Fundamentals of Grid Connected Photo-Voltaic Power
Fundamentals of Grid Connected
Photo-Voltaic Power Electronic
Converter Design
Svein Erik Evju
Master of Science in Energy and Environment
Submission date: June 2007
Supervisor:
Lars Einar Norum, ELKRAFT
Norwegian University of Science and Technology
Department of Electrical Power Engineering
Problem Description
The goal of this master thesis is to design a power electronic converter for use with solar power
systems. The converter is meant to be used in the renewable energy laboratory at NTNU. It should
be focused on the overall system, and the design should therefore be made with basic
solutions in order to make the complexity low. In order to make this design, a literature study
giving an overview of photo-voltaic systems and the power electronic converters used should be
made. The study shall focus on both the hardware configurations, but also the control of these
systems. To verify the theoretical studies made, simulations and experimental tests of the system
should be made.
Assignment given: 22. January 2007
Supervisor: Lars Einar Norum, ELKRAFT
Fundamentals of Grid Connected Photo‐Voltaic Power Electronic Converter Design
I
ACKNOWLEDGEMENTS
In this report the efforts of obtaining a masters degree in electrical power engineering at
the Norwegian University of Science and Technology (NTNU) is concluded. The project
which deals with the electrical conversion of power from solar panels was initiated by my
supervisor Lars Norum at the department of electric power conversion. The project is a part
of the integration of solar power in the renewable energy laboratory at NTNU, and
hopefully it can contribute giving some basic understanding of the processes involved in the
power conversion.
The first formulation of the scope for this project was very widely defined, and this gave me
the opportunity to influence the extent and the content of the work in a large degree. At
first the assignment was supposed to have a major focus on control of photo‐voltaic
converters, but because there was need for a DC‐DC converter, the design and construction
of this also became a large part of the thesis. During the work with this thesis there has been several people who has helped me when
things stopped up and given me a different point of view of things. I would first of all like to
thank my supervisor Lars Norum for giving me good ideas and helping me formulate the
thesis. When things stopped up in the laboratory i got lots of helpful tips from PhD student
Pål Andreassen, so a big thanks to him for letting me bother him with all sorts of strange
problems. I would also like to thank my fellow students at the department for support and
encouragement during the last 6 months. Last but not least I have to give a great thanks to my girlfriend Inger who has been home
with our son Emre during my work with this thesis. You have been a great support, and you
have given me the freedom to spend the time I needed on this thesis. So thanks for coping
with almost being a single parent for the last few months of this work.
13 June 2007
Svein Erik Evju
Acknowledgements
II
NTNU Department of Electric Engineering
TABLE OF CONTENTS
1
INTRODUCTION 1
2
OVERVIEW OF PHOTO VOLTAIC SYSTEMS AND CONVERTERS 2
2.1 Grid connection standards .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. 2
2.1.1 Converter requirements . . . . . . . . . . . . . . . . . . . . . . . . . . 3
2.2 Solar Cell Characteristics . .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. 7
2.2.1 PV panel modelling. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
2.3 Solar panel and converter configurations .. .. .. .. .. .. .. .. .. .. .. . 11
2.4 Converter topologies .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. . 13
2.4.1 Transformer. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
2.4.2 DC‐DC converter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
2.4.3 DC‐AC inverter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
2.5 Grid filter topologies .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. . 18
2.5.1 L‐filter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
2.5.2 LC and LCL‐filter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
2.6 Temporary storage .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. . 20
3
CONTROL OF PHOTO‐VOLTAIC CONVERTERS 21
3.1 Maximum power utilization of photo voltaic power sources .. .. .. . 21
3.1.1
3.1.2
3.1.3
3.1.4
3.1.5
Constant voltage (CV) . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Perturb and observe (P&O) . . . . . . . . . . . . . . . . . . . . . . . 21
Incremental conductance (INC) . . . . . . . . . . . . . . . . . . . . . 22
Parasitic Capacitance (PC) . . . . . . . . . . . . . . . . . . . . . . . . 23
Efficiency of the MPPT techniques . . . . . . . . . . . . . . . . . . . 23
3.2 DC‐DC Converter Control. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. . 24
3.3 DC‐AC Converter control . .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. . 25
3.3.1
3.3.2
3.3.3
3.3.4
3.3.5
Transformations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Pulse Width Modulation (PWM) . . . . . . . . . . . . . . . . . . . . 29
PI Controllers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
PR controllers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
State feedback controller . . . . . . . . . . . . . . . . . . . . . . . . 33
3.4 Harmonic compensation . .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. . 33
3.5 Grid synchronisation .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. . 34
3.5.1
3.5.2
3.5.3
3.5.4
Filtered Zero Cross Detection (ZCD) . . . . . . . . . . . . . . . . . . 34
Filtering of grid voltages . . . . . . . . . . . . . . . . . . . . . . . . . 35
Phase Lock Loop (PLL) . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Adaptive PLL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
3.6 Anti Islanding .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. . 37
3.6.1 Passive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
3.6.2 Active . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
3.7 Digital Signal Processing .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. . 38
3.7.1
3.7.2
3.7.3
3.7.4
Table of contents
DSP program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Measurements and analog to digital conversion . . . . . . . . . . . 42
Discretization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Discrete filtering . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Fundamentals of Grid Connected Photo‐Voltaic Power Electronic Converter Design
III
3.7.5 Discrete PI Regulator . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
3.8 P&O algorithm optimization .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. . 44
3.8.1 Minimum time step. . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
3.8.2 Minimum duty cycle step . . . . . . . . . . . . . . . . . . . . . . . . 45
3.9 PLL PI controller Optimization .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. . 46
3.10 Voltage and current controller optimization. .. .. .. .. .. .. .. .. .. . 47
3.10.1 Modulus optimum . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
3.10.2 Symmetrical optimum . . . . . . . . . . . . . . . . . . . . . . . . . . 51
4
SYSTEM DESCRIPTION, MODELLING AND OPTIMIZATION 55
4.1 Converter topology and control description . .. .. .. .. .. .. .. .. .. . 55
4.1.1 DC‐DC converter values . . . . . . . . . . . . . . . . . . . . . . . . . 56
4.1.2 DC‐AC converter and LCL filter values. . . . . . . . . . . . . . . . . . 56
4.1.3 Laboratory setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
4.2 P&O Maximum Power Point Tracker optimization .. .. .. .. .. .. .. . 58
4.3 Phase Locked Loop PI Regulator. .. .. .. .. .. .. .. .. .. .. .. .. .. .. . 60
4.3.1 Model . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
4.3.2 Optimization. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
4.4 Current Regulator .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. . 64
4.4.1 Model . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
4.4.2 Optimization. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
4.5 Voltage controller .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. . 70
4.5.1 Model . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
4.5.2 Optimization. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
4.6 Complete control system model .. .. .. .. .. .. .. .. .. .. .. .. .. .. . 76
5
SIMULATION 77
5.1 DC‐DC Converter.. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. . 77
5.1.1 I‐V Characteristic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
5.1.2 Maximum Power Point Tracker . . . . . . . . . . . . . . . . . . . . . 79
5.2 DC‐AC Converter simulation results .. .. .. .. .. .. .. .. .. .. .. .. .. . 81
5.2.1
5.2.2
5.2.3
5.2.4
6
PLL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
Current control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
Voltage control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
The LCL filter. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
EXPERIMENTAL RESULTS 87
6.1 DC‐DC Converter.. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. . 87
6.1.1 MPPT. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
6.2 DC‐AC Converter.. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. . 87
6.2.1
6.2.2
6.2.3
6.2.4
7
PLL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
Current control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
Voltage control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
LCL‐filter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
DISCUSSION, CONCLUSION AND FURTHER WORK 93
7.1 Discussion. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. . 93
Table of contents
IV
NTNU Department of Electric Engineering
7.1.1
7.1.2
7.1.3
7.1.4
7.1.5
7.1.6
7.1.7
DC‐DC converter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
MPPT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
PLL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
Current control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
Voltage control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
LCL filter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
The overall system . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
7.2 Conclusion .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. . 98
7.3 Proposed further work .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. . 99
LITERATURE 100
References .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. 100
Bibliography . .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. 102
APPENDIX 1
2
3
4
5
6
103
DC‐DC converter Analysis .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. 1
LCL Filter .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. ..19
System rating .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. ..24
Magnetic design .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. ..36
Brief Description of Converter Simulation .. .. .. .. .. .. .. .. .. .. ..41
DC‐DC Converter Problems . .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. ..49
Table of contents
Fundamentals of Grid Connected Photo‐Voltaic Power Electronic Converter Design
V
LIST OF TABLES
Table 2.1 ‐Voltage operating range ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. 4
Table 2.2 ‐Flicker limits ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. 4
Table 2.3 ‐Harmonic current limits . ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. 5
Table 2.4 ‐Power factor limits ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. 6
Table 2.5 ‐Comparison of DC‐DC converters ([7]) .. ... ... ... ... ... ... ... ... ... ... ... ... 16
Table 2.6 ‐Loss comparison dc‐dc converters ([7]) (Full bridge is reference, with loss in pu) . ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... 16
Table 3.1 ‐Efficiency of the MPPT methods [11] ... ... ... ... ... ... ... ... ... ... ... ... ... 24
Table 4.1 ‐DC‐DC Converter component values ... ... ... ... ... ... ... ... ... ... ... ... ... 56
Table 4.2 ‐DC‐DC operating conditions ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... 56
Table 4.3 ‐DC‐AC Converter and LCL filter component values .. ... ... ... ... ... ... ... ... 57
Table 4.4 ‐DC‐AC converter and LCL filter operating conditions ... ... ... ... ... ... ... ... 57
Table 4.5 ‐Equipment in laboratory setup ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... 57
Table 3.1 ‐Component list ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... 29
Table 3.2 ‐HF Transformer leakage inductance and resistance at 50kHz ... ... ... ... ... 30
Table 3.3 ‐Test Points on DC‐DC converter ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... 30
Table 3.4 ‐LCL filter specifications .. ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... 35
Table 3.5 ‐Component list LCL‐filter ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... 35
List of tables
VI
NTNU Department of Electric Engineering
LIST OF FIGURES
Figure 2.1:
Figure 2.2:
Figure 2.3:
Figure 2.4:
Figure 2.5:
Figure 2.6:
Figure 2.7:
Figure 2.8:
Figure 2.9:
Figure 3.1:
Figure 3.2:
Figure 3.3:
Figure 3.4:
Figure 3.5:
Figure 3.6:
Figure 3.7:
Figure 3.8:
Figure 3.9:
Figure 3.10:
Figure 3.11:
Figure 3.12:
Figure 3.13:
Figure 3.14:
Figure 3.15:
Figure 4.1:
Figure 4.2:
Figure 4.3:
Figure 4.4:
Figure 4.5:
Figure 4.6:
Figure 4.7:
Figure 4.8:
Figure 4.9:
Figure 4.10:
List of figures
I‐V characteristic of a solar cell as irradiance decreases . ... ... ... ... ... ... .. 7
I‐V characteristic of a solar cell as temperature increases... ... ... ... ... ... .. 8
P‐V characteristic of a solar cell ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. 9
Historical overview of PV converters. (a) Past centralized technology. (b) Present string technology. (c) Present and future multi‐string technology. (d) Present and future AC‐module and AC cell technologies. ... ... ... ... ... ... 12
PV converter topologies [7].. ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... 13
The full bridge isolated boost (FB), the single‐inductor boost push‐pull (SIC) and the dual‐inductor boost push‐pull (DIC) DC‐DC converter [7]. ... ... ... 15
The instantaneous power in the three phases, and the sum of these powers as the solid line . ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... 17
Full bridge VSI ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... 18
LCL filter model with damping and inductor resistance.. ... ... ... ... ... ... 20
Flow chart of the P&O algorithm [7] .. ... ... ... ... ... ... ... ... ... ... ... ... 22
Flow chart of the INC algorithm [7] ... ... ... ... ... ... ... ... ... ... ... ... ... 23
Direct duty‐cycle control strategy for DC‐DC converter.. ... ... ... ... ... ... 24
Peak switch current control strategy for DC‐DC converter.. ... ... ... ... ... 25
Abc to ab transformation ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... 27
ab to dq transformation .. ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... 28
Generation of Carrier Based PWM signals [31] ... ... ... ... ... ... ... ... ... 30
Space vector representation of output voltage. [31] . ... ... ... ... ... ... ... 30
A basic PLL circuit... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... 35
Schematic of a phase lock loop (PLL) with transformations ... ... ... ... ... 36
Flow chart of superior control with state machine ... ... ... ... ... ... ... ... 41
Frequency response of a modulus optimized control loop.. ... ... ... ... ... 50
Step response of modulus optimized control loop ... ... ... ... ... ... ... ... 51
Frequency response of asymmetrical optimized control loop.. ... ... ... ... 53
Step response of symmetrical optimized control loop ... ... ... ... ... ... ... 54
The basic converter topology ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... 55
Schematic of laboratory setup .. ... ... ... ... ... ... ... ... ... ... ... ... ... ... 58
PLL model ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... 60
Bode plot of transfer function between input and output
Blue dotted: Discretized system
Red continuous: Continuous system .. ... ... ... ... ... ... ... ... ... ... ... ... 62
Bode plot of transfer function between input and error
Blue dotted: Discretized system
Red continuous: Continuous system .. ... ... ... ... ... ... ... ... ... ... ... ... 63
Step response of the continuous and the discrete transfer function, MC(s) and MC(z)
Blue: Discretized system
Red: Continuous system .. ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... 63
Pole‐zero plot of the discrete transfer function MC(z) ... ... ... ... ... ... ... 64
D‐axis current control loop (similar for q‐axis). ... ... ... ... ... ... ... ... ... 64
Reduced current control model ... ... ... ... ... ... ... ... ... ... ... ... ... ... 67
Bode diagram of continuous and discretized closed loop models of the inner control loop
Blue dotted: Discretized system
Fundamentals of Grid Connected Photo‐Voltaic Power Electronic Converter Design
Figure 4.11:
Figure 4.12:
Figure 4.13:
Figure 4.14:
Figure 4.15:
Figure 4.16:
Figure 4.17:
Figure 4.18:
Figure 5.1:
Figure 5.2:
Figure 5.3:
Figure 5.4:
Figure 5.5:
Figure 5.6:
Figure 5.7:
Figure 5.8:
Figure 5.9:
Figure 5.10:
Figure 6.1:
Figure 6.2:
Figure 6.3:
Figure 6.4:
Figure 6.5:
Figure 6.6:
Figure 1.1:
Figure 1.2:
Figure 1.3:
List of figures
VII
Red continuous: Continuous system .. ... ... ... ... ... ... ... ... ... ... ... ... 69
Step response of the discrete and the continuous time model of the inner con‐
trol loop ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... 69
Pole‐zero plot of the discretized closed loop system . ... ... ... ... ... ... ... 70
DC‐link voltage control loop . ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... 70
Bode diagram of the 1.order approximation compared to the 2.order original system
Red: 2.order original system
Blue: 1.order approximation ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... 72
Bode plot of the continuous and discrete voltage control loop
Red continuous: Continuous system
Blue dotted: Discrete system ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... 74
Continuous and discrete step response of the voltage control loop.. ... ... 75
Pole‐Zero plot of the discrete voltage controller... ... ... ... ... ... ... ... ... 75
Overview of the control system of the DC‐DC converter and the DC‐AC con‐
verter .. ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... 76
GUI of the PV‐panel I‐V characteristic under STC .. ... ... ... ... ... ... ... ... 77
GUI of the PV‐panel I‐V characteristic under partial shadowing ... ... ... ... 78
Duty‐cycle steps due to the MPPT . ... ... ... ... ... ... ... ... ... ... ... ... ... 79
PV voltage, current and power during MPP. ... ... ... ... ... ... ... ... ... ... 80
Simulation of PLL with a start‐up angle of and a phase jump of at 20ms. . 81
Step response of d‐ and q‐ axis current with parameters found by modulus op‐
timization. ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... 82
DC‐link voltage step response after a ‐2V step at 55ms.. ... ... ... ... ... ... 83
LCL filter current and voltage. From top: converter inductor voltage, grid in‐
ductor voltage, capacitor voltage, converter inductor current and grid inductor current ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... 84
Harmonic spectrum of grid side inductor current, from 0 to 1650Hz ... ... 85
Harmonic spectrum of grid side inductor current, from 0 to 50kHz .. ... ... 86
Red: Phase locked frequency in PU
Blue: Phase locked angle in PU
Green: PLL PI controller error ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... 88
Step response of the d‐ and q‐axis current to a step from 0.1 to 0.7pu in the current reference. Blue: d‐axis current
Green: q‐axis current .. ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... 89
Step response in the voltage control loop. .. ... ... ... ... ... ... ... ... ... ... 90
Voltage in the LCL filter inductances during steady state
Blue: Inverter side inductor current
Purple: Grid side inductor current . ... ... ... ... ... ... ... ... ... ... ... ... ... 91
Voltage across the LCL filter elements during steady state
Yellow: Inverter side inductor voltage
Purple: Capacitor voltage
Blue: Grid side inductor voltage ... ... ... ... ... ... ... ... ... ... ... ... ... ... 91
Harmonic spectrum in % of fundamental current for three different PWM methods... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... 92
Schematic of DC‐DC converter .. ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. 1
DC‐DC switching scheme . ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. 1
Voltage over primary side of HF transformer, and inductor current and volt‐
VIII
Figure 1.4:
Figure 1.5:
Figure 2.1:
Figure 3.1:
Figure 3.2:
Figure 3.3:
Figure 4.1:
Figure 5.1:
Figure 5.2:
Figure 5.3:
Figure 5.4:
Figure 5.5:
Figure 5.6:
Figure 5.7:
Figure 5.8:
Figure 6.1:
Figure 6.2:
Figure 6.3:
Figure 6.4:
Figure 6.5:
Figure 6.6:
Figure 6.7:
Figure 6.8:
Figure 6.9:
Figure 6.10:
List of figures
NTNU Department of Electric Engineering
age.. ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. 2
Equivalent circuit to the small signal AC equations ... ... ... ... ... ... ... ... 11
Simplified equivalent circuit to the small signal AC equations . ... ... ... ... 11
LCL filter model . ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... 19
Boost inductor as function of the PV voltage ... ... ... ... ... ... ... ... ... ... 27
PV condensator as function of PV voltage ... ... ... ... ... ... ... ... ... ... ... 28
LCL filter with damping resistor ... ... ... ... ... ... ... ... ... ... ... ... ... ... 32
Partitioning of the transformer windings ... ... ... ... ... ... ... ... ... ... ... 39
The three main blocks in the simulink model ... ... ... ... ... ... ... ... ... ... 41
Content of measurement and acquisitions block .. ... ... ... ... ... ... ... ... 42
Content of control block.. ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... 43
Content of plant block ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... 44
The four main blocks in the simulink model ... ... ... ... ... ... ... ... ... ... 45
Content of measurement and acquisitions block .. ... ... ... ... ... ... ... ... 46
Content of Control_DCDC_Converter block. ... ... ... ... ... ... ... ... ... ... 47
Content of plant block ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... 48
Transformer equivalent circuit with a resistive load, and a switched current source at the input. ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... 49
Transformer primary voltage with leakage spike. In the positive pulse two di‐
agonal switches without snubber is turned off, and in the negative pulse two switches with a RC snubber is turned off. ... ... ... ... ... ... ... ... ... ... ... 50
Full bridge boost converter with a passive clamp circuit ... ... ... ... ... ... 51
Left: High load (low resistance)
Right: Low load (high resistance)
Yellow: Switch signal, Blue: Inductor voltage, Purple: Primary voltage, Green: Primary current . ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... 52
Left: High load (low resistance)
Right: Low load (high resistance)
Yellow: Switch signal, Blue: Inductor voltage, Purple: Secondary voltage, Green: Secondary current ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... 53
Simplified transformer equivalent circuit with a resistive load, and a switched current source at the input .. ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... 53
Currents in transformer after the switch is turned on for a finite time .. ... 54
Gate drive ripple, right scope is a close up of the left during the gate ripple.
Yellow: Gate signal lower left switch, Blue: Transformer primary current 2mA/
mV, Purple: Gate signal upper left gate, Green: Voltage across bridge .. ... 55
Equivalent circuit of converter during a positive duty cycle step.. ... ... ... 56
Step response after perturbing the duty cycle
Red: Current in boost inductor
Blue: Voltage DC‐link .. ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... 57
Fundamentals of Grid Connected Photo‐Voltaic Power Electronic Converter Design
IX
ACRONYMS
ADC
‐
Analog to Digital Converter
CB‐PWM‐ Carrier Based PWM
CC Current Control
‐ CCM ‐ Continuous Conduction Mode
CV Constant voltage
‐ DCM ‐
Discontinuous Conduction Mode
DPWM‐
Discontinuous modulation PWM
DSP
‐
Digital Signal Processor
FFT
‐
Fast Fourier Transform
GI
‐
Generalized Integrators
GUI
‐
Graphical User Interface
HF ‐
High Frequency
INC ‐
Incremental conductance
LF ‐
Low Frequency
MPP ‐
Maximum Power Point
MPPT ‐
Maximum Power Point Tracking
NDZ
Non Detection Zone
PCC ‐
‐
Point of Common Coupling (The point where a local EPS is connected to an
area EPS)
PLL ‐
Phase Lock Loop
PR
‐
Proportional Resonant
PV ‐ Photo Voltaic
PWM ‐
Pulse Width Modulation
P&O ‐
Perturb and observe
STC
‐
Standard Test Conditions
SVM ‐
Space Vector Modulation
SVPWM‐
Symmetrical SVM
VC ‐
Voltage Control
VSI ‐
Voltage Source Inverter
ZCD ‐
Filtered Zero Cross Detection
ZSS
Zero Sequence Signal
‐
Acronyms
X
NTNU Department of Electric Engineering
PARAMETER DEFINITIONS
C f - LCL filter capacitance
ISC - PV short circuit current
Li - LCL filter inverter side inductance
Lg - LCL filter grid side inductance
(
ma - modulation ratio Vˆ control /Vˆ tri
)
n - transformer winding ratio
Rd - LCL filter damping resistance
VDC - DC-link voltage
VMPP - PV voltage at maximum power point
VN0 - Voltage between inverter neutral and load neutral
VOC - PV open circuit voltage
VPV - Voltage of the PV module
Parameter definitions
Fundamentals of Grid Connected Photo‐Voltaic Power Electronic Converter Design
XI
ABSTRACT
In this master thesis the basic theory of grid connected photo‐voltaic systems is explained,
giving an introduction to the different aspects of system design. Starting with a look at the
standards concerning grid connection of distributed resources, and working its way through
how the photo‐voltaic cells work, to how photo‐voltaic modules with electrical converters
can be arranged. Some different converter topologies suitable for use with photo‐voltaics
are found, and based on these topologies, solutions for how to control these converters
have been examined. These controls involve methods for utilizing the maximum power
from solar panels, methods for synchronizing with the grid and methods for current and
voltage control. Based on this theory a system model is made, including an isolated current fed full bridge
DC‐DC converter in cascade with a three phase full bridge DC‐AC converter having a LCL filter
as grid interface. This model is simulated in Simulink and experiments are made on a
laboratory setup, where focus has been on the control system. Therefore linear system
models of the control system has been made, and these have formed a basis for the
optimization of the control systems. The simulations have been made using Simulink, and
the control system for the converters has been implemented in two DSP’s, one for each
converter.
The design and construction of the DC‐DC converter has been made in this thesis, but it
showed out to be more complicated then first assumed. Because of this, too little time was
spent in the design of the circuit and too much time was spent on testing and correcting
errors. It ended with a non‐functional converter, and therefore the experiments made had
to be done without the DC‐DC converter. However the report shows that the isolated
current fed full bridge DC‐DC converter is a promising topology in photo‐voltaic systems,
and should be investigated closer.
It is found in the simulations and experiments made, that the system models derived give
a dynamic response close to the real, and are suitable for giving a basic understanding of
the system dynamics and for optimizing the control system. The control system consists of
a maximum power point tracker which effectively finds the point where the photo‐voltaic
modules delivers the highest power, and in order to synchronize to the grid voltage a phase
locked loop is used, which locks the converter output to the grid voltage in less then 10ms.
In order to control the power flow into the grid, current control in a rotating reference
frame locked to the grid voltage is used. This has simplified the control since it gives DC‐
values stationary, and has made it possible to separately control the active and reactive
power flow. Most of the tests made in the simulations and experiments have been made with operating
conditions close to ideal. In order to verify how the system handles varying operating
conditions, and to see if it coincides with the requirements in the standards, more extensive
testing should be made of the system. This includes testing with varying irradiance of the
solar panels, grid disturbances and grid failures. Abstract
1
NTNU Department of Electric Engineering
1 INTRODUCTION
This master thesis deals with the connection of photo‐voltaic power sources to the
electrical grid. Today photo‐voltaics has become one of the major renewable energy
sources in the world, and in order to utilize the energy from this power source, electrical
converters is needed. This study is meant as an introduction to the design of grid connected
photo‐voltaic electrical power converters, and it has been written for the Department of
Electric Power Engineering at NTNU.
The study shall give an overview of the different aspects of designing an electrical
converter. By taking the reader through the basics of what characterizes a photo‐voltaic
system and which requirements is put upon such a system, the report aims on giving a
fundamental understanding of how to supply the energy from the solar panels into an
electrical grid. The theory shall then be put to the test by finding a representative system
model, and then simulating it and test it on an experimental setup. Chapter 2 introduces photo‐voltaic systems and has focus on the characteristics of solar
cells, and how they are arranged. Standards dealing with the interconnection of PV power
sources and the electrical grid are reviewed, and the last part of this chapter describes
different converter topologies, with filters and temporary storage alternatives. Chapter 3 describes different ways to control the converters. Methods for utilizing the
maximum power from the solar panels, methods for controlling the energy flow into the
grid is explained, and some methods for synchronizing the converter output with the grid
voltage is presented. An introduction to islanding detection is given, and to the
implementation of a digital control system is also given. Last in this chapter it is explained
how to optimize the control systems used in this thesis. Chapter 4 gives a description of the system used in the simulations and the laboratory setup
used in this project. It describes what sort of control, and which hardware have been used.
Based on this models for the control system is found based on linear system theory, and the
control systems are optimized using the methods described in chapter 3. Chapter 5 and 6 describes the results of the simulations and the experiments which have
been made. The tests have focus on verifying the models made of the control system, but
also a harmonic analysis will be made in order to verify the quality of the power delivered
to the grid. Chapter 7 concludes the thesis with a discussion of the most important aspects of this
thesis, and ends up with a conclusion and suggestions for further work
Chapter 1 Introduction
Fundamentals of Grid Connected Photo‐Voltaic Power Electronic Converter Design
2
2 OVERVIEW OF PHOTO VOLTAIC SYSTEMS AND CONVERTERS
In the resent years there has been a large increase in the interest for renewable energy. This
is due to an increasing need for energy, increasing power prices and the need for more
environmental friendly power sources. A consequence of this is an enormous amount of
new renewable energy projects. Renewable energy sources are often small (compared to
traditional energy production), and they are often spread around the utility network,
therefore they are often termed distributed resources, and includes sources like solar, wind
and wave power.
Solar power generated from photo‐voltaic (PV) cells is gaining increased importance as a
renewable source due to advantages such as the absence of fuel cost, little maintenance
and no noise and wear due to absence of moving parts. So in theory this is an ideal power
source, but in practice there are several problems that needs to be addressed. There is still
a high installation cost, low energy conversion efficiency and issues concerning the
interaction with other systems.
The energy from PV panels is in the form of DC‐current, and in order to utilize this energy
in the grid, the current must be transformed into AC‐current. The most convenient way to
to this is by the use of electric power converters. Using these converters as a grid interface
for PV panels is not a new technology, and much of the same technology is used in e.g. fuel
cell converter, wind power converters and also converters for motor drives. Even though
they use much of the same technology, there are always some special considerations for
the different cases.
In this chapter the standards concerning the connection of distributed resources to the grid,
and which requirements this has on the system design is examined. Next the characteristics
of photo‐voltaic power will be introduced, and different converter and solar panels
structures will be shown.
2.1 Grid connection standards
Before designing a converter for grid connection of photo‐voltaic power sources, an
overview of which rules and regulations one must follow in order to be allowed to connect
to the grid should be investigated. These rules will however not be the same all over the
world. Depending on the grid type there are different considerations to be made in each
country, and therefore there will always be some adaption to the demands from the local
utilities. The demands from the local utilities are usually based on a national standard or
international standard which deals with the interconnection of distributed resources.
These standards are often very similar, but they might have some variations in the degree
of limitations and in the definitions used. By looking at the standards from two of the major
international standardisation organizations listed below, an overlook of the most important
demands and limitations can be found. • International Electrotechnical Commission ‐ IEC
Chapter 2 Overview of Photo Voltaic Systems and Converters 3
NTNU Department of Electric Engineering
• Institute of Electrical and Electronics Engineers ‐ IEEE
When developing a PV system there is a risk that even though all current standards are
followed, there are new ones released before or right after the product is released, and the
product will become outdated. A major goal when designing a new converter is to make it
compatible with current standards, but also future standards. Below is a list of the most
recent standards of interest from IEC and IEEE.
• IEEE Std 1547‐2003 [1]: Standard for Interconnecting Distributed Resources with
Electric Power Systems
• IEC 61727 Second Edition 2004‐12 [2]: Photovoltaic (PV) systems ‐ Characteristics of the
utility interface.
IEEE has also released a recommended practice document especially for grid connection of
photovoltaic cells, this states mostly the same as [1]
• IEEE STD 929‐2000 [3]: Recommended Practice for Utility Interface of Photovoltaic (PV)
Systems
2.1.1 Converter requirements
Based on the international standards mentioned above a list of requirements for the design
of a converter can be made. Below is a list of requirements which should be followed when
designing a converter in order to make it coincide with the standards.
Grounding
It should be possible to connect the negative pole of the PV panels to ground.
Power Quality
The quality of the power provided by the PV system for the on‐site loads and the power
delivered to the utility is governed by practices and standards addressing voltage, DC‐
injection, flicker, frequency, distortion/harmonics and power factor. These parameters
must, unless otherwise is specified, be measured at the point of common coupling (PCC).
1. Voltage
Grid connected PV systems do not normally control the voltage of the connected grid,
they merely inject current into it, therefore there is usually not any active voltage
control. On the other hand there has to be a certain voltage operating range where
the inverter is allowed to work, in order to detect abnormal utility conditions and
prevent islanding mode. The inverters response to abnormal voltages is specified in
table 2.1.
Chapter 2 Overview of Photo Voltaic Systems and Converters Fundamentals of Grid Connected Photo‐Voltaic Power Electronic Converter Design
4
Table 2.1 ‐ Voltage operating range
Voltagea
Maximum trip timeb
V < 50%
0,1s
50% ≤ V < 85%
2,0s
85% ≤ V ≤ 110%
Continuous operation
110% < V < 135%
2,0s
135% ≤ V
0,05s
a. Limits are in % of the nominal voltage at PCC in RMS.
b. Trip time refers to the time between the abnormal condition occurring and the inverter ceasing to energize the utility line.
Within the specified trip times the inverter must cease to energize the grid, but the
PV control circuits shall remain connected to the grid to allow sensing of the electrical
conditions. The latter for use by a reconnection feature. Unless the voltage is
measured at the PCC, the voltage drop between the inverter and the PCC must be
taken into considerations. For further information on voltage operating range see IEC
61727 §5.2.1 and IEEE 929 §4.1
2. DC‐injection
The inverter shall not inject DC current >0.5% of rated inverter output current into the
utility AC interface under any operating condition. For further information on DC‐
injection see IEC 61727 §4.4 and IEE 929 §5.2
3. Flicker
Only IEC 61727 gives specific limits for flicker, thus these will be used. This standard
states that the amount of flicker must comply with IEC 61000‐3‐3 §4 and IEC 61000‐
3‐5. The flicker limits stated in these standards are approximately equal, so the limits
in table 2.2 can be used for all system sizes. For the calculation of the amount of
flicker the reader is referred to the standards.
Table 2.2 ‐ Flicker limits
Limits Psta
Limits Pltb
≤ 1.0
≤ 0.65
a. Pst is the short term flicker indicator. This is the flicker severity evaluated over a short period (i minutes), where Pst=1 is the conventional threshold of irritability
Chapter 2 Overview of Photo Voltaic Systems and Converters 5
NTNU Department of Electric Engineering
b. Plt is the long term flicker indicator. This is the flicker severity evaluated over a long period (a few hours) using successive Pst values.
4. Frequency
The PV system must operate in synchronism with the grid voltage. If the frequency
deviates outside of the specified condition, the converter shall cease to energize the
grid within a specified time. The allowed operating frequency and trip time differs
between countries, and thus these limits will have to be adjustable. The default limits
will be according to IEC 61727 §5.2.2, which states that when the utility frequency is
outside ± 1Hz of the rated frequency, the system shall cease to energize the utility
within 0,2s. If the utility returns to normal operating frequency within this time, the
converter does not have to cease energizing the utility line.
The limits for North America can be found in IEEE 929 §4.3, and states that the
frequency operating range is between 59.3 ‐ 60.5Hz, and the converter should cease
to energize the utility within 6 cycles (0.1s). For further information on the frequency
limits see IEC 61727 §4.5 and IEEE 929 §4.3.
5. Distortion/Harmonics
It is desirable to have low levels of current and harmonic distortion in the grid, in
order to decrease the potential for adverse effects on connected equipment. In the
standards this is regulated through limits in allowed current distortion. The allowed
current distortion limits the converter is allowed to inject into the grid is given in table
2.3. For further information on the harmonic limits see IEC 61727 §4.6 and IEEE 929
§4.4.
Table 2.3 ‐ Harmonic current limits
Harmonic order h (odd harmonics)a
Distortion limitsb
THD
5%
3rd through 9th
<4.0%
11th through 15th
<2.0%
17th through 21st
<1.5%
23rd through 33rd
<0.6%
above 33rd
<0.3%
a. Even harmonics are limited to 25% of the odd harmonic limits above.
b. All limits are given as percent of the rated fundamental current component
6. Power factor
Chapter 2 Overview of Photo Voltaic Systems and Converters Fundamentals of Grid Connected Photo‐Voltaic Power Electronic Converter Design
6
The converter shall have a power factor according to table 2.4, but in some situations
there is a need for the inverter to supply reactive power. Therefore the inverter
should have the ability to regulate the output power factor. For further information
on the power factor limits see IEC 61727 §4.7 and IEEE 929 §4.5.
Table 2.4 ‐ Power factor limits
Output of convertera
Power factor
>10%
>0.85(lagging)
>50%
>0.9(lagging)
a. In percent of rated output
Anti‐Islanding
A non‐islanding inverter is defined as an inverter that ceases to operate within a certain
time after the islanding occurs, but based on measurements it is not easy to define a set of
limitations defining exactly when an islanding situation occurs. The definition of when an
islanding situation occurs has been defined differently in the standards from IEC and IEEE.
1. IEC 61727:
A utility distribution system is islanded when it is out of the normal operation
specifications for voltage and/or frequency. When this situation occurs, the PV
system must cease to energize the utility within 2 s of loss of utility.
2. IEEE 929 (definition of non islanding inverter):
An inverter that will cease to energize the utility line in ten cycles or less when
subjected to a typical islanded load in which either of the following is true:
a) There is at least a 50% mismatch in real power load to inverter output (that is, real
power load is <50% or >150% of inverter power output).
b) The islanded‐load power factor is < 0.95 (lead or lag).
If the real‐power‐generation‐to‐load match is within 50% and the islanded‐load
power factor is > 0.95, then a non‐islanding inverter will cease to energize the utility
line within 2 s whenever the connected line has a quality factor of 2.5 or less.
Neither of these limits are adequate for determining when a islanding situation occurs in
every possible situation, but to be able to satisfy the standards the to last definitions should
be used. It should however be noted that in IEC 61727 it is stated that the issues of non‐
islanding inverter is the subject of another standard under consideration. So one should be
aware that these requirements may change, and become stricter.
Chapter 2 Overview of Photo Voltaic Systems and Converters 7
NTNU Department of Electric Engineering
Reconnection
When an out‐of‐bounds utility event occurs, in which the inverter has ceased to energize
the utility line, the inverter shall not reconnect before the frequency and voltage have been
maintained within the specified limits for at least 5 min. After these 5 min. The inverter shall
automatically reconnect to the utility.
2.2 Solar Cell Characteristics
Energy sources deliver energy in many forms, some mechanical with conversion to
electrical, some with conversion of chemically stored energy to electricity, and some
produce energy directly as electrical energy. The latter is the case when producing energy
with solar cells, where the energy is delivered as DC current. The photo voltaic cells have a
special current‐voltage (I‐V) characteristic which must be taken into consideration when
designing a PV power system. Defining this characteristic is a short circuit current ISC and an
open circuit voltage VOC. This characteristic varies with irradiance and temperature, and in
figure 2.1 it is shown how this current voltage relationship changes as the irradiance
decreases.
Figure 2.1: I‐V characteristic of a solar cell as irradiance decreases
As can be seen from the figure, it is mostly the current which is affected by the change in
irradiance, and thus the voltage variation due to changes in irradiance is usually neglected.
The response to temperature changes is somewhat different, and is shown in figure 2.2
Chapter 2 Overview of Photo Voltaic Systems and Converters Fundamentals of Grid Connected Photo‐Voltaic Power Electronic Converter Design
8
Figure 2.2: I‐V characteristic of a solar cell as temperature increases
As the figure shows the open circuit voltage is largely dependent on the temperature,
whereas the current is only slightly dependent, therefore the current change due to
temperature variations is usually neglected. In a practical calculation, the voltage variation
with temperature of a module or a string consisting of nc cells in series, is often sat equal to:
dV OC
------------ = – 2.3 ⋅ n c [ mV/°C ]
dT
(2.1) It can be seen from the I‐V characteristic that when drawing power from a solar cell, it is
most beneficial to work in the region where the product of current and voltage is at its
highest, and thus delivers the highest output power. The power‐voltage (P‐V) characteristic
is shown in figure 2.3.
Chapter 2 Overview of Photo Voltaic Systems and Converters 9
NTNU Department of Electric Engineering
Figure 2.3: P‐V characteristic of a solar cell
As seen from the figure it is important to deliver power at the voltage which gives the
highest power, or else the power output end thus the efficiency of the system will rapidly
decrease. This point on the curve giving the highest power, is commonly referred to as the
maximum power point (MPP). It is now important to recognize that the power is depending
on both the current and the voltage, and therefore the MPP will be largely depending on
both irradiance and temperature.
2.2.1 PV panel modelling
In order to simulate the behaviour of a specific solar panel, there have been made different
mathematical models in the literature, which can be used to make theoretical models.
These models will only be approximations to the behaviour of the panels, and the accuracy
of the models depend on how many internal phenomena are considered. The equations
shown below are rather simple and does not give a high degree of accuracy, but they will
give an understanding of the basic behaviour of the solar cells. The definition of the
different variables in the equations is found at the end of this chapter. The cell temperature is a function of the ambient temperature and the irradiance, and is
given in Kelvin.
Tcell = Ta +
NOCT − 20
⋅G
800
(2.2) In eq (2.3) the changes in short circuit current due to temperature and irradiance is shown.
ISC = ISC _ STC (1 + α I ⋅ (Tcell − TSTC ) )
G
GSTC
Chapter 2 Overview of Photo Voltaic Systems and Converters (2.3) Fundamentals of Grid Connected Photo‐Voltaic Power Electronic Converter Design
10
In eq (2.4) it is assumed that the change in open circuit voltage due to changes in irradiance
are so small they can be neglected, therefore the open circuit voltage is only a function of
temperature.
VOC = VOC _ STC (1 + αV ⋅ (Tcell − TSTC ) )
(2.4) The output current of a solar cell is the light induced current minus the diode current, as
can be seen from the equivalent circuit of a PV cell shown in the figure below.
Figure 2.4: Equivalent circuit of a photo.voltaic cell
The light induced current is the same as the short circuit current, and the PV cell output
current is then given in (2.5)
⎡ ⎛ qv
iPV = Il − iD = ISC − I0 ⎢ exp ⎜ PV
⎣⎢ ⎝ kTcell
⎞ ⎤
⎟ − 1⎥
⎠ ⎦⎥
(2.5) Based om (2.5) the dark saturation current I0 can be found by setting iPV=0 and vPV=VOC, as
shown in (2.6).
⎡ ⎛ qV
I0 = ISC ⎢ exp ⎜ OC
⎣⎢ ⎝ kTcell
⎞ ⎤
⎟ − 1⎥
⎠ ⎦⎥
−1
(2.6) By using (2.5) the PV voltage from one cell can also be found.
⎛ i −I ⎞
k ln ⎜ 1 − PV SC ⎟
I0 ⎠
⎝
v pv =
qT
(2.7) A ideal I‐V curve would be rectangular, but in practice this is not so. The “Fill Factor” (FF)
describes how close the I‐V curve is to the ideal one, and is defined as
Chapter 2 Overview of Photo Voltaic Systems and Converters 11
NTNU Department of Electric Engineering
FF =
PMPP
VOC ISC
(2.8) Based on these equations a complete model of the PV panels can be made. This model can
then be implemented in a simulation program and used for simulation of PV‐panels.
Another use of these models or other models for that sake, is in the control of a DC‐power
source used as a PV simulator. A converter of this type can be an alternative to field testing
of PV‐panels and of converters. With this converter one will also be able to do repeatable
tests, and simulations of all sorts of operating conditions. Some examples of such
converters are given in [4,5]. Below is a list of the different parameters found in the
equations presented in this section.
kI - Temperature coeffisient of ISC
k V - Temperature coeffisient of VOC
kP - Temperature coeffisient of PMPP
G - iirradiance [W/m2 ]
ISC -Short circuit current
I0 - Dark saturation current
k = 1.3806 10-23 J/K (Boltzmann constant)
MPP - Maximum Power Point
NOCT - Normal Operating Cell Temperature [°C]
ns - nr of cells in series in one panel
nps - nr of panels in series
nsp - nr of strings in parallel
PMPP - Power at MPP
q = 1.6 10-19 C (Electron charge)
STC - Standard Test Condition (G=1000W/m2 , T=25°C, AM1.5)
Ta - Ambient temperature [K]
Tcell - Cell temperature [K]
G − irradiance [W/m2 ]
VOC - Open circuit voltage
2.3 Solar panel and converter configurations
Throughout the history of solar panels there has been several ways of arranging the solar
panels have been tried. How they are arranged has an effect on which type of converter
which should be used, and this will in turn influence the cost and efficiency of the system.
Figure 2.5 (from [6]) shows a historical overview of the different panel configurations of
panels and converters used in the past, present and future. Chapter 2 Overview of Photo Voltaic Systems and Converters Fundamentals of Grid Connected Photo‐Voltaic Power Electronic Converter Design
12
Figure 2.5: Historical overview of PV converters. (a) Past centralized technology. (b) Present string technology. (c) Present and future multi‐string technology. (d) Present and future AC‐mod‐
ule and AC cell technologies.
In [6] a review of different configurations is presented, and a summary of this is presented
here. In this section the abbreviation MPPT is used a lot, which stands for maximum power
point tracker and is described in chapter 3.1.
Centralized Converters
This is an old technology, and is based on the connection of a large number of PV modules
to the converter (see figure 2.5a)). The advantage of this configuration is the need for few
converters, which give low loss in the power conversion stage, and the possibility to
connect several modules in series to achieve a sufficiently high input voltage and then avoid
further amplification. However the drawbacks are more severe, with limitations such as the
use of high‐voltage DC‐cables between the PV modules and the converter, power losses
due to centralized MPPT, mismatch losses between the PV modules, losses in the string
diodes1, and a non flexible design where the benefits of mass production cannot be
reached. String Converters
As seen in figure 2.5 b), the string converter is a reduced version of the centralized
converter, where only one single string is connected to each converter. In this configuration
one can also gain the advantage of high input voltage, if a sufficiently amount of PV
modules are connected in series. If the input voltage is to low, then the use of a
transformer, or a DC‐DC converter can be used to boost the voltage. Since there is only one
1. String diodes are used to prevent current from one string to enter another string.
Chapter 2 Overview of Photo Voltaic Systems and Converters 13
NTNU Department of Electric Engineering
string, the use of string diodes1 is not necessary, and it allows individual MPPT tracking of
each string. The mismatch losses are also reduced, but not eliminated. All in all this
configuration increases the overall efficiency when compared to the centralized converter,
and it will reduce the price, due to possibility for mass production.
Multi‐String Converters
The multi‐string converter in figure 2.5 c), is a further development of the string converter,
and has many of the advantages of both the centralized converter and the string converter.
In this configuration there is one DC‐DC converter with separate MPPT tracking for each
input, all connected to the same inverter. This is beneficial since the MPPT can be
controlled individually for each string, and a plant can be realized with less components
than the string converter. This gives a flexible design with high efficiency, and will probably
become standard where centralized and string converters are used today.
AC‐Module Converters
With this configuration one PV module is integrated with the converter in one electrical
device, as shown in figure 2.5 d). By incorporating the PV module and the converter into
one device, the possibilities of creating a module based “plug and play” device arises, and
it can than be used by persons without any knowledge of electrical installations. In this
configuration the mismatch losses between the PV modules is removed, and it is possible
to optimize the converter to the PV module, and thus also allowing individual MPPT of each
module. Since there will be need for more devices then with the previous mentioned
configurations, it will give the benefit of large scale production, and thus lower prices. On
the other hand the input voltage will become low, requiring high voltage amplification,
which may reduce the overall efficiency.
2.4 Converter topologies
The converters for all the panel configurations presented in 2.3, are based on the same
basic topologies. In [7] a schematic of the fundamental PV converter topologies is
presented, this is shown in the figure below.
Figure 2.6: PV converter topologies [7]
Chapter 2 Overview of Photo Voltaic Systems and Converters Fundamentals of Grid Connected Photo‐Voltaic Power Electronic Converter Design
14
A seen in the figure, there are three major parts an converter can be constructed of. First
there is the DC‐AC converter (inverter), a DC‐DC converter and transformer (galvanic
isolation) and. The different parts are described in [6,7,8], and is summarized in the
following paragraphs.
2.4.1 Transformer
The transformer has to major functions in the circuit, to amplify the voltage and to gain
galvanic isolation between the PV modules and the grid. There are two basic ways to
connect the transformer, one is by embedding it in a high frequency (HF) DC‐DC converter,
or connecting a low frequency (LF) transformer on the grid side. The latter is in newer
converters often avoided because of increased size, weight and prize. So in modern
converters there is a tendency towards using HF transformers.
The galvanic isolation is often needed in order to ground the PV system properly. This
grounding sometimes involves connecting the negative terminal of the PV array(s) to
ground, and in transformerless systems this might become a problem. Especially in one‐
phase systems with neutral to line connection, where the inverter is already grounded on
the grid side. Galvanic isolation can also, if mounted on the low frequency (LF) side, prevent
DC‐current from entering the connected grid. This can however be solved by using
improved measuring equipment, which is able to detect small DC‐currents.
Some standards demand that the PV modules shall be grounded and monitored by faults,
while others only demand equipment ground (grounding of frames and other metallic
parts) in the absence of galvanic isolation. There is usually not any direct demands for
galvanic isolation in the standards, but it is often the only, or the easiest way to achieve
system grounding and/or to prevent the injection of DC‐currents. Transformerless
topologies are also very interesting because they can offer higher efficiency and reduced
cost, but more research is needed to be done in order to minimize the leakage current and
ensure safety and panels reliability If using a transformer the question will be where to place it, on the high frequency (HF) or
the low frequency (LF) side? The LF transformer is more expensive, larger and heavier, but
the design is more simple then if a HF transformer is used.
2.4.2 DC‐DC converter
PV converters with DC‐DC converter is termed dual stage, and in this topology the DC‐DC
converter will handle the MPPT (see chapter 3.1) and some voltage amplification if needed.
Most converter structures only have one DC‐DC converter, but multi string converters will
have two or more. The output of the DC‐DC converter will depend on the inverter used at the grid interface. If
the inverter is controlling the grid current by means of pulse width modulation (PWM), or
bang‐bang (hysteresis) operation, then the output of the DC‐DC converter can be a pure DC
voltage. The inverter can also switch at line frequency, and then the output of the DC‐DC
Chapter 2 Overview of Photo Voltaic Systems and Converters 15
NTNU Department of Electric Engineering
converter can be a current, modulated to follow a rectified sine wave, thus the inverter will
unfold the rectified sine wave into a full sine wave. According to [6] the latter solution can
give a high efficiency if the nominal power is low, but if the power is high, it is advisable to
operate the inverter in PWM mode, and thus the output of the DC‐DC converter will be a
pure DC voltage.
The choice of DC‐DC converter depends mainly on the use of HF transformer, and
amplification range. When there is no transformer, a buck, boost, buck‐boost or variants of
these can be used, and if a HF transformer is used, a forward, push‐pull, flyback, half‐bride,
full‐bridge or other variants can be applied. Because there is usually a need for galvanic
isolation the ones with a HF transformer is the most interesting. The forward and the flyback converters are typically used for low power applications (up to
approximately 250w for the flyback), because of low utilization of the magnetic
components due to unidirectional core excitation. There are ways to improve the power
handling capabilities of these converters, but this will not be handled here. These
topologies are therefore best suited for small AC‐module converters, or other low power
designs.
For medium power applications, converters with bidirectional core excitation are
preferred, because they utilize the magnetic components better. The push‐pull, half‐bridge
and full‐bridge converters are examples of the latter. In [7] three different topologies with
bidirectional transformer excitation has been considered, with “max efficiency” as
optimization criteria. These topologies are usually used for applications at 750W or more,
and the three topologies are:
• Full bridge isolated boost DC‐DC converter (FB)
• Single‐inductor boost push‐pull converter (SIC)
• Dual‐inductor boost push‐pull converter (DIC)
Chapter 2 Overview of Photo Voltaic Systems and Converters Fundamentals of Grid Connected Photo‐Voltaic Power Electronic Converter Design
16
Figure 2.7: The full bridge isolated boost (FB), the single‐inductor boost push‐pull (SIC) and the dual‐inductor boost push‐pull (DIC) DC‐DC converter [7].
The results of the comparison is shown in the tables presented below.
Table 2.5 ‐ Comparison of DC‐DC converters ([7])
Parameter
Full‐Bridge
SIC
DIC
Number of switches
4
2
2
Number of Boost Inductor
1
1
2
1 primary coil
2 primary coils
1 primary coil
Switch peak voltage
VDC/n
2*VDC/n
VDC/n
Switch rms current
Boost inductor current
IFC
IFC
IFC/2
Inductor current ripple
frequency
2fS
2fS
fS
(VDC/n)*IFC
(VDC/n)*IFC
(VDC/n)*IFC/2
0.69
0.69
0.38
Transformer
Trafo peak volt‐ ampere
Duty‐cycle
Chapter 2 Overview of Photo Voltaic Systems and Converters 17
NTNU Department of Electric Engineering
Table 2.6 ‐ Loss comparison dc‐dc converters ([7]) (Full bridge is reference, with loss in pu)
Loss types
Full‐Bridge
SIC
DIC
PSW, switch
1
∼1
∼0.5
PC, switch
1
∼0.5
∼0.61
PCOPPER, transf
1
∼1
∼0.5
PCORE, transf
1
∼1
∼1
PCOPPER, inductor
1
∼1
∼0.64
PCORE, inductor
1
∼1
∼2.65
The comparison concludes that the full bridge isolated boost DC‐DC converter is
advantageous as it uses the same power stage as the grid inverter (proven technology), and
it is more suitable for applications with higher input voltages. Whereas the push‐pull DC‐DC
converters are more suitable for applications with low input voltage, and the topology with
dual‐inductor yields in slightly higher efficiency as single‐inductor topology. The full bridge isolated boost DC‐DC converter is also called a current fed full bridge
converter. In [26] it is compared to the voltage fed full bridge converter, which is based on
the same converter but with different input circuitry. The current fed converter has a
inductor at the input and therefore has a boost characteristic, whereas the voltage fed has
no inductor and therefore has a buck characteristic. In this thesis they are compared with
each other with respect to their suitability for use with fuel cells, but the results are
interesting also for photo‐voltaic systems. It is here concluded that the current fed
converter has a 1‐2% higher efficiency compared the voltage fed converter, which is due to
lower semiconductor losses. In the voltage fed converter it is also shown that the
transformer leakage inductance has a great influence on the dimensioning of the converter,
and that it limits the maximum output to input voltage ratio or the operating frequency of
the converter. This is not a problem in the current fed, but it will need a clamping circuit for
the energy stored in the transformer leakage inductance. 2.4.3 DC‐AC inverter
The DC‐AC converter is the most fundamental part of the PV converter, and can be made
as one‐ or three‐phase. A single phase converter is the most common solution for small
residential converters up to approximately 5‐6 kW, but the use of a three‐phase converter
has some advantages. First of all the power will be distributed equally in all three phases,
and unlike single‐phase inverters, the three‐phase inverter will under balanced load
conditions have a constant instantaneous load power (see figure 2.8). The latter will
remove the need for capacitive storage elements under the balanced load conditions, but
control techniques that deal with unbalanced three‐phase condition can be needed. Chapter 2 Overview of Photo Voltaic Systems and Converters Fundamentals of Grid Connected Photo‐Voltaic Power Electronic Converter Design
18
Figure 2.8: The instantaneous power in the three phases, and the sum of these powers as the solid line
The inverters used for grid interfacing of the PV panels are usually voltage source inverters
(VSI’s), but current source inverters (CSI) are also used. Since the PV modules are current
sources, a capacitor has to be added in parallel when using a VSI, in this way the inverter
sees a voltage source.
This thesis is based on a three‐phase converter, and the most commonly used topology is
the full bridge VSI (two level), but it is also possible to use more advanced multilevel
inverters (three levels or more). Some of the most common is described in [9], like the
diode clamped multilevel inverter, the flying capacitor structure, and series H‐bridge
multilevel inverter. It is also possible to use a line commutated inverter, but it gives poor
power factor and power quality, and is seldom used.
By using a full bridge VSI as shown in figure 2.9, a near sinusoidal current can be produced
and harmonic distortion can be lower than by using a line commutated inverter. The level
of harmonic distortion is depending on the switching frequency, and the modulation
technique used (see chapter 3.3.2).
Chapter 2 Overview of Photo Voltaic Systems and Converters 19
NTNU Department of Electric Engineering
Figure 2.9: Full bridge VSI
By using a multilevel inverter, advantages such as improved power quality and
electromagnetic compatibility (EMC), lower switching losses, and higher voltage capability
can be achieved. The main disadvantages of this technique is that a larger number of
switching semiconductors are required for lower‐voltage systems and the small voltage
steps must be supplied on the DC side either by a capacitor bank or multiple PV modules
configured to create voltage steps. Multilevel inverters are most often used in larger PV
systems, and it is an area of much research.
2.5 Grid filter topologies
Injection of power from the PV system to the grid is typically done through a VSI. Harmonics
in the output voltage of the inverter is usually attenuated by connecting a filter between
the VSI and the grid in order to cope with the power quality requirements of the utility.
Improvements in the reactive power export to the grid is also constrained by the filter
parameter. The most common filters used for this purpose are reviewed in this chapter
2.5.1 L‐filter
The degree of which the harmonic content is attenuated depends on the filter used. A first
order filter consisting of one inductor in series with the mains is the most commonly used
filter. This is because the filter is easy to make, and it has no resonance problems as higher
order filters may have. The major drawback of this filter is the size of the inductor needed
to achieve a reasonable attenuation of the current harmonics. So with an attenuation of
20dB per decade over the whole frequency range, this filter is most efficient when used
with high frequency PWM converters.
2.5.2 LC and LCL‐filter
Higher order filters consisting of combinations of inductors and capacitors, can give a better
attenuation of the harmonics, but they also make the design more complex. The most
common higher order filters are the second order LC filter and the third order LCL filter. In
grid connected systems the LC filter is seldom used, since the resonance frequency of the
Chapter 2 Overview of Photo Voltaic Systems and Converters Fundamentals of Grid Connected Photo‐Voltaic Power Electronic Converter Design
20
filter will vary with the inductance value of the grid. Instead by using a correctly designed
LCL filter this problem is reduced, because the resonance frequency is mostly depending on
the filter components. The LCL filter will also give a better attenuation than a LC filter given
the same size. The dynamic control of the inverter is more difficult when using a LCL filter compared to
using a simple L filter. With the LCL filter two more poles and two more zeroes are
introduced compared two the simple L filter. So care must therefore be taken when
designing the controller, and the additional poles and zeroes can make the system unstable
if not proper damping is introduced.
Damping
Damping of the LCL filter resonance can be either active using the converter, or passive
using elements like resistors, capacitors and inductors. Several different methods for
passive damping has been proposed ([10]), from a simple resistor in series with the
capacitor, to more complex circuits including resistors, capacitors and inductors in series or
parallel with the condensator. When a resistor is introduced in the circuit, there will be
some increase in the losses, how much depends on the configuration. One should also be
aware that some of the configurations might introduce resonance frequency shifts, and
lower attenuation at higher frequencies compared to the undamped LCL filter.
Several different approaches to active damping has been proposed in the literature. These
methods often require the measurement of the capacitor voltage and/or currents, but
other methods using estimated values have also been used. The use of active damping
removes the losses associated with passive damping, but it increases the complexity of the
control and might introduce other problems if not correctly designed.
In the figure below a LCL filter with a simple passive damping resistor in series with the filter
capacitor is shown.
Figure 2.10: LCL filter model with damping and inductor resistance Chapter 2 Overview of Photo Voltaic Systems and Converters 21
NTNU Department of Electric Engineering
2.6 Temporary storage
In some applications temporary storage of the produced energy might be needed for
several reasons. If the system is connected to a weak grid, some extra capacity might be
useful to stabilize the grid during short periods of high power consumption, and to increase
the short circuit capabilities of the grid. The temporary storage might also be used as a UPS,
where a part of the load will be supplied by the PV system if the grid is disconnected. There
is also the case where the PV system is working as a standalone system, but this is not of
interest here. There are several different technologies for storing the produced energy, but
for grid connected systems some sort of battery storage is the most common.
Chapter 2 Overview of Photo Voltaic Systems and Converters Fundamentals of Grid Connected Photo‐Voltaic Power Electronic Converter Design
22
3 CONTROL OF PHOTO‐VOLTAIC CONVERTERS
Almost all of the converters found in the previous chapter are active converters with
controllable switches. These can be controlled in various ways in order to achieve a desired
effect. In this chapter some control methods which are of interest in PV systems are
presented. An introduction to the implementation of a control system in a DSP is also given.
In order to optimize the control systems, some methods for the optimization of the various
controls is also given.
3.1 Maximum power utilization of photo voltaic power sources
To utilize the maximum power produced by the solar cell at all times, the regulation system
has to be equipped with a maximum power point tracker (MPPT). This is a device which
tracks the voltage at where the maximum power is utilized at all times. It is usually
implemented in the DC‐DC converter, but in systems without a DC‐DC converter the MPPT
is included in the DC‐AC inverter control. Several methods have been developed for this
purpose, and the most well known are presented here, with their major advantages and
drawbacks (from [7,11]).
3.1.1 Constant voltage (CV)
This algorithm is based on the fact that the MPP voltage changes only slightly with varying
irradiance. The MPP voltage is expressed as the ratio between VMPP/VOC, where VMPP is the
voltage at the point of MPP, and VOC is the open circuit voltage. This ratio is depending on
the solar cell parameters, but a commonly used value is 76%. By momentarily setting the
current to zero, this algorithm is allowed to measure the open circuit voltage VOC, and then
calculate VMPP. The drawbacks of this algorithm is the loss off energy when the load is
disconnected, and the MPP is not always located at 76%.
3.1.2 Perturb and observe (P&O)
This is the most commonly used algorithm for MPP tracking, and is based on perturbing the
voltage and observing the dP ⁄ dt . The direction of the derivative shows if the voltage is to
high or to low, and the voltage can thus be decreased or increased until the MPP is reached,
and thus the derivative is zero. Because this algorithm is based on perturbation, there will
always be some oscillations even when the MPP is reached. In figure 3.1 a flow chart from
[7] describing the P&O algorithm is presented.
Chapter 3 Control of Photo‐Voltaic Converters
23
NTNU Department of Electric Engineering
START
Sense
V(k),I(k)
Yes
P(k)-P(k-1)=0
No
No
Yes
P(k)-P(k-1)>0
V(k)-V(k-1)>0
V(k)-V(k-1)>0
Y es
V ref
=
V
No
ref-∆V
Vref
=
V
Yes
No
V ref
ref+∆ V
=
V
ref-∆V
V ref
=
V
ref+∆V
RETUR
N
Figure 3.1: Flow chart of the P&O algorithm [7]
3.1.3 Incremental conductance (INC)
In the incremental conductance algorithm the drawbacks of the P&O algorithm with
oscillations around MPP is removed. This is done by using the PV array’s incremental
conductance to compute the sign of dP ⁄ dt without perturbations. In [7] it is shown that
dP
dI
= I +V
dV
dV
dP
dI
dI
I
At MPP :
= 0 = I +V
⇒
=−
dV
dV
dV
V
P = VI ⇒
(3.1) Based on these equations the algorithm can determine if the MPP is reached, and stop
perturbing the operating point. One disadvantage of this technique is the increased
complexity compared to the P&O algorithm, and In figure 3.2 a flow chart from [7]
describing the INC algorithm is presented.
Chapter 3 Control of Photo‐Voltaic Converters
Fundamentals of Grid Connected Photo‐Voltaic Power Electronic Converter Design
24
START
Sense
V(k),I(k)
Yes
V(k)-V(k -1)=0
No
Yes
=
V
I(k)-I(k1)=0
No
No
dI/dV>-I/
V
No
V ref
dI/dV=-I/
V
-∆V
Yes
V ref
ref
=
V
I(k)-I(k1)>0
No
Vref
+∆V
ref
=
V
Yes
-∆V
ref
Yes
Vref
=
V
+∆V
ref
RETUR
N
Figure 3.2: Flow chart of the INC algorithm [7] 3.1.4 Parasitic Capacitance (PC)
In every solar cell there is a parasitic capacitance, and this capacitance is used to determine
the MPP. The parasitic capacitance technique uses the switching ripple to perturb the array.
To account for the parasitic capacitance, the average ripple in the array power and voltage,
generated by the switching frequency is measured and then used to calculate the array
conductance. Then the incremental conductance algorithm is used to determine in which
direction the operating point of the MPPT has to be moved. It can be seen that this is a
refinement of the INC technique, and is thus at least as complex. A disadvantage of this
method is the size of the parasitic capacitance is very small in each module, and thus it only
comes into play in larger systems with several modules in parallel. There is also a problem
when there are large input capacitors on the DC‐DC converter, as these might overshadow
the effect of the parasitic capacitance.
3.1.5 Efficiency of the MPPT techniques
Even though incremental conductance and parasitic capacitance is more complex than the
other to methods, all the methods presented here are designed to be implemented in low
cost systems with low computational capacity. Results presented in [11] indicates the
efficiency of the three first methods, these are reproduced in table 3.1:
Chapter 3 Control of Photo‐Voltaic Converters
25
NTNU Department of Electric Engineering
Table 3.1 ‐ Efficiency of the MPPT methods [11]
CV
P&O
INC
Array
88.1%
96.5%
98.2%
Simulator
92.7%
97.2%
98.5%
These results indicate that CV has a low efficiency, and the difference in efficiency between
P&O and INC is small, but both have high efficiency. How the parasitic capacitance
compares to these methods is unknown, but since it is a refinement of the INC method, one
can assume an efficiency of the INC or even slightly better. 3.2 DC‐DC Converter Control
The DC‐DC converter is controlling the DC‐link voltage, and in most cases trying to keep it
at a constant voltage, but in the case when the DC‐DC converter is used for MPPT, it’s main
purpose will be to operate the PV system at it’s MPP. Therefore the feedback to this system
is the PV panel power, not the DC‐link voltage. So in the case where the DC‐DC converter is
controlled by an MPPT, the current drawn by the DC‐AC converter will decide the DC‐link
voltage.
In the MPPT algorithms it is usually assumed that the duty cycle is the controlled variable,
but it is also possible to have the peak switch current as the controlled variable. In the
literature (described briefly in [12], and more in depth in [30]), these controls are described
with feedback of the DC‐link voltage, which is not the case when using an MPPT. Then the
power is feed back to the MPPT, and the control of the DC‐link voltage becomes an open
loop control. The principal of these to techniques when using an MPPT as the controller is
shown in the two figures below
Figure 3.3: Direct duty‐cycle control strategy for DC‐DC converter
Chapter 3 Control of Photo‐Voltaic Converters
Fundamentals of Grid Connected Photo‐Voltaic Power Electronic Converter Design
26
Figure 3.4: Peak switch current control strategy for DC‐DC converter
By using the peak switch current control strategy there can be seen some advantages
compared to the direct duty‐cycle control, like better protection of the switches by limiting
the current to acceptable levels and transformer saturation problems due to DC‐bias tend
to disappear. The drawbacks of this strategy is the need for an extra current sensor, and the
control system must be able to accurately switch at the instant the current reaches the
threshold current. It also has a susceptibility to noise, and therefore some filtering of the
feedback is required which will introduce a delay.
3.3 DC‐AC Converter control
In order to control the DC‐AC converter inverter there are to major control strategies,
current control (CC) and voltage control (VC). Where current control is the most common
way to control grid connected VSI’s. A current controller has the advantage of being less
susceptible to voltage phase shifts and to distortion in the grid voltage, thus it reduces the
harmonic currents to a minimum. Whereas voltage control can result in overloading of the
inverter due to small phase errors, and large harmonic currents may occur if the grid
voltage is distorted. If operated in standalone mode, voltage control would be a natural
choice, but when operated in grid connected mode, current control is the most robust
control. Therefore only current controlled VSI’s (CC‐VSI) will be considered here. Some of the control schemes presented in this chapter will involve the use of
transformations between the 3‐phase system and different two‐phase systems, therefore
the concept of transformation is described first.
Common to all the control strategies described in this chapter is a clearly separated current
error compensation and voltage modulation part (PWM modulation). This concept allows
one to exploit the advantages of open‐loop modulators separate from the current error
compensation loop, and therefore this is described next.
In the last chapters three different current control methods are described. The first two are
described in [7,12,13,14,], where the first is a PI controller using a rotating reference frame,
the second is a proportional resonant (PR) controller using a stationary reference frame.
Chapter 3 Control of Photo‐Voltaic Converters
27
NTNU Department of Electric Engineering
The third method is described in [15], which is a state feedback controller working in a
rotating reference frame. Other control strategies like hysteresis and dead‐beat control has
also been reported ([15,16]), but these methods will not be discussed further in this thesis.
3.3.1 Transformations
In order to avoid controlling three current/voltages separately, transformations from a
three‐phase system to different two‐phase systems have been made. These are based on
the fact that in a balanced three‐phase system there are only two independent current/
voltages, thus the third current/voltage can be expressed by the other two. These systems
are often referred to as reference frames, where the frame is the axis system of the
transformed system.
Stationary reference frame (Clarke transform)
When a three‐phase system is transformed into a two‐phase system, this is often called a
abc to αβ (or αβ0 when the zero vector is used) transform, or a transform into the
stationary reference frame. Both the three‐phase and the two‐phase system is said to be
stationary, because the axes is locked in one position, but the term stationary reference
frame usually refers to a two‐phase stationary reference frame.
The transformation is made by applying the Clarke transformation in eq (3.2), where the
three‐phase quantities must be phase values, i.e not line values. By inverting the coefficient
matrix, the three‐phase quantities can be found as a function of the two‐phase quantities.
⎡
⎢1
⎢
⎡ Xα ⎤
2
⎢X ⎥ = ⎢0
⎢ β⎥ 3⎢
⎢
⎢⎣ X 0 ⎥⎦
⎢1
⎢2
⎣
1
2
3
2
1
2
−
1 ⎤
2 ⎥
⎥ ⎡Xa ⎤
3⎥ ⎢ ⎥
−
⋅ Xb
2 ⎥ ⎢ ⎥
⎥ ⎢X ⎥
1 ⎥ ⎣ c⎦
2 ⎥⎦
−
(3.2) The transformation can be thought of as a change of coordinate system, from a three axis
(phase) system to a two axis (phase) system as shown in figure 3.5. It can be seen from the
abc system that only two phases is needed to express the vector Xabc, and thus it can be
expressed in the αβ system as the vector Xab without any loss of information. In the figure
ω is the angular speed of the vector, and θ is the instantaneous angle of the vector. If X is
the grid voltage, then ω represents the grid frequency, and θ represents the instantaneous
phase angle.
Chapter 3 Control of Photo‐Voltaic Converters
Fundamentals of Grid Connected Photo‐Voltaic Power Electronic Converter Design
28
αβ
β
ω
αβ
θ
ω
θ
α
α
Figure 3.5: Abc to αβ transformation
Usually the three‐phase quantities are assumed symmetrical, and thus the zero‐sequence
component can be ignored. When there is no zero‐sequence component the instantaneous
active and reactive power is given by eq (3.3) and (3.4). The factor 3/2 is introduced in order
to have the power from all three phases.
pαβ =
3
(vα iα + v β iβ )
2
(3.3) qαβ =
3
(v β iα − vα iβ )
2
(3.4) Synchronous reference frame (Park transform)
In this system the axis system is no longer locked, and rotates following an arbitrary vector,
hence the term “synchronous reference frame”. It is sometimes also termed the dq system
(or dq0 if zero‐vector is used).
This transformation is widely used in motor drives, where the axis system follows for
instance the rotor position or rotor flux. In grid connected inverters it is most common to
lock the axis system to a voltage or current (usually the grid voltage). In figure 3.6 the d‐axis
is locked to the vector Xab, and therefore Xd=Xab and Xq=0. The axis system will then rotate
with an angular speed of ω, and have an instantaneous angle of θ (referred to the
stationary system). Chapter 3 Control of Photo‐Voltaic Converters
29
NTNU Department of Electric Engineering
β
β
αβ
ω
θ
α
α
Figure 3.6: αβ to dq transformation
The transformation is made using the Park transformation shown in eq (3.5), where the
stationary quantities can be found as a function of the synchronous quantities by inverting
the coefficient matrix.
⎡ X d ⎤ ⎡ cos (θ ) sin (θ ) 0 ⎤ ⎡ X α ⎤
⎢ X ⎥ = ⎢ − sin θ cos θ 0 ⎥ ⋅ ⎢ X ⎥
( )
( ) ⎥ ⎢ β⎥
⎢ q⎥ ⎢
⎢⎣ X 0 ⎥⎦ ⎢⎣ 0
0
1⎥⎦ ⎢⎣ X 0 ⎥⎦
(3.5) θ ‐ Instantaneous phase angle
If the dq‐axis system is locked to the grid voltage, the axes will rotate with the frequency
2πfg, and the dq values will become DC‐values stationary. If it is still assumed that the three‐
phase quantities are symmetrical, then the zero‐sequence component is still zero, and the
active and reactive power is given by eq (3.6) and (3.7)
pdq =
3
( v d id + v q iq )
2
(3.6) qdq =
3
( v q id − v d iq )
2
(3.7) These equations assume that both the voltage and the current is transformed into the dq‐
system using the same reference frame. When the reference frame is oriented at the
voltage vector, then the d‐axis current will represent current in phase with the voltage, and
thus it represents the active power in the circuit. The q‐axis current will then represent
current which is out of phase with the voltage, and thus it represents the reactive power in
the circuit.
Chapter 3 Control of Photo‐Voltaic Converters
Fundamentals of Grid Connected Photo‐Voltaic Power Electronic Converter Design
30
It should be noted that other versions of the Park transform exists, and in these the
orientation of the dq‐axis on the Xab vector might differ. This can for instance lead to having
the active power controlled by the q‐axis, but only the transform given by eq (3.5) will be
used throughout this text.
3.3.2 Pulse Width Modulation (PWM)
The PWM modulators are open‐loop voltage controllers, and the most common methods
for PWM modulation is carrier based PWM (CB‐PWM), space vector modulation (SVM) and
random PWM. The fundamental difference between these methods are described in [31],
and a summary of the operation in the linear modulation range is presented.
Carrier Based (CB‐PWM)
CB‐PWM is the basic and most common way to modulate the switching signals. This
method can be divided into to methods, sinusoidal PWM and CB‐PWM with zero sequence
signal (ZSS). With sinusoidal PWM, three reference sinusoidal signals are compared to a
triangular wave generating logical signals controlling the switches. Whereas the ZSS
method is based on the sinusoidal PWM, with the addition of a zero sequence signal of third
harmonic frequency. The injection of the third harmonic is not producing phase voltage
distortion or affecting load average currents. It does however extend the linear region of
operation, reduce the average switching frequency and reduce the current harmonics. The ZSS method can be further divided into continuous and discontinuous modulation
(DPWM), where the most well known method of continuous modulation is the method with
sinusoidal ZSS, but also triangular ZSS is used. A ZSS amplitude of 1/4 of the fundamental
corresponds to the minimum of output current harmonics, and with 1/6 it corresponds to
the maximum linear range. Discontinuous modulation is formed by unmodulated 60°
segments (converter power switches do not switch) phase shifted from 0 to π/3, and can
reduce the average switching frequency and switching losses, but has higher harmonic
content at lower modulation ratios. The maximum output voltage in the linear region for
the sine PWM and the PWM with ZSS is
VLL _ sine =
VLL _ ZSS
3
VDC = 0.612 ⋅ VDC
2 2
1
=
VDC = 0.707 ⋅ VDC
2
(3.8) The principle of the generation of switch signals is shown in figure 3.7, where a triangular
carrier signal is compared to sinusoidal signals representing the phase voltages. If the
sinusoidal is larger than the carrier wave, then switch turns on, and if less it turns off.
Chapter 3 Control of Photo‐Voltaic Converters
31
NTNU Department of Electric Engineering
Figure 3.7: Generation of Carrier Based PWM signals [31]
Space Vector Modulation (SVM)
SVM is a method based on space vector representation of the converter AC‐side voltages,
and it is shown in [31] that the difference between SVM an CB‐PWM is only the treatment
of the three‐phase quantities. CB‐PWM operates in terms of three‐phase natural
components, whereas SVM uses an artificial vector transformation. With a three‐phase two
level inverter there are eight possible switching states, made up of six active and two zero
switching states. There are several different methods for creating the switching pattern,
the only difference between them is the placement of the zero vectors. The different
switching states is shown in the figure below.
Figure 3.8: Space vector representation of output voltage. [31]
The most popular method is the three‐phase SVM with symmetrical placement of zero
vectors (SVPWM). This method corresponds to CB‐PWM with triangular ZSS of 1/4
amplitude, and has almost equal harmonic content as CB‐PWM with sinusoidal ZSS. It is
Chapter 3 Control of Photo‐Voltaic Converters
Fundamentals of Grid Connected Photo‐Voltaic Power Electronic Converter Design
32
easy to implement in a microprocessor, and is therefore the natural choice of SVM. Two
other techniques for SVM is vector modulation with VN0=0 (voltage between converter
neutral and grid neutral=0, equal to sine PWM), and vector modulation with third harmonic
(equal to CB‐PWM with sinusoidal ZCC), but these are easier to achieve with CB‐PWM. Two‐
phase SVM is another method which is equivalent with the discontinuous CB‐PWM with
ZSS(DPWM). This method will have only one zero state per sampling time, and therefore a
simple calculation, but is best used at high modulation ratios. The maximum line voltage
with the SVPWM and also the two‐phase PWM is
VLL _ SVPWM =
1
2
VDC = 0.707 ⋅ VDC
(3.9) There is also a variant of SVM called adaptive SVM (ASVM), which combines different SVM
techniques into one universal solution. This method gives full control range including
overmodulation and six‐step operation (square wave operation) and higher efficiency of
the inverter, but the inverter will only mostly operate in the upper linear area of
modulation, therefore this method is not of interest.
The generation of the switch signals is for the SVM based on a mathematical approach,
which can easily be implemented into a microprocessor. For details on this the reader is
referred to [31] where this is described in detail.
Random PWM
Random PWM is based on randomly varying the switching period, and thus creating
harmonics more evenly distributed throughout the frequency spectrum. This has
advantages as reducing the acoustic noise, and compliance with standards defining limits
for emission of conducted and radiated EMI may be obtainable with less filtering and
shielding efforts. The implementation of random modulation is strongly dependent on the
hardware used for the PWM, and the distribution of harmonics is not well defined as it is
for fixed carrier period PWM.
3.3.3 PI Controllers
PI controllers can be applied both in the stationary (αβ) or synchronous (dq) reference
frame, but by applying them to the dq system there will be DC currents stationary, and the
PI compensators are able to reduce the stationary error of the fundamental to zero. This is
not the case with PI controllers working in the αβ system, where there is an inherent
tracking error of phase and amplitude. Therefore current control in a synchronous
(rotating) reference frame, using PI controllers is the typical solution in 3‐phase grid
connected inverters. An advantage of current control in the dq system is individual control of active and reactive
power by orienting the dq frame on the grid voltage (see chapter 3.3.1). Where the active
power is controlled by the d‐axis current and the reactive power is controlled by the q‐axis
Chapter 3 Control of Photo‐Voltaic Converters
33
NTNU Department of Electric Engineering
current. Some well known drawbacks of this method is the need for many transformations,
decoupling in three‐phase converters, and limitations in compensating the low harmonics
in order to comply with power quality standards. In its general form the PI controller is
defined as
H PI (s ) = K p
1 + Ti s
Ti s
(3.10) If harmonic compensation (see 3.4) is desired, it is possible to add harmonic compensators
with the same method as described above, but now using reference frames rotating at the
desired harmonic frequency.
3.3.4 PR controllers
The proportional resonant (PR) controller is a new type of controller described in
[7,12,13,14]. In this approach the PI DC‐compensator is transformed into an equivalent AC‐
compensator (using the transforms described in 3.3.1), thus giving the same frequency
response characteristics in the bandwidth of concern. By using this method the complexity
of the calculations will be reduced, and the cross couplings are removed. The PR controller
is defined as
HC ( s ) = K P + K 1
s
s2 + ω 2
(3.11) In combination with the PR controller it is often added a harmonic compensator (HC). The
harmonic compensator consists of a sum of generalized integrators (GI), which are tuned
to have almost infinite gain at different frequencies, called resonant frequencies. Outside
these frequencies the GI’s have almost no attenuation. This is an interesting feature of the
GI, because it does not affect the dynamics of the PR controller outside the tuned
frequency. Thus one can add as many GI as needed without affecting the overall system
dynamics. The harmonic compensator is defined as
H h (s ) =
∑
h = 3,5,...
K Ih
s
s + (ω ⋅ h )
2
2
(3.12) This combination of PR controllers and harmonic compensators, can be tuned to react to
the fundamental frequency for a good regulation, and tuned to harmonic frequencies in
order to compensate them (see 3.4). 3.3.5 State feedback controller
In the methods described above where the control processes have a mathematical
description in the form of transfer functions, it is not possible to observe and control all of
the internal phenomena involved in the control process. Therefore the state space method
Chapter 3 Control of Photo‐Voltaic Converters
Fundamentals of Grid Connected Photo‐Voltaic Power Electronic Converter Design
34
is gaining more and more attention, because this method provides a uniform and powerful
representation in the time domain of multivariable systems of arbitrary order with linear,
nonlinear, or time varying coefficients. There exist different ways to write the state space
equations, but one way described in [32] is
x ( t ) = Ax ( t ) + Bu ( t )
y ( t ) = Cx ( t ) + Du ( t )
(3.13) x ( t ) : State vector
u ( t ) : Input vector
y ( t ) : Output vector
A: State coupling matrix
B : Input coupling matrix
C : Output coupling matrix
D : Input to output coupling matrix
With this system description also the initial conditions are easy to implement, and the state
feedback controller can work in both stationary and synchronous reference frame. When
using this method the poles of the closed loop system can be placed in predetermined
locations in the s‐plane (or z‐plane when discretized), and thus controlling the
characteristics of the response of the system.
Also with this method harmonic compensation (see 3.4) can be achieved, by including a
model of the system at the desired harmonic frequency.
3.4 Harmonic compensation
Nonlinear loads have become a large part of the load profile of the grid nowadays. These
loads draw currents with a harmonic spectrum where the harmonic above the fundamental
becomes distinctive. When these currents go through the impedances of the grid, they
create voltage harmonic drops which deteriorate the grid voltage. This deterioration of the
grid voltage will affect all the grid connected equipment, and if the harmonics are
sufficiently large, it can lead to damage or deterioration of this equipment. It can therefore
be understood that this situation is undesirable, and some sort of compensation is needed
in order to keep the harmonics at a low level. The classical solution to this problem is installing passive filters, but these filters have some
drawbacks. The source impedance will strongly affect the compensation characteristics,
and they are susceptible to undesirable series and parallel resonance with source and load.
In order to alleviate these problems active filters have become more and more interesting,
because they are flexible and have the ability to adapt to varying situations. An active filter
can be a VSI programmed to deliver currents at the desired harmonic frequencies
(harmonic compensation), and thus reduce the harmonic voltage drops. Which means that
any grid connected VSI can be used as an active filter.
Chapter 3 Control of Photo‐Voltaic Converters
35
NTNU Department of Electric Engineering
In order to compensate for any harmonic drawn by the load, the harmonic currents needs
to be isolated and their phase and amplitude must be known. This can for instance be
achieved using filtering or some FFT algorithm. Once the harmonic current is known, it can
be compensated using for example one of the methods described about current control in
chapter 3.3.
3.5 Grid synchronisation
The inverter delivers current to the grid, and the synchronization of the current with the
grid voltage is important to:
• deliver power at a power factor within the limits in the standards, or within limits given
by the utility if there is need for reactive power compensation. • reduce the harmonic current content, by applying a “clean” reference current.
• minimize the grid connection transients.
In [7,18] several methods for grid synchronization are presented. These are summarized
here, discussing their major advantages and disadvantages.
3.5.1 Filtered Zero Cross Detection (ZCD)
With this method the zero‐crossing of the voltage is registered, and the phase angle is
calculated. The method is easy to implement and uses little computational capacity, but the
technique has several drawbacks. Since the technique is based on zero‐crossing detection,
the phase angle is only updated two times per period of the grid voltage frequency, and
therefore the dynamic performance of this technique is low. Also filtering has to be applied
in order to detect the zero‐crossing of the fundamental frequency, and therefore a delay is
introduced. This can be avoided using special high order predictive filter without delay, but
then the complexity becomes very high.
3.5.2 Filtering of grid voltages
By filtering the grid voltage in different reference frames, such as the two‐phase stationary
or the synchronous frame, the phase angle can be extracted directly using the arctangent
function. The filtering is done in either the stationary frame, or in the synchronous where
there are DC‐components. The arctangent function is always applied to the stationary
frame, thus giving the instantaneous phase angle. Therefore when the filtering is done in
the synchronous frame, the signal must be transformed back into the stationary frame
before applying the arctangent function.
In [18] it is reported improved performance over the zero‐crossing method, but the
technique encounters some difficulties in extracting the phase angle when grid variations
and or faults occur in the network. Another drawback of this method is the use of filtering,
since most filter types introduces a delay, the calculated phase angle will lag the real phase
angle.
Chapter 3 Control of Photo‐Voltaic Converters
Fundamentals of Grid Connected Photo‐Voltaic Power Electronic Converter Design
36
3.5.3 Phase Lock Loop (PLL)
A phase lock loop (PLL) produces an output signal which synchronizes in phase and
frequency with the input signal, using a negative feedback loop. The PLL controls the
internal signal such that, the error in phase between input and output is kept to a minimum,
and the frequency is equal at input and output. A basic PLL circuit often consists of three
components, a phase detector, a loop filter and a voltage controlled oscillator. This basic
circuit is shown in figure 3.9. Figure 3.9: A basic PLL circuit
The phase detector is implemented by transforming the voltages into the dq system. By
using the phase locked angle in the dq transformation, the phase difference between the
reference signal and the phase locked signal can be extracted by applying the arctangent
function. This gives the exact phase difference, but the phase difference can also indirectly
be found by recognizing that the phase difference is zero when Vq equals zero. In three‐
phase systems the transformation is easy to implement, but in single phase systems there
is only one voltage, so the orthogonal component of the voltage has to be found artificially.
The loop filter can be some sort of regulator, which brings the phase error to zero. This is
usually a PI regulator, but also higher order regulators can be used. A higher order system
increases the dynamics of the system and enhances the filtering capabilities, but it also
increases the complexity. When choosing the controller order, one must weigh what is
most important of the latter. When using a PI controller, this gives a second order system,
and then the PLL bandwidth and damping factor can be set using linear system theory.
After the loop filter, which output is the frequency, a voltage controlled oscillator is applied.
This is usually a simple integrator, which gives the phase locked angle as output. With the
PLL no delays are introduced, so the phase locked angle will be in phase with the grid angle.
A schematic model based on one presented in [7] is shown in figure 3.10, and shows the
basic principle of a phase lock loop with its transformations of the three‐phase voltages. In
this loop the arctan2 function is applied as the phase detector, giving the exact phase
difference.
Chapter 3 Control of Photo‐Voltaic Converters
37
NTNU Department of Electric Engineering
ω
α
αβ
ε
αβ
ω
ω
∫
θ
β
Figure 3.10: Schematic of a phase lock loop (PLL) with transformations
This algorithm has better rejection of grid harmonics, notches and any other kind of
disturbances then the previous methods, but during grid unbalancing further
improvements has to be done. In the case of a unsymmetrical voltage fault, the second
harmonics produced by the negative sequence will propagate through the PLL and become
reflected at the output. This means that in order to alleviate this problem, the zero‐
sequence signal has to be filtered out, thus the PLL is only estimating the phase angle of the
positive sequence signal.
3.5.4 Adaptive PLL
In [18] a more advanced PLL structure is described, based on a adaptive algorithm. In this
method three PLL systems is used, one for each phase. Where there are three control units
that individually control the frequency, phase angle and voltage magnitude of the grid
voltage. This gives precise information about each phase, and therefore this method is
suitable for grid monitoring, and thus islanding detection (see chapter 3.6) and safety
improvements. The disadvantage of this structure can be the large algorithm needed to
implement the controllers (3x3 controllers in this case, but it can be less in other
structures), and a moving average filter that is involved in the controllers which is
computationally heavy but very precise.
3.6 Anti Islanding
Islanding can be defined as the continued operation of a distributed generation unit while
the mains are tripped due to fault conditions or for maintenance purposes (from[19]).
Unintentional islanding of the PV system is not desirable because it can damage equipment
which remains connected to the inverter, and it can lead to dangerous situations since the
grid may be assumed deenergized. It is also a problem if the supply system is reconnected,
because then the PV system is likely to be out of phase, and large currents can be injected
into the PV system. A non islanding inverter is defined as an inverter that ceases to operate within a certain
time after an islanding situation has occurred. In order to detect the islanding situation,
different algorithms can be implemented in the inverter control. In [20] these algorithms
are divided into two major groups: remotely controlled (communication based) and locally
Chapter 3 Control of Photo‐Voltaic Converters
Fundamentals of Grid Connected Photo‐Voltaic Power Electronic Converter Design
38
built‐in detection schemes. This survey is dealing with the inverter as a locally controlled
device, so the communication based detection schemes are of no interest here. The local
detection schemes can be further divided into two groups, active and passive.
3.6.1 Passive
The passive methods are based on local measurements, and the most common methods
are
• Frequency limitations
‐ Magnitude change
‐ Rate of change
‐ Phase shift
• Voltage limitations
• Power
‐ Change of active power
‐ Change of reactive power
‐ Power factor (P/Q) and (df/dP) indices
• Harmonic content changes
These methods are usually easy to implement and they work without affecting the overall
system, unless the limits are to strict and the inverter trips without being in islanded mode.
One of the main limitations with these methods is that each of the methods have operating
regions where they are not able to detect an islanding situation within the given time limits.
This region is called the non‐detection zone (NDZ). The impact of these zones are usually
neglicible, but they can in some cases (particularly during balanced load conditions, when
the load matches the power produced by the inverter) become a problem. Often
combinations of these methods are used in order to reduce the NDZ.
3.6.2 Active
In these method disturbances is injected into the supply system in order to locally detect
islanding conditions based on system responses. The most common methods are based on
one of the following principles.
• Impedance measurement
• Voltage variation
• Frequency variation
• Output power variation
One of the advantages of these methods is increased ability to detect islanding even during
balanced load conditions, and thus decrease or even remove the NDZ. One of the main
problems with the active methods, is the interference of the disturbances introduced by
Chapter 3 Control of Photo‐Voltaic Converters
39
NTNU Department of Electric Engineering
multiple distributed resources connected to the same grid, and other side effects can also
be found depending on the method. Not much experience has been gained with these
methods yet, but this is an area of growing research activity.
3.7 Digital Signal Processing
In todays control of converters and drives it is mostly digital controllers which are used. The
use of digital controllers is convenient when implementing new control systems, since the
control can be programmed and uploaded into a digital controller. Thus it is easy to make
changes to the control, and problems with non ideal analog components is removed. On
the other hand when using a digital control system then everything is in the discrete
domain, which means one must change the system models and the way of thinking into the
discrete domain. The focus in this chapter is on the implementation of the control system
into a DSP.
3.7.1 DSP program
The control program of a DSP is often written in the high level language like C or C++, and
sometimes pieces of assembly code might be used for special purposes. In order to have
the code readable it is important to organize the code in a logical manner. In C++ the
program code can be organized in a structure where each specific function is given its own
class, and on a higher level it can be organized in separate files. In this way the code is easier
to read and it becomes easier to change the code at a later time. This can also make it easier
to test different algorithms, since it is then possible to change one function without making
changes to the rest of the code.
Interrupts
In a continuous system the calculations are continuous, but in the DSP the calculations are
executed at fixed (discrete) intervals. These intervals are called interrupts, and each
interrupt is started when a defined event occurs. The interrupts may be executed at the
same frequency, but they can be phase shifted, or they can run at different frequencies. In
the DSP there are a set of predefined triggers for the interrupt, and each interrupt has a
priority based on the event that triggered it. The priority means that if two interrupts are
pending, then the one with the highest priority will be executed first. All the algorithms needed to run the converter is executed in the interrupts. Which
algorithms that are executed in the different interrupts, depend on how fast they must
executed, and if some of the algorithms need to be phase shifted to one and another. An
example is the controllers which will usually be driven at the switching frequency in order
to have the fastest possible response, while the ADC (Analog to Digital Converter) can be
executed at the same frequency, but 180 degrees phase shifted in order to have the
measurements ready before the calculations start. In this way the calculations will have
fresh measurements, but will not be delayed by the measuring.
Chapter 3 Control of Photo‐Voltaic Converters
Fundamentals of Grid Connected Photo‐Voltaic Power Electronic Converter Design
40
Superior Control
In order to make everything run when it should run, and make sure things are not executed
if they are not intended to, some superior control is needed. This superior control can
involve a state machine which will have a set of defined states the system can be in. The
state machine will handle the transaction between the different states, and make sure no
illegal state transactions occur. In each state the superior control has defined which
algorithms that are allowed to run, and there is also some logic which tells when it is
allowed to or must leave that state. An example of a superior control with a state machine is shown in figure 3.11, this shows in
principle how the superior control works. The triangles in the figure represent the state
machine, and the squares represent the events which will occur in each state. The different
states can briefly be described as follows.
DSPERROR ‐ This is the state the system is operated in once a serious system error occurs.
The system will here be disabled, and must be manually restarted.
DSPRESET ‐ The system is transferred here when the user or the system needs to reset the
system for some reason. In this state the system is disabled, and once the system is
disabled it is automatically transferred to the next state.
VALUESINIT ‐ In this state the initial values for the measurements is sat, and offset values
for the ADC is found. When this is done the system is automatically transferred to the
next state
CONVINIT ‐ In this state the converter hardware is initialized if needed. When this is done
the system is automatically transferred to the next state
CONVCTRLINIT ‐ In this state the initial values for the control system is sat. When this is
done the system is automatically transferred to the next state
CONVREADY ‐ When the superior control has reached this state everything should be
initialized properly, and the converter should be ready to start. The system will be in
this state until the user sets a start bit. In this state it is also made sure that none of
the system variables is changed from their initial values before the system is started. CONVRUNNING ‐ When the system reaches this state, the converter starts running. All
algorithms concerning the operation of the converter is executed in this state. The
system will be in this state until the user sets the stop bit, or until a system error
occurs and the system is sat in the error state.
Chapter 3 Control of Photo‐Voltaic Converters
41
NTNU Department of Electric Engineering
Figure 3.11: Flow chart of superior control with state machine
Chapter 3 Control of Photo‐Voltaic Converters
Fundamentals of Grid Connected Photo‐Voltaic Power Electronic Converter Design
42
3.7.2 Measurements and analog to digital conversion
In a DSP the measured values has to be sampled before they can be used in any calculations,
and this is done using a analog to digital converter (ADC). When using an ADC it is important
to adjust the offset of the measurements before the measurements begin. If this is not
done, one can risk having a shift in the measured value compared to the actual value, and
in a three phase measurement it can lead to the measured values having a phase
unbalance, even though the real values don’t. According to the sampling theorem the sampled signal should not contain frequencies
above half the sampling frequency in order to avoid aliasing. In order to avoid this the most
common solution is to use an anti aliasing filter to remove higher frequencies before it is
sampled. This filter should then have a corner frequency of
ωc ≤
ωs
2
By using an analog filter to avoid anti aliasing, a phase delay is introduced in the
measurement, and the circuit is more complicated and expensive due to the extra filters.
Therefore it is desirable to avoid these filters if possible. A method called synchronous sampling [17,22] is a much used method in digital drives in
the industry. With this method the ADC is synchronized at the top or bottom peak of the
triangular PWM carrier signal. In this way the ADC conversion is made at an instant when
the switching harmonic currents are negligible. This gives a measurement which is close to
its averaged value, and with negligible ripple. Thus the need for an anti aliasing filter is
reduced, and is therefore not needed for the measurements.
3.7.3 Discretization
In order to analyse the system in the discrete domain, the continuous models will have to
be transformed into discrete models. There are several methods available for this, some
based on numerical integration and some on numerical derivation. Two of the most basic
methods used are the Euler’s forward and backward numerical integration methods, which
are first order transformations, meaning that they utilize only one sample per sampling
interval in the calculations. These methods are quite accurate when the sampled signal has
a frequency which is much lower than the sampling frequency, but the accuracy decreases
as the sampling frequency approaches the frequency of the sampled signal. Another method based on numerical integration called the trapezoidal method (also called
the bilinear transformation or Tustin’s method) is much used. This is a second order
transformation, which means it uses two samplings during each sampling interval.
Therefore this method is more accurate, and will not be as frequency dependent as the
Euler methods, and will therefore be the preferable method. The transformation from the
s‐plane to the z‐plane is achieved by inserting the relation in eq (3.14), into the continuous
time model.
Chapter 3 Control of Photo‐Voltaic Converters
43
NTNU Department of Electric Engineering
s=
2 z −1
Ts z + 1
(3.14) When the system is transformed into the z‐plane it is a small step left in order to implement
it in a computer algorithm. It can be transformed into the discrete time domain by
introducing the z‐operator as a time shift operator, where z means a positive time shift and
1/z means a negative time shift. The transfer function can then be used on discrete time
input and output values by using the relations shown in (3.15). The resulting expression will
be a difference equation, which can easily be implemented in a computer algorithm. It
should be noted that this is not the mathematically correct way, but it yields the correct
answer in an easy manner.
zx [ k ] = x [k + 1]
z −1x [ k ] = x [ k − 1]
(3.15) 3.7.4 Discrete filtering
The measured values might be in need for some filtering in order to remove unwanted
frequency components from the measurements before they are processed in the DSP.
Therefore some kind of filtering might be necessary, and in order to avoid the drawbacks of
the analog filters, a digital filter implementation will be more appropriate. There are lots of filtering techniques available, from simple first order to complex higher
order filters. If it is not necessary to have a very sharp cutoff, a simple first order filter will
usually do an appropriate job. Therefore only the implementation of this filter will be found
here. Based on the continuous model of a first order filter as shown in (3.17), the z‐
transformation can be applied and a computer based algorithm can easily be found. HF (s)
1
1 + sTF
(3.16) The bilinear transformation is found by substituting (3.14) into (3.16)
HF (z ) =
Ts + z −1
(TS + 2TF ) + (TS − 2TF ) z −1
(3.17) Next the time shift operator z is used as shown in (3.15), and a difference equation is found.
y [ k ] = a1x [ k ] + a2 x [ k − 1] + b1y [ k − 1]
Chapter 3 Control of Photo‐Voltaic Converters
(3.18) Fundamentals of Grid Connected Photo‐Voltaic Power Electronic Converter Design
a1 = a2 =
b1 =
44
TS
2TF + TS
TS
TF
−
2TF + TS 2TF + TS
The difference equation in (3.18) can then easily be implemented in a computer algorithm,
and if the sampling frequency is high compared to the corner frequency, the filter constant
can be used from the continuous model.
3.7.5 Discrete PI Regulator
Several places in the control algorithm there will be a need for PI regulators. In (3.19) the
transfer function of a PI regulator is shown. HPI (s ) = K P
1 + Ti s
Ti s
(3.19) In order to use this in a computer algorithm it must be discretized. By using the same
procedure as with the discretization of the filter, the z‐transformed model and a difference
equation can be found.
H PI ( z ) =
( K PTS + 2K PTI ) + ( K PTS − 2K PTI ) z −1
2TI − 2TI z −1
(3.20) The difference equation of this is the same as found in (3.18), but with these coefficients
a1 =
K PTS
+ KP
2TI
a2 =
K PTS
− KP
2TI
b1 = 1
3.8 P&O algorithm optimization
Since the efficiency of the INC and P&O algorithm is so close, and the P&O algorithm is
much easier to implement it will be analysed further. In order to have the efficiency of the
algorithm as high as possible, the algorithm would in an ideal case have an indefinitely small
duty cycle step, and be executed indefinitely often. This however is not possible because of
the characteristics of a real system. Their will be noise, time delays of different sorts and
changes in operating conditions which has to be considered. Therefore the minimum step
size and duty cycle which can be used without risking to “confuse” the algorithm should be
calculated.
Chapter 3 Control of Photo‐Voltaic Converters
45
NTNU Department of Electric Engineering
3.8.1 Minimum time step
A disadvantage of the P&O algorithm is a tracking error which might occur during rapid
changes of the solar irradiance. According to [24] the error occurs when the change in
irradiance during one sampling interval is larger and in the opposite direction of the power
change due to the duty cycle modulation. This will “confuse” the MPPT, and it will adjust
the duty cycle in the opposite direction. In order to reduce the risk of confusing the MPPT
during these changes, the sampling interval of the P&O algorithm should be sat as low as
possible without causing instability. In [23] it is stated that the system sampling interval
should be sat according to the converter’s dynamics, so that after each duty‐cycle
perturbation the system is allowed to reach the steady state operation before the next
perturbation. If the sampling is sat lower than this, the MPPT might become “confused” by
the PV array + converter transient behaviour.
In order to find the time at which the system has reached steady state one has to look at
the system model. It is shown in [23] that the array power is proportional to the PV voltage
squared, as shown in (3.21). Therefore by finding a model for the control to PV‐array
voltage, one can calculate the time before the transients caused by the control
perturbation has reached a certain value. When the system has reached this value, the
MPPT can safely run without being confused by the system dynamics.
pˆ (t ) = −
v pv2 (t )
RMPP
(3.21) Where RMPP is the steady state equivalent resistance of the PV load at the quiescent
operating point, where it is assumed that the operating point is in the vicinity of the MPP.
This relation is given in (3.22)
RMPP =
VMPP
IMPP
(3.22) The sampling interval can now be found by defining a region around the steady state value
of p̂ ( t ) which must be reached before a new sampling is allowed. 3.8.2 Minimum duty cycle step
When the sampling time of the algorithm is found, it is the duty cycle step size which will
appoint the speed of the MPPT. A larger step size gives a faster response, but more steady
state ripple and thus higher steady state loss. The minimum step size is constrained by the
maximum possible change in irradiance between each sampling. By using a to small step
size, the chance of confusing the MPPT during rapid changes in irradiance gets bigger. In
[24] a criteria for avoiding the confusion of the MPPT is found.
∆Pd > ∆PS
Chapter 3 Control of Photo‐Voltaic Converters
(3.23) Fundamentals of Grid Connected Photo‐Voltaic Power Electronic Converter Design
46
The criteria in (3.23) states that the change in PV power due to the perturbation of the duty‐
cycle must be larger than the change in PV power due to irradiation during one sample
period. In [24] eq (3.23) can be expanded and an equivalent expression is found (see [25]
for explanation of the right hand side).
⎛ 1 ∂ 2 i pv
⎜ 2
⎜ 2 ∂ v pv
⎝
VMPP −
MPP
1 ⎞
2
⎟ ( H 0 ⋅ ∆d ) > VMPP K ∆S
RMPP ⎟
⎠
(3.24) Where H0 is the DC gain of the system (4.2) and K is a material constant. For further detail
on this the reader is referred to [24] and [25].
3.9 PLL PI controller Optimization
When choosing the controller parameters for the PLL, a closed loop design which gives fast
tracking and good filtering characteristics should be pursued. These two requirements
cannot be required simultaneously, because they are inconsistent. So a trade of between
these two parameters must be made.
In a PLL using a PI regulator the closed loop control loop will be a second order transfer
function. According to [21] the Wiener method is the most widely used optimization
method, and for a second order loop the transfer function is according to this method given
as
H PLL (s ) =
2ωn s + ωn
s + 2ωn s + ωn 2
2
(3.25) Where closed loop bandwidth can be found by the use of the stochastic information of the
signal and noise, and by the Wiener method it is given as
ωn2 = ∆ωλ
2PS
W0
(3.26) ∆ω: Deviation of the frequency
PS : Input signal power
W0 : Input noise spectral density
λ : Lagrangian multiplier which determines the relative proportions of the noise and transient error
It is however concluded in [21] that it is very difficult to estimate the stochastic information
of the noise, and this relation does not provide the optimum result under the distorted
waveform. Therefore empirical trade‐off will be used instead. As mentioned before both
good filtering and fast tracking response is desired, where a low bandwidth gives a good
filtering effect whereas a high bandwidth gives faster tracking response, so both cannot be
Chapter 3 Control of Photo‐Voltaic Converters
47
NTNU Department of Electric Engineering
fully achieved. Errors caused by phase unbalancing and harmonics can be reduced by using
a low bandwidth, but by choosing a to low bandwidth the dynamic performance of the PLL
can become to low. If the compromise between filtering and dynamic response when using the PI controller is
not acceptable under distorted utility conditions, other methods such as higher order PLL
or other techniques should be considered.
3.10 Voltage and current controller optimization
Two controller optimization methods which are thorougly described in [35] will be used for
the voltage and current controllers of the inverter. Both these optimization methods are
based on modulus hugging, also called frequency response magnitude shaping. The
modulus hugging aims on bringing the modulus (absolute value) of the frequency
characteristic as close to the value of 1 over as wide a frequency range as possible, from
zero and upwards. By using modulus hugging, the result will always be control loops which
give stable operation. Therefore no further investigations of the stability of these control
loops is necessary. 3.10.1 Modulus optimum
The modulus optimum criteria can be used for processes containing several small time
constants, or systems having 1 or 2 large time constants and several small. It can be proved
that if the small time constants are small compared to the integrating time constant of the
controller, then the higher order products of the small time constants does not contribute
to the overall behaviour. Therefore the small time constants are added together and seen
as one equivalent time constant Teq.
The type of controller needed to achieve the modulus hugging depends on the which of
these three systems which is to be controlled. 1. System with several small first order delays
An integrating (I) controller as shown in (3.27) is suitable for this system. H I (s ) =
1
sTI
(3.27) This gives an open loop transfer function for the system as shown in eq (3.28) (small
t’s are used for the small time constants)
H1 ( s ) =
1
1
1
1
1
1
KS
"=
KS
sTI 1 + st1 1 + st 2 1 + st 3
sTI 1 + sTeq 1
The closed loop transfer function with this controller is then
Chapter 3 Control of Photo‐Voltaic Converters
(3.28) Fundamentals of Grid Connected Photo‐Voltaic Power Electronic Converter Design
M1 ( s ) =
KS
K S + sTI + s 2TT
I eq 1
48
(3.29) When optimized using modulus optimum, the controller parameter becomes
TI = 2K STeq1
(3.30) 2. System with one large and several small first order delays
For this system a proportional‐integral (PI) controller as shown in (3.31) is suitable.
This is because the PI controller contains a phase advance which then can be used to
compensate (cancel) the phase delay caused by the large time constant. If the phase
delay is not compensated, the large time constant must be added to the small time
constants and will make the control response slow. This will be shown by the
following equations.
H PI (s ) = K P
1 + sTI
sTI
(3.31) With this controller the open loop transfer function for the system becomes as shown
in eq (3.32) (small t’s are used for the small time constants)
H 2 (s ) = K P
1 + sTI 1
1
1
"
sTI 1 + sT1 1 + st1 1 + st 2
(3.32) If the large time constant is compensated by the PI phase advance (pole‐zero
cancellation) by setting TI=T1, the transfer function becomes as shown in (3.33).
H 2 (s ) = K P
1
1
KS
sTI 1 + sTeq 2
(3.33) The closed loop transfer function with this controller is then
M 2 (s ) =
K P KS
K P K S + sTI + s 2TT
I eq 2
(3.34) When optimized using modulus optimum, the controller parameter becomes
TI = T1
KP =
T1
2K STeq 2
(3.35) 3. System with two large and several small time constants
Chapter 3 Control of Photo‐Voltaic Converters
49
NTNU Department of Electric Engineering
For this system a proportional‐integral‐derivate (PID) controller as shown in (3.36) is
suitable. This is because the PID controller contains two phase advances which can be
used to compensate (cancel) the phase delay caused by the large time constants,
similar to the system with one large time constant. By compensating the two largest
time constant, the speed of the control loop is determined by the sum of the small
time constants. It could be possible to compensate more of the time constants in
order to make the control response even faster, but that would make the loop very
sensible to disturbances and it will be hard to achieve stable control.
H PID (s ) = K P
(1 + sTI )(1 + sTD )
sTI
(3.36) With this controller the open loop transfer function for the system becomes as shown
in eq (3.37) (small t’s are used for the small time constants)
H 3 (s ) = K P
1 + sTI 1
1
1
1
"
sTI 1 + sT1 1 + sT2 1 + st1 1 + st 2
(3.37) If the large time constants are compensated by the PID phase advances (pole‐zero
cancellation) by setting TI=T1 and TD=T2, the transfer function becomes as shown in
(3.38).
H 3 (s ) = K P
1
1
KS
sTI 1 + sTeq 3
(3.38) The closed loop transfer function with this controller is then M 3 (s ) =
K P KS
K P K S + sTI + s 2TT
I eq 3
(3.39) When optimized using modulus optimum, the controller parameter becomes
TI = T1
TD = T2
KP =
T1
2K STeq 3
(3.40) It can be seen from the closed loop transfer functions of these systems, that after
compensating for the large time constants, the systems end up as similar second order
transfer functions. Therefore it can be said that any system which can be compensated or
simplified in such a way that it gives a closed loop transfer function as shown in equation
(3.41), can be compensated using modulus optimum. Chapter 3 Control of Photo‐Voltaic Converters
Fundamentals of Grid Connected Photo‐Voltaic Power Electronic Converter Design
M MO (s ) =
ω02
s 2 + 2ζω0 s + ω02
50
(3.41) The generalized design criteria to achieve modulus hugging is
ζ =
1
2
(3.42) The frequency response of a modulus optimized control loop is shown in figure 3.12.
Figure 3.12: Frequency response of a modulus optimized control loop.
The step response of a modulus optimized control loop is shown in figure 3.13. This has a
rise time of 4.7Teq, a maximum overshoot of 4.3% above the final steady state value, and
the time used to reach the steady state within E2% (settling time) is 8.4Teq.
Chapter 3 Control of Photo‐Voltaic Converters
51
NTNU Department of Electric Engineering
Figure 3.13: Step response of modulus optimized control loop
3.10.2 Symmetrical optimum
If the system to be controlled also involves an integrator, modulus optimum criteria can not
be used. This is because compensation is not possible, since the integration of the
controller will be added to the integration of the controlled system, which in turn will lead
to oscillation of the controlled variable. Therefore another method to achieve modulus
hugging has to be used, which is called symmetrical optimum.
As with the modulus optimum, the type of controller needed to achieve symmetrical
optimum optimization depends on the system.
4. System with one integrating element and several small first order delays
This system will need a PI controller (eq (3.31)), because a phase advance is needed
in order to overcome the effect of the integrating element. This gives a system with
the open loop transfer function in eq(3.43), which can be optimized by symmetrical
optimum
H 4 (s ) = K P
1 + sTI
1 + sTI
1
1
1
1
1
1
" = KP
KS
KS
sTI
sTS 1 + st1 1 + st 2 1 + st 3
sTI
sTS 1 + sTeq 4
(3.43) Since compensation of this function only leads to oscillation, the closed loop transfer
function is found directly.
Chapter 3 Control of Photo‐Voltaic Converters
Fundamentals of Grid Connected Photo‐Voltaic Power Electronic Converter Design
M 4 (s ) =
52
K P K S (1 + sTI )
3
K P K S + sK P K STI + s 2TT
I S + s TT
I STeq 4
(3.44) When optimized with symmetrical optimum, the controller parameters become
TI = 4Teq 4
KP =
TS
2K STeq 4
(3.45) 5. System with one integrating element, one large and several small first order delays
With this system a PID controller (eq (3.36)) is needed in order to compensate the
large delay. The open loop transfer function of this system is H 5 (s ) = K P
(1 + sTI )(1 + sTD )
sTI
KS
1
1
1
1
"
sTS 1 + sT1 1 + st 2 1 + st 3
(3.46) After compensating and adding together the small time constants, the transfer
function becomes.
H 5 (s ) = K P
1 + sTI
1
1
KS
sTI
sTS 1 + sTeq 5
(3.47) Giving the closed loop transfer function
M 5 (s ) =
K P K S (1 + sTI )
3
K P K S + sK P K STI + s 2TT
I S + s TT
I STeq 5
(3.48) This is the same as for the system without one large time delay, so the controller
parameters become similar.
TI = 4Teq 4
TV = T1
KP =
Chapter 3 Control of Photo‐Voltaic Converters
TS
2K STeq 4
(3.49) 53
NTNU Department of Electric Engineering
6. System with only first order delays, where one is at least for times as large as the
remainder
With a system of this type, the large time delay can be approximated as an integrator.
The larger the time delay is compared to the remainder, the more correct this
assumption becomes. If this system is designed according to the symmetrical
optimum criteria, the transient response will be somewhere between that of
symmetrical optimum and modulus optimum. If the large time constant is equal four
times the remainder, the modulus optimum transient response is achieved, if it
becomes larger it will approach symmetrical optimum.
It can be seen from the closed loop transfer functions of these systems, that after
compensating for the large time constant, the systems end up as similar third order transfer
functions. As with the modulus optimum, it can be said that any system which can be
compensated or simplified in such a way that it gives a closed loop transfer function as
shown in eq (3.50), can be compensated using symmetrical optimum. MSO (s ) =
b0 + sb1
a0 + sa1 + s 2 a2 + s 3 a3
(3.50) Here a0=b0 and a1=b1, and if this equation is analysed in order to achieve modulus optimum,
then these design criteria can be found. a12 = 2a0 a2
a22 = 2a1a3
(3.51) The frequency response of a symmetrical optimized control loop is shown in figure 3.14.
Chapter 3 Control of Photo‐Voltaic Converters
Fundamentals of Grid Connected Photo‐Voltaic Power Electronic Converter Design
54
Figure 3.14: Frequency response of asymmetrical optimized control loop
The step response of a symmetrical optimized control loop is shown in figure 3.15. This has
a rise time of 3.1Teq, a maximum overshoot of 43.4% above the final steady state value, and
the time used to reach the steady state within E2% (settling time) is 16.5Teq.
Figure 3.15: Step response of symmetrical optimized control loop
Chapter 3 Control of Photo‐Voltaic Converters
55
NTNU Department of Electric Engineering
4 SYSTEM DESCRIPTION, MODELLING AND OPTIMIZATION
In this thesis a system is designed in order to demonstrate some of the theory described.
The system setup is based on the topologies and control methods shown in the first
chapters. Since most of these methods are well known and are not so complex, it has made
it easier to design and construct a complete system. If it shows out at a later time that more
advanced control is needed, these can easily be implemented at a later time when the
system is up and running. The system has been made first of all to test the different control methods, and therefore
it has not been designed to be a high efficiency system. However the control system has
been optimized with the methods described in chapter 3.10.
4.1 Converter topology and control description
In the setup for this assignment a multi‐string inverter with a DC‐DC converter and a DC‐AC
converter will be used. For the DC‐DC converter the current fed full bridge converter with a
HF transformer will be used, and for the DC‐AC converter an ordinary 3‐phase full bridge VSI
with an LCL filter as the grid interface will be used. The basic topology is shown in figure 4.1.
Figure 4.1: The basic converter topology
The control of the DC‐DC converter will be a P&O MPPT which utilizes the direct duty cycle
control, and the DC‐AC converter will be current controlled by PI regulators in a synchronous
reference frame. By locking the reference frame to the grid voltage, the d‐axis current will
represent the active power, and the q‐axis current the reactive power. In order to
synchronize with the grid a PLL with a PI regulator will be used, and in order to detect anti
islanding, passive methods complying with the requirements stated in chapter 2.1.1 will be
implemented. Pulse width modulation of the switch signals will be made based on SVPWM,
but other methods can also be implemented in order to test the difference.
In this setup no harmonic compensation will be implemented, and there will not be any
temporary storage since the system will always be connected to the grid. Chapter 4 System Description, Modelling and Optimization Fundamentals of Grid Connected Photo‐Voltaic Power Electronic Converter Design
56
4.1.1 DC‐DC converter values
Because the DC‐DC converter topology was not available as a laboratory converter, a new
one had to be constructed. Since this converter type is not so common, models for the
converter is not easily available in the literature, so therefore a steady state model and a
dynamic model based on small ripple AC modelling is derived in appendix 1. Based on the
steady state model, the converter is rated in appendix 3, and the rated values found are
presented in the table below.
Table 4.1 ‐ DC‐DC Converter component values
Component
Value
Input capacitor
330µF
Boost inductor
1.0mH
DC‐link capacitor
165µF
The operating conditions of the DC‐DC converter is shown in figure 4.2.
Table 4.2 ‐ DC‐DC operating conditions
Name
Value
Switching frequency
50kHz
DC‐link voltage
600V
Input voltage
170‐350 V
Input currenta
0.5‐5 A
Transformer ratio
1.4
Duty cycle limitsa
0.12‐0.58
a. Lower limit is based on keeping the converter operating in continu‐
ous mode
The switching devices will be mosfets in the inverter side and fast diodes on the rectifier
side of the converter. 4.1.2 DC‐AC converter and LCL filter values
An IGBT converter which is designed for laboratory use at NTNU SEfAS will be used as the
DC‐AC converter. But LCL filter which is used as a grid interface has to be buildt especially
for this setup. The rating of this filter can be found in appendix 3. The component values of
the filter and the DC‐AC converter are presented in the table below, and the converter
operating conditions is shown in table 4.4.
Chapter 4 System Description, Modelling and Optimization 57
NTNU Department of Electric Engineering
Table 4.3 ‐ DC‐AC Converter and LCL filter component values
Component
Value
DC‐link capacitor
3300µF
Inverter side inductance Li
4.3mH
Filter capacitance Cf
0.68µF
Grid side inductance Lg
2.0mH
Damping resistor Rd
10Ω
.
Table 4.4 ‐ DC‐AC converter and LCL filter operating conditions
Name
Value
Switching frequency
20kHz
DC‐link voltage
600V
Output voltage
0‐400V RMS
Current limit pr leg
25A (at 20kHz)
Pulse width modulation
0‐100%
Resonance frequency fres
5224Hz
4.1.3 Laboratory setup
A schematic of the laboratory setup is shown in figure 4.2, and a equipment specification is
listed in table 4.5. Table 4.5 ‐ Equipment in laboratory setup
Type
Brand
Model
#
Current transducer
LEM
LAH 25‐NP
1
Current transducer
LEM
LA 205‐S
3
Voltage transducer
LEM
LV 25‐600
5
Controller card
NTNU/SEfAS
TMS 320 F2812
2
Measuring board
NTNU/SEfAS
v1.0
1
Variable DC power supply
Sorensen
DLM 300‐10E
1
DC power supply
Traco Power
TXL 060‐0533T
2
Chapter 4 System Description, Modelling and Optimization Fundamentals of Grid Connected Photo‐Voltaic Power Electronic Converter Design
58
The controller cards used are based on the Texas Instruments TMS320F2812, which is a 16/
32bits, 150MHz DSP micro controller. The card utilizes a Xilink XC95288XL CPLD as gate
expansion. The DC‐link has also been equipped with a charging circuit in order to avoid large
inrush currents when connecting the grid. The current and voltage measurements are
made with LEM current and voltage transducers, and when the DSP card is extended with
the external measurement card it can handle eight LEM modules. The DSP has a buildt in
12bit analog to digital converter which can maximum handle 16 channels per conversion. Variable
DC-Power
Supply
VPV
IPV
DC
Power Supply
DSP
DC-DC
Converter
VDC
DC
Power Supply
DSP
DC-AC
Inverter
Iiabc
Measure
Card
LCL-Filter
Vgabc
3-Phase
Grid
Figure 4.2: Schematic of laboratory setup
Chapter 4 System Description, Modelling and Optimization 59
NTNU Department of Electric Engineering
4.2 P&O Maximum Power Point Tracker optimization
Minimum time step
In the appendix 1 a small signal AC model was developed for the DC‐DC converter. This
model gives a third order system, and can be difficult to analyse analytical. In order to
simplify this model it is assumed that the DC‐link is stiff, therefore the AC variations in the
DC‐link is zero. With this simplification the transfer function becomes as shown in (4.1).
Hvpvd
vˆ pv ( s )
=
=−
dˆ ( s )
V ⎞
1 ⎛
IL Ron + DC ⎟
⎜
Cpv Lb ⎝
n ⎠
⎛R
R D ⎞
1
s 2 + s ⎜ on + on m ⎟ +
L
L
C
b
pv Lb
⎝ b
⎠
(4.1) This is a typical 2nd order transfer function, and can be analysed using well known methods.
Equation (4.1) can be written as
Hvpvd =
vˆ pv ( s )
µω02
= 2
2
dˆ ( s ) s + 2ω0ζ s + ω0
(4.2) Where ⎛
µ = − ⎜ IL Ron +
⎝
ω0 =
ζ =
VDC ⎞
n ⎟⎠
1
C pv Lb
C pv Ron (1 + Dm )
Lb
The step response of the PV voltage then becomes
vˆ pv ( s ) =
dˆ ( s )
µω02
s 2 + 2ω0ζ s + ω02 s
(4.3) Transformed into the time domain the step response becomes
⎛
1
vˆ pv ( t ) = µ∆d ⎜ 1 −
e −ζω0t cos
2
⎜
1− ζ
⎝
(
⎞
1 − ζ 2 ω0 t − arcsin (ζ ) ⎟
⎟
⎠
)
(4.4) The sampling interval can now be found by defining a region around the steady state value
of p̂ ( t ) which must be reached before a new sampling is allowed. The steady state value
and the region is defined in (4.5) and (4.6) respectively.
Chapter 4 System Description, Modelling and Optimization Fundamentals of Grid Connected Photo‐Voltaic Power Electronic Converter Design
pˆ (t ) = −
60
µ 2 ∆d 2
t →∞
RMPP
(4.5) ⎡ (1 + ε ) µ 2 ∆d 2 (1 − ε ) µ 2 ∆d 2 ⎤
,−
⎢−
⎥
RMPP
RMPP
⎢⎣
⎥⎦
(4.6) Where ε gives the allowed deviation from the steady state value, and in this case a
deviation of 10% giving ε = 0.1 is assumed to be adequate. Based on (4.4) to (4.6) it is shown
in [23] that the time T ε before p̂ is confined within the region in (4.6) can be approximated
as
Tε ≅ −
1
ζω0
ln ( ε )
(4.7) Based on the chosen component values T ε becomes 9.3ms. To be on the safe side the
sampling time is then chosen to be TS_MPPT = 10ms.
Minimum duty cycle step
The minimum duty cycle step has been calculated based on eq (3.24). The calculated value
became close to 16µs, which would make the MPPT algorithm very slow. There is also a
possibility that this equation is not evaluated correctly since there are so many factors
involved. In order to have a faster process a step size of ∆d = 0.001 will be used. 4.3 Phase Locked Loop PI Regulator
4.3.1 Model
A model of the three‐phase PLL is shown in the figure below
θ( )
θ ( )
Figure 4.3: PLL model
The PI regulator is the same as in eq (3.10), and then the closed loop transfer function with
the grid angle as input and the PLL angle as output becomes as shown in (4.8), and the
phase error is found in (4.9).
Chapter 4 System Description, Modelling and Optimization 61
NTNU Department of Electric Engineering
M c (s ) =
θPLL
=
θg
ε
=
θg
Mε (s ) =
Kps +
Kp
Ti
s2 + K ps +
Kp
ωn =
ζ =
2ζωn s + ωn 2
s + 2ζωn s + ωn 2
2
Ti
s2
Kp
s2 + K ps +
=
(4.8) =
s2
s + 2ζωn s + ωn 2
2
Ti
(4.9) Kp
Ti
Kp
2ωn
=
K pTi
2
4.3.2 Optimization
Based on the optimization criteria found in chapter 3.9, the second order loop parameters
must satisfy
ω0 ≥ 2π fg (lower gives good filtering, higher gives good tracking response)
ζ =
1
2
(4.10) In order to achieve both good filtering and a fast tracking response, the undamped
resonance frequency is sat to 628 rad/s (twice the grid frequency), giving these regulator
parameters.
K P = 890
Ti = 0.0023
The parameters are calculated according to a continuous system, and this can be done if
the sampling time of the discrete system is less then the fastest time constant of the
physical process. In this case the process is a pure integrator, and the time constant of the
regulator is much larger than the sampling time constant (TS=50µs). By using the bilinear transform, which involves substituting eq (3.14) into (4.8) and (4.9) and
rearranging, gives the system in discrete form as shown in (4.11) and (4.12).
Mc (z ) =
( −4T ζω
S
( 4 − 4T ζω
S
0
0
+ TS2ω02 ) z −2 + ( 2TS2ω02 ) z −1 + ( 4TS ζω0 + TS2ω02 )
+ TS2ω02 ) z −2 + ( −8 + 2TS2ω02 ) z −1 + ( 4 + 4TS ζω0 + TS2ω02 )
Chapter 4 System Description, Modelling and Optimization (4.11) Fundamentals of Grid Connected Photo‐Voltaic Power Electronic Converter Design
Me (z ) =
( 4 − 4T ζω
S
0
62
4 z −2 − 8z −1 + 4
+ TS2ω02 ) z −2 + ( −8 + 2TS2ω02 ) z −1 + ( 4 + 4TS ζω0 + TS2ω02 )
(4.12) In figure 4.4 the frequency response of the PLL transfer functions is plotted, and in figure
4.5 the bode diagram of the disturbance rejection is shown. In figures 4.6 and 4.7 the step
response and a pole‐zero plot of the function is shown. It can be seen that the discrete
system shows similar response as the continuous system at frequencies lower than
approximately 5kHz. Figure 4.4: Bode plot of transfer function between input and output
Blue dotted: Discretized system
Red continuous: Continuous system
From figure 4.5 it can be seen that disturbances with frequency above twice the grid
frequency (100Hz) is filtered.
Chapter 4 System Description, Modelling and Optimization 63
NTNU Department of Electric Engineering
Figure 4.5: Bode plot of transfer function between input and error
Blue dotted: Discretized system
Red continuous: Continuous system
From the step response the time used to reach the steady state within E2% (settling time)
is found to be approximately 10ms. Figure 4.6: Step response of the continuous and the discrete transfer function, MC(s) and MC(z)
Blue: Discretized system
Red: Continuous system
Chapter 4 System Description, Modelling and Optimization Fundamentals of Grid Connected Photo‐Voltaic Power Electronic Converter Design
64
All poles and zeroes are inside the unit circle, and therefore the PLL control loop will show
stable performance. Figure 4.7: Pole‐zero plot of the discrete transfer function MC(z)
4.4 Current Regulator
The current regulator is found in the inner control loop of the DC‐link voltage regulator.
These are actually two regulators, one for the d‐ and one for the q‐axis. Both of these
regulators are working on the same system model, and it is adequate to estimate the
parameters of one of them. 4.4.1 Model
The current control loop for the d‐axis can be modelled as shown in figure 4.8 (similar for
q‐axis).
Figure 4.8: D‐axis current control loop (similar for q‐axis).
In this model all non‐linearities and noise in the output voltage is ignored for simplicity. The
blocks in the figure are described as follows.
Chapter 4 System Description, Modelling and Optimization 65
NTNU Department of Electric Engineering
HDSP ‐ Represents the time delay caused by the DSP, as it needs some time to do calculations
and because of the way signals are sampled. The time delay caused DSP will be a minimum
of half the switching period, that is 25µs. H DSP (s ) =
1
1 + TDSP s
(4.13) Hdcac ‐ Represents the time delay caused by the inverter, because the desired output voltage
from the inverter will be the time average over one switching period. It will take
approximately half the switching period from a new voltage reference is applied until it is
averaged over the load, thus the time delay becomes 25µs.
Hdcac (s ) =
1
1 + Tdcac s
(4.14) Hfi ‐ In order to reduce unwanted noise in the measurement a first order digital filter with a
corner frequency of 3 kHz will be used, which gives a delay of 333µs Hfi (s ) =
1
1 + Tfi s
(4.15) HPI ‐ Represents the PI regulator (eq(3.19))
Hiivi ‐ Represents a transfer function of the LCL filter, and will describe how the inverter
output current reacts to a change in output voltage from the inverter. A model of the filter is shown in figure 2.10, and based upon this a mathematical model of
the filter in the dq reference frame has been derived. This result is shown in eq (4.16), and
the derivation can be found in appendix 2.
⎡ R i + Rd
⎡ di id (t ) ⎤ ⎢ −
Li
⎢ dt ⎥ ⎢
⎢
⎥ ⎢
⎢ di iq (t ) ⎥ ⎢ −ω
⎢ dt ⎥ ⎢
⎢
⎥ ⎢
⎢ di gd (t ) ⎥ ⎢ Rd
⎢ dt ⎥ ⎢ Lg
⎢
⎥=⎢
⎢ di gq (t ) ⎥ ⎢
0
⎢ dt ⎥ ⎢
⎢
⎥ ⎢
⎢ dv cd (t ) ⎥ ⎢
1
⎢ dt ⎥ ⎢
C
f
⎢
⎥ ⎢
⎢ dv cq (t ) ⎥ ⎢
0
⎣⎢ dt ⎦⎥ ⎢
⎣
ω
R + Rd
− i
Li
0
−
Rd
Li
0
0
Rd
Li
0
ω
1
Lg
R g + Rd
Lg
Rd
Lg
−ω
0
1
−
Cf
1
Cf
0
−
R g + Rd
Lg
−
−
1
Li
0
0
0
1
Cf
−ω
⎤
0 ⎥
⎡1
⎥
⎢L
1⎥
⎢ i
− ⎥
Li ⎥ ⎡ i id (t ) ⎤ ⎢
0
⎥ ⎢ i iq (t ) ⎥ ⎢
⎢
⎢
⎥
0 ⎥
⎥ ⎢ i gd (t ) ⎥ ⎢ 0
⎥ ⎢ i (t ) ⎥ + ⎢
1 ⎥ ⎢ gq ⎥ ⎢
Lg ⎥ ⎢v cd (t ) ⎥ ⎢ 0
⎥ ⎢
⎥⎢
⎢⎣v cq (t ) ⎥⎦ ⎢
⎥
ω ⎥
⎢0
⎢
⎥
⎢⎣ 0
⎥
0 ⎥
⎦
0
0
1
Li
0
0
−
1
Lg
0
0
0
0
0
0
⎤
0 ⎥
⎥
⎥
0 ⎥
⎥ ⎡ v id (t ) ⎤
⎥ ⎢ v (t ) ⎥
0 ⎥ ⎢ iq ⎥
⎥ ⎢v gd (t ) ⎥
⎢
⎥
1 ⎥ v (t )
− ⎥ ⎣⎢ gq ⎦⎥
Lg ⎥
0 ⎥⎥
0 ⎥⎦
(4.16) Chapter 4 System Description, Modelling and Optimization Fundamentals of Grid Connected Photo‐Voltaic Power Electronic Converter Design
66
From this model it can be seen that the d‐ and q‐ axis of the currents are dependent, so a
decoupling should be used in order to simplify the model. In order to simplify the model
further the capacitor voltage can also be fed forward. Since the capacitor voltage is not
measured it can not be fed forward directly. There are two alternative ways of doing this,
one is to feed forward the grid voltage and assume that the difference between this and the
capacitor voltage is handled by the integrator in the controller. The other solution is to
estimate the capacitor voltage, based on the grid voltage and the inverter current.
Assuming one of these two feed forward methods will be used, the model of the LCL filter
can be simplified.
Based on the mathematical model in (4.16), the converter output current can be expressed
as in eq (4.17) and (4.18), where the feed forward terms are marked with colours. The blue
colour indicates the cross coupling between the d‐ and q‐axis, and the red colour indicates
the filter capacitor voltage. The capacitor voltage also includes the damping resistor, in
order to make the error less by using the grid voltage as feed forward instead.
Li
Li
di id (t )
= Rd ( i gd (t ) − i id (t ) ) − v cd (t ) + v id (t ) − Ri i id (t ) + ω Li i iq (t )
dt
di iq (t )
dt
= Rd ( i gq (t ) − i iq (t ) ) − v cq (t ) + v iq (t ) − Ri i iq (t ) − ω Li i id (t )
(4.17) (4.18) Collecting the feed forward terms into a single term gives the equations (4.19) and (4.20).
v idII = Rd ( i gd (t ) − i id (t ) ) − v cd (t ) + ω Li i iq (t )
v iqII = Rd ( i gq (t ) − i iq (t ) ) − v cq (t ) − ω Li i id (t )
(4.19) (4.20) By applying the feed forward terms, the model gets simplified to the to equations (4.21)
and (4.22).
Li
Li
di id (t )
= v id (t ) − Ri i id (t )
dt
di iq (t )
dt
= v iq (t ) − Ri i id (t )
(4.21) (4.22) These to equations are similar, and will have the same transfer function. The transfer
function of the LCL filter with the decoupling becomes
H iivi (s ) =
i id (s ) i iq (s )
1 Ri
1
=
=
=
v id (s ) v iq (s ) sLi + Ri 1 + Tiivi s
Chapter 4 System Description, Modelling and Optimization (4.23) 67
NTNU Department of Electric Engineering
Using measured values for the inductances (se chapter 4.1.2), the time constant becomes.
Tiivi =
Li 4.45mH
=
= 2.47ms
Ri
1.8Ω
4.4.2 Optimization
The Tiivi time constant is much larger then the rest of the time constant, so this can be seen
as a system of one large and several small time constants. Therefore modulus optimum
with a PI controller can be used as an optimization criteria, as is described in chapter 3.10.1.
The model in figure 4.8 is therefore reduced by adding together the small time delays,
giving the model in figure 4.9.
Figure 4.9: Reduced current control model
Where the sum of the time delays is defined in eq (4.24)
Heqi (s ) =
1
1
=
1 + (TDSP + Tdcac + Tfi ) s 1 + Teqi s
(4.24) Giving the equivalent time delay.
Teqi = TDSP + Tdcac + Tfi = 25 µ s + 25µ s + 333µ s = 383µ s
The sum of these time constants is approximately four times larger then the sampling time
constant Ts, and therefore only a small error will occur if the parameters are designed after
the continuous system. The open loop transfer function of this system then becomes
Hid (s ) = K P
1 + Ti s
1 Ri
1
⋅
⋅
Ti s 1 + Teqi s 1 + Tiivi s
(4.25) In order to compensate the pole from the large time delay, the phase advance from the PI
regulator is used. This leads to an integral time which is equal the large time constant, giving
the closed loop transfer function
Chapter 4 System Description, Modelling and Optimization Fundamentals of Grid Connected Photo‐Voltaic Power Electronic Converter Design
M id (s ) =
H id
=
1 + H id
KP
1 Ri
Ti s (1 + Teqi s )
1 + KP
1 Ri
Ti s (1 + Teqi s )
=
K P Ri
Ti s (1 + Teqi s ) + K P Ri
=
KP
TT
i eqi R i
68
1
s2 +
KP
1
s+
Teqi
TT
i eqi R i
(4.26) Which can be recognized as a second order function on the form of (3.41), giving
ω0 =
ζ =
KP
TT
i eqi R i
1 Ti Ri
2 K PTeqi
(4.27) (4.28) By using the modulus optimum criteria the damping factor ζ is sat equal to 1 ⁄ 2 , giving
the closed loop transfer function the value 1 between zero frequency and as high a
frequency as possible. The controller parameters now become.
Ti = Tiivi = 2.47ms
KP =
Ti Ri
= 5.8
2Teqi
The system is discretized by applying the bilinear transform to eq (3.41), giving the discrete
transfer function in (4.29).
M ( z ) = KTS2ω02
z −2 + 2z −1 + 1
( 4 − 4TSζω0 + TS2ω02 ) z −2 + ( −8 + 2TS2ω02 ) z −1 + ( 4 + 4TSζω0 + TS2ω02 )
(4.29) In figure 4.10 the bode diagram of the continuous system and the discretized system is
plotted. From the diagram it can be seen that the discrete system behaves as a continuous
system up to approximately 5kHz, this proves that the approximation of the system as
continuous was correct. It can also be seen from the magnitude plot that the magnitude has
the value 1 up to a high frequency, as it should using the modulus optimum criteria.
Chapter 4 System Description, Modelling and Optimization 69
NTNU Department of Electric Engineering
Figure 4.10: Bode diagram of continuous and discretized closed loop models of the inner con‐
trol loop
Blue dotted: Discretized system
Red continuous: Continuous system
In figure 4.11 the step response of the system in discrete and continuous form is shown. It
can here be seen that the response of the discrete system follows the continuous system.
Figure 4.11: Step response of the discrete and the continuous time model of the inner control loop
Chapter 4 System Description, Modelling and Optimization Fundamentals of Grid Connected Photo‐Voltaic Power Electronic Converter Design
70
In figure 4.12 a pole zero‐plot of the discretized system is plotted. This shows that the poles
of the closed loop lies inside the unit circle, and therefore the system is stable as predicted
when using modulus hugging optimization.
