120 mm or less, and the combined nominal tolerance is ± 1.5 mm.

The nominal tolerance is in accordance with JEM 1459 for the dimensions over 120 mm.

STANDARD ACCESSORIES

Table Accessories for A2CUKT3

Part Name

Bolt

Nut

Band

Band

Part Number

G9307EM

S9062PB

B1003JB

S9072PB

Quantity

4 pcs

8 pcs

16 pcs

6 pcs

Remarks

M5

M5

SOFTWARE

The A2CUKT3 is supported by CENTUM VP R6.03 or later.

MODEL AND SUFFIX CODES

Cabinet Utility Kit (for RIO System Upgrade)

Description

Model

A2CUKT3

-C

-N

Suffix

Codes

1

2

1

2

4

0

Option

Code

/NHKU

Cabinet Utility Kit (for RIO System Upgrade)

For FCU with Cabinet (for A2FV70/HKU)

For I/O Expansion Cabinet (for ACB21)

Single power source

Dual power sources

100 - 120 V AC power supply

220 - 240 V AC power supply

24 V DC power supply

Basic type

Without HKU interface (*1)

Note: When upgrading the existing field control unit (AFE20, AFM20, AFH20, AFS20, or AFG20), specify “/HKU” on ordering A2FV70.

*1: “/HKU” can be selected in combination with the suffix code of “-N0”.

All Rights Reserved. Copyright © 2016, Yokogawa Electric Corporation GS 33J64E10-01EN June 23, 2016-00

<<Contents>> <<Index>>

15

ORDERING INFORMATION

When the A2FV70 field control unit is used in combination with the A2CUKT3 kit, specify the option code of “/HKU” when ordering the A2FV70.

When directly connecting the HKU (for I/O expansion cabinet) of the A2CUKT3-N with A2NN20D node interface unit, the suffix code of “-5” is required for ordering so that a connector for HKU is provided.

RELATED PRODUCTS

The following products are not included in the A2CUTK3. Please orders of these models/parts separately as necessary.

Product name

Fan unit

Air filter

Model/Part no.

AIP601

T9070CB

The following part is included in the A2CUTK3 as a standard accessory, however, in case a spare part is required, place an order by the following model/part no.

Product name

Terminal cover of main power distribution board

Power supply unit for FCU fan (100 - 120 V AC / 220 - 240 V AC)

Power supply unit for FCU fan (24 V DC)

Fan unit for FCU fan

Fan power supply unit (100 - 120 V AC / 220 - 240 V AC)

Fan power supply unit (24 V DC)

Model/Part no.

T9089KH

S9976FA

S9977FA

S9978FA

S9111FE

S9112FE

Note

— for

A2CUKT3-Cooo for

A2CUKT3-Nooo

All Rights Reserved. Copyright © 2016, Yokogawa Electric Corporation GS 33J64E10-01EN Mar. 20, 2017-00

<<Contents>> <<Index>>

3. Field Control Station (RIO System Upgrade)

INSTALLATION ENVIRONMENT

The following shows the applicable products and installation environment specifications.

Field Control Unit:

Node Interface Unit:

Cabinet Utility Kit:

A2FV70S, A2FV70D

A2NN10D, A2NN20D

A2CUKT3

Item

Ambient temperature

Ambient humidity

Ambient temperature change rate

Normal operating

Transporting

Normal operating

Transporting

Normal operating

Transporting

0 to 50 °C

-20 to 60 °C

5 to 95% RH (no condensation)

5 to 95% RH (no condensation)

Specifications

Within ± 10 °C/h

Within ± 20 °C/h

Power supply

Voltage range

Frequency

Distortion factor

Peak value

Instantaneous power failure

DC power supply ripple rate

Withstanding voltage

(between input and FG terminal)

Insulation resistance (between input and FG terminal)

100 - 120 V AC ±10%

220 - 240 V AC ±10%

24 V DC ±10%

50/60 ±3 Hz

10 % or less

125 V or more (100 V system)

274 V or more (220 V system)

20 ms or less (when receiving rated AC voltage)

1 % p-p or less

1500 V AC for 1 minute (100 V /220 V AC system)

500 V AC for 1 minute (24 V DC system)

20 MΩ at 500 V DC

Grounding

Dust

Corrosive gas

Vibration

Shock

Noise

Altitude

Continuous vibration

Earthquake

Transport vibration

Transport shock

Electric field

Magnetic field

Static electricity

The ground suitable for the power distribution system of the country or region has to be used for protective grounding system.

0.3 mg/m

3

or less

ANSI/ISA S71.04 G2

Displacement amplitude 0.25 mm or less (1 to14 Hz)

Acceleration 2.0 m/s

2

or less (14 to 100 Hz)

Acceleration 4.9 m/s

2

or less

Horizontal: 4.9 m/s

2

Vertical: 9.8 m/s

2

or less, vertical: 9.8 m/s

or less (packed state)

2

or less,

Horizontal: 49.0 m/s

2

Vertical: 98 m/s

2

or less,

or less (packed state)

3 V/m or less (26 M-1 GHz)

3 V/m or less (1.4 GHz - 2.0 GHz)

1 V/m or less (2.0 GHz - 2.7 GHz)

30 A/m or less (AC), 400 A/m or less (DC)

4 kV or less (contact discharge), 8 kV or less (aerial discharge)

2000 m or less

16

All Rights Reserved. Copyright © 2016, Yokogawa Electric Corporation GS 33J64E10-01EN June 1, 2016-00

<<Contents>> <<Index>>

17

The following shows the main applicable products and installation environment specifications.

They are supported by CENTUM VP R6.04 or later.

Node Interface Unit:

Base Plates for N-IO I/O:

24 V DC Output Power Supply Unit:

A2NN30D

A2BN4D, A2BN5D

A2PW503, A2PW504

Ambient temperature

Ambient humidity

Ambient temperature change rate

Power supply (*3) (*4)

Grounding

Dust

Corrosive gas

Vibration

Shock

Noise

Altitude

Item

Normal operating

Transporting/storing

Specifications

0 to 60 °C (A2NN30D, A2PW503, A2PW504)

-20 to 60 °C (A2BN4D (*1), A2BN5D (*1))

-40 to 70 °C (temperature option for A2NN30D (*2), A2PW503, A2PW504)

-20 to 60 °C (A2BN3D, A2NN30D, A2PW503, A2PW504, avoid direct sunlight)

-40 to 85 °C (A2BN4D (*1), A2BN5D (*1), temperature option for A2NN30D

(*2), A2PW503, A2PW504, avoid direct sunlight)

5 to 95 %RH (should have no condensation)

5 to 95 %RH (should have no condensation)

Normal operating

Transporting/storing

Normal operating

Transporting/storing

Voltage range

Within ±10 °C/h

Within ±20 °C/h

100 to 120 V AC -15 to +10 %

220 to 240 V AC -15 to +10 %

24 V DC -15 to +20 %

50/60 ±3 Hz

Frequency

Distortion factor

Peak value

10 % or less

118 V or more (100 V system)

258 V or more (220 V system)

Instantaneous power failure 20 ms or less (when receiving rated AC voltage)

DC power supply ripple rate 1 % p-p or less

The ground suitable for the power distribution system in the country or region has to be used for protective grounding system.

Continuous vibration

Non-continuous vibration

Earthquake

0.3 mg/m

3

or less

ANSI/ISA S71.04 G2 (standard)

ANSI/ISA S71.04 G3

(For A2BN4D and A2BN5D: standard)

(For others: environment-proof support (temperature environment support,

G3 support) options)

Displacement amplitude 1.75 mm or less (5 to 8.4 Hz)

Acceleration 4.9 m/s

2

or less (8.4 to 150 Hz)

Displacement amplitude 3.5 mm or less (5 to 8.4 Hz)

Acceleration 9.8 m/s

2

or less (8.4 to 150 Hz)

Acceleration 4.9 m/s

2

or less

Transport vibration

Transport shock

Horizontal 4.9 m/s

2

or less, vertical 9.8 m/s

2

or less (packed state)

Electric field

Magnetic field

Static electricity

147 m/s

2

or less, 11 ms

10 V/m or less (80 MHz to 1.0 GHz)

3 V/m or less (1.4 to 2.0 GHz)

1 V/m or less (2.0 to 2.7 GHz)

30 A/m or less (AC), 400 A/m or less (DC)

4 kV or less (contact discharge), 8 kV or less (aerial discharge)

3000 m or less (*5)

2000 m or less (A2BN4D, A2BN5D)

*1: To use A2BN4D or A2BN5D at -20 to 0°C, specify the temperature environment support option for the I/O modules to be mounted. The environment in which A2BN4D or A2BN5D is used depends on the specifications of the barrier mounting to

A2BN4D or A2BN5D.

*2: To maintain A2NN30D with the temperature environment support option (at -40 to 70°C), specify the temperature environment support option for the power supply units and N-ESB bus modules as well.

*3: Power supply specifications in the case of the Node Interface Unit (A2NN30D) installed in N-IO Node.

*4: For the power supply specifications for 24 V DC Output Power Supply Units (A2PW503 and A2PW504), refer to the GS “24

V DC Output Power Supply Units” (GS 33J62K51-01EN).

*5: When the Node Interface Unit (A2NN30D) with the following optical ESB bus specifications is used at an altitude of 2000 m or higher, the ambient temperature range is -40 to 60°C.

A2NN30D- 01 

A2NN30D-

A2NN30D-

11 

21 

A2NN30D- 02 

A2NN30D- 12 

A2NN30D- 22 

A2NN30D-

A2NN30D-

10 

20 

All Rights Reserved. Copyright © 2016, Yokogawa Electric Corporation GS 33J64E10-01EN June 1, 2017-00

<<Contents>> <<Index>>

18

COMMUNICATION SPECIFICATIONS

Item

Bus type

Number of connectable nodes

(/FCU)

CENUTM CS/CS1000/

CS3000/VP

RIO system

RIO Bus

RIO node: Max. 8

N-ESB Bus

CENTUM VP for RIO System Upgrade

Optical ESB Bus

N-IO node (*1): Max. 8

ESB Bus

FIO node (*2): Max. 8

Network topology Chain connection only

Star connections:

Max. 8 lines

Chain connections:

Max. 8 rows

Star connections:

Max. 8 lines

Chain connections:

Max. 2 rows

Star connections:

Max. 2 lines

Chain connections:

Max. 8 rows

Transmission redundancy

Transmission speed

Transmission cable

Transmission distance

Dual-redundant or Single Dual-redundant only

2 Mbps

Twisted pair cableC or

Optical fiber cable

Twisted pair cable :

Max. 750 m

Optical fiber cable :

Max. 4 km

100 Mbps

UTP straight cable of

CAT5e

Max. 100 m

Dual-redundant only

192 Mbps

Optical fiber cable

Max. 50 km

Dual-redundant only

128 Mbps

Dedicated cable

(YCB301)

Max. 10 m

*1: An N-IO node refers to an I/O node consisting of a Node Interface Unit (for RIO system upgrade) [A2NN10D, A2NN20D,

A2NN30D].

*2: The FIO node refers to an I/O node consisting of a Node Unit for Dual-Redundant ESB Bus (ANB10D) or a Node Unit for

Dual-Redundant ESB Bus with Optical Repeater (ANB11D).

Cable Specifications

UTP straight cable:

Connector: RJ45 connector (ISO/IEC8877 compliant)

Recommended cable: CAT5e (enhanced category 5) or better (ANSI Standard TIA/EIA-568-B compliant)

Optical fiber cable:

LC (compliant with IEC61754-20)

0 to 10 [email protected] μm

3 to 16 [email protected] μm (*1)

Quartz single-mode optical fiber (*2)

2

50 km

Optical fiber specifications

Optical connector type

Max. Permissible

Optical Loss

5 km

5-50 km

Optical fiber

Type

Required number of cores

Max. Length

*1: When the optical attenuation in the following connections is less than 3 dB, use an attenuator to reduce the attenuation by 3 dB.

Between ANT411-E and A2NN10D-2

Between ANT411-F and A2NN10D-2

Between A2NN10D-2 and A2NN10D-2

Between A2NN10D-2 and ANT512-E

Between A2NN10D-2 and ANT512-F

Between ANT411-E and A2NN20D-2

Between ANT411-F and A2NN20D-2

Between A2NN20D-2 and A2NN20D-2

Between A2NN20D-2 and ANT512-E

Between A2NN20D-2 and ANT512-F

*2: JIS C 6835 SSMA -9.3/125 or IEC 60793-2-50 B1.1 type

INSTALLATION OF COMMUNICATION MODULE AND BUS INTERFACE MODULE

When installing a communication module or a bus interface module to the ANB10D/ANB11D node unit or the optical

ESB node unit, refer to the GS of “N-IO System Overview” (GS33J62A10-01EN).

All Rights Reserved. Copyright © 2016, Yokogawa Electric Corporation GS 33J64E10-01EN June 1, 2017-00

<<Contents>> <<Index>>

4. Applicable Standards

Refer to the General Specifications of “Integrated Production Control System CENTUM VP System Overview” (GS

33J01A10-01EN).

19

5. Trademarks

• CENTUM is a registered trademark of Yokogawa Electric Corporation.

• Other company and product names appearing in this document are trademarks or registered trademarks of their respective holders.

All Rights Reserved. Copyright © 2016, Yokogawa Electric Corporation

Subject to change without notice.

GS 33J64E10-01EN June 1, 2017-00

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals

advertisement