countis e30 / e31 / e32 / e33 / e34 / e35 / e36

countis e30 / e31 / e32 / e33 / e34 / e35 / e36
COUNTIS
E30 / E31 / E32 / E33 / E34 / E35 / E36
site_334_a
count_179_b_1_cat
Active energy meter and concentrator
3-phase - Direct 100 A
 Function
The COUNTIS E3x is an active electrical
energy meter designed for three-phase
networks. It is used for direct connections
up to 100 A.
The COUNTIS E3x is protected against
phase/neutral inversion and detects wiring
errors.
 Conformity to
standards
• IEC 62053-21 class 1
• IEC 62053-23
class 2
• EN 50470-1
• EN 50470-3
 Applications
The COUNTIS E30 displays the total energy consumed
and allows remote access through a pulse output.
Metering over a specific period can be managed through
a partial counter.
In addition to the COUNTIS E31 functions, the
COUNTIS E30, is a double tariff meter intended for dual
tariff invoicing. A partial counter is available for each tariff.
In addition to the COUNTIS E31 functions, the
COUNTIS E32 also offers MID certification. They have
no partial counter.
In addition to the COUNTIS E30 functions, the
COUNTIS E33 also offers JBUS/MODBUS RTU
communication via RS485.
In addition to the COUNTIS E33 functions, the
COUNTIS E34 also offers MID certification.
In addition to the COUNTIS E30 functions, the
COUNTIS E35 also offers M-BUS communication via
RS485.
In addition to the COUNTIS E35 functions, the COUNTIS E36
also offers MID certification.
The MID meters have no partial counter and cannot be reset.
Meters with communication do not have a pulse output.
The COUNTIS E33 and E35 are bi-directional
(i.e. counting energy production or consumption).
Active energy meter and concentrator
COUNTIS E30 / E31 / E32 / E33 / E34 / E35 / E36
 Electrical characteristics
 Front panel
1. Terminal shrouds (COUNTIS E32,
E34 and E36).
2. LCD display.
3. MID marking (COUNTIS E32,
E34 and E36).
4. Serial number (COUNTIS E32,
E34 and E36).
5. Navigation key.
5 6. Reset key.
6
7 7. Metrological LED.
1
count_179x_b_1_cat
2
3
Current measurement
Type
Input consumption
Startup current (Ist)
Minimum current (Imin)
Transition current (Itr)
Reference current (Iref)
Permanent overload (Imax)
Intermittent overload
Voltage measurement
Range of measurement
Consumption (VA)
Permanent overload
4
 Case
62.5
45
126
COUNTIS E30
Partial
45
90
count_192_b_1_x_cat
Error
3-phase - Direct 100 A
0.5 VA max. per phase
80 mA
0,5 A(1)
2 A(2)
20 A(3)
100 A
3 000 A max for 10 ms
RESET
3X230(400)VAC 50/60Hz 0.5-20(100)A
C=2Wh / imp
100A
Type
Number of modules
Dimensions W x H x D
Case protection index
Front protection rating
Display type
Rigid cable cross-section
Flexible cable cross-section
Weight
Modular
7
126 x 90 x 62.5 mm
IP20
IP51
Backlit LCD display
2.5 to 35 mm2
2.5 to 35 mm2
490 g
230 ... 400 V +/- 20 %
2
280 V phase-neutral / 480 V phase-phase
Energy accuracy
Active (according to IEC 62053-21)
Active (according to EN 50470)
Class 1
Class B
Power supply
Self-supplied
Frequency
Yes
50 / 60 Hz
Output (pulsed)
Number
Type of optocoupler
Fixed pulse weight
Pulse duration
1
IEC 62053-31 Class A (20 ... 30 VDC)
100 Wh
100 ms
Operating conditions
Operating temperature
Storage temperature
Relative humidity
-10 to 55 °C
-20 to 70 °C
85 %
Communication
Link
Type
Protocol
JBUS/MODBUS® speed
M-BUS speed
RS485
2 … 3 half duplex wires
JBUS/MODBUS® RTU
4 800 … 38 400 bauds
300 … 9 600 bauds
(1) I(min) ≤ 0.5 * Itr
(2) The accuracy class is guaranteed between Itr and Imax.
(3) I(ref) = I(b) (base current) = 10 * I(tr) for direct connection COUNTIS.
 Connection
1
1
+ 2
4 6
N
COUNTIS E30
1 3 5 7 9 11
L1
L1’
L2
L2’
L3
L3’
L1
L2
L3
N
L1’
L2’
L3’
1
1
1
+ 2
15 17 13
N
RS485
COUNTIS E33/E34/E35/E36
1 3 5 7 9 11
L1
L1’
L2
L2’
L3
L3’
N
L1’
L2’
L3’
1
L1
L2
L3
count_185_c_1_x_cat
count_184_c_1_x_cat
L3
N
L1’
L2’
L3’
1
count_188_e_1_x_cat
L1
L2
1
1
+ 2
N
4 6 8 10
COUNTIS E31/E32
T1/2
1 3 5 7 9 11
L1
L1’
L2
L2’
L3
L3’
1. 100 A gG / Am fuses max.
 References
Type
3-phase - Direct 100 A
100 A direct - 3-phase - Dual tariff
100 A direct - 3-phase - Dual tariff - MID
100 A direct with JBUS/MODBUS communication via RS485 (1)
100 A direct with JBUS/MODBUS communication via RS485 - MID(1)
100 A direct with M-BUS communication via RS485 (1)
100 A direct with M-BUS communication via RS485 - MID(1)
COUNTIS
E30
Reference
4850 3005
COUNTIS
E31
Reference
COUNTIS
E32
Reference
COUNTIS
E33
Reference
COUNTIS
E34
Reference
COUNTIS
E35
Reference
COUNTIS
E36
Reference
4850 3006
4850 3007
4850 3012
(1) 4 tariffs through RS485 communication.
 Management software for COUNTIS
See page
MID Certification
The Measuring Instruments Directive (MID) authorises the use of MID COUNTIS in applications for
which sub-billing of the electrical energy consumed is necessary (apartments, commercial units, etc.).
It guarantees each user that meters meets a high level of accuracy, quality design and manufacturing
through a 3rd party verification.
4850 3013
4850 3025
4850 3026
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertisement