UniPOS Fire Extinguishing Control Panel FS
5200Е
Fire Extinguishing Control Panel
FS5200Е
Instruction Manual
Revision 8/01.17
INSTRUCTION MANUAL
Revision 8/01.17
Page 1 of 63
UniPOS Fire Extinguishing Control Panel FS
5200Е
9.1.
9.2.
9.3.
10.1.
10.2.
10.3.
11.1.
11.2.
11.3.
12.1.
12.2.
12.3.
12.4.
12.4.1.
7.3.
8.1.
8.2.
8.3.
8.4.
5.3.
6.1.
6.2.
6.3.
7.1.
7.2.
4.2.10.
4.2.11.
4.2.12.
4.2.13
4.3.
5.1.
5.2.
4.1.
4.2.
4.2.1.
4.2.2.
4.2.3.
4.2.4.
4.2.5.
4.2.6.
4.2.7.
4.2.8.
4.2.9.
Table of contents
Terminology ...............................................................................................................
Technical Data...........................................................................................................
Contents of Delivery...................................................................................................
Installation and Arrangements....................................................................................
To Mount the Control Panel........................................................................................
Description of Inputs and Outputs. Periphery Devices Assembly .............................
Description and Mounting of Devices to L1, L2 and L3 Inputs...................................
Description and Mounting of Devices to Manual Release Input ................................
Description and Mounting of Devices Mode Select Input ..........................................
Description and Mounting of Devices Hold Input .......................................................
Description and Mounting of Devices On/Off Exting Input .........................................
Description and Mounting of Devices Low Press Input ..............................................
Description and Mounting of Devices Exting Output ..................................................
Description and Mounting of Devices Sounder S1 and Sounder S2 Outputs ............
Description and Mounting of Devices to Outputs OK1, OK and и OK3 Open
Collector Type.............................................................................................................
Description and Mounting of Devices to Rel Fire Output............................................
Description and Mounting of Devices Rel 1
ST
and Rel 2ST Outputs .........................
Description and Mounting of Devices to Rel Fault Output .........................................
Description and Mounting of Devices to RS485 Interface Terminals.........................
Power Supply Connection ..........................................................................................
General Information ..................................................................................................
Access Levels ............................................................................................................
Indications and Buttons for Control.............................................................................
Conditions of the Fire Extinguishing Control Panel.....................................................
Duty Mode ..................................................................................................................
Description..................................................................................................................
Indication ....................................................................................................................
Using the Keypad .......................................................................................................
Fire Condition Stage I.................................................................................................
Description..................................................................................................................
Indication.....................................................................................................................
Using the Keypad .......................................................................................................
Fire Condition Stage II ...............................................................................................
Description.................................................................................................................
Indication ....................................................................................................................
Using the keypad........................................................................................................
Using the Switch for Mode Selection (Automatic/Manual/Disabled)
……...................
Fault Condition............................................................................................................
Description..................................................................................................................
Indication.....................................................................................................................
Using the Keypad .......................................................................................................
Disabled Component ..................................................................................................
Description .................................................................................................................
Indication ....................................................................................................................
Using the Keypad .......................................................................................................
Test Mode ..................................................................................................................
Description..................................................................................................................
Indication.....................................................................................................................
Using the Keypad .......................................................................................................
Information and Control Mode ....................................................................................
Description .................................................................................................................
Indication ....................................................................................................................
Using the Keypad .......................................................................................................
Using the Menus ........................................................................................................
Menu View Faults .......................................................................................................
Instruction Manual
Revision 8/01.17
26
27
30
31
31
31
31
32
32
28
29
29
29
30
30
30
30
20
21
21
21
21
21
21
22
15
16
16
16
16
17
17
18
22
23
23
23
25
26
26
12
13
13
14
14
15
15
8
8
11
12
4
6
8
8
Page 2 of 63
UniPOS
12.4.2.
12.4.3.
12.4.4.
12.4.5.
13.1.
13.2.
13.3.
13.4.
13.4.1.
13.4.2.
13.4.3.
13.4.4.
13.4.5.
13.4.6.
13.4.7.
13.4.8.
Menu View Disables...................................................................................................
Menu View Test .........................................................................................................
Menu Statuses ...........................................................................................................
Menu System Functions .............................................................................................
Setup Mode ................................................................................................................
Description..................................................................................................................
Indication ....................................................................................................................
Using the Keypad .......................................................................................................
Using the Menus ........................................................................................................
Menu Fire Extinguishing Control Panel.......................................................................
Menu
„CAN Parameters”.............................................................................................
Menu Inputs/Outputs ..................................................................................................
Menu Time Extinguishing............................................................................................
Menu Time Evacuation...............................................................................................
Menu Factory Settings................................................................................................
Menu Clear archive.....................................................................................................
Menu new Password...................................................................................................
Extinguishing Control Algorithm..................................................................................
Labour Protection Requirements ...............................................................................
Fire Extinguishing Control Panel Start Up .................................................................
Operation, Storage and Transportation .....................................................................
Warranty .....................................................................................................................
Appendixes ...............................................................................................................
Fire Extinguishing Control Panel FS
5200Е
46
46
48
54
56
56
57
57
33
34
35
36
44
44
45
45
57
57
59
59
59
59
60
Instruction Manual
Revision 8/01.17
Page 3 of 63
UniPOS Fire Extinguishing Control Panel FS
5200Е
Introduction
The fire extinguishing control panel FS5200Е is designated for fire protection, monitoring and control of systems for active extinguishing.
After processing the signals from the automatic fire detectors and/or manual call points the control panel it sends commands to the executive devices for extinguishing, sound-light signalers, air conditioning and ventilation devices, it sends information to a repeater, PC or another intelligent devices.
FS5200Еcould be used in – gas, powder, aerosol, water and other types of systems for active extinguishing.
The fire extinguishing control panel is designed for extinguishing in one zone. It is possible up to
15 zones to be protected when the fire extinguishing control panel is connected in a network via interface RS485 and a repeater FS5200R.
The fire extinguishing control panel could be connected and become a part of the Interactive Fire
Control System IFS7002 /UniPOS production/.
The fire extinguishing control panel
FS5200Е is designed and produced in compliance with standards EN 54-2:1997/
А1:2006/AC: 2009, EN 54-4:1997/A2: 2006/AC: 2009, EN 12094-1: 2003.
Some of its main features and possibilities are:
adjustment of operating modes and parameters of each fire alarm line, output and input via built in keypad;
user oriented menu dialogue for easy and convenient operation;
LCD for visualization of system checkup and set up modes;
LEDs indication for early warning of a break down or extreme conditions;
energy independent archive memory saving the event type, date and time, allowing for detailed analysis of the actions of the authorized personnel and of possible problems in the fire protection process of the area;
user oriented test modes allowing for a total control of the site protected;
built-in serial interface RS485 and CAN for connection to other fire control panels;
compatible to random installation design, within the range of the available fire extinguishing control panels resources.
All these are realizable via fire extinguishing control panel’s keypad and after a detailed examination of the instructions set herewith.
1. Terminology
OUTPUT
– monitored or relay output, programmed by the user to be activated during the different stages of the extinguishing.
EVACUATION TIME
– the time from occurring the situation for extinguishing to the moment of switching on the extinguishing automatics. This time should be enough for the evacuation of the staff from the premises. The evacuation time is user defined for the specific site. The evacuation time is shown on the LCD display and it counts down the remaining time until the release of the extinguishing automatics.
DISABLED LINE
– the fire detecting line is switched off (not power supplied) and it is not monitored for turned out fire detector and a fault condition. This feature is user defined. The indication for a disabled line is common light indication and text messages on the LCD display.
DISABLED OUTPUT
– the output is switched off (the executive device can not be activated) and is not monitored for a fault condition in the monitored outputs. This feature is user defined. The indication for a disabled monitored output is common light indication and text messages on the LCD display.
DISABLE EXTINGUISHING
– condition of the fire extinguishing control panel when regardless the input actions the executive extinguishing device cannot be activated. Disable extinguishing is
Instruction Manual
Revision 8/01.17
Page 4 of 63
UniPOS Fire Extinguishing Control Panel FS
5200Е defined by “on” status of the monitored input “On/Off Exting” (See section 4.2.) or by the secret switch on the front panel. The indication for disable extinguishing is an individual light indication.
HOLD EXTINGUISHING
– condition of the fire extinguishing control panel when the release signal to the executive extinguishing device is delayed. Hold extinguish ing is defined by “on” status of the monitored input
„Hold”. Hold extinguishing could be controlled by a manual button if extra evacuation time is needed and monitoring if the doors of the protected premise are tightly closed.
After the hold signal is cancelled the timer for the evacuation time is started automatically. After the evacuation time expires the extinguishing executive device is switched on. The indication for hold extinguishing is an individual light indication.
GROUNDS
– non-system non-fatal fault condition, due to leakage to a grounded wire.
MONITORED INPUT
– input that monitors the serviceability of the connection wires between the fire extinguishing control panel and the executive devices. Follow the special diagram for connection.
(See section 5.2.).
MONITORED OUTPUT
– a potential output that monitors the serviceability of the connection wires between the fire extinguishing control panel and the executive device. Follow the special diagram for connection. (See section 5.2.).
SHORT CIRCUIT IN A LINE, MONITORED OUTPUT OR MONITORED INPUT
– non-system,
non-fatal fault condition, entered due to registered current value, exceeding a threshold value.
LINE IN TEST
– a line, set in Test condition by the user. The line is switched on (supplied) and reset (the power supply is switched off for 3 s) periodically every 60 s. The events registered in a line in Test condition are not saved in the archive and do not trigger the outputs or the light and sound signaling. The indication for a line in Test condition is a text message in the display field for the respective line.
LOCAL SOUNDER
– a sounder built-in the fire extinguishing control panel.
NON-FATAL FAULT CONDITION
– fault condition that allows the fire extinguishing control panel to continue operation. The non-fatal fault condition is not usually a system fault condition. The indication is common light indication, local sound indication and text messages on the LCD display.
ACCESS LEVEL
– access level to various indications and control functions (See section 5.1).
LOW BATTERY
– non-system fatal fault condition due to full discharge of the backup batteries upon interrupted power supply.
SUPPRESSED OUTPUT
– a monitored or relay output, which should be activated (for the respective Extinguishing stage) but it is switched off manually by the user.
FIRE DETECTING LINE (further in the text only LINE)
– a combination of fire detectors, physically connected by two-wire connection. Maximum 32 fire detectors could be connected in each line.
FIRE CONDITION STAGE I
– phase of Fire condition; upon activation of automatic fire detector only in one line the fire extinguishing control panel enters Fire condition. It continues until the line is manually reset by Reset Alarm. The indication for Fire condition stage 1 is common light indication.
Local sound signaling and text messages on the LCD display.
FIRE CONDITION STAGE II
– phase of Fire condition when active extinguishing procedure is started. The fire extinguishing control panel enters this stage in the event of: а) Fire condition along both fire detecting lines;
Instruction Manual
Revision 8/01.17
Page 5 of 63
UniPOS Fire Extinguishing Control Panel FS
5200Е
b) Manual button release for forced extinguishing.
The indication for Fire condition stage 1 is common light indication. Local sound signaling and text messages on the LCD display.
INTERRUPTED LINE, MONITORED OUTPUT OR MONITORED INPUT
– non-system non-fatal fault condition entered when parameters lower than the threshold value are registered.
RELAY OUTPUT
– a relay, potential-free switching outputs provided for controlling external executive devices.
MANUAL RELEASE
– condition entered by the fire extinguishing control panel in the event of
Fire condition stage II, regardless the status of the Fire detecting lines. The manual release is defined by “on” status of the monitored input „Manual Release”.
MANUAL MODE
– condition when the fire extinguishing control panel could release the extinguishing devices only by manual release command.
The manual mode is defined by “on” status of the monitored input
„Mode Select”. The mode indication is an individual light indication.
SYSTEM FAULT CONDITION
– fault condition due to a fault in the fire extinguishing control panel (system’s) component panel. The system fault condition could be fatal or non-fatal. The indication is common light indication, local sound indication and text messages on the LCD display.
REMOVED FIRE DETECTOR /FD/
– non-system non-fatal fault condition entered when a removed fire detector in a line is registered. In order this function to be utilized follow the special diagram for connection (See section 5.2.).
LINE STATUS, MONITORED OUTPUT OR MONITORED INPUT
– the current status of a line,
monitored output or input: duty mode; fire condition (only for the fire detecting lines); fault condition
(specifying the type of the fault condition).
FATAL FAULT CONDITION
– fault condition that prevents the fire extinguishing control panel, or the part of it related to the communication with the user, from continuing its operation. The fatal fault condition is usually a system one, except Law Battery fault condition. The indication is common light indication, local sound indication and text messages on the LCD display.
