test report - PULS Power Supply

test report - PULS Power Supply
Page 2 of 34
Report No.: T223-0314/02
Particulars: test item vs. test requirements
Equipment mobility .......................... : Built in equipment, not intended for direct connection to mains.
Operating condition .......................... : Continuous stand-by mode and intermittent charging/ hold-up time
mode.
Mains supply tolerance (%) .............. : 22,5 Vdc – 30 Vdc (charging from 23 Vdc to 28 Vdc)
Tested for IT power systems ........... : No
IT testing, phase-phase voltage (V) : Class of equipment .......................... : class II
Mass of equipment (kg).................... : 0,7 kg.
Protection against ingress of water . : IP20
Test case verdicts
Test case does not apply to the test object :
N/A
Test item does meet the requirement ........:
P(ass)
Test item does not meet the requirement ..:
F(ail)
Testing
Date of receipt of test item .........................:
2002-09-10
Date(s) of performance of test ...................:
2002-09-10 to 2002-10-08
General remarks
”This report is not valid as a CB Test Report unless appended to a CB Test Certificate issued by a NCB, in
accordance with IECEE 02”.
This report shall not be reproduced except in full without the written approval of the testing laboratory.
The test results presented in this report relate only to the item(s) tested.
”(see remark #)" refers to a remark appended to the report.
"(see Annex #)" refers to an annex appended to the report.
Throughout this report a comma is used as the decimal separator.
This Test Report includes the following documents:
1. Test Report - 34 pages
2. National Differences - Enclosure 1 - 52 pages
3. Additional Test Data - Enclosure 2 - 5 pages
4. Pictures - Enclosure 3 - 5 pages
5. Schematics - Enclosure 4 - 10 pages
TRF No.:1950__F
TRF originator: FIMKO
Page 3 of 34
Report No.: T223-0314/02
Copy of marking plate and summary of test results (information/comments):
TRF No.:1950__F
TRF originator: FIMKO
Page 4 of 34
Report No.: T223-0314/02
Summary of Testing
Summary of testing:
This component has been judged on the basis of the required spacings in the Standard for Safety of
Information Technology Equipment, IEC60950 and CSA C22.2 No. 60950 * UL60950,
Third Edition, dated December 1, 2000.
1.
The products were tested on a DC source with the current capability of 40 A.
2.
The input and output is rated SELV, hazardous energy level.
3.
The terminals and connectors are suitable for field wiring only.
4.
The unit generates internally voltage exceeding the limits of SELV. The unit is class II. The hazard
internal voltage is separated from the enclosure by double insulation.
The metal enclosure of the unit can be connected to Protective Earth. The input of the unit is also
allowed to be connected to Protective Earth.
5.
The unit is intended for built in use. It is not required, that the unit will be earthed within the
application.
6.
The maximum working voltage present is 188 V rms; 192 V pk.
7.
The equipment has been evaluated for use in a Pollution Degree 2 environment.
8.
A suitable Electrical and Fire enclosure shall be provided.
TRF No.:1950__F
TRF originator: FIMKO
Page 5 of 34
Report No.: T223-0314/02
General product information:
The unit is in parallel to a 24 Vdc output. It generates internally out of the 24 Vdc a high secondary voltage
of 180 Vdc loading internal capacitors. In case mains gets away, the unit transfers the internal loaded
energy to 24 Vdc and buffers for around 400 msec. the output. (see drawing below)
The unit has a threshold adjustment via a jumper in front. It starts supplying energy to the output (to buffer)
if the voltage of the external power supply drops either below 22,5 Vdc or 1 Vdc below the average.
Safety aspects:
1. The unit has protection by diodes against wrong connection (+ and – exchanged).
2. The unit provides an voltage regulation of the internal hazard voltage and an over voltage
protection, in case the voltage regulation would fail to avoid overload of the capacitors.
3. The unit provides a current limitation at the output.
4. The unit provides for the output voltage regulation, current limitation and over voltage protection. In
case of an error, the internal capacitors (high voltage) will be deloaded immediately. In addition
transorb diodes rated 36 Vdc, which limit the output voltage in case any electronical protection
would fail to assure, that the output will stay SELV. The input is protected by two diodes,
transistors against back-feeding of the internal hazard voltage. Additional abnormal testing was
performed to assure, that the input will remain SELV in case of an failure.
The loading current is adjusted, therefore there is no high inrush current.
TRF No.:1950__F
TRF originator: FIMKO
Page 6 of 34
TRF No.:1950__F
Report No.: T223-0314/02
TRF originator: FIMKO
Page 7 of 34
Report No.: T223-0314/02
IEC 60 950
Clause
Requirement – Test
1.5
Components
1.5.1
Comply with IEC 60950 or relevant component
standard
(see appended table 1.5.1)
P
1.5.2
Evaluation and testing of components
Certified components are used
in accordance with their ratings,
certifications and they comply
with applicable parts of this
standard.
Components not certified are
used in accordance with their
ratings and they comply with
applicable parts of IEC 60950
and the relevant component
standard.
Components, for which no
relevant IEC-standard exists,
have been tested under the
conditions occurring in the
equipment, using applicable
parts of IEC 60950.
P
1.5.3
Thermal controls
No thermal controls.
1.5.4
Transformers
1.5.5
Interconnecting cables
No interconnecting cables.
N/A
1.5.6
Capacitors in primary circuits ............................. :
The unit is SELV in / SELV out
and does not provide primary
voltage.
N/A
1.5.7
Double or reinforced insulation bridged by
components
No such components bridging
double or reinforced insulation.
N/A
1.5.7.1
Bridging capacitors
N/A
1.5.7.2
Bridging resistors
N/A
1.5.7.3
Accessible parts
N/A
1.5.8
Components in equipment for IT power systems
1.6
Power interface
N/A
1.6.1
AC power distribution systems
N/A
1.6.2
Input current
(see appended table 1.6.2)
N/A
1.6.3
Voltage limit of hand-held equipment
The equipment is not handheld.
N/A
1.6.4
Neutral conductor
No Neutral is provided
N/A
1.7
Marking and instructions
TRF No.:1950__F
Result – Remark
Verdict
P
N/A
N/A
No primary circuit.
N/A
P
TRF originator: FIMKO
Page 8 of 34
Report No.: T223-0314/02
IEC 60 950
Clause
Requirement – Test
1.7.1
Power rating
Result – Remark
Verdict
P
Rated voltage(s) or voltage range(s) (V) ............:
See Type Label
P
Symbol for nature of supply, for d.c. only............:
“DC” is used.
P
Rated frequency or rated frequency range (Hz) :
N/A
Rated current (A) ...............................................:
See Type Label
P
Manufacturer’s name/Trademark ......................:
See Type Label
P
Type/model ........................................................:
See Type Label
The unit is for built in use. The
function of the unit is to
simulate a back-up battery for
short interruptions.
P
Symbol of Class II ..............................................:
Other symbols .................................................... :
N/A
N/A
Certification marks ............................................. :
Refer to copy of markings.
P
1.7.2
Safety instructions
See manual enclosed.
P
1.7.3
Short duty cycles
N/A
1.7.4
Supply voltage adjustment ................................. :
N/A
1.7.5
Power outlets on the equipment ........................ :
No standard power outlet.
N/A
1.7.6
Fuse identification .............................................. :
No fuse is provided.
N/A
1.7.7
Wiring terminals
The terminals are properly
marked, see photo enclosed.
1.7.7.1
Protective earthing and bonding terminals
N/A
1.7.7.2
Terminal for a.c. mains supply conductors
N/A
1.7.8
Controls and indicators
A diffuse status LED is
provided. This was not
considered as an indicator
relevant for safety.
N/A
1.7.8.1
Identification, location and marking .................... :
There are no controls affecting
safety.
N/A
1.7.8.2
Colours .............................................................. :
For functional indication a LED
lights when the equipment is
operating
N/A
1.7.8.3
Symbols according to IEC 60417........................ :
There are no switches in the
equipment.
N/A
1.7.8.4
Markings using figures ...................................... :
No controls in the sense of this
clause.
N/A
1.7.9
Isolation of multiple power sources .................... :
Only one connection supplying
hazardous voltages and energy
levels to the equipment.
N/A
1.7.10
IT power distribution systems
TRF No.:1950__F
P
N/A
TRF originator: FIMKO
Page 9 of 34
Report No.: T223-0314/02
IEC 60 950
Clause
Requirement – Test
Result – Remark
Verdict
1.7.11
Thermostats and other regulating devices
No thermostats or other
regulating devices.
1.7.12
Language ...........................................................:
Instructions and markings shall
be in a language acceptable for
the country where the
equipment is to be used.

1.7.13
Durability
The marking withstands
required tests.
P
1.7.14
Removable parts
No removable parts.
N/A
1.7.15
Replaceable batteries
No battery is in the equipment.
N/A
N/A

Language ............................................................:
Built in unit, not for operator
access.
Equipment not intended for
installation in RAL.
1.7.16
Operator access with a tool ................................:
N/A
1.7.17
Equipment for restricted access locations ..........:
2
PROTECTION FROM HAZARDS
P
2.1
Protection from electric shock and energy hazards
P
2.1.1
Protection in OPERATOR access areas
Component level power supply
not intended for operator
access. Must be checked in the
end product.
N/A
2.1.1.1
Access to energized parts
This is a component level
power supply. Protection must
be checked in the end product.
N/A
N/A
Test by inspection ..............................................:
N/A
Test with test finger ............................................:
N/A
Test with test pin ................................................:
N/A
Test with test probe ............................................:
N/A
2.1.1.2
Battery compartments ........................................:
N/A
2.1.1.3
Access to ELV wiring
N/A
2.1.1.4
Working voltage (V); minimum distance (mm)
through insulation
(see appended table 2.10.5)
Access to hazardous voltage circuit wiring
The internal parts and circuits
containing hazard secondary
energy are separated from the
enclosure (not operator
accessibly) by reinforced
insulation. Therefore, the
enclosure was treated within
this report as dead metal.
TRF No.:1950__F

N/A
TRF originator: FIMKO
Page 10 of 34
Report No.: T223-0314/02
IEC 60 950
Clause
Requirement – Test
2.1.1.5
Energy hazards ..................................................:
2.1.1.6
Manual controls
2.1.1.7
Discharge of capacitors in the primary circuit
Result – Remark
The output of the unit
represents an energy
hazard.(see Enclosure 2 for
test results)
No shafts of knobs etc. at ELV
or hazardous voltage.
Verdict
N/A
N/A
N/A

Time-constant (s); measured voltage (V) ...........:
2.1.2
Protection in service access areas
2.1.3
Protection in restricted access locations
2.2
SELV circuits
2.2.1
General requirements
SELV limits (at accessible
parts) are not exceeded under
normal condition and after a
single fault.
P
2.2.2
Voltages under normal conditions (V)................. :
Within SELV limits
P
2.2.3
Voltages under fault conditions (V) ..................... :
Single fault conditions: < 60
Vdc. (see appended table 5.3).
P
2.2.3.1
Separation by double insulation or reinforced
insulation (method 1)
There is distance between
PWB traces and enclosure
which could be connected to
PE which meets double
insulation. See appended table
2.10.3. There are also two
diodes D200 and D201
connected between + and –
pole of input/output.The diodes
are voltage protection if internal
voltage Vboost comes to
input/output.
P
2.2.3.2
Separation by earthed screen (method 2)
N/A
2.2.3.3
Protection by earthing of the SELV circuit
(method 3)
N/A
2.2.4
Connection of SELV circuits to other circuits ....... : The unit generates internally
hazardous secondary voltage.
Reliability testing was
performed to make sure., that
in case of one failure the output
will remain SELV.
2.3
TNV circuits
TRF No.:1950__F
Checked by inspection,
unintentional contact is unlikely
during service operations.
P
N/A
P
P
N/A
TRF originator: FIMKO
Page 11 of 34
Report No.: T223-0314/02
IEC 60 950
Clause
Requirement – Test
2.5
Limited power sources
N/A
2.6
Provisions for earthing and bonding
N/A
2.6.1
Protective earthing
2.7
Overcurrent and earth fault protection in primary circuits
N/A
2.8
Safety interlocks
N/A
2.9
Electrical insulation
2.9.1
Properties of insulating materials
Neither natural rubber,
materials containing asbestos
nor hygroscopic materials are
used as insulation. No driving
belts or couplings used.
P
2.9.2
Humidity conditioning
Humidity treatment performed
for 48h at 91-95%.
P
2.9.3
Requirements for insulation
The insulation complies with
sub-clauses 4.5.1, 5.2 and
2.10.
P
2.9.4
Insulation parameters
Application of insulation and
working voltage are considered.
P
2.9.5
Categories of insulation
Input to Output: SELV to SELV,
no separation.
Input and output to enclosure:
Double insulation between part
at 190 Vdc and enclosure.
P
2.10
Clearances, creepage distances and distances through insulation
P
2.10.1
General
P
2.10.2
Determination of working voltage
P
2.10.3
Clearances
P
2.10.3.1
General
P
2.10.3.2
Clearances in primary circuit
TRF No.:1950__F
Result – Remark
Verdict
The unit is rated SELV in and
SELV out. The unit contains
hazard internally secondary
voltage. The hazard secondary
voltage is separated from the
enclosure by double insulation.
The enclosure of the unit is
allowed to be connected to PE.
N/A
P
No primary circuit.
N/A
TRF originator: FIMKO
Page 12 of 34
Report No.: T223-0314/02
IEC 60 950
Clause
Requirement – Test
Result – Remark
2.10.3.3
Clearances in secondary circuits
(see appended table 2.10.3 and
2.10.4)
2.10.3.4
Measurement of transient voltage levels
2.10.4
Creepage distances
(see appended table 2.10.3 and
2.10.4)
P
CTI tests..............................................................:
III

2.10.5
Solid insulation
2.10.5.1
Minimum distance through insulation
2.10.5.2
Thin sheet material
Verdict
N/A
P
Insulation foil below PCB (basic
insulation). (see appended
table 2.10.5). This insulation
meets the requirements for
basic insulation.
2.10.5.3
P
N/A

Number of layers (pcs)........................................:
Electric strength test
P
(see appended table 5.2)

Printed boards
N/A
Distance through insulation
N/A
Electric strength test for thin sheet insulating
material
(see appended table 5.2)
—
Number of layers (pcs)........................................:
N/A
Wound components
N/A
Number of layers (pcs)........................................:
N/A
Two wires in contact inside wound component;
angle between 45° and 90° ................................:
N/A
2.10.6
Coated printed boards
N/A
2.10.6.1
General
N/A
2.10.6.2
Sample preparation and preliminary inspection
N/A
2.10.6.3
Thermal cycling
N/A
2.10.6.4
Thermal ageing (°C)............................................:
N/A
2.10.6.5
Electric strength test
2.10.6.6
Abrasion resistance test
2.10.5.4

N/A

Electric strength test
2.10.7
2.10.8
Enclosed and sealed parts..................................:
N/A
Temperature T1=T2 = Tma – Tamb +10K (°C)........:
N/A
Spacings filled by insulating compound ..............:
Approved optocouplers are
used.
P
Electric strength test

2.10.9
Component external terminations
P
2.10.10
Insulation with varying dimensions
N/A
TRF No.:1950__F
TRF originator: FIMKO
Page 13 of 34
Report No.: T223-0314/02
IEC 60 950
Clause
Requirement – Test
Result – Remark
Verdict
3
WIRING, CONNECTIONS AND SUPPLY
3.1
General
3.1.1
Current rating and overcurrent protection
No internal wires.
N/A
3.1.2
Protection against mechanical damage
No internal wires.
N/A
3.1.3
Securing of internal wiring
No internal wires.
N/A
3.1.4
Insulation of conductors
3.1.5
Beads and ceramic insulators
3.1.6
Screws for electrical contact pressure
3.1.7
Non-metallic materials in electrical connections
No contact pressure through
insulating material.
N/A
3.1.8
Self-tapping and spaced thread screws
N/A
3.1.9
Termination of conductors
Thread-cutting or space thread
screws are not used for
electrical connections.
Terminations cannot become
displaced so that clearances
and Creepage distances can
not be reduced.
P
N/A
N/A
No beads or similar ceramic
insulators on conductors.
N/A
10 N pull test
3.1.10
Sleeving on wiring
3.2
Connection to a.c. mains supplies
N/A
N/A
N/A
.
N/A
3.2.1
Means of connection ..........................................:
3.2.2
Multiple supply connections
3.2.3
N/A
Permanently connected equipment
Built in Power Supply with
approved connector (see list of
safety critical components).
Only one supply connection.
N/A
The equipment is not intended
for permanent connection to the
mains.
N/A
N/A

Number of conductors, diameter (mm) of cable
and conduits ......................................................:
3.2.4
Appliance inlets
No appliance inlet is used.
N/A
3.2.5
Power supply cords
Power supply cord is not
provided (built in Power
Supply).
N/A

Type.....................................................................:
2

Rated current (A), cross-sectional area (mm ),
AWG ...................................................................:
3.2.6
Cord anchorages and strain relief
Equipment not provided with a
non-detachable power supply
cord.
N/A
Mass of equipment (kg), pull (N) ...................... :

Longitudinal displacement (mm) ........................ :

TRF No.:1950__F
TRF originator: FIMKO
Page 14 of 34
Report No.: T223-0314/02
IEC 60 950
Clause
Requirement – Test
3.2.7
Protection against mechanical damage
3.2.8
Cord guards
Result – Remark
No sharp points or cutting
edges on the equipment
surfaces.
The equipment is neither handheld nor intended to be moved
during operation.
Verdict
P
N/A
D (mm); test mass (g) ........................................ :

Radius of curvature of cord (mm)....................... :

3.2.9
Supply wiring space
3.3
Wiring terminals for connection of external conductors
N/A
3.3.1
Wiring terminals
N/A
3.3.2
Connection of non-detachable power supply
cords
3.3.3
Screw terminals
3.3.4
Rated current (A), cord/cable type, cross2
sectional area (mm )...........................................:
N/A
3.3.5
Rated current (A), type and nominal thread
diameter (mm) ...................................................:
N/A
3.3.6
Wiring terminals design
N/A
3.3.7
Grouping of wiring terminals
N/A
3.3.8
Stranded wire
3.4
Disconnection from the a.c. mains supply
N/A
3.5
Interconnection of equipment
N/A
3.5.1
General requirements
N/A
3.5.2
Types of interconnection circuits.........................:
N/A
3.5.3
ELV circuits as interconnection circuits
N/A
4
PHYSICAL REQUIREMENTS
4.1
Stability
TRF No.:1950__F
Not permanently connected
equipment or equipment with
connection of ordinary nondetachable power supply cord.
Unit is intended for connection
to SELV voltage and not to
mains supply. The unit is for
building-in. Approved terminals
are used.
N/A
N/A
Screws do not clamp the
external supply wiring.
Only SELV connections,
therefore this test is not
relevant.
N/A
N/A
P
N/A
TRF originator: FIMKO
Page 15 of 34
Report No.: T223-0314/02
IEC 60 950
Clause
Requirement – Test
Result – Remark
Verdict
Angle of 10°
The unit is for built in use.
Therefore, the test is not
applicable.
Test: force (N) .....................................................:
N/A
N/A
4.2
Mechanical strength
P
4.2.1
General
P
4.2.2
Steady force test, 10 N
See enclosed test results.
4.2.3
Steady force test, 30 N
No operator access part
protected by a door or cover.
4.2.4
Steady force test, 250 N
N/A
4.2.5
Impact test
N/A
4.2.6
Drop test
N/A
4.2.7
Stress relief
N/A
4.2.8
Cathode ray tubes
N/A
Picture tube separately certified..........................:
N/A
4.2.9
High pressure lamps
N/A
4.2.10
Wall or ceiling mounted equipment; force (N) ...:
N/A
4.3
Design and construction
4.3.1
Edges and corners
4.3.2
Handles and manual controls; force (N) .............:
N/A
4.3.3
Adjustable controls
N/A
4.3.4
Securing of parts
4.3.5
Connection of plugs and sockets
4.3.6
Direct plug-in equipment
P
N/A
P
All edges and corners are
rounded and/or smoothed.
All hazardous parts are fixed to
retain position in event of
termination failure.
P
P
N/A
Not intended to plug directly
into a wall socket-outlet.
N/A
Dimensions (mm) of mains plug for direct plug-in
............................................................................ :
N/A
Torque (Nm) ....................................................... :
N/A
4.3.7
Heating elements in earthed equipment
4.3.8
Batteries
N/A
4.3.9
Oil and grease
N/A
TRF No.:1950__F
No heating elements provided.
N/A
TRF originator: FIMKO
Page 16 of 34
Report No.: T223-0314/02
IEC 60 950
Clause
Requirement – Test
4.3.10
Dust, powders, liquids and gases
N/A
4.3.11
Containers for liquids or gases
N/A
4.3.12
Flammable liquids ...............................................:
N/A
Quantity of liquid (l) .............................................:
N/A
Flash point (°C) ...................................................:
N/A
Radiation; type of radiation ................................:
N/A
Equipment using lasers
N/A
4.4
Protection against hazardous moving parts
N/A
4.4.1
General
4.4.2
Protection in operator access areas
4.4.3
Protection in restricted access locations
4.4.4
Protection in service access areas
4.5
Thermal requirements
4.5.1
Temperature rises
4.3.13
Result – Remark
Verdict
N/A
No moving parts
N/A
.
N/A
N/A
P
(see appended table 4.5)
Normal load condition per Annex L.....................:
4.5.2
Resistance to abnormal heat
4.6
Openings in enclosures
4.6.1
Top and side openings
Dimensions (mm) ...............................................:
4.6.2
Bottoms of fire enclosures
Construction of the bottom..................................:
P
N/A
No thermoplastic parts carrying
hazardous voltages.
N/A
N/A
The enclosure of this
component is not rated as fire
or electrical enclosure. For
description of the enclosure
refer to the list of safety critical
components.
N/A

N/A

4.6.3
Doors or covers in fire enclosures
N/A
4.6.4
Openings in transportable equipment
N/A
4.6.5
Adhesives for constructional purposes
N/A
4.7
Conditioning temperature /time...........................:

Resistance to fire
P
TRF No.:1950__F
TRF originator: FIMKO
Page 17 of 34
Report No.: T223-0314/02
IEC 60 950
Clause
Requirement – Test
Result – Remark
Verdict
4.7.1
Reducing the risk of ignition and spread of flame
The unit uses appropriate and
approved components.
P
4.7.2
Conditions for a fire enclosure
Fire enclosure must be
considered for the end product.
N/A
4.7.2.1
Parts requiring a fire enclosure
The fire enclosure is required to
cover all parts.
N/A
4.7.2.2
Parts not requiring a fire enclosure
The fire enclosure is required to
cover all parts.
N/A
4.7.3
Materials
4.7.3.1
General
4.7.3.2
Materials for fire enclosures
4.7.3.3
Materials for components and other parts outside
fire enclosures
4.7.3.4
Materials for components and other parts inside
fire enclosures
4.7.3.5
Materials for air filter assemblies
4.7.3.6
Materials used in high-voltage components
5
ELECTRICAL REQUIREMENTS AND SIMULATED ABNORMAL CONDITIONS
5.1
Touch current and protective conductor current
5.1.1
General
5.1.2
Equipment under test (EUT)
N/A
5.1.3
Test circuit
N/A
5.1.4
Application of measuring instrument
N/A
5.1.5
Test procedure
N/A
5.1.6
Test measurements
N/A
P
Components and materials
have adequate flammability
classification.
P
N/A
No parts outside the fire
enclosure.
N/A
N/A
No air filters in the equipment.
N/A
N/A
P
N/A
Unit is not intended for
connection to mains supply.
N/A
Test voltage (V) ..................................................:

Measured (mA) ..................................................:

Max. allowed current (mA) .................................:

5.1.7
Equipment with touch current exceeding 3.5 mA
............................................................................:
N/A
5.1.8
Touch currents to and from telecommunication
networks
N/A
5.1.8.1
Limitation of the touch current to a
telecommunication network
N/A
Test voltage (V) ..................................................:
TRF No.:1950__F

TRF originator: FIMKO
Page 18 of 34
Report No.: T223-0314/02
IEC 60 950
Clause
Requirement – Test
Result – Remark
Verdict
Measured current (mA) ......................................:

Max. allowed current (mA) .................................:

5.1.8.2
Summation of touch currents from
telecommunication networks ..............................:
N/A
5.2
Electric strength
5.2.1
General
(see appended table 5.2)
P
5.2.2
Test procedure
(see appended table 5.2)
P
5.3
Abnormal operating and fault conditions
5.3.1
Protection against overload and abnormal
operation
5.3.2
Motors
N/A
5.3.3
Transformers
N/A
5.3.4
Functional insulation ...........................................:
5.3.5
Electromechanical components
5.3.6
Simulation of faults
5.3.7
Unattended equipment
5.3.8
Compliance criteria for abnormal operating and
fault conditions
6
CONNECTION TO TELECOMMUNICATION NETWORKS
N/A
A
ANNEX A, TESTS FOR RESISTANCE TO HEAT AND FIRE
N/A
A.1
Flammability test for fire enclosures of movable equipment having a total mass
exceeding 18 kg, and of stationary equipment (see 4.7.3.2)
N/A
A.1.1
Samples ..............................................................:

Wall thickness (mm) ...........................................:

A.1.2
Conditioning of samples; temperature (°C).........:
N/A
A.1.3
Mounting of samples...........................................:
N/A
A.1.4
Test flame
N/A
A.1.5
Test procedure
N/A
A.1.6
Compliance criteria
N/A
P
P
(see appended table 5.3)
Complies with a) and c).
P
P
N/A
(see appended table 5.3)
No thermostats, temperature
limiters or thermal cutouts.
No fire or molten metal
occurred and no deformation of
enclosure during the tests. No
reduction of clearance and
Creepage distances.
P
N/A
P
Sample 1 burning time (s)...................................:

Sample 2 burning time (s)...................................:

Sample 3 burning time (s)...................................:

TRF No.:1950__F
TRF originator: FIMKO
Page 19 of 34
Report No.: T223-0314/02
IEC 60 950
Clause
Requirement – Test
Result – Remark
Verdict
A.2
Flammability test for fire enclosures of movable equipment having a total mass not
exceeding 18 kg, and for material and components located inside fire enclosures
(see 4.7.3.2 and 4.7.3.4)
A.2.1
Samples, material ...............................................:

Wall thickness (mm) ...........................................:

N/A
A.2.2
Conditioning of samples
N/A
A.2.6
Compliance criteria
N/A
A.2.7
Sample 1 burning time (s)...................................:

Sample 2 burning time (s)...................................:

Sample 3 burning time (s)...................................:

Alternative test acc. to IEC 60695-2-2, cl. 4, 8
N/A
Sample 1 burning time (s)...................................:

Sample 2 burning time (s)...................................:

Sample 3 burning time (s)...................................:

A.3
High current arcing ignition test (see 4.7.3.2)
N/A
A.3.1
Samples, material
N/A
Wall thickness (mm) ..........................................:
N/A
Compliance criteria
N/A
Sample 1 number of arcs to ignition (pcs) .........:
N/A
Sample 2 number of arcs to ignition (pcs) .........:
N/A
Sample 3 number of arcs to ignition (pcs) .........:
N/A
Sample 4 number of arcs to ignition (pcs) .........:
N/A
Sample 4 number of arcs to ignition (pcs) .........:
N/A
A.4
Hot wire
N/A
A.4.1
Samples, material ...............................................:
N/A
Wall thickness (mm) ...........................................:
N/A
Compliance criteria
N/A
Sample 1 ignition time (s) ...................................:
N/A
Sample 2 ignition time (s) ...................................:
N/A
Sample 3 ignition time (s) ...................................:
N/A
Sample 4 ignition time (s) ...................................:
N/A
Sample 5 ignition time (s) ...................................:
N/A
A.5
Hot flaming oil test (see 4.6.2)
N/A
A.6
Flammability tests for classifying materials V-0, V-1 or V-2
N/A
A.6.1
Samples, material ...............................................:

Wall thickness (mm) ...........................................:

A.3.5
A.4.5
A.6.5
Compliance criteria
N/A
A.6.6
Permitted retest
N/A
TRF No.:1950__F
TRF originator: FIMKO
Page 20 of 34
Report No.: T223-0314/02
IEC 60 950
Clause
Requirement – Test
Result – Remark
Verdict
A.7
Flammability test for classifying foamed materials
HF-1, HF-2 or HFB
N/A
A.7.1
Sample, material ................................................:

Wall thickness (mm) ...........................................:

A.7.4
Compliance criteria
N/A
A.7.5
Compliance criteria, HF-2
N/A
A.7.6
Compliance criteria, HF-1
N/A
A.7.7
Compliance criteria, HBF
N/A
A.7.8
Permitted retest, HF-1 or HF-2
N/A
A.7.9
Permitted retest, HBF
N/A
A.8
Flammability test for classifying materials HB
N/A
A.8.1
Samples, material ...............................................:
N/A
Sample thickness (mm) ......................................:

A.8.2
Conditioning of samples; temperature (°C).........:
N/A
A.8.4
Test procedure
N/A
A.8.5
Compliance criteria
N/A
A.8.6
Permitted retest
N/A
A.9
Flammability test for classifying materials 5V
N/A
A.9.1
Samples, material ...............................................:

Sample thickness (mm) ......................................:

A.9.4
Test procedure, test bars
N/A
A.9.5
Test procedure, test plaques
N/A
A.9.6
Compliance criteria
N/A
A.9.7
Permitted retest
N/A
A.10
Stress relief conditioning (see 4.2.7)
N/A

Temperature (°C)................................................:
B
ANNEX B, MOTOR TESTS UNDER ABNORMAL CONDITIONS (see 4.7.2.2 and
5.3.2)
N/A
C
ANNEX C, TRANSFORMERS (see 1.5.4 and 5.3.3)
N/A
G
ANNEX G, ALTERNATIVE METHOD FOR DETERMINING MINIMUM
CLEARANCES
N/A
H
ANNEX H, IONIZING RADIATION (see 4.3.13)
N/A
J
ANNEX J, TABLE OF ELECTROCHEMICAL POTENTIALS (see 2.6.5.6)
TRF No.:1950__F
P
TRF originator: FIMKO
Page 21 of 34
Report No.: T223-0314/02
IEC 60 950
Clause
Requirement – Test
Result – Remark
Verdict

Metal used .........................................................:
K
ANNEX K, THERMAL CONTROLS (see 1.5.3 and 5.3.7)
N/A
U
ANNEX U, INSULATED WINDING WIRES FOR USE WITHOUT INTERLEAVED
INSULATION (see 2.10.5.4)
N/A
See separate test report
TRF No.:1950__F

TRF originator: FIMKO
This is an extract of the CB-Scheme report with the most important information.