TST WU

STARTUP

Important !

You must read the function description before operating, connecting or starting up door controller.

preliminary public (B)

2008-04-09

WU_Inbetriebnahme13_GB.doc

TST Startup

Notes

© Copyright 2006 by

FEIG ELECTRONIC GmbH

Lange Straße 4

D-35781 Weilburg-Waldhausen

Tel.: +49 6471 3109-0 http://www.feig.de

This edition replaces all earlier versions.

The specifications contained in this document may be changed without prior notice.

Transmission and reproduction of this document, use and revealing of its contents are not permitted without express consent. Violations will result in liability for damages. All rights reserved in case of patent granting or utility model listing.

This Manual is directed especially at persons involved with starting up / commissioning the TST WU door controller of FEIG ELECTRONIC GmbH. Starting up the controller must be carried out only by officially trained electrical experts who are familiar with the safety standards of electrical drive and automation technology.

The entity which has placed the TST WU door controller in service is solely responsible for the completeness of the startup manual.

This Manual shows only a small range of the controller functions. Further functions and descriptions for individual door functions as well as more exact specifications for the controller and hazard notes can be found in the main description.

The collecting of information in this document has been done to the best of our knowledge and with due diligence. FEIG ELECTRONIC GmbH does not warrant the correctness and completeness of the information in this document. In particular, FEIG ELECTRONIC GmbH cannot be held liable for following damages due to faulty or incomplete information.

Since mistakes can never be completely avoided in spite of our best efforts, we always welcome feedback.

The installation recommendations contained in this document presume favorable surrounding conditions.

FEIG ELECTRONIC GmbH assumes no liability for perfect function in environments alien to the system.

FEIG ELECTRONIC GmbH provides no warranty that the information in this document is free of foreign copyrights. FEIG ELECTRONIC GmbH does not grant any licenses for its own or foreign patents or other copyrights in connection with this document. Warranty claims against FEIG ELECTRONIC GmbH are the right of the direct contractual partner only and are not transferable. Warranty is assumed only for the products supplied by FEIG ELECTRONIC GmbH. There is no warranty for the overall system.

The description of products, their use, possibilities and performance data are not to be taken as assured properties and are subject to technical changes.

General notes concerning this document

The following symbols are used in this function description to alert the user to various hazards and useful tips.

WARNING alerts to a possible hazard to

persons if the procedure is not performed as described

.

ATTENTION

alerts to possible damage to

the controller.

IMPORTANT alerts to information which is important to the function of the door controller or door.

) refers to useful information which is useful but

not absolutely necessary for using the TST WU door controller

WU

FEIG ELECTRONIC GmbH Page 2 of 24 WU_Inbetriebnahme13_GB.doc

TST Startup

Table of Contents

1 Safety information

2 Technical data

3 Installation of the control system

4 Electrical connection

4.1

Power supply connection............................................................................................................8

7

8

4

5

4.2

4.3

Motor connection .........................................................................................................................9

Safety edge connection.............................................................................................................10

4.4

Limit switch connection ............................................................................................................11

4.4.1 Absolute encoder .........................................................................................................................11

4.4.2 Mechanical limit switches.............................................................................................................11

5 General operating instructions for parameterisation

6 Basic settings

6.1

12

13

Automatic querying of the basic data......................................................................................13

6.2

Changing parameters ................................................................................................................13

7 Putting into operation...

7.1

14

... with absolute value transmitter or incremental encoder ...................................................14

7.2

7.3

... with mechanical limit switches.............................................................................................14

New request for calibration of the end positions ...................................................................15

8 Other connection possibilities

8.1

15

Photo eye ....................................................................................................................................15

8.2

External control device..............................................................................................................15

9 Outputs overview

10 Inputs overview

11 Functions

12 Messages overview

12.1

12.2

Internal system-related errors F.9xx ........................................................................................22

Information messages ...............................................................................................................23

15

16

17

20

WU

FEIG ELECTRONIC GmbH Page 3 of 24 WU_Inbetriebnahme13_GB.doc

TST Startup WU

.

ATTENTION: IMPORTANT SAFETY INSTRUCTIONS

IT IS IMPORTANT FOR THE SAFETY OF PERSONS TO OBSERVE THESE INSTRUCTIONS. THESE

INSTRUCTIONS MUST BE KEPT:

- All work concerning installation, set-up and maintenance must be carried out exclusively by qualified staff. You must specifically pay attention to the following regulations : VDE0100, EN 50110

(VDE0105), EN 60204 (VDE0113), EN 50178 (VDE0160), EN 60335 (VDE0700), fire prevention regulations, accident prevention regulations and the regulations relevant to industrial gates

(ZH1/494, EN12453, EN12978)

- The control system should only be opened when the power supply is completely switched off.

- If the potential-free contacts of the relay outputs or other contact points are operated with external power. i.e. with a dangerous voltage which can still be live after switching off the control system or when the mains plug is disconnected, an appropriate warning sticker must be clearly visible on the control system casing. ("ATTENTION! all mains electricity circuits must be switched off before accessing the connecting terminals.")

- The control system must never be operated when it is open.

- The control system should only be operated with dismantled CEE connector if the mains supply can be completely disconnected from the control system by means of a corresponding switch. The mains plug or the switch used as a substitute must be easily accessible.

- If the connecting cable of this appliance is damaged, it must be replaced by the manufacturer or his after-sales service or by a similarly qualified person in order to avoid dangers.

- Even after switching off the power supply, there are still dangerous voltages for up to ½ a minute on the DC-bus capacitors. The discharge time until the voltage values are less than 60 V DC is a maximum of 1 minute. Touching internal control system components during this discharge time is dangerous.

- If the switching power supply is defective, the discharge time for the DC-bus capacitors to reach less than 60 V DC can increase significantly. Here, discharge times of up to 2 minutes can occur.

- If the 24 V control system is short-circuited or extremely overloaded, the switching power supply does not start although the DC-bus capacitors are charged. The display and LEDs remain dark. It is not possible to start the power supply unit until after the short-circuit or extreme overload has been resolved.

- After switching off the power, the power supply unit is still supplied for several seconds by the DCbus capacitors and still maintains the power supply function for a certain time depending on the power supply unit loading.

- The control system must not be operated without a connected protection earth. The absence of protection earth results in dangerous high voltages, caused by discharge capacities, on the control system housing. The protection earth connection must be carried out in accordance with EN50178

Section 5.2.11.1 for increased leakage currents >3,5mA.

- The system must not be switched on or operated when wet. This can result in destruction of the control system.

- If the control systems are used outside the specified temperature range, it must be ensured, using a regulated and monitored heating system, that the specified operating temperature range is maintained when the power supply is switched on and during operation of the control system.

- It is prohibited to operate the control system if the keypad or screen is damaged.. Damaged keypads and screens must be replaced. Touching the keypad with sharp objects must be avoided in order to avoid damaging the keypad. The keypad is basically only intended to be touched with the fingers.

- Before switching on the control system for the first time, it must be ensured that the plug connectors and evaluation cards (plug-in modules) are in the correct position. Misplaced or skewed plugging-in the cards can result in damage to the control system as can installing unauthorised third-party cards.

- When the gate is operated in dead-man operating mode, it must be ensured that the gate area can be viewed by the operator as safety equipment such as safety rail and light barrier are not effective in this mode.

- It is forbidden to operate the contactors manually. If the protective foil is destroyed, the guarantee is void.

- In order to avoid hazards due to a defective or sticking contactor, a mechanical stop must be installed in the end positions for all gate types

FEIG ELECTRONIC GmbH Page 4 of 24 WU_Inbetriebnahme13_GB.doc

TST Startup

- The parameter setting and operation of the safety equipment must be checked. The adjustment of the parameters, bridges and other operating elements must only be carried out by qualified staff.

WARNING Disregarding the safety information can be detrimental to health or damage the control system.

We do not claim to have fully covered the safety information. Please contact your supplier for further information about the product.

The manufacturer has carefully tested the appliance hardware and software and the product documentation, however cannot make any guarantee of complete correctness.

Appliance identification (type plate with information about the name and address of the manufacturer, serial number, type description, power supply and temperature range) must be done by the user.

WU

Housing dimensions (W x H x D):

Mounting:

Power supply range for 3-phase current with N

Power supply range for 3-phase current without N ca.: 182 x 320 x 93mm (without emergency stop button) upright

3 x 200 ... 415V ±10% / 50 .. 60Hz corresponds to mains power supply voltage of

115 ... 240V ±10% / 50 .. 60Hz

3 x 115 ... 240V ±10% / 50 .. 60Hz corresponds o mains power supply voltage of

115 ... 240V ±10% / 50 .. 60Hz

IMPORTANT N must be connected with L2.

Power supply range for 3-phase current without N in connection with the option

TST WU-0.0-A –

Supply adjustment 400V

Required fuse

Power consumption

Power supply unit without motor

Power consumption

Power supply unit with AC3 motor at

3 x 360 ... 400V ±10% / 50 .. 60Hz

3x 10A Type K max. 30W

External power supply (230 V):

Control voltage / external power supply 2:

External power supply 12V:

400V 230V

Max. 2.2 kW

230 V

AC

±10%, 50...60 Hz

Max. 1.5 kW

(fused on the printed circuit board: 2 AT)

115V

Max. 0.75 kW

24 V

DC

±5% max. 500 mA including all plug-in modules and 12 V connections fused via self-resetting semiconductor fuse

11.3 VDC

±5%, regulated, max. 150 mA

Control inputs:

Safety chain / emergency stop

24 VDC / typ.15 mA min. signal duration for input control commands: > 100 ms all inputs must be connected potential-free or:

IN1 ... IN8:

(with TST RWU: IN21 ... IN 28)

< 2 V: inactive Æ logical 0

> 17 V: active Æ logical 1

IN9 ... IN10: < 5 V: inactive Æ logical 0

>16 V: active Æ logical 1

RS485 A and B: Only for electronic limit switches

RS485 level, terminated with 100Ω

All inputs must be connected potential-free

< 15 V: inactive Æ logical 0

>17 V: active Æ logical 1

Contact load capacity:

≥ 35 V

DC

/

≥ 200 mA

If the safety chain is interrupted, no movement of the drive is possible, not even in dead-man

FEIG ELECTRONIC GmbH Page 5 of 24 WU_Inbetriebnahme13_GB.doc

TST Startup

Safety rail input

Relay outputs

Relays K1, K2:

(with TST RWU: K3 ... K6) for electric safety rails with 1.2kΩ or 8.2kΩ terminal resistance and for dynamic optical systems if inductive loads are switched (e.g. further relays or brakes), they must be equipped with corresponding noise suppresion measures (free-wheeling diodes, varistors, RC elements)

⇒ 24VDC / 500 mA

⇒ 230 VAC / min. 0.1 A / max.

80 W

Contacts which have been used once for power switching can no longer switch extra-low

potential-free switching, changeover contact

voltage

Drive output: 3x 400VAC, max. 2.2 kW for AC-3

Reversing contactor is prepared for operating three-phase drives

Max. length of the motor cable: 30m electromechanical brake 230 V

Operating temperature range:

AC

-control via switched motor phase and N

-20...+50°C

Storage temperature range

Air humidity

Mains cable installation

-20...+70°C up to95% not condensating

Y, the mains cable must only be replaced by the manufacturer or his after-sales service or by another qualified person

Equipment mobility

Protection class

Equipment type

Vibration

Protection class stationary

Protection class I

Motor appliance, external motor is not part of the delivery from

FEIG ELECTRONIC GMBH low vibration installation, e.g. on a brick wall

IP54 (IP65 by replacing CEE connection and sealing cable entries)

All unused cable entries must be closed.

Weight

Directives

EMV-Directive: 89/336/EWG modified by: 91/263/EWG

92/031/EWG

93/068/EWG ca. 2.8 kg

Standards:

EN 50081-1 / 03.93:

EN 50081-2 / 03.94: interference emissions, residential area interference emissions, industrial area

Low voltage directive: modified by:

73/023/EWG

93/068/EWG

Prototype tested according to:

Applied national technical specifications concerning the directives mentioned above

EN 61000-6-2 / 2001: interference resistance, industrial area

EN 60335-1 / 2003: Safety of electrical appliances for domestic use and similar purposes /

Part 1

EN12453 / 2001:

EN12445 / 2001:

EN12978 / 2003:

Usage safety of power-operated gates

– requirements

Usage safety of power-operated gates

– test methods

Gates – safety equipment – requirements and test methods

WU

FEIG ELECTRONIC GmbH Page 6 of 24 WU_Inbetriebnahme13_GB.doc

TST Startup

3 Installation of the control system

ATTENTION: IMPORTANT INFORMATION FOR SAFE INSTALLATION.

OBSERVE ALL INSTRUCTIONS; WRONG INSTALLATION CAN RESULT IN SERIOUS INJURIES.

WARNING

ATTENTION

During install of control system, system must be disconnected from the mains.

Figure 1: Cover installation

Keypad connection

Before installation, the control system must be checked to make sure it does not show any signs of transport or other damage. Damage inside the control system can result in significant consequential damages to the control system and risk of injury to the user.

Touching the electronic parts, especially the components of the processor circuit, is forbidden.

Electronic components can be damaged or destroyed by electrostatic discharge.

Before opening the casing cover, it must be ensured there are no drill filings lying on the cover which can fall inside the casing.

It must be ensured the system is disconnected from the mains during installation.

Unused cable entries must be sealed using suitable measures in order to guarantee the protection class IP54 of the casing.

The cable entries must not be subjected to any mechanical loads, especially tensile loads.

WU

Min. 100mm

-20°C

50°C

3x400VAC,

N, PE

80

160

Min. 100mm

Figure 2: Installation of the control system

FEIG ELECTRONIC GmbH Page 7 of 24

Figure 3: Drilling plan

WU_Inbetriebnahme13_GB.doc

TST Startup WU

WARNING

Connection, testing and maintenance work on the open control system must only be carried out in a voltage-free state. You must pay particular attention to the points mentioned in the safety information.

There are still up to 2 minutes of dangerous voltage after switching off the control system.

Touching the electronic components is dangerous due to residual voltages.

The control system must never be operated while the housing cover is open.

ATTENTION

Before switching on the system for the first time after completing the wiring, it must be checked whether all motor connections on the control system and on the motor are tightened and the motor is switched to star or delta correctly.

4.1 Power supply connection

All control voltage inputs are galvanically isolated from the power supply by means of a reinforced insulation. We recommend at least one additional isolation with a nominal voltage

> 230 V (according to EN 60335-1) for all components which are to be connected to the control system.

Very high electrostatic charges take place especially for fast-operating rollup plastic gates. Damage to the control system can result from this voltage discharge. Therefore, suitable countermeasures must be taken to prevent electrostatic charging.

Maximum cross sections for connection of the printed circuit board terminals.:

Screw terminals

Plug-in terminals

Motor terminals

Mains connection

Single wire

(rigid)

2.5

1.5

2.5

2.5

Fine strand

(with/without wire end ferrule)

1.5

1.0

2.5

1.5

L3 L2 L1

L3 L2 L1

13 +A1 L1 L2 L3 13 +A1

X28

1

T1 T2 T3 14 -A2 T1 T2 T3 14 -A2

L3.1

extern

L1.3

X10

N

N

N

PE

PE PE N T1

X13

T2 T3

PE

10 12 20

IMPORTANT

The mains plug must be visible and accessible from the control system.

FEIG ELECTRONIC GmbH

CEE plug

5 pole, 16A, red

Fuse

10 A / Type K

L3

L2

L1

N

PE

Figure 4: Mains cable connection

Page 8 of 24 WU_Inbetriebnahme13_GB.doc

TST Startup

T1 T2 T3 14 -A2

T1

T2 T3 14

-

A2

X28

1

L3.1

X10

N

N

PE PE PE

PE N

N

T1

T1

X13

T2 T3

T2 T3

10 11

X14

12 20 21 22

X15

WU

PE

T1

T2

T3

M

3~

Figure 5: Motor connection

+

L

~ ~

N

-

Break rectifier

FEIG ELECTRONIC GmbH Page 9 of 24 WU_Inbetriebnahme13_GB.doc

TST

4.3 Safety edge connection

Startup WU

Spiral cable

X22

41 42 43 44 45

51 52 53

X23

Electrical safety edge

J400

J 400: 1 - 2

3

1

,2K

1

8,2K

Terminal box

Optional slip door

OFF S300 ON

J400

3

1,2K

1

8,2K

41

42

43 44 brown white

Safety edge

Slack rope switch

The jumper

J400 is located on the top right corner of the printed circuit board

Inside

(brown)

Outside

(white)

Terminal resistor

Dynamical optical system

J400

J 400: 1 - 2

3

1

,2K

1

8,2K

X22

41 42 43 44 45

51 52 53

X23

Spiral cable

Terminal box

41

42

43 44 45

Optional slip door

Slack rope switch

Receiver

Green

White

Brown

Trans mitter

Figure 6: Safety edge connection

Different types of safety edges can be connected, such as e.g.:

• Electrical safety edge with 1.2kΩ or 8.2kΩ terminal resistor.

• Dynamic optical systems.

If one of these types of safety edges is connected when the TST WU gate control system is switched on, it will be recognised automatically.

IMPORTANT If no safety edge is connected, automatic closing of the door is not possible.

It is possible to connect other types of safety edges. Please contact the gate manufacturer for this.

FEIG ELECTRONIC GmbH Page 10 of 24 WU_Inbetriebnahme13_GB.doc

TST Startup

4.4 Limit switch connection

Three different limit switch systems can be used with the TST WU gate control system.

An absolute encoder and mechanical cam limit switch can be used as limit switches.

4.4.1 Absolute encoder

3

6

5

2

1

4

+12V

GND

RS 485-B

Emergency stop chain

24V emergency stop chain

RS 485-A

31 32 33 34 35 36

1 5 6 2 4 3

Absolute encoder

Figure 8: Absolute value transmitter connection

Figure 7: Absolute encoder

4.4.2 Mechanical limit switches

WU

Figure 9: Cam limit switch

31 32

33 34 35

X20

Hand crank switch

54

61 62 63 64 65

66

X24

71

thermopill

Emergency end switch

OPEN

Emergency end switch

CLOSE

Figure 10: Cam limit switch connection

IMPORTANT

Check the electrical connection again before operating the control system.

The appliance can be damaged by wrong connections.

FEIG ELECTRONIC GmbH Page 11 of 24 WU_Inbetriebnahme13_GB.doc

TST Startup

5 General operating instructions for parameterisation

1.

2.

3.

4.

5.

1.

2.

3.

or

4.

or

5.

Starting parameterisation mode

SERVICE

Switch off gate control system

Switch off power supply completely

(Observe safety instructions)

Put DIP switches in the

ON position

Service mode is activated, close the switch cabinet.

(See Section 6.2 for the position of the DIP switches)

7-segment display goes out after a delay of several seconds

Å

¿

¿

À

Switch on the gate control system

STOP

(permanent)

Up

(permanent)

Switch on control system the first decimal position flashes when service mode is active

.

‘

. . .

Press Stop button and keep it pressed

Press Up key and keep it pressed

Content of the display depends on the status of the control system pending messages are displayed, e.g.;: after ca. 2 seconds waiting:

In parameterisation mode

E. 2 0 1

P. 0 0 0

UP or

DOWN

Parameter selection when parameterisation mode is active

select desired parameter

A T T E N T I O N:

Not all parameters are directly visible or modifiable depending on password and type of security level set the parameter value can be displayed or modified (see below) display varies according to the selection

P. . . .

Parameter editing for selected parameter

Control system in parameterisation mode

Display of the desired parameter name

P

.

Å

STOP (short) Open the parameter the current parameter value is displayed:

¿

Up

Up key for increasing parameter value if the current parameter value in force is changed, the decimal positions flash

À

Down

Down key for reducing the parameter value

Å

STOP (long) save amended parameter value

STOP (short) discard amended parameter value

Å

STOP (short) for changing to the display of the parameter name the parameter counts as saved when no positions are flashing any more cancellation, the original parameter value is displayed again

Display parameter name

P

.

Å

0 1 0

5

6

4

6

4

0 1 0

STOP (long)

Leaving parameterisation mode

parameterisation mode is stopped immediately, gate operation is active again

The last saved value is obtained automatically

. . . .

Reset the control system

Å

+¿+À press simultaneously and keep pressed for ca. 3 seconds.

‘

‘

IMPORTANT

Service mode is exited automatically after ca. 1 hour. If you want to return to service mode, the control system must be switched off for a short time and turned on again afterwards or a reset must be performed.

WU

FEIG ELECTRONIC GmbH Page 12 of 24 WU_Inbetriebnahme13_GB.doc

TST Startup WU

Please follow the other steps in these instructions in order to operate the TST WU gate control system.

6.1 Automatic querying of the basic data

If the TST WU gate control system has not already been set up by the manufacturer, the following parameters are queried automatically:

IMPORTANT The DIP switch must be switched on (see Figure 11: Position S300) so that the TST WU gate control system can retrieve the parameters automatically

.

)

If the DIP switch is not switched on and the basic parameters are not set, the error F.090 is displayed.

)

The "-1" indicator on the display tells the control system that this parameter is forcibly queried.

Positioning system P.205

The limit switch system witch is used must be set with the parameter P.205.

P.205: 0 = Mechanical limit switch

P.205: 1 = Reserved

P.205: 2 = Reserved

P.205: 3 = Absolute value transmitter DES-A

P.205: 4 = Reserved

P.205: 5 = Reserved

P.205: 6 = reserved

P.205: 7 = Absolute encoder DES-B

P.205: 8 = Absolute encoder TST PD

)

The automatic querying of the basic data can be cancelled by pressing the

¿ UP key during the

switching on of the control system. This gives direct access to the parameterisation level.

)

Changing the basic data is not necessary if these were previously automatically queried and set.

Proceed as follows to change parameters:

X403

X302

1

OFF

S300

ON

- Unplug the mains plug

- Switch the DIP switch S300 on.

- Plug in the mains plug.

Å

STOP and the ¿ UP keys simultaneously for ca. 3 sec to reach the parameterisation mode of the gate control system.

- Change the desired parameters.

- After completing the adjustments, exit from parameterisation mode by pressing the

Å

STOP key for ca. 3 sec.

1,2K

8,2K

Figure 11: Position S300

J400

FEIG ELECTRONIC GmbH Page 13 of 24 WU_Inbetriebnahme13_GB.doc

TST Startup

7 Putting into operation...

7.1 ... with absolute value transmitter or incremental encoder

1. Open calibration mode by pressing the

Å

STOP key for a short time

2. Move to the gate-CLOSED position with the À DOWN key and save by pressing the Å STOP key for ca. 3 sec.

IMPORTANT If the gate movement direction is wrong, the motor rotating field is incorrect: switch off the control system and change 2 motor connections.

3. Move to the gate-OPEN position with the ¿ UP key and save by pressing the

Å

STOP key for ca. 3 sec.

)

The limit switch bands are set automatically by running the gate in automatic mode.

7.2 ... with mechanical limit switches

1. Move the gate to ca. 10 cm before the closed position with the À DOWN key.

IMPORTANT

Distance is very much dependent on the type of gate and the speed, increase the

value for fast gates.

If the gate movement direction is wrong, the motor rotating field is incorrect: switch off the control system and change 2 motor connections.

2. Set the bottom limit switch so that it just activates.

IMPORTANT Limit switch in the end positions must not be run over!

3. Move the gate to ca. 10 cm before the open position with the ¿ UP key.

IMPORTANT

Distance is very much dependent on the type of gate and the speed, increase the

value for fast gates.

4. Set the top limit switch so that it just activates.

IMPORTANT Limit switch in the end positions must not be run over!

5. If required for the type of gate: set the top and bottom EMERGENCY limit switches.

)

Connect N.C. contacts e.g. in the safety circuit in series with thermopile.

6. Go to parameterisation mode by pressing the

Å

STOP and ¿ UP keys and select parameter P.980

"Service Mode", open this and set parameter value "2" to "0" (automatic mode)

7. Leave the parameterisation mode by pressing the Å STOP key for a long time (3 sec.).

8. If necessary correct the gate-OPEN and gate-CLOSED limit switch positions by fine adjustment of the stop positions in automatic mode.

WARNING In order to avoid unintended operation of the gate, only carry out the adjustment

of the limit switches when EMERGENCY STOP is pressed or the control system is switched off !