Figure 4.12: Pole‐zero plot of the discretized closed loop system
4.5 Voltage controller
The voltage controller is found in the outer control loop of the DC‐link voltage control. The
output from this regulator is the reference to the d‐axis current controller in the inner
control loop. 4.5.1 Model
The DC‐voltage controller is found in the outer control loop, and is shown in the figure
below
Figure 4.13: DC‐link voltage control loop
Chapter 4 System Description, Modelling and Optimization 71
NTNU Department of Electric Engineering
Hfi ‐ In order to reduce unwanted noise in the measurement a first order digital filter with a
corner frequency of 3 kHz will be used, which gives a delay of 333µs.
Hfv (s ) =
1
1 + Tfv s
(4.30) HPI ‐ Represents the PI regulator (eq (3.19))
Mid ‐ Represents the d‐axis current controller, and in order to use the symmetrical optimum
criteria, the system should be approximated as a first order system. This can be justified
knowing that the outer control loop must be slower than the inner control loop. Based on
eq (3.41), the inner control loop transfer function can be rewritten as follows.
1
1 2 2ζ
s +
s +1
2
M id (s ) = K
ω0
ω0
(4.31) At frequencies below ω0
1
ω
2
0
s2 1
And the system can be approximated as the first order function in eq (4.32).
M id (s ) =
1
2ζ
ω0
s +1
=
1
4ζ Tsum s + 1
2
=
1
2
⎛ 1 ⎞
4⎜
⎟ Tsum s + 1
⎝ 2⎠
=
1
1 + 2Tsum s
(4.32) The difference between the approximation and the 2.order system is shown in figure 4.14,
and it can here be seen that the approximation is correct at low frequencies.
Chapter 4 System Description, Modelling and Optimization Fundamentals of Grid Connected Photo‐Voltaic Power Electronic Converter Design
72
Figure 4.14: Bode diagram of the 1.order approximation compared to the 2.order original sys‐
tem
Red: 2.order original system
Blue: 1.order approximation
HDC ‐ Represents the transfer function between the d‐axis current and the DC‐link voltage.
The DC‐link voltage will vary with the DC‐link current according to the following transfer
function
H DC (s ) = K DC
1
CDC s
(4.33) The constant KDC is a constant relating the d‐axis current to the dc‐current. The currents can
be related knowing the power balance in eq (4.34), and the relation between the dc‐link
voltage and the d‐axis voltage. The latter relation is derived in (4.35)
3
VDC IDC = Vd Id
2
Vab =
3
2 2
(4.34) VDC ma
2
1
Vd = Vˆα = Vˆa =
Vab = VDC ma
2
3
(4.35) By combining (4.34) and (4.35), the relation between the currents is found in (4.36).
Chapter 4 System Description, Modelling and Optimization 73
NTNU Department of Electric Engineering
K DC =
IDC 3 Vd
3 1 VDC
3
=
=
ma = ma
2 VDC 2 2 VDC
4
Id
(4.36) 0 ≤ ma ≤ 1 with sinusoidal CB-PWM
0 ≤ ma ≤ 2
3
with SVM or CB-PWM with third harmonic injection
Assuming SVPWM is to be used, and in order to generate a voltage close to the grid voltage
a modulation ratio close to maximum will be used most of the time. Therefore the constant
relating the DC‐link current and the d‐axis current becomes.
3
3 2
3
K DC = ma ,max =
=
≈ 0.87
4
4 3
2
4.5.2 Optimization
The voltage control system contains two phase delays where both are of the same order,
and can be summed together as one time constant. The system then satisfies the
symmetrical optimum criteria where there is one integrator, several time constants and a
PI regulator. The open loop transfer function of the voltage control system can now be
written as
H DC (s ) = K P K DC
1 + Ti s
1 + Ti s
1
1
= K P K DC
CDCTi s 2 1 + (2Teqi + Tfv )s
CDCTi s 2 1 + Teqv s
(4.37) Teqv = 2Teqi + Tfv
Giving the closed loop transfer function in (4.38). If compared to eq (3.50) it can be seen
that it satisfies the symmetrical optimum criteria.
M DC (s ) =
H DC (s )
Ti s + 1
= K P K DC
3
2
1 + H DC (s )
CDCTT
i eqv s + CDC Ti s + K P K DCTi s + K P K DC
(4.38) According to the symmetrical optimum criterion the parameters can now be found
Ti = 4Teqv = 4.4ms
KP =
1 CDC
= 1.72
2 K DCTeqv
By inserting the controller parameters into eq (4.38), an equation called the standard
equation for the symmetrical optimum is obtained
Chapter 4 System Description, Modelling and Optimization Fundamentals of Grid Connected Photo‐Voltaic Power Electronic Converter Design
M DC (s ) =
74
1 + 4Teq s
8Teq s + 8Teq 2 s 2 + 4Teq s + 1
3 3
(4.39) In figure 4.15 a bode diagram of the model is shown, where the continuous model is
compared to a discretized model. The system is discretized using the c2d function in Matlab
with the sampling time TS.
Figure 4.15: Bode plot of the continuous and discrete voltage control loop
Red continuous: Continuous system
Blue dotted: Discrete system
The step response of the optimized loop is similar to the one shown in figure 3.15, and it
can be seen that the step response is equal for the discretized and the continuous system.
Chapter 4 System Description, Modelling and Optimization 75
NTNU Department of Electric Engineering
Figure 4.16: Continuous and discrete step response of the voltage control loop
As expected also all the poles are inside the unit circle as it should when using a modulus
hugging technique.
Figure 4.17: Pole‐Zero plot of the discrete voltage controller
Chapter 4 System Description, Modelling and Optimization Fundamentals of Grid Connected Photo‐Voltaic Power Electronic Converter Design
76
4.6 Complete control system model
With the controller optimization and model simplifications made in the previous chapters,
an overview of the complete control system can be made. This is shown in the figure below
α
αβ
αβ
β
θ
α
αβ
β
αβ
α
ω
ω
αβ
αβ
β
θ
2/3
Figure 4.18: Overview of the control system of the DC‐DC converter and the DC‐AC converter
Chapter 4 System Description, Modelling and Optimization 77
NTNU Department of Electric Engineering
5 SIMULATION
The simulation of the converters are made in Simulink, which is a simulation program based
on the Matlab platform. In the simulation the converters are simulated separately since the
DC‐DC converter and the DC‐AC converter are supposed to work as separate units
connected to the same DC‐link. A brief description of the simulations can be found in
appendix 5.
5.1 DC‐DC Converter
In the simulation of the DC‐DC converter the MPPT is simulated with a simplified model of
the converter, based upon the small signal AC model derived in appendix 1. As the PV panel
input the I‐V characteristic of a PV panel is incorporated as a look up table. The look up table
is loaded from a GUI (Graphical User Interface), in which the user can change the solar panel
operating conditions. The look up table values are calculated based on the equations found
in chapter 2.2.1
5.1.1 I‐V Characteristic
The I‐V characteristic of the simulated PV panels under STC is shown in the GUI in figure 5.1. Figure 5.1: GUI of the PV‐panel I‐V characteristic under STC
Chapter 5 Simulation
Fundamentals of Grid Connected Photo‐Voltaic Power Electronic Converter Design
78
The I‐V characteristic is based on values from actual solar panels, but it was found that the
calculated values are closer to an ideal I‐V characteristic than the panels actually are. This
is due to the fact that the models found in chapter 2.2.1 does not consider e.g the
resistances and other nonidealities in the PV cells. This however will not be of any
significance since the model will only be used to simulate the MPPT, and not simulate real
cells. This model can easily be made more accurate if needed later, by adding more
accurate models of the PV cells.
In the next figure the characteristic of the PV panels is shown under a partial shadow
condition. The shadow is across 40% of the cells with 50% shadowing, and all the cells are
in series. From the P‐V characteristic two maximum power points can be found, and these
will confuse the MPPT. The simple algorithm used in the P&O algorithm will not be able to
see the difference between these points, and it will find one of these points depending on
where the tracker was before the shadowing. In order to test how much this will influence
the efficiency of the MPPT, the tracker should be tested over some time with varying
degrees of shadowing. No simulations with varying conditions have been made here.
Figure 5.2: GUI of the PV‐panel I‐V characteristic under partial shadowing
Chapter 5 Simulation
79
NTNU Department of Electric Engineering
5.1.2 Maximum Power Point Tracker
The simulation of the MPPT was made with the I‐V characteristic at STC shown in figure 5.1.
No tests where made with shadowing since it is obvious that it will not work as explained in
the previous section. In figure 5.3 the duty‐cycle steps from the MPPT is shown when a step
in the irradiance from 0 to 100% is given. It can here be seen that with the chosen values of
sampling time and step size the MPPT reaches steady state in approximately 0.8s. Figure 5.3: Duty‐cycle steps due to the MPPT
The current, voltage and power values of the PV panel when the MPPT has reached steady
state is shown in figure 5.5. It can here be seen that after each perturbation, there is some
transient behaviour in the values as expected, and from figure XX it can be seen that within
the next perturbation this is approximately within 10% of the initial value. In the
simulations a steady state efficiency of the MPPT of 99.9% was found.
Figure 5.4: Ripple in PV power after a perturbation in the duty cycle
Chapter 5 Simulation
Fundamentals of Grid Connected Photo‐Voltaic Power Electronic Converter Design
Figure 5.5: PV voltage, current and power during MPP
Chapter 5 Simulation
80
81
NTNU Department of Electric Engineering
5.2 DC‐AC Converter simulation results
A description of the simulation model can be found in appendix 5. Most of the simulations
has been made on a simplified model of the plant with a pure sinusoidal output from the
inverter, since the dynamics of the control system will be the same. But in the harmonic
analysis full PWM was used in order to test the filtering effect of the LCL filter.
In order to reduce the complexity of the model, carrier based modulation is used instead of
space vector modulation. This modulation technique is simpler to implement in Simulink,
and by using third harmonic injection with a ZSS signal of 1/4 the amplitude of the
fundamental, an equal result to that of SVPWM can be achieved.
5.2.1 PLL
In figure 5.6 the results from the simulation of the PLL is plotted. This shows that the time
used to reach the steady state within 2% (settling time) is approximately 10ms, when a
phase jump of 30° is applied. Figure 5.6: Simulation of PLL with a start‐up angle of 30° and a phase jump of 30° at 20ms.
Chapter 5 Simulation
Fundamentals of Grid Connected Photo‐Voltaic Power Electronic Converter Design
82
5.2.2 Current control
The current control system is simulated with a fixed DC‐link voltage, where the DC‐link
voltage controller is disconnected. Instead a step of 1A in the d‐axis current reference is
applied, and the d‐ and q‐ axis current response is found. When using the parameters found
in chapter 4.4, the step response of the d‐ and q‐ axis current becomes as shown in figure
5.7. The step response has a rise time of 8.3Teqi,an overshoot of ca 1.5% and a settling time
equal the rise time
Figure 5.7: Step response of d‐ and q‐ axis current with parameters found by modulus optimiza‐
tion
The q‐current also reacts to a step in the d‐axis current. This shows that the circuit is not
completely decoupled as it should be. With the modulus optimized controller parameters
the loop become slower than what was predicted, and this had consequences for the
cascaded voltage control loop. By adjusting the parameters gain to 1.6KP, the control loop
acted approximately as it should according to the modulus optimization.
5.2.3 Voltage control
To test the voltage controller a step is applied in the DC‐link voltage reference. In figure 5.8
the step response of the DC‐link is shown, this is the response to a step of 1V applied at
55ms. The DC‐link voltage response has a rise time of 2.7Teqv,, an overshoot of 34%, and the
Chapter 5 Simulation
83
NTNU Department of Electric Engineering
time used to reach the steady state within E2% of the step size is 13Teqv. It was also noted
that by running steps larger then approximately 1V, the voltage controller went into
saturation.
Figure 5.8: DC‐link voltage step response after a ‐2V step at 55ms
5.2.4 The LCL filter
In figure 5.9 the currents and voltages across the different elements of the LCL filter is
plotted at start‐up. At 0ms the grid is connected to the LCL filter, and at approximately 8ms
the inverter is given a current step of 1.85A in the d‐axis current regulator. As expected
most of the voltage and current ripple can be seen in the inverter side inductor, the grid side
inductor has therefore only a small amount of the total ripple, as it was designed for. The
voltage across the capacitor is a smoothed sinusoidal voltage with low ripple in the voltage.
Chapter 5 Simulation
Fundamentals of Grid Connected Photo‐Voltaic Power Electronic Converter Design
Figure 5.9: LCL filter current and voltage. From top: converter inductor voltage, grid inductor voltage, capacitor voltage, converter inductor current and grid inductor current
Chapter 5 Simulation
84
85
NTNU Department of Electric Engineering
Harmonic analysis
In the simulation an analysis of the harmonic content in the grid inductor current of the LCL
is made using the Powergui FFT tool. The analysis is made with a phase current of 1.3A rms,
and sinusoidal PWM with third harmonic injection with a modulation ratio close to 1.15 is
used. In figure 5.10 a spectrum analysis of the grid inductor current is shown, where the
harmonics from 1st to 33rd of the fundamental are included. Figure 5.10: Harmonic spectrum of grid side inductor current, from 0 to 1650Hz
The lower harmonics found in figure 5.10 was not expected when using PWM at 20kHz.
During the simulation it could be seen that the calculation of the pulse width had to be
accurate in order to reduce these lower harmonic components. The calculation of the pulse
width is in the simulation made the same way as in the DSP, using a up/down counter and
a compare value for each phase. In the harmonic analysis a timer value (resolution) of 7500
was used. This corresponds to a clock frequency of 150MHz, which is the same as in the
DSP. If much lower resolutions where used then the lower harmonic content soon crossed
the limits of the allowed values, but the distribution of the harmonics changed. Therefore
reducing the resolution could reduce the 2nd harmonic but increase the 5th harmonic, and
in total increase the THD.
In figure 5.11 the same spectrum analysis is shown, but now including the harmonics up to
50kHz. In this figure harmonics in the side bands of the switching frequency and in the side
bands of the multiple of the switching frequency is seen. The highest value of the side band
harmonics is the one closest to the switching frequency, having an amplitude of
approximately 0.2%. Chapter 5 Simulation
Fundamentals of Grid Connected Photo‐Voltaic Power Electronic Converter Design
Figure 5.11: Harmonic spectrum of grid side inductor current, from 0 to 50kHz
Chapter 5 Simulation
86
87
NTNU Department of Electric Engineering
6 EXPERIMENTAL RESULTS
6.1 DC‐DC Converter
During the testing of the DC‐DC converter it was several design errors which caused
problems for the correct operation of the converter. Some of the most severe problems are
explained in appendix 6. It is there shown that since there is a leakage inductance in the
transformer, a clamping circuit will be needed in order to reduce the voltage spike which
will be generated across the full bridge (see [26] and [27]). Also there where some problems
with a very small magnetizing inductance in the transformer, which led to nonlinear
operation of the converter. It showed out that the core used had a small gap in the centre
leg which it was not supposed to have. When the core was replaced, this problem was
solved. It also showed out that when positive duty cycle steps where applied, an inrush
current proportional to the step size was experienced. This current was due to the charging
of the DC‐link capacitor, and could be troublesome because it could become quite large.
The problems listed above where solved, but the final problem caused malfunction of the
converter, with breakdown of the full bridges as a result. This problem was with high ripple
in the gate of two diagonal mosfets already on when the two remaining diagonal switches
where turned on, which is probably caused by some large di/dt‘s in the circuit and the
problem increased with increased voltage across the bridge. Because of this improper
operation of the DC‐DC converter, only some limited testing of the MPPT algorithm was
made converter.
6.1.1 MPPT
The MPPT was tested on a resistive load with the DC power supply at reduced input voltage
since DC‐DC converter was not capable of handling higher voltages. The idea was to use the
DC‐power supply as an ideal PV‐power source, by setting a voltage and a current limit. This
however was not working because there is one constant current region and one constant
voltage region. In the constant current region the MPPT will work, but in the constant
voltage region it can not function properly because the MPPT is depending on the direction
of the voltage change. Ideally there would not be any change in voltage in the constant
voltage region, but due to measurement noise, some inaccuracy of the power supply and
rounding errors of the DSP, the voltage measurements fluctuates a little but in an arbitrary
direction. These fluctuations confused the MPPT, and made the duty cycle step go in an
arbitrary direction. This was the only tests made before the full bridge was destroyed, and therefore no more
effort was put into testing of the DC‐DC converter.
Chapter 6 Experimental Results
Fundamentals of Grid Connected Photo‐Voltaic Power Electronic Converter Design
88
6.2 DC‐AC Converter
Since the DC‐DC converter was not functioning properly the DC‐AC converter had to be
tested separately. Since no high voltage isolated DC power source was available at the
moment of testing, the DC‐AC converter was not connected to the grid, but the grid voltage
was measured.
Many tests could have been made on this converter, but due to lack of time and the fact
that the converter could not be connected to the grid only tests of the controllers, and a
harmonic analysis was made. Other tests which would have been of interest is tests of grid
standard compatibility, where the requirements in chapter 2.1.1 where put to the test. 6.2.1 PLL
In order to test the PLL it is difficult to apply a step in the angle of the grid voltage, so instead
the response at start‐up of the PLL is analysed. In figure 6.1 a plot of this response is plotted,
where the frequency has a rise time of 2.8ms, with a overshoot of 5.3% and a settling time
of approximately 7ms. Figure 6.1: Red: Phase locked frequency in PU
Blue: Phase locked angle in PU
Green: PLL PI controller error
Chapter 6 Experimental Results
89
NTNU Department of Electric Engineering
6.2.2 Current control
The step response of the current controllers where tested with the optimized parameters,
and a step from 0.1pu of current to 0.7pu of current. The response can be seen in figure 6.2.
The response of the d‐axis current has more overshoot and shorter rise time than expected
from the optimization. By adjusting the controller parameters to 0.5KP and 1.08Ti, the
response became close to what was expected from the modulus optimization. The q‐axis current shows a minor response to the step in the d‐axis current. Due to the
feedback used, there should ideally not have been any response at all. During steady state
it could be seen a ripple of 200Hz superimposed on the d‐ and q‐ axis current which the
current controllers where not able to reduce to zero.
Figure 6.2: Step response of the d‐ and q‐axis current to a step from 0.1 to 0.7pu in the current reference. Blue: d‐axis current
Green: q‐axis current
6.2.3 Voltage control
The voltage control was tested with the given controller parameters, but with these
parameters the control loop became extremely sensitive to noise and made the controller
fluctuate between its upper and lower limit. This was due to the proportional gain being to
high compared to the ripple in the measurements. The proportional gain is proportional to
Chapter 6 Experimental Results
Fundamentals of Grid Connected Photo‐Voltaic Power Electronic Converter Design
90
the size of the DC‐link capacitance, and since the DC‐AC converter in this system is much
larger than the rating of the rest of the system, the gain becomes large compared to the
system rating. In order to reduce this problem a filter with a corner frequency of 1kHz was used in the
feedback instead of the one with 3kHz, and new controller parameters where calculated
based on that. This reduced the noise in the feedback and made the control loop less
responsive to the noise, but still the gain of the controller is so large that only a minor step
in the DC‐link voltage reference could be applied without going into saturation. In the figure
below a step of ‐0.5 V in the reference value is applied, and it can be seen that it has a rise
time of approximately 7ms, which equals 3.95 times the new Teqv. The overshoot and the
settling time is more difficult to decide since there is still some noise in the measurement. Figure 6.3: Step response in the voltage control loop.
6.2.4 LCL‐filter
In figure 6.4 and 6.5 the currents and voltages across the different elements of the LCL filter
is plotted during steady state at 1.3A rms phase current. The PWM method used is the
SVPWM method at maximum modulation ratio within the continuous mode. As expected
most of the voltage and current ripple can be seen in the inverter side inductor, the grid side
inductor has therefore only a small amount of the total ripple. The voltage across the
capacitor is a smoothed sinusoidal voltage with low ripple in the voltage.
Chapter 6 Experimental Results
91
NTNU Department of Electric Engineering
Figure 6.4: Voltage in the LCL filter inductances during steady state
Blue: Inverter side inductor current
Purple: Grid side inductor current
Figure 6.5: Voltage across the LCL filter elements during steady state
Yellow: Inverter side inductor voltage
Purple: Capacitor voltage
Blue: Grid side inductor voltage
Harmonic analysis
The harmonic content of the current in the grid side inductor was measured with three
different PWM methods. When measuring the harmonic content the modulation was ran
at the maximum modulation ratio within the linear range, and the input voltage was
adjusted in order to get the same fundamental current from all of them. The harmonic
spectrum was measured with a Fluke 43 Power Quality Analyser, which can measure up to
the 50th harmonic. This means the harmonics around the swithcing frequency could not be
found. In the figure below the spectrum of the harmonics from 1st to 33rd are shown,
above this the harmonic content was neglicible, and was therefore not plotted. The
fundamental current had a rms value of 1.3A, and the load was a resistive load of 50Ω.
Chapter 6 Experimental Results
Fundamentals of Grid Connected Photo‐Voltaic Power Electronic Converter Design
92
14
12
10
8
6
4
2
0
1
4
7
10
13
DPWM
16
19
sinusoidal CB-PWM
22
25
28
31
THD
SVPWM
Figure 6.6: Harmonic spectrum in % of fundamental current for three different PWM methods
Chapter 6 Experimental Results
93
NTNU Department of Electric Engineering
7 DISCUSSION, CONCLUSION AND FURTHER WORK
7.1 Discussion
In this thesis much of the basic theory on designing a converter for grid connection of PV
systems have been explained. Based on the theory described in the first chapters a
laboratory setup has been buildt. This setup has been simulated using Simulink and the
setup has been tested in the laboratory. The laboratory setup has as far as possible been
made with well known solutions and techniques, which are not always the most efficient or
reliable but usually easier to implement. It has however made it possible to create a
complete system in the time available, instead of focusing on some minor part of the
system, which would have been the case if more advanced solutions where to be used. Even though the system was designed in this manner, not everything worked out easily. The
DC‐DC converter has caused a lot of problems, as will be explained in the next chapter, and
because of this the system could not be tested with this converter. This has made it
impossible to run some tests, and the time for testing became very reduced.
7.1.1 DC‐DC converter
The DC‐DC converter has been the major troublemaker in this design. It showed out that
this converter topology was a design very few people had any experience with, and the
combination of this being a current fed full bridge with a transformer and a rectifier in
cascade, made it much more complex than a converter with only one stage.
Much of the work done in this thesis has been on designing and testing of the DC‐DC
converter. Lots of time has been used during the design process and on learning how to
build a converter, but most of the time is probably spent on testing and correcting design
errors in the lab. From the beginning of this assignment it was the intention that as little
time as possible should be used on designing and building this converter. It can be seen now
that since the converter is not working properly, that either building the converter should
not have been a part of this thesis or it should have been a much larger one.
However the isolated current fed full bridge converter is a topology which according to
chapter 2.4.2 should be well suited for use with PV‐systems, because of its high suitability
for high input voltages, high efficiency and bidirectional core excitation. Therefore it is still
of interest to do further research on this topology, and a converter for laboratory use and
testing should be buildt. 7.1.2 MPPT
In the simulation the MPPT tracked the MPP as it was expected to, but there where some
experiences made during the simulations. First it was seen that the model for the PV panels
found in chapter 2.2.1 was not very accurate, this was due to the fact that none of the
internal resistances and other nonidealities where included in the model. This means the
model is not useful for simulating specific solar panels, but for testing a MPPT algorithm it
Chapter 7 Discussion, Conclusion and Further work
Fundamentals of Grid Connected Photo‐Voltaic Power Electronic Converter Design
94
is adequate. The model also showed that under partially shadowed conditions two or more
maximum power points may occur, and this can “confuse” the P&O algorithm so that it
does not always find the most efficient power point. Therefore it can be stated that in order
to maximize the efficiency during cloudy days, a more advanced power point tracker which
is able to track the most efficient power point should be used. Based on the calculations made when calculating the sampling time of the P&O algorithm,
the oscillations should have reached 10% of its initial value before the next perturbation,
and it can be seen from in the simulation that this is approximately true.
It was found that with a step in irradiance of 100%, the tracker would use 0.8s before
reaching the new power point. This shows that the tracker is not a fast process, but since
the operating conditions of the PV panels are also slow, it is suspected that this will not have
any large influence on the dynamic tracking error and the efficiency. During steady state
operation the efficiency of the algorithm was as high as 99.9% with the optimized MPPT,
but this is expected to decline with 1‐3% during dynamic conditions. In order to test the
tracker during dynamic conditions, the simulation model should be expanded in order to
test the system over time, with changing operating conditions for the solar panels.
The MPPT in the experimental setup was not tested, but it was found that an ordinary DC‐
power supply with the current voltage characteristic of an ideal solar cell can not be used
to test if the MPPT tracker works. Therefore in order to make reliable tests, field testing of
solar panels must be made, or if possible a DC‐power supply which is able to accurately
simulate a PV power source should be used. The latter would be an enormous help in
testing of the PV converter in order to run accurate and repetitive tests.
7.1.3 PLL
Both in the simulation and in the experimental tests the PLL manages to lock the phase to
the grid voltage in approximately 10ms. This shows that the loop is not very fast, so the
dynamics of the loop becomes poor, but the filtering effect of the control loop is high.
Therefore it will not be so sensitive to harmonics and phase unbalancing. Since both the
dynamics and the filtering effect should be as high as possible, and they are inconsistent,
the PLL should be tested during different grid conditions to see if the current parameters
are the best. It should then be tested with a grid given phase jumps, harmonics and phase
unbalance.
7.1.4 Current control
The response from a step in the d‐axis current reference led to a to a slow response in the
simulation and to fast response in the experimental test. These where only minor errors,
and by small adjustments of the controller parameters the response became as expected
by modulus optimization. The reason for these small errors can be many, e.g errors due to
simplifications made in the model when optimizing, inaccurate values of the components
used in the laboratory setup, computational rounding errors and decoupling errors. Chapter 7 Discussion, Conclusion and Further work
95
NTNU Department of Electric Engineering
The decoupling did not remove the coupling between the axes completely. A probable
reason for this is the different time delays in the control loop. In order for the feed forward
term to work as expected the q‐axis voltage must be updated immediately when the d‐axis
current changes. This is not possible in a real system and the decoupling will therefore have
reduced effect.
Even though the optimization did not give the correct response without adjusting the
values, this cannot be expected either from a real system since the models used will only
be approximations to the real system. However the system response was so close to the
expected, that it can be said that the system models used are sufficient for optimizing the
control system. 7.1.5 Voltage control
In the simulation a step in the DC‐link voltage led to a faster response with less overshoot
then what was expected, but it is so close that it shows that the system models used in the
optimization is close to the simulated model. In the experimental setup the combination of a high gain due to a large capacitor bank and
some noise in the measurements, led to the fluctuations between the upper and lower limit
in the output of the voltage controller. To reduce the effect of this ripple the feedback filter
corner frequency was reduced from 3kHz to 1 kHz, thus reducing the ripple. Still it can be
seen from figure 6.3 that there is some ripple which makes the response unclear, but it can
be seen that the response is close to the expected, but with less overshoot. In this control loop it is possible that a filter with an even lower cutoff frequency should
have been used, or the controller itself could have been adjusted to have a larger filtering
effect, in order to remove even more of the fluctuations in the control loop because of the
noise. This would however lead to a slower control loop. If the feedback filter becomes
much larger then the other time constants, it could be possible to compensate this phase
delay by using a PID controller instead of the PI controller as explained in chapter 3.10.2,
which would probably have improved the response.
It should be noted that because of the large capacitor bank and the small current rating of
the converter, the voltage controller will saturate by very small changes in the voltage.
Therefore the effect of the improved response will only have an influence during small
variations in the DC‐link voltage.
7.1.6 LCL filter
The plots of the currents and voltages from the LCL filter in the simulations and in the
practical case is similar. The amplitude of the high frequency voltage ripple is almost equal
in the simulated and in the experimental case. As expected most of the ripple in the output
voltage is handled by the inverter side inductor since it is closest to the source and the
largest. It can also be seen that the current ripple in the grid side inductor is largely reduced,
so the current is almost sinusoidal.
Chapter 7 Discussion, Conclusion and Further work
Fundamentals of Grid Connected Photo‐Voltaic Power Electronic Converter Design
96
Harmonic analysis
In the harmonic analysis made in the simulation, harmonics where found in the side bands
of the switching frequency and in the side bands of the multiples of the switching frequency
of the grid side current in the LCL filter. This is as expected from the ideal case, and the
highest of these where 0.2% of the fundamental. This is approximately as the LCL filter was
dimensioned for, and the attenuation is below the levels stated in table 2.3. The THD is also
inside the limit given, but there are some harmonics around the fundamental frequency
which is not expected. It was experienced that when reducing the counter value (reducing
the resolution of the pulse width), the amount of harmonics of the fundamental increased.
It can therefore be concluded that the calculation and implementation of the correct pulse
width is important in order to generate the desired waveform.
In the analysis in the experimental setup three PWM methods was tested, and all with very
different results. First it can be said that the analysis did not include the higher harmonics
of the switching frequency, so the attenuation of these remain unknown. What was not
expected was the high content of harmonics of the fundamental frequency, from 2nd
harmonic and up. This was so high that the harmonics content becomes higher than
allowed by the standards when SVPWM an sinusoidal CB‐PWM is used. This must mean
that the generated sine wave is not completely sinusoidal, and since the LCL filter is
designed with a much higher cutoff frequency, these are not attenuated by the filter.
This is basically the same problem as in the simulations, but the harmonic content is
different. In the simulations it was showed that it is very important that the pulse width is
calculated correctly in order to generate the wanted waveform. Probably the same is the
problem in the DSP, but since the resolution is the same as in the simulations and the
harmonic content is much higher, it is probably something else causing the deviation from
the ideal pulse width. This problem can also explain the 4th harmonic which is seen in the
d‐ and q‐ axis current, since the 4th harmonic with the SVPWM is quite noticeable. The pulse width was generated based on an angle going linearly from 0 to 2π, so the basis
should be correct assuming this angle is updated each sampling interval. Based on this
angle the pulses are modulated according to the different algorithms used for the PWM
methods. Since the calculations are digital, there will be some rounding errors which can
contribute to this. Another possibility is that not all the interrupts are executed as they
should, and then the angle and the compare values will not be updated. Ideally the new
compare values for the generation of the PWM signals should be updated at the underflow
or period match of the counter (top or bottom of triangular carrier wave), but because
there are some calculations which has to be made that is not always the case. There will
also be different time delays and dead times in the loop from the DSP through the gate
driver and into the gate. All of this can contribute to making the effective pulse width of the
inverter deviate from ideal. Chapter 7 Discussion, Conclusion and Further work
97
NTNU Department of Electric Engineering
Since this problem occurs in all the three PWM techniques used, it can therefore be
assumed that the problem is not with the algorithms them self but more with the timing of
the algorithms. Therefore the execution of the algorithms should be controlled and if
possible adjusted to make the timing better. It should also be checked if it is possible to
reduce the rounding errors, and it should be checked if all the interrupts run as they should.
It is also possible that in order to reduce the problem even more, some sort of
compensation for the dead time and time delays in the loop should be implemented. The
PWM modulation should at least be corrected such that the harmonic content is below the
limits of the standards.
7.1.7 The overall system
Even though only limited testing of the system was possible, most of the system that was
tested worked as expected. However the system has only been tested under limited
operating conditions, with a reduced number of components. In order to see if the system
is stable under other operating conditions and as a complete system, more extensive
testing should be made. First of all the system should be made complete with an isolated high output voltage DC‐DC
converter, and a PV panel or a powersupply able to simulate a PV panel, should be used a
power source. This system should then first be tested separately to see if the MPPT tracker
works as expected, both during steady state and during different operating conditions.
When the testing of the DC‐DC converter is finished, the converters can be connected
together and to the grid. The overall system can now be tested, and the DC‐AC converter
should be phased into the grid. When this is done the tests mentioned in the sections above
should be made. Also it should be verified if the converter is working according to the
requirements given in the standards from chapter 2.1., including anti‐islanding and a power
quality analysis.
Chapter 7 Discussion, Conclusion and Further work
Fundamentals of Grid Connected Photo‐Voltaic Power Electronic Converter Design
98
7.2 Conclusion
In this thesis the most basic theory on the design of an electrical power converter for photo‐
voltaic systems has been shown. Based on the theory described a complete system model
has been designed. The model is designed with focus on testing of the theoretical models
derived for the control systems, and with low focus on hardware efficiency. The system is
based on the use of a multi string inverter, which consists of an isolated current fed full
bridge DC‐DC converter, a 3‐phase full bridge DC‐AC converter with a LCL filter as the grid
interface. This system has been simulated in Simulink, and an experimental setup has been
made.
The DC‐DC converter was not available as a laboratory converter, and therefore it had to be
designed and constructed. Since the converter topology is not a common one, theoretical
models was developed for the converter, and based on this a converter was constructed.
However the converter did not function as expected during the testing, because of
problems caused by phenomena not included in the ideal models developed. It was also
shown that since the converter was buildt on a printed circuit board with an integrated full
bridge, it was difficult to apply changes and troubleshoot the circuit. The full bridge in the
circuit eventually broke down, so the converter had to be put aside for the rest of the
experiments. It is however shown that the current fed full bridge DC‐DC converter is an
interesting topology for use in photo‐voltaic systems, and therefore further studies should
be made on this converter topology. The three phase full bridge DC‐AC converter was
therefore tested on a resistive load instead of the grid, since isolation was needed.
The simulations of the PV panels showed that the models used in this thesis is to simple to
accurately model a real PV panel, but for testing of the a maximum power point tracker
algorithm they are adequate. The model also showed that during partial shadowing of the
solar panels, two or more power points might occur, and then the perturb & observe
method used would not be able to track the power point with the maximum power. The
algorithm showed an efficiency close to 100% during steady state operation, but it is
predicted to be lower during dynamic operating conditions. Therefore the efficiency of the
algorithm should be simulated with varying operating conditions. The same tests should be
made on the experimental setup once a functional DC‐DC converter is made.
Both the simulations and the experimental tests showed that the models developed for the
control systems was close to the real and simulated system. A phase locked loop with a PI
controller was used for the synchronization with the grid, and this was able to lock the
phase in approximately 10ms. For the power flow into the grid, current controllers in a
rotating reference frame was used, and when locked to the grid frequency the active power
could be controlled by the current in direct axis and the reactive power by the quadrature
axis. The direct current reference was sat by a DC‐link voltage controller in cascade. These
control systems has been modelled and optimized, and the results from the simulations and
the experiments showed that the deviation from the expected result was small. However
there was some problems with noise in the feedback to the DC‐voltage controller in the
experimental setup.
Chapter 7 Discussion, Conclusion and Further work
99
NTNU Department of Electric Engineering
The LCL filter worked as expected, as it attenuated the ripple around the side bands of the
switching frequency in the grid side current below the limits in the standards from IEEE and
IEC. What was not expected was that the harmonic analysis also showed high levels of
harmonics centered around the fundamental frequency, which ideally should not have
been there. The reason for these have been found to be inaccurate pulse width causing the
output of the inverter to deviate from the ideal sinusoidal shape it should have.
Since the DC‐DC converter could not be used, and less time has been available for testing,
there is still much work that can be done on this project. First of all the DC‐DC converter
should be finished, and then more extensive testing of the systems should be made in order
to see how it works during grid disturbances and failures. The simulations could also be
extended in order to simulate the same problematic.
7.3 Proposed further work
A PV simulator should be made, which is able to give accurate repeatable outputs
simulating a given PV panel during different operating conditions. The simulator could be a
DC‐DC converter with a graphical computer interface, in order to make the adjustments
intuitive and simple. In that way the simulator will be a good tool for educational purposes
as well as for testing purposes.
Since the isolated current fed DC‐DC converter topology is a promising for use with photo‐
voltaic systems, a more optimal design of the converter used in this project should be
made. The new converter should be made for laboratory use, with a wide operating range
and more hardware based protection of the circuitry.
Develop the laboratory setup made in this thesis further, with the goal of one day creating
a setup which can be used in the renewable energy laboratory at NTNU. This will also
include further testing of the setup, with the tests that have been suggested in the
discussion. The setup should have a user friendly graphical computer based interface,
which is suitable for both research and educational purposes.
Chapter 7 Discussion, Conclusion and Further work
Fundamentals of Grid Connected Photo‐Voltaic Power Electronic Converter Design
100
LITERATURE
References
[1] ‐ IEEE Standard for Interconnecting Distributed Resources with Electric Power Systems,
IEEE Std. 1547, 2003.
[2] ‐ Photovoltaic (PV) systems ‐ Characteristics of the utility interface, IEC 61727
International Standard, 2004.
[3] ‐ IEEE Recommended Practice for Utility Interface of Photovoltaic (PV) Systems, IEEE Std
929, 2000.
[4] ‐ Zeng Q, Song P, Chang L, A Photovoltaic Simulator Based On DC Chopper, Proceedings
of the 2002 IEEE Canadian Conference on Electrical and Computing Engineering, 2002
[5] ‐ Khouzam K, Hoffman K, Real‐Time Simulation of Photovoltaic Modules, Solar Energy,
Vol 56, No 6, pages 521‐526, 1996.
[6] ‐ Kjear S.B, Pedersen J.K, Blaabjerg F, A Review of Single‐Phase Grid‐Connected Inverters
for Photovoltaic Modules, IEEE Transactions On Industry Applications, Vol. 41, No.9,
2005 [7] ‐ Teodorescu R, Liserre M, Power Electronics for Renewable Energy, Slides presented at
the course PERES, Aalborg, Denmark, March 2006
[8] ‐ Myrzik J.M.A, Calais M, String and Module Integrated Inverters for Single‐Phase Grid
Connected Photovoltaic Systems ‐ A Review, Paper accepted for presentation at 2003
IEEE Bologna PowerTech Conference, Bologna, Italy, June 2003.
[9] ‐ Corzine K, Operation and Design of Multilevel Inverters, (report developed for the
Office of Naval Research, 2003, Power Electronic and Machinery Group at University
of Missouri ‐ Rolla, UMR)
[10] ‐ Wang T CY, Ye Z, Sinha Gautam, Yuan X, Output filter design for a Grid‐interconnected
Three‐Phase Inverter, Power Electronics Specialist Conference, 2003. PESC '03. 2003
IEEE 34th Annual, Vo No. 2, June 2003.
[11] ‐ Hohm D.P, Ropp M.E, Comparative Study of Maximum Power Point Tracking
Algorithms Using an Experimental, Programmable, Maximum Power Point Tracking
Test Bed, Electrical Engineering Department at South Dakota State University,
Brooking
[12] ‐ Blaabjerg F, Teodorescu R, Chen Z, Liserre M, Power Converters and Control of
Renewable Energy Systems, Proceedings of the 6‐th International Conference on
Power Electronics, 18‐22 October 2004 (plenary session)
Literature
101
NTNU Department of Electric Engineering
[13] ‐ Teodorescu R, Blaabjerg F, Liserre M, Proportional‐Resonant Controllers. A New
Breed of Controllers Suitable for Grid‐Connected Voltage‐Source Converters,
Proceedings of OPTIM’04, 20‐21 may 2004, Brasov, vol. III pp 9‐14
[14] ‐ Teodorescu R, Blaabjerg F, Liserre M, Borup U, A New Control Structure for Grid‐
Connected PV Inverters with Zero Steady‐State Error and Selective Harmonic
Compensation, Proceedings of APEC’04, Anaheim, CA
[15] ‐ Kazmierkowski M.P, Current Control Techniques for Three‐Phase Voltage‐Source
PWM Converters: A Survey, IEEE Transactions on Industrial Electronics, Vol No. 45, No
5, October 1998.
[16] ‐ Hwang I.H, Ahn K.S, Lim H.C, Kim S.S, Design, development and performance of a 50
kW grid connected PV system with three phase current‐controlled inverter,
Photovoltaic Specialists Conference, 2000. Conference Record of the Twenty‐Eighth
IEEE, 15‐22 Sept. 2000.
[17] ‐ Ahmet H, Carrier Based PWM‐VSI Drives in the Overmodulation Region, (Doctoral
dissertation, University of Wisconsin ‐ Madison 1998).
[18] ‐ Timbus A, Teodorescu R, Blaabjerg F, Synchronization Methods for Three Phase Power
Generation Systems. An overview and Evaluation, Power Electronics Specialists, 2005
IEEE 36th Conference, 11‐14 Sept. 2005
[19] ‐ Woyte A ,Brabandere K.D, Dommelaen D.V, Belmans R, Nijs J, International
Harmonization of Islanding Prevention Requirements, Published in Progress in
Photovoltaics: Resarch and Applications 11(6) pp.407‐424 (preprint, not edited),
2003
[20] ‐ Xu W, Mauch K, Martel S, An Assessment of Distributed Generation Islanding
Detection Methods and Issues for Canada, A report for CANMET Energy Technology
Centre ‐ Varennes, 2004
[21] ‐ Chuong S.K, A phase tracking system for Three Phase Utility Interface Inverters, IEEE
Transactions On Power Electronics, Vol. 15, No. 3, May 2000.
[22] ‐ Sype D. M, Gussemé D, Bossche A. P, Melkebeek J.A, A Sampling Algorithm for
Digitally Controlled Boost PFC Converters, IEEE Transactions on Power Electronics,
Vol. 19, No. 3, May 2004
[23] ‐ Femia N, Petrone G, Spagnuolo, Vitelli M, Increasing the efficiency of P&O MPPT by
converter dynamic matching, Industrial Electronics, 2004 IEEE International
Symposium on, Vol . 2, 4‐7 May 2004, Page 1017 ‐ 1021 [24] ‐ Femia N, Petrone G, Spagnuolo, Vitelli M, Industrial Electronics, Perturb and observe
MPPT technique robustness improved, 2004 IEEE International Symposium on, Vol. 2,
4‐7 May 2004, Page 845 ‐ 850 Literature
Fundamentals of Grid Connected Photo‐Voltaic Power Electronic Converter Design
102
[25] ‐ Liu S, Dougal R. A, Dynamics Multiphysics Model for Solar Array, IEEE Transactions on
Energy Conversion, Vol. 17, No 2, June 2002, Page 285 ‐ 294
[26] ‐ Mohr M, Fuchs F.W, Voltage Fed and Current Fed Full Bridge Converter for Use in
Three Phase Grid Connected Fuel Cell Systems, Power Electronics and Motion Control
Conference, 2006. IPEMC '06. CES/IEEE 5th International
[27] ‐ Yakushev V, Meleshin V, Fraidlin S, Full‐Bridge Isolated Current Fed Converter with
Active Clamp, Applied Power Electronics Conference and Exposition, 1999. APEC '99.
Fourteenth Annual
Bibliography
[28] ‐ Markvart T., Solar Electricity, 2nd ed. England: John Wiley & Sons Ltd, 2000
[29] ‐ Mohan N.,Undeland T.M, William R.P, Power Electronics, 3rd ed. USA: John Wiley &
Sons, Inc, 2003
[30] ‐ Erickson R.W, Fundamentals of Power Electronics, USA: Chapman & Hall, 1997
[31] ‐ Kazmierkowski M.P, Krishnan R., Blaabjerg F., Control in Power Electronics Selected
Problems, USA: Academic Press, 2002
[32] ‐ Santina M.S., Stubberud A.R., Hostetter G.H.,Digital Control System Design, 2nd ed.
USA: Saunders College Publishing, 1994
[33] ‐ Nilsen R., Elektriske Motordrifter (Kompendium ), Trondheim: NTNU department of
energy conversion, 2006
[34] ‐ Balchen J.G, Andresen T, Foss B.A, Reguleringsteknikk, 5th ed, Norway, Institutt for
teknisk kybernetikk, 2004
[35] ‐ Frohr F, Orttenburger F, Introduction to Electric Control Engineering, Berlin and
Munchen: Heyden & Son Ltd., London, 1982
Literature
103
NTNU Department of Electric Engineering
APPENDIX
1
DC‐DC CONVERTER ANALYSIS 1
1.1 Steady state analysis .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. 1
1.1.1 DC‐link voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
1.1.2 DC‐link current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.1.3 Inductor current ripple. . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.1.4 Boost inductor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.1.5 PV capacitor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.1.6 DC‐link capacitor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.1.7 Limit between continuous and discontinuous conduction . . . . . . . 5
1.1.8 Max blocking voltage switches . . . . . . . . . . . . . . . . . . . . . . 5
1.1.9 Max blocking voltage diodes . . . . . . . . . . . . . . . . . . . . . . . 6
1.1.10 Current rating switches . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.1.11 Current rating diodes . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.1.12 Transformer winding ratio. . . . . . . . . . . . . . . . . . . . . . . . . 6
1.2 Small signal AC modelling .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. 6
1.2.13 Constructing small signal AC equations by perturbing and linearizing. 8
1.2.14 State equations: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
1.2.15 State‐space equations in matrix form . . . . . . . . . . . . . . . . . 12
1.3 State‐Space Averaging .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. ..12
1.3.16
1.3.17
1.3.18
1.3.19
1.3.20
Linear system equations interval 1 and 3 . . . . . . . . . . . . . . . 12
Linear system equations interval 2 and 4 . . . . . . . . . . . . . . . 13
Averaged matrices for the constants of proportionality . . . . . . . 14
The equilibrium vectors . . . . . . . . . . . . . . . . . . . . . . . . . 15
State equations of small signal AC model . . . . . . . . . . . . . . . 15
1.4 Transfer function of DC‐DC converter .. .. .. .. .. .. .. .. .. .. .. .. ..16
2
LCL FILTER 19
2.1 Differential equations . .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. ..19
2.2 Transfer functions .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. ..20
3
SYSTEM RATING 24
3.1 Description of solar panels at NTNU .. .. .. .. .. .. .. .. .. .. .. .. .. ..24
3.2 DC‐DC converter .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. ..24
3.2.1
3.2.2
3.2.3
3.2.4
3.2.5
3.2.6
3.2.7
3.2.8
3.2.9
Switching . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Voltage rating. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Current rating. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Transformer ratio . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Duty cycle limits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Boost inductor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
PV Capacitor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
DC Capacitor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Circuit design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
3.3 DC‐AC inverter . .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. ..31
3.3.1 Switching . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
3.3.2 Inverter specifications . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Appendix
Fundamentals of Grid Connected Photo‐Voltaic Power Electronic Converter Design
104
3.4 LCL filter .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. 31
3.4.1 Design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
4
MAGNETIC DESIGN 36
4.1 LCL Filter inductance .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. 36
4.1.1 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
4.1.2 Design of converter side inductance . . . . . . . . . . . . . . . . . . 36
4.1.3 Design of grid side inductance . . . . . . . . . . . . . . . . . . . . . . 37
4.2 High frequency transformer .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. 37
4.2.4 Specification. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
4.2.5 Design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
4.3 High frequency boost inductor Design .. .. .. .. .. .. .. .. .. .. .. .. .. 39
4.3.6 Specification. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
4.3.7 Design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
5
BRIEF DESCRIPTION OF CONVERTER SIMULATION 41
5.1 DC‐AC Converter . .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. 41
5.1.1 Measurements and Acquisitions . . . . . . . . . . . . . . . . . . . . 41
5.1.2 Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
5.1.3 Plant . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
5.2 DCDC Converter .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. 44
5.2.4
5.2.5
5.2.6
5.2.7
6
Measurements and Acquisitions . . . . . . . . . . . . . . . . . . . . 45
Control DC‐AC Converter . . . . . . . . . . . . . . . . . . . . . . . . . 46
Control DC‐DC Converter. . . . . . . . . . . . . . . . . . . . . . . . . 46
Plant . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
DC‐DC CONVERTER PROBLEMS 6.1
6.2
6.3
6.4
Appendix
49
Voltage spikes . .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. 49
Magnetizing inductance . .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. 52
Gate drive ripple . .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. 54
Duty‐cycle steps .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. 56
105
NTNU Department of Electric Engineering
1 DC‐DC CONVERTER ANALYSIS
In this chapter different calculations and models has been made from the DC‐DC shown in
figure 1.1. This converter type is called an isolated full bridge boost converter.
Figure 1.1: Schematic of DC‐DC converter
1.1 Steady state analysis
The switching scheme for the DC‐DC converter is shown in figure 1.2.
Figure 1.2: DC‐DC switching scheme
Appendix 1 DC‐DC converter Analysis
Fundamentals of Grid Connected Photo‐Voltaic Power Electronic Converter Design
106
With this switching scheme, the voltage at the primary side of the transformer vp(t), and the
inductor current iL(t) and voltage vL(t) for one period, is shown in the figure below.
Figure 1.3: Voltage over primary side of HF transformer, and inductor current and voltage.
From figure 1.3 it can be seen that the inductor ripple frequency is.
2
f L = 2f s = ----Ts
(1.1) 1.1.1 DC‐link voltage
DTs
T
≤t ≤ s
2 the voltage balance is:
For 2
v PV (t ) + v L (t ) =
v DC (t )
V
⇒ VPV + VL = DC
n
n
Sum of voltage over the inductor must equal zero
Appendix 1 DC‐DC converter Analysis
(1.2) 107
NTNU Department of Electric Engineering
DTs
(1 − D )Ts
= VL
2
2
D
VL = VPV
1− D
VPV
(1.3) (1.3) inserted in (1.2) gives the steady state DC‐link voltage
D
1− D
D ⎞
D ⎞
n
⎛
⎛ 1− D
+ VPV
VDC = n ⎜ VPV + VPV
⎟ = n ⎜ VPV
⎟ = VPV
1− D ⎠
1− D ⎠
1− D
⎝
⎝ 1− D
VL = VPV
(1.4) Solving for the duty cycle as a function of output and input voltage
D = 1−
VPV ⋅ n
VDC
(1.5) 1.1.2 DC‐link current
Solving for the average DC‐link current as a function of PV current and duty‐cycle
IDC =
2
nTs
Ts
2
2
Ts
2
∫ I dt = nT ∫ I
L
DTs
2
PV
dt
s DTs
2
DTs ⎞
D
2 ⎛ Ts
1
⎜ IPV − IPV
⎟ = IPV − IPV
2 ⎠
nTs ⎝ 2
n
n
(1 − D )
= IPV
n
=
(1.6) 1.1.3 Inductor current ripple
The ripple during steady state is derived using the inductor voltage equation
v L (t ) = Lboost
∆VL = Lboost
∆IL _ PP =
∆IL =
di L (t )
dt
∆IL _ PP
∆t
1
Lboost
∆IL _ PP
2
∆VL ⋅ ∆t = VPV
= VPV
Appendix 1 DC‐DC converter Analysis
V − VPV ⋅ n
D
Ts = VPV DC
Ts
2Lboost
2Lboost VDC
VDC − VPV ⋅ n
Ts
4Lboost VDC
(1.7) Fundamentals of Grid Connected Photo‐Voltaic Power Electronic Converter Design
108
1.1.4 Boost inductor
The largest boost inductor will be needed close to the limit between continuous and
discontinuous conduction mode, so by inserting ILB into equation (1.7), and solving for the
inductor gives
Lboost = VPV
VDC − VPV ⋅ n
Ts
4ILBVDC
(1.8) 1.1.5 PV capacitor
The PV capacitor is calculated based on the assumption that all the inductor current ripple
will be delivered by the capacitor.Current ripple in the capacitor is given by.
iCPV = CPV
dVPV
dt
∆VPV
∆t
∆ICPV = ∆IL = CPV
(1.9) Having the expression for the inductor current ripple from (1.7), and solving for the PV
capacitor.
CPV = ∆IL ⋅
DTS
∆t
= ∆IL ⋅
∆VPV
2∆VPV
⎛ VPV ⋅ n ⎞
⎛ VPV ⋅ n ⎞
⎜1−
⎟
⎜1−
⎟
VDC ⎠
VDC ⎠
⎝
= VPV
Ts ⋅ ⎝
TS = VPV
4Lboost
2∆VPV
2
⎛ VPV ⋅ n ⎞
⎜1−
⎟
VDC ⎠ 2
⎝
Ts
8Lboost ∆VPV
(1.10) Where ∆VPV is the allowed voltage ripple at the PV side during steady state.
1.1.6 DC‐link capacitor
Assuming the DC‐link current to be constant, the capacitor is given at the PV maximum
power. The capacitor must deliver current during the 1st and 3rd interval, and the length of
one of these intervals is
∆t =
DTS
2
(1.11) The voltage ripple in the DC‐link can be found by
Appendix 1 DC‐DC converter Analysis
109
NTNU Department of Electric Engineering
iCDC = IDC = CDC
dVDC
dt
(1.12) From this the capacitor can be derived as
CDC = IDC
DTS
∆t
= IDC
= IDC
2∆VDC
∆VDC
⎛ VPV ⋅ n ⎞
⎜1−
⎟TS
VDC ⎠
I (VDC − VPV ⋅ n )TS
⎝
= DC
2∆VDC
2∆VDC
VDC
(1.13) Where ∆VDC is the allowed voltage ripple in the DC‐link during steady state.
1.1.7 Limit between continuous and discontinuous conduction
Inductor current at the limit:
⎛ V − VPV ⋅ n ⎞
ILB = ∆IL _ l im it = ⎜ VPV DC
Ts ⎟
4
L
V
boost DC
⎝
⎠lim it
(1.14) DC‐link current as a limit (by applying (1.6)):
IDCB = ILB ⋅
(1 − D )
n
(1.15) 1.1.8 Max blocking voltage switches
During the first and third interval the voltage over all the switches is zero, during the second
interval the voltage over the switches is:
VS1 = VS 4 = 0V
VS 2 = VS 3 =
VDC
n
(1.16) and during the fourth interval:
VS 2 = VS 3 = 0V
VS1 = VS 4 =
VDC
n
(1.17) The maximum blocking voltage over the switches is therefore:
VS _ max =
Appendix 1 DC‐DC converter Analysis
VDC
1
= VPV
n
1− D
(1.18) Fundamentals of Grid Connected Photo‐Voltaic Power Electronic Converter Design
110
1.1.9 Max blocking voltage diodes
When reverse biased, the maximum voltage over one diode is the secondary voltage of the
transformer, which equals the DC‐voltage
VD _ max = VDC
(1.19) 1.1.10 Current rating switches
Maximum average current through one switch:
IS _ MAX =
IPV
2
(1.20) Max peak current through one switch
⎛ V −V ⋅ n ⎞
IS _ P _ MAX = IPV _ MAX + ∆IL _ MAX = IPV _ MAX + ⎜ VPV DC PV T ⎟
4LboostVDC ⎠MAX
⎝
(1.21) 1.1.11 Current rating diodes
Maximum average current through one diode
ID _ MAX =
IDC
(1 − D )
= IPV _ MAX
2
2n
(1.22) Max peak current through one diode:
ID _ P _ MAX =
1
( IPV _ MAX + ∆IL _ MAX ) =
n
⎛ V −V ⋅ n ⎞ ⎞
1⎛
⎜⎜ IPV _ MAX + ⎜ VPV DC PV T ⎟ ⎟⎟
n⎝
4LboostVDC ⎠MAX ⎠
⎝
(1.23) 1.1.12 Transformer winding ratio
Based on equation (1.4) the transformer winding ratio can be found by
n=
VDC
VPV _ min
Appendix 1 DC‐DC converter Analysis
(1 − Dmax ) =
VDC
VP
(1.24) 111
NTNU Department of Electric Engineering
1.2 Small signal AC modelling
In this chapter an equivalent circuit based on the small signal AC model will be derived.
Based on the methods described in [30]
In this derivation the duty cycle is defined as
d (t ) = dutycycle
d '(t ) = 1 − d (t )
(1.25) The switch intervals are divided into these four, where Sx denotes which switches are on
DTs
(S1 ,S2 ,S3 ,S4 )
2
DT
T
Int 2 : s ≤ t ≤ s (S1 ,S4 )
2
2
T
(1 + D )Ts (S ,S ,S ,S )
Int 3 : s ≤ t ≤
1 2
3
4
2
2
(1 + D )Ts ≤ t ≤ T (S ,S )
Int 4 :
s
2
3
2
Int1 : 0 ≤ t ≤
(1.26) Small ripple approximations of interval 1 and 3:
v L (t ) = v PV (t )
Ts
v DC (t )
iC ( t ) = −
− i L (t )
Ts
⋅ Ron
Ts
RDC
iPV (t ) = i L (t )
Ts
+ CPV
d v PV (t )
Ts
dt
(1.27) Small ripple approximations of interval 2 and 4:
v L (t ) = v PV (t )
iC ( t ) =
i L (t )
−
Ts
Ts
n
iPV (t ) = i L (t )
Ts
−
v DC (t )
Ts
n
v DC (t ) Ts
Ts
⋅ 2Ron
RDC
+ CPV
d v PV (t )
dt
Averaging inductor voltage over one period:
Appendix 1 DC‐DC converter Analysis
− i L (t )
Ts
(1.28) Fundamentals of Grid Connected Photo‐Voltaic Power Electronic Converter Design
Lboost
d i L (t )
dt
= v L (t )
Ts
= d (t ) ( v PV (t )
Ts
− i L (t )
Ts
⋅ Ron )
⎛
v DC (t ) Ts
⎞
+d '(t ) ⎜⎜ v PV (t ) Ts −
− i L (t ) Ts ⋅ 2Ron ⎟⎟
n
⎝
⎠
= d (t ) v PV (t ) Ts − d (t ) i L (t ) Ts ⋅ Ron + d '(t ) v PV (t )
−d '(t )
v DC (t )
Ts
n
− d '(t ) i L (t )
= v PV (t )
( d (t ) + d '(t ) ) −
Ts
= v PV (t )
− i L (t )
Ts
Ts
112
Ts
⋅ 2Ron
⋅ Ron ( d (t ) + 2d '(t ) ) − d '(t )
Ts
i L (t )
⋅ Ron (1 + d '(t ) ) − d '(t )
Ts
v DC (t )
v DC (t )
Ts
n
Ts
n
(1.29) Averaging capacitor current over one period:
CDC
d v DC (t )
dt
⎛ v DC (t ) Ts ⎞
⎛ i L (t ) Ts v DC (t )
= d (t ) ⎜⎜ −
−
⎟⎟ + d '(t ) ⎜⎜
R
n
RDC
DC
⎝
⎠
⎝
v DC (t ) Ts
i L (t ) Ts
v DC (t ) Ts
= −d (t )
+ d '(t )
− d '(t )
RDC
n
RDC
= iC ( t )
=−
=−
Ts
v DC (t )
( d (t ) + d '(t ) ) + d '(t )
Ts
RDC
v DC (t )
+ d '(t )
Ts
RDC
i L (t )
i L (t )
Ts
⎞
⎟⎟
⎠
Ts
n
Ts
n
(1.30) Averaging input current over one period:
iPV (t )
= i L (t )
Ts
+ CPV
Ts
d v PV (t )
Ts
dt
(1.31) 1.2.13 Constructing small signal AC equations by perturbing and linearizing
The inputs:
v PV (t )
Ts
= VPV + vˆPV (t )
d (t ) = D + dˆ (t )
d '(t ) = 1 − d (t ) = 1 − (D + dˆ (t )) = D '− dˆ (t )
The response to the inputs:
Appendix 1 DC‐DC converter Analysis
(1.32) 113
NTNU Department of Electric Engineering
v DC (t )
i L (t )
Ts
Ts
iPV (t )
= VDC + vˆDC (t )
= IL + iˆL (t )
Ts
= IPV + iˆPV (t )
(1.33) The averaged inductor equation
Large signal averaged inductor equation:
Lboost
(
d IL + iˆL (t )
dt
) = (V
PV
(
) (
+ vˆPV (t ) ) − IL + iˆL (t ) ⋅ Ron 1 + D '− dˆ (t )
)
(V + vˆ (t ) )
− D '− dˆ (t ) DC DC
n
(
)
(1.34) Multiplying out and collecting terms (DC terms, 1st and 2nd order terms):
⎛ dI diˆ (t ) ⎞ ⎛
V ⎞
Lboost ⎜⎜ L + L ⎟⎟ = ⎜ VPV − ILRon (1 + D ' ) − D ' DC ⎟
dt ⎠ ⎝
n ⎠
⎝ dt
vˆ (t )
V ⎞
⎛
+ ⎜ vˆPV (t ) + ILRondˆ (t ) − iˆL (t )Ron (1 + D ' ) − D ' DC + dˆ (t ) DC ⎟
n
n ⎠
⎝
vˆ (t ) ⎞
⎛
+ ⎜ iˆL (t )dˆ (t ) + dˆ (t ) DC ⎟
n ⎠
⎝
(1.35) Assuming the second order terms are much smaller in magnitude then the first‐order
terms, and the DC‐terms must equal zero, the small‐signal AC equation becomes:
Lboost
V
diˆL (t )
D'
⎛
= vˆPV (t ) − vˆDC (t ) + ⎜ IL Ron + DC
dt
n
n
⎝
⎞ˆ
ˆ
⎟ d (t ) − Ron (1 + D ) i L (t )
⎠
(1.36) The equation for the quiescent value (DC‐terms):
0 = VPV − Ron (1 + D ' ) IL −
Appendix 1 DC‐DC converter Analysis
D'
VDC
n
(1.37) Fundamentals of Grid Connected Photo‐Voltaic Power Electronic Converter Design
114
The averaged capacitor equation
Large signal averaged capacitor equation:
CDC
d (VDC + vˆDC (t ) )
dt
=−
(VDC + vˆDC (t ) ) +
RDC
(
D '− dˆ (t )
)
(I
L
+ iˆL (t )
)
n
(1.38) Multiplying out and collecting terms (DC terms, 1st and 2nd order terms):
dvˆ (t ) ⎞ ⎛ I V ⎞ ⎛ iˆ (t )
I vˆ (t ) ⎞ ⎛
iˆ (t ) ⎞
⎛ dV
CDC ⎜ DC + DC ⎟ = ⎜ D ' L − DC ⎟ + ⎜⎜ D ' L − dˆ (t ) L − DC ⎟⎟ + ⎜⎜ −dˆ (t ) L ⎟⎟
dt ⎠ ⎝ n RDC ⎠ ⎝
n
n RDC ⎠ ⎝
n ⎠
⎝ dt
(1.39) Assuming the second order terms are much smaller in magnitude then the first‐order
terms, and the DC‐terms must equal zero, the small‐signal AC equation becomes
CDC
dvˆDC (t ) D ' ˆ
I
1
= i L (t ) − L dˆ (t ) −
vˆDC (t )
dt
n
n
RDC
(1.40) The equation for the quiescent value (DC‐terms):
0=
D'
1
IL −
VDC
n
RDC
(1.41) The averaged input current equation
Large signal averaged capacitor equation:
(I
PV
d (VPV + vˆPV (t ) )
+ iˆPV (t ) = IL + iˆL (t ) + CPV
dt
) (
)
(1.42) The DC terms must be equal in size and therefore the small‐signal AC equation becomes
dvˆ (t )
iˆPV (t ) = iˆL (t ) + CPV PV
dt
(1.43) The equation for the quiescent value (DC‐terms):
IPV = IL
Appendix 1 DC‐DC converter Analysis
(1.44) 115
NTNU Department of Electric Engineering
The equivalent circuit based on the averaged inductor, capacitor and input current
equations.
Figure 1.4: Equivalent circuit to the small signal AC equations
The first transformer has a ratio of 1:1, and can therefore be removed, a simplified circuit
without the transformer is shown in the figure below.
Figure 1.5: Simplified equivalent circuit to the small signal AC equations
1.2.14 State equations:
dvˆPV (t )
= − iˆL (t ) + iˆPV (t )
dt
ˆ
V
di (t )
D'
⎛
Lboost L = vˆPV (t ) − Ron (1 + D ) iˆL (t ) − vˆDC (t ) + ⎜ IL Ron + DC
dt
n
n
⎝
dvˆ (t ) D '
I
1
CDC DC = iˆL (t ) −
vˆDC (t ) − L dˆ (t )
dt
n
RDC
n
CPV
Appendix 1 DC‐DC converter Analysis
⎞ˆ
⎟ d (t )
⎠
(1.45) Fundamentals of Grid Connected Photo‐Voltaic Power Electronic Converter Design
116
1.2.15 State‐space equations in matrix form
⎡CPV
⎢
⎢ 0
⎢⎣ 0
0
Lboost
0
⎡ dvˆDC (t ) ⎤ ⎡
⎤
⎢ dt ⎥ ⎢0
0 ⎥ vˆ (t )
−1
⎥ ⎢
⎥ ⎡ PV ⎤
0 ⎤⎢
ˆ
⎥
⎢
⎥
di
t
D
(
)
'
⎢
⎥⎢
0 ⎥⎥ ⎢ L ⎥ = ⎢ 1 −Ron (1 + D ) − ⎥ ⎢ iˆL (t ) ⎥
dt ⎥
n ⎢
⎢
⎥ vˆ (t ) ⎥
CDC ⎥⎦ ⎢
1 ⎥ ⎣ DC ⎦
D'
⎢ dvˆDC (t ) ⎥ ⎢0
−
⎢ dt ⎥ ⎢
n
RDC ⎥⎦
⎣
⎣
⎦
⎛⎡
⎜ ⎢0 0
⎡ 1⎤
⎜⎢
⎢
⎥
ˆ
⎡
⎤
+ ⎢0⎥ ⎣ iPV (t ) ⎦ + ⎜ ⎢0 Ron
⎜⎢
⎢⎣0⎥⎦
⎜⎢
⎜⎜ ⎢0 − 1
n
⎝⎣
⎞
⎤
⎟
0⎥
⎥ ⎡VPV ⎤ ⎟
1⎥ ⎢ ⎥⎟ ˆ
I L d (t )
n⎥⎢ ⎥⎟
⎥ ⎢⎣VDC ⎥⎦ ⎟
⎟⎟
0⎥
⎦
⎠
(1.46) 1.3 State‐Space Averaging
The state equations in matrix form (bold letters denotes matrixes).
dx(t )
= Ax(t ) + Bu(t )
dt
y(t ) = Cx(t ) + Eu(t )
K
(1.47) The state, input and output vectors are listed below.
⎡v PV (t ) ⎤
x(t ) = ⎢⎢ i L (t ) ⎥⎥
⎢⎣v DC (t ) ⎥⎦
u(t ) = [ iPV (t )]
y(t ) = [v DC (t ) ]
(1.48) 1.3.16 Linear system equations interval 1 and 3
State equations:
dv PV
= −i L (t ) + iPV (t )
dt
di (t )
Lboost L = v PV (t ) − Ron i L (t )
dt
dv DC (t )
1
CDC
v DC (t )
=−
dt
RDC
CPV
Appendix 1 DC‐DC converter Analysis
(1.49) 117
NTNU Department of Electric Engineering
Output equations:
v DC (t ) =
RDC
i L (t )
n
(1.50) The constants of proportionality matrices for these intervals:
⎡
⎢0 −1
⎢
A 1 = ⎢ 1 −Ron
⎢
⎢0
0
⎢⎣
⎡ 1⎤
B1 = ⎢⎢ 0 ⎥⎥
⎢⎣ 0 ⎥⎦
⎡ RDC
C1 = ⎢0
n
⎣
E1 = [ 0 ]
⎤
0 ⎥
⎥
0 ⎥
⎥
1 ⎥
−
RDC ⎥⎦
⎤
0⎥
⎦
(1.51) 1.3.17 Linear system equations interval 2 and 4
State equations:
dv PV
= − i L (t ) + iPV (t )
dt
di (t )
1
Lboost L = v PV (t ) − 2Ron i L (t ) − v DC (t )
dt
n
dv (t ) 1
1
CDC DC = i L (t ) −
v DC (t )
dt
n
RDC
CPV
(1.52) Output equations:
v DC (t ) =
RDC
i L (t )
n
The constants of proportionality matrices for these intervals:
Appendix 1 DC‐DC converter Analysis
(1.53) Fundamentals of Grid Connected Photo‐Voltaic Power Electronic Converter Design
⎡
⎢0
−1
⎢
⎢
A 2 = ⎢ 1 −2Ron
⎢
1
⎢0
⎢⎣
n
⎡ 1⎤
B2 = ⎢⎢0 ⎥⎥
⎢⎣0 ⎥⎦
⎡ RDC
C2 = ⎢0
n
⎣
E 2 = [ 0]
118
⎤
0 ⎥
⎥
1 ⎥
− ⎥
n
⎥
1 ⎥
−
RDC ⎥⎦
⎤
0⎥
⎦
(1.54) 1.3.18 Averaged matrices for the constants of proportionality
⎡
⎤
⎢0
−1
0 ⎥
⎢
⎥
⎢
0 ⎥ + D ' ⎢ 1 −2Ron
⎥
⎢
1 ⎥
1
−
⎢0
RDC ⎥⎦
⎢⎣
n
⎤
0 ⎥
⎥
1⎥
−D ' ⎥
n
⎥
1 ⎥
−
RDC ⎥⎦
⎡
⎢ 0 −1
⎢
A = DA1 + D ' A 2 = D ⎢ 1 −Ron
⎢
⎢0
0
⎢⎣
⎤
0 ⎥
⎥
1 ⎥
− ⎥
n
⎥
1 ⎥
−
RDC ⎥⎦
⎡
⎢0
−1
⎢
⎢
= ⎢ 1 − ( DRon + D '2Ron )
⎢
1
⎢0
D'
⎢⎣
n
⎡ 1⎤
⎡ 1 ⎤ ⎡ 1⎤
⎢
⎥
B = DB1 + D ' B2 = D ⎢ 0 ⎥ + D ' ⎢⎢0 ⎥⎥ = ⎢⎢ 0 ⎥⎥
⎢⎣ 0⎥⎦
⎢⎣0 ⎥⎦ ⎢⎣ 0 ⎥⎦
⎡ RDC
⎤
⎡ RDC
C = DC1 + D ' C2 = D ⎢0
0⎥ + D ' ⎢0
n
n
⎣
⎦
⎣
E = DE 1 + D ' E 2 = D [ 0 ] + D ' [ 0 ] = [ 0 ]
⎡CPV
K = ⎢⎢ 0
⎢⎣ 0
0
Lboost
0
0 ⎤
0 ⎥⎥
CDC ⎥⎦
Appendix 1 DC‐DC converter Analysis
⎤ ⎡ RDC
0⎥ = ⎢0
n
⎦ ⎣
⎤
0⎥
⎦
(1.55) 119
NTNU Department of Electric Engineering
1.3.19 The equilibrium vectors
X = − A −1BU
Y = ( −CA −1B + E ) U
(1.56) ⎡ R onn 2D + 2Ron n 2D '+ D '2 RDC ⎤
⎥
⎡VPV ⎤ ⎢
n2
⎢
⎥
⎢I ⎥ =
−
1
⎢
⎥ [IPV ]
PV
⎢ ⎥
⎢
⎥
⎢⎣VDC ⎥⎦
D ' RDC
⎢
⎥
−
⎢⎣
⎥⎦
n
RDC ⎤
⎥ [IPV ]
⎣ n ⎦
[VDC ] = ⎡⎢ −
(1.57) 1.3.20 State equations of small signal AC model
The state, input and output vectors:
⎡vˆPV (t ) ⎤
⎢
⎥
xˆ (t ) = ⎢ iˆL (t ) ⎥
⎢vˆ (t ) ⎥
⎣ DC ⎦
uˆ (t ) = ⎡⎣ iˆPV (t ) ⎤⎦
yˆ (t ) = [vˆDC (t )]
(1.58) State and output equations on matrix form:
dxˆ (t )
= Axˆ (t ) + Buˆ (t ) + ⎡⎣( A 1 − A 2 ) X + ( B1 − B2 ) U⎤⎦ dˆ (t )
dt
yˆ (t ) = Cxˆ (t ) + Euˆ (t ) + ⎡⎣( C1 − C2 ) X + ( E1 − E 2 ) U⎤⎦ dˆ (t )
K
Appendix 1 DC‐DC converter Analysis
(1.59) Fundamentals of Grid Connected Photo‐Voltaic Power Electronic Converter Design
⎡
⎤ ⎢
0
−1
0 ⎥ ⎢
⎥ ⎢
0 ⎥ − ⎢ 1 −2Ron
⎥
1 ⎥ ⎢
1
−
⎢
RDC ⎥⎦ ⎢ 0
n
⎣
⎡ 1 ⎤ ⎡ 1⎤ ⎡ 0 ⎤
B1 − B2 = ⎢⎢0 ⎥⎥ − ⎢⎢ 0 ⎥⎥ = ⎢⎢ 0⎥⎥
⎢⎣0 ⎥⎦ ⎢⎣ 0 ⎥⎦ ⎢⎣ 0⎥⎦
⎡
⎢ 0 −1
⎢
A 1 − A 2 = ⎢ 1 −Ron
⎢
⎢0
0
⎢⎣
⎡ RDC
⎤ ⎡ RDC
C1 − C2 = ⎢ 0
0⎥ − ⎢0
n
n
⎣
⎦ ⎣
E1 − E 2 = [ 0 ] − [ 0 ] = [ 0 ]
⎤ ⎡
⎥
⎢0 0
0
⎥ ⎢
1 ⎥
− ⎥ = ⎢ 0 Ron
⎢
n
⎥ ⎢
1 ⎥
1
⎢0 −
−
RDC ⎥⎦ ⎣
n
120
⎤
0⎥
⎥
1⎥
n⎥
⎥
0⎥
⎦
⎤
0 ⎥ = [ 0 0 0]
⎦
(1.60) The state equations:
⎡CPV
⎢ 0
⎢
⎢⎣ 0
0
Lboost
0
⎡ dvˆPV (t ) ⎤ ⎡
⎤
⎢ dt ⎥ ⎢ 0
0 ⎥ ⎡vˆ (t ) ⎤
−1
⎥ ⎢
0 ⎤ ⎢
⎥ PV
D' ⎥ ⎢ ˆ ⎥
⎢ diˆL (t ) ⎥ ⎢
⎥
0 ⎥⋅⎢
⎥ = ⎢ 1 −Ron (1 + D ' ) − n ⎥ ⋅ ⎢ i L (t ) ⎥
dt
⎥ ⎢
⎥ ⎢vˆ (t ) ⎥
CDC ⎥⎦ ⎢
1 ⎥ ⎣ DC ⎦
D'
⎢ dvˆDC (t ) ⎥ ⎢ 0
−
⎢ dt ⎥ ⎢
n
RDC ⎥⎦
⎣
⎦ ⎣
⎛⎡
⎜ ⎢0 0
⎡ 1⎤
⎜⎢
⎢
⎥
ˆ
+ ⎢ 0 ⎥ ⋅ ⎡⎣ iPV (t ) ⎤⎦ + ⎜ ⎢0 Ron
⎜⎢
⎢⎣ 0 ⎥⎦
⎜⎢
⎜⎜ ⎢0 − 1
n
⎝⎣
⎞
⎤
⎟
⎥
0
⎥ ⎡VPV ⎤ ⎟
1⎥ ⎢ ⎥⎟ ˆ
IPV d (t )
n⎥⎢ ⎥⎟
⎥ ⎢⎣VDC ⎥⎦ ⎟
⎟⎟
0⎥
⎦
⎠
(1.61) The output equation:
[vˆDC (t )] = ⎡⎢0
⎣
RDC
n
⎡vˆPV (t ) ⎤
⎥
⎤ ⎢
0⎥ ⋅ ⎢ iˆL (t ) ⎥
⎦ ⎢
vˆ (t ) ⎥
⎣ DC ⎦
(1.62) The state equations of (1.61) is equal that derived in (1.46), so it should be correct. The
output equation is controlled by inspection, and is correct.
Appendix 1 DC‐DC converter Analysis
121
NTNU Department of Electric Engineering
1.4 Transfer function of DC‐DC converter
Finding the Laplace transformed of the differential equations in (1.45).
sCPV vˆPV (s ) = − iˆL (s ) + iˆPV (s )
(1.63) V
D'
⎛
sLboost iˆL (s ) = vˆPV (s ) − Ron (1 + D ' ) iˆL (s ) − vˆDC (s ) + ⎜ IL Ron + DC
n
n
⎝
sCDC vˆDC (s ) =
⎞ˆ
⎟ d (s )
⎠
I
1
D' ˆ
i L (s ) −
vˆDC (s ) − L dˆ (s )
n
RDC
n
(1.64) (1.65) The photovoltaic voltage:
vˆPV (s ) =
(
1
−iˆL (s ) + iˆPV (s )
sCPV
)
(1.66) Solving (1.63),(1.64) and (1.65) for the DC‐link voltage gives these transfer functions
vˆ (s )
H1 (s ) = DC = K1
dˆ (s )
H 2 (s ) =
s2 − s
D 'VDC − nRON IL
1
+
nLBoost IL
LBoost CPV
s 3 + s 2G2 + sG1 + G0
vˆDC (s )
1
= K2 3 2
ˆi (s )
s + s G2 + sG1 + G0
PV
(1.67) Doing the same for the PV‐voltage
H 3 (s ) =
H 4 (s ) =
vˆPV (s )
= K3
dˆ (s )
vˆPV (s )
= K4
iˆ (s )
s−
nVDC + n 2 RON IL − D ' RDC IL
nCDC RDC (VDC + nRON IL )
s 3 + s 2G2 + sG1 + G0
s2 + s
PV
LBoost + CDC RDC RON + D ' CDC RDC RON D '2 RDC + n 2 RON + n 2 D ' RON
+
LBoost CDC RDC
n 2 LBoost CDC RDC
s 3 + s 2G2 + sG1 + G0
(1.68) and the inductor current
H 5 (s ) =
iˆL (s )
= K5
dˆ (s )
s2 + s
n ( nVDC + n 2 RON IL + D ' RDC IL )
CDC RDC (VDC + nRON IL )
s + s 2G2 + sG1 + G0
3
1
s+
ˆi (s )
C
R
H 6 (s ) = L
= K 6 3 2 DC DC
s + s G2 + sG1 + G0
iˆPV (s )
Appendix 1 DC‐DC converter Analysis
(1.69) Fundamentals of Grid Connected Photo‐Voltaic Power Electronic Converter Design
122
Where the constants are defined as
G2 =
LBoost + CDC RON RDC + D ' CDC RON RDC
LBoost CDC RDC
G1 =
D '2 CPV RDC + n 2CDC RDC + n 2 D ' CPV RON + n 2CPV RON
n 2 LBoost CPV CDC RDC
G0 =
1
LBoost CPV CDC RDC
(1.70) and
K1 = −
K2 =
D'
nLBoost CPV CDC
K3 = −
Appendix 1 DC‐DC converter Analysis
IL
nCDC
VDC + nRON IL
nLBoost CPV
K4 =
1
CPV
K5 =
VDC + nRON IL
nLBoost
K6 =
1
LBoost CPV
(1.71) 123
NTNU Department of Electric Engineering
2 LCL FILTER
A figure of the filter is shown in the figure below
Figure 2.1: LCL filter model
2.1 Differential equations
The differential functions of the LCL filter, which is valid in the stationary abc and αβ
reference frame is
di i (t ) 1
=
v i ( t ) − v c ( t ) − Rd ( i i ( t ) − i g ( t ) ) − R i i i (t )
dt
Li
(
di g (t )
dt
=
(
)
1
v c ( t ) − v g ( t ) + Rd ( i i ( t ) − i g ( t ) ) − R g i g (t )
Lg
)
dv c (t ) 1
= ( i i (t ) − i g (t ) )
dt
Cf
(2.1) There are no cross couplings between the phases, and thus the equations are equal for all
phases. If expressed in matrix form they become.
⎡ di i (t ) ⎤ ⎡ − Ri + Rd
⎢ dt ⎥ ⎢
Li
⎢
⎥ ⎢
⎢ di g (t ) ⎥ ⎢ Rd
⎢ dt ⎥ = ⎢ L
g
⎢
⎥ ⎢
⎢
(
)
dv
t
⎢ c ⎥
1
⎢⎣ dt ⎥⎦ ⎢
C
⎣⎢
f
Rd
Li
−
R g + Rd
Lg
−
1
Cf
⎡1
1⎤
⎢
⎥
Li ⎥
⎢ Li
⎡ i i (t ) ⎤ ⎢
1 ⎥⎢
⎥
⎥ i g (t ) ⎥ + ⎢ 0
Lg ⎥ ⎢
⎢
⎢
⎥
⎥ ⎣v c ( t ) ⎦ ⎢
⎢0
0 ⎥
⎦⎥
⎣⎢
−
⎤
0 ⎥
⎥
1 ⎥ ⎡ v i (t ) ⎤
− ⎥⎢
⎥
Lg ⎥ ⎣v g (t ) ⎦
⎥
0 ⎥
⎦⎥
(2.2) This can be transformed into the dq‐system by inserting the inverse transformation of the
dq currents as shown in equation (2.3) (where X is the current or voltage of interest) into
(2.2)
Appendix 2 LCL Filter
Fundamentals of Grid Connected Photo‐Voltaic Power Electronic Converter Design
124
X α = X d cos θ − X q sinθ
X β = X d sinθ + X q cos θ
(2.3) The solving of these equations can be quite tedious if solved by hand, but by using a
program like maple, it becomes rather simple. Solving for the dq currents gives the
expression in (2.4). ⎡ R i + Rd
⎡ di id (t ) ⎤ ⎢ −
Li
⎢ dt ⎥ ⎢
⎢
⎥ ⎢
⎢ di iq (t ) ⎥ ⎢ −ω
⎢ dt ⎥ ⎢
⎢
⎥ ⎢
⎢ di gd (t ) ⎥ ⎢ Rd
⎢ dt ⎥ ⎢ Lg
⎢
⎥=⎢
⎢ di gq (t ) ⎥ ⎢
0
⎢ dt ⎥ ⎢
⎢
⎥ ⎢
⎢ dv cd (t ) ⎥ ⎢
1
⎢ dt ⎥ ⎢
⎢
⎥ ⎢ Cf
⎢ dv cq (t ) ⎥ ⎢
0
⎢⎣ dt ⎥⎦ ⎢
⎣
ω
R + Rd
− i
Li
−
0
Rd
Li
0
0
Rd
Li
0
ω
1
Lg
R g + Rd
Lg
Rd
Lg
−ω
0
1
−
Cf
1
Cf
0
−
−
R g + Rd
0
Lg
−
1
Li
0
0
1
Cf
−ω
⎤
0 ⎥
⎡1
⎥
⎢L
1⎥
⎢ i
− ⎥
Li ⎥ ⎡ i id (t ) ⎤ ⎢
0
⎥ ⎢ i iq (t ) ⎥ ⎢
⎥ ⎢
0 ⎥⎢
⎥ ⎢ i gd (t ) ⎥ ⎢ 0
⎥+⎢
⎥⎢
1 ⎥ ⎢ i gq (t ) ⎥ ⎢
Lg ⎥ ⎢v cd (t ) ⎥ ⎢ 0
⎥ ⎢
⎥⎢
v
t
(
)
⎢
⎢
⎥
cq
⎣
⎦
ω ⎥⎥
⎢0
⎢
⎥
⎢⎣ 0
⎥
0 ⎥
⎦
0
0
1
Li
0
0
−
1
Lg
0
0
0
0
0
0
⎤
0 ⎥
⎥
⎥
0 ⎥
⎥ ⎡ v id (t ) ⎤
⎥ ⎢ v (t ) ⎥
0 ⎥ ⎢ iq ⎥
⎥ ⎢v gd (t ) ⎥
⎢
⎥
1 ⎥ v (t )
− ⎥ ⎢⎣ gq ⎥⎦
Lg ⎥
0 ⎥⎥
0 ⎥⎦
(2.4) 2.2 Transfer functions
Transfer functions are derived based on the three phase differential equations derived in
the previous chapter, but in these equations the inductor resistance is not considered. Appendix 2 LCL Filter
i i (s ) =
1
( −Rd ii (s) + Rd ig (s) − v c (s) + v i (s) )
sLi
ig (s ) =
1
( Rd i i ( s ) − Rd i g ( s ) + v c ( s ) − v g ( s ) )
sLg
v c (s ) =
1
( i i ( s ) − i g (s ) )
sCf
(2.5) 125
NTNU Department of Electric Engineering
Solving the equations.
i i (s ) =
−
i g (s ) =
−
v c (s ) =
+
s 2 Lg Cf + sCf Rd + 1
(
s s 2 Li Lg Cf + s ( Li Cf Rd + Lg Cf Rd ) + ( Lg + Li )
)
v i (s )
)
v g (s )
)
v i (s )
)
v g (s )
sCf Rd + 1
(
2
(
2
s s Li Lg Cf + s ( Li Cf Rd + Lg Cf Rd ) + ( Lg + Li )
sCf Rd + 1
s s Li Lg Cf + s ( Li Cf Rd + Lg Cf Rd ) + ( Lg + Li )
s 2 Li Cf + sCf Rd + 1
(
s s 2 Li Lg Cf + s ( Li Cf Rd + Lg Cf Rd ) + ( Lg + Li )
Lg
s Li Lg Cf + s ( Li Cf Rd + Lg Cf Rd ) + ( Lg + Li )
2
v i (s )
Li
v g (s )
s Li Lg Cf + s ( Li Cf Rd + Lg Cf Rd ) + ( Lg + Li )
2
(2.6) Defining the resonant frequency
2
=
ωres
1
Cf
⎛1 1⎞
⎜⎜ + ⎟⎟
⎝ Li Lg ⎠
(2.7) and the impedances
2
zLC
=
1
Lg Cf
2
zLCg
=
and 1
Li Cf
(2.8) Inserting the definition of the resonant frequency into the solutions
i i (s ) =
s 2 Lg Cf + sCf Rd + 1
sCf Rd + 1
1
1
v i (s ) −
v g (s )
2
2
2
2
2
sLi Lg Cf ( s 2 + sRd Cf ωres
sL
L
C
+ ωres
s
+
sR
)
i g f (
d Cf ωres + ωres )
ig (s ) =
sCf Rd + 1
s 2 Li Cf + sCf Rd + 1
1
1
v
s
−
v (s )
(
)
i
2
2
2
2
sLi Lg Cf ( s 2 + sRd Cf ωres
sLi Lg Cf ( s 2 + sRd Cf ωres
+ ωres
+ ωres
)
)g
v c (s ) =
Lg
Li
1
1
v i (s ) −
v g (s )
2
2
2
2
2
2
Li Lg Cf ( s + sRd Cf ωres
L
L
C
+ ωres
+
s
sR
C
)
i g f (
d f ωres + ωres )
Appendix 2 LCL Filter
(2.9) Fundamentals of Grid Connected Photo‐Voltaic Power Electronic Converter Design
126
The transfer functions of the damped system.
H iivi =
2
2
+ zLC
i i (s )
1 s 2 + sCf Rd zLC
=
2
2
2
v i (s ) sLi ( s + sRd Cf ωres + ωres
)
H iivg =
2
2
sCf Rd zLC
+ zLC
i i (s )
1
=
2
2
v g (s ) sLi ( s 2 + sRd Cf ωres
+ ωres
)
H igvi =
H igvg =
i g (s )
v i (s )
ig (s )
v g (s )
=
2
2
sCf Rd zLC
+ zLC
1
2
2
2
sLi ( s + sRd Cf ωres + ωres
)
=
2
2
2
1 s + sCf Rd zLCg + zLCg
2
2
sLg ( s 2 + sRd Cf ωres
+ ωres
)
2
Hvcvi =
zLCg
v c (s )
= 2
2
2
v i (s ) ( s + sRd Cf ωres
+ ωres
)
Hvcvg =
2
v c (s )
zLC
= 2
2
2
v g (s ) ( s + sRd Cf ωres
+ ωres
)
(2.10) By considering the inverter as a harmonic generator at high frequencies, and the grid as a
short circuit, the converter voltage harmonic at the switching frequency becomes
v i ( h sw ) ≠ 0 , and the grid voltage harmonic at the switching frequency becomes
v g ( h sw ) ≠ 0 . With these assumptions the current equations becomes
i i (hsw ) =
2
2
+ zLC
1 s 2 + sCf Rd zLC
v (h )
2
2
sLi ( s 2 + sRd Cf ωres
+ ωres
) i sw
i g (hsw ) =
2
2
sCf Rd zLC
+ zLC
1
v (h )
2
2
sLi ( s 2 + sRd Cf ωres
+ ωres
) i sw
(2.11) The transfer function between the inverter side and grid side current at switching
frequency becomes
v i (hsw ) =
2
2
sLi ( s 2 + sRd Cf ωres
+ ωres
)
2
2
s 2 + sCf Rd zLC
+ zLC
i i (hsw )
2
2
2
2
2
2
sLi ( s 2 + sRd Cf ωres
+ ωres
) i (h )
sCf Rd zLC
+ zLC
sCf Rd zLC
+ zLC
1
1
i g (hsw ) =
v i (hsw ) =
i
sw
2
2
2
2
2
2
2
2
2
sLi ( s + sRd Cf ωres + ωres )
sLi ( s + sRd Cf ωres + ωres ) s + sCf Rd zLC + zLC
i g (hsw )
i i (hsw )
=
2
2
sCf Rd zLC
+ zLC
2
2
s 2 + sCf Rd zLC
+ zLC
Appendix 2 LCL Filter
(2.12) 127
NTNU Department of Electric Engineering
Transfer functions of the undamped system.
H iivi =
2
i i (s )
1 s 2 + zLC
=
2
2
v i (s ) sLi ( s + ωres
)
H iivg =
2
zLC
i i (s )
1
=
2
v g (s ) sLi ( s 2 + ωres
)
ig (s )
H igvi =
v i (s )
=
i g (s )
H igvg =
v g (s )
2
zLC
1
2
2
sLi ( s + ωres
)
=
2
2
1 s + zLCg
2
sLg ( s 2 + ωres
)
Hvcvi =
2
zLCg
v c (s )
= 2
2
v i (s ) ( s + ωres
)
Hvcvg =
v c (s )
z2
= 2 LC 2
v g (s ) ( s + ωres )
(2.13) With the same assumptions as for the damped system the transfer function between the
inverter side current and the grid side current at switching frequency becomes.
i g (hsw )
i i (hsw )
Appendix 2 LCL Filter
=
2
zLC
2
s 2 + zLC
(2.14) Fundamentals of Grid Connected Photo‐Voltaic Power Electronic Converter Design
128
3 SYSTEM RATING
A multi‐string converter with full bridge boost converters on the input, and a three‐phase
full bridge inverter on the output is to be used. The converters will be dimensioned to be
used on the solar panels at NTNU, and should be able to connect to a 400V grid. Each string
will have its own full bridge boost converter, and the DC‐DC converter will therefore be
dimensioned for one string only. The DC‐AC inverter on the other hand, must be
dimensioned to withstand the power delivered from all the strings. 3.1 Description of solar panels at NTNU
The solar panels at NTNU are mounted on the southern wall of electro building b, and cover
192m2. They are integrated in a 455m2 double glass facade mounted on the outside of the
buildings existing cladding. The solar modules are delivered from BP Solar, and the modules
consist of series of 60 or 90 monocrystalline silicone cells from Saturn Technology. These
modules are arranged in strings with four 90 cell modules and one 60 cell module, with a
total peak power of 14.56kW. Electrical data for one PV string
Open circuit voltage VOC_STC
300V
Short circuit current ISC_STC
5A
Maximum power PMAX_STC
910W
Voltage at maximum power VMAX_STC 210V
Current at maximum power IMAX_STC
4.3A
All data is given at STC (Standard Test Condition), with irradiance of 1 kW/m2, air mass (AM)
of 1.5, and a cell temperature of 25ºC.
3.2 DC‐DC converter
In this chapter the DC‐DC converter will be rated, and most of the calculations made here
are based on equations derived in appendix 1.1.
3.2.1 Switching
The switching scheme of this converter is shown in the DCDC converter appendix, and to
reduce the size of the magnetic components the DC‐DC converter will be switched at a high
frequency. A switching frequency of f S = 50kHz will be used, and therefore mosfets will
be a natural choice of switches.
Appendix 3 System rating
129
NTNU Department of Electric Engineering
3.2.2 Voltage rating
The inverter will be connected to a three‐phase 400V grid, and this will therefore be the
rated output voltage of the full bridge inverter, that is VLL = 400V. Based on this the needed
DC‐link voltage can be calculated. To achieve the maximum output voltage without
overmodulation, the inverter must run at approximately unity modulation ratio, that is ma
= 1. Once the modulation ratio is known, then the DC‐link voltage can be calculated based
on the maximum voltage with space vector modulation, given in equation (3.9) in the
master thesis.
VDC = 2VLL = 2 ⋅ 400 = 565V
This is the minimum voltage on the DC‐link, but because there will be a voltage drop across
the LCL filter the voltage is sat to 600V. Based on the DC‐link voltage and the PV panel
voltage, the transformer winding ratio and the DC‐DC converter can be dimensioned. The
input voltage is a function of the temperature, and the input voltage range of one string can
be calculated by using equation (2.1) from the master thesis. Assuming the temperature of
the cells can vary from – 30 ° C to 60 ° C , and the number of cells in series per string is
n c = 1 ⋅ 60 + 4 ⋅ 90 = 420 , the open circuit voltage range is:
VOC _ max = −2.3 ⋅ 10−3 ⋅ nc ⋅ (Tmin − TSTC ) + VOC _ STC
= −2.3 ⋅ 10−3 ⋅ 420 ⋅ ( −30 − 25) + 300
= 353V
VOC _ min = −2.3 ⋅ 10−3 ⋅ nc ⋅ (Tmax − TSTC ) + VOC _ STC
= −2.3 ⋅ 10−3 ⋅ 420 ⋅ (60 − 25) + 300
= 266V
This is the maximum and minimum voltages at open circuit, and the converter should be
able to handle the maximum open circuit voltage even though it is not the normal operating
voltage at MPP. So the maximum operating voltage of the DC‐DC converter becomes:
VPV _ max = VOC _ max = 353V
Since the converter will be working at the MPP voltage, which is lower then the open circuit
voltage, the minimum voltage the DC‐DC converter must handle will be lower then
V OC_min . By finding the MPP voltage at max temperature, and a voltage 10% below this
value will give an approximation of the lowest allowable operating voltage. The minimum
operating voltage of the DC‐DC converter is then: Appendix 3 System rating
Fundamentals of Grid Connected Photo‐Voltaic Power Electronic Converter Design
VPV _ min =
130
VMAX _ STC
210
⋅ VOC _ MIN ⋅ 0.9 =
⋅ 266 ⋅ 0.9 = 168V
300
VOC _ STC
Should the voltage be above or below these values, the converter must cease to energize
the DC‐link. 3.2.3 Current rating
Since the converter will operate in continuous conduction mode (CCM), a lower current
limit must be set, which also will become the limit between continuous and discontinuous
conduction mode (DCM). It is desired to have a large operating range of the converter, and
thus a low limit, but at the same time it is desired to keep the boost inductor as small as
possible, and thus a higher limit. So a minimum input current limit of 10% of ISC is therefore
used, and the maximum input current is equal the short circuit current of the PV panels.
Giving an operating range of:
0.5 A ≤ IPV ≤ 5.0 A
The lower limit equals the limit between CCM and DCM, ILB.
3.2.4 Transformer ratio
To be able to use mosfets in the DC‐DC converter the voltage over the switches must be
kept at an acceptable level. The highest voltage over the switches will be equal to the
primary voltage of the transformer, and is therefore a direct function of the winding ratio
and the DC‐link voltage. A 500V mosfet is assumed used, and there should be some safety
margins, so the primary voltage of the transformer should never exceed 400V. Based on
this the transformer ratio becomes:
n=
VDC 565
=
= 1.4
VP
400
3.2.5 Duty cycle limits
Based on the previous calculations, the duty cycle limits becomes
Dmax = 1 −
Dmin = 1 −
Appendix 3 System rating
VPV _ min ⋅ n
VDC
VPV _ max ⋅ n
VDC
= 1−
168 ⋅ 1.4
= 0.58
565
= 1−
353 ⋅ 1.4
= 0.17
600
131
NTNU Department of Electric Engineering
3.2.6 Boost inductor
The inductance of the boost inductor is governed by the minimum current the circuit must
deliver in CCM, the PV voltage and the DC‐link voltage. This is shown in equation (1.14) in
appendix 1.1, so the boost inductor becomes:
Lboost = VPV
VDC − VPV ⋅ n
Ts
4ILBVDC
(3.1) As seen from the equation, the only variable is the PV voltage. In the figure below the boost
inductor is shown as a function of the PV voltage. Figure 3.1: Boost inductor as function of the PV voltage
It can be shown that the maximum inductor appears at:
VPV _ max L =
VDC
2n
By inserting this into equation (3.1), the boost inductor needed is:
Lboost =
Appendix 3 System rating
VDC
600
Ts =
⋅ 20 ⋅ 10−6 = 1.1mH
16n ⋅ ILB
16 ⋅ 1.4 ⋅ 0.5
(3.2) Fundamentals of Grid Connected Photo‐Voltaic Power Electronic Converter Design
132
3.2.7 PV Capacitor
The PV panel can be seen as a current source, and as mentioned in the master thesis, it is
needful to convert it to a voltage source by adding a capacitor in parallel. In this way the
capacitor will handle the ripple current from the boost inductor, smooth the current from
the PV panel, and keep the PV panel voltage ripple at a minimum. The capacitor can be
found as shown in appendix 1.1
2
CPV
⎛ VPV ⋅ n ⎞
⎜1−
⎟
VDC ⎠ 2
⎝
= VPV
Ts
8Lboost ∆VPV
(3.3) Choosing a maximum voltage ripple of 0.1V, and plotting
Figure 3.2: PV condensator as function of PV voltage
It can be seen from the plot that the capacitor needs to be highest at the lowest input
voltage, and using equation (3.4) gives a capacitor value of approximately 30 µ F . But if a
electrolytic capacitor is to be used the maximum current ripple must also be considered. In
appendix 1.1 an expression for the current ripple is derived
Appendix 3 System rating
133
NTNU Department of Electric Engineering
∆IL = VPV
VDC − VPV ⋅ n
Ts
4Lboost VDC
(3.4) Solving this equation for the highest current ripple, gives a maximum ripple of 0.50A, with
an rms value of 0.29A.
3.2.8 DC Capacitor
The instantaneous power drawn from the DC‐link is constant and equal the power drawn
from the PV panels, as shown in figure 2.8 in the master thesis. Assuming the DC‐link
voltage is held constant, the current drawn from the DC‐link is also constant, so therefore
the capacitor must deliver all the current during switching intervals 1 and 3 (see appendix
1.1 for switching schemes). Based on this the capacitor size is in appendix 1.1 derived as
CDC =
IDC _ MAX (VDC − VMAX _ STD ⋅ n )TS
VDC
2∆VDC
(3.5) At the maximum power, the DC current is 1.6A, and setting a maximum voltage ripple of 1V,
the capacitor size becomes C DC = 7.7 µ F . If an electrolytic capacitor is to be used, then
the current ripple must also be taken into consideration, and in this case the rms current
ripple is the same as the maximum DC‐link current.
3.2.9 Circuit design
Based on the calculations made in the previous chapters, the DC‐DC converter has been
designed. For the design of the circuit, the OrCad 10.5 program pack was used, where the
circuit design was made in Capture CIS, and the PCB layout was done in Layout. A schematic
of the circuit is shown in the figure 3.3, and the component specification can be found in
table .3.1
Appendix 3 System rating
Fundamentals of Grid Connected Photo‐Voltaic Power Electronic Converter Design
Figure 3.3: DC‐DC converter schematics from OrCad Capture
Appendix 3 System rating
134
135
NTNU Department of Electric Engineering
Table 3.1 ‐ Component list
Type
Brand
Description
19MT050XF
International
Rectifier
Mosfet full bridge IR2113
International
Rectifier
High and low side
driver
8ETH06
International
Rectifier
High speed diode
ETD49/25/16
Ferroxcube
3F3 ferrite core
55109A2
Magnetics
Kool mu toroid
FA‐NR: 607418
Block
Litz wire
LAH 25‐NP
LEM
Current transducer
25A
1
NMV0515SAC
Newport
Components
Isolated converter
1W
4
EETED2G331DA
Panasonic
Electrolyte capacitor
400VDC,
330uF
3
Tantal condensator
0.1uF, 35V
4
Tantal condensator
10uF, 16V
2
Surface resistor
Size
Count
500V
1
2A
2
600V, 18ns
4
2
77110
1
0.1mm2
DC‐DC
mounted
10Ω
A circuit board with standard copper layer thickness of 35µm is used, and the track width
of the high power tracks is 5mm. According to [21], a track width of 5mm gives a 10 °
temperature rise at a current of 7A. A boost inductor was built on the Kool mu toroid, and a high frequency transformer on the
3F3 ferrite core. The calculations is shown in appendix 4, and the leakage inductance of the
buildt transformer is shown in the table below.
Table 3.2 ‐ HF Transformer leakage inductance and resistance at 50kHz
Transformer
Leakage Inductance
Resistance
1.3µH
1.4Ω
Litz wire ‐ partitioned (S‐P‐S‐P‐S)
Appendix 3 System rating
Fundamentals of Grid Connected Photo‐Voltaic Power Electronic Converter Design
136
Also some test points where added to the design, these are shown in the table below.
Table 3.3 ‐ Test Points on DC‐DC converter
Name
Description
Additional information
GND
Ground
VC
Input capacitor voltage and PV voltage
Vi
Voltage boost inductor
Vp
Primary voltage of transformer
Vs
Secondary voltage of transformer
Vdc
Voltage DC‐link
Vg2
Voltage gate 2
Vg4
Voltage gate 4
Ig2
Current gate 2
Voltage across gate resistance
Ig4
Current gate 4
Voltage across gate resistance
3.3 DC‐AC inverter
3.3.1 Switching
To decrease the lower harmonic content, a high switching frequency will be applied, even
though it reduces the effectivity of the inverter. It also reduces the size of the capacitive and
inductive components connected to the inverter, and enables faster response of the
controller. A switching frequency of 20kHz will be used.
3.3.2 Inverter specifications
An IGBT converter which is designed as a general building block for DC‐DC converters, DC‐
AC converters and motor drives will be used. The converter is designed for laboratory use
at NTNU SEfAS, and the converter rating is
Power 20kW
DC‐Voltage: 0‐650V
Switching frequency
0‐25kHz, 0‐100% pulse width modulation
The total peak power of all the solar panels at NTNU is 14.56kW, so the converter is
oversized. Therefore no further calculations will be made in the DC‐AC inverter.
Appendix 3 System rating
137
NTNU Department of Electric Engineering
3.4 LCL filter
The goal when designing an LCL filter is to reduce high‐order harmonics on the grid side. But
when designing the filter care must be shown, or the attenuation can become lower than
expected, or it can even lead to a distortion increase because of oscillation effects. The
inverter current harmonics can in fact cause saturation of the filter inductors or give filter
resonance. So it is important to design the inductors correct considering current ripple, and
the filter should be damped to avoid resonance. The LCL filter with damping resistor is
shown in the figure below.
Figure 3.4: LCL filter with damping resistor
3.4.1 Design
The design is based on some of the design considerations given in [19,20], and the goal is
to lower the current harmonics below the limits given by the standards. In [23] it is shown
that the highest harmonic voltage occurs at m f ± 2 at unity modulation ratio, where mf =
fs
fg
At these frequencies, the amplitude of the harmonic voltages is shown to be 0.32pu of the
fundamental when using sinusoidal PWM. For space vector modulation, the harmonics will
become different, but in order to find the amplitude of these harmonic voltages the PWM
scheme should be simulated. In order to avoid simulating the SVM scheme, it is instead
assumed that the harmonics with this scheme is the same as with sinusoidal PWM. This can
be justified by the fact that the harmonics produced by SVM is lower than those produced
by sinusoidal PWM, as stated in chapter 3.3.2 of the master thesis.
Appendix 3 System rating
Fundamentals of Grid Connected Photo‐Voltaic Power Electronic Converter Design
138
In table 2.3 of the master thesis the harmonic current limit is sat to 0.3% of the fundamental
for harmonics above the 33rd, therefore the filter should be designed to reduce the
harmonics around the switching frequency below this limit. Since the highest amplitude of
the harmonics occur close to the switching frequency, it should be adequate to calculate
the attenuation of the currents at the switching frequency, and design the filter according
to this.
Base values
Base voltage, power, current and frequency.
En = Vg = 400V
Pn = PMAX _ STC = 910W
Ig =
Pn
3Vg
= 1.31A
ωn = 2π fg = 2π 50 = 314 rad s
Base impedance and base capacitance
Zb =
Cb =
E n2 4002
=
= 176Ω
Pn
910
1
ωn Z b
=
1
= 18 µF
314 ⋅ 176
Inverter side inductor
The harmonic current at switching frequency should be limited to I399 = 0.3% ⋅ Ig = 0.003 ⋅ 1.31 = 3.93mA
The selection of an appropriate limit for the current harmonics through the converter side
inductor, is a trade‐off among inductor size, switching and conduction losses, and inductor
coil and core losses (from [20]). Higher limits gives lower switching and conduction losses,
but a larger inductor, resulting in larger coil and core losses. In this case a current limit of
20 times the limit at the output of the filter is used, giving an inductor size of
Li =
V399
0.32 ⋅ 400
=
= 4.3mH
399 ⋅ ωn ⋅ I399
3 ⋅ 399 ⋅ 314 ⋅ 0.0039 ⋅ 20
Capacitor
The maximum reactive power of the capacitor should be 5% of the rated power, this gives
a maximum capacitor size of
Appendix 3 System rating
139
NTNU Department of Electric Engineering
Qf = k pf Prated = 3ωg Cf Vgf2
Cf _ max = k pf
Prated
910
= 0.05
= 0.9µ F
3ωgVgf2
3 ⋅ 314 ⋅ 2302
k pf : percentage reactive power of rated power
Vgf : grid phase voltage
This demand is equal to Cf ≤ 0.05Cbase , and the largest standard size capacitor below this
value is 0.68µF. Therefore this size will be used.
Grid side inductance
In a two level VSI the current harmonics is centred around the switching frequency and
above, with the highest harmonic in the vicinity of the switching frequency. The ripple
attenuation at switching frequency from the inverter current to the grid current, without
considering the damping resistor, can be expressed as (see appendix 2.2 for derivation of
this transfer function)
H igii (ωsw ) =
i g (ωsw )
i i (ωsw )
=
z
2
LC
(z − ω
2
LC
2
sw
)
2
=
1
Lg Cf
⎛ 1
⎞
2
− ωsw
⎜⎜
⎟⎟
⎝ Lg Cf
⎠
2
=
1
( Lg Cf ωsw2 − 1)
2
= ka
(3.6) k a : current attenuation from iL1 to iL2
In order to comply with the standards, the harmonic current at switching frequency has to
be reduced to 5% of the inverter side current.
Lg =
1
+1
k a2
2
Cf ωsw
1
+1
2
0.05
=
= 2mH
2
0.68 ⋅ 10−6 ⋅ ( 2π ⋅ 19950 )
Total inductance value
The total inductance value should be less then 0.1pu to limit the AC‐voltage drop during
operation.
−3
ZLf ωn ( Li + Lg ) 2π 50 ( 4.3 + 2 ) ⋅ 10
=
=
= 0.011pu
176
Zb
Zb
Resonant frequency
Appendix 3 System rating
Fundamentals of Grid Connected Photo‐Voltaic Power Electronic Converter Design
The resonant frequency should be in the range of fres =
1
1
2
=
ωres
2π
2π
1
Cf
⎛1 1⎞ 1
⎜⎜ + ⎟⎟ =
⎝ Li Lg ⎠ 2π
140
10fg ≤ fres ≤ 0.5fsw ⇒ 500Hz ≤ fres ≤ 9975Hz
1
1
1
⎛
+
−6 ⎜
−3
0.68 ⋅ 10 ⎝ 4.3 ⋅ 10
2 ⋅ 10−3
⎞
⎟ =5224Hz
⎠
Damping resistor
A large resistor gives effective damping, but it also tends to reduce the attenuation above
the resonant frequency, and increase the losses. When using a resistor in series with the
capacitor, the resistor size is often sat to one third of the capacitor impedance at resonant
frequency. X cf =
1
ωresCf
=
1
= 34.6Ω
2π ⋅ 6762 ⋅ 0.68 ⋅ 10-6
Rd =
X cf 34.6
=
≈ 10Ω
3
3
LCL filter specifications
In table 3.4 the filter specifications is summarized, and in table 3.5 the components used
are listed, and the inductance values are measured using an RLC meter.
Table 3.4 ‐ LCL filter specifications
Parameter
Value
Inverter side inductance Li
4.3mH
Filter capacitance Cf
0.68µF
Grid side inductance Lg
2.0mH
Damping resistor Rd
10Ω
Resonance frequency fres
5224Hz
Table 3.5 ‐ Component list LCL‐filter
Type
Brand
Resistor
Capacitor
Appendix 3 System rating
Epcos
Description
#
10Ω, 50W
3
0.68µF
3
141
NTNU Department of Electric Engineering
Table 3.5 ‐ Component list LCL‐filter
Type
Brand
Description
#
Inductor
Magnetics KoolMu
2.06mH, 1.1Ω(at 50Hz)
2.07mH, 2.2Ω(at 20kHz)
3
Inductor
Magnetics KoolMu
4.45mH, 1.8Ω(at 50Hz)
4.47mH, 3.9Ω(at 20kHz
3
Appendix 3 System rating
Fundamentals of Grid Connected Photo‐Voltaic Power Electronic Converter Design
142
4 MAGNETIC DESIGN
4.1 LCL Filter inductance
4.1.1 Specifications
The required specifications of the inductor is:
Li = 4.3mH
Lg = 2.0mH
IDC = IRMS =
PPV
910
=
= 2.3 A
VRMS 400
IDC _ bias = 0 A
A KoolMu core from Magnetics will be used, and in the design of the inductor a design
procedure described in “Magnetics Powder Core Catalogue” (found at www.mag‐inc.com)
is used.
4.1.2 Design of converter side inductance
2
−3
2
2
1. LIDC = 4.3 ⋅ 10 ⋅ 2.3 = 22.7mHA
2. From a Core Selector Chart a core with a permeability of 60µ and core number 77110
is found.
3. a) Calculating the number of turns
Worst case:
AL = 75 ⋅ 0.92 = 69 mH
Nmin =
1000turns
Ln ⋅ 10
4.3 ⋅ 106
=
= 250turns
69
AL
6
b) The dc‐bias
No DC‐bias
c) Determine the rolloff in per unit from dc‐bias curves
No roll off
d) Increasing the number of turns
No increase in number of turns
4. Choosing wire size using a wire table
JL = 6 A
ACU
mm 2
= 0.41mm 2
The skin depth at 20kHz is 0.53mm2 (table 30‐2 in [29]), and therefore an ordinary single
conductor wire is adequate.
Appendix 4 Magnetic design
143
NTNU Department of Electric Engineering
4.1.3 Design of grid side inductance
2
−3
2
2
1. LIDC = 2.0 ⋅ 10 ⋅ 2.3 = 10.6mHA
2. From a Core Selector Chart a core with a permeability of 60m and core number 77071
is found. Because 77110 is in stock this will be used instead.
3. a) Calculating the number of turns
Worst case:
AL = 75 ⋅ 0.92 = 69 mH
Nmin =
1000turns
Ln ⋅ 10
2.0 ⋅ 106
=
= 170turns
AL
69
6
b) The dc‐bias
No DC‐bias
c) Determine the rolloff in per unit from dc‐bias curves
No roll off
d) Increasing the number of turns
No increase in number of turns
4. Choosing wire size using a wire table
JL = 6 A
mm 2
= 0.41mm 2
ACU
The skin depth at 20kHz is 0.53mm2 (table 30‐2 in [29]), and therefore an ordinary single
conductor wire is adequate.
4.2 High frequency transformer
4.2.4 Specification
The design criteria of the transformer is.
fs = 50kHz
n = 1.4
S = 910W
Vpri =
I pri =
2
Ts
∫
(1−Dmin )Ts / 2
0
2
Vˆpri dt =
2
Ts
⎛ Vˆpri 2 (1 − Dmin )Ts
⎞
⎜
− 0 ⎟ = Vˆpri 2 (1 − D min) = 4002 (1 − 0.12) = 375V
⎜
⎟
2
⎝
⎠
S 910
=
= 2.4 A
Vpri 375
k cu = 0.3 (litz wire)
Appendix 4 Magnetic design
Fundamentals of Grid Connected Photo‐Voltaic Power Electronic Converter Design
144
4.2.5 Design
In the design of the transformer, a simplified calculation will be used. Losses in the
transformer will be neglected, and instead the transformer will be made sufficiently large. The core chosen is a Ferroxcube ETD 49/25/16 with these specifications:
Acore = 2.11cm 2
Aw = 3.1cm 2 (2.73 in datasheet)
AP = 5.76cm 4
Bˆ = 0.2T (at 50kHz)
The number of turns needed is
Np =
Vˆp
2π f ⋅ Acore Bˆ
=
400
= 30turns
2π ⋅ 50e 3 ⋅ 2.11e − 4 ⋅ 0.2
Ns = N p ⋅ n = 30 ⋅ 1.4 = 42turns
In order to fill the window completely the optimal wire sizes becomes
ACUp =
k cu AW 0.3 ⋅ 273
=
= 1.1mm 2
2N p
2 ⋅ 37
ACUs =
k cu AW 0.3 ⋅ 273
=
= 0.68mm 2
2N s
2 ⋅ 60
Using a wire size of ACU = 0.94mm for both windings utilizes 226mm of the total window,
and leaves some place for isolation. Estimating the maximum rating of the transformer
2
2
2.4
= 2.55 A
mm 2
0.94
= 2.22 ⋅ k cu ⋅ f ⋅ J rms ⋅ Bˆ ⋅ Acore Aw = 2.22 ⋅ 0.3 ⋅ 50e 3 ⋅ 2.55 ⋅ 0.2 ⋅ 6.54e − 2 = 1.1kVA
J rms =
Smax
The maximum rating of the transformer is larger than the rating of the PV panels, and
should therefore be sufficiently large. It should also be noted that the PV panels almost
never work at maximum rating, and therefore the transformer will normally have some
capacity left.
Appendix 4 Magnetic design
145
NTNU Department of Electric Engineering
Reduction of leakage inductance
In order to reduce the leakage inductance the windings has to be partitioned into multiple
sections, and thus the leakage inductance is reduced. This arrangement also reduces the
eddy current losses, but increases the interwinding capacitance and increases the amount
of safety insulation between the sections. The increased amount of insulation is not a
problem since the windings themselves does not fill the whole window. In the figure below
the partitioning is shown.
S P S P S
S P S P S
Figure 4.1: Partitioning of the transformer windings
4.3 High frequency boost inductor Design
4.3.6 Specification
The required specifications of the inductor is:
LBoost = 1.02mH
IDC = 4.3 A
IDC _ bias = 0.43 A (at required inductance)
Appendix 4 Magnetic design
Fundamentals of Grid Connected Photo‐Voltaic Power Electronic Converter Design
146
4.3.7 Design
A KoolMu core from Magnetics will be used, and in the design of the inductor a design
procedure described in “Magnetics Powder Core Catalogue” (found at www.mag‐inc.com)
is used. 2
−3
2
2
1. LIDC = 1.02 ⋅ 10 ⋅ 4.3 = 18.9mHA
2. From a Core Selector Chart a core with a permeability of 60µ and core number 77716
is found, one size larger is used (77110) to increase the number of turns per layer and
thus reduce the capacitive coupling between input and output.
3. a) Calculating the number of turns
Worst case:
AL = 75 ⋅ 0.92 = 69 mH
Nmin =
1000turns
Ln ⋅ 10
1.1⋅ 106
=
= 126turns
AL
69
6
b) The dc‐bias:
H=
0.4π NIDC _ bias
Ie
=
0.4π ⋅ 126 ⋅ 0.43
= 4.8oersteds
14.3
c) Determine the rolloff in per unit from dc‐bias curves
Rolloff=0.97
d) Increasing the number of turns
Nadj =
Nmin
126
=
= 130turns
Rolloff 0.97
4. Finding the wire size
JL = 2 A
ACU
Appendix 4 Magnetic design
mm 2
= 2.0mm 2
147
NTNU Department of Electric Engineering
5 BRIEF DESCRIPTION OF CONVERTER SIMULATION 5.1 DC‐AC Converter
The converter is simulated in simulink, and this appendix contains a brief description of how
the simulation is made. The simulink model consists of three major blocks as shown in
figure 5.1.1. These three blocks are described in the following chapters. All variables are
defined in a m‐file called constants.m, and from this file all process and controller variables
can be changed. This file must be executed before the simulation is started.
Figure 5.1: The three main blocks in the simulink model
This description of the model is very brief, but there is also added more detailed
information in the model itself.
5.1.1 Measurements and Acquisitions
This block handles the measurements of the process variables. First the block filters the
signals, and then it samples the filtered signals at the specified sampling interval TS. The
content of this block is shown in figure 5.2.
Appendix 5 Brief Description of Converter Simulation Fundamentals of Grid Connected Photo‐Voltaic Power Electronic Converter Design
148
Figure 5.2: Content of measurement and acquisitions block
5.1.2 Control
In this block all transformations, phase synchronization and control of current and voltage
is handled. Instead of using SVM, CB‐PWM with third harmonic injection is used. They give
equal output, but the carrier based is easier to implement in simulink.The content of this
block is shown in figure 5.3
Appendix 5 Brief Description of Converter Simulation 149
NTNU Department of Electric Engineering
Figure 5.3: Content of control block
5.1.3 Plant
The last block is the plant block, and in this block all the physical processes are simulated.
The content of this block is shown in figure 5.4. The grid voltage is in this model simulated
as a pure sinusoidal three phase voltage, without any harmonics. It is possible to set the
initial voltage angle, and to give the voltage a phase jump at a specified instant.
The DC‐link is modelled as a capacitor with currents as input and the DC‐link voltage as
output. The current drawn from the DC‐link is the d‐axis current multiplied with a constant
KDC, which relates the d‐axis current and the current from the DC‐link. The source feeding
the DC‐link, is a source having similar current voltage characteristics as a solar panel. The model of the inverter includes full PWM, and the switch signals are generated at a
similar way as they are generated in a DSP. As an interface to the grid a model of the LCL
filter is used. Appendix 5 Brief Description of Converter Simulation Fundamentals of Grid Connected Photo‐Voltaic Power Electronic Converter Design
150
Figure 5.4: Content of plant block
5.2 DCDC Converter The converter is simulated in simulink, and this appendix contains a brief description of how
the simulation is made. The simulink model consists of four major blocks as shown in figure
5.5, which are described in the following chapters. All variables are defined in a m‐file called
DCDC_constants.m, and from this file all process and controller variables can be changed.
This file must be executed before the simulation is started. Appendix 5 Brief Description of Converter Simulation 151
NTNU Department of Electric Engineering
Figure 5.5: The four main blocks in the simulink model
This description of the model is very brief, but there is also added more detailed
information in the model itself.
5.2.4 Measurements and Acquisitions
This block handles the measurements of the process variables. First the signals are filtered,
then it samples the filtered signals at the specified sampling interval. The content of this
block is shown in figure 5.6. The measurements made here corresponds to the
measurements made in a real system.
Appendix 5 Brief Description of Converter Simulation Fundamentals of Grid Connected Photo‐Voltaic Power Electronic Converter Design
152
Figure 5.6: Content of measurement and acquisitions block
5.2.5 Control DC‐AC Converter
This block is the same as the control block of the DCAC simulation, see chapter 5.1.2.
5.2.6 Control DC‐DC Converter
The control of the DCDC converter is in this case only the MPP tracker. The MPPT is based
on the P&O algorithm, and this algorithm is executed at a specified sampling interval.
Appendix 5 Brief Description of Converter Simulation 153
NTNU Department of Electric Engineering
Figure 5.7: Content of Control_DCDC_Converter block
5.2.7 Plant
In this block all the physical processes are simulated. The content of this block is shown in
figure 5.8
In the DCAC simulation a very simple model of the PV array was used, but in this model the
full I‐V characteristic, with a model of the DCDC converter is added. The I‐V characteristic
comes from the GUI “PV_Panel.fig”, and is transferred to and stored in the simulink model
as a look up table.
The DCDC converter model is based on the small signal model derived in the preliminary
project. This model is averaged across one switching interval, and this is considered an
adequate approximation since the converter is much faster than the MPPT. The DC‐link is modelled as a capacitor with currents as input and the DC‐link voltage as
output. The current drawn from the DC‐link is the d‐axis current multiplied with a constant
KDC, which relates the d‐axis current and the current from the DC‐link.
The grid voltage is in this model simulated as a pure sinusoidal three phase voltage, without
any harmonics. It is possible to set the initial voltage angle, and to give the voltage a phase
jump at a specified instant.
Appendix 5 Brief Description of Converter Simulation Fundamentals of Grid Connected Photo‐Voltaic Power Electronic Converter Design
154
In this model a simplified converter model is used in the grid interface compared to the one
used in the DCAC simulation. Instead of using full PWM, it is assumed that the output from
the inverter is a pure sine wave. This reduces the need for running the model at a sampling
rate higher than specified sampling rate TS. The LCL filter is the same as the one used in the
DCAC simulation.
Figure 5.8: Content of plant block
Appendix 5 Brief Description of Converter Simulation 155
NTNU Department of Electric Engineering
6 DC‐DC CONVERTER PROBLEMS
The DC‐DC converter topology wanted was not available, and a new converter was
therefore built and tested. It can be mentioned before reading this appendix that the
design was not a success, as it ended with two broken mosfet full bridges. This chapter will
deal with some of the problems and solutions found during the testing, and will finish off
with some unsolved problems. 6.1 Voltage spikes
During turn off of two of the diagonal switches a voltage spike was encountered across the
full bridge during the commutation of the current from the bridge and into the transformer.
This voltage spike is not wanted, but unfortunately in current fed designs with transformers
this is a normal problem. This spike is known from the isolated flyback topology, and is there
called a leakage spike. The name is due to the fact that this spike is caused by the leakage
inductance of the transformer, when the current is forced into the transformer windings. The circuit can be analysed by looking at the transformer equivalent circuit in figure 6.1. In
this figure the parasitic elements and the magnetizing inductance is taken into
consideration. When S1 is turned on (equivalent to turning off two diagonal switches), the
current will be forced into Cp and then gradually into LlP. On the secondary side the same will
happen. The transformer capacitance combined with other parasitic capacitances in
parallel, together with the leakage inductance will mainly decide the switching speed and
the peak value of the voltage spike.
=
Figure 6.1: Transformer equivalent circuit with a resistive load, and a switched current source at the input
This spike can cause problems if it is not reduced, because it can outgo the SOA of the
switch and cause breakdown. It can also cause some oscillations across the bridge, which
can be a source to noise. The di/dt of the leakage inductance will also influence the
switching speed, and thus increase the switching losses. In figure 6.2 the voltage across the
bridge is shown in a setup where the leakage inductance is considerable. In the positive
pulse two diagonal switches without snubber is turned off, and in the negative pulse two
switches with a RC snubber is turned off.
Appendix 6 DC‐DC Converter Problems
Fundamentals of Grid Connected Photo‐Voltaic Power Electronic Converter Design
156
Figure 6.2: Transformer primary voltage with leakage spike. In the positive pulse two diagonal switches without snubber is turned off, and in the negative pulse two switches with a RC snub‐
ber is turned off.
In order to reduce this problem there are several methods, but the first thing to address is
reduction of the leakage inductance. In an ideal case this would be zero and there would
not be a voltage spike, therefore an optimization of the transformer is the first one should
do. Transformer optimization
This section will only give some general design tips on how to reduce the leakage
inductance, for further information the reader is referred to the literature. First one should
make sure a core with no air gap is used (E‐cores come with gap in the centre leg, which had
been used by a mistake in the transformer design here), this will lead to an increased
leakage, but also reduced magnetizing inductance which causes other problems (these are
described later in this chapter). Another solution is to partition the windings, where the primary and secondary winding is
interleaved. This is often done to reduce the eddy current losses, but there will also be a
reduction in the leakage inductance because of the reduction in stored magnetostatic
energy resulting from the smaller peak magnetic fields. It should be noted that this method
is not without its disadvantages. It increases the complexity of the transformer, and the
interwinding capacitances is increased in proportion to the number of sections. There is
also an increased need for isolation between the layers, which in turn leads to a decrease
in reliability of the insulation and the copper fill factor. In [29] a general expression for the
leakage inductance of a partitioned winding arrangement is found. µ0 ( NPr i ) l w b w
2
LLeak ≈
Appendix 6 DC‐DC Converter Problems
3p 2 hw
(6.1) 157
NTNU Department of Electric Engineering
NPr i : Number of primary turns
lw
: Mean turn length of the windings
b w : Bobbin window depth
hw : Bobbin window height
p
: Number of interfaces between winding sections
From this expression it can be seen that by reducing the mean turn length of the windings
the leakage inductance is reduced. For an E‐core this can be done by using e.g a core with
a round centre leg instead of a square leg. It is also important to increase the magnetic
coupling between the windings and the core, this is done by reducing the amount of air and
insulation between the windings and the core to a minimum. Clamping circuit
Sometimes it is not enough to reduce the leakage inductance of the transformer, and then
other alternatives must be found. Some sort of snubber circuit can be utilized. Since the
voltage across the to switches at turn off is the same as the voltage across the bridge, it is
adequate to have a snubber circuit across the bride and not one in parallel with each switch
as would be normal in an h‐bridge. Several different solutions has been tested for this
purpose, both active and passive circuits.
A passive clamping circuit (described in [26]) is implemented in the circuit in figure 6.3,
which consists of a diode and a capacitor in series connected across the bridge. The idea of
this circuit is to let the capacitor clamp the voltage across the bridge, so during turn off of
the two diagonal switches the current is fed into the capacitor first and then gradually into
the transformer. The excess energy in the clamping capacitor is discharged across a resistor.
This will however lead to extra losses due to the resistor and diode losses, and the reactive
energy absorbed in the capacitor due to the leakage inductance will also lead to increased
current rating loss and current rating due to energy circulation in the current‐fed side of the
converter. The resistor has to be designed to burn off the maximum excess energy the
capacitor has take up, and therefore the losses will be close to the maximum losses during
any load condition. These losses will be proportional to the leakage inductance, and again
a low leakage inductance is desirable.
Figure 6.3: Full bridge boost converter with a passive clamp circuit
Appendix 6 DC‐DC Converter Problems
Fundamentals of Grid Connected Photo‐Voltaic Power Electronic Converter Design
158
Other methods to avoid the inductor energy to be force commutated over to the leakage
inductance involves active clamping circuits or more sophisticated soft switching control
schemes. A method is proposed in [27] which utilizes a switch instead of the diode in the
passive voltage clamp, and thus the energy can be transferred back to the circuit instead of
being dissipated in the resistor. 6.2 Magnetizing inductance
In one of the tests made the load voltage is highly depending on the load resistance, which
it according to the ideal case should not be. With lower loads (higher resistance) the voltage
across the load becomes higher, and with higher loads it becomes lower. In figure 6.4 a plot
of the boost inductor voltage, and the primary voltage and current of the transformer is
shown. In the left figure it can be seen how the voltage across the primary winding of the
transformer is on during the time the switch is off, but in the right the voltage across the
primary goes to zero before the switch is turned on again. In figure 6.5 the primary values
have been changed with the secondary values, and here it can be seen how the secondary
voltage is on for the same duration as the primary voltage. The secondary current is also on
for the same duration as the voltage, where the current is going from its peak value at the
beginning, and falling gradually reaching zero the same instant the primary and secondary
voltage collapses.
Figure 6.4: Left: High load (low resistance)
Right: Low load (high resistance)
Yellow: Switch signal, Blue: Inductor voltage, Purple: Primary voltage, Green: Primary current
Appendix 6 DC‐DC Converter Problems
159
NTNU Department of Electric Engineering
Figure 6.5: Left: High load (low resistance)
Right: Low load (high resistance)
Yellow: Switch signal, Blue: Inductor voltage, Purple: Secondary voltage, Green: Secondary cur‐
rent
In order to analyse this phenomena, the equivalent circuit of figure 6.1 can be simplified to
the circuit in figure 6.6, assuming all transients from the parasitics are neglected. =
Figure 6.6: Simplified transformer equivalent circuit with a resistive load, and a switched cur‐
rent source at the input
By analysing how the currents in this circuit will behave if the switch is turned on end left
on for an infinite amount of time. The currents will in principle be as shown in the figure
below.
Appendix 6 DC‐DC Converter Problems
Fundamentals of Grid Connected Photo‐Voltaic Power Electronic Converter Design
160
Figure 6.7: Currents in transformer after the switch is turned on for a finite time
As shown in figure 6.7 the current in the magnetizing inductance reaches I0 after a finite
time, and during the same time the secondary current reaches zero. The time it takes for
the magnetizing current reaches to reach the input current, is depending on the size of the
magnetizing inductance. If figure 6.7 is compared to figure 6.4 and 6.5, it can be seen that
they behave in the same way. This means that in the converter circuit which switches at
50kHz, the magnetizing inductance must be very small in order for this to happen. Normally
the magnetizing inductance should be so large that it can be ignored during the switching
interval, but in this case it could not.
The solution to the magnetizing inductance problem in this case was simple, but hard to
figure out. When buying a the core it was assumed that the core was gap‐less, but upon
further investigations it showed out that the core could also be delivered with a gap in the
centre leg. This was not discovered upon receiving the core and after it was mounted it is
impossible to see. But by replacing this the magnetizing current became much smaller, and
the problem with load dependency was removed.
6.3 Gate drive ripple
During turn on of two diagonal switches it was noticed that as voltage increased across the
bridge, ripple across the gate terminals becomes noticable. At high voltage levels this led to
unstable behaviour of the mosfets, as they began an uncontrolled turn on/off cycle.
Breakdown of the mosfets was another consequence of the high voltage, but it was not
necessarly connected to the unstable behaviour, as breakdown occurred without the
unstable behaviour. The breakdown was always two diagonal mosfets.
Appendix 6 DC‐DC Converter Problems
161
NTNU Department of Electric Engineering
Figure 6.8: Gate drive ripple, right scope is a close up of the left during the gate ripple.
Yellow: Gate signal lower left switch, Blue: Transformer primary current 2mA/mV, Purple: Gate signal upper left gate, Green: Voltage across bridge
No solution was found to this problem, but some ideas of the origin of this problem was
found. It should be mentioned however that there was some problems with noise in the
measurements, and that possibly the probes led to an increase in the amount of noise. This
seemed to be reduced when using differential probes, but some noise might still be a
problem.
• High di/dt of the mosfets can lead to malfunction of the level shifting inside the
bootstrap drive circuits, and this might in turn lead to the unstable behaviour. Drivers
with optocouplers where also tried, and these did not seem to have the same problem. • Large di/dt of the reverse recovery currents of the rectifier diodes are reflected into the
primary when the switches are turned on. This can be seen as the blue signal of figure
6.8. Where this current ends up in the bridge is unknown since the bridge is an
integrated circuit, and the currents can’t be measured through each of the switches.
With the high di/dt this current can probably find its way through some of the parasitic
capacitances of the mosfets, and possibly disrupt the gate signal. The origin of this problem is not known, so care should be taken in a possible new design.
First of all the circuit should be made especially for testing with lots of test points, and the
mosfets should be discrete components so one can be able to measure the currents
through them. It is also a good idea to have the gate drive circuit on a separate card, as this
makes it easier to change drivers. It can also be smart to have the full bridge, the
transformer and the rectifier bridge as separate units, with the transformer as a plug in
module. This will make it easier to see the effects of the transformer in the circuit. Noise
should also be considered in the new design, and probes which are resistant to noise should
be used. Appendix 6 DC‐DC Converter Problems
Fundamentals of Grid Connected Photo‐Voltaic Power Electronic Converter Design
162
6.4 Duty‐cycle steps
During this testing it was discovered that when a large positive step in duty cycle was
applied the protective circuit in the software triggered on overcurrent. An analysis of the
current and voltage during a positive duty cycle step is shown below. When a large negative
step is applied, the current will be reduced and the voltage across the bridge is clamped to
the DC‐link voltage. Therefore no problems will arise due to a negative step. Positive step in duty cycle
If a positive step is applied to the duty cycle, it can be seen from equation (6.2) that the DC‐
link voltage will rise.
VDC = VPV
n
1− D
(6.2) Since the DC‐link voltage is clamped with a capacitor, the output voltage can not rise
instantaneously. During this charging period the input current to the converter will only be
limited by the boost inductor, and the series resistance of the circuit. If one assumes the
input is an ideal voltage source, and the transformer is ideal, then an equivalent circuit
during the positive duty cycle change is
Figure 6.9: Equivalent circuit of converter during a positive duty cycle step
As long as one assumes that only positive steps in deducible occurs (due to the diode), and
assuming that the input voltage is constant, a small signal AC model of the circuit can be
made (see [30] for description of method). The response of the boost inductor current and
the DC‐link voltage due to a small step in the duty cycle can than be described as.
H IL (s ) =
( nVDC + Rload ILD ' ) + ( nCDC RloadVDC ) s
iˆL (s )
=− 2
2
n CDC RLoad LBoost s + n 2 (CDC RLoad RSeries + LBoost ) s + ( n 2RSeries + RLoad D '2 )
dˆ '(s )
Appendix 6 DC‐DC Converter Problems
(6.3) 163
HVDC (s ) =
NTNU Department of Electric Engineering
RLoad ( nRSeries IL − VDC D ' ) + ( nLBoost Rload IL ) s
vˆDC (s )
= 2
dˆ '(s ) n CDC RLoad LBoost s 2 + n 2 (CDC RLoad RSeries + LBoost ) s + ( n 2RSeries + RLoad D '2 )
(6.4) ˆ
ˆ
where d '(s ) = 1 − d (s )
Since this model is only valid for small variations of the duty cycle, only a step response of
0.01 will be applied. The step response of these functions then become as shown in figure
6.10. It can be seen that the current has a peak value which is much larger then the steady
state value. The value of this peak is depending on the system values and the step size.
Figure 6.10: Step response after perturbing the duty cycle
Red: Current in boost inductor
Blue: Voltage DC‐link
With a larger value of the DC‐link capacitance the peak value will increase some, and the
duration of the pulse will increase. This pulse will have influence on the speed of the MPPT
tracker, and this has already been considered in the optimization of the MPPT tracker.
Another problem is how the protective circuits reacts, and if the circuit can handle this
overcurrent for the duration of the pulse. This will usually not be a problem when the MPPT
tracker is used since the duty cycle step will be small, but during turn on and during manual
control care must be taken not to overload the circuit. Therefore this type of converter
should always have a charging circuit, and there should be some ramp function or a current
controller should be used during manual control. Appendix 6 DC‐DC Converter Problems
Fundamentals of Grid Connected Photo‐Voltaic Power Electronic Converter Design
164
Another solution to this problem is to use current control of the converter instead of duty
cycle control. This was described in the preliminary project, and will control the current
through the switches instead of the duty cycle. This however will require that the current
through the switches is measured. Appendix 6 DC‐DC Converter Problems