WGE Weatherproof Strobes and Horn Strobes

WGE Weatherproof Strobes and Horn Strobes
Fire Alarm Systems | WGE Weatherproof Strobes and Horn Strobes
WGE Weatherproof Strobes and Horn
Strobes
www.boschsecurity.com
The Gentex WGE family of weatherproof strobes and
horn strobes offer dependable visible and audible
alarms. The horns have a synchronizable (using the
AVSM Synchronization Module) chime and whoop
tones. You can select high or low volume and choose a
2400 Hz (remote signaling) tone or a low frequency
(1500 Hz to 3000 Hz) mechanical sounding tone where
doors could prevent hearing the other tone. They are
easily field‑changeable from temporal Code 3 to a
continuous tone. They are shipped from the factory on
the temporal lower frequency mode, and come
standard with a rugged die‑cast metal mounting plate.
The strobes have a low operating current and a
minimum flash rate of 1 Hz regardless of the input
voltage.
These devices are equipped with the SuperSlide
feature to test supervision and the Instant Voltage
Verification feature for measuring voltage drop draw.
The GOE Outdoor Enclosure is included with each
unit. The unit and GOE enclosure must be used
together to meet the UL outdoor listing.
u
Wide voltage range, 16 to 33 VDC or FWR
u
75 cd strobe meets ADA 4.28.3 requirements
u
Listed for outdoor use when used with the GOE
outdoor enclosure
u
Jumper selection for high or low frequency and for
temporal Code 3 or continuous tone patterns
u
Separate horn and strobe functions; silences horn
while strobes remain flashing
Certifications and approvals
Gentex Corporation holds these Listings and
Approvals:
Region
Certification
USA
UL
ULSZ: Audible-signal Appliances
(ANSI/UL 464), ULSZ7: Audible-signal
Appliances Certified for Canada (CAN/
ULC-S525), UVAV: Visual-signal Appliances for Fire-protective Signaling Systems (ANSI/UL 1638), and UEES7: Visual-signal Appliances Certified for Canada
[CAN/ULC-S526 (1987)]
CSFM
see our website
Installation/configuration notes
Compatible Products
The following products are compatible with these
strobes and horn strobes:
Control Panels:
Active1: FPA-1000 family and FPD-7024 family
2 | WGE Weatherproof Strobes and Horn Strobes
Legacy1: D10024A, D9412, D8024, D70242, and D70223
Mechanical
Synchronization Modules:
Candela Rating
AVSM‑R and AVSM‑W
Dimensions (HxWxD):
75 cd
For synchronization, use the AVSM‑R or AVSM‑W Synchronization
Modules with these control panels.
• without GOE
enclosure
5 in. x 4.5 in. x 2.5 in. (12.7 cm x
11.4 cm x 6.4 cm)
When used with a D7039 Multiplex Expansion Module, the D7024
becomes an addressable fire alarm control panel (FACP).
• with GOE enclosure
5.75 in. x 4.75 in. x 4.2 in. (14.6 cm x
12.1 cm x 10.6 cm)
1
2
The D7022 must be set for 24 VDC operation and requires the AVSM‑R
or AVSM‑W Synchronization Modules for synchronization.
3
Mounting Considerations
For an outdoor application or a severe environment
(NEMA 3R) application, the WGES Strobes and WGEC
Horn Strobes must be surface mounted on a flat wall
in a GOE Outdoor Enclosure. The enclosure is
supplied. Knockout holes are sized for 3/4‑inch
conduit and matching connector. Use a watertight
conduit fitting.
Wiring
Alarm Ratings
Notice
The sound output for the temporal (Code 3) tone
is rated lower because the time the horn is off is
averaged into the sound output rating. When the
horn is producing a tone in the temporal mode its
sound pressure is the same as the continuous
mode.
Horn (Continuous, 2400 Hz)
Audible Device Current
(maximum)
28 mA RMS; 48 mA FWR
Do not use these units in coded or pulsed
signaling circuits.
Sound output at 10 ft (3 m) at
24 VDC
High output: 86 dBA; Low output:
78 dBA
The input terminals accept wires with diameters
between 18 AWG and 12 AWG (ISO 0.75 mm2 and
4 mm2).
Horn (Continuous, Mechanical)
Audible Device Current
(maximum)
25 mA RMS; 44 mA FWR
Parts included
Sound output at 10 ft (3 m) at
24 VDC
High output: 84 dBA; Low output:
76 dBA
Notice
Quant.
Component
1
Strobe or horn strobe with finish plate
Horn (Temporal Code 3, 2400 Hz)
1
Die‑cast mounting plate
28 mA RMS; 48 mA FWR
1
GOE outdoor enclosure
Audible Device Current
(maximum)
1
Plastic test card
Sound output at 10 ft (3 m) at
24 VDC
High output: 83 dBA; Low output:
75 dBA
1
Hardware pack
1
Literature pack
Horn (Temporal Code 3, Mechanical)
Technical specifications
Electrical
Strobe Current (maximum)
180 mA RMS; 245 mA FWR
Voltage (Input):
• nominal
24 VDC or FWR
• range
16 VDC or FWR to 33 VDC or FWR
Environmental
Temperature (Operating):
• Indoor
+32°F to +120°F (0°C to +49°C)
• Outdoor
-31°F to +150°F (-35°C to +66°C)
Audible Device Current
(maximum)
25 mA RMS; 44 mA FWR
Sound output at 10 ft (3 m) at
24 VDC
High output: 81 dBA; Low output:
73 dBA*
* If you operate the horn in this mode at this voltage, it does not meet the
UL reverberant sound level required for public mode fire protection
service. These settings are acceptable only for private mode fire alarm
use. Use the high output setting for public mode application.
3 | WGE Weatherproof Strobes and Horn Strobes
Accessories
Chime (Continuous)
Audible Device Current
(maximum)
15 mA RMS; 30 mA FWR
Sound output at 10 ft (3 m) at
24 VDC
High output: 71 dBA*; Low
output: 68 dBA*
* If you operate the horn in this mode at this voltage, it does not meet the
UL reverberant sound level required for public mode fire protection
service. These settings are acceptable only for private mode fire alarm
use. Use the high output setting for public mode application.
Chime (Temporal Code 3)
Audible Device Current
(maximum)
15 mA RMS; 30 mA FWR
Sound output at 10 ft (3 m) at
24 VDC
High output: 71 dBA*; Low
output: 68 dBA*
* If you operate the horn in this mode at this voltage, it does not meet the
UL reverberant sound level required for public mode fire protection
service. These settings are acceptable only for private mode fire alarm
use. Use the high output setting for public mode application.
Whoop
Synchronization module for use with all Gentex
synchronizable notification appliances except the
HS24 Series and the ST24 Series.
Not Available.
Order number AVSM-R
AVSM‑W Synchronization Control Module (white)
Synchronization module for use with all Gentex
synchronizable notification appliances except the
HS24 Series and the ST24 Series.
Not Available.
Order number AVSM-W
GOE‑R Outdoor Enclosure (red)
The Gentex GOE-R Outdoor Enclosure is ANSI/UL 464
listed for use in indoor and outdoor applications when
used with the Gentex GEH Series horn and WGE
Series strobe and horn/strobe. It is red.
Not Available.
Order number GOE-R
GOE‑W Outdoor Enclosure (white)
Audible Device Current
(maximum)
56 mA RMS; 62 mA FWR
Sound output at 10 ft (3 m) at
24 VDC
High output: 83 dBA; Low output:
72 dBA
Ttademarks
All hardware and software product names used in this
document are likely to be registered trademarks and
must be treated accordingly.
Ordering information
WGEC24‑75WR Weatherproof Horn Strobe (red)
Red, 24 VDC weatherproof device with 75 cd strobe
and field‑selectable for high or low frequency, high or
low volume, and temporal (Code 3) or continuous tone
pattern
Order number WGEC24-75WR
WGEC24‑75WW Weatherproof Horn Strobe (off-white)
White, 24 VDC weatherproof device with 75 cd strobe
and field‑selectable for high or low frequency, high or
low volume, and temporal (Code 3) or continuous tone
pattern
Order number WGEC24-75WW
WGES24‑75WR Weatherproof Strobe (red)
Red, 24 VDC weatherproof 75 cd strobe
Order number WGES24-75WR
WGES24‑75WW Weatherproof Strobe (off‑white)
White, 24 VDC weatherproof 75 cd strobe
Order number WGES24-75WW
AVSM‑R Synchronization Control Module (red)
The Gentex GOE-W Outdoor Enclosure is ANSI/UL 464
listed for use in indoor and outdoor applications when
used with the Gentex GEH Series horn and WGE
Series strobe and horn/strobe. It is off‑white.
Not Available.
Order number GOE-W
4 | WGE Weatherproof Strobes and Horn Strobes
Represented by:
Americas:
Bosch Security Systems, Inc.
130 Perinton Parkway
Fairport, New York, 14450, USA
Phone: +1 800 289 0096
Fax: +1 585 223 9180
security.sales@us.bosch.com
www.boschsecurity.us
Europe, Middle East, Africa:
Bosch Security Systems B.V.
P.O. Box 80002
5617 BA Eindhoven, The Netherlands
Phone: + 31 40 2577 284
Fax: +31 40 2577 330
emea.securitysystems@bosch.com
www.boschsecurity.com
© Bosch Security Systems 2014 | Data subject to change without notice
2720229003 | en, V3, 14. Nov 2014
Asia-Pacific:
Robert Bosch (SEA) Pte Ltd, Security
Systems
11 Bishan Street 21
Singapore 573943
Phone: +65 6571 2808
Fax: +65 6571 2699
apr.securitysystems@bosch.com
www.boschsecurity.asia
China:
America Latina:
Bosch (Shanghai) Security Systems Ltd. Robert Bosch Ltda Security Systems Division
201 Building, No. 333 Fuquan Road
Via Anhanguera, Km 98
North IBP
CEP 13065-900
Changning District, Shanghai
Campinas, Sao Paulo, Brazil
200335 China
Phone: +55 19 2103 2860
Phone +86 21 22181111
Fax: +55 19 2103 2862
Fax: +86 21 22182398
latam.boschsecurity@bosch.com
www.boschsecurity.com.cn
www.boschsecurity.com
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertising