IOM TSTBM4H2CPH-A_6720220380.indd

Add to my manuals
24 Pages

advertisement

IOM TSTBM4H2CPH-A_6720220380.indd | Manualzz

Owner’s Manual

Thermostat

Series

BOSch cOMMunicaTing TherMOSTaTS

TSTBT4h2cP SerieS

TSTBT4H2CP-M--A

TSTBT4H2CPHM--A

6 720 220 380 Revised 06-13

2 TSTBT4H2CP SERIES

Table of ConTenTs

The TSTBT4H2CP Series offers: ................................... 3

Thermostat Application Guide ..................................... 3

TSTBT4H2CP Series Thermostat Quick Reference ...... 4

Features of the Transmitting and Receiving Module

(TRM) ........................................................................... 5

Installing the TSTBT4H2CP Thermostat Series ............ 6

Wall Locations ............................................................. 6

Installing the TRM Receiving Module ........................... 6

Temperature Sensor Connections ............................... 7

TS1 and TS2 ................................................................ 7

Remove the Battery Tab ............................................... 8

Install the Thermostat on the Sub-Base ....................... 8

Displaying and Resetting the Service Messages .......... 9

Fault Codes .................................................................. 9

Enabling Fault Code Messages..................................... 9

Displaying Equipment Service Messages ..................... 9

High Pressure Alert ...................................................... 9

Low Pressure Alert ....................................................... 9

Freeze Condition Alert ............................................... 10

Condensate Line Alert ............................................... 10

Brownout Alert .......................................................... 10

Evaporator Freeze Alert ............................................. 10

Lost Equipment Communication ............................... 11

Lost Gateway Communication ................................... 11

Low Heating Output ................................................... 11

Low Cooling Output ................................................... 11

Lost Power ................................................................. 11

Initial Thermostat Settings ........................................ 12

Selecting Heating or Cooling ..................................... 12

Selecting Auto or Cont Fan ........................................ 12

Adjusting the Temperature Setting. ........................... 12

Adjusting RH Setpoints for Humidity Control. ............ 12

Selecting Operating Mode ......................................... 12

Setting the Time and Day of the Week ........................ 13

Schedule Programming.............................................. 13

7 Day Program Schedule ............................................ 14

Custom Program Schedule ........................................ 14

Locking the Thermostat ............................................. 15

Hidden Lock key ......................................................... 15

Displaying the Time and Temperature Schedule ........ 15

TSTBT4H2CP Thermostat Series Installation

Troubleshooting ........................................................ 17

Available Accessories for the

TSTBT4H2CP Thermostat Series ............................... 18

Product Limited Warranty .......................................... 19

Warranty Coverage .................................................... 19

Items Not Covered ..................................................... 19

Limited Warranty ....................................................... 20

Warranty Claims Process ........................................... 20

6 720 220 380 Subject to change without prior notice Revised 06-13

Thermostat application Guide

TSTBT4H2CP SERIES

3

The Bosch TSTBT4H2CP Thermostat Series consists of

4-wire MODBUS communicating thermostats. Utilizing

RS485 MODBUS protocol, the TSTBT4H2CP Thermostat

Series can communicate with the equipment, monitor the performance, and report the status of the equipment.

The MODBUS protocol is received and then translated to pulses to be received by the HVAC equipment. This translation is performed by the TRM (Transmitting and

Receiving Module). The thermostat and TRM communicate via 2 wire MODBUS, the TRM and the HVAC equipment communicates via 4-12 wires utilizing pulses.

The Bosch TSTBT4H2CP Thermostat Series communicates utilizing MODBUS protocol to the TRM

ThermosTaT aPPliCaTion Guide

Description

Gas or Oil Heat

Electric Furnace

Heat Pump (No Aux. or Emergency Heat)

Heat Pump (With Aux. or Emergency Heat)

Multi-Stage Systems

Heat Only Systems

Cool Only Systems

Dual Fuel Systems

Milivolt

Humidifier Control

Auto Changeover

MODBUS Communicating

The TsTbT4h2CP series offers:

• Modbus thermostat with large LCD and touch screenwith blue LED back lighting

Available

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

• Low back light level when touch keys not used

• Four schedules per day, 7-day programmable

• Up to four-stage heating and 2-stage cooling

• Optional automatic fan operation during daytime on selected days

• Compatible with conventional and dual fuel heatpumps and gas electric systems

• Optional temperature sensors for dis-charge air temperature and outdoor air temperature

• Optional remote space temperature sensors

• Diagnostic monitor indicates equipment alerts and loss of communications

• Service monitors for filter, UV Bulb and humidifier pad

• Optional keyboard lock

• Receiving Module COM LED blinks during

Modbuscommunication and turns red if communication with thermostat is lost

• Optional return air temperature sensor maintains safe space temperature if communication with thermostat is lost for 10 minutes

Revised 06-13 Subject to change without prior notice 6 720 220 380

Caution

4 TsTbT4h2CP series quick reference

TsTbT4h2CP series ThermosTaT quiCK referenCe

Getting to know your thermostat

Displays the operating mode,

Schedule, Temporary Hold or Hold.

Schedule, Temporary Hold or Hold.

Displays the schedule period,

Morning, Daytime, Evening or Night.

Morning, Daytime, Evening or Night.

Displays time of day and weekday

Displays time of day and weekday

Day

Day

We

Schedule

We

Schedule

AM

AM

Battery charge indicator .

(program saving battery only; the battery will not power the thermostat)

.

(program saving battery only; the battery will not power the thermostat)

Displays heating, cooling or RH setpoint.*

Displays heating, cooling or RH setpoint.*

Heat

Heat

Set To

Set To

Insid e

HEAT

Insid e

HEAT

MENU

MENU

MODE

MODE

NEXT

NEXT

ENTER

ENTER

SYSTEM

SYSTEM

AUTO

AUTO

FAN

FAN

Up and Down keys used to adjust setpoints.* to adjust setpoints.*

System key selects Off, Heat only,

Em Heat, Cool only or Autmatic

Heat/Cool.

