SYSMAC LINK
Product Specifications
CS1 CPU Bus Unit
CS1 Series
SYSMAC LINK
SYSMAC LINK Units: CS1W-SLK11/SLK21
SYSMAC LINK Support Boards: 3G8F5-SLK21/SLK22
A Basic FA Network with Data Links and Message Communications.
Both Wired and Optical Networks Supported.
An FA network SYSMAC LINK Network supports
data links between PCs or between PCs and
personal computers (data constantly shared over a
given area), as well as communications messages
between PCs or between PCs and personal
computers (i.e., send and receive data when
necessary).
What is the SYSMAC LINK?
The SYSMAC LINK is an FA network that can transfer data among
OMRON Programmable Controllers (CS1-series, C200HX/HG/HE,
and CV-series PCs) and IBM PC/AT or compatible computers. The
SYSMAC LINK supports data links that enable data sharing and a
message service that enables sending and receiving data when
required.
Wired Unit
CS1W-SLK21
Optical Unit
CS1W-SLK11
Automatic settings
Data link
Manual settings
SYSMAC LINK
Message
service
SEND/RECV
instructions
CMND instruction
Personal Computer Board
3G8F5-SLK21/22 (Wired Board)
There are two types of SYSMAC LINK Systems: The Wired System,
which is connected using coaxial cables, and the Optical System,
which is connected using optical fiber cables.
Ethernet
Controller Link
SYSMAC LINK
CompoBus/D
CompoBus/S
Information network
Controller network
Component network
High-speed
ON/OFF bus
“Programmable Controller” is abbreviated as “PC” in these Specification Sheets.
1
Product Specifications
SYSMAC LINK
System Configuration
The CS1-series, CVM1, CV-series, C1000H/HF, C2000H, C200HX/HG/HE, and C200HS PCs can be connected.
Wired System (Coaxial Cable)
CS1W-SLK21
SYSMAC
LINK Unit
CS1-series
PC
C200HW-SLK23/
24 SYSMAC
LINK Unit
CV500-SLK21
C1000H-SLK21 IBM PC/AT or
SYSMAC
-V1 SYSMAC compatible
C1000H,
LINK Unit
LINK Unit
C1000HF,
CVM1, CV
C2000H
series PC
series PC
C200HX/
HG/HE PC
C
P
U
C
P
U
C
P
U
IBM PC/AT or
compatible
C
P
U
Coaxial cable
3G8F5-SLK21,
3G8F5-SLK22
SYSMAC LINK
Support Board
Optical System (Optical Fiber Cable)
CS1W-SLK11
SYSMAC
LINK Unit
C200HW-SLK13
C200HW-SLK14
SYSMAC LINK Unit
C
P
U
24-VDC
Backup
Power Supply
CVM1, CV
series PC
C200HX/
HG/HE PC
CS1-series
PC
CV500-SLK11
SYSMAC
LINK Unit
C
P
U
C1000H-SLK11
SYSMAC LINK
C1000H, Unit
C1000HF,
C2000H
series PC
C
P
U
C
P
U
Optical fiber cable
(Daisy-chain
connection)
C200H-APS03
Power Supply Unit
C1000H-APS01
Power Supply Unit
24-VDC
Backup
Power Supply
Note:
IBM PC/AT or compatible personal computers cannot be connected using optical fiber cables.
Features
Data Links
Data links allow the constant sharing of data in predetermined data
areas between nodes, between PCs, or between a PC and an IBM
PC/AT or compatible computer on the network. Data links do not require the use of communications programs on the PC (CPU Unit) or
IBM PC/AT or compatible computer. Data written in the send area of
the local node will be automatically sent to the receive area of other
nodes.
Any portions of the I/O area (CIO Area), data link area (LR Area),
and data memory area (DM Area) can be specified as the send or
receive words.
•
Manual Setting
Used for flexible data link processing depending on each system.
Using the CX-Net of the CX-Programmer, individual data link tables
can be set for each node and the data link words can be freely allocated for each node. Send data size per node can be freely set. It is
also possible to set nodes for only send or receive data.
SYSMAC LINK Unit
PC
PC
PC
Number of send words per node: 508 words max. (CIO Area: 254
words + DM Area: 254 words)
•
Number of send and receive words per node: 2,966 words max.
(sum of CIO Area and DM Area)
The data link area can be set automatically or manually.
Automatic Setting
Used for simple data link processing. Data link can be performed by
simply setting parameters in the DM Area of the PC. Send data size
per node is the same for all nodes. All nodes participating in the data
link share the same data.
PC
SYSMAC
LINK Unit
PC
PC
Constant data exchange (sharing)
(CIO Area, LR Area, DM Area)
2
Message Service
This function controls data transmission with particular nodes, reading or writing of status data, changing of operation modes, etc., by
executing communications instructions on a program. The communications instructions include SEND/RECV instructions for data
transmission and CMND instructions for issuing various commands.
SEND/RECV
The SEND or RECV instruction sends or receives data in an area of
a particular node.
The SEND instruction sends data from an area of the local node and
writes to an area in the designated node.
The RECV instruction requests the designated node to send area
data and writes the data to the local node.
SYSMAC LINK
Product Specifications
CMND
The CMND instruction issues a command to read or write data of
other nodes, control, or read error logs. With the SYSMAC LINK
Unit, OMRON’s command protocol called “FINS commands” is
used.
•
SYSMAC LINK Unit for CVM1 and CV-series Programmable
Controllers
•
SYSMAC LINK Unit for C200H and C200HS Programmable
Controllers
•
SYSMAC LINK Unit for C1000H, C1000HF, and C2000H
Programmable Controllers
SYSMAC LINK Unit
PC
PC
PC
CS1
Flexible Inter-network Connections
• The SYSMAC LINK Network can connect to
other networks
(Ethernet, Controller Link, and SYSMAC LINK) via CVM1,
CV-series, or CS1-series PCs. By installing a Communications
Unit for the Ethernet, Controller Link, or SYSMAC LINK on the
same CS1-series, CVM1, or CV series-PC as a Controller Link
Unit, a message service can be created with nodes in
interconnected networks through this PC. Up to three network
levels are possible.
Message
User program
Data transmission (under
certain conditions) as required
Communications instruction (SEND/RECV/CMND)
•
Coaxial Cable or Optical Fiber Cable Connection
The SYSMAC LINK Units can be connected to the network using
either coaxial cables or optical fiber cables. Select the system that
suits your application.
Features of System Using Coaxial Cable
The 5C-2V Coaxial Cable is used for wiring the SYSMAC LINK Unit
or Board.
Features of System Using Optical Fiber Cable
• Optical Fiber Cable has superior noise resistance, so this
system can provide highly reliable communications even in very
noisy conditions.
•
The communications distance can be up to 10 km in total (1 km
max. between nodes), which allows long-distance or large-scale
networks.
Compatible with Different Node Configurations
• The following SYSMAC LINK Units are available for
communications between different models. It must be noted,
however, that the wired system and optical system cannot exist
in one SYSMAC LINK Network.
The programming and monitoring of other PCs on the network
can be conducted from Programming Devices connected to the
PC’s CPU Unit. Inter-network connections are possible in this
case also and can cover up to three network levels.
Node Bypass (Optical System Only)
With the Optical SYSMAC LINK network, data communications can
be continued by bypassing the node, even when a node in the communications line malfunctions or the PC or IBM PC/AT or compatible computer power supply is turned OFF. This prevents the whole
network system from being affected by a node malfunction or power
interruption.
To use the bypass node function, 24-VDC backup power must be
supplied to the SYSMAC LINK Unit.
RAS
RAS performs real-time monitoring of the network status. If an error
occurs in the network, RAS records and displays the time and contents of the error.
Status Area
•
Data Link Status Area
When the data link function is used, the data link status is
reflected in the data link status area of the PC.
Network Status Area
The network status such as the state of node participation is
reflected in the status area of the PC.
Wired system
•
•
•
SYSMAC LINK Unit for CS1-series Programmable Controllers
Error Log
•
SYSMAC LINK Unit for CVM1 and CV-series Programmable
Controllers
•
SYSMAC LINK Unit for C200H and C200HS Programmable
Controllers
•
SYSMAC LINK Unit for C1000H, C1000HF, and C2000H
Programmable Controllers
•
SYSMAC LINK Support Board for IBM PC/ATs or compatibles
SYSMAC LINK Unit for C200HX/HG/HE Programmable
Controllers
Optical System
•
•
SYSMAC LINK Unit for CS1-series Programmable Controllers
The error log function records contents (codes) and times of errors
that occur in the network into the RAM, or EEPROM in the SYSMAC
LINK Unit.
The recorded errors can be read using the CX-Net of the CX-Programmer or the message service function.
Data Link Settings Using CX-Programmer
You can make data link table settings, monitor the status of data
links, and perform similar operations for the CS1-series SYSMAC
LINK Unit using the CX-Programmer programming software. (You
cannot directly connect the SYSMAC Support Software to a
CS1-series CPU Unit using RS-232C.)
SYSMAC LINK Unit for C200HX/HG/HE Programmable
Controllers
3
Product Specifications
SYSMAC LINK
SYSMAC LINK Communications Specifications
Specifications
Item
Wired system
Optical system
Communications functions
Data links, message communications
Communications method
N:N token bus
Code
Manchester code
Modulation
Baseband code
Synchronization
Flag synchronization (conforms to HDLC frames)
Transmission path form
Bus
Daisy-chain
Baud rate and maximum transmission
distance
Baud rate: 2 Mbps (fixed)
Baud rate: 2 Mbps (fixed)
Maximum transmission distance: 1 km
Maximum transmission distance: 10 km
Maximum distance between nodes:
Crimp cut: 800 m
Adhesive: 1 km (see note)
Transmission path
Coaxial cable (5C-2V)
H-PCF cable (optical two-core cable)
Node connection method
BNC connector
Special full-lock connector (a half-lock
connector can also be used)
Maximum number of nodes
62 nodes (32 nodes when the 3G8F5-SLK22 is used)
Number of data link words
Send words per node: 508 words max. (254 words in CIO Area + 254 words in DM Area)
Data link words (send and receive) that can be created in a single CS1-series CPU Unit:
2,966 words max. (CIO Area + DM Area)
Data link areas
Automatic settings: CIO 1000 to CIO 1063 (Data Link Area), D00000 to D00127 (DM Area)
Manual settings: CIO 0000 to CIO 6143 (entire CIO), entire DM Area (D00000 to D32767)
Message length
552 bytes max. (including header)
RAS functions
Automatic polling node backup
Automatic polling node backup
Self-diagnostics (startup hardware check)
Self-diagnostics (startup hardware check)
Internode testing, broadcast test (using FINS
command)
Internode testing, broadcast test (using FINS
command)
Watchdog timer
Watchdog timer
Error log
Error log
Node bypath function (by Power Supply Unit)
Error control
Manchester encoding check
CRC check (CCITT X16 + X12 + X5 + 1)
Note:
The maximum distance between nodes depends on the connector and cable processing methods.
Data Link Specifications
Type of Data Link
Automatic settings
Manual settings
No. of data link nodes
62 nodes max. (2 nodes min.)
No. of data link
words
Number of
send/receive
words per node
2,966 words max. (CIO Area + DM Area total)
Data link areas
CIO Area
Data Link Area:
CIO 1000 to CIO 1063
DM Area
D00000 to D00127
CIO Area
CIO 1000
Manual settings can be made
between CIO 0000 to CIO 6143
DM Area
D00000
Manual settings can be made
between D00000 to D32767
Number of words
sentt per node
d
CIO Area
Either 4, 8, 16, or 32 words (same for each node)
DM Area
Either 8, 16, 32, or 64 words (same for each node)
0 to 254 words (separate
( p
for each
node)
d )
Allocating data
link words
CIO Area
Each node has the same number of data link words
and words are allocated to nodes in the order of node
addresses
addresses.
Starting data link
word
od
DM Area
Note:
4
Select from the following:
CIO
C
O Area
ea only,
o y, DM Area
ea
l CIO + DM Areas
A
only,
CIO Area (CIO 0000 to CIO 6143)
(See note)
DM Area (D00000 to D32767)
(See note)
The number of data link words and
the order of allocation can be set for
each node.
node The same order of
allocation must be used for both the
CIO Area and the DM Area.
When creating manually set data link tables using CX-Programmer Ver. 1.2 Service Pack 1, the words that can be set by the user are
limited to the same words as for CVM1/CV, as follows:
CIO Area: CIO 0000 to CIO 2555
DM Area: D00000 to D24575
SYSMAC LINK
Product Specifications
Message Communications Specifications
Instruction
SEND/RECV
CMND
Application
Sending and receiving data
Reading and writing data (file memory, etc.)
from other nodes, changing the operating
mode, other control operations, reading error
log, etc.
Message contents
Commands for sending and receiving data
Sends any FINS command
PC to PC
Possible
Possible
PC to computer
Possible (requires a program to return
responses from computer)
Possible (requires a program to return
responses from computer)
Computer to PC
Possible (requires a program to receive
responses at the computer)
Possible (requires a program to receive
responses at the computer)
SEND instruction: 1:1 or 1:N (broadcasting
data)
SEND instruction: 1:1 or 1:N (broadcasting
data)
Local node to
d ti ti node
destination
d
Local node: Destination node
RECV instruction: 1:1
Number of words sent and received
256 words max. (512 bytes)
542 bytes max.
SYSMAC LINK Units
Models
Applicable PC
CS1
Unit classification
CPU Bus Unit
Type
Media
Wired
Coaxial cable
Optical fiber
Optical fiber cable
Type of communications
Data links (manual settings,
automatic settings), message
communications (using SEND,
RECV, and CMND instructions)
Model number
CS1W-SLK21
CS1W-SLK11
SYSMAC LINK Unit Programming Software
Type
SYSMAC LINK
programming software
Note:
Name
CX-Programmer Ver. 1.2
Service Pack 1 or later
Specifications
Manual data link settings, data link start/stop, read
network status, read error log, routing table settings,
network testing, changing network parameter settings
Model number
WS02-CXPC1-J
1. When creating manually set data link tables using CX-Programmer Ver. 1.2 Service Pack 1, the words that can be set by the user
are limited to the same words as for CVM1/CV, as follows:
CIO Area: CIO 0000 to CIO 2555
DM Area: D00000 to D24575
2. You cannot use SYSMAC LINK support software in the CS1 SYSMAC LINK Unit.
5
Product Specifications
SYSMAC LINK
SYSMAC LINK Unit Specifications
Specifications
Item
CS1W-SLK21
CS1W-SLK11
Wired Unit
Optical Unit
Unit classification
CS1 CPU Bus Unit
Applicable PCs
CS1-series PC
Maximum number of Units
4 Units max. (total of Wired and Optical Units)
Mounting position
Mount in any 4 slots on the CPU Rack or CS1 Expansion Rack
Unit number settings
0 to F
Data exchange
g
with
ith CPU Units
U it
CPU Bus Unit I/O
A
Area
25 words per Unit
Data exchange
g
with
ith CPU Units
U it
CPU Bus Unit
words
d iin DM A
Area
100 words per Unit (however, only the first one word is used.)
SYSMAC LINK Unit to CPU Unit:
Data link status, network participation status, error information, etc.
CPU Unit to SYSMAC LINK Unit:
Polling node/polled note mode setting, data link start, data link mode (automatic/manual) setting,
data link words for automatic setting, etc.
Settings switches
Rotary switches: Unit number, node address
Indicators
There are nine LED indicators on Optical Unit or eight LED indicators on Wired Unit: RUN
(operating), communications error, CPU Unit error, participating in network, polling node,
sending, receiving, participating in data link, and power ON (Optical Units only).
Front-panel connections
BNC connector
Effect on CPU Unit cycle time
0.2 ms
Optical connector × 2
24-VDC power terminal block
If data links are operating, add 1.5 ms + (number of words transferred x 0.001 ms)
If message service is operating, also add event execution time
Power consumption (supplied from
Power Supply Unit)
330 mA at 5 VDC
470 mA at 5 VDC
Backup power supply
–
24 VDC, 200 mA max.
Dimensions
35 × 130 × 101 mm (W × H × D)
Weight
400 g
500 g (excluding cable mounting)
Standard accessories
F-type Adapter (C1000H-CE001), insulating
cover
Cable Bracket
Catalog number
W367
6
SYSMAC LINK
Product Specifications
Applicable CPU Units
PC
CPU Unit model number
CS1-series
CS1H-CPUjj (-V1)
CS1G-CPUjj (-V1)
Maximum number of Units that can be mounted
on CPU Racks and CS1 Expansion Racks
4 Units max. (total for Wired and Optical Units)
(Settable unit numbers: 0 to F)
Mounting position
limitations
None
SYSMAC LINK Support Boards
Models and Specifications
Specification
Item
3G8F5-SLK21
3G8F5-SLK22
Type
Wired Board
Maximum number of nodes
that can be connected to
the network
62 nodes
Computer
IBM PC/AT or compatible
Compatible OS
IBM PC DOS Ver. 5.0 or later, Windows 95/NT (see note)
Compatible language
Microsoft C Ver. 6.0
Quick BASIC Ver. 4.5
Setting switches
DIP switch: Memory allocations
32 nodes (node address: 1 to 62)
Short pin: Interrupt level
Indicators
There are seven LED indicators: RUN (operating), communications error, EEPROM error, participating in
network, sending, receiving, and participating in data link.
Connectors
BNC connector (connect the coaxial cable using the F-adapter supplied), card edge connector
Power consumption
0.6 A max. at 5 VDC
Dimensions
120 × 260 mm (W × L)
Weight
250 g
Product configuration
1 Board + SYSMAC LINK Support Software (3.5-inch floppy disk, 1.44 MB)
Standard accessories
1 F-connector (C1000H-CE001)
Catalog No.
W220
Note:
120 × 163 mm (W × L)
---
FinsGateway is required separately for Windows 95 or Windows NT.
7
Product Specifications
SYSMAC LINK
Accessories (Sold Separately)
Coaxial Cables
Name
Model
Coaxial Cable
Manufacturer
5C-2V
Fujikura Ltd.
ECXF5C-2V
Hitachi Cable, Ltd.
Connector
BNC-P-5C-CR10-B
Daiichi Denshi Kogyo Co., Ltd.
F-connectors
C1000H-CE001
OMRON
Terminating Resistors
C1000H-TER01
OMRON
Note:
The CR-H-1130 Hand Crimp Tool is required to assemble connectors.
Optical Fiber Cables
Specifications
Name
Product
Optical
p
fiber cable
Hard plastic-clad
p
fiber
(H PCF)
(H-PCF)
Black
Orange
g
8
Model
Cable color, etc.
Cable length
10 m
S3200-HCCB101
50 m
S3200-HCCB501
100 m
S3200-HCCB102
500 m
S3200-HCCB502
1,000 m
S3200-HCCB103
10 m
S3200-HCCO101
50 m
S3200-HCCO501
100 m
S3200-HCCO102
500 m
S3200-HCCO502
1,000 m
S3200-HCCO103
Optical connector
For node connection, full lock type, crimp cut
S3200-COCF2011
Inline adapter
Used in cable relays (extension)
S3200-COIAT2000
Optical
p
fiber cable
with
ith connector
t
Optical
p
connector:
B th ends
Both
d on
S3200-COCF2011
2m
S3200-CN201-20-20
5m
S3200-CN501-20-20
10 m
S3200-CN102-20-20
15 m
S3200-CN152-20-20
20 m
S3200-CN202-20-20
Over 20 m
S3200-CN-20-20
(Specify length when ordering.)
Optical connector
assembly tool
Applicable optical connector: S3200-COCF2011
S3200-CAK1062
Optical power tester
Applicable optical connector S3200-COCF2011
(applicable head unit: S3200-CAT2702)
S3200-CAT2700
Master fiber
Applicable head unit: S3200-CAT2702
S3200-CAT2001H
SYSMAC LINK
Product Specifications
Nomenclature
CS1W-SLK21 Wired Unit
CS1W-SLK11 Optical Unit
LED indicators
Display Unit status and network status
LED indicators
Display Unit status and network status
Uni number setting switch
A single rotary switch. Use to set the unit number
on the PC as a single hexadecimal digit.
Node address setting switch
Two rotary switches. Use to set the node
address on the SYSMAC LINK network as a
2-digit decimal number.
Unit number setting switch
A single rotary switch. Use to set the Unit
number on the PC as a single hexadecimal digit.
Node address setting switch
Two rotary switches. Use to set the node address
on the SYSMAC LINK network as a 2-digit
decimal number.
Optical connector
Connect the optical fiber communications cable
from the SYSMAC LINK Network.
Coaxial connector
Connects to the SYSMAC LINK network
communications coaxial cable.
Power supply terminal block
Connect the backup power supply for the node
bypass function.
LED Indicators
Indicator
Color
RUN (operating)
( p
g)
Green
P/S
(power supply ON,
ON
CS1W-SLK11 only)
Green
ERC (error detected
Unit))
by U
Red
ERH (error in the
CPU
Unit))
C
UU
Red
INS (participating
(p
p
g in
network)
t
k)
Yellow
SD ((sending
g data))
Yellow
RD (receiving
(
g data))
Yellow
LNK (data
link))
(
Yellow
Display
Meaning
Lit
Operating normally
Not lit
Unit error
Lit
Power is being supplied from the backup power supply.
Not lit
Power is not being supplied from the backup power supply.
Lit
Communications Controller error, node address setting error,
duplicate node address setting
Not lit
Communications operating normally
Lit
CPU Unit error, CPU Unit interface error, EEPROM error, unit number
setting error, duplicate unit number setting, I/O tables not set
Not lit
CPU Unit operating normally
Lit
Participating in network
Not lit
Not participating in network
Lit
Sending data
Not lit
Not sending data
Lit
Receiving data
Not lit
Not receiving data
Lit
Data links operating
Slow flashing
Data link table settings error
Quick flashing
Data link table communications cycle time is too short.
Not lit
Data links not operating
9
Product Specifications
SYSMAC LINK
External Connections
Wired Units
Connect each node using coaxial cables by means of multidrop connections.
F-adapter
Connector
Terminating
resistance
Terminating
resistance
5C-2V Coaxial Cable
Optical Units
Connect all the nodes in series in a daisy chain using the optical fiber cable (H-PCF cable).
SYSMAC LINK Unit
SYSMAC LINK Unit
SYSMAC LINK Unit
Optical
connector
cover
Optical
connector
cover
Upstream
Downstream
Specified connectors and optical fiber cable (H-PCF)
Dimensions
Wired Unit
CS1W-SLK21
Unit: mm
CS1W-SLK11
Unit: mm
Optical Unit
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.
10