Operating Instructions - ACS-Control
User manual M2
User manual M2
Strain gauge amplifier with a calibration for 350 Ω melt pressure sensors
Strain gauge amplifier with a calibration for 350 Ω melt pressure sensors
Operating Instructions
DAL-111x900S
Strain gauge amplifier with a calibration for 350 Ω melt pressure sensors
Technical features:
Technical features:
• red display of -19999…99999 Digits (optional: green, orange or blue display)
•• minimal
installation
depth: 70 mm
without
plug-in
screw
terminal
red display
of -19999…99999
Digits
(optional:
green,
orange
or blue display)
•• min/max-memory
minimal installation depth: 70 mm without plug-in screw terminal
•• 30
additional adjustable supporting points
min/max-memory
•• display
flashing
at threshold
value exceedance
/ threshold value undercut
30 additional
adjustable
supporting
points
•• zero-key
for
triggering
of
hold,
Tara
or
sensor
alignment
display flashing at threshold value exceedance / threshold value undercut
•• digital
input
triggering
of hold,
Tara
or sensor
alignment
zero-key
forfor
triggering
of hold,
Tara
or sensor
alignment
•• permanent
min/max-value
recording
digital input for triggering of hold, Tara or sensor alignment
•• sensor
alignment
with integrated
switching output
permanent
min/max-value
recording
•• mathematic
functions
reciprocal
value, square
sensor alignment
withlike
integrated
switching
output root, squaring or rounding
•• sliding
average
determination
mathematic functions like reciprocal value, square root, squaring or rounding
•• brightness
control
sliding average
determination
•• programming
interlock via access code
brightness control
•• protection
class
IP65 atvia
theaccess
front side
programming
interlock
code
•• plug-in
screw
terminal
protection
class
IP65 at the front side
•• optional:
2 relay
outputs
plug-in screw
terminal
•• accessories:
PC-based
optional: 2 relay
outputsconfiguration-kit PM-TOOL with CD & USB-adapter for devices without
keypad
andconfiguration-kit
for a simple adjustment
of with
standard
• accessories: PC-based
PM-TOOL
CD &devices
USB-adapter for devices without
keypad and for a simple adjustment of standard devices
M2_1MGB.pdf update: 12.03.2015
96x48
M2_1MGB.pdf update: 12.03.2015
96x48
Order code
0
2
3
4
power supply
230V AC
10...30V DC galvanic seperated
230V AC with sensor supply 24V DC/50 mA and digital input (no analog output possible)1)
10...30V DC galvanic seperated with sensor supply 24V DC/ 50 mA and
digital input (no analog output possible) 1)
9
function input
weighing technology
0
DAL-111
2
9
0
function output
display
0
standard configuration
S
0
standard, protection IP65 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
S
ACS-CONTROL-SYSTEM GmbH l Lauterbachstr. 57 l D-84307 Eggenfelden l www.acs-controlsystem.de l [email protected]
Contents
1.
Brief description
2
2.
Assembly
3
3.
Electrical connection
4
4.
Functions and operation description
6
4.1. Programming software PM-TOOL
7
Setting up the device
8
5.1. Switching on
8
5.2. Standard parameterisation (flat operation level)
8
5.
Value assigment for triggering of the singal input
5.3. Programming interlock „RUN“
11
Activation/Deactivation of the programming interlock or change into the professional level
respectively back into the flat operation level
5.4. Extended parameterisation (professional operation level)
5.4.1. Signal input parameter „INP“
12
12
Value assigment for triggering of the singal input incl. linearisation
5.4.2. General device parameter „FCT“
15
Higher device functions like Hold, Tara, min/max permanent, average determination,
brightness control, as well as the control of the digital input and the keyboard configuration
5.4.3. Safety parameter „COD“
18
Assignment of user and master code for locking or access to certain
parameters like e.g. analog output and alarms, etc.
5.4.4. Relay functions „rel“
19
Parameter for the definition of the setpoints
5.4.5. Alarm parameter „AL1…AL4“
21
Activator and dependencies of the alarms
6.
Reset to factory settings
22
Reset of the parameter to the factory default settings
7.
Alarms / Relays
23
Function principle of the switching outputs
8.
Sensor alignment
24
Function diagram for sensors with existing trimming resistor
9.
Technical data
25
10.
Safety advices
27
11.
Error elimination
28
1
ACS-CONTROL-SYSTEM GmbH l Lauterbachstr. 57 l D-84307 Eggenfelden l www.acs-controlsystem.de l [email protected]
3
1. Brief description
1. Brief description
Thepanel
panelmeter
meterDAL-111
M2-1M isisaa5-digit
5-digitdevice
deviceforfor
connection
a 4-wire-measuring
bridge
calibration
The
connection
to ato4-wire-measuring
bridge
with with
calibration
contact(80%
(80%alignment)
alignment)and
andaavisual
visualthreshold
thresholdvalue
valuemonitoring
monitoring
display.
The
configuration
happens
contact
viavia
thethe
display.
The
configuration
happens
via
via four
viaoptional
the optional
PC software
PM-TOOL.
An integrated
programming
interlock
prevents
four
frontfront
keyskeys
or viaorthe
PC software
PM-TOOL.
An integrated
programming
interlock
prevents
unreunrequested
changes
the parameters
and
be unlocked
again
by an individual
code. Optional
the
quested
changes
of theofparameters
and can
becan
unlocked
again by
an individual
code. Optional
the following
following are
functions
are available:
a 10
bridge a
feeding,
a digital
for the
triggering
Hold
(Tara) or
the
functions
available:
a supply for
theVsensor,
digital input
for input
triggering
of Hold
(Tara)ofor
an analog
output
80%-alignment
and two
optional
galvanic isolated setpoints, by which free adjustable threshold values can
for
further processing
in the
equipment.
beuse
controlled
andoptional
reportedgalvanic
to a superior
master
display.
By
of the two
isolated
setpoints,
free adjustable threshold values can be controlled and
The electrical
connection
is carried
outThe
on electrical
the back side
via plug-in
terminals.
reported
to a superior
master
display.
connection
is carried
out on the back side via plug-in terSelectable functions like e.g. the request of the min/max-value, an average determination of the measuring
minals.
signals, a nominal
respectively
setpoint
preset, a direct change
of threshold
value of
in the
operation
mode
Selectable
functionspreset
like e.g.
the request
of the min/max-value,
an average
determination
measuring
and additional
measuring
supporting points
forpreset,
linearisation
complete
modern device
signals,
a nominal
preset respectively
setpoint
a direct
changethe
of threshold
value concept.
in operation mode
and additional measuring supporting points for linearisation complete the modern device concept.
2
4
ACS-CONTROL-SYSTEM GmbH l Lauterbachstr. 57 l D-84307 Eggenfelden l www.acs-controlsystem.de l [email protected]
2. Assembly
2. Assembly
Please read the Safety advices on page 27 before installation and keep this user manual for future reference.
48,0
3,0
M2
Se
alin
g
,0
89
Gap for physical unit
1.
2.
3.
After removing the fixing elements, insert the device.
Check the seal to make sure it fits securely.
Click the fixing elements back into place and tighten the clamping screws by hand. Then use a
screwdriver to tighten them another half a turn.
CAUTION! The torque should not exceed 0.1 Nm!
The dimension symbols can be exchanged before installation via a channel on the side!
3
ACS-CONTROL-SYSTEM GmbH l Lauterbachstr. 57 l D-84307 Eggenfelden l www.acs-controlsystem.de l [email protected]
5
3. Electrical connection
3. Electrical connection
supply of 115 VAC
Type M2-1MR5B.020X.470CD
DAL-111x900S
Type M2-1MR5B.020X.570CD
DAL-111x900S
supply of 230 VAC
supply of 10-30 VDC
Type M2-1MR5B.020X.670CD
DAL-111x900S
6
ACS-CONTROL-SYSTEM GmbH l Lauterbachstr. 57 l D-843074Eggenfelden l www.acs-controlsystem.de l [email protected]
4. Function and operation description
4. Function and operation description
Operation
The operation is divided into three different levels.
Menu level (delivery status)
This level is for the standard settings of the device. Only menu items which are sufficent to set the device
into operation are displayed. To get into the professional level, run through the menu level and parameterise
“prof“ under menu item RUN.
Menu group level (complete function volume)
Suited for complex applications as e.g. linkage of alarms, setpoint treatment, totaliser function etc. In this
level function groups which allow an extended parameterisation of the standard settings are availabe. To
leave the menu group level, run through this level and parameterise „uloc„ under menu item RUN.
Parameterisation level:
Parameter deposited in the menu item can here be parameterised. Functions, that can be changed or
adjusted, are always signalised by a flashing of the display. Settings that are made in the parameterisation
level are confirmed with [P] and thus safed. By pressing the [O]-key (zero-key) it leads to a break-off of the
value input and to a change into the menu level. All adjustments are safed automatically by the device and it
changes into operating mode, if no further key operation is done within the next 10 seconds.
Level
Key
Description
Change to parameterisation level and deposited values.
Menu level
Keys for up and down navigation in the menu level.
Change into operation mode.
To confirm the changes made at the parameterization level.
Parameterisation
level
Adjustment of the value / the setting.
Change into menu level or break-off in value input.
Change to menu level.
Menu group level
Keys for up and down navigation in the menu group level.
Change into operation mode or back into menu level.
5
ACS-CONTROL-SYSTEM GmbH l Lauterbachstr. 57 l D-84307 Eggenfelden l www.acs-controlsystem.de l [email protected]
7
4. Function and operation description
Function chart:
4.1 Parameterisation software PM-TOOL:
Part of the PM-TOOL are the software on CD and one USB-cable with device adapter. The connection
happens via a 4-pole micromatch-plug on the back side of the device, to the PC-side the connection
happens via an USB plug.
System requirements: PC incl. USB interface
Software: Windows XP, Windows VISTA
With this tool the device configuration can be generated, omitted and safed on the PC. The parameters can
be changed via the easy to handle program surface, whereat the operating mode and the possible selection
options can be preset by the program.
CAUTION!
During parameterisation with connected measuring signal, make sure that the measuring signal has no
mass supply to the programming plug. The programming adapter is galvanic not isolated and directly
connected with the PC. Via polarity of the input signal, a current can discharge via the adapter and destroy
the device as well as other connected components!
8
ACS-CONTROL-SYSTEM GmbH l Lauterbachstr. 57 l D-84307 Eggenfelden l www.acs-controlsystem.de l [email protected]
6
5. Setting up the device
5. Setting up the device
5.1. Switching-on
Once the installation is complete, start the device by applying the voltage supply. First, check once again that
all electrical connections are correct.
Starting sequence
For 1 second during the switching-on process, the segment test (8 8 8 8 8) is displayed followed by an
indication of the software type and, after that, also for 1 second the software version. After the starting
sequence, the device switches to operation/display mode.
5.2. Standard parameterisation: (Flat operation level)
To parameterise the display, press the [P]-key in operating mode for 1 second. The display then changes to
the menu level with the first menu item TYPE.
Menu level
Parameterisation level
Selection of the input signal, tYPE:
Default: sens.f
There are 3 measuring input options available for known sensor sensibilities: SENS.1 for 1mV/V,
SENS.2 for 2mV/V and SENS.3 for 3.3mV/V. Each sensor is measured and calibrated up to 4mV/V
via SEnS.F. Confirm the selection with [P] and the display switches back to menu level.
Setting the measuring range end value, END:
Default: 10000
Set the end value from the smallest to the highest digit with [▲] [▼] and confirm each digit with
[P]. A minus sign can only be parameterized on the highest value digit. After the last digit, the
display switches back to the menu level. If Sens was selected as input option, one can only
select between noca and cal. With noca, only the previously set display value is taken over, and
with cal, the device takes over both the display value and the analogue input value.
Setting up the measuring range start/offset value, offs:
Default: 0
Enter the start/offset value from the smallest to the highest digit with [▲] [▼] and confirm each
digit with [P]. After the last digit the display switches back to the menu level. If Sens was
selected as input option, one can only select between noca and cal. With noca, only the
previously set display value is taken over, and with cal, the device takes over both the display
value and the analogue input value.
7
ACS-CONTROL-SYSTEM GmbH l Lauterbachstr. 57 l D-84307 Eggenfelden l www.acs-controlsystem.de l [email protected]
9
5. Setting up the device
Menu level
Parameterisation level
Setting the comma, decimal point, dot :
Default: 0
The decimal point on the display can be moved with [▲] [▼] and confirmed with [P]. The
display then switches back to the menu level again.
Setting up the display time, SEC :
Default: 1.0
then
The display time is set with [▲] [▼]. The display moves up in increments of 0.1 up to 1 second
and in increments of 1.0 up to 10.0 seconds. Confirm the selection by pressing the [P] button.
The display then switches back to the menu level again.
Special function [O]-key, tASt.4:
Default: no
…
For the operation mode, special functions can be deposited on the [O]-key. Activate this
function by pressing the key. With tArA the display is tared to zero und safed permanently as
offset. The device acknowledges the correct taring with oo0oo in the display. Set.tA switches into
the offset value and can thus be changed via the navigation keys [▲] [▼]. EHt.rE deletes the
min/max memory. ActuA shows the measurand, then the display changes onto the
parameterised display value. The same goes for AVG, here the sliding average value is
displayed. If HOLD has been selected, the moment can be hold constant by pressing the [O]-key,
and is updated by releasing the key. Advice: Hold is activated only, if HOLD was selected under
parameter DISPL. If AbS.UA (absolute value) was selected, the display shows the values that have
been measured since the voltage has been connected, without consideration of a previous
taring. With t.tAra (temporarily Tara) the offset is determined by rising shoulder of the digital
input and kept only for the period of the signal. Via SE.CAL a sensor calibration is done by
pushing the zero-key, the flow diagram is shown in chapter 4.4. At AL-1…AL-8 an output can be
set and therewith e.g. a switch of the metering point can be done. If no is selected, the [O]-key
is without any function in the operation mode.
8
10
ACS-CONTROL-SYSTEM GmbH l Lauterbachstr. 57 l D-84307 Eggenfelden l www.acs-controlsystem.de l [email protected]
5. Setting up the device
Menu level
Parameterisation level
Special function digital input, dIG.In:
Default: se.cal
…
The above given parameters can be set for the operation mode onto the optional digital input
aswell. See function description tASt.4.
Threshold values / limit values, LI-1:
Default: 2000
This limit value defines the threshold, that leads to an activation / deactivation of the alarm.
Hysteresis for limit values, HY-1:
Default: 0
The difference to the threshold value that causes the delay of the actuation of the alarm, is
defined by the hysteresis.
Function if display falls below / exceeds limit value, FU-1:
Default: high
The limit value undercut can be selected with Louu (LOW = lower limit value) and limit value
exceedance can be selected with high (HIGH = upper limit value). If e.g. limit value 1 is on a
switching threshold of 100 and occupied with function high, the alarm will be activated by
reaching the threshold. If the limit value is allocated to Low, an alarm will be activated by
undercut of the threshold.
Threshold values / limit values, LI-2:
Default: 3000
This limit value defines the threshold, that leads to an activation / deactivation of the alarm.
9
ACS-CONTROL-SYSTEM GmbH l Lauterbachstr. 57 l D-84307 Eggenfelden l www.acs-controlsystem.de l [email protected]
11
5. Setting up the device
Menu level
Parameterisation level
Hysteresis for threshold values, HY-2:
Default: 0
The difference to the threshold value that causes the delay of the actuation of the alarm, is
defined by the hysteresis.
Function if display falls below / exceeds limit value, FU-2
Default: high
The limit value undercut can be selected with Louu (LOW = lower limit value) and limit value
exceedance can be selected with high (HIGH = upper limit value). If e.g. limit value 1 is on a
switching threshold of 100 and occupied with function high, the alarm will be activated by
reaching the threshold. If the limit value is allocated to Low, an alarm will be activated by
undercut of the threshold.
User code (4-digit number-combination, free available), U.CodE:
Default: 0000
If this code is set (>0000), all parameters are locked for the user, if LOC has been selected under
menu item run. By pressing [P] for approx. 3 seconds in operation mode, the message CODE is
shown in the display. Enter the preset u.code to get access to the set of parameters which are
unlocked for the user. The code needs to be entered bevor each try of parameterisation, as
long as A.Code (Master code) all parameters are unlocked again.
Master code (4-digit number-combination free available), A.CodE:
Default: 1234
After LOC has been activated under menu item Run, this code can be used for unlocking all
parameters. By pressing [P] for approx. 3 seconds in operation mode, the message CODE is
shown in the display and offer the user access to all parameters by entering A.codE. While
leaving this parameterisation it can be unlocked permanently under run by selecting ULOC or
ProF. So, at an anew pressing of [P] in operating mode, an anew entereing of the code is not
needed.
12
10
ACS-CONTROL-SYSTEM GmbH l Lauterbachstr. 57 l D-84307 Eggenfelden l www.acs-controlsystem.de l [email protected]
5. Setting up the device
Menu level
Parameterisation level
5.3. Programming interlock
Activation / Deactivation of the programming interlock or completion of the standard
parameterisation with change into menu group level (complete function volume), run:
Default: uloc
Choose between the deactivated key lock Uloc (works setting), the activated key lock Loc, or the
menu group level ProF with the navigation keys [▲] [▼]. Confirm the selection with [P]. After
this, the display confirms the settings with "- - - - -", and automatically switches to operating
mode. If Loc was selected, the keyboard is locked. To get back into the menu level, press [P]
for 3 seconds in operating mode. Now enter the CODE (works setting 1234) that appears using
[▲] [▼] plus [P] to unlock the keyboard. FAIL appears if the input is wrong.
To parameterise further functions, ProF needs to be set. The device confirms this setting with
„- - - - -„ and changes automatically into operation mode. By pressing [P] for approx. 3 seconds
in operation mode, the first menu group InP is shown in the display and thus confirms the
change into the extended parameterisation. It stays as long activated as ULOC is entered in
menu group RUN, thus the display is set back in standard parameterisation again.
11
ACS-CONTROL-SYSTEM GmbH l Lauterbachstr. 57 l D-84307 Eggenfelden l www.acs-controlsystem.de l [email protected]
13
5. Setting up the device
5.4. Extended parameterisation (Professional operation level)
5.4.1. Signal input parameters
Menu group level
Menu level
Menu level
Parameterisation level
Selection of the input signal, tYPE:
Default: sens.f
There are 3 measuring input options available for known sensor sensibilities: SENS.1 for 1mV/V,
SENS.2 for 2mV/V and SENS.3 for 3,3mV/V. Each sensor is measured and calibrated up to 4mV/V
via SEnS.F. Confirm the selection with [P] and the display switches back to menu level.
Setting the measuring range end value, END:
Default: 10000
Set the end value from the smallest to the highest digit with [▲] [▼] and confirm each digit with
[P]. A minus sign can only be parameterized on the highest value digit. After the last digit, the
display switches back to the menu level. If Sens was selected as input option, one can only
select between noca and cal. With noca, only the previously set display value is taken over, and
with cal, the device takes over both the display value and the analogue input value.
Setting up the measuring range start/offset value, offs:
Default: 0
Enter the start/offset value from the smallest to the highest digit with [▲] [▼] and confirm each
digit with [P]. After the last digit the display switches back to the menu level. If Sens was
selected as input option, one can only select between noca and cal. With noca, only the
previously set display value is taken over, and with cal, the device takes over both the display
value and the analogue input value.
Setting up the display time, SEC:
Default: 1.0
then
The display time is set with [▲] [▼]. The display moves up in increments of 0.1 sec up to 1 sec
and in increments of 1.0 sec up to 10.0 sec. Confirm the selection by pressing the [P] button.
The display then switches back to the menu level again.
14
12
ACS-CONTROL-SYSTEM GmbH l Lauterbachstr. 57 l D-84307 Eggenfelden l www.acs-controlsystem.de l [email protected]
5. Setting up the device
Menu level
Parameterisation level
Rescaling the measuring input values, EndA:
Default: 10000
With this function, you can rescale the input value of e.g. 1.1 mV (works setting) without
applying a measuring signal.
Rescaling the measuring input values, OFFA:
Default: 0
With this function, you can rescale the input value of e.g. 0.1 mV (works setting) without
applying a measuring signal.
Setting up the tare/offset value, tArA:
Default: 0
The given value is added to the linearized value. In this way, the characteristic line can be
shifted by the selected amount.
Setting up the balance point, Adj.pt:
Default: 80.00
The balance point is preset to 80%. Assume an 80% detuning while switching the alignment
relay during an automatic sensor alignment. This value can be freely adjusted.
Number of additional setpoints, SPCt:
Default: 00
30 additional setpoints can be defined to the initial value and final value, so linear sensor
values are not linearised. Only activated setpoint parameters are displayed.
Display values for setpoints, dIS.01 … dIS.30:
Under this parameter setpoints are defined according to their value. At the sensor calibration,
like at final value/offset, one is asked at the end if a calibration shall be activated.
13
ACS-CONTROL-SYSTEM GmbH l Lauterbachstr. 57 l D-84307 Eggenfelden l www.acs-controlsystem.de l [email protected]
15
5. Setting up the device
Menu level
Parameterisation level
Analog values for setpoints, InP.01 … InP.30:
The setpoints are always preset according to the selected input signal mA/V. The demanded
analog values can be freely adjusted in ascending order.
Device undercut, dI.Und:
Default: -i9999
With this function the device undercut (_ _ _ _ _) can be defined on a definite value. Exception is
input type 4-20 mA, it already shows undercut at a signal <1 mA, so a sensor failure is marked.
Display overflow, dI.OUE:
Default: 99999
_____
With this function the display overflow (
) can be defined on a definite value.
Back to menu group level, rEt:
With [P] the selection is confirmed and the device changes into menu group level „–INP–“.
14
16
ACS-CONTROL-SYSTEM GmbH l Lauterbachstr. 57 l D-84307 Eggenfelden l www.acs-controlsystem.de l [email protected]
5. Setting up the device
5.4.2. General device parameters
Menu group level
Menu level
Menu level
Parameterisation level
Display time, DISEC:
Default: 01.0
then
The display time is set up with [▲] [▼]. Thereby you switch up to 1 second in increments of
0.1 and up to 10.0 seconds in increments of 1.0. With [P] the selection is confirmed and the
device changes into menu level.
Rounding of display values, round:
Default: 00001
This function is for instable display values, where the display value is changed in 1-, 5-, 10- or
50-steps. This does not affect the resolution of the optional outputs. With [P] the selection is
confirmed and the device changes into menu level.
Arithmetics, ArItH:
Default: no
Reciprocal
Root extraction
Square
With this function the calculated value, not the measuring value, is shown in the display. With
no, no calculation is deposited. With [P] the selection is confirmed and the device changes into
menu level.
Sliding average determination, AVG:
Default: 10
Under this menu item, the number of measurements that need to be averaged are preset. The
averaging time results from the product of measuring time SEC and the averaged measurements
AVG. With selection of AVG in menu level DISPL the result is shown in the display and evaluated
when entered in the alarm AL1-Al4.
Zero point slowdown, ZErO:
Default: 00
At the zero point slowdown, a value range around the zero point can be preset, so the display
shows a zero. If e.g.10 is set, the display would show a zero in the value range from -10 to +10;
below continue with -11 and beyond with +11. The maximum adjustable range of value is 99.
15
ACS-CONTROL-SYSTEM GmbH l Lauterbachstr. 57 l D-84307 Eggenfelden l www.acs-controlsystem.de l [email protected]
17
5. Setting up the device
Menu level
Parameterisation level
Display, dISPL:
Default: actua
With this function the current measuring value, the min/max-value, the totaliser, the processcontrolled hold-value, the sliding average value, the constant value or the difference between
constant value and current value can be allocated to the display. With [P] the selection is
confirmed and the device changes into menu level.
Brightness control, Light:
Default: 15
The brightness of the display can be adjusted in 16 levels from 00 = very dark to 15 = very
bright via this parameter or alternatively via the navigation keys from the outside. During the
start of the device the level that is deposited under this parameter will always be used, even
though the brightness has been changed via the navigation keys in the meantime.
Display flashing, FLASH:
Default: no
A display flashing can be added as additional alarm function either to single or to a combination
of off-limit condition. With no, no flashing is allocated.
Assignment (deposit) of key functions, tASt:
Default: no
For the operation mode, special functions can be deposited on the navigation keys [▲] [▼], in
particular this function is made for devices in housing size 48x24mm which do not have a 4th
key ([O]-key). If the min/max-memory is activated with EHtr, all measured min/max-values are
safed during operation and can be recalled via the navigation keys. The values get lost by
restart of the device. If the threshold value correction LI.12 or LI.34 is choosen, the values of the
threshold can be changed during operation without disturbing the operating procedure. With
tArA the device is tared to zero and safed permanently as Offset. The device confirms the
correct taring by showing ooooo in the display. Set.tA changes into the offset value and can be
changed via the navigation keys [▲] [▼]. The configuration of EHt.rE deletes the min/maxmemory.
16
18
ACS-CONTROL-SYSTEM GmbH l Lauterbachstr. 57 l D-84307 Eggenfelden l www.acs-controlsystem.de l [email protected]
5. Setting up the device
Menu level
Parameterisation level
Continuation of „Assignment (deposit) of key functions, tASt“
Under ActuA the measurand is shown, after this the display returns to the parametrised display
value. If AbS.UA (absolute value) was selected, the display shows the value that has been
measured since voltage connection, without consideration of a previous taring. The adjustment
of the brightness of display is done via light; this adjustment is not safed and gets lost by
restart of the device. If no is selected, the navigation keys are without any function in the
operation mode.
Special function [O]-key, tASt.4:
Default: no
…
For the operation mode, special functions can laid be on the [O]-key. Activate this function by
pushing the key. With tArA the display is tared to zero and is safed permanently as offset. The
display confirms the correct taring by showing ooooo in the display. Set.tA switches into the
offset value and can be change via the navigation keys [▲] [▼]. EHt.rE deletes the min/maxmemory. ActuA shows the measuring value. Then the display switches to the parameterised
display value. The same goes for AVG, here the sliding average value is displayed. At selected
HOLD the instant value is held by pushing the [O]-key and updated by releasing the key. Advice:
Hold can only be activated if HOLD was selected under parameter DISPL. If AbS.UA (absolute value)
was selected, the display shows the values that have been measured since the voltage has
been connected, without consideration of a previous taring. With t.tAra (temporarily Tara) the
offset is determined by rising shoulder of the digital input and kept only for the period of the
signal. Via SE.CAL a sensor calibration is done by pushing the zero-key, the flow diagram is
shown in chapter 8. At AL-1…AL-8 an output can be set and therewith e.g. a switch of the
metering point can be done. If no is selected, the [O]-key has no function in the operation
mode.
Special function digital input, dIG.In:
Default: no
…
For the operation mode, the above shown parameters can be laid on the optional digital input,
too. Functions description see tASt.4.
Back to menu group level, rEt:
With [P] the selection is confirmed and the device changes into menu group level „–fct–“.
17
ACS-CONTROL-SYSTEM GmbH l Lauterbachstr. 57 l D-84307 Eggenfelden l www.acs-controlsystem.de l [email protected]
19
5. Setting up the device
5.4.3. Safety parameters
Menu group level
Menu level
Menu level
Parameterisation level
Adjustment of user code, U.Code:
Default: 0000
Via this code reduced sets of parameters out.le and al.lev can be unlocked during locked
programming. Further parameters are not available via this code. The U.CodE can only be
changed via the correct input of the A.CodE (Master code).
Master code, A.Code:
Default: 1234
By entering A.CodE the device will be released and all parameters unlocked.
Release/lock alarm parameters, AL.LEU:
Default: all
This parameter describes the user release/user lock of the alarm.
- LIMIt, here only the range of value of the threshold values 1-4 can be changed
- ALrM.L, here the range of value and the alarm trigger can be changed
- ALL, all alarm parameters are released
- no, all alarm parameters are locked
Back to menu group level, rEt:
With [P] the selection is confirmed and the device changes into menu group level „–cod–“.
20
ACS-CONTROL-SYSTEM GmbH l Lauterbachstr. 57 l D-84307
18Eggenfelden l www.acs-controlsystem.de l [email protected]
5. Setting up the device
5.4.4. Relay functions
Menu group level
Menu level
Menu level
Parameterisation level
Alerting relay 1, rEL-1:
Default: al-1
….
….
Each setpoint (optional) can be linked up via 4 alarms (by default). This can either be inserted
at activated alarms AL1/4 or deactivated alarms ALN1/4. If LOGIC is selected, logical links are
available in the menu level LoG-1 and CoM-1. Access to these two menu levels is via LOGIC, at all
other selected functions, these two parameters are overleaped. Via On/OFF the setpoints can be
activated/deactivated, in this case the output and the setpoint display are set/not set on the
front of the device. With [P] the selection is confirmed and the device changes into menu level.
Logic relay 1, Log-1
Default: or
Here, the switching behavior of the relay is defined via a logic link, the following schema
describes these functions with inclusion of AL-1 and AL-2: This parameter can only be selected if
LOGIC was selected under REl-1 .
A1 v A2
As soon as a selected alarm is activated, the relay
operates. Equates to operating current principle.
A1 v A2 = A1 Λ A2
The relay operates only, if no selected alarm is
active. Equates to quiescent current principle.
A1 Λ a2
The relay operates only, if all selected alarms are
active.
A1 Λ A2 = A1 v A2
As soon as a selected alarm is not activated, the
relay operates.
____ _ _
____ _ _
With [P] the selection is confirmed and the device changes into menu level.
Alarms for relay 1, CoM-1:
Default: a.1
….
The allocation of the alarms to relay 1 happens via this parameter, one alarm or a group of
alarms can be chosen. This parameter can only be selected if LOGIC was selected under REl-1.
With [P] the selection is confirmed and the device changes into menu level.
19
ACS-CONTROL-SYSTEM GmbH l Lauterbachstr. 57 l D-84307 Eggenfelden l www.acs-controlsystem.de l [email protected]
21
5. Setting up the device
Menu level
Parameterisation level
Alerting relay 2, reL-2:
Default: al-2
….
….
Each setpoint (optional) can be linked up via 4 alarms (by default). This can either be inserted
at activated alarms AL1/4 or deactivated alarms ALN1/4. If LOGIC is selected, logical links are
available in the menu level LoG-1 and CoM-1. Access to these two menu levels is via LOGIC, at all
other selected functions, these two parameters are overleaped. Via On/OFF the setpoints can be
activated/deactivated, in this case the output and the setpoint display are set/not set on the
front of the device. With [P] the selection is confirmed and the device changes into menu level.
Logic relay 2, LoG-2:
Default: or
Here, the switching behavior of the relay is defined via a logic link, the following schema
describes these functions with inclusion of AL-1 and AL-2: This parameter can only be selected if
LOGIC was selected under REl-1 .
A1 v A2
As soon as a selected alarm is activated, the relay
operates. Equates to operating current principle.
A1 v A2 = A1 Λ A2
The relay operates only, if no selected alarm is
active. Equates to quiescent current principle.
A1 Λ a2
The relay operates only, if all selected alarms are
active.
A1 Λ A2 = A1 v A2
As soon as a selected alarm is not activated, the
relay operates.
____ _ _
____ _ _
With [P] the selection is confirmed and the device changes into menu level.
Alarms for relay 2, CoM-2:
Default: a.2
….
The allocation of the alarms to relay 1 happens via this parameter, one alarm or a group of
alarms can be chosen. This parameter can only be selected if LOGIC was selected under REl-1.
With [P] the selection is confirmed and the device changes into menu level.
Back to menu group level, rEt:
With [P] the selection is confirmed and the device changes into menu group level „–rel–“.
20
22
ACS-CONTROL-SYSTEM GmbH l Lauterbachstr. 57 l D-84307 Eggenfelden l www.acs-controlsystem.de l [email protected]
5. Setting up the device
5.4.5. Alarm parameters
Menu group level
Menu level
Menu level
Parameterisation level
Depedency of alarm.1, ALrM.1:
Default: actua
The dependency of alarm.1 can be related to special functions, in detail these are the current
measurand, the min-value, the max-value, the absolute value or the sliding average value. If
Hold is selected the alarm is hold and processed just after deactivation of HOLD. EHtEr causes the
dependency either by pressing the [O]-key on the front of the housing or by an external signal
via the digital input. With [P] the selection is confirmed and the device changes into menu level.
Example:
By using the maximum value Alarm.1=Max.va in combination with a threshold monitoring
Fu-1=High, an alarm confirmation can be realised. Use the navigation keys or the fourth key for
confirmation.
Threshold values / limits, LI-1:
Default: 2000
This limit value defines the threshold, that leads to an activation / deactivation of the alarm.
Hysteresis for threshold values, HY-1:
Default: 00000
The difference to the threshold value that causes the delay of the actuation of the alarm, is
defined by the hysteresis.
Function for threshold value exceedance/-undercut, Fu-1:
Default: high
The limit value undercut can be selected with Louu (LOW = lower limit value) and limit value
exceedance can be selected with high (HIGH = upper limit value). If e.g. limit value 1 is on a
switching threshold of 100 and occupied with function high, the alarm will be activated by
reaching the threshold. If the limit value is allocated to Low, an alarm will be activated by
undercut of the threshold.
21
ACS-CONTROL-SYSTEM GmbH l Lauterbachstr. 57 l D-84307 Eggenfelden l www.acs-controlsystem.de l [email protected]stem.de
23
6. Reset to factory settings
Menu level
Parameterisation level
Switching-on delay, ton-1:
Default: 000
For limit value 1 one can preset a delayed switching-on of 0-100 seconds.
Switching-off delay, toF-1:
Default: 000
For limit value 1 one can preset a delayed switching-off of 0-100 seconds.
Back to menu group level, rEt:
With [P] the selection is confirmed and the device changes into menu group level „–Ali–“.
The same applies to –Al2– to –Al4–.
Programming interlock:
Menu-group level
Description see page 11, menu-level run
6. Reset to factoty settings
To return the unit to a defined basic state, a reset can be carried out to the default values.
The following procedure should be used:
• Switch off the power supply
• Press button [P]
• Switch on voltage supply and press [P]-button until „- - - - -“ is shown in the display.
With reset, the default values of the program table are loaded and used for subsequent operation. This sets
the unit back to the state in which it was supplied.
Caution! All application-related data are lost.
24
ACS-CONTROL-SYSTEM GmbH l Lauterbachstr. 57 l D-84307 Eggenfelden l www.acs-controlsystem.de l [email protected]
22
7. Alarms / Relays
7. Alarms / Relays
This device has 4 virtual alarms that can monitor one limit value in regard of an undercut or exceedance.
Each alarm can be allocated to an optional relay output S1-S2; furthermore alarms can be controlled by
events like e.g. Hold or min/max-value.
Function principle of alarms / relays
Alarm / Relay x
Deactivated, instantaneous value, min/max-value, Hold-value, sliding
average value or an activation via the digital input or the [O]-key.
Switching threshold
Threshold / limit value of the change-over
Hysteresis
Broadness of the window between the switching thresholds
Working principle
Operating current / Quiescent current
Operating current
By operating current the alarm S1-S2 is off
below the threshold and on on reaching the
threshold.
Quiescent current
By quiescent current the alarm S1-S2 is on
below the threshold and switched off on
reaching the threshold.
Switching-on delay
The switching-on delay is activated via an
alarm and e.g. switched 10 seconds after
reaching the switching threshold, a shortterm exceedance of the switching value does
not cause an alarm, respectively does not
cause a switching operation of the relay. The
switching-off delay operates in the same way,
keeps the alarm / the relay switched longer
for the parameterised time.
23
ACS-CONTROL-SYSTEM GmbH l Lauterbachstr. 57 l D-84307 Eggenfelden l www.acs-controlsystem.de l [email protected]
25
8. Sensor calibration offset / final value
8. Sensor calibration offset / final value
The device has an automatic calibration at mass pressure sensors, where an integrated switching output
operates an often available 80% calibration. Like this offset and final value are adjusted, and the sensor
can be applied directly after this. The calibration can be done via the 4th key or the digital input, depending
on the parameterisation.
Push Trigger for minimum 3
seconds.
For min. 1 measuring cycle,
min. 1s or max. by trigger.
Current measuring range
value in per cent.
For min. 1 measuring cycle, min. 1s
or max. by trigger.
Breached at +/- 20% range
monitoring.
80%-switching output
activated.
For min. 1 measuring cycle,
min. 1s or max. by trigger.
Current measuring range value
in per cent.
For min. 1 measuring cycle,
min. 1s or max. by trigger.
Breached at +/20% range
monitoring.
Switch-off 80%-switching ouput
and display for min. 1 measuring
cycle or min. 1s waiting time.
Back to regular operation mode.
Back to regular operation mode
after 1s or 1 measuring cycles.
If a special input range SENS.1, SENS.2, SENS.3 was selected under type, a checking of the range is done for
offset and final value. At an undercut/exceedance of ± 20% of adjustment range, an C.FAIl is given out.
26
24
ACS-CONTROL-SYSTEM GmbH l Lauterbachstr. 57 l D-84307 Eggenfelden l www.acs-controlsystem.de l [email protected]
9. Technical data
9. Technical data
Housing
Dimensions
96x48x70 mm (BxHxD)
96x48x89 mm (BxHxD) including plug-in terminal
Panel cut-out
92.0+0.8 x 45.0+0.6 mm
Wall thickness
up to 15 mm
Fixing
screw elements
Material
PC Polycarbonate, black, UL94V-0
Sealing material
EPDM, 65 Shore, black
Protection class
standard IP65 (front), IP00 (back side)
Weight
approx. 200 g
Connection
plug-in terminal; wire cross-section up to 2.5 mm2
Display
Digit height
14 mm
Segment colour
red (optional green, orange or blue)
Display range
-19999 up to 99999
Setpoints
one LED per setpoint
Overflow
horizontal bars at the top
Underflow
horizontal bars at the top
Display time
0.1 to 10.0 seconds
Input
Sensor sensitivity
1mV/V, 2mV/V, 3.3mV/V, free up to 4 mV/V with 80% calibration
Measuring bridge
250 – 500 Ω / 20 – 40 mA
Measuring error
0,2% of measuring range in electromagnetic dominated environment,
1% of measuring range in industrial invironment with strong disturbing
source
Digital input
< 2.4 V OFF, 10 V ON, max. 30 VDC
RI ~ 5 kΩ
Sensor calibration
always required
Accuracy
Temperature drift
100 ppm / K
Measuring time
0.1…10.0 seconds
Measuring principle
U/F-conversion
Resolution
approx. 18 bit at 1s measuring time, 3.3 mV/V measuring range
25
ACS-CONTROL-SYSTEM GmbH l Lauterbachstr. 57 l D-84307 Eggenfelden l www.acs-controlsystem.de l [email protected]
27
9. Technical data
Output
Switching outputs
Relay with change-over contacts
Switching cycles
250 VAC / 5 AAC; 30 VDC / 5 ADC
30 x 103 at 5 AAC, 5 ADC ohm resistive burden
10 x 106 mechanically
Diversification according to DIN EN50178 /
Characteristics according to DIN EN60255
Power supply
230 VAC ±10 % max. 10 VA
10-30 VDC galv. isolated, max. 4 VA
Memory
EEPROM
Data life
≥ 100 years at 25°C
Ambient conditions
28
Working temperature
0…50°C
Storing temperature
-20…80°C
Weathering resistance
relative humidity 0-80% on years average without dew
EMV
EN 61326
CE-sign
Conformity according to directive 2004/108/EG
Safety standard
According to low voltage directive 2006/95/EG
EN 61010; EN 60664-1
26
ACS-CONTROL-SYSTEM GmbH l Lauterbachstr. 57 l D-84307 Eggenfelden l www.acs-controlsystem.de l [email protected]
10. Safety advices
10. Safety advices
Please read the following safety advices and the assembly chapter 2 before installation and keep
it for future reference.
Proper use
The M2-1M
DAL-111--device
is designed
for the
evaluation
display
of sensor
signals.
The
device is designed
for the
evaluation
andand
display
of sensor
signals.
Attention! Careless use or improper operation can result in
personal injury and/or cause damage to the equipment.
Control of the device
The panel meters are checked before dispatch and sent out in perfect condition. Should there be
any visible damage, we recommend close examination of the packaging. Please inform the
supplier immediately of any damage.
Installation
The
device must
be be
installed
by a
qualified
specialist
The M2-1M
DAL-111-device
must
installed
bysuitably
a suitably
qualified
specialist(e.g.
(e.g.with
witha aqualification
qualificationinin
industrial
industrial electronics).
electronics).
Notes on installation
• There must be no magnetic or electric fields in the vicinity of the device, e.g. due to
transformers, mobile phones or electrostatic discharge.
• The fuse rating of the supply voltage should not exceed a value of 6A N.B. fuse.
• Do not install inductive consumers (relays, solenoid valves etc.) near the device and
suppress any interference with the aid of RC spark extinguishing combinations or free-wheeling
diodes.
• Keep input, output and supply lines separate from one another and do not lay them parallel with
each other. Position “go” and “return lines” next to one another. Where possible use twisted pair.
So, you receive best measuring results.
• Screen off and twist sensor lines. Do not lay current-carrying lines in the vicinity. Connect the
screening on one side on a suitable potential equaliser (normally signal ground).
• The device is not suitable for installation in areas where there is a risk of explosion.
• Any electrical connection deviating from the connection diagram can endanger human life
and/or can destroy the equipment.
• The terminal area of the devices is part of the service. Here electrostatic discharge needs to be
avoided. Attention! High voltages can cause dangerous body currents.
• Galvanic isolated potentials within one complex need to be placed on an appropriate point
(normally earth or machines ground). So, a lower disturbance sensibility against impacted
energy can be reached and dangerous potentials, that can occur on long lines or due to faulty
wiring, can be avoided.
27
ACS-CONTROL-SYSTEM GmbH l Lauterbachstr. 57 l D-84307 Eggenfelden l www.acs-controlsystem.de l [email protected]
29
11. Error elimination
11. Error elimination
30
Error description
Measures
1.
The unit permanently indicates
overflow.
• The input has a very high measurement, check
the measuring circuit.
• With a selected input with a low voltage signal,
it is only connected on one side or the input is
open.
• Not all of the activated switching points are
parameterised. Check if the relevant
parameters are adjusted correctly.
• An absolutely incorrect alignment has been
done bevor, e.g. without connected sensor. In
this case a reset to the factory setting should
be carried out.
2.
The unit permanently shows
underflow.
• The input has a very low measurement, check
the measuring circuit .
• With a selected input with a low voltage signal,
it is only connected on one side or the input is
open.
• Not all of the activated switching points are
parameterised. Check if the relevant
parameters are adjusted correctly.
• An absolutely incorrect alignment has been
done bevor, e.g. without connected sensor. In
this case a reset to the factory setting should
be carried out.
3.
The word "HELP " lights up in the
7-segment display.
• The unit has found an error in the configuration
memory. Perform a reset on the default values
and reconfigure the unit according to your
application.
4.
Program numbers for parameterising
of the input are not accessible.
• Programming lock is activated
• Enter correct code
5.
"Err1" lights up in the 7-segment
display
• Please contact the manufacturer if errors of
this kind occur.
6.
The device does not react as
expected.
• If you are not sure that the device has been
parameterised before, then follow the steps as
written in chapter 6 and set it back to its
delivery status.
28
ACS-CONTROL-SYSTEM GmbH l Lauterbachstr. 57 l D-84307 Eggenfelden l www.acs-controlsystem.de l [email protected]
ACS-CONTROL-SYSTEM GmbH l Lauterbachstr. 57 l D-84307 Eggenfelden l www.acs-controlsystem.de l [email protected]
31

Pegel
Druck


Temperatur Durchfluss
Registrierung
Visualisierung
¸



Füllstand



Messumformer
Sensorik
USV
Wir erwarten Ihren Anruf.
ACS-CONTROL-SYSTEM GmbH
Lauterbachstr. 57
D- 84307 Eggenfelden
know how mit System
Ihr Partner für Messtechnik und Automation
¸
[email protected]
www.acs-controlsystem.de
Stand 03/2015
ACS-CONTROL-SYSTEM
Tel: +49 (0) 8721-9668-0
Fax: +49 (0) 8721-9668-30
Was this manual useful for you? yes no
Thank you for your participation!