Fan key selectsAutomatic or On.

Previous key when in programming mode

Menu key used to display

User menu selection.

Mode key selects between Schedule, temporary Hold or continuous Hold.

Displays the indoor temperature when setting the heating or cooling or the indoor

RH% when setting the RH setpoint*.

Switches the setpoint display between heating, cooling or RH%*.

MENU, MODE, NEXT, & ENTER buttons change functionalities during programming or other type of menu setting changes. Their function is described for that specifi c function within the Tech Setup Section.

Press the hidden schedule key to program the Morning, Day,

Evening and Night schedules.

Press the hidden clock key to set the time of day and weekday.

Press the hidden Message key when blinking to display the equipment alert messages.

Press the hidden Lock key when

Press the hidden Lock key when the Lock feature is enabled to lock or unlock the keys using the

2-digit code.

When in a menu setup, this

MornDay EveNight

Temp Hold

Mo

MornDay EveNight

Temp Hold

Mo

We

Tu We

Message

Option

Schedule

Th Fr SaSu

Com

Com

AuxHeat

Clean

Vacant

Locked

MENU MODE

Zone

Home Zone

Home

HeatCool RH%

NEXT

Set To

FrAi r

FrAi r

HeatCool RH%

Set To

Outside

RH%

Inside

Filter

RH%

HumPad

UV Bulb

ENTER

EmHeat

OFF

EmHeat

COOL

AUTO

FAN

SYSTEM

AUTO

ON

When in a menu setup, this

MODE button is blank and is used as a Cancel button.

MENU MODE NEXT ENTER FAN

Filter, HumPad or UV Bulb will blink when

Filter, HumPad or UV Bulb will blink when service is required. Press the hidden key area to reset the service timers after servicing the equipment.

*Humidity Features only available with the TSTBT4H2CPHM--A model and the TSTBT4H2CPHMW-A model.

*Humidity Features only available with the TSTBT4H2CPHM--A model and the TSTBT4H2CPHMW-A model.

6 720 220 380 Subject to change without prior notice Revised 06-13

Transmitting and receiving module TSTBT4H2CP SERIES

5 feaTures of The TransmiTTinG and reCeivinG module (Trm)

Caution

Mercury Notice: All Bosch thermostats are mercury free. However, if the product you are replacing contains mercury, dispose of it properly.

Your local waste management authority can give you instructions on recycling.

Features, Receiving Module

Optional Return Air Temperature Sensor

If communication is lost between the Receiving

Module and Thermostat for 10 minutes, the sensor is used to control the space temperature.

HVAC Status

Red if heating call, blinks during second stage heating call.

Yellow if cooling call, blinks during second stage cooling call.

Green if fan call.

Communication Status

Blinks green during Modbus communication with thermostat and turns red if communication with thermostat fails 10 times.

Relay

HVAC Control

Terminals can be configured for conventional or dual fuel heat pumps or gas/electric systems.

Relay

Relay

Relay

Relay

Relay

Relay

Relay

Modbus Thermostat Communication

A 4-wire thermostat cable between the Receiving

Module and the Thermostat provides Modbus communication using RS485.

Optional Temperature Sensors

TS1 and TS2 can be used to monitor dis-charge air temperature, outdoor temperature or can be used as remote space temperature sensors. See Installer options 13 and 14.

Equipment Monitor

The PDU terminal is used to monitor

Bosch equipment and indicate any alert messages at the Thermostat.

Humidifier Control

These terminals are used to control a humidifier.

De-Humidication Control

The HUM terminal can be used to control de-humidification using the cooling or hot gas reheat.

Revised 06-13 Subject to change without prior notice 6 720 220 380

Caution

Caution

6 TsTbT4h2CP series installing the Thermostat insTallinG The TsTbT4h2CP

ThermosTaT series

Caution

A trained, experienced technician must install this product. Carefully read these instructions. You could damage this product or cause a hazardous condition if you fail to follow these instructions. See the product specifi cations at the end of this manual prior to installing.

To insure a solid fi t between the thermostat and the subbase:

1. Mount subbase to a fl at wall

2. Use screws provided

3. Drywall anchors should be fl ush with the wall

4. Wires should be pushed into the wall

wall loCaTions

Do not install thermostats in locations that are:

• On an exterior Wall

• In direct sunlight

• Where there may be concealed chimneys or pipes behind the wall

• Close to a window or door leading outside

• Close to objects radiating heat such as fi re places, lighting, space radiators, or any other applicance

• In areas that do not require conditioning

• In dead spots or where drafts can occur (behind doors or in corners)

• Close to hot or cold air ducts

Pick an installation location that is easy for the user to access. The temperature of the location should be representative of the building.

mounting the Thermostat

First, separate the thermostat and sub-base using a fl at blade screw driver as shown below.

insTallinG The Trm reCeivinG module

TRM stands for Transmitting and Receiving Module. The

TRM communicates with the TSTBT4H2CP Thermostat

Series using the MODBUS protocol and then translates the MODBUS protocol to pulses and relays these signals to the HVAC equipment.

The Receiving Module can be installed adjcent to or within the HVAC equipment.

Secure to wall or equipment with screws at top and bottom.

P/N 7738002948

Descriptive Part#

TSTB-TRM--6--A

Receiving Module

24VAC, 2VA, No Load

Made in USA

COM

HVAC

Remove these screws (4) to access terminals.

Screw driver

Rotate the screw driver tip so the thermostat separates from the sub-base and then pull the thermostat away from the sub-base.

Align the 4 tabs on the subbase with corresponding slots on the back of the thermostat or base module. Then push gently until the thermostat or base module.

