B2 Series UPS15
B2 Series UPS 15-20 kVA Three / Single phase
Three Level Inverter
Digital Power Factor Correction
NEW TECHNOLOGY
Three level inverter
High and stable online efficiency (up to 94%)
High input PF ( 0.99)
Low input current THD (<5%)
Low output voltage THD (<2%)
Short response time (<2ms)
High input and output performance
RELIABLE & USER FRIENDLY
Parallel option up to 6 units
Intelligent redundancy management (n, n+1 and n+x)
Programmable high overload capacity
Short circuit protection
Low investment and operation cost
Short return on investment time
Highest efficiency eco-mode (up to 98%)
Reduced weight/volume/footprint
Wide input voltage tolerances (-25%, +20%)
Cold start
Energy-saving sleep mode
Short circuit, lightning and surge protection
Remote emergency power off (EPO)
Generator compatibility
1-7A adjustable battery charger
Extended battery life with intelligent battery management
Automatic and manual battery test
LCD interface and LED operation mode diagram
Remote monitoring panel (optional)
512 real time event log
Battery capacity, load percentage and ambient temperature display
SNMP (optional), RS232, RS485, Modem, MODBUS communication
Remote monitoring and management software
Dry contacts and custom inputs
Smart fan control
Internal battery
Manual bypass
Easy installation and maintenance
10 years spare part warranty
7/24 technical support and customer service
STANDARDS
EN 62040-1 (Safety)
EN 62040-2 (EMC)
CE, ISO 9001:2008, ISO 14001, GOST
ELECTROMEDICAL DEVICES
LOCAL AREA
NETWORKS
TELECOM
APPLICATIONS
INDUSTRIAL
PROCESSES
E-BUSINESS
(SERVERS FARMS,
ISP/ASP/POP)
SMALL COMPUTERS
NETWORK
PERSONAL
COMPUTERS
CASH
REGISTERS
SERVERS
B2 Series UPS 15-20 kVA
B2 SERIES UPS TECHNICAL SPECIFICATIONS
Power (kVA)
380 / 400 / 415 Vac 3ph + N
Voltage
- 25%, +20% (without downgrading)
Voltage Tolerances
INPUT
20
15
50 / 60 Hz
Frequency
± 10%
Frequency Tolerances
Power Factor
0.99
< 8%
THDi
Voltage
Voltage Tolerances
220 / 230 / 240 Vac 1ph + N
± 1% (static load), dynamic load in accordance with VFI-SS-11
50 / 60 Hz
Frequency
OUTPUT
Frequency Tolerances
± 0.1% (self-synchronize), ± 1% (mains-synchronize)
0.7 (0.8 optional)
Power Factor
2% (linear load),
THDv
5% (non-linear load)
Crest Factor
3:1
110%
30 min.
OVERLOAD
CAPACITY
130%
10 min.
150%
160%
1 min.
10 sec.
EFFICIENCY
Online
Eco-mod
up to 94%
up to 98%
Technology
Three level inverter, PFC
Control
GENERAL
Dual-DSP, SPWM
Paralleling Units
Up to 6 units
Communication
SNMP(Optional), RS232, RS485, MODEM, MODBUS
Remote Monitoring
SNMPView, Remote monitoring panel(optional)
Programmable 3 dry contacts
Dry Contacts
Custom Inputs
Generator, Remote EPO, Remote Start/Stop
Cold Start
Standard
Maintenance Bypass
Standard
Operating Temperature
from 0 °C up to +40 °C (from 20 °C to 25 °C for maximum battery life)
Relative Humidity
0% - 85% (without condensation)
Maximum Altitude
2000 m
< 55 dB (A)
ENVIRONMENT
Noise Level
Dimensions (W x D x H) (mm)
UPS
CABINET
Weight (kg)
Degree of Protection
Colour
Internal Battery Quantity
BATTERY
STANDARDS
Internal Battery Capacity (Ah)
External Battery Cabinet Socke
Safety
EMC
UPS LIFETIME
ELEN reserve the right of changing information in this without report.
255 x 730 x 870
49
51
IP20
RAL7012
30
7-9
Standard
EN 62040-1
EN 62040-2
10 YEARS
30 / 01 / 2013