9. Gate can now be operated in automatic mode.

WU

FEIG ELECTRONIC GmbH Page 14 of 24 WU_Inbetriebnahme13_GB.doc

TST Startup

7.3 New request for calibration of the end positions

If the end positions using electronic limit switches have already been calibrated but are not suitable for the gate, calibration of the end positions can be requested again.

The following parameter must be set for this:

P.210: 5 = New calibration of all end positions

WU

8 Other connection possibilities

8.2 External control device

64 65

66

X25

71 72 73 74 75 76

X23

51 52 53 54 61

X24

Figure 12: Photo eye connection

Figure 13: External control device

T1 T2 T3 14 -A2 T1 T2 T3 14 -A2

L3.1

X10

N

N

PE

PE

PE N

T1

X13

T2 T3

X14

10 11 12

20 21 22

X15

FEIG ELECTRONIC GmbH

T1

PE

T2 T3

M

3~

Door is

OPEN

Door is

CLOSE

Page 15 of 24 WU_Inbetriebnahme13_GB.doc

TST

10 Inputs overview

Startup

31 32 33 34 35 36

A B

41 42

43

44

45

51 52 53 54 61 62 63 64 65 66 71 72 73 74 75 76

ng EU +2

81 82

83

84 85 86 91 92

WU

31 32 33 34 35 36 41 42

43

44

45

51 52 53 54 61 62 63 64 65 66 71 72 73 74 75 76

+24V AU

81 82

83

84 85 86 91 92

i-Lei +24V g E1 +24V

FEIG ELECTRONIC GmbH Page 16 of 24 WU_Inbetriebnahme13_GB.doc

TST Startup WU

11 Functions

P.

000

005

010

011

025

[Unit]

Adjustment

Gate functions

range

[Cycles] Display gate cycles counter

Display: 1234567

⇒ 1234. À-press .567

Display: 67

⇒ 67

[Cycles] Display the number of cycles still operable until maintenance is necessary.

Display: 1234567

⇒ 1234. À-press .567

Display: 67

⇒ 67

[s]

0..200

[s]

0..200

Auto close time 1 (Stop position Top - Eo)

0 = automatic closing deactivated

Auto close time 2 (Intermediate holding position - E1)

0 = automatic closing deactivated

[s]

0..200

Pre warning time / clearance time

0 = pre warning time deactivated

Factory setting

-1

10

10

0

P.

205

[Unit]

Range

0..8

Selecting the limit switch system

Selecting the positioning system:

0. Limit switch 1 (limit switch as normally closed, pre-limit switch normally open)

1. Limit switch 2 (limit switch and pre-limit switch normally closed)

2. Incremental encoder (reference switch in lower end position)

3. Absolute encoder DES-A

4. Absolute encoder TST PB-A

5. SSI encoder (only with UL-Version)

6. Reserved

7. Absolute encoder DES-B

8. Absolute encoder TST PD

Default

-1

P.

210

215

221

231

[Unit]

Adjustment range

0..5

0..1

Calibration of the stop positions with electronic limit switches

Selection of the position to be calibrated by deadman operation

("teach in"):

0: no

→ none/cancel

1: Eu

→ Limit switch Bottom, Top (intermediate stop see P244)

2: Eo

→ Limit switch Top (intermediate stop see P244)

3: uo

→ Limit switch Bottom and Top

4: E1

→ Limit switch intermediate position (P244 is ignored)

5: al

→ (all) limit switches Bottom, Top & intermediate stop (according to P244)

Request new calculation of the pre-end switch positions and limit switch bands

0: do not make any correction

1: request correction of the limit switch bands and pre-end switches

Factory setting

0

0

[Inc]

± 125

[Inc]

± 60

Parameter is only active if automatic correction was set at the factory.

Correction value for stop position Bottom

(is set to 0 for new calibration !)

Correction value for stop position Top

(is set to 0 for new calibration !)

0

0

FEIG ELECTRONIC GmbH Page 17 of 24 WU_Inbetriebnahme13_GB.doc

TST Startup

P.

910

920

925

930

Eb 1

Eb 2

...

Eb 7

Eb 8

Ebcl

Eb -

[Unit]

Adjustment range

0..22

Diagnostics

Selecting display mode

(request by STOP button or during motor movement)

0: Controller sequence (Automatic mode)

1: [Hz] current rotary field frequency

2: [A] current motor current (> 1A)

3: [V] current motor voltage

4: [A] current link current (effective current)

5: [V] link voltage

6: [°C] final stage temperature in °C

7: [°F] final stage temperature in °F

8: last measured run time (1/10 to 99.9s, 1/1 starting at 100s)

For electronic limit switches only:

9: [Inc] current position progress

10: [Inc] current reference position

11: [dig] current channel 1 value of absolute encoder

12: [dig] current channel 2 value of absolute encoder

13: [dig] current reference voltage (2.5V)

14: 14: Temperature in housing in [°C]

15: 15: Temperature in housing in [°F]

16: Reserved

17: Reserved

18: Rotation speed of the TST PD shaft

) only with TST PD

19: Reserved

20: Reserved

21: Number of position requisition without answere

22: Number of wrong received signs in TST PD encoder

(activates also the output in P.955)

[s]

0..120,0

Display error memory / faults

⇒ Open by pressing STOP key again,

⇒ Scroll with UP / DOWN keys

⇒ Close by pressing STOP key.

⇒ Leave with Cancel "EB-".

• Eb 1 → Error messages 1 (most recent) or. Er--

• Eb 2 → Error messages 2 or Er--

...

• Eb 7 → Error messages 3

• Eb 8 → Error messages 4 or. Er-or. Er--

• Ebcl → delete complete failure memory

• Eb - → Cancel

(Display noEr: no errors)

Display the software version

Run time of the motor during the last gate operation

WU

Factory setting

0

Eb 1

FEIG ELECTRONIC GmbH Page 18 of 24 WU_Inbetriebnahme13_GB.doc

TST Startup

P.

973

980

999

[Unit]

Adjustment range

0..1

Service operating modes

Reset of the service counter: Reset (1) / Cancel (0)

0..3

Service mode

0: Automatic (automatic opening and closing)

1: Deadman Close (manual closing / automatic opening)

2: Deadman (manual opening and closing)

3: Emergency operation (deadman opening and closing, all errors and safeties are ignored).

0..FFFF

Password input

Factory setting

0

0

1

WU

FEIG ELECTRONIC GmbH Page 19 of 24 WU_Inbetriebnahme13_GB.doc

TST Startup

12 Messages overview

F.000

Door position too far up

F.005

Door position too far down

Improper end positions

Too small a parameter value for upper emergency limit switch

Upper limit switch range (limit switch band) too small

Mechanical brake defective or improperly set

Too small a parameter value for lower emergency limit switch

Lower limit switch range (limit switch band) too small

Mechanical brake defective or improperly set

F.020

F.030

F.031

F.043

Implausibilities in door movement

Run time exceeded (during opening, closing or deadman)

Lag error (position change of the door is less than expected)

Detected rotational direction deviates from expected

Pre-limit switch fault (light barrier)

• current motor run time has exceeded set maximum run time, door may be sticking or is blocked

If using mechanical limit switches, one may not have tripped

Door or motor is blocked

Too little power for lift torque

To little speed

Mechanical limit switch was not left or is defective

Absolute or incremental encoder not tightened sufficiently in its mounting

Wrong positioning system selected (P.205)

When using incremental encoders: Channel A and B reversed

Motor rotation direction reversed compared with calibration setting

Too much „pancaking“ when starting, brake releases too soon, or too little torque, adjust boost as necessary.

The pre-limit switch for the light barrier remains activated even in the middle end position or upper end position.

F.080

Maintenance counter exceeded

Fault: Maintenance is required •

Service counter has expired

F.090

Parameters not set

Controller not parameterized •

The basic parameters (P.205, P.100 to P.103) for the TST WU controller have not yet been set.

F.201

Internal E-Stop „push-button“ tripped

Safety chain faults

E-Stop chain was interrupted starting at input „internal E-Stop“ without parameterizing mode having been selected

Internal parameter or EEPROM checks defective, pressing the

STOP key provides additional information about the cause

F.211

F.212

or Watchdog (computer monitor)

External E-Stop 1 tripped

External E-Stop 2 tripped

E-Stop chain was interrupted starting at Input 1 (terminals 1 and 2)

E-Stop chain was interrupted starting at Input 2 (terminals 3 and 4)

WU

FEIG ELECTRONIC GmbH Page 20 of 24 WU_Inbetriebnahme13_GB.doc

TST Startup

F.360

F.361

F.363

F.364

F.366

F.369

F.374

F.385

Faults in the safety chain

Short circuit detected on edge input

Short circuit detected on edges with normally closed contact

Number of edge trips for closing has reached set limit

Interruption on edge input

Parameterized, maximum number of safety edge trips during a door cycle was exceeded

Safety edge testing failed

Too high a pulse frequency for optical safety edge

Internal safety edge incorrectly parameterized

Connection cable defective or not connected

Termination resistor incorrect or missing

Jumper J600 incorrectly set

• Safety edge was not activated as expected when requesting a test.

• The time between request for testing and actual testing not in agreement optical safety edge

Defective input for internal safety edge

An internal safety edge is connected but deactivated

Safety bar testing failed

Fault in pre-limit switch for safety edge

Pre-limit switch for safety edge incorrectly set or defective

Processing module defective

Safety edge defective

Pre-limit switch for turning off the safety edge or reversing after safety edge tripping remains tripped even in the upper end position.

F.400

Controller hardware reset detected

General hardware faults

• Excessive noise on supply voltage

• Internal watchdog tripped

F.401

F.40

A

Internal reset detected

Internal reset detected

• Watchdog-Error

F.524

24V faulty

General hardware faults

• The external 24V supply is disturbed

• Shortcut or overload of the external 24V

F.700

Positioning system faults

Position sensing defective

For mechanical limit switches

:

• At least one limit switch does not correspond to the configured active status.

• An implausible combination of at least 2 active limit switches

For electronic limit switches

:

• After invoking activation of the factory parameters

(Parameter P.990) the corresponding positioning system was not parameterized.

• Calibration not completed or is incorrect and must be repeated.

• When activating the intermediate stop the intermediate stop is implausible.

• Synchronization not finished or reference switch defective.

WU

FEIG ELECTRONIC GmbH Page 21 of 24 WU_Inbetriebnahme13_GB.doc

TST Startup

F.750

F.751

F.752

F.760

Positioning system faults

Protocol

Transmission error

• Defective hardware or electrically noisy environment

Synchronization FU <-> absolute encoder

Timeout with protocol transmission

• Defective hardware or electrically noisy environment

• Absolute encoder processor electronics defective

• Interface cable defective / interrupted

• Absolute encoder processor electronics defective

• Defective hardware or electrically noisy environment

Position outside of window

• Position encoder drive defective

• Absolute encoder processing electronics defective

• Defective hardware or electrically noisy environment

12.1 Internal system-related errors F.9xx

These are internal errors which cannot be eliminated by the user.

If such an error occurs, call customer service immediately.

WU

FEIG ELECTRONIC GmbH Page 22 of 24 WU_Inbetriebnahme13_GB.doc

TST Startup

12.2 Information messages

EICH

NA

NOTF

'Hd'

ParA

'Au'

'Hc'

WU

STOP

_Eu_

Eu

ZUF@

-Eo-

Eo

@AUF

-E1-

E1

FAIL

E.i.E.u.

E.i.E.o.

E.i.E.1.

Hd.cL

Hd.oP

Hd.Eu

Hd.Eo

Hd.Ao

I.080

I.160

I.170

I.180

I.185

I.199

I.310

I.500

I.502

I.505

I.507

I.510

I.515

I.555

General messages

Stop

/ Reset state, wait for next incoming command

End position Lower Eu

End position Lower locked

→ no raising possible (e.g., lock-door)

Closing active

End position Upper Eo

End position Upper locked

→ no closing possible (e.g., safety edge)

Opening active

End position middle E1 (intermediate stop position)

End position middle locked

→ no closing possible (e.g., safety edge)

Fault

→ only deadman travel is possible, possibly automatic opening

Calibration

→ Setting the end positions in deadman travel

(for absolute encoder )

→ Start procedure using STOP key

E-Stop

→ No travel possible, hardware safety chain interrupted

E-travel

→ Deadman travel without taking into account safeties, etc.

Manual

→ Deadman mode

Parameterizing

Automatic

→ indicates change from „Manual“ to „Automatic“ status

Semi-automatic

→ indicates change from „Manual“ to „Semi-automatic“

Initial display after power up (Power Up and self-test)

Status messages during calibration

Calibration of the End position Lower requested (in deadman travel)

Calibration of the End position Upper requested (in deadman travel)

Calibration of the intermediate position E1 (in deadman travel)

Status messages during deadman

Deadman close (membrane key: CLOSE)

Deadman open (membrane key: OPEN)

End position Lower reached, no further deadman close possible

End position Upper reached, no further deadman open possible

Outside of permitted Eo position (no deadman open possible)

Information messages during Automatic mode

Maintenance required soon / service counter nearly expired

Continuous CLOSED still active

Forced opening being performed

Waiting for Foil key pad command

Reset necessary (P.408)

Door cycle not plausible (re-initialize Æ Parameters)

Open-command on Door2 being issued

Correction of upper limit switch running

Upper limit switch band corrected

Correction of lower limit switch running

Lower limit switch band corrected

Limit switch correction finished

Controller is preparing automatic teach-in of the limit switches

Limit switches being corrected

noEr

Er--

Prog

Information messages while parameterizing

Error memory: no error saved

Error memory: if error but no associated message found

Programming message while carrying out original parameter or default set

FEIG ELECTRONIC GmbH Page 23 of 24

WU

WU_Inbetriebnahme13_GB.doc

TST

E.201

E.211

E.212

E.360

E.363

E.370

E.373

E.379

E.000

E.050

E.090

E.101

E.102

E.103

E.104

E.105

E.106

E.107

E.108

E.109

E.110

E.121

...

E.128

E.401

E.402

E.501

E.502

Startup

General inputs

OPEN key on membrane keypad

STOP key on membrane keypad

CLOSE key on membrane keypad

Input 1

Input 2

Input 3

Input 4

Input 5

Input 6

Input 7

Input 8

Input 9

Input 10

Input 21

...

Input 28

Safety/Emergency stop chain

Internal E-Stop „pushbutton“ tripped

External E-Stop 1 tripped

External E-Stop 2 tripped

Safety edge, general

Activation of internal safety edge

Fault in internal safety edge

Activation of external safety edge

Fault in external safety edge

External safety edge activated but not yet plugged in

RC plug-in module

RC Channel 1

RC Channel 2

Induction loop processor plug-in module

Detector Channel 1

Detector Channel 2

WU

FEIG ELECTRONIC GmbH Page 24 of 24 WU_Inbetriebnahme13_GB.doc