Eaton 9170+ UPS
Product Brochure
Eaton 9170+ UPS
Features
•N+X redundancy for both power and logic eliminates systemlevel single point-of-failure
•Easily scalable to adapt to changing IT environments by simply
adding power and/or battery modules
•True double-conversion design
•Universal components fit in any order without affecting UPS
operation
•Provides protection against all nine power problems
•Complete offering of power management software included to
ensure data integrity
•Provides investment protection with a two-year limited warranty
and a $250,000 load protection guarantee (U.S. and Canada)
Product Snapshot
Power Rating:
3–18 kVA
Input Voltage:
200–240 Vac
Output Voltage: 200–240 Vac
Frequency:
50/60 Hz (auto-sensing)
Configuration:
Tower or rackmount
The Eaton® 9170+ UPS is uniquely designed to meet the
everchanging needs of customers with applications such as data
centers, networks and call centers. Built for global deployment,
the 9170+ is a scalable, modular, flexible solution that combines
the highest level of reliability with the lowest cost of ownership in
the 3–18 kVA range.
The 9170+ enables customers to build a power solution specific to
their needs, with an expandable level of redundancy and increases
runtimes through plug-and-play 3 kVA UPS and battery modules.
The 9170+ can be configured to fit three-, six-, nine- or twelve-slot
enclosures, and is available for tower and rackmount applications.
The 9170+ also features a Power Saver mode, a user-selectable
feature that increases unit efficiency from 88% in normal
operating mode to 97%. With its low initial investment, doubleconversion technology, ABM battery management system and
high-efficiency. Power Saver mode, you never have to compromise
reliability for efficiency.
Unique to the 9170+ is its global deployment capability. By using
a high-frequency design, housing both logic and power in the
power module, and offering a single-cabinet design, distributors
and purchasing departments around the world have fewer system
components to contend with, regardless of where the system is
deployed.
Technical spotlight: Network
level N+X redundancy
As business moves from a “bricks and mortar” model to “clicks
and mortar,” the need for system availability at all levels of
enterprise is rising exponentially. From servers to routers to
telecommunication installations, the interdependence of the
technological components of the wired world can make systems
vulnerable to downtime. Many precautions and preventive
measures are taken when designing the network, including power
protection.
systems with a single-module UPS. The 9170+ overcomes this
potential obstacle with its modular design. Redundancy comes
from the 3 kVA power modules plugged into the system. For
example, if you have a 9 kVA solution, and are looking for N+2
redundancy, you only need a 15 kVA UPS (five power modules)
with the 9170+, instead of 18 kVA. That’s because the five
UPS modules run in parallel within the system, giving you N+2
redundancy, without the additional cost and space requirements.
In this shifting world, however, it’s becoming more evident that
simple power protection isn’t enough. A new level of reliability
is needed, one with redundancy, and thereby system availability.
Today users can opt for an even greater degree of redundancy,
with N+1, N+2, N+3, etc. However, this level of redundancy can
quickly become cost prohibitive if the user is creating redundant
The 9170+ eliminates a system-level single point-of-failure.
Because both the logic and power are housed in the module and
not in the enclosure, there is a redundancy for the entire UPS.
This is a critical distinction when looking for multiple levels of
redundancy in the UPS, as there is inherent vulnerability in a UPS
that limits redundancy in any part of the system.
Sample configuration
With a variety cabinet sizes and a user-friendly design you can
configure the scalable and redundant 9170+ with 3 kVA power
modules and battery modules to grow with your requirements.