2. Technical data
Fire detecting lines
For extinguishing control
Without extinguishing control
Maximum number of fire detectors in a line
Type of the connecting line
Maximum resistance of a loop
Output resistance of the line
- 2
- 1
- 32
- two-wire
- 100
- 164
2.1. Current thresholds in a line per default parameters for:
0÷3mA*
3÷12mA*
12÷60mA*
>80mA
- interruption
- duty mode
- fire condition
- short circuit
* It is possible the current in the lines for interruption, duty mode and fire condition to be adjusted (13.4.2.1.).
2.2. Monitored outputs for control the fire extinguishing control panel performance:
Instruction Manual
Revision 8/01.17
Page 6 of 63
UniPOS Fire Extinguishing Control Panel FS
5200Е
Type
2.3. Monitored outputs for the sound-light indication
Type
Electrical characteristics
2.4. Monitored output for the extinguishing devices
Type
Electrical characteristics
2.5. Relay outputs for common purpose
Type
Electrical characteristics
2.6. Relay output for fault condition
Type
Electrical characteristics
- balanced
- potential relay
-
-
(24±3)V/0.5 A
- potential relay
(24±3)V/1.5A
- potential free, switching
- 3A/125VAC; 3A/30VDC
- potential free, switching
- 3A/125VAC; 3A/30VDC
2.7. Relay output for fire alarm
Type
Electrical characteristics
2.9. Indications of registered events
Light indication
Text message
Sound signaling
2.10. Power supply
- potential free, switching
- 3A/125VAC; 3A/30VDC
2.8. Performance characteristics
Control over the lines, the monitored inputs and outputs for fault condition (short circuit and interruption) and automatic reset
Control over the lines for removed fire detector and automatic reset
Ability to set the evacuation time
Ability to set the time when the extinguishing executive device is switched on
Built-in sounder for fire alarm first stage
– one tonal, discontinuous, can be switched off
Built-in sounder for fire alarm second stage
– one tonal, continuous, can be switched off
Built-in sounder for fault condition
– one tonal, discontinuous, can be switched off
Built-in real time clock
Set of test modes and options for adjustment:
Setting the clock;
Check ups on light and sound indications;
Test of the fire detecting lines;
Adjustment of outputs and integrated external devices;
Current measurement in the fire detecting lines;
Programming of parameters and modes of operation;
Remote programming of the parameters from distant operator control point;
Energy independent archive of registered events by the fire extinguishing control panel with the events type, date and hour
– up to 100 events;
Interfaces for communication with external devices - RS-485 and CAN 2.0
- LED
- LED display -
4 lines 20 characters per line,
Cyrillic, backlit
- built-in sounder
2.10.1. Mains
voltage
frequency
2.10.2. Back up batteries
battery type
number of batteries
connection
- 220/230V
- 50/60Hz
- led, gel electrolyte
- 2 pcs
- serial connection
Instruction Manual
Revision 8/01.17
Page 7 of 63
UniPOS Fire Extinguishing Control Panel FS
5200Е
nominal voltage of the back up battery
nominal capacity C
20
extreme discharge voltage
charge voltage
2.10.3. Consumption on back up batteries supply
At 24V
2.10.4. Power supply to external devices
Voltage
Maximum current value (including current of monitored outputs )
2.11. Dimensions
Overall dimensions
2.12. Weight
weight (batteries not included), maximum
- 2x12V
- (7-12)Ah
- 21V
- 28,2V
- < 120mA
-
(24±3)V
- 2,5
-
А
450х355х115mm
- 6,6kg
3. Contents of delivery
3.1. Fire extinguishing control panel
Fire detecting control panel FS5200
Е
Resistors 3,0k
/ 0,25W
Resistors 1,5k
/ 0,25W
Diode 1N4004
Jumper for the back up batteries
Fuse 4A
CD (Instruction manual,
Operator’s manual)
Packing
4. Installation and arrangements
- 1 pc.
- 11 pcs.
- 5 pcs.
- 1 pc.
- 1 pc.
- 2 pcs.
- 1 pc.
- 1 pc.
When fire detectors and periphery devices are integrated in the fire extinguishing control panel, avoid arranging wires in closed loops; it will reduce the control panel’s resistance to electro magnetic interferences.
4.1. To mount the control panel
unpack the control panel;
put the dowels on the determined places for fixing the control panel;
fasten the control panel to the dowels through the three holes provided on the chassis.
4.2. Description of inputs and outputs. Periphery devices assembly to the control panel.
All connections are to be made by means of terminals, mounted on the printed circuit board. Be advised, that the total consumption of the voltage powering the external devices (terminal “+ 28V”) plus the consumption of the monitored outputs shall not exceed 2.5A in heavy duty mode.
“L1”, “L2” – Inputs for switching automatic Fire detectors. In Fire condition an extinguishing procedure starts along both lines according to set up algorithm.
“L3” – Fire detecting line input.
“Manual Release” – Input with line status monitoring. The input sends a signal to the control panel from a manual button to start the extinguishing procedure.
“Mode Select” - Input with line status monitoring. The input sends a signal to the control panel from a switch for the operating mode. The modes are Manual-Automatic and Manual.
“Hold” - Input with line status monitoring. The input sends a signal to the control panel
Instruction Manual
Revision 8/01.17
Page 8 of 63
UniPOS Fire Extinguishing Control Panel FS
5200Е from a manual button or controlled contact for holding (delaying) the extinguishing procedure.
“On/Off Exting” - Input with line status monitoring. The input sends a signal to the control panel from a switch for disabling the extinguishing procedure.
“Low Press” - Input with line status monitoring. The input sends a signal to the control panel from pressostat contact, balance or other device to show the extinguishing agents draining.
“GND” – Terminal for sending GND potential to the periphery devices.
“Еxting” – Active level output with line status monitoring. The output switches the extinguishing automation valves on.
“S2 Sounder” – Active level output with line status monitoring. The output switches the sound-light indication on in Fire condition stage II.
“S1 Sounder” – Active level output with line status monitoring. The output switches the sound-light indication on in Fire condition stage I.
“Rele Fire” – Output, relay, potential free, the line status is not monitored. The output controls the devices in Fire condition of the control panel, registered by the fire detecting lines.
“Rel Fault” – Output, relay, potential free, the line status is not monitored. The output controls the devices in Fault condition of the control panel.
“+28V” – Three terminals for supplying 28V voltage to the periphery devices as well as the positive potential of the open collectors OK1, OK2 and OK3.
“OK1” – Output open collector /in active status it supplies GND potential, in non-active status it has potential +28V via resistor 47k/0.125W/. The output controls relays, LEDs and other devices, with total consumption not exceeding 100mA. The output is active when the control panel has registered extinguishing reagent leakage.
“OK2” – Output open collector /in active status it supplies GND potential, in non-active status it has potential +28V via resistor 47k/0.125W/. The output controls relays, LEDs and other devices, with total consumption not exceeding 100mA. The output is active when the control panel is in Disable Extinguishing Mode.
“OK3” – Output open collector /in active status it supplies GND potential, in non-active status it has potential +28V via resistor 1k/0.125W/. The output controls relays, LEDs and other devices, with total consumption not exceeding 100mA. The output is active when the control panel is in manual Mode.
“Rel 2ST” – Output, relay, potential free, the line status is not monitored. The output controls the devices in Fire condition stage II of the control panel.
“Rel 1ST” – Output, relay, potential free, the line status is not monitored. The output controls the devices in Fire condition stage I of the control panel.
“CAN” – Terminals to connect the two-wire line of CAN interface. The connection with the
Interactive system IFS7002 /production of UniPOS LTD/ is executed via this interface. A jumper is provided that shunts the line by 120 ohms. It is needed if the fire extinguishing control panel is the final point in the interface line. The interface requires resistors 120 ohms to be mounted in both ends of the line.
“RS 485” – Terminals to connect the two-wire line of RS 485 interface. The connection with a repeater, PC and other devices realized by exchange protocol - UniProtocol
/FS5200E interface/ is executed via this interface. As the case with CAN interface, a jumper is provided here too with the same functions.
“┴” – Terminal to connect a third wire /screen/ of the interfaces cable.
Instruction Manual
Revision 8/01.17
Page 9 of 63
UniPOS
Jump (RS485)
Jump (CAN)
Jump Rel 1ST
Jump Rel 2ST
Jump relay Fire
Instruction Manual
Revision 8/01.17
Fire Extinguishing Control Panel FS
5200Е
Rel
1ST
Rel
2ST
OK1
+28V
OK2
+28V
OK3
+28V
Interface CAN
(join to system IFS7002)
Interface RS 485
(repeater, PC and other devices)
Relay output in condition Fire Alarm Phase 1
Relay output in condition Fire Alarm Phase 2
Output Open Collector
– Active in case of extinguisher leakage (+28V)
Output Open Collector
– Active in case of extinguishind disable (+28V)
Output Open Collector
– Active in manual mode (+28V)
Relay output in Fault Alarm condition
1N4004
Relay output in Fire condition
Sounder Fire Alarm Phase 1
(28V/0,5A)
Sounder Fire Alarm Phase 2
(28V/0,5A)
Device Extinguishing
(28V/1,5A)
Switch for monitoring extinguisher leakage
Switch for extinguishing disable
Button for extinguishing delay
Switch mode manual/manual-automatic
Buttons manual extinguishing activation
Fire Alarm Line 1
Fire Alarm Line 2
Fire Alarm Line 3
Drawing1
Page 10 of 63
UniPOS Fire Extinguishing Control Panel FS
5200Е
4.2.1. Description and mounting of devices to L1, L2 and L3 inputs
Connect a two-wire line at L1, L2 and L3 inputs for connection with the Fire detectors. The line total resistance shall not exceed 100
. The recommended wire section depending on the lines length is:
To 500 m
To 1000 m
To 1500 m
-cable
2 х 0.5 mm
-cable
2 х 1.0 mm
-cable
2 х.1.5 mm
2
2
2
It is recommended to make a check with a multicet before connecting the fire detecting line to the fire extinguishing control panel. If the line is installed correctly (with mounted final resistor 3k
Ω /
0.25W) between the plus and minus of the cable entering the fire extinguishing control panel the measured resistance should be 3k
Ω (+/-10%). Also when measuring both wires to ground the multicet should show no connection or leakage.
Make the connection to the terminals
– “+ Lx -” (where “x” is the line number). Observe the shown polarity (Drawing 2).
First detector
Last detector
1N5819*
FS5200E
1N5819*
+OUT
FD80xx
+IN
-IN/OUT RI/KL -
5
2
FD30xx
4
1
3k/0.25W
* Diode 1N5819 or similar
Drawing 2
Use automatic fire detectors FD3000 or FD8000 series or other compatible automatic fire detectors. Mount resistor 3 k
Ω / 0.25W on the last fire detector in the line.
Mount diodes, for example 1N5819 or similar in the shown direction if you are to use the fire extinguishing control panel function to register Fault condition
– removed fire detector.
Maximum 32 fire detectors could be mounted to one line regardless of their type.
When mounting the fire detectors take into consideration the specific technical characteristics of the fire detector with the fire extinguishing control panel parameters for the current threshold in the different conditions. Change the current threshold from Set up menu.
Current thresholds in a line with default parameters for the conditions:
0÷3mA*
- interruption
3÷12mA*
12÷80mA*
>80mA
- duty mode
- fire condition
- short circuit
Mount fire detectors on Lines 1 and 2 in the premise where the extinguishing will be performed.
The first and the second line are in a logical dependence „I”; the fire extinguishing control panel enters
Fire condition stage II if only both lines are activated and the extinguishing algorithm is possible to be executed.
Line 3 is only Fire detecting and it serves for fire protection of the adjoining premises to the extinguished zone. When this line is activated it switches on the outputs for Fire condition stage I as well as the common output for Fire condition. This line is not included in the extinguishing algorithm logic. Line 3 can be assumed as a standard line of a Fire control panel.
Instruction Manual
Revision 8/01.17
Page 11 of 63
UniPOS Fire Extinguishing Control Panel FS
5200Е
4.2.2. Description and mounting of devices to Manual Release input
Connect a two-wire line to the Manual Release input for connection with the manual release buttons for extinguishing activation. It is possible to mount maximum three buttons. The line is balanced and it is monitored for interruption and short circuit. Install resistors to the button terminals as shown in the connecting diagrams to monitor the condition. Install resistor 3k to the last button if 2 or 3 buttons are mounted (Drawing 3).
Connecting diagram with 1 button
Button for manual activation of the extinguishing
FS5200E
3k/
0.25W
1.5k/
0.25W
Connecting diagram with 2 buttons
Button 1 Button 2
FS5200E
1.5k/
0.25W
3k/
0.25W
1.5k/
0.25W
Connecting diagram with 3 buttons
Button 1 Button2 Button 3
FS5200E
1.5k/
0.25W
1.5k/
0.25W
3k/
0.25W
1.5k/
0.25W
Drawing 3
When the contact is closed the fire extinguishing control panel accepts the button to be active.
4.2.3. Description and mounting of devices to Mode Select input
Connect a two-wire line to the Mode Select input for connection with a switch to select the fire extinguishing control panel mode
– Manual-Automatic or Manual. The line is balanced and it is monitored for interruption and short circuit. Install the two resistors to the switch terminals as shown in the connecting diagram to monitor the condition.
When the contact is closed the fire extinguishing control panel accepts Manual Mode; when it is opened
– Manual-Automatic Mode. Output Open collector type is activated in Manual Mode. That output could be used as switch indication, if this option is provided.
Instruction Manual
Revision 8/01.17
Page 12 of 63
UniPOS Fire Extinguishing Control Panel FS
5200Е
Switch modes
Manual/Manual-automatic
FS5200E
1.5k/
0.25W
4.2.4. Description and mounting of devices to Hold input
Connect a two-wire line to the Hold input for connection with a switch to activate hold extinguishing function. The line is balanced and it is monitored for interruption and short circuit. Install the two resistors to the switch terminals as shown in the connecting diagram to monitor the condition
(Drawing 4).
Switch
Extinguishing delay
FS5200E
3k/
0.25W
1.5k/
0.25W
Drawing 4
Set up the input active status: OPEN or CLOSED contact from menu System functions > Set up
> Input/Outputs > Hold input.
Attention! The active status of the default parameters is OPEN contact of the switch in order the fire extinguishing control panel to accept Hold Extinguishing function.
4.2.5. Description and mounting of devices to On/Off Exting input
Connect a two-wire line to the On/Off Exting input for connection with a switch to disable extinguishing. The line is balanced and it is monitored for interruption and short circuit. Install the two resistors to the switch terminals as shown in the connecting diagram to monitor the condition
(Drawing 5).
Switch
Extinguishing disable
FS5200E
3k/
0.25W
1.5k/
0.25W
When the contact is closed the fire extinguishing control panel accepts Disable Extinguishing.
Output Open collector type is activated in Disable Extinguishing. That output could be used as switch indication, if this option is provided.
Drawing 5
Instruction Manual
Revision 8/01.17
Page 13 of 63
UniPOS Fire Extinguishing Control Panel FS
5200Е
4.2.6. Description and mounting of devices to Low Press input
Connect a two-wire line to the Low Press. input for connection with a pressostat contact, balance or other devices registering a Fault condition in the extinguishing installation. The line is balanced and it is monitored for interruption and short circuit. Install the two resistors to the switch terminals as shown in the connecting diagram to monitor the condition (Drawing 6).
Pressure
FS5200E
3k/
0.25W
1.5k/
0.25W
Drawing 6
Set up the input active status: OPEN or CLOSED contact from menu System functions > Set
up > Input/Outputs > Low Press input.
Attention! The active status of the default parameters is OPEN contact of the switch in order the fire extinguishing control panel to accept the function Leaked extinguishing agent or Fault condition.
4.2.7. Description and mounting of devices to
“Exting” output
Connect a two-wire line to the Exting output for connection with a magnetic valve or other device to activate the extinguishing automation. The line is balanced and it is monitored for interruption and short circuit. Install a diode 1N4004 or similar to the executive device terminals in the direction as shown in the connecting diagram as the valve winding resistance shall be in the range: 30
Ω ÷ 3kΩ.
(Drawing 7).
Install a parallel resistor 3k
Ω / 0.25W and a serial diode 1N5401 on the line if the winding resistance is less than 30
Ω (Drawing 8).
Connecting diagram if the winding valve active resistance is from 30
Ω to 3к Ω
Electromagnetic valve
FS5200E
V
1N4004
Rv - 30 Ohms up to 3 k
Drawing 7
Connecting diagram if the winding valve active resistance is less than 30
Ω
Instruction Manual
Revision 8/01.17
Page 14 of 63
UniPOS Fire Extinguishing Control Panel FS
5200Е
Electromagnetic valve
FS5200E
3k/
0.25W
1N5401
V
Rv - < 30 Ohms
Drawing 8
Upon the output activation the supplied voltage
(24±3)V is with load-carrying capacity of 1.5А.
The time for output activation could be set from 2 to 255 seconds from menu System functions >
Set up > Extinguishing time and it depends on the type of the used executive device. The default setting is 10 seconds.
4.2.8. Description and mounting of devices to Sounder S1 and Sounder S2 outputs
Connect a two-wire line to the Sounder output for connection with sound and light signaling devices. The line is balanced and it is monitored for interruption and short circuit. Install a resistor
3k
Ω/0.25W to the signaling device terminals to monitor the condition (Drawing 9).
FS5200E
3k/
0.25W
Drawing 9
Upon the outputs activation the supplied voltage (24±3)V is with load-carrying capacity of 0.5А.
The outputs are activated for Fire condition stage I and Fire condition stage II, respectively.
The fire extinguishing control panel provides the option for Sounder S1 output disable from menu
System functions > Disables > Disable S1 output .
4.2.9. Description and mounting of devices to outputs OK1, OK2 and OK3 open collector type
OKx outputs send a signal to relays, LEDs and other devices to follow and monitor the fire extinguishing control panel condition. The outputs are not monitored for the line status.
2 8V
+28V
4 7k
OKx
GND
Drawing 10
Upon activation of the outputs GND potential is supplied with loadcarrying capacity of 0.1А.
The internal diagram of output Open collector type is presented on the drawing (Drawing 10).
4.2.10. Description and mounting of devices to Rel Fire output
Rel Fire is a potential free, relay output. The logic of the contact - Normally Open or Normally
Closed could be adjusted by means of a jumper. The output is not monitored. The output is activated in Fire condition along one or both fire detecting lines.
Instruction Manual
Revision 8/01.17
Page 15 of 63
UniPOS Fire Extinguishing Control Panel FS
5200Е
4.2.11. Description and mounting of devices to Rel 1
ST
and Rel 2
ND
outputs
Rel 1
ST
and Rel 2
ND
are potential free, relay outputs. The logic of the contact - Normally Open or
Normally Closed could be adjusted by means of a jumper. The outputs are not monitored. The outputs are activated in Fire condition stage I and Fire condition stage II, respectively. The fire extinguishing control panel provides the option to disable the activation of Rel 1
ST
and Rel 2
ND
outputs from menu System functions > Disables > Disable Rel 1ST / Disable Rel 2ND.
4.2.12. Description and mounting of devices to Rel Fault output
Rel Fault is a potential free, relay output, as both relay contacts are possible Normally Open or
Normally Closed. The output is not monitored.
4.2.13. Description and mounting of devices to RS485 interface terminals
RS485 interface is designed to transmit information and to receive commands from FS5200R repeater. The following connection configurations are possible:
One fire extinguishing control panel and one repeater
One fire extinguishing control panel and up to 6 repeaters
Up to 15 fire extinguishing control panels and 1 repeater
Up to 6 repeaters and up to 10 fire extinguishing control panels (If less than 6 repeaters are installed they could be substituted by fire extinguishing control panels, i.e. configuration of 3 repeaters and 13 fire extinguishing control panels, etc.)
FS5200R repeater receives information from all fire extinguishing control panels as it indicates the occurred events by sound signaling, light indication and text messages. It is also possible a remote fire extinguishing control panel to be reset.
RS485 interface could be used also for communication with other intelligent devices and PCs.
The connection between the devices along RS485 is parallel connection. Observe the requirement potential A and B not to be crossed. The maximum distance between the end devices is
1000 meters. Jumper to shunt the line by 120 ohms has to be installed on the first and the last device regardless the line length. On all other devices the jumper has to be removed (Drawing 11).
End device
FS5200x
FS5200x
End device
FS5200x
120
120 120
J
А В
J
А В
RS485
RS485
А В
RS485
RS485
А В
RS485
А В
120 120
FS5200x FS5200x
Drawing 11
4.3. Power supply connection
Connect a feeding cable to the terminal with mains fuse, observing the following positions
(Appendix 3):
P
– power wire “Phase”;
Instruction Manual
Revision 8/01.17
Page 16 of 63
UniPOS Fire Extinguishing Control Panel FS
5200Е
N
– power wire “Null”;
Ground - safety ground wire.
The cable shall be double insulated and of 0,5mm
2
section for the power supply wires, and of
1,5mm
2
section for the safety ground wire.
The other end of the feeding cable is connected to the mains power supply by means of junction box.
The mains power supply of the fire control panel shall be in a separate loop.
5. General information
5.1. Access levels
4 levels of access to the variable indications and control functions of FS5200
Е are available.
5.1.1. Access level 1
All persons who would presumably find out and react to alarm upon fire condition or fault condition have access to level 1.
The following actions are accessible:
Displaying suppressed messages for Fire condition stage I, Fire Condition stage II, Fault condition, Disabled components;
Forced proceeding from phase Fire condition stage I to phase Fire condition stage II ;
Suppressing the local sounder;
Displaying the status of the lines and the monitored outputs (see section 12.5);
All light indicators are visible.
5.1.2. Access level 2
The personnel in charge of the fire protection have access to level 2; they shall be trained and authorized to operate the fire control panel in the following conditions:
Duty Mode;
Fire condition stage I;
Fire condition stage II;
Fault condition;
Disabled component;
Information and adjustment.
To enter Access level 2, turn the key on the front panel of the fire extinguishing control panel into position .
The following features of the fire extinguishing control panel are accessible:
All features accessible at Level 1;
Switching off the outputs, activated upon fire condition;
Exit of Fire condition;
System functions of the fire extinguishing control panel except entering Set up Mode
(see section Error! Reference source not found.).
5.1.3. Access level 3
Accessible for personnel trained and authorized for:
Reconfiguration of specific data
– of the protected site or of the fire extinguishing control panel
– saved in the memory;
Maintenance of the fire control panel.
This level has two sublevels of access - 3A and 3B.
Level 3, sublevel 3A, is accessed through a password entered at Access level 2. At this sublevel the functions for reconfiguration of specific data for the protected site or the fire extinguishing control panel are accessible.
Level 3, sublevel 3B is accessed when the fire extinguishing control panel is opened. The following features are accessible:
Replacing a burnt fuse;
Adding, removing or replacing a module;
Connecting fire detecting lines and executive devices.
Instruction Manual
Revision 8/01.17
Page 17 of 63
UniPOS Fire Extinguishing Control Panel FS
5200Е
5.1.4. Access Level 4
Accessible for personnel trained and authorized by the Producer to repair the fire extinguishing control panel and to modify the software.
Special means are required to enter this level.
5.2. Indications and buttons for control
Table 1 gives detail description of the indications for each status, Table 2 presents the basic function of the control buttons. Appendix 1 shows the front panel of FS5200 with the indications and buttons for control.
