Below you will find brief information for Power Meter EPR-04S. This power meter is a 3-phase powermeter and energymeter that can measure active power, active energy, reactive power, reactive energy, apparent power, and power factor. It has a MODBUS serial interface and can be connected to a PC for data analysis. The EPR-04S also measures maximum demand, demand, maximum and minimum values of power, all of which can be accessed through the device's interface or via MODBUS communication. It can connect up to 247 devices using a repeater.
PDF
Download
Document
Advertisement
Advertisement
DIGITAL POWERMETER DIGITAL POWERMETER EPR-04S EPR-04S EPR-04S DIGITAL POWERMETER FUNCTIONS OF BUTTONS EPR-04S is a 3-phase digital powermeter and energymeter which measures: -Active Power (W) -Active Energy (kWh) -Reactive Power (VAr) -Reactive Energy (kVArh) -Apparent Power (VA) -Cosj EPR-04S PC CONNECTION These values are scrolled between by the set button ( ) First 3 displays show L1, L2 and L3 phase values and the 4th display show total value of each selected measured value (W, VAr,VA,kWh or kVArh). EPR-04S also measures Maximum Demand, Demand, maximum and minimum values of power. EPR-04S has MODBUS serial interface. 31 DEVICE CAN BE CONNECTED AT SAME LINE MAX. 1200 mt. SET When : RS485/RS232 CONVERTER B A 1. W led lights: Active Power 2. VAr led lights: Reactive Power 3. VA led lights: Apparent Power 4. kWh led lights: a-) A-I :Imported Active Energy b-) A-E : Exported Active Energy 5. KVArh led lights: a-) r-L :Reactive-Inducitive Energy b-) r-C :Reactive-Capacitive Energy 6. Cosj led lights :Cosj of the network is measured. PC GND ESC Current Transformer Ratio Setup In this menu, current transformer ratio is adjusted. Note: If the current transformer is not used between the system and EPR-04S, current transformer ratio is entered as 1. Example: ; If a current transformer which has a ratio of 250/5A is used between the system and EPR-04S; Current transformer ratio is entered as = 250/5 = 50 . Push SET button 5 seconds L1 L2 L3 (Ctr menu is displayed) DIGITAL POWERMETER Push SET button (The number which k L1 EPR- 04S is the last digit of second display Cosj blinks) Operating Principle: TR B A GND ... EPR-04S-31 TR B A GND TR B EPR-04S-2 A GND EPR-04S displays the energy and power values by multiplying voltage and current ratios by values read from input. So, the displayed values are the real values of system. Energy Pulse Outputs EPR-04S has 2 Energy Pulse Outputs; Pul1, Pul2. Pul1 (Reactive Energy Pulse Output): A 400msec. pulse output is given, if measured energymeter value increases 1 KVArh. Pul1 is used for Reactive Inductive energy values. Pul2 (Active Energy Pulse Output): A 400msec. pulse output is given, if measured energy meter value increases 1KWh. Pul2 is used for both (Active Import) and (Active Export) energy values. Min. pulse period is 1.6 sec. 9 PIN CONNEKTOR EPR-04S-1 MAX. 1200 mt. MAX. 1200 mt. RS485/RS232 CONVERTER ... EPR-04S-247 ... PC Phase Monitoring Display EPR-04S-31 EPR-04S-2 EPR-04S-1 REPEATER Kilo led L1 Mega led L2 L2 Cosj W k S M 64EPR4S0/10-05 DIGITAL POWERMETER L2 In this menu, voltage transformer ratio is adjusted. Note: If the voltage transformer is not used between the system and EPR-04S, voltage transformer ratio is entered as 1. Example: ; If a voltage transformer which has a ratio of 34.5KV/100V is used between the system and EPR-04S; Voltage transformer ratio is entered as = 34500/100 = 345 L3 k L3 M EPR-04S VAr VA kWh kWArh Voltage Transformer Ratio Setup Esc Down ESC DIGITAL POWERMETER W k S M Push SET button when (SAU SEt yES) appears at the display. (When SAU SEt yES appears at the display,If you push ESC button or choose no option instead of yES option, new data will be canceled and previous value will be activated. Set SET k VAr VA kWh kWArh L3 Push ESC button one by one until (SAU SEt yES) appears at the display. Up L1 Cosj L2 k L3 M Push set button,Ctr is