5 power modules:
15 kVA or
12 kVA N+1 or
9 kVA N+2
20 battery modules
9-slot UPS enclosure
2
EATON Eaton 9170+ UPS
9-slot battery enclosure
PRE-CONFIGURED SYSTEMS WITH HARDWIRE INPUT AND OUTPUT
Power
rating
Input
connection
Output
connections
Dimensions
(H x W x D in/cm)
Weight
(lb/kg)
(1) 3-slot enclosure
(1) power module
(2) battery modules
(1) caster kit
3 kVA expandable
to 3 kVA N+1
Hardwired
Hardwired
19.5 x 17.0 x 25.5/
49.5 x 43.0 x 65.0
155.0/69.9
(1) 6-slot enclosure
(1) power module
(2) battery modules
(1) caster kit
3 kVA expandable
to 9 kVA N+X
Hardwired
Hardwired
33.3 x 17.0 x 25.5/
84.5 x 43.0 x 65.0
155.0/69.9
(1) 6-slot enclosure
(2) power modules
(4) battery modules
(1) caster kit
6 kVA expandable
to 9 kVA N+X
Hardwired
Hardwired
33.3 x 17.0 x 25.5/
84.5 x 43.0 x 65.0
232.0/104.8
(1) 6-slot enclosure
(3) power modules
(6) battery modules
(1) caster kit
9 kVA expandable
to 9 kVA N+X
Hardwired
Hardwired
33.3 x 17.0 x 25.5/
84.5 x 43.0 x 65.0
346.0/156.7
PW9S9K
(1) 9-slot enclosure
(3) power modules
(6) battery modules
9 kVA expandable
to 18 kVA N+X
Hardwired
Hardwired
47.0 x 24.0 x 28.5/
119.5 x 61.0 x 72.5
389.0/176.7
PW12S9K
(1) 12-slot enclosure
(3) power modules
(6) battery modules
9 kVA expandable
to 18 kVA N+X
Hardwired
Hardwired
60.7 x 24.0 x 28.5/
154.5 x 61.0 x 28.5
427.0/193.7
PW12S12K
(1) 12-slot enclosure
(4) power modules
(8) battery modules
12 kVA expandable
to 18 kVA N+X
Hardwired
Hardwired
60.7 x 24.0 x 28.5/
154.5 x 61.0 x 28.5
504.0/228.6
PW12S15K:
(1) 12-slot enclosure
(5) power modules
(10) battery modules
15 kVA expandable
to 18 kVA N+X
Hardwired
Hardwired
60.7 x 24.0 x 28.5/
154.5 x 61.0 x 28.5
581.0/263.5
PW12S18K
(1) 12-slot enclosure
(6) power modules
(12) battery modules
18 kVA expandable
to 18 kVA N+X
Hardwired
Hardwired
60.7 x 24.0 x 28.5/
154.5 x 61.0 x 28.5
658.0/298.4
Model number
Included items
PW3S3K
PW6S3K
PW6S6K
PW6S9K
Pre-configured systems with hardwire input and receptacles output options
PW6S3K-PD
(1) 6-slot enclosure
(1) power module
(2) battery modules
(1) caster kit
3 kVA expandable
to 9 kVA N+X
Hardwired
(2) L14-30R,
(2) L6-30R,
(12) 5-20R
33.3 x 17.0 x 25.5/
84.5 x 43.0 x 65.0
192.0/86.9
(1) 6-slot enclosure
(2) power modules
(4) battery modules
(1) caster kit
6 kVA expandable
to 9 kVA N+X
Hardwired
(2) L14-30R,
(2) L6-30R,
(12) 5-20R
33.3 x 17.0 x 25.5/
84.5 x 43.0 x 65.0
269.0/121.8
(1) 6-slot enclosure
(3) power modules
(6) battery modules
(1) caster kit
9 kVA expandable
to 9 kVA N+X
Hardwired
(2) L14-30R,
(2) L6-30R,
(12) 5-20R
33.3 x 17.0 x 25.5/
84.5 x 43.0 x 65.0
346.0/160.7
PW9S9K-PD
(1) 9-slot enclosure
(3) power modules
(6) battery modules
9 kVA expandable
to 18 kVA N+X
Hardwired
(2) L14-30R,
(2) L6-30R,
(12) 5-20R
47.0 x 24.0 x 28.5/
119.5 x 61.0 x 72.5
389.0/176.7
PW12S9K-PD
(1) 12-slot enclosure
(3) power modules
(6) battery modules
9 kVA expandable
to 18 kVA N+X
Hardwired
(3) L14-30R,
(3) L6-30R,
(12) 5-20R
60.7 x 24.0 x 28.5/
154.5 x 61.0 x 28.5
427.0/193.7
PW12S12K-PD
(1) 12-slot enclosure
(4) power modules
(8) battery modules
12 kVA expandable
to 18 kVA N+X
Hardwired
(3) L14-30R,
(3) L6-30R,
(12) 5-20R
60.7 x 24.0 x 28.5/
154.5 x 61.0 x 28.5
504.0/228.6
PW12S15K-PD
(1) 12-slot enclosure
(5) power modules
(10) battery modules
15 kVA expandable
to 18 kVA N+X
Hardwired
(3) L14-30R,
(3) L6-30R,
(12) 5-20R
60.7 x 24.0 x 28.5/
154.5 x 61.0 x 28.5
581.0/263.5
PW12S18K-PD
(1) 12-slot enclosure
(6) power modules
(12) battery modules
18 kVA expandable
to 18 kVA N+X
Hardwired
(3) L14-30R,
(3) L6-30R,
(12) 5-20R
60.7 x 24.0 x 28.5/
154.5 x 61.0 x 28.5
658.0/298.4
PW6S6K-PD
PW6S9K-PD
Pre-configured systems with line cord input and receptacles output options
PW3S3K-LPD
(1) 3-slot enclosure
(1) power module
(2) battery modules
3 kVA expandable
to 3 kVA N+1
L14-30P
(1) L14-30R,
(1) L6-30R,
(4) 5-20R
19.5 x 17.0 x 25.5/
49.5 x 43.0 x 65.0
155.0/69.9
PW6S3K-LPD
(1) 6-slot enclosure
(1) power module
(2) battery modules
3 kVA expandable
to 6 kVA N+1
14-50P
(2) L14-30R,
(2) L6-30R,
(12) 5-20R
33.3 x 17.0 x 25.5/
84.5 x 43.0 x 65.0
192.0/86.9
PW6S6K-LPD
(1) 6-slot enclosure
(2) power modules
(4) battery modules
6 kVA expandable
to 6 kVA N+1
14-50P
(2) L14-30R,
(2) L6-30R,
(12) 5-20R
33.3 x 17.0 x 25.5/
84.5 x 43.0 x 65.0
269.0/121.8
Notes: 50/60 Hz automatic frequency selection. Input/Output voltages 208–240V or 100/200,120/208, 127/220, 110/220 and 120/240V. Split phase power module offers both high and low output voltage. Universal power
module offers only high output voltage. All 3- and 6-slot enclosure dimensions include caster kit.
EATON Eaton 9170+ UPS
3
UPS CABINET ENCLOSURES WITH HARDWIRE INPUT AND OUTPUT CONNECTIONS
Description
Power
rating
Input
connection
Output
connections
Dimensions
(H x W x D in/cm)
Weight
(lb/kg)
PW9170+ 3-slot
3 kVA
Hardwired
Hardwired
17.8 x 17.0 x 25.5/
45.0 x 43.0 x 65.0
66.0/30.0
PW9170+ 6-slot
3 to 9 kVA
Hardwired
Hardwired
31.5 x 17.0 x 25.0/
80.0 x 43.0 x 65.0
103.0/47.0
PW9170+ 9-slot
3 to 18 kVA
Hardwired
Hardwired
47.0 x 24.0 x 28.5/
119.5 x 61.0 x 72.5
158.0/72.0
Rack Mount
3 to 18kVA
Hardwired
Hardwired
110.0/50.0
PW9170+ 12-slot
3 to 18 kVA
Hardwired
Hardwired
Rack Mount
3 to 18 kVA
Hardwired
Hardwired
47.0 x 17.0 x 28.5/
119.5 x 43.0 x 72.5
60.8 x 24.0 x 28.5/
154.0 x 61.0 x 72.5
60.8 x 17.0 x 28.5/
154.0 x 43.0 x 72.5
6-slot battery cabinet
–
DC interconnect
option ASY-0525
required
–
31.5 x 17.0 x 25.0/
80.0 x 43.0 x 65.0
93.0/42.2
9-slot battery cabinet
–
DC interconnect
option ASY-0525
required
–
47.0 x 24.0 x 28.5/
119.5 x 61.0 x 72.5
148.0/67.1
12-slot battery cabinet
–
–
60.8 x 24.0 x 28.5/
154.0 x 61.0 x 72.5
186.0/84.4
Rack Mount
–
DC interconnect
option ASY-0525
required
–
–
60.8 x 17.0 x 28.5/
154.0 x 43.0 x 72.5
138.0/62.6
Split-phase power module
3 kVA/2.5 kW
–
–
4.2 x 14.1 x 15.3/
10.6 x 35.8 x 38.9
17.0/7.7
Universal-phase power module
3 kVA/2.1 kW
–
–
4.2 x 14.1 x 15.3/
10.6 x 35.8 x 38.9
17.0/7.7
–
–
–
4.2 x 7.0 x 14.8/
10.6 x 17.8 x 37.6
30.0/13.6
3 kVA
–
–
4.2 x 14.1 x 15.3/
10.6 x 35.8 x 38.9
17.0/7.7
196.0/89.0
148.0/67.0
Battery cabinet enclosures
Available modules
Battery module
20 amp charger module
TECHNICAL SPECIFICATIONS1
ELECTRICAL INPUT
GENERAL
Voltage
208–240V or 200/100, 208/120,
220/110, 240/120 Vac
Voltage range176–276V
Input power factor
.98
Frequency 50/60 Hz (±3 Hz)
Topology
Diagnostics
UPS bypass
Dimensions & weights
ELECTRICAL OUTPUT
ENVIRONMENTAL AND SAFETY
On utility voltage ±3% of nominal
regulation
On battery ±3% of nominal
voltage regulation
Efficiency
88% normal operation; 97% power saver
mode (optional programmable)
Frequency regulation
±3 Hz online; ±0.1 Hz on battery Safety markings UL, cUL EMC markings FCC class A
Surge IEEE/ANSI C62.41
suppression
Audible noise <50 dBA
Ambient operating/
0 to 40ºC (32 to 104ºF)/
storage temperature
-20 to 40ºC (60ºC without battery)
-4 to 104ºF (140ºF without battery)
Relative humidity
5% to 95%, non-condensing
REPO port
Meets NEC code 645-11 intent
and UL requirements
COMMUNICATIONS
LCD
4 x 20 character backlit display,
programmable
Language English, French, Spanish and German
support
Communication RS-232 (DB-9)
ports
Communication Two slots (standard)
slots
SNMP capability
Web/SNMP enabled card options
Contact closures
Relay card option
Emergency power off Input for external EPO
(EPO) general
True double-conversion online
Full system self-test on power up
Automatic on overload or UPS failure
See Pre-configured systems table
BATTERY
Internal battery type
Battery runtime
Battery replacement Recharge time
Sealed, lead-acid; maintenance free
See Battery Runtimes on back page
Hot-swappable
<4 hours standard
1. Due to continuing product improvement programs, specifications are subject to change without notice.
EATON Eaton 9170+ UPS
4
LCD panel
9170+ 9-slot configuration
3 kVA power or charger
module (one per slot)
Communication cards
Battery module (two per slot)
Maximum performance
Maximum availability
Maximum flexibility
• The lowest overall cost of
ownership is a direct result
of the low initial investment,
higher operating efficiencies
and programmable high
efficiency
• Double-conversion online
technology is universally
recognized as providing the
highest availability in an
internet-centric global
marketplace
• Modular design delivers
scalable, flexible solutions
to constantly changing
equipment requirements
• A UPS solution that is as
easy to install and operate as­
a­ PC­ —­ universal components
fit in any order in any
slot without affecting the
operation of the system or
its protection of the critical
load
• Provides protection against
all nine common power
problems
• Easily expanded by installing
additional power, charger or
battery modules to support
additional critical applications
and devices
Maximum service plans
• Internal options: line cord,
receptacles, communications
• Featuring user-friendly
LCD and two internal
communication slots, which
accept a wide variety of
connectivity devices and
the new ConnectUPS Web/
SNMP card
• Lightweight, highperformance power and
battery modules weigh under
30 pounds for easy service
and hot-swapping
Maximum reliability
• N+X power and logic
redundancy eliminates single
point-of-failure, providing
highest reliability and
availability
• Eaton Gold Plan Plus:
Enhance and extend your
standard UPS warranty with
added assurance of knowing
your UPS is installed and
operating properly from
the start
• Comprehensive coverage
for the entire UPS
Rackmount
Rackmount
configurations
Adding yet another level of
flexibility to the unique design
of the 9170+ is the ability to
configure it into a rackmount
solution. Imagine all the
standard benefits of the 9170+
installed in a standard 19-inch
computer rack with return
brackets.