Table 1
Conditions of the fire extinguishing control panel
All conditions -
The fire extinguishing control panel is power supplied
Fire condition
Fire condition
Fire condition
– Fire condition Stage I and Stage II
– Fire condition Stage I
– Fire condition Stage II
Manual Mode
– a signal for manual mode of extinguishing control is given
Manual Mode
– a signal for manual mode of extinguishing control is given
Disabled extinguishing
– a signal disabling the extinguishing is given
Extinguishing held
– a signal holding the extinguishing is given
Fire Condition and Fault Condition
– the sound indication is suppressed
Fire condition Stage I -
The fire condition stage I outputs are suppressed
Fault condition - All faults except for Battery Low
Fault condition
– System Error and new
Configuration
Fault condition
– Fault in mains supply or backup battery
Fault condition
Fault condition
– fault condition in monitored line
– fault condition Low pressure in the extinguishing installation
Disabled component -
Disabled line or monitored output
Fire condition Stage I
Fire condition Stage II
Indication
Indicator Power Supply
– continuous green light
Individual indicators for
Fire condition in the fire detecting lines
Common indicator Fire condition
Stage I
– continuous red light
Common indicator Fire condition
Stage II
– flashing red light during the evacuation time and continuous red light after the automated extinguishing is switched on
Indicator Manual Mode - continuous yellow light
Indicator Manual-Automatic Mode - continuous yellow light
Indicator Disabled Extinguishing - continuous yellow light
Indicator Extinguishing Held - - continuous yellow light
Indicator Stop Alarm - continuous red light
Indicator Suppressed Outputs - continuous red light
Common indicator Fault Condition
- continuous yellow light
Indicator System Error - continuous yellow light
Indicator mains Supply Fault - continuous yellow light
Indicator Monitored Line Fault - continuous yellow light
Indicator Low Pressure Fault - continuous yellow light
Indicator Disabled Component
– continuous yellow light
Local sounder
– discontinuous signal: 4 sound impulses for 1 s, followed by 1 s break
Local sounder
– continuous signal
Instruction Manual
Revision 8/01.17
Page 18 of 63
UniPOS Fire Extinguishing Control Panel FS
5200Е
Conditions of the fire extinguishing control panel
Fault condition - All faults except for Battery Low
Fault condition -
Low battery
Indication
Local sounder
– discontinuous signal: 1 s sound, followed by 1 s break
Local sounder
– discontinuous signal: 1 s sound, followed by 3 s break
Instruction Manual
Revision 8/01.17
Page 19 of 63
UniPOS Fire Extinguishing Control Panel FS
5200Е
Table 2
Means of control
Condition of the fire extinguishing control panel
Access level operation
Level 1
Status
Access level 2 key
Level 2
Status
Button Line Reset
Fire condition Level 2
Output from Fire Condition stage I or Fire condition stage II initiated on the display
Button
Outputs
Fire condition, phase
Fire condition Stage I
Fire condition, phase
Fire condition Stage II
Level 2
Level 2
- if outcomes for Fire condition Stage I are activated
– to suppress them;
- if outcomes for Fire condition Stage I are suppressed
– to activate them
- If the common output for fire condition is activated
– to suppress it;
- if there is no activated common output for fire condition
– to activate it
Button Alarm
Button Menu
Button Down
Button Up
Fire condition Stage I or Stage II and Fault condition*
Level 1 To suppress/activate the local sounder
Duty Mode, Fire condition, Fault condition*, Test and
Disabled component
Information and
Control Mode
Set up Mode
Levels 1 and 2
To enter Information and Control Mode
- To enter the selected menu;
- To execute the selected command;
- To save the modified parameter
Fire condition
Levels 1 and 2
To show on the display the next message for fire condition
Information and
Control Mode
Set up Mode
Levels 1 and 2
Level
3А
- To show on the display the next element from the menu;
- To move the cursor;
- To modify the selected parameter
Fire Condition
Information and
Control Mode
Set up Mode
Levels 1 and 2
Level
3А
Levels 1 and 2
Levels 1 and 2
Level
3А
To show on the display the previous message for fire condition
- To show on the display the previous element from the menu;
- To modify the selected parameter
Button Cancel
Information and
Control Mode
Levels 1 and 2
- To exit a function without saving changes in the parameter; the command will not be
Set up Mode
Level
3А executed;
- To exit the current menu and to move to an upper hierarchy menu
* Not operating in Fault condition (fatal fault condition except New Configuration).
5.3. Conditions of the Fire Extinguishing Control Panel
The fire extinguishing control panel FS5200
Е monitors the fire detecting lines and the monitored outputs as it scans consecutively their status. Depending on the current the fire extinguishing control panel could be in Duty Mode, in Fire condition or Fault condition (short circuit or interruption).
Depending on the measured parameters the inputs could be in Fault condition (short circuit or
Instruction Manual
Revision 8/01.17
Page 20 of 63
UniPOS Fire Extinguishing Control Panel FS
5200Е interruption) or active status. Simultaneously the monitored outputs are followed constantly for in Fault condition (short circuit or interruption).
The fire extinguishing control panel FS5200
Е operates in eight main conditions: Duty Mode, Fire condition Stage I, Fire condition Stage II, Fault Condition, Disabled component, Test Mode,
Information and Control Mode and Set up Mode.
At any time the fire extinguishing control panel could be in each one of these conditions or in random combination of the conditions: Fire condition Stage I, Fire condition Stage II, Fault Condition,
Disabled component, Test Mode, Information and Control Mode.
Duty Mode, Set up Mode and Remote Control cannot be combined with another condition:
the fire extinguishing control panel enters Duty Mode when it is not in any of the other conditions;
to enter Set up Mode and Remote Control the fire extinguishing control panel has to exit the other conditions.
6. Duty Mode
6.1. Description
The fire extinguishing control panel is in Duty Mode, when it is not in any other of the rest eight possible conditions.
6.2. Indication
6.2.1. LED and sound indication
In Duty Mode only the green LED indicator is activated (Power supply) and the yellow indicator (Manual Mode
– activated if only the fire extinguishing control panel is in Manual
Mode. The local sounder is off.
6.2.2. Text message
The display is divided into panels. The last line shows the condition of both Fire detecting lines that shall be in Protection status. The display also shows the message Protection and the current astronomic time:
1 2 3
6.3. Using the keypad
The only accessible button in Duty Mode is enters Information and Control Mode (p.12).
7. Fire Condition Stage I
(Menu). Press it and the fire control panel
7.1. Description
The fire extinguishing control panel enters Fire condition phase Fire condition Stage I, when
- An automatic fire detector is activated only along one of the Fire detecting lines;
Instruction Manual
Revision 8/01.17
Page 21 of 63
UniPOS Fire Extinguishing Control Panel FS
5200Е
- An automatic fire detector is activated along the first or the second or the third line
at Access level 2 To exit this condition press button
7.2. Indication
7.2.1. LED and sound indication
In this condition:
- The indicator
- The indicator
(Power Supply) illuminates in green light;
(Fire condition Stage I) illuminates in red light;
- The indicator of the respective line in Fire condition illuminates in red light;
- If the outputs for phase Fire condition Stage I are suppressed by button
LED indicator of the button illuminates in continuous red light.
- If the sound indication is suppressed by button illuminates in continues red light.
(Outputs), the
(Alarm) the LED indicator of the button
- The indicator (Manual Mode) or the indicator in yellow light depending on the selected mode of operation.
The local sounder produces discontinuous signal.
(Manual-Automatic Mode) illuminates
7.2.2. Text message
In this condition the display is divided into two text fields. The top one shows the condition of the control panel, the bottom one
– the condition of the lines.
Example: Fire condition is registered along the first line. The indicator of line 1 and the indicator for Fire condition Stage I illuminate in red light. The text message shows the Fire condition stage and the line in which the fire extinguishing control panel is in
Fire condition.
1 2 3
Potential free relays Rele 1St and Rele Fire are activated. Voltage 28V DC is supplied to the sounder output S1.
Button
(Alarm)
7.3. Using the keypad
Button Access level
all Press it to:
-
-
Operation
suppress the local sounder; activate the local sounder if the fire extinguishing control panel is in Fire condition
Stage I or Fault condition and the local sounder has been suppressed by previous pressing of the same button.
Additional information
The
The button reversive i.e. press it once to change the current condition alternatively
– suppressed or activated local sounder. The
LED indicator illuminates if the active condition of the local sounder is suppressed. local activated again:
- when operation sounder the is is fire
Instruction Manual
Revision 8/01.17
Page 22 of 63
UniPOS Fire Extinguishing Control Panel FS
5200Е
Button
(Outputs)
Button
(Line Reset)
2, 3 and
4
2, 3 and
4 all extinguishing control panel to exit
Fire condition Stage I and to reset the line that was in Fire condition
(the power supply is switched off for
3s).
Press the button to:
suppress the outputs activated for phase Fire condition Stage I
to activate the suppressed outputs, if any extinguishing panel enters control
Fire condition Stage II;
- upon Fault condition.
Access level 2 is required to for operation with this button. The key on the front panel should be
Press it to force the fire
Press it to enter Information and Control Mode. in position . The button operation is reversive i.e. press it once to change the current condition alternatively
– suppressed or activated outputs.
The LED indicator illuminates if the active condition is suppressed outputs.
Access level 2 is required to for operation with this button. The key on the front panel should be in position .
Button
(Menu)
Button
(Cancel) all
8. Fire Condition Stage II
Press it to exit Information and
Control Mode. The main screen for the current status Fire condition
Stage I is visualized. of:
8.1. Description
The fire extinguishing control panel enters Fire condition phase Fire condition Stage II, in the case а) fire condition along both fire detecting lines; б) manual button activation for forced extinguishing.
In this phase the active extinguishing procedure is initiated.
In phase Fire Condition Stage II the following steps are formed connected with the algorithm of the extinguishing procedure:
Evacuation time;
Activation of the devices to Release the extinguishing mixture
8.2. Indication
8.2.1. LED and sound indication
In Fire Condition Stage II and the fire extinguishing control panel in the evacuation step the LED indicator illuminates in red flashing light (Fire Stage II).
Instruction Manual
Revision 8/01.17
Page 23 of 63
UniPOS Fire Extinguishing Control Panel FS
5200Е
In Fire Condition Stage II and expired evacuation time the fire extinguishing control panel activates the extinguishing devices and the LED indicator continuous light.
(Fire Stage II) illuminates in red
The indicator (Manual Mode) or the indicator yellow light depending on the selected mode of operation.
(Manual-Automatic Mode) illuminates in
The local sounder produces continuous signal. If the sound signaling is suppressed by button
(Alarm), the LED indicator of the button illuminates in continuous red light.
8.2.2. Text messages during the evacuation step and fire along both lines.
The display shows:
The message EVACUATION and the remaining time for the activation of the extinguishing devices
message FIRE STAGE 2 and information for the current status of the lines:
Example: Fire condition along line
1 and line 2. The fire extinguishing control panel is in evacuation phase. The indicator for Fire condition Stage II illuminates in
1 2 3
flashing red light. The individual indicators for line 1 and line 2 are
illuminated too.
Text message for the phase of fire alarm, the remaining time for activation of the extinguishing devices and the current status of the lines is visualized on the display. The local sounder produces continuous signal. Potential free relays Rele 2St and Rele Fire are activated. Voltage 28V DC is supplied to the sounder output S2.
8.2.3. Text messages during the evacuation step and manual button activation.
The display shows:
The message EVACUATION and the remaining time for the activation of the extinguishing devices
message FIRE STAGE 2
Message showing manual activation and information for the current status of the lines
1 2 3
8.2.4. Text messages when the extinguishing device is activated.
Instruction Manual
Revision 8/01.17
Page 24 of 63
UniPOS Fire Extinguishing Control Panel FS
5200Е
The display shows:
The message ATTENTION
GAS! and EXTINGUISHING ON indicating that the extinguishing agent is released.
Information for the current status of the lines:
This indication could be suppressed by the screens in
Fire condition. The suppressed messages could be displayed in
Information and Control Mode.
1 2 3
Example: Fire condition along line 1 and line 2. The fire extinguishing control panel is in phase to start extinguishing procedure. The indicator for Fire condition Stage II illuminates in continuous red light. The individual indicators for line 1 and line 2 are illuminated too. The display shows warning messages and the condition of the fire detecting lines. The local sounder produces continuous signal.
Potential free relays Rele 2St and Rele Fire are activated. Voltage 28V DC is supplied to the outputs
S2 and Exting. .
Note: The entry of the fire extinguishing control panel in Fire condition along a new line (e.g. the
3 rd
one) is indicated by the standard sound and light indication and text messages.
8.3. Using the keypad
Button Access level
Operation Additional information
Button
(Alarm) all Press it to:
- suppress the local sounder;
- activate the local sounder if the fire extinguishing control panel is in Fire condition
Stage II or Fault condition and the local sounder has been suppressed by previous pressing of the same button.
The button alternatively operation sounder is suppressed. is reversive i.e. press it once to change the current condition
– suppressed or activated local sounder. The
LED indicator illuminates if the active condition of the local
The local sounder is activated again:
- when the extinguishing fire control panel enters Fire condition long a new line;
- upon Fault condition.
Button
(Outputs)
2, 3 and
4
Press the button to suppress/activate the fire relay
Rele Fire
Access level 2 is required to for operation with this button. The key on the front panel should be in position . The button operation is reversive i.e. press it once to change the current condition alternatively
– suppressed or activated outputs.
The LED indicator illuminates if the active condition is suppressed outputs.
Instruction Manual
Revision 8/01.17
Page 25 of 63
UniPOS Fire Extinguishing Control Panel FS
5200Е
Button
(Line Reset)
2, 3 and
4
Press it to force the fire extinguishing control panel to exit
Fire condition Stage II and to reset the lines that were in Fire condition
(the power supply is switched off for
3s).
Access level 2 is required to for operation with this button. The key on the front panel should be in position
8.4. Using the switch for mode selection (Automatic/Manual/Disabled)
Use the switch for mode selection to prolong or cancel the evacuation if it turns out that it is not necessary the extinguishing devices to be activated.
Turn the switch to the right,
. in position to disable the activation of the extinguishing devices.
In addition the indicators for disabled extinguishing start to illuminate in yellow light. The display shows a text message for the entered disable and the fire
1 2 3
condition stage.
Turn the switch to position Manual to enable the extinguishing and the evacuation time to be counted down again.
9. Fault condition
9.1. Description
The fire extinguishing control panel enters Fault Condition when any of the events below have been registered:
Battery low
– backup batteries discharged due to interruption of mains supply;
Fault in a processor programme;
Fault in the real time clock;
Fault in the line
– removed fire detector, short circuit or interruption;
Fault in a monitored output
– short circuit or interruption;
Fault in a monitored input
– short circuit or interruption;
Signal for lack of extinguishing agent;
Fault in the mains supply;
Fault in backup battery supply;
Short circuit to ground wire;
Fault in the positive supply of the lines;
Fault in the negative supply of the lines;
Fault in the power supply of external devices.
Upon fault condition Short circuit to ground wire the following faults occur:
Fault condition in a line (removed fire detector)
– when the short circuit is to a fire detecting line element;
Fault condition in a monitored output (interruption)
– when the short circuit is to a monitored output element.
Fault condition is indicated by text messages on the display. The LEDs indicators provide additional information.
Instruction Manual
Revision 8/01.17
Page 26 of 63
UniPOS Fire Extinguishing Control Panel FS
5200Е
9.2. Indication
9.2.1. LED and sound indication
Upon Fault battery low LED indicator is not activated. The local sounder produces a discontinuous signal (sound for 1s, followed by 3s break). The LCD display illumination is off.
All other fault conditions are designated by indicator (Fault condition), illuminating in continuous yellow light. Depending on the specific fault, the following indicators are illuminated too:
Upon System error - indicator (System error) in flashing yellow line;
Upon Fault in a monitored line - indicator interruption) in continuous yellow light;
(Fault
– short circuit or monitored line
Upon Fault in mains supply or Backup battery supply - indicator in continuous yellow light;
(Fault in mains supply)
Upon Fault in the extinguishing device or Extinguishing agent release - indicator low pressure) in continuous yellow light;
(Fault
The local sounder produces a discontinuous signal. If the sound indication is suppressed by button
(Alarm),the LED indicator of the button illuminates in continuous red light.
9.2.2. Text messages
The fault conditions messages are displayed by priority as given in section 9.1.
The fatal system errors screens suppress all other messages. If more than one non-fatal faults are registered, they are indicated by priority as the message with the highest priority suppresses the rest of the fault messages.
Upon registration of a Fault condition, the relay REL Fault is activated, as it closes contact NO and opens contact NC.
When the fire extinguishing control panel enters Fire condition the messages for Fault conditions are suppressed. To view the suppressed messages enter Information and Control Mode.
Upon registration of a Fault
Number ot the faults
Type ot the faults condition the fire extinguishing control panel displays the respective light indication and text messages:
- the common indicator for fault condition is illuminated
- the specialized indicator showing the type of the fault condition is illuminated;
- the total number of faults and the type of the specific fault are visualized on the display;
1 2 3
Upon non-fatal faults when the fire extinguishing control panel is not in Fire condition, the following information screens appear:
Instruction Manual
Revision 8/01.17
Page 27 of 63
UniPOS Fire Extinguishing Control Panel FS
5200Е
Faults in monitored outputs:
(The field
“ЕEЕ” shows the number of the faults;
The field
“Status” shows the monitored output status, i.e. the type of the fault)
Fault in the mains supply:
(The field “ЕEЕ” shows the number of the faults).
In this case the display illumination is off. To turn it on press the button. 20s after the last pressing of the button it is off again.
Fault in backup battery supply:
(The field “ЕEЕ” shows the number of the faults).
Fault in the power supply of external devices activated fuse:
(The field “ЕEЕ” shows the number of the faults).
Short circuit to grounded wire:
(The field “ЕEЕ” shows the number of the faults).
–
Duty 17:05:34
Fault:ЕEЕ MONN Status
L1:Dut.L2:Dut.L3:Dut
Duty 17:05:34
Fault:ЕEЕ Flt Mn Power
L1:Dut.L2:Dut.L3:Dut
Duty 17:05:34
Fault:ЕEЕ Flt Battery
L1:Dut.L2:Dut.L3:Dut
Duty 17:05:34
Fault:ЕEЕ FltPower 28V
L1:Dut.L2:Dut.L3:Dut
Duty 17:05:34
Fault:ЕEЕ Fault Earth
L1:Dut.L2:Dut.L3:Dut
Fault in the negative supply:
(The field “ЕEЕ” shows the number of the faults).
Duty 17:05:34
Fault:ЕEЕ FltPower -5V
L1:Dut.L2:Dut.L3:Dut
When the fire extinguishing control panel is in Fire condition, the fault messages are suppressed.
The suppressed messages could be seen in Information and Control Mode.
Upon fault in the Fire detecting line, the type of fault could be seen in the individual field of the respective line, as the abbreviations mean:
„Sho” – Fault - Short circuit;
„Int” – Fault – interruption;
„ReD” – Fault – Removed fire detector.
9.3. Using the keypad
None of the buttons is active upon fatal fault condition (except for New Configuration).
For all other fault condition 2 buttons are being supported. Where the fire extinguishing control panel operates in combination of other conditions, their buttons are active too.
Operation Additional information Button Access level
all
Button
(Alarm)
Press it to:
- suppress the local sounder;
- activate the local sounder if the fire extinguishing control panel is in Fire condition or
Fault condition and the local sounder has been suppressed by previous
The button operation is reversive i.e. press it once to change the current condition alternatively
– suppressed or activated local sounder.
The LED indicator illuminates if the active condition of the local sounder is suppressed.
Instruction Manual
Revision 8/01.17
Page 28 of 63
UniPOS Fire Extinguishing Control Panel FS
5200Е all
Button
(Menu)
10. Disabled component
pressing of the same button.
Press it to enter Information and Control Mode. All occurred faults could be viewed in Menu View
Faults.
The local sounder is activated again:
- when the extinguishing fire control panel condition; enters Fire
- new Fault condition occurs;
For detailed information how to view all faults in Information and Control Mode see section
12.
10.1. Description
The fire extinguishing control panel enters Disabled component after a manual operation, disabling a fire alarm line or an output.
At access level 2
– Secret switch in position
and menu System Functions> Disables it is possible the following inputs and outputs to be disabled:
> Disable Line 1 ;
> Disable Line 2 ;
> Disable Line 3 ;
> Disable Rel 1ST ;
> Disable Rel 2ST ;
> Disable Out. S1 .
Upon fire detecting line disable the power supply to the line is switched off and nor processing is done.
Upon output disable, the respective output is not activated under any circumstances.
10.2. Indication
10.2.1. LED and sound indication
If a component is disabled the indicator starts to illuminate.
No sound indication is supported for this condition.
10.2.2. Text messages
When a fire detecting line is disabled it is indicated on the display in the status of the line.
There is no text message for disabled output.
All entered disables could be viewed in Information and Control mode.
Example: Disable for line 1 is entered. The indicator is illuminated, in the line status there
is a text message “Dis”.
1 2 3
Instruction Manual
Revision 8/01.17
Page 29 of 63
UniPOS Fire Extinguishing Control Panel FS
5200Е
Button
(Menu)
10.3. Using the keypad
Button Access level
all
Operation
Press it to enter Information and Control Mode. All entered disables could be viewed in Menu
View Disables.
Additional information
For detailed information how to view all entered disables in
Information and Control Mode see section 12.
11. Test Mode
11.1. Description
The fire extinguishing control panel enters Test Mode through manual operation setting a fire alarm line to Test Mode. The condition is handled via Information and Control Menus.
Where a fire alarm line is set to Test Mode, the following changes take effect:
Where Fire condition stage I or Fire condition stage II is detected in the line, sound and LEDs indications are not triggered; i.e. the fire extinguishing control panel does not enter Fire
Condition;
- in Test Mode the line is reset, the power supply is interrupted every 64 seconds for a period of
3 seconds;
- from the possible faults along the line only the fault condition Short Circuit is processed.
11.2. Indication
11.2.1. LED and sound indication
This condition does not have specific LED and sound indication.
11.2.2. Text messages
Where a fire alarm line is set to Test Mode, a text message showing the status of the line appears on the display.
All lines in Test Mode could be viewed in Information and
Control Mode.
Example: Line 1 is set to Test
Mode. In the status of the line
there is a text message “Tes”.
1 2 3
Button
(Menu)
11.3. Using the keypad
Button Access level
all
Operation
Press it to enter Information and Control Mode. All lines set to
Test Mode could be viewed in Menu
View Test.
Additional information
For detailed information how to view all lines set to Test Mode in Information and Control Mode see section 12.
Instruction Manual
Revision 8/01.17
Page 30 of 63
UniPOS Fire Extinguishing Control Panel FS
5200Е
12. Information and Control Mode
12.1. Description
Information and Control Mode provides the user with the possibilities to display information associated with the settings of the fire extinguishing control panel, and to enter control data.
The operation in this mode could be in combination with the following modes of the fire extinguishing control panel:
- Duty Mode;
- Fire condition Stage I;
- Fire condition Stage II;
- Disabled component;
- Test;
- Fault condition
- Setup.
12.2. Indication
12.2.1. LED and sound indication
No specific LEDs or sound indication is provided for this Mode.
12.2.2. Text messages
The screens visualized on the display are organized in a tree structure, containing subordinate menus (Appendix 2).
Information and Control Mode shows information in the first two lines of the display that are used by Fire condition as a text field to indicate the first line in which the fire extinguishing control panel has entered in fire condition.
Each screen has specific text message referring the operations that are performed in it. The specific text messages are described for the respective screens. .
12.3. Using the keypad
Press the button to enter Information and Control Mode from the screens of Duty Mode,
Fire condition, Fault condition, Test Mode and Disabled Component, thus their text messages are suppressed. Where the fire extinguishing control panel operates in combination of Information and
Control Mode and Fault Condition, button (Alarm) is active too. Where the fire extinguishing control panel operates in combination of Information and Control Mode and Fire Condition, buttons
(Alarm) and (Outputs) are active.
Transition to a lower hierarchy menu is performed by the means of button upper hierarchy menu use button
; to revert to an
. To switch between elements of one menu use buttons
and .
The screens containing specific information (information screens) or providing the possibility for changing the parameters and executing the commands (command screens) are at the lowest level.
The button is not active with the information screens as the other three buttons keep their functions. A cursor appears when a screen for changing a parameter or a command screen is activated. In this case the buttons has the following action:
press the button to save the changed parameter or to execute the selected command, then the screen is deactivated and the cursor disappears (the different operation of the button in some cases are specifically pointed);
press the button to deactivate the screen without saving the changed parameter or without executing the respective command, and the cursor disappears;
Instruction Manual
Revision 8/01.17
Page 31 of 63
UniPOS Fire Extinguishing Control Panel FS
5200Е
button is active only in the screens for changing the parameter. Press it to:
move the cursor one position to the right. Upon reaching the last position of the parameter the cursor returns to the first one;
decrease the parameter to the next possible value. Upon reaching the minimal possible value it turns to the maximum value of the class or the parameter;
button is active only in the screens for changing the parameter. Press it to increase by one unit the class marked by the cursor or to increase the parameter to its next possible value.
In both cases upon reaching the maximum possible value it turns to the minimum value of the class or the parameter.
12.4. Using the menus
When the Information and Control Mode is entered the first menu is displayed. It contains the following subordinate menus:
View Faults
View Disables
View Test
Statuses
System functions
12.4.1. Menu View Faults
The menu is accessible for all Access levels and contains information screens with suppressed messages for fault condition.
From the current status of the fire extinguishing control panel, press button
to enter the main menu. The cursor
„>” is positioned at the first point in the menu.
Press the button once again to visualize the screen for faults view.
1 2 3
If there are no faults a text message
“No
Faults
” appears on the display.
1 2 3
Instruction Manual
Revision 8/01.17
Page 32 of 63
UniPOS Fire Extinguishing Control Panel FS
5200Е
If there are fault condition the display shows information about the first fault. The screen contains the following information:
- consecutive number of the fault;
- total number of the faults;
- type of the fault;
- status of the lines
To display the remaining faults (if more than 1), use the buttons and .
To exit the menu
– button
.
1 2 3
Example: Two fault conditions are registered: fault in the back up battery power supply and
interruption of line 3. The common indicator for fault condition and the specific indicator for power supply fault are illuminated.
-
From the current status of the fire extinguishing control panel press twice button display a screen with the first fault (fault in the back up battery power supply);
-
Press button and the display shows the second fault (Fault interruption in line 3);
to
-
To exit the menu, use button .
12.4.2. Menu View Disables
The menu is accessible for all Access levels and contains information screens with suppressed messages for the entered disables.
From the current status of the fire extinguishing control panel, press the button
to enter the main menu. The cursor
„>” is positioned at the first point of the menu.
Press once the button and the cursor moves to the second point in the menu.
1 2 3
Press the button to visualize the screen to view the entered disables.
If there are no disabled components the following information screen is displayed.
1 2 3
Instruction Manual
Revision 8/01.17
Page 33 of 63
UniPOS Fire Extinguishing Control Panel FS
5200Е
If there are disables all active disables are displayed simultaneously on the screen.
To exit the menu
– use the button
.
Example: All entered disables are visualized on the screen: line1, line 2, line 3, the two relays that are activated for fire condition stage I and stage II and the sounder output for fire condition stage I. As disables are entered for the lines to the last line on the display these disables are also shown in the
statuses of the lines.
1 2 3
12.4.3. Menu View Test
The menu is accessible for all Access levels and contains information screens showing the lines in test.
From the current status of the fire extinguishing control panel, press the button
to enter the main menu. The cursor
„>” is positioned at the first point of the menu.
Press button until the cursor
„>” moves to point 03 of the menu.
1 2 3
Press the button to display the screen to view the lines in test.
If there are no lines in test a text message
“No Lines in Test” appears on the display.
1 2 3
Instruction Manual
Revision 8/01.17
Page 34 of 63
UniPOS Fire Extinguishing Control Panel FS
5200Е
If there is/are line/lines in test, their numbers appear on the display. Information on the changed status is provided on the fourth line of the display.
To exit the menu use button .
Example: The displayed screen provides information that Line 1 and Line 2 are set to
Test Mode.
1 2 3
12.4.4. Menu Statuses
The menu contains information screen for the statuses of the fire alarm lines, the monitored inputs and outputs. It is accessible for all Access levels.
From the current status of the fire extinguishing control panel, press the button
to enter the main menu. The cursor
„>” is positioned at the first point of the menu.
Press button until the cursor
„>” moves to point 04 of the menu.
1 2 3
Press the button to display the subordinate menu. It contains 11 elements, which status could be seen:
- Line 1;
- Line 2;
- Line 3;
-
”Manual Release”;
-
“Mode Select”;
-
“Hold”;
-
“On/Off”;
-
“Low Press”;
-
“Exting”;
-
“Sound 1”
-
“Sound 2”.
1 2 3
The cursor
„>” is positioned at the first point of the subordinate menu.
The active buttons are: and for moving the cursor in the menu, button enter the respective point from the menu and button for exit.
to
Instruction Manual
Revision 8/01.17
Page 35 of 63
UniPOS
Information screen containing the line number and the current at that moment is displayed for the status (current condition) of the line. The current value in the line provides information about its status.
Fire Extinguishing Control Panel FS
5200Е
1 2 3
The following statuses are possible for the monitored inputs and outputs:
Normal
– for monitored input or output in normal condition;
Active - for monitored input or output in active condition;
Short - for monitored input or output in short circuit;
Interruption
– for interrupted for monitored input or output;
1 2 3
12.4.5. Menu System Functions
From the current status of the fire extinguishing control panel, press the button main menu. The cursor
„>” is positioned at the first point of the menu.
Press button until the cursor
„>” moves to point 05 of the menu.
The menu contains the following subordinate menus and functions (Appendix
2):
Check LEDs and sound indicators;
Clock Setup;
Lines in Test
Disables
View Parameters;
Setup;
Fire counter;
View Archive.
1 2 3
The subordinate menus are accessible at Access Level 2.
Press button to enter the subordinate menu.
to enter the
Instruction Manual
Revision 8/01.17
Page 36 of 63
UniPOS
12.4.5.1. Function Check LEDs and Sound
Indicators
”
Fire Extinguishing Control Panel FS
5200Е
1 2 3
Press the button . All LEDs indicators are illuminated and the sounder produces continuous signal.
Press button function.
to deactivate the
Note: During the check the LEDs of the system error indicator automatic mode indicator illuminated.
and the
are not
12.4.5.2. Menu Clock Setup
The menu contains the following functions:
calendar date
day of the week
the time
calibration index
Use the function Date to set or adjust the current calendar date.
Upon activation of the function the factory set date appears and the cursor flashes on the first left digit of the date.
Admissible values are:
Use:
- for the date (two characters,
01
31)
- for a month (two characters,
0
12)
- for a year (four characters)
Instruction Manual
Revision 8/01.17
1 2 3
1 2 3
1 2 3
Page 37 of 63
UniPOS Fire Extinguishing Control Panel FS
5200Е
button
button
– to change the calendar date;
– to move to the next character;
button
– to confirm the entered or set calendar date;
button - to exit.
Use Function Day to adjust the current day of the week. The field contains the current day.
Upon activation a screen appears with the entered current day of the week.
To change, save the data and to exit the function, use:
buttons (Down) and (Up) for selecting the day (Monday, Tuesday, etc.);
button entered day;
(Menu)
– to confirm the
1 2 3
button (Exit).
Use Function Time to set or adjust the current time.
Upon activation of the function the factory set time appears and the cursor flashes on the first left digit of the hour.
Admissible values are:
- for hour (two characters, 00
23);
- for minutes (two characters, 00
59);
- for seconds (two characters, 00
59).
Use:
button
button
(Down)
(Up)
– to change the value of the hour;
– to move to the next character;
button
button (Exit).
1 2 3
(Menu) - to confirm the entered or adjusted date;
Instruction Manual
Revision 8/01.17
Page 38 of 63
UniPOS
Use function Calibration to “accelerate/ delay” the clock. Each entered positive unit
(“+”) accelerates the clock at the rate of 10,7s per month; each negative unit delays the clock at the rate of 5,35s per month.
The maximum rate is е +5,5min per month or -2,75min per month.
12.4.5.3. Fire Alarm Lines in Test
Use this menu to set each of the three fire alarming lines in Test Mode or to exit that mode.
Upon selection of Test FA Lines, a subordinate menu is entered:
- Test Line 1
- Test Line 2
- Test Line 3
Use the buttons and to choose the line to be set to test mode and confirm with button
The displayed screen provides the option for alternating change of the parameter
Test
“ON/OFF”. If it is “ON”, then the respective line is set to test Mode. Use the buttons Up and Down for the change.
Confirm the change of the parameter with button .
A text message “Saved” appears for the stored change.
The status of the line on the fourth line in the display is changed to Tes.
For exit use button
12.4.5.4. Disables
The menu serves to disable/enable the entered disable of fire alarm lines and some outputs of the fire extinguishing control panel.
It contains the following functions:
Disable Line 1
Disable Line 2
Disable Line 3
Disable Rel 1ST
Disable Rel 2ST
Disable Output S1
Instruction Manual
Revision 8/01.17
Fire Extinguishing Control Panel FS
5200Е
1 2 3
1 2 3
1 2 3
1 2 3
Page 39 of 63
UniPOS Fire Extinguishing Control Panel FS
5200Е
When the function to disable a fire alarm line or an output from the fire extinguishing control panel is selected from the subordinate menu, a screen appears displaying the current status of the disable in the specific input/output. Use the buttons and
for alternating change the parameter
Disable
“ON/OFF”.
Confirm the change with button , thus it is stored and a text message
“Saved” appears on the display.
To exit use the button .
1 2 3
The indicator illuminates in yellow light. It turns off when all entered disables are cancelled. If the disabled element is a fire alarm line, then the message on the fourth line of the display is changed for the specific line. The text message Dis appears for the status.
12.4.5.5. Menu View parameters
The menu allows the current parameters of the fire extinguishing control panel to be viewed and contains the following screens:
01 Lines parameters
02 Number of checks
03 Check removed FD
04 Input Hold
05 Input Low Press
06 Time Switch Extinguishing
07 Evacuation Time
08 Check Ground
09 RS485 Address
10 Software version
The active buttons in the menu and the screens are
1 2 3
, , and .
Screen Lines Parameters provides information about the value of the current in the lines (short circuit, interruption and fire current).
1 2 3
Instruction Manual
Revision 8/01.17
Page 40 of 63
UniPOS
Screen Number of Checks
In order the number of the false activations to be reduced, the fire extinguishing control panel provides the option to setup a parameter indicating the number of the activations of an automatic fire detector within 60 seconds that would trigger the fire extinguishing control panel for fire condition. This screen provides information about the parameter value.
Screen Check removed FD
The fire extinguishing control panel recognizes the fault condition Removed Fire
Detector if the bases that are used are diodes. Otherwise the function Removed Fire
Detector should be switched off.
Fire Extinguishing Control Panel FS
5200Е
1 2 3
1 2 3
Screen Input Hold
The screen provides information about if the input
‘Hold’ is active or not and the status of the contacts.
1 2 3
Screen Input LowPress
The screen provides information about if the input
‘LowPress’ is active or not and the status of the contacts.
1 2 3
Instruction Manual
Revision 8/01.17
Page 41 of 63
UniPOS
Screen Time for Extinguishing
The screen provides information about the setup time while the extinguishing devices are switched. The time is in seconds.
Fire Extinguishing Control Panel FS
5200Е
1 2 3
Screen Evacuation Time
The screen provides information about the setup time for evacuation. The time is in seconds.
1 2 3
Screen Check Ground
The screen provides information if the check for ground is switched.
1 2 3
Screen RS485 Address
The screen displays the setup network address.
Instruction Manual
Revision 8/01.17
Page 42 of 63
UniPOS
Screen Software Version
The screen provides information about the software version.
Fire Extinguishing Control Panel FS
5200Е
1 2 3
12.4.5.6. Menu Setup
The configuration parameters of the fire extinguishing control panel are set in the menu Setup. It is described in details in Setup Mode (section13).
12.4.5.7. Screen Fire Counter
The screen Fire Counter is part of the menu System Functions.
The active buttons to enter and exit it are
, , and .
1 2 3
The screen provides information about the entries of the number of times when the fire extinguishing control panel has entered
Fire condition.
1 2 3
Instruction Manual
Revision 8/01.17
Page 43 of 63
UniPOS Fire Extinguishing Control Panel FS
5200Е
12.4.5.8. Screen Archive
The screen Archive Counter is part of the menu System Functions.
The active buttons to enter it, to move to another entry in the archive and to exit the screen are:
, , and .
The information recorded in the archive has the following structure:
- No. of the record;
- Total number of the records;
- Text of the event in the archive (fire condition, initial reset, activated input, etc.);
- Time of the record;
- Date of the record.
13. Setup Mode
13.1. Description
1 2 3
Set Up mode is used for setting the configuration parameters of the fire extinguishing control panel. Access to the Set Up screen is provided through menu System Functions in Information and
Control Mode.
When the fire extinguishing control panel enters Set Up mode, it exits all other conditions and saves the configuration in its energy independent memory.
Important: In Setup Mode the fire extinguishing control panel discontinues the service of its fire alarm lines, inputs and outputs.
13.2. Indication
13.2.1. LED and sound indication
In Set Up mode only the green LED indicator sounder is off.
13.2.2. Text message
(Power supply) is illuminated. The local
The text message shown on the display is specific for each menu, function or screen. The screens with the respective text message for each of the setup parameter are given in the part describing the operation in menu Setup.
13.3. Using the keypad
Setup Mode requires Access Level 3. It is necessary:
- The switch to be in position
- To enter a password.
;
The text messages in this mode are organized in a tree structure, of main and subordinate menus.
Press the button to enter Setup Mode from the screens of Duty Mode, Fire condition, Fault condition, Test Mode and Disabled Component, thus their text messages are suppressed. Where the fire extinguishing control panel operates in combination of Setup Mode and Fault Condition, button
(Alarm) is active too. Where the fire extinguishing control panel operates in combination of
Setup Mode and Fire Condition, buttons (Alarm) and (Outputs) are active.
Instruction Manual
Revision 8/01.17
Page 44 of 63
UniPOS Fire Extinguishing Control Panel FS
5200Е
Transition to a lower hierarchy menu is performed by the means of button ; to revert to an upper hierarchy menu use button . To switch between elements of one menu use buttons
and .
The screens containing specific information (information screens) or providing the possibility for changing the parameters and executing the commands (command screens) are at the lowest level.
The button is not active with the information screens as the other three buttons keep their functions. A cursor appears when a screen for changing a parameter or a command screen is activated. In this case the buttons has the following action:
press the button to save the changed parameter or to execute the selected command, then the screen is deactivated and the cursor disappears (the different operation of the button in some cases are specifically pointed);
press the button to deactivate the screen without saving the changed parameter or without executing the respective command, and the cursor disappears;
button is active only in the screens for changing the parameter. Press it to:
move the cursor one position to the right. Upon reaching the last position of the parameter the cursor returns to the first one;
decrease the parameter to the next possible value. Upon reaching the minimal possible value it turns to the maximum value of the class or the parameter;
button is active only in the screens for changing the parameter. Press it to increase by one unit the class marked by the cursor or to increase the parameter to its next possible value.
In both cases upon reaching the maximum possible value it turns to the minimum value of the class or the parameter.
Instruction Manual
Revision 8/01.17
Page 45 of 63
UniPOS
13.4. Using the menus
Enter Setup Mode through menu System
Function.
Fire Extinguishing Control Panel FS
5200Е
1 2 3
Enter a password (four-digit number) to have an access to the menu. The factory set password is
“0000”.
Use:
button character;
(Down)
– to change the
button (Up)
– to move to the next character;
button (Menu)
– to confirm the entered password;
1 2 3
button (Exit).
The menu has the following subordinate menus
01 Fire Extinguishing RS485 address (section13.4.1.1)
Control Panel: RS485 On/Off (section 13.4.1.2)
02 CAN Settings
Language (section 13.4.1.3.)
Check Ground (section13.4.1.4.)
CAN On/Off (section 13.4.2.1.)
Text message (section 13.4.2.2.)
03 Input/Outputs
04 Extinguishing time
05 Evacuation time
06 Factory settings
07 Clear Archive
08 New password
CAN speed (section 13.4.2.3.)
CAN Address (section 13.4.2.4.)
CAN AddressRem.Panel (section 13.4.2.5.)
CAN Rem.Inputs (section 13.4.2.6.)
Number FD FuncAnd (section 13.4.2.7)
Current fire alarm lines (section 13.4.3.1.)
Number of checks of lines (section 13.4.3.2.)
Check removed fire detector (section 13.4.3.3.)
Input Hold (section 13.4.3.4.)
Input Low Press (section 13.4.3.5.)
13.4.1. Menu Fire Extinguishing Control Panel
The menu includes the functions for setting the parameters: network address, language and if the function heck ground is active or not.
Instruction Manual
Revision 8/01.17
Page 46 of 63
UniPOS Fire Extinguishing Control Panel FS
5200Е
13.4.1.1. The value of the parameter
Network Address defines uniquely the fire extinguishing control panel within the established network of remote control panels and repeaters.
A screen for entry of the data appears in setting (entry) of a network address.
The permissible values of the network address are from 0000 to 9999.
The value of the default parameter is
„1234”.
Use:
button
button
(Down)
(Up)
– to change the character;
– to move to the next character;
button
button
(Menu)
(Exit).
– for confirmation;
1 2 3
When the parameter is changed and the new value is saved with the button message “Saved!” appears! Exit – [x]”.
13.4.1.2. To set ON or OFF RS485 Network
Parameter permits values ON of OFF
Active buttons :
to change - buttons and
;
to save the change - button
(„Menu”);
to exit press - button
(„Exit”).
a text
13.4.1.3. The fire extinguishing control panel supports menus and screens in two of three languages:
- Bulgarian;
- English;
- Russian.
Use the buttons (Down) and
(Up) for alternating change of the language, confirm the new value of the
1 2 3
parameter using the button and the button to exit it.
When the parameter is changed and the new value is saved with the button a text message “Saved!” appears! Exit – [x]”. The fire extinguishing control panel is factory set to English language.
Instruction Manual
Revision 8/01.17
Page 47 of 63
UniPOS Fire Extinguishing Control Panel FS
5200Е
13.4.1.4. Function Check Ground
The screen provides the possibility to indicate if check ground is being performed or not. Check ground is disabled only if Zener barriers or other devices that might cause ground fault are used however that disable does not have an effect on the functions of the of the fire extinguishing control panel.
The factory setting of this parameter is Check
Ground ON.
The admissible values are
– Check
Ground ON or OFF.
1 2 3
(Up) to change alternatively the parameter, the Use the buttons (Down) and button to confirm the new value and the button
13.4.2.
Menu “CAN Parameters”
to exit.
Fire extinguishing Control Panel communicates in a network on CAN interface with the devices from
IFS7000 as transmitting and receiving information. It is necessary for the programable sofwear of the panel to be 13.10 version or higher.
Functionallity:
Connected in network, FS5200E operates with up to 8 Control panels (Remote control panels) of series 7000.
It is necessary for the local network to operate with at least 1 panel from series 7000;
Only the panel from 7000 series is definedas the main panel;
Information of Fire condition or Fault condition of FS5200E is accepted and indicated only from panels 7000 series;
Maximum number of devices on CAN network - up to 32 ( i.e maximum laden network can be built of 8 panels series 7000 and 24 FS5200E panels.
Communication
Communication
“FS5200E IFS7000”
• In Fire condition of FS5200E, 3 types of conditions are transmitted and indicated of all the panels series 7000:
- FIRE Condition Stage 1;
- FIRE Condition Stage 2 evacuacion;
- FIRE Condition Stage 2 exting.ON
• In Fault condition of FS5200E the following conditions are indicated and transfered into the panels series 7000:
- Fault in Fire detector of Line 1;
- Fault in Fire detector of Line 2;
- Fault in Fire detector of Line 3;
- Fault in Manual Release Mode;
- Fault in Line Mode;
- Fault in Line Disable Extinguishing;
-
Fault in Line Low Pressure;
-
Fault in Line Hold Extinguishing;
-
Fault in Exit Extinguishing;
-
Fault Exit Fire Stage 1;
-
Fault Exit Fire Stage 2;
-
Fault in Back up battery supply;
-
Fault in Mains supply
Communication ''5200E IFS
7000”
Instruction Manual
Revision 8/01.17
Page 48 of 63
UniPOS Fire Extinguishing Control Panel FS
5200Е
• Fire Extinguishing Control Panel 5200Е receives and uniquely distinguishes data from activated inputs of up to 5 manual call points (FD7150), up to 8 automatic fire detectors (FD71xx) and inputs of devices FD7203 within the systems series 7000.
Inputs can be configured to all of the Control Panels of type 7000 included into the network.
• Fire Extinguishing Control panel 5200E receives and single-distinguishes data from activated inputs of device FD7203. Inputs could be configured to all Control
Panels of series 7000, connected in the network.
• 4 inputs can be configured in the 5200E Control Panel, these inputs affect the functions of the extinguishing algorithm.
Inputs are for the following functions :
-
Manual Extingushing Activation (by means of a manual call point) or automatic (by means of an automatic fire detector);
-
Disable Extinguishing;
-
Switches to Manual / Manual Automatic Mode;
-
Hold Extinguishing.
• In 5200E Fire condition can be reset from the display of panels series 7000. The reset Panel transmitts information to all the panels of (7000 series) for resetting of Fire
Condition.
• Sound indicator can be suppressed from the IFS7002 display in case of Fire or
Fault Condition in the Extinguishing panel.
• In case of disconnected communication, the Control Panel FS5200Е registers fault condition
„Fault CAN” („Fault RS485”).
In the menu
“CAN Parameters” set the parameters for operating on CAN network, together with 7000 serie (the programable softwear of the panel should be 13.10 version or higher).
Menu contains the following positions:
01. CAN On/Off
02. Text message
03. CAN speed
04. CAN Address
05. CAN AddressRem.Panel
06. CAN Rem.Inputs
07. Numb FD FuncAnd
13.4.2.1. To set ON or OFF CAN Network
Parameter permits values ON of OFF
1 2 3
Active buttons :
to change - buttons and
;
to save the change - button
(„Menu”);
to exit press - button
(„Exit”).
1 2 3
Instruction Manual
Revision 8/01.17
Page 49 of 63
UniPOS Fire Extinguishing Control Panel FS
5200Е
13.4.2.2. To enter text message.
The screen allows the user to enter a text message for identifying the Control Panel
(name) within 20 characters - Cyrillic and
Latin. If an event occurs (Fault condition or
Fire Condition), the text is shown on the display of the panels series 7000.
Active buttons:
to change the character
–
to position the next character
to save the text - button ;
;
1 2 3
to exit - button
(„Exit”).
13.4.2.3. Set Up speed on CAN network communication.
Enter in the screen the exchange rate of the network.
Important : The speed entered for Panel
FS5200E must correspond to the speed, entered for IFS7000 panels.
Parameter permits the following values: 40,
80, 100 или 160 kb/s.
Active buttons:
to change
– buttons and
to save the change - button
(„Menu”);
;
1 2 3
to exit - button
Recommendation :
(„Exit”).
If the length of the wire network is longer than 500 meters, recommended speed is 40 kb / s.
13.4.2.4. Setting network address of
FS5200E panel.
Set the address of the Panel on the screen.
Address must be unique.
Admissible values: 01÷31.
Active buttons:
to change - buttons and
to save the change - button
(„Мenu”);
;
1 2 3
to exit - button
(„Exit”).
Notice:
CAN address value has no connection with ''Master/Slave
“ Setting.
Instruction Manual
Revision 8/01.17
Page 50 of 63
UniPOS
13.4.2.5. Inserting addresses of the Remote
Control Panels.
This option of the Menu permits entering the addresses in the Remote Panels for communication with FS5200E.
Мenu includes :
01 CAN Master Remote Panel 01;
02 CAN Remote Panel 02;
03 CAN Remote Panel 03;
04 CAN Remote Panel 04;
05 CAN Remote Panel 05;
06 CAN Remote Panel 06;
07 CAN Remote Panel 07;
08 CAN Remote Ranel 08;
In article 1 of the subordinate menu enter the address of the ''Master
“ panel. The panel is required to be from series 7000.
Active buttons:
to change
– buttons
and ; to save the change - button
to exit - button
(„Мenu”);
(„Exit”).
In article s 02÷08 from the Menu, insert by analogical order the addresses of the other control panels series 7000, comminicating with the Extinguishing Panel.
The addresses of the Remote panels are to be entered in ascending order. (RP1, RP2,
RP8 ...).
Important: If the number of the control panels series 7000 is less than 8, then in the spaces for addressing panels, which are not in use save Address "00" (entered by default)
Fire Extinguishing Control Panel FS
5200Е
1 2 3
1 2 3
1 2 3
Instruction Manual
Revision 8/01.17
Page 51 of 63
UniPOS
13.4.2.6. If devices of type FD7203, manual or automatic detectors are also used as an input of the fire Extinguishing Panel, their paremetres must be set in FS5200E.
Four inputs of the Control Panel are possible to be set :
01 Input Manual Activation;
02 Input Autom.Activation
03 Input Manual/automatic Mode;
04 Input Disable Extinguishing;
05 Input Hold Extinguishing.
13.4.2.6.1. Input Manual Activation includes the opportunity for activation from manual call point type FD7150, of system series 7000, operating in a common network together with
Fire Extinguishing Control Panel. Insert data for the address of the Control Panel, the address of the loop and the address of the manual call point. The admissible number of manual call points that can be included is 5.
Fire Extinguishing Control Panel FS
5200Е
13.4.2.6.2. Input Automatic Activation includes the opportunity for activation from automatic fire detectors type FD71
ХХ, of system series 7000, operating in a common network together with the Fire Extinguishing
Control Panel. Insert data for the address of the Control Panel, the address of the loop and the address of the manual call point in the loop. The admissible number of automatic fire detectors that can be included is 8. In factory setting at least two of them are connected in logical dependency ’’AND’’
(item.13.4.2.7).
13.4.2.6.3. Inputs
„Mode Manual/Automatic”, „Disable Extinguishing” and „Hold Extinguishing” are to be set by the same procedure.
Setting targets uniquely distinguishing which input, of what type FD7203 device, from which loop, and of which Control Panel the command impact will come the the Extinguishing Panel and it includes the following items: o 01 On/Off.Rem.Input; o 02 Number Remote Panel; o 03 Number Loop; o 04 Number Device 7203; o 05 Number Input 7203.
Instruction Manual
Revision 8/01.17
Page 52 of 63
UniPOS
13.4.2.6.3.1. ON/OFF Remote input.
Admissible values of the parameter are : ''On'' and ''Off''
Аctive buttons :
to change
– buttons
and
to save the change
– button
(„Мenu”);
;
to exit - button
(„Exit”).
13.4.2.6.3.2. Address of the Remote Panel, where the device FD7203 is situated.
Admissible values of the parameter are :
01÷31(i.e the addresses of Control Panels in the network.
Аctive buttons :
to change
– buttons
and
;
to save the change
– button
(„Меnu”);
to exit - button
(„Exit”).
13.4.2.6.3.3. Number of a loop where the
FD7203 device is situated.
Admissible values of the parametre are 01 and 02.
Аctive buttons :
to change
– buttons
and
to save the change
– button
(„Мenu”);
;
to exit - button
(„Exit”).
Fire Extinguishing Control Panel FS
5200Е
1 2 3
1 2 3
1 2 3
Instruction Manual
Revision 8/01.17
Page 53 of 63
UniPOS Fire Extinguishing Control Panel FS
5200Е
13.4.2.6.3.4. Number of the addressable device FD7203.
Admissible values of the parametres are:
01÷125 (address of the device in the relevant loop).
Аctive buttons :
to change
– buttons
and
;
to save the change
– button
(„Мenu”);
to exit - button
(„Exit”).
13.4.2.6.3.5. Number of the input of the addressable device FD7203.
Admissible values of the parameter are 01,
02 and 03 (IN1, IN2 and IN3 of FD7203).
Аctive buttons :
to change
– buttons
and
to save the change
– button
(„Мenu”);
;
to exit - button
(„Exit”).
1 2 3
1 2 3
The procedure for inserting parametres for inputs ''Manual/AutomaticMode'',''Disable
Extinguishing'' and ''Hold Exti nguishing“ is performed analogically according to the described in articles 13.4.2.6.3.
1.÷13.4.2.6.3.5. and operations.
Instruction Manual
Revision 8/01.17
Page 54 of 63
UniPOS
13.4.2.7. Insert the number of the automatic fire detectors of type FD71XX, connected in logical dependency
„AND”.The inserted number indicates how many fire detectors should be be activated in order the control panel to enter Fire Condition 2 nd
Stage .
Fire Extinguishing Control Panel FS
5200Е
13.4.3. Menu Input/Outputs
This menu includes the setting of the following parameters:
- current of fire alarm lines
- number of checks for accepting the signal for fire condition from a fire detector
- checking the lines for removed fire detector
- setting the input Hold
- setting the input Low Press
13.4.3.1. Function Current of Fire Alarm Line
The screen provides the option to set the current value of the fire alarm lines when interruption and fire condition is registered.
The interruption threshold could be set within the range 3 to 12 mA, and for fire condition
– from 12 to 60 mA. The difference between the two conditions provides the screen for
Duty Mode.
The factory setting is 3 and 12 mA for interruption and fire condition respectively.
The active buttons are:
1 2 3
button
button
button
button
– to change the character (e.g.: 03, 04 ......);
(Up)
– to pass from setting the current of interruption to setting the current of fire;
(Menu)
(Exit)
– to confirm the changes;
– to exit the function.
Instruction Manual
Revision 8/01.17
Page 55 of 63
UniPOS Fire Extinguishing Control Panel FS
5200Е
13.4.3.2. Screen Number of Checks of Lines
Use this screen to set the number of checks upon which the fire extinguishing control panel registers a fire condition along a fire alarm line. The possible values of this parameter are 1, 2 and 3 checks.
The factory setting is 2 checks.
Use the buttons and to change alternatively the parameter, the button to confirm the new value and the button to exit.
13.4.3.3. Screen Check for Removed Fire
Detector
The value of this parameter determines if the fire extinguishing control panel shall monitor the fault condition
– removed fire detector. If this function will be used then diode should be installed in the bases of the fire detectors as it is shown in the diagram for connecting the fire detectors. The factory setting is Check ON.
Use the buttons (Down) and (Up) to change alternatively the parameter, the
1 2 3
1 2 3
button to confirm the new value and the button to exit.
13.4.3.4. Setup Input Hold
Due to the specificity of the input Hold, the active status for this function is OPEN contact. it is provided the logic of the contact to be turned in the case of not standard installations as the active level could be with
Closed contact.
According to the standard this input should function with active level OPEN contact, otherwise the other option is an exception.
The factory setting is active level with
OPEN contact.
1 2 3
Use the buttons button
(Down) and (Up) to change alternatively the parameter, the
to confirm the new value and the button to exit.
Instruction Manual
Revision 8/01.17
Page 56 of 63
UniPOS Fire Extinguishing Control Panel FS
5200Е
13.4.3.5. Setup Input Low Press
Due to the specificity of the input to monitor the leaking of the extinguisher, the active status for this function is OPEN contact. it is provided the logic of the contact to be turned in the case of not standard installations as the active level could be with
Closed contact.
According to the standard this input should function with active level OPEN contact, otherwise the other option is an exception.
The factory setting is active level with
OPEN contact.
The active buttons are and - to reduce/increase the time for evacuation. To confirm the new value use the button to exit
– press button
.
,
1 2 3
Use the buttons (Down) and (Up) to change alternatively the parameter, the button to confirm the new value and the button
13.4.4. Function Time Extinguishing
Use this function to set the time for extinguishing. The specific value of the parameter depends on the utilized automatic devices. The factory setting is 10 seconds as the admissible values are within the range from 1 to 255 seconds.
The active buttons are and
- to reduce/increase the time for extinguishing. To confirm the new value use the button , to exit
– press button
.
to exit.
1 2 3
13.4.5. Function Time Evacuation
Use this function to set the time for evacuation The factory setting is 120 seconds as the admissible values are within the range from 1 to 255 seconds.
1 2 3
Instruction Manual
Revision 8/01.17
Page 57 of 63
UniPOS
13.4.6. The function Factory Settings returns the parameters of the fire extinguishing control panel repeater to their default settings.
The specific values of the parameters are given in the previous sections of the instruction manual.
Fire Extinguishing Control Panel FS
5200Е
1 2 3
13.4.7. Function Clear Archive
This function allows the archive to be cleared from the energy independent memory.
Press the button to activate the function and to clear the archive.
Important: The fire counter is not cleared.
It is reset in a special mode (Access Level 4).
13.4.8. Function new Password
This function serves to change the existing password for Access Level 3. The admissible values are from 0000 to 9999.
The factory setting is
„0000”.
1 2 3
.
1 2 3
14. Extinguishing Control Algorithm
The algorithm to control the outputs and the indication depending on the input influences and the set parameters for the fire extinguishing control panel operation is shown on Drawing 12.
Instruction Manual
Revision 8/01.17
Page 58 of 63
UniPOS Fire Extinguishing Control Panel FS
5200Е
Algorithm for the procedures during decision for extinguishing in Fire Extinguishing Panel FS 5200E
Duty mode
Automatic control of the extinguishing
Manual control of the extinguishing
No
Fire in 1 or 2 fire alarm lines
Yes
Fire Phase 1
Relay Fire Phase 1 - On
Sounder Fire Phase 1 - On
LED Fire phase 1 - On
Sound buzzer - 1Hz/4Hz
LCD
– indication for line in Fire
Is it switched on extinguishing manual call point?
Yes
No
Yes
Fault in the manual call point line?
No
Sound buzzer switched off
Relay Fire Phase 1 - Off
Sounder Fire Phase 1 - Off
Yes
Is it pressed button for
No
Relay Fire Phase 1 - Off
Sounder Fire Phase 1
– Off
LED Fire Phase 1 - Off
Sound buzzer - Off
LCD
– Duty mode
Sound indicator switched off
Yes
Is it pressed button for sound suppression?
No
Yes Button
Reset Fire?
No
Fire in another (1 or 2)
Fire alarm line
Yes
Relay Fire Phase 1
– Off
Sounder Fire Phase 1 - Off
LED Fire Phase 1 - Off
Yes
Is it pressed button for sound suppression?
No
No
MODE SWITCH
Manual
Fire Phase 2
Relay Fire Phase 2 - On
LED Fire phase 2 - 1 Hz
Sound indicator - On
LCD indication for Fire Phase 2
Automatic
EXTIGUISHING
Fire Phase 2
Relay Fire Phase 2 - On
Sounder Fire Phase 2 - 2 Hz
LED Fire Phase 2 - 1 Hz
Sound indicator - On
LCD
– indication for Fire Phase 2
Is there fault in disable extinguishing line?
No
Is there disable extinguishing ?
No
Time EVACUATION = Time
LCD- Time evacuation
Sounder Fire Phase 2 - On
Yes
Yes
Button delay extinguishing ?
No
No
Is it elapsed the evacuation time ?
Yes
Sound indicator
– On
LCD- Attention Gas
Yes
SWITCH ON EXTINGUISHING
OUTPUT
LED Fire Phase 2
– light continuously
Extinguishing impulse = Time
Ехт
Relay Fire Phase 2 - Off
Sounder Fire Phase 2- Off
Yes
Is it pressed button for
No
Relay Fire Phase 2 - Off
Sounder Fire Phase 2 - Off
LED Fire Phase 2
– Off
Sound buzzer - Off
LCD
– Duty mode
Yes
Button
Reset Fire?
No
No Is it elapsed the time of extinguishing impulse ?
Yes
Switch off the extinguishing output
Indicator low pressure - On
No
Is there pressure in the system?
Yes
Button
Reset Fire?
Yes
No
No
Button
Reset Fire?
Yes
18.01.2008 /
М.Киров
Drawing 12
Instruction Manual
Revision 8/01.17
Page 59 of 63
UniPOS Fire Extinguishing Control Panel FS
5200Е
15. Labour protection requirements
The installation and maintenance staff shall be well grounded in equipment’s mechanism and operation, as well as in common technical safety regulations.
Connection to unearthed or to indirectly earthing mains supply is prohibited.
Troubleshoots are to be cleared after disconnecting the feeding cable from the mains supply.
The fire extinguishing control panel is designed for installing in premises with a normal fire hazard, as per the Fire Precaution Technical Regulations in Building Construction.
16. Fire extinguishing control panel start up
Make sure that the connection to mains power supply is properly made.
Make sure that the periphery devices are correctly connected.
Place the fuse in the terminal with mains fuse, the display illuminates and appears text message with the name of the producer, the initials of the control panel and the software version. Then the display shall show the current time and date.
Connect the feeding cable and the backup batteries; the batteries shall be in a series connection.
Connect the red wire to the positive backup battery pole, and the blue wire
– to the negative pole.
The overall voltage of both batteries shall not exceed 17.6V, otherwise the fire extinguishing control panel will not recognize them.
Enter Set Up Mode and configure the common parameters and the lines parameters.
Upon exit of Set Up Mode the fire extinguishing control panel runs all system operations and enters Duty Mode
– the control panel is ready to fire protect the site.
17. Operation, storage and transportation
17.1 Operation and storage
The fire extinguishing control panel shall operate and be kept in closed premises, under the following conditions:
17.1.1. Temperature
storage
transportation
operational
- from 5
- from minus10
- from minus 5
С to 35
С to 50
С to 40
C
C
С
17.1.2. Relative humidity
storage
operational
- to 80
- to 93
17.2. Transportation
The fire extinguishing control panel shall be transported by vehicles, in factory packing, in the above stated environmental conditions and at sinusoidal vibrations with acceleration amplitude not more than 4,9m/s
2
in frequency range 10 to 150Hz.
18. Warranty
The producer guarantees compliance of the device with EN 54-2:1997/
А1:2006/AC: 2009,
EN 54-4:1997/A2: 2006/AC: 2009, EN 12094-1: 2003. The warrant period is 24 months from the date of the purchase, providing that
the conditions of storage and transportation have been observed;
the startup has been done by authorized personnel only
the requirements for operation stated herein have been observed.
UniPOS
47,
“San Stefano” Str., 5800 Pleven, BULGARIA phone +359 64 891111, +359 64 891 100, fax +359 64 891 110 e-mail: [email protected]
Mladost 1, bl.79B, entr.2, ap.17, 1784 Sofia, BULGARIA phone/fax +359 2 9744469, +359 2 9743925 e-mail: [email protected]
www.unipos-bg.com
Instruction Manual
Revision 8/01.17
Page 60 of 63
UniPOS
Аppendixes
1
2
3 4 5 6 7 8 9
Fire Extinguishing Control Panel FS
5200Е
Appendix 1
10
1 2 3
11 12 13 14 15 16 17 18 19 20 21 22
Front panel of fire extinguishing control panel FS5200E
1 Indicator Hold extinguishing
23
2 Indicator Fault in a circuit of signal wires
3 Indicator System Error
4 Indicator Fault in power supply
5 Common Indicator Fault Condition
6 Indicator Manual Mode
7 Indicator Power Supply
8 Indicator Disabled Component
9 Indicator Low Pressure
10 LCD display
(4х20)
11 Indicator Automatic Mode
12 Indicator Fire condition stage II
– Extinguishing
13 Switch
– Automatic / Manual / Disable
14 Indicator Fire condition stage I
15 Individual indicators of the Fire detecting lines
16 Indicator Disable extinguishing
17 Button Reset
18 Button Menu
19 Button Down
20 Button Alarm with indicator Stop alarm
21 Button Up
22 Button Outputs with indicator Suppressed outputs
23 Switch
– Access level
24 Button Cancel
24
Instruction Manual
Revision 8/01.17
Page 61 of 63
UniPOS Fire Extinguishing Control Panel FS
5200Е
Appendix 2
Instruction Manual
Revision 8/01.17
Page 62 of 63
UniPOS Fire Extinguishing Control Panel FS
5200Е
Appendix 3
Instruction Manual
Revision 8/01.17
Page 63 of 63