The DiamondPlus 1100 1100A and 1100B UPSs offer a variety of communication options, from basic I/O port interfacing to network communication or Modbus communications. These options allow you to monitor the UPS remotely, perform remote server shutdowns, and communicate with a Building Management System (BMS).

advertisement

Assistant Bot

Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.

Mitsubishi Electric DiamondPlus 1100 Series UPS Application Note | Manualzz

MITSUBISHI ELECTRIC POWER PRODUCTS, INC.

THORN HILL INDUSTRIAL PARK

530 KEYSTONE DRIVE

WARRENDALE, PA 15086-7538 U.S.A.

Phone: (724) 772-2555 Fax: (724) 778-5146

Home Page: www.meppi.com

ORIGINATOR: Kevin Beamer/Ed Meluch/Mike Meinert

DISTRIBUTION: All Reps Internal

DATE: May 15, 2013 DOCUMENT NUMBER: AB00015

TOPIC: 1100 Communications Options

The purpose of this application note is to explain the various communication options that are available for the DiamondPlus 1100 series UPS. The various communications options are explained below along with their primary application and features as each one serves a specific purpose. Applications beyond those stated below should be verified with your factory

Applications Engineer to ensure proper application.

The communication options range from simple I/O port interfacing to other equipment to network communications or Modbus communications.

Summary of the UPS I/O options

The DiamondPlus UPS is provided with a standard I/O (IOAU-11, for the 1100A and IOAU-12, for the 1100B) which is preinstalled in the UPS this board offers basic I/O communication and a

DB-9 connector for additional communication features. There is also an optional I/O board available (IOAU-17, p/n PCB10318) which offers expanded functionality as well as a DB-9 connector. Please refer to the table below for the specific features of each I/O board.

These I/O boards are installed on the communications tray located inside the UPS unit.

IOAU-17 requires UPS software version Control (BYP): RK9UC0_BYP, Control (UPS):

RK9VC0_UPS, Control (FPGA): RFHRB0, LCD: RK9WC0 or later.

Feature

Power Supply

DB-9 connector

Major Fault Summary

Alarm contact

Major Fault Alarm

Output contact for on bypass

Output contact for on inverter

Output contact for on battery

Output contact for converter on-line

Output contact for low battery

Output contact for

IOAU-11 IOAU-12 IOAU-17 Comments

X X 12VDC Max. XXX Amps

X

X

X

X

X

Form C contact

X

X

X

X

X

X

X

2 contacts (NO and NC)

Page 1 of 3

Feature overload indication

Summary alarm contact

Remote EPO function

IOAU-11 IOAU-12

X X

IOAU-17

X

X

Remote transfer to inverter

Remote transfer to bypass

X

Battery Hi-temp to turn off charger

Power Demand Function

X

X

*The I/O contacts are rated for 24VDC maximum current of 1A.

**I/O boards are not interchangeable with one another.

***Unless otherwise noted all contacts are NO

X

Comments

0.5s – 4s single duration

0.5s – 4s single duration

0.5s – 4s single duration

0.5s – 4s single duration

0.5s – 4s single duration

Network Communication (Netcom)

The ability to monitor the UPS remotely via a TCP/IP network can be accomplished by adding a

Netcom interface box to the standard I/O board. This option provides the end user with the real time ability to monitor the UPS condition, status of voltages and currents, review error logs, and receive email notifications (often referred to as SNMP traps) of errors as they occur. In addition this option provides the ability to perform remote server shutdowns.

Remote server shutdown licenses can be purchased in blocks of 10, only 1 license is required for each device that the user wishes to power down. The setting can be changed with regard to the amount of battery run-time left in order to provide the proper amount of time for a “soft” shut down. These shutdown licenses are available for use with most of the commonly used operating systems that are widely in use.

The Netcom adapter is installed on the communications tray located inside the UPS unit.

Remote Communications

Modbus (MCUM)

Should the customer wish to communicate with a Building Management System (BMS) via

Modbus then a MCUM Modbus adapter can be provided. This adapter will take the information provided by the UPS and translate that into a full set of Modbus registers that the BMS then can handle. A complete listing of available Modbus registers can be found in the MUCM Manual.

The communication from the MCUM is provided by any of the following options RS-232, RS485, and RS-422.

The MCUM is provided with an LCD display provide an easier way to configure the MCUM w/o the need for another computer to be hooked to it, and it allows for easier troubleshooting as data flow can be monitored w/o the need for another computer to be hooked up.

The MCUM is installed on the communications tray located inside the UPS unit.

Remote Status Alarm Panel (RASP)

The RASP option allows for the user to install a remote panel with a LED mimic bus of the UPS and see the current operating status of the UPS from another room or area of the facility up to a

maximum distance of 300 feet from the UPS. This option can only be used with the IOAU-17 optional I/O board and is not available with the standard I/O board. Also, a 120VAC source is required at the location of the RSAP.

Maintenance Panel Interlock

This option provides additional wiring to extend the aux. contact from the bypass contactor to terminal block for use when interfacing with the UPS maintenance panel. This interface would provide an interlock to an electrically operated key interlock system so that the user has a positive indication at the maintenance panel that the UPS has been placed in bypass. This is helpful in preventing the user from putting the inverter and utility on the line at the same time.

Field Retrofit options

Field retrofits due to the number of configurations should be handled by consulting with your

Applications Engineer. In the event that the customer wishes to return any of these devices for credit they must be returned in an unopened package, otherwise no credit will be given.

Communication Options Configurations

Communication Options that can be selected from at the time of purchase are listed below:

IOAU-11 IOAU-12 IOAU-17

I/O board only

I/O w/Netcom/SKRU

I/O w/MCUM/SKRU

I/O w/SKRU only

RSAP

(1100A Only)

N/A

UD100111G01

UD100111G02

UD100111G03

N/A

(1100B Only)

N/A

UD100350G01

UD100350G02

UD100350G03

N/A

(Optional I/O)

UD100299G04

UD100299G01

UD100299G02

UD100299G04

RASP-100

*Either a Netcom or MUCM can be supplied with any IOAU board but not both at the same time.

advertisement

Key Features

  • Basic I/O port interfacing
  • Network communication
  • Modbus communication
  • Remote monitoring
  • Remote server shutdowns
  • Building Management System (BMS) integration

Frequently Answers and Questions

What communication options are available for the DiamondPlus 1100 series UPS?
The DiamondPlus 1100 series UPS offers a range of communication options, including basic I/O port interfacing, network communication, and Modbus communication.
How can I monitor the UPS remotely?
You can monitor the UPS remotely by adding a Netcom interface box to the standard I/O board. This option provides real-time monitoring of UPS condition, status of voltages and currents, error logs, and email notifications of errors.
How can I perform remote server shutdowns?
Remote server shutdown licenses can be purchased in blocks of 10. Each device you wish to power down requires one license. You can adjust the battery runtime setting to provide enough time for a soft shutdown.
How can I communicate with a Building Management System?
You can communicate with a Building Management System (BMS) using a MCUM Modbus adapter. This adapter translates information from the UPS into Modbus registers that the BMS can handle.