• External options: rackmount
kit, casters (standard on
9- and 12-slot enclosures),
extended runtime battery
cabinets (housing up to 8
hours of additional runtime),
wall-mounted maintenance
bypass cabinets
• On-site startup by authorized
Eaton product representative
• Replacement UPS or module
delivered to your location
• Original UPS or module
picked up from your location
• Please call for details
• Redundant modularity
virtually eliminates downtime
and enhances serviceability
EATON Eaton 9170+ UPS
5
9170+ runtime charts
IN MINUTES (FULL LOAD/HALF LOAD) SPLIT-PHASE MODULE ASY-0673
1 String 2 String 3 String
4 String
5 String
6 String
7 String
Load (VA) number of strings (two battery modules per string)
8 String
9 String
10 String
3 kVA
6.5/16
16/40
27.5/67.5 40/98
53.5/132 67.5/167 83/204
98/242
115/283
132/324
6 kVA
6.5/16
11/27.5
16/40
21.5/53.5 27.5/68
33.5/83
40/98
46.5/115 53.5/132
9 kVA
6.5/16
9.5/23.5 13/31.5
16/40
20/49
23.5/58
27.5/67.5 31.5/78
12 kVA
6.5/16
9/21.5
11/27.5
13.5/33.5 16/40
19/46.5
21.5/53.5
15 kVA
6.5/168/20.510/2512/3014/3516/40
18 kVA
6.5/16
8/20
9.5/23.5 11/27.5
12.5/30
13 String 14 String 15 String 16 String 17 String
18 String 19 String 20 String 21 String 22 String
3 kVA 185/456
204/501
223/549242/595262/640 283/692302/750323/790345/850365/900
6 kVA
75/185 83/204
90/223
98/242
106/262
115/285
123/302
132/324
140/345
149/365
9 kVA
44/109 49/120
53.5/132 58/143
63/154
68/167
73/179
78/191
83/204
88/210
12 kVA 30.5/75 33.5/83 37/90
40/98
43/106
46.5/115 50/123
53.5/132 57/140
60/149
15 kVA 23/56
25/62
27.5/67.5 30/73.5
32.5/79.5 35/86
37.5/92
40/98
42.5/105 45/111
18 kVA 18/44
20/49
21.5/53.5 23.5/58
25.5/63
27.5/68
29.5/73
31.5/78
33.5/83
35.5/88
IN MINUTES (FULL LOAD/HALF LOAD) UNIVERSAL MODULE ASY-0674
1 String 2 String 3 String 4 String 5 String
6 String 7 String
3 kVA 8/24 24/59 43/95 58/140 80/175
6 kVA
8/24 16/40 24/59 32/83
9 kVA
8/24
13/35
18/46
12 kVA
8/24
13/33
15 kVA
8/24
18 kVA
13 String 14 String 15 String 16 String 17 String
11 String
12 String
149/365
167/408
60.5/149
67.5/167
35.5/88
40/98
24.5/60.5
27.5/68
18.5/45
20.5/50.5
14.5/35.5 16/40
23 String
24 String
387/955 408/1015
157/388
167/408
93/229
98/242
64/157
68/167
48/118
51/124
38/93
40/98
Load (VA) number of strings (two battery modules per string)
8 String
9 String
10 String
95/215 119/240135/290155/33565/365
40/10349/11458/14069/15683/175
24/59
29/63
35/86
40/103
46/115
16/40
19.5/43.5 24/59
29/70
33/80
11.5/31
14.5/31.5 18/46
20.5/51
24/58
8/24
11/31.5
13/36
15.5/41
18/45
18 String 19 String 20 String 21 String 22 String
3 kVA 225/500
245/540
270/600290/620315/650 335/690350/720365/780375/850395/890
6 kVA
113/335 123/255 135/273 143/290 148/315
156/333
165/350
175/365
183/385
190/395
9 kVA
63/150 73/165
80/178
86/190
93/200
100/210
107/225
115/240
121/255
125/270
12 kVA 47/110 52/121
56/130
58/140
65/147
70/156
75/165
80/175
85/185
90/195
15 kVA 34/83
38/94
41.5/103 44.5/113 46.5/117 51/127
56/130
58/140
61/149
66/158
18 kVA
27/6531.5/72
34.5/77
36/83 38/94 41/10044/10545/11548/12254/131
11 String
12 String
200/395 215/450
90/190 103/205
54/125
58/140
36/90
41/100
28/66
31/73
20.5/51
24/58
23 String
24 String
425/920 450/950
198/420
205/440
135/280
143/290
95/205
100/215
71/165
73/170
57/137 58/140
For additional information about the
9170+, please visit: Eaton.com/9170+
or call 800.356.5794.
Eaton
Electrical Sector
1000 Eaton Boulevard
Cleveland, OH 44122 USA
Eaton.com
Eaton.com/powerquality
© 2014 Eaton
All Rights Reserved
Printed in USA
9170PLFXA
May 2014
Eaton, PowerChain Management, LanSafe,
PowerVision and Forseer are registered
trademarks of Eaton.
All other trademarks are property of their
respective owners.
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertisement