Relay PadPuls M2, M2 pulse collector User Manual
Below you will find brief information for pulse collector PadPuls M2. The PadPuls M2 is a 2-channel pulse collector for wall mounting, designed to adapt consumption measuring instruments like current, gas or water meters to the M-Bus system. It allows you to connect up to two impulse meters to its inputs and optionally activate a tariff function for separate energy or volume pulse accumulation for primary and secondary tariffs. The device also features a built-in battery that ensures continued metering in case of M-Bus interruption. The PadPuls M2 can be configured using MBCONF software where you can adjust pulse increments, physical units, and set up due dates for counter data storage. It's ideal for applications where accurate energy or volume measurement is required.
Advertisement
Advertisement
GmbH, Stettiner Str. 38, D-33106 Paderborn
PadPuls M2
Art.No.: IM003G + IM003GB
(Valid from M-Bus generation: $40)
Art.-No. IM003G: 2-channel pulse collector for wall mounting with 0,23Ah battery
Art.-No. IM003GB: 2-channel pulse collector for wall mounting with 1,35Ah battery
Contents
PadPuls M2 User Manual 26.09.01, Version 1.2 1
GmbH, Stettiner Str. 38, D-33106 Paderborn
1 Functional description
The PadPuls M2 serves for the adaptation to the M-Bus system of consumption measuring instruments, such as, current, gas or water meters. However, the meters to be adapted must have a floating pulse output. Up to two impulse meters can simultaneous be connected to the inputs of this device. Optionally the user can activate a tariff function, by which energy or volume pulses are accumulated in separate meter readings for primary and secondary tariffs. In this case a floating signal for tariff switch is used at Port 2.
Each port or each tariff of the PadPuls M2 can be read on M-Bus using its own primary and secondary address. The PadPuls M2 thus acts as two stand-alone M-Bus Slaves!
The user configures the pulse collector with the software MBCONF. The accumulated pulses are converted into kWh, m
3
, J or other physical units. The user interface of
MBCONF allows the operator to get an easy access to the configuration.
When connected to the M-Bus the PadPuls M2 is powered from the bus. A built-in battery ensures that metering continues if the M-Bus is interrupted. Two battery options are available. The version with the higher capacity allows M-Bus independent metering for several years.
Another feature of the PadPuls M2 is the due-date function. Meter data are saved separately at the preset due-date at 00:00 hour (day change to the due-date) by the implemented clock with calendar function. The due-date can be changed without lost of the already stored counters. Additionally the M-Bus Master can initiate an immediate execution of the due-date function by sending of the so-called „Freeze“ command. A
„Freeze“ sent to all pulse collectors using the broadcast address 254 is helpful for generating reading profiles of an M-Bus system. Afterwards the master software polls the data of all meters.
The complete configuration data is saved into a non-volatile memory (EEPROM).
Additional security is provided by daily saving of meter readings into this EEPROM. In case of M-Bus fail and empty battery the last saved data is restored on power up.
The configuration data can be protected against unauthorized manipulation. The
PadPuls M2 can therefore be switched to protection mode with a special M-Bus telegram. Subsequent changes to device parameters cannot be made in this operating mode. The protection mode can then only be disabled by opening the sealed housing and pressing the unprotect pushbutton for minimum 4 seconds.
2 26.09.01, Version 1.2 PadPuls M2 User Manual
GmbH, Stettiner Str. 38, D-33106 Paderborn
2 Installation and Startup
2.1 Mounting the case
The bottom part of case is first attached to the wall with the terminals arranged downward. Please use 2 screws mounted through the outside drillings at the case.
The cable for pulse generator and M-Bus interface are led through the self sealing cable glands in the housing. You should break the cable glands with a small screw driver if you use flexible cables. To ensure a high protective class of up to IP65 the hole must be much smaller than the outer diameter of the cable. If you lift the terminal connectors and feed the cables far enough through the glands, you can connect the wires comfortably outside of the housing. Afterwards please withdraw the cables again and put the terminals on the appropriate pin rows on the circuit board. The strain relief is given by looping the enclosed cable straps around the cable. If you have completed all assembly and configuration work, you should protect the device against manipulation with one sticking on each screw on the cover of the case.
The accompanying drawing defines the measures for wall mounting in mm:
PadPuls M2 User Manual 26.09.01, Version 1.2 3
GmbH, Stettiner Str. 38, D-33106 Paderborn
2.2 Activating
Coming from factory the PadPuls M2 must first be activated. The cover of the housing is to be removed. On the circuit board there is a 2pin row marked with “BAT”. Here the jumper must be put on both pins to allow battery operation and security function in case of M-Bus failure.
•
If the device is not used for a longer time, it is advisable to deactivate battery operation by removing the jumper to preserve the battery.
•
If the battery should be empty, it can be exchanged. See section 5.
The PadPuls M2 is supplied from M-Bus if it is available. In this normal state the internal battery is then not loaded. Only when the M-Bus fails the battery takes over automatically the supply. There is no lost of data and the counting function is continued. The PadPuls M2 draws approximately 1.5mA current ( one unit load) from the
M-Bus.
4 26.09.01, Version 1.2 PadPuls M2 User Manual
GmbH, Stettiner Str. 38, D-33106 Paderborn
2.3 Connecting
The following figure shows the link of two counters with impulse outputs to the PadPuls
M2. We recommend to use 2-wire cables (twisted pair, NYM or j-Y(St)Y) with a max. length of 10m. In any case it must be noted that the total capacity of the cable plus impulse generator attached at any port may not exceed 2nF (optional 12nF with activated “extended pulse sampling”).
+
CR2032 unprotect
-
+
-
+
Port1 Port2
-
+
-
+
M-Bus M-Bus
001234, 3 m
3
001234, 3 m
3
M-Bus
•
If not all ports of PadPulse M2 are used, you should not attach a cable to the respective unused port. The capacity of an open-circuited cable reduces the lifetime of the battery in stand-alone operation (no M-Bus available).
PadPuls M2 User Manual 26.09.01, Version 1.2 5
GmbH, Stettiner Str. 38, D-33106 Paderborn
The following graph represents the diagram of connections in the tariff mode with one counter and a tariff signal generator:
+
CR2032 unprotect
-
+
-
+
Port1 Port2
-
+
-
+
M-Bus M-Bus
001234, 3 m
3
M-Bus
The specifications of the impulse and tariff signal generator can be taken from the technical data. The maximum pulse frequency to be counted is 14Hz.
•
If the pulse frequency is over 14 Hz, false countings can occur.
6 26.09.01, Version 1.2 PadPuls M2 User Manual
GmbH, Stettiner Str. 38, D-33106 Paderborn
3 Parameterization using MBCONF
The configuration of the device must be adapted by the customer to the respective installation. The current version $40 of PadPuls M2V requires the use of the program
MBCONF for configuration. The older DOS version PADCON may not be used anymore.
3.1 Installation
The software MBCONF for configuration of the pulse adaptor is a 32-bit application, which can be executed on IBM-PC compatible computers under the operating systems
Windows 95 / 98 / NT 4.0. The desktop PC or laptop must have a free serial RS232C interface to connect the M-Bus level converter. The PadPuls M2 to be parameterized must be connected directly (i.e. as only M-Bus device) to the M-Bus output of the level converter.
Please start the file “MBCONF_SETUP.EXE” from Windows Explorer or via “Start –
Execute” to install the software from version 1.40 up. Subsequently you select the language of the installation procedure. The setup software can create a program group and a link on the desktop on demand. You can then execute both versions for German and English language either from start menu or desktop.
3.2 Operation
After program start the user operates the software according to the Windows conventions with the mouse or the keyboard. If you stay with the mouse on a button or an input field, then a hint to its function appears. Light-grey fields and boxes are not capable for editing.
All input fields and buttons have an underlined letter. The function can be activated by simultaneous pressing of the keys [ALT] and the respective letter. Within dialogs the cursor can be moved with the keys [TAB] or [SHIFT][TAB ] forwards and back.
[SPACE ] activates or deactivates selection boxes. Multiple selection boxes (arrow at the right edge) can be activated with [
⇓
]. The user then selects an entry with [
⇓
] and [
⇑
].
By pressing [RETURN] the selected entry is taken over. With [ESC] the selection box is left without transfer.
The program is arranged as a sheet system. The sheet “Info” contains general options of the communication with the M-Bus device to be configured. In this sheet the user can select the serial port of the PC, the baudrate of the PC, the baudrate of the M-Bus device and the M-Bus primary address which is used for communication. After a successful connection with the M-Bus device, further manufacturer information is shown in the sheet “Info” and additional device-specific sheets are displayed.
PadPuls M2 User Manual 26.09.01, Version 1.2 7
3.3 Sheet Info
GmbH, Stettiner Str. 38, D-33106 Paderborn
This sheet shows some photos of supported M-Bus devices from the product range of the Relay GmbH, the PadMess GmbH and further manufacturer. Here are also links to the Internet page, from which the current version of the program can be downloaded, and to the email address for criticism and suggestions to the program.
The lower third of this card is likewise visible in every other card. Here the following input fields and buttons are always attainable:
COM-Port
Baudrate
is the serial port of the PC to which the M-Bus level converter is connected. The selected port will be saved in an INI file and will be restored on startup. Therefore the COM-Port has to be configured only once. ist the transmission speed of the serial port of the PC used for parameterization. Possible selections for this used M-Bus baudrate are 300, 2400 or 9600 baud. Attention: Baudrates of more than
8 26.09.01, Version 1.2 PadPuls M2 User Manual
GmbH, Stettiner Str. 38, D-33106 Paderborn
New M-Bus
Baudrate
2400 baud are not supported by all M-Bus level converters which are available on the market! The selected baudrate must be identical to the baudrate of the M-Bus device. (see: “New M-Bus
Baudrate”). The PadPuls M2 supports the baudrates 300 and 2400
Bd. allows reprogramming the baudrate of the M-Bus device. The new baudrate is sent to the M-Bus device after a change in the appropriate selection box. If the M-Bus slave accepts this command, it acknowledges the telegram with the single character
„$E5“ ($ for hexadecimal notation) using the old baudrate.
Afterwards the device switches to the new baudrate. This button is not needed for the PadPuls M2V, since it automatically detects the baudrate used by the master.
M-Bus Address
is the primary address of the connected M-Bus slave. In a direct connection with only one slave you can use the broadcast address
254. Using this address every M-Bus device must answer regardless of its own address.
Connect to meter
is used to request data from the slave. The type of device is then automatically recognized. The items “Manufact.”, “Generation”,
“Type” and “M-Bus State” will then be refreshed. New sheets are generated depending on manufacturer and type of the M-Bus device. A single sheet for each channel appears in case of PadPuls
M2. The sheets are labelled “M2 Port1” for the first and “M2 Port2” for the second channel.
Manufact.
Generation
Type
M-Bus State
is an item that shows the 3-letter manufacturer code after successful reading (“Connect to meter”). The item is read only. shows the software revision of the firmware of the connected M-
Bus device. The item is read only. shows the type (here: PadPuls M2) of the connected device. This item is read only. shows the M-Bus state of the connected device. This item is read only.
ZVEI optical mode
If this option is activated, devices with an optical interface and protocol according to EN 1434-3 can be read and programmed using an optical reading head (e.g. PadPuls M4 / M4L).
Autom. readout
The software always reads the data after writing, if this option is activated (useful for checking the correct programming).
PadPuls M2 User Manual 26.09.01, Version 1.2 9
GmbH, Stettiner Str. 38, D-33106 Paderborn
Log-Window
The so-called log window is always visible. All M-Bus communication steps are logged in this window. Data is displayed in hexadecimal notation. It is possible to mark outputs in the log window and copy them with the keys “CTL-C” to the windows clipboard. Then the data can be easily imported to any text editor for documentation. As soon as the max. storage capacity of the window is achieved, no more data is logged. If you want to log further, you must delete the logged data.
The following buttons are also always visible:
Erase log
Exit
clears all outputs inside the log window. terminates the program and stores the current setting of serial port
(port no.) into the INI file.
10 26.09.01, Version 1.2 PadPuls M2 User Manual
GmbH, Stettiner Str. 38, D-33106 Paderborn
3.4 Sheets M2 Port1 and M2 Port2
These sheet shows the current settings and values of the respectively pulse channel
(port) of the PadPuls M2 (in this example: Port 1). The following input boxes and buttons are used to change the params of the pulse adapter:
Primary address is the M-Bus address of the selected port. Values between 1 and
250 can be entered in this field for new assignment of the address.
After pressing the “Write” button the software programs this primary address and further variable settings on this sheet into the M-Bus device.
ID (sec. adr.)
Medium
is the 8 digit M-Bus ID (identification no.), which is also used for secondary addressing of this port. describes the measured medium of the connected meter.
Examples: Oil, Water, Heat, Electricity
PadPuls M2 User Manual 26.09.01, Version 1.2 11
GmbH, Stettiner Str. 38, D-33106 Paderborn
Multiplicator
Unit
Counter
Current time
Due-date
Due-date cnt.
Next
Due-date is the pulse increment (multiplicator) of the connected meter. For each registered pulse the device adds “multiplicator” to the counter.
The numerator can take values between 0 (no counting) and 99, the denominator between 1 and 256. is the physical unit of the counter and of the pulse increment. All proper units including variants with power of ten from the DIN EN
1434-3 are offered in the selection list. is the accumulated counter. It has to be related to the unit mentioned above. The counter can be programmed equal to the counter of the connected meter in a range of 0 to 99999999. is the current date and time-of-day of the internal clock in the format
DD.MM.YY_hh.mm. This field can be only edited and modified in the PadPuls, if the switch “Edit and change time” is activated. The button “Read clock of PC” transfers once the current date and time of the PC into this window. The time-of-day and the date always apply to all ports of PadPuls M2. is the last due-date (date of the last storage of the due-date counter) in the format DD.MM.YY. This field is read only. is the counter which was saved at the due-date. This field is read only. is the next (future) due-date (date of the next storage of the counter) in the format DD.MM.YY. The counter will be saved at
00:00, e.g. with due-date 01.01 at change from 31th of December
23:59 to 1 st
of January 00:00. This field can be edited and programmed only, if the switch “Edit and change time” is marked.
The due-date always applies to all ports of PadPuls M2.
State of ports shows the current input state of all ports (a closed contact is marked). This item is read only.
Write protection is marked, if the device is protected against programming. Then you cannot configure the adapter. The protection can be removed after opening the sealable housing and pressing the “Unprotect” pushbutton for a minimum of 4 seconds.
EEPROM error is marked, if there was an error while reading the non-volatile memory. In this case you must reconfigure the device.
12 26.09.01, Version 1.2 PadPuls M2 User Manual
GmbH, Stettiner Str. 38, D-33106 Paderborn
Tariff A (P1/2)
Long pulse sampling
activates a longer charging of the contacts before sampling the inputs. This allows higher capacitors and / or many pulse generators with So interface (photocoupler with capacitors) to be connected. On delivery the extended pulse sampling is activated.
The lifetime of battery is increased for about 15% if this feature is not used.
Edit and change
activation of this check box allows editing and programming of the
time “Current time” and “Next due-date”. The checkbox is deactivated automatically after successful configuration with “Write”.
Freeze
is used for activation tariff mode on port 1 and 2. The tariff mode will be selected after pressing the “Write” button, if the check box is marked. Port 1 is then used as pulse input and port 2 is the tariff switch. With an open tariff switch the pulses are accumulated to the counter for port 1 (main tariff). With a closed tariff contact the pulses increment the counter for port 2 (special tariff). transmits a command to the PadPuls M2 telling it to freeze the counters. The PadPuls M2 then copies the current counter to the
“Due-date counter” and the current date to the (last) “Due-date”.
The storage is done for all ports simultaneously. This the same behaviour as at due-date. The freeze command can be used with the broadcast address 255 to order all PadPuls to save the current counters. Then the M-Bus master has enough time to read all meters and get values of the same time (reading profiles).
Read clock of PC once gets the current date and time from the clock of the PC and transfers it into the item “Current time”.
Write protect Transmits a command to the PadPuls M2 to activate write protect.
The PadPuls M2 then allows no further configuration. It is protected against unnoticed manipulation.
Read
Write reads the M-Bus device and refreshes the data on the selected sheet. sends the current options to the pulse converter, which saves this data into the non-volatile memory. The PadPuls M2 changes the options only if the write protect is deactivated. It is recommended to read the data after writing and check it.
PadPuls M2 User Manual 26.09.01, Version 1.2 13
GmbH, Stettiner Str. 38, D-33106 Paderborn
Notes:
1. The variables „Current time“, „Next due-date“, „Write protection“, „Long pulse sampling “ and the command „Freeze“ always apply to all ports. Therefore you need to edit these items only in one sheet. The write protect should be activated after successful configuration of all ports.
2. Please press first the button „Connect to meter“ after connecting a new M-Bus device. Afterwards all sheets are refreshed.
3. Examples for configuration of pulse increment and unit:
•
Water meter with counter = 45120 l and 1 Pulse = 10 l:
Choice 1: Unit = 10 l, Multiplicator = 1 / 1, Counter = 4512 ( x 10 l)
Choice 2: Unit = 1 l, Multiplicator = 10 / 1, Counter = 45120 ( x 1 l)
•
Electricity meter with counter = 78346 kWh and 64 pulses / kWh:
Choice: Unit = 1kWh, Multiplicator = 1 / 64, Counter = 78346 ( x 1kWh)
•
Electricity meter with counter = 112,345 kWh and 1000 pulses / kWh:
Choice: Unit = 1Wh, Multiplicator = 1 / 1, Counter = 1123454 ( x 0,001Wh)
4. With activated tariff option the pulses are evaluated with the adjustments of the respective port. Therefore you should take care that both ports have the same pulse increment and unit.
14 26.09.01, Version 1.2 PadPuls M2 User Manual
GmbH, Stettiner Str. 38, D-33106 Paderborn
4 Notes on malfunctionings
Error
No function in battery mode
No function after installation, although the battery jumper is placed and the M-
Bus is connected
Pulses are not counted or wrong
Possible source of error
-
Battery jumper is not placed
-
Battery is empty (voltage min. 2.9V)
-
After placing the jumper a reset is generated using an R/C combination.
It is possible that the reset was not correct. Please lift the jumper, wait about 10 seconds and place it again.
-
Check connection of the pulse meter
-
Activate the „extended pulse sampling” if your system has: a) long cables (> 10m) b) high capacitors c) electronic S
0
interface
-
Check configuration (especially pulse increment and tariff mode)
5 Exchange of battery
The battery of the PadPuls M2 (IM003G with coin-type) can be exchanged by the user.
The empty battery must be removed from the battery clip and a new lithium coin-type cell CR2032 is to be inserted. You can acquire these batteries in the trade or directly from us.
The M-Bus voltage should be connected to the PadPuls M2 to ensure that the device is counting on while battery exchange. If the device is not attached to the M-Bus, you can supply it alternatively with a DC voltage within the range of 12 to 45 VDC on the M-Bus terminals.
PadPuls M2 User Manual 26.09.01, Version 1.2 15
GmbH, Stettiner Str. 38, D-33106 Paderborn
6 M-Bus Telegrams
Position 1 2 3 4 5 6 7 8
Start
0
9
ID
1
10
ID
2
11 12
ID
3
Man
0
13 14 15 16 17 18 19 20 21 22 23 24 25 26
Man
1
Gen Med TC State Sig
0
Sig
1
DIF1 VIF1 Stand
0
Stand
1
Stand
2
Stand
3
DIF2
27 28 29 30 31 32 33 34 35 36 37 38 39 40
VIF2 Date
0
Date
1
Date
2
Date
3
DIF3 VIF3
LeStD
0
LeStD
1
DIF4 VIF4 StStn
0
StStn
1
StStn
2
41 42 43 44 45 46 47 48
StStn
3
DIF5 VIF5 VIFE5 StDat
0
StDat
1
DIF6 Info ator
49 50
Denomi nator
51 52 53
PStat CS Stop
RSP_UD telegram
ID
0-3
: identification no. for secondary addressing
Man
0-1
: manufacturer
Gen: revision of firmware (at this time $40, reserved range $40 to $4F)
Med: medium
TC:
State: transmission counter (number of transmitted RSP_UD) most significant bit set (bit 7) -> write protected bit 3 set (permanent error) -> error in EEPROM data
VIF1=VIF4: selected VIF (value information field -> physical unit)
Date:
LeStD:
StDat:
Info: current date (IEC870-5-4: data type F) last due-date, date of the due-date counter (IEC870-5-4: data type G) next (future) due-date
1 byte with information about tariff and sampling method)
Denominator: denominator of pulse increment (1..255, 0 -> 256)
1
Pulse
=
Numerator
Deno
min
ator
∗
VIF
PStat: state of inputs (current input state of the ports)
16 26.09.01, Version 1.2 PadPuls M2 User Manual
GmbH, Stettiner Str. 38, D-33106 Paderborn
Byte 48 (Info)
Bit
Value
(bin)
7 x
6
Sampling
5 x
4
Tariff A
3 2 1 0
Select: number of the port, for which the data is valid
Tariff A:
0: Port1, 1: Port2 tariff A (Port 1 = count input, Port2 = counter / tariff signal)
0: tariff off (Port2=count input), 1: tariff on (Port2=tariff signal)
Sampling: duration of a sampling
0: short (0.5ms), 1: long (1.5ms)
Position 1 2 3 4 5 6 7 8 9 10 11 12
Name: Start Length A CI DIF1 VIF1 Anw. DIF2 VIF2
13 14 15 16
PAdr DIF3 VIF3 ID
0
17
ID
1
18
ID
2
19 20 21 22 23 24 25 26
ID
3
Man
0
Man
1
Gen Med DIF4 VIF4 Stand
0
27 28 29 30 31 32 33 34 35 36 37 38 39 40
Stand
1
Stand
2
Stand
3
DIF5 VIF5 Date
0
Date
1
Date
2
Date
3
DIF6 VIF6 StDat
0
StDat
1
DIF7
41 42
Opt. Numer ator
43
Deno minat.
44 45
CS Stop
16
SND_UD telegram (Abbreviations see RSP_UD)
Port: seleced port (used with address 254)
PAdr: new primary address of the port
Numerator: Numerator of pulse increment (1..99, BCD format)
Denominator: Denominator of pulse increment (1..255, 0 -> 256, binary fromat)
Option: Options (tariff, sampling). Coding like Info (Byte 48 RSP_UD).
The PadPuls M2 analyzes the individual data records on the basis of the DIF. Therefore the order of the records is allowed to vary. It is also possible to transmit only parts of the SND_UD specified above. The manufacturer-specific appendix of the telegram is always first analysed and must be included therefore in any case. The optional record
„DIF1 VIF1 Anw“ selects a port to be addressed with global address 254. This must be always the first record in the telegram.
PadPuls M2 User Manual 26.09.01, Version 1.2 17
GmbH, Stettiner Str. 38, D-33106 Paderborn
Position 1 2 3 4 5 6 7 8 9 10 11
Name: Start Length Length Start C A CI DIF Prot. CS Stop
Protection-Telegram
This telegram activates the write protection.
Position 1 2 3 4 5 6 7 8 9 10 11
Name: Start Length Length Start C A CI DIF Anw. CS Stop
Select telegram (old method)
Position 1 2 3 4 5 6 7 8 9 10 11
Name: Start Length Length Start C A CI DIF VIF Anw. CS
12
Stop
16
Select telegram (new method)
Anw. specifies the Port of the PadPuls M2, which answers to a REQ_UD2 at address
254:
Port1: Anw=00
Port2: Anw=01
Position 1 2 3 4 5 6 7 8 9
Name: Start Length Length Start C A CI CS Stop
Freeze telegram
On reception of this telegram the pulse adapter saves the current counters of all ports into the due-date counters and the current date into the due-date.
18 26.09.01, Version 1.2 PadPuls M2 User Manual
GmbH, Stettiner Str. 38, D-33106 Paderborn
7 Technical Data
Case
Material polystyrol
Colour light-grey
W x H x D
Protection type
(80 x 80 x 52) mm
IP54, up to IP65 is possible
Environment
Operating temperature
Storage temperature
Humidity (non condensing)
Terminals
Diameter of solid wires
Diameter of flexible wires
0 to 55 °C
-20 to 70 °C
10% to 70%
0,14 to 1,5 mm
0,14 to 1,0 mm
2
2
Specifications to contacts of pulse generators
Potential floating, insulation to earth > 1M
Ω
Resistance open > 1M
Ω
, closed < 2k
Ω
Maximum capacity (incl. cable) 2nF (short sampling), 12nF (long sampling)
Minimum contact duration 30 ms
Minimum pause between contacts 30 ms
Maxium pulse frequenz 14 Hz
Specifications to contact of tariff generator
Potential floating, insulation to earth > 1M
Ω
Resistance open > 1M
Ω
, closed < 2k
Ω
Maximum capacity (incl. cable)
Possible signal wave forms
2nF (short sampling), 12nF (long sampling)
50 / 60 Hz or static signals
PadPuls contact input:
Contact voltage
Contact current
Guaranteed debounce time
Connection cable
2.5V to 3.6V
30
µ
A
5.0 ms maximum 10 m (Twisted Pair recommended)
PadPuls M2 User Manual 26.09.01, Version 1.2 19
GmbH, Stettiner Str. 38, D-33106 Paderborn
Current consumption
Bus operation
Battery standard optional
Battery operation
Battery lifetime in battery operation automatic changeover to battery on bus failure max. 1.5 mA (unit load), no battery loading
Lithium 3V, coin-type, 230mAh, exchangable
Lithium 3V, type 2/3AA, 1350mAh at 25°C ca. 50
µ
A (long sampling) standard battery: optional battery: at 25°C ca. 1/2 year at 25°C ca. 3 years
Max. no. of days with M-Bus fail standard battery: at 25°C ca. 18 days p.a. per year for 10 years operation optional battery: at 25°C ca. 110 days p.a.
Short sampling Battery lifetime is lengthened by ca.15% if short sampling is activated.
M-Bus: physical characteristics
M-Bus quiescent current typ. 1.4 mA, max. 1.5 mA (1 unit load)
Space(0-Bit) current
M-Bus Interface quiescent current (1.4 mA) + typ. 13 mA
TI TSS721 with 2 x 215
Ω
protection resitors
M-Bus Protocol
Standard EN1434-3
Transmission speed 300, 2400 baud with automatic detection
Addressing
Supported functions
Data structure
Primary- and secondary addressing with wildcards, per input port : 1 primary and 1 secondary address
SND_NKE, REQ_UD2, SND_UD, ignores FCB-Bit (according to EN1434-3) variable structure, Low-Byte-First (CI: 72h) length = 53 Bytes
1. data record: counter
2. data record: date and time
3. data record: last due-date
4. data record: last due-date counter
5. data record: next due-date
6. data record: manufacturer specific data
Configuration telegram Identification no., medium, primary address, pulse increment, pulse unit, initial counter, tariff mode, date / time and next due-date: can be parameterized via SND_UD through M-Bus or optical interface
20 26.09.01, Version 1.2 PadPuls M2 User Manual
Advertisement
Key Features
- 2-channel pulse collector
- Wall mounting
- M-Bus system adaptation
- Tariff function
- Battery backup
- MBCONF configuration
- Due-date function
- Write protection
- Extended pulse sampling