6 720 220 380

There are two LED lights on the TRM. One is the COM light which blinks green when communication is happening between the TRM and the thermostat. This light will normally blink about every 10 seconds as the thermostat and TRM are in constant communication for status updates. If communication is lost for more than 10 minutes, the COM LED will become red. A certifi ed licensed technician should be called to service the system if this occurs.

The other LED is labeled HVAC. This light indicates if the unit is actively heating or cooling. If the unit is cooling, then the

LED is yellow, if the unit is in heating, then the LED is red. If the thermostat is satisfi ed, then the LED if off.

Subject to change without prior notice Revised 06-13

Caution

Temperature sensor Connections TsTbT4h2CP series

7

Terminal Designations on the TSTBT4H2CP Thermostat Series

3 Heat / 2 Cool Conventional System

C 24 Volt Common

R 24 Volt Power

O Energized in Cooling

B Energized in Heating

W1 Heating - 1st Stage Aux

W2 Heating - 2nd Stage Aux

Y1 Compressor - 1st Stage Cooling

Y2 Compressor - 2nd Stage Cooling

G Fan Relay

DH

"Cool to Dehumidify Relay

(Cooling Mode Only)”

HUM

HUM

ALR

3 Heat / 2 Cool Heat Pump System

24 Volt Common

24 Volt Power

Energize Reversing Valve in Cooling

Energize Reversing Valve in Heating

Heating - 1st Stage Aux

Emergency Heat Relay

Compressor - 1st Stage Heating/Cooling

“Cool to Dehumidify Relay

(Cooling Mode Only)”

4 Heat / 2 Cool Heat Pump System

24 Volt Common

24 Volt Power

Energize Reversing Valve in Cooling

Energize Reversing Valve in Heating

Heating - 1st Stage Aux / Emergency Heat

Heating - 2nd Stage Aux

Compressor - 1st Stage Heating/Cooling

Compressor - 2nd Stage Heating/Cooling Compressor - 2nd Stage Cooling

Fan Relay Fan Relay

“Cool to Dehumidify Relay

(Cooling Mode Only)”

"Humidifi er Contact Relay

(Dry Contact-Heating Mode Only)”

“Humidifi er Contact Relay

(Dry Contact-Heating Mode Only)”

“Humidifi er Contact Relay

(Dry Contact-Heating Mode Only)”

“Humidifi er Contact Relay

(Dry Contact-Heating Mode Only)”

“Humidifi er Contact Relay

(Dry Contact-Heating Mode Only)”

“Humidifi er Contact Relay

(Dry Contact-Heating Mode Only)”

This terminal is used only for Bosch / Florida Heat Pump Equipment. This connection is used for fault code communication from the

UPM board in the heat pump. The fault type being transmitted will be displayed on the thermostat. Do not use with any other equipment.

TSTBT4H2CP Thermostat Series Wiring

Notes: Bosch Water Source Heat Pumps utilize “O” type reversing valve operation. If your heat pump utilizes “B” type reversing valve operation, substitute the wiring for the

“O” terminals for “B”.

TemPeraTure sensor ConneCTions zonb-las---m--a return air

Temperature sensor

Optionally, a temperature sensor can be installed in the return air duct. This sensor is automatically detected by the TRM and used to control the equipment should the communication between the thermostat and TRM fail.

This insures the indoor temperature does not drop below

55°F or rise above 85°F.

Use AWG 18–22 thermostat wire to connect the sensors to the TRM.

Ts1 and Ts2

Temperature sensor 1 and Temperature sensor 2 inputs on the TRM can be confi gured in the thermostat setup menu as an outdoor temperature sensor, a leaving air temperature sensor, or as a remote room temperature sensor.

Either TS1 or TS2 can be designated as the outside air temperature sensor, however once one of the input sensors are designated as the outdoor temperature sensor, the option will not be available for the other sensor input in the menu setup. The same logic applies for the leaving air temp. You cannot have two sensor inputs designated as outdoor temperature or leaving air temp.

For the remote room temperature sensor function, either

TS1 or TS2 can be desingnated or both can. Two remote room temp sensors are allowed.

Ts1 used as outdoor Temperature sensor

An outdoor temperature sensor is required for dual fuel heal pumps and for automatic emergency heat activation in cold weather. The sensor should be installed under the eves and in the shade.

Revised 06-13 Subject to change without prior notice 6 720 220 380

8 TSTBT4H2CP SERIES

Ts1 used as leaving air Temperature sensor

A sensor can be installed in the supply duel to monitor the

Leaving air temperature for monitoring equipment performance. The stainless steel tube should inserted in the duct down stream from the plenum.

battery Tab

Ts1 used as a remote space

Temperature sensor

A sensor can be installed in a remote location, such as the second floor, and the temperature at the remote sensor will be averaged with the sensor in the thermostat when controlling the heating and cooling.

When both TS 1 and TS2 are used as remote space temperature sensors, both sensor readings will be averaged with the thermostat sensor reading.

See the available accessories at the end of this manual for compatibility, part numbers and descriptions for ordering.

remove The baTTery Tab

The TSTBT4H2CP-M--A Thermostat Series has a coin cell battery for maintaining the clock, schedules, and user settings during power outages. After the wiring of the installation, remove the battery tab. Do not remove the tab until the Receiving Module, Thermostat and equipment wiring is complete.

Ts2 Temperature sensor #2 insTall The ThermosTaT on The sub-base

Align the four prongs on the sub-base with the square holes in the thermostat back cover and push the thermostat onto the sub-base until it locks in place.

6 720 220 380 Subject to change without prior notice Revised 06-13

Caution

Caution

service messages

TsTbT4h2CP series

9 disPlayinG and reseTTinG The serviCe messaGes

The“Filter”,“HumPad”or“UV Bulb”will blink whenever their service hours have exceeded the time interval in

100s of hours for cleaning or replacement. After servicing the fi lter, humidifi er pad or UV bulb, press and hold the key area in gray for 4 seconds to reset the hours.

“Filter” linking

Day

We

Schedule

AM

Heat

Set To

Inside

Filter

HEAT

MENU MODE NEXT ENTER

SYSTEM

AUTO

FAN

Press and hold in this area for 4 seconds to reset filter monitor hours.

If multiple fl ags are blinking, you will have to repeat the process for each fl ag.

faulT Codes

The TSTBT4H2CP Thermostat Series communicates with a Florida Heat Pump or Bosch heat pump through the compressor protection module (UPM) board. The UPM communicates fault codes utilizing a combination of pulses. The translating module deciphers these pulses and relays the associated fault to be displayed on the thermostat.

enablinG faulT Code messaGes

Run a low voltage wire from the ALR-OUT terminal connection on the UPM board to the PDU terminal on the

TRM.

This feature is only available with a Florida

Heat Pump or Bosch Heat Pump.

See page 8 for wiring diagram.

disPlayinG equiPmenT serviCe messaGes

The word“Message”will blink anytime an equipment service message is present. To display the message, Press in the key area shown in gray for 4 seconds.

Day

We

Message

Schedule

AM

Heat

Set To

Inside

HEAT

MENU MODE NEXT ENTER

SYSTEM

AUTO

FAN

hiGh Pressure alerT

The equipment has detected a high head pressure condition and prohibited heating and cooling calls.

Contact your local contractor for service. Press the

enTer key to return to normal thermostat display.

Message

MENU MODE

Message

MENU MODE

HEAT

NEXT ENTER

SYSTEM

AUTO

FAN

HEAT

NEXT ENTER

SYSTEM

AUTO

FAN

low Pressure alerT

The equipment has detected a low head pressure condition and prohibited heating and cooling calls.

Contact yourlocal contractor for service. Press the enTer key to return to normal thermostat display.

Revised 06-13 Subject to change without prior notice 6 720 220 380

Caution

10 TsTbT4h2CP series freeze Condition alert

Message

HEAT

MENU MODE NEXT ENTER

SYSTEM

AUTO

FAN

Message

HEAT

MENU MODE NEXT ENTER

SYSTEM

AUTO

FAN

Message

HEAT

MENU MODE NEXT ENTER

SYSTEM

AUTO

FAN

HP & LP faults will indicate whether the fault has occurred on compressor 1 or compressor

2. HP1 is a high pressure fault on compressor

1, LP2 is a low pressure fault on compressor 2

freeze CondiTion alerT

The equipment has detected a freeze condition and prohibited heating and cooling calls.

The sensor that has triggered this fault is monitoring the refrigerant temperature between the TXV and the air coil.

The UPM board is aware of the mode of operation, and this sensor will be monitored in the cooling mode.

Contact your local contractor for service. Press enTer key to return to normal thermostat display.

brownouT alerT

The equipment has detected a power brownout condition and prohibited heating and cooling calls. Contact yourlocal contractor for service. Press the enTer key to return to normal thermostat display.

Message

MENU MODE NEXT ENTER

HEAT

SYSTEM

AUTO

FAN

evaPoraTor freeze alerT

The equipment has detected a freeze condition and prohibited heating and cooling calls.

The sensor that has triggered this fault is monitoring the refrigerant temperature between the TXV and the water coil. The UPM board is aware of the mode of operation, and this sensor will be monitored in the heating mode.

Contact your local contractor for service. Press enTer key to return to normal thermostat display.

Message

HEAT

Message

HEAT

MENU MODE NEXT ENTER

SYSTEM

AUTO

FAN

MENU MODE NEXT ENTER

SYSTEM

AUTO

FAN

CondensaTe line alerT

The equipment has detected a condensate line blockage condition and prohibited cooling calls. Contact yourlocal contractor for service. Press the enTer key to return to normal thermostat display.

6 720 220 380 Subject to change without prior notice Revised 06-13

lost equipment Communication

TSTBT4H2CP SERIES 11 losT equiPmenT CommuniCaTion

The thermostat has detected a loss of communication with the equipment,receiving module or zoning panel.

Check the wiring connections. See the troubleshooting section at the end of this manual or contact your local contractor for service. Press the enTer key to return to normal thermostat display.

.

Message

MENU MODE NEXT ENTER

HEA T

SYSTEM

AUT O

FA N

Message

MENU MODE NEXT ENTER

HEAT

SYSTEM

AUTO

FAN

losT GaTeway CommuniCaTion

This fault will only be produced if Option 29 - Internet

Connection is being utilized. See the Tech Menu Setup

Explanation for more information. The thermostat has detected a loss of communication with the Gateway and internet access. If the condition persists, see the troubleshooting section at the end of this manual or contact your local contractor for service. Press the enTer key to return to normal thermostat display.

low CoolinG ouTPuT

This fault will only be produced if Option 20 - Cooling

Equipment Monitoring is being utilized. See the Tech

Menu Setup Explanation for more information. The thermostat has detected the cooling equipment output is below its limit. This can be caused by unusually severe hot weather. If the condition persists, contact your local contractor for service. Press the enTer key to return to normal thermostat display.

Message

MENU MODE NEXT ENTER

COOL

SYSTEM

AUT O

FA N

Message

MENU MODE NEXT ENTER

HEA T

SYSTEM

AUT O

FA N

low heaTinG ouTPuT

This fault will only be produced if Option 19 - Heating

Equipment Monitoring is being utilized. See the Tech

Menu Setup Explanation for more information. The thermostat has detected the heating equipment output is below its limit. This can be caused by unusually severe cold weather. If the condition persists, contact your local contractor for service. Press the enTer key to return to normal thermostat display.

losT Power

If the power to the equipment is lost, the Receiving

Module and Thermostat loss power and the thermostat goes into a low power operating mode to maintain the clock using the 3V coin cell. The keys and back lighting are inhibited until power is restored. Only the time and “noP” is shown on the LCD indicating there is no power available to operate the equipment.

We Su

AM

Revised 06-13 Subject to change without prior notice 6 720 220 380

12 TSTBT4H2CP SERIES initial Thermostat settings iniTial ThermosTaT seTTinGs

The user options can be accessed using Menu key or by pressing certain areas on the LCD.

seleCTinG heaTinG or CoolinG

By pressing SYSTEM button, you can rotate through the 4 operation mode choices: off, heaT, emheaT, Cool,

auTo. Select off to turn both heating and cooling off.

Select heaT for heating only or Cool for cooling only.

Select auTo for automatic changeover of heating and cooling. When used for heat pump control, the emergency heating can be operated by selecting EmHeat.

Day

We

Schedul e

AM

Heat

Set To

Inside

HEAT

System

Key

MENU MODE NEXT ENTER

SYSTEM

AUTO

FAN

seleCTinG auTo or ConT fan

Select AUTO to allow the fan to be activated when needed by a heating or cooling call. Select CONT to operate the fan continuously for ventilation.

Day

We

Schedul e

MENU MODE

AM

Heat

Set To

Inside

NEXT ENTER

HEAT

SYSTEM

AUTO

FAN

Fan Key

adjusTinG The TemPeraTure seTTinG.

Press the press the

arrow to raise the temperature setting or

arrow to lower the setting. To change the non-calling system temperature setting, press the neXT key to switch from heat to cool setting or cool to heat setting and use the

 and

arrows to set the temperature. The mode in which the set point is being established will be displayed underneath the set point temperature (ie. Heat will be displayed when establishing the set point for heating).

Day

We

Schedul e

MENU MODE

AM

Heat

Set To

Inside

NEXT ENTER

HEAT

SYSTEM

AUTO

FAN

Up/Down

Keys

adjusTinG rh seTPoinTs for humidiTy ConTrol.

(Only available with TSTBT4H2CPHM--A &

TSTBT4H2CPHMW-A model thermostats)

If a thermostat has an RH sensor, use the neXT key to select RH setting for dehumidification or humidifier control. Use the

 and

keys to raise or lower the RH setting.

RH setting

Day

We

Schedul e

AM

RH%

Set To

Inside

RH%

HEAT

MENU MODE NEXT ENTER

SYSTEM

AUTO

FAN

Indoor RH

seleCTinG oPeraTinG mode

There are four operating modes: Schedule Operation,

Temporary Hold, Permanent Hold, and Vacant Mode.

Press and hold the mode key to switch between

Schedule Operation, Temporary Hold, Permanent Hold, or

Vacant Mode.

In Schedule Operation, the temperature settings for heating and cooling are automatically set according to the

Morning, Daytime, Evening, and Night times and temperature settings for each day of the week. See the schedule programming section above on instructions how to establish temperature set points and time of day that each program will apply.

The Temporary Hold mode is activated when the

 or

 keys are pressed to adjust the temperature setting during the schedule operation. “TempHold” will be displayed instead of “Schedule” for the duration for the temporary set point once the back light has dimmed. The temperature settings are held for 3 hours and then will resume with the normal schedule settings for that specific time of day.

6 720 220 380 Subject to change without prior notice Revised 06-13

13 TsTbT4h2CP series setting the Time and day of the week

Permanent Hold mode is a permanent temperature override and ignores the schedule and maintains the settings established by the

 and

keys until the status is manually changed by the user.

The Vacant mode maintains the space to temperatures established by the user to minimize energy consumption while maintaining necessary space conditions when they are away for an extended amount of time; on vacation for example. This is a permanent holding feature until the status is manually changed by the user.

Press and hold the mode button until “Vacant” is displayed.

1. Use the

 and

buttons to establish the heating set point.

Caution

2. Push neXT.

3. Use the

 and

buttons to establish the cooling set point.

4. Push neXT.

5. Use the

 and

buttons to establish the humidity set point.

6. The back light will dim within 5 seconds and the settings will take affect.

DisplaysTempHold, Hold or Schedule.

Day

We

Schedul e

Caution

AM

HEAT

Inside

MENU

SYSTEM

AUTO

FAN MODE NEXT ENTER

Mode Key

seTTinG The Time and day of The weeK

The time of day and day of the week can be set using the

menu key or by pressing AM-PM key area shown in gray.

Press here to change

.

Day

We

Schedul e

AM

Heat

Set To

Inside

HEAT

SYSTEM

AUTO

FAN MENU MODE NEXT

Menu Key

ENTER

1. Press the “AM” or “PM” text or menu button once.

2. Use the

 or

button to adjust the hour of day.

Pay attention to ensure the PM or AM is set correctly

3. Push neXT to proceed to set the minutes.

4. Use the

 or

button to adjust the minutes.

5. Push neXT to proceed to set the Day of the week.

6. Use the

 or

button to adjust the Day of the week.

7. Push enTer to exit the setup menu and back to the home screen.

ENTER can be pressed at any time during the time setup procedure to exit the setup menu and back to the home screen

sChedule ProGramminG

All communicating Bosch thermostats are shipped with an energy saving pre-program. You can customize this default program by following the programming instructions below.

Day

We

Schedul e

Press here to change the Schedule.

AM

Heat

Set To

Inside

HEAT

ENTER

SYSTEM

AUTO

FAN MENU MODE NEXT

Menu Key

The thermostat schedule can be set by pushing the menu button twice or by pressing “Schedule” from the thermostat home screen. There are 4 different time periods for each day (Morn, Day, Eve, Night). Each time

6 720 220 380 Subject to change without prior notice Revised 06-13

14 TSTBT4H2CP SERIES

7 day Program schedule

period has two set points, one for Cooling Mode and one for Heating Mode.

1. From the thermostat home screen, press menu twice or “Schedule” to enter the Programming Setup Menu.

2. morn is the first time period displayed.

3. Use the

 or

button to adjust the start time for the current time period. The time duration is in 15 minute intervals.

4. Push neXT.

5. Set the set point for the Heating mode using the

 or

button. You will see “Heat” beneath the set point temperature.

6. Push neXT.

7. Set the set point for the Cooling mode using the

 or

button. You will see “Cool” beneath the set point temperature.

8. Push neXT.

9. The next time period is now displayed.

10. Repeat steps 3-8 to establish the start time for that time period and the heating and cooling set points for that time period.

11. Push neXT.

The current screen at this point is used to assign the current schedule being established to specific days.

7 day ProGram sChedule

(ConTinued from sChedule

ProGramminG)

The time schedule and set points have been determined, but they have not been assigned to specific day at this point.

The default setting for the TSTBT4H2CP Thermostat

Series is a 7 Day Schedule. All 7 days are displayed. All 7 days will utilize the schedule just created if no changes are made at this point.

12. Press enTer to apply the schedule just created to all

7 days of the week.

CusTom ProGram sChedule

(ConTinued from sChedule

ProGramminG)

Some days may require a different schedule program; whether it be a different time period definition or different heating / cooling set points. To create specific schedules for specific days, continue from the Schedule

Programming Steps 1-11 from above and continue with the following instructions. Each day can have its own unique programmed schedule and set points; for a total of 7 possible unique schedules for the TSTBT4H2CP

Thermostat Series.

The decision to be made here is what days the scheduled program will be assigned to; this is accomplished by removing the days that the program will not be associated with. The remaining days being displayed are the days that the current schedule will be assigned to.

Picking up after step 11 from above:

Currently all 7 days are being displayed and an “01” is displayed in the u day. By pressing the

 or

button, you will see “Mon” appear or disappear. This is how you add or remove Monday from the current schedule program. The

button adds “Mon” to the list of days affected, the

button removes “Mon” from the list of days affected.

Creating a 5+2 Schedule Example (Weekday Schedule +

Weekend Schedule):

13. Press the neXT button until “06” is displayed in the upper right hand corner (Day 6 which is Saturday).

14. Press the

button to remove “Sat” from the days being displayed.

15. Press the neXT button to change the day number to

“07” (Day 7 is Sunday).

16. Press the

button to remove “Sun” from the days being displayed.

17. Currently you should only see Mon, Tue, Wed, Thu, Fri being displayed. Press enTer button.

You should now be back to the thermostat home screen and the schedule that was just created has been applied to Mon-Fri.

18. Repeat Steps 1-11 from above establishing times and set points to apply for the weekend (Sat & Sun).

19. All days should be displayed and “01” should be in the upper right hand corner. Press the

button to remove “Mon” from the days being displayed.

20. Press the neXT button to change the day number to

“02” (Day 2 is Tuesday).

21. Press the

button to remove “Tue” from the days being displayed.

6 720 220 380 Subject to change without prior notice Revised 06-13

locking the Thermostat

TsTbT4h2CP series 15

22. Continue in this fashion to remove “Wed”, “Thu”, &

“Fri’ from the days being displayed.

3. Press enTer

Press enTer button.

You should now be back to the thermostat home screen and the schedule that was just created has been applied to Saturday and Sunday.

loCKinG The ThermosTaT

If the key locking option was enabled in the Tech Menu

Setup (Option #26), the keys can be locked or unlocked to keep unauthorized changes to the thermostat. With the thermostat locked, no changes can be made; including set point temperatures, operation mode, and fan control.

If the thermostat is unlocked, “Lock” will be displayed, if the thermostat is locked, “Locked” will be displayed.

Day

We

Schedul e

AM

Heat

Set To

Inside

HEAT

Lock

MENU MODE NEXT ENTER

SYSTEM

AUTO

FAN

Caution

Hidden Lock key

hidden loCK Key

To Lock the Thermostat

1. Push loCK and hold for 2 seconds (the screen shot below will be displayed).

The Cancel key (blank key-second from the left) can be pushed at any time to cancel out of the sequence and will return to the home screen without changes saved.

To Unlock the Thermostat

1. Push loCKed and hold for 2 seconds (the screen shot below will be displayed).

2. Push the

button until the two digit code is displayed in the upper right hand corner (see the screen shot below).

3. Press enTer.

The Cancel key (blank key-second from the left) can be pushed at any time to cancel out of the sequence and will return to the home screen without changes saved.

disPlayinG The Time and

TemPeraTure sChedule

The complete lime and temperature schedule can be displayed.

By pressing the menu button 4 times from the thermostat home screen, the display below appears

2. Push the

button until the two digit code is displayed in the upper right hand corner (see the screen shot below).

Repeatedly press the neXT key to display the scheduled times and temperature settings. The factory set schedule is shown on the following page.

Revised 06-13 Subject to change without prior notice 6 720 220 380

16 TSTBT4H2CP SERIES 7 day factory default Program

Day of the

Week

Weekday

Saturday

Sunday

7 day factory default Program

Time Period Time

Setpoint

Events Time

Temperature (Heat)

Morn

6 a.m. 70° F (21° C)

Day

8 a.m. 62° F (17° C)

Eve

6 p.m. 70° F (21° C)

Setpoint

Temperature (Cool)

78° F (26° C)

85° F (29° C)

78° F (26° C)

Night

10 p.m. 62° F (17° C) 82° F (28° C)

Morn

6 a.m. 70° F (21° C) 78° F (26° C)

Day

8 a.m. 62° F (17° C) 85° F (29° C)

Eve

6 p.m. 70° F (21° C) 78° F (26° C)

Night

10 p.m. 62° F (17° C) 82° F (28° C)

Morn

6 a.m. 70° F (21° C) 78° F (26° C)

Day

8 a.m. 62° F (17° C) 85° F (29° C)

Eve

6 p.m. 70° F (21° C) 78° F (26° C)

Night

10 p.m. 62° F (17° C) 82° F (28° C)

use The Table below To Plan your CusTomized

ProGram sChedule if usinG 5+1+1.

Day of the

Week

Weekday

Custom user schedule

Time Period Time

Setpoint

Events Time

Temperature (Heat)

Morn

Day

Eve

Setpoint

Temperature (Cool)

Saturday

Sunday

Night

Morn

Day

Eve

Night

Morn

Day

Eve

Night

6 720 220 380 Subject to change without prior notice Revised 06-13

Troubleshooting TSTBT4H2CP SERIES 17

TsTbT4h2CP ThermosTaT series insTallaTion TroubleshooTinG

Problem Possible Explanation Possible Solution

1

Display on thermostat not illuminated

Power is not available to the thermostat

1. Verify the unit circuit breaker is not tripped.

2. Detach the thermostat from wall plate and verify that all wires are connected on the base make sure the thermostat is properly seated on the wall.

2

3

4

5

6

7

8

9

10

No Cooling

No Heating

No Heating or Cooling

Heating comes on during a cooling call with a heat pump

"Filter" is displayed on the thermostat

"UV Bulb" is displayed on the thermostat

"HumPad" is displayed on the thermostat

Fan will not turn off

The set point will not go any higher or lower

Thermostat Settings are not correct

Thermostat Settings not correct

Thermostat has locked out compressor due to minimum off time setting

1. Verify that the thermostat mode is in “COOL”. If not, push the SYSTEM button until “COOL” is displayed.

2. Verify the set point temperature is not higher than the space temperature. If it is, use the (down) button to adjust the set point to below the space temperature to initiate a cooling call.

1. Verify that the thermostat mode is in “HEAT”. If not, push the SYSTEM button until “HEAT” is displayed.

2. Verify the set point temperature is not lower than the space temperature. If not use the (up) button to adjust the set point to above the space temperature to initiate a heating call.

Once the space temperature matches the set point temperature on the thermostat, the heating or cooling call is removed and the equipment turns off. If the user changes the set point temperature within the minimum off time, the equipment will not come on. This is a protection feature for the compressor and is normal.

Wait 10 min and verify if equipment has began operating in heating or cooling mode. If unit remains off, call a licensed technician.

Call a technician as the thermostat must be set up correctly. There are many settings to be made and should only be attempted by a trained technician.

The thermostat is not set up correctly for a heat pump.

The time duration for a filter change has been surpassed.

The time duration for a

UV bulb change has been surpassed.

The time duration for a

Humidifier Pad change has been surpassed.

Fan setting is set to ON instead of AUTO

Change the filter and reset the filter timer by pressing the area of where "Filter" is displayed

Call a technician for UV Bulb maintenance.

Call a technician for Humidifier pad maintenance.

Press the FAN button to change the status to AUTO

The set point limits have been reached

There is a maximum temperature in heating that cannot be surpassed and a minimum temperature in cooling that cannot be surpassed. The technician who installed the thermostat may have set these limits to protect the equipment. The end user should not modify these settings and should consult with a trained technician who is familiar with the equipment being used.

Revised 06-13 Subject to change without prior notice 6 720 220 380

Troubleshooting

Problem

11

A fault code is being displayed on the thermostat screen

Possible Explanation Possible Solution

Reference the Fault Code section in this manual to indentify the fault

Consult a licensed professional if any of the following faults occur: HP1, HP2, LP1, LP2, FrA, CLA, bOA, EFA,

LEC, LHO, LCO

Consult the literature for the gateway for fault code LGC in order to re-establish communication with the gateway

13

14

15

17

18

19

Loss of Equipment

Communication / No

Communication

Verify that the COM LED on the TRM at the equipment is blinking green. If it is red, please call for technical assistance.

Equipment is not responding to thermostat changes

Loss of Equipment

Communication COM

LED light is red on the

TRM

There is not power to the

TRM

Loose Wiring on thermostat

Loose Wiring on TRM

Check the circuit breaker that powers the air conditioning unit if it is tripped please reset it.

If after resetting the breaker the TRM LEDs are not lit, please contact the local a technician

Remove the thermostat from the back mounting plate and ensue that all 4 wires are securely seated in the terminals. Also verify that there are not wire strands present as this will cause a short.

Remove the cover off of the TRM and verify that all wires are securely seated in the terminals.

Compressor(s) comes on in Heating when using AC with electric heat

Heat Pump is in cooling mode when thermostat is in heating mode or vise a versa

Thermostat is set up to operate a heat pump

"O" terminal is being used when the "B" terminal should be or vise a versa

Thermostat was not set correctly by the technician, please contact local technician.

Thermostat was no installed correctly please contact local technician

The thermostat setpoint is not satisfied, yet there is no heating or cooling call to the equipment

Menus described in the Tech Menu Setup

Table are not available on the thermostat

Remote room temperature sensors are connected and average the space temperatures with the thermostat

Missing menu does not apply to the equipment being used

When remote room temperature sensors are connected to the TRM, the space temperatures from the thermostat and the room sensor(s) are averaged. It is possible to have the thermostat not satisfying the set point and still not have the equipment running. The average of the sensor(s) and the thermostat has satisfied the setpoint.

When the equipment type is chosen using Option #3, certain features or options will not apply. When this is the case, that menu setup is skipped when going through the list of menu setup options.

available aCCessories for The TsTbT4h2CP ThermosTaT series

Descriptive Part Number

ZONB-OTS---M--A

Bosch Part Number

7738002978

Description

Outdoor Temperature

Sensor / Remote Room

Temperature Sensor

Model Compatibility

TSTBT4H2CP-M--A

TSTBT4H2CPHM--A

ZONB-LAS---M--A

TSTB--TRM--6--A

7738002979

7738002948

Leaving Air Temperature

Sensor

Translator Communicating

Remote Module

TSTBT4H2CP-M--A

TSTBT4H2CPHM--A

TSTBT4H2CPHMW-A

TSTBT4H2CP-M--A

TSTBT4H2CPHM--A

6 720 220 380 Subject to change without prior notice Revised 06-13

Product limited warranty

TSTBT4H2CP SERIES 19

Contact your local Bosch Dealer or Installing Contractor for product support.

field Technical support:

Your local Bosch contractorwww.bosch-climate.us

ProduCT limiTed warranTy models Covered

This limited warranty is provided by FHP Manufacturing

Company (“FHP”) and covers the Bosch TST Thermostat

(hereinafter referred to as “Product”). This warranty is provided to the original purchaser of the Product as long as the Product remains installed at its original place of installation.

warranTy CoveraGe limited warranty

FHP warrants that all internal components incorporated into the Product at the time of shipment by FHP shall remain free from defects in workmanship and materials for the shorter of five (5) years from proof of certificate of occupancy date, five (5) years from proof of certified start up date or six (6) years from date of manufacture provided it is installed and properly maintained by a qualified and trained HVAC contractor and the other conditions of this warranty are met. If FHP determines that the Product has a defect in workmanship or materials, FHP, at its option, will repair or replace the defective part.

iTems noT Covered

This limited warranty does not cover the following circumstances:

1. Components or parts not provided by FHP.

2. Components or parts on which the tags or nameplates have been removed, altered or defaced.

3. Scratches in or discoloration of finishes.

4. Serviceable items and normal maintenance as required per the Installation and Maintenance

Manual.

5. The workmanship of any installer. FHP disclaims and does not assume any liability of any nature for unsatisfactory performance caused by improper installation, repair or maintenance.

6. Any labor or material costs for removal, reinstallation, repair and replacement of the defective component or part.

7. Electricity or fuel costs, or any increases or unrealized savings in same, for any reason whatsoever.

8. Damage caused by excessive temperatures or pressures, fuel or gas explosion, electrochemical reaction, water and air impurities, electrical failures, use during construction, flooding or acts of God.

9. Any damage or failure resulting from the introduction of harmful chemicals, caustic fluids, or liquids detrimental to any unit component, including but not limited to improperly applied or maintained heat transfer fluids or chlorinated pool or spa water

10. Any damage or failure resulting from improper unit sizing.

11. Shipping charges, delivery expenses or administrative fees incurred by the purchaser in repairing or replacing the Product.

CondiTions of warranTy

The warranty herein is void under the following circumstances:

1. Failure or malfunction resulting from improper or negligent operation, accident, abuse, freezing, electrical imbalance characteristics, misuse, unauthorized alteration, incorrect electrical supply, electrical surges, or improper installation, repair or maintenance. See the Installation and Maintenance

Manual for installation and maintenance information.

2. Failure or malfunction resulting from any conditions within the structure, including mold and/or mildew and/or any chemical or toxin secreted there from or damage resulting from mold, fungus or bacteria.

3. Failure or malfunction resulting from a contaminated or corrosive air or liquid supply, the addition of unapproved chemicals, operation at abnormal temperatures, pressures or flow rates, opening of the refrigerant circuit by unqualified personnel or any attachment, accessory or component not authorized and approved by FHP. See the Installation and

Maintenance Manual for installation and maintenance information.

4. Failure or malfunction due to misapplication or faulty building design or construction, including inadequate refrigerant levels, condensate drain, duct work design or installation.

Revised 06-13 Subject to change without prior notice 6 720 220 380

Caution

Caution

20 TsTbT4h2CP series

Product limited warranty

5. Product on which payment to FHP is or has been in default.

6. Work performed without prior authorization or approval and without authorization/requisition number and without proper documentation verifying compliance with above terms.

limiTed warranTy

OTHER THAN THE OBLIGATIONS OF FHP EXPRESSLY SET

FORTH HERIN, fhP disClaims all warranTies,

eXPress or imPlied, inCludinG buT noT limiTed

To any imPlied warranTies of merChanTabiliTy

or fiTness for a ParTiCular PurPose. FHP’S

SOLE OBLIGATION WITH RESPECT TO THE PRODUCT

AND PurChaser’s eXClusive remedies are seT

forTh in The foreGoinG limiTed warranTy. fhP shall noT be liable for any indireCT, PuniTive, inCidenTal, sPeCial, ConsequenTial or similar

damaGes INCLUDING, WITHOUT LIMITATION, INJURY

OR DAMAGE TO PERSONS OR PROPERTY OR DAMAGES

FOR LOSS OF USE, LOST PROFITS, INCONVENIENCE OR

LOSS OF TIME.

Note that any repaired or replaced product will be warranted for only the unexpired tem of the original warranty.

65th Court, Ft. Lauderdale, FL 33309. To process your claim, you will need a copy of your original invoice or other proof of purchase, the product serial number and documentation showing the original installation date and location. The alleged defective components or parts must be returned to FHP in accordance with FHP procedure then in force for handling goods returned for the purpose of inspection to determine cause of failure (contact FHP if you have questions regarding the return process). If FHP determines that the returned components and/or parts are defective and that this warranty applies, FHP will furnish the repaired or replacement components and/or parts to the contractor who installed your Product.

This Warranty applies to FHP products installed in the

Continental United States and Canada only.

Some states do not allow the exclusion of limitation of damages, or limitations on how long an implied warranty lasts, so the above limitations and exclusions may not apply to you.

warranTy Claims ProCess

If you have a warranty claim you should notify the contractor who installed your Product and ask that the contractor notify FHP Manufacturing Company, 601 N.W.

6 720 220 380 Subject to change without prior notice Revised 06-13

TSTBT4H2CP SERIES 21

Revised 06-13 Subject to change without prior notice 6 720 220 380

22 TSTBT4H2CP SERIES

6 720 220 380 Subject to change without prior notice Revised 06-13

TSTBT4H2CP SERIES 23

Revised 06-13 Subject to change without prior notice 6 720 220 380

601 N.W. 65th Court, Ft. Lauderdale, FL 33309

Phone: 866-642-3198 | Fax: 954-776-5529 www.bosch-climate.us

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals