Cyberwave Express UPS - United Engineering Company, Inc.
CYBERWAVEEXPRESS
Data Sheet
Rugged Industrial UPS. Fast delivery. Those two features have
never gone together – until now. Introducing the CyberWave
EXPRESS from Cyberex, a standard UPS built for the Industrial
Market that is delivered in very short lead times!
CyberWave EXPRESS has standard features no other UPS
manufacturer can match, including modular independence and
the world’s first VGA, full-color touch-screen 8"x11" control panel
(PowerPad). In addition, every CyberWave EXPRESS incorprates
Cyberex’s patented Digital Static Transfer Switch design for
increased system redundancy and reliability.
CyberWave EXPRESS has been configured to include the
most popular UPS hardware & software features. Even though
CyberWave EXPRESS is a standard unit to allow for fast delivery,
popular options are still available as well.
Hardware Configuration
INPUT
RECTIFIER
BATTERY
System Input Breaker (Auto)
6-pulse Recifier/Charger
Battery Disconnect Switch
Input Isolation Transformer
Charger Output Fuse
120V DC Bus Voltage
Battery Fuse
INVERTER
BYPASS
SYSTEM
IGBT PWM Inverter
Bypass CB
Maintenance Bypass Switch
Internal IGBT Fuses
Fully Rated, Bi-Directional Static Switch
Output Isolation Transformer
System Output CB (non-auto)
Normal
Source
Rectifier/
Charger
Inverter
Input Isolation
Transformer
Output Isolation
Transformer
Static Switch
Battery
Disconnect
Alternate Bypass Isolation Transformer
(External to UPS,Optional)
Source
Bypass
Input CB
System
Output CB
To Load
Maintenance
Bypass
Switch
CyberWave EXPRESS Selection Guide
UPS Model
kVA
CW-10
10
Input
Input Voltage
Number of Phases
Number of Wires
Input Frequency
Input Power Factor
Maximum Input Current
@ 480V, 100% Load,120VDC
Input Breaker @ 480V
DC Bus
Voltage
Battery Disconnect Switch
Maximum Battery Current
@ 120VDC, 100% Load
CW-25
25
CW-30
30
21A
35A
32A
50A
83A
125A
43A
60A
53A
80A
64A
90A
120V
167A
Rotary 3 Position Switch
Standard
208A
250A
224A
268A
120 VDC
Standard
89A
Output
Output Voltage
Output Frequency
Number of Phases
Number of Wires
Output Isolation Switch/Breaker
UPS Output Current
@ 120VAC, 100% Load
15 Minute Overload Current
@ 120VAC Unity PF, 150% KW Rating
Overload: Static Bypass (One Loop)
Inverter Efficiency
100% Load
75% Load
50% Load
25% Load
Full Load Heat Rejection (BTU/Hr)
Module Weights (lbs)
Base Unit
CW-20
20
480 Volts
3 Phases
Standard: 3 wire + Ground
Standard: 60 Hz
0.75 pf at rated output and load
Bypass
Input Voltage
Nominal Bypass Current @ 120V
Maintenance Bypass Switch
Bypass Line Input Disconnect Switch
General
Module Dimensions W"x D"xH"
Base Unit
CW-15
15
134A
179A
120VAC
60 Hz
Single Phase
2 Wire
Standard
83A
125A
167A
208A
250A
100A
700%
150A
700%
200A
700%
250A
700%
300A
600%
4200
5600
88%
88%
88%
88%
7460
12050
14460
77.25x37x34.5
77.25x37x34.5
77.25x37x34.5
77.25x60.25x34.5
77.25x60.25x34.5
1600
1600
1600
2560
2850
Standard Events, Alarms & Meters
Events/Alarms Parameter
Rectifier
DC Bus
Battery
Inverter
Bypass
Output
Rectifier Input Available
Rectifier Input Failure
On Rectifier
Rectifier OK
Rectifier Fail
RCB Communications Failure
Rectifier Equalize Mode
Rectifier Output Voltage High
Rectifier Output Voltage Low
Rectifier Output Current High
Rectifier Input Voltage High
Rectifier Input Voltage Low
Rectifier Input CB Open
Rectifier Output Fuse Blown
DC Bus OK
DC Ground Fault Positive
DC Ground Fault Negative
DC Caps Due for Maintenance
DC Bus Fuse Blown
On Battery
Low Battery
Battery Equalize Initiated
Battery Equalize Aborted
Battery Equalize Complete
Battery Available (Disk Closed)
Battery Not Available (Disk Open)
Battery End Voltage
Battery Due for Maintenance
Battery Blown Fuse
Battery CB Open
Inverter OK
Inverter Failure
Inverter Overload
Inverter Current Limit
Inverter Sat Trip
Inverter Temperature OK
Inverter Overtemp
Inverter Output Voltage High
Inverter Output Voltage Low
Inverter Output Frequency High
Inverter Output Frequency Low
Inverter Input Fuse Blown
Inverter Control Failure
Alt Line Available
Alt Line Fail
Sync Loss
STS on Alternate
Manual Transfer Enable
Alt Line CB Open
Load on Inverter
Load on Alternate
UPS Overload
MBS in Normal Position
MBS in Bypass
MBS in Bypass Isolate
STS Active Short
Events/Alarms Parameter
Output (continued) STS Inactive Short
STS Open SCR
STS Receive Error
STS Timeout Error
STS Control Failure
STS on Alternate
Output Failure
STS Output CB Open
General
System Reset
Overload Timer Started
Overload Timer Ended
EPROM Write Error
Control DSP Failure
Summary Alarm
Summary Overtemp
Cabinet Overtemperature
Fan Failure
STS Power Supply Failure
System Logic Power Supply Failure
Login/Logout
Login Failure
Air Filter Needs Cleaning
Fans Due for Maintenance
Other
Event Log
Service Notebook
Mimic Panel
Modbus Communications
Metering
Metering Value (1% Accuracy)
Rectifier
Input Voltage (A, B, C)
Input Current (A, B, C)
Output Voltage DC
Output Current DC
Voltage DC
Current DC
Runtime
Power
Cycles
Total Cycles
Voltage RMS
Current RMS
Frequency
Output Voltage RMS
Output Current RMS
Output Frequency
Output Real Power (Watts)
Output Apparent Power (VA)
% Loading
Crest Factor
UPS Peak Current
Power Factor
Input Voltage
Input Frequency
Battery
Inverter
Output
Alt Line
Standard Specifications
IGBT-Based PWM Inverter
Modular Independence
Full Digital Controls with DSP’s
Full Isolation Input/Output Transformers
Full Color Touch Screen Monitor Panel
RS 232 Communications Port
Bidirectional Fully Rated Static Switch
Maintenance Bypass Switch
Fiber Optic Datapaths
Screw Mounted Nameplates
Wire Markers
14 Pre-Defined Remote Alarm Contacts
Breaker Position Indicator Package
Blown Fuse Indicator Package
Standard Documentation
-Manual -Outline
-Oneline -Wiring Diagram
AC Input Rating
Input Voltage
Frequency
Input Power Factor
Input Inrush Current
Current Walk-In Ramp
Surge Withstand
Transient Energy
Environmental Specifications
Accoustical Noise Level
60dBA Typical at 3 Feet
Operating Temperature
0-40°C, 0-50° C Optional
Relative Humidity
0-95% Non-Condensing
Access
No Rear or Side Access Required
for Operations or Maintenance
Cooling
Forced Air; Optional Redundant
Fan Assemblies for Cabinet
Operating Altitude
Up to 1500 m at 40°C; Derate by 9%
for Every 1000m Altitude Increase
Paint
Light Gray ANSI 61
UPS EXPRESS OPTIONS
Option 1- Cooling Package
Redundant Cabinet Fans
Option 2- Mechanical Package
Lexan Barrier
Drip Shield
Vermin Screen
Current Limit
Input Current THD
480V, +10% and –20%
60 Hz, ± 5%
[email protected] Full Load and Nominal Input
400% Max of Nominal Input Current
Up To Full Load in 15 Seconds
Meets IEEE 587/ANSI C62.41
160 Joules (Max Ratings at 85° C,
10/10,000msec & Combination Wave Tests)
125% of Rated 0.8pf Current
30% Typical
DC Bus Rating
DC Voltage
DC Regulation
DC Voltage Ripple
120VDC
± .25% from No Load to Full Load, ± 300mV
<2% RMS Ripple @ Full Load, without Battery Connected
AC Output Rating
Inverter Power
Voltage
Voltage Adjustability
Voltage Regulation
Transient Response
Voltage Recovery
Voltage Distortion
Overload: Inverter
Overload: Static Bypass
Frequency
Frequency Stability
Frequency Slew Rate
Option 3- Complete Package
Cooling Package
Mechancial Package
10-30kVA, Rated at 0.8 Power Factor
120V
± 5% of Nominal, 114-126V
<± 2% Steady State for 0-100% Load Change
<± 5% for a 100% Load Step
<± 1% for Loss or Return of AC Input Power
<± 5% for Manual Transfer to Bypass and Back @100% Load
Return to Within ± 2.5% of Nominal Value Within
16 Milliseconds (One Cycle)
Linear Loads: <5% Typical at Full Load
Non Linear Loads (Crest Factor = 3.1): Max 5% at Full Load
Up to 150% of Rated output power for 15 Minutes
at Min DC Bus and Input Voltage at 40° C
Up to 150% of Rated output power for 5 Minutes at 50° C
10 to 25kVA – 700%
30kVA – 600%
60Hz
± .1% Free Running
1.0Hz/Sec Maximum
©Copyrght 2001, Cyberex. CyberWave EXPRESS and Cyberex are trademarks of Cyberex.
All other brand and product names are trademarks or registered trademarks of their respective companies.
Danaher Power Solutions
5900 Eastport Boulevard
Richmond,VA 23231-4453
Tel: 800-238-5000
Fax: 804-236-4040
www.cyberex.com
E-mail: [email protected]
Bulletin 94-58-20013 (PDF/6.03) CYB-2771
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertisement