Below you will find brief information for HMDW80 HMD82, HMDW80 HMD82D, HMDW80 TMD82, HMDW80 HMD83, HMDW80 HMD83D, HMDW80 TMD83, HMDW80 HMW82, HMDW80 HMW88, HMDW80 HMW88D, HMDW80 HMW89, HMDW80 HMW89D, HMDW80 HMS82, HMDW80 HMS83. Vaisala INTERCAP® Humidity and Temperature Transmitter Series HMDW80 measure relative humidity and temperature in various building automation applications. They combine easy installation and reliable operation with minimal maintenance requirements. The series includes transmitters for wall and duct mounting, humid areas, and for outdoor installation. It also includes temperature-only transmitters and transmitters with an optional display. Calculated humidity parameters – dewpoint, wet bulb temperature, and enthalpy – are also available.
Advertisement
Advertisement
USER'S GUIDE
Vaisala INTERCAP® Humidity and
Temperature Transmitters
HMDW80 Series
M211510EN-D
PUBLISHED BY
Vaisala Oyj
P.O. Box 26
FI-00421 Helsinki
Finland
Phone (int.): +358 9 8949 1
Fax:
Visit our Internet pages at www.vaisala.com
.
+358 9 8949 2227
© Vaisala 2015
No part of this manual may be reproduced, published or publicly displayed in any form or by any means, electronic or mechanical (including photocopying), nor may its contents be modified, translated, adapted, sold or disclosed to a third party without prior written permission of the copyright holder. Translated manuals and translated portions of multilingual documents are based on the original English versions. In ambiguous cases, the English versions are applicable, not the translations.
The contents of this manual are subject to change without prior notice.
This manual does not create any legally binding obligations for Vaisala towards customers or end users. All legally binding obligations and agreements are included exclusively in the applicable supply contract or the General Conditions of Sale and
General Conditions of Service of Vaisala.
_________________________________________________________________________________
Table of Contents
GENERAL INFORMATION ............................................................................ 4
About This Manual ................................................................... 4
Contents of This Manual ....................................................... 4
Version Information ............................................................... 5
Related Manuals ................................................................... 5
Documentation Conventions ................................................. 5
Safety ......................................................................................... 6
ESD Protection ...................................................................... 6
Recycling .................................................................................. 6
Regulatory Compliances ......................................................... 7
Trademarks ............................................................................... 7
Software License ...................................................................... 7
Warranty .................................................................................... 7
Introduction to HMDW80 Series ............................................. 8
HMDW80 Series Transmitter Models ...................................... 9
Output Parameters Explained ............................................... 9
Transmitter Parts – Duct Models .......................................... 10
Transmitter Parts – Wall Models ........................................... 11
Transmitter Parts – Outdoor Models .................................... 13
Display ..................................................................................... 14
Analog Output Overrange Behavior ..................................... 15
Selecting Location ................................................................. 16
Installing Duct Models HMD82/83 and TMD82/83 ............... 17
Installing Wall Models HMW88 and HMW89 ........................ 19
Installing Wall Models HMW82/83 and TMW82/83 .............. 20
Installing Outdoor Models HMS82/83 ................................... 21
Configuration and Wiring ..................................................... 22
Pole installation ................................................................... 23
Wall installation ................................................................... 24
Wiring ...................................................................................... 25
HMD82(D), HMW88(D), and HMS82 .................................. 25
TMD82 ................................................................................. 26
HMD83(D), HMW89(D), and HMS83 .................................. 26
TMD83 ................................................................................. 27
HMW82 ............................................................................... 27
TMW82 ................................................................................ 28
HMW83 ............................................................................... 28
TMW83 ................................................................................ 29
VAISALA _________________________________________________________________________ 1
User's Guide _______________________________________________________________________
DIP Switches ........................................................................... 30
Cleaning ................................................................................... 32
Calibration ............................................................................... 32
Replacing the INTERCAP ® Humidity Sensor ....................... 33
Replacing the INTERCAP ® Sensor on Models
HMD82/83 and HMW88/89 ................................................. 33
Replacing the INTERCAP ® Sensor on Wall Models
HMW82/83 ........................................................................... 34
Replacing the INTERCAP ® Sensor on Outdoor Models
HMS82/83 ............................................................................ 35
Problem Situations ................................................................. 39
Analog Output Error State ..................................................... 40
Error Messages on the Display ............................................. 40
Technical Support .................................................................. 41
Specifications ......................................................................... 42
Spare Parts and Accessories ................................................ 46
2 ____________________________________________________________________ M211510EN-D
_________________________________________________________________________________
List of Figures
Figure 1 Parts of Duct Mounted Models (HMD82/83 and TMD82/83) ... 10
Figure 2 Parts of Wall Mounted Models (HMW88/89) ............................ 11
Figure 3 Parts of Wall Mounted Models (HMW82/83 and TMW82/83) .. 12
Figure 4 Parts of Outdoor Models (HMS82/83) ...................................... 13
Figure 5 Startup Screens (HMD83D) ..................................................... 14
Figure 6 Measurement Screen (HMD83D) ............................................. 14
Figure 7 Measurement Screen with Error (HMD83D) ............................ 14
Figure 8 Duct Model Installation ............................................................. 18
Figure 9 Position the Sensor to Center of Duct ...................................... 18
Figure 10 Duct Model Dimensions (HMD82/83 and TMD82/83) .............. 18
Figure 11 Wall Model Dimensions (HMW88/89) ...................................... 19
Figure 12 Wall Model Dimensions (HMW82/83 and TMW82/83) ............ 20
Figure 13 Outdoor Model Dimensions (HMS82/83) ................................. 21
Figure 14 Location of DIP Switches and Screw Terminal ........................ 22
Figure 15 HMS82/83 Pole Installation ...................................................... 23
Figure 16 Securing the Cable on a Pole .................................................. 23
Figure 17 HMS82/83 Wall Installation ...................................................... 24
Figure 18 Securing the Cable on a Wall ................................................... 24
Figure 19 DIP Switches on Component Board ......................................... 30
Figure 20 Sensors on HMD82/83 and HMW88/89 Models ...................... 33
Figure 21 INTERCAP ® Sensor on HMW82/83 Models ............................ 34
Figure 22 Unplugging the Screw Terminal ............................................... 35
Figure 23 Opening the Radiation Shield Screws ...................................... 36
Figure 24 Removing the Radiation Shield Screws ................................... 36
Figure 25 Location of Locking Tab ........................................................... 37
Figure 26 Removing the Radiation Shield ................................................ 37
Figure 28 Sensors on HMS82/83 Models ................................................ 38
List of Tables
Table 1 Manual Revisions ....................................................................... 5
Table 2 Related Manuals ........................................................................ 5
Table 3 HMDW80 Series Transmitter Models ......................................... 9
Table 4 Parameters Supported by HMDW80 Series .............................. 9
Table 5 DIP Switch Positions for Metric Output .................................... 31
Table 6 DIP Switch Positions for Non-Metric Output ............................ 31
Table 7 Possible Problem Situations and Their Remedies ................... 39
Table 8 Error Messages on the Display ................................................ 40
Table 9 Specifications for Models HMW82/83 and TMW82/83 ............ 42
Table 10 Specifications for Models HMD82/83, TMD82/83,
HMW88/89, and HMS82/83 ..................................................... 43
Table 11 Specifications for Models HMD82/83D and HMW88/89D ........ 44
Table 12 Operating Environment (All Models) ........................................ 45
Table 13 Inputs and Outputs ................................................................... 45
Table 15 HMDW80 Series Spare Parts and Accessories ....................... 46
VAISALA _________________________________________________________________________ 3
User's Guide _______________________________________________________________________
CHAPTER 1
GENERAL INFORMATION
This chapter provides general notes for the manual and the HMDW80 series.
About This Manual
This manual provides information for installing, operating, and maintaining HMDW80 series transmitters.
Contents of This Manual
This manual consists of the following chapters:
- Chapter 1, General Information, provides general notes for the manual and the HMDW80 series.
- Chapter 2, Product Overview, introduces the features and options of
the HMDW80 series transmitters.
- Chapter 3, Installation, provides you with information that is intended
to help you install HMDW80 series transmitters.
- Chapter 4, Maintenance, provides information that is needed in basic
maintenance of HMDW80 series.
- Chapter 5, Troubleshooting, describes possible problems, their
probable causes and remedies, and provides contact information for technical support.
- Chapter 6, Technical Data, provides the technical data of the
HMDW80 series.
4 ____________________________________________________________________ M211510EN-D
Chapter 1 _________________________________________________________ General Information
Version Information
Table 1 Manual Revisions
Manual Code Description
M211510EN-D March 2015. This manual. Changes:
- Updated wiring information for models HMD82(D),
HMW88(D), and HMS82.
- Updated troubleshooting instructions.
- Updated technical specification: accuracy of calculated parameters and current consumption of voltage output models.
- Updated list of spare parts and accessories.
M211510EN-C June 2013. Previous version. Changes:
- Added outdoor transmitter models HMS82 and
HMS83.
- Changed PTFE membrane filter model from 230727SP
(30 mm long) to ASM210856SP (24.5 mm long).
- Changed PTFE filter model from 219452SP (40 mm long) to DRW239993SP (22 mm long).
- Improved IP classification of models with display to
IP65.
Related Manuals
Table 2
Manual Code
M211507EN
M211508EN
M211328EN
M211509EN
Related Manuals
Manual Name
HMD82 HMD83 Wiring Diagram
HMW88 HMW89 Wiring Diagram
HMW82 HMW83 Quick Guide
HMS82 HMS83 Quick Guide
Documentation Conventions
Throughout the manual, important safety considerations are highlighted as follows:
WARNING Warning alerts you to a serious hazard. If you do not read and follow instructions very carefully at this point, there is a risk of injury or even death.
CAUTION Caution warns you of a potential hazard. If you do not read and follow instructions carefully at this point, the product could be damaged or important data could be lost.
NOTE Note highlights important information on using the product.
VAISALA _________________________________________________________________________ 5
User's Guide _______________________________________________________________________
Safety
The HMDW80 series transmitter delivered to you has been tested for safety and approved as shipped from the factory. Note the following precautions:
WARNING Installation of HMDW80 series transmitters may involve working at a height. Assess the risks and plan your work so it is carried out safely.
Try avoiding work at height, if you can.
CAUTION Make sure the wires are de-energized when you connect them to the screw terminals.
CAUTION Do not modify the unit. Improper modification can damage the product or lead to malfunction.
ESD Protection
Electrostatic Discharge (ESD) can cause immediate or latent damage to electronic circuits. Vaisala products are adequately protected against
ESD for their intended use. It is possible to damage the product, however, by delivering electrostatic discharges when touching, removing, or inserting any objects inside the equipment housing.
To make sure you are not delivering high static voltages yourself, always hold component boards by the edges and avoid touching the component contacts.
Recycling
Recycle all applicable material.
Dispose of the unit according to statutory regulations. Do not dispose of with regular household refuse.
6 ____________________________________________________________________ M211510EN-D
Chapter 1 _________________________________________________________ General Information
Regulatory Compliances
HMDW80 series complies with the following performance and environmental test standards:
- EMC-Directive
Conformity is shown by compliance with the following standards:
- EN 61326-1: Electrical equipment for measurement, control, and laboratory use – EMC requirements – For use in industrial locations.
- EN 550022: Information technology equipment – Radio disturbance characteristics – Limits and methods of measurement.
Trademarks
INTERCAP ® is a registered trademark of Vaisala Oyj.
Software License
This product contains software developed by Vaisala. Use of the software is governed by license terms and conditions included in the applicable supply contract or, in the absence of separate license terms and conditions, by the General License Conditions of Vaisala Group.
Warranty
Visit our Internet pages for standard warranty terms and conditions: www.vaisala.com/warranty .
Please observe that any such warranty may not be valid in case of damage due to normal wear and tear, exceptional operating conditions, negligent handling or installation, or unauthorized modifications. Please see the applicable supply contract or Conditions of Sale for details of the warranty for each product.
VAISALA _________________________________________________________________________ 7
User's Guide _______________________________________________________________________
CHAPTER 2
PRODUCT OVERVIEW
This chapter introduces the features and options of the HMDW80 series transmitters.
Introduction to HMDW80 Series
Vaisala INTERCAP ® Humidity and Temperature Transmitter Series
HMDW80 measure relative humidity and temperature in various building automation applications. Transmitters combine easy installation and reliable operation with a low requirement for maintenance.
HMDW80 series includes transmitters for wall and duct mounting, humid areas, and for outdoor installation. It also includes temperatureonly transmitters and transmitters with an optional display. Calculated humidity parameters – dewpoint, wet bulb temperature, and enthalpy – are also available.
HMDW80 series transmitters require minimal maintenance thanks to their excellent sensor stability and high-quality materials. If necessary, the INTERCAP ® humidity sensor can be easily exchanged in the field with practically no downtime.
Features provided by transmitters in the HMDW80 series:
- ±3.0 %RH accuracy.
- 0 ... 100 %RH measurement range.
- User exchangeable INTERCAP ® humidity sensor for easy field replacement.
- Several output parameters; see section HMDW80 Series Transmitter
Models on page 9 for list of supported parameters by transmitter
model.
- Several IP65-classified models for demanding HVAC applications.
- UL-V0 flammability rating.
8 ____________________________________________________________________ M211510EN-D
Chapter 2 ___________________________________________________________ Product Overview
HMDW80 Series Transmitter Models
Table 3 below lists the most important differences between the HMDW80
series transmitter models. For technical specifications, see Chapter 6, Technical
Table 3 HMDW80 Series Transmitter Models
Model
HMD82
HMS82
HMS83
Type
Duct
HMD82D Duct
TMD82
HMD83
Duct
Duct
HMD83D Duct
TMD83
HMW82
TMW82
HMW83
TMW83
HMW88
HMW88D Wall
HMW89
Duct
Wall
Wall
Wall
Wall
Wall
Wall
HMW89D Wall
Outputs
2 × 4 ... 20 mA No
2 × 4 ... 20 mA Yes
1 × 4 ... 20 mA No
2 × 0 ... 10 V
2 × 0 ... 10 V
No
Yes
1 × 0 ... 10 V No
2 × 4 ... 20 mA No
1 × 4 ... 20 mA No
2 × 0 ... 10 V
1 × 0 ... 10 V
2 × 0 ... 10 V
2 × 0 ... 10 V
Outdoor 2 × 4 ... 20 mA No
Outdoor 2 × 0 ... 10 V
Display IP Rating Output Parameters
No
No
2 × 4 ... 20 mA No
2 × 4 ... 20 mA Yes
No
Yes
No
IP65
IP65
IP65
IP65
IP65
IP65
IP30
IP30
IP30
IP30
IP65
IP65
IP65
IP65
IP65
IP65
T, RH, Td, h, Tw
T, RH, Td, h, Tw
T
T, RH, Td, h, Tw
T, RH, Td, h, Tw
T
T, RH
T
T, RH
T
T, RH, Td, h, Tw
T, RH, Td, h, Tw
T, RH, Td, h, Tw
T, RH, Td, h, Tw
T, RH, Td, h, Tw
T, RH, Td, h, Tw
Output Parameters Explained
Table 4 Parameters Supported by HMDW80 Series
Parameter
Temperature T
Relative humidity
Dewpoint
Enthalpy
Wet bulb temperature
Symbol Unit(s) Description
RH
Td h
Tw
°C
°F
%
°C
°F kJ/kg
BTU/lb
°C
°F
Temperature in Celsius or Fahrenheit scale.
Ratio of the partial pressure of water vapor in the air to the saturation vapor pressure of air at the current temperature.
Temperature at which the water vapor in the air will condense into water at the current pressure.
When the dewpoint is below 0 °C, the transmitter outputs frostpoint (Tf) instead of dewpoint.
Sum of the internal energy of a thermodynamic system.
The minimum temperature that can be reached by evaporative cooling in the current conditions.
VAISALA _________________________________________________________________________ 9
User's Guide _______________________________________________________________________
Transmitter Parts – Duct Models
4 5
1
2
3
6
7
8
9
10
11 12
13
Figure 1 Parts of Duct Mounted Models (HMD82/83 and
TMD82/83)
1302-018
1 = PTFE membrane filter (spare part item ASM210856SP).
2 = INTERCAP ® humidity sensor and temperature sensor.
Not included in TMD82 and TMD83 models.
3 = Probe.
4 = Fastening flange.
5 = Tightening screw for fastening flange.
6 = Screws for attaching the flange to a duct (2 pcs included).
7 = Type label.
8 = DIP switches for selecting humidity parameter and display units.
Not included in TMD82 and TMD83 models.
9 = Cable gland. Suitable for 4 ... 8 mm diameter cable.
10 = Display (in HMD82D and HMD83D models).
11 = Screw terminals.
12 = Window for display (in HMD82D and HMD83D models).
13 = Transmitter cover with captive screws.
10 ___________________________________________________________________ M211510EN-D
Chapter 2 ___________________________________________________________ Product Overview
Transmitter Parts – Wall Models
1
4
1
5
2
3
6
7
10
11
8
9
Figure 2 Parts of Wall Mounted Models (HMW88/89)
1302-019
1 = Screw holes for mounting (2 pcs).
2 = Display (in HMW88D and HMW89D models).
3 = Type label.
4 = DIP switches for selecting humidity parameter and display units
5 = Cable gland. Suitable for 4 ... 8 mm diameter cable.
6 = Screw terminals.
7 = Probe.
8 = INTERCAP ® humidity sensor and temperature sensor.
9 = PTFE filter (spare part item DRW239993SP).
10 = Window for display (in HMW88D and HMW89D models)
11 = Transmitter cover with captive screws.
VAISALA ________________________________________________________________________ 11
User's Guide _______________________________________________________________________
1
2
3
4
5
6
Figure 3 Parts of Wall Mounted Models (HMW82/83 and
TMW82/83)
1 = Opening tab: push down to open the transmitter.
2 = Direction arrow. Must point up after mounting base has been installed on the wall.
3 = Wiring label.
4 = Screw terminals.
5 = Mounting base.
6 = Transmitter cover with component board.
1302-020
12 ___________________________________________________________________ M211510EN-D
Chapter 2 ___________________________________________________________ Product Overview
Transmitter Parts – Outdoor Models
1
4
2
3
6 5
7
8
9
10
12
11
Figure 4 Parts of Outdoor Models (HMS82/83)
1304-048
1 = Radiation shield. Do not remove for installation, only when changing sensor or filter.
2 = Long screws that keep the radiation shield in place (2 pcs),
3 mm hex socket.
3 = INTERCAP ® humidity sensor and temperature sensor under
PTFE membrane filter (filter spare part item ASM210856SP).
4 = Screw terminal. Detachable for easy installation.
5 = Transmitter body.
6 = Screws for pole mounting (2 pcs), medium size crosshead type
(Pozidriv).
7 = Clamp for pole mounting. The holes are threaded for the included pole mounting screws and set screw.
8 = Set screw, medium size crosshead type (Pozidriv).
Install after pole mounting to stop the transmitter from turning.
9 = Medium size crosshead screws (6 pcs) that hold the transmitter cover in place.
10 = Transmitter cover.
11 = Cable gland. Suitable for 4 ... 8 mm diameter cable.
12 = Configuration DIP switches. See section DIP Switches on page 30.
VAISALA ________________________________________________________________________ 13
User's Guide _______________________________________________________________________
Display
Display is present on the following models:
- HMD82D and HMD83D
- HMW88D and HMW89D
When the transmitter is powered on, it displays a sequence of information screens about the transmitter and its analog outputs.
The screens are shown for a few seconds each. Checking the screens on startup is a good way to verify that the transmitter’s configuration DIP switches are set correctly.
Figure 5 Startup Screens (HMD83D)
1302-021
After the startup screens have been displayed, the transmitter will show the measurement screen.
Figure 6
1302-024
Measurement Screen (HMD83D)
If one of the transmitter’s error states is active, a notification symbol and error text will appear on the screen. Depending on the error, the affected measurement readings may be replaced by asterisks “*”. For more
information on the possible errors, see section Error Messages on the
Figure 7
1302-025
Measurement Screen with Error (HMD83D)
14 ___________________________________________________________________ M211510EN-D
Chapter 2 ___________________________________________________________ Product Overview
Analog Output Overrange Behavior
Analog outputs of the HMDW80 series transmitters have a defined behavior when the values measured by the transmitter are outside the scaled analog output range:
- Output is clipped at the end of the range.
- Output is set to error state when measured value is 5% outside the
scaled range. See section Analog Output Error State on page 40.
- Output resumes normal function when measured value is back on the scaled range.
NOTE HMW82/83 and TMW82/83 transmitters are different from the rest of the HMDW80 series. Their analog output is clipped at 10% outside the scaled range, and their analog outputs enter the error state when the measured value is 20% outside the range.
For example, consider the temperature output of the HMD82 transmitter.
The output is 4 ... 20 mA, scaled to -40 ... +60 °C (-40 ... +140 °F).
- When measured temperature rises above +60 °C (+140 °F), the output rises to 20 mA and stops rising even if temperature rises further.
- If the temperature rises above +65 °C (+149 °F), the output enters the error state of 3.6 mA.
NOTE This overrange behavior does not mean there is a problem with the measurements, and it does not affect the readings shown on the display
(if included in the transmitter model). The display always shows the currently measured readings if the measurement is operating without
error. For more information on transmitter errors, see section Error
Messages on the Display on page 40.
VAISALA ________________________________________________________________________ 15
User's Guide _______________________________________________________________________
CHAPTER 3
INSTALLATION
This chapter provides you with information that is intended to help you install HMDW80 series transmitters.
Selecting Location
When mounting duct model transmitters:
- Avoid installing in a location where condensation may fall on the sensor inside the duct.
- Position the sensor in the center of the duct.
- Select a site where the transmitter can be installed horizontally, onto the side of the duct.
When mounting wall model transmitters:
- Select a location that represents well the area of interest.
- Do not install on the ceiling.
- Avoid placing the transmitter near heat and moisture sources, close to the discharge of the supply air ducts, and in direct sunlight.
When mounting outdoor transmitters:
- Install in a place that receives minimal direct sunlight. In the northern hemisphere, the North side of the building typically provides a suitable shaded location.
- Avoid placing the transmitter near windows, air conditioning units, or other heat and moisture sources such as cooling towers.
- Install the transmitter at least 2.5 m above ground level.
16 ___________________________________________________________________ M211510EN-D
Chapter 3 ________________________________________________________________ Installation
Installing Duct Models HMD82/83 and TMD82/83
REQUIRED
TOOLS
- Medium size crosshead screwdriver (Pozidriv) for screws on cover and flange.
- Small slotted screwdriver for screw terminals.
- Drill with 2.5 mm and 13 mm bits for making the installation holes.
- Tools for cutting and stripping wires.
- 19 mm open-end wrench for tightening the cable gland.
1. Remove the yellow transport protection cap and separate the fastening flange from the transmitter.
2. Use the flange to mark the location and size of the installation holes on the side of the duct.
3.
Drill the installation holes in the duct. Refer to Figure 8 below.
4. Secure the fastening flange to the duct with the two screws
(included).
5. Push the probe of the transmitter through the flange and into the duct. The probe should reach far enough so that the sensor is located in the middle of the duct.
6. Secure the transmitter to the flange by tightening the screw on the flange that holds the probe in place.
7. Open the transmitter cover, and route the power and signal cable through the cable gland. Connect the wires to the screw terminals.
Refer to section Wiring on page 25.
8. Check that the DIP switches (if present in your transmitter model)
are set as desired. See section DIP Switches on page 30.
9. Tighten the cable gland and close the transmitter cover.
VAISALA ________________________________________________________________________ 17
User's Guide _______________________________________________________________________
Figure 8 Duct Model Installation
1302-026
Figure 9
72
Position the Sensor to Center of Duct
1302-027
40.6
290.8
250.2
244.5
Ø12
Ø3.5
Ø12
84
Ø4...8
99
1302-028
Figure 10 Duct Model Dimensions (HMD82/83 and TMD82/83)
18 ___________________________________________________________________ M211510EN-D
Chapter 3 ________________________________________________________________ Installation
Installing Wall Models HMW88 and HMW89
REQUIRED
TOOLS
- Medium size crosshead screwdriver (Pozidriv) for cover screws.
- Small slotted screwdriver for screw terminals.
- Two installation screws: Ø < 3.5 mm, head Ø < 10 mm.
- Depending on the wall material and screw type, you may need a drill and a suitable drill bit to make installation holes for screws.
- Tools for cutting and stripping wires.
- 19 mm open-end wrench for tightening the cable gland.
1. Open the transmitter cover and use two screws (not included) to attach the transmitter to the wall. The probe and cable gland should point down.
2. Route the power and signal cable to the screw terminals and
connect the wires. Refer to section Wiring on page 25.
3. Close the transmitter cover and remove the yellow transport protection cap from the probe.
72 40.6
Ø3.5
Ø10
Ø3.5
Ø10
Ø4...8
Figure 11 Wall Model Dimensions (HMW88/89)
Ø12
1302-029
VAISALA ________________________________________________________________________ 19
User's Guide _______________________________________________________________________
Installing Wall Models HMW82/83 and
TMW82/83
REQUIRED
TOOLS
NOTE
- Small flat head screwdriver for opening the transmitter and for screw terminals.
- Two screws, max Ø 4 mm.
- Depending on the wall material and screw type, you may need a drill and a suitable drill bit to make installation holes for screws.
- Tools for cutting and stripping wires.
1. Use a flat head screwdriver to push down the tab on top of the transmitter and separate the mounting base from the transmitter cover.
2. Use the mounting holes to attach the mounting base securely. Use at least two screws (not included, max Ø 4 mm).
The arrow on the mounting base must point straight up after installation.
Proper orientation is important: air must flow through the vents on the bottom and top.
3. Route the power and signal cable to the screw terminals and
connect the wires. Refer to section Wiring on page 25.
4. Close the transmitter cover when done.
76.9
81 24
9
5
Ø4.4
Ø4.4
32.4
5.5
60.3
1302-030
Figure 12 Wall Model Dimensions (HMW82/83 and TMW82/83)
20 ___________________________________________________________________ M211510EN-D
Chapter 3 ________________________________________________________________ Installation
Installing Outdoor Models HMS82/83
WARNING Assess the risks posed by the height and accessibility of the installation location, and plan your work so it is carried out safely. Try avoiding work at height, if you can.
REQUIRED
TOOLS
- Medium size crosshead screwdriver (Pozidriv)
- Small slotted screwdriver for screw terminals.
- Tools for cutting and stripping wires.
- 19 mm open-end wrench for tightening the cable gland.
Additional tools for pole installation:
- Zip ties for securing the cable to the pole.
Additional tools for wall installation:
- Drill and bits.
- Screws (2 pcs, Ø < 5.5 mm) and wall plugs
- Cable clips for securing the cable to the wall.
121.5
Ø5.5
Ø4...8
264.2
Figure 13 Outdoor Model Dimensions (HMS82/83)
1304-053
VAISALA ________________________________________________________________________ 21
User's Guide _______________________________________________________________________
Configuration and Wiring
To minimize working at height at the installation location, prepare the transmitter configuration and wiring before climbing up.
1. Open the six screws that hold the transmitter cover.
2.
Check that the DIP switches are set as desired. See section DIP
3. Route the power and signal cable to the screw terminals and
connect the wires. Refer to section Wiring on page 25.
4. Disconnect the screw terminal block by pulling it away from the component board.
5. Adjust the length of cable between the cable gland and the terminal block. Make the cable short enough to close the cover without leaving a cable loop in the transmitter.
6. Tighten the cable gland. Leave the cover off for now.
Figure 14 Location of DIP Switches and Screw Terminal
1304-059
22 ___________________________________________________________________ M211510EN-D
Chapter 3 ________________________________________________________________ Installation
Pole installation
NOTE Recommended pole diameter for HMS82/83 installation with the supplied clamp and screws is 25 ... 60 mm.
1. Use the supplied clamp and screws to mount the transmitter on a pole.
2. To prevent the transmitter from turning on the pole, tighten the set screw on the center hole of the clamp.
1304-054
Figure 15 HMS82/83 Pole Installation
3. Plug in the screw terminal block, close the cover, and tighten the screws.
4. Secure the cable to the pole using a zip tie. Allow some cable to hang down from the cable gland to prevent water from entering the transmitter along the cable.
1304-056
Figure 16 Securing the Cable on a Pole
VAISALA ________________________________________________________________________ 23
User's Guide _______________________________________________________________________
Wall installation
1. Drill two holes for wall plugs 100 mm apart.
2. Place the wall plugs in the holes.
3. Mount the transmitter using two screws of sufficient length.
100 mm
Ø 5.5 mm
Figure 17 HMS82/83 Wall Installation
1304-055
4. Plug in the screw terminal block, close the cover, and tighten the screws.
5. Secure the cable to the wall using cable ties. Allow some cable to hang down from the cable gland to prevent water from running to the transmitter along the cable.
1304-057
Figure 18 Securing the Cable on a Wall
24 ___________________________________________________________________ M211510EN-D
Chapter 3 ________________________________________________________________ Installation
Wiring
WARNING Connect only de-energized wires.
NOTE Transmitters with a configurable humidity output parameter use the marking HUM on the screw terminal labels. The default output parameter is relative humidity (RH) with output scaled to 0 ... 100 %RH, but the parameter can be changed using DIP switches. Changing the
parameter also changes the output scaling. See section DIP Switches on page 30.
HMD82(D), HMW88(D), and HMS82
Two 4 ... 20 mA outputs, temperature output scaling
-40 ... +60 °C
(-40 ... +140 °F).
You must connect the
HUM channel even if you only want to measure temperature.
Connecting the T channel is optional.
HUM+
HUM-
T+
T-
1
2
3
4 mA mA
+
-
+
10
10
...
28 VDC
...
28 VDC
RL = 0 ...
600 Ω
Alternate wiring with one power supply.
HUM+
HUM-
T+
T-
1
2
3
4 mA mA
+
-
-
10
...
28 VDC
RL = 0 ...
600 Ω
VAISALA ________________________________________________________________________ 25
User's Guide _______________________________________________________________________
TMD82
4 ... 20 mA output, scaling -40 ... +60 °C
(-40 ... +140 °F).
Leave terminals 3 and 4 unconnected.
T+
T-
1
2
3
4 mA
RL = 0
HMD83(D), HMW89(D), and HMS83
+
10
...
28 VDC
...
600 Ω
Two 0 ... 10 V outputs, temperature output scaling -40 ... +60 °C
(-40 ... +140 °F).
VDC+/AC
VDC-/AC
T+
HUM+
T-/HUM-
1
2
3
4
5
V V
+
18
...
35 VDC or 24 VAC
Terminals 2 and 5 are internally connected on the transmitter, so you can also use a cable with four wires.
VDC+/AC
VDC-/AC
T+
HUM+
T-/HUM-
1
2
3
4
5
RL = min. 10 kΩ
+
18
...
35 VDC or 24 VAC
V
V
RL = min. 10 kΩ
26 ___________________________________________________________________ M211510EN-D
Chapter 3 ________________________________________________________________ Installation
TMD83
One 0 ... 10 V output, scaling -40 ... +60 °C
(-40 ... +140 °F).
Terminals 2 and 5 are internally connected on the transmitter, so you can also use a cable with three wires.
VDC+/AC
VDC-/AC
T+
HUM+
T-/HUM-
1
2
3
4
5
VDC+/AC
VDC-/AC
T+
HUM+
T-/HUM-
1
2
3
4
5
V
+
-
18
...
35 VDC or 24 VAC
V
RL = min. 10 kΩ
+
18
...
35 VDC or 24 VAC
RL = min. 10 kΩ
HMW82
Two 4 ... 20 mA outputs, temperature output scaling
-5 ... +55 °C
(+23 ... +131 °F).
You must connect the
RH channel of the
HMW82, even if you only want to measure temperature. Connecting the T channel is optional.
-T +T -RH +RH mA mA
10
...
28 VDC
+
10
...
28 VDC
RL = 0 ...
600 Ω
VAISALA ________________________________________________________________________ 27
User's Guide _______________________________________________________________________
TMW82
One 4 ... 20 mA output, scaling -5 ... +55 °C
(+23 ... +131 °F).
Leave the two terminals on the left unconnected.
HMW83
Two 0 ... 10 V outputs, temperature output scaling -5 ... +55 °C
(+23 ... +131 °F).
This is the recommended wiring for long cables.
-T +T mA
-RH +RH -T +T -VS +VS
V V
RL = min. 10 kΩ
10
...
28 VDC
RL = 0 ...
600 Ω
+
-
18
...
35 VDC or 24 VAC
3-wire connection with -
VS as common ground.
Not recommended if cable resistance is more than 2.5 Ω.
-RH +RH -T +T
V
-VS +VS
+
-
18
...
35 VDC or 24 VAC
V
RL = min. 10 kΩ
28 ___________________________________________________________________ M211510EN-D
Chapter 3 ________________________________________________________________ Installation
TMW83
One 0 ... 10 V output, scaling -5 ... +55 °C
(+23 ... +131 °F).
This is the recommended wiring for long cables.
-T +T -VS +VS
V
RL = min. 10 kΩ
+
-
18
...
35 VDC or 24 VAC
3-wire connection with
-VS as common ground.
Not recommended if cable resistance is more than 2.5 Ω.
-T +T -VS +VS
V
RL = min. 10 kΩ
+
-
18
...
35 VDC or 24 VAC
VAISALA ________________________________________________________________________ 29
User's Guide _______________________________________________________________________
DIP Switches
The DIP switches on the component board control the humidity output parameter and scaling, and the units that are shown on the display.
The switches are present on the following models:
- HMD82(D) and HMD83(D)
- HMW88(D) and HMW89(D)
- HMS82 and HMS83
Figure 19 below shows the default position of the DIP switches. The
default settings are:
- Metric units shown on display.
- Relative humidity (RH) selected as humidity output parameter.
Metric
RH
Non-metric
Td h
Tw
1302-053
Figure 19 DIP Switches on Component Board
30 ___________________________________________________________________ M211510EN-D
Chapter 3 ________________________________________________________________ Installation
Table 5 DIP Switch Positions for Metric Output
DIP Position Analog Output
Parameter and Scaling
Relative humidity (RH)
0 ... 100 %
Temperature (T)
-40 ... +60 °C
Parameters and Units on Display
RH (%)
T (°C)
Dewpoint (Td)
-40 ... +60 °C
Temperature (T)
-40 ... +60 °C
Td (°C)
T (°C)
Enthalpy (h)
-40 ... +460 kJ/kg
Temperature (T)
-40 ... +60 °C h (kJ/kg)
T (°C)
Wet bulb temperature (Tw)
-40 ... +60 °C
Temperature (T)
-40 ... +60 °C
Tw (°C)
T (°C)
Table 6 DIP Switch Positions for Non-Metric Output
DIP Position Analog Output
Parameter and Scaling
Relative humidity (RH)
0 ... 100 %
Temperature (T)
-40 ... +140 °F
Parameters and Units on Display
RH (%)
T (°F)
Dewpoint (Td)
-40 ... +140 °F
Temperature (T)
-40 ... +140 °F
Enthalpy (h)
-10 ... +190 BTU/lb
Temperature (T)
-40 ... +140 °F
Td (°F)
T (°F) h (BTU/lb)
T (°F)
Wet bulb temperature (Tw)
-40 ... +140 °F
Temperature (T)
-40 ... +140 °F
Tw (°F)
T (°F)
VAISALA ________________________________________________________________________ 31
User's Guide _______________________________________________________________________
CHAPTER 4
MAINTENANCE
This chapter provides information that is needed in basic maintenance of
HMDW80 series.
Cleaning
NOTE
The body of the transmitter can be cleaned by wiping with a moistened lint-free cloth. Do not use cleaning agents or solvents, or blow pressurized air into the transmitter housing or on the filter.
Do not attempt to clean contaminated INTERCAP ® sensors or filters.
Instead, replace them with new parts. Filters and sensors can be
purchased from Vaisala. For order codes, see section Spare Parts and
Calibration
You can verify the performance of your HMDW80 series transmitter by comparing its reading with the reading from a portable reference instrument such as the HM70 Hand-Held Humidity and Temperature
Meter. For operating instructions, refer to the documentation of your reference instrument.
If the comparison indicates that the reading from the transmitter is not within specification, the transmitter may need to have its filter and sensor replaced.
32 ___________________________________________________________________ M211510EN-D
Chapter 4 _______________________________________________________________ Maintenance
Replacing the INTERCAP
®
Humidity Sensor
HMDW80 series transmitters use the Vaisala INTERCAP ® humidity measurement. The INTERCAP ®
sensor for
sensor is designed to be replaced when necessary, and does not require adjustment by the user.
Replacing the INTERCAP
®
Sensor on
Models HMD82/83 and HMW88/89
REQUIRED
TOOLS
- New INTERCAP ® humidity sensor.
- New filter (always recommended when replacing the sensor).
- Duct models only: medium size crosshead screwdriver (Pozidriv).
1. Power down the transmitter.
2. Duct models only: loosen the tightening screw on the fastening flange, and pull the probe out of the duct.
3.
Remove the filter to access the sensors. See Figure 20 below.
4. Pull out the old INTERCAP ® sensor, and insert the new one.
5. Insert the new filter.
6. Duct models only: push the probe back into the duct, to the same depth where it was before. Tighten the tightening screw on the fastening flange.
7. Power up the transmitter.
8. Verify that the transmitter now provides a valid humidity reading.
1
2
3
4
1305-024
Figure 20 Sensors on HMD82/83 and HMW88/89 Models
1 = Vaisala INTERCAP® sensor. Handle by the plastic frame.
2 = Temperature sensor. Do not touch or attempt to remove.
3 = Sensor socket.
4 = Transmitter probe.
VAISALA ________________________________________________________________________ 33
User's Guide _______________________________________________________________________
REQUIRED
TOOLS
Replacing the INTERCAP
®
Wall Models HMW82/83
Sensor on
- New INTERCAP ® humidity sensor.
- Small flat head screwdriver.
1. Use the screwdriver to push down on the tab on the top of the transmitter and open the transmitter cover.
2.
Remove the old sensor, and insert the new one. See Figure 21 below.
3. Reconnect the cover to the mounting base.
4. Verify that the transmitter now provides a valid humidity reading.
1
1305-018
Figure 21 INTERCAP ® Sensor on HMW82/83 Models
34 ___________________________________________________________________ M211510EN-D
Chapter 4 _______________________________________________________________ Maintenance
REQUIRED
TOOLS
NOTE
Replacing the INTERCAP
®
Outdoor Models HMS82/83
Sensor on
- New INTERCAP ® humidity sensor.
- New filter (always recommended when replacing the sensor).
- Medium size crosshead screwdriver (Pozidriv)
- Flat head screwdriver
- 3 mm hex key (Allen key) for opening the radiation shield screws.
- If transmitter mounted on pole: 2.5 mm hex key for opening and tightening the set screw.
You will need to remove the radiation shield to access the sensor, and this is difficult to do while the transmitter remains mounted on a pole or wall. The procedure below takes advantage of the detachable screw terminal to allow the cable to remain in place during the operation.
1. Power down the transmitter.
2. Open the transmitter cover and unplug the screw terminal. This allows you to leave the cable and cover at the installation site.
1305-019
Figure 22 Unplugging the Screw Terminal
3. Remove the transmitter from its installation point.
VAISALA ________________________________________________________________________ 35
User's Guide _______________________________________________________________________
4. Open the two long screws that hold the radiation shield, and pull them out.
1305-020
Figure 23 Opening the Radiation Shield Screws
1305-021
Figure 24 Removing the Radiation Shield Screws
36 ___________________________________________________________________ M211510EN-D
Chapter 4 _______________________________________________________________ Maintenance
5. Use a flat head screwdriver to push on the visible plastic tab below the radiation shield.
Figure 25 Location of Locking Tab
1305-022
6. Tilt the radiation shield away from the opened tab. This opens the second tab on the other side, allowing you to remove the radiation shield.
1305-023
Figure 26 Removing the Radiation Shield
VAISALA ________________________________________________________________________ 37
User's Guide _______________________________________________________________________
7. Open the filter to expose the sensors.
1305-017
Figure 27 Filter Removed
8. Pull out the old INTERCAP ® sensor, and insert the new one.
1
2
3
4
1305-024
Figure 28 Sensors on HMS82/83 Models
1 = Vaisala INTERCAP® humidity sensor.
Handle by the plastic frame.
2 = Temperature sensor. Do not touch or attempt to remove.
3 = Sensor socket.
4 = Transmitter probe.
9. Insert the new filter.
10. Reassemble, remount, and reconnect the transmitter.
11. Power up the transmitter.
12. Verify that the transmitter now provides a valid humidity reading.
38 ___________________________________________________________________ M211510EN-D
Chapter 5 ____________________________________________________________ Troubleshooting
CHAPTER 5
TROUBLESHOOTING
This chapter describes possible problems, their probable causes and remedies, and provides contact information for technical support.
Problem Situations
Table 7 Possible Problem Situations and Their Remedies
Problem
Transmitter outputs an incorrect humidity reading.
Temperature reading shown by the transmitter is too high.
Current output on the temperature channel is
~24 mA.
Analog output reading is unchanging and incorrect.
Probable Cause and Remedy
1. Models with probes: check if the yellow transport protection cap has been left over the probe. Remove it if present.
2. Models with configurable output parameter: check that the desired output parameter has been selected using the DIP switches.
1. The transmitter may be installed in an unsuitable location, for example, near a heat source or in sunlight. Use a portable reference meter to check this.
2. HMW82 and HMW83: Check that the transmitter is installed in proper orientation, with the arrow on the mounting base pointing up.
Check that the humidity output channel is powered. Loop powered HMDW80 series models that have humidity measurement require that the humidity output channel is connected, even if only measuring temperature.
The analog output channel may be in an
error state. See section Analog Output Error
VAISALA ________________________________________________________________________ 39
User's Guide _______________________________________________________________________
Analog Output Error State
HMDW80 series transmitters set the output channel(s) into a defined error level instead of the measured result in two situations:
- Transmitter detects a measurement malfunction. This means an actual measurement problem, such as sensor damage or unsuitable environmental conditions.
- Measured value(s) are well outside the scaled output range. For a
more detailed explanation, see section Analog Output Overrange
The error level depends on the output type:
- For 0 ... 10 V output, the error level is 11 V.
HMW83 and TMW83 are an exception to this, their error level is 0 V.
- For 4 ... 20 mA output, the error level is 3.6 mA.
The transmitter resumes normal operation of the analog output(s) when the cause of the error state is removed.
Error Messages on the Display
Table 8
Error Message
INTERNAL 1
INTERNAL 2
INTERNAL 3
ERROR HUM
ERROR T
Error Messages on the Display
Possible Cause and Solution
Internal problem with the transmitter. Restart the transmitter to see if the problem remains. Contact Vaisala technical support if unable to remove the problem.
Humidity measurement failed. Check if the humidity sensor is damaged or missing.
Temperature measurement failed. Check if the temperature sensor is damaged or missing.
40 ___________________________________________________________________ M211510EN-D
Chapter 5 ____________________________________________________________ Troubleshooting
Technical Support
For technical questions, contact the Vaisala technical support by e-mail at [email protected]
. Provide at least the following supporting information:
- Name and model of the product in question
- Serial number of the product
- Name and location of the installation site
- Name and contact information of a technically competent person who can provide further information on the problem.
For Vaisala Service Center contact information, see www.vaisala.com/servicecenters .
VAISALA ________________________________________________________________________ 41
User's Guide _______________________________________________________________________
CHAPTER 6
TECHNICAL DATA
This chapter provides the technical data of the HMDW80 series.
Specifications
Table 9 Specifications for Models HMW82/83 and TMW82/83
Property
Operating environment
Operating temperature range
Operating humidity range
Relative humidity
Measurement range
Accuracy
Temperature range
+10 ... +30 °C (+50 ... +86 °F)
30 ... 70 %RH ±3 %RH
0 … 30 %RH, 70 … 100 %RH ±5 %RH
Temperature range
-5 ... +10 °C, +30 ... + 55 °C
(+23 ... +50 °F, +86 ... +131 °F)
0 …100 %RH
Stability in typical HVAC applications
Humidity sensor
Temperature
Measurement range
Accuracy
Description / Value
-5 ...+55 °C (+23 ... +131 °F)
0 …100 %RH, non-condensing
0 … 100 %RH
±7 %RH
±2 %RH over 2 years
Vaisala INTERCAP ®
-5 ...+55 °C (+23 ... +131 °F)
+10 … +30 °C (+50 °F … +86 °F) ±0.5 °C (±0.9 °F)
-5 … +10 °C, +30 … +55 °C
(+23 ... +50 °F, +86 ... +131°F)
Temperature sensor
±1.0 °C (±1.8 °F)
Digital temperature sensor
42 ___________________________________________________________________ M211510EN-D
Chapter 6 _____________________________________________________________ Technical Data
Table 10 Specifications for Models HMD82/83, TMD82/83,
HMW88/89, and HMS82/83
Property
Operating environment
Operating temperature range
Operating humidity range
Relative humidity
Measurement range
Accuracy
Temperature range
+10 ... +30 °C (+50 ... +86 °F)
0 ... 90 %RH
90 … 100 %RH
Temperature range
-20 ... +10 °C, +30 ... +60 °C
(-4 ... +50 °F, +86 ... +140 °F)
0 ... 90 %RH
90 … 100 %RH
Measurement range for enthalpy
Accuracy of the calculated parameters should be calculated at the actual condition based on the relative humidity and temperature specification.
Accuracy at +20 °C (+68 °F) and 80 %RH:
Dewpoint
Wet bulb temperature
Enthalpy
Description / Value
-40 ...+60 °C (-40 ... +140 °F)
0 …100 %RH
0 … 100 %RH
±3 %RH
±5 %RH
±5 %RH
±7 %RH
Temperature range -40 … -20 °C
(-40 … -4 °F)
0 … 100 %RH
Stability in typical HVAC applications
Humidity sensor
Temperature
Measurement range
Accuracy
±7 %RH
±2 %RH over 2 years
Vaisala INTERCAP ®
-40 ...+60 °C (-40 ... +140 °F)
At +20 °C (+68 °F)
Temperature dependence
Temperature sensor
Calculated parameters
±0.3 °C (±0.54 °F)
±0.01 °C/°C
Pt1000 RTD Class F0.1 IEC 60751
Measurement range for dewpoint temperature and wet bulb temperature -40 ...+60 °C (-40 ... +140 °F)
-40…460 kJ/kg (-10…+190 BTU/lb)
±0.9 °C (1.6 °F)
±0.7 °C (1.3 °F)
±2kJ/kg (0.9 BTU/lb)
VAISALA ________________________________________________________________________ 43
User's Guide _______________________________________________________________________
Table 11 Specifications for Models HMD82/83D and
HMW88/89D
Property
Operating environment
Operating temperature range
Operating humidity range
Relative humidity
Measurement range
Accuracy
Temperature range
+10 ... +30 °C (+50 ... +86 °F)
0 ... 90 %RH
90 … 100 %RH
Temperature range
-5 ... +10 °C, +30 ... +60 °C
(+23 ... +50 °F, +86 ... +140 °F)
0 ... 90 %RH
90 … 100 %RH
Measurement range for enthalpy
Accuracy of the calculated parameters should be calculated at the actual condition based on the relative humidity and temperature specification.
Accuracy at +20 °C (+68 °F) and 80 %RH:
Dewpoint
Wet bulb temperature
Enthalpy
Description / Value
-5 … +60 °C (+23 … +140 °F)
0…100 %RH, non-condensing
0 … 100 %RH
±3 %RH
±5 %RH
Stability in typical HVAC applications
Humidity sensor
Temperature
Measurement range
(Analog output scaling)
Operating temperature range of the display
Accuracy
±5 %RH
±7 %RH
±2 %RH over 2 years
Vaisala INTERCAP ®
-40 … +60 °C (-40 … +140 °F)
At +20 °C (+68 °F)
Temperature dependence
Temperature sensor
Calculated parameters
-5 … +60 °C (+23 … +140 °F)
±0.3 °C (±0.54 °F)
±0.01 °C/°C
Pt1000 RTD Class F0.1 IEC 60751
Measurement range for dewpoint temperature and wet bulb temperature -40 ...+60 °C (-40 ... +140 °F)
-40…460 kJ/kg (-10…+190 BTU/lb)
±0.9 °C (1.6 °F)
±0.7 °C (1.3 °F)
±2kJ/kg (0.9 BTU/lb)
44 ___________________________________________________________________ M211510EN-D
Chapter 6 _____________________________________________________________ Technical Data
Table 12 Operating Environment (All Models)
Property
Operating environment
Maximum wind/flow speed
Storage temperature
Electromagnetic compliance
Table 13 Inputs and Outputs
Description / Value
See model specifications
30 m/s
-40 ... +60 °C (-40 ... +140 °F)
EN61326-1, industrial environment
Property
Current output models (2-wire)
Outputs
Loop resistance
Supply voltage
Voltage output models (3-wire)
Outputs
Load resistance
Supply voltage
Current consumption
Description / Value
4 ... 20 mA, loop powered
0 ... 600 Ω
20 ... 28 VDC at 600 Ω load
10 ... 28 VDC at 0 Ω load
0 ... 10 V
10 kΩ min
18 ... 35 VDC
24 VAC ±20 % 50/60 Hz
10 mA on DC power
30 mA on AC power
Table 14 Mechanics
Property
Max. wire size
Standard housing color
Housing material
HMW82/83, TMW82/83
HMW88/89(D), HMD82/83(D),
TMD82/83, HMS82/83
Description / Value
1.5 mm 2 (AWG 16)
White (RAL9003)
ABS/PC (UL-V0 approved)
PC + 10%GF (UL-V0 approved)
VAISALA ________________________________________________________________________ 45
User's Guide _______________________________________________________________________
Spare Parts and Accessories
Information on spare parts, accessories, and calibration products is available online at www.vaisala.com
and store.vaisala.com
.
Table 15 HMDW80 Series Spare Parts and Accessories
Description Item Code
Sensors
Vaisala INTERCAP ®
Vaisala INTERCAP ®
humidity sensor, 1 piece
humidity sensor, 10 pcs
Sensor protection
PTFE membrane filter
● ● ● ● 15778HM
● ● ● ● INTERCAPSET-10PCS
PTFE filter
Accessories and Spare Parts
Fastening flange assembly (screws included)
Fastening set for HMS80
Cable gland with O-ring
Lid assembly with window for display
● ● ● ASM210856SP
● DRW239993SP
● ● ASM210771SP
● 237805
● ●
● ●
● ● CABLEGLANDORING
● ASM210793SP
(screws included)
Conduit fitting + O-ring (M16x1.5 / NPT1/2 Inch) ● ● ● ● 210675SP
Conduit fitting + O-ring (M16x1.5 / PG9, RE-MS) ● ● ● ● 210674SP
Terminal block, blue ● ● ● ● 236620SP
● = Part is compatible
46 ___________________________________________________________________ M211510EN-D
www.vaisala.com
*M211510EN*

Public link updated
The public link to your chat has been updated.
Advertisement
Key features
- ±3.0 %RH accuracy
- 0 ... 100 %RH measurement range
- User exchangeable INTERCAP® humidity sensor
- Several output parameters
- Several IP65-classified models
- UL-V0 flammability rating