displayed. (Data is entered but is not activated yet. For activating the new data please follow the below steps). EPR- 04S Total (S) Monitoring Display 8 Cosj 000 k L2 M By using UP-DOWN buttons, enter to the last digit of desired value. kWh kVArh k L2 M SET ESC L1 k L1 M k k L1 M 000 k By using UP-DOWN buttons, enter to the second digit of desired value Set Push SET button (The number EPR-04S Esc which is the last digit of third display blinks). If you did not enter the second digit correct, you can reentry by pressing the ESC button DIGITAL POWERMETER k L3 k S L3 kWh kVArh Push SET button (The number which is in the middle of the third display blinks. If you did not enter the third digit correct, you can reentry by pressing the ESC button. Phase Monitoring leds L1 k L3 k By using UP-DOWN buttons, enter to the third digit of desired value. Min. and Max. values are defined for Active Power(W),reactive power(VAr) and apparent power(VA). Demand values are defined for total active power(W),total reactive power(VAr) and total apparent power(VA). If measured instant value is smaller than min. value which was stored before, it is stored as new min. value. If measured instant value is greater than max. value which was stored before, it is stored as new max. value. Demand value is the smallest value of the measured values in demand time. If the smallest value of the measured values (for example 15 minute) in demand time is greater than the demand value which was stored before, it is stored as new demand value. If one of defined parameters is displayed when deman button is pressed , min.,max or demand values are displayed. When an undefined parameter is displayed if demand button is pressed, instant value is continued to display. For example when power factor is displayed instant values are continued to display because min., max. and demand values are undefined. CONNECTOR (DB9) L2 Push SET button (First number of the third display blinks). If you did not S enter the fourth digit correct, you can reentry by pressing the ESC button. Watching of Min.,Max. and Demand Values: B A GND TRB A GND By using UP-DOWN buttons enter to the fourth digit of desired value. Demand and Maximum Demand Demand is average of power for the demand time. Demand time can be changed between 1-60 minutes. Maximum demand is the max. value of the average power values measured during demand time. If the new average value exceeds the maximum demand value, the new demand value is recorded as maximum demand. U P TO 2 4 7 D E V I C E C A N B E C O N N E C T E D AT S A M E L I N E B Y U S I N G R E P E AT E R . When W led lights,it shows max.power values which are measured instantaneously and it shows total average demand values. Also it is used for moving upwards in the menu. When W led lights,it shows min.power values which are measured instantaneously and it shows total average demand demand values. Also it is used for moving downwards in the menu. It is used for passing between parameters such as W, Var, VA, KWh, KVArh, cosj. When it is pressed for 5 second, adjustment mode is entered. In the adjustment mode it is used for saving parameters and moving to the sub menu. In the adjustment mode, it is used for entering to the upper menu or it is used for quiting from the adjustment mode without saving the values. Push SET button 5 seconds (Ctr menu is displayed) Set By using UP-DOWN buttons find the Utr menu. Esc Push SET button (The number which is the last digit of second display blinks) 1 DIGITAL POWERMETER DIGITAL POWERMETER EPR-04S EPR-04S Push SET button 5 seconds (Ctr menu is displayed) 000 k SET L1 k L1 M Cosj 000 W k L2 M L2 L3 VAr VA kWh kWArh Push set button,Utr is displayed. (Data is entered but is not activated yet. For activating the new data please follow the below steps. L1 Push SET button 5 seconds (Ctr menu is displayed) Push ESC button one by one until (SAU SEt yES) appears at the display. Push SET button whenl (SAU SEt yES) appears at the display. (When SAU SEt yES appears at the display,If you push ESC button or choose no option instead of yES option, new data will be canceled and previous value will be activated. Bu using UP-DOWN buttons find Pýn menu. Push SET button (Pýn ACt menu is displayed.) Demand Time Setup: L1 Push SET button 5 seconds (Ctr menu is displayed) L1 L2 L3 DIGITAL POWERMETER k Cosj EPR- 04S L3 By using UP-DOWN buttons, enter to the second digit of desired value S By using UP-DOWN-SET button enter the new password 000 k SET Cosj L1 k L1 M Cosj 000 W k L2 M L2 L3 k L3 M VAr VA kWh kWArh DIGITAL POWERMETER Esc Voltage Measuring Input k L1 M W k L2 M L2 L3 k L3 M VAr VA kWh kWArh Set k S M EPR-04S Esc DIGITAL POWERMETER L1 L2 L3 N 1 4 2 3 IL1 5 6 k K L1 L2 l L 7 8 9 10 In this menu, values of min.,max. or energymeters are erased. It saves the instantaneously measured min. and max. values of EPR04S into its memory. Please kindly look at to the section of FUNCTIONS OF BUTTONS for min. and max. values. Note: Informations which are saved to the memory are not affected from the electric interruptions. In the CLr dE or En menu ; when you choose and quit from all menus, if you confirm the changes,min. and max. values of all parameters or values of energymeters are erased at the same time.For erasing the values of min. and max. or energymeter;In the measurement position, By using UP-DOWN buttons find Pýn menu. L1 Push SET button (Pýn ACt menu is displayed.) L2 2 L2 L3 Cosj l L + _ 18 17 16 15 24 23 22 21 20 19 TR B A GND RS-485 18 17 16 15 TR B A GND RS-485 k K l L k K 4 5 6 2 3 IL2 IL3 Un 7 8 9 10 13 14 l L k K L2 l L k K L3 Current Measuring Input IL1 L1 L2 L3 N 2 3 4 5 6 k K L3 IL2 IL3 7 8 9 10 l Lk K l L 3 Phase without neutral current input with Aron wiring configuration Max: 30 VDC + _ (12-48V DC) + + - 18 17 16 15 24 23 22 21 20 19 TR B A GND RS-485 Voltage Measuring Input Auxiliary Supply Un 13 14 1A l L k K N 1A Max: 30 VDC Voltage Measuring Input L2 ESC N 1 + + - L1 SET L1 L2 L3 IL1 L1 24 23 22 21 20 19 1 000 13 14 Auxiliary Supply Current Measuring Input + _ EPR- 04S kWh kVArh Voltage Measuring Input Un (12-48V DC) k k k K Max: 30 VDC Auxiliary Supply 3 Phase neutral DIGITAL POWERMETER k L3 k Push SET button (The number S which is the last digit of second display blinks) 3 Phase without neutral current input with Aron wiring configuration 1A N L1 L3 + + - IL3 L3 Push SET button 5 sn. (Ctr menu is displayed) Monitoring and Erasing of minimum and maximum values: l L (12-48V DC) IL2 This menu is used for activating the user password. After the user password is activated for entering to the menus; while the instant values are observed,user password is required if the button is pushed for 5 sn. If the user password is entered wrong device does not latch Note: Factory default value of user password is 1234 For activating the user password; In the measurement mode, Push SET button when (SAU SEt yES) appears at the display. (When SAU SEt yES appears at the display,If you push ESC button or choose no option instead of yES option, you quit from adjustment menu without saving new settings and device continues to work with previous settings. L2 Max: 30 VDC Current Measuring Input Activating the user password: Push ESC button one by one until (SAU SEt yES) appears at the display. l L IL3 SET Push SET button when (SAU SEt yES) appears at the display. (When SAU SEt yES appears at the display,If you push ESC button or choose no option instead of yES option, you quit from adjustment menu without saving new settings and device continues to work with previous settings. Set k S M Push set button,dt is EPR-04S displayed. (Data is entered but is not activated yet. For activating the new data please follow the below steps). k K IL2 ESC Push SET button, Pýn CHg is displayed. Data is entered but is not activated yet. For activating the new data please follow the below steps). Push ESC button one by one until (SAU SEt yES) appears at the display. Push SET button (The number which is the last digit of third display blinks). If you did not enter the second digit correct, you can reentry by pressing the ESC button. k K L1 24 23 22 21 20 19 EPR- 04S 000 k By using UP-DOWN-SET button reenter the new password. ESC IL1 N L3 kWh kVArh L3 k 000 L2 L1 N (12-48V DC) k Cosj ~ 1A l L RS-485 + _ By using UP-DOWN-SET button enter the old password kWh kVArh Un IL3 3 Phase without neutral DIGITAL POWERMETER k k L3 k L3 IN1 L2 Push SET button (The number which is in the middle of the third display blinks.) ESC L2 L2 l L k K Gnd A B TR Auxiliary Current Measuring Input Supply Voltage Measuring Input + + - L1 By using UP-DOWN buttons find the dt menu. By using UP-DOWN buttons, enter to the last digit of desired value. L1 By using the UP-DOWN buttons S find Pýn CHg menu. In this menu,demand time is adjusted . k K IL2 PR-16 Box Connection Diagram This menu is used for changing the user password . Note: Factory default value for user password is 1234 For changing the user password;In the measurement mode, Esc IL1 N L3 L2 Changing of User Password: Set EPR-04S DIGITAL POWERMETER L2 L1 N 1A L1 In this menu user password is defined and activated. You must define and activate a 4 digit user password for preventing device settings from the illegal usage. There are 2 sub menu under the Pýn menu. k L3 M k S M ~ User password Setup: Push SET button (The number which is the last digit of third display blinks). If you did not enter the second digit correct, you can reentry by pressing the ESC button By using UP-DOWN buttons, enter to the last digit of desired value. Un Push ESC button. By using UP-DOWN buttons, enter to the second digit of desired value RS-485 Auxiliary Current Measuring Input Supply Voltage Measuring Input Push SET button. (CLr dE is displayed) ESC Gnd A B TR IN2 INC PUL2 PUL1 PULC Push SET button (The number which is in the middle of the third S display blinks. If you did not enter the third digit correct, you can reentry by pressing the ESC button. By using the UP-DOWN buttons ; If you want to delete the values choose yEs, if not choose no. IN1 kWh kVArh L3 k IN2H IN2L IN1H IN1L PUL1H PUL1L PUL2H PUL2L Push SET button.(CLr dE no menu is displayed) k (12-48V DC) - + - + (12-48V DC) - + - + Current Measuring Input L1 L2 L3 N IL1 1 4 5 6 2 3 IN2 INC PUL2 PUL1 PULC Cosj EPR- 04S + _ + _ By using the UP-DOWN buttons find the CLr dE or En menu. DIGITAL POWERMETER IN1 L3 IN2H IN2L IN1H IN1L PUL1H PUL1L PUL2H PUL2L L2 L2 k IN1 L1 IN2 INC PUL2 PUL1 PULC L1 Push SET button (First number of the third display blinks). If you did not enter the fourth digit correct, you can reentry by pressing the ESC button. By using UP-DOWN buttons, enter to the third digit of desired value. Max: 30 VDC Max: 30 VDC IN2 INC PUL2 PUL1 PULC By using UP-DOWN buttons enter to the fourth digit of desired value. IL2 18 17 16 15 TR B A GND RS-485 Auxiliary Supply IL3 Un 7 8 9 10 N 13 14 1A L1 L2 l L L3 3 Phase without neutral 7 k K l L k K l L 3 Phase without neutral current input with Aron wiring configuration N DIGITAL POWERMETER DIGITAL POWERMETER EPR-04S EPR-04S PR 19 Box Connection Diagram L1 K L2 k By using UP-DOWN buttons enter to the fourth digit of desired value. L K l L k L3 K l L k N 1 2 IL1 3 4 L1 K L2 k 5 IL2 ( 12-48V DC ) InC In1 In2 L3 6 IL3 1 6 5 Pul C ( 12-48V DC ) InC In1 In2 IL3 GND A B TR Pul 2 Auxiliary Supply Voltage Measuring Input 12 L2 8 L1 7 L1 N Push SET button (The number which is the last digit of third display blinks). If you did not enter the second digit correct, you can reentry by pressing the ESC button) N 10 L3 9 11 By using UP-DOWN buttons, enter to the last digit of desired value. 12 3 Phase neutral L1 N 3 Phase without neutral current input with Aron wiring configuration ESC W k L2 M L1 L2 K L2 k L K l L k L3 K l L k 1 2 IL1 3 4 5 IL2 L1 K L2 L3 L2 k EPR- 04S kWh kVArh By using UP-DOWN buttons find 000 k SET l 1 Pul 2 L2 8 Pul C Auxiliary Supply N 10 11 1A L3 9 4 5 IL2 Max: 30 VDC GND A B TR Voltage Measuring Input L1 7 IL1 3 ( 12-48V DC ) InC In1 In2 13 14 15 16 17 18 Pul 1 L2 8 L1 7 L1 N N 10 11 Max: 30 VDC Max: 30 VDC + _ Auxiliary Current Measuring Input Supply Voltage Measuring Input ~ L1 1A L2 L3 N L1 L2 L3 N k K IL2 l L Un ~ 1A k K l L L1 k K RS-485 Auxiliary Current Measuring Input Supply Voltage Measuring Input IL3 l L L2 L1 L2 L3 N IL1 IMPORTANT NOTE: In order communicate with ENTES software Baudrate has to be 38400 bps and parity has to be no MODBUS RTU PROTOCOL Standart MODBUS RTU message is shown below. T Adjustment of Parameters Adjustment of Device ADDRESS 12 By using UP-DOWN buttons find L1 N IL3 l L k K l L FUNCTION 8 BIT ADDRESS 8 BIT DATA NX8BIT CRCH CRCL T The T times corresponds to a time in which data must not be exchanged on the communication bus to allow the connected devices to recognize the end of one message and the beginning of another. This time must be at least 3.5 characters at the selected baud rate. Adress range (1-247 ) is address of the connected device. The data field contains data sent to the slave by master or data sent to master by slave. Push SET button 5 sec. bulun CRC is a error check method by using MODBUS RTU protocol and consists of 2 bytes. Push SET button again. Available Modbus Function: ESC 03H READ HOLD REGISTERS 06H PRESET SINGLE REGISTER 10H PRESET MULTIPLE REGISTERS Read Hold (03) function is used for reading measured values and transformers ratio. Registers can be read are between 0-68. For example to read phase1 voltage; 001 01 03 00 00 00 01 84 0A Push SET button when (SAU SEt yES) appears at the display. (When SAU SEt yES appears at the display,If you push ESC button or choose no option instead of yES option, you quit from adjustment menu without saving new settings and device continues to work with previous settings. 01 Device adres 03 Function 00 MSB adres 00 LSB adres 00 Register number MSB 01 Register number LSB 84 CRC MSB 0A CRC LSB Preset Single Register (06) function is used to set transformer ratio or for clearing one of min.,max., Demand values. Adjustment of Baud Rate Baud Rate can be chosen as a value of 1200,2400,4800,9600,19200, 38400 bps Push SET button 5 sec. k K 3 Phase without neutral current input with Aron wiring configuration 6 IL2 N L3 3 Phase neutral DIGITAL POWERMETER 002 Gnd A B TR IN2H IN2L IN1H IN1L PUL1H PUL1L PUL2H PUL2L IN2H IN2L IN1H IN1L PUL1H PUL1L PUL2H PUL2L RS-485 Push SET button when (SAU SEt yES) appears at the display. (When SAU SEt yES appears at the display,If you push ESC button or choose no option instead of yES option, you quit from adjustment menu without saving new settings and device continues to work with previous settings. VAr VA kWh kWArh Push ESC button one by one until (SAU SEt yES) appears (12-48V DC) - + - + Gnd A B TR W k S M Push SET button for saving the new value. + _ (12-48V DC) - + - + Push ESC button one by one until (SAU SEt yES) appears k L3 M By using UP-DOWN buttons adjust the desired value. PK 26 Box Connection Diagram Push SET button for saving the new value. L3 L2 EPR-04S has MODBUS RTU communication protocol which is optical isolated. All measured parameters can be transfer to the computer.Transformer ratios and parameters of communication can be set. Saved demand and energy values can erase Auxiliary Supply 3 Phase without neutral current input with Aron wiring configuration IL1 IL3 Pul 2 L3 9 By using UP-DOWN buttons adjust the desired value. Serial Communication GND A B TR Voltage Measuring Input 12 3 Phase without neutral Un 6 RS485 19 20 21 22 1A + _ Pul 1 2 Current Measuring Input RS485 19 20 21 22 13 14 15 16 17 18 l 6 IL3 + _ Pul C ( 12-48V DC ) InC In1 In2 000 L k Current Measuring Input Max: 30 VDC Cosj K bulunuz Push SET button again. ESC Push SET button, Pýn ACt oF is displayed (Data is entered but is not activated yet. For activating the new data please follow the below steps) Push ESC button one by one until (SAU SEt yES) appears at the display.. k L2 M ESC Push SET button 5 sec. k Push SET button whenl (SAU SEt yES) appears at Set the display. (When SAU EPR-04S Esc SEt yES appears at the display,If you push ESC button or choose no option instead of yES option, new data will be canceled and previous value will be activated. l L3 Adjustment of Parity: Parity can be adjust as NO, ODD or EVEN. DIGITAL POWERMETER Cosj k L1 M L Push SET button when (SAU SEt yES) appears at the display. (When SAU SEt yES appears at the display,If you push ESC button or choose no option instead of yES option, you quit from adjustment menu without saving new settings and device continues to work with previous settings. DIGITAL POWERMETER L1 L1 Push ESC button one by one until (SAU SEt yES) appears VAr VA kWh kWArh k 600 Push SET button for saving the new value. L3 k L3 M L3 k S L2 By using UP-DOWN buttons adjust the desired value. k S M L1 By using UP-DOWN buttons, enter to the second digit of desired value RS485 19 20 21 22 13 14 15 16 17 18 Pul 1 1A 11 4 IL2 Current Measuring Input Auxiliary Supply N 10 L3 9 3 Max: 30 VDC Pul 2 L2 8 L1 7 2 IL1 1A + _ Pul 1 l Cosj GND A B TR Voltage Measuring Input L1 k L1 M 000 RS485 19 20 21 22 13 14 15 16 17 18 L k + _ Pul C K l l Current Measuring Input Max: 30 VDC Push SET button (First number of the third display blinks). If you did not enter the fourth digit correct, you can reentry by pressing the ESC button By using UP-DOWN buttons, enter to the third digit of desired value. Set Push SET button EPR-04S Esc (The number which is in the middle of the third display blinks. If you did not enter the third digit correct, you can reentry by pressing the ESC button) L ESC Current transformers ratio can be set 5-10000, voltage transformer ratio can be set 1-2000 min.,Max. and Demand values can be only clear. If sent value is outside of this range device responds with an error message. Setting CT to 100; By using UP-DOWN buttons find Push SET button again. 9 3 DIGITAL POWERMETER DIGITAL POWERMETER EPR-04S EPR-04S You may change setup parameters using the MPR-SW-1 / SW-2 Software: Set Transformer ratios, Reset Energy and Demand values and change the device address up to 247. MPR-SW-2 can communicate with multiple (max. 247) EPR-04S devices. The setup software will install the MPR-SW-1/SW-2 Software under START -> ENTES -> Mpr-SW.exe directories. You may browse and run it 18 90mm 90mm 96mm 143 79.3mm 70mm 121 34.5 138.4 143 Type PR 19 (96x96) DESCRIPTION 58mm 50mm Type PR 16 96mm 58mm Type PR 16 IMPORTANT NOTICE: SIZE (BYTE) 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 Please use the softwares own EXIT buttons while quitting the menu or the Main Window. 10.8 30.1 7.6 9.5 60.6 TECHNICAL DATA Clicking the START button on the main window, starts the real time analysis of EPR04S device values. SETTINGS button is for setting up communication parameters (Adress, Parity, Baud Rate) between the PC and EPR-04S device. Both side parameters should be the same for correct data transmission. There are CLEAR ENERGY and CLEAR DEMAND buttons for resetting those values. Transformer ratio is able to setup with the TRANS.RATIOS button on the main menu. The Parameters are sent in 16bit Hexadecimal format. For Example, 230V voltage will be sent as 00E6H. Cosj values shall be divided to 100. 0.98 Cosj will be sent as 0062H. While Cosj is a negative value the MSB bit will be sent as 1. Energy values are sent in 8 bytes (in decimal). 1234567891234,567kWh = 12 34 56 78 91 23 45 67 / 1000 Specifications for data cable ; - 24 AWG or thicker - Less than 100 ohm/ km - Nominal characteristic impedance at 100 kHz of 100 ohms - Less than 60 pF/m mutual capacitance (between two wires in a pair) - Less than 120 pF/m mutual pair capacitance ( the capacitance between one wire and all others connected to earth). - Twisted Pair Graphic Button and Statistics : The Graphic menu, shows records and values for past 1 year period on a graphical interface. Users are able to choose the statistics period, hourly,daily and monthly from the window shown below. ERROR CODES Slave device (EPR-04S) sends error message when receive any missing query. Error codes are given below. 01 Invalid Function: If any message except given above is used, then 01 error messages will be sent. 02 Invalid Register: EPR-04S uses registers between 0 and 57. If any message is been sent out of this range, then 02 error message will be sent. 03 Invalid data: If any different value is been set for dedicated Transformer values and nonzero for demand value, then error message 03 will be sent. Operating Voltage (Un) : Please look at the back labels on the device Operating frequency (f) : 50/60 Hz Auxiliary supply Power Consumption: < 4 VA Measuring Input Power Consumption : < 1VA VIn : 10-300VAC 50/60Hz. (L-N) : 10-500VAC 50/60Hz. (L-L) IIn : 0.05 - 5.5 A~ Measuring Range : 0-900 M (W,VAr,VA) Measuring Category : CAT III Class : 1±1digit [(%10-%110) xFull Scale] Voltage Transformer Ratio : 1 ... 2000 Current Transformer Ratio : 1 ... 2000 Demand Time : 1-60 min. (programmable) Serial Interface : MODBUS RTU (RS 485) : Optically Isolated, programmable : Baud Rate 1200-38400 bps : Address 1-247 : No , odd ,even Parity Pulse Output : NPN Transistor Switch Period : Min. 1,6 Sec. (400 msec pulse width) Operation Current : Max. 50 mA Operation Voltage : 5.....24 V DC, max. 30 VDC Input : 12...48 V DC Ambient Temprature : -5°C; +50°C Display : Red LED Display Dimensions : PR-19 Equipment Protection Class : Double Insulation-Class II ( ) Box Protection Class : IP 40 Box Material : Non-flammable Installation : Panel Mounted (PR-16, PR-19) Rail Mounted (PK-26) Wire Thickness(for terminal block) : 2.5 mm2 Weight : 0.45 kg (PR-19, PK-26) 0.8 kg (PR-16) Installation Category : Class III 26.5 106.0 10.0 Type PK-26 PRECAUTIONS FOR INSTALLATION AND SAFE USE Failure to follow those instructions will result in death or serious injury. - Disconnect all power before working on equipment.. - When the device is connected to the network, do not remove the front panel. - Do not try to clean the device with solvent or the like.Only clean with dry cloth. - Verify correct terminal connections when wiring. - Electrical equipment should be serviced only by your component seller. - No responsibility is assured by manufacturer or any of its subsidiaries for any consequences arising out of the use of this material. - Only for rack panel mounting. M P R - S W -1 / S W - 2 : E P R - 0 4 S s e r i a l I n t e r f a c e S o f t w a r e MPR-SW-1 / SW-2 Software is designed for use with EPR-04S device and analyze its measurement values. MPR-SW -1 / SW-2 is able to view realtime measurements and parameters on a PC screen. The software records all parameters and values into a database for future graphical analysis. The Graphical Analysis is designed flexible for view past records in hour,day and month periods. Inductive/Reactive and Capacitive/Reactive values can be viewed on the main window. Energy reports can also be viewed between specific dates. 4 21.5 53.0 58.0 8.5 S-REACTIVE POWER MAX S-REACTIVE POWER MIN T-REACTIVE POWER MAX T-REACTIVE POWER MIN R-APPARENT POWER MAX R-APPARENT POWER MIN S-APPARENT POWER MAX S-APPARENT POWER MIN T-APPARENT POWER MAX T-APPARENT POWER MIN ACTIVE ENERGY kWh.-1 ACTIVE ENERGY kWh.-2 ACTIVE ENERGY kWh.-3 ACTIVE ENERGY kWh.-4 ACTIVE ENERGY kWh.(EXPORT) -1 ACTIVE ENERGY kWh.(EXPORT) -2 ACTIVE ENERGY kWh.(EXPORT) -3 ACTIVE ENERGY kWh.(EXPORT) -4 REACTIVE ENERGY kVArhL-1 REACTIVE ENERGY kVArhL-2 REACTIVE ENERGY kVArhL-3 REACTIVE ENERGY kVArhL-4 REACTIVE ENERGY kVArhC-1 REACTIVE ENERGY kVArhC-2 REACTIVE ENERGY kVArhC-3 REACTIVE ENERGY kVArhC-4 VOLTAGE TRANS. RATIO CURRENT TRANS. RATIO DEMAND TIME (SEC.) 140mm 50mm Dimensions 18 34.5 Tip 19 Type PR 19 (96x96) 14.0 SIZE ADDRESS (BYTE) 2 1DH 2 1EH 2 1FH 2 20H 2 21H 2 22H 2 23H 2 24H 2 25H 2 26H 2 27H 2 28H 2 29H 2 2AH 2 2BH 2 2CH 2 2DH 2 2EH 2 2FH 2 30H 2 31H 2 32H 2 33H 2 34H 2 35H 2 36H 2 37H 2 38H 2 39H 92mm Run The MPR-SW Program : Wall 79.3mm 70mm 45.0 R-ACTIVE POWER S-ACTIVE POWER T-ACTIVE POWER TOTAL ACTIVE POWER R-REACTIVE POWER S-REACTIVE POWER T-REACTIVE POWER TOTAL REACTIVE POWER R-APPARENT POWER S-APPARENT POWER T-APPARENT POWER TOTAL APPARENT POWER R-COS S-COS T-COS WATT DEMAND V Ar DEMAND VA DEMAND WATT DEMAND MAX V Ar DEMAND MAX VA DEMAND MAX R-ACTIVE POWER MAX R-ACTIVE POWER MIN S-ACTIVE POWER MAX S-ACTIVE POWER MIN T-ACTIVE POWER MAX T-ACTIVE POWER MIN R-REACTIVE POWER MAX R-REACTIVE POWER MIN 92mm Insert the Setup CD into the CD-ROM drive. Browse the CD by double clicking My Computer and CD-Rom icons. Run Setup.EXE by double clicking its icon or use the START menu button and choose Run. Write d:\setup.exe into the text box opened below.The setup program will install the software to your computer. 90.0 00H 01H 02H 03H 04H 05H 06H 07H 08H 09H 0AH 0BH 0CH 0DH 0EH 0FH 10H 11H 12H 13H 14H 15H 16H 17H 18H 19H 1AH 1BH 1CH Wall MPR-SW Software Setup 01 10 00 37 00 02 00 64 00 C8 84 8F 01 Device Address 10 Function 00 MSB adres 37 LSB adres 00 Register number MSB 02 Register number LSB 04 Byte count 00 Data MSB 64 Data LSB 00 Data MSB C8 Data LSB 84 CRC MSB 8F CRC LSB ADDRESS DESCRIPTION The area Measurements on The Control Panel 140mm 01 Device Address 06 Function 00 MSB adres 37 LSB adres 00 Data MSB 64 Data LSB D8 CRC MSB 35 CRC LSB Preset Multiple Register(10H) is used to set more then one register at same time. Setting CT to 100,Ut to 20; 99 01 06 00 37 00 64 D8 35 5 ">
Advertisement
Key Features
- 3-phase powermeter and energymeter
- Measures active, reactive, and apparent power
- Measures active and reactive energy
- MODBUS serial interface for PC connection
- Maximum demand, demand, max/min power measurement
- 2 Energy Pulse Outputs (Reactive and Active)
- Up to 247 devices can be connected using repeater
- Programmable transformer ratios
Frequently Answers and Questions
What is the purpose of the EPR-04S Power Meter?
The EPR-04S power meter is a 3-phase digital powermeter and energymeter that measures a wide range of electrical parameters, including active power, active energy, reactive power, reactive energy, apparent power, and power factor. It also provides information about maximum demand, demand, and maximum and minimum values of power. These measurements are crucial for monitoring and managing electrical systems efficiently.
Can I connect multiple EPR-04S devices to my system?
Yes, you can connect up to 247 EPR-04S devices to your system using a repeater. This allows you to monitor a larger network of power sources and loads.
What is the MODBUS serial interface used for?
The MODBUS serial interface enables communication between the EPR-04S power meter and a PC or other compatible devices. This allows you to read and manage all the measured parameters of the device, including transformer ratios, demand values, energy values, and other settings. By connecting to a PC, you can analyze the data and generate reports for monitoring and control purposes.
How do I set the transformer ratios for the EPR-04S?
The EPR-04S allows you to set the transformer ratios for both voltage and current transformers. This ensures that the device captures accurate measurements of voltage and current in your electrical system. You can set these ratios using the device's interface, a PC, or a dedicated software such as the MPR-SW-1/SW-2 software.
What is the meaning of maximum demand and demand values?
Maximum demand represents the maximum value of average power values measured during the demand time, which you can set between 1 and 60 minutes. Demand refers to the average power value measured during the specified demand time. These values are critical for understanding peak loads and ensuring that your electrical system can handle them efficiently.